A SEMINAR REPORT ON “POWER SYSTEM PROTECTION” Thesis submitted by partial fulfillment of the requirements For the degree of Bachelor of technology In Electrical engineering SUBMITTED BY: CHANDANA MALLIK ROLL NO: 32269 REGISTRATION NO: 1421105031 UNDER THE GUIDANCE OF ASST. PROF. ADITYA KUMAR PATI ASST. PROF. BINAY KUMAR NAYAK DEPT. OF ELECTRICAL ENGINEERING INDIRA GANDHI INSTITUTE OF TECHNOLOGY, SARANG 2016-2017 Page | 1

Upload: chandana-mallik

Post on 12-Apr-2017

50 views

Category:

Engineering


0 download

TRANSCRIPT

Page 1: Chandna seminar report  1421105031

A SEMINAR REPORT ON

“POWER SYSTEM PROTECTION”Thesis submitted by partial fulfillment of the requirements

For the degree of

Bachelor of technology

In

Electrical engineering

SUBMITTED BY:

CHANDANA MALLIK

ROLL NO: 32269

REGISTRATION NO: 1421105031

UNDER THE GUIDANCE OF

ASST. PROF. ADITYA KUMAR PATI

ASST. PROF. BINAY KUMAR NAYAK

DEPT. OF ELECTRICAL ENGINEERING

INDIRA GANDHI INSTITUTE OF TECHNOLOGY, SARANG

2016-2017

Page | 1

Page 2: Chandna seminar report  1421105031

ACKNOWLEDGEMENT

The satisfaction and euphoria that accompany the successful completion

of any task would be incomplete without the mentioning of the people whose

constant guidance and encouragement made it possible. I take pleasure in

presenting before you, my seminar, which is a result of studied blend of both

research and knowledge.

I express my earnest gratitude to Asst. Prof. Aditya Kumar Pati and

Asst. Prof. Binay Kumar Nayak of Department Of Electrical Engineering, our

project guides, for their constant support, encouragement and guidance. I am

grateful for their cooperation and valuable suggestion.

I am especially grateful to Dr. B.P. Panigrahi, the Head of the

Department, Electrical Engineering, IGIT, Sarang for his time-to-time, much

needed valuable guidance.

I would like to express my sincere thanks to my colleagues for their

constant inspiration, motivation and encouragement without which it would

have not come into success.

Finally, I express my gratitude to all other members who are involved

directly or indirectly for the completion of this project.

CHANDANA MALLIK

REGD. NO: 1421105031

ROLL NO: 32269

7TH SEM

Page | 2

Page 3: Chandna seminar report  1421105031

CERTIFICATE

This is to certify that Mr. Chandana Mallik, bearing Roll No:

32269 and University Registration No-1421105031, a student of

7th semester has submitted the seminar report entitled “Power

System Protection” as per the requirement of the Biju Patnaik

University Of Technology in partial fulfilment of Degree of

Bachelor of technology (Electrical Engineering Department) for

the academic year 2014-2017.

Dr. B.P. Panigrahi

(Head of the Department)

IGIT, Sarang

Page | 3

Asst. Prof. Aditya Kumar Pati

Asst. Prof. Binay Kumar Nayak

(Seminar Guide)

Page 4: Chandna seminar report  1421105031

DECLARATIONI, CHANDANA MALLIK, hereby declare that the seminar

report Entitled “POWER SYSTEM PROTECTION” submitted

to the IGIT SARANG is a record of an original work done by me

under the guidance of ASST. PROF. ADITYA KUMAR PATI and

ASST. PROF. BINAY KUMAR NAYAK in Electrical

Engineering, I N D I R A G A N D H I I N S T I T U T E O F

T E C H N O L O G Y , S A R A N G .

This report is submitted in the partial fulfilment of the requirements for the award of the degree of Bachelor of Technology in Electrical Engineering. The results embodied in this thesis have not been submitted to any other University or Institute for the award of any degree or diploma.

Page | 4

Page 5: Chandna seminar report  1421105031

INDEXABSTRACT

INTRODUCTION

THREE PHASE DIAGRAM OF PROTECTION

COMPONENTS OF PROTECTION SYSTEM

CURRENT TRANSFORMER (CT)

POTENTIAL TRANSFORMER (PT)

PROTECTION RELAY

CIRCUIT BREAKER (CB)

LIGHTINING ARRESTER (LA)

ISOLATOR

CONCLUSION

REFERENCES

Page | 5

Page 6: Chandna seminar report  1421105031

POWER SYSTEM PROTECTIONAbstractAs we know the safety is very first requirement for any system. So here I am discussing about some protection devices use in the Electrical Power Substation.

Power-system protection is a branch of electrical power engineering that deals with the protection of electrical power systems from faults through the isolation of faulted parts from the rest of the electrical network.

The objective of a protection scheme is to keep the power system stable by isolating only the components that are under fault, whilst leaving as much of the network as possible still in operation.

In Electrical Power Substation(switch yard) various type of protection devices are used to protect from different fault.

Some of them are:

Current Transformer(CT) Potential Transformer(PT) Protection Relay Circuit Breaker(CB) Lightning Arrester(LA) Fuse

When any type of fault occurs in the system, it is detected by Current Transformer or Potential Transformer or Lightning Arrester. These devices give the controlling signal to Relays biased with them. Relay decides whether fault occurs in the particular part of system or not. When the faults occurs in any section of the system, Protection Relay of that section comes in operation and closes the trip of the Circuit Breaker, which disconnects the faulty section. The healthy section continue to supply loads as usual and thus there is no damage to the equipment and no complete interruption of supply.

Page | 6

Page 7: Chandna seminar report  1421105031

Introduction Power-system protection is a branch of electrical power engineering that deals with the protection of electrical power systems from faults through the isolation of faulted parts from the rest of the electrical network. The objective of a protection scheme is to keep the power system stable by isolating only the components that are under fault, whilst leaving as much of the network as possible still in operation. Thus, protection schemes must apply a very pragmatic and pessimistic approach to clearing system faults.

A substation is a part of an electrical generation, transmission, and distribution system. Substations transform voltage from high to low, or the reverse, or perform any of several other important functions. Between the generating station and consumer, electric power may flow through several substations at different voltage levels.

The apparatus or equipments and their associated auxiliaries employed for controlling, regulating and switching on or off the electrical circuits in the electrical power system is known as “Protection devices” or “switchgear”.

An automatic Protection consists of the Relays, Circuit Breakers(CB), Lightning Arrester(LA) and Fuse. When the faults occurs in any section of the system, Protection Relay of that section comes in operation and closes the trip of the Circuit Breaker, which disconnects the faulty section. The healthy section continue to supply loads as usual and thus there is no damage to the equipment and no complete interruption of supply.

In this lesion we shall discuss about the various Protection Devices used in Substation Protection System.

Page | 7

Page 8: Chandna seminar report  1421105031

Three-Phase Diagram of the Protection

Page | 8

Page 9: Chandna seminar report  1421105031

Components of Protection SystemAn automatic protection system has mainly six components:

1. Instrumentation Transformer Current Transformer(CT) Potential Transformer(PT)

2. Protective Relay3. Circuit Breaker(CB)4. Lightning Arrester(LA)(Surge Diverter)5. Isolators(Disconnecting switch) 6. Fuse

A typical Substation

Page | 9

Page 10: Chandna seminar report  1421105031

Current Transformer(CT)A current transformer (CT) is used for measurement of alternating electric current. Current transformers, together with voltage (or potential) transformers (VT or PT), are known as instrument transformers. When current in a circuit is too high to apply directly to measuring instruments, a current transformer produces a reduced current accurately proportional to the current in the circuit, which can be conveniently connected to measuring and recording instruments. Current transformers are commonly used in metering and protective relays in the electrical power industry.

Design

Like any other transformer a current transformer has a primary winding, a magnetic core and a secondary winding. The alternating current in the primary produces an alternating magnetic field in the core, which then induces an alternating current in the secondary winding circuit. An essential objective of current transformer design is to ensure the primary and secondary circuits are efficiently coupled, so the secondary current is linearly proportional to the primary current.

Basic operation of current transformer

Page | 10

Page 11: Chandna seminar report  1421105031

SF6 110 kV current transformer

UsageCurrent transformers are used extensively for measuring current and monitoring the operation of the power grid. Along with voltage leads, revenue-grade CTs drive the electrical utility's watt-hour meter on virtually every building with three-phase service and single-phase services greater than 200 amperes.

CT used in metering equipment for three-phase 400-ampere electricity supply

Current Transformers are also used as the protection device including with Relay and Circuit Breaker.

Page | 11

Page 12: Chandna seminar report  1421105031

Potential Transformer(PT)

Potential transformers (PT) (also called voltage transformers (VT)) are a parallel connected type of instrument transformer. They are designed to present negligible load to the supply being measured and have an accurate voltage ratio and phase relationship to enable accurate secondary connected metering.

It gives the reference voltage to the Relay for Over-voltage or Under-voltage Protection.

Page | 12

Page 13: Chandna seminar report  1421105031

Protective Relay

A Relay is a logical elements which process the inputs(mostly voltage and currents) from the system and issue a trip decision if a fault within its jurisdiction is detected.

Inputs to the Relays are

• Current from current transformer(CT)

• Voltage from voltage transformer(VT)

Principle of operation

Electromechanical protective relays operate by either magnetic attraction, or magnetic induction. Unlike switching type electromechanical relays with fixed and usually ill-defined operating voltage thresholds and operating times, protective relays have well-established, selectable and adjustable time/current (or other operating parameter) operating characteristics. Protection relays may use arrays of induction disks, shaded-pole magnets, operating and restraint coils, solenoid-type operators, telephone-relay contacts, and phase-shifting networks.

Types of Relay

According to construction

Electromechanical Induction disc over-current relay Static relay Digital relay Numerical relay

Relays by functions

Page | 13

Page 14: Chandna seminar report  1421105031

Over current relay Distance relay Current differential protection Directional relay Synchronism check

Basic elements of Relay

Sensing Element Comparison Element Control Element

Page | 14

Sensing Element

Comparison

Element

Control Element

Relay

To trip or signal circuit(CB)

Page 15: Chandna seminar report  1421105031

A typical Protective Relay

Relay panel

Page | 15

Page 16: Chandna seminar report  1421105031

Circuit breaker(CB)A circuit breaker is an automatically operated electrical switch designed to protect an electrical circuit from damage caused by overload or short circuit. Its basic function is to detect a fault condition and interrupt current flow. Unlike a fuse, which operates once and then must be replaced, a circuit breaker can be reset (either manually or automatically) to resume normal operation. Circuit breakers are made in varying sizes, from small devices that protect an individual household appliance up to large switchgear designed to protect high voltage circuits feeding an entire city.

Operation

The circuit breaker must detect a fault condition; in low voltage circuit breakers this is usually done within the breaker enclosure. Circuit breakers for large currents or high voltages are usually arranged with protective rela pilot devices to sense a fault condition and to operate the trip opening mechanism. The trip solenoid that releases the latch is usually energized by a separate battery, although some high-voltage circuit breakers are self-contained with current transformers, protective relays and an internal control power source.

Once a fault is detected, within the circuit breaker must open to interrupt the circuit; some mechanically-stored energy (using something such as springs or compressed air) contained within the breaker is used to separate the contacts, although some of the energy required may be obtained from the fault current itself. Small circuit breakers may be manually operated, larger units have solenoids to trip the mechanism, and electric motors to restore energy to the springs.

Types of circuit breakers

Low-voltage circuit breakers Magnetic circuit breakers Thermal magnetic circuit breakers Common trip breakers

Page | 16

Page 17: Chandna seminar report  1421105031

Medium-voltage circuit breakers High-voltage circuit breakers Sulphur hexafluoride (SF6) high-voltage circuit breakers Disconnecting circuit breaker (DCB) Carbon dioxide (CO2) high-voltage circuit breakers

Oil circuit breaker

Page | 17

Page 18: Chandna seminar report  1421105031

Air circuit breaker

SF 6 Circuit breaker

Page | 18

Page 19: Chandna seminar report  1421105031

Lightning arrester(LA)A lightning arrester is a device used on electrical power systems and telecommunications systems to protect the insulation and conductors of the system from the damaging effects of lightning. The typical lightning arrester has a high-voltage terminal and a ground terminal. When a lightning surge (or switching surge, which is very similar) travels along the power line to the arrester, the current from the surge is diverted through the arrestor, in most cases to earth.

Page | 19

Page 20: Chandna seminar report  1421105031

Isolators

Isolators are used to isolate the high voltage from flow through line into the bus. It allows only needed voltage and rest is earth by itself if required.

Page | 20

Page 21: Chandna seminar report  1421105031

Conclusion

The objective of the protection devices(system) is to keep the power system stable by isolating only the components that are under fault, while leaving as much of the network as possible.

• There is no ‘fault free’ system.

• It is neither practical nor economical to build a ‘fault free’ system.

• Electrical system shall tolerate certain degree of faults.

Usually faults are caused by breakdown of insulation due to various reasons: Short Circuit, High Voltage, system aging, lighting, etc.

Page | 21

Page 22: Chandna seminar report  1421105031

References

1.Power System Protection and Switchgear by Badri Ram Tata McGraw-Hill Education, 01-Nov-2011

2. Fundamentals of Power System Protection  By Yeshwant G. Paithankar, S. R. Bhide

3. Electrical Power System Protection  By C. Christopoulos, A. Wright

4. Wikipedia

Page | 22