cergas detectores de gas para cc60 cc64
TRANSCRIPT
Cerberus® CerGasGas detectors for CC60/64
Commissioning and Maintenance instructions
Fire & Security ProductsSiemens Building Technologies
Data and design subject to change
without notice. / Supply subject to
availability.
� Copyright by
Siemens Building Technologies AG
Wir behalten uns alle Rechte an
diesem Dokument und an dem in ihm
dargestellten Gegenstand vor. Der
Empfänger anerkennt diese Rechte
und wird dieses Dokument nicht ohne
unsere vorgängige schriftliche
Ermächtigung ganz oder teilweise
Dritten zugänglich machen oder
ausserhalb des Zweckes verwenden,
zu dem es ihm übergeben worden ist.
We reserve all rights in this document
and in the subject thereof. By
acceptance of the document the
recipient acknowledges these rights
and undertakes not to publish the
document nor the subject thereof in
full or in part, nor to make them
available to any third party without our
prior express written authorization,
nor to use it for any purpose other
than for which it was delivered to him.
Nous nous réservons tous les droits
sur ce document, ainsi que sur l’objet
y figurant. La partie recevant ce
document reconnaît ces droits et elle
s’engage à ne pas le rendre
accessible à des tiers, même
partiellement, sans notre autorisation
écrite préalable et à ne pas
l’employer à des fins autres que
celles pour lesquelles il lui a été
remis.
Ci riserviamo ogni diritto relativo al
presente documento e sull’oggetto
illustrato in esso. La parte che riceve
il documento si impegna a non
renderlo accessibile a terzi, né per
intero né in parte, senza la nostra
previa autorizzazione scritta ed a non
usarlo per altri scopi di quello per il
quale è stato rilasciato.
Fire & Security Products
Siemens Building Technologies 10.2002
I
1 DP60/64–01 Pellistor Detector 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.1 Configuration of DP60/64 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.2 Calibration of DP60/64 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.3 Programming of the system for DP60/64 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.4 Change of the sensor 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.5 Remarks to DP60/64 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2 DO61–XX Optoacoustical Detectors 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2.1 Configuration of DO61 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2.2 Switch settings on detector module 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2.3 Calibration of DO61 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2.4 Programming of the system for DO61 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2.5 Change of the sensor 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2.6 Remarks to DO61 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3 DH60/64–XX Semiconductor Detectors 6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3.1 Configuration of DH60/64 6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3.2 Calibration of DH60/64 6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3.3 Programming of the system for DH60/64 7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3.4 Change of the sensor 7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3.5 Remarks to DH60/64 7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4 DE60/64–XX Electrochemical detectors 8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.1 Configuration of DE60/64 8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.2 Calibration of DE60/64 9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.3 Programming of the system for DE60/64 11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.4 Change of sensors 11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.5 Remarks to DE60/64 12. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5 Accessories for maintenance 13. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6 Assembly of detectors 14. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7 Hints for installation 15. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.1 Terminal connections 15. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.2 Dimensions 15. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.3 Explsosion hazard zones 15. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8 Calibration factors for Ex–detectors 16. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8.1 K–Factors DP60/64–01 (selection) 16. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8.2 K–Factors for DO61–02 (selection) 17. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8.3 Use of calibration factors (exemples) 18. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9 Properties of selected substances 19. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9.1 Combustible gases and vapours 19. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9.2 Toxic gases 20. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
10 Glossary 21. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Fire & Security Products
Siemens Building Technologies
II
10.2002
Changes Description
1368e New SIEMENS Layout.
New design of document structure.
Description of difference between New calibration and Re–cali-braion (CC60).
Description of detector assembly.
New calibration factors for DP and DO – Detectors.
New calibration gas for DE60/64–08 (NO2).
New calibration procedure for the oxygen detection.
1368f Design (Division/Group)
Fire & Security Products
Siemens Building Technologies e1368f
1
10.2002
1 DP60/64–01 Pellistor Detector
1.1 Configuration of DP60/64
Following material is necessary to compose a detector (see also section 6, page 15):
Type ofdetector
Detectorhousing
Detector print Configurationprint
Gas sensor Water pro-tection cap
Cable glandydetector housing
MG60–02439118
MPHP60438232
MPHP64439273
gprint
KPP60–01438070
tection cap
SSHP60438591
Z3I430(477662)
Ø3.5–8.7mm
Z3I650(499543)
Ø3.5–8.7mm
Z3I440(477675)
Ø8–11.7mm
DP60–01 X X X GSP60–01 X X X
DP64–01 X X XGSP60–01
438753 X X X
iTo keep the approvals the cable gland always has to be considered! Depending on thecable type choose the according cable gland. If you design the detector line as a stubevery detector has to be closed with the blind gland at the non used cable entry.
1.2 Calibration of DP60/64
Part of the commissionin of a gas detector is the calibration procedure. On a CC60 we de-fine two types of calibration modes:
New calibration (or first cali-bration)
This is the calibration done when the detector is com-missioned for the first time or if a sensor has beenchanged.
Recalibration This is the procedure done every time you calibrate adetector which has been already commissioned once,until you change the sensor.
For a proper calibration following points have to be considered:
Calibration gas: 2.64% methane (CH4) in synthetic air = 60% LEL
Flow rate: 0.5 – 1 l/min
Exposure to gas: 1 min
If zero gas has to be used:
Zero gas: Synthetic air (20% Oxygen O2 + 80% Nitrogen N2)
Flow rate: 0.5 – 1 l/min
Exposure to gas: 1 min
i If you calibrate on a CC60 please note that you have to follow exactly the times givenabove. If not, the CC60 won’t accept the calibration.
1.2.1 New calibration (or first calibration)
Conditioning time: at least 30 min
Detector signal default (I0): < 5 mA
Minimum required signal increase: 5 mA
iIf a sensor cannot reach the minimum required signal increase it has to be changed.With standard programming the CC60 unit doesn’t allow to store the calibration data ofsuch a detector. For special cases you can use the sensor code 99 (Tool G60 5min 2mA).
Fire & Security Products
Siemens Building Technologies e1368f
2
10.2002
1.2.2 Recalibration
If the deviation of the display of the concentration varies more than 10% you have to recali-brate the detector. At least, it is recommended to do such a recalibration every 12 month.
1.3 Programming of the system for DP60/64
The following programming parameters refer to the calibration concentration given in sec-tion 1.2.
CC60 CC64 Thresholds
Substance /Application
Zerogas
(Gas 1)
Calibra�tion gas Gas 2)
Detector type(Code on the
unit; Type in Tool)
Bargraph Detector type Range(if type
OTHER)
Cali�bration
gas
WarningWA
PrealarmPA
AlarmAL
Methane(Standard)
0 60 Code: 101PE60 (Norm)
0 − 60 EXPLO fix 60 20% LEL 40% LEL 60% LEL
Solvents(ReferenceHexane)
0 150 Code: 101PE60 (Norm)
0 − 30 OTHER(Display %)
0−150% 150 20% LELcorresp.
2000 ppm
25% LELcorresp.
2500 ppm
30% LELcorresp.
3000 ppm
LPG 0 120 Code: 101PE60 (Norm)
0 − 60 EXPLO fix 120 20% LEL 40% LEL 60% LEL
Propane (C3H8) 0 108 Code: 101PE60 (Norm)
0 − 60 EXPLO fix 108 20% LEL 40% LEL 60% LEL
Butane (C4H10) 0 120 Code: 101PE60 (Norm)
0 − 60 EXPLO fix 120 20% LEL 40% LEL 60% LEL
Biogas1) 0 60 Code: 101PE60 (Norm)
0 − 60 EXPLO fix 60 20% LEL 40% LEL 60% LEL
Hydrogen (H2) 0 84 Code: 101PE60 (Norm)
0 − 60 EXPLO fix 84 20% LEL 40% LEL 60% LEL
1) Because of the risk of poisoning of the Pellistor due to compounds contained in biogas, we recommend to use the DO61–02 instead.
If another calibration gas is used or another application is requested please conctact CE–CH.
1.4 Change of the sensor
If the loss of signal since the commissioning day is >30% (means that the actual signal in-crease is <70% of the signal incrase at commissioning) than the sensor has to be replaced.
On sensor change you must execute a new calibration! On a CC60 you first have todelete the old calibration data (with F4 160 ––> OFF) before starting the new calibration.
1.5 Remarks to DP60/64
Life time The sensor life time is reduced if lead, halogens, sulfur compounds or silicones affect thesensor.
Positioning The mentioned indications are generally given. For special cases the positioning of the de-tector can vary. For cases of unclearness please contact your local gas specialist orCE–CH.Methane, Hydrogen: top, ceilingPropane, Butane, LPG:bottom, floorBiogas: both, on the floor as well as on the ceilingSolvents: on the floor
Fire & Security Products
Siemens Building Technologies e1368f
3
10.2002
2 DO61–XX Optoacoustical Detectors
2.1 Configuration of DO61
Following material is necessary to compose a detector (see also section 6, page 15):
Type ofdetector
Detectorhousing
Detectorprint
Sensor housingSocket
Sensor housingCover
Gas sensor Cable glandydetector housing
MG60–02439118
MPO61–01508890
gSocket
GVX61–01501460
gCover
GKX61–01508845
Z3I430(477662)
Ø3.5–8.7mmCC60
Z3I650(499543)
Ø3.5–8.7mmCC64
Z3I440(477675)
Ø8–11.7mmCC60/64
DO61–01 X X X X GSO61–01 (CO2)501295
X X X
DO61–02 X X X X GSO61–02 (HC)518518
X X X
iTo keep the approvals the cable gland always has to be considered! Depending on thecable type choose the according cable gland. If you design the detector line as a stubevery detector has to be closed with the blind gland at the non used cable entry.
2.2 Switch settings on detector module
Before commissioning, the swiches S1 and S2 have to be set according to the applicationdesired (CC60 or CC64).
MPO61–01
S1 S2
O N1 2
OFF OFF: TEST
ON OFF: CC64
OFF ON: not used
ON ON: CC60
S2: CC60: Adress 1 to E (1 – 14)0 and F not used
CC64:
0 (4 mA) and F (20 mA)
For this application the
between 1 to Edetector switch has to be set
If you turn on the system, the detectors are initialized. It is possible that at this moment,the concentration on the display rises up (increase of signal current). For this reason itis recommended to suppress all the transmissions of the alarm on this moment.
2.3 Calibration of DO61
Part of the commissionin of a gas detector is the calibration procedure. On a CC60 we de-fine two types of calibration modes:
New calibration (or first cali-bration)
This is the calibration done when the detector is com-missioned for the first time or if a sensor has beenchanged.
Recalibration This is the procedure done every time you calibrate adetector which has been already commissioned once,until you change the sensor.
Fire & Security Products
Siemens Building Technologies e1368f
4
10.2002
For a proper calibration following points have to be considered:
Detector type Substance Calibration gas
DO61–01: CO2 2.0% carbon dioxide (CO2) in synthetic air
DO61–02: HC 2.64% methane (CH4) in synthethic air = 60% LEL
Flow rate: 0.5 – 1 l/min
Eposure to gas: 5 min
If zero gas has to be used:
Zero gas: Synthetic air (20% Oxygen O2 + 80% Nitrogen N2)
Flow rate: 0.5 – 1 l/min
Exposure to gas: 5 min
i If you calibrate on a CC60 please note that you have to follow exactly the times givenabove. If not, the CC60 won’t accept the calibration.
2.3.1 New calibration (or first calibration)
Conditioning time: at least 30 min
Detector signal default (I0): 4 mA ± 0.5 mA
Min. required signal incr. DO61–01: 14 mA
Min. required signal incr. DO61–02: 8 mA
2.3.2 Recalibration
If the deviation of the display of the concentration varies more than 10% you have to recali-brate the detector. At least, it is recommended to do such a recalibration every 12 month.
2.4 Programming of the system for DO61
The following programming parameters refer to the calibration concentration given in sec-tion 2.3.
CC602) CC64 Thresholds
Substance /Application
Zerogas
(Gas 1)
Calibra�tion gas(Gas 2)
Detector type(Code on
unit; Type inTool)
Bargraph Detectortype
Range(if type OTHER)
Calibrationgas
WarningWA
PrealarmPA
AlarmAL
CO2(Standard)3)
0 20 Code: 225PA61 (CO2)
0 − 20 OTHER(Display %)
0 − 20 % 20 55000 ppm
1010000ppm
2020000ppm
Methane(Standard)
0 60 Code: 140PA61 (CH4)
0 − 60 EXPLO fix 60 20% LEL 40% LEL 60% LEL
Solvents(normal)
0 60 Code: 140PA61 (CH4)
0 − 30 EXPLO fix 60 20% LEL 25% LEL 30% LEL
Solvents(sensitive)
0 120 Code: 140PA61 (CH4)
0 − 30 EXPLO fix 120 20% LEL 25% LEL 30% LEL
LPG 0 42 Code: 140PA61 (CH4))
0 − 60 EXPLO fix 42 20% LEL 40% LEL 60% LEL
Propane(C3H8)
0 42 Code: 140PA61 (CH4)
0 − 60 EXPLO fix 42 20% LEL 40% LEL 60% LEL
Butane(C4H10)
0 42 Code: 140PA61 (CH4)
0 − 60 EXPLO fix 42 20% LEL 40% LEL 60% LEL
Biogas 0 60 Code: 140PA61 (CH4)
0 − 60 EXPLO fix 60 20% LEL 40% LEL 60% LEL
2) The programming of optoacoustical detectors on a CC60 is only possible starting from Eprom–Version 5.18 (1.05–18).3) The values displayed on the units is always in per mil. This means that a value of 5 displayed corresponds to a concentration of 0.5% CO2. On aCC64 the display of the % sign is confusing and should be ignored.
If another calibration gas is used or another application is requested please conctactCE–CH.
Fire & Security Products
Siemens Building Technologies e1368f
5
10.2002
2.5 Change of the sensor
If the loss of signal since the commissioning day is >30% (means that the actual signal in-crease is <70% of the signal incrase at commissioning) than the sensor has to be replaced.
On sensor change you must execute a new calibration! On a CC60 you first have todelete the old calibration data (with F4 160 ––> OFF) before starting the new calibration.
2.6 Remarks to DO61
Heavy vibrations and air movements can affect the detector signal (incorporated micr-phone!). In such cases an appropriate cushion system has to be designed.The DO61–02 (HC) can not be used for the detection of Hydrogen (H2)!
Positioning The mentioned indications are generally given. For special cases the positioning of the de-tector can vary. For cases of unclearness please contact your local gas specialist orCE–CH.Carbon dioxide (CO2): bottom, floorMethane: top, ceilingPropane, Butane, LPG:bottom, floorBiogas: both, on the floor as well as on the ceilingSolvents: bottom, floor
Fire & Security Products
Siemens Building Technologies e1368f
6
10.2002
3 DH60/64–XX SemiconductorDetectors
3.1 Configuration of DH60/64
Following material is necessary to compose a detector (see also section 6, page 15):
Type ofdetector
Detectorhousing
Detector print Configura-tion print
Gas sensor(Manufac
Sensorhousing
Water pro-tection cap
Cable glandydetector housing
MG60–02439118
MPHP60438232
MPHP64439273
gtion print
KPH60–01/7438106
(Manufac-turer’stype)
housing
SGH60438737
tection cap
SSHP60438591
Z3I430(477662)
Ø3.5–8.7mm
Z3I650(499543)
Ø3.5–8.7mm
Z3I440(477675)
Ø8–11.7mm
DH60–03 X X X GSH60–03438902
X X X X
DH64–03 X X X438902
(TGS 826) X X X X
DH60–05 X X X GSH60–05438928
X X X X
DH64–05 X X X438928
(TGS823) X X X X
DH60–06 X X X GSH60–06438931
X X X X
DH64–06 X X X438931
(TGS832) X X X X
iTo keep the approvals the cable gland always has to be considered! Depending on thecable type choose the according cable gland. If you design the detector line as a stubevery detector has to be closed with the blind gland at the non used cable entry.
3.2 Calibration of DH60/64
Part of the commissionin of a gas detector is the calibration procedure. On a CC60 we de-fine two types of calibration modes:
New calibration (or first cali-bration)
This is the calibration done when the detector is com-missioned for the first time or if a sensor has beenchanged.
Recalibration This is the procedure done every time you calibrate adetector which has been already commissioned once,until you change the sensor.
For a proper calibration following points have to be considered:
Detector type Substance Calibration gas
DH60/64–03: NH3 1000 ppm ammonia (NH3) in synthethic air
DH60/64–05: Solvents 600 ppm hexane (C6H14) in synthethic air
DH60/64–06: Freons 3000 ppm R–134a in synthethic air
Flow rate: 0.5 – 1 l/min
Exposure to gas: 2 min (for CC60 until version 5.17 (Code 99): 5 min)
If zero gas has to be used:
Zero gas: Synthetic air (20% Oxygen O2 + 80% Nitrogen N2)
Flow rate: 0.5 – 1 l/min
Exposure to gas: 2 min
i If you calibrate on a CC60 please note that you have to follow exactly the times givenabove. If not, the CC60 won’t accept the calibration.
Fire & Security Products
Siemens Building Technologies e1368f
7
10.2002
3.2.1 New calibration (or first calibration)
Conditioning time: at least 2 h
Detector signal default (I0): < 4 mA
Min. required signal incr. (all types): 2 mA
iThe conditioning time has to be kept. The sensors need a certain time to be set up tothe existing conditions. If you callibrate the sensors too early, the signal can drift and arecalibration would be necessary.
3.2.2 Recalibration
If the deviation of the display of the concentration varies more than 10% you have to recali-brate the detector. At least, it is recommended to do such a recalibration every 12 month.
3.3 Programming of the system for DH60/64
The following programming parameters refer to the calibration concentration given in sec-tion 3.2.
CC604) CC64 Thresholds5)
Substance /Application
Zerogas
(Gas 1)
Calibra�tion gas(Gas 2)5)
Detector type(Code on unit;Type in Tool)
Bargraph Detector type Range(if type
OTHER)
Cali�brationgas5)
WarningWA
PrealarmPA
AlarmAL
AmmoniaDH60/64−03
0 10001000 ppm
Code: 171HL60 (NH3)
0 − 1000 OTHER(Display ppm)
0 − 2000 ppm 10001000 ppm
600200 ppm
830500 ppm
10001000 ppm
SolventsDH60/64−05(Standard)
0 870600 ppm
Code: 170HL60
(Solvent)
0 − 1000 OTHER(Display %)
0 − 2000 ppm 870600 ppm
595200 ppm
820500 ppm
10001000 ppm
SolventsDH60/64−05(less sensitive)
0 1470600 ppm
Code: 170HL60
(Solvent)
0 − 2000 OTHER(Display %)
0 − 3000 ppm 1470600 ppm
1390500 ppm
16901000 ppm
20002000 ppm
FreonsDH60/64−06
0 30003000 ppm
Code: 172HL60 (Freon)
0 − 3000 OTHER(Display %)
0 − 5000 ppm 30003000 ppm
1000300 ppm
19501000 ppm
30003000 ppm
4) Up to Version 5.17 (1.05–17), semiconductor detectors where programmed on a CC60 with code 99 (Tool: G60 5min 2mA)!5) The values given are the values which have to be programmed on the unit. The corresponding concentration in ppm is given below.
Differing programmings have to be discussed with CE–CH.Because of its non–linearity a semiconductor sensor cannot display a quantitative va-lue according to the concentration measured on site. The concentration displayed cor-responds only at one point to the effective value on site (e.g. at the alarm point). Werecommend therefore to label only the thresholds Warning, Prealarm and Alarm wi-thout any mention to the concentration value. Important: The displayed values are not ppm’s! You can describe them better as scaling units or display units!
3.4 Change of the sensor
If the loss of signal since the commissioning day is >30% (means that the actual signal in-crease is <70% of the signal incrase at commissioning) than the sensor has to be replaced.
On sensor change you must execute a new calibration! On a CC60 you first have todelete the old calibration data (with F4 160 ––> OFF) before starting the new calibra-tion.
3.5 Remarks to DH60/64
Fire & Security Products
Siemens Building Technologies e1368f
8
10.2002
Because of the non–linearity and the high sensitivity of semiconductor sensors, applica-tions with it have to be considered carefully. Please conctact CE–CH if you have anydoubts.
Fire & Security Products
Siemens Building Technologies e1368f
9
10.2002
4 DE60/64–XX Electrochemicaldetectors
4.1 Configuration of DE60/64
Following material is necessary to compose a detector (see also section 6, page 15):
Detectortype
Detectorhousing
Detector print Configura-tion print
Gas sensor Sensor housing Cable glandtype housing
MG60–02439118
MPE60438261
MPE64439286
gtion print
SGE60–014386986)7)
SGE60–044873778)
Z3I430(477662)
Ø3.5–8.7mm
Z3I650(499543)
Ø3.5–8.7mm
Z3I440(477675)
Ø8–11.7mm
DE60–02X
X KPE60–1/2 GSE60–02 XX X
DE64–02X
XKPE60–1/2
437806GSE60–02
437916X
X X
DE60–03X
X KPE60–03 GSE60–03 XX X
DE64–03X
XKPE60–03
438180GSE60–03
437929X
X X
DE60–05X
X KPE60–05 GSE60–05 XX X
DE64–05X
XKPE60–05
439134GSE60–05
437945X
X X
DE60–06X
X KPE60–06 GSE60–06 XX X
DE64–06X
XKPE60–06
437822GSE60–06
437958X
X X
DE60–07X
X KPE60–07 GSE60–07 XX X
DE64–07X
XKPE60–07
437848GSE60–07
437961X
X X
DE60–08X
X KPE60–08 GSE60–08 XX X
DE64–08X
XKPE60–08
437851GSE60–08
437974X
X X
DE60–09X
X KPE60–09 GSE60–09 XX X
DE64–09X
XKPE60–09
437864GSE60–09
437987X
X X
DE60–10X
X KPE60–10 GSE60–10 XX X
DE64–10X
XKPE60–10
438067GSE60–10
437990X
X X
DE60–11X
X KPE60–11 GSE60–11 XX X
DE64–11X
XKPE60–11
437880GSE60–11
438407X
X X
DE60–12X
X KPE60–12 GSE60–12 XX X
DE64–12X
XKPE60–12
439176GSE60–12
439163X
X X
DE60–13X
X KPE60–13 GSE60–13 XX X
DE64–13X
XKPE60–13
518013GSE60–13
518000X
X X
DE60–21X
X KPE60–21 GSE60–21 SGE60–02 X X
DE64–21X
XKPE60–21
437877GSE60–21
438805SGE60–024384527)
X X
7) Ex–d8) not approved for the application in Ex–zones. If such an application is required please contact CE–CH.
iTo keep the approvals the cable gland always has to be considered! Depending on thecable type choose the according cable gland. If you design the detector line as a stubevery detector has to be closed with the blind gland at the non used cable entry
When assembling the sensor please be careful with the mounting of the sensor cell. Itcan happen that if the sensor housing is closed, the caused vibrations can unplug thesensor cell again and it drops out of the plug.
Fire & Security Products
Siemens Building Technologies e1368f
10
10.2002
4.2 Calibration of DE60/64
Part of the commissionin of a gas detector is the calibration procedure. On a CC60 we de-fine two types of calibration modes:
New calibration (or first cali-bration)
This is the calibration done when the detector is com-missioned for the first time or if a sensor has beenchanged.
Recalibration This is the procedure done every time you calibrate adetector which has been already commissioned once,until you change the sensor.
For the calibration of electrochemical sensors they can be divided into two different groups,depending of the time of calibration needed:– for the first group following data is given:
Detector type Substance Calibration gas
DE60/64–02: CO 500 ppm carbon monoxide (CO) in synthetic air
DE60/64–03: H2S 25 ppm hydrogen sulfide (H2S) in synthetic air
DE60/64–05: SO2 50 ppm sulfur dioxide (SO2) in synthetic air
DE60/64–06: NO 50 ppm nitrogen monoxide (NO) in nitrogen (N2)
DE60/64–07: Cl2 20 ppm chlorine (Cl2) in synthetic air (or nitrogen)
DE60/64–09: HCN 50 ppm hydrocyanic acid (HCN) in synthetic air
DE60/64–12: H2 1000 ppm hydrogen (H2) in synthetic air
DE60/64–21: N2 Nitrogen (N2) 100%
Flow rate: 0.5 – 1 l/min
Exposure to gas: 3 min
– for the second group following data is given:
Detector type Substance Calibration gas
DE60/64–08: NO2 20 ppm nitrogen dioxide (NO2) in synthetic air
DE60/64–10: HCl 50 ppm hydrogen chloride (HCl) in synthetic air (or N2)
DE60/64–11: NH3 60 ppm ammonia (NH3) in syntheic air
DE60/64–13: C2H4O 20 ppm ethylene oxide (ETO) in synthetic air
Flow rate: 0.5 – 1 l/min
Exposure to gas: 5 min
If zero gas has to be used:
Zero gas: Synthetic air (20% Oxygen O2 + 80% Nitrogen N2)
Flow rate: 0.5 – 1 l/min
Exposure to gas: 3 min
i If you calibrate on a CC60 please note that you have to follow exactly the times givenabove. If not, the CC60 won’t accept the calibration.
4.2.1 New calibration (or first calibration)
Conditioning time: at least 2 h
Detector signal default (I0): < 4 mA
Minmum required signal increase: 2 mA for NH3 and ETO–sensor4 mA all other types
iThe conditioning time has to be kept. Some sensors are delivered with a bias–battery on it. If this battery is low or missing,the sensors have to be connected to a control unit for at least 48h. Do not start the cali-bration before the detector signal default (I0) is <4 mA.
Fire & Security Products
Siemens Building Technologies e1368f
11
10.2002
4.2.2 Recalibration
If the deviation of the display of the concentration varies more than 10% you have to recali-brate the detector. At least, it is recommended to do such a recalibration every 12 month.
4.2.3 Calibration of oxygen detectors (DE60/64–21)
The calibration of oxygen sensors can be done as follow (see also drawing below):� CC60
– Oxygen displacement (O2–removal)After having started the calibration � wait at least 1 min before applying the calibrationgas �. Apply the calibration gas (nitrogen, N2) to the sensor for exactly 3 min �.
When you program a oxygen detector for the monitoring of oxygen displacement it’svery important that you program the sensor (and the bargraph) as invers (see alsosection 4.3).
– Oxygen increase monitoring (O2–increase)After you start � the calibration apply the calibration gas (nitrogen) for at least 4 minbevore you remove it for 3 min �. After this 3 min you must reapply the calibration gas(nitrogen) for at least 3 min �!
4 min 3 min 3 min� � �
Oxygen increase monitoring (O2–in-crease)
1 min 3 min 3 min� � �
Oxygen displacement (O2–removal)
Det
ecto
r si
gnal
Det
ecto
r si
gnal
� CC64– Oxygen displacement (O2–removal) or oxygen increase monitoring (O2–increase)
After having started the calibration � wait at least 1 min before applying the calibrationgas �. Apply the calibration gas (nitrogen, N2) to the sensor for exactly 3 min �.
Fire & Security Products
Siemens Building Technologies e1368f
12
10.2002
4.3 Programming of the system for DE60/64
The following programming parameters refer to the calibration concentration given in sec-tion 4.2.
CC60 CC64 Thresholds
Detector /Application
Zerogas
(Gas 1)
Calibra�tion gas(Gas 2)
Detector type(Code on unit;Type in Tool)
Bargraph Detectortype
Range(if type
OTHER)
Calibra�tion
gas5)
WarningWA
PrealarmPA
AlarmAL
DE60−02(People)
0 500 Code: 066EC60 (CO)
0 − 60 GSE60−02 fix 500 15 30(TLV/TWA)
60(STEL)
DE60−02(Parking)9)
0 500 Code: 066EC60 (CO)
0 − 200 GSE60−02 fix 500 50 100 200
DE60−03(People)
0 25 Code: 061EC60 (H2S/50)
0 − 20 GSE60−03 fix 25 5 10(TLV/TWA)
20(STEL)
DE60−05(People)
0 50 Code: 063EC60 (SO2)
0 − 10 GSE60−05 fix 50 2(TLV/TWA)
4(STEL)
10
DE60−06(People)
0 50 Code: 064EC60 (NO)
0 − 50 GSE60−06 fix 50 15 25(TLV/TWA)
50
DE60−07(People)
0 10 Code: 067EC60 (CL2)
0 − 5 GSE60−07 fix 10 1 3 5
DE60−08(People)
0 20 Code: 068EC60 (NO2)
0 − 10 GSE60−08 fix 20 3(TLV/TWA)
6(STEL)
10
DE60−09(People)
0 50 Code: 021EC60 (HCN)
0 − 50 GSE60−09 fix 50 10(TLV/TWA)
20(STEL)
50
DE60−10(People)
0 50 Code: 022EC60 (HCL)
0 − 25 GSE60−10 fix 50 5(TLV/TWA)
10(STEL)
25
DE60−11(People)
0 60 Code: 071EC60 (NH3)
0 − 40 GSE60−11 fix 60 10 20(TLV/TWA)
40(STEL)
DE60−12(Sensitive)
0 1000 Code: 020EC60 (H2)
0 − 1000 OTHER(Display ppm)
0 − 2000 ppm 1000 250 500 1000
DE60−13(People)
0 10 Code: 070EC60 (ETO)
0 − 5 OTHER(Display ppm)
0 − 20 ppm 10 1(TLV/TWA)
2 5
DE60−21(O2−removal)
21 0 Code: 001EC60 (O2)
Sensor invers
21 − 17(invers)
OXY25−0% fix 0 19 18 17
DE60−21(O2−increase)
0 21 Code: 001EC60 (O2)
0 − 25 OXY0−25% fix 0 23 24 25
9) if no statutory regulations exist (e. g. CH: SWKI 96–1, D: VDI 2053).
If another calibration gas is used or another application is requested please conctact CE–CH.
4.4 Change of sensors
If the loss of signal since the commissioning day is >30% (means that the actual signal in-crease is <70% of the signal incrase at commissioning) than the sensor has to be replaced.
On sensor change you must execute a new calibration! On a CC60 you first have todelete the old calibration data (with F4 160 ––> OFF) before starting the new calibration.
Fire & Security Products
Siemens Building Technologies e1368f
13
10.2002
4.5 Remarks to DE60/64
Following sensors are delivered with a bias–battery (remove it before commissioning):– GSE60–06 (NO), GSE60–10 (HCl), GSE60–11 (NH3), GSE60–13 (ETO)Following sensors are delivered with a short–circuit guard (remove it before commissioning):– GSE60–02 (CO), GSE60–03 (H2S), GSE60–05 (SO2), GSE60–07 (Cl2) GSE60–08
(NO2), GSE60–09 (HCN), GSE60–12 (H2) und GSE60–21 (O2)
Use only PTFE– (Teflon) tubes for the calibration of electrochemical detectors (exep-tion can be made on CO–, H2– and O2–detectors)!
Positioning For cases of unclearness please contact your local gas specialist or CE–CH. Some in-formations about can be found in the application sheets in the CerGas documentation (e.g.1708, detection of carbon monoxide).
Fire & Security Products
Siemens Building Technologies e1368f
14
10.2002
5 Accessories for maintenance
Following material can be ordered directly at CE–CH:
Type Art.�Nr. Designation
DZ60−TS 504043 Test case complete (incl. pressure regulator, teflon tube,
test adapters RE11 and KAE60−1, without gas cans)
RE11 381224 Test adapter for DP60/64− and DH60/64−Detectors
KAE60−1 439147 Test adapter for DO61− and DE60/64−Detectors
KA61−01 532251 Test adapter for DX61−Detectors (not for DO61!)
DZ60−TGCH4 538404 Gas can methane 60% LEL
DZ60−TGCO 538417 Gas can carbon monoxide CO 500 ppm
DZ62−TGCO 551672 Gas can carbon monoxide CO 250 ppm
DZ60−TGCO2 538420 Gas can carbon dioxide CO2 2%
DZ60−TGHEXAN 538433 Gas can hexane 600 ppm
DZ60−TGH2S 538446 Gas can hydrogen sulfide H2S 25ppm
DZ60−TGN2 538459 Gas can nitrogen N2 100%
DZ60−TGNH3−H 538463 Gas can ammonia NH3 1000 ppm
DZ60−TGAIR 538475 Gas can synthetic air
DZ60−TGETO 538488 Gas can ethylene oxide EtO (C2H4O) 20 ppm
DZ60−TGH2 538491 Gas can hydrogen H2 1000 ppm (2.5% LEL)
DZ60−TGNH3−L 538501 Gas can ammonia NH3 60 ppm
DZ60−TGNO 538514 Gas can nitrogen monoxide NO 50 ppm
DZ60−TGSO2 538527 Gas can sulfur dioxide SO2 50 ppm
DZ60−TGR134A 538530 Gas can freon R134a 3000 ppm
LT60 507477 Line tester for CC60
KUNS60−01 438193 Artificial sensor10)
10) works only with MPHP60/64 and KPH60−01/07
Fire & Security Products
Siemens Building Technologies e1368f
15
10.2002
6 Assembly of detectors
SGH60
PellistorGSP60–01
MPO61–01
MG60–02
SinterEl.–chem.sensorsSemi–
conductor
Water protection cap (SSHP60)
PPOwithoutSinter
Alu
Detector housing
Ex–d
Ex–d
Ex–d
SinterSinter
MPE60
KPP60
KPH60
KPE60–xx
MPHP60
Ex–d
ÄÄÄÄ
Z3Ixxx
Alu
Ex–d
SGE60–04Non Ex –applications
SGE60–02Oxygen
SGE60–01
O2
Fire & Security Products
Siemens Building Technologies e1368f
16
10.2002
7 Hints for installation
7.1 Terminal connections
The description about the terminal connections given in this document is only general. Adetailed description of all the possible connections of detectors to the CerGas units can befound in document e1954 ’Installation instructions for CerGas detectors’.The assignment of the connections is all the same for all detector types. Only the definitionof the supply earthing (+ or –) can be different.
Clamp CC60 CC64
4a n.c. n.c.
6 – 24V 0V (GND) (–)
4 – 24V not used
5 Signal Signal
1 Signal GND not used
1a 0V (GND) (+) + 24V
7.2 Dimensions
ÉÉÉÉÉÉÉÉÉ
88142
ÉÉÉÉÉÉ
E = 47P = 39H = 55O = 64
O, E = 47P, H = 36
Electrochemical sensor EPellistor PSemiconductor sensor HOptoacoustic sensor O
M20x1,5
M6
max. ∅ 6
max. ∅ 6
108
88
112
The cable entry thread connection of the detector housing MG60–02 has core diameterM20x1,5mm (not PG16!).
7.3 Explsosion hazard zones
– Earthing of the detector housing– Comply with the regulations for each country
4A 6 4 5 1 1A
4A 6 4 5 1 1A
Fire & Security Products
Siemens Building Technologies e1368f
17
10.2002
8 Calibration factors for Ex–detectors
As the use of these calibration factors affects the functioning of a gas warning system only atrained person should work with it. For most of the applications standard programming issufficient. If there is a need to fulfill special requirements we recommend to contact the localgas specialist or directly CE–CH.
iThe lists above contain only a selection of detectable substances. If you don’t find therequested substance on these lists it doesn’t mean that the detector doesn’t detect thissubstance!More informations can be given by local gas specialist or directly by CE–CH.
8.1 K–Factors DP60/64–01 (selection)
Substance K–Factor
Acetaldehyde 1.6
Acetone 2.0
Ammonia 0.9
Fuel (car) 3.5
Butadiene, 1,3– 1.8
Butane, n– 2.1
Butylacetate 4.0
Cyclohexane 2.5
Diethylether 2.2
Acetic acid 4.7
Ethane 1.4
Ethanol 1.6
Ethylacetate 2.5
Ethylenchloride Inhibitor, no such application with DP60/64
Ethylmercaptane Poison, no such application with DP60/64
Ethylmethylcetone (MEK) 2.5
Heptane 2.6
Hexamethyldisiloxane (HMDSO) Gift, keine solche Applikation mit DP60/64
Hexane 2.4
Hydrogen 1.4
Isobutane 1.9
Isopentane 2.3
Isopropanol 2.4
Methane 1.0 (Reference)
Methanol 1.6
Methylmetacrylate (MMA) 2.1
Octane 3.8
Pentane 2.1
Propane 1.7
Tetrahydrofurane 3.2
Toluene 2.4
Trichlorethane Inhibitor, no such application with DP60/64
Triethylamine (TEA) 3.1
Xylene 4.0
Fire & Security Products
Siemens Building Technologies e1368f
18
10.2002
8.2 K–Factors for DO61–02 (selection)
Substance K–Factor
Acetaldehyde 1.8
Acetone 2.4
Fuel (car) 1.8
Butadiene, 1,3– 4.0
Butane, n– 0.7
Butylacetate 1.3
Cyclohexane 0.6
Diethylether 0.6
Acetic acid 0.3
Ethane 0.5
Ethanol 0.5
Ethylacetate 1.3
Ethylenchloride 1.5
Ethylmercaptane 1.0
Ethylmethylcetone (MEK) 1.5
Heptane 0.5
Hexamethyldisiloxane (HMDSO) 1.9
Hexane 0.7
Isobutane 0.9
Isopentane 0.6
Isopropanol 0.9
Methane 1.0 (Reference)
Methanol 0.4
Methylisobutilcetone (MIBK) 1.0
Methylmetacrylate (MMA) 1.2
Methyl–t–Butylether (MTBE) 0.5
Octane 0.7
Pentane 0.5
Propane 0.7
Tetrahydrofurane 0.7
Toluene 1.8
Trichlorethane 1.8
Triethylamine (TEA) 0.7
Xylene 1.8
Fire & Security Products
Siemens Building Technologies e1368f
19
10.2002
8.3 Use of calibration factors (exemples)
Calibration factors are used whenever a detector is calibrated not with the substance todetect but with another type of gas, e.g. a reference gas. Cerberus uses 2.64% methane inair (corresponding to 60% LEL) as reference (K–factor = 1).
To calculate the correct calibration concentration to program you can use following formula(all the concentrations are given in % LEL of the corresponding substances):
Concentration(calibration gas) * K–factor(gas to detect) � K–factor(calibration gas)
8.3.1 Exemple 1: Detection of hexane, calibration gasmethane (Cerberus reference gas)
If you have to calibrate a Pellistor (DP60/64) with 60% LEL methane for the detection ofhexane you have to program following concentration:
60% UEG * K–factor(hexane) = 60% LEL * 2.5 = 150% LEL
This programming means, that 150% LEL hexane produce the same signal at the detectoras 60% LEL methane do. If you test for example such a sensor with 60% LEL methane youwill get a display of 150%. If you test it with 50% LEL hexane you will get also 50% displayed(± measuring error).
8.3.2 Exemple 2: Detection of hydrogen (H2), calibration gaspropane
If you calibrate a Pellistor (DP60/64) wtih 50% LEL propane to detect hydrogen (H2) youhave to program following concentration:
50% LEL * K–factor(hydrogen) ÷ K–factor(propane) =50% LEL * 1.4 ÷ 1.7 = 41% LEL
This means, that you need ’only’ (relative, related to %LEL) a concentration of 41% LEL ofhydrogen to get the same signal at the detector as with 50% LEL propane!
iThe proper calculation of the calibration concentration to program is very important asit is neccessary for the correct functioning of the system. If there are any unclearnes-ses please contact your local gas specialist or CE–CH directly.
Fire & Security Products
Siemens Building Technologies e1368f
20
10.2002
9 Properties of selected substances
9.1 Combustible gases and vapours
Name Formula MoleWt.
BP°C
Vap.Dens.Air=1
Liq.Dens.g/l
FP°C
LELVol.%
UELVol.%
Acetone C3H6O 58.1 56 2.0 790 –19 2.15 13
Acetylene C2H2 26.0 –84 0.9 – –18 2.3 78
Ammonia NH3 17.0 –33 0.6 – –20 15.4 33.6
Butane C4H10 58.1 –1 2.1 – –60 1.4 9.3
Butyl alcohol C4H9OH 74.1 118 2.6 810 29 1.4 11.3
Carbon disulphide CS2 76.1 46 2.6 1260 –30 0.6 60
Carbon monoxide CO 28.0 –191 0.97 – – 10.9 76
Cyclohexane C6H12 84.2 81 2.9 780 –18 1.2 8.3
Cyclopentane C5H10 70.1 49 2.4 750 –51 1.5 8.7
Decane C10H22 142.3 174 4.9 730 46 0.7 5.4
Diethyl ether (C2H5)2O 74.1 34 2.55 710 –20 1.7 36
Ethane C2H6 30.1 –89 1.0 440 –135 2.7 14.7
Ethyl alcohol C2H5OH 46.1 78 1.6 790 12 3.5 15
Ethylene C2H4 28.0 –104 0.97 – –136 2.3 32
Ethylene oxide C2H4O 44.0 11 1.52 880 –18 2.6 100
Heptane C7H16 100.2 98 3.46 680 –4 1.1 6.7
Hexane C6H14 86.2 69 2.79 660 –21 1.0 8.1
Hydrogen H2 2.0 –253 0.07 – – 4.0 77
Hydrogen sulphide H2S 34.0 –60 1.19 – – 4.3 45.5
Methane CH4 16.0 –161 0.55 – – 4.4 16.5
Methyl alcohol CH3OH 32.0 65 1.11 790 11 5.5 36
Nonane C9H20 128.3 151 4.43 720 30 0.7 5.6
Octane C8H18 114.2 126 3.94 700 12 0.8 6.5
Pentane C5H12 72.2 36 2.48 630 –20 1.4 7.8
Propane C3H8 44.1 –42 1.56 – – 1.7 10.9
Toluene C7H8 92.1 111 3.18 870 6 1.2 7.8
Xylene C8H10 106.2 144 3.66 880 30 1.0 7.0
While CERBERUS has taken care to ensure the accuracy of the information contained herein, it accepts no responsi-bility for the consequences of any use thereof.
Fire & Security Products
Siemens Building Technologies e1368f
21
10.2002
9.2 Toxic gases
Name Formula MAK*ppm
TLV* (TWA)ppm
STELppm
Odour thresholdppm
Ammonia NH3 50 25 35 5
Carbon dioxide CO2 5000 5000 30000 –
Carbon disulfide CS2 10 4 12 0.2
Carbon monoxide CO 30 35 60 –
Chlorine Cl2 0.5 0.5 1 0.02
Ethylene oxide C2H4O 1 1 5 700
Hydrogen chloride HCl 5 5 10 5
Hydrogen cyanide HCN 10 10 20 1
Hydrogen sulfide H2S 10 10 15 0.1*) Treshold values vary from country to country! The values above are CH and USA figures (1997).
Fire & Security Products
Siemens Building Technologies e1368f
22
10.2002
10 Glossary
Bias battery The bias battery is used for the preconditioning of electrochemical sensors. Its battery sup-plies a bias current, preparing the sensor for the use at the shortest possible time. The sen-sors which require a conditioning period are normally delivered with this bias battery.
Conditioning time The period required to prepare an electrochemical sensor for use. The sensor must eitherbe connected to the unit while it is running, or be pre–conditioned by the bias battery
Detector signal default The current delivered by a gas detector, when no gas concentration is detected at the sen-sor.
Calibration current The current delivered by a gas detector , when the calibration concentration is detected atthe sensor.
TLV/TWA The Threshold Limit Value/Time Weighted Average is the concentration to which a personcan be exposed for eight hours a day (within a week of 40h) without danger to health.
STEL The Short Term Exposure Limit is the concentration, which can not be exceeded for morethan 10 min for one time during a day.
IDLH Immediately dangerous to life or healthA person must not be exposed to the given concentration for more than 30 minutes.
Calibration factor The calibration factor can be used for calibration of gas detectors for flammable gases andliquids. Because of the different cross sensitivity of the detectors the calibration factor isused to set up those detectors according to the desired application.
Fire & Security Products
Siemens Building Technologies Back
23
10.2002
Fire & Security Products
Siemens Building Technologies Back
24
10.2002Document no.
Edition
e1368f
10.2002
Siemens Building Technologies AG
CH�8708 Männedorf
Alte Landstrasse 411
Phone
Fax
www.cerberus.ch
+41 1 − 922 61 11
+41 1 − 922 64 50
CG60
7
CG64
7
Manual
Section