CENTERLINE 2500 Motor Control CentersSelection Guide
Contents
CENTERLINE® 2500 Motor Control Centers 5Unit Design 23Units 34Selection Data 69Unit Selection 72Technical Data 74Checklist 79 79
3
4
CENTERLINE® 2500 Motor Control CentersThe CENTERLINE 2500 Motor Control Center (MCC) consists of one or more columns secured together forming a rigid, free-standing assembly. The MCC columns are designed to allow the addition of future columns.
The MCC is designed with full isolation of electrical components from the front side of the structure. When the doors are latched and the covers are secured, a person on the operating side of the equipment is not exposed to live parts.
Units installed in the MCC columns are populated with a full line of IEC components, contactors, overload relays, AC drives, soft starters and other devices.
Product Features
• Meets Global Standards– Designed to IEC 60439-1– Designed to IEC 60529– KEMA (TTA) Certified
• Fully withdrawable unit design allows for faster replacement, helping minimize maintenance and downtime– Plug-in line, load, control, ground and network communications– Four unit positions (connected, test, disconnected and withdrawn)– Lever operated mechanism for tool-less withdrawal and insertion
• Built-in network and IntelliCENTER® technology– Improve performance through system-wide communications– Share diagnostic information for predictive maintenance– Initiate warnings before potential faults occur
• ArcShield helps you reduce arc flash hazards• Three and four wire bus bar power systems available to help meet your
local requirements• High unit density optimizes column utilization• Fully isolated structures for maximum arc containment• Multiple column widths of 600, 700, 800, 900 and 1000 mm available for
scalable solutions
5
IntelliCENTER Technology
Built-in Networking
• Media protected behind barriers• Access ports in wireways• Trunk and drop topology allows for addition and
removal of devices without shutting down the network
Intelligent Motor Controls
• PowerFlex Drives• SMC™ 3 and SMC™-Flex Soft Starters• E1 Plus, E3 Plus Electronic Overload Relays• DeviceNet Starter Auxiliaries
IntelliCENTER Software
• Elevation View• Monitor View• Documentation View• Spreadsheet View
Factory Configuration
• Network media validation• Node configuration• Device communication check
IntelliCENTER Technology improves the intelligence of your MCC using built-in DeviceNet to capture information used for predictive maintenance, process monitoring, and advanced diagnostics.
DeviceNet
Based on the latest in network technology, DeviceNet is a simply, open networking solution, allowing for real-time control, data exchange, configuration and data connection at regular intervals or on demand. This robust communication link connects industrial devices (such as limit switches, photoelectric sensors, motor starters, push buttons, variable frequency drives and operator interface devices) to a network and eliminates time-consuming and costly hard wiring.
The cost and performance of a DeviceNet network makes it ideal for MCC applications. The open specifications and protocol, managed by the Open DeviceNet Vendor Association (ODVA), means vendors are not required to purchase hardware, software or licensing rights to connect to a system. Over 300 vendors offer DeviceNet products with over a half million nodes installed worldwide.
6
IntelliCENTER Software
The CENTERLINE 2500 MCC is available with pre-configured IntelliCENTER software. IntelliCENTER software is an intuitive softare package that is customized to your MCC. This software package includes several preconfigured views for easy access to important information and is capable of viewing multiple MCC line-ups. IntelliCENTER software can be installed and operated on Ethernet, EtherNet/IP, ControlNet or DeviceNet. The IntelliCENTER software is capable of functioning as a stand alone software package or as an ActiveX control in a Human Machine Interface (HMI). The IntelliCENTER software displays the following:
Elevation View
The Elevation View is an easy-to-identify, graphical representation of your entire MCC lineup. The condition of each motor controller is quickly established with status light indicators. Customizable text allows for instant identification of the motor, machine or process.
• Navigate immediately to units of concern by simply double-clicking on them• Re-arrange the elevation view using simple drag-and-drop • Select units for which you would like to see manuals, wiring diagrams or
spare parts
Monitor View
The Monitor View displays an overview of the intelligent motor control device being monitored, with configurable gauges, trend graphs, I/O status on the device and configurable data fields.
• Monitor parameters from the intelligent devices• Change configuration parameters • Record up to 5000 data points with the trend graph and export • Change which parameters are displayed in the monitor view
Documentation Views
Documentation View has access to the various manuals and diagrams for your MCC along with other important MCC information.
Manuals and Wiring Diagrams
The IntelliCENTER Software data CD comes with the complete documentation for your MCC, including wiring diagrams and device manuals. So your manuals are quickly available when you need them most.
• Troubleshoot problems using the exact manuals for your MCC• Trace out wiring and understand control circuits using wiring diagrams• Add new documentation ( procedures, engineering notes) associated with your MCC• Substitute ‘as-built’ drawings with your ‘as-installed’ drawings
7
Spreadsheet View
The spreadsheet view allows you to access MCC data such as:• Node number (network address)• Unit description• Nameplate data• Device type
Event Log View
The Event Log records and stores events with date and time information occurring within you MCC and stores them with their date and time. Events can include device warnings and faults as well as parameter or device changes.
Spare Parts List
The spare parts list provides you with the exact replacement part needed to repair your MCC unit. This helps save time when calling your authorized Allen-Bradley distributor.
8
Networking
DeviceNet Cabling
All trunk and drop DeviceNet cabling is ODVA certified Class 1, with 600V insulation and 8 A rating. The DeviceNet cabling system for IntelliCENTER Technology has been extensively tested for noise immunity with network cables in close proximity to high current motor leas and VFD outputs. As a result, IntelliCENTER MCCs provide a very robust network solution with no special separation, barriers or internal conduit required.
DeviceNet Cable Layout
The DeviceNet trunk line is routed through the control and network wireway and top horizontal wireway of the MCC. Trunk lines are routed behind barriers to isolate the cable from the unit space and wireways to help prevent accidental damage.
DeviceNet Trunk Line
Up to 24 DeviceNet ports can be provided in the control and network wireway. Each DeviceNet component in an MCC unit is connected to the network through a port located in the control and network wireway. Adding or removing units from the network does not interrupt the other units operating in the system.
DeviceNet System Performance
The DeviceNet system in the MCC is designed to operate at 500 kbaud to maximize performance, unless precluded by the cumulative length of the trunk and drop lines. To achieve best performance, all MCCs are engineered for a 250 kbaud minimum communication rate.
The DeviceNet system in the MCC is qualified to communicate and perform under normal and adverse electrical environments (for example, contactor electrical operation, contactor jogging duty and unit short circuit fault).
The DeviceNet system has the following capabilities:• Automatic Device Replacement (ADR).• On-Line Scanlist Changes at Run, allowing network modifications to be performed on a DeviceNet system that is
running.• Scan modes: Polled, Change of State (COS), Strobe and Cyclic. By choosing the appropriate scan mode for different
data, DeviceNet systems can achieve better throughput performance than networks with much higher communication rates.
• Transmit and receive data via I/O and explicit messaging. This allows the control system to access every parameter in the device, not just a few registers.
9
DeviceNet Components
Each unit can be provided with a DeviceNet component. • Starter units can be provided with an E1 Plus with DeviceNet module, E3 or E3 Plus overload relays or solid-state
overload relays with a DeviceNet Starter Auxiliary. • Contactor units can be provided with a DeviceNet Starter Auxiliary. • AC drives can be provided with a DeviceNet communication module. • Solid-state controllers can be provided with DeviceNet communication modules and, in some instances, a
DeviceNet Starter Auxiliary. • Fusible disconnect and circuit breaker feeder circuits can be provided with a DeviceNet Starter Auxiliary.
Programming of Parameters
The DeviceNet node address is programmed for each unit. All other parameters are left at the factory default setting.
The DeviceNet components are configured to operate at the specified communication rate.
Testing
CENTERLINE 2500 motor control centers with IntelliCENTER Technology can save you time because each MCC is powered up, configured and tested at the factory. Each unit is preconfigured with node addresses and communication rates to ensure it communicates properly.
For more information on MCCs with DeviceNet, refer to CENTERLINE 2500 DeviceNet Motor Control Centers, publication 2500-TD002.
IntelliCENTER Database
The IntelliCENTER Database contains all of your order-specific information. One IntelliCENTER Database is needed for each MCC lineup or for individual units (when the unit is purchased separately). The database is installed on the computer or computers running the IntelliCENTER software. The database CD includes the IntelliCENTER data files, all of the electronic documentation, all theup-to-date EDS files for the DeviceNet devices and the DeviceNet configuration file as recorded during the final system test of the MCC. The EDS and configuration files are very useful for programming the control system, allowing the programmer to complete the project before the equipment is even energized. Additionally, when used with RSLogix 5000 and RSNetworx for DeviceNet software, the programmer can use the DeviceNet Tag Generator utility in RSLogix 5000 to instantly generate descriptive tags for every device in the MCC.
10
ArcShieldCENTERLINE 2500 MCC’s with ArcShield offers you better protection against harmful arc flash hazards. Using a CENTERLINE 2500 MCC with ArcShield helps protect your personnel if an arc flash were to occur within an MCC.
CENTERLINE 2500 MCC with ArcShield provides personnel and assembly protection per IEC/TR 61641:2008 for arcing durations up to 300 ms(1).
In combination with the standard safety features built into every CENTERLINE 2500 MCC, choosing ArcShield provides additional benefits, including:• Structures with no front ventilation• Pressure relief system designed to exhaust gases through the top of the
structure, away from personnel• Arc containment latches on all doors capable of withstanding the high
internal pressure generated by an arc blast• Insulated power bus closing plates included at the ends of each MCC lineup
For even more protection, optical and current sensing technology for use with crowbar or shunt trip devices is available as an option.
(1) 300ms rating is available for systems at 415V (max), with 65kA (max) available current
Arc Containment Latches
Pressure Relief System
11
StructureThe CENTERLINE 2500 MCC structure consists of columns, wireways, doors and withdrawable or fixed units.
Columns
The rigid, free-standing columns have heavy duty external mounting channels running the continuous width of the shipping block. Columns are secured at the installation site by bolting together clearance holes in the mounting channels or welding together.
All shipping blocks are provided with a removable continuous steel lifting angle. Two lifting angles are provided on all double-front columns.
Fault containment is enhanced with two side sheets on every column. This helps prevent a single fault from cascading throughout the structure, limiting equipment damage.
The CENTERLINE 2500 MCC’s rigid design helps ensure a longer life. Plug-in units can still be installed and removed and doors close securely after years of dependable service.
12
Column Construction
Control and Network Wireway
Vertical Power Bus
Horizontal Power Bus
Nameplates
Vertical Wireway (door closed)
Vertical-to-Horizontal Bus Connection
Unit Support Pan
Vertical Bus Covers (Automatic Shutters)
Horizontal Protective Earth Conductor
Vertical Plug-in Protective Earth Conductor
Optional ArcShield End Closing Plate Insulator
Optional ArcShield Pressure Relief Plate
Customer Load Terminal Forms of Separation
Top Horizontal Wireways
Bottom Horizontal Wireways
13
Column Dimensions
The standard column width is 700 mm. Each column is 2300 mm high and 600 mm deep. Double-front columns are also available.
Unit size is described in terms of modules. Each module is approximately 80 mm high x 500 mm wide. Columns can accommodate 24 modules of varying unit combinations.
Horizontal wireways extend the full depth of the column. Vertical wireways are approximately 350 mm deep.
Approximate Weight
This table lists approximate weights for MCC columns. Many factors (number of units, horizontal power bus, wireway width, column depth) affect the weight of columns. Weight is also added when the product is packaged for shipping.
170 (6.69)
1980 (77.95)
115 (4.53)
500 (19.69)
200 - 500 (7.87 - 19.69)
600 (23.62)
2300 (90.55)
35 (1.38)
700 - 1000 (27.56 - 39.37
Column Width
Total Column Width
Unit Width Vertical Wireway Width
600 mm(1)
(1) Frame mount only.
600 mm No vertical wireway
700 mm (standard) 500 mm 200 mm (standard)
800 mm 500 mm 300 mm
900 mm 500 mm 400 mm
1000 mm 500 mm 500 mm
Column Depth
Front Only Double-Front
600 mm 1200 mm
800 mm —
Column Height
Feature Height
Total Height 2300 mm
Available Unit Height 1980 mm
Top Horizontal Wireway 170 mm
Bottom Horizontal Wireway
115 mm
External Mounting Channel 35 mm
Column Width Approximate Weight (1)
(1) Weights are for a typical Motor Control Center with 6 units per column. Weights do not include packaging. Refer to the packing slip shipped with your MCC for exact shipping weights.
600 mm, 700 mm 350 kg
800 mm 400 kg
900 mm 450 kg
1000 mm 500 kg
14
Structure
You can select the degree of protection and the paint color for your CENTERLINE 2500 MCC.
Degree of Protection
In accordance with IEC 60529, structures are available with the following IP ratings.• IP 20 (non-filtered vented doors)• IP 30 (filtered vented doors)• IP 42 (non-vented doors, standard)• IP 54 (gasketed with bottom plates)
Structure sheet metal has rounded edges and is tightly fitted with no visible air gaps.
Paint and Plating
Structural metal undergoes a multi-step cleaning, rinsing and painting process resulting in complete uniform-thickness, paint coverage. This process is maintained and controlled by ISO 9001 quality standards.
Zinc with trivalent chromate is used to plate unpainted surfaces for corrosion resistance.
The standard exterior paint color is Pebble Grey (RAL 7032). Closing plates, channel supports, lifting angles, and horizontal wireway covers are painted Black Grey (RAL 7021). Interior vertical wireways and unit mounting plates are painted high visibility gloss white.
Other colors are available by request.
15
Wireways
Each MCC has horizontal, vertical and control and network wireways, for continuous dedicated wire and cable location.
Horizontal Wireways
Horizontal wireways are located at the top and bottom of each MCC column. Horizontal wireways extend the full width and depth of the MCC. A barrier is present in the top horizontal wireway to provide a connection point for DeviceNet receptacles. The top horizontal wireway is 170 mm high, while the bottom horizontal wireway is 115 mm high. Complete wireway access from front to rear is available for double-front configured MCC columns..
Horizontal wireways have removable front covers that are held in place by captive screws. Openings in in the side plate of the column allow access to the top and bottome norizontal wireways between joined columns. Plates are provided to cover these openings for columns located at the end of a MCC lineup.
Horizontal wireways are isolated from the power bus. Horizontal wireways for incoming line sections are reduced depth to maintain isolation from the incoming line area.
Vertical Wireway
The vertical wireway is located on the right side of each column and extends 1980 mm, between the top and the bottom horizontal wireway. The vertical wireway is approximately 350 mm deep. The standard vertical wireway is 200 mm wide. Vertical wireways are also available in widths of 300, 400 and 500 mm. Wider wireways are recommended for MCCs with higher bus ratings and higher unit density per section.
The vertical wireway is isolated from power bus and is independent of unit space. Vertical wireways are not present in columns with fixed (frame-mounted) units.
Vertical wireways are covered with steel doors, held in place by four door latches.
See Nameplates on page 32 for more information.
Vertical wireway cable supports are available to help you keep your cable wireways organized.
Continuous Horizonal Top Wireway
Continuous Horizonal Bottom Wireway
Continuous Vertical Wireway
16
Control and Network Wireway
A separate wireway isolates control and network cables from power wiring.
The control and network wireway is located on the left side of the column in the unit space. Control and network connections are made to withdrawable units through receptacles located in this wireway.
Control Connector
DeviceNet Network Connector
Units Removed
Control Wireway
17
Incoming PowerThe MCC can be configured to work on a system with any of the following incoming line voltages: 380, 400, 415, 440, 480, 600 and 690 V.
The MCC can be configured to operate at a frequency of 50 or 60 Hz.
CENTERLINE 2500 MCCs are suitable for use on three-phase, three-wire or four-wire, wye connected power systems, rated 690V or less, 50 or 60 Hz, with a solidly grounded neutral. CENTERLINE 2500 MCCs may also be used on other power system configurators, however, some units and options may not be available. Consult the factory for additional information.
Power BusThe MCC features the time-proven Allen-Bradley CENTERLINE power bus system. The horizontal power bus is mounted near the vertical center of the structure providing optimum heat dissipation, power distribution, and ease of maintenance and installation. It is mounted in recessed channels of the bus support to protect against accumulation of dust and tracking between phases.
The vertical power bus allows power distribution both above and below the center-mounted horizontal bus, effectively doubling the capacity in each column. This feature also helps allow a virtually unrestricted unit arrangement.
Horizontal and vertical power bus is fastened together with a two bolt assembly. This two-bolt connection helps minimize the likelihood of “hot spots.” The factory-made horizontal to vertical power bus connection is tightened by a computerized torquing system.
The power bus system is supported, braced and isolated by a bus support molded of high strength, non-tracking glass polyester material. The horizontal power bus is mounted on-edge in a vertical plane providing maximum strength against magnetic forces. Vertical power busbars are continuously braced and sandwiched by a polycarbonate molded bus cover isolating the vertical power bus from the other vertical phases and the horizontal power bus.
Bus bracing is available with the following rms symmetrical current ratings.• 50 kA for 3 cycles at 60 Hz (standard)• 65 kA for 3 cycles at 60 Hz• 50 kA for 1 second• 50 kA for 3 seconds (horizontal power bus only)• 80 kA for 1 second (horizontal power bus only)
18
CENTERLINE Power Bus and Neutral (Cover Removed)
Horizontal Power Bus
The standard horizontal power bus material is unplated copper. Tin-plated copper horizontal power bus is optional.
Vertical Power Bus
The tin-plated copper vertical power bus is cylindrical for optimum contact with the plug-in unit stabs.
The standard vertical power bus is rated for 300 A above and below the horizontal power bus for an effective 600 A rating. An optional vertical power bus rated for 600 A above and below the horizontal power bus for an effective 1200 A rating is available.
Two-bolt Assembly
Optional Neutral Vertical Bus Bar
Optional Neutral Horizontal Bus Bar
Horizontal Power Bus Ratings and Descriptions
Power Bus Rating Busbar Quantity and Dimensions
800 A (standard) (1) 3 x 100 mm
1250 A (1) 6 x 100 mm
1600 A (2) 6 x 100 mm
2000 A (1) 6 x 100 mm and (1) 10 x 100 mm
2500 A (2) 10 x 100 mm
3200 A (3) 10 x 100 mm with 10 mm spacers
4000 A (4) 10 x 100 mm with 10 mm spacers
19
Neutral Bus
The optional horizontal neutral bus is provided across the full width of the MCC and located above or below the horizontal power bus.
The neutral bus matches the material and specifications of the vertical power bus.
The horizontal neutral bus is available with a full or half current rating.
The vertical neutral bus is connected to the horizontal neutral bus and provides a neutral connection for units throughout the column.
The neutral bus is braced the same way as the horizontal and vertical power bus.
Automatic Shutters
Automatic shutters are standard on CENTERLINE 2500 MCCs. Automatic shutters open as withdrawable units are inserted and close when the unit is removed. This safety feature helps ensure the vertical bus is immediately isolated when a withdrawable unit is removed.
Back of MCC (back plate removed) - Neutral bus shown
20
Protective Earth Conductor The horizontal protective earth conductor along with the vertical plug-in protective earth conductor form a complete internal protective earth circuit.
Horizontal Protective Earth Conductor
The horizontal protective earth conductor (PE) is unplated copper or tin-plated copper is available, and is located in the bottom horizontal wireway. The horizontal PE is continuous for the width of the column and consists of one, two or three 6 x 50 mm conductors. The horizontal PE has 12 holes along the length of the conductor for making equipment connections.
A pressure-type mechanical lug is mounted on the horizontal PE conductor in the incoming line section.
Vertical Plug-in Protective Earth Conductor
An unplated copper vertical plug-in PE conductor is provided in each standard column. An optional tin-plated copper vertical plug-in PE conductor is also available. The vertical plug-in PE conductor is mechanically connected to the horizontal PE conductor.
The vertical plug-in PE conductor in combination with the unit PE contact establishes a first make, last break operation of the PE connection with respect to power connections. This first make, last break connection assures the unit to be grounded when inserting or removing the unit.
21
Module SpaceUnit size is described in modules. One module is approximately 80 mm high x 500 mm wide. Withdrawable units are available in the following sizes: 1, 2, 4, 6, 8, 10 and 12 modules. Fixed units range in size from 2 to 24 modules.
Each MCC column can accommodate 24 modules.
Continuous Horizontal Wireway
Continuous Horizontal Wireway
Continuous Vertical
Wireway
24 Modules Total
2 Module Unit
4 Module Unit
8 Module Unit
22
Unit DesignUnits are designed as either withdrawable or fixed. Withdrawable units can be removed from the structure and have a maximum current rating of 225 A.
The amount of current drawn by fixed units is determined by the rating of the horizontal power bus. Fixed units are frame-mounted and cannot be moved or rearranged once installed in the column.
Two Module Unit
Withdrawable Unit Design Features
Withdrawable units consist of the unit, unit support pan and unit door. Withdrawable units are held securely in the column when inserted and are designed with an interlock to help ensure that units cannot be inserted or withdrawn when the disconnect means is in the ON/I position. Withdrawable units range from 1 up to 12 module sizes.
Tools are not required to insert or remove withdrawable units.
Withdrawable units are characterized by being able to release the line, load, control, network and protective earth (PE) connections. Outgoing load and control connections are in the vertical wireway.
23
Withdraw Lever and Alignment Slides
Withdrawable units use low friction alignment slides and a mechanical withdraw lever for easy unit inserting and removing. The withdraw lever features a locking mechanism that the user disengages to change positions. Detents are present to help confirm that the unit is secured in each position.
Withdraw Lever
Operating Positions
Withdrawable units have four operating positions: connected, test, disconnected and withdrawn. See the following descriptions for additional information about the features of each position. shows the withdrawable unit operating positions.
Connected - Line, load, control, network and PE connections are all engaged. Closing the unit door ensures the withdraw lever is in the connected position. To engage the interlock or turn the disconnect means to the ON/I position, the unit door must be fully closed.
24
Test - Control, network and PE connections are engaged. Line and load connections are isolated. This allows the user to verify control and network wiring. Units can be locked in this position.
Disconnected - The unit remains housed in the column, but no connections are present. This is an isolated position. Units can be locked in the disconnected position.
Withdrawn - Withdrawable units can be completely removed from the columns. When units are withdrawn from the MCC, they are isolated from connections. Withdrawn units can be locked to prevent insertion.
Withdrawable Unit Operating Positions
Operating Position
Connection Present Lockable in Position
Line Load PE Control Network
Connected x x x x x x(1)
(1) Unit is lockable when door is closed.
Test x x x x
Disconnected Connections not present. Unit remains inserted in column. x
Withdrawn Connections not present. Unit is removed from column. x
25
Fixed (Frame-mounted) Unit Design Features
Fixed units are permanently mounted in the column, all connections are made directly to the components. Fixed units range from 2 up to 24 module sizes. For units 12 module size and above, fixed unit design is standard.
Fixed (Frame-mounted) Unit Connections
In fixed units, line, load, PE and control connections are made directly to components. Network connections can be made through fixed or plug-in terminal blocks. shows possible unit connections.
Operating Handle
Rotary Operating Handle
An industrial, heavy duty, rotary operating handle is supplied for control of the disconnecting means in each unit. When the unit door is closed, the handle is engaged with the disconnect means.
The operating handle can be locked in the OFF/O position with up to three 8 mm diameter shackle padlocks. The operating handle can be modified to enable locking in the ON/I position.
The unit operating handle is interlocked with the unit door to help prevent opening the unit door unless the disconnect means is in the OFF/O position. An externally operated defeater is provided to access the unit without interrupting service. The operating handle is interlocked with the unit so the unit cannot be inserted or withdrawn with the operating handle in the ON/I position.
Unit Connections
Withdrawable Unit Connections
Fixed Unit Connections
Line Withdrawable Fixed
Load Withdrawable Fixed
PE Withdrawable Fixed
Control Withdrawable Fixed
Network Withdrawable Disconnectable
Rotary Operating Handle
Rotary Operating Handle for One Module Units
26
Flange-mounted Handle
Flange style disconnect handles (vertical or horizontal mounted) are available for units with circuit breaker disconnects. The flange handle helps prevent the disconnect from being switched to the ON/I position when the unit door is open.
Units with vertical flange handles must be at least 4 modules. Units with horizontal flange handles must be at least 2 modules.
Unit Disconnect Means
The unit disconnect switch is available as a circuit breaker or fusible disconnect.
Withstand ratings for combination starter units are based on the short circuit protective devices and components selected.
Circuit Breakers
Allen-Bradley circuit breakers are provided as the disconnecting means for units with a circuit breaker unit main switch. Bulletin 140M motor circuit protectors are used for combination motor control units. Bulletin 140M motor protection circuit breakers and Bulletin 140U molded case circuit breakers are utilized for feeder units.
Circuit breaker unit main switches are available in the following ratings based on circuit breaker and component selection.
Circuit Breaker Ratings
Rating Amperage and Voltage
Type 1 Up to 100 kA at 400 V
Type 2 Up to 65 kA at 400 V
Up to 50 kA at 500 V
Up to 25 kA at 600 V
Up to 10 kA at 690 V
Vertical Flange Operating Handle
27
Disconnect Switches
When specified, Allen-Bradley disconnect switches are provided. The Bulletin 194R fused disconnect switch is used in combination starter and feeder units. One module combination starter and feeder units utilize the Bulletin 194E unfused switch.
When requested, NH fuses are supplied in the following styles: DIN gG and DIN aM.
Disconnect unit main switches are available in the following ratings based on component and fuse selection.
Stab Assembly
Power Stab Assembly
The two-piece power stab housing is made of high strength, non-tracking glass polyester material and provides a separate, isolated pathway for each phase.
The power cable connection at the plug-in stab is made with a maintenance free crimp style connection. There is no exposed wiring at the back of the unit between the disconnecting means and the plug-in stabs.
Unit plug-in power stabs are rated 225 A. The stabs are made of tin-plated copper for a low resistance connection and are designed to tighten during heavy current surges.
The free-floating and self aligning unit plug-in power stabs are backed by stainless steel spring clips to provide and maintain a high pressure, four-point connection to the vertical power bus.
Disconnect Ratings
Rating Amperage and Voltage(1)
(1) For 690V information, please consult the factory.
Type 2 Up to 100 kA at 400 V
Up to 100 kA at 500 V
Up to 100 kA at 600 V
28
Neutral Stab Assembly
The neutral stab assembly can be supplied on withdrawable units for 4-wire systems. The neutral stab assembly has the same design and features as the power stab assembly, but is a separate piece.
One Module Stab Assembly
The one module stab assembly consists of a receptacle for line and load connections that plugs into a subplate connected to the vertical power bus. The two guide pins help ensure the connector is properly aligned. Because of the subplate connection, one module units must be installed in pairs.
One module units stabs are rated at 32 A.
Protective Earth Contact
An unplated copper PE contact is provided on withdrawable units. This contact establishes a connection with the PE circuit before other connections are made and is the last withdrawable connection to be disconnected.
Control and Network Connections
Plug-in control and network connections are made automatically for withdrawable units. A 15-pin connector plug, rated at 10 A, is used for control connections. DeviceNet network connections are made through a separate connector. The control and network connectors use a spring-loaded mechanism to ensure proper connection.
Neutral Stab
29
PE Contact, Control and Network Connections
Unit Doors
Each unit is provided with a removable unit door, mounted on hinges with removable pins. Unit doors are held closed with ¼ turn latches. See Door Latches on page 31 for more explanation.
The unit door is mounted to the structure so it is not necessary to remove a nit door when installing or removing units. The door can be closed with the unit removed to isolate the power bus. A unit door can be removed from any location on the MCC without disturbing other unit doors.
Control stations for pilot devices and low profile external reset buttons for overload relays are often mounted to the unit door.
Control Connection
PE Contact
Network Connection
30
Door Latches
There are two types of door latches available for the 2500 MCC. Standard CENTERLINE 2500 MCCs have quarter-turn door latches. If you select an MCC with ArcShield, the MCC will have arc containment door latches.
Door Latches (Standard)
Door latches are provided on unit and vertical wireway doors to hold the door closed and isolate personel from the column. Door latches can be locked or released by rotating the latch ¼ turn. An arrow on the door latch head indicates the position of the latch.
Arc Containment Latch
Optional arc containment latches are available. Arc containment latches help protect personnel in the vicinity of an MCC if an arc fault occurs when structure doors are closed and latched. Arc containment latches can be locked or released by rotating the latch ¼ turn.
Released Position Locked Position
Released Position Locked Position
31
Nameplates
The MCC master nameplate, when specified, is available with up to five lines of engraving and is located on the top horizontal wireway cover.
Unit nameplates are available and can accommodate three or four lines of engraving. The following types of unit nameplates are available:
• Clear cardholders - insert printed cards into cardholder• Engraved acrylic nameplates - white with black lettering or black with white lettering• Engraved phenolic nameplates - white with black lettering, black with white lettering or red with white lettering
Nameplates are secured using two steel self-tapping screws. Stainless steel screws are also available.
Unit Nameplate
Control Power
Unit control power is specified as: 24V DC, or 110, 115, 120, 220, 230 or 240V AC.
Unit control power is normally supplied by a single common control power transformer unit within each MCC lineup. This common control power allows the test function of withdrawable units to work most effectively. The common control source operates at line voltage with an option for common control fusing.
Individual control circuit transformers, mounted in each unit, are available. One leg of the secondary side of the control circuit transformer is fused while the other leg is connected to PE. Primary protection is then provided by primary fusing.
Control Wire
Control wire is ‘multistrand’ or ‘stranded’ copper. (Need to add type of insulation and rating (90 °C what)
Wire markers are sleeve type; heat shrink is optional.
Power Wire
The power wire is double-insulated copper and rated at 105°C or higher. The power wire is sized to meet the current rating of the unit, with a minimum size of 6 mm2.
NEED FAULT FREE ZONE TEXT
32
Mounting Configurations
The MCC is available in two mounting configurations – front-only and double-front.
• Front-only columns are joined and installed side-by-side. • Double-front columns are two separate columns joined at the rear, back
plates are removed. The two columns have separate power bus systems providing the same phasing for all units. The horizontal power bus is linked, front to rear, with a factory installed U-shaped bus splice assembly.
For shipping purposes, only 600mm deep columns can have double-front configurations.
Front-only (standard configuration)
Double-front (optional configuration)
33
UnitsColumns can be populated with several different types of units, such as mains, feeders, direct on line starters and contactors, soft starters, AC drives and PLCs.
DeviceNet Scanner Modules
DeviceNet in the MCC requires a DeviceNet scanner module that meets DeviceNet requirements. The scanner module may be located in the MCC or mounted remotely.
Network Linking Devices
Network linking devices allow CENTERLINE 2500 MCC customers to connect to different communication networks. With network linking devices you are able to connect to ControlNet or EtherNet/IP directly from you MCC. NetLinx technology enables you to link from one network to another easily, making data transfer from the MCC’s DeviceNet network onto the controller’s EtherNet/IP or ControlNet simple.
DeviceNet Power Supply
DeviceNet in the MCC requires a power supply providing 24V DC and rated no less than 8 amperes.
A quality power supply is essential to reliable system operation. To ensure system integrity and reliability, the Allen-Bradley Bulletin 2500-DPS 8 A DeviceNet Power Supply unit is recommended. This power supply meets DeviceNet requirements, ODVA approval, and is supplied with a buffer for enhanced ride-through performance. A redundant power supply is also available for added reliability..
Linking Devices
Unit Description Module Size1 = 80 mm
ControlNet to DeviceNet Bridge 2
Ethernet to DeviceNet Bridge 2
Profibus to DeviceNet Bridge 2
DeviceNet Power Supply Units
Unit Description Module Size1 = 80 mm
DeviceNet Power Supply 2
Redundant DeviceNet Power Supply 4
Back-up DeviceNet Power Supply
One Module Unit
34
Main Incoming Line (Lug-only) Compartment
Main incoming line lug compartments are available in either the top or bottom entry and use mechanical screws or crimp/compression lugs. The compartments are front accessible.
Main Incoming Circuit Breaker
Air circuit breakers (ACB) or molded case circuit breakers (MCCB) are available for main incoming circuit breakers.
Main circuit breaker units are front accessible with removable protective barriers on the line side, helping reduce the possibility of accidental contact with line terminals.
The ACB compartments have trip ratings available from 400…4000 A. These ACBs are available with a drawout or fixed style. The ACBs for mains include an option to utilize 4-pole breakers. ACBs may be integrated into auto-transfer switch schemes.
This table provides more information on available incoming air circuit breaker compartment arrangements and sizes.
MCCBs are inverse time circuit breakers and can be classified as thermal magnetic or electronic.
Main Incoming Fusible Disconnect
Mains with fusible disconnects are available. Fuses can be factory installed or supplied and installed by others.
Main Incoming Line Compartments
Incoming Line Compartment Rating
6 modules (480 mm), variable column width 600 A (using vertical power bus)
24 modules (full column), 700 mm wide 800, 1250, 1600, 2000 A
24 modules (full column), 800 mm wide 2500, 3200, 4000 A
Incoming Air Circuit Breaker Compartment Arrangement
Incoming Air Circuit Breaker Compartment Rating
24 modules (full column), 800 mm deep x 800 mm wide 800, 1250, 1600, 2000 A
24 modules (full column), 800 mm deep x 900 mm wide 2500, 3200, 4000 A
35
Pilot Devices
Pilot devices are housed in a door mounted control station. Each control station can accommodate up to four 22 mm devices. Multiple control stations can be mounted on a unit door, if more than four pilot devices are required.
Control stations are equipped with a quick connect plug for ease in connecting and disconnecting control wiring.
The control station is easily removed using captive screws. If a control station is removed, closing plates are available to cover the opening in the unit door and provide isolation.
Main and Feeder Units
Incoming Main Lug Compartments and Outgoing Feeder Lug Compartments
The line lug compartments provide a lug connection for incoming lines (mains) to distribute power to the motor control center or for outgoing cables (feeders) to feed power from the motor control center to an external load. Line lug compartments are available in ratings from 300…4000 A and are fixed mounted.
Main and Feeder Circuit Breaker Units
The circuit breaker units have trip ratings available from 15…4000 A. These units are available with thermal magnetic trip circuit breaker up to 1200 A and electronic trip circuit breaker 100 A and above. The feeder circuit breaker units are available in a withdrawable unit style up to 225 A and are fixed mounted for ratings 250 A and above. The main circuit breaker units are fixed mounted for all ratings.
For main and feeder circuit breaker unit selection go to page .
For main and feeder circuit breaker option selection go to page .
Mains, Air Circuit Breakers
Amperes Circuit Breaker Module Size
Catalog Number(1)
(1) To complete the catalog numbers, please contact the factory
1 = 80 mm Column Width (mm)(3)
(3) Available column widths
Column Depth (mm)(4)
(4) Available column depths
800 140RX-NS**D-D80 24(2)
(2) Fixed mount style
700 600, 800
1250 140RX-NS**D-E12 24(2) 700 600, 800
1600 140RX-NS**D-E16 24(2) 700 600, 800
2000 140RX-RS**D-E20 24(2) 800 800
2500 140RX-RS**D-E25 24(2) 800 800
3200 140RX-SS**D-E32 24(2) 900 800
4000 140RX-SS**D-E40 24(2) 900 800
36
Main Unit Options
• Auxiliary contact for circuit breaker• Shunt trip coil for circuit breaker• Alarm contact for circuit breaker• Minimum voltage coil (undervoltage) for circuit breaker• Combination auxiliary contact and alarm contact for circuit breaker
Mains, Thermal Magnetic Circuit Breakers
Amperes Circuit Breaker Module Size
Catalog Number 1 = 80 mm Column Width (mm)(2)
(2) Available column widths
Column Depth (mm)(3)
(3) Available column depths
150 140U-J*D3-D15 4(1)
(1) Fixed mount style
700, 800, 900, 1000 600, 800
200 140U-J*D3-D20 4(1) 700, 800, 900, 1000 600, 800
250 140U-J*D3-D25 4(1) 700, 800, 900, 1000 600, 800
300 140U-L*D3-D30 8(1) 700, 800, 900, 1000 600, 800
350 140U-L*D3-D35 8(1) 700, 800, 900, 1000 600, 800
400 140U-L*D3-D40 8(1) 700, 800, 900, 1000 600, 800
500 140U-L*D3-D50 8(1) 700, 800, 900, 1000 600, 800
600 140U-L*D3-D60 8(1) 700, 800, 900, 1000 600, 800
700 140U-M*D3-D70 12(1) 700, 800, 900, 1000 600, 800
800 140U-M*D3-D80 12(1) 700, 800, 900, 1000 600, 800
Mains, Electronic with LSI Protection Type
Amperes Circuit Breaker Module Size
Catalog Number 1 = 80 mm Column Width (mm)(2)
(2) Available column widths
Column Depth (mm)(3)
(3) Available column depths
150 140U-J*H3-D16 2 700, 800, 900, 1000 600, 800
250 140U-J*H3-D25 4(1)
(1) Fixed mount style
700, 800, 900, 1000 600, 800
400 140U-L*H3-D40 8(1) 700, 800, 900, 1000 600, 800
600 140U-L*H3-D60 8(1) 700, 800, 900, 1000 600, 800
800 140U-M*H3-D80 8(1) 700, 800, 900, 1000 600, 800
1200 140U-N*H3-E12 12(1) 700, 800, 900, 1000 600, 800
37
Feeders, Air Circuit Breakers
Amperes Circuit Breaker Module Size
Catalog Number (1)
(1) To complete the catalog numbers, please contact the factory
1 = 80 mm Column Width (mm)(3)
(3) Available column widths
Column Depth (mm)(4)
(4) Available column depths
800 140RX-NS**D-D80 24(2)
(2) Fixed mount style
700 600, 800
1250 140RX-NS**D-E12 24(2) 700 600, 800
1600 140RX-NS**D-E16 24(2) 700 600, 800
2000 140RX-RS**D-E20 24(2) 800 800
2500 140RX-RS**D-E25 24(2) 800 800
3200 140RX-SS**D-E32 24(2) 900 800
4000 140RX-SS**D-E40 24(2) 900 800
Feeders, Thermal Magnetic
Amperes Circuit Breaker Module Size
Catalog Number 1 = 80 mm Column Width (mm)(2) Column Depth (mm)(3)
10 140M-C2E-C10 1 700, 800, 900, 1000 600, 800
16 140M-D8E-C16 1 700, 800, 900, 1000 600, 800
20 140M-D8E-C20 1 700, 800, 900, 1000 600, 800
25 140M-D8E-C25 1 700, 800, 900, 1000 600, 800
30 140M-F8E-C32 2 700, 800, 900, 1000 600, 800
35 140M-F8E-C45 2 700, 800, 900, 1000 600, 800
40 140M-F8E-C45 2 700, 800, 900, 1000 600, 800
45 140M-F8E-C45 2 700, 800, 900, 1000 600, 800
50 140U-H*C3-C50 2 700, 800, 900, 1000 600, 800
60 140U-H*C3-C60 2 700, 800, 900, 1000 600, 800
70 140U-H*C3-C70 2 700, 800, 900, 1000 600, 800
80 140U-H*C3-C80 2 700, 800, 900, 1000 600, 800
90 140U-H*C3-C90 2 700, 800, 900, 1000 600, 800
100 140U-H*C3-D10 2 700, 800, 900, 1000 600, 800
110 140U-H*C3-D11 2 700, 800, 900, 1000 600, 800
125 140U-H*C3-D12 2 700, 800, 900, 1000 600, 800
150 140U-J*D3-D15 2 700, 800, 900, 1000 600, 800
175 140U-J*D3-D17 2 700, 800, 900, 1000 600, 800
200 140U-J*D3-D20 2 700, 800, 900, 1000 600, 800
225 140U-J*D3-D22 2 700, 800, 900, 1000 600, 800
250 140U-J*D3-D25 4(1) 700, 800, 900, 1000 600, 800
300 140U-L*D3-D30 8(1) 700, 800, 900, 1000 600, 800
350 140U-L*D3-D35 8(1) 700, 800, 900, 1000 600, 800
400 140U-L*D3-D40 8(1) 700, 800, 900, 1000 600, 800
500 140U-L*D3-D50 8(1) 700, 800, 900, 1000 600, 800
600 140U-L*D3-D60 8(1) 700, 800, 900, 1000 600, 800
38
Feeder Unit Options
• Auxiliary contact for circuit breaker• Shunt trip coil for circuit breaker• Alarm contact for circuit breaker• Minimum voltage coil (undervoltage) for circuit breaker• Combination auxiliary contact and alarm contact for circuit breaker
700 140U-M*D3-D70 8(1) 700, 800, 900, 1000 600, 800
800 140U-M*D3-D80 8(1) 700, 800, 900, 1000 600, 800
1200 140U-N*H3-E12 12(1) 700, 800, 900, 1000 600, 800
(1) Fixed mount style(2) Available column widths(3) Available column depths
Feeders, Electronic with LSI Protection Type
Amperes Circuit Breaker Module Size
Catalog Number 1 = 80 mm Column Width (mm)(2)
(2) Available column widths
Column Depth (mm)(3)
(3) Available column depths
150 140U-J*H3-D16 2 700, 800, 900, 1000 600, 800
250 140U-J*H3-D25 4(1)
(1) Fixed mount style
700, 800, 900, 1000 600, 800
400 140U-L*H3-D40 8(1) 700, 800, 900, 1000 600, 800
600 140U-L*H3-D60 8(1) 700, 800, 900, 1000 600, 800
800 140U-M*H3-D80 8(1) 700, 800, 900, 1000 600, 800
1200 140U-N*H3-E12 12(1) 700, 800, 900, 1000 600, 800
Feeders, Thermal Magnetic
Amperes Circuit Breaker Module Size
Catalog Number 1 = 80 mm Column Width (mm)(2) Column Depth (mm)(3)
39
Starter UnitsDirect On Line Non-reversing Starter Units
These combination direct on line non-reversing starter units are supplied with Allen-Bradley Bulletin 100C or 100D contactors and either a fusible or circuit breaker disconnect. These units are available with a E1 Plus or E3 Plus overload relay and available with or without an external reset button for the overload relay. These units are available in a withdrawable unit style and a fixed unit style.
For direct on line non-reversing starter unit selection, go to page .
For direct on line non -reversing starter option selection, go to page .
Direct On Line Non-reversing Starter Units
Motor Rating Circuit Breaker Non-reversing Contactor
Electronic Overload Relay Module Size
Input Voltage kW(1)
(1) Approximate range of kilowatt ratings
Cat. No.(2)
(2) To complete the catalog numbers, please refer to the Industrial Controls Catalog at http://www.ab.com/en/epub/catalogs/12768/229240/
Cat. No.(2) E1 Plus Cat. No.(3)
(3) If side mount modules are required, please refer to the Industrial Controls Catalog at http://www.ab.com/en/epub/catalogs/12768/229240/
E3 Plus Cat. No. 1 = 80 mm
380/415V
IP20/42/54
0.8 140M-C2N-*** 100-C16*10 193-EECB --- --- 1
0.8 140M-C2N-*** 100-C16*10 --- 193-EC2AB 1
3 140M-D8N-*** 100-C16*10 193-EEDB --- --- 1
3 140M-D8N-*** 100-C16*10 --- 193-EC2BB 1
5.5 140M-D8N-*** 100-C16*10 193-EEDB --- --- 1
5.5 140M-D8N-*** 100-C16*10 --- 193-EC2BB 1
7.5 140M-D8N-*** 100-C16*10 193-EEEB --- --- 2
7.5 140M-D8N-*** 100-C16*10 --- 193-EC2CB 2
11 140M-D8N-*** 100-C23*10 193-EEEB --- --- 2
11 140M-D8N-*** 100-C23*10 --- 193-EC2CB 2
15 140M-F8N-*** 100-C37*10 193-EEFD --- --- 2
15 140M-F8N-*** 100-C37*10 --- 193-EC2DD 2
18.5 140M-H8P-*** 100-C37*10 193-EEFD --- --- 2
18.5 140M-H8P-*** 100-C37*10 --- 193-EC2DD 2
22 140M-H8P-*** 100-C85*10 193-EEGE --- --- 4
22 140M-H8P-*** 100-C85*10 --- 193-EC2EE 4
37 140M-H8P-*** 100-C85*10 193-EEGE --- --- 4
37 140M-H8P-*** 100-C85*10 --- 193-EC2EE 4
45 140M-H8P-*** 100-C85*10 193-EEGE --- --- 4
45 140M-H8P-*** 100-C85*10 --- 193-EC2EE 4
75 140M-J8P-*** 100-D210*11 193-EEJG --- --- 10
75 140M-J8P-*** 100-D210*11 --- 193-EC3GG 193-CBCT4 10
90 140M-J8P-*** 100-D210*11 193-EEJG --- --- 10
90 140M-J8P-*** 100-D210*11 --- 193-EC3GG 193-CBCT4 10
110 140M-J8P-*** 100-D210*11 193-EEJG --- --- 10
110 140M-J8P-*** 100-D210*11 --- 193-EC3HG 193-CBCT4 10
160 140M-L8P-*** 100-D300*11 193-EELG --- --- 12(4)
(4) Fixed mount style
160 140M-L8P-*** 100-D300*11 --- 193-EC3HG 193-CBCT4 12(4)
185 140M-L8P-*** 100-D420*11 193-EELG --- --- 14(4)
185 140M-L8P-*** 100-D420*11 --- 193-EC3JG 193-CBCT4 14(4)
220 140M-L8P-*** 100-D420*11 193-EELG --- --- 14(4)
220 140M-L8P-*** 100-D420*11 --- 193-EC3JG 193-CBCT4 14(4)
40
Direct On Line Non-reversing Starter Units (continued)
Motor Rating Circuit Breaker Non-reversing Contactor
Electronic Overload Relay Module Size
Input Voltage kW(1)
(1) Approximate range of kilowatt ratings
Cat. No.(2)
(2) To complete the catalog numbers, please refer to the Industrial Controls Catalog at http://www.ab.com/en/epub/catalogs/12768/229240/
Cat. No.(2) E1 Plus Cat. No.(3)
(3) If side mount modules are required, please refer to the Industrial Controls Catalog at http://www.ab.com/en/epub/catalogs/12768/229240/
E3+ Cat. No. 1 = 80 mm
440/460/480V
IP20/42/54
0.75 140M-C2N-*** 100-C16*10 193-EECB --- --- 1
0.75 140M-C2N-*** 100-C16*10 --- 193-EC2AB 1
3 140M-D8N-*** 100-C16*10 193-EEDB --- --- 1
3 140M-D8N-*** 100-C16*10 --- 193-EC2BB 1
5.5 140M-D8N-*** 100-C16*10 193-EEDB --- --- 1
5.5 140M-D8N-*** 100-C16*10 --- 193-EC2BB 1
7.5 140M-D8N-*** 100-C16*10 193-EEEB --- --- 2
7.5 140M-D8N-*** 100-C16*10 --- 193-EC2CB 2
11 140M-D8N-*** 100-C23*10 193-EEEB --- --- 2
11 140M-D8N-*** 100-C23*10 --- 193-EC2CB 2
15 140M-F8N-*** 100-C37*10 193-EEFD --- --- 2
15 140M-F8N-*** 100-C37*10 --- 193-EC2DD 2
18.5 140M-F8N-*** 100-C37*10 193-EEFD --- --- 2
18.5 140M-F8N-*** 100-C37*10 --- 193-EC2DD 2
22 140M-H8P-*** 100-C43*10 193-EEFD --- --- 4
22 140M-H8P-*** 100-C43*10 --- 193-EC2DD 4
37 140M-H8P-*** 100-C85*10 193-EEGE --- --- 4
37 140M-H8P-*** 100-C85*10 --- 193-EC2EE 4
45 140M-H8P-*** 100-C85*10 193-EEGE --- --- 4
45 140M-H8P-*** 100-C85*10 --- 193-EC2EE 4
75 140M-J8P-*** 100-D210*11 193-EEJG --- --- 10
75 140M-J8P-*** 100-D210*11 --- 193-EC3GG 193-CBCT4 10
90 140M-J8P-*** 100-D210*11 193-EEJG --- --- 10
90 140M-J8P-*** 100-D210*11 --- 193-EC3GG 193-CBCT4 10
110 140M-J8P-*** 100-D210*11 193-EEJG --- --- 10
110 140M-J8P-*** 100-D210*11 --- 193-EC3GG 193-CBCT4 10
160 140M-L8P-*** 100-D300*11 193-EELG --- --- 12(4)
(4) Fixed mount style
160 140M-L8P-*** 100-D300*11 --- 193-EC3HG 193-CBCT4 12(4)
185 140M-L8P-*** 100-D300*11 193-EELG --- --- 12(4)
185 140M-L8P-*** 100-D300*11 --- 193-EC3JG 193-CBCT4 12(4)
220 140M-L8P-*** 100-D420*11 193-EELG --- --- 14(4)
220 140M-L8P-*** 100-D420*11 --- 193-EC3JG 193-CBCT4 14(4)
41
Direct On Line Non-reversing Starter Unit Options
• Auxiliary contact for contactors• Auxiliary contact for circuit breaker• Surge suppressor• Control circuit transformer• Push buttons• Pilot lights
– Incandescent– LED– Incandescent, Push-to-Test– LED, Push-to-Test
• Selector switch– Two position– Three position
• DeviceNet starter auxiliary– (4) 120V AC inputs and (2) 120V AC outputs– (4) 24V DC inputs and (2) 120V AC outputs
• Back-up DeviceNet power supply
42
Direct On Line Reversing Starter Units
These combination direct on line reversing starter units are supplied with Allen-Bradley Bulletin 104C or 104D contactors and either a fusible or circuit breaker disconnect. The starters are mechanically and electrically interlocked to avoid both contactors being closed simultaneously. These units are available with an E1 Plus or E3 Plus overload relay and available with or without an external reset button for the overload relay. These units are available in a withdrawable unit style and a fixed unit style.
Direct On Line Reversing Starter Units
Motor Rating Circuit Breaker Reversing Contactor
Electronic Overload Relay Module Size
Input Voltage kW(1)
(1) Approximate range of kilowatt ratings
Cat. No.(2)
(2) To complete the catalog numbers, please refer to the Industrial Controls Catalog at http://www.ab.com/en/epub/catalogs/12768/229240/
Cat. No.(2) E1 Plus Cat. No.(3)
(3) If side mount modules are required, please refer to the Industrial Controls Catalog at http://www.ab.com/en/epub/catalogs/12768/229240/
E3 Plus Cat. No. 1 = 80 mm
380/415V
IP20/42/54
0.8 140M-C2N-*** 104-C16*22 193-EECB --- --- 2
0.8 140M-C2N-*** 104-C16*22 --- 193-EC2AB 2
3 140M-D8N-*** 104-C16*22 193-EEDB --- --- 2
3 140M-D8N-*** 104-C16*22 --- 193-EC2BB 2
5.5 140M-D8N-*** 104-C16*22 193-EEDB --- --- 2
5.5 140M-D8N-*** 104-C16*22 --- 193-EC2BB 2
7.5 140M-D8N-*** 104-C16*22 193-EEEB --- --- 2
7.5 140M-D8N-*** 104-C16*22 --- 193-EC2CB 2
11 140M-D8N-*** 104-C23*22 193-EEEB --- --- 2
11 140M-D8N-*** 104-C23*22 --- 193-EC2CB 2
15 140M-F8N-*** 104-C37*22 193-EEFD --- --- 2
15 140M-F8N-*** 104-C37*22 --- 193-EC2DD 2
18.5 140M-H8P-*** 104-C37*22 193-EEFD --- --- 2
18.5 140M-H8P-*** 104-C37*22 --- 193-EC2DD 2
22 140M-H8P-*** 104-C85*22 193-EEGE --- --- 4
22 140M-H8P-*** 104-C85*22 --- 193-EC2EE 4
37 140M-H8P-*** 104-C85*22 193-EEGE --- --- 4
37 140M-H8P-*** 104-C85*22 --- 193-EC2EE 4
45 140M-H8P-*** 104-C85*22 193-EEGE --- --- 4
45 140M-H8P-*** 104-C85*22 --- 193-EC2EE 4
75 140M-J8P-*** 104-D210*24 193-EEJG --- --- 10
75 140M-J8P-*** 104-D210*24 --- 193-EC3GG 193-CBCT4 10
90 140M-J8P-*** 104-D210*24 193-EEJG --- --- 10
90 140M-J8P-*** 104-D210*24 --- 193-EC3GG 193-CBCT4 10
110 140M-J8P-*** 104-D210*24 193-EEJG --- --- 10
110 140M-J8P-*** 104-D210*24 --- 193-EC3HG 193-CBCT4 10
160 140M-L8P-*** 104-D300*24 193-EELG --- --- 14(4)
(4) Fixed mount style
160 140M-L8P-*** 104-D300*24 --- 193-EC3HG 193-CBCT4 14(4)
185 140M-L8P-*** 104-D420*24 193-EELG --- --- 14(4)
185 140M-L8P-*** 104-D420*24 --- 193-EC3JG 193-CBCT4 14(4)
220 140M-L8P-*** 104-D420*24 193-EELG --- --- 14(4)
220 140M-L8P-*** 104-D420*24 --- 193-EC3JG 193-CBCT4 14(4)
43
Direct On Line Reversing Starter Units (continued)
Motor Rating Circuit Breaker Reversing Contactor
Electronic Overload Relay Module Size
Input Voltage kW(1)
(1) Approximate range of kilowatt ratings
Cat. No.(2)
(2) To complete the catalog numbers, please refer to the Industrial Controls Catalog at http://www.ab.com/en/epub/catalogs/12768/229240/
Cat. No.(2) E1 Plus Cat. No.(3)
(3) If side mount modules are required, please refer to the Industrial Controls Catalog at http://www.ab.com/en/epub/catalogs/12768/229240/
E3 Plus Cat. No. 1 = 80 mm
440/460/480V
IP20/42/54
0.75 140M-C2N-*** 104-C16*22 193-EECB --- --- 2
0.75 140M-C2N-*** 104-C16*22 --- 193-EC2AB 2
3 140M-D8N-*** 104-C16*22 193-EEDB --- --- 2
3 140M-D8N-*** 104-C16*22 --- 193-EC2BB 2
5.5 140M-D8N-*** 104-C16*22 193-EEDB --- --- 2
5.5 140M-D8N-*** 104-C16*22 --- 193-EC2BB 2
7.5 140M-D8N-*** 104-C16*22 193-EEEB --- --- 2
7.5 140M-D8N-*** 104-C16*22 --- 193-EC2CB 2
11 140M-D8N-*** 104-C23*22 193-EEEB --- --- 2
11 140M-D8N-*** 104-C23*22 --- 193-EC2CB 2
15 140M-F8N-*** 104-C37*22 193-EEFD --- --- 2
15 140M-F8N-*** 104-C37*22 --- 193-EC2DD 2
18.5 140M-F8N-*** 104-C37*22 193-EEFD --- --- 2
18.5 140M-F8N-*** 104-C37*22 --- 193-EC2DD 2
22 140M-H8P-*** 104-C43*22 193-EEFD --- --- 4
22 140M-H8P-*** 104-C43*22 --- 193-EC2DD 4
37 140M-H8P-*** 104-C85*22 193-EEGE --- --- 4
37 140M-H8P-*** 104-C85*22 --- 193-EC2DD 4
45 140M-H8P-*** 104-C85*22 193-EEGE --- --- 4
45 140M-H8P-*** 104-C85*22 --- 193-EC2EE 4
75 140M-J8P-*** 104-D210*24 193-EEJG --- --- 10
75 140M-J8P-*** 104-D210*24 --- 193-EC3GG 193-CBCT4 10
90 140M-J8P-*** 104-D210*24 193-EEJG --- --- 10
90 140M-J8P-*** 104-D210*24 --- 193-EC3GG 193-CBCT4 10
110 140M-J8P-*** 104-D210*24 193-EEJG --- --- 10
110 140M-J8P-*** 104-D210*24 --- 193-EC3GG 193-CBCT4 10
160 140M-L8P-*** 104-D300*24 193-EELG --- --- 14(4)
(4) Fixed mount style
160 140M-L8P-*** 104-D300*24 --- 193-EC3HG 193-CBCT4 14(4)
185 140M-L8P-*** 104-D300*24 193-EELG --- --- 14(4)
185 140M-L8P-*** 104-D300*24 --- 193-EC3JG 193-CBCT4 14(4)
220 140M-L8P-*** 104-D420*24 193-EELG --- --- 14(4)
220 140M-L8P-*** 104-D420*24 --- 193-EC3JG 193-CBCT4 14(4)
44
Direct On Line Reversing Starter Unit Options
• Auxiliary contact for contactors• Auxiliary contact for circuit breaker• Surge suppressor• Control circuit transformer• Push buttons• Pilot lights
– Incandescent– LED– Incandescent, Push-to-Test– LED, Push-to-Test
• Selector switch– Two position– Three position
• DeviceNet starter auxiliary– (4) 120V AC inputs and (2) 120V AC outputs– (4) 24V DC inputs and (2) 120V AC outputs
• Back-up DeviceNet power supply
45
Soft Starter Units
Soft staters, referred to as reduced voltage solid state units, contain a microprocessor-controlled motor controller, control circuit transformer and either a fusible or circuit breaker disconnect. These units are available as withdrawable or fixed units.
The following soft starters are available for CENTERLINE 2500 MCC’s:• SMC-3 soft starter• SMC Flex soft starter
SMC-3 Soft Starters features:• Three starting modes: soft start, kick start and current limit• Electronic overload protection with selectable overload trip class• Motor and system diagnostics• Soft stop• Integrated bypass contactor
SMC Flex Soft Starters features:• Seven standard modes of operation: soft start, current limit start, dual
ramp, full voltage, linear speed acceleration, preset slow speed and soft stop
• Optional modes of operation: pump control, Smart Motor BrakingTM, Accu-StopTM and slow speed with braking
• Integral SCR bypass• Electronic overload protection with selectable overload trip class• Full metering and diagnostics• DPI communication
For soft starter unit selection, go to page .
For soft starter option selection, go to page .
One Line Diagram
46
SMC-3 Soft Starter Units
Motor Rating Circuit Breaker SMC-3 High Interrupting Capacity Fuses
Module Size
Input Voltage kW(1)
(1) Approximate range of kilowatt ratings
Cat. No.(2)
(2) To complete the catalog numbers, please refer to the Industrial Controls Catalog at http://www.ab.com/en/epub/catalogs/12768/229240/
Cat. No.(2) Cat. No.(3)
(3) High interrupting capacity fuses are optional
1 = 80 mm
380/415V,
IP20/42/54
0.75 140M-C2N-*** 150-C3NBD --- 1
0.75 140M-C2N-*** 150-C3NBD 4A, SIZE 000 6
1.1 140M-D8N-*** 150-C3NBD --- 1
1.1 140M-D8N-*** 150-C3NBD 4A, SIZE 000 6
4 140M-D8N-*** 150-C9NBD --- 1
4 140M-D8N-*** 150-C9NBD 16A, SIZE 000 6
7.5 140M-D8N-*** 150-C19NBD --- 2
7.5 140M-D8N-*** 150-C19NBD 20A, SIZE 000 6
11 140M-D8N-*** 150-C25NBD --- 2
11 140M-D8N-*** 150-C25NBD 40A, SIZE 000 6
15 140M-F8P-*** 150-C30NBD --- 2
15 140M-F8P-*** 150-C30NBD 40A, SIZE 000 6
18.5 140M-H8P-*** 150-C37NBD --- 2
18.5 140M-H8P-*** 150-C37NBD 50A, SIZE 000 6
22 140M-H8P-*** 150-C43NBD --- 4
22 140M-H8P-*** 150-C43NBD 63A, SIZE 000 6
30 140M-H8P-*** 150-C60NBD --- 4
30 140M-H8P-*** 150-C60NBD 80A, SIZE 00 6
45 140M-H8P-*** 150-C85NBD --- 4
45 140M-H8P-*** 150-C85NBD 125A, SIZE 00 6
55 140M-J8P-*** 150-C108NBD --- 12(4)
(4) Fixed mount style
55 140M-J8P-*** 150-C108NBD 125A, SIZE 00 12(4)
75 140M-J8P-*** 150-C135NBD --- 12(4)
75 140M-J8P-*** 150-C135NBD 200A, SIZE 1 12(4)
47
SMC-3 Soft Starter Units (continued)
Motor Rating Circuit Breaker SMC-3 High Interrupting Capacity Fuses
Module Size
Input Voltage kW(1)
(1) Approximate range of kilowatt ratings
Cat. No.(2)
(2) To complete the catalog numbers, please refer to the Industrial Controls Catalog at http://www.ab.com/en/epub/catalogs/12768/229240/
Cat. No.(2) Cat. No.(3)
(3) High interrupting capacity fuses are optional
1 = 80 mm
440/460/480V,
IP20/42/54
0.75 140M-C2N-*** 150-C3NBD --- 1
0.75 140M-C2N-*** 150-C3NBD 4A, SIZE 000 6
1.1 140M-D8N-*** 150-C3NBD --- 1
1.1 140M-D8N-*** 150-C3NBD 4A, SIZE 000 6
4 140M-D8N-*** 150-C9NBD --- 1
4 140M-D8N-*** 150-C9NBD 16A, SIZE 000 6
7.5 140M-D8N-*** 150-C19NBD --- 2
7.5 140M-D8N-*** 150-C19NBD 20A, SIZE 000 6
11 140M-D8N-*** 150-C25NBD --- 2
11 140M-D8N-*** 150-C25NBD 40A, SIZE 000 6
15 140M-F8P-*** 150-C30NBD --- 2
15 140M-F8P-*** 150-C30NBD 40A, SIZE 000 6
18.5 140M-H8P-*** 150-C37NBD --- 2
18.5 140M-H8P-*** 150-C37NBD 50A, SIZE 000 6
22 140M-H8P-*** 150-C43NBD --- 4
22 140M-H8P-*** 150-C43NBD 63A, SIZE 000 6
30 140M-H8P-*** 150-C60NBD --- 4
30 140M-H8P-*** 150-C60NBD 80A, SIZE 00 6
45 140M-H8P-*** 150-C85NBD --- 4
45 140M-H8P-*** 150-C85NBD 125A, SIZE 00 6
55 140M-J8P-*** 150-C108NBD --- 12(4)
(4) Fixed mount style
55 140M-J8P-*** 150-C108NBD 125A, SIZE 00 12(4)
75 140M-J8P-*** 150-C135NBD --- 12(4)
75 140M-J8P-*** 150-C135NBD 200A, SIZE 1 12(4)
48
SMC-3 Soft Starter Unit Options
• Auxiliary contact for contactors• Auxiliary contact for circuit breaker• Surge suppressor• Control circuit transformer• Push buttons• Pilot lights
– Incandescent – LED– Incandescent, Push-to-Test– LED, Push-to-Test
• Selector switch– Two position– Three position
• DeviceNet starter auxiliary– (4) 120VAC inputs and (2) 120VAC outputs– (4) 24VDC inputs and (2) 120VAC outputs
• DeviceNet communication module, mounted internal to Solid State Starter• Isolation contactor• Human interface module
– Blank cover, no functionality, door mounted in bezel– LCD display, full numeric keypad, door mounted in bezel– LCD display, programmer only, door mounted in bezel
• Pump control, provides pump start and stop• Braking control, provides Smart Motor braking, Accu-Stop and Slow Speed braking
49
SMC Flex Soft Starter Units
Motor Rating Circuit Breaker SMC Flex High Interrupting Capacity Fuses
Module Size
Input Voltage kW(1)
(1) Approximate range of kilowatt ratings
Cat. No.(2)
(2) To complete the catalog numbers, please refer to the Industrial Controls Catalog at http://www.ab.com/en/epub/catalogs/12768/229240/
Cat. No.(2) Cat. No.(3)
(3) High interrupting capacity fuses are optional
1 = 80 mm
380/415V,
IP20/42/54
0.75 140M-C2N-*** 150-F5NBD --- 8
0.75 140M-C2N-*** 150-F5NBD 4A, SIZE 000 8
2.2 140M-D8N-*** 150-F5NBD --- 8
2.2 140M-D8N-*** 150-F5NBD 6A, SIZE 000 8
4 140M-D8N-*** 150-F25NBD --- 8
4 140M-D8N-*** 150-F25NBD 16A, SIZE 000 8
7.5 140M-D8N-*** 150-F25NBD --- 8
7.5 140M-D8N-*** 150-F25NBD 20A, SIZE 000 8
11 140M-D8N-*** 150-F25NBD --- 8
11 140M-D8N-*** 150-F25NBD 40A, SIZE 000 8
15 140M-F8P-*** 150-F43NBD --- 8
15 140M-F8P-*** 150-F43NBD 40A, SIZE 000 8
22 140M-H8P-*** 150-F43NBD --- 8
22 140M-H8P-*** 150-F43NBD 63A, SIZE 000 8
30 140M-H8P-*** 150-F60NBD --- 8
30 140M-H8P-*** 150-F60NBD 80A, SIZE 00 8
45 140M-H8P-*** 150-F85NBD --- 8
45 140M-H8P-*** 150-F85NBD 125A, SIZE 00 8
55 140M-J8P-*** 150-F108NBD --- 12(4)
(4) Fixed mount style
55 140M-J8P-*** 150-F108NBD 125A, SIZE 00 12(4)
75 140M-J8P-*** 150-F201NBD --- 24(5)
(5) 600 mm wide column
75 140M-J8P-*** 150-F201NBD 200A, SIZE 1 24(5)
90 140M-J8P-*** 150-F201NBD --- 24(5)
90 140M-J8P-*** 150-F201NBD 250A, SIZE 1 24(5)
110 140M-J8P-*** 150-F251NBD --- 24(5)
110 140M-J8P-*** 150-F251NBD 355A, SIZE 2 24(5)
132 140M-L8P-*** 150-F251NBD --- 24(5)
132 140M-L8P-*** 150-F251NBD 355A, SIZE 2 24(5)
160 140M-L8P-*** 150-F317NBD --- 24(5)
160 140M-L8P-*** 150-F317NBD 500A, SIZE 3 24(5)
185 140M-L8P-*** 150-F361NBD --- 24(5)
185 140M-L8P-*** 150-F361NBD 500A, SIZE 3 24(5)
220 140M-L8P-*** 150-F480NBD --- 24(5)
220 140M-L8P-*** 150-F480NBD 630A, SIZE 3 24(5)
50
SMC Flex Soft Starter Units
Motor Rating Circuit Breaker SMC Flex High Interrupting Capacity Fuses
Module Size
Input Voltage kW(1)
(1) Approximate range of kilowatt ratings
Cat. No.(2)
(2) To complete the catalog numbers, please refer to the Industrial Controls Catalog at http://www.ab.com/en/epub/catalogs/12768/229240/
Cat. No.(2) Cat. No.(3)
(3) High interrupting capacity fuses are optional
1 = 80 mm
440/460/480V,
IP20/42/54
0.75 140M-C2N-*** 150-F5NBD --- 8
0.75 140M-C2N-*** 150-F5NBD 4A, SIZE 000 8
2.2 140M-D8N-*** 150-F5NBD --- 8
2.2 140M-D8N-*** 150-F5NBD 6A, SIZE 000 8
4 140M-D8N-*** 150-F25NBD --- 8
4 140M-D8N-*** 150-F25NBD 16A, SIZE 000 8
7.5 140M-D8N-*** 150-F25NBD --- 8
7.5 140M-D8N-*** 150-F25NBD 20A, SIZE 000 8
11 140M-D8N-*** 150-F25NBD --- 8
11 140M-D8N-*** 150-F25NBD 40A, SIZE 000 8
15 140M-F8P-*** 150-F43NBD --- 8
15 140M-F8P-*** 150-F43NBD 40A, SIZE 000 8
22 140M-H8P-*** 150-F43NBD --- 8
22 140M-H8P-*** 150-F43NBD 63A, SIZE 000 8
30 140M-H8P-*** 150-F60NBD --- 8
30 140M-H8P-*** 150-F60NBD 80A, SIZE 00 8
45 140M-H8P-*** 150-F85NBD --- 8
45 140M-H8P-*** 150-F85NBD 125A, SIZE 00 8
55 140M-J8P-*** 150-F108NBD --- 12(4)
(4) Fixed mount style
55 140M-J8P-*** 150-F108NBD 125A, SIZE 00 12(4)
75 140M-J8P-*** 150-F135NBD --- 12(4)
75 140M-J8P-*** 150-F135NBD 200A, SIZE 1 12(4)
90 140M-J8P-*** 150-F201NBD --- 24(5)
(5) 600 mm wide column
90 140M-J8P-*** 150-F201NBD 250A, SIZE 1 24(5)
110 140M-J8P-*** 150-F201NBD --- 24(5)
110 140M-J8P-*** 150-F201NBD 355A, SIZE 2 24(5)
132 140M-L8P-*** 150-F251NBD --- 24(5)
132 140M-L8P-*** 150-F251NBD 355A, SIZE 2 24(5)
160 140M-L8P-*** 150-F317NBD --- 24(5)
160 140M-L8P-*** 150-F317NBD 500A, SIZE 3 24(5)
185 140M-L8P-*** 150-F361NBD --- 24(5)
185 140M-L8P-*** 150-F361NBD 500A, SIZE 3 24(5)
220 140M-L8P-*** 150-F480NBD --- 24(5)
220 140M-L8P-*** 150-F480NBD 630A, SIZE 3 24(5)
51
SMC Flex Soft Starter Unit Options
• Auxiliary contact for contactors• Auxiliary contact for circuit breaker• Surge suppressor• Control circuit transformer• Push buttons• Pilot lights
– Incandescent – LED– Incandescent, Push-to-Test– LED, Push-to-Test
• Selector switch– Two position– Three position
• DeviceNet starter auxiliary– (4) 120VAC inputs and (2) 120VAC outputs– (4) 24VDC inputs and (2) 120VAC outputs
• DeviceNet communication module, mounted internal to Solid State Starter• Isolation contactor• Human interface module
– Blank cover, no functionality, door mounted in bezel– LCD display, full numeric keypad, door mounted in bezel– LCD display, programmer only, door mounted in bezel
• Pump control, provides pump start and stop• Braking control, provides Smart Motor braking, Accu-Stop and Slow Speed braking
52
Variable Frequency Drive Units
PowerFlex® Variable Frequency AC Drives
The combination variable frequency AC drive units are specifically designed for use in the CENTERLINE 2500 Motor Control Centers. Each unit contains a variable frequency AC drive and either a fusible disconnect switch or circuit breaker. These units are available in a withdrawable unit style and a fixed unit style. Available models include:• PowerFlex 40 Variable Frequency AC drive• PowerFlex 70 Variable Frequency AC drive• PowerFlex 700 Variable Frequency AC drive
PowerFlex drive features include:• Isolated logic and power• Produce a three-phase, pulse width modulated (PWM) adjustable frequency
output and voltage output for exceptional control of motor speed and torque
• Are digitally programmed with access to mode programming, providing precise and repeatedly accurate setup, control and operation, and adaptability to handle a variety of applications
For drive unit selection go to page .
For drive unit option selection go to page .
PowerFlex 40 Variable Frequency Drive Units
Motor Rating Circuit Breaker PowerFlex 40 VFD Reactor Module Size
Input Voltage kW(1)
(1) Approximate range of kilowatt ratings
Cat. No.(2)
(2) To complete the catalog numbers, please refer to the Industrial Controls Catalog at http://www.ab.com/en/epub/catalogs/12768/229240/
Cat. No. Cat. No.(3)
(3) Line or load reactors are optional
1 = 80 mm
380/415V,
IP20
0.37 140M-C2N-*** 22B-D1P4N104 --- 4
0.37 140M-C2N-*** 22B-D1P4N104 1321-3R2-B 6
0.75 140M-C2N-*** 22B-D2P3N104 --- 4
0.75 140M-C2N-*** 22B-D2P3N104 1321-3R4-C 6
1.5 140M-D8N-*** 22B-D4P0N104 --- 4
1.5 140M-D8N-*** 22B-D4P0N104 1321-3R4-B 6
2.2 140M-D8N-*** 22B-D6P0N104 --- 4
2.2 140M-D8N-*** 22B-D6P0N104 1321-3R8-C 6
3.7 140M-D8N-*** 22B-D010N104 --- 4
3.7 140M-D8N-*** 22B-D010N104 1321-3R8-B 6
5.5 140M-D8N-*** 22B-D012N104 --- 8
5.5 140M-D8N-*** 22B-D012N104 1321-3R12-B 8
7.5 140M-D8N-*** 22B-D017N104 --- 8
7.5 140M-D8N-*** 22B-D017N104 1321-3R18-B 8
11 140M-D8N-*** 22B-D024N104 --- 8
11 140M-D8N-*** 22B-D024N104 1321-3R25-B 8
One Line Diagram
53
PowerFlex 40 Variable Frequency Drive Units (continued)
Motor Rating Circuit Breaker PowerFlex 40 VFD Reactor Module Size
Input Voltage kW(1)
(1) Approximate range of kilowatt ratings
Cat. No.(2)
(2) To complete the catalog numbers, please refer to the Industrial Controls Catalog at http://www.ab.com/en/epub/catalogs/12768/229240/
Cat. No. Cat. No.(3)
(3) Line or load reactors are optional
1 = 80 mm
380/415V,
IP42/54
0.37 140M-C2N-*** 22B-D1P4N104 --- 6
0.37 140M-C2N-*** 22B-D1P4N104 1321-3R2-B 6
0.75 140M-C2N-*** 22B-D2P3N104 --- 6
0.75 140M-C2N-*** 22B-D2P3N104 1321-3R4-C 6
1.5 140M-D8N-*** 22B-D4P0N104 --- 6
1.5 140M-D8N-*** 22B-D4P0N104 1321-3R4-B 6
2.2 140M-D8N-*** 22B-D6P0N104 --- 6
2.2 140M-D8N-*** 22B-D6P0N104 1321-3R8-C 6
3.7 140M-D8N-*** 22B-D010N104 --- 6
3.7 140M-D8N-*** 22B-D010N104 1321-3R8-B 6
5.5 140M-D8N-*** 22B-D012N104 --- 10
5.5 140M-D8N-*** 22B-D012N104 1321-3R12-B 10
7.5 140M-D8N-*** 22B-D017N104 --- 10
7.5 140M-D8N-*** 22B-D017N104 1321-3R18-B 10
11 140M-D8N-*** 22B-D024N104 --- 10
11 140M-D8N-*** 22B-D024N104 1321-3R25-B 10
54
PowerFlex 40 Variable Frequency Drive Units (continued)
Motor Rating Circuit Breaker PowerFlex 40 VFD Reactor Module Size
Input Voltage kW(1)
(1) Approximate range of kilowatt ratings
Cat. No.(2)
(2) To complete the catalog numbers, please refer to the Industrial Controls Catalog at http://www.ab.com/en/epub/catalogs/12768/229240/
Cat. No. Cat. No.(3)
(3) Line or load reactors are optional
1 = 80 mm
440/460/480V,
IP20
0.37 140M-C2N-*** 22B-D1P4N104 --- 4
0.37 140M-C2N-*** 22B-D1P4N104 1321-3R2-B 6
0.75 140M-C2N-*** 22B-D2P3N104 --- 4
0.75 140M-C2N-*** 22B-D2P3N104 1321-3R4-C 6
1.5 140M-D8N-*** 22B-D4P0N104 --- 4
1.5 140M-D8N-*** 22B-D4P0N104 1321-3R4-B 6
2.2 140M-D8N-*** 22B-D6P0N104 --- 4
2.2 140M-D8N-*** 22B-D6P0N104 1321-3R8-C 6
3.7 140M-D8N-*** 22B-D010N104 --- 4
3.7 140M-D8N-*** 22B-D010N104 1321-3R8-B 6
5.5 140M-D8N-*** 22B-D012N104 --- 8
5.5 140M-D8N-*** 22B-D012N104 1321-3R12-B 8
7.5 140M-D8N-*** 22B-D017N104 --- 8
7.5 140M-D8N-*** 22B-D017N104 1321-3R18-B 8
11 140M-D8N-*** 22B-D024N104 --- 8
11 140M-D8N-*** 22B-D024N104 1321-3R25-B 8
55
PowerFlex 40 Variable Frequency Drive Units (continued)
Motor Rating Circuit Breaker PowerFlex 40 VFD Reactor Module Size
Input Voltage kW(1)
(1) Approximate range of kilowatt ratings
Cat. No.(2)
(2) To complete the catalog numbers, please refer to the Industrial Controls Catalog at http://www.ab.com/en/epub/catalogs/12768/229240/
Cat. No. Cat. No.(3)
(3) Line or load reactors are optional
1 = 80 mm
440/460/480V,
IP42/54
0.37 140M-C2N-*** 22B-D1P4N104 --- 6
0.37 140M-C2N-*** 22B-D1P4N104 1321-3R2-B 6
0.75 140M-C2N-*** 22B-D2P3N104 --- 6
0.75 140M-C2N-*** 22B-D2P3N104 1321-3R4-C 6
1.5 140M-D8N-*** 22B-D4P0N104 --- 6
1.5 140M-D8N-*** 22B-D4P0N104 1321-3R4-B 6
2.2 140M-D8N-*** 22B-D6P0N104 --- 6
2.2 140M-D8N-*** 22B-D6P0N104 1321-3R8-C 6
3.7 140M-D8N-*** 22B-D010N104 --- 6
3.7 140M-D8N-*** 22B-D010N104 1321-3R8-B 6
5.5 140M-D8N-*** 22B-D012N104 --- 10
5.5 140M-D8N-*** 22B-D012N104 1321-3R12-B 10
7.5 140M-D8N-*** 22B-D017N104 --- 10
7.5 140M-D8N-*** 22B-D017N104 1321-3R18-B 10
11 140M-D8N-*** 22B-D024N104 --- 10
11 140M-D8N-*** 22B-D024N104 1321-3R25-B 10
56
PF40 Drive Unit Options
• Auxiliary contact for contactors• Auxiliary contact for circuit breaker• Surge suppressor• Control circuit transformer• Push buttons• Pilot lights
– Incandescent – LED– Incandescent, Push-to-Test– LED, Push-to-Test
• Selector switch– Two position– Three positio
• DeviceNet starter auxiliary– (4) 120VAC inputs and (2) 120V AC outputs– (4) 24VDC inputs and (2) 120V AC outputs
• DeviceNet communication module, mounted internal to Solid State Starter• ControlNet communication module, mounted internal to drive• Isolation contactor• Human interface module
– Blank cover, no functionality, door mounted in bezel– LCD display, full numeric keypad, door mounted in bezel– LCD display, programmer only, door mounted in bezel
• I/O control interface type– 24V DC control voltage interface with vector control– 120V AC control voltage interface with vector control– 24V DC control voltage interface with sensorless vector control– 120V AC control voltage interface with sensorless vector control
57
PowerFlex 70 Variable Frequency Drive Units (Normal Duty)
Motor Rating Circuit Breaker PowerFlex 70 VFD Isolation Contactor Reactor Module Size
Input Voltage kW(1)
(1) Approximate range of kilowatt ratings
Cat. No.(2)
(2) To complete the catalog numbers, please refer to the Industrial Controls Catalog at http://www.ab.com/en/epub/catalogs/12768/229240/
Cat. No. Cat. No.(2) Cat. No.(3)
(3) Line or load reactors are optional
1 = 80 mm
380/415V,
IP20
0.37 140M-C2N-*** 20AC1P3A0AYNANC0 100-C09*10 --- 6
0.37 140M-C2N-*** 20AC1P3A0AYNANC0 100-C09*10 1321-3R2-B 8
0.75 140M-C2N-*** 20AC2P1A0AYNANC0 100-C09*10 --- 6
0.75 140M-C2N-*** 20AC2P1A0AYNANC0 100-C09*10 1321-3R2-B 8
1.5 140M-D8N-*** 20AC3P5A0AYNANC0 100-C09*10 --- 6
1.5 140M-D8N-*** 20AC3P5A0AYNANC0 100-C09*10 1321-3R4-B 8
2.2 140M-D8N-*** 20AC5P0A0AYNANC0 100-C09*10 --- 6
2.2 140M-D8N-*** 20AC5P0A0AYNANC0 100-C09*10 1321-3R4-B 8
3.7 140M-D8N-*** 20AC8P7A0AYNANC0 100-C09*10 --- 6
3.7 140M-D8N-*** 20AC8P7A0AYNANC0 100-C09*10 1321-3R8-B 8
5.5 140M-D8N-*** 20AD011A0AYNANC0 100-C16*10 --- 8
5.5 140M-D8N-*** 20AD011A0AYNANC0 100-C16*10 1321-3R12-B 10
7.5 140M-D8N-*** 20AC015A0AYNANC0 100-C23*10 --- 8
7.5 140M-D8N-*** 20AC015A0AYNANC0 100-C23*10 1321-3R18-B 10
11 140M-D8N-*** 20AC022A0AYNANC0 100-C37*10 --- 10
11 140M-D8N-*** 20AC022A0AYNANC0 100-C37*10 1321-3R25-B 10
15 140M-F8N-*** 20AC030A0AYNANC0 100-C37*10 --- 10
15 140M-F8N-*** 20AC030A0AYNANC0 100-C37*10 1321-3R35-B 10
18.5 140M-H8N-*** 20AC037A0AYNANC0 100-C43*10 --- 10
18.5 140M-H8N-*** 20AC037A0AYNANC0 100-C43*10 1321-3R35-B 10
22 140M-H8N-*** 20AC043A0AYNANC0 100-C85*10 --- 10
22 140M-H8N-*** 20AC043A0AYNANC0 100-C85*10 1321-3R45-B 10
30 140M-H8N-*** 20AC060A0AYNANC0 100-C85*10 --- 14(4)
(4) Fixed mount style
30 140M-H8N-*** 20AC060A0AYNANC0 100-C85*10 1321-3R55-B 14(4)
37 140M-H8N-*** 20AC072A0AYNANC0 100-C85*10 --- 14(4)
37 140M-H8N-*** 20AC072A0AYNANC0 100-C85*10 1321-3R80-B 14(4)
58
PowerFlex 70 Variable Frequency Drive Units (Normal Duty, continued)
Motor Rating Circuit Breaker PowerFlex 70 VFD Isolation Contactor Reactor Module Size
Input Voltage kW(1)
(1) Approximate range of kilowatt ratings
Cat. No.(2)
(2) To complete the catalog numbers, please refer to the Industrial Controls Catalog at http://www.ab.com/en/epub/catalogs/12768/229240/
Cat. No. Cat. No.(2) Cat. No.(3)
(3) Line or load reactors are optional
1 = 80 mm
380/415V,
IP42/54
0.37 140M-C2N-*** 20AC1P3A0AYNANC0 100-C09*10 --- 8
0.37 140M-C2N-*** 20AC1P3A0AYNANC0 100-C09*10 1321-3R2-B 10
0.75 140M-C2N-*** 20AC2P1A0AYNANC0 100-C09*10 --- 8
0.75 140M-C2N-*** 20AC2P1A0AYNANC0 100-C09*10 1321-3R2-B 10
1.5 140M-D8N-*** 20AC3P5A0AYNANC0 100-C09*10 --- 8
1.5 140M-D8N-*** 20AC3P5A0AYNANC0 100-C09*10 1321-3R4-B 10
2.2 140M-D8N-*** 20AC5P0A0AYNANC0 100-C09*10 --- 8
2.2 140M-D8N-*** 20AC5P0A0AYNANC0 100-C09*10 1321-3R4-B 10
3.7 140M-D8N-*** 20AC8P7A0AYNANC0 100-C09*10 --- 8
3.7 140M-D8N-*** 20AC8P7A0AYNANC0 100-C09*10 1321-3R8-B 10
5.5 140M-D8N-*** 20AD011A0AYNANC0 100-C16*10 --- 12
5.5 140M-D8N-*** 20AD011A0AYNANC0 100-C16*10 1321-3R12-B 12
7.5 140M-D8N-*** 20AC015A0AYNANC0 100-C23*10 --- 12
7.5 140M-D8N-*** 20AC015A0AYNANC0 100-C23*10 1321-3R18-B 12
11 140M-D8N-*** 20AC022A0AYNANC0 100-C37*10 --- 14(4)
(4) Fixed mount style.
11 140M-D8N-*** 20AC022A0AYNANC0 100-C37*10 1321-3R25-B 14(4)
15 140M-F8N-*** 20AC030A0AYNANC0 100-C37*10 --- 14(4)
15 140M-F8N-*** 20AC030A0AYNANC0 100-C37*10 1321-3R35-B 14(4)
18.5 140M-H8N-*** 20AC037A0AYNANC0 100-C43*10 --- 14(4)
18.5 140M-H8N-*** 20AC037A0AYNANC0 100-C43*10 1321-3R35-B 14(4)
22 140M-H8N-*** 20AC043A0AYNANC0 100-C85*10 --- 14 (4)
22 140M-H8N-*** 20AC043A0AYNANC0 100-C85*10 1321-3R45-B 14(4)
30 140M-H8N-*** 20AC060A0AYNANC0 100-C85*10 --- 16(4)
30 140M-H8N-*** 20AC060A0AYNANC0 100-C85*10 1321-3R55-B 24(5)
(5) 600 mm wide column
37 140M-H8N-*** 20AC072A0AYNANC0 100-C85*10 --- 16(4)
37 140M-H8N-*** 20AC072A0AYNANC0 100-C85*10 1321-3R80-B 24(5)
59
PowerFlex 70 Variable Frequency Drive Units (Normal Duty,continued)
Motor Rating Circuit Breaker PowerFlex 70 VFD Isolation Contactor Reactor Module Size
Input Voltage kW(1)
(1) Approximate range of kilowatt ratings
Cat. No.(2)
(2) To complete the catalog numbers, please refer to the Industrial Controls Catalog at http://www.ab.com/en/epub/catalogs/12768/229240/
Cat. No. Cat. No.(2) Cat. No.(3)
(3) Line or load reactors are optional
1 = 80 mm
440/460/480V,
IP20
0.37 140M-C2N-*** 20AD1P1A0AYNANC0 100-C09*10 --- 6
0.37 140M-C2N-*** 20AD1P1A0AYNANC0 100-C09*10 1321-3R2-B 8
0.75 140M-C2N-*** 20AD2P1A0AYNANC0 100-C09*10 --- 6
0.75 140M-C2N-*** 20AD2P1A0AYNANC0 100-C09*10 1321-3R2-B 8
1.5 140M-D8N-*** 20AD3P4A0AYNANC0 100-C09*10 --- 6
1.5 140M-D8N-*** 20AD3P4A0AYNANC0 100-C09*10 1321-3R4-B 8
2.2 140M-D8N-*** 20AD5P0A0AYNANC0 100-C09*10 --- 6
2.2 140M-D8N-*** 20AD5P0A0AYNANC0 100-C09*10 1321-3R4-B 8
3.7 140M-D8N-*** 20AD8P0A0AYNANC0 100-C09*10 --- 6
3.7 140M-D8N-*** 20AD8P0A0AYNANC0 100-C09*10 1321-3R8-B 8
5.5 140M-D8N-*** 20AD011A0AYNANC0 100-C16*10 --- 8
5.5 140M-D8N-*** 20AD011A0AYNANC0 100-C16*10 1321-3R12-B 10
7.5 140M-D8N-*** 20AD014A0AYNANC0 100-C16*10 --- 8
7.5 140M-D8N-*** 20AD014A0AYNANC0 100-C16*10 1321-3R18-B 10
11 140M-D8N-*** 20AD022A0AYNANC0 100-C23*10 --- 10
11 140M-D8N-*** 20AD022A0AYNANC0 100-C23*10 1321-3R25-B 10
15 140M-F8N-*** 20AD027A0AYNANC0 100-C37*10 --- 10
15 140M-F8N-*** 20AD027A0AYNANC0 100-C37*10 1321-3R35-B 10
18.5 140M-F8N-*** 20AD034A0AYNANC0 100-C37*10 --- 10
18.5 140M-F8N-*** 20AD034A0AYNANC0 100-C37*10 1321-3R35-B 10
22 140M-H8N-*** 20AD040A0AYNANC0 100-C43*10 --- 10
22 140M-H8N-*** 20AD040A0AYNANC0 100-C43*10 1321-3R45-B 10
30 140M-H8N-*** 20AD052A0AYNANC0 100-C85*10 --- 14(4)
(4) Fixed mount style
30 140M-H8N-*** 20AD052A0AYNANC0 100-C85*10 1321-3R55-B 24(5)
(5) 600 mm wide column
37 140M-H8N-*** 20AD065A0AYNANC0 100-C85*10 --- 14(4)
37 140M-H8N-*** 20AD065A0AYNANC0 100-C85*10 1321-3R80-B 24 (5)
60
PowerFlex 70 Variable Frequency Drive Units (Normal Duty, continued)
Motor Rating Circuit Breaker PowerFlex 70 VFD Isolation Contactor Reactor Module Size
Input Voltage kW(1)
(1) Approximate range of kilowatt ratings
Cat. No.(2)
(2) To complete the catalog numbers, please refer to the Industrial Controls Catalog at http://www.ab.com/en/epub/catalogs/12768/229240/
Cat. No. Cat. No.(2) Cat. No.(3)
(3) Line or load reactors are optional
1 = 80 mm
440/460/480V,
IP42/54
0.37 140M-C2N-*** 20AD1P1A0AYNANC0 100-C09*10 --- 8
0.37 140M-C2N-*** 20AD1P1A0AYNANC0 100-C09*10 1321-3R2-B 10
0.75 140M-C2N-*** 20AD2P1A0AYNANC0 100-C09*10 --- 8
0.75 140M-C2N-*** 20AD2P1A0AYNANC0 100-C09*10 1321-3R2-B 10
1.5 140M-D8N-*** 20AD3P4A0AYNANC0 100-C09*10 --- 8
1.5 140M-D8N-*** 20AD3P4A0AYNANC0 100-C09*10 1321-3R4-B 10
2.2 140M-D8N-*** 20AD5P0A0AYNANC0 100-C09*10 --- 8
2.2 140M-D8N-*** 20AD5P0A0AYNANC0 100-C09*10 1321-3R4-B 10
3.7 140M-D8N-*** 20AD8P0A0AYNANC0 100-C09*10 --- 8
3.7 140M-D8N-*** 20AD8P0A0AYNANC0 100-C09*10 1321-3R8-B 10
5.5 140M-D8N-*** 20AD011A0AYNANC0 100-C16*10 --- 12
5.5 140M-D8N-*** 20AD011A0AYNANC0 100-C16*10 1321-3R12-B 12
7.5 140M-D8N-*** 20AD014A0AYNANC0 100-C16*10 --- 12
7.5 140M-D8N-*** 20AD014A0AYNANC0 100-C16*10 1321-3R18-B 12
11 140M-D8N-*** 20AD022A0AYNANC0 100-C23*10 --- 14(4)
(4) Fixed mount style
11 140M-D8N-*** 20AD022A0AYNANC0 100-C23*10 1321-3R25-B 14(4)
15 140M-F8N-*** 20AD027A0AYNANC0 100-C37*10 --- 14(4)
15 140M-F8N-*** 20AD027A0AYNANC0 100-C37*10 1321-3R35-B 14(4)
18.5 140M-F8N-*** 20AD034A0AYNANC0 100-C37*10 --- 14(4)
18.5 140M-F8N-*** 20AD034A0AYNANC0 100-C37*10 1321-3R35-B 14(4)
22 140M-H8N-*** 20AD040A0AYNANC0 100-C43*10 --- 14(4)
22 140M-H8N-*** 20AD040A0AYNANC0 100-C43*10 1321-3R45-B 14(4)
30 140M-H8N-*** 20AD052A0AYNANC0 100-C85*10 --- 16(4)
30 140M-H8N-*** 20AD052A0AYNANC0 100-C85*10 1321-3R55-B 24(5)
(5) 600 mm wide column
37 140M-H8N-*** 20AD065A0AYNANC0 100-C85*10 --- 16(4)
37 140M-H8N-*** 20AD065A0AYNANC0 100-C85*10 1321-3R80-B 24(5)
61
PF70 Drive Unit Options
• Auxiliary contact for contactors• Auxiliary contact for circuit breaker• Surge suppressor• Control circuit transformer• Push buttons• Pilot lights
– Incandescent – LED– Incandescent, Push-to-Test– LED, Push-to-Test
• Selector switch– Two position– Three position
• DeviceNet starter auxiliary– (4) 120V AC inputs and (2) 120V AC outputs– (4) 24V DC inputs and (2) 120V AC outputs
• DeviceNet communication module, mounted internal to Solid State Starter• ControlNet communication module, mounted internal to drive• Isolation contactor• Human interface module
– Blank cover, no functionality, door mounted in bezel– LCD display, full numeric keypad, door mounted in bezel– LCD display, programmer only, door mounted in bezel
• I/O control interface type– 24V DC control voltage interface with vector control– 120V AC control voltage interface with vector control– 24V DC control voltage interface with sensorless vector control– 120V AC control voltage interface with sensorless vector control
62
PowerFlex 700 Variable Frequency Drive Units (Normal Duty)
Motor Rating Circuit Breaker PowerFlex 40 VFD Isolation Contactor Reactor Module Size
Input Voltage kW(1)
(1) Approximate range of kilowatt ratings
Cat. No.(2)
(2) To complete the catalog numbers, please refer to the Industrial Controls Catalog at www.ab.com/catalogs
Cat. No. Cat. No.(2) Cat. No.(3)
(3) Line or load reactors are optional
1 = 80 mm
380/415V,
IP20
0.37 140M-C2N-*** 20BC1P3A0AYNANC0 100-C09*10 --- 8
0.37 140M-C2N-*** 20BC1P3A0AYNANC0 100-C09*10 1321-3R2-B 8
0.75 140M-C2N-*** 20BC2P1A0AYNANC0 100-C09*10 --- 8
0.75 140M-C2N-*** 20BC2P1A0AYNANC0 100-C09*10 1321-3R2-B 8
1.5 140M-D8N-*** 20BC3P5A0AYNANC0 100-C09*10 --- 8
1.5 140M-D8N-*** 20BC3P5A0AYNANC0 100-C09*10 1321-3R4-B 8
2.2 140M-D8N-*** 20BC5P0A0AYNANC0 100-C09*10 --- 8
2.2 140M-D8N-*** 20BC5P0A0AYNANC0 100-C09*10 1321-3R4-B 8
3.7 140M-D8N-*** 20BC8P7A0AYNANC0 100-C09*10 --- 8
3.7 140M-D8N-*** 20BC8P7A0AYNANC0 100-C09*10 1321-3R8-B 8
5.5 140M-D8N-*** 20BC011A0AYNANC0 100-C16*10 --- 8
5.5 140M-D8N-*** 20BC011A0AYNANC0 100-C16*10 1321-3R12-B 8
7.5 140M-D8N-*** 20BC015A0AYNANC0 100-C23*10 --- 8
7.5 140M-D8N-*** 20BC015A0AYNANC0 100-C23*10 1321-3R18-B 8
11 140M-D8N-*** 20BC022A0AYNANC0 100-C37*10 --- 8
11 140M-D8N-*** 20BC022A0AYNANC0 100-C37*10 1321-3R25-B 8
15 140M-F8N-*** 20BC030A0AYNANC0 100-C37*10 --- 8
15 140M-F8N-*** 20BC030A0AYNANC0 100-C37*10 1321-3R35-B 10
18.5 140M-H8N-*** 20BC037A0AYNANC0 100-C43*10 --- 8
18.5 140M-H8N-*** 20BC037A0AYNANC0 100-C43*10 1321-3R45-B 10
22 140M-H8N-*** 20BC043A0AYNANC0 100-C85*10 --- 12
22 140M-H8N-*** 20BC043A0AYNANC0 100-C85*10 1321-3R45-B 14(4)
(4) Fixed mount style
37 140M-H8N-*** 20BC072A0AYNANC0 100-C85*10 --- 12
37 140M-H8N-*** 20BC072A0AYNANC0 100-C85*10 1321-3R80-B 14(4)
55 140M-J8N-*** 20BC105A0ANNANC0 100-D180*11 --- 24(5)
(5) 600 mm wide column
55 140M-J8N-*** 20BC105A0ANNANC0 100-D180*11 1321-3R130-B 24(5)
75 140M-J8N-*** 20BC170A0ANNANC0 100-D180*11 --- 24(5)
75 140M-J8N-*** 20BC170A0ANNANC0 100-D180*11 1321-3R160-B 24(5)
90 140M-J8N-*** 20BC170A0ANNANC0 100-D180*11 --- 24(5)
90 140M-J8N-*** 20BC170A0ANNANC0 100-D180*11 1321-3R200-B 24(5)
63
PowerFlex 700 Variable Frequency Drive Units (Normal Duty, continued)
Motor Rating Circuit Breaker PowerFlex 40 VFD Isolation Contactor Reactor Module Size
Input Voltage kW(1)
(1) Approximate range of kilowatt ratings
Cat. No.(2)
(2) To complete the catalog numbers, please refer to the Industrial Controls Catalog at www.ab.com/catalogs
Cat. No. Cat. No.(2) Cat. No.(3)
(3) Line or load reactors are optional
1 = 80 mm
380/415V,
IP42/54
0.37 140M-C2N-*** 20BC1P3A0AYNANC0 100-C09*10 --- 8
0.37 140M-C2N-*** 20BC1P3A0AYNANC0 100-C09*10 1321-3R2-B 10
0.75 140M-C2N-*** 20BC2P1A0AYNANC0 100-C09*10 --- 8
0.75 140M-C2N-*** 20BC2P1A0AYNANC0 100-C09*10 1321-3R2-B 10
1.5 140M-D8N-*** 20BC3P5A0AYNANC0 100-C09*10 --- 8
1.5 140M-D8N-*** 20BC3P5A0AYNANC0 100-C09*10 1321-3R4-B 10
2.2 140M-D8N-*** 20BC5P0A0AYNANC0 100-C09*10 --- 8
2.2 140M-D8N-*** 20BC5P0A0AYNANC0 100-C09*10 1321-3R4-B 10
3.7 140M-D8N-*** 20BC8P7A0AYNANC0 100-C09*10 --- 8
3.7 140M-D8N-*** 20BC8P7A0AYNANC0 100-C09*10 1321-3R8-B 10
5.5 140M-D8N-*** 20BC011A0AYNANC0 100-C16*10 --- 8
5.5 140M-D8N-*** 20BC011A0AYNANC0 100-C16*10 1321-3R12-B 10
7.5 140M-D8N-*** 20BC015A0AYNANC0 100-C23*10 --- 8
7.5 140M-D8N-*** 20BC015A0AYNANC0 100-C23*10 1321-3R18-B 10
11 140M-D8N-*** 20BC022A0AYNANC0 100-C37*10 --- 12
11 140M-D8N-*** 20BC022A0AYNANC0 100-C37*10 1321-3R25-B 14(4)
(4) Fixed mount style
15 140M-F8N-*** 20BC030A0AYNANC0 100-C37*10 --- 12
15 140M-F8N-*** 20BC030A0AYNANC0 100-C37*10 1321-3R35-B 14(4)
18.5 140M-H8N-*** 20BC037A0AYNANC0 100-C43*10 --- 12
18.5 140M-H8N-*** 20BC037A0AYNANC0 100-C43*10 1321-3R45-B 14(4)
22 140M-H8N-*** 20BC043A0AYNANC0 100-C85*10 --- 14(4)
22 140M-H8N-*** 20BC043A0AYNANC0 100-C85*10 1321-3R45-B 16(4)
37 140M-H8N-*** 20BC072A0AYNANC0 100-C85*10 --- 14(4)
37 140M-H8N-*** 20BC072A0AYNANC0 100-C85*10 1321-3R80-B 16(4)
55 140M-J8N-*** 20BC105A0ANNANC0 100-D180*11 --- 24(5)
(5) 600 mm wide column
55 140M-J8N-*** 20BC105A0ANNANC0 100-D180*11 1321-3R130-B 24(5)
75 140M-J8N-*** 20BC170A0ANNANC0 100-D180*11 --- 24(5)
75 140M-J8N-*** 20BC170A0ANNANC0 100-D180*11 1321-3R160-B 24(5)
90 140M-J8N-*** 20BC170A0ANNANC0 100-D180*11 --- 24(5)
90 140M-J8N-*** 20BC170A0ANNANC0 100-D180*11 1321-3R200-B 24(5)
64
PowerFlex 700 Variable Frequency Drive Units (Normal Duty, continued)
Motor Rating Circuit Breaker PowerFlex 40 VFD Isolation Contactor Reactor Module Size
Input Voltage kW(1)
(1) Approximate range of kilowatt ratings
Cat. No.(2)
(2) To complete the catalog numbers, please refer to the Industrial Controls Catalog at www.ab.com/catalogs
Cat. No. Cat. No.(2) Cat. No.(3)
(3) Line or load reactors are optional
1 = 80 mm
440/460/480V,
IP20
0.37 140M-C2N-*** 20BD1P1A0AYNANC0 100-C09*10 --- 8
0.37 140M-C2N-*** 20BD1P1A0AYNANC0 100-C09*10 1321-3R2-B 8
0.75 140M-C2N-*** 20BD2P1A0AYNANC0 100-C09*10 --- 8
0.75 140M-C2N-*** 20BD2P1A0AYNANC0 100-C09*10 1321-3R2-B 8
1.5 140M-D8N-*** 20BD3P4A0AYNANC0 100-C09*10 --- 8
1.5 140M-D8N-*** 20BD3P4A0AYNANC0 100-C09*10 1321-3R4-B 8
2.2 140M-D8N-*** 20BD5P0A0AYNANC0 100-C09*10 --- 8
2.2 140M-D8N-*** 20BD5P0A0AYNANC0 100-C09*10 1321-3R4-B 8
3.7 140M-D8N-*** 20BD8P0A0AYNANC0 100-C09*10 --- 8
3.7 140M-D8N-*** 20BD8P0A0AYNANC0 100-C09*10 1321-3R8-B 8
5.5 140M-D8N-*** 20BD011A0AYNANC0 100-C16*10 --- 8
5.5 140M-D8N-*** 20BD011A0AYNANC0 100-C16*10 1321-3R12-B 8
7.5 140M-D8N-*** 20BD014A0AYNANC0 100-C16*10 --- 8
7.5 140M-D8N-*** 20BD014A0AYNANC0 100-C16*10 1321-3R18-B 8
11 140M-D8N-*** 20BD022A0AYNANC0 100-C23*10 --- 8
11 140M-D8N-*** 20BD022A0AYNANC0 100-C23*10 1321-3R25-B 8
15 140M-F8N-*** 20BD027A0AYNANC0 100-C37*10 --- 8
15 140M-F8N-*** 20BD027A0AYNANC0 100-C37*10 1321-3R35-B 10
18.5 140M-F8N-*** 20BD034A0AYNANC0 100-C37*10 --- 8
18.5 140M-F8N-*** 20BD034A0AYNANC0 100-C37*10 1321-3R35-B 10
22 140M-H8N-*** 20BD040A0AYNANC0 100-C43*10 --- 12(4)
(4) Fixed mount style
22 140M-H8N-*** 20BD040A0AYNANC0 100-C43*10 1321-3R45-B 14(4)
37 140M-H8N-*** 20BD065A0AYNANC0 100-C85*10 --- 12(4)
37 140M-H8N-*** 20BD065A0AYNANC0 100-C85*10 1321-3R80-B 14(4)
55 140M-J8N-*** 20BD096A0AYNANC0 100-D180*11 --- 24(5)
(5) 600 mm wide column
55 140M-J8N-*** 20BD096A0AYNANC0 100-D180*11 1321-3R100-B 24(5)
75 140M-J8N-*** 20BD125A0AYNANC0 100-D180*11 --- 24(5)
75 140M-J8N-*** 20BD125A0AYNANC0 100-D180*11 1321-3R130-B 24(5)
90 140M-J8N-*** 20BD156A0AYNANC0 100-D180*11 --- 24(5)
90 140M-J8N-*** 20BD156A0AYNANC0 100-D180*11 1321-3R160-B 24(5)
110 140M-J8N-*** 20BD180A0AYNANC0 100-D210*11 --- 24(5)
110 140M-J8N-*** 20BD180A0AYNANC0 100-D210*11 1321-3R200-B 24(5)
65
PowerFlex 700 Variable Frequency Drive Units (Normal Duty, continued)
Motor Rating Circuit Breaker PowerFlex 40 VFD Isolation Contactor Reactor Module Size
Input Voltage kW(1)
(1) Approximate range of kilowatt ratings
Cat. No.(2)
(2) To complete the catalog numbers, please refer to the Industrial Controls Catalog at www.ab.com/catalogs
Cat. No. Cat. No.(2) Cat. No.(3)
(3) Line or load reactors are optional
1 = 80 mm
440/460/480V,
IP42/54
0.37 140M-C2N-*** 20BD1P1A0AYNANC0 100-C09*10 --- 8
0.37 140M-C2N-*** 20BD1P1A0AYNANC0 100-C09*10 1321-3R2-B 10
0.75 140M-C2N-*** 20BD2P1A0AYNANC0 100-C09*10 --- 8
0.75 140M-C2N-*** 20BD2P1A0AYNANC0 100-C09*10 1321-3R2-B 10
1.5 140M-D8N-*** 20BD3P4A0AYNANC0 100-C09*10 --- 8
1.5 140M-D8N-*** 20BD3P4A0AYNANC0 100-C09*10 1321-3R4-B 10
2.2 140M-D8N-*** 20BD5P0A0AYNANC0 100-C09*10 --- 8
2.2 140M-D8N-*** 20BD5P0A0AYNANC0 100-C09*10 1321-3R4-B 10
3.7 140M-D8N-*** 20BD8P0A0AYNANC0 100-C09*10 --- 8
3.7 140M-D8N-*** 20BD8P0A0AYNANC0 100-C09*10 1321-3R8-B 10
5.5 140M-D8N-*** 20BD011A0AYNANC0 100-C16*10 --- 8
5.5 140M-D8N-*** 20BD011A0AYNANC0 100-C16*10 1321-3R12-B 10
7.5 140M-D8N-*** 20BD014A0AYNANC0 100-C16*10 --- 8
7.5 140M-D8N-*** 20BD014A0AYNANC0 100-C16*10 1321-3R18-B 10
11 140M-D8N-*** 20BD022A0AYNANC0 100-C23*10 --- 12
11 140M-D8N-*** 20BD022A0AYNANC0 100-C23*10 1321-3R25-B 14(4)
(4) Fixed mount style
15 140M-F8N-*** 20BD027A0AYNANC0 100-C37*10 --- 12
15 140M-F8N-*** 20BD027A0AYNANC0 100-C37*10 1321-3R35-B 14(4)
18.5 140M-F8N-*** 20BD034A0AYNANC0 100-C37*10 --- 12
18.5 140M-F8N-*** 20BD034A0AYNANC0 100-C37*10 1321-3R35-B 14(4)
22 140M-H8N-*** 20BD040A0AYNANC0 100-C43*10 --- 14[(4)
22 140M-H8N-*** 20BD040A0AYNANC0 100-C43*10 1321-3R45-B 16(4)
37 140M-H8N-*** 20BD065A0AYNANC0 100-C85*10 --- 14(4)
37 140M-H8N-*** 20BD065A0AYNANC0 100-C85*10 1321-3R80-B 16(4)
55 140M-J8N-*** 20BD096A0AYNANC0 100-D180*11 --- 24(5)
(5) 600 mm wide column
55 140M-J8N-*** 20BD096A0AYNANC0 100-D180*11 1321-3R100-B 24(5)
75 140M-J8N-*** 20BD125A0AYNANC0 100-D180*11 --- 24(5)
75 140M-J8N-*** 20BD125A0AYNANC0 100-D180*11 1321-3R130-B 24(5)
90 140M-J8N-*** 20BD156A0AYNANC0 100-D180*11 --- 24(5)
90 140M-J8N-*** 20BD156A0AYNANC0 100-D180*11 1321-3R160-B 24(5)
110 140M-J8N-*** 20BD180A0AYNANC0 100-D210*11 --- 24(5)
110 140M-J8N-*** 20BD180A0AYNANC0 100-D210*11 1321-3R200-B 24(5)
66
PF700 Drive Unit Options
• Auxiliary contact for contactors• Auxiliary contact for circuit breaker• Surge suppressor• Control circuit transformer• Push buttons• Pilot lights
– Incandescent – LED– Incandescent, Push-to-Test– LED, Push-to-Test
• Selector switch– Two position– Three position
• DeviceNet starter auxiliary– (4) 120VAC inputs and (2) 120VAC outputs– (4) 24VDC inputs and (2) 120VAC outputs
• DeviceNet communication module, mounted internal to Solid State Starter• ControlNet communication module, mounted internal to drive• Isolation contactor• Human interface module
– Blank cover, no functionality, door mounted in bezel– LCD display, full numeric keypad, door mounted in bezel– LCD display, programmer only, door mounted in bezel
• I/O control interface type– 24 VDC control voltage interface with vector control– 120 VAC control voltage interface with vector control– 24 VDC control voltage interface with sensorless vector control– 120 VAC control voltage interface with sensorless vector control
67
Distribution Panels
PLC and I/O Compartments
68
Selection Data
Column Selection
The following tables outline the CENTERLINE 2500 MCC product offering. Please select your columns and unit types.
Column Dimensions mm (in)
Column Options
Column Type Width Depth Height IP Rating Separation
Withdrawable Units 700 mm (200 mm wireway) 600 mm
800 mm
1200 mm (double-front)
2300 mm IP 20
IP 30
IP 42
IP 54
Form 3b
Form 4b800 mm (300 mm wireway)
900 mm (400 mm wireway)
1000 mm (500 mm wireway)
Fixed Units 700 mm (no vertical wireway)
800 mm (no vertical wireway)
900 mm (no vertical wireway)
1000 mm (no vertical wireway)
170 (6.69)
1980 (77.95)
115 (4.53)
500 (19.69) 200 - 500
(7.87 - 19.69)
600 (23.62)
2300 (90.55)
35 (1.38)
700 - 1000 (27.56 - 39.37
Delete?
69
Horizontal Power Bus Options
Horizontal Power Bus
Bus Rating Short Circuit Withstand Rating
Short Circuit Peak Withstand Rating
Material
800 A 50 kA for 1 second 110 kA Bare Copper or Tin-plated Copper
1250 A 50 kA for 3 second and 80 kA for 1 second
176 kA
1600A
2000 A
2500 A
3200 A 50 kA for 3 second and 100 kA for 1 second
220 kA
4000 A
Vertical Power Bus Options
Vertical Power Bus
Bus Rating Short Circuit Withstand Rating
Short Circuit Peak Withstand
Material
300 A 50 kA for 0.2 second 110 kA for 3 second Tin-Plated Copper
600 A 50 kA for 1 second
Neutral Power Bus Options
Vertical Power Bus
Bus Rating Short Circuit Withstand Rating
Short Circuit Peak Withstand
Material
Full 50 kA for 0.2 second 110 kA for 3 second Tin-Plated Copper
Half 50 kA for 1 second
70
Incoming Power and Control Power Selection
Incoming Power and Control Voltage Options
Line/System Voltage (V)
Frequency (Hz) Control/Coil Voltage (V) Control Type
380 50 24 DC; 110, 220 AC Transformer, Separate, or line to neutral60 24 DC; 110, 120, 220 AC
400 50 24 DC; 110, 230 AC
60
415 50 24 DC; 110, 240 AC
60 24 DC; 120, 240 AC
440 50 24 DC; 110, 220 AC
60 24 DC; 110, 120, 220 AC
480 50
60 24 DC; 120, 240 AC
600 50
60 24 DC; 120, 240 AC
690(1)
(1) Consult the factory
50
60
71
Unit Selection
Incoming Main Lug Compartments and Outgoing Feeder Lug Compartments
The line lug compartments provide a lug connection for incoming lines (mains) to distribute power to the motor control center for outgoing cables (feeders) to feed power from the motor control center to an external load. Mechanical or crimp style lugs are available. Lug compartments are a fixed-unit design and may be located at the top or bottom of the column.
Main and Feeder Lugs
Lug Compartments
Amperes Cable Provisions, Maximum Number per Phase and Maximum Cable Size
Module Size
Mechanical Type Lugs(1) (Single Cable)
(1) Fixed mount style
Crimp Type Lugs(1)
300 (2) 185 mm2 (2) 185 mm2 (2)
(2) Consult factory
400 (2) (2) (2)
600 (2) 185 mm2 (2) 185 mm2 6(2)
(1) 240 mm2 (2) 185 mm2 6(2)
(2) 400 mm2 (1) 400 mm2 6(2)
(1) (2) 240 mm2 6(2)
(4) 400 mm2 (4) 400 mm2 6(2)
800 (2) 400 mm2 (2) 400 mm2 6(2)
(4) 300 mm2 (4) 240 mm2 24(2)
(1) 400 mm2 (3) 240 mm2 24(2)
(2) 300 mm2 (4) 185 mm2 24(2)
(4) 240 mm2 24(2)
(1) 400 mm2 (2) 400 mm2 24(2)
(2) 400 mm2 (4) 240 mm2 24(2)
(4) 300 mm2 24(2)
(4) 400 mm2 (4) 400 mm2 24(2)
1250 (2) (2) 24(2)
1600 (4) 400 mm2 (4) 400 mm2 24(2)
2000 (6) 400 mm2 (6) 400 mm2 24(2)
2500 (2) (2) 24(2)
3200 (2) (2) 24(2)
4000 (2) (2) 24(2)
Main LugFeeder Lug
72
Miscellaneous Units
DeviceNet Power Supply
DeviceNet Power Supply
Units are supplied with a circuit breaker or fusible disconnect
Central Control Transformer Units
Module Size
Unit Description
4 Central Control Transformer
DeviceNet Power Supply Units
Module Size
Unit Description
2 DeviceNet Power Supply
4 Redundant DeviceNet Power Supply
Bridge Units
Module Size
Unit Description
2 ControlNet to DeviceNet Bridge
2 Ethernet to DeviceNet Bridge
2 Profibus to DeviceNet Bridge
73
Technical Data
Technical Standards and Certifications
The MCC is designed and tested to meet or exceed the requirements defined by the following IEC standards and directives.
• EN 60439-1:1999 + A1:2004, the standard for type-tested and partially type-tested assemblies of low voltage switchgear and control gear assemblies (TTA, PTA)
• EN 60204-1:2006, the general requirements for the safety of electrical equipment of machines• 2006/95/EC, Low Voltage Directive• 2004/108/EC, EMC Directive• 2002/95/EC, the restriction of hazardous substances directive (RoHS)• KEMA certified (TTA)
The MCC columns, units and components are available with the CE Conformance Mark and the China Compulsory Certification (CCC).
The MCC is designed, manufactured and tested in facilities registered to ISO 9001 quality standards.
Operating Environment
The MCC is intended for use in a pollution degree 3 environment.
The MCC is designed to operate in the following ambient conditions. The ambient operating temperature shall range from -5…40 °C, with the average temperature in any 24 hour period not exceeding 35 °C.
The MCC is designed to operate at altitudes up to 1000 m. For altitudes exceeding 1000 m, contact your Rockwell Automation representative for derating information.
74
Forms of Separation
Internal isolation and separation exists between the following:• Individual units• Units and wireways• Units and the bus system• Wireways and the bus system
In addition, the vertical wireway for power wiring is separate from the vertical wireway for control and network wiring.
Standard internal separation within the MCC is Form 3b. Form 4b is available by enclosing terminals for external conductors in a metal box within the vertical wireway.
Internal Separation
Form 3b Form 4b
75
CENTERLINE 2500 Specifications
StandardsEN 60439-1:1999 + A1:2004 Low-voltage switchgear and controlgear assemblies
Part 1: Type-tested and partially type-tested assemblies
EN 60204-1:2006 Safety of machinery – Electrical equipment of machinesPart 1: General requirements
EC Directives2006/95/EC Low Voltage Directive2004/108/EC EMC Directive
2002/95/EC(1)
(1) Low voltage Motor Control Center products are exempt under Category 9, however Rockwell Automation is committed to demonstrating the highest standard of global environmental management. It is the goal of Rockwell Automation to meet the material restrictions on products, even where compliance is not legally required.
Restriction of the Use of Certain Hazardous Substances in Electrical and Electronic Equipment (RoHS)
Certifications and MarkingsChina Compulsory Certificate (CCC)CE Conformance MarkedKEMA certified (TTA)
Rated VoltagesRated Operating Voltage, Ue Up to 690 V, 3-Phase
Rated Frequency, fn 50 – 60 Hz
Rated Insulation Voltage, Ui 1000 V, 3-Phase
Rated Currents Horizontal Bus Vertical BusContinuous Current Rating, Ie Up to 4000 A Up to 600 A
Short Circuit Peak Withstand, Ipk Up to 176 kA for 1 second Up to 110 kA for 3 second
Short Time Withstand Rating, Icw Up to 80 kA for 1 second Up to 50 kA for 1 second
Neutral (N) Full or half ratedCreepage Distances and Clearances
Rated Impulse Withstand Voltage, Uimp 6, 8, or 12 kV
Material Group (Overvoltage Category) IIIa (175 </= CTI < 400)Pollution Degree 3
Bus Material and PlatingHorizontal Power Bus Copper (optional tin plating)Vertical Distribution Bus Copper with tin platingProtective Earth Conductor (PE) Copper (optional tin plating)
Degrees of ProtectionIEC 60529 IP 20, 40, 42 or 54
Forms of SeparationIEC 60439-1 Form 3b or 4b
Column DimensionsHeight 2300 mmWidth 700, 800, 900, or 1000 mmDepth 600 or 800 mm (1200 mm, double-front)
UnitsApproximate Module Size 80 mm high x 500 mm wide = 1 moduleModules per Column 24Withdrawable Unit Sizes 1, 2, 4, 6, 8, 10, 12 modules
Structural Surface TreatmentsInterior High Visibility White Paint (Additional colors available by request.)Exterior RAL 7032 Pebble Grey Paint or Munsell 6.5 Paint (Additional colors available by request.)
EnvironmentStorage Temperature -25…55°COperating (Ambient) Temperature -5…40°CAltitude Up to 1000 m
76
Structure Material
This list has the approximate thickness and gauge of the MCC structural components and external covers.
CENTERLINE 2500 MCC Structure Details
Structural Components Thickness (mm)
Side Plate 2.0
Back Plate 2.5
Covers and Panels
Top Plate 2.0
Bottom Plate 2.0
End Closing Plate 2.0
Horizontal Wireway Cover 2.0
Doors
Unit Door 2.0
Vertical Wireway Door 2.0
Other Steel
External Mounting Channel 3.5
77
78
ChecklistExplanation of why using the checklist is important.
Customer User
Reviewed the customer documents prior to filling out this form
Office
Standards and Certifications
KEMA CE CCC Other ____________
Incoming Power
Line Voltage: 380V 400V 415V 440V 480V 600V 690V
System Power: Delta Grounded Delta
Grounded Wye Grounded Wye with Impedance
Frequency: 50 Hz 60 Hz
Available Fault Current: kA
Control Power
Voltage: 24V DC 110V AC 115V AC 120V AC 220V AC 230V AC 240V AC
Source: Individual Control Transformer
Standard VA Extra Capacity
Common Control Power Transformer
Separate Control Power Source
Control Terminal Blocks Location: Top Horizontal Wireway Vertical Wireway
Structure
Enclosure Rating:
IP 20 (vented doors) IP 42 (non-vented, standard)
IP 40 (vented doors with filters) IP 54 (fully gasketed, doors and bottom plates)
Forms of Internal Separation: 3b (standard) 4b
Mounting Configuration Stand Alone Add to Existing
Front Only Double-front
Depth: 600mm 800mm
Width: 700mm (200mm vertical wireway, standard) 900mm (400mm vertical wireway)
800mm (300mm vertical wireway) 1000mm (500mm vertical wireway)
Options: Space Heater w/ Thermostat Arc Containment Latches
Cable Supports Other ________________________
External Paint: RAL7032 Pebble Grey (standard) Other _____________
Internal Paint: High Visibility Gloss White Other _____________
Ambient Temperature: °C maximum Altitude: meters
79
Bus
Fault Rating/Bracing: 50kA for 3 cycles 65kA for 3 cycles 50kA for 1 second
50kA for 3 seconds (horizontal power bus only)
80kA for 1 second (horizontal power bus only)
Horizontal Power Bus Rating: 800A (standard) 1250A 1600A
2000A 2500A 3200A 4000A
Material: Copper Copper, Tin Plated
Neutral Bus: Full Rated Half Rated
Vertical Distribution Bus
Rating: 300A
(provides 600A capacity, standard) 600A
(provides 1200A capacity)
Material: Copper, Tin Plated
Protective Earth Conductor (PE) Horizontal Location: Bottom (standard)
Material: Copper, Unplated Copper, Tin Plated
Size: 1-6 x 50 mm 2-6 x 50 mm 3-6 x 50 mm
Vertical (Plug-in): Copper, Unplated Copper, Tin Plated
Stab Openings: Automatic Shutters (standard)
IntelliCENTER Technology
IntelliCENTER: DeviceNet Cabling DeviceNet Cabling with IntelliCENTER Software
Linking Device: EtherNET/IP ControlNet Profibus Other _____________
ArcShield
Yes
80
Incoming Cable Termination/Provision
Ampere Rating: __________A
Located in Column Number: __________ Top Bottom
Number of cables per phase: __________ Cable Size _______________________
Main Lug Only (MLO): Crimp Compression Lugs Mechanical Lugs Lugs Not Supplied
Main Fusible Disconnect (MFD): Fuses Supplied Fuse Type __________________
Fuses Not Supplied
Main Circuit Breaker (MCB): Ground Fault Shunt Trip
Auxiliary Contacts - Qty. __________ Other ______________
Number of current transformers required _______________
Number of potential transformers required ______________
Incoming Metering Options: Analog Ammeter Ammeter Switch
Analog Voltmeter Voltmeter Switch
Powermonitor 3000
1404-M5
1404-M6
Digital Volt/Ammeter
1405-M610
Outgoing Cable Termination/Provision
Ampere Rating:__________A Number of cables per phase __________ Cable Size _______________________
Lug Type: Crimp Compression Lugs Mechanical Lugs Lugs Not Supplied
Feeder Units
Fuse Switch: Fuses Supplied Fuse Type _____________________
Fuses Not Supplied
Circuit Breaker (Thermal Magnetic): Interrupting Rating _______________kA Ampere Rating ________A
Other__________________________________________
Nameplates
Unit Nameplates: Cardholder Engraved Acrylic Engraved Phenolic
Color Scheme Black letters on white White letters on black
White letters on black (phenolic only)
Door Latches
Door Latch Type: 1/4 Turn 1/4 Turn with T-handle
Arc Containment Arc Containment with T-handle
Wire Markers
Wire Marker Type: Sleeve Data Tab Heat Shrink
Spares
Spare Parts Spare Units
81
Direct On Line Starter Units (copy and complete for each unit needed)
Unit Type: Non-reversing Starter Reversing Starter
Ampere Rating: ________A Kilowatt Rating: _______kw
Disconnecting Means: Fused (rotary operator only) Fuse Type _____________
Fuses not supplied
Circuit Breaker
Handle Operator: Rotary Operator Flange Operator (2 module minimum)
Overload:
Type: E1 Plus E1 Plus with Ground Fault
E3 Plus E3 Plus with Ground Fault
Reset: External (door mounted)
Duty Rating: AC3 (standard) AC4
Protection: Type 1 Type 2
Unit Type: Withdrawable Semi-withdrawable Fixed
Options and Accessories
Pilot Lights: Qty_______ Transformer Type Push-to-test LED Lamps
Text on Legend Plate: On Off Fault
Emergency Other ____________________________
Pushbuttons: Qty_______
Text on Legend Plate: On Off Reset
Emergency Other ____________________________
Selector Switch: Yes
Starter Auxillary Contacts: Normally Open, Qty _____ Normally Closed, Qty _____
Relays or Timers, Describe ____________________________
Others, Describe ____________________________
Notes
82
Soft Starter Units (copy and complete for each unit needed)
Unit Type: SMC-3 SMC Flex
Connection: Line Connection Delta Connection
Ampere Rating: ________A Kilowatt Rating: _______kw
Disconnecting Means: Fused (rotary operator only) Fuse Type _____________
Fuses not supplied
Circuit Breaker
Handle Operator: Rotary Operator Flange Operator (2 module minimum)
Unit Type: Withdrawable Semi-withdrawable Fixed
Options and Accessories
Pilot Lights: Qty_______ Transformer Type Push-to-test LED Lamps
Text on Legend Plate: Start Stop
Other ____________________________
Pushbuttons: Qty_______
Text on Legend Plate: On Off Fault
Other ____________________________
Selector Switch: Yes
Human Interface Module (HIM): LCD Display, Full Numeric Keypad LCD Display, Programmer Only
Starting Mode: Pump Control Braking Control
Others, Describe ____________________________
Notes
83
Variable Frequency AC Drive Units (copy and complete for each unit needed)
Unit Type: PowerFlex 40 PowerFlex 70
PowerFlex 700 PowerFlex 700H
Rating: Normal Duty Heavy Duty
Ampere Rating: ________A Kilowatt Rating: _______kw
Disconnecting Means: Fused (rotary operator only) Fuse Type ________________
Fuses not supplied
Circuit Breaker
Handle Operator: Rotary Operator Flange Operator (2 module minimum)
Unit Type: Withdrawable Semi-withdrawable Fixed
Options and Accessories
Pilot Lights: Qty_______ Transformer Type Push-to-test LED Lamps
Text on Legend Plate: Start Stop
Other ____________________________
Pushbuttons: Qty_______
Text on Legend Plate: On Off Fault
Other ____________________________
Selector Switch: Yes
Human Interface Module (HIM): LCD Display, Full Numeric Keypad LCD Display,
Programmer Only
Braking Mode: Pump Control Braking Control
Reactors: Line Reactor Load Reactor
Others, Describe ____________________________
Notes
84
Miscellaneous Units (copy and complete for each unit needed)
DeviceNet Power Supply Unit
Redundant DeviceNet Power Supply Unit
DeviceNet Back-up Power Supply Unit Specify unit location _____________________________
Programmable Controllers: Number of Slots ___________ Power Supply___________
Describe: ________________________________________
Other Units, Options or Modifications: Describe: ________________________________________
________________________________________________
Extra Space for Future Units: Describe: ________________________________________
________________________________________________
Comments / Additional Notes:
85
Fill in blanks as required.
Motor List
Unit Description Rating Module Size
Comments/Additional Notes
86
Publication 2500-SG001B-EN-P—May 200988
Supersedes Publication 2500-SG001A-EN-P—January 2008 Copyright © 2009 Rockwell Automation, Inc. Printed in the U.S.A.