ceiling-floor, cassette and ducts - … · ceiling-floor, cassette and ducts. 2 eng 3 eng ... false...

22
ENG WITH AXIALS FAN OUTDOOR UNITS Installation Manual CEILING-FLOOR, CASSETTE AND DUCTS

Upload: hoangthuy

Post on 06-Sep-2018

233 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: CEILING-FLOOR, CASSETTE AND DUCTS - … · CEILING-FLOOR, CASSETTE AND DUCTS. 2 ENG 3 ENG ... false ceiling to ensure the unit will suit the dis-tance. - Using the installation template

ENG

WITH AXIALS FAN OUTDOOR UNITS

Installation Manual

CEILING-FLOOR, CASSETTE AND DUCTS

Page 2: CEILING-FLOOR, CASSETTE AND DUCTS - … · CEILING-FLOOR, CASSETTE AND DUCTS. 2 ENG 3 ENG ... false ceiling to ensure the unit will suit the dis-tance. - Using the installation template

2

ENG

3

ENG

Having a policy of continuous product improvement, Saunier Duval reserves the right to modify the specifications, giving no prior warning.

Saunier Duval cannot anticipate all possible circumstances that could pose a potential risk. This equipment has been designed and manufactured for air conditioning. The use of this equip-

ment for other domestic and industrial use shall be the responsibility of whoever plans this, or installs or uses the equipment in such a manner..

Reproduction of this manual is forbidden without written permission. For any queries, contact your nearest Saunier Duval supplier.

WARNINGS

These items must be fitted and used in accordance with the Regulations and Standards in effect for cooling, electrical and mechanical installations for where they are to be fitted.

EXTREME OPERATION CONDITIONS

This air conditioner is designed for the following temperatures. Keep the unit operating within these limits.

REFRIGERATION HEATING

Indoor

Outdoor 43ºC D.B.

0ºC D.B.

24ºC D.B.

-5ºC D.B.

32ºC D.B.

19ºC D.B.

27ºC D.B.

15ºC D.B.

(*) Range on remote controller: from 30ºC to 18ºC (from 30ºC to 16ºC on the cable remote).

Page 3: CEILING-FLOOR, CASSETTE AND DUCTS - … · CEILING-FLOOR, CASSETTE AND DUCTS. 2 ENG 3 ENG ... false ceiling to ensure the unit will suit the dis-tance. - Using the installation template

2

ENG

3

ENG

Prior to any intervention in the appliance, installation, start-up, use and maintenance, the staff in charge of these operations must be familiar with all the instructions and recommendations appearing in the appliance installation manual, likewise the elements in the technical dossier of the product.

The staff in charge of the appliance recep-tion must carry out a visual control to verify the damages which might have occurred to the appliance during transport.

Installation of the appliance close to a heat source, combustible and corrosive materials or the air intake conduit of an adjacent building is prohibited.

The appliance is to be installed, maintained and repaired by qualified staff pursuant to the demands of the guidelines, current regulations not to mention the training of the professional him/herself.

Check that the mounting and fastening devices are sufficient to withstand the weight of the unit. If they are not, the unit may fall and cause an accident.

Do not use any coolant other than R-407C. The mixture of gases in the cooling cycle can lead to damage or impaired perfor-mance.

While connecting the outdoor unit, keep the cabling conduit rigid. Faulty cable fitting can cause overheating, electrical discharges or fire at these connections.

Place the drainage hose in a suitable posi-tion. An improperly fitted hose will force the water back to the room, thus damaging the furniture.

During the appliance maintenance phase, heat sources and cooling fluids must be controlled.

The system must always be earthed. If it is not, this may lead to electrical discharges.

Prior to intervening the refrigeration circuit, it is compulsory to stop the appliance for a few minutes to reduce the compressor and piping temperature, because during normal functioning they may reach temperatures exceeding 100ºC involve the risk of burns.

Any welding intervention is to be perfor-med by qualified welders.

Use the voltage indicated in the manual. Incorrect voltage may cause fires or other problems.

Always use original Saunier Duval spare parts. Do not use components removed from defective refrigeration appliances as replacements.

It is expressly prohibited to carry out any modifications to the refrigeration circuit, the cooling gas type indicated on the characteristics place, likewise application of the appliance outside those application limits appearing in the documentation or any other kind of modification. Any modi-fication will cancel out the EC marking pursuant to the PED (97/23/EC Guideline) and the person who carries out the said modification will be liable for the same.

1- SAFETY REGULATIONS

Installation, maintenance and repair

Page 4: CEILING-FLOOR, CASSETTE AND DUCTS - … · CEILING-FLOOR, CASSETTE AND DUCTS. 2 ENG 3 ENG ... false ceiling to ensure the unit will suit the dis-tance. - Using the installation template

4

ENG

5

ENG

2- DIMENSIONS

MODEL H (mm)

050 EKI 261

065 EKI 263

085 EKI 263

105 EKI 420

130 EKI 420

Units in mm

Model A B C D E F 050 EKI 580 580 521 460 700 700

065 EKI 580 580 521 460 700 700

085 EKI 580 1089 521 995 700 1205

105 EKI 875 875 830 665 950 950

130 EKI 875 875 830 665 950 950

2.1 CEILING-FLOOR INDOOR UNITS (EFI)

2.2 CASSETTE INDOOR UNITS (EKI)

On fitting trim make sure air swing engine is not placed below the cooling pipes.

Units in mm

MODEL A B C D E F Kg

050 EFI 645 955 199 280 185 873 30

065 EFI 645 955 199 280 185 873 30

085 EFI 645 1.250 199 280 185 1.168 40

105 EFI 645 1.750 199 280 185 1.668 56

Page 5: CEILING-FLOOR, CASSETTE AND DUCTS - … · CEILING-FLOOR, CASSETTE AND DUCTS. 2 ENG 3 ENG ... false ceiling to ensure the unit will suit the dis-tance. - Using the installation template

4

ENG

5

ENG

2- DIMENSIONS

Units in mm

Distances in cm

It’s advisable to respect the specified minimum distances around the apparatus.

MODELS A B C D E F G H J K L Kg

050 EDI 1.000 525 240 878 156 940 170 1.040 246 34 100 29

065 EDI 1.000 525 240 878 156 940 180 1.040 260 34 100 29

085 EDI 1.010 666 279 900 196 950 250 1.050 335 34 100 40

105 EDI 1.210 666 279 1.100 196 1.150 250 1.250 335 34 100 47

130 EDI 1.310 700 320 1.100 196 1.250 252 1.350 335 34 60 53

180 EDI 1.400 840 361 1.047 225 1.305 305 1.405 455 34 100 60

2.3 DUCTS INDOOR UNITS (EDI)

Page 6: CEILING-FLOOR, CASSETTE AND DUCTS - … · CEILING-FLOOR, CASSETTE AND DUCTS. 2 ENG 3 ENG ... false ceiling to ensure the unit will suit the dis-tance. - Using the installation template

6

ENG

7

ENG

2- DIMENSIONS

2.4 INDOOR UNITS (EZI)

Units in mm

It’s advisable to respect the specified minimum distances around the apparatus.

Is very important the positioning of a siphon in each water-drainage.

Units in mm

MODELS A C D K L M N O P R S T U Kg.

230 EZI 1.660 650 660 147 364 125 331 600 575 50 38 200 110 111

Page 7: CEILING-FLOOR, CASSETTE AND DUCTS - … · CEILING-FLOOR, CASSETTE AND DUCTS. 2 ENG 3 ENG ... false ceiling to ensure the unit will suit the dis-tance. - Using the installation template

6

ENG

7

ENG

Models 050 / 065

Models 105 / 105T / 130

Model 180

Model 085

180

Liq. 1/2"

Gas 7/8"

Units in mm

Model 120 M2

2- DIMENSIONS

2.5 OUTDOOR UNITS

050 - 065

Liq. 3/8"

Gas 5/8"

085

Liq. 3/8"

Gas 3/4"

A 105 - 105T 130

Liq. 3/8" 1/2"

Gas 3/4" 3/4"

050

065

Page 8: CEILING-FLOOR, CASSETTE AND DUCTS - … · CEILING-FLOOR, CASSETTE AND DUCTS. 2 ENG 3 ENG ... false ceiling to ensure the unit will suit the dis-tance. - Using the installation template

8

ENG

9

ENG

Model 230

Units in mm

Units in mmUnits in mm

230

Liq. 5/8"

Gas 1 1/8"

2- DIMENSIONS

2.5 OUTDOOR UNITS

2.5.1 OUTDOOR UNIT LOCATION

Location for a correct air flow

Page 9: CEILING-FLOOR, CASSETTE AND DUCTS - … · CEILING-FLOOR, CASSETTE AND DUCTS. 2 ENG 3 ENG ... false ceiling to ensure the unit will suit the dis-tance. - Using the installation template

8

ENG

9

ENG

- When the direction are selected, drill 4” (100 mm) dia. hole on the wall so that the hole is tilted downward toward the outdoor for smooth water flow. When the pipe is led out from the rear, make a hole at the posi-tion shown.

3- INDOOR UNIT INSTALLATION

3.1.1 INSTALLATION PROCEDURE

A. PREPARING INDOOR UNIT INSTALLATION

Remove the intake grille and side cover(s) by remo-ving the tapping screws.

B. FLOOR INSTALLATION

B.1 DRILLING FOR PIPING

Select piping and drain direction. The piping and drain can be made in two directions.

- The drain hose can be connected to the drain port either left or right side.

B.2 INSTALLING DRAIN HOSE

Be sure to arrange the drain hose so that it is levelled lower than the drain port of the indoor unit.

When the directions are installed, drill a 3 1/8” (80 mm) or 6” (150 mm) dia. hole on the wall so that the hole is tilted downward toward the outdoor for smooth water flow.

C. CEILING INSTALLATION

Using the distance between drilling holes as shown below, drill holes for piping and anchor bolts.

C.1 DRILLING FOR PIPING

Select piping directions.

- Install the drain hose at the rear, it should not be installed on the top.

3.1 CEILING-FLOOR: INDOOR UNITS

Page 10: CEILING-FLOOR, CASSETTE AND DUCTS - … · CEILING-FLOOR, CASSETTE AND DUCTS. 2 ENG 3 ENG ... false ceiling to ensure the unit will suit the dis-tance. - Using the installation template

10

ENG

11

ENG

C.4 INSTALLING INDOOR UNIT

Reset the bolts as shown below.

Apply the indoor unit to hangers.

C.2 DRILLING HOLES FOR ANCHOR BOLTS AND INSTALLING THE ANCHOR BOLTS

With a concrete drill, drill four 3/8” (9,5 mm) dia. holes.

Insert the anchor bolts into the drilled holes, and drive the pins completely into the anchor bolts with a hammer.

C.3 INSTALLING HANGERS

Install the hangers with nuts and spring was-hers.

Now, securely tighten the bolts in both sides.

C.5 INSTALL THE DRAIN HOSE

Be sure to arrange the drain hose so that its level lower than the drain port of the indoor unit.

Always check that the drain cap is installed to the unused drain port and is fastened with the nylon fastener. If the drain cap is not installed, or is not sufficiently fastened by the nylon fastener, water may drip during the cooling operation.

3- INDOOR UNIT INSTALLATION

Page 11: CEILING-FLOOR, CASSETTE AND DUCTS - … · CEILING-FLOOR, CASSETTE AND DUCTS. 2 ENG 3 ENG ... false ceiling to ensure the unit will suit the dis-tance. - Using the installation template

10

ENG

11

ENG

3- INDOOR UNIT INSTALLATION

3.2.1 INSTALL THE INDOOR UNIT IN A POSI-TION:

- Having sufficient strength to carry the weight of the indoor unit.

- Where the inlet and outlet grilles are not obstruc-ted and the conditioned air is able to blow all over the room.

- From where pipes can be easily run to the outdoor unit.

- From where condensate can be easily run to drain.

- Check the distance between the upper slab and false ceiling to ensure the unit will suit the dis-tance.

- Using the installation template open ceiling panels and install the suspension bolts.

3.2.2 INSTALLATION METHOD

- Ensure the ceiling is horizontally level, otherwise condensate water cannot drain.

- The casing is fixed to the slab with 4 drop rods. The rods should have two nuts and washers to lock the unit in position. The Cassette brackets will then hook over the washers.

- When lifting the Cassette into position care should be taken not to lift the unit by the drip tray, which could be damaged.

3.2 CASSETTE: INDOOR UNIT

- Ensure there is sufficient space around the unit to service it.

- Lift unit (without the air panel) with care by its four corners only. Do not lift unit by the conden-sate drain discharge pipe or by the piping connec-tions.

- Incline unit and insert it into the false ceiling. Insert the rods into the brackets slot.

With false ceilings minimum height (see table), it might be necessary to remove some T brackets of the false ceiling.

Page 12: CEILING-FLOOR, CASSETTE AND DUCTS - … · CEILING-FLOOR, CASSETTE AND DUCTS. 2 ENG 3 ENG ... false ceiling to ensure the unit will suit the dis-tance. - Using the installation template

12

ENG

13

ENG

MODEL A (mm)

050 / 065 EKI 3

085 EKI 3

105 / 130 EKI 83

- We recommend that screened cable be used in electrically noisy areas.

- To avoid electro-magnetic control systeminterfe-rence, always separate (5 VCC) low voltage signal wires from (220 VCA) power line.

- Do not install the unit where electromagnetic waves are directly radiated at the infra red receiver

105 / 130 EKI 050 / 065 / 085 EKI

3.2.3 INTERCONNECTING WIRING

- Using level guide, line up the unit with a spirit level, and keep dimension between the fiber glass body and the lower part of the false cei-ling.

3- INDOOR UNIT INSTALLATION

- Line up the unit to the supporting bars of the false ceiling tightening the nuts and counternuts of the threaded rods.

- After connection of the condensate drain piping and piping connections, check again that the unit is level.

on the unit.- Install the unit and components as far as practical

(at least five metres away from the electromagne-tic wave source).

- Install a noise filter if any harmful noise exists in the power supply.

Page 13: CEILING-FLOOR, CASSETTE AND DUCTS - … · CEILING-FLOOR, CASSETTE AND DUCTS. 2 ENG 3 ENG ... false ceiling to ensure the unit will suit the dis-tance. - Using the installation template

12

ENG

13

ENG

- The side opening allows separate ductwork to be installed for outside air intake and branch ducting.

- Cut and remove anti-condensate insulating mate-rial.

Indoor Unit:

- The unit is fitted with a condensate pump with a

500 mm lift.- The unit is provided with 22 mm bore flexible

hose 300 mm long.- The flexible hose should be fitted into a 22 mm

3.2.5 DRAIN PIPEWORK

3- INDOOR UNIT INSTALLATION

3.2.4 FRESH AIR RENEWAL AND BRANCH DUCTING

- Install your flanges and conduits to casing. Con-duits can be flexible polyester with spring core or corrugated aluminum externally coated (dia.4 in.) with anti-condensate material (fiberglass 12-25 mm thickness).

polyvinyl tube and sealed. The 22 mm drain must be installed with a downward slope.

- On completion the drain line should be insula-ted.

Page 14: CEILING-FLOOR, CASSETTE AND DUCTS - … · CEILING-FLOOR, CASSETTE AND DUCTS. 2 ENG 3 ENG ... false ceiling to ensure the unit will suit the dis-tance. - Using the installation template

14

ENG

15

ENG

3.3.3 INDOOR UNIT INSTALLATION

- Insert and screw down a nut on each supporting rod.

- Lift the indoor unit and insert the rods in the holes provided on the mounting brackets.

- Place a washer and nut on each of the rods.- Level out the machine and fix it tightening so that

nuts are pressed against each other.- It is advisable to place a lock nut against the

lower nut on the suspension rods.- This indoor unit has been originally designed for

installation on false ceilings. Where the unit is to be mounted on a location with easy access, the electric wiring bar must be protected to prevent hazardous situations.

3.3.4 DRAIN PIPE INSTALLATION

- Special care should be taken when laying drain tubing, otherwise if any problem occurs the con-densed water of the evaporator could spill.

- Do not place the drain pipe in an upwards posi-tion otherwise drain water would go back to the unit and spill when the unit would stop.

- Do not connect the drain pipe to the sanitary drains, waste water drains or any other drain facility if a trap is not installed.

- When a common drain pipe is connected to other indoor units, connection positions of each unit should be at a higher level than the common pipe. The common pipe length should be appro-priate for the size and number of existing units.

3.3.5 SUSPENSION OF THE INDOOR UNIT

Hang up the indoor unit as shown in the figure below.Parts supplied by the filter:- Suspension Rod, Nut and Washer

3.3.1 INITIAL CHECK

- Install indoor unit allowing for enough clearance around the unit so there is room for handling and maintenance operations as shown below.

- Avoid any obstacles that could impair air take-up or discharge flow.

- Do not install the indoor unit in a machinery workshop or in a kitchen where oil or smoke mist could flow into the indoor unit. Oil would be deposited in the heat exchanger resulting in a reduced unit performance. Also, internal plastic parts could be deformed or they could even break as a result.

- Note the following items when the indoor unit is to be installed in a hospital or premises where electromagnetic waves from medical equipment may be present.

A) Do not install the indoor unit where electromag-netic waves directly impinge on the electric box, the remote control switch or the remote control cable.

B) Install the unit as far as possible from the elec-tromagnetic wave source. A 3 metre clearance should be arranged.

C) Install a noise filter when the power supply pro-duces disturbing noises.

D) Select final location and direction of the indoor unit paying special attention to tubes, cables and maintenance.

E) When selecting the indoor unit location, the air ducting network should be borne in mind in order to facilitate distribution.

3.3.2 FIXING THE UNIT

- Use the appropriate fasteners for each structure type paying special attention to any possible transmission of vibrations and noise. Noise or vibration proof items should be provided if it is considered to be necessary.

NOTE:Is very important the positio-ning of a siphon in each water-drainage.

400

200

500

3- INDOOR UNIT INSTALLATION

3.3 DUCTS: INDOOR UNIT

Page 15: CEILING-FLOOR, CASSETTE AND DUCTS - … · CEILING-FLOOR, CASSETTE AND DUCTS. 2 ENG 3 ENG ... false ceiling to ensure the unit will suit the dis-tance. - Using the installation template

14

ENG

15

ENG

4.2 PIPE CONNECTION

4.1. OUTDOOR UNIT

- Install de outdoor unit in a place where it will be free from being dirty or getting by rain as much as possible.

- During heating operation, drain water flows from the outdoor unit. Therefore, install the outdoor unit in a place where the drain water flow will not be obstructed. (Heat pump model only).

- Do not place animals and plants in the path of the warm air.

- Take the air conditioner weight into account and select a place where noise and vibration are less.

- Select a place so that the warm air and noise from the air conditioner do not disturb neigh-bours.

- Provide the space so that the air flow is not bloc-ked. Also for efficient operation, leave open three or the four directions front, rear and both sides.

Type A height: Outdoor Unit above Indoor Unit.Type B height: Outdoor Unit below Indoor Unit.(1) Auxiliary siphons every 7 m.NOTE:In vertical layouts always place an oil trap (small siphon) at the beginning of the vertical stretch. In the case of the heat pump and with the outdoor unit below the indoor unit place siphons every 7 m.

4.2.1 INSTALLATION DETAILS

4- OUTDOOR UNIT INSTALLATION

PIPE DETAILS

- When the outdoor unit will be exposed to strong wind, fasten it with bolts at the places indicated by the arrows.

- When installing the drain pipe, plug another hole () in the bottom of the outdoor unit with drain cap so there is no water leakage.

Page 16: CEILING-FLOOR, CASSETTE AND DUCTS - … · CEILING-FLOOR, CASSETTE AND DUCTS. 2 ENG 3 ENG ... false ceiling to ensure the unit will suit the dis-tance. - Using the installation template

16

ENG

17

ENG

Option

4.3 PIPE LENGTH

ORIGIN DISTANCE IN LINEALS m. Models Load R-407C (kg) Lines (‘‘) 15 m (4 curves) 20 m (6 curves) 30 m (8 curves) 50 m (6 curves) Max. Height (m)

Cool Heat Gas Liq. % Aprox. R-407C Oil % Aprox. R-407C Oil % Aprox. R-407C Oil % Aprox. R-407C Oil Over Under (g) (g) (g) (g) (g) (g) (g) (g) IU IU

050

1,7 2,0 5/8” 3/8” 99 250 --- 98 400 --- 96 800 20 92 1.500 50

45 20 --- --- --- --- --- --- --- --- --- --- --- --- --- ---

065

1,6 1,9 5/8” 3/8” 98 250 --- 96 400 --- 92 800 --- 87 1.500 50

45 20 3/4” 3/8” 100 300 --- 99 500 --- 97 800 20 94 1.500 50

085

2,3 2,6 3/4” 3/8” 100 300 --- 97 500 --- 94 800 20 89 1.500 50

45 20 7/8” 3/8” 102 300 --- 101 500 --- 99 900 20 96 1.600 50

105

2,8 3,55 3/4” 3/8” 97 300 --- 95 500 --- 92 800 20 85 1.500 50

45 20 7/8” 3/8” 101 300 --- 100 500 --- 98 900 20 94 1.600 50

105T 2,8 3,55

3/4” 3/8” 97 300 --- 95 500 --- 91 800 20 85 1.500 50 45 20

7/8” 3/8” 101 300 --- 100 500 --- 98 900 20 94 1.600 50

130

3,8 4,2 3/4” 1/2” 96 500 --- 93 850 20 88 1.500 50 80 2.800 100

45 20 7/8” 1/2” 102 500 --- 100 900 20 97 1.500 50 91 2.900 100

180*

-- 6,0 7/8” 1/2” 96 900 --- 93 1.500 20 88 2.700 50 80 5.100 100

45 20 7/8” 1/2” 102 900 --- 100 1.500 20 97 2.700 50 91 5.100 100

230*

-- 8,4 1-1/8” 5/8”(1) 97 1.500 --- 95 2.500 --- 92 4.500 50 87 8.500 100

45 20 1-3/8” 5/8”(1) 102 1.800 --- 101 3.000 --- 99 5.400 50 97 10.200 100

(1) It isn’t necessary to isolate this line of liquid.

(* Without loading, value for 7.5 m. Model 180: 120 g/m; Model 230: 200 g/m)

4- OUTDOOR UNIT INSTALLATION

Page 17: CEILING-FLOOR, CASSETTE AND DUCTS - … · CEILING-FLOOR, CASSETTE AND DUCTS. 2 ENG 3 ENG ... false ceiling to ensure the unit will suit the dis-tance. - Using the installation template

16

ENG

17

ENG

4.7 POWER

(1) The rate voltage of this product is monophase (230V/1Ph/50 Hz) or triphase (400V/3Ph/50Hz).

(2) Perform wiring work in accordance with stan-dards so that the room air conditioner can be operated safely and positively.

4.8 ELECTRICAL WIRING

(1) Connect the connection cords fi rmly to the terminal block. Imperfect installation may cause a fire.

(2) If the indoor unit connection cord (to the outdoor unit) and power supply are wired inco-rrectly, the air conditioner may be damaged.

(3) Always connect the ground wire.

4.9 MAINTENANCE INSTRUCTIONS

- Never add oil to the appliance; the compressor is filled with polyaldohol oil, a special oil which cannot tolerate the presence of other oils.

- The instruments used for filling, pressure measu-rements, emptying under vacuum and recovering the fluid, must be compatible and only used for the R-407C fluid.

- The weight of the refrigerant contained in the storage bottle must be checked constantly. Do not use it from the moment the remaining weight is less than 10% of the total weight.

- In the case of a new charge do not use the char-ging cylinder, use a balance and a dip pipe type R-407C cylinder, charge the weight of R-407C as per the value indicated on the unit’s identification plate (for “split systems”, refer to the installation instructions as the charge must consider the length of the connecting lines).

- The charge must be undertaken in liquid phase.- In the case of leakage, do not complete the

charge: recover the remaining refrigerant or recycling and perform a total charge. Recovery, recycling or the destruction of the fluid must be done in compliance with the laws in force in the country concerned.

- If the refrigerant circuit is opened, you must avoid the entry of air into the circuit as much as possible, replace the filter drier and perform the “vacuum operation” at a minimum level of 3.0 mbar (static).

4- OUTDOOR UNIT INSTALLATION

4.5 HEAT INSULATION ON THE PIPE JOINTS

- Put coupler heat insulator on the joints.

AIR PURGE

- Check if the piping connections are secure.- Check that the stems of both 3- way valves are

closed fully.- Operate the vacuum pump and start pump

down.- Pump down the system for at least 15 minutes,

then check if the compound pressure gauge reads - 100kPa (- 76 cm Hg, -1bar)

- At the end of pump down, close the low pressure side gauge of the gauge manifold fully and stop the vacuum pump.

- Slowly loosen the valve stem of the 3- way valve.

- Firmly tighten both 3- way valves blank cap and the charging port cap.

4.4 CHECKING THE PIPE CONNECTIONS FOR GAS LEAKING

- For both the indoor and outdoor unit sides, check the joints for gas leaking by the use of a gas leakage detector without fail when the pipes are connected.

ADDITIONAL CHARGE

- Refrigerant suitable for a piping length of 10 m. is charged in the indoor unit at the factory.

- When the piping is longer than 10 m., additional charging is necessary.

4.6 GAS LEAKAGE INSPECTION

WARNING!- After connecting the piping, check the joints for gas leakage with gas leak detector.

Page 18: CEILING-FLOOR, CASSETTE AND DUCTS - … · CEILING-FLOOR, CASSETTE AND DUCTS. 2 ENG 3 ENG ... false ceiling to ensure the unit will suit the dis-tance. - Using the installation template

18

ENG

19

ENG

5- WIRING DIAGRAMS

* Don’t forget the earth connection

Riht section mm2 MODELS Power Supply* Up to 25 m. Magnetothermique Differential

(V/Ph/Hz) Manoeuvre Force Type D 1Δn

050 230/1/50 1,5 1,5 10 A 0,03 A

065 230/1/50 1,5 2,5 20 A 0,03 A

085 230/1/50 1,5 4,0 25 A 0,03 A

105 230/1/50 1,5 4,0 32 A 0,03 A

105T 400/3/50 1,5 2,5 16 A 0,03 A

130 400/3/50 1,5 2,5 20 A 0,03 A

180 400/3/50 1,5 4,0 25 A 0,03 A

230 400/3/50 1,5 4,0 32 A 0,03 A

120 M2 230/1/50 1,5 4,0 32 A 0,03 A

050 / 065 / 085 / 105 105T / 130 / 180

230 120 M2

Page 19: CEILING-FLOOR, CASSETTE AND DUCTS - … · CEILING-FLOOR, CASSETTE AND DUCTS. 2 ENG 3 ENG ... false ceiling to ensure the unit will suit the dis-tance. - Using the installation template

18

ENG

19

ENG

The installation of electric assault to the machine should have a Bipolar or Tetrapolar switch according to machine model, (monophase or treephase), of at least 3 mm of separation among contacts (norm EN-60335-2-40).

To ensure that this appliance complies with EN-61000-3-11 standard verify that the service current supply capacity is >100A at the interface point.

PAD WIRING DIAGRAM

THREE WIRES

Heat Pump Option

Cooling Only Option

Dry Auto Cool Heat FanHour

Prog.

Dry Cool FanHour

Prog.

5- WIRING DIAGRAMS

Connection

Thread

Black Thread

Red Thread

White Thread

ThreadYellow Thread

Black Thread

Red Thread

White Thread

THREE WIRES

FOUR WIRES

FOUR WIRES

Page 20: CEILING-FLOOR, CASSETTE AND DUCTS - … · CEILING-FLOOR, CASSETTE AND DUCTS. 2 ENG 3 ENG ... false ceiling to ensure the unit will suit the dis-tance. - Using the installation template

20

ENG

21

ENG

6- CONTROL UNITS DIAGRAMS

6.1 CEILING-FLOOR INDOOR UNITS

HTR Heater Relay AS Deflector Relay CN4 ON-OFF Switch Conn. 4WV 4-Way Valve Relay M-L-H Fan Relay TFULL Inner Jumper Float ODH Outdoor Unit Fan Relay COMP Compressor Relay ROOM Room Temp. Sensor WTP Condensation Pump Relay F1 Fuse ID I. Unit Coil Sensor CN1 Louver Connector CN6 Receiver Connector OD O. Unit Coil Sensor

6.2 CASSETTE INDOOR UNITS

Page 21: CEILING-FLOOR, CASSETTE AND DUCTS - … · CEILING-FLOOR, CASSETTE AND DUCTS. 2 ENG 3 ENG ... false ceiling to ensure the unit will suit the dis-tance. - Using the installation template

20

ENG

21

ENG

HTR Heater Relay AS Deflector Relay CN4 ON-OFF Switch Conn. 4WV 4-Way Valve Relay M-L-H Fan Relay TFULL Inner Jumper Float ODH Outdoor Unit Fan Relay COMP Compressor Relay ROOM Room Temp. Sensor WTP Condensation Pump Relay F1 Fuse ID I. Unit Coil Sensor CN1 Louver Connector CN6 Receiver Connector OD O. Unit Coil Sensor

6.3 DUCTS INDOOR UNITS

HTR Heater Relay AS Deflector Relay CN4 ON-OFF Switch Conn. 4WV 4-Way Valve Relay M-L-H Fan Relay TFULL Inner Jumper Float ODH Outdoor Unit Fan Relay COMP Compressor Relay ROOM Room Temp. Sensor WTP Condensation Pump Relay F1 Fuse ID I. Unit Coil Sensor CN1 Louver Connector CN6 Receiver Connector OD O. Unit Coil Sensor

6- CONTROL UNITS DIAGRAMS

6.4 OUTDOOR UNIT (EXCEPT 085 ECO/EHO UNITS)

Page 22: CEILING-FLOOR, CASSETTE AND DUCTS - … · CEILING-FLOOR, CASSETTE AND DUCTS. 2 ENG 3 ENG ... false ceiling to ensure the unit will suit the dis-tance. - Using the installation template

22

ENG

6- CONTROL UNITS DIAGRAMS

+

R S T

Com

p.

V.4

.V. I

N

Pot

. Ven

t..

Pre

sost

ato

V.4

.V. O

UT

Sol

enoi

de

Bob

ina

FAN

230 w

Sen

sor

Pre

sión

de A

spira

ción

L N L N G

L L L L L LCON1

CON2 CON3

TE

RM

OS

TA

TO

(C

ompr

esor

)

V4V

IN

Pot

. VE

NT

.

PRESOSTATO

V4V

OU

T

SO

LEN

.

BO

BIN

A (

Com

pres

or)

L N G

VDR2

VDR1

ICO

C4

L7

C7

C5LED1

R10

R7

L2

TRC1

R15

TRC3TRC2TRC1

R11

R14R13R12

N7N1

RSST

R6R5R4R3

+ -

S S

PRESOS.TERMOS. V.4.V.

+ + + + +LED2 LED3 LED4 LED5

CON4

IC7 IC8 IC9 IC10IC4IC3

TEST

DB1

DB2

R25R24BOBINA

FANLED8LED6 LED7

SOLEN.V.4.V. OUTC11

RA1

+

+ + +

R23

+

R27

R28

+-

S

S

+-

S

SDB3

CON5

C14

C10

C9 C13C12

C18

C15REG1 R22 C16

C17

5VSeñ

al

0V

JP1

LED10

XTAI1

R17

R21

R20

+

NT

C a

spira

ción

NT

C a

mbi

ente

ext

erio

r

Pre

sión

0VSeñ

al

5V

NT

C d

eses

carc

he

Klix

on

230 w

230 w

6.5 OUTDOOR UNITS (085 ECO/EHO)

9002

439

/ V03