Cat.8 Field Testing “The certification of new Cat.8 installations in the field is a reality” BICSI Europe / Cat.8 Field Testing Rome / 2017.10 (C) FlukeNetworks 1 Christian Schillab EMEA Marketing Engineer / FlukeNetworks [email protected]

Upload: others

Post on 04-Jul-2020

2 views

Category:

Documents


1 download

TRANSCRIPT

Page 1: Cat.8 Field Testing - Cabling & Wireless · 2017-11-10 · Agenda BICSI Europe / Cat.8 Field Testing Rome / 2017.10 (C) FlukeNetworks 2 Cat.8 / Class I and II overview Basic Test

Cat.8 Field Testing “The certification of new Cat.8 installations

in the field is a reality”

BICSI Europe / Cat.8 Field Testing Rome / 2017.10 (C) FlukeNetworks 1

Christian Schillab EMEA Marketing Engineer /

FlukeNetworks [email protected]

Page 2: Cat.8 Field Testing - Cabling & Wireless · 2017-11-10 · Agenda BICSI Europe / Cat.8 Field Testing Rome / 2017.10 (C) FlukeNetworks 2 Cat.8 / Class I and II overview Basic Test

Agenda

BICSI Europe / Cat.8 Field Testing Rome / 2017.10 (C) FlukeNetworks 2

Cat.8 / Class I and II overview

Basic Test Regime & Test Interfaces

What makes RJ work at high frequencies

Component testing in the lab

Field Testing Requirements

Extended Test Regimes

Performance of Cat.8 samples

Page 3: Cat.8 Field Testing - Cabling & Wireless · 2017-11-10 · Agenda BICSI Europe / Cat.8 Field Testing Rome / 2017.10 (C) FlukeNetworks 2 Cat.8 / Class I and II overview Basic Test

3

Which Cat.8 ?

TIA ISO 11801

Channel / Perm. Link Cat.8 Class I (DRAFT) Class II (DRAFT)

Max. Frequency 2000 MHz

Components Cat.8 Cat.8.1 Cat.8.2

Extrapolated from Cat.6A (equivalent) Class EA Class FA

Style RJ45 Non-RJ45 (TERA, GG45,

ARJ45,….)

Field Test Standard TIA 1152a IEC 61935-1 Ed.5 (DRAFT)

… Accuracy Level 2G Level VI for Cl.I Level VI for Cl.II

BICSI Europe / Cat.8 Field Testing Rome / 2017.10 (C) FlukeNetworks

Page 4: Cat.8 Field Testing - Cabling & Wireless · 2017-11-10 · Agenda BICSI Europe / Cat.8 Field Testing Rome / 2017.10 (C) FlukeNetworks 2 Cat.8 / Class I and II overview Basic Test

Step 1A: Basic (Minimum) Test Regime

BASIC Tests

EXT. Tests

no

yes

Trouble Shoot

EXTENDED Tests

Create ProjX ™

Monitor & Document

…Optional / Conditional Testing

BICSI Europe / Cat.8 Field Testing Rome / 2017.10 (C) FlukeNetworks 4

Page 5: Cat.8 Field Testing - Cabling & Wireless · 2017-11-10 · Agenda BICSI Europe / Cat.8 Field Testing Rome / 2017.10 (C) FlukeNetworks 2 Cat.8 / Class I and II overview Basic Test

Test Interfaces & Reference Planes

Application

LINK

CHANNEL

BICSI Europe / Cat.8 Field Testing Rome / 2017.10 (C) FlukeNetworks 5

Page 6: Cat.8 Field Testing - Cabling & Wireless · 2017-11-10 · Agenda BICSI Europe / Cat.8 Field Testing Rome / 2017.10 (C) FlukeNetworks 2 Cat.8 / Class I and II overview Basic Test

6 BICSI Europe / Cat.8 Field Testing Rome / 2017.10 (C) FlukeNetworks

Cable 97%

1000MHz

Cable 42% Connector

58%

1000MHz

What Limits The Bandwidth more … Connectors or Cable ?

Example: 30m Link

• IL (Insertion Loss)

• NEXT (Near End Crosstalk)

CHANNEL

Cable 56%

Connector 44%

500Mhz

Cable 69%

Connector 31%

100MHz

Cable 97%

100MHz

Cable 97%

500Mhz

Page 7: Cat.8 Field Testing - Cabling & Wireless · 2017-11-10 · Agenda BICSI Europe / Cat.8 Field Testing Rome / 2017.10 (C) FlukeNetworks 2 Cat.8 / Class I and II overview Basic Test

What makes a Cat.5e, -.6, -.6A, .-8.1 Connector work ?

Note: Above is shown for the most critical pair 3,6/4,5 at 100MHz

NEXT: 37dB …14mV

Cat.6, Cat.6A, Cat.8.1 …“Mated NEXT” > 54dB … < 1.9mV

BICSI Europe / Cat.8 Field Testing Rome / 2017.10 (C) FlukeNetworks 7

Page 8: Cat.8 Field Testing - Cabling & Wireless · 2017-11-10 · Agenda BICSI Europe / Cat.8 Field Testing Rome / 2017.10 (C) FlukeNetworks 2 Cat.8 / Class I and II overview Basic Test

8 BICSI Europe / Cat.8 Field Testing Rome / 2017.10 (C) FlukeNetworks

Let‘s assume the plug is …

Cat.6, Cat.6A, Cat.8.1 …“Mated NEXT” > 54 dB … < 1.9mV

… “worse” … “better”

The jack „under compensates“ because the plug is to “LOW”

The jack „over compensates“ because the plug is to “HIGH”

Page 9: Cat.8 Field Testing - Cabling & Wireless · 2017-11-10 · Agenda BICSI Europe / Cat.8 Field Testing Rome / 2017.10 (C) FlukeNetworks 2 Cat.8 / Class I and II overview Basic Test

9 BICSI Europe / Cat.8 Field Testing Rome / 2017.10 (C) FlukeNetworks

Plug / Jack NEXT Compensation at 2GHz is not trivial

Cat.6/6A Cat.8.1

Good performance rquires that the plug and jack NEXT are in perfect balance.

Page 10: Cat.8 Field Testing - Cabling & Wireless · 2017-11-10 · Agenda BICSI Europe / Cat.8 Field Testing Rome / 2017.10 (C) FlukeNetworks 2 Cat.8 / Class I and II overview Basic Test

Back in 2002: Many Plugs, Many Pyramids ….

10 BICSI Europe / Cat.8 Field Testing Rome / 2017.10 (C) FlukeNetworks

Multiple plugs used to test jacks for Cat.6 compliance Included High, Low and

Centered Plugs

Up to 12 plugs used

Finding 3 meeting all requirements would be like getting all right in a lottery

The jack had to demonstrate compliant “Mated Next” in all 12 cases

Low Center High

Page 11: Cat.8 Field Testing - Cabling & Wireless · 2017-11-10 · Agenda BICSI Europe / Cat.8 Field Testing Rome / 2017.10 (C) FlukeNetworks 2 Cat.8 / Class I and II overview Basic Test

“New” in 2006: One Centered Plug & Mathematics

A single plug can be used to test for compliance in 14 cases

– Instead of 12 actual plug

“Leaded” or PCB based test plugs may be used

Most of the time a PCB based plug is preferred … off the shelf

…stable

…convenient

…proven in “round robins”

BICSI Europe / Cat.8 Field Testing Rome / 2017.10 (C) FlukeNetworks

Page 12: Cat.8 Field Testing - Cabling & Wireless · 2017-11-10 · Agenda BICSI Europe / Cat.8 Field Testing Rome / 2017.10 (C) FlukeNetworks 2 Cat.8 / Class I and II overview Basic Test

Cat.8.1: Combined Laboratory & Field Test Concept

… Auxiliary Tools

12

Requires adapters and artifacts for the proprietary test plug interface in order

1. … Neutralize the effect of the test plug interface

2. … Verify the compliance of the test plug

BICSI Europe / Cat.8 Field Testing Rome / 2017.10 (C) FlukeNetworks

Page 13: Cat.8 Field Testing - Cabling & Wireless · 2017-11-10 · Agenda BICSI Europe / Cat.8 Field Testing Rome / 2017.10 (C) FlukeNetworks 2 Cat.8 / Class I and II overview Basic Test

How simple was Cat.6A in comparison! Cat.8.1 Action photos from the lab

13

BICSI Europe / Cat.8 Field Testing Rome / 2017.10 (C) FlukeNetworks

Page 14: Cat.8 Field Testing - Cabling & Wireless · 2017-11-10 · Agenda BICSI Europe / Cat.8 Field Testing Rome / 2017.10 (C) FlukeNetworks 2 Cat.8 / Class I and II overview Basic Test

14 BICSI Europe / Cat.8 Field Testing Rome / 2017.10 (C) FlukeNetworks

Requirements for Feld Testers

• ISO/IEC 61935-1 Ed.5 (CD): Specification for

the testing of balanced and coaxial information technology cabling – Part 1: Installed balanced cabling as specified in ISO/IEC 11801 and related standards

• ANSI/TIA-1152A: Requirements for Field Test

Instruments and Measurements for Balanced Twisted- Pair Cabling

+

Class D E EA F FA I II

Level IIe III IIIe IV V VI (Cl.I) VI (Cl.II)

Cat. 5e 6 6A 8

Level IIe III IIIe 2G

Page 15: Cat.8 Field Testing - Cabling & Wireless · 2017-11-10 · Agenda BICSI Europe / Cat.8 Field Testing Rome / 2017.10 (C) FlukeNetworks 2 Cat.8 / Class I and II overview Basic Test

Question #1: “In a Cat.6A project should I demand Level-IIIe or prefer Level-IV or better?”

Answer: Aboluetely NO ! Level IV/V is in this case without Relevance Afuture Level VI (für Class I) would be relevant.

15

Level IIe III IIIe VI (Cl.I)

Level IV V VI (Cl.II)

Level IV V VI (Cl.II)

Cat. 5e 6 6A 7 7A 8.1 8.2

BICSI Europe / Cat.8 Field Testing Rome / 2017.10 (C) FlukeNetworks

Page 16: Cat.8 Field Testing - Cabling & Wireless · 2017-11-10 · Agenda BICSI Europe / Cat.8 Field Testing Rome / 2017.10 (C) FlukeNetworks 2 Cat.8 / Class I and II overview Basic Test

Comparing PERMANENT LINK Results

16 16 BICSI Europe / Cat.8 Field Testing Rome / 2017.10 (C) FlukeNetworks

Page 17: Cat.8 Field Testing - Cabling & Wireless · 2017-11-10 · Agenda BICSI Europe / Cat.8 Field Testing Rome / 2017.10 (C) FlukeNetworks 2 Cat.8 / Class I and II overview Basic Test

A combined Field & Lab Tester Concept for Cat.8.1….

17 17

Test Plug “Centered Plug”

Test Plug

Interface (proprietary)

Test Plug

Adapter

Definition of the key elements

BICSI Europe / Cat.8 Field Testing Rome / 2017.10 (C) FlukeNetworks

Page 18: Cat.8 Field Testing - Cabling & Wireless · 2017-11-10 · Agenda BICSI Europe / Cat.8 Field Testing Rome / 2017.10 (C) FlukeNetworks 2 Cat.8 / Class I and II overview Basic Test

Permanent Link Adapter with a “CENTERED” Test Plug for the „Heavy Duty Field Use“

Test Plug “Centered Plug”

Test Plug

Interface (proprietary)

Test Plug

Adapter

Consumable

BICSI Europe / Cat.8 Field Testing Rome / 2017.10 (C) FlukeNetworks 18

Page 19: Cat.8 Field Testing - Cabling & Wireless · 2017-11-10 · Agenda BICSI Europe / Cat.8 Field Testing Rome / 2017.10 (C) FlukeNetworks 2 Cat.8 / Class I and II overview Basic Test

Question #2: Does ANSI/TIA define a more accurate tester than ISO/IEC ?

19 BICSI Europe / Cat.8 Field Testing Rome / 2017.10 (C) FlukeNetworks

2.3 4.6

Page 20: Cat.8 Field Testing - Cabling & Wireless · 2017-11-10 · Agenda BICSI Europe / Cat.8 Field Testing Rome / 2017.10 (C) FlukeNetworks 2 Cat.8 / Class I and II overview Basic Test

20 BICSI Europe / Cat.8 Field Testing Rome / 2017.10 (C) FlukeNetworks

Status Cat.8 : Field Tester Requirements

• ISO/IEC 61935-1 : Specification for the testing of balanced and coaxial information technology cabling – Part 1: Installed balanced cabling as specified in ISO/IEC 11801 and related standards Committe Draft

ANSI/TIA-1152: Requirements for Field Test Instruments and Measurements for Balanced Twisted- Pair Cabling PUBLISHED

Page 21: Cat.8 Field Testing - Cabling & Wireless · 2017-11-10 · Agenda BICSI Europe / Cat.8 Field Testing Rome / 2017.10 (C) FlukeNetworks 2 Cat.8 / Class I and II overview Basic Test

Step 1B: Extended Test Regime

EXT. Tests

no

yes

Trouble Shoot

Create ProjX ™

Monitor & Document

…Optional / Conditional Testing

BASIC Tests

EXTENDED Tests

BICSI Europe / Cat.8 Field Testing Rome / 2017.10 (C) FlukeNetworks 21

Page 22: Cat.8 Field Testing - Cabling & Wireless · 2017-11-10 · Agenda BICSI Europe / Cat.8 Field Testing Rome / 2017.10 (C) FlukeNetworks 2 Cat.8 / Class I and II overview Basic Test

Why EXTENDED Testing ?

BICSI Europe / Cat.8 Field Testing Rome / 2017.10 (C) FlukeNetworks 22

Page 23: Cat.8 Field Testing - Cabling & Wireless · 2017-11-10 · Agenda BICSI Europe / Cat.8 Field Testing Rome / 2017.10 (C) FlukeNetworks 2 Cat.8 / Class I and II overview Basic Test

Why EXTENDED Testing ?

BICSI Europe / Cat.8 Field Testing Rome / 2017.10 (C) FlukeNetworks 23

Page 24: Cat.8 Field Testing - Cabling & Wireless · 2017-11-10 · Agenda BICSI Europe / Cat.8 Field Testing Rome / 2017.10 (C) FlukeNetworks 2 Cat.8 / Class I and II overview Basic Test

WHAT IF …

TCL / ELTCTL is not compliant ?

BICSI Europe / Cat.8 Field Testing Rome / 2017.10 (C) FlukeNetworks 24

Page 25: Cat.8 Field Testing - Cabling & Wireless · 2017-11-10 · Agenda BICSI Europe / Cat.8 Field Testing Rome / 2017.10 (C) FlukeNetworks 2 Cat.8 / Class I and II overview Basic Test

• Transverse Conversion Loss is the ratio (in dB) of a common-mode voltage measured on a wire pair relative to a differential-mode voltage applied to the same end of the pair. The TCL value shows you how well the impedances of the pair’s conductors are balanced.

TCL (Transverse Conversion Loss)

Differential Signal Applied

Common Mode Voltage Measured

BICSI Europe / Cat.8 Field Testing Rome / 2017.10 (C) FlukeNetworks 25

Page 26: Cat.8 Field Testing - Cabling & Wireless · 2017-11-10 · Agenda BICSI Europe / Cat.8 Field Testing Rome / 2017.10 (C) FlukeNetworks 2 Cat.8 / Class I and II overview Basic Test

• 18km cable of identical type was installed

• 30% of the links don’t carry 1000BASE-T

Mode Conversion – Real World Example GOOD vs. BAD Drum of Cable

Drum #1 Drum #2

BICSI Europe / Cat.8 Field Testing Rome / 2017.10 (C) FlukeNetworks 26

Page 27: Cat.8 Field Testing - Cabling & Wireless · 2017-11-10 · Agenda BICSI Europe / Cat.8 Field Testing Rome / 2017.10 (C) FlukeNetworks 2 Cat.8 / Class I and II overview Basic Test

WHAT IF …

TCL / ELTCTL is not compliant

Even a legacy application like 1000Base-T may not work on an otherwise compliant Cat.6/6A system !

Resistive Unbalance is not compliant

Shield Integrity is not given

?

BICSI Europe / Cat.8 Field Testing Rome / 2017.10 (C) FlukeNetworks 27

Page 28: Cat.8 Field Testing - Cabling & Wireless · 2017-11-10 · Agenda BICSI Europe / Cat.8 Field Testing Rome / 2017.10 (C) FlukeNetworks 2 Cat.8 / Class I and II overview Basic Test

• Difference in Resistance between wires in the pair

• Example:

Resistance Unbalance

1.87 Ω

1.85 Ω

Resistance= 3.7 Ω Resistance Unbalance = 0.02 Ω

BICSI Europe / Cat.8 Field Testing Rome / 2017.10 (C) FlukeNetworks 28

Page 29: Cat.8 Field Testing - Cabling & Wireless · 2017-11-10 · Agenda BICSI Europe / Cat.8 Field Testing Rome / 2017.10 (C) FlukeNetworks 2 Cat.8 / Class I and II overview Basic Test

WHAT IF …

TCL / ELTCTL is not compliant

Even a legacy application like 1000Base-T may not work on an otherwise compliant Cat.6/6A system !

Resistive Unbalance is not compliant

Shield Integrity is not given ?

POE operation is at risk during maximum load Poor contacts may further degrade over time

BICSI Europe / Cat.8 Field Testing Rome / 2017.10 (C) FlukeNetworks 29

Page 30: Cat.8 Field Testing - Cabling & Wireless · 2017-11-10 · Agenda BICSI Europe / Cat.8 Field Testing Rome / 2017.10 (C) FlukeNetworks 2 Cat.8 / Class I and II overview Basic Test

Shield Integrity … Opinions

Even when the shield is open at the both ends the requiremens for 10GBASE-T are met

Opinion B: Opinion A:

Requirements for 10GBASE-T are not met if

the shield is open (floating)

1.) Experiments prove it (both

opinions)

2.) The EMI gets significantly worse

BICSI Europe / Cat.8 Field Testing Rome / 2017.10 (C) FlukeNetworks 30

Page 31: Cat.8 Field Testing - Cabling & Wireless · 2017-11-10 · Agenda BICSI Europe / Cat.8 Field Testing Rome / 2017.10 (C) FlukeNetworks 2 Cat.8 / Class I and II overview Basic Test

In The Past:

• Field testers could only verify that there is DC Continuity

• DC Continuity is given by grounding and earth

• Any open shields/ends could not be detected

Shield Integrity

BICSI Europe / Cat.8 Field Testing Rome / 2017.10 (C) FlukeNetworks 31

Page 32: Cat.8 Field Testing - Cabling & Wireless · 2017-11-10 · Agenda BICSI Europe / Cat.8 Field Testing Rome / 2017.10 (C) FlukeNetworks 2 Cat.8 / Class I and II overview Basic Test

Does your field tester verify the shield ? Use a UTP Cable and shielded jacks to find out

Tester 1 Tester 2

Tester 3

Tester 4 • Only 1 tester will detect the lack of a shield

• NOTE: In special applications it may be essential to verify that the shield is open on a defined end

BICSI Europe / Cat.8 Field Testing Rome / 2017.10 (C) FlukeNetworks 32

Page 33: Cat.8 Field Testing - Cabling & Wireless · 2017-11-10 · Agenda BICSI Europe / Cat.8 Field Testing Rome / 2017.10 (C) FlukeNetworks 2 Cat.8 / Class I and II overview Basic Test

Field tester – Shield Test Requirements

Published TIA 1152A states: …for level 2G testers, it is understood that the screen continuity is tested along the path of the cabling.

33 BICSI Europe / Cat.8 Field Testing Rome / 2017.10 (C) FlukeNetworks

-80

-75

-70

-65

-60

-55

-50

-45

-40

0 500 1000 1500 2000

PSA

NEX

T (d

B)

Frequency (MHz)

11801-1 PSANEXT

EA

FA

Class I

For Class EA, where the alien crosstalk requirements are based on UTP cabling, this may not be of concern, however Class I/II alien crosstalk requirements are 10dB tighter than FA and need the screen to be well terminated to ensure compliance.

Page 34: Cat.8 Field Testing - Cabling & Wireless · 2017-11-10 · Agenda BICSI Europe / Cat.8 Field Testing Rome / 2017.10 (C) FlukeNetworks 2 Cat.8 / Class I and II overview Basic Test

Results of poor shield termination

It is important to check that the shield has continuity along the path of the cable – here the Disturbed cable has its shield open on one end

34 BICSI Europe / Cat.8 Field Testing Rome / 2017.10 (C) FlukeNetworks

Schirm korrekt aufgeschaltet

Schirm schlecht aufgeschaltet

Page 35: Cat.8 Field Testing - Cabling & Wireless · 2017-11-10 · Agenda BICSI Europe / Cat.8 Field Testing Rome / 2017.10 (C) FlukeNetworks 2 Cat.8 / Class I and II overview Basic Test

WHAT IF …

TCL / ELTCTL is not compliant

Even a legacy application like 1000Base-T may not work on an otherwise compliant Cat.6/6A system !

Resistive Unbalance is not compliant

POE operation is at risk during maximum load Poor contacts may further degrade over time

Shield Integrity is not given

10 or 20 dB of electromagnetic immunity (EMI) is lost. Alien Crosstalk may become non-compliant

BICSI Europe / Cat.8 Field Testing Rome / 2017.10 (C) FlukeNetworks 35

Page 36: Cat.8 Field Testing - Cabling & Wireless · 2017-11-10 · Agenda BICSI Europe / Cat.8 Field Testing Rome / 2017.10 (C) FlukeNetworks 2 Cat.8 / Class I and II overview Basic Test

Standards Compliant Cat.8 Field Testing…

Standards defined requirements for field testers

Manufacturer endorsed Cat.8 Field Testers

Testing Cat.8 links is no more complex the Cat.6A

BICSI Europe / Cat.8 Field Testing Rome / 2017.10 (C) FlukeNetworks 36

Page 37: Cat.8 Field Testing - Cabling & Wireless · 2017-11-10 · Agenda BICSI Europe / Cat.8 Field Testing Rome / 2017.10 (C) FlukeNetworks 2 Cat.8 / Class I and II overview Basic Test

Manufacturer Endorsements

Panduit

– “…pleased to endorse and

recommend the DSX-8000

Cable Analyzer by Fluke

Networks for use in field-

testing for PANDUIT’s copper

connectivity solutions…”

Visit the DSX-8000 website

for a current list of

endorsements

BICSI Europe / Cat.8 Field Testing Rome / 2017.10 (C) FlukeNetworks 37

Page 38: Cat.8 Field Testing - Cabling & Wireless · 2017-11-10 · Agenda BICSI Europe / Cat.8 Field Testing Rome / 2017.10 (C) FlukeNetworks 2 Cat.8 / Class I and II overview Basic Test

Cat.8 … „It‘s not walking on thin ice“

1. Channel: Manufacturer A NEXT 3.2 RL 4.3

2. Perm. Link: Manufacturer B NEXT 5.6 RL 3.8

3. Mix & Match Channel NEXT 8.3 RL 5.9

BICSI Europe / Cat.8 Field Testing Rome / 2017.10 (C) FlukeNetworks 38

Page 39: Cat.8 Field Testing - Cabling & Wireless · 2017-11-10 · Agenda BICSI Europe / Cat.8 Field Testing Rome / 2017.10 (C) FlukeNetworks 2 Cat.8 / Class I and II overview Basic Test

Conclusio

BICSI Europe / Cat.8 Field Testing Rome / 2017.10 (C) FlukeNetworks 39

Qualified instruments and personnel paired with an efficient work flow ensures …

… “Next Generation Readiness” by extending the certification to all parameters specified for a cabling system

… a profitable certification of twister pair cabling systems

Ver.3.6 © Fluke Networks 2015

Page 40: Cat.8 Field Testing - Cabling & Wireless · 2017-11-10 · Agenda BICSI Europe / Cat.8 Field Testing Rome / 2017.10 (C) FlukeNetworks 2 Cat.8 / Class I and II overview Basic Test

[email protected]

THANK YOU FOR YOUR ATTENTION !

Questions?

For an animated PPT … http://tiny.cc/kkm2017

BICSI Europe / Cat.8 Field Testing Rome / 2017.10 (C) FlukeNetworks 40