caso estudio armonicos y correccion fp - fabrica

Upload: marcio-camargo

Post on 14-Apr-2018

221 views

Category:

Documents


0 download

TRANSCRIPT

  • 7/30/2019 Caso Estudio Armonicos y Correccion Fp - Fabrica

    1/19

    Harmonic Analysis and Power FactorHarmonic Analysis and Power Factor

    Correction Evaluation Correction Evaluation

    Plastic Creations Line 13Plastic Creations Line 13

    Prepared by:

    Electrotek Concepts, Inc.Knoxville, TNwww.electrotek.com

    Wade EcklerPower Systems Engineer

  • 7/30/2019 Caso Estudio Armonicos y Correccion Fp - Fabrica

    2/19

    Plastic Creations Line 13 Harmonics and Power Factor Correction Evaluation

    ElectrotekConcepts, Inc. ii

    - Table of Contents -

    Executive Summary ______________________________________________________1

    1.0 I ntroduction _________________________________________________________2

    One Line Diagram ___________________________________________________________ 2

    2.0 Field Measur ements at Newtown ________________________________________3

    2.1 AC Drive Characteristics Roll 1 _________________________________________3

    AC Drive Characteristics Roll 2 ______________________________________________ 4

    2.2 AC Drive Characteristics Kneader B_____________________________________6

    Overall Load Characteristics Line 13 __________________________________________ 7

    2.3 Voltage Distortion Evaluations ___________________________________________ 9

    3.0 Recommended Power Factor Correction _________________________________13

    3.1 Summary of Reactive Power Requirements ________________________________ 13

    4.0 Proposed F il ter Design _______________________________________________14

    Appendix A: Low Vol tage Power Factor Correction Equipment Manuf acturers ____16

  • 7/30/2019 Caso Estudio Armonicos y Correccion Fp - Fabrica

    3/19

    Plastic Creations Line 13 Harmonics and Power Factor Correction Evaluation

    ElectrotekConcepts, Inc. 1

    Executive Summary

    The Plastic Creations in Newtown has a new Line 13 with ac variable frequency drives for

    the calender line. The drives have high harmonic current levels but do not require the

    level of power factor correction that dc drives require.

    This evaluation characterizes the loads on Line 13. Power factor correction needs are

    calculated and the impact of the existing capacitor bank (provides about 600 kvar of

    compensation) is illustrated. The capacitor increases distortion levels at the 7th

    and 11th

    harmonics, resulting in overall voltage distortion levels exceeding 5% on the 480 volt

    system. Although this should not cause problems for now, the distortion levels are likely

    to be unacceptable with additional loading from Line 14. Also, the capacitor creates the

    potential for magnified transient voltages if the utility switches capacitor banks on the

    transmission system.

    The capacitor should be converted into a tuned filter and it should be able to provide

    power factor correction for the existing Line 13 (correction to a power factor of aboutunity) and should also be sufficient even after the addition of Line 14 (power factor

    around 0.97). Specifications for the reactor to tune this bank are provided here.

    480 Volt Bus

    Tuned

    Capacitor

    Bank

    Capacitor Bank:937.5 kvar600 volts

    Inductors:0.046 mH per phaserms current rating = 15th harmonic current r775 amps

    Circuit Brea480 Volt, 20

    Proposed Filter Configuration for Line 13 and Line 14

  • 7/30/2019 Caso Estudio Armonicos y Correccion Fp - Fabrica

    4/19

    Plastic Creations Line 13 Harmonics and Power Factor Correction Evaluation

    ElectrotekConcepts, Inc. 2

    1.0 Introduction

    The Plastic Creations plant in Newtown has a new Line 13 with a dedicated transformer.

    Line 13 includes ac variable frequency drives instead of the dc drives that are used onother Plastic Creations lines. This has a dramatic impact on the power factor

    characteristics of the load. The ac drives have much better displacement power factor

    (not as much compensation needed) but have significant harmonic distortion levels. The

    measurements and recommendations presented in this report deal with the power factor

    correction and filtering requirements for this line, including the impact of a future Line 14

    with similar characteristics to Line 13.

    One Line Diagram

    Utility 13.8 kV Feeder

    138 kV substation

    3750 kVA, 7.0 %13.8 kV/480 volts

    937.5 kvar600 volts

    H110 Kneader13-2

    Calender Controls(Protected by 24

    UPS)

    MCC7H22

    H111Kneader

    13-1

    H112

    Mixer

    Grinders

    CalenderHeaters

    H113

  • 7/30/2019 Caso Estudio Armonicos y Correccion Fp - Fabrica

    5/19

    Plastic Creations Line 13 Harmonics and Power Factor Correction Evaluation

    ElectrotekConcepts, Inc. 3

    2.0 Field Measurements at Newtown

    Measurements were taken to characterize the ac drive loads and the overall load

    characteristics for Line 13. The measurements also evaluated the impact of the existing

    capacitor bank on distortion levels on the 480 volt system supplying Line 13.

    2.1 AC Drive Characteristics Roll 1

    The following waveforms and harmonic spectrums are typical for Roll 1. This is also

    typical for Roll 3.

    Event waveform/detail

    Pre/Post-trigger at 02/25/98 11:32:34.312

    CHA Amps

    11:32:34.31 11:32:34.32 11:32:34.33 11:32:34.34 11:32:34.35 11:32:34.36 11:32:34.37 11:32:34.38

    Amps

    -150

    -100

    -50

    0

    50

    100

    150

    Event waveform/detail

    Total RMS: 61.27 Amps

    Total harmonic distortion: 32.52 Amps

    Even contribution (H02-H50): 1.31 Amps

    Odd contribution (H03-H49): 32.50 Amps

    Pre/Post-trigger at 02/25/98 11:32:34.362

    CHA Amps

    THDabs H05 H10 H15 H20 H25 H30

    Amps

    0

    10

    20

    30

    40

    50

    60

  • 7/30/2019 Caso Estudio Armonicos y Correccion Fp - Fabrica

    6/19

    Plastic Creations Line 13 Harmonics and Power Factor Correction Evaluation

    ElectrotekConcepts, Inc. 4

    AC Drive Characteristics Roll 2

    The following waveforms and harmonic spectrums are typical for Roll 2. This is also

    typical for Roll 4.

    Event waveform/detail

    Timed event at 02/25/98 12:48:18.000

    CHA A mps

    12:48:18.000 12:48:18.005 12:48:18.010 12:48:18.015 12:48:18.020

    Amps

    -300

    -200

    -100

    0

    100

    200

    300

    Event waveform/detail

    Total RMS: 123.67 Amps

    Total harmonic distortion: 56.36 Amps

    Even contribution (H02-H50): 0.45 Amps

    Odd contribution (H03-H49): 56.37 Amps

    Timed event at 02/25/98 12:48:18.000

    CHA A mpsTHDabs H05 H10 H15 H20 H25 H30

    Amps

    0

    25

    50

    75

    100

    125

  • 7/30/2019 Caso Estudio Armonicos y Correccion Fp - Fabrica

    7/19

    Plastic Creations Line 13 Harmonics and Power Factor Correction Evaluation

    ElectrotekConcepts, Inc. 5

    Example waveform and spectrum from BMI 3030

    Roll 2 Current Waveform

    0 10 20 30 40-200

    -100

    0

    100

    200

    Time (mS)

    Roll 2 Harmonic Characteristics

    0 10 20 30 400

    20

    40

    60

    80

    100

    Frequency (H pu)

    Freq :Fund :THD :TID :TD :

    RMSh :RMSi :

    RMSfh:

    RMS :ASUM :TIF :IT :

    189.578452.7698052.769847.27030101.286

    101.286179.963454.67446051.9

  • 7/30/2019 Caso Estudio Armonicos y Correccion Fp - Fabrica

    8/19

    Plastic Creations Line 13 Harmonics and Power Factor Correction Evaluation

    ElectrotekConcepts, Inc. 6

    2.2 AC Drive Characteristics Kneader B

    The following waveforms and harmonic spectrums are typical for Kneader B. This is also

    typical for Kneader A.

    Event waveform/detail

    Snapshot event at 02/25/98 14:53:43.000

    CHA A mps

    14:53:43.000 14:53:43.005 14:53:43.010 14:53:43.015 14:53:43.020

    Amps

    -750

    -500

    -250

    0

    250

    500

    750

    Event waveform/detail

    Total RMS: 224.85 Amps

    Total harmonic distortion: 98.85 Amps

    Even contribution (H02-H50): 9.78 Amps

    Odd contribution (H03-H49): 98.38 Amps

    Snapshot event at 02/25/98 14:53:43.000

    CHA A mps

    THDabs H05 H10 H15 H20 H25 H30

    Amps

    0

    50

    100

    150

    200

    250

  • 7/30/2019 Caso Estudio Armonicos y Correccion Fp - Fabrica

    9/19

    Plastic Creations Line 13 Harmonics and Power Factor Correction Evaluation

    ElectrotekConcepts, Inc. 7

    Overall Load Characteristics Line 13

    The following summarizes the overall load characteristics for Line 13. This includes the

    ac drives characterized in the previous sections along with the calender heaters and other

    loads that are part of the Line. This information can be used for evaluating harmonic filterand power factor correction requirements.

    The table also illustrates the effect of the existing capacitor bank on the distortion levels

    and the power factor. Note that the 7th

    harmonic is significantly increased when the

    capacitor bank is in service and the voltage distortion often exceeds 5%. The current

    distortion increases to more than 30% with 20% at the 7th

    harmonic. This is an indication

    of the magnification at the 7th

    harmonic component.

    Current 1300-1800 amps 1300-1600 amps

    Power 1.1-1.3 MVA 1.0-1.1 MVA

    kvar 480-500 kvar 150-180 kvar lead

    PF .88-.90 0.95

    dPF .88-.91 0.99 lead

    THDv 2.9-3.2 % 4.5-5.9 %

    THDi 15-17 % 25-32 %

    V5 1.9-2.0 % 2.5 %

    I5 12-13 % 19 %

    V7 1.8 % 3.2 %

    I7 8-9 % 20 %

    No Cap Bank with Cap Bank

  • 7/30/2019 Caso Estudio Armonicos y Correccion Fp - Fabrica

    10/19

    Plastic Creations Line 13 Harmonics and Power Factor Correction Evaluation

    ElectrotekConcepts, Inc. 8

    The following waveform and harmonic spectrum represent typical load characteristics for

    Line 13 (without the capacitor bank).

    Line 13 Current Waveform

    0 10 20 30 40-3000

    -2000

    -1000

    0

    1000

    2000

    3000

    Time (mS)

    Line 13 Current Harmonic Spectrum

    0 3 6 9 12 150

    250

    500

    750

    1000

    1250

    1500

    1750

    Frequency (H pu)

    Freq :Fund :THD :TID :TD :

    RMSh :RMSi :

    RMSfh:

    RMS :ASUM :TIF :IT :

    11529.8914.4941014.4941221.74401545.87

    1545.871939.8985.7982132633

  • 7/30/2019 Caso Estudio Armonicos y Correccion Fp - Fabrica

    11/19

    Plastic Creations Line 13 Harmonics and Power Factor Correction Evaluation

    ElectrotekConcepts, Inc. 9

    2.3 Voltage Distortion Evaluations

    The following measurement results summarize the voltage distortion concerns at the 480

    volt bus supplying Line 13.

    Voltage Character ist ics withou t Capaci tor Bank

    Typical voltage waveforms and spectrums are provided below without the capacitor bank

    in service. The distortion is dominated by the 5th

    harmonic component since that is the

    highest current injection from the drive loads.

    Event waveform/detail

    Total RMS: 464.93 Volts

    Total harmonic distortion: 15.76 Volts

    Even contribution (H02-H50): 2.68 Volts

    Odd contribution (H03-H49): 15.54 Volts

    Snapshot event at 02/25/98 15:48:40.000

    CHA V olts

    THDabs H05 H10 H15 H20 H25 H30

    Volts

    0

    100

    200

    300

    400

    500

    Event waveform/detail

    Snapshot event at 02/25/98 15:48:40.000

    CHA Volts

    15:48:40.00

    15:48:40.01

    15:48:40.02

    15:48:40.03

    15:48:40.04

    15:48:40.05

    15:48:40.06

    15:48:40.07

    Volts

    -750

    -500

    -250

    0

    250

    500

    750

  • 7/30/2019 Caso Estudio Armonicos y Correccion Fp - Fabrica

    12/19

    Plastic Creations Line 13 Harmonics and Power Factor Correction Evaluation

    ElectrotekConcepts, Inc. 10

    Voltage Character ist ics with Capaci tor Bank

    Typical voltage waveforms and spectrums are provided below after the capacitor bank

    was switched in. The capacitor creates a resonance between the 7th

    and 11th

    harmonics,magnifying both of these components. The voltage distortion levels are increased overall

    and can exceed 5%. The highest distortion is typically at the 7th

    harmonic with the

    capacitor bank in due to the magnification.

    Event waveform/detail

    Meter mode snapshot at 02/25/98 16:20:59.000

    CHA V olts

    16:20:59.000 16:20:59.005 16:20:59.010 16:20:59.015 16:20:59.020

    Volts

    -750

    -500

    -250

    0

    250

    500

    750

    Event waveform/detail

    Total RMS: 473.33 Volts

    Total harmonic distortion: 24.32 Volts

    Even contribution (H02-H50): 0.59 Volts

    Odd contribution (H03-H49): 24.33 Volts

    Meter mode snapshot at 02/25/98 16:20:59.000

    CHA V olts

    THDabs H05 H10 H15 H20 H25 H30

    Volts

    0

    100

    200

    300

    400

    500

  • 7/30/2019 Caso Estudio Armonicos y Correccion Fp - Fabrica

    13/19

    Plastic Creations Line 13 Harmonics and Power Factor Correction Evaluation

    ElectrotekConcepts, Inc. 11

    Compar ison of Vol tage Character ist ics

    The figure below shows the THD of the voltage on the Line 13 Main Bus and the values

    of the 5th, 7

    th, 11

    th, and 13

    thharmonic as percentages of the fundamental with the capacitor

    bank on line and with it off line. The chart makes it easier to see how placing the

    capacitor bank on line at the Line 13 Main Bus magnifies the 7th and 11th harmonics. The7

    thharmonic is virtually non-existent, at 0.02% of the fundamental, with the capacitor

    bank off line. The 11th

    harmonic was measured at 0.75% without the capacitor banks.

    After placing the capacitor banks on line, the 7th

    increases to 3.73% and the 11th

    increases

    to 2.23% of the fundamental.

    Line 13 Main Bus

    0.00

    1.00

    2.00

    3.00

    4.00

    5.00

    6.00

    THDv 5th 7th 11th 13th

    Harmonic

    VoltageDistortion(%)

    No Caps

    With Caps

  • 7/30/2019 Caso Estudio Armonicos y Correccion Fp - Fabrica

    14/19

    Plastic Creations Line 13 Harmonics and Power Factor Correction Evaluation

    ElectrotekConcepts, Inc. 12

    Descr ipt ion of the Resonance Problem

    The capacitor bank introduces a resonance between the 7th

    and 11th

    harmonics that

    magnifies both of these components. The frequency scan below illustrates the voltage at

    the 480 volt bus per amp injected by the drive loads with and without the capacitor bankin service.

    Frequency Scan with and Without Capacitor Bank

    0.00 3.00 6.00 9.00 12.00 15.00 18.00 21.00 24.00 27.000.0

    0.1

    0.2

    0.3

    0.4

    Frequency (H pu)

    This problem can be avoided by converting the capacitor bank into a tuned filter. The

    frequency scan plots below show the effect of the tuned filter in preventing resonances

    close to the characteristic harmonics of the drive loads (5th

    and 7th).

    Frequency Scan Showing Effect of Filter

    0.00 3.00 6.00 9.00 12.00 15.00 18.00 21.00 24.00 27.000.0

    0.1

    0.2

    0.3

    0.4

    Frequency (H pu)

  • 7/30/2019 Caso Estudio Armonicos y Correccion Fp - Fabrica

    15/19

    Plastic Creations Line 13 Harmonics and Power Factor Correction Evaluation

    ElectrotekConcepts, Inc. 13

    3.0 Recommended Power Factor Correction

    This section summarizes the power factor correction needs for the existing configuration

    with Line 13 and estimates the impacts of a similar line (Line 14) in the future.

    3.1 Summary of Reactive Power Requirements

    The following table summarizes the load characteristics measured for Line 13 and shows

    the impact of the 600 kvar of compensation on the power factor of the overall load. The

    table also shows the effect of this capacitor bank if the load is doubled to include the effect

    of Line 14 in the future.

    The power factor with just Line 13 is corrected to unity with the existing capacitor bank.

    With Line 14, the capacitor bank will correct the power factor to about 0.97 lagging when

    both lines are running.

    Line 13 Line 13 and Line 14

    Transformer Size 3750 3750

    Transformer Impedance 7% 7.00%

    Peak Load (kVA) 1300 2600

    Displacement Power Factor 0.9 0.9

    Reactive Power (kvar) 567 1133

    Real Power (kW) 1170 2340

    Compensation (kvar) 600 600

    Total Reactive Power with Compensation (kvar) -33 533

    Power Factor with Compensation 1.00 0.97

    Fifth Harmonic Current (%) 15% 15%

    The capacitor should be configured as a tuned bank to prevent excessive distortion and

    problems with magnification of capacitor switching transients. The next section gives

    parameters for the tuning reactor.

  • 7/30/2019 Caso Estudio Armonicos y Correccion Fp - Fabrica

    16/19

    Plastic Creations Line 13 Harmonics and Power Factor Correction Evaluation

    ElectrotekConcepts, Inc. 14

    4.0 Proposed Filter Design

    Plastic Creations has already purchased a capacitor bank for power factor correction. The

    capacitor is rated 600 volts so it can easily be used as part of a tuned filter. The proposed

    filter design is illustrated in the one line diagram below. The following page gives the

    specifications for the filter reactor that should be purchased.

    480 Volt Bus

    Tuned

    Capacitor

    Bank

    Capacitor Bank:937.5 kvar

    600 volts

    Inductors:

    0.046 mH per phase

    rms current rating = 1100 amps

    5th harmonic current rating =

    775 amps

    Circuit Breaker:480 Volt, 2000 A

    Proposed Filter Configuration for Lines 13 and 14

  • 7/30/2019 Caso Estudio Armonicos y Correccion Fp - Fabrica

    17/19

    Plastic Creations Line 13 Harmonics and Power Factor Correction Evaluation

    ElectrotekConcepts, Inc. 15

    Low Voltage Filter Calculations: 600 kvar 480 Volt Filter

    SYSTEM INFORMATION:

    Filter Specification: 5 th Power System Frequency: 60 Hz

    Capacitor Bank Rating: 937.5 kVAr Capacitor Rating: 600 Volts

    Rated Bank Current: 902 Amps 60 Hz

    Nominal Bus Voltage: 480 Volts Derated Capacitor: 600 kVAr

    Capacitor Current (actual): 721.7 Amps Total Harmonic Load: 2500 kVA

    Filter Tuning Harmonic: 4.7 th Filter Tuning Frequency: 282 Hz

    Cap Impedance (wye equivalent): 0.3840 Cap Value (wye equivalent): 6907.8 uF

    Reactor Impedance: 0.0174 Reactor Rating: 0.0461 mH

    Filter Full Load Current (actual): 755.9 Amps Supplied Compensation: 628 kVArFilter Full Load Current (rated): 944.9 Amps

    Transformer Nameplate: 3750 kVA Utility Side Vh: 2.00 % THD

    (Rating and Impedance) 7.00 % (Utility Harmonic Voltage Source)

    Load Harmonic Current: 20.00 % Fund Load Harmonic Current: 601.4 Amps

    Utility Harmonic Current: 175.5 Amps Max Total Harm. Current: 776.9 Amps

    CAPACITOR DUTY CALCULATIONS:

    Filter RMS Current: 1084.0 Amps Fundamental Cap Voltage: 502.8 Volts

    Harmonic Cap Voltage: 103.3 Volts Maximum Peak Voltage: 606.1 Volts

    RMS Capacitor Voltage: 513.3 Volts Maximum Peak Current: 1532.8 Amps

    CAPACITOR LIMITS: (IEEE Std 18-1980) FILTER CONFIGURATION:

    Limit Actual

    Peak Voltage: 120 % 101%

    Current: 180% 120%

    KVAr: 135% 103%

    RMS Voltage: 110% 86 %

    FILTER REACTOR DESIGN SPECIFICATIONS:

    Reactor Impedance: 0.0174 Reactor Rating: 0.0461 mH

    Fundamental Current: 755.9 Amps Harmonic Current: 776.9 Amps

    4 8 0 V o l t B u s

    6 0 0 k V A r @

    6 0 0 V o l t s

    X l = 0 . 0 27 2

  • 7/30/2019 Caso Estudio Armonicos y Correccion Fp - Fabrica

    18/19

    Plastic Creations Line 13 Harmonics and Power Factor Correction Evaluation

    ElectrotekConcepts, Inc. 16

    Appendix A: Low Voltage Power Factor Correction Equipment

    Manufacturers

    ABBSteve Colvin

    1206 Hatton RoadWichita Falls, TX 76302

    817-761-3232 / 817-761-3202

    Aerovox Group

    John Childs

    740 Belleville Ave.

    New Bedford, MA 02745-6194

    508-994-9661 / 508-990-8696

    ASC Industr ial

    Bruce Marzley / Larry Burch / Chuck Gougler

    8967 Pleasantwood Ave NW

    North Canton, OH 44720216-499-1210 / 216-499-1213

    Commonwealth Sprague

    Frank Smith

    Brown Street

    North Adams, MA 01247

    413-664-4466 / 413-664-4465

    Control l ix

    Paul Griesmer

    21415 Alexander Road

    Walton Hills, OH 44146

    216-232-8757 / 216-232-1893

    Freeborn IndustriesRudy Wodrich / Kevin Simpson

    6675 Rexwood Road

    Mississauga, Ontario

    L4V 1V1 Canada

    905-677-9272 / 905-677-5448

    General ElectricPeter Baltz

    14131 Midway Road, Suite 500

    Dallas, TX 75244

    214-702-5274 / 214-702-5283

    Gilbert/K&M

    Neal Ciurro / Jess Hancock

    P.O. Box 1141

    Beckly, WV 25802

    304-252-6243 / 304-252-6292

  • 7/30/2019 Caso Estudio Armonicos y Correccion Fp - Fabrica

    19/19

    Plastic Creations Line 13 Harmonics and Power Factor Correction Evaluation

    Electrotek C t I 17

    Macroamp LesatBob Stuefen / Allan Freebury

    P.O. 1512

    Ukiah, CA 95482

    707-462-2222 / 707-462-3068

    Myron ZuckerJim Holley315 East Parent Street

    Royal Oak, MI 48067

    810-543-2277 / 810-543-1529

    RobiconDennis Lorenzi

    100 Sagamore Hill Road

    Pittsburgh, PA 15239-2982

    412-325-7260 / 412-733-8093

    TCI

    J. P. Thorpe7878 North 86th St.

    Milwaukee, WI 53224

    414-357-4480 / 414-357-4480

    Tech-Tran Corp

    Ted Furst / Charles Roney

    50 Indel Avenue

    Rancocas, NJ 08703

    800-257-9420 / 609-267-6751

    VAR+ Controls

    Bill McConnellMail Box 585

    Whitmore Lake, MI 48189

    800-KILOVAR / 313-449-8710

    Versatex Indus tries

    Ted Noutko

    P.O. Box 354

    Brighton, MI 48116

    810-229-5751 / 810-229-7863