Major Fault Caused by Stator Winding Circuit Ring Failure

Case study

IRMC 2018, Long Beach, CA

Joël Pedneault-Desroches, P. Eng.

Page 2: Case study Major Fault Caused by Stator Winding …...Inspection report: Stator circuit ring 6 60 cm Circuit E1 (phase A) Circuit S2 (phase B) Circuit ring insulation is burned and

Presentation Outline

2 IRMC 2018, Long Beach, CA

Introduction

Inspection report

Chronology of events

Repair

Conclusion

Page 3: Case study Major Fault Caused by Stator Winding …...Inspection report: Stator circuit ring 6 60 cm Circuit E1 (phase A) Circuit S2 (phase B) Circuit ring insulation is burned and

Introduction

3

August 13, 2017 : 202 MVA, 13.8 kV generator failed and forced the evacuation of a power house

IRMC 2018, Long Beach, CA

Page 4: Case study Major Fault Caused by Stator Winding …...Inspection report: Stator circuit ring 6 60 cm Circuit E1 (phase A) Circuit S2 (phase B) Circuit ring insulation is burned and

Presentation Outline

4 IRMC 2018, Long Beach, CA

Introduction

Inspection report

Chronology of events

Repair

Conclusion

Page 5: Case study Major Fault Caused by Stator Winding …...Inspection report: Stator circuit ring 6 60 cm Circuit E1 (phase A) Circuit S2 (phase B) Circuit ring insulation is burned and

Inspection report

5

Main damages to the generator:

• Stator circuit ring (section of 6 feet)

• 18 Bottom bars seriously damaged

• Cable ducts and instruments

IRMC 2018, Long Beach, CA

Page 6: Case study Major Fault Caused by Stator Winding …...Inspection report: Stator circuit ring 6 60 cm Circuit E1 (phase A) Circuit S2 (phase B) Circuit ring insulation is burned and

Inspection report: Stator circuit ring

6

60 cm

Circuit E1

(phase A)

Circuit S2

(phase B)

Circuit ring insulation is burned and damaged around the fault

60 cm (3 feet) of S2 circuit ring is missing (copper pipe of 3 ½ inches and ¾ thickness)

IRMC 2018, Long Beach, CA

Page 7: Case study Major Fault Caused by Stator Winding …...Inspection report: Stator circuit ring 6 60 cm Circuit E1 (phase A) Circuit S2 (phase B) Circuit ring insulation is burned and

Inspection report: Stator circuit ring (2)

7

Golf ball hole in circuit E1 (phase A)

Circuit E1 moved by a inch

Support bloc opened by the force of the fault

IRMC 2018, Long Beach, CA

Page 8: Case study Major Fault Caused by Stator Winding …...Inspection report: Stator circuit ring 6 60 cm Circuit E1 (phase A) Circuit S2 (phase B) Circuit ring insulation is burned and

Inspection report: Bottom bars

8

Insulation of 18 bottom bars was seriously burned and covered by copper

IRMC 2018, Long Beach, CA

Page 9: Case study Major Fault Caused by Stator Winding …...Inspection report: Stator circuit ring 6 60 cm Circuit E1 (phase A) Circuit S2 (phase B) Circuit ring insulation is burned and

Inspection report: Instrumentation

9

Many cable ducts and instruments were burned

Neutral cable, neutral CTs cables, RTDs cables…

IRMC 2018, Long Beach, CA

Page 10: Case study Major Fault Caused by Stator Winding …...Inspection report: Stator circuit ring 6 60 cm Circuit E1 (phase A) Circuit S2 (phase B) Circuit ring insulation is burned and

Inspection report: Generator circuit breaker

10

Burned spots in the mobiles contacts

Current fault: ~ 100 kA rms(~12 𝑝𝑢)

IRMC 2018, Long Beach, CA

Page 11: Case study Major Fault Caused by Stator Winding …...Inspection report: Stator circuit ring 6 60 cm Circuit E1 (phase A) Circuit S2 (phase B) Circuit ring insulation is burned and

Presentation Outline

11 IRMC 2018, Long Beach, CA

Introduction

Inspection report

Chronology of events

Repair

Conclusion

Page 12: Case study Major Fault Caused by Stator Winding …...Inspection report: Stator circuit ring 6 60 cm Circuit E1 (phase A) Circuit S2 (phase B) Circuit ring insulation is burned and

Chronology of events: Protection

12

08:57:03: After being stopped for a part of the night, the group is started08:58:03: The generator circuit breaker is closed 09:00:46: Abnormal voltage of third harmonic at the neutral of the generator detected

09:00:47: Smoke detected in the generator

09:01:06: Current in reverse sequence detected 09:01:21: Current in reverse sequence alarm09:01:24: First overvoltage in the neutral of the generator

09:01:27: Tripping with complete stop by differential protection, fire protection activated

1 min

2 min 43 sec

1 sec

19 sec

15 sec

3 sec

3 sec

IRMC 2018, Long Beach, CA

Page 13: Case study Major Fault Caused by Stator Winding …...Inspection report: Stator circuit ring 6 60 cm Circuit E1 (phase A) Circuit S2 (phase B) Circuit ring insulation is burned and

Chronology of events: Protection

13

08:57:03: After being stopped for a part of the night, the group is started08:58:03: The generator circuit breaker is closed 09:00:46: Abnormal voltage of third harmonic at the neutral of the generator detected

09:00:47: Smoke detected in the generator

09:01:06: Current in reverse sequence detected 09:01:21: Current in reverse sequence alarm (400 ms)09:01:24: First overvoltage in the neutral of the generator (15-25 ms)

09:01:27: Tripping with complete stop by differential protection, fire protection activated

Duration of the fault ≈ 41 seconds

Alarm

Tripping alarm

1 min

2 min 43 sec

1 sec

19 sec

15 sec

3 sec

3 sec

IRMC 2018, Long Beach, CA

Page 14: Case study Major Fault Caused by Stator Winding …...Inspection report: Stator circuit ring 6 60 cm Circuit E1 (phase A) Circuit S2 (phase B) Circuit ring insulation is burned and

Chronology of events: Summary of the event

14 IRMC 2018, Long Beach, CA

Fault started with a resistive contact that made circuit S2 (phase B; neutral end) rise in temperature and start an arc that caused :

• Smoke detection inside the generator;

• Intermittent ground fault not constant enough to shut down the unit by the operation of protections (lower voltage side);

• Damage the insulation of the circuit E1 (phase A; high voltage end).

It ends by a phase-to-phase fault with E1 and S2 causing the unit to trip by differential protection.

Page 15: Case study Major Fault Caused by Stator Winding …...Inspection report: Stator circuit ring 6 60 cm Circuit E1 (phase A) Circuit S2 (phase B) Circuit ring insulation is burned and

Presentation Outline

15 IRMC 2018, Long Beach, CA

Introduction

Inspection report

Chronology of events

Repair

Conclusion

Page 16: Case study Major Fault Caused by Stator Winding …...Inspection report: Stator circuit ring 6 60 cm Circuit E1 (phase A) Circuit S2 (phase B) Circuit ring insulation is burned and

Repair: Stator bars

16

Wave winding

First bottom bar cost 20 top bars

Bars replaced: 18 bottom and 37 top (55 total)

Challenge: Work to be done with the rotor in place

IRMC 2018, Long Beach, CA

Page 17: Case study Major Fault Caused by Stator Winding …...Inspection report: Stator circuit ring 6 60 cm Circuit E1 (phase A) Circuit S2 (phase B) Circuit ring insulation is burned and

Repair: Stator bars (2)

17

1 – Removing the bars after debrazing and removing the wedges

IRMC 2018, Long Beach, CA

Page 18: Case study Major Fault Caused by Stator Winding …...Inspection report: Stator circuit ring 6 60 cm Circuit E1 (phase A) Circuit S2 (phase B) Circuit ring insulation is burned and

Repair: Stator bars (3)

18

2 – Replacing the bars after cleaning and painting the slots with semi-conductive paint

(Hipot tests on spare bars before installation: 34 kVac, after insertion of the bottom bars: 32 kVac, after insertion of the top bars: 30 kVac)

“U” packing with semi-conductive resin:

Semi conductive paper (0.1 mm)

Semi conductive resin

Roebel Bar

IRMC 2018, Long Beach, CA

Page 19: Case study Major Fault Caused by Stator Winding …...Inspection report: Stator circuit ring 6 60 cm Circuit E1 (phase A) Circuit S2 (phase B) Circuit ring insulation is burned and

Repair: Stator bars (4)

19

3 – Final tests after the radial wedging with original wedges (ripple springs), brazing and attaching the bars

- Final Hipot: 13.8 kVac

- Winding resistance

IRMC 2018, Long Beach, CA

Page 20: Case study Major Fault Caused by Stator Winding …...Inspection report: Stator circuit ring 6 60 cm Circuit E1 (phase A) Circuit S2 (phase B) Circuit ring insulation is burned and

Repair: Circuit ring

20

Preparing and brazing the junction

Original junction :

New junction:

IRMC 2018, Long Beach, CA

Page 21: Case study Major Fault Caused by Stator Winding …...Inspection report: Stator circuit ring 6 60 cm Circuit E1 (phase A) Circuit S2 (phase B) Circuit ring insulation is burned and

Repair: Final look

21 IRMC 2018, Long Beach, CA

Page 22: Case study Major Fault Caused by Stator Winding …...Inspection report: Stator circuit ring 6 60 cm Circuit E1 (phase A) Circuit S2 (phase B) Circuit ring insulation is burned and

Presentation Outline

22 IRMC 2018, Long Beach, CA

Introduction

Inspection report

Chronology of events

Repair

Conclusion

Page 23: Case study Major Fault Caused by Stator Winding …...Inspection report: Stator circuit ring 6 60 cm Circuit E1 (phase A) Circuit S2 (phase B) Circuit ring insulation is burned and

Conclusion

23

• Bad junction in the circuit ring can be difficult to detect with conventional protection setting and can cause serious damages to the generator.

• Protection logic has to be revised to reduce the damages in case of failure (protection sensitivity, combining smoke detection with ground fault for tripping…).

• Other monitoring solutions such as permanent thermal imaging should be considered to enable early detection of such faults.

• The fault caused a down time of 3 months; repair was a success.

IRMC 2018, Long Beach, CA