capacitor analysis for 64
TRANSCRIPT
1
Distribution System Operation Optimization through Capacitor Size Allocation by Genetic Algorithm for
69-bus System
ByYifang Ni (Electrical Engineering)
Faculty Advisor:Dr. Robert O’Connell, PhD, PE (Electrical and Computer Engineering)
ECE 4995 Undergraduate Honor Research Project Report
Department of Electrical and Computer Engineering
University of Missouri - Columbia
Columbia, Missouri
November 22, 2014
2
Abstract
This paper shows use of MATLAB to solve a research project. In my research
project, I worked on capacitor optimization by analyzing the data on minimum power
loss, minimum voltage, number of switching operations and system load balancing
index, mainly focus on minimum power loss for light load, average load and heavy
load. In this paper, a detailed discussion of capacitor optimization will be included.
Results are provided by using the genetic algorithm.
Introduction
There are three main advantages to using capacitors in power loads: first,
capacitors reduce power loss in the load; second, they can raise voltages; and third,
they can be used for power factor correction. Therefore, capacitors play an important
role in power distribution systems. My research project is distribution system
operation optimization through capacitor size allocation by genetic algorithm using
MATLAB for a 69-bus test system (figure 1).
3
Figure 1, 69-bus test system [8]
Genetic Algorithm and Code
Genetic Algorithm
My research project is based on the Genetic Algorithm method. The Genetic
Algorithm method can be divided into two categories: single function and multi-
objective functions. The single function “is formulated as a single objective
4
regardless of the number of objects and constraints” [1]. Multi-objective functions
generate a set of solutions based on non-dominated sorting. The steps of using the
genetic algorithm always includes codification of individuals (chromosomes),
population generation, evaluation (fitness) and crossover, mutation, and selection. [1]
Code
The following is the code I wrote to change the capacitor value at bus 65 in figure 1
from 0 to 1 mega-volt-amps reactive (MVAR) in steps of 0.1 MVAR, then got 11
solutions and compare the 11 minimum power loss values and output the minimum
power loss value form the 11 solutions and its corresponding capacitor size. All the
code belongs to file NDSGA2t.m in [2].
[NDSGA2t.m.]
The following code is used to change the average load to light lode and heavy load.
The code belongs to file Data_69_2.m.
[Data_69_2.m]
5
Results and Discussion
Capacitor size = 0 MVAR analysis
1st run
6
Figure 2, capacitor size = 0 MVAR solutions
7
Figure 3, capacitor size = 0 MVAR analysis
8
For my research project, I used MATLAB to run the program and analyze the data.
The program gives random solutions (sets of possible selections) for each run but
there are always 33 to 35 of them. The above figures are the data when capacitor size
is equal to 0 MVAR for one run. Figure 2 is the output solutions of tie switches,
power loss, minimum voltage, number of switching operations, and system load
balancing index.
The first row in figure 3 shows the maximum values of power loss, maximum
minimum voltage, maximum number of switching operations and maximum system
load balancing index. The second row are the minimum values for power loss,
minimum voltage, number of switching operations, system load balancing index. The
third line to last line values are calculated by using the actual value minus minimum
value divide by maximum value minus minimum value. The equation is:
(Xactual – Xminimum) / (Xmaximum – Xminimum)
For example, in the third row the first value 0 is calculated by (0.09959-0.09959) /
(0.22493-0.09959) = 0. The last column in figure 3 is the sum value of the values on
the first four columns. For example, 0 + 0.000596 + 0.6 + 0.514465 = 1.115062. If we
care about all four objects, the smaller the sum value is, the better the solution is.
9
2nd run
Figure 4 and figure 5 are analysis of 0 MVAR, same process as first run.
Figure 4, capacitor size = 0 MVAR solutions
10
Figure 5, capacitor size = 0 MVAR analysis
11
Power loads
Results vary with the size of the load. In this section, average, light and heavy loads
are compared.
Average load
The following data is the mode results for each capacitor value after running
MATLAB ten times.
average load modesize min power lossloss (MW)
0 0.099590.1 0.096730.2 0.094780.3 0.093730.4 0.093560.5 0.094260.6 0.095790.7 0.09206 middle0.8 0.094370.9 0.09436
1 0.0951
Table 1, mode results for each capacitor value
12
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 10.088
0.09
0.092
0.094
0.096
0.098
0.1
0.102
Series1
Figure 6, plot of the data in table 1
In order to get a smooth curve, I ran the program five more times. The minimum
power loss mode value for the 0.7 MVAR is then 0.09513 MW.
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 10.09
0.092
0.094
0.096
0.098
0.1
0.102
Figure 7, plot of the data in table 1 with new value at 0.7 MVAR
In this case, when capacitor size is equal to 0.4 MVAR, it gives the minimum power
loss of 0.09356 MW. Its mode corresponding tie switches are 69, 70, 14, 56 and 61.
13
Light load (0.5 average)
The following data is the mode result for each capacitor value after running
MATLAB ten times.
light load modesize min power lossloss (MW)
0 0.023710.1 0.022570.2 0.022290.3 0.022850.4 0.022430.5 0.022660.6 0.023580.7 0.025180.8 0.2527 middle0.9 0.02733 middle
1 0.3398 middle
Table 2, mode results for each capacitor value
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 10
0.05
0.1
0.15
0.2
0.25
0.3
0.35
0.4
Figure 8, plot of the data in table 2
14
If we ignore the values at 0.8 MVAR, 0.9 MVAR and 1.0 MVAR, we get figure 7.
From figure 7, when capacitor size is equal to 0.2 MVAR, it gives the minimum
power loss of 0.02229 MW. Its mode corresponding tie switches are 69, 70, 14, 56
and 61.
0 0.1 0.2 0.3 0.4 0.5 0.6 0.70.0205
0.021
0.0215
0.022
0.0225
0.023
0.0235
0.024
0.0245
0.025
0.0255
Figure 9 plot of the data in table 1 except the last three values
Heavy load (1.6 average)
The following data is the mode results for each capacitor size after running MATLAB
ten times.
15
heavy load modesize min power lossloss (MW)
0 0.272310.1 0.266850.2 0.262650.3 0.259430.4 0.257160.5 0.255820.6 0.255410.7 0.255890.8 0.257250.9 0.25947
1 0.26252
Table 3, mode results for each capacitor value
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 10.245
0.25
0.255
0.26
0.265
0.27
0.275
Series1
Figure 10, plot of the data in table 3
From the data, we can get a conclusion that when capacitor size is equal to 0.6
MVAR, it gives the minimum power loss 0.25541 MW for heavy load (1.6). Its mode
corresponding tie switches are 69, 70, 12, 57 and 73.
16
Summary and Conclusion
This report discusses and analyzes the data for distribution system operation
optimization through capacitor size allocation by genetic algorithm for the 69-bus test
System. I analyzed the 69-bus system for three different load: light load (0.5), average
load (1.0) and heavy load (1.6). For light load, when capacitor size is equal to 0.2
MVAR, it gives the minimum power loss 0.02229 MW. Its mode corresponding tie
switches are 69, 70, 14, 56 and 61. For average load, when capacitor size is equal to
0.4 MVAR, it gives the minimum power loss 0.09356 MW with following mode tie
switches: 69, 70, 14, 56 and 61. For heavy load, when capacitor size is equal to 0.6
MVAR, it gives the minimum power loss 0.25541 MW. Its mode corresponding tie
switches are 69, 70, 12, 57 and 73. Thus, the optimization capacitor size and tie
switches depends on the type of the load.
17
18
References
[1] A.M. Eldurssi, R. M. O’Connell. “A Fast Non-dominated Sorting Guided Genetic
Algorithm for Multi-Objective Power Distribution System Reconfiguration
Problem,” Power Systems, IEEE Transactions on, Volume:PP , Issue: 99, July
2014.
[2] A. M. Eldurssi, private communication.
[3] Guimaraes, M.A.N. et al., “Distribution systems operation optimisation through
reconfiguration and capacitor allocation by a dedicated genetic algorithm,”
Generation, Transmission & Distribution, IET, Volume:4 , Issue: 11, November
2010.
[4] C. Wang and Y. Gao, “Determination of power distribution network
configuration using non-revisiting genetic algorithm,” IEEE Trans.
Power Syst., vol. 28, no. 4, pp. 3638–3648, Nov. 2013.
[5] M. Assadian, M. M. Farsangi et al., “Optimal reconfiguration of distribution
system by PSO and GA using graph theory,” in Proc. 6th WSEAS Int. Conf.,
Istanbul, Turkey, May 2007, pp. 83–88.
19
[6] Y. T. Hsiao, “Multi-objective evolution programming method for
feeder reconfiguration,” IEEE Trans. Power Syst., vol. 19, no. 1, pp.
594–599, Feb. 2004.
[7] S. Civanlar, J. J. Grainger et al., “Distribution feeder
reconfiguration for loss reduction,” IEEE Trans. Power Del., vol. 3, no.
3, pp. 1217–1223, Jul. 1988.
[8] N. Rugthaicharoencheep and S. Sirisumrannukul, “Feeder reconfiguration with
dispatchable distributed generators in distribution systems by tabu search,” in
Proc. IEEE 44th Int. Universities Power Engineering Conf., 2009, pp. 1–5.