calculation of lossess

Upload: ashish-sawant

Post on 03-Apr-2018

220 views

Category:

Documents


0 download

TRANSCRIPT

  • 7/28/2019 Calculation of Lossess

    1/23

    1

    Calculation of lossess

    From the given cooling towerparameters,evaluate the following:

    ) Make up water requirement per day

    ) Evaporation loss

    i) Blow down loss

    Cooling water temperature : 37C

    Outlet water temperature : 32 C

    Drift losses : 0.1 %

    No. of concentrating cycles : 3

    Estimation of cooling tower losses:

    a) Drift loss : 0.1%

    b) Evaporation loss : Range (temp. difference, C) x 100/675

    ={(37-32)/675} x100=0.74%

    c) Blow down loss : Evaporation loss/(No. of concentrating cycle-1)

    ={0.74/(3-1)}=0.37%

    Total make up water requirement : 0.1 + 0.74 + 0.37 = 1.21%

    Cooling water circulation rate : 1260 m3/h

    Make up water requirement : 1260 x 0.0121 = 15.2 m3/h

  • 7/28/2019 Calculation of Lossess

    2/23

    2

    =364.8 m3/day

    By using a ruggedized portable ultrasonic leak detector, Mr. Brian Thorp, PdM

    Technician for Seminole Electric has been able to provide quick leak detection and

    repair on an aging steam condenser, allowing the utility to provide maximum powerduring high demand periods.

    In today's competitive electric power generation market attention must be given to

    improving the condensers operating efficiency. Steam turbines cannot attain their

    specified performance without an efficient condenser. Tube leaks that affect condenser

    performance are critical. Most condenser tubes are designed to last at least 30 years

    before replacement is required. Unfortunately, normal plant operation, changes in water

    chemistry and other unforeseen circumstances often create a much shorter life for

    tubes. Most condensers are overbuilt to allow for a certain percentage of tubes to be

    plugged when a leak is detected.

    When high sodium levels occur in the condensate, the water leaving the condenser

    must be polished through resin exchange and a boiler blow down. When this happens,

    cost is increased and the output of the power plant is reduced.

    Ultrasonic Technology

    Ultrasonic Leak detectors work like simple microphones that are sensitive to high

    frequency sounds ranging from 20 kHz (a kHz or kilohertz is one thousand cycles per

    second) to 100 kHz. To put that in perspective, most humans can hear up to 17-19 kHz.

  • 7/28/2019 Calculation of Lossess

    3/23

    3

    Using a sensitive piezoelectric crystal element as a sensor element, minute high

    frequency sound waves excite or flex the crystal creating an electrical pulse that is

    amplified and then heterodyned or translated into an audible frequency that the

    technician can hear through a pair of noise reduction headphones.

    As a leak passes from a high pressure to a low pressure, it creates turbulence. The

    turbulence generates a high frequency sound component, which is detected by the

    sensitive piezoelectric element, allowing the technician to quickly guide the instrument

    to the loudest point in order to pinpoint the leak.

    Several ultrasonic detectors use parabolic reflectors or elliptical reflectors to enhance

    and concentrate the leak signal, which can be useful when detecting small leaks or

    scanning at a great distance.

    The effects of condenser tube leaks

    The condenser is the largest heat exchanger in the condensate/feedwater network. It is

    located under the steam turbine generator. When the steam exits the turbine, it is

    passed over cool pipes that condense it back to liquid water. The purified water is

    pumped back

  • 7/28/2019 Calculation of Lossess

    4/23

    4

    to the boiler to be heated to steam again. The same purified water is boiled and

    condensed over and over.

    Keeping the condenser tubes in the condenser from leaking river water used for cooling

    into the steam or clean side of the condenser is a key to achieving optimum

    performance of the plant. Fresh water leaking into the purified system can wreak havoc

    by causing corrosion throughout the system and can significantly reduce operating life if

    not rapidly addressed.

    COAL DEMAND RATE FOR THERMAL POWER PLANT

    The poorer the plants overall efficiency (n), the plant load factor (PLF) and the coal

    quality being used, the higher will be the coal demand rate for Thermal Power

    Generation.

    The quality of coal is a function of its carbon content, which is appreciated to some

    extent by volatile matter content (an inducing force) and depreciated by moisture

    content and ash content (opposing forces) when analyzed on equilibrated basis (at 40degree C temperature and 60% Relative Humidity).

  • 7/28/2019 Calculation of Lossess

    5/23

    5

    The plant load factor (PLF) is the ratio of Average load and Maximum load on plant for a

    particular period, say, an hour or a day or a month or a year. In many cases, the

    maximum demand is less than the capacity of plant (designated as 50 MW or 110 MW

    or 210 MW or 500MW unit).

    The plants overall efficiency (n) is the ratio of theoretical heat rate (output 860 K.Cal.)

    and actual heat rate(input- GCV in K.Cal.) required for generation of 1 unit of

    power(Kwh). It depends on many variables and is usually around 27%. The theoretical

    heat rate can be calculated as follows:

    1 Kwh = 1000 x 1 x 60 x 60 Joule/Second

    = 3.6 x 1,000,000 Joule

    = 3.6 x 238.8 K.Cal (1 Mega Joule =238.8K.Cal)

    = 860 K.Cal.

    Input = 1 (in million K.Cal/hr.)= a+bL+cL2+dL3)

    Where L = Output or load in KWH and a, b, c and d are constants.

    Heat Rate = I/L = a/L+b+cL+dL2

    Plants overall = L/1.

    efficiency (n)

    Thus, there is a very complex calculation of exact heat input required and hence the

    exact specific consumption of coal. However, a hypothetical estimate of coal demand

    rate for Thermal Power can be arrived at for varying specific consumption of coal and

    PLF on pro-rata basis as given in the table below.

  • 7/28/2019 Calculation of Lossess

    6/23

    6

    COAL DEMAND RATE in T/100 MW/DAY

    SPECIFIC COAL CONSUMPTION IN KG/KWH

    PLF %

    Sp. Con. 0.6 0.65 0.70 0.75 0.80 0.85 0.90

    50

    55

    60

    720

    792

    864

    780

    858

    936

    840

    924

    1008

    900

    990

    1080

    960

    1056

    1152

    1020

    1122

    1224

    1080

    1188

    129665 936 1014 1092 1170 1248 1326 1404

    70

    75

    1008

    1080

    1092

    1170

    1176

    1260

    1260

    1350

    1344

    1440

    1428

    1530

    1512

    1620

    80 1152 1248 1344 1440 1536 1632 1728

    85

    90

    95

    100

    1224

    1296

    1368

    1440

    1326

    1404

    1482

    1560

    1428

    1512

    1596

    1680

    1530

    1620

    1710

    1800

    1632

    1728

    1824

    1920

    1734

    1836

    1938

    2040

    1836

    1944

    2052

    2160

    For Grade E Coal of

    UHV=3361 K.Cal/Kg

    GCV =4400 K.Cal/Kg

    For Grade F Coal of

    UHV=2401K.Cal/Kg

    GCV=3800 K.Cal. /kg

    For Grade G Coal of

    UHV =1301 K.Cal. /Kg

    32.6 30.1 27.9

    32.3

    26.1

    30.2

    24.4

    28.3

    23.0

    26.6

    33.7

    21.7

    25.1

    31.8

  • 7/28/2019 Calculation of Lossess

    7/23

    7

    GCV=3000 K.Cal/Kg.

    Required Overall efficiency (n) of Thermal Power Plant in

    %

    From the above table, it may be seen that the coal demand rate remains the same even

    if the quality of coal goes down provided the plants overall efficiency is improvedcorrespondingly (say, by about 3% - 4% for switching over from Grade E to F and about

    6% - 7% for F to G and Vice Versa.

    However, for referable gnomon, it may be worthwhile to remember that while the day-to-

    day demand of coal at 80% PLF may be around 1500T/day/100 MW the annual

    demand at 62.5%PLF (National average of 1996-97 upto Dec.96) will be roughly 4

    million T/1000MW for E Grade of coal at about 27% plant efficiency).

    Utilisation of installed generating Capacity

  • 7/28/2019 Calculation of Lossess

    8/23

    8

    With the introduction of new design of generating units, certain difficulties arose in their

    efficient operation and maintenance. The availability of coal in the country is such that

    the higher grades of coal, which have higher calorific value, have been exhausted and

    progressively lower grades of coal are being made available for electricity generation in

    the power stations. This had resulted into operational problems with the boilers

    designed for higher grades of coal and also put more pressure on coal handling plants

    etc. As a result of these technical and managerial problems, the utilisation level of coal

    based power stations in the country declined in the late 1970s and early 1980

    Besides quantity, the quality of Indian coal has been a major problem and concern for

    the power supply industry. With ash content of coals being in the range of 30-50%, the

    beneficiation of coal assumes special significance. Establishment of washeries

    therefore assumes a great importance and country has t o address this problem

    seriously.

    Energy extract ion from coal

    The two fundamental processes for extraction of energy from coal are (i) Direct Solid

    Combustion such as conventional Pulverised Coal (PC) Combustion or the emerging

    Fluidised Bed Combustion (FBC) and (ii) Indirect combustion through Coal Gasification

    followed by coal gas combustion. Fluidised Bed Combustor is a three-in-one

    device characterised by highly desirable features of multi-fuel capability,

    pollution (SO2 and Nox) control, and energy conservation. All the four members of

    this family, namely Atmospheric Fluidised Bed Combustor (AFBC), Circulating Fluidised

    Bed Combustor (CFBC), Pressurised Fluidised Bed Combustor (PFBC) andPressurised Circulating Fluidised Bed Combustor (PCFBC) have the potential for clean

    power generation. Additionally, PFBC and PCFCB systems operating in a combined

    cycle mode (Rankine and Brayton) have the potential for overall plant efficiencies of the

    order of 40-45% compared to 33-37% efficiencies offered by power plants based on

    Conventional PC firing, AFBC and CFBC operating on a single (Rankine) cycle.

  • 7/28/2019 Calculation of Lossess

    9/23

    9

    EFFICIENCY (STATION HEAT RATE) OF COAL/LIGNITE BASED

    THERMAL POWER STATION

    Station Heat Rate (SHR) is an important factor to assess the efficiency of a thermal

    power station. Efficiency of TPS is a function of station heat rate and it is inversely

    proportional to SHR. If SHR reduces, efficiency increase, resulting in fuel saving.

    Station heat rate improvement also helps in reducing pollution from TPS. On

    monitoring, the data of station heat rate parameters had been received from, 54 Nos.

    Thermal Power Stations during 2000-01. The data of operating station heat rate

    parameters so received have been compiled & analysed for instituting an incentive

    scheme on Improved Station Heat Rate (SHR) and have been compared with design

    SHR of the above thermal power station, for the year 2000-01 . The analysis of station

    heat rate so carried out has been highlighted in Annexures- I to V. The analysis of

    Station Heat parameters as given below has been carried out broadly in two categories

    of the stations with SHR variation between (a) 0-10% and (b) >10%. The stations under

    0-10% categories have been considered as efficient and greater than 10% as poorly

    operating. All the stations analysed have used coal as primary fuel to generate power

    and oil as secondary fuel for starting purposes.. The analysis has been carried out on

    the station basis. Stations may comprise of any size of units.

    The following assumptions have been taken for the analysis of station heat rate

    ASSUMPTIONS:-

    1. Analysis of only those power stations has been carried out where data of at least 9

    months operation was available.

  • 7/28/2019 Calculation of Lossess

    10/23

    10

    2. Design station heat rate has been evaluated based on design data of turbine heat

    rate and boiler efficiency as submitted by TPS and compared with operating

    station heat.

    3. The data of various parameters of station heat rate such as fuels calorific value

    generation, fuel consumption etc. have been taken from TPS authorities / SEBs

    /utilities on monthly basis.

    4. Actual oil consumption is converted into equivalent coal consumption and added to

    actual coal consumption to make it as effective coal for calculating heat rate w.r.t.

    coal GVC on monthly basis as oil consumption is less compared to coal.

    Weighted average of coal GVC and oil GCV have been computed yearly for

    calculating heat rate for the year.

    5. Oil GCV has been assumed as 10,000 Kcal/1 in case any station has not submitted

    the data of oil GVC.

    6. All India figures are indicated on weighted average basis with respect to generation of

    the year for available data for the year 2000-01.

    3.0 SALIENT FEATURES OF THE GROSS STATION HEAT RATE DATA ANALYSIS:

    3.1 The gross Station Heat Rate (SHR) deviation of operating SHR with respect

    to design SHR for the year 2000-01 given at Annexture-I & II and main

    highlights of outcomes for the years 2000-01 is given below.

  • 7/28/2019 Calculation of Lossess

    11/23

    11

    a) ALL INDIA STATION HEAT RATE

    Year Capacity(M

    W)

    Design

    SHR

    (Kcal/kwh)

    Operating

    SHR

    (Kcal/Kwh)

    % deviation %

    Improveme

    nt over

    2000-01

    1999-00 - 2422.51 2914 20.28 -

    2000-01 33060.5 2408.34 2763 14.71 -

    Above table indicates that the estimated weighted average operation SHR at All India

    basis are as 2914 Kcal/Kwh, and 2763 Kcal/Kwh for the year 1999-2000 and 2000-01

    respectively. This analysis indicates that there is significant improvement in operating

    station heat rate during 2000-01 with respect to 1999-00. Similar is the case with also

    SHR variation for 1999-2000 and 2000-01 w.r.t. design heat rate which would be

    evident from Chart- ALL INDIA STATION HEAT RATE;

    (b) REGION WISE STATION HEAT RATE

    Region Years Design SHR Operating

    SHR

    % Deviation %Improvem

    ent w.r.t.

    preceding

    year

    Northern 2000-2001 2483.18 2972.27 19.7 -

    Southern 2000-2001 2434.38 2722.36 11.83 -

    Western 2000-2001 2357.02 2612.17 10.83 -

    Eastern 2000-2001 2381.75 3306.02 38.81 -

    The above table indicates that the OPSHR level of Northern Region as 2972.27

    K.Cal/Kwh the years 2000-2001. The OPSHR of Southern Region indicated as 2722.36

  • 7/28/2019 Calculation of Lossess

    12/23

    12

    Kcal/Kwh for the years 2000-01. Western Region and Eastern Region do not show any

    improvement in OPSHR

    c) The number of efficient power stations during the years 2000-01 whose SHR

    deviation w.r.t. design heat rate in the range of two categories (0-5%, 5-10%) are given

    in the following table.Details are given at Annexure-II.

    Total station analysed 54

    No. of stations in the range of SHR deviation (0-5%) 7

    No. of stations in the range of SHR deviation (5-10%) 9

    Total efficient stations SI. No.(2+3) in the range of (0-10%) 16

    No. of stations with SHR deviation more than 10% 38

    d) As per Annexure-I & II, it is observed that, Ib Valley (OPGC), Sikka (RPL),

    Bhusawal (MSEB) have been assessed as best station for 2000-2001 with SHR

    deviations 0.34%, 1.65% and 3.41% respectively.

    e) Barauni, Nellore, Chandrapura (DVC), Paricha and Santaldih (WBSEB) have been

    assessed as poorly performing TPS with SHR deviation more than 60% and up to

    103%.

    f) About 40 stations at an average of last three years are operating at very poor SHR

    having variations in SHR greater than 10% and up to 100%. These stations need proper

    monitoring and Energy Audit implementation.

    g) Efficiency of all Stations is highlighted in Annexure-IV , it indicates that the efficiency

    of Thermal Power Stations varies from 19% to 37% for the Year, 2000-2001. Dahanu

    (BSES), Chandrapur (MSEB). Rayalseema & Ib valley are some of the stations which

    have recorded their efficiency in the range of 35% to 37%.

    LEVEL OF IMPROVEMENT

  • 7/28/2019 Calculation of Lossess

    13/23

    13

    Level of Improvement in Station Heat Rate for the year 1999-00 & 2000-

    2001 with respect to preceding year is given at Annexure-III.

    The outcomes are given below:

    4.1 The Station Heat Rate is improving consistently form the year 2000-01

    with respect to preceding year including efficient Station as well as poor

    Station. The level of improvement varies form 0.03% to 20.5% over the

    preceding year. The numbers of Stations showing improvement are given

    in the following table:

    Year No. of Stations No. of Improved Level of % of improved

    Analysed Stations Improvement(%) Stations

    2000-01 54 27 0.12% - 14.4% 50%

    UNIT CAPACITY GROUPWISE ANALYSIS

    Annexure-V indicates that

    5.1 The operating heat rate of the 250 MW group stations is 2313

    Kcal/kWh for the year 2000-2001

    5.2 The operating station heat rate of the 200/210 MW group stations is as

    2678 Kcal/kWh for the year 2001-01.

    5.3 The operating station heat rate of67.5 MW group stations are as 3243

    Kcal/kWh for the year 2000-01 .

  • 7/28/2019 Calculation of Lossess

    14/23

    14

    5.4 The operating station heat rate of 62.5 Mw group stations are as

    3050.48 Kcal/kWh for the year 2000-01.

    5.5 The operating stations heat rate of (30-140) MW combination group

    stations are as 3562 Kcal/kWh for the year 2000-01 .

    5.6 There is no significant improvement in operating station heat rate of

    the group of 250MW, 120MW, 110MW, 60MW, 55MW, (30-500)

    MW combination and 30 MW.

  • 7/28/2019 Calculation of Lossess

    15/23

    15

  • 7/28/2019 Calculation of Lossess

    16/23

    16

  • 7/28/2019 Calculation of Lossess

    17/23

    17

    MAJOR FACTORS AFFECTING HEAT RATE

    IT SHOULD BE KNOWN

    Under normal circumstances the system efficiency of a power plant may be improved

    only by 0.5% to 1% through additional energy efficiency measure.

    There are success stories and reports about power plants in India that reduced Gross

    Heat Rate i.e. specific energy consumption per kWh generated, by 20% within 1 year.

    It is true that under normal circumstances, the system efficiency of a power plant may

    be improved only by 0.5 % to 1%, as the overall power plant efficiency calculations

  • 7/28/2019 Calculation of Lossess

    18/23

    18

    includes the losses in the condenser, which is maximum for a steam cycle (or combined

    cycle) power plant, and mostly this system operates up to the expectation and nothing

    much can be done, if already the power plant has a good maintenance management

    system. The Turbine and Generator efficiency cannot be increased much. So the

    efficiency gain comes from the different measures like reducing the boiler losses by

    taking various actions in this regard.

    Gross Unit Heat Rate=

    Gross Turbin e Heat Rate

    Boi lerEff ic iency

    Heat Rate depends on a lot of factors, including the boiler efficiency. It not only

    depends on the boiler efficiency but the other factors like Steam temperature, Flue

    gas losses, Make up losses, Unburnt carbon losses, Fuel properties and overall

    the ageing factor of the TURBINE.

    If the conditions are already up to the maximum achievable limits, it may not be possible

    to reduce the heat rate by as much as 20%. But if the plant is not being maintained up

    to the mark and the operational parameters are not being maintained, it is certainly

    possible to do by taking various measures.

    First: Ageing of Turbine

    The manufacturers guaranteed heat rate for equipment like Turbine also has a gradually

    aging tendency. The ageing increases the heat rate. This heat rate deterioration is on

    account of increase of clearances, disturbing of seals; deposits on turbine blade etc. To

    arrest the deterioration and to bring back the heat rate to its design value the only

    solution available is to take the turbine under Capital Overhaul.

  • 7/28/2019 Calculation of Lossess

    19/23

    19

    If flow path correction, re-adjustment of clearances between the stationary & moving

    parts, refining if required will help in bringing back the heat rate to its original value. The

    quality of work carried out during the overhaul, will play vital role in heat rate

    improvement. The turbine heat rate is further affected by boiler efficiency to arrive at the

    station heat rate. Similar exercise carried out at the boiler to improve efficiency will

    resulting heat rate improvement in station. The equipment like turbine has a gradually

    ageing tendency. The ageing increases the heat rate over a period of time.

    As per BHEL, after the major overhauling, the turbine performance is considered

    to be as good as new turbine and the ageing calculation again starts from the

    commissioning of the turbine after the major overhaul.

    Second:Parameters other than ageing of turbine, which affects

    the Gross Heat Rate.

    For a designed 250 MW unit, the approximation of the parameters can be as

    follows:

    1. Main Steam and Reheat temperature:

    For every 1drop in Main Steam/ R H temperature than the designed value of 537 C,

    causes a heat loss ofapprox 0.67 KCal/KWh,

    2. Main Steam Pressure

    For every 1 KG/CM2 drop in Main Steam Pressure at Turbine Inlet than the design

    value i.e 150 KG/CM2 causes a heat loss of approx. 1.31 KCal/KWh

    3. Flue gas temperature

  • 7/28/2019 Calculation of Lossess

    20/23

    20

    Forevery 1C rise in Flue gas temperature at Air Preheater outlet than the design

    value i.e 134 C causes a heat loss of approx. 1.13 KCal/KWh

    The Inputs required for Calculation of Heat Rate are:

    Load (MW)

    MS flow (Feed water flow to Eco.) ton/h

    MS temperature Deg C

    MS pressure kg/sq.cm

    Reheater Flow ton/h

    CRH temperature Deg C

    CRH pressure kg/sq cm

    Reheater temperature Deg C

    Reheater Pressure kg/sq cm

    FW Temp. at Eco.inlet Deg C

    FW pre. Eco.inlet kg/sq.cm

    Condenser vacuum

    Auxiliary Power Consumption %

  • 7/28/2019 Calculation of Lossess

    21/23

    21

    MS/CRH/HRH/FW Enthalpy kJ/kg K

    By using these inputs actual heat rate is calculated. If a power plant is maintaining

    these parameters up to the maximum possible conditions and there is no scope

    for further improvement, it may not be possible to improve the heat rate any further by

    a larger extent, although the conditions are not always ideal and there is always a scope

    for improvement somewhere or the other. If the power plant is old or not being

    maintained properly or even the operational parameters are not being monitored

    properly, surely the heat rate will go up for that plant. Then by proper monitoring and

    control and by following a stringent maintenance management system, the parameters

    can be improved to have a moving trend towards achieving the design value and this

    will lead to improvement (reduction) in the heat rate for that plant. So it is not such that

    heat rate cannot be reduced by 20%. The only thing is that it totally depends on the

    operating condition of the plant and a will to achieve that. There are instances where not

    only heat rate but also several other parameters have been improved by a large extent

    by NTPC in the cases where it has taken over the plants from SEBs.

    Third: Loading of the plant

    This factor also plays a very important role in the gross unit heat rate of the power

    station.Generally a power plant operates consistently at full or rated capacity, as it feeds

    to the grid or sell the power to a larger base of consumer like State Electricity Boards

    and the load variation is much less, unless otherwise necessary. So maintaining the

    various parameters required for obtaining a good heat rate is not a much problem,

    assuming the other conditions in the plant being good.

    But in the plant like ours, the generation has to be varied as per the demand of the

    consumers, which have a general tendency to fall down during night hours and

    again move up in the morning hours, especially in the winter season. So to match the

    demand, the power station has to back down the generation below the rated

  • 7/28/2019 Calculation of Lossess

    22/23

    22

    capacity of the plant (say our load goes down to 420-450 MW, whereas the rated

    capacity is 500 MW) during night hours and again move up in the day time.. During this

    process of variation of load, while going down or going up, the parameters affecting

    the HEAT RATE cannot be kept at the constant level, as the demand have to be

    matched with the generation at every point of time. So a variation occurs in the

    various parameters affecting the Heat Rate. In this condition it is very difficult to control

    the heat rate and keep it down to the expected level. As we have seen above the affect

    of variation of some parameters on the heat rate, it can be easily understood that the

    variation in these parameters is going to deteriorate the heat rate rather than to lower it.

    So this factor cannot be neglected.

    Fourth: Average load of the plant.

    Also if the plant is run at a lower load than its rated capacity, not only the other

    parameters will be affected but also the auxiliary power consumption of the plant

    will be higher than the somewhat designed aux power consumption, which will

    affect (increase) the sent out heat rate, the calculation and projection of which is still not

    prevalent in case of Indian power plant. In foreign countries, this factor is very well taken

    into account for the calculation and benchmarking purposes. So overall it can be seen

    that Whether the HEAT RATE CAN BE IMPROVED & TO WHAT EXTENT , depends

    totally on several factors related to the calculation of Heat Rate and not a single factor.

    But yes, it is true that that still a lot of plants are there in India, whose heat rate can be

    improved, if so desired by taking various actions, as is clear from the above explanation.

    Fifth: Tripping of the Unit

    Last but not the least is the condition of unit tripping. If by proper monitoring,

    maintenance and other preventive measures, the trippings are brought to the

    minimum, the heat rate improvement can be achieved. After the tripping, when the unit

    is lighted up again, a loss called Start up loss come into picture, which increases the

    heat rate as the quantum of loss increases. So if avoidable Unit trippings are arrested,

  • 7/28/2019 Calculation of Lossess

    23/23

    23

    this loss will become less and the improvement in Heat Rate can be achieved. Thus we

    can see that the various conditions, under which there is deterioration in the Heat Rate,

    can be possibly controlled to improve this important aspect of a power plant.