calculation for the value of stabilizing resistor ref setting

17
1.Calculation For The Value of Stabilizing Resistor_1000kVA Calculation for the Value of Stabilizing Resistor & Relay Setting Enter the values on cells highlighted in white,Result will be displayed in cells highlighted in Green & general datas in Blue The CT requirements are class X with a knee point voltage in excess of twice the setting voltage. Setting: The setting volatge may be determined by: V S =I F /n [R ct + 2R L + R a ] V S = Setting Voltage I S = Setting Current I F = Fault level in CT Primary n = CT Ratio R ct = Resistance of CT at operating temperature R L = Lead resistance at operating temperature R a = Additional resistance due to relay,contact/connection resistance etc at operating temperature The Full CT requirement is therefore : Class X, ratio N,CT resistance R ct and knee point voltage > 2 x V s Dated:3/12/2011 Transformer Details TRF Capacity = 1000 kVA TRF Primary = 11000 Volts TRF Secondary = 400 Volts TRF Impedance = 5% CT Primary(n) = 2000 Amps CT Secondary = 1 Amps n = 2000 CT Secondary wiring Length = 30 Meters Neutral CT traveling distance CT Secondary wiring size = 2.5 Sq.mm Resistance of conductor = 7.41 Ohms / KM Refer the chart CT resistance(R CT ) = 8 Ohms CT Manufacturer to advice CT magnitization current(I m ) = 64 mA CT Manufacturer to advice Fault level in CT Primary: I F = TRF Capacity x 1000 Example: I F =1600 x 1000 / 415 x 1.732 x 0.06 = 37100 Amps TRF Secondary x 1.732 x Imp I F = 28868 Amps Dated:3/12/2011

Upload: 1453h

Post on 08-Nov-2014

175 views

Category:

Documents


19 download

TRANSCRIPT

Page 1: Calculation for the Value of Stabilizing Resistor REF Setting

1.Calculation For The Value of Stabilizing Resistor_1000kVA

Calculation for the Value of Stabilizing Resistor & Relay SettingEnter the values on cells highlighted in white,Result will be displayed in cells highlighted in Green & general datas in Blue

The CT requirements are class X with a knee point voltage in excess of twice the setting voltage.

Setting:The setting volatge may be determined by:

VS = IF/n [Rct + 2RL + Ra ]VS = Setting VoltageIS = Setting CurrentIF = Fault level in CT Primaryn = CT Ratio

Rct = Resistance of CT at operating temperatureRL = Lead resistance at operating temperatureRa = Additional resistance due to relay,contact/connection resistance etc at operating temperature

The Full CT requirement is therefore : Class X, ratio N,CT resistance Rct and knee point voltage > 2 x Vs

Dated:3/12/2011

Transformer DetailsTRF Capacity = 1000 kVATRF Primary = 11000 Volts

TRF Secondary = 400 VoltsTRF Impedance = 5 %

CT Primary(n) = 2000 AmpsCT Secondary = 1 Amps

n = 2000CT Secondary wiring Length = 30 Meters Neutral CT traveling distance

CT Secondary wiring size = 2.5 Sq.mmResistance of conductor = 7.41 Ohms / KM Refer the chart

CT resistance(RCT) = 8 Ohms CT Manufacturer to adviceCT magnitization current(Im) = 64 mA CT Manufacturer to advice

Fault level in CT Primary:IF = TRF Capacity x 1000 Example: IF=1600 x 1000 / 415 x 1.732 x 0.06 = 37100 Amps

TRF Secondary x 1.732 x ImpIF = 28868 Amps

Dated:3/12/2011

Page 2: Calculation for the Value of Stabilizing Resistor REF Setting

1.Calculation For The Value of Stabilizing Resistor_1000kVA

Lead resistance:RL = CT Secondary wiring Length x Resistance of conductor per meterRL = 0.22 Ohms Example: RL=20 x 7.41/1000 = 0.15 Ohms

Additional Resistance:Ra is usually ignored,but may have the value 0.01ohms

Ra = 0.01 OhmsVS = IF/n [Rct + 2RL + Ra ] Example: VS=37000/2500 [8 + 2(0.15) + 0.01] = 123 VoltsVS = 122 Volt

CT Knee Point voltage must be in excess of 2 x VS:

VKn = 244 Volts Example: Vkn=2 x 123 = 246 Volt

Required Loop Resistance Value:RS = VS / ISIS = 40 %IS = 0.4 Amps Example: IS=0.2 x 1(CT Secondary Amps) = 0.2A

Dated:3/12/2011

IS = 0.4 Amps Example: IS=0.2 x 1(CT Secondary Amps) = 0.2AVS = 122 Volts RS=123 / 0.2 = 615 OhmsRS = 305 Ohms

With the MREF relay the relay burden is less than 0.005VA and may therefore be neglectedRstab = 305 Ohms Stabilizing Resistor Value

Note:Under Fault Condition this resistor must pass

Value = 14.43 Amps Example: 37000 / (2500/1) = 14.8A

Peak Voltages:Under Fault conditions the peak voltage ignoring saturation of the C.T given by

VP = IF/n [Rct + 2RL + Ra + Rstab + Rr ] Rr = Relay resistance can be neglected= 4524 Volts Example: VP=37100/2500 [8 + 2(0.15) +0 .01 + 615] = 9250 Volt

VP = 4.524 KV

Dated:3/12/2011

Page 3: Calculation for the Value of Stabilizing Resistor REF Setting

1.Calculation For The Value of Stabilizing Resistor_1000kVA

Peak Voltage including saturation of the CT given by Vpk Value must be below approximately 3KV

Vpk = 2 √ 2 Vkn [ Vp - Vkn ] Example: Vpk=2 √ 2 246 [ 9250 - 246 ] = 4209 Volt= 2890 Volt

Vpk = 2.89 KV

In Case the value exceed 3KV,we must adjust the setting current and re-caulculate as below:If the VPK value was less than 3KV please fill the same setting current value so as to attain the P.O.C value.

RS = VS / IS Example: IS=0.4 x 1 = 0.4AIS = Setting Current ( May be taken in % ) RS=123 / 0.4 = 307.5 OhmsIS = 20 % Enter the value until VPK falls below 3KVIS = 0.2 Amps

VS = 122 VoltsRS = 610 Ohms

Rstab = 610 Ohms Stabilizing Resistor ValueVP = IF/n [Rct + 2RL + Ra + Rstab + Rr ] Rr = Relay resistance can be neglected

8927 V lt

Dated:3/12/2011

= 8927 VoltVP = 8.927 KV

Vpk = 2 √ 2 Vkn [ Vp - Vkn ]= 4117 Volt

Vpk = 4.12 KV

Effective setting [ Primary operating Current ] 20 %Setting CurrentP.O.C = n [N x Im + Inr + Is]

N = The number of connected CTsIm = The magnitization current for a single CT at setting VoltageIs = Setting current

Inr = Non Linear resistor current at setting VoltageInr = [(Vs)

/ (MI)]4

Inr = 0 Amps Inr Value is Zero since Non-Linear Resistor not used.P.O.C = 912 Amps Example: POC = 2500 [(4 x 0.013) + 0 + 0.4] = 1130Amps

% of Transformer rating = 45.6 %As per ESI 48-3 standard,the fault current setting shall be between 10% to 60% of the rated current of the winding.

Dated:3/12/2011

Page 4: Calculation for the Value of Stabilizing Resistor REF Setting

1.Calculation For The Value of Stabilizing Resistor_1000kVA

Limiting Peak VoltageIf it is not possible to limit the peak voltage,by careful selection of setting current,a voltage dependent Non-Linear resistor should be used.A Non-Linear Resistor Must be used with 40 % setting

Vp = MV [ IF / n ]0.25

MV = Coefficient Value Refer the chartMV = 900 Example: Vp=450[3700/2500]0.25 = 883Volt

IF = 28868 Ampsn = 2000 Amps

Vp = 1754 Volt

Inr = [(Vs) / (MI)]4

Vs = 122 VoltMI = Coefficient Value

= 900Inr = 0.0003 Amps Example: Inr =[123/450]4 =0.0056Amps

Dated:3/12/2011

P.O.C = 1312.6 Amps Example: POC = 2500 [(4 x 0.013) + 0.0056 + 0.2] = 644Amps% of Transformer rating = 65.63 %

As per ESI 48-3 standard,the fault current setting shall be between 10% to 60% of the rated current of the winding.

Dated:3/12/2011

Page 5: Calculation for the Value of Stabilizing Resistor REF Setting

1.Calculation For The Value of Stabilizing Resistor_1000kVA

Dated:3/12/2011Dated:3/12/2011

Page 6: Calculation for the Value of Stabilizing Resistor REF Setting

Calculation for the Value of Stabilizing Resistor & Relay SettingEnter the values on cells highlighted in white,Result will be displayed in cells highlighted in Green & general datas in Blue

The CT requirements are class X with a knee point voltage in excess of twice the setting voltage.

Setting:The setting volatge may be determined by:

VS = IF/n [Rct + 2RL + Ra ]VS = Setting VoltageIS = Setting CurrentIF = Fault level in CT Primaryn = CT Ratio

Rct = Resistance of CT at operating temperatureRL = Lead resistance at operating temperatureRa = Additional resistance due to relay,contact/connection resistance etc at operating temperature

The Full CT requirement is therefore : Class X, ratio N,CT resistance Rct and knee point voltage > 2 x Vs

Transformer DetailsTRF Capacity = 2000 kVATRF Primary = 11000 Volts

TRF Secondary = 400 VoltsTRF Impedance = 6.3 %

CT Primary(n) = 4000 AmpsCT Secondary = 1 Amps

n = 4000CT Secondary wiring Length = 30 Meters Neutral CT traveling distance

CT Secondary wiring size = 2.5 Sq.mmResistance of conductor = 7.41 Ohms / KM Refer the chart

CT resistance(RCT) = 17 Ohms CT Manufacturer to adviceCT magnitization current(Im) = 64 mA CT Manufacturer to advice

Fault level in CT Primary:IF = TRF Capacity x 1000 Example: IF=1600 x 1000 / 415 x 1.732 x 0.06 = 37100 Amps

TRF Secondary x 1.732 x ImpIF = 45823 Amps

Page 7: Calculation for the Value of Stabilizing Resistor REF Setting

Lead resistance:RL = CT Secondary wiring Length x Resistance of conductor per meterRL = 0.22 Ohms Example: RL=20 x 7.41/1000 = 0.15 Ohms

Additional Resistance:Ra is usually ignored,but may have the value 0.01ohms

Ra = 0.01 OhmsVS = IF/n [Rct + 2RL + Ra ] Example: VS=37000/2500 [8 + 2(0.15) + 0.01] = 123 VoltsVS = 200 Volt

CT Knee Point voltage must be in excess of 2 x VS:

VKn = 400 Volts Example: Vkn=2 x 123 = 246 Volt

Required Loop Resistance Value:RS = VS / ISIS = 20 %IS = 0.2 Amps Example: IS=0.2 x 1(CT Secondary Amps) = 0.2AIS = 0.2 Amps Example: IS=0.2 x 1(CT Secondary Amps) = 0.2A

VS = 200 Volts RS=123 / 0.2 = 615 OhmsRS = 1000 Ohms

With the MREF relay the relay burden is less than 0.005VA and may therefore be neglectedRstab = 1000 Ohms Stabilizing Resistor Value

Note:Under Fault Condition this resistor must pass

Value = 11.46 Amps Example: 37000 / (2500/1) = 14.8A

Peak Voltages:Under Fault conditions the peak voltage ignoring saturation of the C.T given by

VP = IF/n [Rct + 2RL + Ra + Rstab + Rr ] Rr = Relay resistance can be neglected= 11656 Volts Example: VP=37100/2500 [8 + 2(0.15) +0 .01 + 615] = 9250 Volt

VP = 11.656 KV

Page 8: Calculation for the Value of Stabilizing Resistor REF Setting

Peak Voltage including saturation of the CT given by Vpk Value must be below approximately 3KV

Vpk = 2 √ 2 Vkn [ Vp - Vkn ] Example: Vpk=2 √ 2 246 [ 9250 - 246 ] = 4209 Volt= 6002 Volt

Vpk = 6 KV

In Case the value exceed 3KV,we must adjust the setting current and re-caulculate as below:If the VPK value was less than 3KV please fill the same setting current value so as to attain the P.O.C value.

RS = VS / IS Example: IS=0.4 x 1 = 0.4AIS = Setting Current ( May be taken in % ) RS=123 / 0.4 = 307.5 OhmsIS = 20 % Enter the value until VPK falls below 3KVIS = 0.2 Amps

VS = 200 VoltsRS = 1000 Ohms

Rstab = 1000 Ohms Stabilizing Resistor ValueVP = IF/n [Rct + 2RL + Ra + Rstab + Rr ] Rr = Relay resistance can be neglected

11656 V lt= 11656 VoltVP = 11.656 KV

Vpk = 2 √ 2 Vkn [ Vp - Vkn ]= 6002 Volt

Vpk = 6 KV

Effective setting [ Primary operating Current ] 20 %Setting CurrentP.O.C = n [N x Im + Inr + Is]

N = The number of connected CTsIm = The magnitization current for a single CT at setting VoltageIs = Setting current

Inr = Non Linear resistor current at setting VoltageInr = [(Vs)

/ (MI)]4

Inr = 0 Amps Inr Value is Zero since Non-Linear Resistor not used.P.O.C = 1824 Amps Example: POC = 2500 [(4 x 0.013) + 0 + 0.4] = 1130Amps

% of Transformer rating = 45.6 %As per ESI 48-3 standard,the fault current setting shall be between 10% to 60% of the rated current of the winding.

Page 9: Calculation for the Value of Stabilizing Resistor REF Setting

Limiting Peak VoltageIf it is not possible to limit the peak voltage,by careful selection of setting current,a voltage dependent Non-Linear resistor should be used.A Non-Linear Resistor Must be used with 20 % setting

Vp = MV [ IF / n ]0.25

MV = Coefficient Value Refer the chartMV = 900 Example: Vp=450[3700/2500]0.25 = 883Volt

IF = 45823 Ampsn = 4000 Amps

Vp = 1656 Volt

Inr = [(Vs) / (MI)]4

Vs = 200 VoltMI = Coefficient Value

= 900Inr = 0.0024 Amps Example: Inr =[123/450]4 =0.0056Amps

P.O.C = 1833.6 Amps Example: POC = 2500 [(4 x 0.013) + 0.0056 + 0.2] = 644Amps% of Transformer rating = 45.84 %

As per ESI 48-3 standard,the fault current setting shall be between 10% to 60% of the rated current of the winding.

Page 10: Calculation for the Value of Stabilizing Resistor REF Setting
Page 11: Calculation for the Value of Stabilizing Resistor REF Setting

Calculation for the Value of Stabilizing Resistor & Relay SettingEnter the values on cells highlighted in white,Result will be displayed in cells highlighted in Green & general datas in Blue

The CT requirements are class X with a knee point voltage in excess of twice the setting voltage.

Setting:The setting volatge may be determined by:

VS = IF/n [Rct + 2RL + Ra ]VS = Setting VoltageIS = Setting CurrentIF = Fault level in CT Primaryn = CT Ratio

Rct = Resistance of CT at operating temperatureRL = Lead resistance at operating temperatureRa = Additional resistance due to relay,contact/connection resistance etc at operating temperature

The Full CT requirement is therefore : Class X, ratio N,CT resistance Rct and knee point voltage > 2 x Vs

Transformer DetailsTRF Capacity = 1600 kVATRF Primary = 11000 Volts

TRF Secondary = 400 VoltsTRF Impedance = 6.3 %

CT Primary(n) = 3000 AmpsCT Secondary = 1 Amps

n = 3000CT Secondary wiring Length = 30 Meters Neutral CT traveling distance

CT Secondary wiring size = 2.5 Sq.mmResistance of conductor = 7.41 Ohms / KM Refer the chart

CT resistance(RCT) = 12 Ohms CT Manufacturer to adviceCT magnitization current(Im) = 64 mA CT Manufacturer to advice

Fault level in CT Primary:IF = TRF Capacity x 1000 Example: IF=1600 x 1000 / 415 x 1.732 x 0.06 = 37100 Amps

TRF Secondary x 1.732 x ImpIF = 36658 Amps

Page 12: Calculation for the Value of Stabilizing Resistor REF Setting

Lead resistance:RL = CT Secondary wiring Length x Resistance of conductor per meterRL = 0.22 Ohms Example: RL=20 x 7.41/1000 = 0.15 Ohms

Additional Resistance:Ra is usually ignored,but may have the value 0.01ohms

Ra = 0.01 OhmsVS = IF/n [Rct + 2RL + Ra ] Example: VS=37000/2500 [8 + 2(0.15) + 0.01] = 123 VoltsVS = 152 Volt

CT Knee Point voltage must be in excess of 2 x VS:

VKn = 304 Volts Example: Vkn=2 x 123 = 246 Volt

Required Loop Resistance Value:RS = VS / ISIS = 50 %IS = 0.5 Amps Example: IS=0.2 x 1(CT Secondary Amps) = 0.2AIS = 0.5 Amps Example: IS=0.2 x 1(CT Secondary Amps) = 0.2A

VS = 152 Volts RS=123 / 0.2 = 615 OhmsRS = 304 Ohms

With the MREF relay the relay burden is less than 0.005VA and may therefore be neglectedRstab = 304 Ohms Stabilizing Resistor Value

Note:Under Fault Condition this resistor must pass

Value = 12.22 Amps Example: 37000 / (2500/1) = 14.8A

Peak Voltages:Under Fault conditions the peak voltage ignoring saturation of the C.T given by

VP = IF/n [Rct + 2RL + Ra + Rstab + Rr ] Rr = Relay resistance can be neglected= 3867 Volts Example: VP=37100/2500 [8 + 2(0.15) +0 .01 + 615] = 9250 Volt

VP = 3.867 KV

Page 13: Calculation for the Value of Stabilizing Resistor REF Setting

Peak Voltage including saturation of the CT given by Vpk Value must be below approximately 3KV

Vpk = 2 √ 2 Vkn [ Vp - Vkn ] Example: Vpk=2 √ 2 246 [ 9250 - 246 ] = 4209 Volt= 2944 Volt

Vpk = 2.94 KV

In Case the value exceed 3KV,we must adjust the setting current and re-caulculate as below:If the VPK value was less than 3KV please fill the same setting current value so as to attain the P.O.C value.

RS = VS / IS Example: IS=0.4 x 1 = 0.4AIS = Setting Current ( May be taken in % ) RS=123 / 0.4 = 307.5 OhmsIS = 20 % Enter the value until VPK falls below 3KVIS = 0.2 Amps

VS = 152 VoltsRS = 760 Ohms

Rstab = 760 Ohms Stabilizing Resistor ValueVP = IF/n [Rct + 2RL + Ra + Rstab + Rr ] Rr = Relay resistance can be neglected

9439 V lt= 9439 VoltVP = 9.439 KV

Vpk = 2 √ 2 Vkn [ Vp - Vkn ]= 4713 Volt

Vpk = 4.71 KV

Effective setting [ Primary operating Current ] 20 %Setting CurrentP.O.C = n [N x Im + Inr + Is]

N = The number of connected CTsIm = The magnitization current for a single CT at setting VoltageIs = Setting current

Inr = Non Linear resistor current at setting VoltageInr = [(Vs)

/ (MI)]4

Inr = 0 Amps Inr Value is Zero since Non-Linear Resistor not used.P.O.C = 1368 Amps Example: POC = 2500 [(4 x 0.013) + 0 + 0.4] = 1130Amps

% of Transformer rating = 45.6 %As per ESI 48-3 standard,the fault current setting shall be between 10% to 60% of the rated current of the winding.

Page 14: Calculation for the Value of Stabilizing Resistor REF Setting

Limiting Peak VoltageIf it is not possible to limit the peak voltage,by careful selection of setting current,a voltage dependent Non-Linear resistor should be used.A Non-Linear Resistor Must be used with 50 % setting

Vp = MV [ IF / n ]0.25

MV = Coefficient Value Refer the chartMV = 900 Example: Vp=450[3700/2500]0.25 = 883Volt

IF = 36658 Ampsn = 3000 Amps

Vp = 1683 Volt

Inr = [(Vs) / (MI)]4

Vs = 152 VoltMI = Coefficient Value

= 900Inr = 0.0008 Amps Example: Inr =[123/450]4 =0.0056Amps

P.O.C = 2270.4 Amps Example: POC = 2500 [(4 x 0.013) + 0.0056 + 0.2] = 644Amps% of Transformer rating = 75.68 %

As per ESI 48-3 standard,the fault current setting shall be between 10% to 60% of the rated current of the winding.

Page 15: Calculation for the Value of Stabilizing Resistor REF Setting
Page 16: Calculation for the Value of Stabilizing Resistor REF Setting

5 1 7.5 5 1 7.5 5 1 7.5

0 2 5 0 2 5 0 2 5

0 3 10 0 3 10 0 3 10

0 4 20 0 4 20 0 4 20

0 5 40 0 5 40 0 5 40

6 6 6

Is = 40% Is = 50%Is = 20%

Relay Setting - Front Panel - DIP Switch Position

P+B MREF Restricted Earth Fault Relay

2000kVA 1000kVA 1600kVA

Page 17: Calculation for the Value of Stabilizing Resistor REF Setting

Summary Sheet For Stabilizing Resistor

TransfomerCapacity

TransfomerPrimary

TransfomerSecondary

Transfomer% Impedance Busbar Rating Fault Level Incomer

1000kVA 11000 V 400 V 5% 2000A 65kA for 1Sec 2000AT/2000AF

1600kVA 11000 V 400 V 6.3% 3200A 65kA for 1Sec 3200AT/3200AF

2000kVA 11000 V 400 V 6.3% 4000A 65kA for 1Sec 4000AT/4000AF

Restricted Earth Fault Relay CT's

Distance Between Star Point(Neutral) of ''CT'' To Relay

Cable Size From Star Point(Neutral) of

''CT'' To Relay

CT Knee Point Voltage [Vkn]

CT Resistance [RCT]

CT magnetizing current [Im]

2000/1A CL.X 30 meters 2.5 Sq.mm 350 V 8 Ω -

3000/1A CL.X 30 meters 2.5 Sq.mm 500 V 12 Ω -

4000/1A CL.X 30 meters 2.5 Sq.mm 700 V 17 Ω -

Calculated Fault Current in "CT"

Primary [IF]

Calculated "CT"Knee point Voltage

[Vkn]

Relay Setting[% Is]

Stabilizing Resistor [Rstab]

Non-Linear Resistor (Metrosil)

Primary Operating

Current

% of Transformer

Rating

Current Transformer Details

6594_Resistor Vaue

Transfomer Details SwitchBoard Details