Cables selection
-
8/12/2019 Cables Selection
2/17
Cables selection
Power cables
IntroductionOverhead distribution or transmission becomes difficult in densely populated areas like cities
and towns. In such areas it is necessary to use cables laid below the ground surface, these are known
as underground cables. All cables are fundamentally similar in that they contain conductors for
carrying current, insulation for surrounding the conductor, and some form of covering to provide
mechanical and possible corrosion protection to ensure that the insulator may continue to operate is
satisfactorily throughout the life of the cable once the cable has been installed. The primary function
of cable is to carry energy reliably between source and utilization and source equipment. In carrying
this energy, there are heat losses generate in the cable that must be dissipated. The ability to dissipate
these losses depends on how the cables are insulated, and this affects their ratings. The selection of
conductor size requires consideration of the load current to be carried and the load cycle, emergency
overloading requirements and duration, fault clearing time and interrupting capacity of the cable overcurrent protection or source capacity, voltage drop, and ambient temperatures for particular
installation conditions. Cable may be installed in raceway, in cable trays, underground in duct or
direct buried, in cable bus, or as open runs of cable.
In general, Cables are classified according to their uses into the following categories
1! "ower Cables
o #ingle core
o $ouble cores %often &ine '(eutral).
o Triple cores %often *!phase).
o +our cores %often *!phase '(eutral).
o +ive cores %often *!phase, (eutral 'round).
2! Control ' measurement cables %multi!core with the same color).
3! Telephone cables %in pairs).
Electrical power could be transmitted via two methods
-verhead lines.
nderground cables.
' we can compare them as a following
Underground cableOverhead lineeature
/igher.
$ifficult.
sed in congested industrial areas '
urban areas.
p to ** k0
1&"2 up to 345 k0.
&ower.
2asy.
sed in open country for
long distance.
p to highest voltage.
Cost
!aintenance
Use
"ated voltage
67
-
8/12/2019 Cables Selection
3/17
-
8/12/2019 Cables Selection
4/17
Cables selection
!etallic sheath!aterials used for cable sheathing are lead layer, aluminum layer or copper wire.
%he main function of it is to provide&
o ood method of cable earthing.
o ood path to the fault current.
.edding *illing+It consists of plastics materials which provide&
o 9ound cross!section!area of cables to take largest volume in least space area.
o #eparate the metallic sheath from the armored layer to prevent galvanic corrosion.
/rmoredIt is a protective noncorrosion la'er which provides&
o Carrying earth fault current.
o ives some protection against mechanical damage both during installation ' in
service.
E-ternal 0acetIt is a protective >acket which saves the cable from the surrounding solid.
It could be made of
o "0C material.
o ?ute impregnated with bitumen.
a'ing of cables%here are different methods for laying depended on cable type, cable importance ' soil
surrounding cable. #uch as
Cable supported using brackets above ground level.
Cables laid directly in dug in trenches below ground level %direct burial), the depth of trench
may be vary between 6 to 6.@m depends on voltage level. p to 66 k0 h5.@m
BB k0 h5.7@m
6*4 k0 h 6.55m
445 k0 h6.@m
The bottom of the trench is leveled freed from stones had sharp edge of rock, a layer 65cm
thick of clean sand is laid at the bottom of the trench .After laying The cable it is covered once again
with a 65cm thick layer of sand.
-
8/12/2019 Cables Selection
5/17
-
8/12/2019 Cables Selection
6/17
Cables selection
)election of cable si4e%o achieve ma:imum economy in first cost and subsequent appertain of cables, an important
aspect is the selection of the optimum size of conductor. )everal factors are involved which are&
o Continuous current carrying capacity.
o Ability to carry short circuit current.
o Cost of losses.
o 0oltage drop.
%hese factors are based on certain standard conditions such as
o Type of conductor material copper or aluminumo Core construction single or multi!core.
o Insulation material "0C, 1&"2 E
o 8ethod of installation in air or in ground.
o #urrounding ambient temperature.
o #oil thermal resistively.
o $epth of laying.
o 8ethod of cable grouping.
46
-
8/12/2019 Cables Selection
7/17
Cables selection
Classification of cables according to voltageCables can be classified according to rated voltage as follows
1! &ow voltage cables 2! 8edium voltage cables 3! /igh voltage cables
ow voltage cables3556755 8 9756:75 *)tranded Copper Conductor+
;escription&
)oft annealed solid or stranded copper conductors insulted with "0C compound rated
75F C or =@F C./pplication
or indoor fi:ed installations in dry locations, laid in conduits, as well as in steel
support brackets.
#ingle core cable with stranded and "0C Insulated
3556755 8 9756:75 *le-ible Copper+
;escription&
)oft annealed Copper fine wires bunched in sub ! units or stranded bunched together
groups into a main unit, which forms the fle:ible conductor. Insulated with soft "0C 75 FCor =@ FC Compound.
/pplication
or indoor fi:ed installations in dry locations, where particular fle:ibility is required
for electrical panelsG connection or for electrical apparatus they can be laid in groups around
steak sheets.
#ingle Core Cable and "0C Insulated
3556755 *le-ible Copper+
;escription)oft annealed Copper fine wires bunched together in sub ! units or stranded bunched
groups into a main unit, which forms the fle:ible conductor. These conductors are insulated
with "0C compound rated 75 FC and sheathed with "0C compound layer.
/pplication&
or indoor movable installation in dry location connecting to source power portable
electrical appliances operating under unfavorable conditions, such as portable lamps, fans,
refrigerators, washing machines, vacuum cleaners, T0 ' house hold heating and ventilating
apparatus.
44
-
8/12/2019 Cables Selection
8/17
Cables selection
8ulticore Cable with "0C Insulated and "0C #heathed
5
-
8/12/2019 Cables Selection
9/17
Cables selection
5
-
8/12/2019 Cables Selection
10/17
Cables selection
8ulticore Cables, with #tranded Copper Conductors, "0C Insulated,
#teel acket of
"0C compound.
/pplication&
or outdoor installations in damp wet locations where mechanical damages aree:pected to occur.
8ulticore Cables, with #tranded Aluminum Conductors, "0C Insulated, #teel
acket of "0C compound.
/pplication
or outdoor and indoor installations in damp and wet locations. They are normally
used for power distribution in urban networks, in industrial plants, as well as in Thermo '
/ydro power stations.
4@
-
8/12/2019 Cables Selection
11/17
Cables selection
8ulticore Cables, with #tranded, Copper Conductors, 1&"2 Insulatedand "0C #heathed
5
-
8/12/2019 Cables Selection
12/17
Cables selection
or outdoor installations in damp wet locations where mechanical damages are
e:pected to occur.
8ulticore Cables, with #tranded Aluminum Conductors, 1&"2 Insulated, #teel Tape
Armored and "0C #heathed
5
-
8/12/2019 Cables Selection
13/17
Cables selection
!edium voltage cables
B615 *12+ *!ulticore with )tranded Copper Conductors, >PE Insulated, )teel #ire
/rmored and PC )heathed)
;escription&
)tranded circular compacted Copper conductor, semi conducting layer as conductor
screen, 1&"2 insulated, semi conducting layer as non metallic insulation screen, Copper tape
or wire as metallic insulation screen, three cores assembled together with non!/ygroscopic
"olypropylene fillers, wrapped with polyester tape and "0C sheathed.
/pplication&
%hese cables are generally suitable for direct burial or for installation on trays or
ducts.
8ulticore Copper Conductors 1&"2 Insulated and "0C #heathed
=615 *12+ *!ulticore with )tranded /luminum Conductor, >PE Insulated, )teel #ire
/rmored and PC )heathed+;escription&
)tranded circular compacted Aluminum conductor, semi conducting layer as
conductor screen, 1&"2 insulated, semi conducting layer as non metallic insulation screen,
Copper tape or wire as metallic insulation screen, three cores assembled together with non
hygroscopic "olypropylene fillers, wrapped with polyester tape and "0C sheathed.
/pplication&
%hese cables are generally suitable for direct burial or for installation on trays or
ducts.
8ulticore Aluminum Conductors, 1&"2 Insulated and "0C #heathed
=615 *12+ *!ulticore Copper or /luminum Conductors, >PE Insulated, )teel %ape/rmored and PC )heathed+
4=
-
8/12/2019 Cables Selection
14/17
Cables selection
;escription&
)tranded circular compacted Copper or Aluminum conductor, semi conducting layer
as conductor screen, 1&"2 insulated, semi conducting layer as non metallic insulation
screen, Copper tape or wire as metallic insulation screen, three cores assembled together with
non hygroscopic polypropylene fillers, wrapped with polyester tape, covered with a layer of
"0C compound as a bedding, steel tape armored and "0C sheathed.
/pplication&
%hese cables are generally suitable for direct burial or for installation on trays or
ducts.
8ulticore Copper or Aluminum Conductors, 1&"2 Insulated, #teel Tape
Armored and "0C #heathed.
=615 *12+ *!ulticore Copper or /luminum Conductors, >PE Insulated, )teel #ire
/rmored and PC )heathed+
;escription&
)tranded circular compacted Copper or Aluminum conductor, semi conducting layer
as conductor screen, 1&"2 insulated, semi conducting layer as non metallic insulation
screen, Copper tape or wire as metallic insulation screen, three cores assembled together with
non hygroscopic "olypropylene fillers, wrapped with polyester tape, covered with a layer of
"0C compound as a bedding, steel wire armored and "0C sheathed.
/pplication
%hese cables are generally suitable for direct burial or for installation on trays or
ducts.
4
-
8/12/2019 Cables Selection
15/17
Cables selection
8ulticore Copper or Aluminum Conductors, 1&"2 Insulated, #teel
-
8/12/2019 Cables Selection
16/17
Cables selection
#ingle Core Copper Conductor, 1&"2 Insulated, &ead #creenedand /$"2 #heathing
;esign of underground cables under stud')everal factors are considered in selecting cable si4e, such as&
o Continuous current carrying capacity.
o Ability to carry short!circuit current.
o Cost of losses.
Continuous current carr'ing capacit'&
Current carrying capacity or Ampacity of cable is defined as the ma:imum allowable
current, which may flow through cable conductor without damaging the conductor or its insulation.
3*46
)%
FFFFF
A
=
=
)(factorratingOerall
factorratingOerall
currentrated!ableAmpacit"!able
#here
6F 9ating factor of soil temperature.
4F 9ating factor of soil thermal resistivity.*F grouping factor.3F 9ating factor of buried depth.
(ote&or cables installed in air there is only one rating factor % F ) which is called Gthe air
temperature rating factorG
8ost cable manufacturers issue catalogues which contain ratings for the cables which they
supply. ?owever these ratings are based on certain standard conditions such as&
o Type of conductor material, copper or aluminum.
o Core construction, single!core or multi!core depends on the rated current in cable.
o Insulation material, "0C, 1&"2 E
o 8ethod of installation, in air or in ground %direct buried or in duct).
o
#urrounding ambient temperature.o #oil thermal resistivity.
*6
-
8/12/2019 Cables Selection
17/17
Cables selection
o $epth of laying.
o 8ethod of cable grouping.
All of these previous factors should be taken into consideration in order to get the current
carrying capacity of the cable under actual operating conditions.
)hortcircuit current
%he most important factor for the cable selection is the capability of cable to carry the short
circuit current. The permissible rise in temperature during period of short circuit is 6@5FC in "0C
cable and 4@5FC in 1&"2 cables.
The electrodynamics load induced due to short circuit reduces the time that cable can be withstood.
In addition the symmetrical short circuit increases the armored and the outer sheath losses of the
cable.
Cost of losses
One important factor for cable selection is the cost of losses, which means that the cost of
power which dissipated in the cable core resistance.Cable manufacturers issue catalogues which contain resistance, inductance ' capacitance for the
cables which they supply.