MECHANICAL
COVER SHEET
M0-01
HVAC GENERAL NOTES
FIRE DAMPER
FD
DUCTWORK
DUCTWORK - AIR TERMINALS
DUCTWORK - EQUIPMENT
SMOKE DAMPER
SD
COMBINATION FIRE & SMOKE DAMPER
FSD
M
SMOKE DETECTOR
SDT
EQUIPMENT - HVAC
EDH-x
ELECTRIC DUCT HEATER, WITH TAG
AC AIR CONDITIONING UNIT
AD ACCESS DOOR
AFF ABOVE FINISHED FLOOR
AHU AIR HANDLING UNIT
AMB AMBIENT
AP ACCESS PANEL
AS AIR STREAM
ATM ATMOSPHERE
BD BALANCING DAMPER
BDD BACK DRAFT DAMPER
BHP BRAKE HORSEPOWER
BLDG BUILDING
BOD BOTTOM OF DUCT
BTU BRITISH THERMAL UNIT
BTUH BTU PER HOUR
CC COOLING COIL
CF CUBIC FEET
CFM CUBIC FEET PER MINUTE
CLG CEILING
ABBREVIATIONS
CU,
HP-x
CU,
HP-x
VAV-x
VARIABLE AIR VOLUME BOX WITH TAG,
DUCT SHOWN
ROOF/CURB MOUNTED AIR HANDLING
UNIT, DUCT NOT SHOWN
INDOOR HORIZONTAL AIR HANDLING
EQUIP, DUCT SHOWN
INDOOR VERTICAL AIR HANDLING
EQUIP, DUCT NOT SHOWN
GF, WSHP, A/C-x
GF, WSHP, A/C-x
EF-x
ROOF/CURB MOUNTED EXHAUST FAN
WITH TAG, DUCT SHOWN
INLINE SUSPENDED MOUNT EXHAUST
FAN WITH TAG, DUCT SHOWN
EF-x
EF-x
CEILING MOUNTED EXHAUST FAN
WITH TAG, DUCT SHOWN
CONDENSING UNIT ON
EQUIPMENT RAILS WITH TAG
CONDENSING UNIT ON CONCRETE
HOUSE KEEPING PAD WITH TAG
SIDEWALL GRILLE TAP WITH
MANUAL VOLUME DAMPER, SQ
24x24
24"
SIDEWALL GRILLE TAP WITH
MANUAL VOLUME DAMPER, RND
MOTORIZED DAMPER
EXHAUST AIR GRILLE; EXHAUST
DUCT AND MVD IN SECTION
RETURN AIR GRILLE; RETURN
DUCT AND MVD IN SECTION
SUPPLY AIR DIFFUSER; SUPPLY
DUCT AND MVD IN SECTION
MVD; MANUAL
BALANCING/VOLUME DAMPER
HVAC LEGEND
FPS FEET PER SECOND
FS FLOW SWITCH
FSD COMB SMOKE FIRE DAMPER
FT FOOT OR FEET
G GAS
GAL GALLONS
GALV GALVANIZED
GPM GALLONS PER MINUTE
HP HORSEPOWER
HR HOUR
HT HEIGHT
HX HEAT EXCHANGER
Hz FREQUENCY
ID INSIDE DIAMETER
IN INCH
kW KILOWATT
kWh KILOWATT HOUR
L LENGTH
RLA RUNNING LOAD AMPS
RM ROOM
SA SUPPLY AIR
SD SMOKE DAMPER
SF SUPPLY FAN
SG SPECIFIC GRAVITY
SH SENSIBLE HEAT
SHR SENSIBLE HEAT RATIO
SP STATIC PRESSURE
SPEC SPECIFICATIONS
SQ SQUARE
TOD TOP OF DUCT
TYP TYPICAL
U HEAT TRANSFER COEFFICIENT
UCD UNDERCUT DOOR
UH UNIT HEATER
V VOLTS
VAV VARIABLE AIR VOLUME
VFD VARIABLE FREQUENCY DRIVE
VOL VOLUME
W WATT
WB WET BULB
WC WATER COLUMN
WPD WATER PRESSURE DROP
COL COLUMN CONC CONCRETE
CRAC COMPUTER ROOM UNIT
CU CONDENSING UNIT
DB DRY BULB
DC DRY COOLER
DDC DIRECT DIGITAL CONTROL
DIA DIAMETER
DP DIFFERENTIAL PRESSURE
DX DIRECT EXPANSION
LAT LEAVING AIR TEMPERATURE
LF LINEAR FEET
LH LATENT HEAT
LRA LOCKED ROTOR AMPS
LVR LOUVER
LWT LEAVING WATER TEMPERATURE
MBU THOUSAND BTUH
MFR MANUFACTURER
MIN MINIMUM
MVD MANUAL VOLUME DAMPER
N/A NOT APPLICABLE
NC NOISE CRITERIA
NOM NOMINAL
NTS NOT TO SCALE
OA OUTSIDE AIR
OD OUTSIDE DIAMETER
P PUMP
PH PHASE (ELECTRICAL)
PLBG PLUMBING
PPM PARTS PER MILLION
PSFG POUNDS PER SQUARE FOOT
PSIG POUNDS PER SQUARE INCH
QTY QUANTITY
R RADIUS
RA RETURN AIR
REQ'D REQUIRED
RF RETURN FAN
RH HUMIDITY, RELATIVE
BDD
BACK DRAFT DAMPER WITH
AIR FLOW INDICATION
NEW FLEXIBLE DUCTWORK
N E
EXISTING DUCTWORK TO NEW
DUCTWORK CONNECTION
24x12
24x12
24x12
SQUARE DUCT TAKE OFF, TOP
SQUARE DUCT TAKE OFF, BOTTOM
SQUARE DUCT TAKE OFF, TOP
RND ELBOW 45°, RADIUS
24"
SQ ELBOW 45°, RADIUS
24x24
SQ ELBOW 45°, MITERED
24x24
SQ TO RND CONCENTRIC
TRANSITION IN DROP
SQ TO RND CONCENTRIC
TRANSITION IN RISE
SQ TO SQ ECCENTRIC TRANSITION
SQ TO SQ CONCENTRIC TRANSITION
SQ TO RND ECCENTRIC TRANSITION
SQ TO RND CONCENTRIC
TRANSITION
24x12
24x12
24x12
24x12
24x12
24"
24"
RND ELBOW 45°, RADIUS
24"
RND ELBOW 90°, MITERED
RND ELBOW 90°, RADIUS
SQUARE ELBOW, NO
TURNING VANES
RND DUCT ELEVATION CHANGE, UP
RND DUCT ELEVATION CHANGE,
DOWN
NEW DUCTWORK WITH LINER
ROUND DUCT TAKE OFF
24"
DUCTWORK DIMENSION LABEL
(24" DIAMETER)
24x12
DUCTWORK DIMENSION LABEL
(24" WIDTH x 12" HEIGHT)
SQUARE DUCT TAKE OFF, SIDE
SQ DUCT ELEVATION CHANGE, 90°
UP
SQ DUCT ELEVATION CHANGE, 90°
DOWN
NEW RIGID DUCTWORK
EXISTING DUCTWORK TO BE
DEMOLISHED
EXISTING DUCTWORK TO REMAIN
SQUARE ELBOW WITH DOUBLE
THICKNESS TURNING VANES
Ø
Ø
Ø
Ø
Ø
Ø
Ø
Ø
Ø
Ø
Ø
Ø
Ø
Ø
Ø
SPACE SENSOR/THERMOSTAT
S
EA EACH OR EXHAUST AIR
EAT ENTERING AIR TEMPERATURE
EF EXHAUST FAN
EWT ENTERING WATER TEMPERATURE
EXP EXPANSION
F FAHRENHEIT
FA FACE AREA
FD FIRE DAMPER
FP FAN POWERED
FPM FEET PER MINUTE
1. THESE GENERAL NOTES APPLY TO ALL MECHANICAL DRAWINGS. IN THE EVENT THAT
ANY GENERAL NOTE CONFLICTS WITH THE WRITTEN CONSTRUCTION SPECIFICATIONS,
THE MOST STRINGENT OF THE TWO SHALL RULE.
2. CONTRACTOR SHALL PROVIDE ALL MATERIALS, EQUIPMENT AND LABOR REQUIRED TO
INSTALL A COMPLETE AND OPERABLE MECHANICAL SYSTEM AS INDICATED ON THE
DRAWINGS, SPECIFICATIONS AND IN ACCORDANCE WITH APPLICABLE CODES.
3. ALL EQUIPMENT SHALL BE INSTALLED IN STRICT COMPLIANCE WITH THE
MANUFACTURER'S WRITTEN INSTRUCTIONS. THE CONTRACTOR SHALL PROVIDE ALL
HANGERS AND SUPPORTS (IN COMPLIANCE WITH SEISMIC CATEGORY “C”) REQUIRED
FOR A COMPLETE INSTALLATION.
4. THE MECHANICAL DRAWINGS ARE DIAGRAMMATIC AND ARE INTENDED TO CONVEY
SCOPE AND GENERAL ARRANGEMENT ONLY. DO NOTE SCALE DRAWINGS.
5. COORDINATE ALL MECHANICAL WORK WITH OTHER TRADES TO INSURE PROPER
CLEARANCE AND SPATIAL RELATIONSHIPS TO OTHER EQUIPMENT AND STRUCTURAL
COMPONENTS.
6. COORDINATE ALL EQUIPMENT CONNECTIONS WITH MANUFACTURER'S CERTIFIED
DRAWINGS. COORDINATE AND PROVIDE ALL DUCT AND PIPE TRANSITIONS REQUIRED
FOR FINAL CONNECTIONS TO FURNISHED EQUIPMENT. FIELD VERIFY ALL DUCT AND
PIPE DIMENSIONS PRIOR TO FABRICATION.
7. PROVIDE FLEXIBLE DUCT AND PIPE CONNECTIONS TO ALL MECHANICAL EQUIPMENT.
8. ALL CONTROL WIRING AND CONDUIT SHALL COMPLY WITH THE NATIONAL ELECTRIC
CODE. ALL CONTROL WIRING IN RETURN PLENUMS SHALL BE PLENUM RATED. CONTROL
WIRING LOCATED IN MECHANICAL ROOMS SHALL BE ROUTED IN RIGID CONDUIT.
9. CONTRACTOR IS RESPONSIBLE FOR THE RESTART OF ANY SYSTEMS DE-ENERGIZED TO
ACCOMMODATE THIS WORK.
10. INSTALL SMOKE DETECTORS (PROVIDED BY ELECTRICAL) AT EACH A/C UNIT HANDLING
OVER 2000 CFM, MOUNTED IN SA DUCT (NFPA 90A, 4-4.2), AND IN RA DUCT PRIOR TO
EXHAUST OR MIXING (SMC 406.1). ALSO INSTALL SMOKE DETECTOR AT EACH A/C UNIT
SERVING BUILDING EGRESS (REGARDLESS OF SIZE), MOUNTED IN SA DUCT.
DETECTOR(S) TO STOP UNIT FAN IF SMOKE IS DETECTED. INTERLOCK WITH FIRE
ALARM SYSTEM IF APPLICABLE.
11. PROVIDE AND INSTALL ACCESS PANELS/DOORS IN WALLS, CEILINGS AND DUCTWORK AS
REQUIRED TO ACCESS/SERVICE VALVES, DUCT DETECTORS, CONTROL COMPONENTS,
FIRE DAMPERS AND OTHER CONCEALED MECHANICAL DEVISES.
12. ALL DUCT DIMENSIONS ARE INSIDE CLEAR UNLESS OTHERWISE NOTED. ALL DUCT
DIMENSIONS SHALL BE MODIFIED AS REQUIRED TO ACCOUNT FOR DUCT INSULATION.
13. LOCATE ALL MECHANICAL EQUIPMENT TO FACILITATE UNOBSTRUCTED AIR/WATER FLOW
AND ACCESS TO UNIT SERVICE PANELS, CONTROLS AND VALVES AS REQUIRED BY THE
MANUFACTURER AND APPLICABLE CODES.
14. ALL AIR/HYDRONIC LEAK TESTING AND INSPECTIONS SHALL BE COMPLETED PRIOR TO
THE APPLICATION OF INSULATING MATERIALS. FAILURE TO COMPLY WITH THIS
REQUIREMENT MAY RESULT IN THE REMOVAL AND REAPPLICATION OF THE INSULATION
AT THE CONTRACTORS EXPENSE.
15. LOCATE ALL TEMPERATURE, PRESSURE, FLOW MEASURING DEVICES AND COMPONENTS
IN ACCESSIBLE LOCATIONS WITH STRAIGHT SECTIONS OF PIPE/DUCTWORK UP AND
DOWN STREAM OF DEVICE AS OUTLINED BY THE EQUIPMENT MANUFACTURER.
16. TESTING, ADJUSTING AND BALANCING CONTRACTOR SHALL BE A CURRENT AND
RECOGNIZED MEMBER OF THE AABC OR NEBB AS OUTLINED IN THE CONSTRUCTION
SPECIFICATIONS.
17. ALL DUCTWORK, PIPING OR EQUIPMENT SUPPORTED FROM THE STRUCTURE SHALL BE
COORDINATED WITH THE GENERAL CONTRACTOR. CONTRACTOR RESPONSIBLE FOR THE
REPAIR/REPLACEMENT OF ANY FIREPROOFING REMOVED TO ACCOMMODATE HANGER
ATTACHMENT.
18. ALL NEW/MODIFIED SUPPLY DUCTWORK SHALL BE EXTERNAL INSULATED IN
ACCORDANCE WITH THE CONSTRUCTION SPECIFICATIONS. EXPOSED SUPPLY DUCT
WITHIN THE SPACE SERVED DOES NOT NEED TO BE WRAPPED.
19. CONFIRM LOCATIONS OF FIRE RATED CEILINGS, WALLS AND FLOORS. FIRE SEAL ALL
PENETRATIONS WITH FIRE STOP SEALANT. DUCTWORK THAT PENETRATES FIRE
PARTITIONS SHALL BE EQUIPPED WITH FIRE DAMPERS.
20. OFFSET DUCTWORK AS REQUIRED TO ACCOMMODATE THE ARCHITECTURAL REFLECTIVE
CEILING PLAN.
21. NO SUPPLY DIFFUSER SHALL BE LOCATED WITHIN 36” OF ANY SMOKE DETECTOR OR
AUTOMATIC SPRINKLER HEAD/DEVICE.
22. ALL 45 DEGREE OR GREATER ELBOWS (INCLUDING THOSE AT DIFFUSER CONNECTIONS)
SHALL BE CONSTRUCTED OF RIGID DUCTWORK.
23. ALL WORK SHALL BE PREFORMED IN ACCORDANCE WITH SITE CONSTRUCTION AND
SAFETY REQUIREMENTS. NO WORK SHALL BE PERFORMED WITHOUT A VALID JOB
SCHEDULE AND FIRE ALARM PERMITS (WHERE REQUIRED). ALL WORKERS MUST
REGISTER WITH THE LOCAL MAINTENANCE CONTRACTOR PRIOR TO PERFORMING ANY
WORK.
24. ALL WASTE OR DISCARDED MATERIALS SHALL BE RECYCLED IN ACCORDANCE WITH SITE
CONSTRUCTION POLICIES. REPORT ALL RECYCLED MATERIAL QUANTITIES TO PROJECT
ENGINEER. WRITTEN REPORT SHALL INCLUDE MATERIAL TYPE, QUANTITIES, AND
DISPOSITION OF THE MATERIALS.
25. MECHANICAL CONTRACTOR IS RESPONSIBLE FOR PROVIDING A COMPLETE SET OF
AS-BUILT DRAWINGS DETAILING ALL FIELD MODIFICATIONS TO THE DESIGN DRAWINGS.
DRAWINGS SHALL INCLUDE LOCATION AND ELEVATION REFERENCED FROM FINISHED
FLOOR.
26. EACH BRANCH DUCT SERVING A DIFFUSER SHALL HAVE A MANUAL BALANCING DAMPER
INSTALLED AT MAIN DUCT TAKE-OFF REGARDLESS OF DRAWING OMISSION.
5
0
%
C
D
S
E
T
MECHANICAL SHEET INDEX
D
ATE
2/13/17
X
TITLE#
M0-01 MECHANICAL COVER SHEET
M1-01 MECHANICAL - HVAC - 1ST FLOOR
M1-02 MECHANICAL - HVAC - 2ND / 3RD FLOOR
M1-03 MECHANICAL - HVAC - 4TH FLOOR / ROOF
M2-00 MECHANICAL - SCHEDULES
M2-01 MECHANICAL - SCHEDULES
M2-02MECHANICAL - DETAILS 1 of 3
M2-03 MECHANICAL - DETAILS 2 of 3
X
X
X
X
X
X
X
CONSTRUCTION SPECIFICATIONS
TEST AND BALANCE (MINIMUM REQUIREMENTS)
1. TAB FIRM QUALIFICATIONS: ENGAGE A TAB FIRM CERTIFIED BY AABC, NEBB, OR TABB.
2. TAB CONFERENCE: MEET WITH OWNER'S AND/OR OWNERS REPRESENTATIVES ON
APPROVAL OF TAB STRATEGIES AND PROCEDURES PLAN TO DEVELOP A MUTUAL
UNDERSTANDING OF THE DETAILS. ENSURE THE PARTICIPATION OF TAB TEAM
MEMBERS, EQUIPMENT MANUFACTURERS' AUTHORIZED SERVICE REPRESENTATIVES,
HVAC CONTROLS INSTALLERS, AND OTHER SUPPORT PERSONNEL. PROVIDE SEVEN
DAYS' ADVANCE NOTICE OF SCHEDULED MEETING TIME AND LOCATION.
3. TAB REPORT FORMS: USE STANDARD FORMS FROM SMACNA'S TABB "HVAC SYSTEMS - TESTING,
ADJUSTING, AND BALANCING.
4. COORDINATE THE EFFORTS OF FACTORY-AUTHORIZED SERVICE REPRESENTATIVES FOR SYSTEMS
AND EQUIPMENT, HVAC CONTROLS INSTALLERS, AND OTHER MECHANICS TO OPERATE HVAC
SYSTEMS AND EQUIPMENT TO SUPPORT AND ASSIST TAB ACTIVITIES.
5. PERFORM TAB AFTER LEAKAGE AND PRESSURE TESTS ON AIR AND WATER DISTRIBUTION SYSTEMS
HAVE BEEN SATISFACTORILY COMPLETED.
6. COMPLETE SYSTEM READINESS CHECKS AND PREPARE SYSTEM READINESS REPORTS. VERIFY THE
FOLLOWING:
· PERMANENT ELECTRICAL POWER WIRING IS COMPLETE.
· HYDRONIC SYSTEMS ARE FILLED, CLEAN, AND FREE OF AIR.
· AUTOMATIC TEMPERATURE-CONTROL SYSTEMS ARE OPERATIONAL.
· EQUIPMENT AND DUCT ACCESS DOORS ARE SECURELY CLOSED.
· BALANCE, SMOKE, AND FIRE DAMPERS ARE OPEN.
· ISOLATING AND BALANCING VALVES ARE OPEN AND CONTROL VALVES ARE OPERATIONAL.
7. PERFORM TESTING AND BALANCING PROCEDURES ON EACH SYSTEM ACCORDING TO THE
PROCEDURES CONTAINED IN SMACNA'S TABB "HVAC SYSTEMS - TESTING, ADJUSTING, AND
BALANCING" AND THIS SECTION.
8. CUT INSULATION, DUCTS, PIPES, AND EQUIPMENT CABINETS FOR INSTALLATION OF TEST PROBES
TO THE MINIMUM EXTENT NECESSARY TO ALLOW ADEQUATE PERFORMANCE OF PROCEDURES.
AFTER TESTING AND BALANCING, CLOSE PROBE HOLES AND PATCH INSULATION WITH NEW
MATERIALS IDENTICAL TO THOSE REMOVED. RESTORE VAPOR BARRIER AND FINISH ACCORDING
TO INSULATION SPECIFICATIONS FOR THIS PROJECT.
9. MARK EQUIPMENT AND BALANCING DEVICE SETTINGS WITH PAINT OR OTHER SUITABLE,
PERMANENT IDENTIFICATION MATERIAL, INCLUDING DAMPER-CONTROL POSITIONS, VALVE
POSITION INDICATORS, FAN-SPEED-CONTROL LEVERS, AND SIMILAR CONTROLS AND DEVICES, TO
SHOW FINAL SETTINGS.
10. TAKE AND REPORT TESTING AND BALANCING MEASUREMENTS IN INCH-POUND (IP) UNITS.
11. PREPARE TEST REPORTS FOR BOTH FANS AND OUTLETS. OBTAIN MANUFACTURER'S OUTLET
FACTORS AND RECOMMENDED TESTING PROCEDURES. CROSSCHECK THE SUMMATION OF
REQUIRED OUTLET VOLUMES WITH REQUIRED FAN VOLUMES.
12. PREPARE SCHEMATIC DIAGRAMS OF SYSTEMS' "AS-BUILT" DUCT LAYOUTS.
13. DETERMINE THE BEST LOCATIONS IN MAIN AND BRANCH DUCTS FOR ACCURATE DUCT AIRFLOW
MEASUREMENTS.
14. CHECK AIRFLOW PATTERNS FROM THE OUTSIDE-AIR LOUVERS AND DAMPERS AND THE RETURN-
AND EXHAUST-AIR DAMPERS, THROUGH THE SUPPLY-FAN DISCHARGE AND MIXING DAMPERS.
15. LOCATE START-STOP AND DISCONNECT SWITCHES, ELECTRICAL INTERLOCKS, AND MOTOR
STARTERS.
16. VERIFY THAT MOTOR STARTERS ARE EQUIPPED WITH PROPERLY SIZED THERMAL PROTECTION.
17. CHECK DAMPERS FOR PROPER POSITION TO ACHIEVE DESIRED AIRFLOW PATH.
18. CHECK FOR AIRFLOW BLOCKAGES.
19. CHECK CONDENSATE DRAINS FOR PROPER CONNECTIONS AND FUNCTIONING.
20. CHECK FOR PROPER SEALING OF AIR-HANDLING UNIT COMPONENTS.
21. CHECK FOR PROPER SEALING OF AIR DUCT SYSTEM.
22. ADJUST FANS TO DELIVER TOTAL INDICATED AIRFLOWS WITHIN THE MAXIMUM ALLOWABLE FAN
SPEED LISTED BY FAN MANUFACTURER.
23. MEASURE FAN STATIC PRESSURES TO DETERMINE ACTUAL STATIC PRESSURE AS FOLLOWS:
· MEASURE OUTLET STATIC PRESSURE AS FAR DOWNSTREAM FROM THE FAN AS PRACTICABLE
AND UPSTREAM FROM RESTRICTIONS IN DUCTS SUCH AS ELBOWS AND TRANSITIONS.
· MEASURE STATIC PRESSURE DIRECTLY AT THE FAN OUTLET OR THROUGH THE FLEXIBLE
CONNECTION.
· MEASURE INLET STATIC PRESSURE OF SINGLE-INLET FANS IN THE INLET DUCT AS NEAR THE
FAN AS POSSIBLE, UPSTREAM FROM FLEXIBLE CONNECTION AND DOWNSTREAM FROM DUCT
RESTRICTIONS.
· MEASURE INLET STATIC PRESSURE OF DOUBLE-INLET FANS THROUGH THE WALL OF THE
PLENUM THAT HOUSES THE FAN.
24. MEASURE STATIC PRESSURE ACROSS EACH COMPONENT THAT MAKES UP AN AIR-HANDLING
UNIT, ROOFTOP UNIT, AND OTHER AIR-HANDLING AND -TREATING EQUIPMENT.
25. SIMULATE DIRTY FILTER OPERATION AND RECORD THE POINT AT WHICH MAINTENANCE
PERSONNEL MUST CHANGE FILTERS.
26. MEASURE STATIC PRESSURES ENTERING AND LEAVING OTHER DEVICES SUCH AS SOUND TRAPS,
HEAT RECOVERY EQUIPMENT, AND AIR WASHERS, UNDER FINAL BALANCED CONDITIONS.
27. COMPARE DESIGN DATA WITH INSTALLED CONDITIONS TO DETERMINE VARIATIONS IN DESIGN
STATIC PRESSURES VERSUS ACTUAL STATIC PRESSURES. COMPARE ACTUAL SYSTEM EFFECT
FACTORS WITH CALCULATED SYSTEM EFFECT FACTORS TO IDENTIFY WHERE VARIATIONS
OCCUR. RECOMMEND CORRECTIVE ACTION TO ALIGN DESIGN AND ACTUAL CONDITIONS.
28. DO NOT MAKE FAN-SPEED ADJUSTMENTS THAT RESULT IN MOTOR OVERLOAD. CONSULT
EQUIPMENT MANUFACTURERS ABOUT FAN-SPEED SAFETY FACTORS. MODULATE DAMPERS AND
MEASURE FAN-MOTOR AMPERAGE TO ENSURE THAT NO OVERLOAD WILL OCCUR. MEASURE
AMPERAGE IN FULL COOLING, FULL HEATING, ECONOMIZER, AND ANY OTHER OPERATING
MODES TO DETERMINE THE MAXIMUM REQUIRED BRAKE HORSEPOWER.
29. ADJUST VOLUME DAMPERS FOR MAIN DUCT, SUBMAIN DUCTS, AND MAJOR BRANCH DUCTS TO
INDICATED AIRFLOWS WITHIN SPECIFIED TOLERANCES.
30. MEASURE STATIC PRESSURE AT A POINT DOWNSTREAM FROM THE BALANCING DAMPER AND
ADJUST VOLUME DAMPERS UNTIL THE PROPER STATIC PRESSURE IS ACHIEVED.
31. PREPARE SCHEMATIC DIAGRAMS OF SYSTEMS' "AS-BUILT" PIPING LAYOUTS.
32. PREPARE HYDRONIC SYSTEMS FOR TESTING AND BALANCING ACCORDING TO THE FOLLOWING,
IN ADDITION TO THE GENERAL PREPARATION PROCEDURES SPECIFIED ABOVE:
· OPEN ALL MANUAL VALVES FOR MAXIMUM FLOW.
· CHECK EXPANSION TANK LIQUID LEVEL.
· CHECK MAKEUP-WATER-STATION PRESSURE GAGE FOR ADEQUATE PRESSURE FOR HIGHEST
VENT.
· CHECK FLOW-CONTROL VALVES FOR SPECIFIED SEQUENCE OF OPERATION AND SET AT
INDICATED FLOW.
· SET DIFFERENTIAL-PRESSURE CONTROL VALVES AT THE SPECIFIED DIFFERENTIAL PRESSURE.
DO NOT SET AT FULLY CLOSED POSITION WHEN PUMP IS POSITIVE-DISPLACEMENT TYPE
UNLESS SEVERAL TERMINAL VALVES ARE KEPT OPEN.
· CHECK AIR VENTS FOR A FORCEFUL LIQUID FLOW EXITING FROM VENTS WHEN MANUALLY
OPERATED.
33. SET CALIBRATED BALANCING VALVES, IF INSTALLED, AT CALCULATED PRESETTINGS.
34. MEASURE FLOW AT ALL STATIONS AND ADJUST, WHERE NECESSARY, TO OBTAIN FIRST
BALANCE.
35. SYSTEM COMPONENTS THAT HAVE CV RATING OR AN ACCURATELY CATALOGED
FLOW-PRESSURE-DROP RELATIONSHIP MAY BE USED AS A FLOW-INDICATING DEVICE.
36. MEASURE FLOW AT MAIN BALANCING STATION AND SET MAIN BALANCING DEVICE TO
ACHIEVE FLOW THAT IS 5 PERCENT GREATER THAN INDICATED FLOW.
37. CHECK THE SETTING AND OPERATION OF AUTOMATIC TEMPERATURE-CONTROL
VALVES, SELF-CONTAINED CONTROL VALVES, AND PRESSURE-REDUCING VALVES.
RECORD THE FINAL SETTING.
38. VERIFY THAT CONTROLLERS ARE CALIBRATED AND COMMISSIONED.
39. CHECK TRANSMITTER AND CONTROLLER LOCATIONS AND NOTE CONDITIONS THAT
WOULD ADVERSELY AFFECT CONTROL FUNCTIONS.
40. RECORD CONTROLLER SETTINGS AND NOTE VARIANCES BETWEEN SET POINTS AND
ACTUAL MEASUREMENTS.
41. CHECK THE OPERATION OF LIMITING CONTROLLERS (I.E., HIGH- AND
LOW-TEMPERATURE CONTROLLERS).
42. CHECK FREE TRAVEL AND PROPER OPERATION OF CONTROL DEVICES SUCH AS DAMPER
AND VALVE OPERATORS.
43 CHECK THE SEQUENCE OF OPERATION OF CONTROL DEVICES. NOTE AIR
PRESSURES AND DEVICE POSITIONS AND CORRELATE WITH AIRFLOW AND WATER
FLOW MEASUREMENTS. NOTE THE SPEED OF RESPONSE TO INPUT CHANGES.
44. CHECK THE INTERACTION OF ELECTRICALLY OPERATED SWITCH TRANSDUCERS.
45. CHECK THE INTERACTION OF INTERLOCK AND LOCKOUT SYSTEMS.
46. RECORD VOLTAGES OF POWER SUPPLY AND CONTROLLER OUTPUT. DETERMINE
WHETHER THE SYSTEM OPERATES ON A GROUNDED OR NONGROUNDED POWER
SUPPLY.
47. NOTE OPERATION OF ELECTRIC ACTUATORS USING SPRING RETURN FOR PROPER
FAIL-SAFE OPERATIONS.
48. SET HVAC SYSTEM AIRFLOW AND WATER FLOW RATES WITHIN THE FOLLOWING
TOLERANCES:
· SUPPLY, RETURN, AND EXHAUST FANS AND EQUIPMENT WITH FANS: PLUS 5 TO
PLUS 10 PERCENT.
· AIR OUTLETS AND INLETS: 0 TO MINUS 10 PERCENT.
· HEATING-WATER FLOW RATE: 0 TO MINUS 10 PERCENT.
· COOLING-WATER FLOW RATE: 0 TO MINUS 5 PERCENT.
49. FINAL REPORT SHALL BE TYPEWRITTEN, OR COMPUTER PRINTOUT IN LETTER-QUALITY
FONT, ON STANDARD BOND PAPER, IN THREE-RING BINDER, TABULATED AND DIVIDED
INTO SECTIONS BY TESTED AND BALANCED SYSTEMS.
50. FINAL REPORT CONTENTS: IN ADDITION TO CERTIFIED FIELD REPORT DATA, INCLUDE
THE FOLLOWING:
· FAN CURVES.
· MANUFACTURERS' TEST DATA.
· FIELD TEST REPORTS PREPARED BY SYSTEM AND EQUIPMENT INSTALLERS.
· OTHER INFORMATION RELATIVE TO EQUIPMENT PERFORMANCE, BUT DO NOT
INCLUDE SHOP DRAWINGS AND PRODUCT DATA.
51. TEST CONDITIONS FOR FANS AND PUMP PERFORMANCE FORMS INCLUDING THE
FOLLOWING:
· SETTINGS FOR OUTSIDE-, RETURN-, AND EXHAUST-AIR DAMPERS.
· CONDITIONS OF FILTERS.
· COOLING COIL, WET- AND DRY-BULB CONDITIONS.
· FACE AND BYPASS DAMPER SETTINGS AT COILS.
· FAN DRIVE SETTINGS INCLUDING SETTINGS AND PERCENTAGE OF MAXIMUM PITCH
DIAMETER.
· SETTINGS FOR SUPPLY-AIR, STATIC-PRESSURE CONTROLLER.
· OTHER SYSTEM OPERATING CONDITIONS THAT AFFECT PERFORMANCE.
52. SYSTEM DIAGRAMS: INCLUDE SCHEMATIC LAYOUTS OF AIR AND HYDRONIC
DISTRIBUTION SYSTEMS. PRESENT EACH SYSTEM WITH SINGLE-LINE DIAGRAM AND
INCLUDE THE FOLLOWING:
· QUANTITIES OF OUTSIDE, SUPPLY, RETURN, AND EXHAUST AIRFLOWS.
· WATER AND STEAM FLOW RATES.
· DUCT, OUTLET, AND INLET SIZES.
· PIPE AND VALVE SIZES AND LOCATIONS.
· TERMINAL UNITS.
· BALANCING STATIONS.
· POSITION OF BALANCING DEVICES.
55. AIR-HANDLING UNIT TEST REPORTS: FOR AIR-HANDLING UNITS WITH COILS,
INCLUDE THE FOLLOWING:
· UNIT IDENTIFICATION.
· LOCATION.
· MAKE AND TYPE.
· MODEL NUMBER AND UNIT SIZE.
· MANUFACTURER'S SERIAL NUMBER.
· UNIT ARRANGEMENT AND CLASS.
· DISCHARGE ARRANGEMENT.
· SHEAVE MAKE, SIZE IN INCHES, AND BORE.
· SHEAVE DIMENSIONS, CENTER-TO-CENTER, AND AMOUNT OF ADJUSTMENTS IN
INCHES.
· NUMBER OF BELTS, MAKE, AND SIZE.
· NUMBER OF FILTERS, TYPE, AND SIZE.
MOTOR DATA:
· MAKE AND FRAME TYPE AND SIZE.
· HORSEPOWER AND RPM.
· VOLTS, PHASE, AND HERTZ.
· FULL-LOAD AMPERAGE AND SERVICE FACTOR.
· SHEAVE MAKE, SIZE IN INCHES, AND BORE.
· SHEAVE DIMENSIONS, CENTER-TO-CENTER, AND AMOUNT OF ADJUSTMENTS IN
INCHES.
TEST DATA (INDICATED AND ACTUAL VALUES):
· TOTAL AIRFLOW RATE IN CFM.
· TOTAL SYSTEM STATIC PRESSURE IN INCHES WG.
· FAN RPM.
· DISCHARGE STATIC PRESSURE IN INCHES WG.
· FILTER STATIC-PRESSURE DIFFERENTIAL IN INCHES WG.
· PREHEAT COIL STATIC-PRESSURE DIFFERENTIAL IN INCHES WG.
· COOLING COIL STATIC-PRESSURE DIFFER`ENTIAL IN INCHES WG.
· HEATING COIL STATIC-PRESSURE DIFFERENTIAL IN INCHES WG.
· OUTSIDE AIRFLOW IN CFM..
· RETURN AIRFLOW IN CFM.
· OUTSIDE-AIR DAMPER POSITION.
· RETURN-AIR DAMPER POSITION.
· VORTEX DAMPER POSITION.
MECHANICAL SPECIFICATIONS
EQUIPMENT INSTALLATION - COMMON REQUIREMENTS
1. INSTALL EQUIPMENT LEVEL AND PLUMB, PARALLEL AND PERPENDICULAR TO OTHER
BUILDING SYSTEMS AND COMPONENTS IN EXPOSED INTERIOR SPACES, UNLESS
OTHERWISE INDICATED.
2. INSTALL HVAC EQUIPMENT TO FACILITATE SERVICE, MAINTENANCE, AND REPAIR OR
REPLACEMENT OF COMPONENTS. CONNECT EQUIPMENT FOR EASE OF
DISCONNECTING, WITH MINIMUM INTERFERENCE TO OTHER INSTALLATIONS.
EXTEND GREASE FITTINGS TO ACCESSIBLE LOCATIONS.
3. INSTALL EQUIPMENT TO ALLOW RIGHT OF WAY FOR PIPING INSTALLED AT
REQUIRED SLOPE.
4. DAMAGE AND TOUCHUP: REPAIR MARRED AND DAMAGED FACTORY-PAINTED
FINISHES WITH MATERIALS AND PROCEDURES TO MATCH ORIGINAL FACTORY
FINISH.
DUCT HANGER AND SUPPORT INSTALLATION
1. COMPLY WITH SMACNA'S "HVAC DUCT CONSTRUCTION STANDARDS - METAL AND
FLEXIBLE," CHAPTER 4, "HANGERS AND SUPPORTS."
2. HANGER SPACING: COMPLY WITH SMACNA'S "HVAC DUCT CONSTRUCTION
STANDARDS - METAL AND FLEXIBLE," TABLE 4-1, "RECTANGULAR DUCT HANGERS
MINIMUM SIZE," AND TABLE 4-2, "MINIMUM HANGER SIZES FOR ROUND DUCT," FOR
MAXIMUM HANGER SPACING; INSTALL HANGERS AND SUPPORTS WITHIN 24 INCHES
OF EACH ELBOW AND WITHIN 48 INCHES OF EACH BRANCH INTERSECTION.
3. HANGERS EXPOSED TO VIEW: THREADED ROD AND ANGLE OR CHANNEL SUPPORTS.
4. SUPPORT VERTICAL DUCTS WITH STEEL ANGLES OR CHANNEL SECURED TO THE
SIDES OF THE DUCT WITH WELDS, BOLTS, SHEET METAL SCREWS, OR BLIND
RIVETS; SUPPORT AT EACH FLOOR AND AT A MAXIMUM INTERVALS OF 16 FEET.
5. INSTALL UPPER ATTACHMENTS TO STRUCTURES. SELECT AND SIZE UPPER
ATTACHMENTS WITH PULL-OUT, TENSION, AND SHEAR CAPACITIES APPROPRIATE
FOR SUPPORTED LOADS AND BUILDING MATERIALS WHERE USED.
DUCT INSTALLATION
1. DRAWING PLANS, SCHEMATICS, AND DIAGRAMS INDICATE GENERAL LOCATION AND
ARRANGEMENT OF DUCT SYSTEM. INDICATED DUCT LOCATIONS, CONFIGURATIONS,
AND ARRANGEMENTS WERE USED TO SIZE DUCTS AND CALCULATE FRICTION LOSS
FOR AIR-HANDLING EQUIPMENT SIZING AND FOR OTHER DESIGN CONSIDERATIONS.
INSTALL DUCT SYSTEMS AS INDICATED UNLESS DEVIATIONS TO LAYOUT ARE
APPROVED ON SHOP DRAWINGS AND COORDINATION DRAWINGS.
2. INSTALL DUCTS ACCORDING TO SMACNA'S "HVAC DUCT CONSTRUCTION STANDARDS -
METAL AND FLEXIBLE" UNLESS OTHERWISE INDICATED.
3. INSTALL DUCTS WITH FEWEST POSSIBLE JOINTS.
4. INSTALL FACTORY- OR SHOP-FABRICATED FITTINGS FOR CHANGES IN DIRECTION,
SIZE, AND SHAPE AND FOR BRANCH CONNECTIONS.
5. UNLESS OTHERWISE INDICATED, INSTALL DUCTS VERTICALLY AND HORIZONTALLY,
AND PARALLEL AND PERPENDICULAR TO BUILDING LINES.
6. INSTALL DUCTS CLOSE TO WALLS, OVERHEAD CONSTRUCTION, COLUMNS, AND
OTHER STRUCTURAL AND PERMANENT ENCLOSURE ELEMENTS OF BUILDING.
7. INSTALL DUCTS WITH A CLEARANCE OF 1 INCH, PLUS ALLOWANCE FOR INSULATION
THICKNESS.
8. ROUTE DUCTS TO AVOID PASSING THROUGH TRANSFORMER VAULTS AND ELECTRICAL
EQUIPMENT ROOMS AND ENCLOSURES.
9. WHERE DUCTS PASS THROUGH FIRE-RATED INTERIOR PARTITIONS AND EXTERIOR
WALLS, INSTALL FIRE DAMPERS UNLESS FIRE DAMPER EXCEPTION IS MET PER NOTE
(THIS SHEET).
10. PROTECT DUCT INTERIORS FROM MOISTURE, CONSTRUCTION DEBRIS AND DUST,
AND OTHER FOREIGN MATERIALS
11. PROTECT EXPOSED DUCTS FROM BEING DENTED, SCRATCHED, OR DAMAGED.
12. TRIM DUCT SEALANTS FLUSH WITH METAL. CREATE A SMOOTH AND UNIFORM
EXPOSED BEAD. DO NOT USE TWO-PART TAPE SEALING SYSTEM.
13. GRIND WELDS TO PROVIDE SMOOTH SURFACE FREE OF BURRS, SHARP EDGES, AND
WELD SPLATTER. WHEN WELDING STAINLESS STEEL WITH A NO. 3 OR 4 FINISH,
GRIND THE WELDS FLUSH, POLISH THE EXPOSED WELDS, AND TREAT THE WELDS TO
REMOVE DISCOLORATION CAUSED BY WELDING.
14. MAINTAIN CONSISTENCY, SYMMETRY, AND UNIFORMITY IN THE ARRANGEMENT AND
FABRICATION OF FITTINGS, HANGERS AND SUPPORTS, DUCT ACCESSORIES, AND AIR
OUTLETS.
15. REPAIR OR REPLACE DAMAGED SECTIONS AND FINISHED WORK THAT DOES NOT
COMPLY WITH THESE REQUIREMENTS.
16. SEAL DUCTS TO THE FOLLOWING SEAL CLASSES ACCORDING TO SMACNA'S "HVAC
DUCT CONSTRUCTION STANDARDS - METAL AND FLEXIBLE":
· COMPLY WITH SMACNA'S "HVAC DUCT CONSTRUCTION STANDARDS - METAL
AND FLEXIBLE."
· OUTDOOR, SUPPLY-AIR DUCTS: SEAL CLASS A.
· OUTDOOR, EXHAUST DUCTS: SEAL CLASS C.
· OUTDOOR, RETURN-AIR DUCTS: SEAL CLASS C.
· UNCONDITIONED SPACE, SUPPLY-AIR DUCTS IN PRESSURE CLASSES 2-INCH WG
AND LOWER: SEAL CLASS B.
· UNCONDITIONED SPACE, SUPPLY-AIR DUCTS IN PRESSURE CLASSES HIGHER
THAN 2-INCH WG: SEAL CLASS A.
· UNCONDITIONED SPACE, EXHAUST DUCTS: SEAL CLASS C.
· UNCONDITIONED SPACE, RETURN-AIR DUCTS: SEAL CLASS B.
· CONDITIONED SPACE, SUPPLY-AIR DUCTS IN PRESSURE CLASSES 2-INCH WG
AND LOWER: SEAL CLASS C.
· CONDITIONED SPACE, SUPPLY-AIR DUCTS IN PRESSURE CLASSES HIGHER THAN
2-INCH WG: SEAL CLASS B.
· CONDITIONED SPACE, EXHAUST DUCTS: SEAL CLASS B.
· CONDITIONED SPACE, RETURN-AIR DUCTS: SEAL CLASS C.
17. THE INSTALLATION OF ALL INSULATION SHALL BE PERFORMED BY AN EXPERIENCED
CRAFTSMAN IN A NEAT WORKMANSHIP-LIKE MANNER AND SHALL BE IN ACCORDANCE
WITH THE MANUFACTURER'S WRITTEN PUBLISHED RECOMMENDATIONS FOR SERVICE
INTENDED.
18. CONCEALED INDOOR SUPPLY, RETURN & OUTDOOR AIR DUCTS SHALL BE INSULATED
WITH A MINERAL-FIBER BLANKET, R-6 MINIMUM.
19. LIMIT ALL DUCT LINER TO A MAXIMUM OF 20' IMMEDIATELY UPSTREAM AND
DOWNSTREAM OF AIR HANDLING UNITS. LINER MUST BE CLOSED CELL ELASTOMERIC.
20. EXPOSED OUTDOOR SUPPLY & EXHAUST AIR DUCTS SHALL BE INSULATED WITH A
MINERAL-FIBERBOARD, R-8 MINIMUM. INSTALL JACKET OVER INSULATION MATERIAL.
FOR INSULATION WITH FACTORY-APPLIED JACKET, INSTALL THE FIELD-APPLIED
JACKET OVER THE FACTORY-APPLIED JACKET. DUCTS AND PLENUMS, EXPOSED, UP TO
48 INCHES IN DIAMETER OR WITH FLAT SURFACES UP TO 72 INCHES: ALUMINUM,
SMOOTH MINIMUM 0.020 INCHES THICK.
21. ALL SUPPLY, RETURN & OUTDOOR AIR DUCTS ROUTED IN UNCONDITIONED SPACE
SHALL HAVE MINIMUM R-8 INSULATION. ALL OTHER INSULATION SHALL BE PER
ENERGY CODE UNLESS OTHERWISE NOTED.
22. PROVIDE UV PROTECTIVE COATING/COVERING ON ALL ELASTOMERIC PIPE
INSULATION WHERE EXPOSED TO SUNLIGHT.
METAL DUCT
1. DUCT CONSTRUCTION, INCLUDING SHEET METAL THICKNESSES, SEAM AND JOINT
CONSTRUCTION, REINFORCEMENTS, AND HANGERS AND SUPPORTS, SHALL COMPLY
WITH SMACNA'S "HVAC DUCT CONSTRUCTION STANDARDS - METAL AND FLEXIBLE"
AND PERFORMANCE REQUIREMENTS AND DESIGN CRITERIA INDICATED IN "DUCT
SCHEDULE" ARTICLE.
2. STRUCTURAL PERFORMANCE: DUCT HANGERS AND SUPPORTS SHALL WITHSTAND
THE EFFECTS OF GRAVITY LOADS AND STRESSES WITHIN LIMITS AND UNDER
CONDITIONS DESCRIBED IN SMACNA'S "HVAC DUCT CONSTRUCTION STANDARDS -
METAL AND FLEXIBLE".
3. AIRSTREAM SURFACES: SURFACES IN CONTACT WITH THE AIRSTREAM SHALL
COMPLY WITH REQUIREMENTS IN ASHRAE 62.1-2004.
REFRIGERANT PIPING INSTALLATION
A. DRAWING PLANS, SCHEMATICS, AND DIAGRAMS INDICATE GENERAL LOCATION AND
ARRANGEMENT OF PIPING SYSTEMS; INDICATED LOCATIONS AND ARRANGEMENTS
WERE USED TO SIZE PIPE AND CALCULATE FRICTION LOSS, EXPANSION, PUMP
SIZING, AND OTHER DESIGN CONSIDERATIONS. INSTALL PIPING AS INDICATED
UNLESS DEVIATIONS TO LAYOUT ARE APPROVED ON SHOP DRAWINGS.
B. INSTALL REFRIGERANT PIPING ACCORDING TO ASHRAE 15.
C. INSTALL PIPING IN CONCEALED LOCATIONS UNLESS OTHERWISE INDICATED AND
EXCEPT IN EQUIPMENT ROOMS AND SERVICE AREAS.
D. INSTALL PIPING INDICATED TO BE EXPOSED AND PIPING IN EQUIPMENT ROOMS AND
SERVICE AREAS AT RIGHT ANGLES OR PARALLEL TO BUILDING WALLS. DIAGONAL
RUNS ARE PROHIBITED UNLESS SPECIFICALLY INDICATED OTHERWISE.
E. INSTALL PIPING ABOVE ACCESSIBLE CEILINGS TO ALLOW SUFFICIENT SPACE FOR
CEILING PANEL REMOVAL.
F. INSTALL PIPING ADJACENT TO MACHINES TO ALLOW SERVICE AND MAINTENANCE.
G. INSTALL PIPING FREE OF SAGS AND BENDS.
H. INSTALL FITTINGS FOR CHANGES IN DIRECTION AND BRANCH CONNECTIONS.
I. SELECT SYSTEM COMPONENTS WITH PRESSURE RATING EQUAL TO OR GREATER
THAN SYSTEM OPERATING PRESSURE.
J. INSTALL PIPING AS SHORT AND DIRECT AS POSSIBLE, WITH A MINIMUM NUMBER OF
JOINTS, ELBOWS, AND FITTINGS.
K. ARRANGE PIPING TO ALLOW INSPECTION AND SERVICE OF REFRIGERATION
EQUIPMENT. INSTALL VALVES AND SPECIALTIES IN ACCESSIBLE LOCATIONS TO
ALLOW FOR SERVICE AND INSPECTION. INSTALL ACCESS DOORS OR PANELS AS IF
VALVES OR EQUIPMENT REQUIRING MAINTENANCE IS CONCEALED BEHIND FINISHED
SURFACES.
L. INSTALL REFRIGERANT PIPING IN PROTECTIVE CONDUIT WHERE INSTALLED
BELOWGROUND.
M. INSTALL REFRIGERANT PIPING IN RIGID OR FLEXIBLE CONDUIT IN LOCATIONS
WHERE EXPOSED TO MECHANICAL INJURY.
N. SLOPE REFRIGERANT PIPING AS FOLLOWS:
1. INSTALL HORIZONTAL HOT-GAS DISCHARGE PIPING WITH A UNIFORM SLOPE
DOWNWARD AWAY FROM COMPRESSOR.
2. INSTALL HORIZONTAL SUCTION LINES WITH A UNIFORM SLOPE DOWNWARD TO
COMPRESSOR.
3. INSTALL TRAPS AND DOUBLE RISERS TO ENTRAIN OIL IN VERTICAL RUNS.
4. LIQUID LINES MAY BE INSTALLED LEVEL.
P. WHEN BRAZING OR SOLDERING, REMOVE SOLENOID-VALVE COILS AND SIGHT
GLASSES; ALSO REMOVE VALVE STEMS, SEATS, AND PACKING, AND ACCESSIBLE
INTERNAL PARTS OF REFRIGERANT SPECIALTIES. DO NOT APPLY HEAT NEAR
EXPANSION-VALVE BULB.
Q. INSTALL PIPING WITH ADEQUATE CLEARANCE BETWEEN PIPE AND ADJACENT WALLS
AND HANGERS OR BETWEEN PIPES FOR INSULATION INSTALLATION.
R. INSTALL SLEEVES FOR PIPING PENETRATIONS OF WALLS, CEILINGS, AND FLOORS.
S. INSTALL SLEEVE SEALS FOR PIPING PENETRATIONS OF CONCRETE WALLS AND
SLABS.
T. INSTALL ESCUTCHEONS FOR PIPING PENETRATIONS OF WALLS, CEILINGS, AND
FLOORS.
REFRIGERANT PIPE JOINT CONSTRUCTION
A. SOLDERED JOINTS: CONSTRUCT JOINTS ACCORDING TO ASTM B 828 OR CDA'S
"COPPER TUBE HANDBOOK."
B. BRAZED JOINTS: CONSTRUCT JOINTS ACCORDING TO AWS'S "BRAZING HANDBOOK,"
CHAPTER "PIPE AND TUBE."
1. USE TYPE BCUP, COPPER-PHOSPHORUS ALLOY FOR JOINING COPPER SOCKET
FITTINGS WITH COPPER PIPE.
2. USE TYPE BAG, CADMIUM-FREE SILVER ALLOY FOR JOINING COPPER WITH
BRONZE OR STEEL.
REFRIGERANT PIPE HANGERS AND SUPPORTS
PIPING HANGERS AND SUPPORTS MUST ACCOMMODATE EXPANSION AND CONTRACTION,
VIBRATION, DEAD LOAD OF PIPING AND ITS CONTENTS, AND SEISMIC-BRACING
REQUIREMENTS.
A. HANGER, SUPPORT, AND ANCHOR PRODUCTS ARE SPECIFIED IN SECTION 230529
"HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT."
B. INSTALL THE FOLLOWING PIPE ATTACHMENTS:
1. ADJUSTABLE STEEL CLEVIS HANGERS FOR INDIVIDUAL HORIZONTAL RUNS LESS
THAN 20 FEET LONG.
2. ROLLER HANGERS AND SPRING HANGERS FOR INDIVIDUAL HORIZONTAL RUNS 20
FEET OR LONGER.
3. PIPE ROLLER: MSS SP-58, TYPE 44 FOR MULTIPLE HORIZONTAL PIPING 20 FEET
OR LONGER, SUPPORTED ON A TRAPEZE.
4. SPRING HANGERS TO SUPPORT VERTICAL RUNS.
5. COPPER-CLAD HANGERS AND SUPPORTS FOR HANGERS AND SUPPORTS IN
DIRECT CONTACT WITH COPPER PIPE.
C. INSTALL HANGERS FOR COPPER TUBING WITH THE FOLLOWING MAXIMUM SPACING
AND MINIMUM ROD SIZES:
VERIFY ACTUAL SUPPORTED LOADS FOR HANGER SIZES AND SPACING. CONSULT
STRUCTURAL ENGINEER. SPACING AND SIZES IN SUBPARAGRAPHS BELOW ARE FROM THE
2000 ASHRAE HANDBOOK - "HVAC SYSTEMS AND EQUIPMENT."
1. NPS 1/2: MAXIMUM SPAN, 60 INCHES; MINIMUM ROD SIZE, 1/4 INCH.
2. NPS 5/8: MAXIMUM SPAN, 60 INCHES; MINIMUM ROD SIZE, 1/4 INCH.
3. NPS 1: MAXIMUM SPAN, 72 INCHES; MINIMUM ROD SIZE, 1/4 INCH.
4. NPS 1-1/4: MAXIMUM SPAN, 96 INCHES; MINIMUM ROD SIZE, 3/8 INCH.
5. NPS 1-1/2: MAXIMUM SPAN, 96 INCHES; MINIMUM ROD SIZE, 3/8 INCH.
6. SUPPORT MULTIFLOOR VERTICAL RUNS AT LEAST AT EACH FLOOR.
REFRIGERANT PIPE FIELD QUALITY CONTROL
A. PERFORM TESTS AND INSPECTIONS AND PREPARE TEST REPORTS.
B. TESTS AND INSPECTIONS:
1. COMPLY WITH ASME B31.5, CHAPTER VI.
2. TEST REFRIGERANT PIPING AND SPECIALTIES. ISOLATE COMPRESSOR,
CONDENSER, EVAPORATOR, AND SAFETY DEVICES FROM TEST PRESSURE IF THEY
ARE NOT RATED ABOVE THE TEST PRESSURE.
3. TEST HIGH- AND LOW-PRESSURE SIDE PIPING OF EACH SYSTEM SEPARATELY AT
NOT LESS THAN THE PRESSURES INDICATED IN PART 1 "PERFORMANCE
REQUIREMENTS" ARTICLE.
a. FILL SYSTEM WITH NITROGEN TO THE REQUIRED TEST PRESSURE.
b. SYSTEM SHALL MAINTAIN TEST PRESSURE AT THE MANIFOLD GAGE
THROUGHOUT DURATION OF TEST.
c. TEST JOINTS AND FITTINGS WITH ELECTRONIC LEAK DETECTOR OR BY
BRUSHING A SMALL AMOUNT OF SOAP AND GLYCERIN SOLUTION OVER
JOINTS.
d. REMAKE LEAKING JOINTS USING NEW MATERIALS, AND RETEST UNTIL
SATISFACTORY RESULTS ARE ACHIEVED.
REFRIGERANT SYSTEM CHARGING
A. CHARGE SYSTEM USING THE FOLLOWING PROCEDURES:
1. INSTALL CORE IN FILTER DRYERS AFTER LEAK TEST BUT BEFORE EVACUATION.
2. EVACUATE ENTIRE REFRIGERANT SYSTEM WITH A VACUUM PUMP TO 500
MICROMETERS. IF VACUUM HOLDS FOR 12 HOURS, SYSTEM IS READY FOR
CHARGING.
3. BREAK VACUUM WITH REFRIGERANT GAS, ALLOWING PRESSURE TO BUILD UP TO
2 PSIG.
4. CHARGE SYSTEM WITH A NEW FILTER-DRYER CORE IN CHARGING LINE.
REFRIGERANT SYSTEM ADJUSTING
A. ADJUST THERMOSTATIC EXPANSION VALVE TO OBTAIN PROPER EVAPORATOR
SUPERHEAT.
B. ADJUST HIGH- AND LOW-PRESSURE SWITCH SETTINGS TO AVOID SHORT CYCLING IN
RESPONSE TO FLUCTUATING SUCTION PRESSURE.
C. ADJUST SET-POINT TEMPERATURE OF AIR-CONDITIONING OR CHILLED-WATER
CONTROLLERS TO THE SYSTEM DESIGN TEMPERATURE.
D. PERFORM THE FOLLOWING ADJUSTMENTS BEFORE OPERATING THE REFRIGERATION
SYSTEM, ACCORDING TO MANUFACTURER'S WRITTEN INSTRUCTIONS:
1. OPEN SHUTOFF VALVES IN CONDENSER WATER CIRCUIT.
2. VERIFY THAT COMPRESSOR OIL LEVEL IS CORRECT.
3. OPEN COMPRESSOR SUCTION AND DISCHARGE VALVES.
4. OPEN REFRIGERANT VALVES EXCEPT BYPASS VALVES THAT ARE USED FOR OTHER
PURPOSES.
5. CHECK OPEN COMPRESSOR-MOTOR ALIGNMENT AND VERIFY LUBRICATION FOR
MOTORS AND BEARINGS.
E. REPLACE CORE OF REPLACEABLE FILTER DRYER AFTER SYSTEM HAS BEEN ADJUSTED
AND AFTER DESIGN FLOW RATES AND PRESSURES ARE ESTABLISHED.
HVAC - AIR DISTRIBUTION TAG
DIFFUSER SIZE EXAMPLE:
24x24 DIFFUSER WITH A
10"ø NECK.
NOTES:
RUNOUT SIZE TO
ROUND NECK
DIFFUSER IS THE
SAME SIZE AS THE
DIFFUSER NECK UNLESS
NOTED OTHERWISE.
2410
360 CFM
DIFFUSER TYPE
DESIGNATION
AIR QUANTITY
B
SQUARE DUCT TAKE OFF, BOTTOM
2/1/2017 5:14:29 P
M
El P
aso
, T
exa
s
TR
U b
y H
ilto
n - E
l P
as
o
Tru
H
ote
l P
artn
ers, L
LC
16105
Revision Schedule
Rev.
Num.Rev. Date Revision Description
AEED,
Advanced Energy Engineering & Design, Inc
CHATTANOOGA, TN 37405
BUS. (423) 752-3438
FAX (423) 752-1369
P.O. BOX 4934
408 McCALLIE AVE
inc.
AEED JOB NO.001-17
COPYRIGHT NOTICE
THE DRAWINGS ARE THE
PROPERTY OF RIVER STREET
ARCHITECTURE LLC. ANY USE,
REUSE, REPRODUCTION,
DISPLAY OR SALE OF THESE
DRAWINGS WITHOUT THE
EXPRESS WRITTEN CONSENT
OF THE ARCHITECT IS
STRICTLY PROHIBITED.
714 cherry street, chattanooga, tennessee 37402
p.423 634 0806 f.423 752 8499 w
ww
.riverstreetarchitecture.com
Release Date:
Project No.:
9
0
%
C
D
S
E
T
X
X
X
X
X
X
X
X
3/13/17
M2-03 MECHANICAL - DETAILS 3 of 3
9
0
%
C
D
S
E
T
X
X
X
X
X
X
X
X
5/11/17
X
________________________________________________________________________
BY DATE
05/31/2017
ENGINEERING & CONSTRUCTION
MANAGEMENT DEPARTMENT
MECHANICAL REVIEW
These Plans Have Been Reviewed For General Conformity And
Permit May be Issued Subject To All Applicable Provisions Of
The City Plumbing and Gas Code.
__________________________________________________________
BY DATE
05/31/2017
C
D
H C
14
14
15
15
16
16
17
17
D D
C C
A A
B B
E E
cen
F F
13
13
12
1211
10
10
6
6
7
7
8
8
9
9
5
5
4
4
3
3
1
1
2
2
G G
0.a 0.a
LOUNGE
1003
WORK ZONE
1002
VESTIBULE
1000
COMMAND
CENTER
1001
DINING
1004
GAME ZONE
1005
WATER/ICE
1008
ELEVATOR
LOBBY
1006
3500
2500
COORIDOR
1007A
WOMEN
1010
MEN
1011
DRYERS
019
CORRIDOR
1026
STAIR 2
S102
PBX
1028
OFFICE
1030
G.M. OFFICE
1029
MECH
1024
RISER ROOM
1025
FITNESS
1009
ELEV. EQUIP
1015
LAUNDRY
1017
LINEN STORAGE
1016
PASSAGE
1020
ELECTRICAL
1023
WATER ROOM
1021
JANITOR
1022
PANTRY
1027
STAIR 1
S101
EMPLOYEE
BREAK ROOM
1013
GUEST
CORRIDOR
1007B
SHAFT 1
LINEN
TERMINATION
1018
108
104
109
ACC KING
SHOWER
HEARING
107
105
103
101
KING
102
QQ HEARING
106
BREAKFAST
005
8"∅ 6"∅ 4"∅6"∅ 4"∅
PTAC-1
CFM 30
8x8
A
CFM 30
8x8
E
8"∅
8"∅ 6"∅
PTAC-1
111
1
CCU-1
S
HWFC-1
CFM200
2408
A
(TYPICAL OF 4)
24x24
B
14x12 10"∅
S
CFM 75
2406
A
CFM175
2408
A
(TYPICAL OF 3)
12x10
12x12
S
6"∅
10"∅
CFM180
2408
A
8"∅
6"∅
10x10
14x10
10"∅
6"∅
8"∅
10"∅
CFM 30
8x8
B
CFM 50
2406
C
CFM150
24x24
B
CFM 60
12x12
B
6"∅12x12
24x12
CFM150
24x24
B
8"∅
24x12
20x16
D
CFM
300
48" x 2 Slot
10"∅
20x10
CFM1200
24x24
B
FSD
FSD
FSD
10"∅
AHU-3
AHU-5
FD FD
FD FD
FD FD
FD
FD
FD
FD
FD
CFM 30
6x6
C
CFM 30
6x6
C
CFM 30
6x6
C
CFM 30
6x6
C
CFM 30
6x6
C
CFM 30
6x6
C
CFM180
2408
A
17
EWH-4
12
11
8
2
5
6
2
CFM 50
12x12
B
CFM 50
12x12
B
4
HP-3
HP-6
4
HP-8
4
4
HP-5
77
7
7
M
9
10
20x14
16
CFM 30
6x6
C
CFM 30
6x6
C
CFM 30
6x6
C
8"∅
PTAC-1
111
PTAC-1
111
PTAC-1
111
PTAC-1
111
PTAC-1
111
PTAC-1
111
PTAC-1
111
24x24
B
S
MAU-1
19
18 18 18
18
18
18
22
18
20
19
20
20
24x14
CFM665
36x8
C
16x14 16x12
CFM665
36x8
C
CFM150
2408
AD
CFM
300
48" x 2 Slot
10"∅D
CFM
200
48" x 2 Slot
10"∅(TYPICAL OF 2)
10"∅
18x14
D
CFM
250
48" x 2 Slot
10"∅
D
CFM
250
48" x 2 Slot
10"∅D
CFM
250
48" x 2 Slot
10"∅
18x12 18x10 12"∅ 10"∅
CFM300
36x8
C
CFM300
36x8
C
CFM135
2408
A
CFM150
2408
A
CFM120
2406
A
CFM120
2406
A
24x12
B
12x12
B
(TYPICAL OF 3)
S
S
S
16x12
CFM 50
8x8
B
8"∅
10"∅
6"∅
AHU-1
AHU-2
AHU-4
FD
FD
16
EWH-1
2
2
4
HP-2
4
HP-1
4
HP-4
3
EWH-2
7
12x10
10x10
10
1010
1010
1313
1313
SD
T
SD
T
SDT
16
EWH-3
16
HP-7
4
HWFC-2
5
18
18
18
19
18
18
1818
18
19
1 M
M
2
12x12
M
3
22x14
22x18
1
M
M 2
3 M
FD
SDT
21
22
14
14
6"∅
24x24
B
(TYPICAL OF 2)
10
D
CFM
250
48" x 2 Slot
10"∅
24x24
B
20
BRD
19
S
MAU-2
23
12x10
FSD
FD
8"∅
CFM 60
12x12
B
6"∅6"∅
6"∅CFM 80
8x8
B
6"∅
10"∅
22x18
8"∅
8"∅
15
15
7
6"∅
M1-01
1
SCALE: 1/8"= 1'-0"
MECHANICAL - HVAC - 1ST FLOOR
MECHANICAL
HVAC
1ST FLOOR
M1-01
a. FOR GENERAL HVAC NOTES SEE COVER SHEET. IN THE CASE OF CONFLICTING NOTES THE MOST
STRINGENT OF THE TWO SHALL APPLY PER APPLICABLE JOB CODE.
b. ROUND DUCT RUNOUTS TO INDIVIDUAL DIFFUSERS TO BE SAME SIZE AS DIFFUSER NECK UNLESS
NOTED.
c. MAINTAIN 10 FT. (MIN.) SEPARATION BETWEEN OUTSIDE AIR INTAKES AND EXHAUST OR VENT
OPENINGS.
d. EXTEND FULL SIZE CONDENSATE DRAIN LINE FROM EACH A/C UNIT AND TERMINATE AT FLOOR DRAIN,
ROOF DRAIN, FRENCH DRAIN, OR OTHER TERMINATION POINTS AS DIRECTED. TRAP AND VENT DRAIN
LINE AT CONNECTION TO COIL.
e. INSTALL SMOKE DETECTORS (PROVIDED BY ELECTRICAL) AT EACH A/C UNIT HANDLING OVER 2000 CFM,
MOUNTED IN SA DUCT (NFPA 90A, 4-4.2), AND IN RA DUCT PRIOR TO EXHAUST OR MIXING (SMC 406.1).
ALSO INSTALL SMOKE DETECTOR AT EACH A/C UNIT SERVING BUILDING EGRESS (REGARDLESS OF SIZE),
MOUNTED IN SA DUCT. DETECTOR(S) TO STOP UNIT FAN IF SMOKE IS DETECTED. INTERLOCK WITH
FIRE ALARM SYSTEM.
f. REFRIGERANT PIPING TO BE SIZED BY EQUIPMENT MANUFACTURER OR FACTORY- AUTHORIZED
REPRESENTATIVE. SIZING CALCULATIONS TO BE BASED ON ACTUAL FIELD ROUTING AND
CONFIGURATION.
g. FOR ALL GUEST ROOM THERMOSTATS: REMOTE THERMOSTAT TO BE MOUNTED AT 48" ABOVE
FINISH FLOOR IN ACCESSIBLE ROOMS AND AT 54" ABOVE FINISH FLOOR IN NON-ACCESSIBLE
ROOMS AT DEMISING WALL. SEE SHEET LARGE SCALE ROOM PLAN (SHEET E3-01) FOR
THERMOSTAT TYPICAL LOCATIONS.
HVAC SHEET NOTES - UNREFERENCED
2/1/2017 5:14:29 P
M
El P
aso
, T
exa
s
TR
U b
y H
ilto
n - E
l P
as
o
Tru
H
ote
l P
artn
ers, L
LC
16105
Revision Schedule
Rev.
Num.Rev. Date Revision Description
AEED,
Advanced Energy Engineering & Design, Inc
CHATTANOOGA, TN 37405
BUS. (423) 752-3438
FAX (423) 752-1369
P.O. BOX 4934
408 McCALLIE AVE
inc.
AEED JOB NO.001-17
COPYRIGHT NOTICE
THE DRAWINGS ARE THE
PROPERTY OF RIVER STREET
ARCHITECTURE LLC. ANY USE,
REUSE, REPRODUCTION,
DISPLAY OR SALE OF THESE
DRAWINGS WITHOUT THE
EXPRESS WRITTEN CONSENT
OF THE ARCHITECT IS
STRICTLY PROHIBITED.
714 cherry street, chattanooga, tennessee 37402
p.423 634 0806 f.423 752 8499 w
ww
.riverstreetarchitecture.com
Release Date:
Project No.:
1
HVAC SHEET NOTES - REFERENCED
MOUNT PACKAGED THROUGH-THE -WALL HEAT PUMP UNITS AS DIRECTED BY MANUFACTURER.
· PROVIDE UNIT WITH ACCESSORIES LISTED IN SCHEDULE
· CONFIRM ALL ROUGH-IN DIMENSIONS AND REQUIREMENTS WITH GENERAL CONTRACTOR IN THE
FIELD. ACCOUNT FOR SUB-BASE HEIGHT WHEN DETERMINING A.F.F. INSTALLATION HEIGHT
· SEAL ALL WALL PENETRATIONS WEATHER TIGHT
· ROUTE CONDENSATE LINES AS SHOWN, SLOPE LINE 1/8" PER 1'-0" AWAY FROM COIL
2
HORIZONTAL MOUNTED AIR HANDLER
· SUSPEND AIR HANDLER ABOVE CEILING USING VIBRATION ISOLATION HANGERS
· PROVIDE AUXILIARY CONDENSATE DRAIN PAN UNDER UNIT
· PROVIDE REINFORCED NEOPRENE FLEXIBLE DUCT AT SUPPLY AND RETURN CONNECTION POINTS
· INSTALL MANUAL BALANCING DAMPERS IN OUTSIDE AIR AND RETURN DUCTS FOR PROPER BALANCING
· ROUTE FULL SIZE CONDENSATE DRAIN LINE AS SHOWN, SLOPE LINE 1/8" PER 1'-0" AWAY FROM COIL
3
FLOOR MOUNTED VERTICAL AC UNIT
· MOUNT A/C UNIT ON 1/4" NEOPRENE ISOLATOR ON 24" HIGH RETURN AIR PLENUM AND CONFIGURE
FOR BOTTOM RETURN
· PROVIDE REINFORCED NEOPRENE FLEXIBLE DUCT AT SUPPLY AND RETURN CONNECTION POINTS
· ROUTE CONDENSATE DRAIN LINE AS SHOWN, SLOPE LINE 1/8" PER 1'-0" AWAY FROM COIL
· CONFIGURE UNIT IN SPACE TO ALLOW MFG SERVICE CLEARANCES & FILTER ACCESS
4 MOUNT CONDENSING UNIT AT GRADE ON 6" THICK RE-INFORCED CONCRETE PAD
· PAD EXTENDS 6" ON EVERY SIDE OF UNIT
· MAINTAIN 36" CLEARANCE TO ELECTRICAL ACCESS PANELS
· ROUTE REFRIGERANT PIPING FROM CONDENSING UNIT UP IN EXTERIOR WALL (OR CHASE) AND TO
CORRESPONDING A/C UNIT
· MINIMIZE PIPING EXPOSED ON EXTERIOR
· SEAL ALL PENETRATIONS TO EXTERIOR WEATHER TIGHT
· MAINTAIN MANUFACTURERS RECOMMENDED CLEARANCES BETWEEN/AROUND UNITS
5INDOOR WALL MOUNT AC UNIT
· MOUNT AT A MINIMUM OF 6'-0" A.F.F. AND IN A MANNER TO NOT INTERFERE WITH ELEVATOR
EQUIPMENT
· ROUTE CONDENSATE DRAIN LINE TO FLOOR DRAIN IN ELEVATOR ROOM AS SHOWN, SLOPE LINE
1/8" PER 1'-0" AWAY FROM COIL
6CEILING MOUNTED CASSETTE UNIT
· SUSPEND UNIT FLUSH WITH CEILING USING VIBRATION ISOLATION HANGERS
· PROVIDE 6"∅ OUTDOOR AIR DUCT, PROVIDE MANUAL BALANCING DAMPER
· UNIT USES CONDENSATE DRAIN PUMP TO ACHIEVE PROPER SLOPE FOR CONDENSATE RUN OFF
· ROUTE CONDENSATE DRAIN LINE AS SHOWN, SLOPE LINE 1/8" PER 1'-0" AWAY FROM COIL
7 DOOR MOUNTED TRANSFER GRILLE
· 12x6 GRILLE MOUNTED 12" ABOVE BOTTOM OF DOOR
· GRILLE SIZE BASED ON MFG: TITUS MODEL: CT-700L
· PROVIDE COMPLETE WITH AUXILIARY FRAME
8
9
10
CABLE CONTROLLED BALANCING DAMPER (SEE DETAIL)
· INSTALL PER MANUFACTURERS SUGGESTED GUIDELINES
· TYPICAL OF ANY APPLICATION WHERE ACCESS TO MANUAL DAMPER IS RESTRICTED OR UNDESIRED.
11
OUTDOOR AIR SUPPLY AND EXHAUST DUCTS FROM FLOOR ABOVE.
· 14x10 SUPPLY
· 12x12 EXHAUST
· PROVIDE COMBINATION FIRE/SMOKE DAMPER AT BOTTOM OF CHASE PENETRATION POINTS.
12
OUTDOOR AIR SUPPLY AND EXHAUST DUCTS FROM FLOOR ABOVE.
· 20x14 SUPPLY
· 20x16 EXHAUST
· PROVIDE COMBINATION FIRE/SMOKE DAMPER AT CHASE PENETRATION POINTS.
13
SIDE WALL SUPPLY GRILLE
· MOUNT GRILLE IN SIDE OF SOFFIT
· PROVIDE WITH FACE ACCESSIBLE MANUAL BALANCING DAMPER
14
15 DUCT MOUNTED SMOKE DETECTORS IN SUPPLY AND RETURN DUCTS
· SUPPLY DETECTOR TO BE INSTALLED PRIOR TO ANY TAKEOFFS
· RETURN DETECTOR TO BE INSTALLED PRIOR TO MIXING WITH OUTDOOR AIR
· DETECTORS TO BE PROVIDED AND WIRED BY ELECTRICAL CONTRACTOR AND INSTALLED
IN DUCT BY MECHANICAL CONTRACTOR
16ELECTRIC HEATER
· MOUNT WALL HEATER MINIMUM 6" A.F.F., UNIT TO BE SURFACE MOUNTED ON WALL.
· SET UNIT THERMOSTAT TO ENERGIZE UPON A DETECTION OF SPACE TEMPERATURE TO BE
DETERMINED BY OWNER
176x6 EXHAUST GRILLE TYPE 'E' WITH 4"∅ DUCT CONNECTION
· PROVIDE WITH MANUAL BALANCING DAMPER
· BALANCE GRILLE TO 25CFM OF EXHAUST AIR
· TYPICAL OF ALL GUEST BATHROOMS UNLESS NOTED OTHERWISE
DRYER VENTILATION SYSTEM
· EXTEND 14" ROUND DRYER VENT FROM COMMERCIAL-TYPE CLOTHES DRYER TO PLENUM OFF BACK OF
COMMON LOUVER IN EXTERIOR WALL
· WRAP VENT WITH ZERO CLEARANCE FIRE RESISTANT DUCT WRAP EQUAL TO 3M FIRE BARRIER DUCT
WRAP OR LIKE MATERIAL TO WITHSTAND DRYER VENT HEAT
· DRYER VENTS TERMINATE AT 42x24 WALL LOUVER. SLEEVE AND SEAL PENETRATION WEATHER TIGHT.
· LOUVER SIZED TO PROVIDE A FREE AREA OF 3.30ft2 TO ALLOW 2760CFM EXHAUST AT 850FPM. (920CFM
PER DRYER x 3)
· LOUVER BASED ON MANUFACTURER: UNITED ENERTECH MODEL: FL-D-4
· VENTS TO BE SINGLE WALL GALVANIZED STEEL MIN. 0.0195 INCHES THICK
· INSTALL ESCUTCHEON PLATE AT PENETRATION OF ROOM SURFACES
· REVIEW MANUFACTURER'S VENTING REQUIREMENTS BEFORE COMMENCING WORK
· DRYER VENTS ARE TO HAVE SMOOTH INTERIOR SURFACES
· RIVET ALL CONNECTIONS & MAINTAIN CODE REQUIRED CLEARANCES
PROVIDE ONE (1) 24x18 WALL LOUVER TO PROVIDE COMBUSTION/VENTILATION AIR FOR DRYERS.
· MOUNT LOUVER 6" BELOW CEILING/ROOF STRUCTURE.
· SLEEVE BUILDING PENETRATION AND SEAL WEATHER TIGHT.
· LOUVER DESIGN BASED ON UNITED ENERTECH MODEL FL-D-4.
· PROVIDE LOUVER WITH A MOTORIZED DAMPER INTERLOCKED WITH DRYERS FOR SIMULTANEOUS
OPERATION.
· DAMPER SHALL ACTUATE OPEN FULLY UPON A MINIMUM OF ONE DRYER ACTIVATION.
· EXACT LOUVER LOCATION IS TO BE COORDINATED WITH ARCHITECTURAL.
· LOUVER IS SIZED TO ALLOW A MINIMUM 135.0 SQinch (0.94 SQft) OF FREE AREA PER LOUVER AS
REQUIRED BY 2012 INT FUEL GAS CODE (304.6.2) (1 SQinch OF FREE AREA PER 3,000 btuh OF
COMBUSTION AT A TOTAL INPUT LOAD OF 405,000 btuh)
· PROVIDE COMPLETE WITH BUG SCREEN.
18
3/4" CONDENSATE PIPING
· ROUTE CONDENSATE LINE DOWN IN EXTERIOR WALL
· CONDENSATE LINES SHALL BE INSULATED TO PREVENT PIPE SWEATING IN WALL/ABOVE CEILING.
· SLOPE CONDENSATE DRAIN LINE 1/8" PER 1'-0" AWAY FROM COIL
· LINE EXITS WALL AT SLAB LEVEL, SLEEVE AND SEAL BUILDING PENETRATION WEATHER TIGHT.
· LINE IS TO SPILL IN DRY WELL AT GRADE. (SEE DRY WELL DETAIL)
19
2" CONDENSATE STACK
· ROUTE CONDENSATE LINE DOWN IN EXTERIOR WALL
· CONDENSATE LINE SHALL BE INSULATED TO PREVENT PIPE SWEATING IN WALL/ABOVE CEILING.
· SLOPE CONDENSATE DRAIN LINE 1/8" PER 1'-0" AWAY FROM COIL
· LINE EXITS WALL AT SLAB LEVEL, SLEEVE AND SEAL BUILDING PENETRATION WEATHER TIGHT.
· LINE IS TO SPILL IN DRY WELL AT GRADE. (SEE DRY WELL DETAIL)
20
ECONOMIZER ASSEMBLY FOR AIR HANDLING UNIT
· EXTEND DUCT OFF RETURN SECTION OF AIR HANDLER TO OUTDOOR AIR LOUVER AS SHOWN
· MOTORIZED DAMPERS ALLOW FULL ECONOMIZER CYCLE PER ECONOMIZER SEQUENCE OF
OPERATIONS (SHEET M2-03)
21 30x18 OUTDOOR AIR LOUVER
· SLEEVE AND SEAL AROUND LOUVER WEATHER TIGHT
· LOUVER SELECTION BASED ON MFG: UNITED ENERTECH MODEL: FL-D-4
· LOUVER SIZED TO ALLOW FULL ECONOMIZER CYCLE INTAKE OF 1600cfm @ A MAXIMUM OF 1000fpm
22 30x24 OUTDOOR AIR LOUVER
· SLEEVE AND SEAL AROUND LOUVER WEATHER TIGHT
· LOUVER SELECTION BASED ON MFG: UNITED ENERTECH MODEL: FL-D-4
· LOUVER SIZED TO ALLOW FULL ECONOMIZER CYCLE INTAKE OF 2180cfm @ A MAXIMUM OF 1000fpm
POSITIVE PRESSURE RELIEF ASSEMBLY (FOR ECONOMIZER CYCLE OF AHU-1 & AHU-2)
· PROVIDE 24x18 DUCT FROM GRILLE TO 24x18 LOUVER IN EXTERIOR WALL
· INSTALL BAROMETRIC RELIEF DAMP IN DUCT TO ACTUATE OPEN UPON EXCESS BUILD UP
OF OUTSIDE AIR DUE TO ECONOMIZER CYCLE OF AHU-1 & AHU-2
· LOUVER SELECTION BASED ON MFG: UNITED ENERTECH MODEL: FL-D-4
23ROOF MOUNTED OUTDOOR AIR UNIT CONTROLS
· LOCATE MAU-1 & MAU-2 SYSTEM CONTROLS IN ENGINEERING OFFICE AS SHOWN.
· UNITS ARE TO RUN CONTINUOUSLY, CONTROLS ARE FOR SHUTDOWN AND MONITORING
PURPOSES ONLY.
________________________________________________________________________
BY DATE
05/31/2017
D D
C C
A A
B B
E E
cen
F F
G G
ELEVATOR
LOBBY
2001
3500
2500
LINEN AND
STORAGE
2004
LINEN DROP
2002
ELECTRICAL
2003
CORRIDOR
2000
STAIR 2
S102
STAIR 1
S101
SHAFT 1
SHAFT 2
X501
LINEN
AREA OF
REFUGE
AREA OF
REFUGE
KING
213
211
KING HEARING
215
KING
217
KING
219
QQ CONNECTOR
212
ACC QUEEN
210
KING
226
KING
224
222
QQ HEARING
220
KING
218
KING
216
KING
214
208
206
204
KING
202
KING
227
KING
225
KING
223
KING HEARING
221
205
201
203
ACC KING
207
QQ CONECTOR
209
8"∅FD FD FD
6"∅ 4"∅FD FD FD
FDFDFD
FD
FD
FD
10"∅FDFD
8"∅FD
FD
FDFD
FD FD
FD
FD
FD
10"∅FD FD
8"∅FD
FD
FD
12x1012x10
FD
FD
FD FD FD FD
8"∅ 6"∅ 4"∅
10"∅ 8"∅ 6"∅FDFDFD
FD
FDFD
10"∅8"∅FD FD FD FD FD FD FDFD
6"∅
10"∅FD
8"∅FD
FD FDFD FD
8"∅FD FD
4"∅FD
6"∅4"∅FDFDFDFDFDFDFD
FSD
FSD
PTAC-1
1
PTAC-1
1
FDFD
1
1
4
4
10
5
5
5
CFM 30
6x6
C
CFM 30
6x6
C
CFM 30
6x6
C
CFM 30
6x6
C
CFM 30
6x6
C
CFM 30
6x6
C
CFM 30
6x6
C
CFM 30
6x6
C
CFM 30
6x6
C
CFM 35
6x6
C
CFM 30
6x6
C
CFM 30
6x6
C
CFM 30
6x6
C
CFM 30
6x6
C
CFM 30
6x6
C
CFM 30
6x6
C
CFM 30
6x6
C
CFM 30
6x6
C
CFM 30
6x6
C
CFM 30
6x6
C
CFM 30
6x6
C
CFM 30
6x6
C
CFM 30
6x6
C
CFM 30
6x6
C
CFM 30
6x6
C
CFM 30
6x6
C
CFM 30
6x6
C
5
5
5
5
6 6 66
PTAC-1
11
PTAC-1
11
PTAC-1
11
PTAC-1
11
PTAC-1
11
PTAC-1
11
PTAC-1
11
PTAC-1
11
PTAC-1
11
PTAC-1
11
PTAC-1
11
PTAC-1
11
PTAC-1
11
PTAC-1
11
PTAC-1
11
PTAC-1
11
PTAC-1
11
PTAC-1
11
PTAC-1
11
PTAC-1
11
PTAC-1
11
PTAC-1
11
PTAC-1
11
PTAC-1
11
PTAC-1
11
10"∅8"∅
8"∅
8"∅ 8"∅ 8"∅ 8"∅
8888
8888
8
8
8
8
8
8
8
8 8
8
FD
FD
FD
FD
FD FD
FD
FD
FSD
FSD
18x10
4
4
4 4
4
9
FD
CFM 15
8x8
A
CFM180
2408
A
22x10
CFM200
12x24
B
20x10
14x10
24x10
CFM120
12x6
C
CFM120
12x6
C
CFM120
12x6
C
CFM120
12x6
C
CFM 20
8x8
B
CFM160
12x8
C
CFM500
24x24
B
10x10
8"∅
14 15 16 17
D D
C C
A A
B B
E E
cen cen
F F
131211106 7 8 95431 2
G G
S302
3002
3004
3003
S301
ELEVATOR
LOBBY
3001
3500
X01
2500
X02
SHAFT 1
X500
LINEN AND
STORAGE
3004
LINEN DROP
3002
ELECTRICAL
3003
SHAFT 2
X501
CORRIDOR
3000
STAIR 2
S102
STAIR 1
S101
LINEN
X502
QQ CONNECTOR
312
ACC QUEEN
310
308
306
304
KING
302
KING
326
KING
324
322
320
KING
318
KING
316
KING
314
KING
327
KING
325
KING
323
KING
321
KING
319
KING
317
KING HEARING
315
KING
313
311
QQ CONNECTOR
309
ACC KING
307
305
303
301
8"∅FD FD FD
6"∅ 4"∅FD FD FD
FDFDFD
FD
FD
FD
10"∅FDFD
8"∅FD
FD
FDFD
FD FD
FD
FD
FD
10"∅FD FD
8"∅FD
FD
FD
12x1012x10
FD
FD
FD FD FD FD
8"∅ 6"∅ 4"∅
10"∅ 8"∅ 6"∅FDFDFD
FD
FDFD
10"∅8"∅FD FD FD FD FD FD FDFD
6"∅
10"∅FD
8"∅FD
FD FDFD FD
8"∅FD FD
4"∅FD
6"∅4"∅FDFDFDFDFDFDFD
FSD
PTAC-1
1
PTAC-1
1
FDFD
1
1
4
4
3
5
5
5
5
5
5
5
6 6 66
PTAC-1
11
PTAC-1
11
PTAC-1
11
PTAC-1
11
PTAC-1
11
PTAC-1
11
PTAC-1
11
PTAC-1
11
PTAC-1
11
PTAC-1
11
PTAC-1
11
PTAC-1
11
PTAC-1
11
PTAC-1
11
PTAC-1
11
PTAC-1
11
PTAC-1
11
PTAC-1
11
PTAC-1
11
PTAC-1
11
PTAC-1
11
PTAC-1
11
PTAC-1
11
PTAC-1
11
PTAC-1
11
EWH-5
EWH-6
7
7
FSD
10"∅8"∅
8"∅
8"∅ 8"∅ 8"∅ 8"∅
8888
8
888
8
8
8
8
8
8
8
8 8
8
CFM 30
6x6
C
CFM 30
6x6
C
CFM 30
6x6
C
CFM 30
6x6
C
CFM 30
6x6
C
CFM 30
6x6
C
CFM 30
6x6
C
CFM 30
6x6
C
CFM 30
6x6
C
CFM 35
6x6
C
CFM 30
6x6
C
CFM 30
6x6
C
CFM 30
6x6
C
CFM 30
6x6
C
CFM 30
6x6
C
CFM 30
6x6
C
CFM 30
6x6
C
CFM 30
6x6
C
CFM 30
6x6
C
CFM 30
6x6
C
CFM 30
6x6
C
CFM 30
6x6
C
CFM 30
6x6
C
CFM 30
6x6
C
CFM 30
6x6
C
CFM 30
6x6
C
CFM 30
6x6
C
FD
FD
FD
FD
FD FD
FD
FSD
FSD
18x10
4
4
4 4
4
2
FD
CFM 15
8x8
A
CFM180
2408
A
22x10
CFM200
12x24
B
20x10
24x10
FD
CFM120
12x6
C
CFM120
12x6
C
CFM120
12x6
C
CFM120
12x6
C
CFM 20
8x8
B
CFM160
12x8
C
CFM500
24x24
B
14x10
8"∅
M1-02
1
SCALE: 1/8"= 1'-0"
MECHANICAL - HVAC - 2ND FLOOR
MECHANICAL
HVAC
2ND & 3RD FLOOR
M1-02
a. FOR GENERAL HVAC NOTES SEE COVER SHEET. IN THE CASE OF CONFLICTING NOTES THE MOST
STRINGENT OF THE TWO SHALL APPLY PER APPLICABLE JOB CODE.
b. ROUND DUCT RUNOUTS TO INDIVIDUAL DIFFUSERS TO BE SAME SIZE AS DIFFUSER NECK UNLESS
NOTED.
c. MAINTAIN 10 FT. (MIN.) SEPARATION BETWEEN OUTSIDE AIR INTAKES AND EXHAUST OR VENT
OPENINGS.
d. EXTEND FULL SIZE CONDENSATE DRAIN LINE FROM EACH A/C UNIT AND TERMINATE AT FLOOR DRAIN,
ROOF DRAIN, FRENCH DRAIN, OR OTHER TERMINATION POINTS AS DIRECTED. TRAP AND VENT DRAIN
LINE AT CONNECTION TO COIL.
e. INSTALL SMOKE DETECTORS (PROVIDED BY ELECTRICAL) AT EACH A/C UNIT HANDLING OVER 2000 CFM,
MOUNTED IN SA DUCT (NFPA 90A, 4-4.2), AND IN RA DUCT PRIOR TO EXHAUST OR MIXING (SMC 406.1).
ALSO INSTALL SMOKE DETECTOR AT EACH A/C UNIT SERVING BUILDING EGRESS (REGARDLESS OF SIZE),
MOUNTED IN SA DUCT. DETECTOR(S) TO STOP UNIT FAN IF SMOKE IS DETECTED. INTERLOCK WITH
FIRE ALARM SYSTEM.
f. REFRIGERANT PIPING TO BE SIZED BY EQUIPMENT MANUFACTURER OR FACTORY- AUTHORIZED
REPRESENTATIVE. SIZING CALCULATIONS TO BE BASED ON ACTUAL FIELD ROUTING AND
CONFIGURATION.
g. FOR ALL GUEST ROOM THERMOSTATS: REMOTE THERMOSTAT TO BE MOUNTED AT 48" ABOVE
FINISH FLOOR IN ACCESSIBLE ROOMS AND AT 54" ABOVE FINISH FLOOR IN NON-ACCESSIBLE
ROOMS AT DEMISING WALL. SEE SHEET LARGE SCALE ROOM PLAN (SHEET E3-01) FOR
THERMOSTAT TYPICAL LOCATIONS.
HVAC SHEET NOTES - UNREFERENCED
1
HVAC SHEET NOTES - REFERENCED
OUTDOOR AIR SUPPLY AND EXHAUST DUCTS FROM FLOOR ABOVE.
· 22x22 SUPPLY
· 26x20 EXHAUST
· PROVIDE COMBINATION FIRE/SMOKE DAMPER AT CHASE PENETRATION POINTS.
2
OUTDOOR AIR SUPPLY AND EXHAUST DUCTS FROM FLOOR ABOVE.
· 24x14 SUPPLY
· 24x14 EXHAUST
· PROVIDE COMBINATION FIRE/SMOKE DAMPER AT CHASE PENETRATION POINTS.
3
ROUTE DUCT UP INTO RATED FLOOR ASSEMBLY ABOVE
· PROVIDE FIRE DAMPER AT ASSEMBLY PENETRATION POINT
4
EXHAUST AND SUPPLY BRANCH DUCTS DOWN FROM BOTTOM OF MAIN DUCTS IN FIRE
RATED FLOOR SYSTEM ABOVE.
· PROVIDE FIRE DAMPER AT RATING PENETRATION. (TYPICAL)
5
6
M1-02
2
SCALE: 1/8"= 1'-0"
MECHANICAL - HVAC - 3RD FLOOR
7ELECTRIC HEATER
· MOUNT WALL HEATER MINIMUM 6" A.F.F., UNIT TO BE SURFACE MOUNTED ON WALL.
· SET UNIT THERMOSTAT TO ENERGIZE UPON A DETECTION OF SPACE TEMPERATURE TO BE
DETERMINED BY OWNER
8PTAC CONDENSATE RISER CONFIGURATION
· 3/4" LINE FROM EACH PTAC CONNECTS TO 2" COMMON STACK AS SHOWN.
· 3/4" CONNECTION TO 2" STACK IS TO BE SOLID, AIR GAPS ARE UNACCEPTABLE IN WALL CAVITY.
· STACK SERVES 1ST-4TH FLOOR PTAC UNITS TERMINATING IN DRY WELL AT GRADE.
MOUNT PACKAGED THROUGH-THE -WALL HEAT PUMP UNITS AS DIRECTED BY MANUFACTURER.
· PROVIDE UNIT WITH ACCESSORIES LISTED IN SCHEDULE
· CONFIRM ALL ROUGH-IN DIMENSIONS AND REQUIREMENTS WITH GENERAL CONTRACTOR IN THE
FIELD. ACCOUNT FOR SUB-BASE HEIGHT WHEN DETERMINING A.F.F. INSTALLATION HEIGHT
· SEAL ALL WALL PENETRATIONS WEATHER TIGHT
· ROUTE 3/4" COPPER CONDENSATE LINE TO SPILL IN 2" COPPER RISER AS SHOWN.
· 3/4" CONNECTION TO 2" STACK IS TO BE SOLID, AIR GAPS ARE UNACCEPTABLE IN WALL CAVITY.
· CONDENSATE LINES SHALL BE INSULATED TO PREVENT PIPE SWEATING IN WALL.
· SLOPE CONDENSATE DRAIN LINE 1/8" PER 1'-0" AWAY FROM COIL
6x6 EXHAUST GRILLE TYPE 'E' WITH 4"∅ DUCT CONNECTION
· PROVIDE WITH MANUAL BALANCING DAMPER
· BALANCE GRILLE TO 25CFM OF EXHAUST AIR
· TYPICAL OF ALL GUEST BATHROOMS UNLESS NOTED OTHERWISE
OUTDOOR AIR SUPPLY AND EXHAUST DUCTS FROM FLOOR ABOVE.
· 22x14 SUPPLY
· 26x16 EXHAUST
· PROVIDE COMBINATION FIRE/SMOKE DAMPER AT CHASE PENETRATION POINTS.
9
OUTDOOR AIR SUPPLY AND EXHAUST DUCTS FROM FLOOR ABOVE.
· 22x14 SUPPLY
· 22x14 EXHAUST
· PROVIDE COMBINATION FIRE/SMOKE DAMPER AT CHASE PENETRATION POINTS.
10
2/1/2017 5:14:29 P
M
El P
aso
, T
exa
s
TR
U b
y H
ilto
n - E
l P
as
o
Tru
H
ote
l P
artn
ers, L
LC
16105
Revision Schedule
Rev.
Num.Rev. Date Revision Description
AEED,
Advanced Energy Engineering & Design, Inc
CHATTANOOGA, TN 37405
BUS. (423) 752-3438
FAX (423) 752-1369
P.O. BOX 4934
408 McCALLIE AVE
inc.
AEED JOB NO.001-17
COPYRIGHT NOTICE
THE DRAWINGS ARE THE
PROPERTY OF RIVER STREET
ARCHITECTURE LLC. ANY USE,
REUSE, REPRODUCTION,
DISPLAY OR SALE OF THESE
DRAWINGS WITHOUT THE
EXPRESS WRITTEN CONSENT
OF THE ARCHITECT IS
STRICTLY PROHIBITED.
714 cherry street, chattanooga, tennessee 37402
p.423 634 0806 f.423 752 8499 w
ww
.riverstreetarchitecture.com
Release Date:
Project No.:
________________________________________________________________________
BY DATE
05/31/2017
14 15 16 17
D D
C C
A A
B B
E E
F F
131211106 7 8 95431 2
G G
ELECTRICAL
4003
S402
4003
4004
S401
ELEVATOR
LOBBY
4001
3500
X01
2500
X02
LINEN AND
STORAGE
4004
SHAFT 2
X501
LINEN DROP
4002
SHAFT 1
X500
LINEN
X502
STAIR 1
S101
CORRIDOR
4000
STAIR 2
S102
QQ CONNECTOR
412
QUEEN WIDE
410
KING
426
KING
424
422
QQ HEARING
420
KING
418
KING
416
KING
414
QQ HEARING
406
404
KING
402
KING
427
KING
423
KING HEARING
421
KING
419
KING
417
KING
415
KING
413
411
409
KING WIDE
407
405
403
401
408
KING
425
BUILDING
SIGNAGE
8"∅FD FD FD
6"∅ 4"∅FD FD FD
FD
FDFDFD
FD
FD
FD
CFM120
12x6
C
10"∅FDFD
8"∅FD
FD
CFM120
12x6
C
FDFD
FD
FD FD
FD
FD
FD
10"∅FD FD
8"∅FD
FD
FD
12x1012x10
FD
FD
FD
FD FD FD FD
8"∅ 6"∅ 4"∅
CFM120
12x6
C
CFM120
12x6
C
CFM 20
8x8
B
10"∅ 8"∅ 6"∅FDFDFD
FD
FDFDFD
10"∅8"∅FD FD FD FD FD FD FDFD
6"∅FD FD
FD
FD
FSD
FSD
10"∅FD
8"∅FD
FD FDFD FD
8"∅FD FD
4"∅FD
6"∅4"∅FDFDFDFDFDFDFD
FSD
PTAC-1
1
PTAC-1
1
FDFD
24x10
18x10
1
1
4
4
4 4
4
4
4
2
3
5
5
5
FD
5
5
5
5
6 6 66
PTAC-1
11
PTAC-1
11
PTAC-1
11
PTAC-1
11
PTAC-1
11
PTAC-1
11
PTAC-1
11
PTAC-1
11
PTAC-1
11
PTAC-1
11
PTAC-1
11
PTAC-1
11
PTAC-1
11
PTAC-1
11
PTAC-1
11
PTAC-1
11
PTAC-1
11
PTAC-1
11
PTAC-1
11
PTAC-1
11
PTAC-1
11
PTAC-1
11
PTAC-1
11
PTAC-1
11
PTAC-1
11
CFM 15
8x8
A
FSD
10"∅
CFM160
12x8
C
8"∅
8"∅
8"∅ 8"∅ 8"∅ 8"∅
12121212
12
121212
12
12
12
12
12
12
12
12 12
12
CFM 30
6x6
C
CFM 30
6x6
C
CFM 30
6x6
C
CFM 30
6x6
C
CFM 30
6x6
C
CFM 30
6x6
C
CFM 30
6x6
C
CFM 30
6x6
C
CFM 30
6x6
C
CFM 35
6x6
C
CFM 30
6x6
C
CFM 30
6x6
C
CFM 30
6x6
C
CFM 30
6x6
C
CFM 30
6x6
C
CFM 30
6x6
C
CFM 30
6x6
C
CFM 30
6x6
C
CFM 30
6x6
C
CFM 30
6x6
C
CFM 30
6x6
C
CFM 30
6x6
C
CFM 30
6x6
C
CFM 30
6x6
C
CFM 30
6x6
C
CFM 30
6x6
C
CFM 30
6x6
C
CFM180
2408
A
22x10
CFM200
12x24
B
20x10
CFM500
24x24
B
14x10
8"∅
D D
C C
A A
B B
E E
cen
F F
G G
0.a 0.a
SLO
PE
1/4" P
ER
1'-0"
RD-1
SLO
PE
1/4" P
ER
1'-0"
SLO
PE
1/4" P
ER
1'-0"
SLO
PE
1/4" P
ER
1'-0"
SLO
PE
1/4" P
ER
1'-0"
SLO
PE
1/4" P
ER
1'-0"
SLO
PE
1/4" P
ER
1'-0"
SLO
PE
1/4" P
ER
1'-0"
SLO
PE
1/4" P
ER
1'-0"
SLO
PE
1/4" P
ER
1'-0"
SLO
PE
1/4" P
ER
1'-0"
SLO
PE
1/4" P
ER
1'-0"
SLO
PE
1/4" P
ER
1'-0"
RD-2 RD-3 RD-4
RD-5
RD-6 RD-7
2 HOUR ROOF OVER
STAIR SHAFT
2 HOUR ROOF OVER
STAIR SHAFT
ROOF ACCESS HATCH
MAKE-UP AIR
UNIT AREA
MAKE-UP AIR
UNIT AREA
WALKWAY
PROTECTION PAD
IN CONTRASTING
COLOR TO ROOF
TYP.
2 HOUR ROOF OVER
ELEVATOR SHAFT
SLOPE 1/4" PER 1'-0"
GUTTER &
DOWNSPOUT
BUILDING SIGNAGE
SCUPPER
SCUPPER
LINEN CHUTE
ROOF PARAPET
2 PARAPET VENTS BETWEEN
EACH DRAFT STOP (TYP.)
DRAFT STOP
AT MAX OF
EVERY 20'
ROOF PARAPET
2 PARAPET VENTS BETWEEN
EACH DRAFT STOP (TYP.)
DRAFT STOP
AT MAX OF
EVERY 20'
DRAFT STOP
AT MAX OF
EVERY 20'
SCUPPER
SCUPPER SCUPPER
DRAFT STOP
AT MAX OF
EVERY 20'
SLO
PE
SLO
PE
SLOPESLOPE
CANOPY BELOW
ROOF DRAIN /
DOWNSPOUT IN EIFS
COLUMN BUILD-OUT
ROOF DRAIN /
DOWNSPOUT IN EIFS
COLUMN BUILD-OUT
CANOPY BELOW
SLOPE SLOPE
SCUPPER & DOWNSPOUT
TO CONCRETE SPLASH
BLOCK, BOTH SIDES
BUILDING SIGNAGE
DRAFT STOP
AT MAX OF
EVERY 20'
DRAFT STOP
AT MAX OF
EVERY 20'
M
11
MAU-1
8
SD
TSD
T
9
MAU-2
8
SD
TSD
T
9
M
10
10
M1-03
1
SCALE: 1/8"= 1'-0"
MECHANICAL - HVAC - 4TH FLOOR
MECHANICAL
HVAC
4TH FLOOR & ROOF
M1-03
a. FOR GENERAL HVAC NOTES SEE COVER SHEET. IN THE CASE OF CONFLICTING NOTES THE MOST
STRINGENT OF THE TWO SHALL APPLY PER APPLICABLE JOB CODE.
b. ROUND DUCT RUNOUTS TO INDIVIDUAL DIFFUSERS TO BE SAME SIZE AS DIFFUSER NECK UNLESS
NOTED.
c. MAINTAIN 10 FT. (MIN.) SEPARATION BETWEEN OUTSIDE AIR INTAKES AND EXHAUST OR VENT
OPENINGS.
d. EXTEND FULL SIZE CONDENSATE DRAIN LINE FROM EACH A/C UNIT AND TERMINATE AT FLOOR DRAIN,
ROOF DRAIN, FRENCH DRAIN, OR OTHER TERMINATION POINTS AS DIRECTED. TRAP AND VENT DRAIN
LINE AT CONNECTION TO COIL.
e. INSTALL SMOKE DETECTORS (PROVIDED BY ELECTRICAL) AT EACH A/C UNIT HANDLING OVER 2000 CFM,
MOUNTED IN SA DUCT (NFPA 90A, 4-4.2), AND IN RA DUCT PRIOR TO EXHAUST OR MIXING (SMC 406.1).
ALSO INSTALL SMOKE DETECTOR AT EACH A/C UNIT SERVING BUILDING EGRESS (REGARDLESS OF SIZE),
MOUNTED IN SA DUCT. DETECTOR(S) TO STOP UNIT FAN IF SMOKE IS DETECTED. INTERLOCK WITH
FIRE ALARM SYSTEM.
f. REFRIGERANT PIPING TO BE SIZED BY EQUIPMENT MANUFACTURER OR FACTORY- AUTHORIZED
REPRESENTATIVE. SIZING CALCULATIONS TO BE BASED ON ACTUAL FIELD ROUTING AND
CONFIGURATION.
g. FOR ALL GUEST ROOM THERMOSTATS: REMOTE THERMOSTAT TO BE MOUNTED AT 48" ABOVE
FINISH FLOOR IN ACCESSIBLE ROOMS AND AT 54" ABOVE FINISH FLOOR IN NON-ACCESSIBLE
ROOMS AT DEMISING WALL. SEE SHEET LARGE SCALE ROOM PLAN (SHEET E3-01) FOR
THERMOSTAT TYPICAL LOCATIONS.
HVAC SHEET NOTES - UNREFERENCED
1
HVAC SHEET NOTES - REFERENCED
OUTDOOR AIR SUPPLY AND EXHAUST DUCTS FROM FLOOR ABOVE.
· 30x22 SUPPLY
· 34x20 EXHAUST
· PROVIDE COMBINATION FIRE/SMOKE DAMPER AT CHASE PENETRATION POINTS.
2
OUTDOOR AIR SUPPLY AND EXHAUST DUCTS FROM FLOOR ABOVE.
· 24x16 SUPPLY
· 24x16 EXHAUST
· PROVIDE COMBINATION FIRE/SMOKE DAMPER AT CHASE PENETRATION POINTS.
3
ROUTE DUCT UP INTO RATED FLOOR ASSEMBLY ABOVE
· PROVIDE FIRE DAMPER AT ASSEMBLY PENETRATION POINT
4
EXHAUST AND SUPPLY BRANCH DUCTS DOWN FROM BOTTOM OF MAIN DUCTS IN FIRE
RATED FLOOR SYSTEM ABOVE.
· PROVIDE FIRE DAMPER AT RATING PENETRATION. (TYPICAL)
5
6
7ELECTRIC HEATER
· MOUNT WALL HEATER MINIMUM 6" A.F.F., UNIT TO BE SURFACE MOUNTED ON WALL.
· SET UNIT THERMOSTAT TO ENERGIZE UPON A DETECTION OF SPACE TEMPERATURE TO BE
DETERMINED BY OWNER
M1-03
2
SCALE: 1/8"= 1'-0"
MECHANICAL - HVAC - ROOF
8
9
68x16 LOUVER WITH AT LEAST 3 SQUARE FEET OF FREE AREA FOR EACH CAR FOR ELEVATOR SHAFT RELIEF
· COORDINATE LOCATION WITH ARCHITECTURAL.
· MODEL BASED ON RUSKIN ELC445D.
· PROVIDE LOUVERS WITH MOTORIZED DAMPERS TIED INTO THE FIRE ALARM SYSTEM.
· SLEEVE AND SEAL AROUND LOUVER WEATHER TIGHT
· PROVIDE COMPLETE WITH BUG SCREEN
10
11
VERTICAL SUPPLY / EXHAUST DUCTS DOWN INTO CHASE THROUGH ROOF CURB.
· OFFSET/TRANSITION DUCTWORK IN CURB TO ALLOW PROPER ENTRY INTO CHASE
MOUNT MAU UNIT AS SHOWN ON FACTORY ROOF CURB (MIN. 24" HIGH).
· MAINTAIN 36" CLEARANCE TO ELECTRICAL ACCESS PANELS.
· SUPPLY DUCT IS TO BE SIDE DISCHARGE FROM CURB, ROUTE TO CURBED ROOF PENETRATION AS SHOWN.
· EXHAUST DUCT IS TO BE SIDE DISCHARGE FROM CURB, ROUTE TO CURBED ROOF PENETRATION AS
SHOWN.
· ROUTE FULL SIZE CONDENSATE DRAIN TO SPILL ON ROOF. SLOPE CONDENSATE LINE 1/8" AWAY FROM
UNIT.
· PROVIDE CURB EXTENSION AS NEEDED TO TRANSITIONS DUCTS INTO CHASE BELOW.
· INSTALL FIRE/SMOKE DETECTORS IN SUPPLY AND EXHAUST AIR STREAMS AS REQUIRED BY CODE/NFPA.
DETECTORS SUPPLIED BY MECHANICAL CONTRACTOR AND INSTALLED/WRIED BY ELECTRICAL
CONTRACTOR.
· SECURE UNIT TO CURB USING HURRICANE CLIPS, SEE FLORIDA BUILDING CODE - MECHANICAL SECTION
301.15 WIND LOADS FOR CLIPPING REQUIREMENTS
· SEE HURRICANE CLIP DETAIL ON SHEET M2.02
CURB MOUNTED GRAVITY RELIEF ON TOP OF LINEN CHUTE
· MOUNT CAP LEVEL ON ROOF CURB TO OFFSET ANY SLOPE
· MAP MFG: GREENHECK MODEL: GRSR-24
· PROVIDE COMPLETE WITH BUG SCREEN
· 10'-0"∅ CLEARANCE TO FRESH AIR INTAKE RADIUS SHOWN
12PTAC CONDENSATE RISER CONFIGURATION
· 3/4" LINE FROM EACH PTAC CONNECTS TO 2" COMMON STACK AS SHOWN.
· 3/4" CONNECTION TO 2" STACK IS TO BE SOLID, AIR GAPS ARE UNACCEPTABLE IN WALL CAVITY.
· STACK SERVES 1ST-4TH FLOOR PTAC UNITS TERMINATING IN DRY WELL AT GRADE.
MOUNT PACKAGED THROUGH-THE -WALL HEAT PUMP UNITS AS DIRECTED BY MANUFACTURER.
· PROVIDE UNIT WITH ACCESSORIES LISTED IN SCHEDULE
· CONFIRM ALL ROUGH-IN DIMENSIONS AND REQUIREMENTS WITH GENERAL CONTRACTOR IN THE
FIELD. ACCOUNT FOR SUB-BASE HEIGHT WHEN DETERMINING A.F.F. INSTALLATION HEIGHT
· SEAL ALL WALL PENETRATIONS WEATHER TIGHT
· ROUTE 3/4" COPPER CONDENSATE LINE TO SPILL IN 2" COPPER RISER AS SHOWN.
· 3/4" CONNECTION TO 2" STACK IS TO BE SOLID, AIR GAPS ARE UNACCEPTABLE IN WALL CAVITY.
· CONDENSATE LINES SHALL BE INSULATED TO PREVENT PIPE SWEATING IN WALL.
· SLOPE CONDENSATE DRAIN LINE 1/8" PER 1'-0" AWAY FROM COIL
6x6 EXHAUST GRILLE TYPE 'E' WITH 4"∅ DUCT CONNECTION
· PROVIDE WITH MANUAL BALANCING DAMPER
· BALANCE GRILLE TO 25CFM OF EXHAUST AIR
· TYPICAL OF ALL GUEST BATHROOMS UNLESS NOTED OTHERWISE
2/1/2017 5:14:29 P
M
El P
aso
, T
exa
s
TR
U b
y H
ilto
n - E
l P
as
o
Tru
H
ote
l P
artn
ers, L
LC
16105
Revision Schedule
Rev.
Num. Rev. Date Revision Description
AEED,
Advanced Energy Engineering & Design, Inc
CHATTANOOGA, TN 37405
BUS. (423) 752-3438
FAX (423) 752-1369
P.O. BOX 4934
408 McCALLIE AVE
inc.
AEED JOB NO.001-17
COPYRIGHT NOTICE
THE DRAWINGS ARE THE
PROPERTY OF RIVER STREET
ARCHITECTURE LLC. ANY USE,
REUSE, REPRODUCTION,
DISPLAY OR SALE OF THESE
DRAWINGS WITHOUT THE
EXPRESS WRITTEN CONSENT
OF THE ARCHITECT IS
STRICTLY PROHIBITED.
714 cherry street, chattanooga, tennessee 37402
p.423 634 0806 f.423 752 8499 w
ww
.riverstreetarchitecture.com
Release Date:
Project No.:
________________________________________________________________________
BY DATE
05/31/2017
MECHANICAL
SCHEDULES
M2-00
ELECTRIC HEATER SCHEDULE
MFR.
EWH-1
MARK MODEL # VOLTS/PH.KW MOUNTING REMARKS
NOTES:
OPTIONS-ACCESSORIES-NOTES
EWH-2
EWH-3
EWH-4
1. PROVIDE WITH WALL SURFACE MOUNTING KIT.
MOCP
TOTAL CAPACITY SENSIBLETOTAL CAPACITY wbdb
VOLT.-PH.-CY.MCA
ELECTRIC
MAU-1
SERVICE
MANUFACTURER & MODEL
SYSTEM MBH (ENERGY RECOVERY INCLUDED)COIL EAT
COOLING CAPACITIES
NO.
EQUIPMENT
GAS FIRED ROOF MOUNTED MAKE UP AIR UNIT WITH DX COOLING
FAN
(HP)
MAU-2
OPTIONS-ACCESSORIES-NOTES
FAN
(HP)(MBH)
INPUT
EXT. S.P.
(IN. W.G.)
SUPPLY
AIR (CFM)
EXHAUST
AIR (CFM)
TOTAL S.P.
(IN. W.G.)
SUPPLY FAN SECTION EXHAUST FAN SECTION GAS HEAT
UNIT
OPERATING
WEIGHT
(LBS)
wbdb
COIL LAT
HOT GAS RE-HEAT
TC
(MBH)
NOTES:
1. FACTORY ASSEMBLED, PIPED, WIRED AND TESTED AS A SINGLE PACKAGE
2. UNIT SHALL INCLUDE HEAT RECOVERY WHEEL WITH INTEGRAL EXHAUST FAN
3. UNIT SHALL INCLUDE 2 STAGE COOLING, 2 COMPRESSOR CIRCUITS WITH INTERLACED-CIRCUIT DX COIL (HORIZONTAL SPLIT NOT ACCEPTABLE)
4. UNIT SHALL INCLUDE MODULATING GAS HEATING WITH 304 SERIES STAINLESS STEEL HEAT EXCHANGER WITH A 25 YEAR WARRANTY (PARTS ONLY)
5. UNIT SHALL INCLUDE HOT GAS BYPASS ON ALL REFRIGERATION CIRCUITS (FROST-STAT COMPRESSOR CYCLING NOT ACCEPTABLE)
6. UNIT SHALL INCLUDE MODULATING HOT GAS REHEAT COIL FOR DEHUMIDIFICATION (2-POSITION OR DEDICATED HEAT PUMP CIRCUIT NOT ACCEPTABLE)
7. UNIT SHALL INCLUDE STAINLESS STEEL DRAIN PAN
8. UNIT SHALL INCLUDE MANUAL RESET HIGH PRESSURE SWITCHES & AUTO RESET LOW PRESSURE SWITCHES
9. UNIT SHALL INCLUDE ECM CONDENSER FAN MOTORS FOR CONDENSER HEAD PRESSURE CONTROL
10. UNIT SHALL INCLUDE 4" MERV 12 FILTERS AND 2" MERV 8 PRE-FILTERS
11. UNIT SHALL INCLUDE 2" MERV 8 EXHAUST AIR FILTERS
12. CONTROLS: WATTMASTER/ORION VCMX CONTROLLER WITH AMBIENT DEWPOINT SENSOR; ELECTRONIC SEQUENCING OF COMPRESSORS AND HEATING.
FIELD MOUNTED CONTROLS SHALL INCLUDE A DUCT MOUNTED LEAVING AIR STAT AND A WALL MOUNTED STAT (SEE PLANS FOR LOCATION)
ALL UNIT MOUNTED CONTROLS FOR COMPLETE OPERATION SHALL BE INSTALLED BY THE EQUIPMENT MANUFACTURER
13. UNIT SHALL INCLUDE INTEGRAL NON-FUSED DISCONNECT
14. DUCT MOUNTED SMOKE DETECTORS PROVIDED BY ELECTRICAL, INSTALLED BY MECHANICAL
15. UNIT SHALL INCLUDE A 30" HIGH FACTORY ASSEMBLED AND INSULATED ROOF CURB/PLENUM WITH VIBRATION ISOLATION RAILS
16. UNIT SHALL BE AHRI LISTED AND CERTIFIED (COIL ONLY CERTIFICATION NOT ACCEPTABLE)
17. COMPRESSORS SHALL HAVE 5 YEAR WARRANTY (PARTS ONLY)
18. PROVIDE UNIT WITH DUCT MOUNTED SMOKE DETECTORS IN SUPPLY AND RETURN DUCTS OF UNIT. DETECTORS TO BE PROVIDED AND WIRED BY ELECTRICAL CONTRACTOR AND INSTALLED IN DUCT BY MECHANICAL CONTRACTOR.
MAX
TEMP
RISE °F
19. PROVIDE HURRICANE CLIPS FOR ALL MAKE UP AIR ROOFTOP UNITS AND CURBS.
(MBH)
OUTPUT
GUEST ROOM - OUTSIDE AIR / EXHAUST
GUEST ROOM - OUTSIDE AIR / EXHAUST
MARKEL
MARKEL
MARKEL
MARKEL
EWH-5 MARKEL
FINISHAIR CONTROL MATERIAL
AIR DISTRIBUTION SCHEDULE
MODEL/CAT#DESCRIPTION
TITUS
TITUS
MFGR.
NOTES:
DESIG.OPTIONS-ACCESSORIES-NOTES
TITUS
1. ACCEPTABLE MANUFACTURERS: METALAIRE, ANEMOSTAT, OR BY ENGINEER
2. PROVIDE COMPLETE WITH ALL CLIPS, MARGINS AND HARDWARE FOR INSTALLATION TYPE. CONTRACTOR/MFG REP SHALL EXAMINE DRAWINGS TO DETERMINE INSTALLATION TYPE.
3. COORDINATE COLOR WITH ARCHITECT.
4. SEE DRAWING FOR CONNECTION SIZE.
TITUS
3
A
B
D
C
ETITUS
ALL
ALL
4635 4255
LAT
db °F
2750 2005
MARKEL
5 208/1 WALL SURFACE MOUNTED W/ INTERGRAL T'STAT1 2
MARKEL
5 208/1 WALL SURFACE MOUNTED W/ INTERGRAL T'STAT1 2
MARKEL
5 208/1 WALL SURFACE MOUNTED W/ INTERGRAL T'STAT1 2
MARKEL
5 208/1 WALL SURFACE MOUNTED W/ INTERGRAL T'STAT1 2
MARKEL
5 208/1 WALL SURFACE MOUNTED W/ INTERGRAL T'STAT1 2
STEEL
ALUM
ALUM
OPPOSED BLADE DAMPER
N/A
350RS
TMS
50F
24x24 LAY-IN/SURFACE MOUNTED SUPPLY DIFFUSER, ROUND NECK
EGGCRATE STYLE RETURN / TRANSFER GRILLE
SURFACE MOUNTED RETURN GRILLE
N/A
ALUMN/A
1 2
1 2
1 2
1 2
301RS
SIDEWALL SUPPLY GRILLE
ALUM
TBD-10
N/A
1 2
HIGH ADJUSTABLE CAPACITY LINEAR SLOT WITH (2 x 1.5" SLOT WIDTH 4'-0" LONG)
3
3
3
34 5
6
6
EWH-6 MARKEL MARKEL
5 208/1 WALL SURFACE MOUNTED W/ INTERGRAL T'STAT1 2
SYSTEM EAT
wbdb
2/1/2017 5:14:29 P
M
El P
aso
, T
exa
s
TR
U b
y H
ilto
n - E
l P
as
o
Tru
H
ote
l P
artn
ers, L
LC
16105
Revision Schedule
Rev.
Num. Rev. Date Revision Description
AEED,
Advanced Energy Engineering & Design, Inc
CHATTANOOGA, TN 37405
BUS. (423) 752-3438
FAX (423) 752-1369
P.O. BOX 4934
408 McCALLIE AVE
inc.
AEED JOB NO.001-17
COPYRIGHT NOTICE
THE DRAWINGS ARE THE
PROPERTY OF RIVER STREET
ARCHITECTURE LLC. ANY USE,
REUSE, REPRODUCTION,
DISPLAY OR SALE OF THESE
DRAWINGS WITHOUT THE
EXPRESS WRITTEN CONSENT
OF THE ARCHITECT IS
STRICTLY PROHIBITED.
714 cherry street, chattanooga, tennessee 37402
p.423 634 0806 f.423 752 8499 w
ww
.riverstreetarchitecture.com
Release Date:
Project No.:
OPTIONS-ACCESSORIES-NOTES
2. PROVIDE SINGLE POINT CONNECTION.
5. VERIFY PROPER VOLTAGE WITH ELECTRICAL CONTRACTOR BEFORE ORDERING EQUIPMENT.
3. ACCEPTABLE MANUFACTURERS: CARRIER, TRANE, YORK, LENNOX
4. VERIFY PROPER VOLTAGE WITH ELECTRICAL CONTRACTOR BEFORE ORDERING EQUIPMENT.
HEAT PUMP
HEATING CAPACITY
(MBH)
1. PROVIDE COMPLETE WITH PROGRAMMABLE T'STAT
NOTES:
3. ACCEPTABLE MANUFACTURERS: CARRIER, TRANE, YORK, LENNOX
1. PROVIDE COMPLETE WITH COIL GUARDS
MARK
AHU-1
NOTES:
CFM
SUPPLY
COOLING
(MBH)
CAPACITY
MOCPVOLT.-PH.-CY.
BACKUP ELECTR.
RESIST. HEATING
KW
ELECTRICAL
MCA
MANUFACTURER & MODEL
OPTIONS-ACCESSORIES-NOTES
ELECTRICAL
VOLT.-PH.-CY.
INDOOR UNIT
HP-1
REFRIG. PIPING
SUCTION LIQUID
MANUFACTURER & MODEL
SPLIT SYSTEM HEAT PUMP - OUTDOOR UNIT SCHEDULE
SPLIT SYSTEM HEAT PUMP - INDOOR UNIT SCHEDULE
AHU-2
TOTAL
COOLING
(MBH)
CAPACITY
SENSIBLE
EER
HP-2
COOLING
CAPACITY
(MBH)
HEATING
CAPACITY
(MBH)
AHU-3
HP-3
AHU-4
HP-4
7. PROVIDE UNIT WITH DUCT MOUNTED SMOKE DETECTORS IN SUPPLY AND RETURN DUCTS OF UNIT.
DETECTORS TO BE PROVIDED AND WIRED BY ELECTRICAL CONTRACTOR AND INSTALLED IN DUCT BY
MECHANICAL CONTRACTOR.
6. PROVIDE UNIT WITH AUXILIARY CONDENSATE DRAIN PAN UTILIZING SHUT DOWN FLOAT SWITCH.
PROVIDE COMPLETE WITH CONDENSATE DRAIN PUMP CAPABLE OF ACHIEVING PROPER FLOW AS
INDICATED BY DRAWINGS.
5. DURING AUXILIARY HEATING MODE OUTDOOR UNIT SHALL DE-ENERGIZE TO PREVENT SIMULTANEOUS
OPERATION OF ACCESSORY HEAT AND HEAT PUMP.
9. WRAP UNITS WITH FOIL FACED FIBERGLASS OR CLOSED CELL ELASTOMERIC INSULATION. WRAP IN A MANNER TO
ALLOW OPERATION/ACESS OF ALL FILTERS, CONTROL PANELS, ACCESS DOOR, S ETC.
8. DURING AUXILIARY HEATING MODE OUTDOOR UNIT SHALL DE-ENERGIZE TO PREVENT SIMULTANEOUS
OPERATION OF ACCESSORY HEAT AND HEAT PUMP.
4. PROVIDE WITH FILTER RACK AND 1" THICK PLEATED-MEDIA DISPOSABLE FILTERS,
EQUAL TO FARR 30/30.
HP-5
AHU-5
OUTDOOR
UNIT
MIN. O.A.
AIR CFM
EXT. S.P.
(IN. W.G.)
MCA MOCP
MARK
2. REFRIGERANT PIPING TO BE SIZED BY EQUIPMENT MANUFACTURER OR FACTORY- AUTHORIZED REPRESENTATIVE. SIZING CALCULATIONS TO BE BASED ON ACTUAL FIELD ROUTING AND CONFIGURATION.
ALL
ALL
ALL
ALL
ALL
ALL
ALL
ALL
ALL
ALL
CARRIER 38AUQA07
62.39 67.0 11.0 NOTE 2 NOTE 2
208/3/60
28 45 AHU-1
CARRIER 40RUQA07
2180 670
480
0.65 67.0 51.3 62.39 10
208/3/60
32.6 35.0 HP-1
CARRIER 25HCD348 44.55 44.83 12.0 NOTE 2 NOTE 2
208/3/60
18.7 30 AHU-2
CARRIER FV4CNB006 1600 0.50 44.83 33.6 44.55 11.3
208/1/60
76.3 80.0 HP-2
CARRIER 25HCE430 27.81 28.04 11.5 NOTE 2 NOTE 2
208/1/60
18.3 30 AHU-3
120CARRIER FV4CNF002 875 0.50 28.04 16.50 27.81 7.5
208/1/60
53.8 60.0 HP-3
NOMINAL
TON
2.5
4
6
CARRIER 25HCE418 17.36 16.26 12.0 NOTE 2 NOTE 2
208/1/60
11.8 20 AHU-41.5
70CARRIER FV4CNF002 525 0.50 16.26 11.61 17.36 3.8
208/1/60
31.2 35.0 HP-4
CARRIER 25HCE418 17.62 16.68 12.0 NOTE 2 NOTE 2
208/1/60
11.8 20 AHU-51.5
95CARRIER FV4CNF002 600 0.50 16.68 13.19 17.62 3.8
208/1/60
31.2 35.0 HP-5
10. OUTDOOR AIR PRETREATED BY MAKE UP AIR UNITS ON ROOF
2.0 3 2.0 2 150.0 100.8 93.1 58.24 19.5 101 70 83.5 67.3 55.2 55.2 128.74 124.73 54 60
208/3
1950 62DCCL12-RNB3EETD3
2.0 10 2.0 5 300.0 201.6 99.7 119.8 23.6 101 70 82.6 69.0 54.3 54.3 221.44 214.69 122 150
208/3
2100 62DCFL20-V4B3EGTD3
________________________________________________________________________
BY DATE
05/31/2017
MECHANICAL
SCHEDULES
M2-01
PACKAGE THROUGH-THE-WALL A/C UNIT
MANUFACTURER
MODEL NO.
TH
COOLING (BTUH)ENTERING
AIR
db wb
EER
VOLT/PH
ELECTRCAL DATA
NOTES:
CFM
TOT OA
2. PROVIDE COMPLETE WITH SUB-BASE CONDENSATE DRAIN KIT.
MCA MOCP
PTAC-1
OPTIONS-ACCESSORIES
ALL
3. PROVIDE COMPLETE WITH FACTORY SUB-BASE, HARDWIRE KIT AND POWER DISCONNECT SWITCH. ACCOUNT FOR SUB-BASE HEIGHT WHEN DETERMINING A.F.F. INSTALLATION HEIGHT.
ELECTRIC
HEATER
(KW)
WEIGHT
(LBS)
4. PTAC RISER BY PLUMBING CONTRACTOR, CONNECTION FROM PTACS TO RISER BY MECHANICAL.
5. ACCEPTABLE ALTERNATES ARE AMANA & GE.
1. PROVIDE WITH WALL SLEEVE, STANDARD GRILLE, UNIVERSAL DRAIN KIT REMOTE MOUNTED MANUAL T-STAT WITH TWO SPEED FAN CONTROL CAPABILITY.
6. PROVIDE WITH REMOTE MOUNTED MANUAL T-STAT WITH TWO SPEED FAN CONTROL CAPABILITY.
VOLTS
OA CFM
CFM
OUTDOORMANUFACTURERDESIG.
DUCTLESS A/C SCHEDULE
INDOOR COOLING (MBH)
INDOOR
1. SANYO OR MITSUBISHI ARE ACCEPTABLE ALTERNATIVES.
2. VERIFY PROPER VOLTAGE WITH ELECTRICAL CONTRACTOR.
3. PROVIDE WITH MOUNTING KIT COMPATIBLE WITH WALL MOUNTING APPLICATION.
OPTIONS-ACCESSORIES
NOTES:
5. PROVIDE ACCESSORY LONG RUN REFRIGERANT LINE KIT.
VOLTS
OUTDOOR
(MCA/MOCP) (MOCP/MCA)
6. MAIN POWER SUPPLIED TO OUTDOOR UNIT. FIELD SUPPLIED CONNECTION CABLE FROM OUTDOOR
TO INDOOR SUPPLIES POWER TO INDOOR UNIT. HIGH WALL UNITS ONLY.
7. PROVIDE CONDENSATE PUMP INSTALLED INSIDE UNIT (REMOTE MOUNT UNACCEPTABLE)
8. PROVIDE WITH LOW AMBIENT OPERATION KIT, WIND BAFFLE & CRANKCASE HEATER.
4. ROUTE CONDENSATE DRAIN LINES AS SHOWN ON PLANS.
HI - MED - LOW
9. COORDINATE OUTDOOR UNIT MOUNTING TYPE WITH PLANS. METAL EQUIPMENT RAILS FOR ROOF INSTALLATION & METAL WALL BRACKET FOR 1ST FLOOR ELEVATOR ROOM.
HEATING (MBH)
HW-FC-1 / HP-6
HIGH WALL UNITS
10. PROVIDE WITH INTEGRAL THERMOSTATS.
DESIG.
FLOOR AIR BALANCE
FLOOR ITEM SERVICE
OUTSIDE AIR (CFM) EXHAUST AIR (CFM) FLOOR TOTAL (CFM)
MAU-1
MAU-2
1ST FLOOR
2ND FLOOR
MAU-1
MAU-2
3RD FLOOR
MAU-1
MAU-2
4TH FLOOR
MAU-1
MAU-2
OUTDOOR AIR CALCULATIONS
AIR HANDLING UNIT PROVIDING OUTSIDE AIR AREA SERVED OUTSIDE AIR CALCULATIONS
TOTAL SPACE CALCULATED
OUTSIDE AIR (CFM)
SCHEDULED OUTSIDE AIR
SERVING SPACE (CFM)
1640 -1480
+260
OUTDOOR AIR / BUILDING EXHAUST
OUTDOOR AIR / BUILDING EXHAUST
OUTDOOR AIR / BUILDING EXHAUST
OUTDOOR AIR / BUILDING EXHAUST
OUTDOOR AIR / BUILDING EXHAUST
OUTDOOR AIR / BUILDING EXHAUST
OUTDOOR AIR / BUILDING EXHAUST
OUTDOOR AIR / BUILDING EXHAUST
MAU-1FRONT DESK / LOBBY AREA / VESTIBULE 2465sqft 0.30cfm per sqft of outside air = 2465 x 0.30 740 745
MAU-1 DINNING 575sqft 0.70cfm per sqft of outside air = 575 x 0.70 402 405
MAU-1GM OFFICE 1029 / OFFICE 1030 / PANTRY 1027 80sqft 0.09cfm per sqft of outside air = 80 x 0.09 / 80sqft 0.09cfm per sqft of outside air = 80 x 0.09 / 328sqft 0.12cfm per sqft of outside air = 328 x 0.12 7056
MAU-1 FITNESS 455sqft 0.26cfm per sqft of outside air = 455 x 0.26 118 120
MAU-2 EMPLOYEE BREAK ROOM 185sqft 0.25cfm per sqft of outside air = 185 x 0.25 46 50
MAU-2 LAUNDRY 555sqft 0.17cfm per sqft of outside air = 555 x 0.17 94 95
MAU-2 CORRIDOR 1007 / CORRIDOR 1012 520sqft 0.11cfm per sqft of outside air = 520 x 0.11 57 300**
KING - (TYPICAL OF SIMILAR UNITS) 195sqft 0.11cfm per sqft of outside air = 195 x 0.11 21 30
KING - (TYPICAL OF SIMILAR UNITS) 175sqft 0.11cfm per sqft of outside air = 175 x 0.11 19 30
QUEEN - (TYPICAL OF SIMILAR UNITS) 220sqft 0.11cfm per sqft of outside air = 220 x 0.11 24 30
QUEEN ACC - (TYPICAL OF SIMILAR UNITS) 316sqft 0.11cfm per sqft of outside air = 316 x 0.11 34 35MAU-1 & MAU-2
MAU-1 & MAU-2
MAU-1 & MAU-2
MAU-1 & MAU-2
MAU-2 LINEN AND STORAGE - (TYPICAL OF SIMILAR UNITS) 180sqft 0.12cfm per sqft of outside air = 180 x 0.12 22 25
ELEV. LOBBY / CORRIDOR - (TYPICAL OF GUEST FLOORS) 1300sqft 0.11cfm per sqft of outside air = 1300 x 0.11 78 640**MAU-1 & MAU-2
NOTES:
* TABLE VALUES PER HILTON - VENTILATION RATES ARE BASED UPON ASHRAE STANDARD 62.1-2007 USING DEFAULT OCCUPANCY VALUES, AND HAVE OTHER INDOOR AIR QUALITY REQUIREMENTS THAT ARE INCLUDED IN THE STANDARD.
** QUANTITY SHOWN IS TO PROVIDE SPACE COOLING AS WELL AS MEET OUTSIDE AIR REQUIREMENTS
HW-FC-2 / HP-7
CARRIER 038MAQB012-3 12.015/15
1 32 4 5
208/1/60
7
6
8
380 - 360 - 300
9
6
40MAQ012B-3 12.0
10
CARRIER 5038MAQB18 18.020/15
1 32 4 5
208/1/60
7 8
420 - 350 - 290
9
40BQB018 19.7
CEILING CASSETTE UNITS
10
CCU-1 / HP-8
208/111.36780 9.0300 19.5 20AMANA PTC093G35 3.0 145-
CARRIER 038MAQB012-3 12.015/15
1 32 4 5
208/1/60
7
6
8
380 - 360 - 300
9
6
40MAQ012B-3 12.0
10
370 -175
+235
855 -595
1260 -1220
MAU-2 LINEN DROP - (TYPICAL OF SIMILAR UNITS) 80sqft 0.12cfm per sqft of outside air = 80 x 0.12 14 15
TOTAL AMPS
14.1
2/1/2017 5:14:29 P
M
El P
aso
, T
exa
s
TR
U b
y H
ilto
n - E
l P
as
o
Tru
H
ote
l P
artn
ers, L
LC
16105
Revision Schedule
Rev.
Num.Rev. Date Revision Description
AEED,
Advanced Energy Engineering & Design, Inc
CHATTANOOGA, TN 37405
BUS. (423) 752-3438
FAX (423) 752-1369
P.O. BOX 4934
408 McCALLIE AVE
inc.
AEED JOB NO.001-17
COPYRIGHT NOTICE
THE DRAWINGS ARE THE
PROPERTY OF RIVER STREET
ARCHITECTURE LLC. ANY USE,
REUSE, REPRODUCTION,
DISPLAY OR SALE OF THESE
DRAWINGS WITHOUT THE
EXPRESS WRITTEN CONSENT
OF THE ARCHITECT IS
STRICTLY PROHIBITED.
714 cherry street, chattanooga, tennessee 37402
p.423 634 0806 f.423 752 8499 w
ww
.riverstreetarchitecture.com
Release Date:
Project No.:
370 -175
+235
1260 -1220
370 -175
+235
1260 -1220
66
________________________________________________________________________
BY DATE
05/31/2017
MECHANICAL
DETAILS
M2-02
2/1/2017 5:14:29 P
M
El P
aso
, T
exa
s
TR
U b
y H
ilto
n - E
l P
as
o
Tru
H
ote
l P
artn
ers, L
LC
16105
Revision Schedule
Rev.
Num. Rev. Date Revision Description
AEED,
Advanced Energy Engineering & Design, Inc
CHATTANOOGA, TN 37405
BUS. (423) 752-3438
FAX (423) 752-1369
P.O. BOX 4934
408 McCALLIE AVE
inc.
AEED JOB NO.001-17
COPYRIGHT NOTICE
THE DRAWINGS ARE THE
PROPERTY OF RIVER STREET
ARCHITECTURE LLC. ANY USE,
REUSE, REPRODUCTION,
DISPLAY OR SALE OF THESE
DRAWINGS WITHOUT THE
EXPRESS WRITTEN CONSENT
OF THE ARCHITECT IS
STRICTLY PROHIBITED.
714 cherry street, chattanooga, tennessee 37402
p.423 634 0806 f.423 752 8499 w
ww
.riverstreetarchitecture.com
Release Date:
Project No.:
TYPICAL BOTTOM OF DUCT DIFFUSER CONNECTION
SCALE: NONE
SUPPLY DUCT MAIN
FLEX DUCT WHERE
REQUIRED (MAX.
LENGTH 6'-0")
FLEX DUCT SIZES SHALL
MATCH NECK SIZES
OPPOSED BLADE
DAMPER
DRAW BAND WITH
SILICONE SEALER
HAND DAMPER
CEILING
DIFFUSER
COLLAR
CEILING
DRAIN PAN
CONDENSATE DRAIN DETAIL
SCALE: NONE
EACH DIMENSION IS
EQUAL TO FAN NEGATIVE
STATIC PRESSURE
UNION
REMOVABLE CAP
FULL SIZE OF
DRAIN
CONNECTION
APPROVED AIR
GAP HEIGHT
LOCAL ROOF DRAIN,
FLOOR DRAIN, OR
FLOOR SINK.
LEVELING LEG
FOUNDATION WALL
OUTSIDE WALL
EXTERIOR LOUVER AND
DAMPER
LOCKED CONTROL PANEL
WALL SLEEVE
PTAC UNIT
PACKAGED THROUGH THE WALL TERMINAL AC UNIT
SCALE: NONE
ELECTRIC WALL HEATER MOUNTING DETAIL
SCALE: NONE
2
"
4
"
6" THICK CONC. PAD - EXTEND
6" BEYOND UNIT ALL AROUND
SIGHT GLASS WITH
MOISTURE INDICATOR
FILTER-DRYER
CONDUIT - POWER
AND CONTROL
REFRIGERANT LIQUID LINE
REFRIGERANT SUCTION
LINE WITH INSULATION
CONDENSING UNIT
FAN GUARD
CONDENSING UNIT - SLAB MOUNTED AT GRADE
SCALE: NONE
BACK-SEATED REFRIGERANT
VALVE
DUCT HANGER DETAILS
SCALE: NONE
SHEET METAL SCREW
SECURE TO STRUCTURE
ABOVE AS RECOMMENDED
BY SMACNA
HANGER ROD
TYPE "B" 5/16" DIA.
TYPE "C" 3/8" DIA.
TYPE "D" 1/2" DIA.
FOR BRACING ANGLES
SEE NOTES
NUT & WASHER AT
END OF ROD
TYPE "A"
TYPE "B", "C", "D"
MAX SIDE
M
A
X
S
I
D
E
RIVET OR BOLT TO
BOTH SIDES OF DUCT
& A MIN. OF 1"
BENEATH DUCT FOR
BOTH STRAPS
1" X 16 GA
GALV. IRON
STRAP OR
ALUMINUM
(8 FT. MAX HANGER SPACING. ALSO
PROVIDE 3 HANGERS AT EACH TAKE-OFF
OR BRANCH.)
(8 FT. MAX HANGER SPACING )
NOTES:
1.) FOR SEVERAL DUCTS ON ONE HANGER, TYPE "B", "C",
OR "D" MAY BE USED. SIZE OF HANGER WILL BE
SELECTED ON SUM OF DUCT WIDTHS EQUAL TO MAXIMUM
WIDTH OF DUCT SCHEDULE.
2.) SCHEDULE FOR ANGLES FOR BRACING: TYPE "B" -
1-1/2 X 1-1/2 X 1/8 ANGLE, MAX. SPACING 8'-0"
CENTERS; TYPE "C" - 1-1/2 X 1-1/2 X 3/16 ANGLE,
MAX. SPACING 8'-0" CENTERS; TYPE "D" - 2 X 2 X 1/4
ANGLE, MAX SPACING 4'-0" CENTERS.
DUCT SCHEDULE
DUCT
DIMENSIONS
(INCHES)
TYPE
HANGER
A
A
A/B
B
B
B
C
C
DOVER 96
85 " 96
61 " 84
55 " 60
43 " 54
31 " 42
19 " 30
13 " 18
UP THRU 12
OPENING HEIGHT
TOP BLADE RIVETED
TO FRAME
SLEEVE
COLLAR
STEEL BLADES WITH
INTERLOCKING JOINTS
BLADE AND LINK
CINCH
FUSIBLE LINK
STEEL FRAME
ASSEMBLED
INTO WELDED
HOUSING
1" TYPICAL
3 SIDES
3/4" TYP.
3 SIDES
DUCT HEIGHT LESS
1/4" 100% FREE-
AREA
(DAMPER HEIGHT
IS 1/4" LESS)
3"
5"
FIRE DAMPER DETAIL
SCALE: NONE
DUCT SUPPORTS OFF ROOF DETAIL
SCALE: NONE
INSULATION
METAL DECK
SUPPORT
PROVIDE PITCH WITH INSULATION
MATERIAL FOR DRAINAGE
STRUCTURAL SHAPE
AS PER SMACNA
(ANGLE IRON OR PIPE)
SUPPORT LEGS
WELD TO ANGLE (TYPICAL)
ANGLE IRON FASTENED
TO EQUIPMENT SUPPORT
COUNTER FLASHING HOOD
MEMBRANE ROOF
PREFABRICATED
EQUIPMENT
INVERTED ANGLE IRON
ANCHOR EQUIPMENT SUPPORT
TO METAL DECK
DUCTWORK SUPPORTED AS PER SMACNA
SEAL ALL ANGLES WEATHER TIGHT
ANGLE IRON WELD TO PIPE
OR ANGLE IRON (TYPICAL)
AT ROOF DUCT SUPPORT-INSULATE
OVER ANGLE IRON SUPPORTS AND
SEAL ALL CORNERS OF ANGLES IN A
WEATHER TIGHT MANNER
MIN
IM
UM
2'-0"
INSULATED DOUBLE WALL SUPPLY OR
RETURN DUCTWORK WITH WATER TIGHT
SEAMS AND WEATHER RESISTANT FINISH.
FACTORY SUB- BASE KIT
6" ABOVE FINISHED FLOOR (MINIMUM)
UNIT SURFACED MOUNTED
PER MFG GUIDELINES
ELECTRIC HEATER,
RECESSED WALL MOUNTED
SEE DETAIL A
10
7
5
6
9
12
4
9
1
211
1/2"
1" MIN.
1 1/2"
DUCTLESS AND FLEX DUCT SUPPLY
ITEM DESCRIPTION
1. CEILING RADIATION DAMPER
2. GRILLE FRAME (20 GA. MIN.)
3. DUCT (WHERE SHOWN)
4. #8 SHEET METAL SCREW
5. #10 SHEET METAL SCREW
6. 16 MSG X 1 1/2" CHANNEL
7. CEILING GRID (UL CLASSIFIED)
8. DUCT DROP (WHERE SHOWN)
9. 12 SWG STEEL WIRE
10. ACOUSTICAL LAY-IN PANELS (UL CLASSIFIED)
11. DIFFUSER OR GRILLE CORE (METALLIC OR NON-METALLIC)
12. RIGID GYPSUM WALL BOARD CEILING (UL CLASSIFIED)
8
CEILING RADIATION DAMPER DETAIL
SCALE: NONE
9
5
DETAIL A
HANGING WIRE & LOOP
CURB AND EQUIPMENT HURRICANE CLIP DETAIL
SCALE: NONE
BELOW GRADE
ABOVE GRADE
DRIVE PINS
Z CLIP
LAG SCREWS
EXISTING
SUPPORT
ROOF
FRAMING CLIP
BLOCKING
EXISTING JOISTS
1" MIN.
(GRADE TO TOP OF GRAVEL)
EXTERIOR FLOOR DRAIN
INSTALLED FLUSH WITH GRADE, PROVIDE
A MINIMUM 2" PIPE TO GRAVEL
48" MIN.
(FOR PTAC CONDENSATE STACK SPILL)
24" MIN.
(FOR SINGLE UNIT CONDENSATE SPILL)
24" MIN.
(FOR PTAC CONDENSATE STACK SPILL)
12" MIN.
(FOR SINGLE UNIT CONDENSATE SPILL)
ABOVE GRADE
ROCK (3/4" - 2" DIAMETER)
PIPE EXTENDS MINIMUM
3" INTO ROCK FILL
CONDENSATE DRAIN LINE FROM INTERIOR
A/C COIL, SEE DRAWING FOR SIZE& ROUTING
TYPICAL CONDENSATE DRY WELL DETAIL
SCALE: NONE
________________________________________________________________________
BY DATE
05/31/2017
MECHANICAL
DETAILS
M2-03
2/1/2017 5:14:29 P
M
El P
aso
, T
exa
s
TR
U b
y H
ilto
n - E
l P
as
o
Tru
H
ote
l P
artn
ers, L
LC
16105
Revision Schedule
Rev.
Num.Rev. Date Revision Description
AEED,
Advanced Energy Engineering & Design, Inc
CHATTANOOGA, TN 37405
BUS. (423) 752-3438
FAX (423) 752-1369
P.O. BOX 4934
408 McCALLIE AVE
inc.
AEED JOB NO.001-17
COPYRIGHT NOTICE
THE DRAWINGS ARE THE
PROPERTY OF RIVER STREET
ARCHITECTURE LLC. ANY USE,
REUSE, REPRODUCTION,
DISPLAY OR SALE OF THESE
DRAWINGS WITHOUT THE
EXPRESS WRITTEN CONSENT
OF THE ARCHITECT IS
STRICTLY PROHIBITED.
714 cherry street, chattanooga, tennessee 37402
p.423 634 0806 f.423 752 8499 w
ww
.riverstreetarchitecture.com
Release Date:
Project No.:
NOTES:
1 SPIN IN CONICAL BRANCH TAP FITTING WITH MANUAL VOLUME DAMPER. BRANCH
RUNOUT DUCT SHALL BE THE SAME DIAMETER AS THE AIR TERMINAL INLET.
2 DUCT STRAP HANGER. ATTACH TO STRUCTURE.
3 STRAP HANGER REQUIRED IF BRANCH RUNOUT LENGTH IS GREATER THAN 4 FT.
4 MAXIMUM FLEXIBLE DUCT LENGTH IS 5 FT. FLEXIBLE DUCT SHALL BE THE SAME
DIAMETER AS THE AIR TERMINAL INLET. FLEXIBLE DUCT SHALL BE INSULATED.
STRETCH FLEXIBLE DUCT TO A MINIMUM OF 90% OF ITS FULLY EXTENDED LENGTH.
SEAL CONNECTIONS AIR TIGHT.
5 HARD ELBOW TO AIR TERMINAL CONNECTION.
6 COMPRESSION FITTING AT AIR TERMINAL CONNECTION.
7 PROVIDE ALL CLIPS AND MARGINS REQUIRED FOR A COMPLETE INSTALLATION.
COORDINATE LOCATION AND FINISH WITH OWNER/ARCHITECT.
1
2 3
4
5
6
7
TYPICAL SUPPLY AIR TERMINAL CONNECTION
SCALE: NONE
COMBINATION FIRE/SMOKE DAMPER
SCALE: NONE
CONTROLLED ROUND OR RECTANGULAR DAMPERS, AND CAN BE MOUNTED IN A WIDE
SYSTEM IS DESIGNED FOR USE WITH EXTERNALLY 1)
NOTES:
LINEAR SLOT DIFFUSER
RIGID DUCTWORK
FLEXIBLE DUCTWORK
AND WIRE (50'-0"
RACK & PINION
FLEXIBLE CASING
MAXIMUM)
OPERATOR
MOUNTING BRACKET
VARIETY OF LOCATIONS INCLUDING CEILING JOISTS, LAY-IN CEILINGS, BEHIND GRILLES,
SOCKET WRENCH
WITH PLENUM BOX
LOCKING
CABLE SHALL CONSIST OF 0.054" STAINLESS STEEL CONTROL WIRE
ENCAPSULATED IN 1/16" FLEXIBLE GALVANIZED SPIRAL WIRE SHEATH.
LOCKING RACK AND PINION GEAR DRIVE SHALL BE CONSTRUCTED OF 14 GAUGE STEEL
AND SHALL BE USED TO CONVERT ROTARY MOTION INTO PUSH-PULL MOTION.
CONTROL SHAFT SHALL BE "D"-STYLE FLATTENED 1/4" DIAMETER WITH 265° ROTATION
PROVIDING 1-1/2" LINEAR TRAVEL CAPABILITY.
2)
3)
4)
ON OR INSIDE OTHER VARIOUS TYPES OF DIFFUSERS, ETC.
RECTANGULAR
ROUND DAMPER OR
OPPOSED BLADE DAMPER
TYPICAL GUEST FLOOR EXHAUST/OUTDOOR AIR DUCT ROUTING
SCALE: NONE
ALL RELAYS, WIRING AND TRANSFORMERS REQUIRED TO INTERLOCK
SMOKE DETECTOR WITH SMOKE DAMPER OPERATOR ARE THE
RESPONSIBILITY OF DIV. 15000
SMOKE DETECTOR BY
DIV. 16000, INSTALLED
WIRING BY
DIV. 15000
WIRING TO FIRE ALARM CONTROL
PANEL, BY DIV. 16000
BY DIV. 15000
UL LISTED OPERATOR
SLEEVE
SEAL WITH FIRE CAULK
RETAINING ANGLES-
ACTUATOR AND FUSIBLE LINK
WITH DAMPER MOUNTED
FIRE/SMOKE DAMPER
FIRE/SMOKE BARRIER
(VERTICAL OR
HORIZONTAL)
DUCT
PANEL
DUCT ACCESS
SA
Supply Fan
T
Smoke Detector
M 1
OA
RA
AI - Supply Air Temp
SCALE: NONE
ECONOMIZER SEQUENCE OF OPERATION - SINGLE ZONE CONSTANT VOLUME SPLIT SYSTEM (AHU-1 & AHU-2)
ECONOMIZER:
THE CONTROLLER SHALL MEASURE THE ZONE TEMPERATURE AND MODULATE THE
ECONOMIZER DAMPERS IN SEQUENCE TO MAINTAIN SET POINT 2°F LESS THAN THE ZONE
COOLING SET POINT.
THE ECONOMIZER SHALL BE ENABLED WHENEVER:
• OUTSIDE AIR TEMPERATURE IS LESS THAN 60°F (ADJ.).
• AND THE OUTSIDE AIR ENTHALPY IS LESS THAN 22BTU/LB (ADJ.).
• AND THE OUTSIDE AIR TEMPERATURE IS LESS THAN THE RETURN AIR TEMPERATURE.
• AND THE OUTSIDE AIR ENTHALPY IS LESS THAN THE RETURN AIR ENTHALPY.
• AND THE SUPPLY FAN STATUS IS ON.
THE ECONOMIZER SHALL CLOSE WHENEVER:
• MIXED AIR TEMPERATURE DROPS FROM 45°F TO 40°F (ADJ.).
• OR ON LOSS OF SUPPLY FAN STATUS.
• OR FREEZESTAT (IF PRESENT) IS ON.
DAMPER POSITIONING WHEN ECONOMIZER CYCLE IS CALLED FOR:
· THE OUTSIDE (M1) SHALL BE OPEN
· THE RETURN AIR DAMPER (M2) SHALL BE CLOSED
· PETREATED OA DAMPER (M3) SHALL BE CLOSED
DAMPER POSITIONING WHEN ECONOMIZER CYCLE IS OFF:
· THE OUTSIDE (M1) SHALL BE CLOSED
· THE RETURN AIR DAMPER (M2) SHALL BE OPEN
· PRETREATED OA DAMPER (M3) SHALL BE OPEN
E
TEMPERATURE / ENTHALPY
SENSOR LOCATED OUTSIDE.
COORDINATE FINAL
LOCATION WITH
OWNER/ARCHITECT.
DX COIL
M
2
FILTER
MINIMUM OUTSIDE AIR VENTILATION - FIXED PERCENTAGE:
· THE PRETREATED OUTSIDE AIR DAMPER (M3) SHALL ACTUATE TO MAINTAIN A MINIMUM
POSITION (SEE SCHEDULES) DURING NORMAL COOLING CYCLE.
POSITIVE PRESSURE RELIEF DURING ECONOMIZER CYCLE:
· BAROMETRIC DAMPER ASSEMBLY DESIGNED TO ALLOW EXCESS POSITIVE PRESSURE
RELIEF TO OUTDOORS VIA WALL LOUVER (SEE SHEET M1.01)
M3
OA FROM MAKE UP
UNIT ON ROOF
Smoke Detector
S
S
NOTES:
1 SPIN IN CONICAL BRANCH TAP FITTING WITH MANUAL VOLUME DAMPER. BRANCH
RUNOUT DUCT SHALL BE THE SAME DIAMETER AS THE AIR TERMINAL INLET.
2 DUCT STRAP HANGER. ATTACH TO STRUCTURE.
3 STRAP HANGER REQUIRED IF BRANCH RUNOUT LENGTH IS GREATER THAN 4 FT.
4 MAXIMUM FLEXIBLE DUCT LENGTH IS 5 FT. FLEXIBLE DUCT SHALL BE THE SAME
DIAMETER AS THE AIR TERMINAL INLET. STRETCH FLEXIBLE DUCT TO A MINIMUM OF
90% OF ITS FULLY EXTENDED LENGTH. SEAL CONNECTIONS AIR TIGHT.
5 HARD ELBOW TO AIR TERMINAL CONNECTION.
6 SHEET METAL PLENUM. PLENUM SHALL BE SAME SIZE AS GRILLE CONNECTION.
7 PROVIDE ALL CLIPS AND MARGINS REQUIRED FOR A COMPLETE INSTALLATION.
COORDINATE LOCATION AND FINISH WITH OWNER/ARCHITECT.
1
2 3
4
5
6
7
NOTES:
1 SPIN IN CONICAL BRANCH TAP FITTING WITH MANUAL VOLUME DAMPER. BRANCH
RUNOUT DUCT SHALL BE THE SAME DIAMETER AS THE AIR TERMINAL INLET.
2 DUCT STRAP HANGER. ATTACH TO STRUCTURE.
3 STRAP HANGER REQUIRED IF RUN OUT LENGTH IS GREATER THAN 4 FT.
4 MAXIMUM FLEXIBLE DUCT LENGTH IS 5 FT. FLEXIBLE DUCT SHALL BE THE SAME
DIAMETER AS THE AIR TERMINAL INLET. STRETCH FLEXIBLE DUCT TO A MINIMUM OF
90% OF ITS FULLY EXTENDED LENGTH. SEAL CONNECTIONS AIR TIGHT.
5 SPIN IN CONICAL BRANCH TAP FITTING. BRANCH RUNOUT DUCT SHALL BE THE SAME
DIAMETER AS THE AIR TERMINAL INLET.
6 SHEET METAL PLENUM. PLENUM SHALL BE SAME SIZE AS GRILLE CONNECTION.
7 PROVIDE ALL CLIPS AND MARGINS REQUIRED FOR A COMPLETE INSTALLATION.
COORDINATE LOCATION AND FINISH WITH OWNER/ARCHITECT.
1
2
3
56
7
TYPICAL AIR TERMINAL CONNECTION
LIMITED CLEARANCE APPLICATION
SCALE: NONE
TYPICAL RETURN & EXHAUST AIR TERMINAL CONNECTION
SCALE: NONE
CEILING EXHAUST FAN DETAIL
SCALE: NONE
FLEXIBLE CONNECTION
SUPPORT FAN FROM
STRUCTURE ABOVE WITH
THREADED RODS &
VIBRATION ISOLATORS
PROVIDE INTEGRAL GRILLE
UNLESS OTHERWISE INDICATED
PROVIDE FAN COMPLETE WITH BACK
DRAFT DAMPER AND WALL CAP
CURB MTD.
EQUIPMENT
MATERIAL
ROOFING
ROOF
DISTANCE EQUAL TO
INSULATION THICKNESS
INSULATION
ROOF
LOWEST POINT
DECK
FINISHED ROOF AT
MINIMUM, 12" ABOVE
NOTE:
1. COORDINATE FLASHING DETAIL WITH ROOFING SYSTEM PROVIDER
TYPICAL ROOF CURB DETAIL
SCALE: NONE
AS REQ'D
12"
AS REQ
'D
4
5
1" MAX.
4"
16 GA. SHEET
METAL
DRILL & CAULK
IN FIELD.
1"INSULATIONPROVIDE WASHER FOR WATER
TIGHT CONNECTION.
PIPING THRU ROOF DETAIL
SCALE: NONE
NOTE:
PIPES TO EXIT IN HORIZONTAL
ARRANGEMENT ONLY. DO NOT
STACK PIPES OVER ONE ANOTHER.
THICKNESS FROM TOP OF ROOF
TO TOP OF DECK.
SUPPLY & EXHAUST
DUCTS IN 2HR CHASE
DUCTS REMAIN BELOW FIRE RATED ASSEMBLY
DROP CEILING, NO RATING
FIRE RATED LID
TYPICAL G
UEST RO
O
M
TYPICAL CO
RRID
O
R
TYPICAL G
UEST FLO
O
R ABO
VE
FIRE DAMPER AT RATED FLOOR ASSEMBLY PENETRATION (TYPICAL)
FIRE DAMPER AT FIRE RATED CORRIDOR WALL (TYPICAL)
NO FIRE DAMPER REQUIRED IN GUEST ROOM PARTITIONS
PENETRATIONS WHEN DUCT IS LOCATED IN FIRE RATED FLOOR
ASSEMBLY
TYPICAL G
UEST FLO
O
R BELO
W
FSD
FD
FD
EXHAUST GRILLE LOCATED IN DROP CEILING TO
PROVIDE EXHAUST FOR GUEST RESTROOMS, PROVIDE
MANUAL BALANCING DAMPER
SUPPLY REGISTER SIDE DISCHARGES OUT OF SOFFIT TO
PROVIDE OUTDOOR AIR IN GUEST, PROVIDE MANUAL
BALANCING DAMPER
FD
FD
COMBINATION FIRE/SMOKE DAMPER AT CHASE WALL
PENETRATION.
DUCTS ROUTED IN FIRE RATED ASSEMBLY
NOTES:
· DRAWING IS MEANT TO CONVEY GENERAL INTENT WHILE ADDRESSING MOST ROUTING SITUATIONS
· THIS SCHEMATIC DOES NOT REFLECT A SPECIFIC SECTION OF DUCTWORK ON THIS JOB
SUPPLY & EXHAUST
DUCTS IN 2HR CHASE
CABLE CONTROLLED DAMPER DETAIL
SCALE: NONE
________________________________________________________________________
BY DATE
05/31/2017