building/fire code references 2006 · pdf filebuilding/fire code references 2006 edition this...

30
BUILDING/FIRE CODE REFERENCES 2006 EDITION This document provides a cross reference with the International Building Code and NFPA 1/Uniform Fire Code. The IBC references the IFC in 97 Code sections. This document identifies these references and provides the applicable reference in NFPA 1/UFC. This would be part of the adoption language when adopting NFPA 1/UFC in place of the IFC. Jim Dolan, Manager NFPA Fire Code Field Office 1100 Bandon Road Toms River, NJ 08753 voice: 732.270.0277 fax: 732.270.1366 e-mail: [email protected] website: http://www.nfpa.org Source documents: NFPA 1 Uniform Fire Code 2006 International Building Code2006 International Fire Code 2006

Upload: doannguyet

Post on 06-Mar-2018

218 views

Category:

Documents


1 download

TRANSCRIPT

Page 1: BUILDING/FIRE CODE REFERENCES 2006 · PDF fileBUILDING/FIRE CODE REFERENCES 2006 EDITION This document provides a cross reference with the International Building Code and NFPA 1/Uniform

BUILDING/FIRE CODE REFERENCES

2006 EDITION This document provides a cross reference with the International Building Code and NFPA 1/Uniform Fire Code. The IBC references the IFC in 97 Code sections. This document identifies these references and provides the applicable reference in NFPA 1/UFC. This would be part of the adoption language when adopting NFPA 1/UFC in place of the IFC.

Jim Dolan, Manager NFPA Fire Code Field Office 1100 Bandon Road Toms River, NJ 08753 voice: 732.270.0277 fax: 732.270.1366 e-mail: [email protected]: http://www.nfpa.org

Source documents: NFPA 1 Uniform Fire Code 2006 International Building Code 2006 International Fire Code 2006

Page 2: BUILDING/FIRE CODE REFERENCES 2006 · PDF fileBUILDING/FIRE CODE REFERENCES 2006 EDITION This document provides a cross reference with the International Building Code and NFPA 1/Uniform

2

IBC FIRE CODE CROSS REFERENCES 2006 EDITION

IBC SECTION IFC SECTION NFPA 1/UFC SECTION

101.4.6 The provisions of the International Fire Code shall apply to matters affecting or relating to structures, processes and premises from the hazard of fire and explosion arising from the storage, handling or use of structures, materials or devices; from conditions hazardous to life, property or public welfare in the occupancy of structures or premises; and from the construction, extension, repair, alteration or removal of fire suppression and alarm systems or fire hazards in the structure or on the premises from occupancy or operation.

101.2 This Code establishes regulations affecting or relating to structures, processes and premises and safeguards from the hazard of fire and explosion arising from the storage, handling or use of structures, materials or devices; from conditions hazardous to life, property or public welfare in the occupancy of structures or premises from fire hazards in the structure or on the premise from occupancy or operation; and, matters related to the construction, extension, repair, alteration or removal of fire suppression and alarm systems.

1.2 The purpose of this Code is to prescribe minimum requirements necessary to establish a reasonable level of fire and life safety and property protection from the hazards created by fire, explosion, and dangerous conditions.

102.6 Existing structures.

The legal occupancy of any structure existing on the date of adoption of this Code shall be permitted to continue without change, except as is specifically covered in this Code, the International Property Maintenance Code or the International Fire Code, or as is deemed necessary by the building official for the general safety and welfare of the occupants and the public.

102.2 Administrative, operational and maintenance provisions. The administrative, operational and maintenance provisions of this Code shall apply to:

1. Conditions and operations arising after the adoption of this Code.

2. Existing conditions and operations.

1.3.6.2 Buildings in existence or permitted for construction prior to the adoption of this Code shall comply with the provisions stated herein or referenced for existing buildings.

Page 3: BUILDING/FIRE CODE REFERENCES 2006 · PDF fileBUILDING/FIRE CODE REFERENCES 2006 EDITION This document provides a cross reference with the International Building Code and NFPA 1/Uniform

3

IBC FIRE CODE CROSS REFERENCES 2006 EDITION

IBC SECTION IFC SECTION NFPA 1/UFC SECTION

201.3 Terms defined in other Codes. Where terms are not defined in this Code and are defined in the International Fuel Gas Code, International Fire Code, International Mechanical Code or International Plumbing Code, such terms shall have the meanings ascribed to them as in those Codes.

201.1 Scope. Unless otherwise expressly stated, the following words and terms shall, for the purposes of this Code, have the meanings shown in this chapter.

3.1 General. The definitions contained in this chapter shall apply to the terms used in this Code. Where terms are not defined in this chapter or within another chapter, they shall be defined using their ordinarily accepted meanings within the context in which they are used. Merriam-Webster’s Collegiate Dictionary, 11th edition, shall be the source for the ordinarily accepted meaning.

307.1. Hazardous uses are classified in Groups H-1, H-2, H-3, H-4 and H-5 and shall be in accordance with this section, the requirements of Section 415 and the International Fire Code. 1. Buildings and structures that contain not more than the maximum allowable quantities per control area of hazardous materials…that such buildings are maintained in accordance with the International Fire Code.

3. Buildings and structures occupied for the application of flammable finishes, provided that such buildings or areas conform to the requirements of Section 416 and NFPA 33, NFPA 34 and the International Fire Code.

4. Wholesale and retail sales and storage of flammable and combustible liquids in mercantile occupancies conforming to NFPA 30 and the International Fire Code.

13. Buildings and structures occupied for aerosol manufacturing or storage shall be classified as Group F-1 or S-1, provided that such buildings conform to the requirements of NFPA 30B and the International Fire Code.

2701.1 Prevention, control and mitigation of dangerous conditions related to storage, dispensing, use and handling of hazardous materials shall be in accordance with this chapter.

This chapter shall apply to all hazardous materials, including those materials regulated elsewhere in this Code, except that when specific requirements are provided in other chapters, those specific requirements shall apply in accordance with the applicable chapter. Where a material has multiple hazards, all hazards shall be addressed.

60.1.1 Occupancies containing high hazard contents shall comply with Chapter 60 in addition to other applicable requirements of this Code, except as specified in 60.1.2.

Page 4: BUILDING/FIRE CODE REFERENCES 2006 · PDF fileBUILDING/FIRE CODE REFERENCES 2006 EDITION This document provides a cross reference with the International Building Code and NFPA 1/Uniform

4

IBC FIRE CODE CROSS REFERENCES 2006 EDITION

IBC SECTION IFC SECTION NFPA 1/UFC SECTION

307.1.1 Hazardous materials. Hazardous materials in any quantity shall conform to the requirements of this Code, including Section 414, and the International Fire Code.

2701.1 Scope. Prevention, control and mitigation of dangerous conditions related to storage, dispensing, use and handling of hazardous materials shall be in accordance with this chapter.

60.1.1 Occupancies containing high hazard contents shall comply with Chapter 60 in addition to other applicable requirements of this Code, except as specified in 60.1.2.

Table 307.1(1) e. Quantities shall be increased 100 percent when stored in approved cabinets, gas cabinets, exhausted enclosures, or safety cans as specified in the International Fire Code.

Table 2703.1.1(1) e. Maximum allowable quantities shall be increased 100 percent when stored in approved storage cabinets, gas cabinets, or exhausted enclosures. Where Note d also applies the increase for both notes shall be applied accumulatively.

Table 60.1.3.1 g. Quantities are permitted to be increased 100 percent where stored in approved cabinets, gas cabinets, exhausted enclosures, explosives magazines, or safety cans, as appropriate for the material stored, in accordance with this Code.

Table 307.1(2) f. Quantities shall be increased 100 percent when stored in approved storage cabinets, gas cabinets, or exhausted enclosures as specified in the International Fire Code.

Table 2703.1.1(1) e. Maximum allowable quantities shall be increased 100 percent when stored in approved storage cabinets, gas cabinets, or exhausted enclosures.

Table 60.1.3.1 g. Quantities are permitted to be increased 100 percent where stored in approved cabinets, gas cabinets, exhausted enclosures, explosives magazines, or safety cans, as appropriate for the material stored, in accordance with this Code.

404.2 Use. The floor of the atrium shall not be used for other than low fire hazard uses and only approved materials and decorations in accordance with the International Fire Code.

801.1 Scope. The provisions of this chapter shall govern furniture and furnishings, interior finishes, interior trim, decorative materials and decorative vegetation in buildings.

12.6 Furnishings, Contents, Decorations, and Treated Finishes. Furnishings, contents, decorations, and treated finishes in buildings and structures shall meet the requirements of NFPA 101, Life Safety Code, and this Code.

406.5.1 Construction. Motor vehicle service stations shall be constructed in accordance with the International Fire Code and this section.

2201.1 Scope. Automotive service stations, marine service stations, fleet vehicle service stations and repair garages shall be in accordance with this chapter and the International Building Code, and the International Mechanical Code.

30.2 Repair Garages. The construction and protection of, as well as the control of hazards in, garages used for major repair and maintenance of motorized vehicles and any sales and servicing facilities associated therewith shall comply with NFPA 30A.

Page 5: BUILDING/FIRE CODE REFERENCES 2006 · PDF fileBUILDING/FIRE CODE REFERENCES 2006 EDITION This document provides a cross reference with the International Building Code and NFPA 1/Uniform

5

IBC FIRE CODE CROSS REFERENCES 2006 EDITION

IBC SECTION IFC SECTION NFPA 1/UFC SECTION

406.6.1 General. Repair garages shall be constructed in accordance with the International Fire Code and this section. This occupancy shall not include motor fuel-dispensing facilities, as regulated in Section 406.5.

2211.1 General. Repair garages shall comply with this section and the International Building Code. Repair garages for vehicles that use more than one type of fuel shall comply with the applicable provisions of this section for each type of fuel used.

Chapter 42 shall apply to refueling of automotive vehicles, marine vessels, and aircraft.

410.3.6 Scenery. Combustible materials used in sets and scenery shall meet the fire propagation performance criteria of NFPA 701, in accordance with Section 807 and the International Fire Code. Foam plastics and materials containing foam plastics shall comply with Section 2603 and the International Fire Code.

807.1 General requirements. In 0ccupancies in Groups A, E, I and R-1 and dormitories in Group R-2, curtains, draperies, hangings and other decorative materials suspended from walls or ceilings shall meet the flame propagation performance criteria of NFPA 701 in accordance with Section 806.2 or be noncombustible.

20.1.2.1 Combustible scenery of cloth, film, vegetation (dry), and similar materials shall meet the requirements of NFPA 701, Standard Methods of Fire Tests for Flame Propagation of Textiles and Films.

411.1 General.

Special amusement buildings having an occupant load of 50 or more shall comply with the requirements for the appropriate Group A Exception:

Amusement buildings or portions thereof that are without walls or a roof and constructed to prevent the accumulation of smoke. For flammable decorative materials, see the International Fire Code.

801.1 Scope.

The provisions of this chapter shall govern furniture and furnishings, interior finishes, interior trim, decorative materials and decorative vegetation in buildings. Sections 803, 804 and 805 shall be applicable to new and existing buildings. Section 806 shall be applicable to existing buildings.

12.6 Furnishings, Contents, Decorations, and Treated Finishes.

Furnishings, contents, decorations, and treated finishes in buildings and structures shall meet the requirements of NFPA 101, Life Safety Code, and this Code.

412.4.1 Occupancy group.

Aircraft paint hangars shall be classified as Group H-2. Aircraft paint hangars shall comply with the applicable requirements of this Code and the International Fire Code.

1101.1 Scope.

Airports, heliports, helistops and aircraft hangars shall be in accordance with this chapter.

21.1 The construction and protection of aircraft hangars from fire shall comply with this section; NFPA 409, Standard on Aircraft Hangars; NFPA 410, Standard on Aircraft Maintenance; and Section 40.6 and Section 42.6 of NFPA 101 Life Safety Code.

Page 6: BUILDING/FIRE CODE REFERENCES 2006 · PDF fileBUILDING/FIRE CODE REFERENCES 2006 EDITION This document provides a cross reference with the International Building Code and NFPA 1/Uniform

6

IBC FIRE CODE CROSS REFERENCES 2006 EDITION

IBC SECTION IFC SECTION NFPA 1/UFC SECTION

413.1 General. High-piled stock or rack storage in any occupancy group shall comply with the International Fire Code.

2301.1 Scope. High-piled combustible storage shall be in accordance with this chapter. In addition to the requirements of this chapter, the following material-specific requirements shall apply: 1. Aerosols shall be in accordance with Chapter 28.

2. Flammable and combustible liquids shall be in accordance with Chapter 34.

3. Hazardous materials shall be in accordance with Chapter 27.

4. Storage of combustible paper records shall be in accordance with NFPA 13 and NFPA 230.

5. Storage of combustible fibers shall be in accordance with Chapter 29.

6. Storage of miscellaneous combustible material shall be in accordance with Chapter 3.

20.15.7.1 Buildings containing high-piled storage shall comply with NFPA 13, Chapter 34, and 20.15.7.

414.1.1 Other provisions.

Buildings and structures with an occupancy in Group H shall also comply with the applicable provisions of Section 415 and the International Fire Code.

2701.1 Scope. Prevention, control and mitigation of dangerous conditions related to storage, dispensing, use and handling of hazardous materials shall be in accordance with this chapter.

60.1.1 Occupancies containing high hazard contents shall comply with Chapter 60 in addition to other applicable requirements of this Code, except as specified in 60.1.2.

414.1.2 Materials. The safe design of hazardous material occupancies is material dependent. Individual material requirements are also found in Sections 307 and 415, and in the International Mechanical Code and the International Fire Code.

2701.1 Scope. Prevention, control and mitigation of dangerous conditions related to storage, dispensing, use and handling of hazardous materials shall be in accordance with this chapter.

60.1.1 Occupancies containing high hazard contents shall comply with Chapter 60 in addition to other applicable requirements of this Code, except as specified in 60.1.2.

Page 7: BUILDING/FIRE CODE REFERENCES 2006 · PDF fileBUILDING/FIRE CODE REFERENCES 2006 EDITION This document provides a cross reference with the International Building Code and NFPA 1/Uniform

7

IBC FIRE CODE CROSS REFERENCES 2006 EDITION

IBC SECTION IFC SECTION NFPA 1/UFC SECTION

414.1.2.1 Aerosols. Level 2 and 3 aerosol products shall be stored and displayed in accordance with the International Fire Code.

2801.1 Scope. The provisions of this chapter, the International Building Code and NFPA 30B shall apply to the manufacturing, storage and display of aerosol products. Manufacturing of aerosol products using hazardous materials shall also comply with Chapter 27.

61.1.1.1 The manufacture, storage, use, handling, and display of aerosol products shall comply with the requirements of Chapter 61; NFPA 30B, Code for the Manufacture and Storage of Aerosol Products; and Section 60.1 and Section 60.2 of this Code.

414.2 Control areas. Control areas shall comply with Sections 414.2.1 through 414.2.5 and the International Fire Code.

2703.1.1 Maximum allowable quantity per control area. The maximum allowable quantity per control area shall be as specified in Tables 2703.1.1(1) through 2703.1.1(4).

60.1.3.1 General. Maximum allowable quantities of hazardous materials per control area shall be as specified in Table 60.1.3.1, except as modified by 60.1.3.2 and 60.1.3.3.

414.2.5 Hazardous material in Group M display and storage areas and in Group S storage areas. Provided that the materials are displayed and stored in accordance with the International Fire Code and quantities do not exceed the maximum allowable specified in Table 414.2.5(1).

2703.11.3 Storage and display. Storage and display shall be in accordance with Sections 2703.11.3.1 through 2703.11.3.10.

60.1.3.3.1 Maximum Allowable Quantity Increases for Mercantile, Storage, and Industrial Occupancies. The aggregate quantity of nonflammable solid and nonflammable or noncombustible liquid hazardous materials permitted within a single control area of a mercantile, storage, or industrial occupancy shall be permitted to exceed the maximum allowable quantities specified in Table 60.1.3.1.

Table 414.2.5 (1) a Maximum allowable quantity per indoor and outdoor control area in group M and S occupancies nonflammable solids and nonflammable and noncombustible liquids

2703.11.3 Storage and display. Storage and display shall be in accordance with Sections 2703.11.3.1 through 2703.11.3.10.

60.1.3.3.1 Maximum Allowable Quantity Increases for Mercantile, Storage, and Industrial Occupancies. The aggregate quantity of nonflammable solid and nonflammable or noncombustible liquid hazardous materials permitted within a single control area of a mercantile, storage, or industrial occupancy shall be permitted to exceed the maximum allowable quantities specified in Table 60.1.3.1.

Page 8: BUILDING/FIRE CODE REFERENCES 2006 · PDF fileBUILDING/FIRE CODE REFERENCES 2006 EDITION This document provides a cross reference with the International Building Code and NFPA 1/Uniform

8

IBC FIRE CODE CROSS REFERENCES 2006 EDITION

IBC SECTION IFC SECTION NFPA 1/UFC SECTION

414.2.5 Hazardous material in Group M display and storage areas and in Group S storage areas. …displayed and stored in accordance with the International Fire Code and quantities do not exceed the maximum allowable quantities specified in Table 414.2.4.

2701.3 Retail and wholesale storage and display. For retail and wholesale storage and display of nonflammable solid and nonflammable or noncombustible liquid hazardous materials in Group M retail sales occupancies, see Section 2703.11.

60.1.1.2 Buildings and portions thereof containing high hazard contents that are limited to the following need not comply with Chapter 60: (2) Flammable and combustible liquids associated with wholesale and retail sales and storage in mercantile occupancies and complying with Chapter 66.

414.3 Ventilation. Rooms, areas or spaces of Group H in which explosive, corrosive, combustible, flammable or highly toxic dusts, mists, fumes, vapors or gases are or may be emitted due to the processing, use, handling or storage of materials shall be mechanically ventilated as required by the International Fire Code and the International Mechanical Code.

2701.1 Prevention, control and mitigation of dangerous conditions related to storage, dispensing, use and handling of hazardous materials shall be in accordance with this chapter.

60.1.1 Occupancies containing high hazard contents shall comply with this chapter in addition to other applicable requirements of this Code, except as specified in 60.1.2.

414.5 The inside storage, dispensing and use of hazardous materials in excess of the maximum allowable quantities per control area of Tables 307.7(1) and 307.7(2) shall be in accordance with Sections 414.5.1 through 414.5.5 and the International Fire Code.

2705.1 Use, dispensing and handling of hazardous materials in amounts not exceeding the maximum allowable quantity per control area set forth in Section 2703.1 shall be in accordance with Sections 2701 and 2703.

60.1.3.1 General. Maximum allowable quantities of hazardous materials per control area shall be as specified in Table 60.1.3.1, except as modified by 60.1.3.2 and 60.1.3.3.

414.5.1 Explosion control shall be provided in accordance with the International Fire Code

911.1 Explosion control shall be provided in the following locations:

60.3.2.6 Explosion Control. Buildings, or portions thereof, required to comply with Protection Level 1 through Protection Level 3 and containing materials shown in Table 60.3.2.6 shall be provided with a means of explosion control.

Page 9: BUILDING/FIRE CODE REFERENCES 2006 · PDF fileBUILDING/FIRE CODE REFERENCES 2006 EDITION This document provides a cross reference with the International Building Code and NFPA 1/Uniform

9

IBC FIRE CODE CROSS REFERENCES 2006 EDITION

IBC SECTION IFC SECTION NFPA 1/UFC SECTION

Table 414.5.1 b. see the International Fire Code.

Table 911.1 Explosion Control Requirements 60.3.2.6 Explosion Control. Buildings, or portions thereof, required to comply with Protection Level 1 through Protection Level 3 and containing materials shown in Table 60.3.2.6 shall be provided with a means of explosion control.

414.5.2 Monitor control equipment.

Monitor control equipment shall be provided where required by the International Fire Code.

Table 911.1 Explosion Control Requirements 60.3.2.6 Explosion Control. Buildings, or portions thereof, required to comply with Protection Level 1 through Protection Level 3 and containing materials shown in Table 60.3.2.6 shall be provided with a means of explosion control.

414.5.4 Standby or emergency power. Where mechanical ventilation, treatment systems, temperature control, alarm, detection or other electrically operated systems are required, such systems shall be provided with an emergency or standby power system in accordance with this Code or the ICC Electrical Code. Exceptions: 3. Storage, use and handling areas for highly toxic or toxic materials as provided for in the International Fire Code.

2705.1.5 Standby or emergency power. Where mechanical ventilation, treatment systems, temperature control, manual alarm, detection or other electrically operated systems are required, such systems shall be provided with an emergency or standby power system in accordance with the ICC Electrical Code and Section 604.

60.3.2.7.1 Where mechanical ventilation, treatment systems, temperature control, alarm, detection, or other electrically operated safety systems are required by this Code or the building code, such systems shall be provided with standby power or emergency power as required by 60.3.2.7.

414.5.5 Spill control, drainage and containment. Rooms, buildings or areas occupied for the storage of solid and liquid hazardous materials shall be provided with a means to control spillage and to contain or drain off spillage and fire protection water discharged in the storage area where required in the International Fire Code.

2704.2 Spill control and secondary containment for liquid and solid hazardous materials. Rooms, buildings or areas used for the storage of liquid or solid hazardous materials shall be provided with spill control and secondary containment in accordance with Sections 2704.2.1 through 2704.2.3.

60.3.2.8.3.1 Buildings, or portions thereof, used for any of the following shall be provided with secondary containment:

Page 10: BUILDING/FIRE CODE REFERENCES 2006 · PDF fileBUILDING/FIRE CODE REFERENCES 2006 EDITION This document provides a cross reference with the International Building Code and NFPA 1/Uniform

10

IBC FIRE CODE CROSS REFERENCES 2006 EDITION

IBC SECTION IFC SECTION NFPA 1/UFC SECTION

414.6 The outside storage, dispensing and use of hazardous materials shall be in accordance with the International Fire Code.

2701.1 Prevention, control and mitigation of dangerous conditions related to storage, dispensing, use and handling of hazardous materials shall be in accordance with this chapter.

60.1.1 Occupancies containing high hazard contents shall comply with this chapter in addition to other applicable requirements of this Code, except as specified in 60.1.2.

415.1 The provisions of this section shall apply to the storage and use of hazardous materials in excess of the maximum allowable quantities. Buildings and structures with an occupancy in Group H shall also comply with the applicable provisions of Section 414 and the International Fire Code.

2705.1 Use, dispensing and handling of hazardous materials in amounts exceeding the maximum allowable quantity per control area set forth in Section 2703.1 shall be in accordance with Sections 2701, 2703 and 2705.

60.1.1 Occupancies containing high hazard contents shall comply with this chapter in addition to other applicable requirements of this Code, except as specified in 60.1.2.

415.3 Group H shall be located on property in accordance with the other provisions of this chapter. Exceptions:

1. Liquid use, dispensing and mixing rooms having a floor area of not more than 500 square feet where they are in accordance with the International Fire Code and NFPA 30.

2. Liquid storage rooms having a floor area of not more than 1,000 square feet where they are in accordance with the International Fire Code and NFPA 30.

2701.1 Prevention, control and mitigation of dangerous conditions related to storage, dispensing, use and handling of hazardous materials shall be in accordance with this chapter.

60.1.1 Occupancies containing high hazard contents shall comply with this chapter in addition to other applicable requirements of this Code, except as specified in 60.1.2.

415.3.1 Group H occupancy minimum fire separation distance. Buildings containing Group H occupancies …when separation is provided in accordance with the quantity distance tables specified for explosive materials in the International Fire Code.

Table 3304.5.2 (1) American Table of Distances for Storage of Explosives

65.9.1 The manufacture, transportation, storage, sale, and use of explosive materials shall comply with NFPA 495, Explosive Materials Code, and NFPA 498, Standard for Safe Havens and Interchange Lots for Vehicles Transporting Explosives.

Page 11: BUILDING/FIRE CODE REFERENCES 2006 · PDF fileBUILDING/FIRE CODE REFERENCES 2006 EDITION This document provides a cross reference with the International Building Code and NFPA 1/Uniform

11

IBC FIRE CODE CROSS REFERENCES 2006 EDITION

IBC SECTION IFC SECTION NFPA 1/UFC SECTION

Table 415.3.1 e. Magazine is a building or structure approved for storage of explosive materials. In addition to the requirements of this Code, magazines shall comply with the International Fire Code.

Table 3304.3 Storage Amounts and Magazine Requirements for Explosives, Explosive Materials and Fireworks Maximum Allowable Quantity per Control Area

65.9.1 The manufacture, transportation, storage, sale, and use of explosive materials shall comply with NFPA 495, Explosive Materials Code, and NFPA 498, Standard for Safe Havens and Interchange Lots for Vehicles Transporting Explosives.

Table 415.3.2 a. See Chapter 33 International Fire Code

3301.1 Scope. The provisions of this chapter shall govern the possession, manufacture, storage, handling, sale and use of explosives, explosive materials, fireworks and small arms ammunition.

65.1.1 The storage, use, and handling of explosives, fireworks and model rocketry shall comply with the requirements of this chapter, NFPA Standards referenced within this chapter and Section 60.1 and Section 60.2 of this Code.

415.6 Group H-2. Occupancies in Group H-2 shall be constructed in accordance with Sections 415.7.1 through 415.7.4 and the International Fire Code.

2701.1 Prevention, control and mitigation of dangerous conditions related to storage, dispensing, use and handling of hazardous materials shall be in accordance with this chapter.

60.1.1 Occupancies containing high hazard contents shall comply with this chapter in addition to other applicable requirements of this Code, except as specified in 60.1.2.

Page 12: BUILDING/FIRE CODE REFERENCES 2006 · PDF fileBUILDING/FIRE CODE REFERENCES 2006 EDITION This document provides a cross reference with the International Building Code and NFPA 1/Uniform

12

IBC FIRE CODE CROSS REFERENCES 2006 EDITION

IBC SECTION IFC SECTION NFPA 1/UFC SECTION

415.6.1 Combustible dusts, grain processing and storage.

The provisions of Sections 415.7.1.1 through 415.7.1.5 shall apply to buildings in which materials that produce combustible dusts are stored or handled. Buildings which store or handle combustible dusts shall comply with the applicable provisions of NFPA 61, NFPA 65, NFPA 120, NFPA 651, NFPA 654, NFPA 655, NFPA 664 and NFPA 8503, and the International Fire Code.

1304.1 Standards. The fire Code official is authorized to enforce applicable provisions of the Codes and standards listed in Table 1304.1 to prevent and control dust explosions.

Standard Subject

NFPA 61 Agricultural and Food

NFPA 69 Explosion Prevention

NFPA 85 Boiler and Combustion System Hazards

NFPA 120 Coal Preparation Plants

NFPA 484 Combustible Metals, Metal Powders and Metal Dusts

NFPA 654 Manufacturing, Processing and Handling of Combustible Particulate Solids

NFPA 655 Prevention of Sulfur Fires and Explosions

NFPA 664 Prevention of Fires and Explosions in Wood Processing and Woodworking Facilities

ICC Electrical Code Electrical Installations

40.1 Equipment, processes, and operations that involve the manufacture, processing, blending, repackaging, or handling of combustible particulate solids or combustible dusts regardless of concentration or particle size shall be installed and maintained in accordance with the following standards as applicable: (1) NFPA 61, Standard for the Prevention of Fires and Dust Explosions in Agricultural and Food Processing Facilities

(2) NFPA 69, Standard on Explosion Prevention Systems

(3) NFPA 85, Boiler and Combustion Systems Hazards Code

(4) NFPA 120, Standard for Coal Preparation Plants

(5) NFPA 484, Standard for Combustible Metals, Metal Powders, and Metal Dusts

(6) NFPA 654, Standard for the Prevention of Fire and Dust Explosions from the Manufacturing, Processing, and Handling of Combustible Particulate Solids

(7) NFPA 655, Standard for Prevention of Sulfur Fires and Explosions

(8) NFPA 664, Standard for the Prevention of Fires and Explosions in Wood Processing and Woodworking Facilities

415.6.1.4 Explosion control shall be provided as specified in the International Fire Code.

911.1 General. Explosion control shall be provided in the following locations:

60.3.2.6 Explosion Control. Buildings, or portions thereof, required to comply with Protection Level 1 through Protection Level 3 and containing materials shown in Table 60.3.2.6 shall be provided with a means of explosion control.

Page 13: BUILDING/FIRE CODE REFERENCES 2006 · PDF fileBUILDING/FIRE CODE REFERENCES 2006 EDITION This document provides a cross reference with the International Building Code and NFPA 1/Uniform

13

IBC FIRE CODE CROSS REFERENCES 2006 EDITION

IBC SECTION IFC SECTION NFPA 1/UFC SECTION

415.6.2 Flammable and combustible liquids. The storage, handling processing and transporting shall be in accordance with the International Mechanical Code, International Fire Code.

3401.1 Prevention, control and mitigation of dangerous conditions related to storage, use, dispensing, mixing and handling of flammable and combustible liquids shall be in accordance with Chapter 27 and this chapter.

66.1.1 The storage, use, and handling of flammable and combustible liquids, including waste liquids, shall comply with this chapter, NFPA 30, Flammable and Combustible Liquids Code, and Section 60.1 and Section 60.2 of this Code.

415.6.2.3 Storage tanks shall be approved tanks conforming to the requirements of the International Fire Code.

3404.2.7 Design, construction and general installation requirements for tanks. The design, fabrication and construction of tanks shall comply with NFPA 30. Each tank shall bear a permanent nameplate or marking indicating the standard used as the basis of design.

66.2.1 Scope. Chapter 66 shall apply to the following:

(3) The design, installation, testing, operation, and maintenance of such tanks, portable tanks, and bulk containers

415.6.2.5 Leakage containment. A liquid-tight containment area compatible with the stored liquid shall be provided. The method of spill control, drainage control and secondary containment shall be in accordance with the International Fire Code.

3403.4 Spill control and secondary containment. Where the maximum allowable quantity per control area is exceeded, and when required by Section 2704.2, rooms, buildings or areas used for storage, dispensing, use, mixing or handling of Class I, II and III-A liquids shall be provided with spill control and secondary containment in accordance with Section 2704.2.

60.3.2.8.1 General. Buildings, or portions thereof, required to comply with Protection Level 1 through Protection Level 5 shall be provided with spill control and secondary containment in accordance with 60.3.2.8.2 and 60.3.2.8.3, except for outdoor storage on containment pallets complying with 60.3.2.10.

415.6.2.7 Tank vent. Storage tank vents for Class I, II or IIIA liquids shall terminate to the outdoor air in accordance with the International Fire Code.

3404.2.7.3 Tank vents for normal venting. Tank vents for normal venting shall be installed and maintained in accordance with Sections 3404.2.7.3.1 through 3404.2.7.3.6.. The vents shall be installed and maintained in accordance with Section 2.2.5.1 of NFPA 30 or API 2000.

66.1.1 The storage, use, and handling of flammable and combustible liquids, including waste liquids, shall comply with this chapter, NFPA 30, Flammable and Combustible Liquids Code, and Section 60.1 and Section 60.2 of this Code.

Page 14: BUILDING/FIRE CODE REFERENCES 2006 · PDF fileBUILDING/FIRE CODE REFERENCES 2006 EDITION This document provides a cross reference with the International Building Code and NFPA 1/Uniform

14

IBC FIRE CODE CROSS REFERENCES 2006 EDITION

IBC SECTION IFC SECTION NFPA 1/UFC SECTION

415.6.2.8 Room ventilation. Storage tank areas storing Class I, II or IIIA liquids shall be provided with mechanical ventilation. The mechanical ventilation system shall be in accordance with the International Mechanical Code and the International Fire Code.

3406.4.4 Ventilation. Ventilation shall be provided for rooms, buildings and enclosures in which Class I liquids are pumped, used or transferred. Design of ventilation systems shall consider the relatively high specific gravity of the vapors. When natural ventilation is used, adequate openings in outside walls at floor level, unobstructed except by louvers or coarse screens, shall be provided. When natural ventilation is inadequate, mechanical ventilation shall be provided in accordance with the International Mechanical Code.

66.4.4.2.7 Liquid storage areas where dispensing is conducted shall be provided with either a gravity or a continuous mechanical exhaust ventilation system. Mechanical ventilation shall be used if Class I liquids are dispensed within the room.

415.6.2.9 Explosion venting. Where Class I liquids are being stored, explosion venting shall be provided in accordance with the International Fire Code.

Section 911 Explosion Control

Such areas shall be provided with explosion (deflagration) venting, explosion (deflagration) prevention systems, or barricades in accordance with this section and NFPA 69, or NFPA 495 as applicable. Deflagration venting shall not be utilized as a means to protect buildings from detonation hazards.

60.3.2.6 Explosion Control. Buildings, or portions thereof, required to comply with Protection Level 1 through Protection Level 3 and containing materials shown in Table 60.3.2.6 shall be provided with a means of explosion control. A.60.3.2.6 (4) NFPA 68, Guide for Venting of Deflagrations, provides information and guidance on how to design and install deflagration (explosion) venting.

415.6.3 Liquefied petroleum gas-distribution facilities. The storage and handling of liquefied petroleum gas systems shall conform to the International Fire Code.

3801.1 Scope. Storage, handling and transportation of LP-gas and the installation of LP-gas equipment pertinent to systems for such uses shall comply with this chapter and NFPA 58.

69.1.1.1 The storage, use, and handling of liquefied petroleum gases (LP-Gas) shall comply with the requirements of this chapter; NFPA 58, Liquefied Petroleum Gas Code; and Sections 60.1 and 60.2 of this Code.

Page 15: BUILDING/FIRE CODE REFERENCES 2006 · PDF fileBUILDING/FIRE CODE REFERENCES 2006 EDITION This document provides a cross reference with the International Building Code and NFPA 1/Uniform

15

IBC FIRE CODE CROSS REFERENCES 2006 EDITION

IBC SECTION IFC SECTION NFPA 1/UFC SECTION

415.6.3.3.3 Explosion venting. Explosion venting shall be provided in accordance with the International Fire Code.

Section 911 Explosion Control

Such areas shall be provided with explosion (deflagration) venting, explosion (deflagration) prevention systems, or barricades in accordance with this section and NFPA 69, or NFPA 495 as applicable. Deflagration venting shall not be utilized as a means to protect buildings from detonation hazards.

60.3.2.6 Explosion Control. Buildings, or portions thereof, required to comply with Protection Level 1 through Protection Level 3 and containing materials shown in Table 60.3.2.6 shall be provided with a means of explosion control. A.60.3.2.6 (4) NFPA 68, Guide for Venting of Deflagrations, provides information and guidance on how to design and install deflagration (explosion) venting.

415.6.3.5 Rooms within buildings. Where liquefied petroleum gas-distribution facilities are located in rooms within buildings, such rooms shall be located in the first story above grade plane and shall have at least one exterior wall with sufficient exposed area to provide explosion venting as required in the International Fire Code.

Section 911 Explosion Control

Such areas shall be provided with explosion (deflagration) venting, explosion (deflagration) prevention systems, or barricades in accordance with this section and NFPA 69, or NFPA 495 as applicable. Deflagration venting shall not be utilized as a means to protect buildings from detonation hazards.

60.3.2.6 Explosion Control. Buildings, or portions thereof, required to comply with Protection Level 1 through Protection Level 3 and containing materials shown in Table 60.3.2.6 shall be provided with a means of explosion control. A.60.3.2.6 (4) NFPA 68, Guide for Venting of Deflagrations, provides information and guidance on how to design and install deflagration (explosion) venting.

415.6.4 Dry cleaning plants. The construction and installation of dry cleaning plants shall be in accordance with the requirements of this Code, and NFPA 32. Dry cleaning solvents and systems shall be classified in accordance with the International Fire Code.

1201.1 Scope. Dry cleaning plants and their operations shall comply with the requirements of this chapter.

24.1.1 Drycleaning plants shall comply with NFPA 32, Standard for Drycleaning Plants, and this chapter.

415.7 Groups H-3 and H-4. Groups H-3 and H-4 shall be constructed in accordance with the applicable provisions of this Code and the International Fire Code.

3405.3.7.1 Construction, location and fire protection. Rooms or buildings classified in accordance with the International Building Code as Group H-2 or H-3 occupancies based on use, dispensing or mixing of flammable or combustible liquids shall be constructed in accordance the International Building Code.

60.2.4.1 Construction Requirements for Control Areas. Control areas shall be separated from each other by fire barriers in accordance with Table 60.2.4.1.1.

Page 16: BUILDING/FIRE CODE REFERENCES 2006 · PDF fileBUILDING/FIRE CODE REFERENCES 2006 EDITION This document provides a cross reference with the International Building Code and NFPA 1/Uniform

16

IBC FIRE CODE CROSS REFERENCES 2006 EDITION

IBC SECTION IFC SECTION NFPA 1/UFC SECTION

415.8.1 General. In addition to the requirements set forth elsewhere in this Code, Group H-5 shall comply with the provisions of Section 415.9 and the International Fire Code.

408.4 Group H-5 occupancies. Group H-5 occupancies shall comply with the requirements of Sections 408.4.1 through 408.4.4 and Sections 401 through 407.

60.3.1.5 Protection Level 5. Buildings, and portions thereof, used for fabrication of semiconductors or semiconductor research and development and containing quantities of hazardous materials exceeding the maximum allowable quantities of high hazard Level 5 contents permitted in control areas shall comply with applicable regulations for Protection Level 5, as set forth in the building code.

415.8.2.7 Transporting hazardous production materials to fabrication areas. HPM shall be transported to fabrication areas through enclosed piping or tubing systems that comply with Section 415.8.6.1, through service corridors complying with Section 415.8.4, or in corridors as permitted in the exception to Section 415.8.3. The handling or transporting of HPM within service corridors shall comply with the International Fire Code.

1803.9 Service corridors. Hazardous materials shall not be used in an open-system use condition in service corridors.

60.4.12.2 Emergency Alarm for Transportation of Hazardous Materials in Corridors or Exit Enclosures. When hazardous materials having a hazard ranking of 3 or 4 in accordance with NFPA 704 are transported through corridors or exit enclosures, there shall be an emergency telephone system, a local manual alarm station, or an approved alarm-initiating device at not more than 150 ft (46 m) intervals and at each exit throughout the transport route. The signal shall be relayed to an approved central, proprietary, or remote station service or constantly attended on-site location and shall also initiate a local audible alarm.

Page 17: BUILDING/FIRE CODE REFERENCES 2006 · PDF fileBUILDING/FIRE CODE REFERENCES 2006 EDITION This document provides a cross reference with the International Building Code and NFPA 1/Uniform

17

IBC FIRE CODE CROSS REFERENCES 2006 EDITION

IBC SECTION IFC SECTION NFPA 1/UFC SECTION

415.8.5.1 General. Storage of HPM in fabrication areas shall be within approved or listed storage cabinets or gas cabinets, or within a workstation. The storage of hazardous production materials in quantities greater than those listed in Tables 307.7(1) or 307.7(2) shall be in liquid storage rooms, HPM rooms or gas rooms as appropriate for the materials stored. The storage of other hazardous materials shall be in accordance with other applicable provisions of this Code and the International Fire Code.

1805.2 Fabrication areas. The use of hazardous materials in fabrication areas shall be in accordance with Sections 1805.2.1 through 1805.2.3.5.

60.3.1.5 Protection Level 5. Buildings, and portions thereof, used for fabrication of semiconductors or semiconductor research and development and containing quantities of hazardous materials exceeding the maximum allowable quantities of high hazard Level 5 contents permitted in control areas shall comply with applicable regulations for Protection Level 5, as set forth in the building Code

415.8.7.2 Gas-detection system operation. Monitoring for highly toxic and toxic gases shall also comply with the requirements for such material in the International Fire Code.

3704.2.2.10 Gas detection system. A gas detection system shall be provided to detect the presence of gas at or below the PEL or ceiling limit of the gas for which detection is provided. The system shall be capable of monitoring the discharge from the treatment system at or below one-half the IDLH limit.

Chapter 68 Highly Toxic and Toxic Solids and Liquids

NFPA 55:7.9.6 Gas Detection. Except as provided in 7.9.6.1, a continuous gas detection system in accordance with the requirements of 7.9.6.2 through 7.9.6.6 shall be provided for the indoor storage or use of toxic or highly toxic compressed gases.

415.8.9.3 Signals. 8. Exhaust ventilation flow alarm devices for pyrophoric liquids and Class 3 water-reactive liquids cabinet exhaust ventilation systems required in Section 1805.2.3.5 of the International Fire Code.

1805.2.3.5 Pyrophoric liquids and Class 3 water-reactive liquids.

71.1 General. The storage, use, and handling of pyrophoric solids and liquids shall comply with the requirements of Chapter 60. The storage, use, and handling of pyrophoric solids and liquids in amounts exceeding the maximum allowable quantity permitted in control areas as set forth in Chapter 60 shall also comply with the requirements of Chapter 71.

Page 18: BUILDING/FIRE CODE REFERENCES 2006 · PDF fileBUILDING/FIRE CODE REFERENCES 2006 EDITION This document provides a cross reference with the International Building Code and NFPA 1/Uniform

18

IBC FIRE CODE CROSS REFERENCES 2006 EDITION

IBC SECTION IFC SECTION NFPA 1/UFC SECTION

415.8.10.1 Required electrical systems. Emergency power shall be provided for electrically operated equipment and connected control circuits for the following systems: 10. Flow alarm switches for pyrophoric liquids and Class 3 water-reactive liquids cabinet exhaust ventilation systems required in Section 1805.2.3.5 of the International Fire Code.

1805.2.3.5 Pyrophoric liquids and Class 3 water-reactive liquids.

71.1 General. The storage, use, and handling of pyrophoric solids and liquids shall comply with the requirements of Chapter 60. The storage, use, and handling of pyrophoric solids and liquids in amounts exceeding the maximum allowable quantity permitted in control areas as set forth in Chapter 60 shall also comply with the requirements of Chapter 71.

416.1 General. The provisions of this section shall apply to the construction, installation and use of buildings and structures, or parts thereof, for the spraying of flammable paints, varnishes and lacquers or other flammable materials or mixtures or compounds used for painting, varnishing, staining or similar purposes. Such construction and equipment shall comply with the International Fire Code.

1501.1 Scope. This chapter shall apply to locations or areas where any of the following activities are conducted:

1. The application of flammable or combustible paint, varnish, lacquer, stain, fiberglass resins or other flammable or combustible liquid applied by means of spray apparatus in continuous or intermittent processes.

43.1.1* Operations involving the spray application of flammable and combustible materials shall comply with NFPA 33, Standard for Spray Application Using Flammable or Combustible Materials, and Section 43.1.

420.1 General. When required by the International Fire Code, hydrogen cutoff rooms shall be designed and constructed in accordance with this section.

2209.3.2.3 Indoors. Generation, compression, storage and dispensing equipment shall be located in indoor rooms or areas constructed in accordance with the requirements of the International Building Code, the International Fuel Gas Code and the International Mechanical Code and one of the following:

42.5.1.1.3 NFPA 52 shall apply to the design, installation, operation, and maintenance of compressed hydrogen (GH2), liquefied compressed hydrogen (LH2), and blends of hydrogen up to 20 percent with the balance natural gas (NG) vehicle fueling (dispensing) systems and engine fuel systems and facilities.

420.7 Explosion control. Explosion control shall be provided in accordance with Chapter 9 of the International Fire Code.

Section 911 Explosion Control 63.6 Gaseous Hydrogen Systems. Gaseous hydrogen systems shall comply with NFPA 55.

63.7 Liquefied Hydrogen Systems. Liquefied hydrogen systems shall comply with NFPA 55.

Page 19: BUILDING/FIRE CODE REFERENCES 2006 · PDF fileBUILDING/FIRE CODE REFERENCES 2006 EDITION This document provides a cross reference with the International Building Code and NFPA 1/Uniform

19

IBC FIRE CODE CROSS REFERENCES 2006 EDITION

IBC SECTION IFC SECTION NFPA 1/UFC SECTION

704.8.2 First story. In occupancies other than Group H, unlimited unprotected openings are permitted in the first story of exterior walls facing a street that have a fire separation distance of greater than 15 feet (4572 mm), or facing an unoccupied space, and shall have access from a street by a posted fire lane in accordance with the International Fire Code.

503.1 Where required. Fire apparatus access roads shall be provided and maintained in accordance with Sections 503.1.1 through 503.1.3

18.1.1.1 Fire Apparatus Access Roads.

901.2 Fire protection systems. Fire protection systems shall be installed, repaired, operated and maintained in accordance with this Code and the International Fire Code.

901.1 Scope. The provisions of this chapter shall specify where fire protection systems are required and shall apply to the design, installation, inspection, operation, testing and maintenance of all fire protection systems Code and the applicable referenced standards.

13.1.1 The AHJ shall have the authority to require that construction documents for all fire protection systems be submitted for review and approval and a permit be issued prior to the installation, rehabilitation, or modification. 13.1.7 All fire protection systems and devices shall be maintained in a reliable operating condition and shall be replaced or repaired where defective.

901.3 Modifications. No person shall remove or modify any fire protection system installed or maintained under the provisions of this Code or the International Fire Code without approval by the building official.

105.3 Conditions of a permit. A permit shall constitute permission to maintain, store or handle materials; or to conduct processes which produce conditions hazardous to life or property; or to install equipment utilized in connection with such activities; or to install or modify any fire protection system equipment or operations will be granted.

13.1.1 The AHJ shall have the authority to require that construction documents for all fire protection systems be submitted for review and approval and a permit be issued prior to the installation, rehabilitation, or modification.

Page 20: BUILDING/FIRE CODE REFERENCES 2006 · PDF fileBUILDING/FIRE CODE REFERENCES 2006 EDITION This document provides a cross reference with the International Building Code and NFPA 1/Uniform

20

IBC FIRE CODE CROSS REFERENCES 2006 EDITION

IBC SECTION IFC SECTION NFPA 1/UFC SECTION

901.5 Acceptance tests. Fire protection systems shall be tested in accordance with the requirements of this Code and the International Fire Code. When required, the tests shall be conducted in the presence of the building official. Tests required by this Code, the International Fire Code and the standards listed in this Code shall be conducted at the expense of the owner or the owner’s representative.

901.5 Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire Code official. The fire code official shall be notified before any required acceptance testing.

13.1.1 The AHJ shall have the authority to require that construction documents for all fire protection systems be submitted for review and approval and a permit be issued prior to the installation, rehabilitation, or modification. Further, the AHJ shall have the authority to require that full acceptance tests of the systems be performed in the authority’s presence prior to final system certification.

901.6.2 Fire alarm systems. Fire alarm systems required by the provisions of Section 907.2 of this Code and Section 907.2 of the International Fire Code shall be monitored by an approved supervising station in accordance with Section 907.14.

907.15 Monitoring. Where required by this chapter or by the International Building Code, an approved supervising station in accordance with NFPA 72 shall monitor fire alarm systems.

13.7.1.4.10.2 Where fire department notification is required by another section of this Code, the fire alarm system shall be arranged to transmit the alarm automatically via any of the following means acceptable to the AHJ and shall be in accordance with NFPA 72.

903.2.6.1 High-piled storage. An automatic sprinkler system shall be provided in accordance with the International Fire Code in all buildings of Group M where storage of merchandise is in high-piled or rack storage arrays.

903.2.6.1 High-piled storage. An automatic sprinkler system shall be provided as required in Chapter 23 in all buildings of Group M where storage of merchandise is in high-piled or rack storage arrays.

13.3.2.25.1 High-Piled Storage. An automatic sprinkler system shall be installed throughout all occupancies containing areas greater than 2500 ft2 (232 m2) for the high-piled storage of combustibles.

903.2.11 During construction. Automatic sprinkler systems required during construction, alteration and demolition operations shall be provided in accordance with the International Fire Code.

903.2.11 During construction. Automatic sprinkler systems required during construction, alteration and demolition operations shall be provided in accordance with Section 1413.

16.3.1 Fire Safety Program. An overall construction or demolition fire safety program shall be developed. Essential items to be emphasized include the following: (3) Installation of new fire protection systems as construction progresses

(4) Preservation of existing systems during demolition

Page 21: BUILDING/FIRE CODE REFERENCES 2006 · PDF fileBUILDING/FIRE CODE REFERENCES 2006 EDITION This document provides a cross reference with the International Building Code and NFPA 1/Uniform

21

IBC FIRE CODE CROSS REFERENCES 2006 EDITION

IBC SECTION IFC SECTION NFPA 1/UFC SECTION

Table 903.2.13 Additional Required Suppression Systems

903.2.13 Other required suppression systems. In addition to the requirements of Section 903.2, the provisions indicated in Table 903.2.13 also require the installation of a suppression system for certain buildings and areas.

13.3.1.1 Automatic sprinklers shall be installed and maintained in full operating condition in the occupancies specified in this Code or in the Codes or standards referenced in Chapter 2.

903.5 Testing and maintenance. Sprinkler systems shall be tested and maintained in accordance with the International Fire Code.

901.4.1 Required fire protection systems. Fire protection systems required by this Code or the International Building Code shall be installed, repaired, operated, tested and maintained in accordance with this Code.

13.3.1.1 Automatic sprinklers shall be installed and maintained in full operating condition in the occupancies specified in this Code or in the Codes or standards referenced in Chapter 2.

904.2.1 Hood system suppression. Each required commercial kitchen exhaust hood and duct system required by the International Fire Code or the International Mechanical Code.

904.2.1 Hood system suppression. Each required commercial kitchen exhaust hood and duct system required by Section 610 to have a Type I hood shall be protected with an approved automatic fire-extinguishing system installed in accordance with this Code.

50.4.3.1 Fire-extinguishing equipment for the protection of grease removal devices, hood exhaust plenums, and exhaust duct systems shall be provided.

905.1 General. Standpipe systems shall be provided in new buildings and structures in accordance with this section. Fire hose threads used in connection with standpipe systems shall be approved and shall be compatible with fire department hose threads. The location of fire department hose connections shall be approved. In buildings used for high-piled combustible storage, fire protection shall be in accordance with the International Fire Code.

2306.8 Fire department hose connections. Where exit passageways are required by the International Building Code for egress, a Class I standpipe system shall be provided in accordance with Section 905.

(NFPA 1/UFC does not require standpipes in exit passageways, it requires the following) 60.4.12.2 Emergency Alarm for Transportation of Hazardous Materials in Corridors or Exit Enclosures. When hazardous materials having a hazard ranking of 3 or 4 in accordance with NFPA 704 are transported through corridors or exit enclosures, there shall be an emergency telephone system, a local manual alarm station, or an approved alarm-initiating device at not more than 150 ft (46 m) intervals and at each exit throughout the transport route. The signal shall be relayed to an approved central, proprietary, or remote station service or constantly attended on-site location and shall also initiate a local audible alarm.

Page 22: BUILDING/FIRE CODE REFERENCES 2006 · PDF fileBUILDING/FIRE CODE REFERENCES 2006 EDITION This document provides a cross reference with the International Building Code and NFPA 1/Uniform

22

IBC FIRE CODE CROSS REFERENCES 2006 EDITION

IBC SECTION IFC SECTION NFPA 1/UFC SECTION

905.3.6 Helistops and heliports. Buildings with a helistop or heliport that are equipped with a standpipe shall extend the standpipe to the roof level on which the helistop or heliport is located in accordance with Section 1107.5 of the International Fire Code.

1107.5 Standpipe systems. Where a building with a rooftop helistop or heliport is equipped with a standpipe system, the system shall be extended to the roof level on which the helistop or heliport is located.

21.3.6.8 Standpipes. If a building with a rooftop heliport is supplied with a standpipe system, a Class II standpipe shall be extended to the roof level on which the rooftop heliport is located. Such standpipe systems shall be installed in accordance with Section 13.2.

906.1 General. Portable fire extinguishers shall be provided in occupancies and locations as required by the International Fire Code.

906.1 Where required. Portable fire extinguishers shall be installed in the following locations. 906.2 General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.

13.6.1.2 Where Required. Fire extinguishers shall be provided where required by this Code as specified in Table 13.6.1.2 and the referenced Codes and standards listed in Chapter 2.

907.2.5 Group H. An automatic smoke detection system shall be installed for highly toxic gases, organic peroxides and oxidizers in accordance with Chapters 37, 39 and 40, of the International Fire Code.

Chapters 37, 39 and 40 13.7.1.4.8.1 Where required by other sections of this Code, actuation of the complete fire alarm system shall occur by any or all of the following means of initiation, but shall not be limited to such means:

907.2.12.2 Emergency voice/alarm communication system. The operation…in accordance with the building’s fire safety and evacuation plans required by Section 404 of the International Fire Code.

404.1 General. Fire safety and evacuation plans shall comply with the requirements of this section.

10.9.1 Where Required. Emergency plans shall be provided for…facilities storing or handling materials covered by Chapter 20, or where required by the AHJ.

907.2.14 High-piled combustible storage areas. An automatic fire detection system shall be installed throughout high-piled combustible storage areas where required by the International Fire Code.

Table 2306.2 General Fire Protection and Life Safety Requirements Note: i. Not required when an automatic fire-extinguishing system is designed and installed to protect the high-piled storage area in accordance with Sections 2307 and 2308.

20.15.7 High-Piled Storage. 20.15.7.1 Buildings containing high-piled storage shall comply with NFPA 13, Chapter 34, and 20.15.7.

Page 23: BUILDING/FIRE CODE REFERENCES 2006 · PDF fileBUILDING/FIRE CODE REFERENCES 2006 EDITION This document provides a cross reference with the International Building Code and NFPA 1/Uniform

23

IBC FIRE CODE CROSS REFERENCES 2006 EDITION

IBC SECTION IFC SECTION NFPA 1/UFC SECTION

907.2.16 Aerosol storage uses. Aerosol storage rooms and general-purpose warehouses containing aerosols shall be provided with an approved manual fire alarm system where required by the International Fire Code.

907.2.16 Aerosol storage uses. Aerosol storage rooms and general-purpose warehouses containing aerosols shall be provided with an approved manual fire alarm system where required by this Code.

61.1.1.1 The manufacture, storage, use, handling, and display of aerosol products shall comply with the requirements of Chapter 61; NFPA 30B, Code for the Manufacture and Storage of Aerosol Products; and Section 60.1 and Section 60.2 of this Code. NFPA 30B 4.7 Fire Alarms. Fire alarm systems shall be installed, tested, and maintained in accordance with applicable requirements of NFPA 72, National Fire Alarm Code.

907.14 Monitoring. Fire alarm systems required by this chapter or the International Fire Code shall be monitored by an approved supervising station in accordance with NFPA 72.

907.15 Monitoring. Fire alarm systems required by this chapter or by the International Building Code shall be monitored by an approved supervising station in accordance with NFPA72.

13.7.1.1 Where building fire alarm systems or automatic fire detectors are required by other sections of this Code, they shall be provided and installed in accordance with NFPA 70, NFPA 72, and Section 13.7.

Page 24: BUILDING/FIRE CODE REFERENCES 2006 · PDF fileBUILDING/FIRE CODE REFERENCES 2006 EDITION This document provides a cross reference with the International Building Code and NFPA 1/Uniform

24

IBC FIRE CODE CROSS REFERENCES 2006 EDITION

IBC SECTION IFC SECTION NFPA 1/UFC SECTION

907.19 Inspection, testing and maintenance. The maintenance and testing schedules and procedures for fire alarm and fire detection systems shall be in accordance with the International Fire Code.

901.6.1 Standards. Fire protection systems shall be inspected, tested and maintained in accordance with the referenced standards listed in Table 901.6.1.

SYSTEM STANDARD

Portable fire extinguishers NFPA 10

Carbon dioxide fire-extinguishing system NFPA 12

Halon 1301 fire-extinguishing systems NFPA 12A

Dry-chemical extinguishing systems NFPA 17

Wet-chemical extinguishing systems NFPA 17A

Water-based fire protection systems NFPA 25

Fire alarm systems NFPA 72

Water-mist systems NFPA 750

Clean-agent extinguishing systems NFPA 2001

13.7.3.2.7 Testing Frequency. Testing shall be performed in accordance with the schedules in Table 13.7.3.2.7, except as modified in other paragraphs of 13.7.3.2, or more often if required by the AHJ.

909.20 Smokeproof enclosures. Where required by Section 1019.1.8, a smokeproof enclosure shall be constructed in accordance with this section. Where access to the roof is required by the International Fire Code.

1009.12 Stairway to roof. In buildings four or more stories in height above grade, one stairway shall extend to the roof surface, unless the roof has a slope steeper than four units vertical in 12 units horizontal (33-percent slope).

14.5.2.8 If a stair enclosure allows access to the roof of the building, the door to the roof either shall be kept locked or shall allow re-entry from the roof.

Page 25: BUILDING/FIRE CODE REFERENCES 2006 · PDF fileBUILDING/FIRE CODE REFERENCES 2006 EDITION This document provides a cross reference with the International Building Code and NFPA 1/Uniform

25

IBC FIRE CODE CROSS REFERENCES 2006 EDITION

IBC SECTION IFC SECTION NFPA 1/UFC SECTION

910.2.2 High-piled combustible storage. Buildings and portions thereof containing high-piled combustible stock or rack storage in any occupancy group in accordance with Section 413 and the International Fire Code.

2301.1 Scope. High-piled combustible storage shall be in accordance with this chapter. In addition to the requirements of this chapter, the following material-specific requirements shall apply: 1. Aerosols shall be in accordance with Chapter 28. 2. Flammable and combustible liquids shall be in accordance with Chapter 34. 3. Hazardous materials shall be in accordance with Chapter 27. 4. Storage of combustible paper records shall be in accordance with NFPA 13 and NFPA 230. 5. Storage of combustible fibers shall be in accordance with Chapter 29. 6. Storage of miscellaneous combustible material shall be in accordance with Chapter 3.

20.15.7 High-Piled Storage.

20.15.7.1 Buildings containing high-piled storage shall comply with NFPA 13, Chapter 34, and 20.15.7.

Table 910.3 Requirements for Draft Curtains and Smoke and Heat Vents a.

Requirements for rack storage heights in excess of those indicated shall be in accordance with Chapter 23 of the International Fire Code For solid-piled storage

2301.1 Scope. High-piled combustible storage shall be in accordance with this chapter. In addition to the requirements of this chapter, the following material-specific requirements shall apply: 1. Aerosols shall be in accordance with Chapter 28. 2. Flammable and combustible liquids shall be in accordance with Chapter 34. 3. Hazardous materials shall be in accordance with Chapter 27. 4. Storage of combustible paper records shall be in accordance with NFPA 13 and NFPA 230. 5. Storage of combustible fibers shall be in accordance with Chapter 29. 6. Storage of miscellaneous combustible material shall be in accordance with Chapter 3.

20.15.7 High-Piled Storage.

20.15.7.1 Buildings containing high-piled storage shall comply with NFPA 13, Chapter 34, and 20.15.7

1001.3 Maintenance. Means of egress shall be maintained in accordance with the International Fire Code.

1027.1 General. The means of egress in existing buildings or portions thereof shall be maintained in accordance with this section.

14.1 Application. Means of egress in new and existing buildings shall comply with this Code and the referenced edition of NFPA 101, Life Safety Code.

Page 26: BUILDING/FIRE CODE REFERENCES 2006 · PDF fileBUILDING/FIRE CODE REFERENCES 2006 EDITION This document provides a cross reference with the International Building Code and NFPA 1/Uniform

26

IBC FIRE CODE CROSS REFERENCES 2006 EDITION

IBC SECTION IFC SECTION NFPA 1/UFC SECTION

1203.4.2 Contaminants exhausted. Contaminant sources in naturally ventilated spaces shall be removed in accordance with the International Mechanical Code and the International Fire Code.

(International Mechanical Code, no requirements in the IFC.)

(Uniform Mechanical Code, no requirements in NFPA 1/UFC)

1203.5 Other ventilation and exhaust systems. Ventilation and exhaust systems for occupancies and operations involving flammable or combustible hazards or other contaminant sources as covered in the International Mechanical Code or the International Fire Code.

2705.1.9 Ventilation. Indoor dispensing and use areas shall be provided with exhaust ventilation in accordance with Section 2704.3.

42.2.6.1.5.7 A mechanical exhaust system that serves only the fuel dispensing area shall be provided.

2702.1 Installation. Emergency and standby power systems required by this Code or the International Fire Code shall be installed in accordance with this Code, NFPA 110 and 111.

604.1 Installation. Emergency and standby power systems required by this Code or the International Building Code shall be installed in accordance with this Code, NFPA 110 and NFPA 111.

11.7.2 Emergency and Standby Power Systems. General. Stationary generators for emergency use or standby power required by this Code, the building code, or other codes and standards shall be installed in accordance with NFPA 110, Standard for Emergency and Standby Power Systems.

2702.2.9 Membrane structures. Emergency power shall be provided for exit signs in temporary tents and membrane structures in accordance with the International Fire Code.

Section 2403 Temporary Tents, Canopies and Membrane Structures

Chapter 25 Grandstands and Bleachers, Folding and Telescopic Seating, Tents, and Membrane Structures

2702.2.11 Highly toxic and toxic materials. Emergency power shall be provided for occupancies with highly toxic or toxic materials in accordance with the International Fire Code.

2705.1.5 Standby or emergency power. 60.4.3 Standby and Emergency Power.

Page 27: BUILDING/FIRE CODE REFERENCES 2006 · PDF fileBUILDING/FIRE CODE REFERENCES 2006 EDITION This document provides a cross reference with the International Building Code and NFPA 1/Uniform

27

IBC FIRE CODE CROSS REFERENCES 2006 EDITION

IBC SECTION IFC SECTION NFPA 1/UFC SECTION

2702.2.12 Organic peroxides. Standby power shall be provided for occupancies with silane gas in accordance with the International Fire Code.

2705.1.5 Standby or emergency power 60.4.3 Standby and Emergency Power

2702.2.13 Pyrophoric materials. Emergency power shall be provided for occupancies with silane gas in accordance with the International Fire Code.

2705.1.5 Standby or emergency power 60.4.3 Standby and Emergency Power

2702.3 Maintenance. Emergency and standby power systems shall be maintained and tested in accordance with the International Fire Code.

2705.1.5 Standby or emergency power 60.4.3 Standby and Emergency Power

3102.1 General. Those erected for a shorter period of time shall comply with the International Fire Code.

Section 2403 Temporary Tents, Canopies and Membrane Structures

Chapter 25 Grandstands and Bleachers, Folding and Telescopic Seating, Tents, and Membrane Structures

3103.1 General. Tents and other membrane structures erected for a period of less than 180 days shall comply with the International Fire Code.

Section 2403 Temporary Tents, Canopies and Membrane Structures

Chapter 25 Grandstands and Bleachers, Folding and Telescopic Seating, Tents, and Membrane Structures

3309.2 Fire hazards. The provisions of this Code and the International Fire Code shall be strictly observed to safeguard against all fire hazards attendant upon construction operations.

Chapter 14 Fire Safety during Construction and Demolition

Chapter 16 Safeguards During Building Construction, Alteration, and Demolition Operations

Page 28: BUILDING/FIRE CODE REFERENCES 2006 · PDF fileBUILDING/FIRE CODE REFERENCES 2006 EDITION This document provides a cross reference with the International Building Code and NFPA 1/Uniform

28

IBC FIRE CODE CROSS REFERENCES 2006 EDITION

IBC SECTION IFC SECTION NFPA 1/UFC SECTION

3401.3 Compliance with other Codes. Alterations, repairs, additions and changes of occupancy to existing structures shall comply with the provisions for alterations, repairs, additions and changes of occupancy in the International Fire Code, Property International Mechanical Code, International Residential Code and ICC Electrical Code.

102.1 Construction and design provisions. The construction and design provisions of this code shall apply to: 1. Structures, facilities and conditions arising after the adoption of this code.

2. Existing structures, facilities and conditions not legally in existence at the time of adoption of this code.

3. Existing structures, facilities and conditions when identified in specific sections of this code.

1.3.6.3 Repairs, renovations, alterations, reconstruction, change of occupancy, and additions to buildings shall conform with NFPA 101 and the building code.

3410.3.2 Compliance with other Codes. Buildings that are evaluated in accordance with this section shall comply with the International Fire Code and International Property Maintenance Code.

102.1 Construction and design provisions. The construction and design provisions of this code shall apply to: 1. Structures, facilities and conditions arising after the adoption of this code.

2. Existing structures, facilities and conditions not legally in existence at the time of adoption of this code.

3. Existing structures, facilities and conditions when identified in specific sections of this code.

1.1.1 The scope includes, but is not limited to, the following: (5) Existing occupancies and conditions, the design and construction of new buildings, remodeling of existing buildings, and additions to existing buildings requirements of the occupancies involved.

Page 29: BUILDING/FIRE CODE REFERENCES 2006 · PDF fileBUILDING/FIRE CODE REFERENCES 2006 EDITION This document provides a cross reference with the International Building Code and NFPA 1/Uniform

29

IBC FIRE CODE CROSS REFERENCES 2006 EDITION

IBC SECTION IFC SECTION NFPA 1/UFC SECTION

3410.6.8.1 Categories. The categories for automatic fire detection are: 1. Category a — None. 2. Category b—Existing smoke detectors in HVAC systems and maintained in accordance with the International Fire Code.

901.6.1 Standards. Fire protection systems shall be inspected, tested and maintained in accordance with the referenced standards listed in Table 901.6.1.

SYSTEM STANDARD

Portable fire extinguishers NFPA 10

Carbon dioxide fire-extinguishing system NFPA 12

Halon 1301 fire-extinguishing systems NFPA 12A

Dry-chemical extinguishing systems NFPA 17

Wet-chemical extinguishing systems NFPA 17A

Water-based fire protection systems NFPA 25

Fire alarm systems NFPA 72

Water-mist systems NFPA 750

Clean-agent extinguishing systems NFPA 2001

13.1.7 All fire protection systems and devices shall be maintained in a reliable operating condition and shall be replaced or repaired where defective.

3410.6.14 Elevator control. Evaluate the passenger elevator equipment and controls that are available to the fire department to reach all occupied floors. Elevator recall controls shall be provided in accordance with the International Fire Code.

Elevator Recall and Maintenance 607.1 Required. Existing elevators with a travel distance of 25 level of a building and intended to serve the needs of emergency personnel for fire-fighting or rescue purposes shall be provided with emergency operation in accordance with ASME A17.3. New elevators shall be provided with Phase I emergency recall operation and Phase II emergency in-car operation in accordance with ASME A17.1.

11.3.1 Fire Fighters’ Emergency Operations. 11.3.1.1 All new elevators shall conform to the fire fighters’ emergency operations of ASME/ANSI A17.1, Safety Code for Elevators and Escalators. 11.3.1.2 All existing elevators having a travel distance of 25 feet or more above or below the level that best serves the needs of emergency personnel for fire fighting or rescue purposes shall conform to the fire fighters’ emergency operations requirements of ASME/ANSI A17.3, Safety Code for Existing acceptable Elevators and Escalators.

Page 30: BUILDING/FIRE CODE REFERENCES 2006 · PDF fileBUILDING/FIRE CODE REFERENCES 2006 EDITION This document provides a cross reference with the International Building Code and NFPA 1/Uniform

30

IBC FIRE CODE CROSS REFERENCES 2006 EDITION

IBC SECTION IFC SECTION NFPA 1/UFC SECTION

3410.6.14.1 Categories. The categories for elevator controls are: 1. Category a — No elevator. 2. Category b—Any elevator without Phase I and II recall.

3. Category c—All elevators with Phase I and II recall as required by the International Fire Code.

Elevator Recall and Maintenance 607.1 Required. Existing elevators with a travel distance of 25 level of a building and intended to serve the needs of emergency personnel for fire-fighting or rescue purposes shall be provided with emergency operation in accordance with ASME A17.3. New elevators shall be provided with Phase I emergency recall operation and Phase II emergency in-car operation in accordance with ASME A17.1.

11.3.1 Fire Fighters’ Emergency Operations. 11.3.1.1 All new elevators shall conform to the fire fighters’ emergency operations of ASME/ANSI A17.1, Safety Code for Elevators and Escalators.

11.3.1.2 All existing elevators having a travel distance of 25 feet or more above or below the level that best serves the needs of emergency personnel for fire fighting or rescue purposes shall conform to the fire fighters’ emergency operations requirements of ASME/ANSI A17.3, Safety Code for Existing acceptable Elevators and Escalators.