building systems wiring

Upload: sasan49

Post on 03-Jun-2018

217 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/12/2019 Building Systems Wiring

    1/37

    Chapter -4- Building Wiring Calculations

    40

    Building Wiring Calculations

    4-1. Introduction:

    Inthis chapter it is required to plan the distribution system of the residentialarea. The planning of this area starts from inside the individual flats of thebuildings.

    The various types of loads in the house like lighting, normal sockets (N.S),power sockets (P.S) and load break switches (L.B.S) are estimated accordingto the standard forms. The feeding circuits are defined and the main wiringc.s.a. are calculated.

    The mains wiring is generally built using insulated copper cables. Thechoice of conductor material is a compromise among electrical properties,mechanical properties, and price. From the start, copper has been the

    material of choice for household branch circuits.

    Aluminum is softer than copper and weaker, and a poorer electricalconductor, so is not widely used in small sizes for home wiring. Aluminumcable material is sometimes used (for economical reasons) for thick mainsfeeder cables coming from electrical utility to the mains distribution panel.

    The ratings of the sub-circuits' miniature circuit breakers (M.C.B) and themain circuit breaker of the flat or the villa as well as energy meter areselected.

    Any house that has been properly wired will have a circuit breaker panel

    used to shut circuits off in case they draw too much current. It is the currentcapacity of circuit breaker (in amperes) that determines how much current acircuit can supply. In case of an overload or a short-circuit on that circuit, thebreaker trips and automatically shuts off power to that circuit. Ground faultcircuit breakers offer protection against more than just overloads.

    After the load of the flat is being calculated, the diversified estimation of thetotal load of the building is made. The buildings are fed from distribution boxesvia cables of suitable sizes, forming a part of the low voltage distributionnetwork. The distribution boxes are fed from 11 KV/380 V distributiontransformers, preferably in loops, to secure the continuity of supply to thedistribution boxes and hence to the buildings.

    The distribution transformers are located in the appropriate sites andconnected in loops to the 11KV Distribution points and the 66/11KVsubstation.

  • 8/12/2019 Building Systems Wiring

    2/37

    Chapter -4- Building Wiring Calculations

    41

    Detailed calculations and planning of the 380V low voltage distributionnetwork, the 11KV medium voltage network as well as details of the 66/11KVsubstation feeding the area, are presented in the following chapters. Beforethis, the principles of lighting and wring are summarized in the followingsections.

    4-2. Lighting background:

    (4-2-1 )Importance of light:

    Light is the prime factor in the human life as all activities of human beingsultimately depend upon the light. Where there is no natural light, use ofartificial is made. Lighting increases production and reduce accidents.

    (4-2-2) Basic Definitions:

    Candela

    International unit (SI) of luminous intensity; term evolved from considering astandard candle, similar to a plumber's candle, as the basis of evaluating theintensity of other light describe the relative intensity of a source .

    Candlepower Distribution CurveA graphic presentation of the distribution of light intensity of a lamp orluminaire.

    Illuminance (E)The quantity of light (measured in foot-candles, Lux, etc) at a point on asurface.

    Inverse Square LawFormula stating that illumination at a point on a surface varies directly with theintensity of a point source, and inversely as the square of the distancebetween the source and the point; it illustrates how the same quantity of lightflux is distributed over a greater area as the distance from the source to thesurface is increased.

    Light Loss FactorThe product of all considered factors that contribute to a lighting system'sdepreciated light output over a period of time, including dirt and lamp lumendepreciation.

    LumenThe international unit of luminous flux or quantity of light.

    LuminaireA complete lighting unit consisting of a lamp (or lamps) together with the partsdesigned to distribute the light, position and protect the lamps, and connectthem to the power supply. This is sometimes referred to as a "fixture".

  • 8/12/2019 Building Systems Wiring

    3/37

    Chapter -4- Building Wiring Calculations

    42

    Lamp efficiencyIt is the amount of output lumen per watt.

    Lux (lumen/m2)SI (international system) unit of illumination. One lumen uniformly distributed

    over an area of one square meter.

    Mounting Height

    Distance from the bottom of the fixture to either the floor or workplane, depending on usage.

    Spacing to Mounting Height RatioRatio of fixture spacing (distance apart) to mounting height above the workplane. Sometimes it is called spacing criterion. A normal range is 11.5

    (4-2-3) Requirements of a good lighting scheme:

    A good lighting scheme should fulfill the following:1. Provide adequate illumination.2. Provide uniform illumination allover the working plan.3. Provide light of suitable color.4. Avoid glare and hard shadows.

    (4-2-4): Factors affecting the illumination and wattage of a certainlamp:

    1-Utilization factor (U.F): (0.2 0.6)It is the ratio of the lumen actually received to the total Lumens emitted by

    the source, it depends on:1- Room dimensions.2- Color of the walls.3- Type of lighting scheme.

    2- Maintenance factor (M.F):It is the ratio between illumination under normal working conditions to the

    illumination when every thing is clean. It depends on the rate of cleaning.

    M.F. = 0.8 for houses.= 0.3 for streets.= 0.60.7 for schools and shopping centers.

    3- Waste factor:The ratio between the resultant illumination due to more than one luminaireto the summation of their illumination when they work individually. Wastefactor is less than unity due to the loss when a place is illuminated by morethan one source due to overlapping.

    4- Reflection factor:Due to the fact that light reflected by an angle of incidence when impinged

    on a surface.

  • 8/12/2019 Building Systems Wiring

    4/37

    Chapter -4- Building Wiring Calculations

    43

    5- Room index (k):

    It is a factor that depends on the dimension of the room. It equals the ratiobetween the product of length (L) and breadth (W) of the room to the productof the mounting height (H) and the summation of the length and breadth ofthat room.

    K=)(*

    *

    WLH

    WL

    +

    Generally K varies from 0.6 to 5.0

    (4-2-5): Designing the lighting system:

    To produce a new lighting system in a construction, it must be designed.The designer must determine the desired light levels for tasks that are to beperformed in a given space, then determine the light output that will berequired to meet those objectives consistently, taking into account all the

    factors that degrade both light output and light levels over time. Equipmentmust then be chosen and placed in a layout to produce the desired lightdistribution.

    A- Types of lamps:The lighting design process in its most basic form entails identifying a task

    and then providing a light source that will provide proper quantity and qualityof light for the task. The fixture protects the light source, connects it to thepower source and distributes its light.

    The light source is the actual light-producing component of the lightingsystem. It may operate simply as a lamp (incandescent/halogen) or as a lamp

    powered by a ballast (fluorescent and high-intensity discharge [HID]).

    I-Incandescent Lamps:Incandescent light sources are the cheapest light sources..

    Do not require a ballast

    It is based on the fact that current is passed through a filament, whichheats until it glows

    Less efficacious light source

    Shorter service life than other light sources in most cases

    Filament is sensitive to vibrations

    Bulb can get very hot during operation Must be properly shielded because incandescent lamps can produce

    direct glare as a point source

    Require proper line voltage as line voltage variations can severelyaffect light output and service life

    An example of incandescent lamps is given in figure 4.1Efficiency of incandescent is 14 lumen/watt.

  • 8/12/2019 Building Systems Wiring

    5/37

    Chapter -4- Building Wiring Calculations

    44

    Fig. 4.1 Incandescent lamps

    ii-Fluorescent Lamps:These lamps rely on the gaseous discharge method.

    Require a ballast

    Low surface brightness compared to point sources

    More efficacious compared to incandescent

    Ambient temperatures and convection currents can affect light outputand life

    Options for starting methods and lamp current loadings

    Requires compatibility with ballast Low temperatures can affect starting unless"cold weather" ballast is

    specified.

    An example of fluorescent lamps is given in figure 4.2Efficiency of fluorescent lamps is 46 lumen/watt

    Fig. 4.2 Different types of Fluorescent lamps

  • 8/12/2019 Building Systems Wiring

    6/37

    Chapter -4- Building Wiring Calculations

    45

    iii- Compact Fluorescent Lamps (CFL): It is a new and advanced lighting technology More efficient than incandescent lamps CFL use 70 - 75% less energy than their incandescent equivalents. When

    replacing a 100 watt incandescent lamp a 28 watt CFL is used. CFL last approximately 10,000 hours, which is 10 to 13 times the life of an

    incandescent lamp (expected life approximately 750 hours).

    Compact fluorescents are most cost-effective when used at least 2-3hours per day.

    Although CFL may appear different than the common incandescent, theyfit most standard fixtures found in homes today. The screw-in base is thesame on both lamps.

    The typical incandescent lamp wastes 90% of the energy it uses,producing heat rather than light.

    CFL will provide the same amount of light (or lumens) at a fraction of theelectricity used.

    An example of CFL lamps is given in figure 4.3

    Fig. 4.3Types of CFL lamps

    B- Lighting Schemes:

    i- Direct LightingIn this type of lighting the light from the source falls directly on the object or

    the surface to be illuminated.

    ii- Semi-direct Lighting

    Only 60-90 % of the light reaches the working plan directly while the rest isreflected to illuminate the ceiling and walls.

    iii- Indirect Lighting:In this form of lighting, light doesn't reach the surface directly from the

    source but indirectly as the ceiling reflects the light. 90% of the light is directedupwards and only 10% reaches the working plane.

  • 8/12/2019 Building Systems Wiring

    7/37

    Chapter -4- Building Wiring Calculations

    46

    iv-Semi-Indirect LightingLike the pervious type except that 75% of the light is directed upwards and

    25% of it reaches the working plane.

    C- Requirements needed to specify right choice ofperfect luminaire:

    First, the engineer must fully understand the demands of the application andconditions in the space that will affect the operation of the lighting system:

    Tasks to be performed in the space

    Desired light levels based on the tasks performed in the space

    Room size and dimensions

    Layout of furniture and obstructions such as partitions

    Special concerns such as safety and security

    Room and object surface colors and reflectances

    Hours of operation

    Cleanliness of the area during operation availability of daylight

    (4-2-6) Lighting loads calculations:

    Installed wattage =efficiencyFMFU

    areaillumenace

    *.*.

    *

    Common figures of M.F and U.F are 0.8 and 0.4 respectivelyApproximate equation to calculate the required wattage for certain area andillumination are given by:

    For incandescent lamp: Required installed wattage =0.2 x lux x area. Watt.

    Rating: 25 , 40 , 50 , 60 , 80 , 100 ,120,200 Watt

    Power factor = 1

    For fluorescent lamp:

    Required installed wattage = 0.068 x lux x area. Watt.

    Rating: 20 , 40 Watt

    Power factor = 0.6

    N.B The recommended lux in every place is given in table 1 in the appendix ofthis chapter.

    The total light load on a line is given by:

    0.66(light loads on this line)

  • 8/12/2019 Building Systems Wiring

    8/37

    Chapter -4- Building Wiring Calculations

    47

    According to the standards, a minimum of two lighting lines are to be foundin the flat. The Cu wire used for wiring of lighting circuits must be of a c.s.a notless than 2 mm2. We will use the 2 mm2for flats and the 3 mm2for villas.

    4-3. Socket Loads:

    4.3.1 Normal sockets (N.S):

    They have different ratings, which can be used such as 3 Amp., 5A,10A theratings of 3A,5A, can be used for bedrooms, entrance, balcony, whichrequires low electrical sets as T.V, radio and small electric fans...etc. Ingeneral we are going to use only the 5A sockets in all the rooms since this ismore practical.

    4.3.2 Power sockets (P.S):

    Sometimes we need some sockets to be used for special purposes like: full

    automatic washing cloth machines, air conditions, water heaters, dishwashers, electric ovens and toasters. Such sockets are called power socketsand they require higher current rating and taking into consideration thestarting period which increases the delivered current to a value higher thannormal operation.

    To estimate the socket load for certain domestic units the following are to beconsidered:

    1- Generally there are 2-5 sockets in the room.2- Generally there are 5-8 normal sockets on a line.3- Referring to the IEC standard specification, the ratings of sockets are:

    *M.C.B. rating for normal socket = 10 A*M.C.B. rating for power sockets = 16 A. or 26 A.

    4- Calculate the normal socket loads on a line is according to theformula:

    Socket load on a line = 100% of largest normal socket rating on theline + (20% to 40%) of ratings of other normal sockets.

    5- Each power socket has its own line.6- Total socket load is given by the formula:

    Total socket load = 100% of largest M.C.B. Rating of sockets + (20%to 40%) of Rating of other M.C.B.

    7- To make calculations more exact, we should expect the loads to be

    used and their power like: Radio cassette : 40w, 0.182 A

    T.V set: 65 w, 0.3 A

    Video: 30w, 0.137 A

    Vacuum cleaner: 800w, a p.f of 0.85 , 4.7 A

    fans :200w, a p.f of 0.85, 1.069 A

    Shaving Machine: 150w, 0.7 A

    Hair dryer: 600w, a p.f of 0.85, 3.2 A

    Small fridge to be placed in the bedroom: 80w, a p.f of 0.85, 0.43 A

  • 8/12/2019 Building Systems Wiring

    9/37

    Chapter -4- Building Wiring Calculations

    48

    Fridge :160w, p.f of 0.85, 0.86 A

    Kitchen machine :600w, p.f of 0.85, 3.2 A

    Heater:1000w, 4.6 A

    Normal washing machines: 400w, p.f of 0.85, 2.14 A.

    Iron: 1000w, 4.64 A.

    Sound system: 800w, 3.64 A

    4-4. Calculations of the riser :

    The riser is cable, which passes upward in each building for transmitting theelectric power from the coffree of the building to each unit of this building, inother words, it starts from the fuse at the bottom of the house to the highestflat.

    It is a three phase cable made usually of copper and has a number ofoutputs equals to the number of floors, the output of riser is connected to thefuses which feeds this floor.

    Riser may be one cable or double cable depending on the height of thehouse, the number of flats and on the load of each flat.

    When choosing the riser we follow the next steps:

    1- Calculating the KVA of the flat before diversification and use todetermine the suitable diversification curve.

    2- We have two methods to get the diversified KVA of the flat:a- Using the total number of flats in the building to get the

    diversified KVA of the flat. Multiply this diversified KVA by thenumber of flats in the building to get the total KVA of the

    building. Dividing this KVA by 3 380 we get the current that

    flows in the riser.b- Using the total number of flats on each phase to get the

    diversified KVA of the flat. Multiply this diversified KVA by thenumber of flats on the phase to get the total KVA per phase.Dividing this KVA by 220 we get the current that flows in theriser.

    3- Assuming that the riser must never be loaded by more than 70% of itscurrent ampacity, we can get the current ampacity of the riser bydividing the current obtained in the last step by 0.7

    4- By knowing the value of the current ampacity and using the tables ofcables attached in the appendix we can get the c.s.a of the riser andalso the rating of the fuse used for protection. In general 3-ph risersthat are used are of the following sizes: 10 mm2, 16mm2, 25mm2,50mm2and 70mm2.

    5- Other services loads like water pumps, elevators (for buildings morethan 6 floors) and stairs lighting are to be considered in ourcalculations.

    6- A fuse is added for protection.

  • 8/12/2019 Building Systems Wiring

    10/37

    Chapter -4- Building Wiring Calculations

    49

    4-5. General points to be considered in the design:

    1- In distribution of loads among light circuits or socket circuits we shouldconnect the rooms that are next to each other on the same subcircuit toavoid crossing between connections. Also it is recommended that thecircuits of the same type are equally loaded.

    2- Diversity factor between the sockets on the same line depends on somefactors like the area of the flat, the larger the area the smaller thediversity factor used.

    3- In calculating the required amount of light for the shaving mirror in thebathroom we consider the recommended lux to be half of that requiredfor the bathroom yet the area is the same area of the bathroom. We useincandescent lamps for the shaving mirror.

    4- Flats of area less than 90 m2 are considered as youth housing thussingle phase energy meters are used in them.

    5- The distribution of flats among riser phases is done in a way to makevoltage drop on each phase exactly equal to other phases.

    6- Single phase energy meters are of ratings 20A and 40A. Three phase

    energy meters are 320A, 325A, 340A and 380A (a catalog ofElsweedy Electrometeris attached in the appendix).

    7- For the c.s.a of the neutral conductor, we follow the Egyptian ElectricCode (EEC) which states " If the c.s.a of the phase conductor is lessthan or equal 16 mm2then the neutral conductor is of the same c.s.a asthe phase conductor. If the phase conductor is of c.s.a less than 35 mm2then the neutral conductor is of c.s.a equal to the one preceding theconcerned phase conductor. If the c.s.a of the phase conductor is morethan or equal 50 mm2 then the c.s.a of the neutral conductor is half ofthe concerned phase conductor.

    8- In general all our distribution of loads among the lines or the phases wemust care that the loads are almost balanced as much as we can to

    avoid the unbalanced operation.9- Low voltage fuses ratings are as follows:

    2,4,6,8,10,16,20,25,32,35,40,50,63,80,100 and 125 according to ABBpocket book(switchgear manual), 8thedition.

  • 8/12/2019 Building Systems Wiring

    11/37

    Chapter -4- Building Wiring Calculations

    50

    4-6. Types of buildings:

    The present calculations are carried out for residential buildings of 4 types:

    a- Flat type (F)

    b- Flat type (J)

    c- Villa type (C)

    d- Villa type (E)

    It was assumed that we have 4,000 persons to be distributed in this

    residential district such that an average of 5 persons live in a flat while an

    average of 8 persons live in a villa. The percentages and number of flats

    required is given in the following table:

    Villa

    Type

    Required

    Percentage

    Total no.

    of

    persons

    required

    No. of

    units

    Unit per

    floor

    No. of

    floors

    per

    building

    No. of

    units

    per

    building

    Total no.

    of

    buildings

    Flat F 60 % 2400 480 3 5 15 32

    Flat J 20 % 800 160 2 5 10 16

    Villa C 10 % 400 50 1 1 1 50

    Villa E 10 % 400 50 1 1 1 50

    Remark: 1 unit =1 villa or 1 flat.

  • 8/12/2019 Building Systems Wiring

    12/37

    Chapter -4- Building Wiring Calculations

    51

    4.6.1 Calculations for flat type (F):

    A- Lighting calculations:

    The following rooms are found in flat (F)

    Roo

    m no. Functionof room

    Area(m2)

    lux lampused

    Req.wattage

    No of lamps Power(w)

    Actual

    current(A)

    1 Bedroom1 3.094.01 150 F 126.39 340 W 120 0.91

    2 Bedroom2 3.094.01 150 F 126.39 340 W 120 0.91

    3Living

    room5.083.00 150 I 457.20

    660+160+160W

    480 2.18

    4 Balcony 1.920.96 50 I 18.43 1 25 W 25 0.11

    5 Kitchen 2.753.00 300 F 168.30 440 W 160 1.21

    6Bedroom3(main

    bedroom)

    4.263.38 150 I 431.96 4100 W 400 1.82

    7 Bathroom 1.923.5 100 F 45.70 140 W 40 0.30

    Shaving

    mirror50 I 67.20 240 W 80 0.36

    8 Hall 4.261.5 150 I 191.70 2100 W 200 0.91

    9 Balcony 5.08*1.5 50 I 76.20 1100 W 100 0.45

    Remarks: F means fluorescent, while I means incandescent.

    Calculations of lighting circuits loads:

    Lighting loads will be divided in 2 circuits

    Circuit (1): L1This circuit containing loads of rooms 1, 2, 3 and 9

    L1 = 0.66 actual currents of the rooms in the circuit)= 0.66 (0.91+0.91+2.182+0.455)= 2.94 Amps.

    And for safety and good design; we take a safety factor of 1.6

    L1 = 4.7 AmpsThe M.C.B used =10 Amps

    The Copper wire used is of c.s.a 2 mm2

  • 8/12/2019 Building Systems Wiring

    13/37

    Chapter -4- Building Wiring Calculations

    52

    Circuit (2): L2This circuit containing loads of rooms 4,5,6,7 and 8

    L2 = 0.66 actual currents of the rooms in the circuit)= 0.66 (0.114+1.212+1.82+0.303+0.364+0.91)= 3.118 Amps.

    And for safety and good design; we take a safety factor of 1.6

    L2 = 5.0 AmpsThe M.C.B used =10 Amps

    The Copper wire used is of c.s.a 2 mm2

    B- Sockets calculations:

    - Since the area of the flat is less than 90 m2 and the flat is of youthhousing we don't expect to have any power sockets in this flat.

    - The following loads are expected in the flat:

    >> Bedroom1:This is the kids' room, we expect the use of 1 fan of 200 W.

    >> Bedroom 2:We expect the use of 1 cassette of 40 W.

    >>Living room:We expect 1 TV set of 65 W and 1 fan of 200 W

    >>BalconySince this balcony is very small and accompanied to the main

    bedroom so no need for sockets in it.

    >> KitchenWe expect the use of a fridge of 160 w and a kitchen machine of 600 w.

    >>Bedroom 3 (main bedroom):we expect the use of a fan of 200 w and a T.V of 65 w.

    >> BathroomWe expect the use of a normal washing machine of 400 w and a shavingmachine of 150 w.

    >>HallWe expect the use of any appliance not more than 3 A.

    >> BalconyThis is the main balcony and we may use a cassette in it.

  • 8/12/2019 Building Systems Wiring

    14/37

    Chapter -4- Building Wiring Calculations

    53

    The result of the required sockets is tabulated in the following table:

    RoomNo.

    1 2 3 4 5 6 7 8 9

    RoomFunction

    Bedrrom1 Bedroom2Livingroom

    balcony kitchen Bedroom3 bathroom Hall balcony

    No. ofN.S

    1 1 2 --------- 2 2 2 1 1

    Calculations of sockets circuits loads:Sockets loads will be divided into to 2 circuits each with 6 normalsockets

    Circuit (3): NS1This circuit contains the loads of rooms 1,2,3,8 and 9NS1 = largest rating socket in ampere + (the rest sockets ratings in

    ampere of the rooms in the circuit)diversity factor= 5+0.3 5 5 = 12.5 A

    The M.C.B. used = 16 AThe copper wire used is of c.s.a 4 mm2

    Circuit (4): NS2This circuit contains the loads of rooms 4,5,6,7 and 8NS2 = largest rating socket in ampere + (the rest sockets ratings in ampereof the rooms in the circuit) diversity factor

    = 5+0.3 5 5 = 12.5 A

    The M.C.B. used = 16 AThe copper wire used is of c.s.a 4 mm2

    -

    C- Calculation of the KVA of the flat:

    Total Socket Load= largest rating M.C.B in amperes + (the rest M.C.Bratings in amperes) diversity factor.

    = 16 + 0.3 16= 20.8 Amps

    Total Lighting Load= L1 + L2 = 5.0 + 4.7 = 9.7 AmpsTotal Load of flat= Total Socket Load + Total Lighting Load

    = 30.5 Amps.

    The incoming M.C.B. used = 32 AThe copper wire used is of c.s.a 16 mm2Energy meter is 40 A single phase meter.

  • 8/12/2019 Building Systems Wiring

    15/37

    Chapter -4- Building Wiring Calculations

    54

    KVA for one flat= 220 30.5 10-3= 6.5 KVA.

    After using diversity curves (done for 15 units)

    Diversified KVA of the flat= 2.75 KVA / flat.

    D- Riser Calculations:

    Flat KVA = 2.75 KVA after diversity for 15 flats.

    Total number of flats in the building = 15 flatsuse one riser

    Total riser KVA= 2.75 x 15 = 41.25 KVA

    Phase KVA = 41.25/3= 13.75 KVA

    Phase current =220

    1000x13.75= 62.5 Amps

    For safety considerations, the riser is loaded with 70%of its ampacity.

    \I phase max= 62.5/0.7 = 89.3 Amps. From the tables attached:

    Riser used is 3x50+ 25 mm2Cu & the resistance per phase is0.836x10-3V/m.

    Let auxiliary loads be:

    a- Water Pump = 1.5 HP, 0.85 p.f. KVA of the pump =85.0

    746x5.1= 1.32

    KVA.

    b- Stairs lighting: if each floor uses one incandescent lamp of 100 W,p.f= 1, KVA of stairs lighting = 5 x 100 x 10-3= 0.5 KVA.

    Total KVA of the building= 41.25 + 1.32 + 0.5 = 43.1 KVA

    For protection we use a three phase fuse 80A.

    Building box is of rating 43.1 KVA.

  • 8/12/2019 Building Systems Wiring

    16/37

    Chapter -4- Building Wiring Calculations

    55

    4.6.2 Calculations for flat type (J):

    A- Lighting calculations:

    The following rooms are found in flat (J)

    Room

    no. Functionof room

    Area (m2) lux lampused

    Req.wattage

    No of lamps Power(w)

    Actual

    current(A)

    1 Kitchen 3.483.63 300 F 257.70 340 +340 W 240 1.82

    2 Bathroom 2.731.9 100 F 35.27 140 W 40 0.30

    Shaving

    mirror50 I 51.87 225 W 50 0.23

    3

    Bedroom1

    (main

    bedroom)

    3.53.63 150 I 381.15 4100 W 400 1.82

    4

    Bedroom2

    (kids'bedroom)

    3.353.62 150 F 123.70 340 W 120 0.91

    5 Balcony 3.35*.88 50 I 62.98 160 W 60 0.27

    6 Living room 3.35*.87 150 I 388.94 225 +660 W 410 1.86

    7 Hall1 1.23.93 130 I 122.62 1100 W 100 0.45

    8Dining

    room4.83.5 150 I 504.00

    660 +160+160W

    480 2.18

    Remarks: F means fluorescent, while I means incandescent.

    Calculations of lighting circuits loads:Lighting loads will be divided in 2 circuits

    Circuit (1): L1

    This circuit containing loads of rooms 1, 2, 7 and 8L1 = 0.66 actual currents of the rooms in the circuit)

    = 0.66 (1.82+0.303+0.455+2.182+0.227)= 3.29 Amps.

    And for safety and good design; we take a safety factor of 1.52

    L1 = 5 AmpsThe M.C.B used =10 Amps

    The Copper wire used is of c.s.a 2 mm2

  • 8/12/2019 Building Systems Wiring

    17/37

    Chapter -4- Building Wiring Calculations

    56

    Circuit ( 2 ): L2This circuit containing loads of rooms 3, 4, 5 and 6

    L2 = 0.66 actual currents of the rooms in the circuit)= 0.66 (1.82+0.91+0.27+1.86)= 3.21 Amps.

    And for safety and good design; we take a safety factor of 1.52

    L2 = 4.88 AmpsThe M.C.B used =10 Amps

    The Copper wire used is of c.s.a 2 mm2

    B- Sockets calculations:

    - Since the area of the flat is less than 90 m2 and the flat is of youth

    housing we don't expect to have any power sockets in this flat.- The following loads are expected in the flat:

    >> Kitchen:We expect the use of a fridge of 160 w and a kitchen machine of 600 w.

    >> BathroomWe expect the use of a normal washing machine of 400 w.

    >>Bedroom 1 (main bedroom):We expect the use of a fan of 200 w and a T.V of 65 w.

    >> Bedroom 2:This is the kids' room. We expect the use of a fan of 200w.

    >>Balcony (of the kids' room)We expect the use of any appliance of rating not more than 3 A.

    >>Living room:We expect 1 TV set of 65 W and 1 fan of 200 W

    >>HallWe expect the use of any appliance like a vacuum cleaner of 800w.

    >> Dinning room.We expect the use of a cassette of 40w and a fan of 200w.

  • 8/12/2019 Building Systems Wiring

    18/37

    Chapter -4- Building Wiring Calculations

    57

    The result of the required sockets is tabulated in the following table:

    RoomNo.

    1 2 3 4 5 6 7 8

    RoomFunction

    Kitchen BathroomBedroom

    1Bedroom

    2Balcony

    Livingroom

    HallDinningroom

    No. ofN.S

    2 1 2 1 1 2 1 2

    Calculations of sockets circuits loads:Sockets loads will be divided into to 2 circuits each with 6 normalsockets

    Circuit (3): NS1

    This circuit contains the loads of rooms 1, 2, 7 and 8.

    NS1 = largest rating socket in ampere + (the rest sockets ratings in ampereof the rooms in the circuit)diversity factor

    = 5+0.3 5 5 = 12.5 A

    The M.C.B. used = 16 AThe copper wire used is of c.s.a 4 mm2

    Circuit (4): NS2

    This circuit contains the loads of rooms 3, 4, 5 and 6

    NS2 = largest rating socket in ampere + (the rest sockets ratings in ampereof the rooms in the circuit) diversity factor

    = 5+0.3 5 5 = 12.5 A

    The M.C.B. used = 16 AThe copper wire used is of c.s.a 4 mm2

    -

    C- Calculation of the KVA of the flat:

    Total Socket Load= largest rating M.C.B in amperes + (the rest M.C.Bratings in amperes) diversity factor.

    = 16 + 0.3 16

    = 20.8 AmpsTotal Lighting Load= L1 + L2 = 5.0 + 4.88 = 9.88 AmpsTotal Load of flat= Total Socket Load + Total Lighting Load

    = 30.68 Amps.

    The incoming M.C.B. used = 32 AThe copper wire used is of c.s.a 16 mm2Energy meter is 40 A single phase meter.

  • 8/12/2019 Building Systems Wiring

    19/37

    Chapter -4- Building Wiring Calculations

    58

    KVA for one flat= 220 30.68 10-3= 6.75 KVA.

    After using diversity curves (done for 10 units)

    Diversified KVA of the flat= 3.02 KVA / flat.

    D- Riser Calculations:

    Flat KVA = 3.02 KVA after diversity for 10 flats.

    Total number of flats in the building = 10 flatsuse one riser

    Total riser KVA= 3.02 x 10 = 30.2 KVA

    Phase KVA = 30.2/3= 10.06 KVA

    Phase current =220

    1000x10.06= 45.71 Amps

    For safety considerations, the riser is loaded with 70%of its ampacity.

    \I phase max= 45.71/0.7 = 65.31 Amps. From the tables attached:

    Riser used is 3x35+ 25 mm2Cu & the resistance per phase is1.097x10-3V/m.

    Let the auxiliary loads be:

    a- Water Pump = 1.5 HP, 0.85 p.f. KVA of the pump =85.0

    746x5.1= 1.32

    KVA.

    b- Stairs lighting: if each floor uses one incandescent lamp of 100 W,p.f= 1, KVA of stairs lighting = 5 x 100 x 10-3= 0.5 KVA.

    Total KVA of the building= 30.2 + 1.32 + 0.5 = 32.02 KVA.

    And since phases R and S have only 3 flats on each while phase T has 4flats, thus to cause relative balance between phases then we feed theauxiliary loads from either phase R or S.

    For protection we use a three phase fuse 63A.

    Building box is of rating 32.02 KVA.

  • 8/12/2019 Building Systems Wiring

    20/37

    Chapter -4- Building Wiring Calculations

    59

    4.6.3 Calculations for villa type (C):

    I- 1st

    floor:

    A- Lighting calculations:

    The following rooms are found in the first floor of villa (C)Room

    no.Function

    of roomArea (m2) lux

    lamp

    used

    Req.

    wattageNo of lamps

    Power

    (w)

    Actual

    current

    (A)

    1 Kitchen 42.8 300 F 228.48340 + 340

    W240 1.82

    2 Bathroom 1.82.8 100 F 34.27 140 W 40 0.30

    Shaving

    mirror50 I 50.40 240 W 80 0.36

    3 Living room 4.54 150 I 540.00860 W

    +21*60 W600 2.73

    4 Dinningroom 3.54 150 I 420.00 660 W +2160 W480 2.18

    5 Salon 3.54 150 I 420.00660 W +2160 W

    480 2.18

    6 Balcony 3.51.5 50 I 52.50 160 W 60 0.27

    7 Balcony 4.51.5 50 I 67.50 160 W 60 0.27

    8 Balcony 0.82.8 50 I 22.40 125 W 25 0.11

    9 Hall1 7.751.5 100 I 232.50 21100 W 200 0.91

    10 Stairs 50 I 50.00 160 W 60 0.27

    11 Entrance 1.52.8 100 I 84.00 1100 W 100 0.45

    Remarks: F means fluorescent, while I means incandescent.

    Calculations of lighting circuits loads:

    Lighting loads will be divided in 3 circuits

    L1

    This circuit containing loads of areas 1, 2, 8, 10 and 11L1 = 0.66 actual currents of the rooms in the circuit)

    = 0.66 (1.82+0.3+0.36+0.11+0.27+0.45)= 2.1846 Amps.

    And for safety and good design; we take a safety factor of 1.6

    L1 = 3.5 AmpsThe M.C.B used =10 Amps

    The Copper wire used is of c.s.a 3 mm2

  • 8/12/2019 Building Systems Wiring

    21/37

    Chapter -4- Building Wiring Calculations

    60

    L2

    This circuit containing loads of areas 3, 7 and 9L2 = 0.66 actual currents of the rooms in the circuit)

    = 0.66 (2.73+0.27+0.91)= 2.581 Amps.

    And for safety and good design; we take a safety factor of 1.6

    L2 = 4.1296 AmpsThe M.C.B used =10 Amps

    The Copper wire used is of c.s.a 3 mm2

    L3This circuit containing loads of areas 4, 5 and 6

    L3 = 0.66 actual currents of the rooms in the circuit)= 0.66 (2.18+2.18+0.27)

    = 3.06 Amps.And for safety and good design; we take a safety factor of 1.6

    L3 = 4.9 AmpsThe M.C.B used =10 Amps

    The Copper wire used is of c.s.a 3 mm2

    B- Sockets calculations:

    - Normal Socket Lines:

    The following loads are expected in each area.>> Kitchen:We expect the use of a fridge of 160 w, a kitchen machine of 600 w anddeep freezer of 160 w.

    >> BathroomWe expect the use of a hair dryer of 600w or a shaving machine of 150w.

    >>Living room:We expect a TV set of 65 W, a video of 30w and a cassette of 40w.

    >> Dinning room.We expect the use of a cassette of 40w and a fan of 200w.

    >>Salon:We expect the use of a T.V of 65w and a sound system of 800w

    >>Balconies of the salon, the living room and the bathroom:We expect the use of any appliance of rating not more than 3 A.

  • 8/12/2019 Building Systems Wiring

    22/37

    Chapter -4- Building Wiring Calculations

    61

    >>Hall 1:Since the hall is long we use at least two normal sockets one at each end.

    The result of the required sockets is tabulated in the following table:

    Room No. 1 2 3 4 5 6 7 8 9

    RoomFunction

    Kitchen Bathroom Livingroom

    Dinningroom

    Salon Balcony Balcony Balcony Hall1

    No. of N.S 3 1 3 2 2 1 1 1 2

    Calculations of normal sockets circuits

    loads:Normal sockets loads will be divided into to 3 circuits

    NS1

    This circuit contains the loads of rooms 1, 2 and 8.NS1 = largest rating socket in ampere + (the rest sockets ratings in ampereof the rooms in the circuit)diversity factor

    = 5+0.2 4 5 = 9 A

    The M.C.B. used = 10 AThe copper wire used is of c.s.a 4 mm2

    NS2

    This circuit contains the loads of rooms 3, 7 and 9.

    NS2 = largest rating socket in ampere + (the rest sockets ratings in ampereof the rooms in the circuit) diversity factor

    = 5+0.2 5 5 = 10 A

    The M.C.B. used = 16 AThe copper wire used is of c.s.a 4 mm2

    NS3

    This circuit contains the loads of rooms 4, 5 and 6..

    NS3 = largest rating socket in ampere + (the rest sockets ratings in ampereof the rooms in the circuit) diversity factor

    = 5+0.2 4 5 = 9 A

    The M.C.B. used = 10 AThe copper wire used is of c.s.a 4 mm2

  • 8/12/2019 Building Systems Wiring

    23/37

    Chapter -4- Building Wiring Calculations

    62

    - Power Socket Lines:The following loads are expected in each area.

    1. PS1 For water heater in the kitchen:Let the water heater be 2000w thus the rated current will be 9.12A thus weuse a power socket 16A and the MCB will be 16A with a copper wire of c.s.a

    4 mm2.

    2. PS2 For dish washer in the kitchen:Let the dish washer be 1500w with a power factor of 0.85 thus the ratedcurrent will be 8.5A and a starting current of 250% of the rated current thuswe use a power socket 26A and the MCB will be 25A with a copper wire ofc.s.a 6 mm2.

    3. PS3 For A.C in the living room:Let the A.C be 2.25HP with a power factor of 0.85 thus the rated current willbe 9.5A and a starting current of 250% of the rated current thus we use a

    Load break switch (L.B.S) 26A and the MCB will be 25A with a copper wireof c.s.a 6 mm2.

    4. PS4 For A.C in the salon:Let the A.C be 2.25HP with a power factor of 0.85 thus the rated current willbe 9.5A and a starting current of 250% of the rated current thus we use aLoad break switch (L.B.S) 26A and the MCB will be 25A with a copper wireof c.s.a 6 mm2.

    C- Distribution of the circuits among the phases:

    Phase LightLines

    SocketLines

    R L1 (3.5A)NS1 (10A)PS1 (16A)PS2 (25A)

    S L2 (4.13A) NS2 (16A)PS3 (25A)

    T L3 (4.9A)NS3 (10A)PS4 (25A)

  • 8/12/2019 Building Systems Wiring

    24/37

    Chapter -4- Building Wiring Calculations

    63

    Calculations of phases current:For phase R:Total Socket Load= largest rating M.C.B in amperes + (the rest M.C.B

    ratings in amperes) diversity factor.= PS2+0.2 (NS1+PS1)= 30.2 Amps

    Total Lighting Load= L1 = 3.5 AmpsTotal Load of phase R for the 1stfloor= Total Socket Load + Total Lighting

    Load= 33.7 Amps.

    For phase S:Total Socket Load= largest rating M.C.B in amperes + (the rest M.C.B

    ratings in amperes) diversity factor.= PS3+0.2 NS2= 28.2 Amps

    Total Lighting Load= L2 = 4.13 AmpsTotal Load of phase S for the 1stfloor= Total Socket Load + Total LightingLoad= 32.33 Amps

    For phase T:Total Socket Load= largest rating M.C.B in amperes + (the rest M.C.B

    ratings in amperes) diversity factor.= PS4+0.2 NS3= 27.0 Amps

    Total Lighting Load= L3 = 4.9 Amps

    Total Load of phase T for the 1

    st

    floor= Total Socket Load + Total LightingLoad= 31.9 Amps

    The incoming M.C.B.of the 1stfloor panel board is 40 A (3 p)The copper wire used is of c.s.a 416 mm2

  • 8/12/2019 Building Systems Wiring

    25/37

    Chapter -4- Building Wiring Calculations

    64

    II- 2nd

    floor:

    A- Lighting calculations:

    The following rooms are found in the 2nd

    floor of villa (C)

    Room

    no.Function

    of roomArea (m2) lux

    lamp

    used

    Req.

    wattageNo of lamps

    Power

    (w)

    Actual

    current

    (A)

    12 Kitchenette 42.8 200 F 152.32 340 W 120 0.91

    13 Bathroom 1.82.8 100 F 34.27 140 W 40 0.30

    Shaving

    mirror50 I 50.40 240 W 80 0.36

    14

    Bedroom1

    (main

    bedroom)

    4.54 150 I 540.004100 W+2160 W

    520 2.36

    15 Bedroom2 3.54 150 I 420.00 4100 W 400 1.82

    16 Bedroom 3 3.54 150 F 142.80 440 W 160 1.21

    17 Balcony 3.51.5 50 I 52.50 160 W 60 0.27

    18 Balcony 4.51.5 50 I 67.50 160 W 60 0.27

    19 Balcony 0.82.8 50 I 22.40 125 W 25 0.11

    20 Hall2 7.751.5 100 I 232.50 21100 W 200 0.91

    Remarks: F means fluorescent, while I means incandescent.

    Calculations of lighting circuits loads:

    Lighting loads will be divided in 3 circuits

    L4

    This circuit containing loads of areas 12, 13, 19 and 20.L4 = 0.66 actual currents of the rooms in the circuit)

    = 0.66 (0.91+0.3+0.36+0.11+0.91)= 1.71 Amps.

    And for safety and good design; we take a safety factor of 1.6

    L4 = 2.74 AmpsThe M.C.B used =6 Amps

    The Copper wire used is of c.s.a 3 mm2

  • 8/12/2019 Building Systems Wiring

    26/37

    Chapter -4- Building Wiring Calculations

    65

    L5

    This circuit containing loads of areas 14 and 18.L5 = 0.66 actual currents of the rooms in the circuit)

    = 0.66 (2.36+0.27)= 1.73 Amps.

    And for safety and good design; we take a safety factor of 1.6

    L5 = 2.78 AmpsThe M.C.B used =6 Amps

    The Copper wire used is of c.s.a 3 mm2

    L6

    This circuit containing loads of areas 15, 16 and 17.L6 = 0.66 actual currents of the rooms in the circuit)

    = 0.66 (1.82+1.21+0.27)= 2.2 Amps.

    And for safety and good design; we take a safety factor of 1.6

    L6 = 3.48 AmpsThe M.C.B used =6 Amps

    The Copper wire used is of c.s.a 3 mm2

    B- Sockets calculations:

    - Normal Socket Lines:

    The following loads are expected in each area.>> Kitchenette:

    We expect the use of a small fridge of 80 w and a toaster of 800w

    >> BathroomWe expect the use of a hair dryer of 600w or a shaving machine of 150wand an air blower of 200w

    >>Bedroom1 (main bedroom):We expect a TV set of 65 W, a cassette of 40w, and a lighting spot of100W.

    >> Bedroom2:We expect the use of a cassette of 40w and an iron of 1000w.

    >>Bedroom3:We expect the use of a T.V of 65w and a fan of 800w

    >>Balcony of bedroom3We expect the use of a cassette of 40w

    >>Balcony of bedroom1We expect the use of any appliance of not more than 3A

  • 8/12/2019 Building Systems Wiring

    27/37

    Chapter -4- Building Wiring Calculations

    66

    >>Balcony next to the bathroom:We expect the use of any appliance of not more than 3A

    >>Hall 2:Like we did in hall1, we use at least two normal sockets one at each end.

    The result of the required sockets is tabulated in the following table:

    Room No. 1 2 3 4 5 6 7 8 9Room

    FunctionKitchen

    etteBathroom

    Bedroom1

    Bedroom2

    Bedroom3

    Balcony Balcony Balcony Hall2

    No. of N.S 2 2 3 2 2 1 1 1 2

    Calculations of normal sockets circuitsloads:

    Normal sockets loads will be divided into to 3 circuits

    NS4

    This circuit contains the loads of rooms 12, 13 and 19.NS4 = largest rating socket in ampere + (the rest sockets ratings in ampereof the rooms in the circuit)diversity factor

    = 5+0.2 4 5 = 9 A

    The M.C.B. used = 10 AThe copper wire used is of c.s.a 4 mm2

    NS5

    This circuit contains the loads of rooms 14, 18 and 20.NS5 = largest rating socket in ampere + (the rest sockets ratings in ampereof the rooms in the circuit) diversity factor

    = 5+0.2 5 5 = 10 A

    The M.C.B. used = 16 AThe copper wire used is of c.s.a 4 mm2

  • 8/12/2019 Building Systems Wiring

    28/37

    Chapter -4- Building Wiring Calculations

    67

    NS6

    This circuit contains the loads of rooms 15, 16 and 17.NS6 = largest rating socket in ampere + (the rest sockets ratings in ampereof the rooms in the circuit) diversity factor

    = 5+0.2 4 5 = 9 A

    The M.C.B. used = 10 AThe copper wire used is of c.s.a 4 mm2

    - Power Socket Lines:

    The following loads are expected in each area.

    1. PS5 for washing machine on the bathroom:

    Let the washing machine be 1500w with a power factor of 0.85 thus therated current is 8.5 A and the starting current is 250% of the rated currentthus we use a power socket of 26 A and the M.C.B is 25A with a copper wireof c.s.a 6 mm2

    2. PS6 for an A.C in bedroom1:Let the A.C be 2.25 HP with a power factor of 0.85 thus the rated current willbe 9.5A and a starting current of 250% of the rated current thus we use aLoad break switch (L.B.S) 26A and the MCB will be 25A with a copper wireof c.s.a 6 mm2.

    3. PS7 For an A.C in bedroom2:Let the A.C be 2.25HP with a power factor of 0.85 thus the rated current willbe 9.5A and a starting current of 250% of the rated current thus we use a

    Load break switch (L.B.S) 26A and the MCB will be 25A with a copper wireof c.s.a 6 mm2.

    C- Distribution of the circuits among the phases:

    Phase LightLines

    SocketLines

    R L4 (2.74A)

    NS4(10A)

    PS5(25A)

    S L5(2.78 A)NS6(10A)PS6(25A)

    T L6(3.48A)NS5(16A)PS7(25A)

  • 8/12/2019 Building Systems Wiring

    29/37

    Chapter -4- Building Wiring Calculations

    68

    Remark: in the 1stfloor, load of phase R> load of phase S> load of phase T;thus in the 2ndfloor we care that the opposite happens to cause a balance onthe phase as a whole.

    Calculations of phases current:

    For phase R:

    Total Socket Load= largest rating M.C.B in amperes + (the rest M.C.Bratings in amperes) diversity factor.

    = PS5+0.2 NS4= 27 Amps

    Total Lighting Load= L4 = 2.74 AmpsTotal Load of phase R for the 2ndfloor= Total Socket Load + Total Lighting

    Load= 29.74 Amps.

    For phase S:Total Socket Load= largest rating M.C.B in amperes + (the rest M.C.B

    ratings in amperes) diversity factor.= PS6+0.2 NS6= 27 Amps

    Total Lighting Load= L5 = 2.78 AmpsTotal Load of phase S for the 2ndfloor= Total Socket Load + Total Lighting

    Load= 29.78 Amps

    For phase T:Total Socket Load= largest rating M.C.B in amperes + (the rest M.C.B

    ratings in amperes) diversity factor.= PS7+0.2 NS5= 28. Amps

    Total Lighting Load= L6 = 3.48 AmpsTotal Load of phase T for the 2ndfloor= Total Socket Load + Total Lighting

    Load= 31.9 Amps

    The incoming M.C.B. of the 2ndfloor panel board 40A (3p)

    The copper wire used is 416 mm2

    D- Calculation of the KVA of the villa:

    For the 1stfloor; KVA of this floor is calculated as follows:KVAbottom= 220 (33.7+32.33+31.9) 10

    -3= 21.54 KVA.

    For the 2nd floor; KVA of this floor is calculated as follows:

  • 8/12/2019 Building Systems Wiring

    30/37

    Chapter -4- Building Wiring Calculations

    69

    KVAupper = 220 (29.74+29.78+31.68) 10-3

    = 20.06 KVA.Thus the KVA of the two floors after making the appropriate diversificationbetween the loads of the two floors is 41 KVA.Let the garden lighting be 1.5 KVA. It will be connected to the phase S since itis the least loaded phase.

    Total KVA of the building= 41 + 1.5 = 42.5 KVA.

    E- Riser Calculations:

    Villa KVA without the garden lighting is 41 KVA.

    Total riser KVA= 41 KVA

    Phase KVA = 41/3= 13.67 KVA

    Phase current = 220

    1000x13.67

    = 62.12 Amps

    For safety considerations, the riser is loaded with 70%of its ampacity.

    \I phase max= 62.12/0.7 = 88.74 Amps. From the tables attached:

    the riser used is 3x50 + 25 mm2Cu & the resistance per phaseis 0.836x10-3V/m.

    We use a three phase energy meter 3 80 A.

    For protection we use a three phase fuse 80A.

    Building box is of rating 42.5 KVA.

  • 8/12/2019 Building Systems Wiring

    31/37

    Chapter -4- Building Wiring Calculations

    70

    4.6.4 Calculations for villa type (E):

    A- Lighting calculations:

    The following rooms are found in villa (E)

    Room

    no.Function

    Of room

    Area

    (m2)lux

    lamp

    used

    Req.

    wattageNo of lamps

    Power

    (w)

    Actual

    current

    (A)

    1

    Bedroom1

    (main

    bedroom)

    55 120 I 600 4100+21100 600 2.73

    2 Bedroom2 55 150 F 255 340 W+340 W 240 1.82

    3 Salon 55 150 I 750 1060 W+2160 W 720 3.27

    4Dinning

    room55 150 I 750 1060 W+2160 W 720 3.27

    5 Hall1 66.5 100 I 780 1060 W+4160 W 840 3.82

    6 Kitchen 45 300 F 359.04 440+440 W 320 2.42

    7 Bathroom 23 100 F 40.8 140 W 40 0.30

    Shaving

    mirror50 I 60 225 W 50 0.23

    8 Hall2 22 100 I 80 1100 W 100 0.45

    9 W.C. 21.2 100 F 16.32 125 W 25 0.19

    10 Hall3 51.5 100 I 150 160+160 W 120 0.55

    11 Hall4 51.5 100 I 150 160+160 W 120 0.55

    Remarks: F means fluorescent, while I means incandescent.

    Calculations of lighting circuits loads:

    Lighting loads will be divided in 3 circuits

    L1

    This circuit containing loads of areas 1, 3 and 11L1 = 0.66 actual currents of the rooms in the circuit)

    = 0.66 (2.73+3.27+0.55)

    = 4.323 Amps.And for safety and good design; we take a safety factor of 1.2

    L1 = 5.1876 AmpsThe M.C.B used =10 Amps

    The Copper wire used is of c.s.a 3 mm2

  • 8/12/2019 Building Systems Wiring

    32/37

    Chapter -4- Building Wiring Calculations

    71

    L2

    This circuit containing loads of areas 2, 5, 7 and 8L2 = 0.66 actual currents of the rooms in the circuit)

    = 0.66 (1.82+3.82+0.303+0.23+0.45)= 4.37 Amps.

    And for safety and good design; we take a safety factor of 1.2

    L2 = 5.244 AmpsThe M.C.B used =10 Amps

    The Copper wire used is of c.s.a 3 mm2

    L3

    This circuit containing loads of areas 4, 6, 9 and 10L3 = 0.66 actual currents of the rooms in the circuit)

    = 0.66 (3.27+2.42+0.189+0.55)= 3.06 Amps.

    And for safety and good design; we take a safety factor of 1.2

    L3 = 5.088 AmpsThe M.C.B used =10 Amps

    The Copper wire used is of c.s.a 3 mm2

    B- Sockets calculations:

    - Normal Socket Lines:

    The following loads are expected in each area.

    >>Bedroom1 (main bedroom):We expect a TV set of 65 W, a small fridge of 80w, and a cassette of 40w.

    >> Bedroom2:We expect the use of a cassette of 40w and an iron of 1000w.

    >>Salon:

    We expect the use of a T.V of 65w, a video of 30w and a sound system of800w.

    >> Dinning room.We expect the use of a cassette of 40w and a fan of 200w.

    >>Hall 1:Since the area is big (6.5 6m2) thus we must spread at least two or threesockets in this area so that the user can use the required appliance

  • 8/12/2019 Building Systems Wiring

    33/37

    Chapter -4- Building Wiring Calculations

    72

    wherever he wishes in the hall. We expect the use of a cassette of 40w, avacuum cleaner of 800w and any other appliance not exceeding 3A.>> Kitchen:We expect the use of a fridge of 160 w, a kitchen machine of 600 w anddeep freezer of 160 w.

    >> BathroomWe expect the use of a hair dryer of 600w or a shaving machine of 150w

    >>Hall 2:We expect the use of any appliance of 3A.

    >> W.CWe expect the use of a hair dryer of 600w or a shaving machine of 150w

    >> Hall3:We expect the use of any appliance of 3A.

    >> Hall4We expect the use of any appliance of 3A.

    The result of the required sockets is tabulated in the following table:

    RoomNo.

    1 2 3 4 5 6 7 8 9 10 11

    RoomBedroom

    1bedroom

    2salon

    Dinningroom

    Hall1

    kitchen bathroomHall

    2W.C

    Hall3

    Hall4

    No. of

    N.S

    3 2 3 2 3 3 1 1 1 1 1

    Calculations of normal sockets circuits

    loads:

    Normal sockets loads will be divided into to 3 circuits with 7 sockets oneach circuit.

    NS1

    This circuit contains the loads of rooms 1, 3 and 11NS1 = largest rating socket in ampere + (the rest sockets ratings in ampereof the rooms in the circuit)diversity factor

    = 5+0.2 6 5 = 11 A

    The M.C.B. used = 16 AThe copper wire used is of c.s.a 4 mm2

  • 8/12/2019 Building Systems Wiring

    34/37

    Chapter -4- Building Wiring Calculations

    73

    NS2

    This circuit contains the loads of rooms 2, 5, 7 and 8 .NS2 = largest rating socket in ampere + (the rest sockets ratings in ampereof the rooms in the circuit) diversity factor

    = 5+0.2 6 5 = 11 A

    The M.C.B. used = 16 AThe copper wire used is of c.s.a 4 mm2

    NS3

    This circuit contains the loads of rooms 4, 6, 9 and 10.NS3 = largest rating socket in ampere + (the rest sockets ratings in ampereof the rooms in the circuit) diversity factor

    = 5+0.2 6 5 = 11 A

    The M.C.B. used = 16 AThe copper wire used is of c.s.a 4 mm2

    - Power Socket Lines:The following loads are expected in each area.

    4-1. PS1 For A.C in bedroom1:Let the A.C be 2.25HP with a power factor of 0.85 thus the rated current will

    be 9.5A and a starting current of 250% of the rated current thus we use aLoad break switch (L.B.S) 26A and the MCB will be 25A with a copper wireof c.s.a 6 mm2.

    4-2. PS2 For A.C in bedroom2:Let the A.C be 2.25HP with a power factor of 0.85 thus the rated current willbe 9.5A and a starting current of 250% of the rated current thus we use aLoad break switch (L.B.S) 26A and the MCB will be 25A with a copper wireof c.s.a 6 mm2.

    4-3. PS3 For A.C in the salon:

    Let the A.C be 2.25HP with a power factor of 0.85 thus the rated current willbe 9.5A and a starting current of 250% of the rated current thus we use aLoad break switch (L.B.S) 26A and the MCB will be 25A with a copper wireof c.s.a 6 mm2.

    4-4. PS4 For water heater in the kitchen:Let the water heater be 1500w thus the rated current will be 6.82A thus weuse a power socket 10A and the MCB will be 10A with a copper wire of c.s.a4 mm2.

  • 8/12/2019 Building Systems Wiring

    35/37

    Chapter -4- Building Wiring Calculations

    74

    4-5. PS5 for washing machine on the bathroom:Let the washing machine be 1500w with a power factor of 0.85 thus therated current is 8.5 A and the starting current is 250% of the rated currentthus we use a power socket of 26 A and the M.C.B is 25A with a copper wireof c.s.a 6 mm2

    C- Distribution of the circuits among the phases:

    Phase Light Lines SocketLines

    R L1 (5.1876A)NS1 (16A)PS1 (25A)

    S L2 (5.244A)

    NS2 (16A)

    PS2 (25A)

    T L3 (5.088A)NS3 (16A)PS5(25A)PS4 (10A)

    Calculations of phases current:

    For phase R:Total Socket Load= largest rating M.C.B in amperes + (the rest M.C.B

    ratings in amperes) diversity factor.= PS1+0.2 NS1= 28.2 Amps

    Total Lighting Load= L1 = 5.1876 AmpsTotal Load of phase R for the 1stfloor= Total Socket Load + Total Lighting

    Load= 33.3876 Amps.

    For phase S:Total Socket Load= largest rating M.C.B in amperes + (the rest M.C.B

    ratings in amperes) diversity factor.= PS2+0.2 NS2= 28.2 Amps

    Total Lighting Load= L2 = 5.244 Amps

    Total Load of phase S for the 1stfloor= Total Socket Load + Total LightingLoad

  • 8/12/2019 Building Systems Wiring

    36/37

    Chapter -4- Building Wiring Calculations

    75

    = 33.44 AmpsFor phase T:Total Socket Load= largest rating M.C.B in amperes + (the rest M.C.B

    ratings in amperes) diversity factor.= PS5+0.2 (NS3 + PS4)= 30.2 Amps

    Total Lighting Load= L3 = 5.088 AmpsTotal Load of phase T for the 1stfloor= Total Socket Load + Total Lighting

    Load= 35.288 Amps

    The incoming M.C.B. 40A (3p)The copper wire used is 416 mm2

    D- Calculation of the KVA of the villa:

    KVAvilla= 220 (33.3876 + 33.44 + 35.288) 10-3

    = 22.5 KVA.

    Let the garden lighting be 1.5 KVA. It will be connected to the phase R since itis the least loaded phase.Total KVA of the building= 22.5 + 1.5 = 24 KVA.

    E- Riser Calculations:

    Villa KVA without the garden lighting is 22.5 KVA.

    Total riser KVA= 22.5 KVA

    Phase KVA = 22.5/3= 7.5 KVA

    Phase current =220

    1000x7.5= 34.1 Amps

    For safety considerations, the riser is loaded with 70%of its ampacity.

    \I phase max= 34.1/0.7 =48.7 Amps. From the tables attached:

    The riser used is 3x25 + 16 mm2Cu

    We use a three phase energy meter 3 40A.

    For protection we use a three phase fuse 50A.

    Building box is of rating 24 KVA.

  • 8/12/2019 Building Systems Wiring

    37/37

    Chapter -4- Building Wiring Calculations

    4-7. Summary of results

    The load and the number of each building type are summarized in the

    following table:

    Building typeLoad of the building

    (KVA)

    No. of buildings

    required

    Flat type (F) 43.1 32

    Flat type (J) 32.02 16

    Villa type (C) 42.5 50

    Villa type (E) 24 50