building science 2 final report
TRANSCRIPT
SCHOOL OF ARCHITECTURE, BUILDING & DESIGN CENTRE OF ARCHITECTURE STUDIES IN SOUTHEAST ASIA (MASSA)
BACHELOR OF SCIENCE (HONOURS) (ARCHITECTURE) BUILDING SCIENCE 2 (BLD61303)
PROJECT 1: LIGHTING & ACOUSTIC PERFORMANCE EVALUATION & DESIGN
AMPM CAFÉ SS15
AIMI FARZANA BINTI AHMAD NORIZAN 0317621
FARAH AKMAL BT MOHD ZAMZURI 0315884
GHADA RASHAD ABDULHAMEED NOMAN 0315601
KIMBERLEY EE SZE ANN 0315391
MUATASIMAH BILLAH BINTI SALEH MOHAMED 0316071
SHERY EDRINA BINTI SALEHUDDIN 0316321
‘
TUTOR: MR. SIVARAMAN KUPPUSAMMY
TABLE OF CONTENT
1.0 LIGHTING
1.1 Introduction…...……………………………………………………………………………………….
1.1.1 Aim and Objective…………………………………………………………………1
1.2 Journal……………………………………………………………………………………………….…
1.2.1 Literature Review………………………………………………………………… 2
1.2.1.1 Architecture Lighting …………………………………………………….2
1.2.1.2 Daylight Factor…………………………………………………………. 4
1.2.1.3 Lumen Method………………………………………………………….. 5
1.2.2 Lighting Precedent Studies……………………………………………………... 6
1.2.2.1 Introduction………………………………………………………………7
1.2.2.2 Result and Discussion………………………………………………… 8
1.2.2.3 Questionnaire Survey………………………………………………….. 9
1.2.2.4 Matrix of the lighting analysis for UKM architecture studio………… 10
1.2.2.5 Conclusion………………………………………………………………. 10
1.3 Research Methodology……………………………………………………………………………….
1.3.1 Measuring Device………………………………………………………………... 11
1.3.2 Data Collection Method…………………………………………………………. 13
1.4 Case Study………………………………………………………………………………………….. 14
1.4.1 Data Collection…………………………………………………………………………….. 16
1.4.2 Limitation & Constraint……………………………………………………………………. 19
1.5 Lighting Analysis………………………………………………………………………………………
1.5.1 Tabulation of data……………………………………………………………………………. 20
1.5.1.1 Data Findings at the zones……………………………………………………… 23
1.5.2 Sun path Diagram……………………………………………………………………………. 29
1.5.3 Natural Lighting Analysis………………………………………………………………………...
1.5.3.1 Daylight factor calculation……………………………………………………….. 31
1.5.3.2 Lighting Diagrammatic Analysis (Daylight) ……………………………………. 46
1.5.4 Artificial Lighting Analysis…………………………………………………………………… 47
1.5.4.1 Identification of lighting fixture…………………………………………………... 47
1.5.4.2 Artificial light location on floor plan……………………………………………... 49
1.5.4.3 Material Reflectance Index……………………………………………………… 50
1.5.4.4 Lumen Method Calculation for Artificial Light…………………………………. 64
1.5.4.5 Lighting Diagrammatic Analysis (Artificial Light)……………………………… 82
1.5.5 Lighting Contour Diagrams……………………………………………………................... 83
1.5.6 Photographs at the site……………………………………………………………………… 86
1.6 Conclusion….…………………………………………………………………………………….... 89
1.7 References…..……………………………………………………………………………………… 90
2.0 ACOUSTIC
2.1 Introduction…...……………………………………………………………………………………….
2.1.1 Aim and Objective……………………………………………………………………………. 91
2.2 Journal…………………………………………………………………………………………………..
2.2.1 Literature Review………………………………………………………………………….. 92
2.2.2 Acoustic Precedent Studies……………………………………………………………… 95
2.2.2.1 Design Intention (Function)……………………………………………………... 96
2.2.2.2 Space Specification…………………………………………………………….... 97
2.2.2.3 Reverberation Analysis………………………………………………………….. 98
2.2.2.4 Analysis of Sound transmission class (STC)…………………………………. 99
2.2.2.5 New Proposed Baffled System…………………………………………………. 100
2.2.2.6 Conclusion………………………………………………………………………… 101
2.3 Research Methodology……………………………………………………………………………….
2.3.1 Measuring Equipment…………………………………………………………………….. 102
2.3.2 Data Collection Method…………………………………………………………………… 104
2.3.3 Limitation & Constraint……………………………………………………………………. 105
2.4 Case Study………………………………………………………………………………………….. 106
2.5 Lighting Analysis………………………………………………………………………………………
2.5.1 Site Study………………………………………………………………………………………….
2.5.1.1 Outdoor Noise Source…………………………………………………………… 108
2.5.1.2 Indoor Noise Source……………………………………………………………... 109
2.5.2 Tabulation of data……………………………………………………………………………. 111
2.5.2.1 Data Findings at the zones……………………………………………………… 113
2.5.3 Material Absorption Coefficient……………………………………………………………... 119
2.5.4 Calculation of Sound Intensity Level (SIL)………………………………………………… 131
2.5.4.1 Sound Intensity Level (SIL) Analysis and Conclusion………………………... 137
2.5.5 Calculation of Sound Reduction Index (SRI)………………………………………………. 141
2.4.5.1 Sound Reduction Index (SRI) Analysis and Conclusion……………………… 147
2.5.6 Calculation of Sound Reverberation Time (SRT)…………………………………………. 149
2.5.6.1 Sound Reverberation Time (SRT) Analysis and Conclusion………………… 153
2.5.7 Acoustic Ray Diagrams……………………………………………………………………… 157
2.6 Conclusion….…………………………………………………………………………………….... 161
2.7 References…..……………………………………………………………………………………… 163
1.0 LIGHTING
1
1.1 Introduction
1.1.1 Aim and Objective
This project focuses on the lighting and acoustic of the chosen case study building, AMPM Cafe, USJ
21, Subang Jaya.
Architectural lighting is essential in creating a pleasant environment for the interior and exterior of
buildings. Without lighting, people would not be able to perceive solid volumes, colours, enclosed
spaces nor textures and thus would not be able to appreciate architecture.
This project exposes students to the methods of designing good lighting acoustic systems through a
series of calculation. The objective of the lighting analysis is to understand the daylighting and artificial
lighting while acoustic analysis will study acoustic characteristics and acoustic requirements in the case
study. Moreover, the objectives of this project are to determine the characteristics and functions of the
day lighting and artificial lighting as well as sound & acoustic within the space. Finally, another objective
of this project is to critically report and analyse the space based on the data collected.
2
1.2 Journal
1.2.1 Literature Review
1.2.1.1 Architecture Lighting
Importance of Light in Architecture
Light is the most important factor in the appreciation and understanding of Architecture. The
relationship between light and architecture is grounded in the principles of physics; it is about energy
and matter but in this particular case it also implies an emotional effect on people. The word of space is
directly connected to the way light integrates with it. Light interact with us and the environment by our
vision, experience and interpretation on elements. Based on architecture study, in any dimension we
can analyse such as space, material or colour, it is essentially dependent on the lighting situation that
involves both the object and the observer. The dynamic daylight and the controlled artificial lighting are
able to affect not only distinct physical measurable setting in a space but also to instigate and provoke
different visual experiences and moods. In addition, light can perceive different atmospheres in the
same physical environment. It also integrates an element of basic relevance for the design of spaces
which plays a significant role in the discussion of quality in architecture.
Natural Daylighting & Artificial Electrical Lighting
Natural light has always been important for architects. In a way, architects sculpt buildings in order that
the light can play off their different surfaces. If done well, space and light can evoke positive emotional
responses in people. Although architects should always strive towards achieving a building which can
draw in as much natural daylight as possible, it is almost impossible to go on without electrical lighting
taking into consideration in design especially that it need to function both day and night. Moreover,
certain building typologies and uses are not suitable for daylighting such as museums and galleries
because exposure to natural light could damage the artifacts. It is an important understanding of
limitations and opportunities in using natural daylighting as well as artificial lighting and be able to apply
it architecturally to achieve the best performing building.
3
Balance between Science & Art
The balance of science & art will create a visually appropriate light scene accordingly to the character
and use of a space. Sciences of light production and luminaire photometric are important as they are
balanced with the artistic application of light as a medium in our built environment. Electrical lighting
systems and daylighting systems should be integrated together while considering the impacts of it.
There are three fundamental aspects in architectural lighting design for the illumination of building and
spaces, including the aesthetic appeal, ergonomic aspect and energy efficiency of illumination.
Aesthetic appeal focuses on the importance of illumination in retail environments. Ergonomic aspect is
the measurement of how much function the lighting produces. Energy efficiency covers the issue of
light wastage due to over illumination which could happen by unnecessary illumination of spaces or
over providing light sources for aesthetic purposes. Each of these aspects are important when lighting
works are carried out. It allows exploration on the attractiveness of the design by either providing subt le
or strong lighting sources which creates different emotions for the users.
4
Table 1: Daylight Factor and Distribution
1.2.1.2 Daylight Factor
It is a ratio that represents the amount of illumination available indoors relative to the illumination
present outdoors at the same time under overcast skies. Daylight factor is usually used to obtain the
internal natural lighting levels as perceived on a plane or surface, in order to determine the sufficiency
of natural lighting for the users in a particular space to conduct their activities. It is also simply known to
be the ratio of internal light level to external light level, as shown below:
Daylight Factor, DF
Indoor Illuminance, Ei
Outdoor Illuminance, Eo
Where, Ei = Illuminance due to daylight at a point on the indoor working planes,
Eo = Simultaneous outdoor illuminance on a horizontal plane from an unobstructed hemisphere of
overcast sky.
Zone DF (%) Distribution
Very bright > 6 Large (including thermal and glare problem)
Bright 3-6 Good
Average 1-3 Fair
Dark 0-1 Poor
.
5
1.2.1.3 Lumen Method
Lumen method is used to determine the number of lamps that should be installed in a space. This can
be done by calculating the total illuminance of the space based on the number of fixtures and determine
whether or not that particular space has enough lighting fixtures.
The number of lamps can be calculated by the formula below:
Where, N = Number of lamps required
E = Illuminance level required (Lux)
A = Area at working plane height (m2)
F = Average luminous flux from each lamp (lm)
UF = Utilisation factor, an allowance for the light distribution of the luminaire and the room surfaces
MF = Maintenance factor, an allowance for reduced light output because of deterioration and dirt
Room Index, RI, is the ratio of room plan area to half wall area between the working and luminaire
planes.
Which can be calculated by:
Where, L = Length of room
W = Width of room
Hm = Mounting height, the vertical distance between the working plane and the luminaire
6
Figure 1: Location of University Kebangsaan Malaysia
Figure 2: Exterior view of University Kebangsaan Malaysia.
1.2.2 Lighting Precedent Studies
UKM Architecture Studio, University Kebangsaan Malaysia
Lighting can be efficiently used to maximize occupant comfort, and to conserve energy. A good building
design requires sufficient daylight for tasks performed within a space. This is achieved by allowing a
sufficient amount of light to enter the building while blocking direct light from the sun to prevent heat
gain and glare.
At UKM architecture studio, lighting is important to the students as high quality lighting is able to
improve student moods, behavior and concentration which will subsequently affect their learning. As
artificial light is used most of the time in UKM architecture studio to optimize student vision and comfort,
the paper focuses on lighting in UKM architecture studio space in order to achieve better IEQ.
7
Figure 3: Location of data collection as labelled L1, L2 and L3
Figure 4: (left to right) the interior views and exterior perspective of the of the year 3 architecture studio
1.2.2.1 Introduction
The study was conducted firstly by collecting the lighting data and second by a questionnaire survey.
Lighting level was recorded by using the equipment LM-8100 (for physical measurement) and FLUKE
Thermal Imager (for infra-red image). Lighting measurement was taken at 3 specific locations at L1, L2,
and L3 as in Figure 1 and the reading was taken for 11-hours over 2 days at UKM year 3 architecture
studio.
The studio chosen for this study was located on the south of the building with floor area of 182 m2.
Figure 2 shows the interior and exterior views of architecture studio.
.
8
Figure 5: Lighting readings at year 3 studio on day 1 and day 2
studio
1.2.2.2 Result and Discussion
Lighting Analysis
The findings in Figure 4 and 5 show that the lighting measurement at L1, L2 and L3 vary on day 1 and
day 2. The lighting data recorded at L1 on day 1 and day 2 shows the lighting rates are very low
compared to at L2 and L3. From the L1 lighting analysis, it is found that the lighting measurement from
8am to 6pm was in the range of 0 lux close to 100 lux. This means that this location (L1) is not suitable
for working or studying. However, this area is part of the students working area; despite supposedly
being the entrance area only.
At L2 and L3, lighting readings for both locations are within 150lux to 250lux. This level of lighting is still
not in accordance to Malaysian Standard MS 1525:2007, where the appropriate illuminance for drawing
office (studio) is in the range of 300-400 lux.
The lighting results for L1, L2 and L3 for both days show the illuminance in the UKM year 3 architecture
studio is below the standard.
9
1.2.2.3 Questionnaire survey
Questionnaires were distributed to all year 3 architecture students. There are three parameters used to
identify the students’ perspective of lighting comfort level: daylighting, glare, and brightness. The scores
are calculated based on response on the importance of lighting comfort and existing scenario.
Figure 7 shows that daylighting and brightness are perceived as important to the students, but
daylighting is not provided in the studio. The scores show that glare is not important at all (as the case
should be) for them. But in existing scenario, the daylighting is not available. This scenario occurred
because the studio is located far from the sources of sunlight. Moreover, this space is not originally
designed for use as an architecture studio. This is the reason why natural lighting is almost 0% for this
studio.
Figure 6: Day lighting, Glare and Brightness scores votes for all architecture student year 3.
studio
10
1.2.2.4 Matrix of the lighting analysis for UKM architecture studio
The objective of the matrix in Figure 8 is to evaluate the overall results on lighting analysis towards the
IEQ for UKM architecture studio. This study is conducted using 2 methods, namely physical
measurement and survey where the lighting measurement result for indoor studio environment is not up
to standard (poor) and the result of the questionnaire for existing scenario shows that 70% of students
are satisfied with the brightness in the year 3 studio (good). The overall result of the lighting analysis
based on in the matrix shows that UKM year 3 architecture studio need improvement in lighting level.
1.2.2.5 Conclusion
In conclusion, the findings from the measurements show that the lighting level in the year 3 studio is not
within the range of Malaysian Standard MS 1525:2007. However, according to the questionnaires, the
students perceived it as normal (good) and thus are not hindered from staying for long hours inside the
studio. This situation will eventually affect student’s health as it will have a negative impact on their
vision.
The overall result presented in the matrix indicates that the lighting in year 3 studio “Needs
Improvement”. The improvement is needed on the lighting level for UKM architecture studio to achieve
a better IEQ scenario.
Figure 7: Matrix of the lighting analysis for UKM architecture studio studio
11
1.3 Research Methodology
1.3.1 Measuring Device
- Digital Lux Meter
Lux meter is an electronic equipment for measuring luminous flux per unit area. It is used to measure
the illuminance level. This device is sensitive to illuminance and accurate for the reading.
Features:
- High accuracy in measuring.
- Sensor COS correction factor meets standard.
- LSI circuit provides high reliability and durability.
- LCD displays use backlighting to enable low light measurement reading.
- Easy to carry out and operate.
12
- Camera
Camera was used to capture the lighting condition and lighting appliances to our case study café.
- Measuring Tape
Measuring tape was used to measure the height of the position of the lux meter at 1.5m high to ease
the data collection for light illuminance level. It is also used to measure the 1.5m x 1.5m grid on the
floor while talking the reading.
13
1.3.2 Data Collection Method
In prior to the data collection, 1.5m x 1.5m gridline are drawn on the floor plan perpendicularly as a
guideline to record the reading. In order to collect accurate reading, both hands are used to optimally
position the photo-detector and the module at the same height from the floor at every point which is
1.5m. This standard was used to ensure the data collected to be accurate. Each recording was done by
facing similar direction to achieve consistent result. The lux meter level should be facing upward and
the person holding it should not block the source of light that will fall on the sensor probe for accurate
result. The process is then repeated for several times in different zones to achieve a minimum reading
of the light.
Figure 8: 1.5x1.5 grid line marked on the plan
14
1.4 Case Study
Located right next to Main Place mall in USJ, AM/PM is a cozy café where people come to have coffee
and cakes. Occupying two floors, AM/PM Cafe has one floor that is suitable for having functions and
events. The 1st floor sits up to 60 people and is set within a cafe setting.
The café is also located at the sidewalk where it is accessible directly from the street. Therefore, the
source of noise could be coming from the vehicle on the street and might affect the acoustic comfort of
the café and give discomfort to the user.
ZONE A: Outdoor Dining Area ZONE D: Semi Outdoor Dining
ZONE B: Dining Room ZONE E: Dining Area
ZONE C: Food and Beverages Preparation area ZONE F: Study/Reading area
Figure 9: Zoning of areas in ground floor and first floor plan
15
‘
Zone A: Outdoor Dining Area
Zone B: Dining Room
Zone C: Study/Reading area
Zone D: Semi Outdoor Dining
Zone E: Dining Area
ZONE F: Food and Beverages Preparation area
16
1.4.1 Data Collection
The lux meter readings at a height of 1m and 1.5m are recorded at each grid point (1.5m x 1.5m)
marked on the ground floor and first floor plans at 11am, 4pm, and 9pm.
Figure 10: Lux meter readings at 11am
0
17
Figure 11: Lux meter readings at 4pm
18
Figure 12: Lux meter readings at 9pm
19
1.4.2 Limitation & Constraint
Human Error
Different holding position of the sensor of the meter might affect the data collection on site.
Natural Causes
Whether are the main natural causes that had cause inaccuracy of the lux value on site. This is
because the weather changes during the period of the time during the recording of the measurement.
Zone Limitation
Some areas are inaccessible, thus not all areas were recorded. The areas include the kitchen and food
storage space.
Device Error
Reading taken before the stabilized value might cause readings taken to be inaccurate.
20
1.5 Lighting Analysis
1.5.1 Tabulation of data
Daytime lux meter reading at 11am - 1pm
Zone A: Outdoor dining area 1
Zone B: Indoor dining area 1
Zone C: Bartender/ F&B preparation area
Zone D: Semi-outdoor dining area
Zone E: Indoor dining area 2
Zone F: Reading area
21
Daytime lux meter reading at 4pm – 6pm
22
Nightime lux meter reading at 9pm – 10pm
23
1.5.1.1 Data Findings at the Zones
Zone A – Outdoor dining area 1
AREA GRIDLINE Morning (11am – 1pm)
Evening (4pm – 6pm)
Night ( 9pm – 10pm)
1.0 M 1.5 M 1.0 M 1.5 M 1.0 M 1.5 M
Ground floor
Zone A
J1 93 150 78 130 63 75
J2 50 101 42 98 33 48 J3 56 73 49 54 37 46
J4 56 65 47 52 34 49
K1 130 150 98 137 88 121
K2 154 250 45 56 26 50
K3 169 131 48 68 33 45 K4 18 24 12 24 13 23
L1 150 360 82 128 62 118
L2 100 320 63 82 54 80
L3 70 200 52 72 33 47
L4 17 20 5 8 4 7 M1 900 950 373 425 62 85
M2 780 900 232 393 74 105
M3 650 880 138 295 51 95
M4 421 740 192 305 67 102
Figure 13: Floor plan of zone A
Table 1: Lux meter reading in zone A
24
Zone B- Indoor dining area 1
AREA GRIDLINE Morning (11am – 1pm)
Evening (4pm – 6pm)
Night ( 9pm – 10pm)
1.0 M 1.5 M 1.0 M 1.5 M 1.0 M 1.5 M Ground
floor
Zone B
D2 105 137 103 128 93 121
D3 17 22 13 19 14 17
D4 170 123 166 95 160 90
E2 93 112 67 81 55 58 E3 8 16 7 13 8 11
E4 53 68 31 53 26 45
F3 14 23 13 19 11 17
F4 68 78 53 77 48 78
G3 58 42 22 33 23 34 G4 140 216 107 125 98 102
H3 50 62 31 39 26 32
H4 210 227 163 165 131 152
I 3 139 145 95 112 49 52
I 4 106 140 103 132 98 129
Figure 14: Floor plan of zone B
Table 2: Lux meter readings in zone B
25
Zone C- Bartender/F&B area
AREA GRIDLINE Morning (11am – 1pm)
Evening (4pm – 6pm)
Night ( 9pm – 10pm)
1.0 M 1.5 M 1.0 M 1.5 M 1.0 M 1.5 M
Ground floor
Zone C
F1 211 185 170 163 160 152 F2 68 75 50 60 60 48
G1 85 95 72 84 68 78
G2 42 79 37 53 29 40
H1 85 137 82 122 79 107 H2 60 106 56 98 69 87
I 1 111 120 77 106 72 90
I 2 180 115 155 107 127 99
Figure 15: Floor plan of zone C
Table 3: Lux meter readings in zone C
26
Zone D- Semi-outdoor dining area
First floor
ZONE D
(Semi outdoor dining)
L1 195 401 188 191 98 163 L2 239 327 121 205 88 129
L3 75 284 68 118 42 78
L4 155 192 125 132 68 `104
M1 1200 1545 385 628 39 82
M2 1280 1320 420 604 26 31 M3 730 980 348 393 19 28
AREA GRIDLINE Morning (11am – 1pm)
Evening (4pm – 6pm)
Night ( 9pm – 10pm)
1.0 M 1.5 M 1.0 M 1.5 M 1.0 M 1.5 M
Figure 16: Floor plan of zone D
Table 4: Lux meter readings in zone D
27
Zone E- Indoor dining area 2
First floor
Zone E
F1 28 35 16 26 11 17 F2 239 290 186 195 182 190
F3 29 38 24 33 23 26
G1 34 37 19 22 33 37
G2 88 108 72 80 55 62
G3 35 48 37 45 32 37 H1 37 32 35 26 22 19
H2 68 75 52 64 53 59
H3 44 55 39 40 29 37
I1 70 81 43 45 20 36 I2 58 70 37 67 32 41
I3 48 64 31 47 29 43
J1 69 115 33 56 30 33
J2 64 68 51 58 49 52
J3 91 82 29 40 19 23 J4 73 85 45 50 32 49
K1 48 106 42 68 31 65
K2 108 113 58 95 49 63
K3 193 270 30 44 23 26 K4 120 80 32 73 31 68
AREA GRIDLINE Morning (11am – 1pm)
Evening (4pm – 6pm)
Night ( 9pm – 10pm)
1.0 M 1.5 M 1.0 M 1.5 M 1.0 M 1.5 M
Figure 17: Floor plan of zone E
Table 5: Lux meter readings in zone E
28
Zone F- Reading area
First floor
Zone F
(Reading area)
A1 67 93 18 42 13 28
A2 61 98 34 53 27 35
A3 56 85 23 46 24 40
A4 188 191 156 182 135 175 B1 29 34 23 35 22 23
B2 85 100 71 82 60 67
B3 86 86 66 81 50 66
B4 230 393 211 344 99 190
C1 48 51 34 47 32 44 C2 82 66 48 63 17 57
C3 86 70 48 61 41 46
C4 175 246 120 152 73 218
D1 23 38 22 26 24 26 D2 66 91 62 84 58 72
D3 67 78 62 74 48 58
D4 126 225 78 85 54 67
E1 25 36 23 32 23 28
E2 72 90 70 77 56 63 E3 88 150 82 111 78 84
AREA GRIDLINE Morning (11am – 1pm)
Evening (4pm – 6pm)
Night ( 9pm – 10pm)
1.0 M 1.5 M 1.0 M 1.5 M 1.0 M 1.5 M
Figure 18: First Floor – Reading area
Table 6: Lux meter readings in zone F
29
1.5.2 Sun path diagram
Note that the orientation of the building is north-south orientation and is place in between two buildings.
Sun path diagram at 11am
The position of the sun at 11am is at the East side which exposes the incident sunlight to zone A, zone D
and zone F. Thus, the sunlight receives by the zones during those hour is very efficient. However, due to
some glaring problem the café has installed wooden blinds at each opening in the café which can be used
to prevent the excessive amount of sunlight from penetrating in to the zones.
Affected areas
Figure 19: Sun path diagram at 11am
Figure 20: Floor plan
30
Sun path diagram at 4pm
The position of the sun at 4pm is at the West side which also exposes the incident sunlight to zone A, zone
D and zone F. However, even though, it is being exposed to incident sunlight, the sky condition affects the
amount of sunlight receives during that day. Artificial lights may still be needed to at certain hour of the day
to supply lights to the zones. Due to only having opening on the north and south sides of the building, the
amount of daylight that enters may sometimes not be sufficient enough to light up the space in the evening.
Figure 21: Sun path diagram at 4pm
Figure 22: Floor plan
Affected areas
31
1.5.3 Natural Lighting Analysis
1.5.3.1 Daylight factor Calculation
The daylight factor was analyzed at 2 different hours, 11am to 1pm and 4pm to 6pm.
Note that the sky during 11am to 1 pm is overcast sky whereas the sky at 4pm to 6pm is cloudy sky.
Zone A (Gridline J-M)
Time Weather Luminance at 1m
Average Luminance at 1.5m
Average
11am Clear sky 17-900 238.4 20-950 332.1
4pm Overcast sky 5-373 51.5 8-425 64.3
Average lux reading 11am 4pm
1m 238.4 51.5 1.5m 332.1 64.3
Illuminance Example
120,000 lux Brightest sunlight
110,000 lux Bright sunlight 20,000 lux Shade illuminated by entire clear blue sky, midday
1,000- 2,000 lux Typical overcast day, midday
<200 lux Extreme of darkest storm clouds, midday
400 lux Sunrise or sunset on a clear day (ambient illumination)
40 lux Fully overcast sunset/sunrise < 1 lux Extreme of darkest storm cloud, sunset/rise
Figure 23: Ground floor: Outdoor seating area 1
32
Daylight factor calculation formula:
D = E internal __________ x 100%
E external
Time 11am
Average lux reading at 1m (Internal) 238.4
Standard direct sunlight 20,000 lux
Calculation D = 238.4 _______ x 100% 20,000 = 1.1
Average lux reading at 1.5 m (Internal) 332.1
Standard direct sunlight 20,000 lux
Calculation D = 332.1 _______ x 100%
20,000
= 1.6
Time 4pm
Average lux reading at 1m (Internal) 51.5
Standard direct sunlight 6600 lux
Calculation D = 51.5 _______ x 100% 6600 = 0.7
Average lux reading at 1.5 m (Internal) 64.3
Standard direct sunlight 6600 lux
Calculation D = 64.3 _______ x 100%
6600
= 0.9
DF,% Distribution >6 Very bright, with thermal and glare problem
3-6 Bright
1-3 Average
0-1 Dark
33
Discussion
Zone A is located at the south area of the building and it is an outdoor seating area. Due to the location on
the outdoor area, zone A manages to receive a decent amount of sunlight at 11am with percentage of 1.1%
and 1.6% which is considered as an average. Thus, it does not need any artificial lighting to light up the
space in the morning whereas, the percentage of daylight factor decreases in the evening at 0.7% and
0.9% due to the sky condition (overcast sky) and also limited amount of sunlight coming in. The percentage
falls under the dark distribution area. Even though, it does not receive lots of sunlight in the evening, the
zone can still be use without artificial lighting, as zone A is open to the outdoor facing the street and lights
coming from every direction and reflected from the ground light.
34
Zone B (Gridline D-I)
Time Weather Luminance at 1m
Average Luminance at 1.5m
Average
11am Clear sky 8-210 87.9 16-227 49.3
4pm Overcast sky 7-166 51.5 19-165 64.3
Average lux reading 11am 4pm
1m 87.9 49.3 1.5m 263.4 12.5
Illuminance Example
120,000 lux Brightest sunlight
110,000 lux Bright sunlight 20,000 lux Shade illuminated by entire clear blue sky, midday
1,000- 2,000 lux Typical overcast day, midday
<200 lux Extreme of darkest storm clouds, midday
400 lux Sunrise or sunset on a clear day (ambient illumination)
40 lux Fully overcast sunset/sunrise < 1 lux Extreme of darkest storm cloud, sunset/rise
Figure 24: Ground floor: Indoor seating area 1
35
Daylight factor calculation formula:
D = E internal __________ x 100%
E external
Time 11am
Average lux reading at 1m (Internal) 87.9
Standard direct sunlight 20,000 lux
Calculation D = 87.9 _______ x 100% 20,000 = 0.5
Average lux reading at 1.5 m (Internal) 263.4
Standard direct sunlight 20,000 lux
Calculation D = 263.4 _______ x 100%
20,000
= 1.3
Time 4pm
Average lux reading at 1m (Internal) 49.3
Standard direct sunlight 6600 lux
Calculation D = 49.3 _______ x 100% 6600 = 0.4
Average lux reading at 1.5 m (Internal) 12.5
Standard direct sunlight 6600 lux
Calculation D = 12.5 _______ x 100%
6600
= 0.3
DF,% Distribution
>6 Very bright, with thermal and glare problem
3-6 Bright
1-3 Average 0-1 Dark
36
Discussion
Zone B is located inside of the café on the ground floor and it is where the dining area is located. Due to the
building is located between the buildings, the only access for the sunlight is through the south (front façade)
and north (rear façade). The café locates its kitchen at the rear area thus it does not allow any sunlight to
come in to zone B except from the front façade. Due to limited openings, zone B could not receive sufficient
amount of daylight and have to depend on the artificial lights to operate the space. The outcome of the data
shows at 11am the daylight factor falls under average (1.3%) and dark (0.5%) whereas at 4pm the daylight
factor is considered dark (0.4% and 0.3%) and also due to the sky condition during that day. Note that
some of the front part of the zone receives some daylight whereas the back part of the zone depends totally
on artificial lighting.
37
Zone C (Gridline F-I)
Time Weather Luminance at 1m
Average Luminance at 1.5m
Average
11am Clear sky 42-211 105.3 75-185 114
4pm Overcast sky 37-170 10.1 53-163 11.5
Average lux reading 11am 4pm
1m 105.3 10.1 1.5m 114 11.5
Illuminance Example
120,000 lux Brightest sunlight
110,000 lux Bright sunlight
20,000 lux Shade illuminated by entire clear blue sky, midday 1,000- 2,000 lux Typical overcast day, midday
<200 lux Extreme of darkest storm clouds, midday
400 lux Sunrise or sunset on a clear day (ambient illumination)
40 lux Fully overcast sunset/sunrise < 1 lux Extreme of darkest storm cloud, sunset/rise
Daylight factor calculation formula:
D = E internal __________ x 100%
E external
Figure 25: Ground floor: Food preparation area
38
Time 11am
Average lux reading at 1m (Internal) 105.3
Standard direct sunlight 20,000 lux
Calculation D = 105.3 _______ x 100% 20,000 = 0.5
Average lux reading at 1.5 m (Internal) 114
Standard direct sunlight 20,000 lux
Calculation D = 114 _______ x 100%
20,000
= 0.57
Time 4pm
Average lux reading at 1m (Internal) 10.1
Standard direct sunlight 6600 lux
Calculation D = 10.1 _______ x 100% 6600 = 0.15
Average lux reading at 1.5 m (Internal) 11.5
Standard direct sunlight 6600 lux
Calculation D = 11.5 _______ x 100%
6600
= 0.17
DF,% Distribution
>6 Very bright, with thermal and glare problem
3-6 Bright
1-3 Average 0-1 Dark
39
Discussion
Zone C is also located inside the café and is divided by glass window to allow daylight to enter to the area.
Based on the data collected at 11am the daylight factor are 0.5% and 0.57% this is due to the sunlight
coming in through the glass window whereas the daylight factor at 4pm are 0.15% and 0.17%. The
percentage declines due to the sky condition during that day. The area needs support from artificial lights to
supply sufficient amount of light on that area due to it being a bartender and preparing food area for the
customers which needs at least 2% to be considered average. Zone C and zone B receives alm ost the
same amount of the daylight due to its location being close to each other.
40
Zone D (Gridline L-M)
Time Weather Luminance at 1m
Average Luminance at 1.5m
Average
11am Clear sky 75-1280 553.4 284-1545 721.3 4pm Overcast sky 68-420 125 118-628 180
Average lux reading 11am 4pm
1m 553.4 125
1.5m 721.3 180
Illuminance Example
120,000 lux Brightest sunlight
110,000 lux Bright sunlight
20,000 lux Shade illuminated by entire clear blue sky, midday
1,000- 2,000 lux Typical overcast day, midday <200 lux Extreme of darkest storm clouds, midday
400 lux Sunrise or sunset on a clear day (ambient illumination)
40 lux Fully overcast sunset/sunrise
< 1 lux Extreme of darkest storm cloud, sunset/rise
Daylight factor calculation formula:
D = E internal __________ x 100%
E external
Figure 26: First floor- Semi-outdoor area
41
Time 11am
Average lux reading at 1m (Internal) 553.4
Standard direct sunlight 20,000 lux
Calculation D = 553.4 _______ x 100% 20,000 = 2.7
Average lux reading at 1.5 m (Internal) 721.3
Standard direct sunlight 20,000 lux
Calculation D = 721.3 _______ x 100%
20,000
= 3.6
Time 4pm
Average lux reading at 1m (Internal) 125
Standard direct sunlight 6600 lux
Calculation D = 125 _______ x 100% 6600 = 1.9
Average lux reading at 1.5 m (Internal) 180
Standard direct sunlight 6600 lux
Calculation D = 180 _______ x 100%
6600
= 2.7
DF,% Distribution
>6 Very bright, with thermal and glare problem
3-6 Bright
1-3 Average 0-1 Dark
42
Discussion
Zone D receives sufficient amount of daylight due to it being located on the first floor, having large openings
(8 window panels) and facing the front façade. Based on the data collected at 11am the daylight factor
percentage falls under average (2.7%) and bright (3.6%) whereas the percentage at 4pm falls under
average only (1.9% and 2.7%). In the morning and evening, the zone can be function without using any
artificial lights. Even though, it manages to supply sufficient amount of daylight in the zone, sometimes
glaring is a problem due to the reflective sunlight coming from the opposite shopping mall which uses glass
as part of its building.
43
Zone F (Gridline A-E)
Time Weather Luminance at 1m
Average Luminance at 1.5m
Average
11am Clear sky 23-230 92.1 34-246 121.6
4pm Overcast sky 18-211 15.8 26-344 91
Average lux reading 11am 4pm
1m 92.1 15.8
1.5m 121.6 21.3
Illuminance Example
120,000 lux Brightest sunlight 110,000 lux Bright sunlight
20,000 lux Shade illuminated by entire clear blue sky, midday
1,000- 2,000 lux Typical overcast day, midday
<200 lux Extreme of darkest storm clouds, midday 400 lux Sunrise or sunset on a clear day (ambient illumination)
40 lux Fully overcast sunset/sunrise
< 1 lux Extreme of darkest storm cloud, sunset/rise
Figure 27: First floor- Study/reading area
44
Daylight factor calculation formula:
D = E internal __________ x 100%
E external
Time 11am
Average lux reading at 1m (Internal) 92.1
Standard direct sunlight 20,000 lux
Calculation D = 92.1 _______ x 100% 20,000 = 0.4
Average lux reading at 1.5 m (Internal) 121.6
Standard direct sunlight 20,000 lux
Calculation D = 121.6 _______ x 100%
20,000
= 0.6
Time 4pm
Average lux reading at 1m (Internal) 15.8
Standard direct sunlight 6600 lux
Calculation D = 15.8 _______ x 100% 6600 = 0.2
Average lux reading at 1.5 m (Internal) 21.3
Standard direct sunlight 6600 lux
Calculation D = 21.3 _______ x 100%
6600
= 0.3
DF,% Distribution
>6 Very bright, with thermal and glare problem
3-6 Bright
1-3 Average 0-1 Dark
45
Discussion
Zone F receives 0.4% and 0.6% daylight factor at 11am and 0.2% and 0.3% at 4pm. Base on its location,
which is at the rear area of the building, zone F should be receiving sufficient amount of daylight as it is
close to the windows which have large openings but the owner of the restaurant decided to pull down the
wooden blind in zone F the most of the time as to consider the customers privacy due to the back building
located quite close to each other. Thus, zone F does not receive much sunlight and it needs artificial lights
to brighten up the space.
46
1.5.3.2 Lighting Diagrammatic Analysis (Daylight)
Sectional diagram shows the amount and way of the daylight penetrates into the building. Zone A and zone
D receives ample amount of light due to it being at the front area of the building where as Zone F at the
back receives low amount sunlight. The middle part of the café only receives partial amount of sunlight thus
it requires artificial light to brighten up the area. The café does not have any openings in the middle to allow
sunlight to penetrate into the spaces. Sometimes, due to glaring from the opposite mall, wooden blinds are
pulled down at the front façade to decrease the problem.
Figure 28: Section A-A
Front Rear
47
1.5.4 Artificial Lighting Analysis
1.5.4.1 Identification of Lighting Fixture
Type of lighting fixture Ceiling Mounted Downlight Type of light bulb Compact Fluorescent Lamp Integrated (CFL)
Dimension, mm 160 x 49
Lamp Wattage, W 20 W
Colour Rendering Index, Ra 82 Ra
Colour Temperature, K 2730 K Colour Designation Cool White
Lumens, LM 1200 Lm
Rated Life, H 10 000 hours
Cap Base E 27
Type of lighting fixture Pendant Light
Type of light bulb Incandescent bulb – Tungsten Filament
Dimension, mm 250 mm x 150 mm
Lamp Wattage, W 40 W Colour Rendering Index, Ra 100 Ra
Colour Temperature, K 2100 K
Colour Designation Warm White
Lumens, LM 130 lm Rated Life, H 30 000 hours
Cap Base E 27
48
Type of lighting fixture Track light Type of light bulb Halogen
Dimension, mm 77mm x 50mm
Lamp Wattage, W 40 W
Colour Rendering Index, Ra 82 Ra Colour Temperature, K 2700 K
Colour Designation Warm White
Lumens, LM 800 Lm
Rated Life, H 2000 hours
Cap Base E 14
Type of lighting fixture Wall Light Type of light bulb Incandescent bulb
Dimension, mm 532 mm x 138 mm
Lamp Wattage, W 60 W
Colour Rendering Index, Ra 100 Ra Colour Temperature, K 2700 K
Colour Designation Warm White
Lumens, LM 245 Lm
Rated Life, H 3000 hours
Cap Base E 26
49
1.5.4.2 Artificial Light Location on Floor plan
50
Figure 29: Floor plan of zone A
1.5.4.3 Material Reflectance Index
Zone A - Outdoor Dining
Element Material Colour Surface Finish
Reflectance Value
Area, 𝑚2
W A L
L
Concrete Grey Matte 25 18.37
Brick Red Matte 20 16.3
C E I
L I
N G
Concrete Dark Grey
Luster 15 26.2
51
F L O O
R
Ceramic Grey Glossy 60 26.2
DOOR
Glass Clear Smooth 8 20.87
F U R N
I T U R E
Wooden Brown Glossy 35 6
Wooden
Brown Glossy 35
Table 7: Reflectance value for components in zone A
52
Figure 30: Floor plan of zone B
Zone B - Dining Area 1
Components Material Colour Surface Finish
Reflectance Value
Area,
𝑚2
W A
L L
Concrete Grey Matte 25 38.48
Fly Ash Brick (FAB)
Grey
Matte 25 11.47
Brick Red Matte 20 8.88
53
C E I L I
N G
Concrete Dark Grey
Luster 15 37.04
F L O O
R
Ceramic Grey Glossy 60 37.04
D O O R
Glass Clear Smooth 8 8.75
F U R
N I T U R E
Cushion Green and Yellow
Luster 50 14.54
Wooden Brown
Glossy 15 4.9
Wooden Light brown Glossy 35 2.9
Table 8: Reflectance value for components in zone B
54
Figure 31: Floor plan of zone C
Zone C – Bartender/ F&B area/
Components Material Colour Surface Finish
Reflectance Value
Area,
𝑚2
W A L L
Concrete Grey Matte 25 6
Porcelain White Glossy 70 6
Fly Ash Brick (FAB)
Grey
Matte 25 7.03
55
C E I L I
N G
Concrete Dark Grey
Luster 15 14.4
F
L O O R
Ceramic White Luster 70 14.4
D O O R
Glass Clear Smooth 8 6.48
F U R N I T U
R E
Concrete Light Grey
Luster 40 6.3
Wooden Black Luster 15 2.6
Table 9: Reflectance value for components in zone C
56
Zone D- Semi outdoor dining area
Component Material Colour Surface Finish Reflectance Value
Area,
𝑚2
W A L L
Concrete Grey Matte 25 14
Brick Red Matte 20 21
C E I L
I N G
Concrete Dark Grey
Luster 15 20.6
Figure 32: Floor plan of zone D
57
F L O O
R
Ceramic Grey Glossy 60 20.6
W I
N D O
W
Glass Clear Smooth 8 4.8
D O O R
Glass Clear Smooth 8 21.91
F U
R N I T U R E
Wooden Brown Luster 15
5.88
Wooden
Brown Luster 15
Table 10: Reflectance value for components in zone D
58
Figure 34: Floor plan of zone E
Zone E- Indoor dining area
Components Material Colour Surface Finish Reflectance Value
Area,
𝑚2
W A L L
Concrete Grey Matte 25 21.7
Plastered Black Matte 10 36.5
C E I L
I N G
Concrete Dark Grey
Luster 15 36.6
59
F L O O
R
Ceramic Grey Luster 60 36.6
D O
O R
Glass Clear Smooth 8 21.91
P A R
T I T I
O N
Glass Semi-clear Smooth 15 5.5
F U R N I
T U R E
Wooden Brown Glossy 35
12.4
Wooden
Brown Glossy 15
60
Wooden Brown Matte 25 1.38
Table 11: Reflectance value for components in zone E
61
Figure 35: Floor plan of zone F
Zone F- Reading area
Element Material Colour Surface Finish
Reflectance Value
Area,
𝑚2
W A L L
Concrete Grey Matte 25 22.05
Brick Red Matte 20 17.4
Plastered White Luster 80 32.0
62
C E I L I
N G
Concrete Grey
Luster 15 47.4
F L O O R
Ceramic Grey Glossy 60 47.4
W I
N
D O W S
Blinds Bamboo Luster 15 15.44
P A
R T I T I
O N
Glass Semi-clear Smooth 15 5.5
F U R N I T U
R E
Cushion Green Yellow Purple
Luster 50 14.54
63
Wooden and Cushion
Green and Purple
Luster 50 5.4
Table 12: Reflectance value for components in zone F
64
1.5.4.4 Lumen Method Calculation for Artificial Light
Zone A: Outdoor Dining
Space Dimension (m) 5.3 x 4.5
Total floor area (𝑚2) 23.85
Type of lighting fixture Tracklight Downlight Pendant Light No. of lighting fixtures / N 6 2 10
Lumens of lighting fixtures / F (Lm)
800 1200 130
Height of luminaire (m) 3.7 3.7 2.7
Work Level (m) 0.75 0.75 0.4
Mounting height (𝐻𝑚) 2.95 2.95 2.3
Assumption of Reflectance Value
Ceiling = 0.15 Wall = 0.25 Floor = 0.6
Room Index / RI
RI = 𝐿 𝑋 𝑊
𝐻𝑚(𝐿+𝑊)
5.3 x 4.5
2.95 (5.3 + 4.5)
= 0.82
5.3 x 4.5
2.95 (5.3 + 4.5)
= 0.82
5.3 x 4.5
2.3 (5.3 + 4.5)
= 1.06
Utilization Factor, UF 0.43 0.43 0.48
Maintenance Factor, MF 0.8
Illuminance level, Lux
E = 𝑁 ( 𝐹 𝑋 𝑈𝐹 𝑋 𝑀𝐹)
𝐴
6(800 x 0.43 x 0.8)
23.85
= 69.23
2(1200 x 0.43 x 0.8)
23.85
= 34.62
10(130 x 0.43 x 0.8)
23.85
= 18.75
Figure 36: Position of artificial lights in zone A
65
Total Illuminance level, Lux
122.6
Standard illuminance, Lux
200
Required illuminance, Lux
200 – 122.6 = 77.4
No. of light required to reach the required illuminance
N = 𝐸 𝑋 𝐴
𝐹 𝑋 𝑈𝐹 𝑋 𝑀𝐹
77.4 x 23.85
800 x 0.43 x 0.8
= 6.7 ≈ 7
77.4 x 23.85
1200 x 0.43 x 0.8
= 4.5 ≈ 5
77.4 x 23.85
130 x 0.48 x 0.8
= 36.9 ≈ 37
Spacing requirement for light fitting (m)
S = 1.0 x 𝐻𝑚 (Direct Light)
S = 1.0 x 2.95 = 2.95
S = 1.0 x 2.95 = 2.95
S = 1.0 x 2.3 = 2.3
66
Discussion
The dining area can be counted as an outdoor meeting space whereby it is quite open to the recessed five-
foot way. Being partially exposed, light from street as well as the brightly lit shopping mall located just
opposite of the café might contribute little illuminance to the space. The material being used in this area is
mostly of low reflectance compromising of brick walls, concrete walls and concrete plastered ceiling. Thus it
does not assist much in illuminating the space. According to MS1525, The standard illuminance level of a
dining area is 200 lux. However, based on the calculations tabulated, the total illuminance level of Zone A is
122.6 lux whereby it does not meet the MS1525 room illuminance standard. Another 77.4 lux is required to
achieve the desired illuminance of 200 lux.
Type of Lighting Fixtures:
Fixture Tracklight Downlight Pendant light Type of bulb Halogen Compact fluorescent
lamp (CFL) Incandescent bulb
Number of additional lightings required:
Fixture Tracklight Downlight Pendant light
No. of light 7 5 37
As for the lighting fixtures, zone A uses mostly halogen bulbs to light up the space which has a high lumen
index of 800 Lm, high CRI value of 82Ra and moderate colour temperature of 2700K which radiates warm
white illuminance to the space. Zone A utilizes a mixture of ambient lighting and accent lighting to illuminate
its space. By using a formula, the number of light required to achieve the desired illuminance is calculated
according to the type of lighting fixtures.
Energy efficiency wise, instead of having an additional 37 pendant lights / 7 tracklights to achieve the
required lux, a suggestion of 5 downlights can be used in order to minimize energy consumption.
Depending on the ambience the space would like to achieve, the interplay of lighting fixtures (tracklight,
downlight, pendant light) can be done accordingly to suit the mood.
In order to ensure illuminance does not fall below a minimum value, the fittings must be placed in a regular
grid pattern and their spacing must not exceed certain distances. A proposed spacing of 2.95m for
tracklight, 2.95m for downlight and 2.3m for pendant light can be used.
67
Zone B : Dining area 1
Space Dimension (m) 9.1 x 4.1
Total floor area (𝑚2) 37.3
Type of lighting fixture Tracklight No. of lighting fixtures / N 15
Lumens of lighting fixtures / F (Lm)
800
Height of luminaire (m) 3.7
Work Level (m) 0.75
Mounting height (𝐻𝑚) 2.95
Assumption of Reflectance Value
Ceiling = 0.15 Wall = 0.25 Floor = 0.6
Room Index / RI
RI = 𝐿 𝑋 𝑊
𝐻𝑚(𝐿+𝑊)
9.1 x 4.1
2.95 (9.1 + 4.1)
= 0.96
Utilization Factor, UF 0.48
Maintenance Factor, MF 0.8
Illuminance level, Lux
E = 𝑁 ( 𝐹 𝑋 𝑈𝐹 𝑋 𝑀𝐹)
𝐴
15(800 x 0.48 x 0.8)
37.3
= 123.54
Total Illuminance level, Lux
123.54
Figure 37: Position of artificial lights in zone B
68
Standard illuminance, Lux
200
Required illuminance, Lux
200 – 123.54 = 76.46
No. of light required to reach the required illuminance
N = 𝐸 𝑋 𝐴
𝐹 𝑋 𝑈𝐹 𝑋 𝑀𝐹
76.46 x 37.3
800 x 0.48 x 0.8
= 9.28 ≈ 10
Spacing requirement for light fitting (m)
S = 1.0 x 𝐻𝑚 (Direct Light)
S = 1.0 x 2.95 = 2.95
69
Discussion
The indoor dining area of zone B is the most highly used space on daily basis. Thus, it is important that this
space provides comfort for its users. Having a full length glass partition and door on its front façade enables
light from zone B to be reflected and penetrate through the space in zone B.
According to MS1525, The standard illuminance level of a dining area is 200 lux. However, based on the
calculations tabulated, the total illuminance level of Zone B is 125.5 lux whereby it does not meet the
MS1525 room illuminance standard. Another 76.46 lux is required to achieve the desired illuminance of 200
lux.
Type of Lighting Fixtures :
Fixture Tracklight Type of bulb Halogen
Number of additional lightings required :
Fixture Tracklight
No. of light 10
The entire of zone B uses tracklights to illuminate its space in order to achieve a poetic and laidback
ambience to the area. Halogen bulbs of 800 Lm, high CRI value of 82Ra and moderate colour temperature
of 2700K is used which radiates warm white illuminance to the space.
By using a formula, the number of light required to achieve the desired illuminance is calculated according
to the type of lighting fixtures. An additional 10 tracklights is required to achieve the required lux to meet
MS1525 standards. Zone B focuses more on accent lighting where the light focuses on a particular area
and objects which adds ‘drama’ to the area by creating visual interest, this creates a poetic and comfortable
ambience for customers to enjoy their meal.
In order to ensure illuminance does not fall below a minimum value, the fittings must be placed in a regular
grid pattern and their spacing must not exceed certain distances. A proposed spacing of 2.95m for
tracklight is required to achieve an optimal illuminance.
70
Zone C: Bartender/ F&B Preparation
Space Dimension (m) 6.0 x 2.4
Total floor area (𝑚2) 14.4
Type of lighting fixture Tracklight Downlight Pendant Light No. of lighting fixtures / N 8 3 8
Lumens of lighting fixtures / F (Lm)
800 1200 130
Height of luminaire (m) 3.7 3.7 2.7
Work Level (m) 0.75 0.75 1.2
Mounting height (𝐻𝑚) 2.95 2.95 1.5
Assumption of Reflectance Value
Ceiling = 0.15 Wall = 0.32 Floor = 0.6
Room Index / RI
RI = 𝐿 𝑋 𝑊
𝐻𝑚(𝐿+𝑊)
6.0 x 2.4
2.95 (6.0 + 2.4)
= 0.58
6.0 x 2.4
2.95 (6.0 + 2.4)
= 0.58
6.0 x 2.4
2.3 (6.0 + 2.4)
= 0.75
Utilization Factor, UF 0.35 0.35 0.43
Maintenance Factor, MF 0.8
Illuminance level, Lux
E = 𝑁 ( 𝐹 𝑋 𝑈𝐹 𝑋 𝑀𝐹)
𝐴
8(800 x 0.35 x 0.8)
14.4
= 124.4
8(1200 x 0.35 x 0.8)
14.4
= 186.67
10(130 x 0.43 x 0.8)
14.4
= 31.06
Total Illuminance level, Lux
342.13
Standard illuminance, Lux
300
Figure 38: Position of artificial lights in zone C
71
Required illuminance, Lux
342.13 – 300 = 42.13 (excess)
No. of light required to reach the required illuminance
N = 𝐸 𝑋 𝐴
𝐹 𝑋 𝑈𝐹 𝑋 𝑀𝐹
42.13 x 14.4
800 x 0.35 x 0.8
= 2.7 ≈ 3 (excess)
42.13 x 14.4
1200 x 0.35 x 0.8
= 1.8 ≈ 2 (excess)
42.13 x 14.4
130 x 0.43 x 0.8
= 5.6 ≈ 6 (excess)
Spacing requirement for light fitting (m)
S = 1.0 x 𝐻𝑚 (Direct Light)
S = 1.0 x 2.95 = 2.95
S = 1.0 x 2.95 = 2.95
S = 1.0 x 1.5 = 1.5
72
Discussion
Functioning as a food and beverages preparation area, zone C is the most critical area in the café which
requires the highest illuminance on a daily basis in order to function. For such a small floor area, zone C
has the highest number of lighting fixtures as compared to zone A and B. According to MS1525, The
standard illuminance level of food and beverages preparation area is 300 lux. However, based on the
calculations tabulated, the total illuminance level of Zone C is 342.13 lux whereby it exceeds the MS1525
room illuminance standard. Zone C is thereby brightly lit where its illuminance exceeds 42.13 from the
optimal illuminance due to the redundance of lighting fixtures in the area.
Type of Lighting Fixtures:
Fixture Tracklight Downlight Pendant light Type of bulb Halogen Compact fluorescent
lamp (CFL) Incandescent bulb
Number of additional lightings required:
Fixture Tracklight Downlight Pendant light No. of light 3 2 6
Compromising of mostly tracklight and pendant lights, zone C utilizes mostly halogen bulbs and
incandescent bulb. Incandescent bulb from the pendant light have a low lumen index of 130 Lm, high CRI
value of 100Ra and moderate colour temperature of 2100K which radiates warm white illuminance to the
space.
By using a formula, the number of lighting fixtures exceeding the MS1525 standards is calculated. In order
to achieve the optimal illuminance, a choice of either reducing 3 tracktlight / 2 downlight / 6 pendant light
can be done. Zone C requires an ample lighting illuminance for food preparation purposes. Nonetheless,
the use of 8 pendant lighting near the counter area functions more as a decorative element rather than its
functionality as it does not contribute much of the illuminance to the area. The downlight works as an
ambient light overhead whereas the pendant light works as a task lighting to illuminate the counter space
area.
In order to ensure illuminance does not fall below a minimum value, the fittings must be placed in a regular
grid pattern and their spacing must not exceed certain distances. A proposed spacing of 2.95m for
tracklight, 2.95m for downlight and 1.5m for pendant light can be used.
73
Zone D: Semi-outdoor Dining area
Space Dimension (m) 6.2 x 3.5
Total floor area (𝑚2) 21.7
Type of lighting fixture Tracklight Downlight Pendant Light
No. of lighting fixtures / N 3 3 5
Lumens of lighting fixtures / F (Lm)
800 1200 130
Height of luminaire (m) 3.0 3.0 2.0 Work Level (m) 0.75 0.75 1.0
Mounting height (𝐻𝑚) 2.25 2.25 1.0
Assumption of Reflectance Value
Ceiling = 0.15 Wall = 0.2 Floor = 0.6
Room Index / RI
RI = 𝐿 𝑋 𝑊
𝐻𝑚(𝐿+𝑊)
6.2 x 3.5
2.25 (6.2 + 3.5)
= 1.0
6.2 x 3.5
2.25 (6.2 + 3.5)
= 1.0
6.2 x 3.5
1 (6.2 + 3.5)
= 2.24
Utilization Factor, UF 0.48 0.48 0.62 Maintenance Factor, MF 0.8
Illuminance level, Lux
E = 𝑁 ( 𝐹 𝑋 𝑈𝐹 𝑋 𝑀𝐹)
𝐴
3(800 x 0.48 x 0.8)
21.7
= 42.5
3(1200 x 0.48 x 0.8)
21.7
= 63.7
5(130 x 0.62 x 0.8)
21.7
= 14.86
Total Illuminance level, Lux
121.06
Standard illuminance, Lux
200
Required illuminance, Lux
200 – 121.06 = 78.9
Figure 39: Position of artificial lights in zone D
74
No. of light required to reach the required illuminance
N = 𝐸 𝑋 𝐴
𝐹 𝑋 𝑈𝐹 𝑋 𝑀𝐹
78.9 x 21.7
800 x 0.48 x 0.8
= 5.57 ≈ 6
78.9 x 21.7
1200 x 0.48 x 0.8
= 3.7 ≈ 4
78.9 x 21.7
130 x 0.62 x 0.8
= 30.3 ≈ 30
Spacing requirement for light fitting (m)
S = 1.0 x 𝐻𝑚 (Direct Light)
S = 1.0 x 2.25 = 2.25
S = 1.0 x 2.25 = 2.25
S = 1.0 x 1.0 = 1.0
75
Discussion
For this zone, the space is passively ventilated whereby it gives an outdoor feeling to the area. Zone C is
located nearest to the window openings where recess lights from the streets and opposite building
illuminates the space at night. Red brick walls and concrete plastered ceilings are the main wall and ceiling
element in zone C whereby it has low reflectance value to light.
According to MS1525, The standard illuminance level of a dining area is 200 lux. However, based on the
calculations tabulated, the total illuminance level of Zone D is 121.06 lux whereby it does not meet the
MS1525 room illuminance standard. Another 78.9 lux is required to achieve the desired illuminance of 200
lux.
Type of Lighting Fixtures:
Fixture Tracklight Downlight Pendant light
Type of bulb Halogen Compact fluorescent lamp (CFL)
Incandescent bulb
Number of additional lightings required:
Fixture Tracklight Downlight Pendant light No. of light 6 4 30
Having a mix of track lights, pendant lights and downlights of varying lumens, CRI index, and colour
temperature. The pendant lights found at the front of the bar seating area provides little to no function to the
space. The pendant lamp is mainly used for decorative purpose and to enhance the overall mood of the
space.
By using a formula, the number of light required to achieve the desired illuminance is calculated according
to the type of lighting fixtures. Energy efficiency wise, instead of having an additional 30 pendant lights / 6
tracklight to achieve the required lux, a suggestion of 4 downlight can be used in order to minimize energy
consumption
In order to ensure illuminance does not fall below a minimum value, the fittings must be placed in a regular
grid pattern and their spacing must not exceed certain distances. A proposed spacing of 2.25m for
spotlight, 2.25m for downlight and 1.0 m for pendant light can be used.
76
Zone E - Indoor Dining area 2
Space Dimension (m)
6.2 x 7.8
Total floor area
(𝑚2)
48.36
Type of lighting fixture
Tracklight Downlight Pendant Light Wall light
No. of lighting fixtures / N
7 3 6 5
Lumens of lighting fixtures / F (Lm)
800 1200 130 245
Height of luminaire (m)
3.0 3.0 2.0 2.0
Work Level (m) 0.75 0.75 1.0 0.75
Mounting
height (𝐻𝑚)
2.25 2.25 1.0 1.25
Assumption of Reflectance Value
Ceiling = 0.15 Wall = 0.1 Floor = 0.6
Room Index / RI
RI = 𝐿 𝑋 𝑊
𝐻𝑚(𝐿+𝑊)
6.2 x 7.8
2.25 (6.2 + 7.8)
= 1.53
6.2 x 7.8
2.25 (6.2 + 7.8)
= 1.53
6.2 x 7.8
1.0(6.2 + 7.8)
= 3.45
6.2 x 7.8
1.25(6.2 + 7.8)
= 2.76
Utilization Factor, UF
0.53 0.53 0.62 0.62
Figure 40: Position of artificial lights in zone E
77
Maintenance Factor, MF
0.8
Illuminance level, Lux E = 𝑁 ( 𝐹 𝑋 𝑈𝐹 𝑋 𝑀𝐹)
𝐴
7(800 x 0.53 x 0.8)
48.36
= 49.1
3(1200 x 0.53 x 0.8)
48.36
= 31.56
6(130 x 0.62x 0.8)
48.36
= 8
5(245 x 0.62x 0.8)
48.36
= 12.56
Total Illuminance level, Lux
101.2
Standard illuminance, Lux
200
Required illuminance, Lux
200 – 101.2 = 98.8
No. of light required to reach the required illuminance
N = 𝐸 𝑋 𝐴
𝐹 𝑋 𝑈𝐹 𝑋 𝑀𝐹
98.8 x 48.36
800 x 0.53 x 0.8
= 14.08 ≈ 14
98.8 x 48.36
1200 x 0.53 x 0.8
= 9.4 ≈ 10
98.8 x 48.36
130 x 0.62 x 0.8
= 74
98.8 x 48.36
245 x 0.62 x 0.8
= 39
Spacing requirement for light fitting (m)
S = 1.0 x 𝐻𝑚 (Direct Light)
S = 1.0 x 2.25 = 2.25
S = 1.0 x 2.25 = 2.25
S = 1.0 x 1.0 = 1.0
S = 1.0 x 1.25 = 1.25
78
Discussion
This space is usually occupied ocassionaly for private functions or gatherings. Having a full length glass
partition and door enables light from zone D to be reflected through the space in zone E by a small amount.
The black painted walls in zone E gives very little reflectance value to the space. According to MS1525,
The standard illuminance level of a dining area is 200 lux. However, based on the calculations tabulated,
the total illuminance level of Zone D is 101.2 lux whereby it does not meet the MS1525 room illuminance
standard. Another 98.8 lux is required to achieve the desired illuminance of 200 lux.
Type of Lighting Fixtures:
Fixture Tracklight Downlight Pendant light Wall light
Type of bulb Halogen Compact fluorescent lamp
(CFL)
Incandescent bulb Incandescent bulb
Number of additional lightings required:
Fixture Tracklight Downlight Pendant light Wall light
No. of light 14 10 74 39
Having mostly bulbs of warm white colour temperature, this area is rather dim most of the time. By using a
formula, the number of light required to achieve the desired illuminance is calculated according to the type
of lighting fixtures. Instead of having an additional 74 pendant lights / 39 wall lights / 14 tracklights to
achieve the required lux, a suggestion of another 10 downlight can be used in order to minimize energy
consumption. Depending on the ambience the space would like to achieve, the interplay of lighting fixtures
(tracklight, downlight, pendant light, wall light) can be done accordingly to suit the mood.
In order to ensure illuminance does not fall below a minimum value, the fittings must be placed in a regular
grid pattern and their spacing must not exceed certain distances. A proposed spacing of 2.25m for
tracklight, 2.25m for downlight, 1.0m for pendant light and 1.25m for wall light can be used.
79
Zone F - Reading Area
Space Dimension (m)
6.2 x 8.8
Total floor area (𝑚2)
54.56
Type of lighting fixture
Tracklight Downlight Pendant Light Wall Light
No. of lighting fixtures / N
7 3 3 3
Lumens of lighting fixtures / F (Lm)
800 1200 130
245
Height of luminaire (m)
3.0 3.0 2.0 2.0
Work Level (m) 0.75 0.75 0.75
0.4
Mounting
height (𝐻𝑚)
2.25 2.25 1.25 1.6
Assumption of Reflectance Value
Ceiling = 0.15 Wall = 0.5 Floor = 0.6
Room Index / RI
RI = 𝐿 𝑋 𝑊
𝐻𝑚(𝐿+𝑊)
6.2 x 8.8
2.25 (6.2 + 8.8)
= 1.6
6.2 x 8.8
2.25 (6.2 + 8.8)
= 1.6
6.2 x 8.8
1.25(6.2 + 8.8)
= 2.9
6.2 x 8.8
1.6(6.2 + 8.8)
= 2.27
Figure 41: Position of artificial lights in zone F
80
Utilization Factor, UF
0.59 0.59 0.67 0.65
Maintenance Factor, MF
0.8
Illuminance level, Lux
E = 𝑁 ( 𝐹 𝑋 𝑈𝐹 𝑋 𝑀𝐹)
𝐴
7(800 x 0.59 x 0.8)
54.56
= 48.4
3(1200 x 0.59x 0.8)
54.56
= 31.1
3(130 x 0.67x 0.8)
54.56
= 3.8
3(245 x 0.65x 0.8)
54.56
= 7
Total Illuminance level, Lux
90.3
Standard illuminance, Lux
150
Required illuminance, Lux
150 – 90.3 = 59.7
No. of light required to reach the required illuminance
N = 𝐸 𝑋 𝐴
𝐹 𝑋 𝑈𝐹 𝑋 𝑀𝐹
59.7 x 54.56
800 x 0.59 x 0.8
= 8.6 ≈ 7
59.7 x 54.56
1200 x 0.59 x 0.8
= 5.75 ≈ 6
59.7 x 54.56
130 x 0.67 x 0.8
= 46.7 ≈ 47
59.7 x 54.56
245 x 0.65 x 0.8
= 25.6 ≈ 26
Spacing requirement for light fitting (m)
S = 1.0 x 𝐻𝑚 (Direct Light)
S = 1.0 x 2.25 = 2.25
S = 1.0 x 2.25 = 2.25
S = 1.0 x 1.25 =1.25
S = 1.0 x 1.6 = 1.6
81
Discussion
Functioning as a reading and working space, this area should provide sufficient illuminance. The right
amount of lighting is needed in order to ensure a comfortable working ambience. As for the material, this
space compromises of mostly white plastered walls of high reflectivity index which indirectly helps to
enhance the illuminance of the reading area. According to MS1525, The standard illuminance level of
casual reading area is 150 lux. However, based on the calculations tabulated, the total illuminance level of
Zone F is 90.3 lux whereby it does not meet the MS1525 room illuminance standard. Another 59.7 lux is
required to achieve the desired illuminance of 200 lux.
Type of Lighting Fixtures:
Fixture Tracklight Downlight Pendant light Wall light
Type of bulb Halogen Compact fluorescent lamp
(CFL)
Incandescent bulb Incandescent bulb
Number of additional lightings required:
Fixture Tracklight Downlight Pendant light Wall light
No. of light 7 6 47 26
Zone C uses a variety of different lighting fixtures from downlights, tracklights, pendant lights to wall lights.
This produces different and uneven lighting tones throughout the area. For a space mainly used for reading
and working purposes, downlight would be a better choice which has a high lumen index of 1200 Lm, high
CRI value of 82Ra and radiates cool white illuminance to the space.
By using a formula, the number of light required to achieve the desired illuminance is calculated according
to the type of lighting fixtures. Energy efficiency wise, instead of having an additional 47 pendant lights / 26
wall lights / 7 tracklights to achieve the required lux, a suggestion of 6 downlight can be used in order to
minimize energy consumption. Since zone F is used mostly for reading and working purposes, a well-lit
space with sufficient illuminance is needed to ensure comfort in reading.
In order to ensure illuminance does not fall below a minimum value, the fittings must be placed in a regular
grid pattern and their spacing must not exceed certain distances. A proposed spacing of 2.95m for
trackight, 2.95m for downlight and 2.3m for pendant light can be used.
82
1.5.4.5 Lighting Diagrammatic Analysis (Artificial Light)
Figure 42: Section A-A
Figure 43: Section B-B
Sectional diagram shows the positioning and intensity of artificial lightings being used in the cafe. Zone C
which is the F&B preparation area shows the highest amount of illuminance whereas zone B shows the
lowest level of illuminance. It can clearly be depicted that am pm café uses a variety of lighting fixtures to
light up the respective spaces ranging from downlights, track lights, wall lights and pendant lights with
different colour rendering index and colour temperature.
Rear Front
Rear Front
83
1.5.5 Lighting Contour Diagrams
Daylighting Contour Diagram
The diagram shows the daylight contour penetrating into the café during daytime. Zones that affected the
most are zone A, zone D and zone F due to its location which is near the entrance or near large openings.
Only some part of zone C, zone B and zone E is affected by the sunlight due to its position being quite far
from the openings. The amount of light entering from zone A to zone C is still quite strong due to the strong
sunlight during that day. Some part in zone D and zone F only receive partial of the sunlight due to the
position being at the back of a column. However, the space behind the column in zone D can still function
well without artificial light due to the strong sunlight.
Figure 44: First Floor Daylight Contour Figure 45: First Floor Daylight Contour
84
Daylighting and Artificial light Contour Diagram
The diagram shows the lighting contour of combined daylight factor and artificial light factor in the café. It
shows that the zones are better and well lit up compared to when the spaces only depends on the sunlight
for lighting in the evening. Due to the artificial lighting, zone C, zone B and zone E receives better intensity
of light thus it the lighting needed to be switch one most of the time starting from the evening until late night.
However, with added artificial lights in the evening, zone B and zone E still have the lowest intensity of light
receive compared to other area, this is due to it being the dining area and the owner intended to have a
warm and calm ambience by applying less artificial light in these areas.
Figure 47: First Floor Daylight and Artificial
Light Contour
Figure 46: Ground Floor Daylight and Artificial
Light Contour
85
Artificial Lighting Contour Diagrams
The artificial lighting contour diagram shows the illuminance level of the café during nighttime. Zone A and
Zone C shows the highest lux readings of up to 160 lux. The lux reading gradually decreases from the
central space of Zone B towards the back area where the lux reading dropped to as low as 8 lux. The
stimulation of the artificial light for the upper floor of the cafe shows a lower illuminance level as compared
to the ground floor where lighting fixtures positions is quite dispersed throughout the floor with no focus
area. Zone D have a more consistent illuminance level and a slightly higher reading than zone E. The lux
reading later shows a decrease in illuminance in zone F.
Figure 48: Ground Floor Artificial Light
Contour with lighting positions
Figure 49: First Floor Artificial Light
Contour with lighting positions
86
1.5.6 Photographs at the site
Figure 50: Wooden blind is installed in front of
the café to minimize glaring problem
Location: Exterior of the cafe
Figure 51: Glass and steel door which acts as
a transparent partition allowing sunlight from
the outside to penetrate into the interior
Location: Zone A
Figure 52: Zoom in of the bartender area and
food preparation area from the outside,
showing the spaces needs support from the
artificial lights to light up the space.
Location: Zone C
87
Figure 53: Wooden blind installed is pull down
most of the time considering the privacy of the
customers.
Location: Zone F
Figure 54: During the day, only limited
amount of sunlight managed to enter the zone
from the back area due to the wooden blind
being pulled down.
Location: Zone F
Figure 55: Due to space being located in the
middle part of the building and having dark
scheme colour as the wall, the zone does not
receive much sunlight during the day, thus
have to rely on the artificial lights to brighten
up the space.
Location: Zone E
88
Figure 57: During the night, the space is
brighten up with artificial lights and
reflectance from the shopping mall opposite
the café.
Location: Zone D
Figure 56: During the day, sufficient amount
of sunlight penetrates into the zone due to
having large openings.
Location: Zone D
89
1.6 Conclusion
The right lighting can make one feel relaxed or productive, but beyond that, there’s function.
Lighting in general is important within restaurants and cafes to create the desired mood and ambience.
Cafe lighting may vary depending on the interior's needs, however the right illuminance level can add to the
diner's experience.
Based on the observation and data collected, it can be concluded that the daylight factor at the
café is mostly below average of a daylight factor required in a café which is mostly 2%. Due to having only
2 openings which is at the front and at the back, most areas in the café does not receive sufficient amount
of daylight. The centre part of the café only receive partial amount of daylight due to the spaces located far
from the openings. In addition, the interior spaces of the café itself uses materials of mostly low reflective
index which does not assist in illuminating the spaces. Artificial light is needed most of the time at the
interior part of the cafe in order for the space to obtain at least an average luminance.
When it comes to food and ambience, nothing sets the mood faster than the play of lights. At
Ampm café, different space area require various options of lighting. The artificial lights here are not meant
to imitate the natural light, it is much warmer and meant to attract customers. The space has a lot of
different luminaires and the most interesting ones are the pendant lights and wall lights which are mostly
used as a decorative purpose rather than its functionality. A good lighting plan combines ambient, task and
accent lighting to light an area according to the function and style. Ampm café utilizes mostly ambient and
accent lighting to add drama to the space or to provide a cozy and intimate atmosphere. The data finding
from the lumen method calculations in general shows that all spaces in the café does not reach the
MS1525 standards except for the F&B preparation area. In other words, the spaces are considered to be
dimmed or poorly lit.
To conclude, the daylight gain in Ampm café is not sufficient to illuminate the spaces, thus it needs
artificial lighting most of the time to light up the areas. Nonetheless, it depends on the mood and
atmosphere the café wants to achieve whereby some spaces in the cafe is purposely made dim to create
the cozy and intimate feel to the space.
90
1.7 REFERENCES
1. Daylight factor. (n.d.). Retrieved October 25, 2016, from
http://www.newlearn.info/packages/clear/visual/daylight/analysis/hand/daylight_factor.html
2. Designing Buildings Wiki The construction industry knowledge base. (n.d.). Retrieved October 23,
2016, from https://www.designingbuildings.co.uk/wiki/The_daylight_factor
3. Daylight Factor. (n.d.). Retrieved October 24, 2016, from
http://patternguide.advancedbuildings.net/using-this-guide/analysis-methods/daylight-factor
4. The Engineering toolbox (n.d). Light reflecting factor materials . Retrieved November 06, 2016,
from http://www.engineeringtoolbox.com/light-material-reflecting-factor-d_1842.html
5. Christopher, N. (2015) How to optimize your lighting based on color temperature. Retrieved
November 06, 2016, from http://www.techhive.com/article/2887143/how-to-optimize-your-home-
lighting-design-based-on-color-temperature.html
6. Morte, R. (2011). Reflectance and reflectivity. Retrieved November 06, 2016, from
http://ricmorte.com/index.php/light-a-colour/optics/reflectance-a-reflectivity
2.0 ACOUSTIC
91
2.1 Introduction
2.1.1 Aim and Objective
This project focuses on the lighting and acoustic of the chosen case study building, AMPM Cafe, USJ
21, Subang Jaya.
Architectural acoustics is essential to promote the creation of environments, both indoors and outdoors,
involving rooms with good listening conditions within a building. Therefore, it has to be reasonably free
from intruding noise and vibrations and designed with acoustic comfort.
This project exposes students to the methods of designing good acoustic systems through a series of
calculation. The objective of the lighting analysis is to understand the daylighting and artificial lighting
while acoustic analysis will study acoustic characteristics and acoustic requirements in the case study.
Moreover, the objectives of this project are to determine the characteristics and functions of the day
lighting and artificial lighting as well as sound & acoustic within the space. Finally, another objective of
this project is to critically report and analyse the space based on the data collected.
2.2 Journal
2.2.1 Literature Review
Acoustics is defined as the science that deals with the production, control, transmission, reception, and
effects of sound. It is the study of mechanical waves such as vibration, sound and infrasound from
gases, liquids and solids form. Accordingly, the science of acoustic spreads across many facts of
human society which are music, medicine, industrial production, warfare and architecture. Many people
mistakenly think that acoustics is strictly musical or architectural in nature. While acoustics does include
the study of musical instruments and architectural spaces.
Architectural Acoustic
Architectural acoustics is the science and engineering of achieving a good sound within a building. It is
the process of managing how both airborne and impact sound is transmitted and controlled within a
building design. While practically every material within a room from furniture to floor coverings to
computer screens affects sound levels to one degree or another.
92
Importance of Acoustic in Architecture
Sound serves to connect sound source to people. Human use their senses of hearing to understand
space and works together with other senses to help people navigate and construct the understanding of
forms, distances and objects. Thus, the acoustic quality of an architectural space is quite important.
Acoustic Comfort
Acoustic comfort is essential to attain adequate level of satisfaction and moral health amongst patrons
that reside within the building, indoor noise and outdoor noise. These two aspects contribute to
acoustical comfort (or discomfort).
93
Sound Intensity Level
Sound intensity is measured as a relative ratio to some standard intensity, lo. The response of the
human ear to sound waves follows closely to a logarithmic function of the form R = k log I , where R is
the response to a sound that has an intensity of I, and k is a constant of proportionality . Thus, the
formula is,
The formula:
Reverberation Time
Reverberation time (RT) is defined as the length of time required for sound to decay from its initial level.
It is created when a sound or signal is reflected causing a large number of reflections to build up and
then decay as the sound is absorbed by the surface of object in the space including furniture, people
and the air.
The formula:
Where : RT is reverberation time, s
: V is volume of the room, m^3
: A is absorption coefficient
The absorption of a surface is determined by multiplying its surface area (S) by its absorption
coefficient (a).
The total room absorption (A) is simply sum of the products, with the inclusion of audience absorption
plus other room contents.
The formula:
Where S = Area of each surface from
A = Absorption coefficient of each surface from
94
Sound Reduction Index
Sound Reduction Index is used to measure the level of sound insulation provided by a as structure
such as wall, window, door or ventilator.
The formula:
Where : SRI is a sound reduction index, dB
: T is a transmission of sound frequency
95
2.2.2 Acoustic Precedent Studies
The Music Café, August Wilson Centre
Acoustics is an important but often overlooked element of architectural design. In certain cases, a poor
acoustical design can ruin an otherwise well designed space. For the August Wilson Centre, acoustics
is certainly paramount. As a centre for arts and culture, the centre will be home to a variety of
acoustical situations from spoken word performances to small recitals to lectures to full theatrical
performances.
Located at sidewalk level on Liberty Avenue, The August Wilson Centre is designed to where it is
accessible directly from the street and from within the center. The facility is a center for the visual and
performing arts for international music and education. The two-story 64,500 gsf facility includes a 486-
seat proscenium theatre, 11,000 gsf of exhibit galleries, a flexible studio, a music café, and an
education center.
Figure 2: Exterior view of August Wilson Centre
Figure 1: Location of August Wilson Center
96
Figure 4: Interior of August Wilson Center
2.2.2.1 Design Intention (Function)
The music café is designed to function as a multipurpose space and as a traditional museum café and
sidewalk café during the day. According to architects Perkins + Will, the music café is modeled after
New York’s BAM café or Joe’s Pub the Café. It is designed to accommodate an on‐going menu of
programs and to function as an alternative performance space for intimate performances with limited
seating for jazz, spoken word, poetry and other new performance forms in a club setting at night.
Not only that, a seating terrace is also located outside and adjacent to the café. Wired for internet
access and designed to accommodate a wide range of emerging technologies, the Café provides an
electronic link to visitors worldwide.
Figure 3: Interior perspective of music cafe
97
2.2.2.2 Space Specification
The music café is a large rectangular box with three glass facades, a hard floor, and sound absorbing
treatment located behind baffles and ductwork on the ceiling. The design does account for acoustical
needs as hanging metal baffles and acoustical blanket covers over 80% of the ceiling.
Based on the needs stated by the architects Perkins and Will, a reverberation time of approximately 1.0
second would be ideal. It means the space would be somewhere between speech and speech/music
use. According to the Architectural Acoustics : Principles and Design, a high STC value over 60+
between the Music Café and lobby would be desirable.
This is relevant so that both spaces do not suffer the noise coming from both sides. For example, a
poetry performance in a café would suffer if the crowds were to gather at the lobby after a musical
performance in the main theatre.
Figure 5: First floor plan of August Wilson Centre
98
2.2.2.3 Reverberation Analysis
Table shows that the reverberation times are not ideal. One important factor that needs to be
considered is that the manufacturer of the metal baffles ceiling system (Chicago Metalic) did not have
acoustical data for the product.
Thus, the product is omitted in the calculations. Including the baffles that would likely reduce the very
high reverberation times at the lower frequencies, but it would also reduce the reverberation times at
the higher frequencies, which is already lower than ideal number.
Table 1: Reverberation time (Existing Design)
Figure 6: Reflected ceiling plan
99
2.2.2.4 Analysis of Sound transmission class (STC)
Sound transmission class (STC) is an index rating of how well a building partition attenuates airborne
sound.
Analysis of the sound transmission class (STC) on the wall between the café and the main lobby
reveals a potential for unwanted noise transfer between the spaces. At 46, the calculated STC falls far
below the ideal value of 60+. This problem is generated by the use of glass doors and partitions
between the spaces instead of proper separating walls.
By changing the glass from ½ tempered glass to ½ laminated glass improves the STC to 49 but it is
only marginal increase.
Therefore, architectural changes are required to improve this situation in order to counter the unwanted
noise.
These changes may include changing the glass to another material such as wood or creating a small
vestibule at the entrances. By adding absorptive insulation (eg: fiberglass batts, recycled cotton denim
batts) in the wall increases the STC for fiberglass to more than 50 with cotton denim depending on stud
and screw spacing.
In contrast to that, improving the reverberation time is a much more realistic approach. In order to do
this, a new baffle system is proposed by eliminating the metal baffles and acoustical blanket, replacing
them with floating fiberglass sound absorbing panels that are faced in perforated metal.
Figure 7: Proposed baffle
system:
Figure 8: Existing hanging metal baffle system from Chicago Metallic
from Chicago Metallic.
100
2.2.2.5 New Proposed Baffled System
Figure 9: Reflected Ceiling Plan (New
Design)
Table 3: New Baffle Schedule of Materials
Table 2: Reverberation Time (New Design)
101
2.2.2.6 Conclusion
In conclusion, the analysis of the original reverberation time and STC rating of The Music Café was not
ideal at all. The proposed solution for improving the reverberation times is both economical and ideal
for the music café. Hence, it can be concluded that the improvement of reverberation time and
increasing the STC value can achieved noise reduction within a space.
The analysis also shows that the new reverberation times are very close to the ideal values and are
optimum as acoustic reverberation. According to Architectural Acoustics: Principles and Design,
optimum reverberation times at 125 hertz should be 1.3 times the ideal reverberation time at 500 hertz
and a multiplier of 1.15 should be used at 250 hertz. These multipliers are used to correct for the fact
that the human ear is less sensitive at lower frequencies. With these factors included, the new design
is very near the target. The new ceiling system will provide superior acoustical performance at a
reduced cost.
The café is somehow similar to our case study - AMPM Café as it is also located facing the street which
may contribute to more noise.
102
2.3 Research Methodology
2.3.1 Acoustic Measuring Equipment
- Sound Level Meter
A sound level meter is an instrument that can measure sound pressure level. It is commonly
used in noise pollution studies for different kinds of noise especially for industrial,
environmental and aircraft noise.
- Camera
Camera was used to capture the source of noise and also all the components that will affect
the acoustic performance in the café.
103
- Measuring Tape
Measuring tape was used to measure the height of the position of the sound level meter which
is at 1.5m high. The measuring tape is also used to measure the 1.5m x 1.5m grid on floor
while taking the reading.
104
2.3.2 Data Collection Method
Measurements were taken on different times, 12 -3pm (non-peak hour) and 4-7pm (peak hours)
intervals with one set of data each. The sound meter was placed on the intersection points at a
standard of 1.5 meter height from the ground. Each recording was done by facing the similar direction
to achieve consistent result. This standard was used to ensure the data collected to be accurate. The
person holding the sound meter will not talk and make any noise so that the readings will not be
affected during the data recording. Floor plan with a perpendicular of 1.5m x 1.5m grid lines were used
as guideline to create intersection points to aid the data collection. Same process is repeated in each
zone as well as different time zone (peak and non-peak).
Figure 10: Shows grid line of 1.5m x 1.5m on the floor plan
105
2.3.3 Limitation & Constraint
Human Limitation
The digital sound level meter device is very sensitive to the surrounding with ranging of recording
between data difference of approximately 3-4 stabilization. Hence, the data recorded is based on the
average data shown on the screen. The device might have been pointed towards the wrong path of
sound source, hence causing the reading taken to be slightly inaccurate.
Zone Limitation
Some areas are inaccessible, thus not all areas recorded. The areas include the kitchen and food
storage space.
Sound Stability
During peak hours, the vehicles sound from the street in front of the café varies from time to time. This
might also influenced the data to vary depending on the traffic condition.
106
2.4 Case Study
Located right next to Main Place mall in USJ, AM/PM is a cosy café where people come to have coffee
and cakes. Occupying two floors, AM/PM Cafe has one floor that is suitable for having functions and
events. The 1st floor sits up to 60 people and is set within a cafe setting.
The café is also located at the sidewalk where it is accessible directly from the street. Therefore, the
source of noise could be coming from the vehicle on the street and might affect the acoustic comfort of
the café and give discomfort to the user.
ZONE A : Outdoor Dinning Area ZONE D : Semi Outdoor Dining
ZONE B : Dining Room ZONE E : Dining Area
ZONE C : Food and Beverages Preparation area ZONE F : Study/Reading area
Figure 12: Zoning of areas in ground floor and first floor plan
Figure 11: AM/PM Cafe
107
‘
Data Collectio
Figure Zone A: Outdoor Dining Area
Figure Zone B: Dining Room
Figure Zone C: Study/Reading area
Figure Zone D: Semi Outdoor Dining
Figure Zone E: Dining Area
Figure Zone F: Food and Beverages Preparation area
108
2.5.1 Site Study
2.5.1.1 Outdoor Noise Source
The vehicular circulation around the site is the main contributor to the outdoor noise. The AMPM Café is the
second shop lot in the row of shop houses located at jalan USJ 21/7. Therefore, it is exposed to most of the
noise coming from the adjacent Elite highway as well as the cross junction at the side of the road. The
vehicular circulation across the road gradually increases during peak hours as the area serves plenty of
cafes, restaurants and the Jaya Grocer, these hangouts too contribute to the noise source however they are
minor.
Due to the heavy vehicular traffic, primarily, and the recreational activities, secondly, the outdoor noise
recorded is around 75dB - 80dB which is considerably high as the exterior noise received highly affects the
front zones of the café.
Figure 13: AMPM café site plan showing exterior noise
source
109
2.5.1.2 Indoor Noise Source
Human activities are the main noise source in the café. Either guests chatting and laughing or staff walking
around, moving objects from one place to the other or handling orders in the preparation area and main
kitchen. The second distinctive noise source are the speakers distributed in each zone for background music.
Followed by the kitchen appliances such as the coffee machine and food blender handled in the open
preparation area. The cooling system however acts as a minor noise source.
Figure 14: Ground floor plan and 1st floor plan showing indoor noise sour, AMPM
café
110
The speakers are located on the wall or next to a column of the dining areas allowing the sound from the
speaker to travel along the spaces. The placement of the speakers is proportionate on each zone to ensure
equal sound transmission of each space for the diners to enjoy music while eating.
The bar Area causes unfavorable noise to the area where the mixers and coffee machine produces loud and
disturbing noise that affects the acoustic quality of the space. This may give discomfort to some diners and
users at the café as the noise may interrupt user’s attention to neither conversation nor work.
Figure Shows the bartender area on the ground floor
Figure 15: Speakers position in section
Speaker
Figure 16: Preparation area in section
Food and beverages preparation area
Front Rear
Front Rear
111
2.5.2 Tabulation of Data
Sound level meter is used to record the acoustic reading at each grid point (1.5m x 1.5m) marked on the
ground floor plan and first floor plan. The height of the sound level meter is maintained to achieve a consistent
reading of data.
Figure 17: Acoustic reading, peak hours
112
Figure 18: Acoustic reading, non- peak hours
113
2.5.2.1 Data Findings at the Zones
Zone A
Time: 10am - 12pm (Non-Peak)
Grid 1 2 3
J 73 71 72
K 71 70 68
L 73 71 72
Time: 2pm - 4pm (Peak)
Grid 1 2 3
J 78 73.5 74.5
K 79.9 73 74.9
L 75.4 74 76
Figure 19: Ground floor plan, AMPM café
Table 1: Sound level meter meter readings in zone A
114
Zone B
Time: 10am - 12pm (Non-Peak)
Grid 2 3 4
D 61 70 70.3
E 59 64 71
F 61 63 65
G 62.5 64
H 62 63
I 64 65
Time: 2pm - 4pm (Peak)
Grid 2 3 4
D 66 75 76
E 67 72 75
F 67.4 70.2 76
G 67.3 71
H 72.1 69
I 70.5 70
Figure 20: Ground floor plan, AMPM café
Table 2: Sound level meter meter readings in zone B
115
Zone C
Time: 10am - 12pm (Non-Peak)
Grid 1 2
F 58 61
G 67 62
H 66 63
I 68 60.5
Time: 2pm - 4pm (Peak)
Grid 1 2
F 75 67.4
G 74 75
H 76.8 68
I 75 72
Figure 21: Ground floor plan, AMPM café
Table 3: Sound level meter meter readings in zone C
116
+Zone D
Time: 10am - 12pm (Non-Peak)
Grid 1 2 3 4
L 73 68 70.5 69
M 71.5 71 72
Time: 2pm - 4pm (Peak)
Grid 1 2 3 4
L 76 70 73 71
M 74 75 75
Figure 22: 1st floor plan, AMPM café
Table 4: Sound level meter meter readings in zone D
117
Zone E
Time: 10am - 12pm (Non-Peak)
Grid 1 2 3 4
F 63 62 61.5
G 66 66 62
H 64 64 63
I 65 65 68
J 65 63 60 62.5
K 62 63 64 61
Time: 2pm - 4pm (Peak)
Grid 1 2 3 4
F 70 69 65
G 78 76 69
H 74 78 75
I 76 78 68
J 73 78 76 73
K 69 77 78 72
Figure 23: 1st floor plan, AMPM café
Table 5: Sound level meter meter readings in zone E
118
Zone F
+
Time: 10am - 12pm (Non-Peak)
Grid 1 2 3 4
A 59 57.5 61 58
B 61.5 62 57 60
C 64 60 59 57.5
D 64 62 60 59
E 63 60 58
F 63 62 61.5
Time: 2pm - 4pm (Peak)
Grid 1 2 3 4
A 65 66 66 70
B 70 70 63 70
C 69 63 65 72
D 68 70 64 70
E 66 67 60
F 70 69 65
Figure 24: 1st floor plan, AMPM café
Table 6: Sound level meter meter readings in zone F
119
2.5.3 Material Absorption Coefficient
Zone A
Components Material Colour Surface Finish Absorption Coefficient
500Hz 2000Hz 4000Hz
W
A L L
Concrete+ Grey Smooth Matte 0.02 0.02 0.05
Brick Red Matte 0.02 0.05 0.05
C E I
L I
N G
Concrete Dark Grey
Luster 0.02 0.05 0.05
Figure 25: Floor plan of zone A
120
F L O O
R
Concrete Grey Smooth Matte 0.02 0.05 0.05
DOOR
Glass Clear Smooth 0.04 0.02 0.02
F U R N I T U
R E
Wooden Brown Glossy
0.15 0.18 0.20
Wooden
Brown Glossy
Table 7: Absorption coefficient for components in zone A
121
Zone B
Components Material Colour Surface Finish Absorption Coefficient
500Hz 2000Hz 4000Hz
W A L L
Concrete Grey Matte 0.03 0.04 0.07
Brick Red Matte 0.02 0.05 0.05
Fly Ash Brick (FAB)
Grey Matte 0.02 0.05 0.05
Figure 26: Floor plan of zone B
122
C E I L I
N G
Concrete Dark Grey
Luster 0.02 0.05 0.05
F L O
O R
Porcelain Grey Glossy 0.03 0.05 0.05
DOOR
Glass Clear Smooth 0.04 0.02 0.02
F U R N I T
U R E
Wooden Brown Glossy 0.15 0.18 0.20
Upholstered Green and
Yellow
Luster 0.26 0.50 0.55
Table 8: Absorption coefficient for components in zone B
123
Zone C
Element Material Colour Surface Finish Absorption Coefficient
500Hz 2000Hz 4000Hz
W A
L L
Concrete Grey Smooth Matte 0.02 0.02 0.05
Ceramic White Glossy 0.01 0.02 0.02
Fly Ash Brick (FAB)
Grey Matte 0.02 0.05 0.05
Figure 27: Floor plan of zone C
124
C E I L I
N G
Concrete Dark Grey
Luster 0.02 0.05 0.05
F L O
O R
Ceramic White Glossy 0.01 0.02 0.02
D
OOR
Glass Clear Smooth 0.04 0.02 0.02
F U R
N I T U R E
Wooden Brown Matte 0.15 0.18 0.20
Table 9: Absorption coefficient for components in zone C
125
Zone D
Element Material Colour Surface Finish Absorption Coefficient
500Hz 2000Hz 4000Hz
W
A L L
Concrete Grey Smooth Matte 0.02 0.02 0.05
Brick Red Matte 0.02 0.05 0.05
C E I
L I
N G
Concrete Dark Grey
Luster 0.02 0.05 0.05
F
L O O R
Porcelain Grey Glossy 0.03 0.05 0.05
Figure 28: Floor plan of zone D
126
DOO
R
Glass Clear Smooth 0.04 0.02 0.02
W I
N D O W
Glass Clear Smooth 0.04 0.02 0.02
F U R N I T U
R E
Wooden
Brown Glossy 0.15 0.18 0.20
Table 10: Absorption coefficient for components in zone D
127
Zone E
Element Material Colour Surface Finish Absorption Coefficient
500Hz 2000Hz 4000Hz
W
A L L
Concrete Grey Matte 0.03 0.04 0.07
Brick Red Matte 0.02 0.05 0.05
Plastered Black Matte 0.01 0.02 0.02
Figure 29: Floor plan of zone E
128
C E I L I
N G
Concrete Dark Grey
Luster 0.02 0.05 0.05
F L O
O R
Porcelain Grey Glossy 0.03 0.05 0.05
D O O R
Glass Clear Smooth
0.04 0.02 0.02
P
A R T I T I
O N
Glass Semi-clear
Smooth
0.04 0.02 0.02
F U R N I T U R
E
Wooden Brown Glossy 0.15 0.18 0.20
Table 11: Absorption coefficient for components in zone E
129
Zone F
Element Material Colour Surface Finish Absorption Coefficient
500Hz 2000Hz 4000Hz
W A L L
Concrete Grey Matte 0.03 0.04 0.07
Brick Red Matte 0.02 0.05 0.05
C E I
L I
N G
Concrete Dark Grey
Luster 0.02 0.05 0.05
Figure 30: Floor plan of zone F
130
F L O O
R
Porcelain Grey Glossy 0.03 0.05 0.05
P
A R T I T I
O N
Glass Semi-clear
Smooth 0.04 0.02 0.02
W I
N D O W
Glass Clear Smooth 0.04 0.02 0.02
F
U R N I T U R E
Upholstered
Green and
Yellow
Luster 0.26 0.50 0.55
Table 12: Absorption coefficient for components in zone F
131
2.5.4 Calculation of Sound Intensity Level (SIL)
Zone A
Peak Hours Non-Peak Hours
Highest Reading 80 dB 73 dB
Lowest Reading 73 dB 70 dB
Intensity of Highest Reading, IH
SIL = 10 log (IH /IO) 80 = 10 log (IH /1x10-12) 8.0 = log (IH /1x10-12) 108 = (IH /1x10-12) IH = 108 (1x10-12) IH = 1 x 10-4 W/m2
SIL = 10 log (IH IO) 73 = 10 log (IH /1x10-12) 7.3 = log (IH /1x10-12) 107.3 = (IH /1x10-12) IH = 107.3 (1x10-12) IH = 1.995 x 10-5 W/m2
Intensity of Lowest Reading, IL
SIL = 10 log (IL /IO) 73 = 10 log (IL /1x10-12) 7.3 = log (IL /1x10-12) 107.3 = (IL /1x10-12) IL = 107.3 (1x10-12) IL = 1.995 x 10-5 W/m2
SIL = 10 log (IL /IO) 70 = 10 log (IL /1x10-12) 7.0 = log (IL /1x10-12) 107 = (IL /1x10-12) IL = 107 (1x10-12) IL = 1 x 10-5 W/m2
Total Intensity, TI
TI = IH + IL
TI = (1 x 10-4) + (1.995 x 10-5) TI = 1.11 x 10-4
TI = IH + IL
TI = (1.995 x 10-5) + (1 x 10-5) TI = 2.995 x 10-5
Combined Sound Intensity Level, SIL SIL = 10 log (TI /1x10-12) SIL = 10 log (1.11 x 10-4/1x10-12) SIL = 80.5 dB
SIL = 10 log (TI /1x10-12) SIL = 10 log (2.995 x 10-5/1x10-12) SIL = 74.8 dB
Figure 31: Floor plan of zone A
132
Zone B
Peak Hours Non-Peak Hours
Highest Reading, 76 dB 70 dB
Lowest Reading 66 dB 59 dB
Intensity of Highest Reading, IH
SIL = 10 log (IH /IO) 76 = 10 log (IH /1x10-12) 7.6 = log (IH /1x10-12) 107.6 = (IH /1x10-12) IH = 107.6 (1x10-12) IH = 3.981 x 10-5 W/m2
SIL = 10 log (IL /IO) 70 = 10 log (IL /1x10-12) 7.0 = log (IL /1x10-12) 107 = (IL /1x10-12) IL = 107 (1x10-12) IL = 1 x 10-5 W/m2
Intensity of Lowest Reading, IL
SIL = 10 log (IH IO) 66 = 10 log (IH /1x10-12) 6.6 = log (IH /1x10-12) 106.6 = (IH /1x10-12) IH = 106.6 (1x10-12) IH = 3.981 x 10-6 W/m2
SIL = 10 log (IL /IO) 59 = 10 log (IL /1x10-12) 5.9 = log (IL /1x10-12) 105.9 = (IL /1x10-12) IL = 105.9 (1x10-12) IL = 7.943 x 10-7 W/m2
Total Intensity, TI
TI = IH + IL
TI = (5.012 x 10-5) + (3.981 x 10-6) TI = 4.379 x 10-5
TI = IH + IL
TI = (1 x 10-5) + (7.943 x 10-7) TI = 1.079 x 10-5
Combined Sound Intensity Level, SIL SIL = 10 log (TI /1x10-12) SIL = 10 log (4.379 x 10-5/1x10-12) SIL = 76.4 dB
SIL = 10 log (TI /1x10-12) SIL = 10 log (1.079 x 10-5/1x10-12) SIL = 70.3 dB
Figure 32: Floor plan of zone B
133
Zone C
Peak Hours Non-Peak Hours
Highest Reading 76 dB 68 dB
Lowest Reading 67.3 dB 60.5 dB
Intensity of Highest Reading, IH
SIL = 10 log (IH /IO) 76 = 10 log (IH /1x10-12) 7.6 = log (IH /1x10-12) 107.6 = (IH /1x10-12) IH = 107.6 (1x10-12) IH = 3.981 x 10-5 W/m2
SIL = 10 log (IH IO) 68 = 10 log (IH /1x10-12) 6.8 = log (IH /1x10-12) 106.8 = (IH /1x10-12) IH = 106.8 (1x10-12) IH = 6.31 x 10-6 W/m2
Intensity of Lowest Reading, IL
SIL = 10 log (IL /IO) 67.3 = 10 log (IL /1x10-12) 6.73 = log (IL /1x10-12) 106.73 = (IL /1x10-12) IL = 106.73 (1x10-12) IL = 5.37 x 10-6 W/m2
SIL = 10 log (IL /IO) 60 = 10 log (IL /1x10-12) 6.0 = log (IL /1x10-12) 106 = (IL /1x10-12) IL = 106 (1x10-12) IL = 1 x 10-6 W/m2
Total Intensity, TI
TI = IH + IL
TI = (6.31 x 10-5) + (5.37 x 10-6) TI = 4.518 x 10-5
TI = IH + IL
TI = (6.31 x 10-6) + (1 x 10-6) TI = 7.31 x 10-6
Combined Sound Intensity Level, SIL SIL = 10 log (TI /1x10-12) SIL = 10 log (6.847 x 10-5/1x10-12) SIL = 76.8 dB
SIL = 10 log (TI /1x10-12) SIL = 10 log (7.31 x 10-6/1x10-12) SIL = 68.6 dB
Figure33: Floor plan of zone C
134
Zone D
Peak Hours Non-Peak Hours Highest Reading, 76 dB 73 dB
Lowest Reading 70 dB 68 dB
Intensity of Highest Reading, IH
SIL = 10 log (IH /IO) 76 = 10 log (IH /1x10-12) 7.6 = log (IH /1x10-12) 107.6 = (IH /1x10-12) IH = 107.6 (1x10-12) IH = 3.981 x 10-5 W/m2
SIL = 10 log (IH IO) 73 = 10 log (IH /1x10-12) 7.3 = log (IH /1x10-12) 107.3 = (IH /1x10-12) IH = 107.3 (1x10-12) IH = 1.995 x 10-5 W/m2
Intensity of Lowest Reading, IL
SIL = 10 log (IL /IO) 70 = 10 log (IL /1x10-12) 7.0 = log (IL /1x10-12) 107 = (I0L /1x10-12) IL = 107 (1x10-12) IL = 1 x 10-5 W/m2
SIL = 10 log (IL IO) 68 = 10 log (IL /1x10-12) 6.8 = log (IL /1x10-12) 106.8 = (IL /1x10-12) IL = 106.8 (1x10-12) IL = 6.31 x 10-6 W/m2
Total Intensity, TI
TI = IH + IL
TI = (3.981 x 10-5) + (1 x 10-5) TI = 4.981 x 10-5
TI = IH + IL
TI = (1.995 x 10-5) + (6.31 x 10-6) TI = 2.626 x 10-5
Combined Sound Intensity Level, SIL SIL = 10 log (TI /1x10-12) SIL = 10 log (4.981 x 10-5/1x10-12) SIL = 77 dB
SIL = 10 log (TI /1x10-12) SIL = 10 log (2.626 x 10-5/1x10-12) SIL = 74.2 dB
Figure34: Floor plan of zone D
135
Zone E
Peak Hours Non-Peak Hours
Highest Reading, 78 dB 66 dB
Lowest Reading 68 dB 61 dB
Intensity of Highest Reading, IH
SIL = 10 log (IH /IO) 78 = 10 log (IH /1x10-12) 7.8 = log (IH /1x10-12) 107.8 = (IH /1x10-12) IH = 107.8 (1x10-12) IH = 6.31 x 10-5 W/m2
SIL = 10 log (IH IO) 66 = 10 log (IH /1x10-12) 6.6 = log (IH /1x10-12) 106.6 = (IH /1x10-12) IH = 106.6 (1x10-12) IH = 3.981 x 10-6 W/m2
Intensity of Lowest Reading, IL
SIL = 10 log (IL /IO) 68 = 10 log (IL /1x10-12) 6.8 = log (IL /1x10-12) 106.8 = (IL /1x10-12) IL = 106.8 (1x10-12) IL = 6.31 x 10-6 W/m2
SIL = 10 log (IL /IO) 61 = 10 log (IL /1x10-12) 6.1 = log (IL /1x10-12) 106.1 = (IL /1x10-12) IL = 106.1 (1x10-12) IL = 1.259 x 10-6 W/m2
Total Intensity, TI
TI = IH + IL
TI = (6.31 x 10-5) + (6.31 x 10-6) TI = 6.941 x 10-5
TI = IH + IL
TI = (3.981 x 10-6) + (1.259 x 10-6) TI = 5.24 x 10-6
Combined Sound Intensity Level, SIL SIL = 10 log (TI /1x10-12) SIL = 10 log (6.941 x 10-5/1x10-12) SIL = 78.4 dB
SIL = 10 log (TI /1x10-12) SIL = 10 log (5.24 x 10-6/1x10-12) SIL = 67.2 dB
Figure35: Floor plan of zone E
136
Zone F
Peak Hours Non-Peak Hours
Highest Reading, 70 dB 64 dB
Lowest Reading 63 dB 57 dB
Intensity of Highest Reading, IH
SIL = 10 log (IH /IO) 70 = 10 log (IH /1x10-12) 7.0 = log (IH /1x10-12) 107.0 = (IH /1x10-12) IH = 107.0 (1x10-12) IH = 1 x 10-5 W/m2
SIL = 10 log (IH IO) 64 = 10 log (IH /1x10-12) 6.4 = log (IH /1x10-12) 106.4 = (IH /1x10-12) IH = 106.4 (1x10-12) IH = 2.512 x 10-6 W/m2
Intensity of Lowest Reading, IL
SIL = 10 log (IL /IO) 63 = 10 log (IL /1x10-12) 6.3 = log (IL /1x10-12) 106.3 = (IL /1x10-12) IL = 106.3 (1x10-12) IL = 1.995 x 10-6 W/m2
SIL = 10 log (IL /IO) 57 = 10 log (IL /1x10-12) 5.7 = log (IL /1x10-12) 105.7 = (IL /1x10-12) IL = 105.7 (1x10-12) IL = 5.012 x 10-7 W/m2
Total Intensity, TI
TI = IH + IL
TI = (1 x 10-5) + (1.995 x 10-6) TI = 1.11 x 10-5
TI = IH + IL
TI = (2.512 x 10-6) + (5.012 x 10-7) TI = 3.013 x 10-6
Combined Sound Intensity Level, SIL SIL = 10 log (TI /1x10-12) SIL = 10 log (1.11 x 10-5/1x10-12) SIL = 70.5 dB
SIL = 10 log (TI /1x10-12) SIL = 10 log (3.013 x 10-6/1x10-12) SIL = 64.8 dB
Figure 36: Floor plan of zone F
137
2.5.4.1 Sound Intensity Level (SIL) Analysis and Conclusion
Zones Sound Intensity Level
Non-Peak Hours Peak Hours
Zone A, Outdoor Dining 74.8 dB 80.5 dB
Zone B, Dining Area 70.3 dB 76.4 dB
Zone C, Food Preparation Area 68.6 dB 76.8 dB
Zone D, Semi Outdoor Dining 74.2 dB 77 dB
Zone E, Dining Area 67.2 dB 78.4 dB
Zone F, Study/Reading Area 64.8 dB 70.5 dB
Figure 37: Ground floor plan and 1st floor plan, AMPM cafe
Table 13: Sound intensity level of all zones during peak non- peak
hours
A
A
A
B
B
B
B
A
A
138
Figure 38: S
ection AA
, AM
PM
café
Fron
t R
ea
r
139
Fig
ure
39
: Se
ction
BB
, AM
PM
café
Fron
t R
ea
r
140
As seen in table 13, the highest sound intensity level during peak hour is 80.5 dB at zone A, the outdoor
dining area. This is due to its contact to the outside chaotic environment as seen in section AA and section
BB, where buffers like trees and fencing are absent causing direct exposure to the noise coming from the
road. However, the presence of an outdoor space at the entrance acts as a buffer to the main indoor dining
area. Even though it’s not extremely effective due to the thin glass partition that separates the two areas, as
seen in tablex, it does help in reducing the sound intensity level of the interior zones, zone B and C.
The second highest sound intensity level during peak hour is 77 dB at zone D, the semi outdoor dining
area located at the 1st floor. Although the SIL is high due to its exposure to the exterior noise traffic, however
compared to zone A, the SIL at zone D is slightly reduced due to the use of the wall and window barrier, as
seen in the sections above, whereas in zone A it is directly open and exposed to the exterior noise.
The third highest sound intensity level during peak hour is 76.8 dB and 76.4 dB at zone C and B
respectively. The SIL exceeds the ideal sound level at a restaurant which is about 70 dB (Restaurant Engine,
2016). This is primarily because of the linear floor plan layout with minimal partitions. As seen in section AA,
zone B, the main dining area with lots of occupants, loud chatters and laughers during peak hours is exposed
to zone C, which is the food and beverages preparation area, which as well have a high noise source, from
electrical appliances like food blender and coffee machines, to staff moving around preparing food. The open
floor plan with minimal partitions, exposes various noise sources to each other, hence, the distance between
the noise source and the receiver is reduced. Besides that, less partitions and barriers between spaces
means less sound absorbing materials. Furthermore, the linearity of the open floor plan layout allows the
sound to easily propagate throughout the whole space increasing the overall sound pressure.
The zone with the least sound intensity level 70.5 dB is zone F, the reading area, located at the 1st
floor. Zone F is the only zone at the café that meets the sound requirement for restaurant which is 70 dB
(Restaurant Engine, 2016). Zone F was able to successfully meet the sound level requirements of
restaurants, primarily due to its location in the café. It is located at the back area of the café’s 1st floor, where
as seen in the sections above, it is facing the back lane from one side where there is no noticeable noise
source, while on the other side, it is partially separated with partitions and walls from the rest of the dining,
as seen in section AA and section BB. Apart from that, it has ample cushioned and upholstered furniture
which helps in absorbing the sound. Therefore, zone F is the most ideal zone in the café to offer studies and
reading activities. To conclude, except for zone F, all the other zones at the café highly exceeds the
restaurant’s sound level requirement. This is due to the outdoor chaotic environment, the linear open floor
plan that exposes the spaces to each other and the little consideration to sound absorbing materials.
141
2.5.5 Calculation of Sound Reduction Index (SRI)
Zone A & Zone B, Wall 1
Surface Type Sound Reduction Index,
SRI (dB) Transmission Coefficient, T
Area, S(m2)
Wall - Smooth Concrete 50 1 x 10-5 7.58
Door/Partition - Glass 30 1 x 10-3 11.32
Figure 40: Ground floor plan, AMPM
café
142
Concrete wall
SRI = 10 log (1/T)
50 = 10 log (1/T)
105 = (1/T)
T = 1/ 105
T = 1 x 10-5
Glass Door/Partition
SRI = 10 log (1/T)
30 = 10 log (1/T)
103 = (1/T)
T = 1/ 103
T = 1 x 10-3
Tav = ( (1 x 10-5 x 7.58) + (1 x 10-3 x 11.32) ) / 18.9
= (1.139 x 10-2) / 18.9
= 6.026 x 10-4
SRI = 10 log (1/T)
= 10 log (1/6.026 x 10-4)
= 32.2 dB
143
Zone B & Kitchen, Wall 2
Surface Type Sound Reduction Index,
SRI (dB) Transmission Coefficient, T
Area, S(m2)
Wall - Fly Ash Brick 54 3.981 x 10-6 30.27
Door – Polished Wood 28 1.585 x 10-3 1.5
Window - Glass 26 2.51 x 10-3 0.42
Figure 41: Ground floor plan, AMPM
café
144
Brick wall
SRI = 10 log (1/T)
54 = 10 log (1/T)
105.4 = (1/T)
T = 1/ 105.4
T = 3.981 x 10-6
Wooden Door
SRI = 10 log (1/T)
2.8 = 10 log (1/T)
102.8 = (1/T)
T = 1/ 102.8
T = 1.585 x 10-3
Glass Window
SRI = 10 log (1/T)
2.6 = 10 log (1/T)
102.6 = (1/T)
T = 1/ 102.6
T = 2.51 x 10-3
Tav = ( (3.981 x 10-6 x 30.27) + (1.585 x 10-3 x 1.5) + (2.51 x 10-3x 0.42) ) / 32.19
= (3.55 x 10-3) / 32.19
= 1.102 x 10-4
SRI = 10 log (1/T)
= 10 log (1/1.102 x 10-4)
= 39.6 dB
145
Zone D, Wall 3
Surface Type Sound Reduction Index,
SRI (dB) Transmission Coefficient, T
Area, S(m2)
Wall - Smooth Concrete 50 1 x 10-5 4.9 Window - Glass 26 2.51 x 10-3 9.8
Figure 42: 1st floor plan, AMPM
café
146
Concrete wall
SRI = 10 log (1/T)
50 = 10 log (1/T)
105 = (1/T)
T = 1/ 105
T = 1 x 10-5
Glass Window
SRI = 10 log (1/T)
2.6 = 10 log (1/T)
102.6 = (1/T)
T = 1/ 102.6
T = 2.51 x 10-3
Tav = ( (1 x 10-5 x 4.9) + (2.51 x 10-3 x 9.8) ) / 14.7
= (2.46 x 10-2) / 14.7
= 1.673 x 10-3
SRI = 10 log (1/T)
= 10 log (1/1.673 x 10-3)
= 27.8 dB
147
2.4.5.1 Sound Reduction Index (SRI) Analysis and Conclusion
Structure Sound Reduction Index
Wall 1 32.2 dB
Wall 2 39.6 dB
Wall 3 27.8 dB
Figure 43: Ground floor plan and 1st floor plan, AMPM cafe
Table 14: Sound reduction index of wall 1, wall 2 and wall 3
148
Sound reduction index is used to measure the level of sound insulation provided by a structure and its
components such as walls, doors, windows…etc. The table below shows the sound reduction index according
to its hearing conditions.
From the table above, we can identify the effectiveness of the walls found in the café. Wall 1 and wall 3 of
the café has a sound reduction index of only 32.3 dB and 27.8 dB respectively, this means norm al speech
can be easily and distinctly heard through the walls. This is due to the use of large area of glass door/partition
to separate zone A from zone B and zone C from the exterior. Wall 1 and 3 are considered to be insufficient
due to their low sound insulation, in which the outdoor noise can be easily heard affecting the overall acoustic
performance of the interior zones. In order to increase the SRI of the two walls to avoid exterior noise from
penetrating, the glass area on the wall needs to be reduced and the thickness of glass needs to be increased.
Wall 2 separates the main kitchen from zone B, the dining area. The wall has a sound reduction index of
39.6, this means that loud noise can be understood fairly well. This is inadequate for the café as the main
kitchen needs to have a higher SRI as to prevent loud noise from the kitchen to penetrate in to the dining
area.
Table 15: The table compares the degree of acoustic privacy with the sound reduction
index. (Mcgarth and Alter, 2000)
149
2.5.6 Calculation of Sound Reverberation Time (SRT)
Zone B and C
Surface Type Surface
Area, (m2)
Absorption Coefficient,
(500Hz)
Sound Absorption
(500Hz)(m2 Sa)
Absorption Coefficient, (2000Hz)
Sound Absorption
(2000Hz)(m2 Sa)
Wall - Rough Concrete
Wall – Smooth Concrete
Wall - Fly Ash Brick
Wall – Bricks
Wall - Ceramic
37.9
9.6
18.13
8.88
11.1
0.03
0.02
0.02
0.02
0.01
1.137
0.192
0.363
0.178
0.111
0.04
0.02
0.05
0.05
0.02
1.516
0.192
0.192
0.444
0.222
Door/Partition - Glass 11.32 0.04 0.453 0.02 0.226
Ceiling - Concrete 50.8 0.02 1.016 0.05 2.54
Floor - Porcelain Tiles
Floor - Ceramic
36.6
14.2
0.03
0.01
1.098
0.142
0.05
0.02
1.83
0.284
Furniture - Wood Furniture - upholstered
34.22
3.7
0.15
0.26
5.133
0.963
0.18
0.50
6.16
1.85
Occupants 15 0.46 6.9 0.51 7.65
Total Absorption (A) 17.684 23.821
Reverberation Time when Absorption Coefficient at 500Hz Room Volume of zone B, V = 50.8 x 3.7 = 187.96m3
Reverberation Time = (0.16 x V) / A = (0.16 x 187.96) / 17.684 = 1.7s
Reverberation Time when Absorption Coefficient at 2000Hz Room Volume of zone B, V = 50.8 x 3.7 = 187.96m3
Reverberation Time = (0.16 x V) / A = (0.16 x 187.96) / 23.821 = 1.26s
Figure 44: Floor plan of zone B and zone
C
150
Zone D
Surface Type Surface
Area, (m2)
Absorption Coefficient,
(500Hz)
Sound Absorption
(500Hz)(m2 Sa)
Absorption Coefficient, (2000Hz)
Sound Absorption
(2000Hz)(m2 Sa)
Wall – Smooth Concrete
Wall - Bricks
10
18
0.02
0.02
0.2
0.36
0.02
0.05
0.2
0.9
Door/Partition - Glass 22.05 0.04 0.882 0.02 0.441
Window - Glass 9.8 0.04 0.392 0.02 0.196
Ceiling - Concrete 20.6 0.02 0.412 0.05 1.03
Floor - Porcelain Tiles 20.6 0.03 0.618 0.05 1.03
Furniture - Wood 5.88 0.15 0.882 0.18 1.058
Occupants 4 0.46 1.84 0.51 2.04
Total Absorption (A) 5.586 6.895
Reverberation Time when Absorption Coefficient at 500Hz Room Volume of zone D, V = 20.6 x 3.5 = 72.77m3
Reverberation Time = (0.16 x V) / A = (0.16 x 72.77) / 5.586 = 2.08s Reverberation Time when Absorption Coefficient at 2000Hz Room Volume of zone D, V = 20.6 x 3.5 = 72.77m3
Reverberation Time = (0.16 x V) / A = (0.16 x 72.77) / 6.895 = 1.68s
Figure 45: Floor plan of zone D
151
Zone E
Surface Type Surface Area,
(m2)
Absorption Coefficient,
(500Hz)
Sound Absorption
(500Hz)(m2 Sa)
Absorption Coefficient, (2000Hz)
Sound Absorption
(2000Hz)(m2 Sa)
Wall - Rough Concrete
Wall - Concrete (black paint finish)
21.7
36.65
0.03
0.01
0.651
0.367
0.04
0.02
0.868
0.733
Door/Partition - Glass 27.6 0.04 1.104 0.02 0.552
Ceiling - Concrete 36.6 0.02 0.732 0.05 1.83
Floor - Porcelain Tiles 36.6 0.03 1.098 0.05 1.83
Furniture - Wood Furniture - Wood Panels
12.4
1.38
0.15
0.17
1.86
0.235
0.18
0.10
2.232
0.138
Occupants 11 0.46 5.06 0.51 5.61
Total Absorption (A) 11.106 13.793
Reverberation Time when Absorption Coefficient at 500Hz Room Volume of zone E, V = 36.6 x 3.5 = 128.31m3
Reverberation Time = (0.16 x V) / A = (0.16 x 128.31) / 11.106 = 1.85s Reverberation Time when Absorption Coefficient at 2000Hz Room Volume of zone E, V = 7.8 x 4.7 x 3.5 = 128.31m3
Reverberation Time = (0.16 x V) / A = (0.16 x 128.31) / 13.793 = 1.49s
Figure 46: Floor plan of zone E
152
Reverberation Time when Absorption Coefficient at 500Hz Room Volume of zone F, V = 47.4 x 3.5 = 165.9m3
Reverberation Time = (0.16 x V) / A = (0.16 x 165.9) / 13.157 = 2.02s Reverberation Time when Absorption Coefficient at 2000Hz Room Volume of zone F, V = 47.4 x 3.5 = 165.9m3
Reverberation Time = (0.16 x V) / A = (0.16 x 165.9) / 20.988 = 1.26s
Zone F
Surface Type Surface
Area, (m2)
Absorption Coefficient,
(500Hz)
Sound Absorption
(500Hz)(m2 Sa)
Absorption Coefficient, (2000Hz)
Sound Absorption
(2000Hz)(m2 Sa)
Wall - Smooth Concrete
Wall - Rough Concrete
Wall - Brick
33.35
25.38
20.44
0.02
0.03
0.02
0.667
0.761
0.409
0.02
0.04
0.05
0.667
1.015
1.022
Window - Glass 15.44 0.04 0.6176 0.02 0.3088
Ceiling - Concrete 47.4 0.02 0.948 0.05 2.37
Floor - Porcelain Tiles 47.4 0.03 1.422 0.05 2.37
Furniture - Wood Furniture - upholstered
Furniture - Curtain
5.44 9.1
9.8
0.15 0.26 0.15
0.816 2.366 1.47
0.18 0.50 0.37
0.9792 4.55 3.626
Occupants 8 0.46 3.68 0.51 4.08
Total Absorption (A) 13.157 20.988
Figure 47: Floor plan of zone F
153
2.5.6.1 Sound Reverberation Time (SRT) Analysis and Conclusion
Zones Reverberation Time (Peak Hours)
500Hz 2000Hz
Zone B and C, Dining Area + Preparation Area 1.7s 1.26s
Zone D, Semi Outdoor Dining 1.08s 1.68s
Zone E, Dining Area 1.85s 1.49s
Zone F, Study/Reading Area 2.02s 1.26s
Figure 48: Ground floor plan and 1st floor plan, AMPM cafe
Table 16: Reverberation time of all zones during peak hours
154
As seen from table 16, all the zones highly exceed 0.6s reverberation time which is the required period for
sound to decay according to the Ashrae standards. This is mainly because of the inadequate acoustic
absorption materials used in the café. In addition to that, the infill design layout of the building doesn’t allow
for window openings along the elongated floorplan, which will allow some of the sound energy to escape the
enclosed space instead of reflecting it within.
As seen in table 16, taking the highest frequency of 2000Hz, it can be seen that zone D has the highest
reverberation time where sound decays in 1.68s. Referring to figure 49, zone D is enclosed with glass from
both sides. A glass partition of 22.05m2 on one side and a glass window of 9.8m2 on the other side facing the
roadway. The abundance use of glass in the space is inadequate as smooth and non-porous materials tend
to reflect more sound than they absorb. Hence, the glass reflects back most of the sound energy and absorbs
only small amount of the sound produced. In addition to that, although the space offers a window openings,
however, most of the time the window remains closed due to the unfriendly outdoor noises. This prevents
the sound from escaping and instead propagates it through the space.
Figure 49: Floor plan of zone D with materials
155
The second highest reverberation time is at zone E. Although zone E accommodates multiple customers that
can considerably enhance the acoustic surrounding, as humans are sufficient in absorbing sound, these are
overshadowed by the extensive use of poor sound absorption materials in the area. As seen in figure 50, the
use of porcelain flooring, glass partitions on both ends, smooth concrete wall and black paint finish are
materials of smooth and glossy surfaces that are hardly sufficient in absorbing the sound energy, this affects
the overall sound performance of the space, making it acoustically uncomfortable during peak hours.
Figure 50: Floor plan of zone E with materials
156
Zone B, C, and F have the least reverberation time of 1.26s. As seen in figure51 and figure 52, this is primarily
because of the abundant use of cushions, upholstered furniture and curtains in the area. The porous nature
of these materials help in absorbing the sounds sufficiently, the more fibrous the material the better the
absorption. In addition to that, these zones use rough surfaces like brick walls and rough concrete rather than
smooth concrete and paint finishes used in other zones. These Rough surfaced materials have slightly higher
absorption coefficient compared to smooth concrete. This is because when sound is projected the friction
between rough area and the air increases resulting in a higher sound absorption. Apart from that, costumers
tend to concentrate in these two areas, hence human considerably enhance the acoustic environment as
they have high absorption coefficient.
Figure 51: Floor plan of zone B and zone C with materials
Figure 52: Floor plan of zone F with materials
157
2.4.7 Acoustic Ray Diagram
Figure 53: Acoustic ray diagram for speaker
The diagram above shows the acoustic rays originated from the speaker located at the ground floor as
indicated in the floor plan. The red circle indicates the position of the speaker.
Based on figure 53, we can observe that the concentration of the bouncing rays in zone A tends to be
concentrated to the stairs as it is position in a way that the sound will reflect back to the inside of the cafe.
Zone A is an outdoor area so most of the sounds ray disperse to the exterior. Hence, the acoustic rays are
reflected but do not contain in the space as it is quite an open space.
Other than that, we can observe that the concentration of the bouncing rays in zone C concentrated on the
north-east side of the plan while the bouncing rays in zone B is concentrated to the south-west side of the
plan. This is due to the open floor plan with minimal partitions, exposed various noise sources to each other.
158
Figure 54: Acoustic ray diagram for speaker
The diagram above shows the acoustic rays originated from the speaker located at first floor as indicated in
the floor plan. The red circle indicates the position of the speaker.
Based on figure 54, we can observe that the concentration of the bouncing rays in zone B tends to be
concentrated equally to all sides of the floor plan. This is due to the location of the speaker and the enclosed
space. Zone D is a semi-outdoor area but the windows are closed due to the noise coming from the exterior.
Hence, the acoustic rays are reflected and contained in the space.
Based on the diagram, we can observe that the concentration of the bouncing rays in zone E tend to be
concentrated on the south-east side of the plan. Due to the position of the speaker and some of the ray
escape to the other side of the wall when it is reflected. While the concentration of the bouncing rays in zone
F tend to be concentrated equally on all side due to the location of the speaker. Some of the rays made
through pass other zones due to minimal partition in the space.
159
Figure 55: Acoustic ray diagram for human activities
The diagram above shows the acoustic rays originated from the speaker located at ground floor as indicated
in the floor plan. The red circle indicates the position of the speaker. Based on figure 55, we can observe that
the concentration of the bouncing rays in the zone B and C are distributed evenly to all side while zone A
tend to be concentrated on the east and west side of the plan.
160
Figure 56: Acoustic ray diagram for human activities
The diagram above shows the acoustic rays originated from the speaker located at first floor as indicated in
the floor plan. The red circle indicates the position of the speaker. Based on figure 56, we can observe that
the concentration of the bouncing rays in zone F for human activities noise tend to be concentrated equally
on all side while some of the rays gets to zone E. Hence, the acoustic rays are reflected and don't contain in
the space.
161
2.6 Acoustic Conclusion
Figure 57: Acoustic ray diagram for human activities
Figure 58: Acoustic ray diagram for speaker
162
Based on the observations and analysis, it can be seen that the noise levels in AMPM Café are
higher in zone B and zone C due to the fact that most of the customers are located there. Moreover, the
presence of speakers also contributes to the noise level in the cafe.
In zone B, the noise produced by the speaker is concentrated on the southwest of the area which is
zone C, while the noise produced by the speaker in zone C is concentrated on the northeast of the area,
zone B. This is due to the open floor plan with minimal partitions, exposed various noise sources to each
other. The sounds propagate throughout the whole space easily with increasing the overall sound pressure.
During peak hours, zone B will have lots of occupants and it is exposed to zone C, which is the food and
beverage preparation area, which as well have a high noise source coming from the electrical appliances to
staff moving around preparing food. But the sounds from the electrical appliances have no significant noise
due to their noise is overshadowed by the loud noise from the speakers and the human activities.
In addition to that, the use of large glass door/partition to separate zone A from zone B and zone C
from the exterior is insufficient due to their low sound insulation. The outdoor noise can be easily heard from
the interior thus affecting the overall acoustic performance of the interior zones, zone B and zone C. Zone B
and zone C are situated near zone A which has the highest sound intensity level during peak hour due to its
contact with the outside chaotic environment with no buffers like trees or fences causing direct exposure to
the main indoor dining area. These causes zone B and zone C to be the noisiest area in the café.
On the other hand, zone F has the lowest noise level in the café. This is because of its strategic
location and the only zone that meets the sound requirement for a restaurant. Zone F is located on the first
floor at the back area of the café, facing the back lane. It will only open to customers during peak hour. Thus,
with the lowest occupancy, the sound tends to be concentrated evenly and equally to all sides of the area.
The presence of ample cushioned and upholstered furniture helps in absorbing the sound sufficiently. In
addition to that, this zone use rough surfaces material which has slightly higher absorption coefficient
compared to smooth concrete like brick walls and rough concrete.
In conclusion, zone B and zone C are the noisiest zones during peak-hour. Whereas zone F is the
least noisy zone regardless the peak hour or non-peak hour.
163
REFERENCES
1. Oosterhoff, H. (2015). Sounds right, Build 149. Retrieved November 9, 2016, from
http://www.buildmagazine.org.nz/assets/PDF/Build-149-68-Feature-Noise-In-Buildings-Sounds-
Right.pdf
2. Paroc. (n.d.). Sound absorption. Retrieved November 09, 2016, from
http://www.paroc.com/knowhow/sound/sound-absorption
3. Woodford, C. (2016). Soundproofing a room | Science of noise reduction. Retrieved November 09,
2016, from http://www.explainthatstuff.com/soundproofing.html
4. August Wilson Center for African American Culture / Perkins Will. (2011). Retrieved November 06,
2016, from http://www.archdaily.com/163047/august-wilson-center-for-african-american-culture-
perkinswill/
5. Importance of INTERIOR ACOUSTICS for Architect and ... (n.d.). Retrieved November 6, 2016,
from https://www.linkedin.com/pulse/importance-interior-acoustics-architect-designer-praveen-
mishra
6. https://www.engr.psu.edu/ae/thesis/portfolios/2008/mpr184/files/final_report/Body_Full.pdf