building 3 operation handbbok
DESCRIPTION
ÂTRANSCRIPT
Building 3 Handbook
Page 1 24/12/2013
Building 3
Handbook
Building 3 Handbook
Page 2 24/12/2013
Table Of Content
Table of Content……………………………………………………………………………..………………...2
Introduction………………………………………………………………………………………………….…...5
1.Definition Of the Building………………………….………….…………………..……………….4
Building Drawings……………………………………………………………………..……………………..6
1. Drawing and definition for level 0…………………………………………...……………….6
2. Drawing and definition for level 2…………………………………………….……………..8
3. Drawing and definition for level 3…………………………………………………………...11
4. Drawing and definition for level 4…………………………………………………………...14
5. Drawing and definition for level 5…………………………………………………………...17
HVAC Service……………………………………………………………………………….….……………….20
Air Handling Unit…………………………………..………………………………………………..21
Fan Coil Unit………………….………………………………………………….….………………..23
Air Cooling Unit …………………………………….……………………….……….................24
Exhaust Fan Unit………………...……………..………………….……………………………....25
Stair Pressurization System……………….….………………………….…………………….26
Control Valves…………………….…………………………….……………………….……………27
Chilled Water Pumps……………………………………….…………….………….…………...28
Motor Control Panels………………………………….……………………………..…………..29
Variable air Valve & Volume Unit…………………………….……………….……...…...30
Fume Hood…………………….………………………………………...………….……………..31
Cold Room………………….………………………………………...……………..……………..32
Fire Smoke Dumpers……………………………..…………………………...………….…...33
Building 3 Handbook
Page 79 24/12/2013
Emergency Contact #: Land Line – 911 Mobile: 012 8080911
I hope this Handbook will be a useful subject in the delivery of the
required information that will aid its readers in the operation of
this facility, I want to thank everyone who had contributed their
efforts, time and skills to complete this Handbook through the col-
lection of its data.
For any additional or unclear matters related to this manual, kindly
be free to contact me as per the below provided information;
WISSAM EL KHATIB
Unit 1A-B Manager
Contact # : 0569738867
Building 3 Handbook
Page 78 24/12/2013
Building 3 Handbook
Page 3 24/12/2013
Table Of Content
Lift & Automation………………………………………………………………………………..…….…….34
1. Elevators………………………………………………………………………………………….….……..34
2. Shutter Doors…………………………………………………………………………..…….…….....36
3. Cradles…………………………………………………………………………………………...….…....36
4. Loading Dock……………………………………………………………………………….…...……..36
Electrical Service…………………………………………………………………………………...….…...37
Distribution Switchgear-Substation……………...………………………………....……...38
Electrical Panel………………………………………………………………..……………….....…..39
3. Dimming System / Lutron System……………………..…………...…..…………...……..40
4. PMS (Power Monitoring System)……………………..…………….…………....…...…….40
5. Motorized Blinds…………………………………………………….………………………....…….40
6. Power Protection………………………………………………….…………………....……..…….41
7. Light Fixtures………………………………………………………….…………………....…..…...…42
Fire Fighting & Alarm System……………………………………………………….....…...47
VESDA (Early Warning Aspirating Smoke Detection)…………………..……….…..….48
Hydraulic & Plumbing Service………………………………………………………...…….49
Fire Fighting System……………………………….………………………………………..….……..50
R.O System………………………………………………………….…………………….……...………..56
N2 System……………………………….…………………………………………………….………..…..57
Vacuum System……………………………………..………………….………………….……..……..58
Compressed Air System……………………….…………………….……………….….……….....59
Drinking Fountain………………………….……………….…………………..……………......……59
Solar System…………………………………………………….…………………………...……….……59
Eye Wash…………………………………………………………………………………………………….59
Building 3 Handbook
Page 4 24/12/2013
Table Of Content
Civil Service…………………………………………………………………………………………..…60
1. Types Of civil Items……………………………………………………………………..…...60
2. Floor finishing tables for the floor materials ………………………………..….63
3. Floor finishing drawings for the types and codes of materials………...64
Audio Visual System …………………………………………………………………………...….69
Core Lab Services……………………………………………………………..………………….....71
Campus Emergency Evacuation Plan……………………………………………….…….74
Thank You…………………………………………………...……………….……...…..79
Building 3 Handbook
Page 77 24/12/2013
Building 3 Handbook
Page 76 24/12/2013
Building 3 Handbook
Page 5 24/12/2013
Introduction
This user guide provides an overview to the main aspects and components
of building 3 and its facilities.
Definition Of The Building.
Building 3 is one of the most sophisticated lab facility in comparison with
the other buildings, it contains 30 Labs that runs different types of re-
searches, The area of the facility is 63,515 SQM. which is divided among 5
levels, each level as well contain 6 areas, the catwalks which are above
the labs holds all the supports & electromechanical wirings & ducting that
provides for the labs a continuous supply of electricity, water, supply of
gas...etc.
This Booklet contains important data that’s mandatory required for it’s us-
ers to operate this facility such as ( HVAC`s , Electricals , Hydraulics , Fire
Alarm Systems , CIVIL`s & Audio Visual) .
Building 3 Handbook
Page 6 24/12/2013
Building 3 Drawings Building 3 Level 0
Building 3 Handbook
Page 75 24/12/2013
Building 3 Handbook
Page 74 24/12/2013
Campus Emergency Evacuation PlanCampus Emergency Evacuation Plan
Building 3 Handbook
Page 7 24/12/2013
Definition of Level 0.
The floor space in level 0 is 13,732.69 sqm, it is mainly a technical area where
all the technical rooms are in area 3 & area 6 in addition to the Labs / clean
room in area 1 & area 4. Also in level 0 we have the auditorium in area 5.
The distribution below shows how many Labs, conference rooms, work-
stations and PI offices we have in level 0 and in which areas.
Area 1 Area 2 Area 3 Area 4 Area 5 Area 6
Level 0 1 1
Area 1 Area 2 Area 3 Area 4 Area 5 Area 6
Level 0 3 9 3 2
Area 1 Area 2 Area 3 Area 4 Area 5 Area 6
Level 0 18 24 7
Conference Rooms
PI Offices/Offices
Workstations
S/N LAB NO.
LOCATION UPDATED as of 10 SEPT 2013
LAB NAME NEW LAB NUMBER
Bldg Level Area ZONE
1 CFO 100
3-0400 B3 L0 A1 600 Advanced Nanofabrication
2 CFO 800
3-0300 B3 L0 A4 800 Imaging & Characterization
3 CFO 900
3-0352 B3 L0 --- --- NMR - Nuclear Magnetic Resonance
List Of the Labs
Building 3 Handbook
Page 8 24/12/2013
Building 3 Level 2
Building 3 Handbook
Page 73 24/12/2013
7- PCW (Process Chilled Water)
Responsible for cooling down the
equipment / tools used by the end
user
8- RAHU
Maintain the parameters inside the lab in
terms of pressure and temperature
9- Nitrogen Purifier
Provide purifier nitrogen for the
end user
10- Dry Scrubber / Wet Scrubber
Neutralizing the toxic gas in case of any
leak
Building 3 Handbook
Page 72 24/12/2013
3- Stream Generator
Maintain the humidity condition for
the lab environment .
4- DDU Dehumidification Unit
Maintain the humidity condition for
the lab environment.
5- CDA Compressed Dried Air
Provide compressed dry air for the
end user for special cleaning pur-
pose
6- AWN Acid Waste Neutra Plant
Treatment of the waste water com-
ing from the Nano lab, for safety
environment purpose
Building 3 Handbook
Page 9 24/12/2013
Definition Of Level 2.
The floor Space in level 2 is 13,699.51 Sqm, it contain labs– conference
Rooms, PI Offices & Workstations.
The Distribution below shows how many labs-Conference Rooms-
Workstation & PI Offices we have and in which areas.
Area 1-4 Area 2 Area 3-6 Area 4 Area 5 Area 6
Level 2 1 1 1
Area 1 Area 2 Area 3 Area 4 Area 5 Area 6
Level 2 2 2
Area 1 Area 2 Area 3 Area 4 Area 5 Area 6
Level 2 40 36 40 36
Conference Rooms
PI Offices/Offices
Workstations
PI Office Workstations
Building 3 Handbook
Page 10 24/12/2013
S/N LAB NO.
LOCATION
UPDATED as of 10 SEPT 2013 LAB NAME NEW LAB
NUMBER Bldg Level Area ZONE
List Of The Labs
1 LFO 10 3-2610 B3 L2 A1 600 Metal Nano structural & High Resolution Tomog-raphy
2 LFO 20 3-2620 B3 L2 A1 600 Functional Materials
3 LFO 40 3-2630 B3 L2 A1 600 Integrated Nanotechnology
4 LFO 59 3-2640 B3 L2 A1 600 (IMPACT) Integrated Microwave Packaging An-tennas & Circuits Tech Lab
5 LFO 54 3-2650 B3 L2 A1 600 Distributed Sensing Systems
6 LFO 60 (S4)
3-2730 B3 L2 A3 700 Macromolecular Science & Engineering (Swing Lab 4)
7 LFO 61 (S4)
3-2730 B3 L2 A3 700 Inorganic Synthesis Lab (Swing Lab 4)
8 LFO 62 (S4)
3-2730 B3 L2 A3 700 NPMWDR - Nanostructured Polymeric Mem-branes & Water Desalination Research (Swing Lab 4)
9 LFO 63 (S4)
3-2730 B3 L2 A3 700 Multicomponent Membranes Lab (Swing Lab 4)
10 LFO 28 3-2820 B3 L2 A4 800 Thin Film
11 LFO 64
(UNDER CON-STRUCTION)
B3 L2 A6 --- Microfluids Thrust Lab
Building 3 Handbook
Page 71 24/12/2013
Core Lab Services High end lab in which the below facilities are maintained by our core labs
maintenance team, it is located in building 3 level 0 .
1- PVAC (vacuum Pumps)
Provide Vacuum to the end users
within the required pressure
2- DIWP (DI Water)
Provide ultra pure water under specific
parameters.
Building 3 Handbook
Page 70 24/12/2013
Plasma TV Projector Controller with Laptop
Projector
Video Camera (TANBERG) Big White screen
IT System
Building 3 Handbook
Page 11 24/12/2013
Building 3 Level 3
Building 3 Handbook
Page 12 24/12/2013
Definition Of level 3.
The floor space in level 3 is 12,023.87 sqm, and it contain Labs,
Conference rooms, workstations, & PI Offices.
The distribution below shows how many labs, conference rooms,
PI Offices & workstations do we have and in which areas.
Conference Rooms
Area 1-4 Area 2 Area 3-6 Area 4 Area 5 Area 6
Level 3 1 1 1 1
PI Offices/Offices
Area 1 Area 2 Area 3 Area 4 Area 5 Area 6
Level 3 6 8 6 8
Workstations
Area 1 Area 2 Area 3 Area 4 Area 5 Area 6
Level 3 55 16 36 57 16 36
Building 3 Handbook
Page 69 24/12/2013
Audio visual System Due to the importance of building 3, it holds many conference rooms in addi-
tion to a big auditorium that can handle up to 150 people, these conference
rooms are equipped with world’s best audio visual systems, the micro-
phones, audio mixers, still and video cameras, film projectors, slide projec-
tors, VCRs, CD and DVD players/recorders, amplifiers and speakers allows
the users of these rooms to have a clear & pleasant experience while watch-
ing or being a part of a scientific lecture
Touch Panel (CRESTRON), IT Controller for the auditorium
Big White Screen in Auditorium
Building 3 Handbook
Page 68 24/12/2013
Building 3 Handbook
Page 13 24/12/2013
List Of The Labs
1 LFO 4 (S2)
3-3730 B3 L3 A3 700 Solar Technology (Swing Lab 2)
2 LFO 42 (S2)
3-3730 B3 L3 A3 700 Organic Spintronics (Swing Lab 2)
3 LFO 45 (S2)
3-3730 B3 L3 A3 700 Functional Nanomaterials (Swing Lab 2)
4 LFO 54 (S2)
3-3730 B3 L3 A3 700 Distributed Sensing Systems (Swing Lab 2)
5 LFO 59 (S2)
3-3730 B3 L3 A3 700 (IMPACT) Integrated Microwace Packaging An-tennas & Circuits Tech Lab (Swing Lab 2)
6 LFO 62 (S2)
3-3730 B3 L3 A3 700 NPMWDR - Nanostructured Polymeric Mem-branes & Water Desalination (Swing Lab 2)
7 LFO 16 3-3810 B3 L3 A4 800 Photonics
8 LFO 25 3-3820 B3 L3 A4 800 Semiconductor and Material Spectroscopy (SMS)
9 LFO 45 3-3830 B3 L3 A4 800 Functional Nanomaterials
10 LFO 35/36
3-3840 B3 L3 A4 800 Advanced Micro & Nano Systems
11 LFO 17 3-3850 B3 L3 A4 800 Sensor
12 LFO 65 3-3910 B3 L3 A6 900 Open Access - Analytical Core Lab
13 LFO 29 3-3930 B3 L3 A6 900 Analytical Core Lab
S/N LAB NO.
LOCATION
UPDATED as of 10 SEPT 2013 LAB NAME NEW LAB
NUMBER Bldg Level Area ZONE
Building 3 Handbook
Page 14 24/12/2013
Building 3 Level 4
Building 3 Handbook
Page 67 24/12/2013
Building 3 Handbook
Page 66 24/12/2013
Building 3 Handbook
Page 15 24/12/2013
Definition Of level 4.
The floor space in level 4 is 12,023.87 sqm, and it contain Labs,
Conference rooms, workstations, & PI Offices.
The distribution below shows how many labs, conference rooms,
PI Offices & workstations do we have and in which areas.
Conference Rooms
Area 1-4 Area 2 Area 3-6 Area 4 Area 5 Area 6
Level 4 1 1 1 1
PI Offices/Offices
Area 1 Area 2 Area 3 Area 4 Area 5 Area 6
Level 4 6 8 6 8
Workstations
Area 1 Area 2 Area 3 Area 4 Area 5 Area 6
Level 4 54 16 36 54 16 36
Building 3 Handbook
Page 16 24/12/2013
List Of The Labs
S/N LAB NO.
LOCATION
UPDATED as of 10 SEPT 2013 LAB NAME NEW LAB
NUMBER Bldg Level Area ZONE
1 LFO 9 3-4620 B3 L4 A1 600 Catalysis Research Center
2 LFO 9 3-4730 B3 L4 A3 700 Catalysis Research Center
3 LFO 9 3-4830 B3 L4 A4 800 Catalysis Research Center
4 LFO 9 3-4930 B3 L4 A6 900 Catalysis Research Center
5 LFO 55 (Inside LFO9)
(UNDER CON-STRUCTIO
B3 L4 A4 --- Micellar and Super molecular Catalysis
6 LFO 56 (Inside LFO9)
(UNDER CON-STRUCTIO
B3 L4 A3 --- Heterogeneous Photocatalysis
Building 3 Handbook
Page 65 24/12/2013
Building 3 Handbook
Page 64 24/12/2013
Building 3 Handbook
Page 17 24/12/2013
Building 3 Level 5
Building 3 Handbook
Page 18 24/12/2013
Definition Of level 5.
The floor space in level 5 is 12,035.28 sqm, and it is mainly a mechanical
area for the AHUs in addition to the conference rooms.
Conference Rooms
Area 1 Area 2 Area 3 Area 4 Area 5 Area 6
Level 5 4 4
Building 3 Handbook
Page 63 24/12/2013
Building 3 - IBN Sina Laboratory Building
Floor Finishing
S/N
Items Level
0 Level
2 Level
3 Level
4 Level
5
Total Quanti-ty SQM
1 Carpet- Fixed Beige C-0A 729 729
2 Carpet - Beige with green circles C-0B
0
3 Carpet - Red C-0C 111 36 36 29 212
4 Carpet - Grey C-0D 101 101
5 Carpet - Syncopation C-50 1,681 1,970 3,029 3,029 9,709
6 Carpet - Syncopation C-53 39 67 67 173
7 Carpet - Soulmate C-55 74 149 74 297
8 Carpet - Syncopation C-63 151 704 704 504 2,063
9 Concrete CO-00
1454 1,019 2,473
10 Epoxy Coating - Jotun 071 E-0A
7,283 123 292 292 9,767 17,868
11 Epoxy Coating - Bolidtop System - 20626 Light Yellow E-0B
1,042 1,042
12 Granite Absolute Black ST-01 265 162 150 150 73 800
13 Limestone - Egyption yellow St-02
1,316 105 105 382 1,908
14 Stone Base
St-50A
722 1,195 970 1,045 241 4,173
15 Vinyle - white QT-01
2,541 2,769 2,055 4,116 11,481
16 Vinyle - Grey Qt-0A 20 28 28 34 110
17 Stainless Steel Mesh
STS-00
24 24
12593 10137 9646 9646 1103
0
Building 3 Handbook
Page 62 24/12/2013
Wooden Wall
Terracotta
CLG-10 Trade 130 (Metal Ceiling), CLG-11 Trade 130 (Ultima) CLG-03B & 03C (Diacaustic)
Bridge between B-2 & B 3
Handrail & Wooden Stair Wall Curtains
Building 3 Handbook
Page 19 24/12/2013
Building 3 Handbook
Page 20 24/12/2013
HVAC SERVICE
Heating, Ventilation, and air conditioning is the technology of indoor and vehicu-
lar environmental comfort
HVAC Equipment
Air Handling Unit
Fan Coil Unit
Air Cooling Unit
Exhaust Fan Unit
Stair Pressurization System
Control Valves
Chilled Water Pumps
Motor Control Panels
Variable air Valve & Volume Unit
Fume Hood
Cold Room
Fire Smoke Dumpers
Building 3 Handbook
Page 61 24/12/2013
Single Steel Door Double Steel Door Single steel door w/window
Double steel door Double wooden door w/
window Double Glass Door
Single wooden door Single wooden door
for toilet cubical
Building 3 Handbook
Page 60 24/12/2013
Civil Service
Double metal door Single metal Door
Double wooden door w/
Push Bar
Single wooden door w/
Push Bar
Single wooden door w/
window
Single steel Door Double Glass Door
Double steel door w/
glass & Push bar
Single metal door w/
glass for all the labs
Building 3 Handbook
Page 21 24/12/2013
Air Handling Unit
AN AIR HANDLER, or air handling unit (often abbreviated to AHU), is a de-
vice used to condition and circulate air as part of a heating, ventilating, and
air-conditioning (HVAC) system. An air handler is usually a large metal box
containing a blower, heating or cooling elements, filter racks or chambers,
sound attenuators, and dampers. Air handlers usually connect to
a ductwork ventilation system that distributes the conditioned air through the
building and returns it to the AHU. Sometimes AHUs discharge (supply) and
admit (return) air directly to and from the space served without ductwork
Air handling unit ( AHU 200 & 100 ) made by:
Area –1 Area –4 Area –3 Area –6
Level –0 - - - 1
Level –5 6 6 6 6
Quantity & Location Of AHU’S
Building 3 Handbook
Page 22 24/12/2013
Building 3 Handbook
Page 59 24/12/2013
5. Compressed Air System Purpose: to supply pure air for LAB .
6. Drinking fountain
There are 42 drinking fountains in
Bldg. 3 distributed into all levels all
areas
7. Solar System
Located in roof top of the building
8. Eye Wash
Located in each lab or any
chemical stores.
Building 3 Handbook
Page 58 24/12/2013
Automatic Dewar Filling Stations: There are 4 LN2 filling stations available in the Lab Building 2 & 3.
1 unit in the Receiving Area of Bldgs. 2 & 3
1 unit in NMR lab
1 unit in Imaging & FEI labs
1 unit in the Clean room
4. Vacuum Systems Purpose: to remove the toxic gases due to the chemical reaction.
Building 3 Handbook
Page 23 24/12/2013
2. Fan Coil Unit (FCU-100)
FAN COIL UNIT (FCU) is a simple device consisting of a heating or cooling coil and fan. It is part of an HVAC system found in residential, commercial, and industrial buildings. Typically a fan coil unit is not connected to ductwork, and is used to control the temperature in the space where it is installed, or serve multiple spaces. It is controlled either by a manual on/off switch or by
thermostat.
Due to their simplicity, fan coil units are more economical to install than duct-
ed or central heating systems with air handling units. However, they can be
noisy because the fan is within the same space. Unit configurations are nu-
merous including horizontal (ceiling mounted) or vertical (floor mounted).
In Building 3
We have 12
FCU
Building 3 Handbook
Page 24 24/12/2013
3. Air Cooling Unit (ACU 101):
AIR COOLING UNIT: is a major or home appliance, system, or mechanism designed to change the air temperature and humidity within an
area (used for cooling and sometimes heating depending on the
air properties at a given time). The cooling is typically done using a sim-
ple refrigeration cycle, but sometimes evaporation is used, commonly for
comfort cooling in buildings and motor vehicles. In construction, a complete
system of heating, ventilation and air conditioning is referred to as "HVAC"
ACU 101 Made by Emerson’s Liebert
In building 3 We have 3 ACU
Building 3 Handbook
Page 57 24/12/2013
3. Liquid nitrogen ( N2 )
is nitrogen in a liquid state at an extremely low temperature.
It is produced industrially by fractional distillation of liquid air. Liquid nitrogen is a colorless clear liquid with density of 0.807 g/mL at its boiling point and a dielectric constant of 1.43. Liquid nitrogen is often referred to by the abbre-
viation LN2 .
LN2 Withdrawal Vessels : Primary Vessel; 34,070 Liters feeding to the Vaporizers then converted to Ni-trogen gas for the Buildings nitrogen gas system .
Secondary Vessel; 22,712 Liters supplying directly Liquid Nitrogen-LN2 thru
vacuum jacketed (VJ) piping system to NMR & Cleanroom .
Building 3 Handbook
Page 56 24/12/2013
Building 3 Handbook
Page 25 24/12/2013
4. Exhaust Fan Unit ( EXF 100 )
Exhaust Fans: A mechanical ventilation device that helps to draw out stale and
impure air from your occupied area and bring in fresh air, thereby improving
the quality of indoor air. Exhaust fans are typically ducted to the exteriors of
your facility, through which bad indoor air can effectively be removed from your
working space.
Building 3 Handbook
Page 26 24/12/2013
5. Stair Pressurization System
STAIR PRESSURIZATION SYSTEMS are the most commonly utilized means
for protecting exit stairwells in high-rise buildings from smoke in the event of
fire. Stair pressurization systems are difficult to design for tall buildings due to
the impact of stack effect on maintaining uniform pressures over the building’s
height, and creation of excessive door overpressures that may impact exiting
is a concern. The effectiveness of a stair pressurization system is also depend-
ent on maintaining the doors predominately closed to maintain the required
pressure differential to keep smoke from entering the stair, a situation that may
not be possible during the event of a full building evacuation or where cata-
strophic damage has occurred to the stair.
Building 3 Handbook
Page 55 24/12/2013
2. Reverse osmosis (RO) :
is a water purification technology that uses a semipermeable membrane.
This membrane-technology is not properly a filtration method. In RO, an ap-
plied pressure is used to overcome osmotic pressure, a colligative property,
that is driven by chemical potential, a thermodynamic parameter. RO can re-
move many types of molecules and ions from solutions and is used in both in-
dustrial processes and in producing potable water. The result is that
the solute is retained on the pressurized side of the membrane and the
pure solvent is allowed to pass to the other side.
Building 3 Handbook
Page 54 24/12/2013
Stand pipes and hose cabinets : In each level behind the landing valve hose cabinet installed for emergency cases. In each cabinet we found two high pressure fire hoses and one water regula-tor gun.
This cabinets should be checked every month by trained team .
Fire Fighting Pumps
Building 3 Handbook
Page 27 24/12/2013
6. Control Valves
Control valves used to control conditions such as
flow, pressure, temperature, and liquid level by fully or partially opening or
closing in response to signals received from controllers that compare a "set
point" to a "process variable" whose value is provided by sensors that moni-
tor changes in such conditions
Building 3 Handbook
Page 28 24/12/2013
7. Chilled Water Pumps
Chilled water Pumps is a commodity often used to cool a building's air and
equipment, especially in situations where many individual rooms must be
controlled separately, such as a hotel.
Building 3 Handbook
Page 53 24/12/2013
Stand pipes and hose cabinets : The stand or the main riser installed in the corner of the emergency stair case . The role of this riser is to supply the water to each branch in the building. Landing valve installed on stand pipe per each level to supply water to the fire hoses in emergency cases . Check valve and alarm control gate valve installed per each level.
Building 3 Handbook
Page 52 24/12/2013
Sprinklers used in the campus are of different manufacturers but of the same specification . There are four types of sprinklers used in the manufactured by two dif-ferent companies Tyco and Reliable . Types of sprinklers used from TYCO :
Fast response pendent sprinklers .
Rapid response residential pendent sprinklers ( white cover )
Recessed pendent sprinklers
Types of sprinklers used from Reliable :
Concealed pendent (chrome cover ) RFC 43
The common specification for all types of sprinklers are:
Ambient temperature : 38 C
Operation temperature : Varies from 68 to 74 C.
Minimum distance between sprinklers : 2200 mm
Maximum covers : 3600*3600 mm2 .
Maximum pressure discharge :12 bars .
Minimum pressure discharge : 7.2 bars
Building 3 Handbook
Page 29 24/12/2013
8. Motor Control Panels
Motor Control Panel is a Power distribution systems used in large commercial
and industrial applications & can be complex. Power may be distributed
through switchgear, switchboards, transformers, and panel boards.
Power distributed throughout a commercial or industrial application is used
for a variety of applications such as heating, cooling, lighting, and motor-
driven machinery
Building 3 Handbook
Page 30 24/12/2013
9. Variable air Valve & Volume Unit
Variable Air Volume (VAV) is a type of heating, ventilating, and/or air-
conditioning (HVAC) system. The simplest VAV system incorporates
one supply duct that, when in cooling mode, distributes approximately 55 °
F (13 °C) supply air. Because the supply air temperature, in this simplest of
VAV systems, is constant, the air flow rate must vary to meet the rising and
falling heat gains or losses within the thermal zone served.
Building 3 Handbook
Page 51 24/12/2013
Building 3 Handbook
Page 50 24/12/2013
1. Fire Fighting System: Supply Piping Network
The riser diagram up shows the supply network for the campus buildings. Each branch controlled by check valve and alarm control gate valve. Three control valves installed on the main line between building 18 and five ,building 3 and 1,the third inside the pump room between building 2 and 14 . The main line supply to RPIC and two hydrants FH9 and FH11 a crossing the road under the ground by 200mm UPVC pipe.
Building 3 Handbook
Page 31 24/12/2013
10. Fume Hood
A fume hood or fume cupboard is a type of local[1] ventilation device that is designed to limit exposure to hazardous or toxic fumes, vapors or dusts. A fume hood is typically a large piece of equipment enclosing five sides of a work area, the bottom of which is most commonly located at a standing work
height.
Two main types exist, ducted and recirculating (aka ductless). The principle is
the same for both types: air is drawn in from the front (open) side of the cabi-
net, and expelled outside the building .
Building 3 Handbook
Page 32 24/12/2013
11. Cold Room
Cold rooms are designed to control temperature and humidity levels at very
close tolerance control levels based on the requirements of each specific
application. Many rooms are utilized for medical and biopharmaceutical re-
search and development, with other applications requiring close tolerance
control for human performance test labs, film testing and development, ma-
terials testing, and stability testing. The designs of these rooms based on
the fundamental guideline
that no compromises concerning room temperature gradient, microprocessor
controls, refrigeration system quality, and humidity control devices can be
allowed past our doors
Building 3 Handbook
Page 49 24/12/2013
Hydraulic Service
1. Fire Fighting System
2. R.O System
3. N2 System
4. Vacuum System
5. Compressed Air System
6. Drinking Fountain
7. Solar System
8. Eye Wash
Building 3 Handbook
Page 48 24/12/2013
1. Vesda ( Early Warning Aspirating Smoke Detection )
VESDA by Xtralis very early warning aspirating smoke detection solutions with
continuous air sampling provide the earliest possible warning of an impending
fire hazard. VESDA ASDs buy the critical time needed to investigate an alarm
and initiate an appropriate response to prevent injury, property damage or
business disruption. VESDA detectors have multi-level warnings and a wide
range of sensitivity that does not degrade or change over time, so even minute
levels of smoke can be detected before a fire has time to escalate. In addition,
VESDA systems are manufactured using targeted Six Sigma techniques and
ISO 9000 standards and have been certified by regulatory bodies worldwide.
Vesda ( Early Warning Aspirating Smoke Detection
Building 3 Handbook
Page 33 24/12/2013
12. Fire Smoke Dumpers
Fire dampers are passive fire protection products used in heating, ventila-
tion, and air conditioning (HVAC) ducts to prevent the spread of fire inside
the ductwork through fire-resistance rated walls and floors.
Building 3 Handbook
Page 34 24/12/2013
LIFT & AUTOMATION
2 panoramic Schindler elevators
2000 KG-26 Persons
One Schindler freight elevator 7200
KG-96 Persons
6 Schindler service elevator 2500
KG-33 persons
Elevators
Building 3 Handbook
Page 47 24/12/2013
Fire Fighting & Alarm SystemsFire Fighting & Alarm Systems
Cultural property management is entrusted with the responsibility of
protecting and preserving an institution's buildings, collections, oper-
ations and occupants. Constant attention is required to minimize ad-
verse impact due to climate, pollution, theft, vandalism, insects, mold
and fire. Because of the speed and totality of the destructive forces of
fire, it constitutes one of the more serious threats. Vandalized or envi-
ronmentally damaged structures can be repaired and stolen objects
recovered. Items destroyed by fire, however, are gone forever. An un-
controlled fire can obliterate an entire room's contents within a few
minutes and completely burn out a building in a couple hours.
The first step toward halting a fire is to properly identify the incident,
raise the occupant alarm, and then notify emergency response profes-
sionals. This is often the function of the fire detection and alarm sys-
tem.
Building 3 Handbook
Page 46 24/12/2013
Sure Lights – EXIT Signs ( X – 04 )
Projector – Flood Lights( H – 25
Square Operator Lights ( H – 23 )
Building 3 Handbook
Page 35 24/12/2013
Locations and numbers of the elevators
6
9
8
3
5 4
7 2
Building 3 Handbook
Page 36 24/12/2013
There are 3 types of shutter doors in
building 3.
Fire Rated: 4 Doors
Aluminum: 9 Doors
Galvanized: 4 doors
One loading dock in level 0 area 6
For loading or unloading any shipment
from or to building 3
2 Sky fold door to separate the confer-
ence room in level 5 area 1&4
2 Cradles in the roof top of the building,
to use them for any maintenance or
cleaning work on the envelop of the
building.
Building 3 Handbook
Page 45 24/12/2013
Sky Dome( F – 40 )
Leda Lite Voice ( F – 40 )
Light cast Down light ( C – 01 )
Building 3 Handbook
Page 44 24/12/2013
Steller ( F – 28 )
Infinite 3 fixture( F – 28 )
HID Mini Base Mount ( H – 28 )
Building 3 Handbook
Page 37 24/12/2013
ELECTRICAL SERVICE Electrical Power System: is a network of electrical components used to sup-
ply, transmit and use electric power.
Electric power is the product of two quantities: Current and Voltage. These two
quantities can vary with respect to time (AC Power) or can be kept at constant
levels (DC Power).
Most refrigerators, air conditioners, Pumps and industrial machinery use AC
Power whereas most computers and digital equipment use DC Power (the dig-
ital devices you plug into the main typically have an internal or external power
adapted to convert from AC to DC power).
Factors and Components of Building Electrical System are:
Distribution Switchgear-Substation– transforms the voltage from high to
low and distribute to low voltage panels.
2. Distribution Panels– Distribute the power to sub panels
3. Distribution Panels– Distribute the power to sub panels
4. Low voltage panels– distribute power to loads like heaters, dumpers,
sockets, etc…
5. Dimming System– Controls the lighting system of the building
6. PMS (Power Monitoring System).
7. Motorized Blinds– it is a motorized and programmable window shade.
8. Lighting protection is a metal rod or metallic object mounted on the top of
the building using a wire or electrical conductor to interface with ground or
earth through an electrode engineered to protect the building in the event of
lighting strike.
Building 3 Handbook
Page 38 24/12/2013
1. Distribution Switch Gear (Substation)
In building 3 there are 4 electrical substations with normal power in level 0 and
one emergency substation– stand by power or backup
Substation input: 13.8 KV 60 HZ Substation Output: 380 V 60 HZ
A Substation is a part of an electrical generation, transmission, and distribu-
tion system. Substation transform voltage from high to low or the reverse.
A substation include transformers to change voltage levels between high
transmission voltages and lower distribution voltages.
Building 3 Handbook
Page 43 24/12/2013
Eklisse ( F – 14 )
CROMPACK Reflectors with wire guard ( F – 17 )
Building 3 Handbook
Page 42 24/12/2013
8. Lighting Fixtures (Low Voltage)
Voice Suspended Product ( F – 39 -1 )
Leda Lite Pure FX ( F – 34 )
Building 3 Handbook
Page 39 24/12/2013
2. Distribution Panel
Distribution panel is a component of an elec-
tricity supply system which divides an electri-
cal power feed into subsidiary circuits, while
providing a protective circuit breaker for each
circuit, in a common enclosure
3. Sub Panel/ Low Voltage Panel
Sub-Panel are separate breaker panels that
can contain new circuits, allowing you to
readjust energy distribution.
Building 3 Handbook
Page 40 24/12/2013
4. Dimming System /Lutron System
Lutron light control products range from individual dimmers to total light
management systems that control entire building complex.
No matter where they are installed or how big the system, every Lurton
product saves energy by reducing electrical consumption.
Lutron also protect the environment by decreasing the demand for light
bulbs. Since lamp life, customers have to buy fewer bulbs, and that re-
duces the energy and environmental impacts associated with the manu-
facturing of fluorescent, incandescent, halogen, and other types of lamps
5. PMS (Power Monitoring System)
6. Motorized blinds
Motorized blinds can complete-
ly raise or lower the window
shade or curtains by using
the touch of a button.
PMS is a monitoring task, such as power
trending, controlling and identification of
source of energy consumption and load
profiles of power supply segments
Building 3 Handbook
Page 41 24/12/2013
7. Lighting Protection
A Lighting Rod or Lighting conductor is a metal rod or metallic object mount-
ed on top of a building, electrically bonded using a wire or electrical conductor
to interface with ground or earth through an electrode, engineered to protect
the building in the event of lighting strike. If lighting hits the building it will pref-
erentially strike the rod and the conducted to ground through the wire, instead
of passing through the building, where it could start a fire or cause electrocu-
tion