BUILDING SERVICES (BLD 60903 / ARC 2423)

Project 2 - Building Services For Old Folks’ Home

Prepared By:

Chia Sue Hwa 0317920Joshua Yim 0317945Khor Yen Min 0318149Koh Sung Jie 0318912Lovie Tey 0318155Low En Huey 0317889

Tutor/Lecturer:

Ar. Sateerah Hassan

Page 2: B.serv   project 2 (final report)

Table of Contents

1. Abstract

2. Project Introduction 2.1 Introduction to the Building 2.2 Introduction of Site

3. Active Fire Protection System 3.1 Literature Review 3.2 Fire Detection System 3.2.1 Smoke Detector and Heat Detector 3.3 Triggers 3.3.1 Manual Pull Station 3.4 Fire Alarm System 3.5 Fire Intercom System 3.6 Fireman Switch 3.7 Main Fire Control Panel 3.8 External Fire Hydrant System 3.9 Fire Sprinkler System 3.9.1 Sprinkler Pump 3.9.2 Water Storage 3.10 Hand Operated Fire Fighting Equipment 3.10.1 Fire Extinguisher 3.10.2 Hose Reel System

4. Passive Fire Protection System 4.1 Literature Review 4.2 Purpose Group and Compartment 4.2.1 Separation of Fire Risk Area 4.2.2 Fire-rated Door 4.2.3 Firewall 4.3 Fire Appliance Access 4.4 Means of Escape 4.4.1 Fire Emergency Staircase 4.4.2 Emergency Exit Signs 4..4.3 Emergency Escape Route 4..4.4 Assembly Point

1

112

3355778

10121314151718202021

232325252628293131333536

Page 3: B.serv   project 2 (final report)

3737393943434445464748

494951525456

58585959606063

65

66

5. Air Conditioning System 5.1 Literature Review 5.2 VRV(Variable Refrigerant Volume) System 5.3.1 Introduction and Justification 5.3.2 Principles of VRV 5.3.3 System Structure 5.3.4 Operation System 5.3.5 Outdoor Unit 5.3.6 Points of Refrigerant Control 5.3.7 Cassette Type Indoor Unit 5.3 Lift Air Conditioners 6. Mechanical Ventilation System 6.1 Literature Review 6.2 Wall Ventilation Fan 6.3 Centrifugal Fan 6.4 Ceiling fan 6.5 Exhaust Hood

7. Mechanical Transportation System 7.1 Literature Review 7.2 Machine-Room-less Elevator 7.2.1 Introduction and Justification 7.2.2 Product Information 7.2.3 Components of System 7.2.4 Operation System

9. Conclusion

10. References

Page 4: B.serv   project 2 (final report)

In this assignment, information regarding mechanical ventilation, air-conditioning system, mechanical transportation system as well as fire protection systems were identified and understood. Basic principles, process and equipment of various building services systems found in buildings were introduced. Each system has its own pro’s and con’s, and thus they were studied. Through the analysis, appropriate measures of building services systems were proposed for a multi-storey public building. Their functions, such as the connections, intersections and installation of different parts and equipment were properly understood. The information was summarized in diagrammatic forms and images. Moreover, all of the systems proposed were compared to the UBBL Law requirement and other legal requirements to make sure they were realistic and practical if the building was to be built with the integrated systems.

The chosen building is an elderly centre under a Studio 4 proposal located at Taman Kanapuram. The elderly centre aims to restore the self-worth of the old folks residing in nursery homes nearby through bonding people of similar interest and recognizing their own talents. The building is a two-storey building with an open ground floor plan and a clustered first floor plan. There are many activity spaces ranging from an interactive sewing station to a quiet reading room to a wide open event space.

It is widely dependent of natural ventilation from its lack of barriers, however mechanical ventilation and air-conditioning are still required for the enclosed rooms present. Accessibility between the two floor involves staircases and lifts as its elderly users might have walking disabilities.

Figure 2.1: Rendering of the elderly centre.

1. Abstract

2. Project Introduction

2.1 Introduction to the Building

1

Page 5: B.serv   project 2 (final report)

Figure 2.2 (Top right): Seksyen 18 (red) pinpointed in map of Petaling Jaya, Figure 2.3 (Overall): Bunglow lot (red) pinpointed in Seksyen 18.

Petaling Jaya used to be a rubber estate for the Indian community in Malaya before being developed by the British for Kuala Lumpur’s economic growth. It is home to Assunta Hospital which is located along Jalan Templer, its retiring doctors are heavily invested into opening nursing homes for the elderly due to the ageing crisis. Thus, the appearance of nursing homes in Petaling Jaya has become a natural occurance.

Taman Kanapuram is located at the southeast corner of Petaling Jaya. It was developed by the Jaffnese Cooperative Housing Society since 1954 and was primarily catered for the Indian community ever since. Recently, low-cost apartments were erected to provide housing demands, however many bungalows lots are abandoned and some are converted for non-residential purposes. There are currently 9 nursing homes around Taman Kanapuram and this has introduced a large number of Chinese inhabitants into its Indian community.

2.2 Introduction of Site

2

Page 6: B.serv   project 2 (final report)

Active Fire Protection is a group of systems that require a certain amount of motion and responses in order to work efficiently in the event of fire. It is also about alerting building occupants and to suppress the fire using systems such as fire alarms, sprinkler systems and fire extinguishers. There are few stages in active fire protection which are:

In the event of fire, fire is detected using the fire detector systems. There are several types of detectors such as smoke detector, heat detector and flame detector. Different detectors are used at different area to detect the different characteristics of fire depending on the individual circumstances. The detectors will send the signal to the main fire control panel and activate the alarm system.

In the event of fire, alarm system has to be activated manually to signal the occupants of the building. There are two types of manual fire alarm activation which are the pull station and the call point. Automatic detection system and the manual fire alarm activation can be used in conjunction as an overall fire detection and alarm system. The manual call points are usually visible from sight and are usually connected to a central fire alarm panel which is in turn connected to the alarm system of the building.

Fire alarm system serves primarily to protect life and secondarily to prevent property loss. A fire alarm system must be tailored to the needs of a specific facility. Fire alarm systems has three basic parts: signal initiation, signal processing and alarm indication whereby the signal initiation can be manual (pull stations) or automatic (smoke detectors). The alarm signal is processed by some sort of control equipment, which in turn activates audible and visible alarms.

Fire Intercom System also known as the Remote Handset Station, provides a reliable communication between the Main Fire Control Panel and the Remote Handset Stations.

When the fire brigade arrives, the fire fighters will have to turn off the hazardous electrical equipment in case of fire or explosion through the fireman switch. The switch is located at a clearly visible location.

I. Fire Detection

II. Triggers

III. Fire Alarm System

IV. Fire Intercom System

V. Fireman Switch

3. Active Fire Protection System

3.1 Literature Review

3

Page 7: B.serv   project 2 (final report)

A fire sprinkler system consists of a water supply system, providing adequate pressure and flowrate to a water distributing piping system and onto which fire sprinklers are connected. It is important to have the fire sprinkler system installed to supress rapid fire. There are different types of fire sprinkler depends on the occupancies. The common sprinkler systems are: wet-pipe system, dry-pipe system, deluge system, mist system and pre-action system

Fire extinguisher is a portable device for firefighting purpose. Portable fire extinguishers are classified based on type of fire they are designed to fight. The number of extinguishers required and location of the extinguishers depends on the hazard of occupancy. The portable fire extinguishers are able to control small fire.

1. Hose Reel System 2. Wet Riser System3. Dry Riser System4. Non Water Based Suppression Systems (eg: CO2, Argonite)

VIII. Fire Sprinkler System

IX. Fire Extinguisher System

Other components of Active Fire Protection includes:

A fire hydrant is a connection point by which firefighters can tap into a water supply. It is part of the active fire protection system. Fire hydrant systems are highly pressured that when assembled together by firefighters, will be able to put off the fire. When there is fire, the firefighters will attach a hose to the fire hydrant, and then a valve is opened to provide a powerful flor of water.

VII. External Fire Hydrant System

The main fire control panel is the controlling component of a fire alarm system. The panel received notifications and signals for potential issues with equipment that could cause a fire. At the same time, it alerts the employees inside the building if fire is detected. There are different types of panels, such as coded panels, conventional panels, addressable panels, and multiplex systems.

VI. Main Fire Control Panel

4

Page 8: B.serv   project 2 (final report)

Under the fire detection systems, smoke detectors provide early warning to the occupant when smokes are detected. The key advantage of smoke detectors is their ability to identify a fire while it is still in its incipient. As such, it is important to use smoke detectors in the elderly day care centre as it buys more time for the elderlies to evacuate when there is fire. They are also highly reliable as they have a very low probability of false alarm that may affect the elderlies.

There are two types of smoke detectors contain either the ionization type or the photo-electronic sensors. Each type of smoke detectors detect different types of fire. Research indicates that photo-electronic detectors provide sufficient time for occupants to escape from smouldering and flaming fires whereas for ionisation detectors, they are more sensitive to the flaming stage of fires.

For the elderly day care centre, photo electronic smoke detectors are chosen as part of the system as they are generally more responsive to fires that begin with a long period of smouldering. They are screwed to the ceiling as that is where smoke heads for when something is burning. In this type of detector, a light source is used to detect smoke. The infra-red LED is a lens that shots a light beam over a large area. At an angle to the LED is a photo-diode which normally does not register the column of light emitted by the LED. When there is smoke present in the room, the smoke particles will cause the light to scatter and hence registered by the photo-diode. It will then trigger the alarm when there is sufficient light on the photo-diode.

Smoke detectors are installed at lift lobbies, lift shafts, corridors, common areas and exit routes. They are mostly installed side by side with sprinkler unit to put out fire at instance. Due to nature of kitchens which are regularly filled with smoke, smoke detectors installed at kitchen might cause false alarms. Thus, heat detectors are more suitable to be installed at the kitchen as they will detect abnormally high temperatures or rapid rises in temperature which will alert a potential fire in kitchen.

3.2.1 Smoke Detector and Heat Detector

3.2 Fire Detection System

Figure 3.1: Diagram of how photo-electronic detector works. Figure 3.2: Example of photo-electronic smoke detector

5

Page 9: B.serv   project 2 (final report)

UBBL 1984 Section 153: Smoke detectors for lift lobbies

(1) All Lift lobbies shall be provided with smoke detectors (2) Lift not opening into a smoke lobby shall not use door reopening devices controlled by light beam or photo-detectors unless incorporated with a force close feature which after thirty seconds of any interruption of the beam causes the door to close within a pre-set time.

Figure 3.3: Location of fire detectors at Ground Floor & First Floor.

6

Page 10: B.serv   project 2 (final report)

In order to activate the pull station alarm system, the user has to pull down the handle to trigger the alarm. After operation, building personnel will reset the fire alarm pull station using a key after investigating the cause of alarm. Hence, alarm is reset from the fire alarm control panel when the handle is back to its original position.

For the elderly day care centre, a dual-action fire alarm pull station is needed. As such, the user is required to perform a second task before pulling the handle down. A clear plastic stopper cover is installed on top of the pull stations. This is to prevent accidental movement from the elderlies that trigger the alarm which in turn creates false alarms. Also, by plastic covers, it is much safer compared to glass as the possibility of broken glass may harm the elderlies. The pull stations are installed at a height of 1.2m above floor level at easily accessible positons.

In the elderly day care centre, the manual pull stations are spaced at a maximum distance of 25m as there are elderlies with limited mobility. Some mounting height of the manual pull stations are at a lower height so that the disabled people can operate the stations. Manual pull stations are located on escape routes, exits points to open air. More stations are installed in the centre as the elderlies are likely to be slow in movement in the event of evacuation.

3.3.1 Manual Pull Station

3.3 Triggers

Figure 3.5: Location of the manual pull stations at Ground Floor & First Floor.

Figure 3.4:: Example of activated pull station

underneath a plastic stopper cover.

7

Page 11: B.serv   project 2 (final report)

For the elderly day care centre, a two stage fire alarm system is used. A two stage alarm system is designed so that the activation of any signal initiating device (manual pull station and smoke detector) will cause an alert signal to sound to alert supervisory staff on duty at the security room or office about the fire emergency. Activation of a key switch in a manual pull station, at the fire alarm control panel or control facility will cause an alarm signal to sound throughout the building. Using this system, it can reduce undue distress of the elderlies and reduce the possibility of false alarms.

During a fire, activation of an alarm sounder is to raise attention of the occupants so that evacuation can be done immediately without causing harm to the occupants. As for alarm bells, a minimum sound level of 65db (A) or 5db (A) above ambient noise level sustainable for a period of minimum 20 seconds should be produced by the Sounder Unit. The alarms are mounted on the wall at a minimum height of 2.1m from floor level. All alarm sounders within a building should have similar sound characteristics. Audible (horns, sounders, speakers) are located in non-patient areas whereas visible appliances (strobes) are allowed to be used in place of audible appliances in patient occupied areas.

Speakers and strobes are installed throughout the buildings to signal the elderlies in the event of fire. Chime strobes are installed at common used spaces for the hearing impaired elderlies.

3.4 Fire Alarm System

Figure 3.6: Photo of Chime strobes. Figure 3.7: Photo of speakers.

UBBL 1984 Section 237 : Fire Alarms

(1) Fire alarms shall be provided in accordance with the Tenth Schedule to these By-laws. (2) All premises and buildings with gross floor area excluding car park and storage areas exceeding 929 square meters or exceeding 30.5 meters in height shall be provided with a two stage alarm system with evacuation (continuous signal) to be given immediately in the affected section of the premises while an alert (intermittent signal) shall be given in adjoining section. (3) Provision shall be made for the general evacuation of the premises by action of a master control. (4) Alarm Bell must provide a minimum sound level of 65db (A) pr +5db (A) above any background noises, which is likely to persist for more than 30 seconds.

8

Page 12: B.serv   project 2 (final report)

Figure 3.8: Location of Fire Speakers(Top) and Chime Strobes(Bottom) at Ground Floor & First Floor.

9

Page 13: B.serv   project 2 (final report)

For the elderly day care centre, a two stage fire alarm system is used. A two stage alarm system is designed so that the activation of any signal initiating device (manual pull station and smoke detector) will cause an alert signal to sound to alert supervisory staff on duty at the security room or office about the fire emergency. Activation of a key switch in a manual pull station, at the fire alarm control panel or control facility will cause an alarm signal to sound throughout the building. Using this system, it can reduce undue distress of the elderlies and reduce the possibility of false alarms.

During a fire, activation of an alarm sounder is to raise attention of the occupants so that evacuation can be done immediately without causing harm to the occupants. As for alarm bells, a minimum sound level of 65db (A) or 5db (A) above ambient noise level sustainable for a period of minimum 20 seconds should be produced by the Sounder Unit. The alarms are mounted on the wall at a minimum height of 2.1m from floor level. All alarm sounders within a building should have similar sound characteristics. Audible (horns, sounders, speakers) are located in non-patient areas whereas visible appliances (strobes) are allowed to be used in place of audible appliances in patient occupied areas.

3.5 Fire Intercom System

The remote handset also known as fire intercom stations are placed at the fire staircase and exit routes as well as near the reception area for the staff to contact the nearest fire station when there is an emergency.

Figure 3.9: Photo of Fire Intercom System.

UBBL 1984 Section 239: Voice Communication System

(1) There shall be two separate approved continuously electrically supervised voice communication systems, one a fire brigade communications system and the other a public address system between the central control station and the following areas: (a) Lifts, lift lobbies, corridors and staircases; (b) In every office area exceeding 92.9 square metres in area; (c) In each dwelling unit and hotel guest room where the fire brigade system may be combined with the public address system.

10

Page 14: B.serv   project 2 (final report)

Figure 3.10: Location of Fire Intercom Stations at Ground Floor & First Floor.

11

Page 15: B.serv   project 2 (final report)

When there is a fire breakout, the firefighters that arrive on scene will be able to operate and off the fire switch. It is a specialized switch that allows firefighters to disconnect power from high voltage devices that may explode when there is fire. The fireman switch is located at an easily accessible location to control the electrical appliances of the building. The switch is used to run the under voltage release or stunt trip in the main incoming breaker. The firefighter uses an insulated rod to pull the handle which isolates the utility supply to the building.

3.6 Fireman switch

The fireman switch is mounted at the outer wall of the security room beside the assembly area so that it is easier for the fire fighters to access the switch when they arrive.

Figure 3.11: Photo of the fireman switch.

Figure 3.12: Location of the fireman switch at Ground Floor.

12

Page 16: B.serv   project 2 (final report)

Figure 3.15: Location of main fire control panel at Ground Floor.

In the elderly day care centre, addressable panels are used as it has greater information capacity and control flexibility. An addressable fire alarm system uses addressable fire detection devices, both automatic and manual. The detectors are equipped with electronic circuitry, usually mounted in a special base. The panel is able to locate the exact location of a fire inside the building, which gives time for the staffs to shut down the device and prevent further property damage and threat to the elderlies. It also detects the conditions that could lead to a fire.

3.7 Main Fire Control Panel

The addressable alarm system connects the detectors and pull stations using a loop. Both ends of the wire loop connect to the control panel using one wire. It helps in reducing false alarms. Every device has its own unique address. In the event of fire, the device’s address shows up on the main control panel, pin point the exact location of fire for evacuation purpose. This will reduce the risk of serious injuries and fatalities and at the same time the staffs can take prompt action to prevent the fire from spreading at the location. The control panel will be located at the security room.

Figure 3.13: Addressable fire control panel.

Figure 3.14: Addressable Alarm System Schematic Diagram

13

Page 17: B.serv   project 2 (final report)

The location of the external fire hydrant is about 58m away from the elderly day care centre. It is a two way hydrant placed beside the road for easy access. There are no parking space allocated in front of the elderly day care centre. Hence, the main road which is Jalan 18/16 will be used for the fire truck to park. As the road is rather narrow, the fire truck might cause a heavy traffic especially during peak hours such as 8am-10am and 5pm-7pm on weekdays.

3.8 External Fire Hydrant System

Figure 3.16: External Fire Hydrant found at Jalan 18/16 Taman Kanagapuram.

Figure 3.17: Figure showing the distance from site to the external fire hydrant.

UBBL 1984 Section 225: Detecting and extinguishing fire

(1) Every building shall be provided with means of detecting and extinguishing fire and with fire alarms together with illuminated exit signs in accordance with the requirements as specified in the Tenth Schedule to these By-laws.

(2) Every building shall be served at least one fire hydrant located not more than 91.5 metres from the nearest point of fire brigade access.

(3) Depending on the size and location of the building and the provision of access for fire appliances, additional fire hydrant shall be provided as may be required by the Fire Authority.

14

Page 18: B.serv   project 2 (final report)

As for the elderly day care centre, quick response sprinklers are used where faster sprinkler operation could enhance life safety. One measure of thermal sensitivity is the response time index (RTI), which indicates how fast the sprinkler can absorb sufficient heat from its surroundings to cause activation. Quick response sprinklers have an RTI of 50 or less. As compared to standard-response sprinklers which have RTI of 80 or more, quick response sprinklers are a better choice for elderly day care centres. The fast-response sprinkler’s operating element has a smaller mass, enabling it to respond to the air temperature rise more quickly. Quick response sprinkler has a smaller bulb whereas standard response sprinkler has a thicker bulb.

The type of sprinkler used is the pendant sprinklers. The pendant sprinkler head hangs down from the ceiling and spray water in a circular array.

Wet-Pipe systems is used for the fire sprinkler system. They are filled with water under pressure and are limited to spaces in which the air temperature does no fall below 4.4 degree Celsius. In the wet pipe system, sprinklers in the affected area are opened by heat-sensitive elements within the sprinkler heads themselves and immediately emit water. The sprinkler piping is carried above suspended ceilings.

3.9 Fire Sprinkler System

Figure 3.18: Comparison between quick response sprinklers and standard response sprinklers.

Figure 3.19: Wet pipe sprinkler system.

15

Page 19: B.serv   project 2 (final report)

Figure 3.20: Location of sprinklers.

16

Page 20: B.serv   project 2 (final report)

Figure 3.21: Duty pump.

Figure 3.22: Jockey pump.

The sprinkler pumps draw water from sprinkler storage tank to feed the sprinkler network. Two sets on pumps, one on duty and other on standby, are provided together with a jockey pump to maintain system pressure. Sprinkler pump capacity should be selected to meet the duties defined for the various classes of hazards. For light hazard occupancies, the flow requirement for the sprinklers is 300cu dm/mon at 1.5 bars. In addition to the above flow requirements, the sprinkler pump should be capable of satisfying two other flows and pressures as described in BS EN 12845.

The standby sprinkler pumpset is diesel engine drive. Electrical cabling to supply power to the sprinkler pumps should be MICC of fire rated type. As for batteries for the diesel engine, should be maintenance-free type.

Sprinkler pumpsets should be capable of automatic starting but should only be stopped manually.

3.9.1 Sprinkler Pump

UBBL 1984 Section 226: Automatic system for hazardous occupancy

UBBL 1984 Section 228: Sprinkler valves

(1) Where hazardous processes, storage or occupancy are of such character as to require automatic sprinklers or other automatic extinguishing system, it shall be of a type and standard appropriate to extinguish fires in the hazardous materials stored or handled or for the safety of the occupants.

(1) Sprinkler valves shall be located in a safe and enclosed position on the exterior wall and shall be readily accessible to the Fire Authority.

(2) All Sprinklers systems shall be electricity connected to the nearest fire station to provide immediate and automatic relay of the alarm when activated.

17

Page 21: B.serv   project 2 (final report)

Water tank plays an important role in storing large amount of water for firefighting purpose. The water storage tank should be designed and constructed that only requires little maintenance or servicing. For light hazard groups, 9cu metres sprinkler storage tank is used. Pressed steel tanks that are hot dipped galvanized and coated internally with bituminous paint for corrosion protection is suitable for the sprinkler storage tank. The tanks should be compartmented and the external surface of the tank should be painted red.

Breeching inlets are provided so that the fireman can pump water into the sprinkler tank to make up for water used. They should be located no more than 18m from the fire appliance access road and not more than 30m from the nearest external hydrant outlet. The water tank for the sprinkler system is installed on top of the roof of the elderly day care centre.

3.9.2 Water Storage

Figure 3.23: Example of pressed steel sprinkler water tank.

UBBL 1984 Section 247: Water Storage

(1) Water storage capacity and water flow rate for firefighting systems and installations shall be provided in accordance with the scale as set out in the Tenth Schedule to theses By-laws.

(2) Main water storage tanks within the building, other than for hose reel systems, shall be located at ground, first or second basement levels, with fire brigade pumping inlet connections accessible to fire appliances.

(3) Storage tanks for automatic sprinkler installations where full capacity is provided without need for replenishment shall be exempted from the restrictions in their location.

18

Page 22: B.serv   project 2 (final report)

Figure 3.24: Location of sprinkler storage tank at roof.

19

Page 23: B.serv   project 2 (final report)

In the elderly day care centre, dry powder extinguishers are placed near the fire staircases, reception desk near the kitchen as well as the security room where there are live electrical equipment. The kitchen has two types of fire extinguishers located nearby, one is the dry powder type and another type is the CO2 type as there are cooking oil and fats present in the kitchen.

3.10.1 Fire Extinguisher

3.10 Hand Operated Fire Fighting Equipment

Figure 3.25: Types of fire extinguishers.

Figure 3.26: Location of fire extinguishers at Ground Floor and First Floor.

UBBL 1984 Section 227: Portable Extinguishers

(1) Portable extinguisher shall be provided in accordance with the relevant codes of practice and shall be sited in prominent positions on exit routes to be visible from all directions and similar extinguishers in a building shall be of the same method of operation.

20

Page 24: B.serv   project 2 (final report)

Fire hose reels control supply of water to combat fire, especially when the building occupants are trapped and could not escape to an emergency exit. In the elderly day care centre, it is important to have hose reel installed as it will buy more time for the elderlies who are slow in movement during evacuation. There are one hose reel as each floor as the coverage of the hose reel is wide, which is 30m. They are located beside the lifts and fire escape staircase for easy access.

Specification for Hose Reel SystemDischarge jet length : 30 l/mMaterial : Rubber hose Length of hose : 30mDiameter of hose : 25mm Diameter of nozzle : 8mmPipework system : 50mm diameter, individual hose is 25mm diameter

Specification for Hose Reel PumpsType of pumps : Duty pump and standby pump Engine : Electrically driven

Specification for Hose Reel Water Tank The water tank is located at the roof and is combined with potable water tank to form one water tank. A pump is installed together with the tank which will run continuously until it is forced to stop manually. The pump is electrically driven as there is only two hose reels in the elderly day care centre. A pump control panel is installed adjacent to the pump and is properly sheltered. 1500l water tank is used for the hose reel.

3.10.2 Hose Reel System

Figure 3.27: Example of Fire Hose Reel.

21

Page 25: B.serv   project 2 (final report)

Figure 3.28: Location of Hose Reel System.

22

Page 26: B.serv   project 2 (final report)

The installation of Passive Fire Protection System in a building or a structure is used to contain or slow down the spread of fire to other areas or part of the building. By delaying the spreading of fire, this can increase the time for occupants to escape from the building. Also, consideration of this system will be made during the planning design stage in the building design of any constructions. The four main criteria for passive fire protection system are:

Separation of fire risk area is where a corridor forms part of a means of escape in one direction only (dead end situation) it must be separated from all adjoining areas – except toilets – by fire- resisting construction. Rooms of high fire risk (e.g. plant rooms, storage areas for flammables/highly flammables) must be separated from adjoining areas, especially corridors forming means of escape, by fire-resisting construction.

Fire rated doors which are thicker than normal door are used in a building to separate it to compartments to prevent fire from spreading. It is usually used for emergency exits or staircases. Fire rated door helps to slow down the fire by restricting the flow of oxygen and prevent the fire from spreading. By using fire rated door, this can improve the flow of evacuation of users and also the safety of the fire fighters.

Firewall is a non-bearing wall which is capable to provide up to 240 minutes’ fire resistance. It can be used to subdivide a building into separate fire areas and are constructed in accordance with the Uniform Building by Laws 1984. Firewall acts as a barrier between two spaces to prevent the spread of fire in a period of time. This can prolong the time for users to escape from the building.

Considerations of Fire Appliances Access is crucial for fire trucks to get in place without hassle during the fire event. Fire hydrants must be situated nearby for fire-fighting and rescue activities to be carried out smoothly. The fire brigade access must be clear from any blockage to allow high reach appliances such as turntable ladders and hydraulic platforms to be used.

I. Purpose Group and Compartment

II. Fire Appliance Access

i. Separation of Fire Risk Area

ii. Fire Rated Door

iii. Firewall

4. Passive Fire Protection System

4.1 Literature Review

23

Page 27: B.serv   project 2 (final report)

Fire emergency staircases are crucial as it is an escape route for users to evacuate out of the building safely.

Emergency exit signs are important to direct users to shortest routes to escape out from the building which will lead them to the safe open outdoor assembly point. The Exit Emergency signage of ‘KELUAR’ means ‘EXIT’ in Malaysia. The ‘KELUAR’ signage is required to be permanently lit and must be visible to users at all times.

Emergency Escape Route plan is very important to provide users an easy and direct route out of the building to a safe open outdoor assembly point in case of fire outbreak in the building.

All emergency escape routes must lead occupants from the building to a safe open outdoor assembly point.

The requirements for this system are stated in the Uniform Building By Laws 1984 in section VII by law 133 to 224.

III. Means of Escape

i. Fire Emergency Staircase

ii. Emergency Exit Sign

iii. Emergency Escape Route

iv. Assembly Point

24

Page 28: B.serv   project 2 (final report)

In the elderly care centre, storage located on ground floor is a potential high fire risk area. This is due to flammable liquids such as household cleaners will be stored in the area. Compartmenting this space can confine the fire and minimizes the risk of loss of users by segregating the storage to control the spread of fire. Thus, separating the storage from other areas such as corridor and staircases forming means of escape are required to protect the safety of the users.

4.2 Purpose Group and Compartment

4.2.1 Separation of Fire Risk Area

UBBL- Section 139: Separation of fire risk areas.

Figure 4.1: Separation of Fire Risk Area

Figure 4.2: Special requirements as to compartment walls and compartment floors

The following area uses shall be separated from the other areas of the occupancy in which they are located by fire resisting construction of elements of structure of a FRP to be determined by local authority based on the degree of hazed:• Boilerroomsandassociatedduelsstoragearea• Laundries• Repairsshopsinvolvinghazardousprocessesandmaterials• Storageareofmaterialsinquantitiesdeemedhazardous• Liquefiedpetroleumgasstorageareas• Linenrooms• Flammableliquidstores

25

Page 29: B.serv   project 2 (final report)

In the elderly care centre, recessed single leaf fire rated doors are used for the enclosed rooms on ground and first floor. The fire rated doors used in this centre has FPR of 3/4-hour with FPR of one-hour walls. They are found in walls of corridors and room partitions in the centre. All the doors in the centre are openable from the inside without the use of a key or any special knowledge or effort. When escaping, the door must be swing at the exit direction of the room as it allows user to exit with ease, allowing smoother and safe escapes. Automatic door closers of swing doors are also installed to allow self-closing. This can help prevent fire from spreading more to the other areas.

4.2.2 Fire Rated Door

Figure 4.3: Dimension of single leaf fire rated door

UBBL- Section 162: Fire doors in compartment walls and separating walls

UBBL- Section 164 (1): Fire doors in compartment walls and separating walls

UBBL- Section 173 (1): Exit Doors

(1) Fire doors of the appropriate FRP shall be provided.(2) Openings in compartment walls and separating walls shall be protected by a fire for having a FRP in accordance with the requirements for that wall specified in the Ninth Schedule to these By-Laws.

All fire doors shall be fitted with automatic door closers of the hydraulically spring operated type in the case of swing doors and of wire rope and weight type in the case of sliding door.

All exit doors shall be openable from the inside without the use of a key or any special knowledge or effort.

26

Page 30: B.serv   project 2 (final report)

Figure 4.4: Placement of Fire Rated Doors.

27

Page 31: B.serv   project 2 (final report)

In elderly care centre, steel stud partition with FPR of 1-hour are placed in between enclosed room which are right next to each other. The material used for the partition is gypsum board. It is most commonly used fire resistive material and is equally well known as a reliable and economic surfacing material. The partition acts as a barrier between two spaces to prevent the spread of fire within 1-hour. It is sufficient to withstand and prolong the escape time for users to evacuate out of the building.

4.2.3 Firewall

Figure 4.5: Terminology of 1-hour rated Steel Stud Partition

Figure 4.6: Placement of Firewall

UBBL- Section 138 (C): Other walls and floors to be comnstructed as compartment walls or compartment floors

UBBL- Section 148 (6): Special requirements as to compartment walls and compartment floors

Any wall or floor separating part of a building form any other part of the same building, which is used or intended to be used mainly for a purpose failing within a different purpose group as, set out in the Fifth Schedule to these by laws.

Any compartment walls or compartment floor which is required by these By-Laws to have FRP of one hour or more shall be constructed wholly of non-combustible materials and, apart from any ceiling, the required FRP of wall or floor shall be obtained without assistance form any non-combustible materials.

28

Page 32: B.serv   project 2 (final report)

In the elderly care centre, Jalan 18/16 (main road) is proposed to be the fire brigade access with a fire hydrant located 60 meters away from the access point. The fire hydrant is located nearby for fire-fighting and rescue activities to be carried out smoothly. It is crucial for fire trucks to get in place without hassle during the fire event in this centre. The fire brigade access is clear from any blockage to allow high reach appliances such as turntable ladders and hydraulic platforms to be used.

4.3 Fire Appliance Access

Figure 4.7: Relationship between building and access roads for high reach fire appliances

UBBL- Section 225 (2): Detecting and extinguishing fire

UBBL- Section 247 (2): Water Storage

Every building shall be served by at least one fire hydrant located not more than 91.5 meters from the nearest point of fire brigade access.

Main water storage tanks within the building, other than for hose reel systems, shall be located at ground, first or second basement levels, with fire brigade pumping inlet connections accessible to the fire appliances.

29

Page 33: B.serv   project 2 (final report)

Figure 4.8: Location of Fire Appliance Access

30

Page 34: B.serv   project 2 (final report)

There is one fire escape staircase located in the middle of the elderly care centre which is accessible for the occupants from the above floors that lead the escape route to the safe outdoor assembly point. The width of exit staircase in the centre is 1200mm. Besides that, the dimension of the tread (290mm) and risers (180mm) are uniform for all steps of the staircase. The material used for the staircase is terrazzo (non-slip surface). It has nosing of radius 10mm which is flushed with the riser to prevent users from slipping. Guiding blocks is provided in order to warn the users the distance from the drop of staircase. It is offset 300mm from the first tread with continuous handrail at both left and right side of the staircase, with 850mm above floor level. The fire escape staircase is open aired, thus natural lighting and air ventilation is provided. This can increase the safety of users when escaping from the building.

4.4 Means of Escape

4.4.1 Fire Escape Staircase

UBBL 1984 - Section 111: Lighting and ventilation of staircases

UBBL 1984 – Section 168 (1): Staircases

Figure 4.9: (LEFT) Stairs for ambulant disabled; (RIGHT) Configuration of steps

All staircases shall be properly lighted and ventilated according to the requirements of the local authority.

Except as provided for in by-law 194 every upper floor shall have means of egress via at least two separate staircases

UBBL 1984 - Section 110: No obstruction in staircases

(1) There shall be no obstruction in any staircase between the topmost landing thereof and the exit discharge on the ground floor.

(2) There shall be no projection, other than handrails in staircases, in any corridor, passage or staircase at a level lower than 2 metres above the floor or above any stair.

31

Page 35: B.serv   project 2 (final report)

Figure 4.10: Placement of Fire Escape Staircase

32

Page 36: B.serv   project 2 (final report)

In the elderly care centre, ‘KELUAR’ signage are placed on both escape staircase and normal staircase and also in every room of first floor whereas four ‘KELUAR’ signage will be placed on ground floor including the main and back entrance of the building. The emergency exit signs are important to direct users to shortest routes to escape out from the building which will lead them to the safe open outdoor assembly point. The ‘KELUAR’ signage is permanently lit at all time and are visible to users in the centre.

4.4.2 Emergency Escape Signs

Figure 4.11: Dimension of “KELUAR” Signage.

UBBL 1984 - Section 172: Emergency Exit Signs

(1) Every exit sign shall have word “KELUAR” in a plainly legible not less than 15mm height with the principle strokes of the letters not less than 18mm wide.

(2) The exits and access to such exit shall be marked by readily visible signs and shall not be obscured by and decorations, furnishing or other equipment.

(3) The sign with the reading of “KELUAR” should indicating the direction shall be placed in every location where the direction of the travel to reach the nearest exit.

(4) All exit signs shall be illuminated continuously during period of occupancy(5) The design and installation of every emergency exit sign shall be in compliance with MS983 and MS619.

33

Page 37: B.serv   project 2 (final report)

Figure 4.12: Placement of Emergency Exit Sign

34

Page 38: B.serv   project 2 (final report)

In the elderly care centre, the first floor has two escape routes through the staircases whereas the ground floor has four escape routes including the main and back entrance. There are no obstructions throughout the emergency escape route. This allows users to escape the fastest and the safest exit route in the building. Besides that, fire escape plans are placed at most frequent used space for users to read.

4.4.3 Emergency Escape Route

Figure 4.13: Example of Fire Escape Plan

UBBL 1984- Section 165 (4): Measurement of travel distance to exits

UBBL 1984- Section 169: Exit route

The maximum travel distance to exits and dead end limits shall be as specified in the Seventh Schedule of these By-Laws.

No exit route may reduce in width along its pathway of travel from the story exit to the final exit.

Figure 4.14: Emergency Escape Route

35

Page 39: B.serv   project 2 (final report)

In this elderly care centre, the assembly point is located directly opposite the main entrance of the building. This will ensure the safety of occupants during the incident.

4.4.4 Assembly Point

Figure 4.15: Emergency Assembly Point Sign

Figure 4.16: Assembly Point

UBBL 1984- Section 178: Exits for institutional and other places of assembly

In buildings classified as institutional or places of assembly, exits to a street or large open space, together with staircases, corridors and passages leading to such exits shall be located, separated or protected as to avoid any undue danger to the occupants of the place of assembly from fire originating in the other occupancy or smoke therefrom.

36

Page 40: B.serv   project 2 (final report)

5. Air Conditioning

5.1 Literature Review

37

I. Central

II. Room

III. Ductless, Split

IV. Evaporative Cooler

A central air conditioner circulates cool air through a home using a system of ducts and registers. It will provide the most even cooling throughout the building. However, ductwork might prove to be costly as it solely relies on it. Moreover, ducting system requires a lot of installation space.

Malaysia is a country with tropical rainforest climate – which is generally sunny throughout the year, with high precipitation rates every month. This hot and humid condition defines thermal comfort in our local context as having sufficient filtered air in a building, at a temperature of 22 to 27 degree Celsius and relative humidity of 55-70%. Thus, the air-conditioning system as part of the ACMV (air-Conditioned and Mechanical Ventilation) system is one of the most crucial building service in typical Malaysian buildings to provide thermal comfort.

There are many types of air-conditioners, they include:

The most popular cooling system, a room air conditioner provides spot cooling and can be either a window unit or a portable air conditioner. It can provide cooling to select spaces at an affordable cost. Inversely, improper installation can result in significant air leakage, as much as 10%.

Mounted on the wall, a ductless, mini-split air conditioner provides zoned cooling without ductwork. It is able to provide cooling as well as heating. Moreover, it is highly efficient and works in all climate zones and can be an affordable alternative to installing a ducted system.

An evaporative cooler cools outdoor air using evaporated water and circulates it throughout the house. It is a cost-effective cooling option in an arid climate. In addition to cooling the air, it adds moisture which can improve comfort. It is a cheap solution but it requires more frequent maintainence and is only suitable for areas with low humidity.

Page 41: B.serv   project 2 (final report)

38

V. Multi-Split System

VI. Variable Refrigerant Volume (VRV)

Multi-split system requires one or more outdoor units mounted outside the home, and one or more indoor blower units installed inside it. Suction lines, refrigerant lines and power cables run between the indoor and outdoor components. It uses wall-mounted air-conditioners only and has high upfront cost. If one condenser is faulty, none of the indoor units will work.

VRV is a large outdoor unit serves multiple indoor units. Its cooling is controlled & monitored by Refrigerant Flow Volume to the indoor units. Any type & any capacity of indoor units can be connected to single same outdoor unit and single refrigerant piping is installed for each system. With less refrigerants and piping, it saves space. VRV allows individual control to indoor units & centralized zonal control. It requires low power consumption due to Inverter technology, where the power is calculated as per to usage of indoor units & corresponding percentage of outdoor unit operating. Furthermore, its is compactable to any BMS network

Page 42: B.serv   project 2 (final report)

The word-for-word definition of the Variable Refrigerant System goes as: •Variable–Systemoutputdependingonrequiredload •Refrigerant–DirectExpansionsystem •Volume–Refrigerantflowregulatedbyelectronicexpansionvalvevaryingcompressorcapacity.

VRV means Variable Refrigerant Volume System, where Cooling is controlled & monitored by Refrigerant Flow Volume to the Indoor Units. VRF is the general term used in the market, whereas VRV is a copyright by Daikin.

5.2 VRV(Variable Refrigerant Volume) System

5.2.1 Introduction and Justification

Variable Refrigerant Flow (VRF) or Variable Refrigerant Volume (VRV) air conditioning systems are an extremely energy efficient means of precisely regulating the temperature within a small-scale commercial bungalow lot, in this case, an elderly activity centre. VRV is also low in power consumption due to Inverter technology, where the power is calculated as per to usage of indoor units & corresponding percentage of outdoor unit operating.

In its simplest form, a single VRF/VRV outdoor unit serves multiple indoor units, which are connected to it via a system of copper pipework containing refrigerant. VRF/VRV technology achieves extremely high efficiencies by varying the flow of refrigerant to the indoor units based on the exact demands of the individual areas. This allows for precise temperature control and resulting zoned comfort in different environments of the activity centre.

I. Energy Efficiency

Figure 5.1: Ventilation for Ground Floor (left), First Floor

(Mid) and Wind direction on First Floor (Right).

Wind direction and entry

Indoor (Air-conditioned)

Outdoor (Natural Ventilation & Fan.

39

Page 43: B.serv   project 2 (final report)

A balance of outdoor and indoor spaces in the activity centre creates varying air temperatures and environments. Wind entry through door and window openings create natural ventilation which varies the need for air conditioning at different times of the day due to natural ventilation and the number of people present etc.

VRF/VRV air conditioning systems also benefit from being flexible and modular in design. Indoor units come in multiple types and sizes making them suitable for most applications. For the activity centre, the cassette type and wall-mounted air-conditioner are most suitable to be used according to the various zones and spaces.

Besides that, more indoor units can be attached to the existing outdoor unit (provided the outdoor unit has sufficient capacity) at any point of time. Thus, if the activity centre decides to renovate the building spaces, the VRV system will still be compatible and fully functional.

Different types of internal unit can be connected to the outdoor unit via the VRV system, allowing for flexibility in space design.

II. Flexible Design

Figure 5.2: Cassette Type Air-Conditioner-Thorough air flow and area coverage andsuitable for larger rooms.

Figure 5.3: Wall-Mounted Air-Conditioner- Smaller area coverage and suitable for smaller rooms.

40

Page 44: B.serv   project 2 (final report)

MS 1525:2007

Section 13a

Room comfort condition is dependent on various factors including air temperature, mean radiant temperature, humidity, clothing, metabolic rate and air movement preference of the occupant.

For the purpose of engineering design, room comfort condition should consider the following three (3) main factors: • Drybulbtemperature; • Relativehumidity;and • Airmovement(airvelocity)

In general, an individual feel comfortable when metabolic heat is dissipated at the rate of which it is produced. The human body temperature needs to be maintained at a constant 37 +_0.5 oc regardless of the prevailing ambient condition. The higher the space relative humidity, the lower the amount of heat the human body will be able to transfer by means of perspiration

At normal comfort room temperature (23°C to 26°C), the acceptable air velocity would be in the region of 0.15 to 0.5 m/s. The indoor design conditions of an air-conditioned space for comfort cooling is recommended to have dry bulb of 23°C to 26°C. The recommended design relative humidity is 55-70%. The recommended air movement is 0.15 to 0.5 m/s. According to Department of Malaysian Standards, the maximum movement is 0.7 m/s.

41

Piping system can also be engineered to minimise or even totally remove the requirement for air distribution ductwork, making them cost effective to implement and easier to install as the centre is built on a small site, with minimal space for installation.

Also, any type & any capacity of indoor units can be connected to a single, same outdoor unit. This conserves space and minimizes the effect on the façade of the building as it is placed on the roof of the activity centre.

Only one outdoor unit (compressor) is sufficient to provide for all the indoor air-conditioners. Placed at the roof, the compressor is hidden from sight at the rear end and takes up minimal space.

III. Space Saving

Figure 5.4: Roof Plan Figure 5.5: Elevation

Compressor and outdoor unit

Page 45: B.serv   project 2 (final report)

Sophisticated controls enable the system to be optimised and allow users of the activity centre complete control over their local environment, with no adverse impact on other areas served by the same system. These controls can also be easily integrated into the buildings BMS control system as required. Individual controls for indoor units & centralized zonal control is possible, allowing flexibility of temperatures in each zone.

IV. Individual and Centralised Controls

MS 1525:2007 code 8.4.4: Off-hour control

MS 1525:2007 code 8.4.1: Temperature control

MS 1525:8.5: Piping insulation

ACMV system should be equipped with automatic controls capable of accomplishing a reduction of energy use for example through equipment shutdown during periods of non-use or alternative use of the spaces served by the system.Exceptions: • Systemsservingareaswhichareexpectedtooperatecontinuously;and • Equipmentwithaconnectedloadof2kWeorlessmaybecontrolledbyreadilyaccessible manual off-hour controls.

Each system should be provided with at least one thermostat for the regulation of temperature.

All piping installed to serve buildings and within buildings should be adequately insulated to prevent excessive energy losses. Additional insulation with vapour barriers may be required to prevent condensation under some conditions.

42

Page 46: B.serv   project 2 (final report)

VRV can easily be related to as the “Rolls Royce” of Air Conditioning Systems. It’s a very sophisticated technological air conditioning system, based on several principles:

A typical system consists of an outdoor unit (comprising one or multiple compressors), several indoor units, refrigerant piping, running from the outdoor to indoors, using Refnet Joints and communication wiring.

Communication wiring consists of a 2 wired cable, chained from the outdoor to indoors in the activity centre compound, creating an internal closed loop network that is an essential part of any VRV installation.

As for the Control, each indoor is controlled by its own wired control panel, while there are some possibilities for wireless remotes (IR) and centralized controllers, enabling controlling indoors from one location in the activity centre.

5.2.2 Principles of VRV

5.2.3 System Structure of VRV

1. Refrigerant only – where refrigerant is the only coolant material in the system (in contrary to the chilled water systems, where refrigerant is used for cooling/heating the water that is circulated throughout the whole system).2. Inverter compressors that allow lowering power consumption with partial cooling/heating loads.3. Several air handlers (indoor units) on the same refrigerant loop / circuit.4. Ability of modular expansion.

Figure 5.6: System Structure of VRV

43

Page 47: B.serv   project 2 (final report)

This process is constantly occurring with any change, performed in the HVAC system. As described, the VRV system is fully automatic, and regulates its power consumption based on the demand arriving from the indoor units and outside prevailing conditions. User can have influence on the desired indoor comfort conditions, modifying: Operation mode (on/off), Operation state (Cool/Heat/Fan/Dry/Auto), set point temperature, fan speed (high/medium/low/auto).

Controlling those parameters is the only thing required for proper operation, and the only thing that is required for proper integration with the VRV system.

The system gets inputs from the user in all rooms of the activity centre (e.g. desired comfort temperature) and from the surroundings (outside ambient temperature), and according to that data it implements its logic in order to get to the desired comfort conditions, utilizing optimal power consumptions. This makes it more convenient for all elderly and visitors in the centre.

The ability to adjust itself to the outdoor conditions is one of the main factors that make VRV systems efficient, compared to the traditional water cooled systems, based on chillers and fan coils.

At the beginning, the system is in standstill condition (everything is turned off).

Once a user turns one of the indoors “ON” by its local remote, the outdoor “gets noted” regarding it, and starts working. At this point, it will examine the outdoor conditions (temperature), the operating indoor requirements (operation mode, set point temperature), and will operate the compressor at the exact level, required to comply with the indoor requirements.

When another indoor unit is turned on, the outdoor recalculates the requirements from all the indoors, and will increase the compressor’s output, according to the required level of demand.

5.2.4 Operation System of VRV

Figure 5.8: Branch controller processes the demand and supply between the

outdoor and indoor units.

Figure 5.7: Operation system of a VRV.

44

Page 48: B.serv   project 2 (final report)

1. The outdoor unit is located in the rear end of the activity centre on the flat roof; it is where the heat from inside your home is dispersed.2. It contains the compressor, condenser coil and a fan. The heat absorbed from the centre’s air is transferred to the refrigerant and then pumped to the outdoor unit. As this heat is absorbed and moved by the refrigerant to the outdoor coil, it passes through the compressor.3. The compressor in your air conditioning system has the primary job of moving the refrigerant throughout the system. This is important as we can then keep reusing the refrigerant to cool our house. As the refrigerant passes through the condenser, a fan delivers ambient air across the condenser coil causing it to cool.4. As the process completes, the heat from inside the centre is dispersed to the air outside. The refrigerant is then pumped back indoors and the whole process repeats. 5. Often there will be a separate ‘outdoor unit’ for each floor or pair of floors sized to match the load.6. Compact design hence less space required on the roof: • 2.9sqmfootprintarea. • Dimensions(1.6mx1.25mx0.75m)7. For VRV, it is flexible in system where any additional indoor units can be connected in future to the same outdoor units provided there is spare capacity present;

5.2.5 Outdoor Unit

Figure 5.9: VRV outdoor unit. Dimensions are 1.6mx1.25mx0.75m

Figure 5.10: Outdoor units are often placed on the roof of a building.

45

Page 49: B.serv   project 2 (final report)

Figure 5.11: Refrigerant cycle in the outdoor unit.

The cooling operation Influenced by the number of operating (thermostat-on) units, capacity, airflow rate, return-air temperature, and humidity of indoor units: • Loadontotalsystemchanges.• Loadsoneveryindoorunitaredifferent.

Compressor Capacity ControlIn order to maintain the cooling capacity corresponding to the capacity of evaporator and load fluctuation, based on the pressure detected by low pressure sensor of the outdoor unit, the compressor capacity is controlled so as to put the low pressure equivalent saturation temperatures close to target value.

In order to maintain the superheated degree in the evaporator and to distribute proper refrigerant flow rate regardless of different loads on every indoor unit, based on the temperature detected by thermistors on the liquid pipes and gas pipes, the indoor electronic expansion valve is regulated so as to put superheated degree at the evaporator outlet close to target value.

1. The compressor pumps vapour refrigerants through the condenser.2. The condenser changes vapour refrigerants to liquid refrigerants. As the gas/vapour works its way through the condenser it begins to cool. The cooling process is because the air that is blown over the outside of lines.3. The expansion valve controls the amount of refrigerants going through the systems.4. The evaporator turns liquid refrigerants into gas. This is where the process of cooling the indoor room happens. The air blown through the evaporator comes in contact with the refrigerants, thus, creating cool air.

5.2.6 Points of Refrigerant Control of VRV System

Figure 5.12: Refrigerant control points

46

Page 50: B.serv   project 2 (final report)

Cassette type air-conditioners are one of the most modern designs of internal units. Discrete yet efficient, these air-conditioners work just as effectively with the VRV system. Below are some properties of cassette type air-conditioners.

1. The cassette units are extremely discreet with only the grille showing in the ceiling. 2. Air can be delivered in up to four directions, giving the room an even temperature distribution. 3. .Weekly timer allows you to plan your usage, helping you save on your power bills. 4. Cassette units are easy to clean and maintain.

5.2.7 Cassette Type Indoor Unit

Figure 5.13: 4-way airflow system of cassette air-conditioners.

Figure 5.15: Only the grilles of the air-conditioner is seen as its body is embedded into the ceiling.

Figure 5.17: Photo showing the air flow of a cassette air-conditioner in a room.

Figure 5.14: Round flow of cassette air-conditioner

Figure 5.16: Components and functions of cassette air-conditioner.

47

Page 51: B.serv   project 2 (final report)

Figure 5.18: Elevator components.

Figure 5.19: Elevator air-conditioner operation system.

The main benefit of installing an elevator air- conditioner is the clean air that it provides. If air is sucked from the elevator’s shaft straight into the car using a fan, the air sucked into the car may be filled with dust mites, germs and bacteria.With an elevator air-conditioner, air provided is much cleaner, because the cold air is the same air that comes from the car itself. Not only that, the cold air that is produced from the air-conditioner also goes through a layer of filter. This filtration removes particles that are harmful to the human body.

5.3 Lift Air Conditioners

48

Page 52: B.serv   project 2 (final report)

Mechanical ventilation is an important part of any structure. It is responsible for the comfort of the users when circulating through the structure. It is instrumental in cycling the air through the building, siphoning stale and pungent air out of the compound and bringing fresh air in. Without proper forms of mechanical ventilation, the users in the building will feel extremely uncomfortable and might even get cases of sick building syndrome. Therefore proper mechanical ventilation systems are required for the comfort of the users in the building.

There are many ventilation systems each serving different purposes but all vital in the role of keeping the air in the compound fresh. All of these systems has a plethora of variations, each suiting a specific need or a unique purpose. Such mechanical ventilation systems are

Wall Ventilation Fan A wall ventilation fan is commonly used to ventilate an enclosed area or to remove a spread out smell. Different variations offer different perks and disadvantages. Certain variations prevents rain from entering through the ventilation fan, some are suited for load bearing walls and others for dry walls. - Wall Axial Shutter - Wall Axial Cabinet - Wall Axial Panel

Centrifugal FanCentrifugal fans, like wall ventilation fans, ventilate an enclosed area. However, centrifugal fans ventilate on a far larger scale than wall ventilation fans and may serve a separate purpose to pressurize an enclosure. There are 2 different centrifugal fans, with different scales and each suiting different buildings. - Single input centrifugal fan - Dual input centrifugal fan

Ceiling Fan Ceiling fans, unlike the wall ventilation fan and centrifugal fan, serve to ventilate both enclosed and exposed spaces. This is the most common ventilation device due to its versatility and effectiveness. The variations of ceiling fans differ in terms of the number of blades which increases the ventilation. - Standard ceiling fan - Low profile ceiling fans - Energy star ceiling fans - Dual motor ceiling fans - Outdoor ceiling fans

6. Mechanical Ventilation

6.1 Literature Review

49

Page 53: B.serv   project 2 (final report)

Exhaust HoodAn exhaust hood is used in the kitchen as a way to ventilate the smell of culinary activities. Due to most of the smell coming from the stove, the exhaust hood is placed above the stove to catch the pungent fumes released from the cooking. The different variations depends on whether the exhaust hood is connected to a ventilation duct. It will either funnel the fumes out of the compound or separate the oil from the fumes and cycle the air back inside. - Ducted Exhaust Hood - Ductless Exhaust Hood

50

Page 54: B.serv   project 2 (final report)

The wall axial shutter is boxed and has louvres on the outside to prevent external rain from entering through the fan. The fan is of a propeller style for easier siphoning of air. The box casing of the wall axial shutter allows it to be placed between load bearing walls.

Used in in the water closet to siphon pungent air from the cubicles out of the compound. This prevents the pungent air from circulating back into the corridor of the structure. The wall ventilation fans used.

The ventilation fan is used in the elevator cabin to ventilate the cabin and prevent stagnant air from building up inside the cabin.

6.2 Wall Ventilation

Figure 6.1: Wall Ventilation Fan Axonometric Drawing Diagram

Figure 6.3: Wall Axial Shutter Ventilation Fan Dimensions

Figure 6.2: Wall Axial Shutter Ventilation Fan

Figure 6.4: Air Flow Diagram Figure 6.5: Wall Ventilation Fan Location (In the lifts)

51

Page 55: B.serv   project 2 (final report)

Used in buildings to cycle the air to keep it from stagnating. The centrifugal fan can also be used to create a draft of air to siphon out smoke for fire safety. The centrifugal fan is located at the roof of the structure and the top of an elevator.

With a dual input centrifugal fan, the air is siphoned from both sides which allows more air to be ventilated and it will have a higher power when necessary. The physical characteristics of the dual input centrifugal fan differs from the single input centrifugal fan when it comes to the width of the fan and the position of the motor.

Using exhaust fans in elevator for ventilation during maintenance. The stagnant air inside the elevator can be dangerous towards humans during maintenance. The exhaust fans are also used for fire safety by pressurizing the air. This allows firemen to safely escort people to safety. The ventilation allows for a certain level of smoke and fire control inside the elevator shaft. The operation of the centrifugal fan can be controlled by firemen outside the elevator shaft for emergencies during a fire.

I. Forward Curved Fan Blades These fan blades are shaped in a wheel and it curves in the direction of the wheel’s rotation. The forward curved fan blades are used as it has a low noise level, small air flow and has high increase in static pressure which makes it ideal for the structure.

II. Motor The motor power and moves the fan and adjusts the fans speed.

III. Vent The vent channels the air from one location to another

6.3 Centrifugal Fan

Figure 6.6: Dual Input Centrifugal Fan

Figure 6.7: Elevator shaft ventilation diagram

Figure 6.8: Axonometric Drawing Diagram

52

Page 56: B.serv   project 2 (final report)

MS 1525 code 8.4.5 Mechanical Ventilation Control

Each mechanical ventilation system (supply/exhaust) should be equipped with a readily accessible switch or other means for shut down or volume reduction when ventilation is not required. Example of such devices should include timer switch control, thermostat control, duty cycle programming and CO/CO2 sensor control.

Figure 6.9: Centrifugal Fan Location (In the lifts)

53

Page 57: B.serv   project 2 (final report)

Figure 6.10: Ceiling Fan – Curved Fan Blades for cycling in both directions

Figure 6.11: Exploded Axonometric Diagram

Ceiling fans are used to ventilate a room or a space. It circulates the air within a space to keep the air from being stagnant. The movement of the air keeps the space cooler and lowers its temperature.

The rooms and corridors require ceiling fans to ventilate the surrounding air to keep the locations from having stagnant air.

The fan used is the Standard 3 Bladed Dual Direction Ceiling Fan.

This ceiling fan is capable of blowing air downwards by moving in one direction. If the direction is changed the ceiling fan will cycle the air upward creating a ventilating cycle without excessive force of wind.

I. Fan Blades The part of the fan used to move and circulate the air with the motion of its surface area

II. Housing A box that stores the motor of the fan which converts electrical energy from the power into kinetic energy for the motion of the fan blades.

III. Mounting Device Used to mount the fan to the ceiling and hold it in position.

IV. Fitter Located at the center of all the fan blades and is used to hold all the fan blades together.

V. Remote Control Module Located inside the fitter and is used to receive any output from remote to remotely control the functions of the ceiling fan.

6.4 Ceiling Fan

54

Page 58: B.serv   project 2 (final report)

Figure 6.12: Ceiling Fan Locations

55

Page 59: B.serv   project 2 (final report)

A ducted exhaust hood is used to channel the fumes from the kitchen out of the compound. Unlike a ductless exhaust hood, its physical characteristics consists of a ventilation duct at the top of the exhaust hood.

The kitchen requires an exhaust hood over the stove to absorb pungent fumes and to restrict it from cycling throughout the rest of the compound.

6.5 Exhaust hood

I. Capture Panel Used in the exhaust hood to capture rising fumes from the stove during cooking.

II. Grease Filters Used to filter out grease and oil in the fumes captured by the Capture Panel and separate it from the rest of the fumes

III. Fan The fan is used to forcibly siphon the fumes through the air duct and out of the compound

IV. Air Ventilation Duct An intermediary between the Exhaust Hood and the outside of the compound that acts as a funnel for the gasses.

Figure 6.13: Ducted Exhaust Hood

Figure 6.14: Exhaust Hood Axonometric Drawing Diagram

MS1525 Code 8.6 Air Handing Duct System Insulation

All Ducts, plenums and enclosures installed in or on buildings should be adequately insulated to prevent excessive energy losses. Additional insulation with vapor barriers may be required to prevent condensation under some conditions.

Exceptions: Duct insulation is not required in the following cases: a. Where the design temperature differential between air in the duct and the surrounding air is 8c or less provided that the duct is within air conditioned space b. When heat gain or loss of the ducts, without insulation, will not increase the energy requirements of the building. c. Within ACMV equipment. d. Exhaust air ducts subject to qualification as in 8.6 items a.

56

Page 60: B.serv   project 2 (final report)

Figure 6.15: Exhaust Hood Location

57

Page 61: B.serv   project 2 (final report)

Mechanical Transportations System is a platform or cabin to transport loads or passengers up and down from one level of a building to another. There are several types of mechanical transportation system which includes elevators and escalators. These systems are generally powered by electric motors that eithers drive traction cables or counterweight systems such as hoist, or pump hydraulic fluid to raise a cylindrical piston like a jack. Mechanical Transportation System is a system where it is needed in most modern buildings for users to travel vertically from one floor to another. It is also a huge help to the disabled and elderlies.According to UBBL 1984 – Clause 124 [ ACT 133 ], any building that exceeds 4 storeys and above or below the main access must provide a elevator, or less when wheelchair movement. The minimum standard of service for one lift is each four storeys, with a maximum walking distance of 45m to the lift lobby. For all buildings, elevators should be placed at the source of traffic flow, which means providing easy means of access to all building users. Elevator performance are classified according to several factors, such as:

• Acceleration• Retardation• Stabilityofspeedandperformancewithvariationsofcarloads.

There are two different drive systems for lifts:1. Hydraulic Elevatorsa. Conventional Hydraulic Elevatorsb. Hole-less Hydraulic Elevatorsc. Roped Hydraulic Elevators2. Traction Elevatorsa. Geared Traction Elevatorsb. Gear-less Traction Elevtorsc. Machine-Room-Less Elevators

7. Mechanical Transportation

7.1 Literature Review

58

Page 62: B.serv   project 2 (final report)

The elevator that we had chosen for this building is machine-room-less elevator ( MRL Elevator ). MRL is considered as a new product which were introduced by the elevator industry. Application of MRL in construction compared to normal standard elevator is important as it will affect the design of elevator hoistway and equipment room.

Machine-room-less elevator is a result of the new technology that allows huge reduction in the size of the electric motors used in traction elevators. The newly designed permanent magnet motors, known as PMM, allows the manufacturers to locate to identify the machines, thus abolishing the need for a machine room, which was the main component for normal traction elevator.

We had proposed MRL as our elevator due to several advantages, as stated below:• Saveanestimatedamountof70%-80%energy,comparedtohydraulicelevators.Thepowerfeeders are reduced due to the more efficient design and counter-balancing which were provided with the traction elevators.• Environmental-friendly.MRLelevatorsdecreasescostandenvironmentalconcerns,ascomparedto buried hydraulic elevator that will cause groundwater pollution. By using MRL elevator, all these issues will be prevented as MRL elevator is a traction elevator with all its components above ground.• Superiorperformance.MRLelevatorusesagearlesstractiontypemachine,whicheffectsthe superior performance and ride quality compared to hydraulic elevators. It can also operate in a faster speed, while increasing the perception of quality over a conventional hydraulic elevator.• Quiet.MRLelevatorcontainsminimalnoisepollutionascomparedtonormalelevators,whichis qvery suitable to be places in the centre for elderly.• MRLelevatorsuseslessspaceascomparedtonormaltractionelevatorasnomachineroomisrequired.• MRLelevatorhavehigherstandbypowerrequirementscomparedtootherelevatorsystemsasthe other elevators uses more power when not in use.

7.2 Machine-Room-less Elevator

7.2.1 Introduction and Justification

59

Page 63: B.serv   project 2 (final report)

7.2.3 Components of System

Figure 7.1: Schematic Diagram of Nexiez- MRL

TBrand: Mitsubishi Electric

Name of Product: NEXIEZ – MRL

Type: Machine-room-less System

Size: Number of persons 6-21 Rated Capacity ( kg ) 450 – 1600

Technology The machine-room-less elevator is a result of our technological such as slim-form gearless traction machine with permanent magnet ( PM ) motor or a significant reduction in the size of the devices ; installing all traction equipment in the hoistway. Thus, overhead machine was eliminated and required space for elevator installation was minimized. It gives more freedom of building layout to architects.

7.2.2 Product Information

60

Page 64: B.serv   project 2 (final report)

The shaft, or known as hoistway, is the vertical passageway for the car and counterweights. On the sidewalls, there are car guide rails and certain mechanical and electrical auxiliaries of the control machine. At the bottom of the hoistway are the car and counterweight buffer, while on top of the platform is where the machine compact machine, or known as traction machine, where MRL elevators uses permanent motor ( PM ) rests. The permanent motor supplies energy to the elevator

The car is the main machine that carries the passengers and stuff. The building’s prestige depends on the design of the elevator car. The car is guided in its vertical travel in the hoistway. It is provided with safety doors, operating-control equipment, floor- level indicators, lighting, emergency exits, smoke detector and ventilation.

Counterweight are made up of cut steel plates, which were stacked in a frame that is attached to the opposite side of the cables, where the car were attached. It is guided in its travel up and down the hoistway by two guide rails, that were normally installed on the back wall of the hoistway. Its weigh equals that of the empty car plus 40% of the rated live load. It is used to provide sufficient traction to the sheave for car-lifting.

I. Hoistway

II. Car

III. Counterweight

UBBL 1984 – Clause 153 [ ACT 133 ]

( 1 ) Smoke detector must be present at all lift lobbies( 2 ) A lift that does not open into a smoke lobby shall not use opening devices controlled by light or photo – detectors unless a force close feature is installed which after 30 seconds of any interruption of the beam, causes the door to close within a preset time.

Figure 7.2: Example of Hoistway

Figure 7.3: Example of car

Figure 7.4: Example of counterweight

61

Page 65: B.serv   project 2 (final report)

Counterweight are made up of cut steel plates, which were stacked in a frame that is attached to the opposite side of the cables, where the car were attached. It is guided in its travel up and down the hoistway by two guide rails, that were normally installed on the back wall of the hoistway. Its weigh equals that of the empty car plus 40% of the rated live load. It is used to provide sufficient traction to the sheave for car-lifting.

IV. Permanent Magnet

Figure 7.5: Example of Permanent Magnet

62

Page 66: B.serv   project 2 (final report)

Figure 7.6: Mistubishi Emergency Landing Device

Figure 7.8: Firefighters’ Emergency Operation (FE)

Figure 7.7: Operation by Emegency Power Source (OEPS)

Figure 7.9: Fire Emergency Return (FER)

In case of emergency, these are operation of the elevator.

Upon power failure, the car will automatically moves to the nearest floor using a rechargeable battery to facilitate the safe evacuation of passengers. Upon power failure, predetermined car uses a building’s emergency power supply to move to a specified floor and open the doors for passengers to evacuate.

When a key switch or a building’s fire alarm is activated, all cars immediately return to a specified floor and open the doors to facilitate the safe evacuation of passengers. When the fire operation switch is activated, the car immediately returns to a predetermined floor. The car then responds only to car calls which facilitate firefighting and rescue operations.

7.2.4 Operation of System

UBBL 1984 – Clause 154 [ ACT 133 ]

( 1 ) During the event of a power failure, all lifts shall return in sequence directly to the designated floor, commencing with fire lifts, without answering any car or landing calls and park with the door open.

63

Page 67: B.serv   project 2 (final report)

Figure 7.10: Placement of elevators in Ground Floor Plan and First Floor Plan

64

Page 68: B.serv   project 2 (final report)

8. Conclusion

65

When people enter a particular building, they will normally be aware of their surroundings on aesthetics, scale or the atmosphere. However, people often neglect the intricate utilities and services that run within the building. They forget that it is these services that provide their needs, comfort and safety. These are the services proposed for the chosen elderly center.

The active fire protection system consists of many different components that works together to react quickly and appropriately if when a fire breaks out. It is composed of detectors, triggers, communication systems and fire response systems. These appliances help identify, notify, evacuate and resolve the fire in rapid succession.

The passive fire protection system however, aims to carefully prevent a fire. It is considered before the building is built as the building materials as well as architectural components are involved in fire prevention. If a fire breaks out, the passive fire protection system protects the inhabitants with a clear evacuation plan. It has to relay instructions as to how to evacuate through exit signs as well as to provide an escape route and an assembly point.

As Malaysia has a warm and humid climate, the users are typically of old age and could not cope with the hot weather. Thus, an air-conditioning system is crucial in providing comfort for the inhabitants. A VRV system is proposed as it is centralised at the same time can control areas individually. This makes it energy efficient, space saving and flexible.

The chosen building has a unique characteristic of being very open. Therefore, mechanical ventilation plays an important role in circulating air at the open spaces. Ceiling fans have to cool down the majority part of the building while the exhaust hood removes gases and odours from the kitchen. Wall ventilation fans and centrifugal fans have to be installed in the elevators to properly circulate air within the cores and cars.

As the building is an elderly center, mobility between two vertical levels becomes an issue. The building has to provide elevators for convenience and the health of the old folks. A machine-room-less elevator is proposed as it saves space without a machine room. It save energy and most ultimately, it is quiet, thus it does not disturb the activities carried out in the center.

The services proposed for the chosen elderly center has to be suitable for the users residing in the building, fulfil criteria given by the government and also respond respectfully to the surrounding climate. Even though they are not noticed, building services is as important if not more than the other elements that make up a building.

Page 69: B.serv   project 2 (final report)

9. References1) Association of Wall & Ceiling Contractors of B. C. (2003). Specification standards manual for the wall and ceiling industry: Lathing, interior plastering, stucco, gypsum board, gypsum shaft walls, steel studs and furring, exterior insulation and finish systems and associated wall and ceiling systems. Surrey, B.C.: Association of Wall and Ceiling Contractors of B.C.

2) 2.1 Compartmentation. (n.d.). Retrieved November 15, 2016, from http://www.gov.scot/resource/buildingstandards/2016NonDomestic/chunks/ch03s02.html

3) Sultan, M. A. (2015). Effect of Gypsum Board Orientation on Board Fall-Off in Fire Resistance Test Assemblies. Advances in Gypsum Technologies and Building Systems, 10-29. doi:10.1520/stp158820150013

4) Designing Buildings Wiki The construction industry knowledge base. (n.d.). Retrieved November 15, 2016, from https://www.designingbuildings.co.uk/wiki/Fire_compartment

5) Uniform Building By-laws 1984 (G.N. 5178/85): As at 20th May 2003. (2003). Petaling Jaya, Selangor Darul Ehsan: International Law Book Services.

6) Basic Fire Door Requirements. (2001). Basic Fire Door Requirements. Retrieved November 20, 2016, from https://www.steeldoor.org/res/118.pdf.

7) Chapter 2 - MEANS OF ESCAPE. (n.d.). MEANS OF ESCAPE, 1-91. Retrieved November 15, 2016, from https://www.scdf.gov.sg/content/scdf_internet/en/building-professionals/publications_and_circulars/fire_code_2002handbooks/_jcr_content/par/download_4/file.res/hb_v3_ch2.pdf.

8) Stein, B., Reynolds, J., & McGuinness, W. J. (1992). Mechanical and electrical equipment for buildings. New York: J. Wiley & Sons.

9) Types of Air Conditioning Systems: Window, Split, Packaged and Central. (2013). Retrieved November 24, 2016, from http://www.brighthubengineering.com/hvac/897-types-of-air-conditioning-systems/ McDowall, R. (2006). Fundamentals of Hvac Systems. Academic Press.

10) Joshua Lee, Student at Taylor’s University Sdn Bhd Follow. (2016). Building Services. Retrieved November 24, 2016, from http://www.slideshare.net/JoshuaLee68/building-services-64048449

11) M. (2010). VRV / VRF demo. Retrieved November 24, 2016, from http://www.youtube.com/watch?v=bjM_Z6LPvYc

12) AM320FNBDEH/EU | Samsung Business UK. (n.d.). Retrieved November 24, 2016, from http://www.samsung.com/uk/business/business-products/vrf-dvm-s/vrf-dvm-s/AM320FNBDEH/EU

66

Page 70: B.serv   project 2 (final report)

13) BE Air Conditioning Ltd - air conditioning installation, service, repair & design in Sussex, UK. (n.d.). Retrieved November 24, 2016, from http://www.beairconditioning.co.uk/air_conditioning_vrv.htm 14) VRV / VRF. (n.d.). Retrieved November 24, 2016, from http://www.ab3s.in/vrv-vrf.php 15) D. (n.d.). Variable Refrigerant Volume Systems [Pamphlet]. 16) Air Curtain Doors - Air One. (n.d.). Retrieved November 24, 2016, from http://aironeinc.com/air-curtain-doors/ 17) Cassette air conditioners. (n.d.). Retrieved November 24, 2016, from http://www.build.com.au/cassette-air-conditioners 18) Air Conditioning Systems. (n.d.). Retrieved November 24, 2016, from http://www.new-learn.info/packages/clear/thermal/buildings/active_systems/ac/ac_systems.html

19) Machine-Room-Less (MRL) Elevators. (n.d.). Retrieved November 22, 2016, from http://www.buildings.com/article-details/articleid/3076/title/machine-room-less-mrl-elevators

20) Stein, B., Reynolds, J., & McGuinness, W. J. (1992). Mechanical and electrical equipment for buildings. New York: J. Wiley & Sons.

67