bor11999 nsw manual bk1 structural fire accustic
TRANSCRIPT
-
8/10/2019 Bor11999 Nsw Manual Bk1 Structural Fire Accustic
1/72
1BOOK1 Structural, Fire and AcousticMasonry Design Guide
New South Wales
Updated May 2008
-
8/10/2019 Bor11999 Nsw Manual Bk1 Structural Fire Accustic
2/72
BOOK
PAGE
1
Introduction
A2BOOK
PAGE
1
Contents
A2
The information presented herein is supplied in good faith and to the best of our knowledge was accurate at the time of preparation. No responsibility can be accepted by
Boral or its staff for any errors or omissions. Users are advised to make their own determination as to the suitability of this information in relation to their particular purpose
and specific circumstances. Since the information contained in this document may be applied under conditions beyond our control, no responsibility can be accepted by us
for any loss or damage caused by any person acting or refraining from action as a result of this information.
C Fire DesignMasonry Design for Fire Resistance (FRL) . . . . . . . . . . . . . . C2
Masonry Design for Structural Adequacy FRL . . . . . . . . . . . C2
Masonry Design for Integrity FRL . . . . . . . . . . . . . . . . . . . . . C3
Masonry Design for Insulation FRL . . . . . . . . . . . . . . . . . . . . C4
Effect of Chases on Fire Rated Masonry . . . . . . . . . . . . . . . C4
How to Select Boral Masonry Units forFire Rated Walls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C5
Structural Adequacy Selection Graphs and Tables . . . . . . . . C8
Index to Structural Adequacy Selection Graphs . . . . . . . . . . C8
D Acoustic DesignAcoustic Performance Ratings (STC and Rw) . . . . . . . . . . . . D2
Designing Masonry Walls forAcoustic Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . D3
Guidelines for Optimum Performance . . . . . . . . . . . . . . . . . D4
Acoustic Performance On-site . . . . . . . . . . . . . . . . . . . . . . . D5
Home Cinema Rooms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . D6
E Fire and Acoustic SystemsFinding Acoustic Systems andTechnical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . E2
FireBrick (F) Scoria Blend . . . . . . . . . . . . . . . . . . . . . . . . . . . E4
FireBlock - Scoria Blend Blocks . . . . . . . . . . . . . . . . . . . . . . E7
FireLight Bricks (FL) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . E9
Basalt-Concrete Bricks (B) . . . . . . . . . . . . . . . . . . . . . . . . . E12
Standard Grey Block and Designer Block . . . . . . . . . . . . . . E16
Acousticell . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . E18
B Structural DesignIntroduction to the Structural Design of Masonry . . . . . . . . B2
Robustness . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B2
Strength . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B5
Bending . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B5
Shear . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B6
Durability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B6
Movement (Control Joints) . . . . . . . . . . . . . . . . . . . . . . . . . . B6
Energy Efficiency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B7
Reinforced Masonry Lintels . . . . . . . . . . . . . . . . . . . . . . . . . B9
Design of Core Filled and Steel ReinforcedMasonry Retaining Walls . . . . . . . . . . . . . . . . . . . . . . . . . . B10
Structural Design Guidelines forCore Filled and Steel ReinforcedMasonry Retaining Walls . . . . . . . . . . . . . . . . . . . . . . . . . . B12
A IntroductionContents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A2
Fast Find Product and Application Guide . . . . . . . . . . . . . . . A3
Products @ a Glance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A4
About This Guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A6
PAGE
PAGE
-
8/10/2019 Bor11999 Nsw Manual Bk1 Structural Fire Accustic
3/72
BOOK
PAGE
1
Introduction
A3BOOK
PAGE
1
Fast Find Guide
A3
The quickest way to find a Boral Masonry Structural, Fire or Acoustic Wall Solution.
Simply follow the FAST FIND GUIDE on the right hand side of the table.
1
BORALMASONRY
BLOCK &
BRICK
PRODUCTSW
ALLF
INISH
2
Select your application
criteria from the top ofthe table
Go straight to the section
letter and page number
indicated at the
intersection of product
rows and application
columns (e.g. Section E,
Page E12 in this example)
Please refer to MDG Book 2, BoralMasonry Block & Brick Guide
Best performance is achievedwith plasterboard lining
NLB LB NLB LB NLB LB NLB LB NLB LBNLB = Non-loadbearing
LB = Loadbearing
Face
Mason
ry
Retaini
ngWall
Fast Find
a Boral
Solution
Rend
ered
Plaste
rboa
rd
NoLinin
g
E4 E4 E4 FireBrick (F) Scoria Blend
E19 E19 E19 E19Designer Block
E12 E12 E12 E12 E12 E12 Basalt-Concrete (B)
E9
E9 E9 FireLight Bricks (FL)
E7 E7 E7 Scoria Blend Blocks
E21 E21 Acousticell
E19 E19 E19 E19 E19 E19 Standard Grey Block
E19 E19 E19 E19E19 E19 E19 E19 E19 E19Core Filled Block
For technical support and sales office details please refer to the outside back cover
-
8/10/2019 Bor11999 Nsw Manual Bk1 Structural Fire Accustic
4/72
BOOK
PAGE
1
Products @ a Glance
A4
Boral Engineered Blocksfor Structural, Fire & Acoustic Wall Systems
Standard Grey and Designer BlockHollow Concrete Block suitable for loadbearing
and non-loadbearing applications. 60 minute
insulation FRL as hollow blockwork. Higher FRLs
are achieved when reinforced and core-filled.
Scoria Blend High Fire Rated BlockManufactured in a unique Scoria Blend material
offering Fire Resistance Levels (FRLs) to 240
minutes without core-filling. Ideal for high rise
buildings with reinforced concrete frames or
portal frame buildings. Suitable for non-
loadbearing walls. If used for l ight load
construction, the lower slenderness ratios of
Designer Block apply.
Core Fill BlockGrey Concrete Block or Designer Block coloured
and textured finishes for reinforced retaining
walls and loadbearing walls requiring increased
robustness.
Acousticell
Engineered block for premium sound absorption
and attenuation of low frequency industrial and
commercial noise.
-
8/10/2019 Bor11999 Nsw Manual Bk1 Structural Fire Accustic
5/72
BOOK
PAGE
1
Introduction
A5BOOK
PAGE
1
Products @ a Glance
A5
Boral Engineered Bricksfor Structural, Fire and Acoustic Wall Systems
FireLight Brick (FL) FireLight Brick for non-loadbearing fire and/or
acoustic systems (high rise) where weight
saving is important. Double Brick format
(162mm height) for faster, more cost effective
construction.
FireBrick (F) Medium weight Scoria Brick for non-loadbearing
fire and/or acoustic systems. Double Brick
format (162mm height) for faster, more cost
effective construction.
Basalt-Concrete Brick (B) Standard Size, Brick-and-a-Half (119mm high) and Double
(162mm high) in Concrete-Basalt material for good fire
performance and loadbearing characteristics.
-
8/10/2019 Bor11999 Nsw Manual Bk1 Structural Fire Accustic
6/72
BOOK
PAGE
1
About This Guide
A6
Boral Masonry
Commercial Construction Solutions
Boral Masonry NSW offers a comprehensive range of proven
products and systems including Masonry Blocks, MasonryBricks, Fire and Acoustic Wall Systems, Segmental Block
Retaining Walls and Segmental Paving Products.
Whats in this Guide
The Boral Masonry Structural, Fire & Acoustic guide
provides a summary of important design information for
structural, fire and acoustic masonry applications and an
extensive range of fire and acoustic systems.
Section B Structural Design
Section B discusses design issues relevant to the selectionof Boral Masonry products for structural adequacy, based on
appropriate wall design criteria.
Section C Fire Design
Section C discusses the relevant design processes for the
selection of Boral Masonry Products forfire rated applications.
This section includes a step-by-step selection guide and a
series of tables and graphs which can greatly speed up the
preliminary selection and comparison of suitable designs
and products.
Section D Acoustic Design
Section D provides a briefoverview of acoustic rating methods,
relevant considerations for acoustic design and guidelines
for good acoustic design and detailing methods.
Section E Fire & Acoustic Systems
Section E of this guide provides an extensive range of fire
and acoustic wall system solutions supported by test results
and acoustic performance estimates.
This guide has been prepared as a comprehensive Boral
Product Reference Guide. It does not attempt to cover all the
requirements of the Codes and Standards which apply to
masonry construction for structural, fire or acoustic
applications. All structural, fire and acoustic detailing shouldbe checked and approved by appropriatelyqualified engineers
before construction. Boral reserves the right to change the
contents of this guide without notice.
Please note that this guide is based on products available at
the time of publication from the Boral Masonry New South
Wales sales region. Different products and specifications may
apply to Boral products sourced from other regions.
Additional Assistance & Information
Contact Details: Please refer to the outside back cover ofthis publication for Boral Masonry contact details.
Colour and Texture Variation: The supply of raw
materials can vary over time. In addition, variation can
occurbetween product types and production batches. Also
please recognise the printed colours in this brochure are
only a guide. Please, always ask to see a sample of your
colour/texture choice before specifying or ordering.
Terms and Conditions of Sale: For a full set of Terms
and Conditions of Sale please contact your nearest Boral
Masonry sales office.
-
8/10/2019 Bor11999 Nsw Manual Bk1 Structural Fire Accustic
7/72
1SECTIONB Structural DesignSTRUCTURAL, FIRE & ACOUSTICMasonry Design Guide
New South Wales
BOOK
1
-
8/10/2019 Bor11999 Nsw Manual Bk1 Structural Fire Accustic
8/72
BOOK
PAGE
1
Structural Design
B2
Introduction to the StructuralDesign of Masonry
The following design information is based on Australian
Standard AS3700:2001 Masonry structures. Reference to
Clauses and Formulae are those used in AS3700. This
information is provided as a guide only to the processes
involved in designing masonry. All masonry should be
designed by a suitably qualified structural engineer.
Robustness
AS3700, Clause 4.6.1 requires walls to have an adequate
degree of Robustness. Robustness is a minimum design
requirement, and may be overridden by Fire, Wind, Snow,Earthquake, Live and Dead Load requirements.
In robustness calculations,there are height, length,and panel
action formulae. Byreworking the standard formulae provided
and inserting known data, it is possible to determine whether
a chosen design and Boral masonry product will provide
adequate robustness. Should the initial product selected not
provide a suitable solution, then a thicker Boral masonry
product more suited to the application should be evaluated,
or alternatively, add extra restraints or reinforcement.
The following section is laid out with AS3700 formulae and
explanation in the left hand column, while worked examples
can be found in the adjacent right hand column.
Legend to Symbols used in Robustness Calculations:
H = the clear height of a member between horizontal
lateral supports, in metres;
= for a member without top horizontal support, theoverall height from the bottom lateral support, in
metres
tr = the minimum thickness of the member, in metres
= in cavity-wall construction, the minimum thickness
of the thicker leaf
or two thirds the sum or thicknesses ofthe two leaves,
whichever is greater, in metres
or in diaphragm wall construction, the overall
thickness of the wall, in metres
kt = a thickness coefficient,values as given in AS3700
Table 7.2 (see the end of this section)
Cv,Ch = robustness coefficient,values as given in AS3700
Table 4.2(see end of this section) foredge restraints
at top, bottom and vertical sides (either separately
or in combination)
Lr = the clear length of the wall between vertical lateral
supports, in metres; or
= for a wall without a vertical support at one end or
at a control joint or for walls containing openings,
the length to that unsupported end orcontrol joint
or edge of opening, in metres.
-
8/10/2019 Bor11999 Nsw Manual Bk1 Structural Fire Accustic
9/72
BOOK
PAGE
1
Structural Design
B3
Isolated Piers
Formula 4.6.2 (1) is used for isolated piers. Masonrywith
a length less than one fifth of its height and free ends,is considered to be an isolated pier.
Formula (1) is:
By re-working formula (1), the maximum height for an
isolated pier can be determined:
H tr x Cv
Where Cv is obtained from AS3700 Table 4.2 (Refer to
Page B5).
H Cv
tr
Formulae and Explanation Worked Examples
Formulae and Explanation Worked Examples
Aim: To determine the Maximum Wall
Height of an Isolated Pier
Example 1: Minimum wall thickness tr = 230mm
A single leaf structure, unreinforced, then
Cv= 13.5
H 0.23 x 13.5
H 3.105m (maximum wall height)
Example 2: Minimum wall thickness, tr = 140mm
A single leaf structure, reinforced, then
Cv= 30
H
0.14 x 30H 4.200m (maximum wall height)
Aim: To determine the Maximum Height of
a Wall with Free Ends
Criteria: Minimum wall thickness, tr = 110mm
kt = 1 (wall without piers)
Example 1: If wall is freestanding, then Cv=6
(must be checked by an engineer for
wind loads etc.)
H 1.0 x 0.11 x 6
H 0.660m
Example 2: If wall is laterally restrained along its top,
then Cv=27
H
1.0 x 0.11 x 27H 2.970m
Example 3: If wall is laterally restrained along its top
and supports a slab, then Cv=36
H 1.0 x 0.11 x 36
H 3.960m
Wall with Free Ends
Formula 4.6.2 (2) is used for walls spanning vertically
(i.e. wall with free ends).
Formula (2) is:
By re-working formula (2), the maximum wall height is:
H kt x tr x Cv.
Where kt is obtained from AS3700 Table 7.2 (Refer to Page
B5)
or
By re-working formula (2), the minimum wall thickness
is:
kt x tr H
Cv
H Cv
kt x tr
-
8/10/2019 Bor11999 Nsw Manual Bk1 Structural Fire Accustic
10/72
BOOK
PAGE
1
Structural Design
B4
Aim: To determine the Maximum Length
of a Wall with Restraint at End or
Ends
Criteria: Wall thickness tr = 110mm
Example 1: If wall is restrained along one end, then
Ch = 12
L 0.11 x 12
L 1.320m
Example 2: If wall is restrained along both ends, then
Ch = 36
L 0.11 x 36
L 3.960mNOTE: If the wall exceeds the permitted length, then a
thicker wall is required or formula 4.6.2 (4) governs and
H will be limited. (See below).
Aim: To determine the Maximum Height of
a Wall with Restraint at Top and End
or Ends
Criteria: Wall thickness tr = 110mm
Wall length = 2m
Example 1: If wall supports a slab, then Cv= 36, and
if restrained along one end, then Ch = 12
H 5.9m
0.11)+ 122 12 x 0.1136(H
Wall with Restraint at Top and End or Ends
Formula 4.6.2 (4) is for walls spanning vertically and
horizontally (i.e. with restraint along the top and one or
two ends) and length L > tr x Ch.
Where Ch is obtained from AS3700 Table 4.2. (Refer to
Page B5)
Formula (4) is:
By re-working formula (4), the maximum wall height is:
NOTE: Control joints, and openings greaterthan one fifth
of wall height are treated as free ends unless specific
measures are taken to provide adequate lateral support.
tr)+ ChLr ChtrCv(H
+Ch
Lr Chtr
H Cv
tr
Wall with Restraint at End or Ends
Formula 4.6.2 (3) is for walls spanning horizontally [i.e.
restrained end(s)]. Walls that have one or both ends
laterally restrained and
i.e. L tr x Ch
Where Ch is obtained from AS3700 Table 4.2. (Refer to
Page B5)
NOTE: This means that although the wall height is not
limited by its thickness, the wall length is limited. Stair
wells and chimneys work to this formula.
H= no limit
tr
L Ch
tr
Formulae and Explanation Worked Examples
Formulae and Explanation Worked Examples
-
8/10/2019 Bor11999 Nsw Manual Bk1 Structural Fire Accustic
11/72
BOOK
PAGE
1
Structural Design
B5
Strength
Compressive strength is resistance to load, measured by the
amount of pressure to crush a masonry unit. The pressure,
usually measured in megapascals (MPa), is the force inkilonewtons (kN) x 1000, divided by the loaded area in square
mm.
Unconfined compressive strength is compressive strength,
multiplied by an aspect ratio, Ka. (Details are in AS4456.4,
Table 1). The unit height divided by its thickness is used to
determine the aspect ratio.
A solid brickwill give a lowercompressive strength if crushed
on its end rather than on its flat, as normally laid. In theory,
the aspectratio will convert both tests to the same unconfined
compressive strength.
The strength of hollow blocks is calculated by dividing the
force by the face shells only. A 90mm hollowand 90mm solid
block are both 10MPa, but since the area of the face shells
on the hollow block is about half the area of the solid block,
the hollow will only carry half the load of the solid.
Characteristic Unconfined Compressive Strength of
masonry UNITS is uc.
uc is the average of crushing forces divided by loaded areas,
multiplied by the aspect ratio, minus the standard deviationx 1.65.
Characteristic Compressive Strength of a masonry
WALL is m.
m is the square root ofuc, multiplied by Km (a mortar
strength factor), multiplied by Kh (a factor for the amount of
mortar joints) as perAS3700, 3.3.2.
The Km factor is 1.4 for M3 mortar on solid and cored units
and is 1.6 for the face shells of hollow units. For the richer
M4 mortar it is 1.5. (Details are in AS3700, Table 3.1).
The Kh factor is 1 for 76mm high units with 10mm mortar
beds and is 1.3 for 190mm units with 10mm mortar beds.
In other words, a wall of 190mm high units is 30% stronger
than a wall of 76mm high units of the sameuc.
Bending
Characteristic Flexural Tensile Strength is mt.
Masonry is good in compression but poor in tension. Mortar
jointstrength is generally zero or 0.2MPa for loads from wind,earthquake etc. Higherbending forces mayrequire masonry
to be partially reinforced.
Horizontallyunreinforced
ChEdge restraints onvertical sides of
wall panels
Horizontallyreinforced orprestressed
SUPPORT
SUPPORT
SUPPORT
12
36
24 with
reinforcementcontinuous past
support.
Otherwise 16
48
CvTop and bottom edge
restraints to wall panels Verticallyunreinforced
Vertically reinforcedor prestressed
Free
SUPPORT
LateralSupport
Load other thanconcrete slab or no load
SUPPORT
LateralSupport
Concrete Slab
SUPPORT
LateralSupport
SUPPORT
ISOLATED PIERS
6
12 withreinforcement
continuous into
support. Otherwise
6.
27 36
36 48
13.5 30
Table B1 (Extract from AS3700 : Table 4.2)
Pier Spacing/PierWidth Thickness Coefficient (kt)
(Refer to Note 1) Pier Thickness Ratio (twp/t)
1 2 3
6 1.0 1.4 2.0
8 1.0 1.3 1.7
10 1.0 1.2 1.4
15 1.0 1.1 1.2
20 or more 1.0 1.0 1.0
Pier Spacing
Pier Width
ttwp
Wall Leaf
Table B2 (Extract from AS3700 : Table 7.2)Thickness Coefficient (kt) for Walls Stiffened by
Monolithically Engaged Piers
NOTES: 1. Pier spacing is taken as the distance between centrelines of piers.
2. Linear interpolation may be used.
-
8/10/2019 Bor11999 Nsw Manual Bk1 Structural Fire Accustic
12/72
BOOK
PAGE
1
Structural Design
B6
Shear
Characteristic Shear Strength is ms.
At damp course, it is zero unless tested. Elsewhere, mortar
joints have ms values of between 0.15 and 0.35MPa.
As with tension, high shear loads may require partially
reinforced masonry.
Durability
Masonry designed forDurability is deemed to satisfywhen
it meets the requirements ofAS3700 Section 5, which details
whatareas require Exposure, General Purpose and Protected
grades. Assessment of these grades is defined in
AS/NZS4456.10 Resistance to Salt Attack.
AS3700 defines the usage of each of these grades as:
Protected Grade (PRO)
Elements above the damp-proof course in non-marine exterior
environments. Elements above the damp-proof course in other
exterior environments, with a waterproof coating, properly
flashed junctions with other building elements and a top
covering (roof or coping) protecting the masonry.
General Purpose Grade (GP)
Suitable for use in an external wall excluding severe marineenvironment.
Exposure Grade (EXP)
Suitable for use in external walls exposed to severe marine
environments, i.e. up to 100m from a surf coast or up to 1km
from a non surf coast. The distances are specified from mean
high water mark.
Mortarmixrequirements fordurability are detailed in AS3700
Table 10.1. Mortar joints must be ironed.
Salt attack is the most common durability problem. The saltin salt water is in solution. It can be absorbed into masonry
or at least, its mortar joints. When the water evaporates, it
migrates towards the outside face taking the salt with it until
the amount ofwater left is saturated. Itcan no longerhold all the
salt in solution and salt crystals begin to form.
The salt crystals then take up space, sometimes more than
the texture of the masonrywill allow. The crystal then pops
a piece of the outer surface off to make room and salt attack
begins.
Walls below damp course also require greater durability.
Even if theyare well awayfrom the coast,theymaybe subjected
to acidic or alkaline soils. In anycase, moisture in the ground
is absorbed into the masonry, creating an environment ideal
for bacteria, which feeds lichens and algae which can
eventually be detrimental.
AS/NZS4456.10 gives methods of testing and definitions for
durability (salt tests). An alternative to testing is a history of
survival in a marine environment. Concrete masonryhas been
used forSurf Club construction around Australia fordecades.
Movement
In general, concrete units contract as theycure while clay units
will expand. They both expand as they take up water and
contract as they dry. They both expand as they get hot andcontract as they cool.
Curing Movement in Concrete Units
AS/NZS4456.12 gives methods for determining coefficients
of curing contraction and coefficients of drying contraction
for concrete units.
Drying Contraction
The drying contraction teston masonryunits is an indication of
their maximum amount of movement from totally saturated to
ambientdry. Atypical result is 0.5mm/m butcan be as high as1mm/m for lightweight units that are more absorptive. For
example, a drying contraction of 0.5mm/m, in an 8m panel of
masonry, has the potential to shrink 4mm from saturated
condition to dry.
External Control Joints
AS3700, Clause 4.8 requires control joint spacing to limit
panel movement to:-
10mm maximum for opening of control joints,
15mm maximum for closing of control joints, and
5mm minimum when closed.
The Australian Masonry Manual recommends control joints
at 8m centres for concrete units, 6m centres for lightweight
(
-
8/10/2019 Bor11999 Nsw Manual Bk1 Structural Fire Accustic
13/72
BOOK
PAGE
1
Structural Design
B7
External control joints should be finished with a flexible
sealant.
Control joints create a free end in terms of robustness and
FRLs for structural adequacy, so their positioning is critical
to the overall design of the structure.
In portal frame construction, the control joint is positioned
at a column so that both ends can be tied to the column
flanges. The mason and renderer must keep the control joint
clean, otherwise,bridging mortaror renderwill induce cracks
from those points as the masonrymoves. If ties are used over
control joints, they must be sleeved to allow movement.
Adding extra cement to mortar or render causes more
shrinkage. Lightweight units are only5MPa,so are susceptible
to cracking if laid in rich mortar or rendered with a cement-rich mix.
Internal Control Joints
The Australian Masonry Manual specifies the spacing of
internal control joints for concrete units at 12m maximum.
Energy Efficiency for Class 2,3 & 4 buildings in ACT
The Building Code ofAustralia (BCA) 2005,Volume 1, requires
the walls of Canberra home units,hotels and similardwellings
to have:-
Total R-Value rating of 1.9 (Climate Zone 7) or
Wall mass > 220kg/m2 and include insulation with an
R value not less than 1.
Total R-Value means the sum of thermal resistances
(m2.K/W) of wall components including air spaces and
associated surface resistances.
In BCA Specification J1.5 Wall Construction, options (a) (b)
& (c) for concrete masonry give theirTotal R-values without
insulation.
The R-value of the insulation needed to make up the required
Total R-value for masonry veneer in Zone 7 is R1.5. Masonry
minimum thickness is 90mm. The insulation is usually placed
between the studs.
Alternative verification can be achieved through a 4 star
assessmentforClass 2& 4buildings using calculations defined
in BCAClause JV1,and forClass 3 buildings,calculating energy
consumption to meet values as per Clause JV2 or comparison
with a reference building as per Clause JV3.
Energy Efficiency for ACT Houses
In the ACT, houses are required to have a 4 star rating as
assessed byan accredited ACTHouse EnergyAssessor or by
equivalent assessment with R1.5 insulation material in the
external walls of brickveneer construction. Cavity brick of 2
x 90mm minimum thicknesses is exempt.
-
8/10/2019 Bor11999 Nsw Manual Bk1 Structural Fire Accustic
14/72
BOOK
PAGE
1
Structural Design
B8
NSW Energy Efficiency: Class1, 2, 3 & 4 buildings
Class 1, 2 and 4 buildings
The Building Code ofAustralia (BCA) 2005,Volume 1, requires
the walls of home units in Sydney(and progressivelyelsewhere
in NSW) to complywith BASIX(building sustainability index),
a web-based planning tool at www.basix.nsw.gov.au
Class 3 buildings
Walls of Class 3 buildings (hostels, hotels, motels) are required
bythe BCA,J1.5 to have one ora combination of the following:
Total R-Valuerating of1.4 in Climate Zone 2& 5 (North Coast
to Sydney)
A rating of 1.7 in Climate Zone 4 & 6 (Western NSW)
A rating of 1.9in Climate Zone 7(Armidale & Sthn Highlands)
A rating of 2.8 in Climate Zone 8 (Thredbo)
or
Wall mass > 220kg/m2 in Climate Zone 4 & 5 and in Zone
6, 7 & 8, include insulation with an R value not less than 1
(floor system in Zone 6 to be slab on ground).
Total R-Value means the sum of thermal resistances
(m2.K/W) of wall components including air spaces and
associated surface resistances.
In Specification J1.5Wall Construction, options (a) (b) & (c)
for concrete masonry give their Total R-values without
insulation.
The R-value of the insulation needed to make up the required
Total R-value for masonry veneer is:
R1.0 in Climate Zone 2 & 5
R1.3 in Climate Zone 4 & 6
R1.5 in Climate Zone 7 and
R2.4 in Climate Zone 8.
The insulation is usually placed between the studs.
For cavity brick, these insulation R-values can be 0.3 lower
than for brick veneer. The insulation is between battens on
the inside face, under 10mm plasterboard.
Minimum masonry thickness is 90mm.
For 190mm hollow concrete blocks, partially core filled and
with a bond beam at the top, the insulation R-values can be
0.1 lower than for brick veneer.
Options for Increasing R values
The insulating properties of masonrywalls may be increased
by the following means:
The addition of polyester or glasswool insulation betweenstuds for masonry veneer construction.
The addition of polystyrene sheets between wall ties for
cavity masonry construction.
The addition of polyester or glasswool insulation behind
plasterboard, between battens on inside face of masonry.
(Battens eliminate the need for chasing for plumbing and
electrical services).
Incorporating reflective insulation within the cavity.
Incorporating foam insulation,pumice orvermiculite within
the cores of the units or in the cavity.
Using masonry units with a rough surface. (This traps a
thicker air film at the surface).
Using masonryunits made from less dense material. (Tiny
air pockets within the material disrupt the flow of heat
energy through the wall).
Using thicker walls.
-
8/10/2019 Bor11999 Nsw Manual Bk1 Structural Fire Accustic
15/72
BOOK
PAGE
1
Structural Design
B9
15.12
70
100
Horizontal
Bars Vc Mc
N12 5.1 2.0N16 6.3 2.9
Vertical
Bars Vc Mc
N12 5.1 2.6N16 6.3 2.6
Cut on-site
Horizontal
Bars Vc Mc
N12 10.2 4.0N16 12.6 4.7
Vertical
Bars Vc Mc
N12 12.5 9.3N16 13.7 16.0
15.12
70
300
100
Horizontal
Bars Vc Mc
N12 8.2 4.0N16 9.3 6.9N20 10.6 9.9
129 (N12 bars)127 (N16 bars)125 (N20 bars)
20.12
Vertical
Bars Vc Mc
N12 7.9 3.6N16 10.2 3.6N20 13.1 3.6
100
Horizontal
Bars Vc Mc
N12 6.4 2.9N16 7.6 5.0N20 9.1 6.5
95
20.12
Vertical
Bars Vc Mc
N12 6.4 2.9N16 7.6 3.6N20 9.1 3.6
Horizontal
Bars Vc Mc
N12 16.4 8.0
N16 18.6 13.4N20 21.3 17.2
129 (Y12 bars)127 (Y16 bars)125 (Y20 bars)
20.20 or20.01 cuton-site
Vertical
Bars Vc Mc
N12 17.9 18.0N16 20.2 30.2N20 23.1 32.2
300
20.12
95
300
20.12
Horizontal
Bars Vc Mc
N12 12.9 5.7
N16 15.2 9.5N20 18.1 9.9
20.20 or20.01 cuton-site
Vertical
Bars Vc Mc
N12 16.4 9.5N16 17.6 16.6N20 19.0 24.4
Reinforced Masonry Lintels
Moment and Shear Capacities for Series 150 Blocks (140mm leaf)
NOTES
Vc = Shear capacity (kN)
Mc = Moment capacity (kNm)
Mortar type, M3
Block characteristic compressive strength,
uc = 15MPa
Grout compressive strength,
c = 20MPa
Cement content min. (Grout) = 300kg/m3
Moment and Shear Capacities for Series 200 Blocks (190mm leaf)
-
8/10/2019 Bor11999 Nsw Manual Bk1 Structural Fire Accustic
16/72
BOOK
PAGE
1
Structural Design
B10
Design of Core Filled &Steel Reinforced MasonryRetaining Walls
Introduction
The information presented here is supplied in good faith and
to the best of our knowledge was accurate at the time of
preparation. However, from time to time, additional ormodified
data may be released by the CMAA. Any such information
will supersede the information presented in this guide.
This section provides specifications,design tables and typical
details for a range of reinforced concrete masonry retaining
walls and their associated reinforced concrete bases. It is
intended as a general guide for suitably qualified andexperienced professional engineers, who for any particular
proposed retaining wall, must accept the responsibility for
carrying out a comprehensive site investigation, determining
the soil characteristics and other design parameters of the
particularsite, and fordesigning and detailing the structures.
It is important forthe professional engineer to determine the
strength and stability of the foundation material and the
drainage system required to ensure there will not be a build
up of hydrostatic pressure behind the wall.
All designs are based on:
Reinforced Concrete Masonry Structures AS3700 : 2001
SA Masonry Code.
Reinforced Concrete Base AS3600 : 1988 Concrete
Structures.
Reinforcement AS1302 : 1982Steel Reinforcing Bars for
Concrete.
Concrete Blocks AS4455 : 1997Concrete Masonry Units.
Wall Types
Design tables in this section are given for walls up to 3.4
metres high and for two base types:
Loading Conditions
These tables cover:
Sloping backfill (up to 1 in 4) without any surcharge
or
Level backfill with a 5kPa surcharge
Since typical cases only are presented, these tables may not
provide an ideal solution for a particular application.
ConstructionRecommendations
General
Recommendations specifically applicable to reinforced
masonry retaining walls include:
The provision of clean-out openings in the bottom course
to permit removal of mortar droppings and other debris
Boundary
Backfill
Ground level
Foundation
Base Type 1
Fig B1 Typical Wall Layout for Base Type 1
Boundary
Backfill
Ground level
Base Type 2
Foundation
Fig B2 Typical Wall Layout for Base Type 2
-
8/10/2019 Bor11999 Nsw Manual Bk1 Structural Fire Accustic
17/72
BOOK
PAGE
1
Structural Design
B11
and to allow vertical reinforcement to be positioned and
tied. These openings should be closed (generallydone with
formwork) before grouting.
The use of H blocks above the first course. These blocks
are easier to fill with grout which provides the required
continuous protection to the reinforcement. If rebated
flush-ended blocks are used in lieu of H blocks, they should
be laid with alternate courses inverted to provide grout
cover to horizontal reinforcement, which should be
supported 20mm clear of the webs of flush-ended blocks.
The forming ofweepholes byleaving out mortarin the vertical
joints at the required locations. Where H blocks are used,
and weepholes are required, theymaybe provided byplacing
25mm diameterPVC pipes through the vertical joint at the
required locations. Alternatively, flush-ended blocks maybe
placed on either side of the required weephole location so
a mortar-free joint may be formed.
The accurate positioning of reinforcement to give a
minimum of 55mm of cover to the face of the bar and its
secure tying before placing concrete or grout.
The removal of mortar dags protruding into cores before
grouting.
The use,wheneveravailable,ofready-mixed groutto workability
specifications given in AS3700 should be used. Site-mixed
grout, if used, should be mixed thoroughly in a tilting-drum
mixer to the same specification as ready-mixed grout.
The filling of all cores with grout, whether reinforced or
not. This is essential to bond and protect horizontal
reinforcement, to provide a full barrier against water
penetration and to give maximum weight for stability.
The thorough compaction of the grout so voids are not left.
Compaction may be achieved with a high-frequency pencil
vibrator, used carefully. (The main vertical reinforcing barsshould not be used to compact the grout). Control joints
should be built into the masonry at all points of potential
cracking.
Backfill Drainage
It is essential thatsteps be taken to preventthe backfill behind
the wall from becoming saturated. These steps should include:
Sealing Backfill Surface
To preventsaturation ofbackfill by surface run-off, the surface
of the backfill should be sealed by covering itwith a compactedlayer of low permeability material. The surface should be
sloped towards an open drain.
Continuous Drainage Within the Backfill
This can be achieved byplacing free-draining gravel orcrushed
stone to a width of approximately300mm immediatelybehind
the wall with a continuous agricultural pipe located at the
base of the wall. The outlets of the pipe must be beyond the
ends of the wall unless the pipe is connected to a proper
stormwater drainage system.
For higher walls, or in cases where excessive groundwater
exists, it may be necessary to provide another agricultural
pipe drain at mid-height of the wall.
Care mustbe taken to ensure that clay and silt do not infiltrate
the drainage material or agricultural pipe. The use of a
geofabric envelope around the gravel and/or a geofabric sock
over the pipe may assist.
Impermeablelayer slopingto drain
Drain
Backfill
Fig B3 Sealing Backfill Surface
Continuousagricultural pipedrain surroundedby free-draininggravel or crushedstone
Vertical layer ofgranular material
To prevent clay orsilt infiltrating thedrainage system ageofabric materialmay be wrappedaround the graveland/or the pipe
Fig B4 Continuous Drainage Within the BackfillWalls with Base Type 1
-
8/10/2019 Bor11999 Nsw Manual Bk1 Structural Fire Accustic
18/72
BOOK
PAGE
1
Structural Design
B12
Weepholes
Weepholes should be provided above the finished ground
level. A drain should be provided in front of the wall to
prevent saturation of the ground.
The horizontal spacing of the weepholes depends on the
provisions made for directing water towards the holes. The
simplest, but most effective, method is to place one or two
buckets of free-draining gravel or crushed stone around the
intake end of each hole. In this case, the horizontal spacing
should not exceed 1.5 metres. If the layers of draining
material are continuous for the full length of the wall,
weephole spacing may be increased to an extent depending
on the quantity of water expected.
Note: For walls higher than 2200mm, a second row of
weepholes may be required. However, staining of the wall
could result.
Locate thecontinuous drainat the bottom ofthe base
Free draininggranular material
Backfill
Fig B5 Continuous Drainage Within the BackfillWalls with Base Type 2
Extraagriculturalpipe drain
Fig B6 Continuous Drainage for High Wallsand/or Excessive Groundwater
Free-draininggravel or stone
Drain
Weepholesbetweenblocks
Fig B7 Continuous Drainage Within the BackfillWalls with Base Type 1
30mm
Clean-outcourse
50mm cover to allbase reinforcement
55mm cover towall reinforcement
Fig B8 Typical Set-out Detail
Water Penetration
If it is considered necessary to reduce the passage of
moisture through the wall, for aesthetic or other reasons
such as aggressive groundwater, the earth face of the wall
should be treated with an appropriate sealer such as water-
resistant render or water-resistant paint, or by tanking with
bituminous materials.
Structural Design Guidelines
Acceptable Soil Combinations
For retaining walls founded on sand (Type A soil), the
retained material must be similar and with a friction angle
of 38 or greater, eg Type A soil clean sand or gravel.
For retaining walls founded on other soils, the retained
material must be a free draining material with a friction
angle of 27 or greater, eg Type A soil clean sand or gravel,
Type B soil coarse grained with silt or some clay.
-
8/10/2019 Bor11999 Nsw Manual Bk1 Structural Fire Accustic
19/72
BOOK
PAGE
1
Structural Design
B13
190
400
230
B
B
250
550
330
300
600minlap
H = 1400to 2000
H = 2200to 3400
Heightof190mmblocks
Height of290mmblocks
450minlap
Longitudinalreinforcement:N12 inalternatecoursescommencingfrom topcourse. Omiton top ofclean-outblock
Longitudinal
reinforcement: N12 inalternate coursescommencing from topcourse. Omit on top ofclean-out block
Slopingbackfill orsurcharge
Sloping backfillor surchargeOptional
capping
Vertical reinforcement:N12 @400 cts
N12 @400cts
N16 @400N16 @400
V Bars
X Bars
V Bars
X Bars
K Bars
Optionalcapping
290
190
140
350
180
B
200
450minlap
H = 800to 1200
Longitudinal reinforcement:N12 in alternate coursescommencing from top course.Omit on top of clean-out block
Slopingbackfill orsurcharge
N12 @400cts
N12 @400
V Bars
X Bars
Optionalcapping
Fig B9 Construction Guidelines for Reinforced & Core Filled Retaining Walls with Base Type 1
Wall Height Reinforcement Base Dimensions
Total
Height Height of Blockwork X-Bars Width, B (mm) (mm) 150 200 300 and with following backfill conditions
H Series Series Series V-Bars K-Bars Level Max 1 in 4 Slope
800 800 N12 at 400 800 1000
1000 1000 N12 at 400 1000 1200
1200 1200 N12 at 400 1100 1500
1400 1400 N12 at 400 1300 1700
1600 1600 N16 at 400 1400 2000
1800 1800 N16 at 400 1600 2200
2000 2000 N16 at 200 1700 2500
2200 1400 800 N16 at 400 N16 at 400 1900 2800
2400 1600 800 N16 at 400 N16 at 400 2000 3100
2600 1600 1000 N20 at 400 N20 at 400 2200 3300
2800 1800 1000 N20 at 400 N20 at 400 2400 3600
3000 2000 1000 N16 at 200 N16 at 200 2600 3900
3200 2000 1200 N20 at 200 N16 at 200 2800 4200
3400 2000 1400 N20 at 200 N16 at 200 2900 4500
Table B3 Design Guidelines for Reinforced & Core Filled Retaining Walls with Base Type 1
-
8/10/2019 Bor11999 Nsw Manual Bk1 Structural Fire Accustic
20/72
BOOK
PAGE
1
Structural Design
B14
190
D
WB B
250250
290
D
W
300
190
600min.lap
H = 1400to 2000
H = 2200to 3400
Height of190mmblocks
Height of290mmblocks
600min.lap
Longitudinal reinforcement:N12@400
N16 in top course only
N16 in topcourse only
Optionalcapping
N12@400 cts
N12@400 cts
V Bars
SL72 Fabric
N16@400N16@400 N16@400
V Bars
K Bars
Optionalcapping
SL72 Fabric
140
D
WB
450min.lap
H = 800to 1200
[email protected] fromtop course. Omit ontop of clean-outcourse
Surcharge orsloping backfill(1 in 4 max.)
Surcharge orsloping backfill(1 in 4 max.)
Surcharge orsloping backfill(1 in 4 max.)
N12@400 cts
V Bars
SL72 Fabric
Optionalcapping
Longitudinal reinforcement2 x N12@400cts. Omit ontop of clean-out course
LongitudinalreinforcementN12@400 cts.Omit on top ofclean-out course
N12@400N12@400
Fig B10 Construction Guidelines for Reinforced & Core Filled Walls with Base Type 2
Table B4 Design Guidelines for Reinforced & Core Filled Walls with Base Type 2
Wall Height Reinforcement Base Dimensions
Max. 1 in 4
Total Level Backfill Sloping Backfill
Height Height of Blockwork Heel Width Base Width Heel Depth Base Width Heel Depth
(mm) 150 200 300 (mm) (mm) (mm) (mm) (mm)
H Series Series Series V-Bars K-Bars W B D B D 800 800 N12 at 400 450 600 500 800 500
1000 1000 N12 at 400 450 800 500 1000 500
1200 1200 N12 at 400 450 1000 500 1200 600
1400 1400 N16 at 400 450 1200 500 1400 600
1600 1600 N16 at 400 450 1400 600 1600 700
1800 1800 N16 at 400 450 1600 700 1800 800
2000 2000 N16 at 200 600 1800 700 2000 800
2200 1400 800 N16 at 400 N16 at 400 600 2000 800 2200 900
2400 1600 800 N16 at 400 N16 at 400 600 2200 900 2400 1000
2600 1600 1000 N20 at 400 N20 at 400 900 2400 900 2600 1000
2800 1800 1000 N20 at 400 N20 at 400 900 2600 900 2800 1100
3000 2000 1000 N16 at 200 N16 at 200 900 2800 1000 3000 1200
3200 2000 1200 N20 at 200 N16 at 200 900 3000 1100 3200 1300
3400 2000 1400 N20 at 200 N16 at 200 900 3200 1200 3400 1500
-
8/10/2019 Bor11999 Nsw Manual Bk1 Structural Fire Accustic
21/72
BOOK
PAGE
1
Structural Design
B15
200
55mmcover
1000
N16 @400 cts orN12 at 200 ctsN12 @400 cts
2700 max.
Floor slabreinforcement
Floor slab reinforcementN12 at 200 cts
Ag. drain
Verticalreinforcement:N16 @400 cts,central
Tanking to back face of walle.g. Bituminous coating
Series 200blocks
Horizontalreinforcement,N12 at 400 cts
Starter bar to matchwall reinforcementabove
One-course bond
beam with N12 bar
Note:Wall blocks andreinforcement asfor 'Typical Details'
200
Drained cavity
False wall
Ag. drain
190
20.20 knock-out blocksaw-cut at floor soffit level
Fig B11 Typical Details Fully Propped Wall
Fig B12 Alternative Details Fully Propped Wall
-
8/10/2019 Bor11999 Nsw Manual Bk1 Structural Fire Accustic
22/72
BOOK
PAGE
1
Structural Design
B16
300300
55mm cover
1500N16 at 200 ctsN12 at 400 cts
2700 max.
1200
Timber floor
Ag. drain
Vertical reinforcementN16 at 400 cts, central
65mm cover toback face
65mm coverto back face
Tanking toback faceof wall
Series 200blocks
Horizontal reinforcement,N12 at 400 cts
Note:Reinforcement asfor Typical Details
Drained cavity
False wall
Ag. drain
Series 300blocks
190
190
290
290
140
Timber floor
Pole plate fixedto bond beam
One-coursebond beam using20.20 knock-out blockwith 1xN12 bar
or N20 at 400 cts
Floor slabreinforcement
Naturalsoil
Naturalsoil
Clean-outcourse
Fig B13 Typical Details Unpropped or Partially Propped Wall
Fig B14 Alternative Details Unpropped or Partially Propped Wall
NOTE: Backfill must be completed prior to construction of timber floor.
-
8/10/2019 Bor11999 Nsw Manual Bk1 Structural Fire Accustic
23/72
BOOK
PAGE
1
Structural Design
B17
450 min.
Bars450 lap
'H' (2200 max.)
600 min.
Ag. drain 65mfall at 1:100 tooutlet
Free-draining gravel
Note:Footing size andreinforcement to suitsite conditions
Note:Retaining wall shall be propped prior tobackfilling and remain in place for aminimum of 7 days after placing floor slab
Verticalreinforcement:N12 at spacing 'S',centrally placed
Horizontalreinforcement,N12 at 400 cts
Knock-out blocksaw-cut at floorsoffit level
Starter bars,N12 @ spacing 'S',centrally placed
Use Double-U or H
blocks forsub-floor wallsection
Clean-out course
190
Floor slab reinforcementto suit site conditions
Vapour barrier andsand bedding under slab
Natural soil
450lap
N12 at same spacing as verticalreinforcement (spacing 'S')lapped 450 in wall and floor
N12 at same spacing asvertical reinforcement
Fig B15 Typical Details Subfloor Retaining Walls
Vertical Reinforcement Spacing
Height H(mm) Spacing S(mm)
1500 600
>1500 2200 400
-
8/10/2019 Bor11999 Nsw Manual Bk1 Structural Fire Accustic
24/72
BOOK
PAGE
1
Structural Design
B18
NOTES
-
8/10/2019 Bor11999 Nsw Manual Bk1 Structural Fire Accustic
25/72
1SECTIONC Fire DesignSTRUCTURAL, FIRE & ACOUSTICMasonry Design Guide
New South Wales
BOOK
1
-
8/10/2019 Bor11999 Nsw Manual Bk1 Structural Fire Accustic
26/72
BOOK
PAGE
1
Fire Design
C2
Masonry Design forFire Resistance
Fire Resistance Levels (FRL)
FRL come from the Building Code of Australias (BCA) tables
for Type A, B or C construction. The Type of construction
depends on the Class of building and the number of stories
or floors.
There are 3 figures in the Fire Resistance Level.
eg: FRL 60/120/120 meaning Structural Adequacy for 60
minutes / Integrity for120 minutes / Insulation for120 minutes.
Structural Adequacy
This governs the wall height, length, thickness and restraints.Masonry unit suppliers do not control the wall height, length
or restraints, therefore do not control Structural Adequacy.
However, information that is useful in the design of masonry
walls is the maximum Slenderness ratio (Srf). Boral Masonry
provides Srfinformation for all of its masonry units, and its
use is discussed in more detail later.
Integrity
This is the resistance to the passage of flame or gas. To
provide integrity, masonry walls must be structurally
adequate because cracks that form when it bows can allowflame through the wall. Since the masonryunit supplier does
not control Structural Adequacy, they cannotcontrol integrity
either.
Insulation
This is resistance to the passage of heat. Insulation is governed
by the type and thickness of the material used to produce the
masonry unit. This is controlled by the masonry unit
manufacturer. In relation to FRL, masonrymustalways provide
Insulation to an equal or better level than is required for
Integrity.
Masonry Design forStructural Adequacy FRL
Legend for the following formulae
Srf = the slenderness ratio in design for fire resistance for
structural adequacy. See table C2 on page C7 for
maximum Srf.
avf = 0.75 ifthe memberis laterallysupported along its top edge.
= 2.0 if the member is not laterally supported along its
top edge.
H = the clear height of a memberbetween horizontal lateral
supports; or
= for a memberwithouttop horizontal support,the overall
height from the bottom lateral support.
t = the overall thickness of the member cross-section
perpendicular to the principal axis underconsideration;
for members of cavity wall construction, the wall
thickness assessed is in accordance with AS3700
Clause 6.3.2.1(a) and (b).
ah = 1.0 if the member is laterally supported along both its
vertical edges.
= 2.5 if the member is laterally supported along onevertical edge.
L = The clear length of a wall between vertical lateral
supports; or
= for a wall without vertical support at one end or at a
control joint orforwalls containing openings, the length
to that unsupported end or control joint or edge of
opening.
NOTE: A control joint in a wall, or an edge to an opening in
a wall, shall be regarded as an unsupported edge to the wallunless specific measures are taken to provide adequate lateral
support at the edge.
Structural Adequacy may be overridden by design for
robustness; wind; live or earthquake loads.
A fire on one side of a wall will heat that side, making it
expand and lean towards the fire. When the lean or bow
reaches half the thickness of the original wall, the wall
becomes structurally inadequate. The formulae in AS3700,
Clause 6.3.2.2 limits masonry panel size, depending on its
restraints and thickness.
-
8/10/2019 Bor11999 Nsw Manual Bk1 Structural Fire Accustic
27/72
BOOK
PAGE
1
Fire Design
C3
The Slenderness ratio (Srf) of the proposed wall is calculated
as per Clause 6.3.2.2. If this value is less than the maximum
Srf in Table 6.1 [or the Srf calculated from Fire Tests and
Clause 6.3.3(b)(ii)], then the wall complies. If the Srfof the
wall is greater than the maximum permissible, it isrecalculated foran increased thickness and/orextra restraints.
There are 4 formulae for calculating Srf: 6.3.2.2 (1) and (2)
are the HEIGHT formulae.
FORMULA 1 and 2 is:
6.3.2.2 (3) is the PANEL ACTION formula.
FORMULA 3 is:
6.3.2.2 (4) is the LENGTH formula.
FORMULA 4 is:
The actual Srfis the lesser of the resulting figures.
Formula (1) and (2) always govern where there is no end
restraint, and often govern where walls are long, relative to
their height. Projects with multiple wall lengths (eg: home
units) can use this formula as a one size fits all method of
calculating the masonry thickness.
Formula (3) allows a wall to exceed the height given by formula
(1) and (2) provided at least one end is restrained as well as
the top.
Formula (4) governs the wall length, often where there is no
top restraint (eg: portal frame factories) and where walls are
short, relative to their height (eg: a lift well orvent shaft).
From a suppliers perspective,it is helpful to be able to calculate
the maximum height* for a given thickness (masonry unit),
eg:
and calculate the thickness from a given wall size.
where t is the OVERALL thickness, whether the units are
solid or hollow.
NOTE:* Refer to the Structural Adequacy Selection Graphs
on pages C9 to C20 for maximum height values.
t =avfx H
Srf
H =Srfx t
avf
Srf = ahL
t
Srf =0.7
t
Srf = avfH
t
Forcavitywalls, two thirds of the total thickness can be used
for t, provided that BOTH leaves are restrained in the same
positions (eg: external leaf stops at slab also). If the external
leaf is a veneerto the slab edge,the internal leaf must provide
the Structural Adequacy FRL on its own.
For reinforced masonry, the Srf of 36, from Table C2 on
page C7 may be used. Reinforcement can be horizontal, as
bond beams when spanning between columns. Reinforcement
can be vertical, as filled cores when spanning between slabs.
In either case, reinforcement can be spaced up to 2m apart,
depending on span. This reinforcement stiffens the masonry
and resists bowing. Reinforced walls with Srf< 36 have a 240
minute FRL for Structural Adequacy.
All calculations should be checked by an engineer. Other
loads may supersede Structural Adequacy requirements.
Masonry Design for
Integrity FRL
It is impractical to provide test results forall possible masonry
wall designs,and therefore Integrity mustbe proved in some
other way. With masonry wall design, the most practical way
to prove Integrity is to prove Structural Adequacy and
Insulationequal to orbetterthan the Integrityrequirement.
(Logically, if the wall is designed to minimise bowing it will
not crack and therefore resist the passage of flame and gas
for the specified time).
This method is also the best way to prove integrity even
when a wall may not be required to complywith a structural
adequacyFRLvalue,such as is the case with non loadbearing
walls. eg: if the BCA requires an FRL of -/90/90,the wall has
no actual structural adequacy requirement, but to prove
integrityof 90 minutes, the wall must be structurallyadequate
for 90 minutes.
avfH ah L
-
8/10/2019 Bor11999 Nsw Manual Bk1 Structural Fire Accustic
28/72
BOOK
PAGE
1
Fire Design
C4
Masonry Design forInsulation FRL
Insulation is the one FRL component that a masonry unit
manufacturer does control. It is governed by the type of
material and the material thickness.
Material thickness is defined in AS3700, Clause 6.5.2as the
overall thickness for solid and grouted units and units with
cores not more than 30% of the units overall volume.
For hollow units (cores > 30%), the material thickness is the
net volume divided by the face area.
For cavitywalls, t = the sum of material thicknesses in both
leaves, (not two thirds as for the Structural Adequacy FRL).
Options for Increasing FRLs
The Structural Adequacy FRL can be increased by adding
wall stiffeners, byincreasing the overall thickness, byadding
reinforcement orbyprotecting the wall with Boral Plasterboard
FireStop board, fixed to furring channels (on both sides of
the wall if a fire rating is required from both sides).
IntegrityFRLs are increased by increasing the other two FRL
values to the required Integrity FRL.
Insulation FRLs can be increased by core filling, by adding
another leaf of masonry, by rendering both sides of the wall
if the fire can come from either side. NOTE: Only ONE
thickness of render is added to the material thickness and
that must be on the cold side because the render on the
exposed face will drop off early in a fire).
Boral FireStopplasterboard on furring channels can increase
the Insulation FRL from either side. Unlike render, the Boral
FireStop and furring system does not drop off the hot side
so quickly due to the boards fire resistance, the mechanical
fixing of the board to furring and the furring to the wall.
Effect of Chases on Fire RatedMasonry
Structural Adequacy FRL
To assess the effect of chases on Structural Adequacy FRLs,
the direction in which the wall spans must be taken into
account.
Walls spanning vertically may be chased vertically. The
horizontal chase is limited to 4 times the wall thickness.
Walls spanning vertically and horizontally may be chased
horizontally up to half the wall length. Horizontal chases
should be kept to a bare minimum. Walls spanning vertically
and horizontally may be chased vertically up to half the wall
height.
If these limits are exceeded, the masonry design thickness
must be reduced by the depth of the recess or, in the case of
vertical chases, designed as 2 walls with unsupported ends
at the chase.
Integrity and Insulation FRLs
Maximum depth of recess is 30mm. Maximum area is
1,000mm2. Total maximum area on both sides of any5m2 of
wall is 100,000mm2
If these limits are exceeded, the masonry design thicknessmust be reduced by the depth of the recess.
Recesses for Services
Recesses that are less than half of the masonrythickness and
are less than 10,000mm2 for both sides within any 5m2 of
the masonry, do not have an effect on fire ratings.
If these limits are exceeded, the masonry design thickness
must be reduced by the depth of the recess.
-
8/10/2019 Bor11999 Nsw Manual Bk1 Structural Fire Accustic
29/72
BOOK
PAGE
1
Fire Design
C5
Step 1
Determine required wall FRL from the Building Code
of Australia (BCA).
The Building Code of Australia (BCA), Section C defines
the CLASS and TYPE of building and designates the
required Fire Resistant Level (FRL) in terms of threecriteria. See adjacent example.
NOTE: For masonry wall design, the FRL for any given wall
must comply with:
Structural Adequacy Integrity Insulation
Refer to the section Design for Integrity on page C3 for
additional explanation.
How to Select Boral Masonry Units for Fire Rated Walls
All design information, table data and graphs in this guide
are derived from formulae in AS3700 : 2001 Masonry
Structures, Part 6.3 for Structural Adequacy Fire ResistanceLevels (FRL) and Part 4.6 for Robustness.
Tables and graphs assume all walls are built on concrete
slabs or broad footings and have adequate restraints. Piers,
cavity walls, freestanding walls, earthquake, wind and otherloads are not addressed in this guide. All fire rated walls
should be designed by a suitably qualified engineer.
eg. If the BCA required FRL is: /120/60
Then the chosen wall design must have anactual FRL of: 120/120/120 or better.
Example
eg: 120/60/60
Insulation
IntegrityStructural Adequacy
Worked Example
A 6m high, 6m long fire rated, non-loadbearing wall in a
3 storey warehouse. BCA specifies Class 7, Type b
Construction.
BCA Section C1.1, Table 4 specifies an FRL 240/240/240.
-
8/10/2019 Bor11999 Nsw Manual Bk1 Structural Fire Accustic
30/72
BOOK
PAGE
1
Fire Design
C6
Material Attributes (New South Wales)
Scoria Blend High Fire Rated Block uc = 4MPa.
Offers excellentInsulation and Structural AdequacyFRLs forNON-
LOADBEARING fire rated walls. 10% lighter than Standard Greyunits. Scoria Blend is hard,durable and suitable forpaintorrender.
Acoustic performance with plasterboard linings is excellent. Acoustic
performance with render is medium range.
FireLight (FL) uc = 3MPa
Insulation FRL of 90 to 120 minutes. High slenderness ratio
(S rf) for Structural Adequacy FRL. Suitable for NON
LOADBEARING fire rated walls. Lightweight, 35% lighter than
Standard Grey units. Acoustic performance with plasterboard
linings is excellent.
Basal t (B) uc = 10MPa for blocks and 12MPa
for bricks
Offers excellentSrfvalues forStructural AdequacyFRL. Suitable
for LOADBEARING walls. Acoustic performance with
plasterboard is excellent. Acoustic performance with render
is excellent.
Designer Blockuc = 15MPa.
Blocks provide a 60 minute Insulation FRL. Suitable for
LOADBEARING applications.
Standard Grey Blockuc = 10MPa.
Suitable for LOADBEARING walls. 60 minute insulation FRL
as hollow blockwork.
Reinforced Grout Filled Masonryuc = 15MPa.
AS3700 allows an Srfvalue of 36 forreinforced masonry. This
in turn allows for the largestwalls to be built using the thinnest
masonry option. Suitable for LOADBEARING applications.Grout strength to be 20MPa. 240 minute insulation FRL as
fully grout filled blockwork.
Step 2
Select an appropriate Boral Masonry Unit based on
the FRL Insulation Requirement.
The third figure in an FRL rating is the Insulation.
Table C1 provides the Insulation values for the various
Boral units.
Check the Materials Attributes (see notes below the table)
to ensure the selection is fit for its purpose.
Worked Example
From Table C1, the following units all achieve 240 minutes
FRL for Insulation:
Scoria Blend 15.401, 20.401, and 11.119F
Calcium Silicate Basalt 165S119B
Grouted Masonry (190mm) 20.42and 20.91.
If the wall is non loadbearing, the use of Scoria Blend may
be the more cost effective.
Table C1 FRL Insulation Values for Boral Masonry Units (New South Wales)
Fire INSULATION FRL (minutes)
Test 30 60 90 120 180 240 Material Product Code/TypeYes FireBlock/FireBrick (F) Scoria Blend 10.201; 15.201; 20.201; 9.162F
Yes FireBlock/FireBrick (F) Scoria Blend 10.331; 15.301; 20.301
Yes FireBlock/FireBrick (F) Scoria Blend 15.401; 20.401; 11.119F
Yes FireLight (FL) 10.01FL; 15.01 FL: 20.01FL; 9.162FL
Yes FireLight (FL) 10.119FL; 11.162FL
d.t.s. Basalt-Concrete (B) 15.01B
d.t.s. +render Basalt-Concrete (B) 10.01B; 10.31B; 20.01B; 9.162B
d.t.s. Basalt-Concrete (B) 10.119B
d.t.s. +render Basalt-Concrete (B) 11.119B + other 110mm cored
d.t.s. Calcium Silicate Basalt M3H119B; + other 90mm
d.t.s. Calcium Silicate Basalt S3H119B; + other 110mm
d.t.s. Calcium Silicate Basalt 140S119B; + other 140mm
d.t.s. Calcium Silicate Basalt 165S119B
d.t.s. DesignerBlockand Standard GreyConcrete 15.01.
d.t.s. +render DesignerBlockand Standard GreyConcrete 10.01; 10.31; 20.01
d.t.s. +render Grouted Masonry 140mm 15.42; 15.91
d.t.s. Grouted Masonry 190mm 20.42; 20.91
d.t.s. deemed to satisfy. +render = 10mm render both faces
* Product Codes listed are for the Full Size Unit. Fractional size blocks in the same range have the same FRL rating.
-
8/10/2019 Bor11999 Nsw Manual Bk1 Structural Fire Accustic
31/72
BOOK
PAGE
1
Fire Design
C7
Step 3
Check the Structural Adequacy of the selected units.
The Slenderness ratio (Srf) of a fire rated wall is calculated
as per AS3700 : 2001, Clause 6.3.2.2, and must not exceedthe Srfvalues given in AS3700 or calculated from Fire Tests.
Table C2provides the maximum Srfvalues forBoral masonry
units.
Worked Example
The calculated Srfvalue for your wall design MUST NOT
EXCEED the value from the accompanying table.
See following page for an explanation on using the BoralSrf graphs to assist preliminary selection.
eg. Scoria Blend required to provide Structural Adequacy
for 240 minutes has an Srf= 24. (refer to Table C2 below).
Also refer to the previous explanation and AS3700 for Srf
calculation methods.
In this example, the 6 x 6m wall,with lateral restraint on 4
sides, 190mm thick has an Srf = 19.2. as per formula
6.3.2.2 (3).
Alternative is 20.91 with reinforcement and core filling,
however,as the wall in this example is non-loadbearing, the
Scoria Blend 20.401 is the more economical solution.
SrfValues
Fire FRL (minutes) for Structural AdequacyTest 30 60 90 120 180 240 Material Condition of use
Yes 25.9 25.9 25.9 25.9 25.9 24 Scoria Blend (F) FireBrick/FireBlock Non loadbearing ONLY
Yes 20.4 20.4 20.4 20.4 20.4 20.4 Custom Scoria Blend (S) Loadbg 110mm made to order
Yes 29 29 26.9 24.9 22.2 20.3 FireLight (FL) Non loadbearing ONLY
d.t.s. 25 22.5 21 20 18 17 Basalt-Concrete (B) Any
d.t.s. 25 22.5 21 20 18 17 Calcium Silicate-Basalt Any
d.t.s. 19.5 18 17 16 15.5 15 Standard Grey and Designer Block Any
d.t.s. 36 36 36 36 36 36 Reinforced & Grouted Masonry Any
d.t.s.= deemed to satisfy, as per AS3700 : 2001,Table 6.1.
Table C2 Maximum Srf Values for Boral Masonry Units
-
8/10/2019 Bor11999 Nsw Manual Bk1 Structural Fire Accustic
32/72
BOOK
PAGE
1
Fire Design
C8
IMPORTANT
The following selection graphs are based on Specific
Products manufactured at New South Wales BoralPlants. Should these units be sourced from other plants,
the specification should be checked with the respective
supply plant.
To assist with the preliminary selection of Boral masonry
units for fire rated walls, a graphical selection method based
on Srfvalues has been developed.
The following pages provide graphs and tables fora selection
of Boral masonry units where at least one end of the wall has
lateral restraint.
Additional tables are provided forwalls with no end restraint
and for reinforced/grout filled masonry,following these graphs.
Boral Structural Adequacy Selection Graphs & Tables
SUPPORT
SUPPORT
SUPPORT
SUPPORT
9
8
7
6
5
4
3
2
1
0
0 1 2 3 4 5 6 7 8 9
Structural Adequacy240 minutes FRL
Laterally supported
both ends and top
Length of wall between supports (m)
Heightofwallbetweensu
pports(m)
140mm
190mm
110mm
90mm
LeafThickness
Worked Example
1. Select the appropriate masonry unit material.
2. Select the appropriate page with Structural
Adequacyforthe required minutes. (240 minutes
for this example).
3. Select the appropriate graph for the chosen wall
restraint (support) criteria. (Support on both sides,
top and bottom for this example).
4. Plot the intersection of the Wall Height and the
Wall Length on the graph. (For this example 6m
height x 6m length).
5. The result MUST FALL BELOW the coloured line
indicated for the chosen masonry unit thickness.
In this example, the result is above the line for
140mm units butbelow the line for190mm units.
Therefore 190mm units would be suitable. (140mm
units would not be suitable for this example).
Scoria-Blend
How to Use the Boral Structural Adequacy FRL Graphs
Product Group FRL Minutes (Structural Adequacy) Page
NSW Firebrick/Fireblock Scoria Blend Masonry (F) 60 180 C9
NSW Firebrick/Fireblock Scoria Blend Masonry (F) 240 C10
FireLight Brick (FL) 90 C11
FireLight Brick (FL) 120 C12
Basalt Concrete Masonry (B) 60 C13
Basalt Concrete Masonry (B) 90 C14
Calcium Silicate Basalt Masonry 60 C15
Calcium Silicate Basalt Masonry 90 C16
Calcium Silicate Basalt Masonry 120 C17
Calcium Silicate Basalt Masonry 180 C18
Standard Grey and Designer Block 60 C19
Standard Grey and Designer Block 90 C20
Walls Restrained at Top (Unrestrained Ends) 60 240 C21
Reinforced Masonry Walls 60 240 C22
Index to Structural Adequacy FRL Graphs & Tables
-
8/10/2019 Bor11999 Nsw Manual Bk1 Structural Fire Accustic
33/72
BOOK
PAGE
1
Fire Design
C9
SUPPORT
SUPPORT
SUPPORT
9
8
7
6
5
4
3
2
1
0
0 1 2 3 4 5 6 7 8 9
Structural Adequacy
60 180 minutes FRL
Laterally supported
one end and top
Length of wall between supports (m)
Heightofwallbetweensupports(m)
140mm
190mm
110mm
90mm
LeafThickness
100mm
SUPPORTSUPPORT
9
8
7
6
5
4
3
2
1
0
0 1 2 3 4 5 6 7 8 9
Structural Adequacy
60 180 minutes FRL
Laterally supported
one end top free
Length of wall between supports (m)
Heightofwallbetweensupports(m
)
140mm190mm
110mm90/100mm
LeafThickness
SUPPORT
SUPPORT
SUPPORT
SUPPORT
9
8
7
6
5
4
3
2
1
0
0 1 2 3 4 5 6 7 8 9
Structural Adequacy
60 180 minutes FRL
Laterally supported
both ends and top
Length of wall between supports (m)
Heightofwallbetweensupp
orts(m)
140mm
190mm
110mm100mm90mm
LeafThickness
SUPPORTSUPPORT
SUPPORT
9
8
7
6
5
4
3
2
1
0
0 1 2 3 4 5 6 7 8 9
Structural Adequacy
60 180 minutes FRL
Laterally supported
both ends, top free
Length of wall between supports (m)
Heightofwallbetweensupports(m)
140mm
190mm
110mm100mm90mm
LeafThickness
NSW FireBrick/FireBlock Scoria Blend Masonry (F) - Srf = 25.9
Structural Adequacy for 60-180 minutes Fire Resistant Level (FRL)
-
8/10/2019 Bor11999 Nsw Manual Bk1 Structural Fire Accustic
34/72
BOOK
PAGE
1
Fire Design
C10
SUPPORT
SUPPORT
SUPPORT
SUPPORT
9
8
7
6
5
4
3
2
1
0
0 1 2 3 4 5 6 7 8 9
Structural Adequacy
240 minutes FRL
Laterally supported
both ends and top
Length of wall between supports (m)
Heightofwallbetweensupp
orts(m)
140mm
190mm
110mm
90mm
LeafThickness
100mm
SUPPORTSUPPORT
SUPPORT
9
8
7
6
5
4
3
2
1
0
0 1 2 3 4 5 6 7 8 9
Structural Adequacy
240 minutes FRL
Laterally supported
both ends, top free
Length of wall between supports (m)
Heightofwallbetweensupports(m)
140mm
190mm
110mm
90mm
LeafThickness
100mm
SUPPORT
SUPPORT
SUPPORT
9
8
7
6
5
4
3
2
1
0
0 1 2 3 4 5 6 7 8 9
Structural Adequacy
240 minutes FRL
Laterally supported
one end and top
Length of wall between supports (m)
Heightofwallbetweensupports(m)
140mm
190mm
110mm
90mm
LeafThickness
100mm
SUPPORTSUPPORT
9
8
7
6
5
4
3
2
1
0
0 1 2 3 4 5 6 7 8 9
Structural Adequacy
240 minutes FRL
Laterally supported
one end top free
Length of wall between supports (m)
Heightofwallbetweensupports(m
)
140mm190mm
110mm90/100mm
LeafThickness
NSW FireBrick/FireBlock Scoria Blend Masonry (F) - Srf = 24
Structural Adequacy for 240 minutes Fire Resistant Level (FRL)
-
8/10/2019 Bor11999 Nsw Manual Bk1 Structural Fire Accustic
35/72
BOOK
PAGE
1
Fire Design
C11
SUPPORT
SUPPORT
SUPPORT
SUPPORT
9
8
7
6
5
4
3
2
1
0
0 1 2 3 4 5 6 7 8 9
Structural Adequacy
90 minutes FRL
Laterally supported
both ends and top
Length of wall between supports (m)
Heightofwallbetweensuppo
rts(m)
140mm
190mm
110mm
90mm100mm
LeafThickness
SUPPORTSUPPORT
SUPPORT
9
8
7
6
5
4
3
2
1
0
0 1 2 3 4 5 6 7 8 9
Structural Adequacy
90 minutes FRL
Laterally supported
both ends, top free
Length of wall between supports (m)
Heightofwallbetweensuppo
rts(m)
140mm
190mm
110mm
90mm100mm
LeafThickness
SUPPORT
SUPPORT
SUPPORT
9
8
7
6
5
4
3
2
1
0
0 1 2 3 4 5 6 7 8 9
Structural Adequacy
90 minutes FRL
Laterally supported
one end and top
Length of wall between supports (m)
Heightofwallbetweensupports(m
)
140mm
190mm
110mm100mm90mm
LeafThickness
SUPPORTSUPPORT
9
8
7
6
5
4
3
2
1
0
0 1 2 3 4 5 6 7 8 9
Structural Adequacy
90 minutes FRL
Laterally supported
one end, top free
Length of wall between supports (m)
Heightofwallbetweensupports(m
)
140mm190mm
110mm90/100mm
LeafThickness
FireLight Bricks (FL) - Srf = 26.9
Structural Adequacy for 90 minutes Fire Resistant Level (FRL)
-
8/10/2019 Bor11999 Nsw Manual Bk1 Structural Fire Accustic
36/72
BOOK
PAGE
1
Fire Design
C12
FireLight Bricks (FL) - Srf = 24.9
Structural Adequacy for 120 minutes Fire Resistant Level (FRL)
SUPPORT
SUPPORT
SUPPORT
SUPPORT
9
8
7
6
5
4
3
2
1
0
0 1 2 3 4 5 6 7 8 9
Structural Adequacy
120 minutes FRL
Laterally supported
both ends and top
Length of wall between supports (m)
Heightofwallbetweensupports(m)
140mm
190mm
110mm
100mm90mm
LeafThickness
SUPPORTSUPPORT
SUPPORT
9
8
7
6
5
4
3
2
1
0
0 1 2 3 4 5 6 7 8 9
Structural Adequacy
120 minutes FRL
Laterally supported
both ends, top free
Length of wall between supports (m)
Heightofwallbetweensuppo
rts(m)
140mm
190mm
110mm100mm90mm
LeafThickness
SUPPORT
SUPPORT
SUPPORT
9
8
7
6
5
4
3
2
1
0
0 1 2 3 4 5 6 7 8 9
Structural Adequacy
120 minutes FRL
Laterally supported
one end and top
Length of wall between supports (m)
Heightofwallbetweensupports(m
)
140mm
190mm
110mm100mm90mm
LeafThickness
SUPPORTSUPPORT
9
8
7
6
5
4
3
2
1
0
0 1 2 3 4 5 6 7 8 9
Structural Adequacy
120 minutes FRL
Laterally supported
one end top free
Length of wall between supports (m)
Heightofwallbetweensupports(m
)
140mm190mm
110mm90/100mm
LeafThickness
-
8/10/2019 Bor11999 Nsw Manual Bk1 Structural Fire Accustic
37/72
BOOK
PAGE
1
Fire Design
C13
Basalt-Concrete Masonry (B) Srf = 22.5
Structural Adequacy for 60 minutes Fire Resistant Level (FRL)
SUPPORT
SUPPORT
SUPPORT
SUPPORT
9
8
7
6
5
4
3
2
1
0
0 1 2 3 4 5 6 7 8 9
Structural Adequacy60 minutes FRL
Laterally supported
both ends and top
Length of wall between supports (m)
Heightofwallbetweensuppo
rts(m)
140mm
190mm
110mm100mm90mm
LeafThickness
SUPPORTSUPPORT
SUPPORT
9
8
7
6
5
4
3
2
1
0
0 1 2 3 4 5 6 7 8 9
Structural Adequacy
60 minutes FRL
Laterally supported
both ends, top free
Length of wall between supports (m)
Heightofwallbetweensuppo
rts(m)
140mm
190mm
110mm90mm
LeafThickness
SUPPORT
SUPPORT
SUPPORT
9
8
7
6
5
4
3
2
1
0
0 1 2 3 4 5 6 7 8 9
Structural Adequacy60 minutes FRL
Laterally supported
one end and top
Length of wall between supports (m)
Heightofwallbetweensupports(m)
140mm
190mm
110mm100mm90mm
LeafThickness
SUPPORTSUPPORT
9
8
7
6
5
4
3
2
1
0
0 1 2 3 4 5 6 7 8 9
Structural Adequacy
60 minutes FRL
Laterally supported
one end, top free
Length of wall between supports (m)
Heightofwallbetweensupports(m)
140mm190mm
110mm90mm
LeafThickness
-
8/10/2019 Bor11999 Nsw Manual Bk1 Structural Fire Accustic
38/72
BOOK
PAGE
1
Fire Design
C14
Basalt-Concrete Masonry (B) - Srf = 21
Structural Adequacy for 90 minutes Fire Resistant Level (FRL)
SUPPORT
SUPPORT
SUPPORT
SUPPORT
9
8
7
6
5
4
3
2
1
0
0 1 2 3 4 5 6 7 8 9
Structural Adequacy
90 minutes FRL
Laterally supported
both ends and top
Length of wall between supports (m)
Heightofwallbetweensuppo
rts(m)
140mm
190mm
110mm100mm90mm
LeafThickness
SUPPORTSUPPORT
SUPPORT
9
8
7
6
5
4
3
2
1
0
0 1 2 3 4 5 6 7 8 9
Structural Adequacy
90 minutes FRL
Laterally supported
both ends, top free
Length of wall between supports (m)
Heightofwallbetweensuppo
rts(m)
140mm
190mm
110mm90mm
LeafThickness
SUPPORT
SUPPORT
SUPPORT
9
8
7
6
5
4
3
2
1
0
0 1 2 3 4 5 6 7 8 9
Structural Adequacy90 minutes FRL
Laterally supported
one end and top
Length of wall between supports (m)
Heightofwallbetweensupports(m)
140mm
190mm
110mm100mm90mm
LeafThickness
SUPPORTSUPPORT
9
8
7
6
5
4
3
2
1
0
0 1 2 3 4 5 6 7 8 9
Structural Adequacy
90 minutes FRL
Laterally supported
one end, top free
Length of wall between supports (m)
Heightofwallbetweensupports(m)
140mm190mm
110mm90mm
LeafThickness
-
8/10/2019 Bor11999 Nsw Manual Bk1 Structural Fire Accustic
39/72
BOOK
PAGE
1
Fire Design
C15
SUPPORT
SUPPORT
SUPPORT
SUPPORT
9
8
7
6
5
4
3
2
1
0
0 1 2 3 4 5 6 7 8 9
Structural Adequacy
60 minutes FRL
Laterally supported
both ends and top
Length of wall between supports (m)
Heightofwallbetweensupp
orts(m)
140mm
110mm
90mm
LeafThickness
SUPPORTSUPPORT
SUPPORT
9
8
7
6
5
4
3
2
1
0
0 1 2 3 4 5 6 7 8 9
Structural Adequacy
60 minutes FRL
Laterally supported
both ends, top free
Length of wall between supports (m)
Heightofwallbetweensupports(m)
140mm110mm90mm
LeafThickness
SUPPORT
SUPPORT
SUPPORT
9
8
7
6
5
4
3
2
1
0
0 1 2 3 4 5 6 7 8 9
Structural Adequacy
60 minutes FRL
Laterally supported
one end and top
Length of wall between supports (m)
Heightofwallbetweensupports(m)
140mm
110mm
90mm
LeafThickness
SUPPORTSUPPORT
9
8
7
6
5
4
3
2
1
0
0 1 2 3 4 5 6 7 8 9
Structural Adequacy
60 minutes FRL
Laterally supported
one end, top free
Length of wall between supports (m)
Heightofwallbetweensupports(m
)
140mm110mm90mm
LeafThickness
Calcium Silicate-Basalt Masonry (Boral Calsil) - Srf = 22.5
Structural Adequacy for 60 minutes Fire Resistant Level (FRL)
-
8/10/2019 Bor11999 Nsw Manual Bk1 Structural Fire Accustic
40/72
BOOK
PAGE
1
Fire Design
C16
SUPPORT
SUPPORT
SUPPORT
SUPPORT
9
8
7
6
5
4
3
2
1
0
0 1 2 3 4 5 6 7 8 9
Structural Adequacy
90 minutes FRL
Laterally supported
both ends and top
Length of wall between supports (m)
Heightofwallbetweensupp
orts(m)
140mm
110mm
90mm
LeafThickness
SUPPORTSUPPORT
SUPPORT
9
8
7
6
5
4
3
2
1
0
0 1 2 3 4 5 6 7 8 9
Structural Adequacy
90 minutes FRL
Laterally supported
both ends, top free
Length of wall between supports (m)
Heightofwallbetweensupports(m)
140mm110mm90mm
LeafThickness
SUPPORT
SUPPORT
SUPPORT
9
8
7
6
5
4
3
2
1
0
0 1 2 3 4 5 6 7 8 9
Structural Adequacy
90 minutes FRL
Laterally supported
one end and top
Length of wall between supports (m)
Heightofwallbetweensupports(m)
140mm
110mm
90mm
LeafThickness
SUPPORTSUPPORT
9
8
7
6
5
4
3
2
1
0
0 1 2 3 4 5 6 7 8 9
Structural Adequacy
90 minutes FRL
Laterally supported
one end, top free
Length of wall between supports (m)
Heightofwallbetweensupports(m
)
140mm110mm90mm
LeafThickness
Calcium Silicate-Basalt Masonry (Boral Calsil) - Srf = 21
Structural Adequacy for 90 minutes Fire Resistant Level (FRL)
-
8/10/2019 Bor11999 Nsw Manual Bk1 Structural Fire Accustic
41/72
BOOK
PAGE
1
Fire Design
C17
SUPPORT
SUPPORT
SUPPORT
SUPPORT
9
8
7
6
5
4
3
2
1
0
0 1 2 3 4 5 6 7 8 9
Structural Adequacy
120 minutes FRL
Laterally supported
both ends and top
Length of wall between supports (m)
Heightofwallbetweensupp
orts(m)
140mm
110mm
LeafThickness
SUPPORTSUPPORT
SUPPORT
9
8
7
6
5
4
3
2
1
0
0 1 2 3 4 5 6 7 8 9
Structural Adequacy
120 minutes FRL
Laterally supported
both ends, top free
Length of wall between supports (m)
Heightofwallbetweensupports(m)
140mm110mm
LeafThickness
SUPPORT
SUPPORT
SUPPORT
9
8
7
6
5
4
3
2
1
0
0 1 2 3 4 5 6 7 8 9
Structural Adequacy
120 minutes FRL
Laterally supported
one end and top
Length of wall between supports (m)
Heightofwallbetweensupports(m)
140mm
110mm
LeafThickness
SUPPORTSUPPORT
9
8
7
6
5
4
3
2
1
0
0 1 2 3 4 5 6 7 8 9
Structural Adequacy
120 minutes FRL
Laterally supported
one end, top free
Length of wall between supports (m)
Heightofwallbetweensupports(m
)
140mm110mm
LeafThickness
Calcium Silicate-Basalt Masonry (Boral Calsil) - Srf = 20
Structural Adequacy for 120 minutes Fire Resistant Level (FRL)
-
8/10/2019 Bor11999 Nsw Manual Bk1 Structural Fire Accustic
42/72
BOOK
PAGE
1
Fire Design
C18
SUPPORT
S