bor11999 nsw manual bk1 structural fire accustic

Upload: emanuel-ifrim

Post on 02-Jun-2018

226 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/10/2019 Bor11999 Nsw Manual Bk1 Structural Fire Accustic

    1/72

    1BOOK1 Structural, Fire and AcousticMasonry Design Guide

    New South Wales

    Updated May 2008

  • 8/10/2019 Bor11999 Nsw Manual Bk1 Structural Fire Accustic

    2/72

    BOOK

    PAGE

    1

    Introduction

    A2BOOK

    PAGE

    1

    Contents

    A2

    The information presented herein is supplied in good faith and to the best of our knowledge was accurate at the time of preparation. No responsibility can be accepted by

    Boral or its staff for any errors or omissions. Users are advised to make their own determination as to the suitability of this information in relation to their particular purpose

    and specific circumstances. Since the information contained in this document may be applied under conditions beyond our control, no responsibility can be accepted by us

    for any loss or damage caused by any person acting or refraining from action as a result of this information.

    C Fire DesignMasonry Design for Fire Resistance (FRL) . . . . . . . . . . . . . . C2

    Masonry Design for Structural Adequacy FRL . . . . . . . . . . . C2

    Masonry Design for Integrity FRL . . . . . . . . . . . . . . . . . . . . . C3

    Masonry Design for Insulation FRL . . . . . . . . . . . . . . . . . . . . C4

    Effect of Chases on Fire Rated Masonry . . . . . . . . . . . . . . . C4

    How to Select Boral Masonry Units forFire Rated Walls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C5

    Structural Adequacy Selection Graphs and Tables . . . . . . . . C8

    Index to Structural Adequacy Selection Graphs . . . . . . . . . . C8

    D Acoustic DesignAcoustic Performance Ratings (STC and Rw) . . . . . . . . . . . . D2

    Designing Masonry Walls forAcoustic Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . D3

    Guidelines for Optimum Performance . . . . . . . . . . . . . . . . . D4

    Acoustic Performance On-site . . . . . . . . . . . . . . . . . . . . . . . D5

    Home Cinema Rooms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . D6

    E Fire and Acoustic SystemsFinding Acoustic Systems andTechnical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . E2

    FireBrick (F) Scoria Blend . . . . . . . . . . . . . . . . . . . . . . . . . . . E4

    FireBlock - Scoria Blend Blocks . . . . . . . . . . . . . . . . . . . . . . E7

    FireLight Bricks (FL) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . E9

    Basalt-Concrete Bricks (B) . . . . . . . . . . . . . . . . . . . . . . . . . E12

    Standard Grey Block and Designer Block . . . . . . . . . . . . . . E16

    Acousticell . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . E18

    B Structural DesignIntroduction to the Structural Design of Masonry . . . . . . . . B2

    Robustness . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B2

    Strength . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B5

    Bending . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B5

    Shear . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B6

    Durability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B6

    Movement (Control Joints) . . . . . . . . . . . . . . . . . . . . . . . . . . B6

    Energy Efficiency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B7

    Reinforced Masonry Lintels . . . . . . . . . . . . . . . . . . . . . . . . . B9

    Design of Core Filled and Steel ReinforcedMasonry Retaining Walls . . . . . . . . . . . . . . . . . . . . . . . . . . B10

    Structural Design Guidelines forCore Filled and Steel ReinforcedMasonry Retaining Walls . . . . . . . . . . . . . . . . . . . . . . . . . . B12

    A IntroductionContents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A2

    Fast Find Product and Application Guide . . . . . . . . . . . . . . . A3

    Products @ a Glance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A4

    About This Guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A6

    PAGE

    PAGE

  • 8/10/2019 Bor11999 Nsw Manual Bk1 Structural Fire Accustic

    3/72

    BOOK

    PAGE

    1

    Introduction

    A3BOOK

    PAGE

    1

    Fast Find Guide

    A3

    The quickest way to find a Boral Masonry Structural, Fire or Acoustic Wall Solution.

    Simply follow the FAST FIND GUIDE on the right hand side of the table.

    1

    BORALMASONRY

    BLOCK &

    BRICK

    PRODUCTSW

    ALLF

    INISH

    2

    Select your application

    criteria from the top ofthe table

    Go straight to the section

    letter and page number

    indicated at the

    intersection of product

    rows and application

    columns (e.g. Section E,

    Page E12 in this example)

    Please refer to MDG Book 2, BoralMasonry Block & Brick Guide

    Best performance is achievedwith plasterboard lining

    NLB LB NLB LB NLB LB NLB LB NLB LBNLB = Non-loadbearing

    LB = Loadbearing

    Face

    Mason

    ry

    Retaini

    ngWall

    Fast Find

    a Boral

    Solution

    Rend

    ered

    Plaste

    rboa

    rd

    NoLinin

    g

    E4 E4 E4 FireBrick (F) Scoria Blend

    E19 E19 E19 E19Designer Block

    E12 E12 E12 E12 E12 E12 Basalt-Concrete (B)

    E9

    E9 E9 FireLight Bricks (FL)

    E7 E7 E7 Scoria Blend Blocks

    E21 E21 Acousticell

    E19 E19 E19 E19 E19 E19 Standard Grey Block

    E19 E19 E19 E19E19 E19 E19 E19 E19 E19Core Filled Block

    For technical support and sales office details please refer to the outside back cover

  • 8/10/2019 Bor11999 Nsw Manual Bk1 Structural Fire Accustic

    4/72

    BOOK

    PAGE

    1

    Products @ a Glance

    A4

    Boral Engineered Blocksfor Structural, Fire & Acoustic Wall Systems

    Standard Grey and Designer BlockHollow Concrete Block suitable for loadbearing

    and non-loadbearing applications. 60 minute

    insulation FRL as hollow blockwork. Higher FRLs

    are achieved when reinforced and core-filled.

    Scoria Blend High Fire Rated BlockManufactured in a unique Scoria Blend material

    offering Fire Resistance Levels (FRLs) to 240

    minutes without core-filling. Ideal for high rise

    buildings with reinforced concrete frames or

    portal frame buildings. Suitable for non-

    loadbearing walls. If used for l ight load

    construction, the lower slenderness ratios of

    Designer Block apply.

    Core Fill BlockGrey Concrete Block or Designer Block coloured

    and textured finishes for reinforced retaining

    walls and loadbearing walls requiring increased

    robustness.

    Acousticell

    Engineered block for premium sound absorption

    and attenuation of low frequency industrial and

    commercial noise.

  • 8/10/2019 Bor11999 Nsw Manual Bk1 Structural Fire Accustic

    5/72

    BOOK

    PAGE

    1

    Introduction

    A5BOOK

    PAGE

    1

    Products @ a Glance

    A5

    Boral Engineered Bricksfor Structural, Fire and Acoustic Wall Systems

    FireLight Brick (FL) FireLight Brick for non-loadbearing fire and/or

    acoustic systems (high rise) where weight

    saving is important. Double Brick format

    (162mm height) for faster, more cost effective

    construction.

    FireBrick (F) Medium weight Scoria Brick for non-loadbearing

    fire and/or acoustic systems. Double Brick

    format (162mm height) for faster, more cost

    effective construction.

    Basalt-Concrete Brick (B) Standard Size, Brick-and-a-Half (119mm high) and Double

    (162mm high) in Concrete-Basalt material for good fire

    performance and loadbearing characteristics.

  • 8/10/2019 Bor11999 Nsw Manual Bk1 Structural Fire Accustic

    6/72

    BOOK

    PAGE

    1

    About This Guide

    A6

    Boral Masonry

    Commercial Construction Solutions

    Boral Masonry NSW offers a comprehensive range of proven

    products and systems including Masonry Blocks, MasonryBricks, Fire and Acoustic Wall Systems, Segmental Block

    Retaining Walls and Segmental Paving Products.

    Whats in this Guide

    The Boral Masonry Structural, Fire & Acoustic guide

    provides a summary of important design information for

    structural, fire and acoustic masonry applications and an

    extensive range of fire and acoustic systems.

    Section B Structural Design

    Section B discusses design issues relevant to the selectionof Boral Masonry products for structural adequacy, based on

    appropriate wall design criteria.

    Section C Fire Design

    Section C discusses the relevant design processes for the

    selection of Boral Masonry Products forfire rated applications.

    This section includes a step-by-step selection guide and a

    series of tables and graphs which can greatly speed up the

    preliminary selection and comparison of suitable designs

    and products.

    Section D Acoustic Design

    Section D provides a briefoverview of acoustic rating methods,

    relevant considerations for acoustic design and guidelines

    for good acoustic design and detailing methods.

    Section E Fire & Acoustic Systems

    Section E of this guide provides an extensive range of fire

    and acoustic wall system solutions supported by test results

    and acoustic performance estimates.

    This guide has been prepared as a comprehensive Boral

    Product Reference Guide. It does not attempt to cover all the

    requirements of the Codes and Standards which apply to

    masonry construction for structural, fire or acoustic

    applications. All structural, fire and acoustic detailing shouldbe checked and approved by appropriatelyqualified engineers

    before construction. Boral reserves the right to change the

    contents of this guide without notice.

    Please note that this guide is based on products available at

    the time of publication from the Boral Masonry New South

    Wales sales region. Different products and specifications may

    apply to Boral products sourced from other regions.

    Additional Assistance & Information

    Contact Details: Please refer to the outside back cover ofthis publication for Boral Masonry contact details.

    Colour and Texture Variation: The supply of raw

    materials can vary over time. In addition, variation can

    occurbetween product types and production batches. Also

    please recognise the printed colours in this brochure are

    only a guide. Please, always ask to see a sample of your

    colour/texture choice before specifying or ordering.

    Terms and Conditions of Sale: For a full set of Terms

    and Conditions of Sale please contact your nearest Boral

    Masonry sales office.

  • 8/10/2019 Bor11999 Nsw Manual Bk1 Structural Fire Accustic

    7/72

    1SECTIONB Structural DesignSTRUCTURAL, FIRE & ACOUSTICMasonry Design Guide

    New South Wales

    BOOK

    1

  • 8/10/2019 Bor11999 Nsw Manual Bk1 Structural Fire Accustic

    8/72

    BOOK

    PAGE

    1

    Structural Design

    B2

    Introduction to the StructuralDesign of Masonry

    The following design information is based on Australian

    Standard AS3700:2001 Masonry structures. Reference to

    Clauses and Formulae are those used in AS3700. This

    information is provided as a guide only to the processes

    involved in designing masonry. All masonry should be

    designed by a suitably qualified structural engineer.

    Robustness

    AS3700, Clause 4.6.1 requires walls to have an adequate

    degree of Robustness. Robustness is a minimum design

    requirement, and may be overridden by Fire, Wind, Snow,Earthquake, Live and Dead Load requirements.

    In robustness calculations,there are height, length,and panel

    action formulae. Byreworking the standard formulae provided

    and inserting known data, it is possible to determine whether

    a chosen design and Boral masonry product will provide

    adequate robustness. Should the initial product selected not

    provide a suitable solution, then a thicker Boral masonry

    product more suited to the application should be evaluated,

    or alternatively, add extra restraints or reinforcement.

    The following section is laid out with AS3700 formulae and

    explanation in the left hand column, while worked examples

    can be found in the adjacent right hand column.

    Legend to Symbols used in Robustness Calculations:

    H = the clear height of a member between horizontal

    lateral supports, in metres;

    = for a member without top horizontal support, theoverall height from the bottom lateral support, in

    metres

    tr = the minimum thickness of the member, in metres

    = in cavity-wall construction, the minimum thickness

    of the thicker leaf

    or two thirds the sum or thicknesses ofthe two leaves,

    whichever is greater, in metres

    or in diaphragm wall construction, the overall

    thickness of the wall, in metres

    kt = a thickness coefficient,values as given in AS3700

    Table 7.2 (see the end of this section)

    Cv,Ch = robustness coefficient,values as given in AS3700

    Table 4.2(see end of this section) foredge restraints

    at top, bottom and vertical sides (either separately

    or in combination)

    Lr = the clear length of the wall between vertical lateral

    supports, in metres; or

    = for a wall without a vertical support at one end or

    at a control joint or for walls containing openings,

    the length to that unsupported end orcontrol joint

    or edge of opening, in metres.

  • 8/10/2019 Bor11999 Nsw Manual Bk1 Structural Fire Accustic

    9/72

    BOOK

    PAGE

    1

    Structural Design

    B3

    Isolated Piers

    Formula 4.6.2 (1) is used for isolated piers. Masonrywith

    a length less than one fifth of its height and free ends,is considered to be an isolated pier.

    Formula (1) is:

    By re-working formula (1), the maximum height for an

    isolated pier can be determined:

    H tr x Cv

    Where Cv is obtained from AS3700 Table 4.2 (Refer to

    Page B5).

    H Cv

    tr

    Formulae and Explanation Worked Examples

    Formulae and Explanation Worked Examples

    Aim: To determine the Maximum Wall

    Height of an Isolated Pier

    Example 1: Minimum wall thickness tr = 230mm

    A single leaf structure, unreinforced, then

    Cv= 13.5

    H 0.23 x 13.5

    H 3.105m (maximum wall height)

    Example 2: Minimum wall thickness, tr = 140mm

    A single leaf structure, reinforced, then

    Cv= 30

    H

    0.14 x 30H 4.200m (maximum wall height)

    Aim: To determine the Maximum Height of

    a Wall with Free Ends

    Criteria: Minimum wall thickness, tr = 110mm

    kt = 1 (wall without piers)

    Example 1: If wall is freestanding, then Cv=6

    (must be checked by an engineer for

    wind loads etc.)

    H 1.0 x 0.11 x 6

    H 0.660m

    Example 2: If wall is laterally restrained along its top,

    then Cv=27

    H

    1.0 x 0.11 x 27H 2.970m

    Example 3: If wall is laterally restrained along its top

    and supports a slab, then Cv=36

    H 1.0 x 0.11 x 36

    H 3.960m

    Wall with Free Ends

    Formula 4.6.2 (2) is used for walls spanning vertically

    (i.e. wall with free ends).

    Formula (2) is:

    By re-working formula (2), the maximum wall height is:

    H kt x tr x Cv.

    Where kt is obtained from AS3700 Table 7.2 (Refer to Page

    B5)

    or

    By re-working formula (2), the minimum wall thickness

    is:

    kt x tr H

    Cv

    H Cv

    kt x tr

  • 8/10/2019 Bor11999 Nsw Manual Bk1 Structural Fire Accustic

    10/72

    BOOK

    PAGE

    1

    Structural Design

    B4

    Aim: To determine the Maximum Length

    of a Wall with Restraint at End or

    Ends

    Criteria: Wall thickness tr = 110mm

    Example 1: If wall is restrained along one end, then

    Ch = 12

    L 0.11 x 12

    L 1.320m

    Example 2: If wall is restrained along both ends, then

    Ch = 36

    L 0.11 x 36

    L 3.960mNOTE: If the wall exceeds the permitted length, then a

    thicker wall is required or formula 4.6.2 (4) governs and

    H will be limited. (See below).

    Aim: To determine the Maximum Height of

    a Wall with Restraint at Top and End

    or Ends

    Criteria: Wall thickness tr = 110mm

    Wall length = 2m

    Example 1: If wall supports a slab, then Cv= 36, and

    if restrained along one end, then Ch = 12

    H 5.9m

    0.11)+ 122 12 x 0.1136(H

    Wall with Restraint at Top and End or Ends

    Formula 4.6.2 (4) is for walls spanning vertically and

    horizontally (i.e. with restraint along the top and one or

    two ends) and length L > tr x Ch.

    Where Ch is obtained from AS3700 Table 4.2. (Refer to

    Page B5)

    Formula (4) is:

    By re-working formula (4), the maximum wall height is:

    NOTE: Control joints, and openings greaterthan one fifth

    of wall height are treated as free ends unless specific

    measures are taken to provide adequate lateral support.

    tr)+ ChLr ChtrCv(H

    +Ch

    Lr Chtr

    H Cv

    tr

    Wall with Restraint at End or Ends

    Formula 4.6.2 (3) is for walls spanning horizontally [i.e.

    restrained end(s)]. Walls that have one or both ends

    laterally restrained and

    i.e. L tr x Ch

    Where Ch is obtained from AS3700 Table 4.2. (Refer to

    Page B5)

    NOTE: This means that although the wall height is not

    limited by its thickness, the wall length is limited. Stair

    wells and chimneys work to this formula.

    H= no limit

    tr

    L Ch

    tr

    Formulae and Explanation Worked Examples

    Formulae and Explanation Worked Examples

  • 8/10/2019 Bor11999 Nsw Manual Bk1 Structural Fire Accustic

    11/72

    BOOK

    PAGE

    1

    Structural Design

    B5

    Strength

    Compressive strength is resistance to load, measured by the

    amount of pressure to crush a masonry unit. The pressure,

    usually measured in megapascals (MPa), is the force inkilonewtons (kN) x 1000, divided by the loaded area in square

    mm.

    Unconfined compressive strength is compressive strength,

    multiplied by an aspect ratio, Ka. (Details are in AS4456.4,

    Table 1). The unit height divided by its thickness is used to

    determine the aspect ratio.

    A solid brickwill give a lowercompressive strength if crushed

    on its end rather than on its flat, as normally laid. In theory,

    the aspectratio will convert both tests to the same unconfined

    compressive strength.

    The strength of hollow blocks is calculated by dividing the

    force by the face shells only. A 90mm hollowand 90mm solid

    block are both 10MPa, but since the area of the face shells

    on the hollow block is about half the area of the solid block,

    the hollow will only carry half the load of the solid.

    Characteristic Unconfined Compressive Strength of

    masonry UNITS is uc.

    uc is the average of crushing forces divided by loaded areas,

    multiplied by the aspect ratio, minus the standard deviationx 1.65.

    Characteristic Compressive Strength of a masonry

    WALL is m.

    m is the square root ofuc, multiplied by Km (a mortar

    strength factor), multiplied by Kh (a factor for the amount of

    mortar joints) as perAS3700, 3.3.2.

    The Km factor is 1.4 for M3 mortar on solid and cored units

    and is 1.6 for the face shells of hollow units. For the richer

    M4 mortar it is 1.5. (Details are in AS3700, Table 3.1).

    The Kh factor is 1 for 76mm high units with 10mm mortar

    beds and is 1.3 for 190mm units with 10mm mortar beds.

    In other words, a wall of 190mm high units is 30% stronger

    than a wall of 76mm high units of the sameuc.

    Bending

    Characteristic Flexural Tensile Strength is mt.

    Masonry is good in compression but poor in tension. Mortar

    jointstrength is generally zero or 0.2MPa for loads from wind,earthquake etc. Higherbending forces mayrequire masonry

    to be partially reinforced.

    Horizontallyunreinforced

    ChEdge restraints onvertical sides of

    wall panels

    Horizontallyreinforced orprestressed

    SUPPORT

    SUPPORT

    SUPPORT

    12

    36

    24 with

    reinforcementcontinuous past

    support.

    Otherwise 16

    48

    CvTop and bottom edge

    restraints to wall panels Verticallyunreinforced

    Vertically reinforcedor prestressed

    Free

    SUPPORT

    LateralSupport

    Load other thanconcrete slab or no load

    SUPPORT

    LateralSupport

    Concrete Slab

    SUPPORT

    LateralSupport

    SUPPORT

    ISOLATED PIERS

    6

    12 withreinforcement

    continuous into

    support. Otherwise

    6.

    27 36

    36 48

    13.5 30

    Table B1 (Extract from AS3700 : Table 4.2)

    Pier Spacing/PierWidth Thickness Coefficient (kt)

    (Refer to Note 1) Pier Thickness Ratio (twp/t)

    1 2 3

    6 1.0 1.4 2.0

    8 1.0 1.3 1.7

    10 1.0 1.2 1.4

    15 1.0 1.1 1.2

    20 or more 1.0 1.0 1.0

    Pier Spacing

    Pier Width

    ttwp

    Wall Leaf

    Table B2 (Extract from AS3700 : Table 7.2)Thickness Coefficient (kt) for Walls Stiffened by

    Monolithically Engaged Piers

    NOTES: 1. Pier spacing is taken as the distance between centrelines of piers.

    2. Linear interpolation may be used.

  • 8/10/2019 Bor11999 Nsw Manual Bk1 Structural Fire Accustic

    12/72

    BOOK

    PAGE

    1

    Structural Design

    B6

    Shear

    Characteristic Shear Strength is ms.

    At damp course, it is zero unless tested. Elsewhere, mortar

    joints have ms values of between 0.15 and 0.35MPa.

    As with tension, high shear loads may require partially

    reinforced masonry.

    Durability

    Masonry designed forDurability is deemed to satisfywhen

    it meets the requirements ofAS3700 Section 5, which details

    whatareas require Exposure, General Purpose and Protected

    grades. Assessment of these grades is defined in

    AS/NZS4456.10 Resistance to Salt Attack.

    AS3700 defines the usage of each of these grades as:

    Protected Grade (PRO)

    Elements above the damp-proof course in non-marine exterior

    environments. Elements above the damp-proof course in other

    exterior environments, with a waterproof coating, properly

    flashed junctions with other building elements and a top

    covering (roof or coping) protecting the masonry.

    General Purpose Grade (GP)

    Suitable for use in an external wall excluding severe marineenvironment.

    Exposure Grade (EXP)

    Suitable for use in external walls exposed to severe marine

    environments, i.e. up to 100m from a surf coast or up to 1km

    from a non surf coast. The distances are specified from mean

    high water mark.

    Mortarmixrequirements fordurability are detailed in AS3700

    Table 10.1. Mortar joints must be ironed.

    Salt attack is the most common durability problem. The saltin salt water is in solution. It can be absorbed into masonry

    or at least, its mortar joints. When the water evaporates, it

    migrates towards the outside face taking the salt with it until

    the amount ofwater left is saturated. Itcan no longerhold all the

    salt in solution and salt crystals begin to form.

    The salt crystals then take up space, sometimes more than

    the texture of the masonrywill allow. The crystal then pops

    a piece of the outer surface off to make room and salt attack

    begins.

    Walls below damp course also require greater durability.

    Even if theyare well awayfrom the coast,theymaybe subjected

    to acidic or alkaline soils. In anycase, moisture in the ground

    is absorbed into the masonry, creating an environment ideal

    for bacteria, which feeds lichens and algae which can

    eventually be detrimental.

    AS/NZS4456.10 gives methods of testing and definitions for

    durability (salt tests). An alternative to testing is a history of

    survival in a marine environment. Concrete masonryhas been

    used forSurf Club construction around Australia fordecades.

    Movement

    In general, concrete units contract as theycure while clay units

    will expand. They both expand as they take up water and

    contract as they dry. They both expand as they get hot andcontract as they cool.

    Curing Movement in Concrete Units

    AS/NZS4456.12 gives methods for determining coefficients

    of curing contraction and coefficients of drying contraction

    for concrete units.

    Drying Contraction

    The drying contraction teston masonryunits is an indication of

    their maximum amount of movement from totally saturated to

    ambientdry. Atypical result is 0.5mm/m butcan be as high as1mm/m for lightweight units that are more absorptive. For

    example, a drying contraction of 0.5mm/m, in an 8m panel of

    masonry, has the potential to shrink 4mm from saturated

    condition to dry.

    External Control Joints

    AS3700, Clause 4.8 requires control joint spacing to limit

    panel movement to:-

    10mm maximum for opening of control joints,

    15mm maximum for closing of control joints, and

    5mm minimum when closed.

    The Australian Masonry Manual recommends control joints

    at 8m centres for concrete units, 6m centres for lightweight

    (

  • 8/10/2019 Bor11999 Nsw Manual Bk1 Structural Fire Accustic

    13/72

    BOOK

    PAGE

    1

    Structural Design

    B7

    External control joints should be finished with a flexible

    sealant.

    Control joints create a free end in terms of robustness and

    FRLs for structural adequacy, so their positioning is critical

    to the overall design of the structure.

    In portal frame construction, the control joint is positioned

    at a column so that both ends can be tied to the column

    flanges. The mason and renderer must keep the control joint

    clean, otherwise,bridging mortaror renderwill induce cracks

    from those points as the masonrymoves. If ties are used over

    control joints, they must be sleeved to allow movement.

    Adding extra cement to mortar or render causes more

    shrinkage. Lightweight units are only5MPa,so are susceptible

    to cracking if laid in rich mortar or rendered with a cement-rich mix.

    Internal Control Joints

    The Australian Masonry Manual specifies the spacing of

    internal control joints for concrete units at 12m maximum.

    Energy Efficiency for Class 2,3 & 4 buildings in ACT

    The Building Code ofAustralia (BCA) 2005,Volume 1, requires

    the walls of Canberra home units,hotels and similardwellings

    to have:-

    Total R-Value rating of 1.9 (Climate Zone 7) or

    Wall mass > 220kg/m2 and include insulation with an

    R value not less than 1.

    Total R-Value means the sum of thermal resistances

    (m2.K/W) of wall components including air spaces and

    associated surface resistances.

    In BCA Specification J1.5 Wall Construction, options (a) (b)

    & (c) for concrete masonry give theirTotal R-values without

    insulation.

    The R-value of the insulation needed to make up the required

    Total R-value for masonry veneer in Zone 7 is R1.5. Masonry

    minimum thickness is 90mm. The insulation is usually placed

    between the studs.

    Alternative verification can be achieved through a 4 star

    assessmentforClass 2& 4buildings using calculations defined

    in BCAClause JV1,and forClass 3 buildings,calculating energy

    consumption to meet values as per Clause JV2 or comparison

    with a reference building as per Clause JV3.

    Energy Efficiency for ACT Houses

    In the ACT, houses are required to have a 4 star rating as

    assessed byan accredited ACTHouse EnergyAssessor or by

    equivalent assessment with R1.5 insulation material in the

    external walls of brickveneer construction. Cavity brick of 2

    x 90mm minimum thicknesses is exempt.

  • 8/10/2019 Bor11999 Nsw Manual Bk1 Structural Fire Accustic

    14/72

    BOOK

    PAGE

    1

    Structural Design

    B8

    NSW Energy Efficiency: Class1, 2, 3 & 4 buildings

    Class 1, 2 and 4 buildings

    The Building Code ofAustralia (BCA) 2005,Volume 1, requires

    the walls of home units in Sydney(and progressivelyelsewhere

    in NSW) to complywith BASIX(building sustainability index),

    a web-based planning tool at www.basix.nsw.gov.au

    Class 3 buildings

    Walls of Class 3 buildings (hostels, hotels, motels) are required

    bythe BCA,J1.5 to have one ora combination of the following:

    Total R-Valuerating of1.4 in Climate Zone 2& 5 (North Coast

    to Sydney)

    A rating of 1.7 in Climate Zone 4 & 6 (Western NSW)

    A rating of 1.9in Climate Zone 7(Armidale & Sthn Highlands)

    A rating of 2.8 in Climate Zone 8 (Thredbo)

    or

    Wall mass > 220kg/m2 in Climate Zone 4 & 5 and in Zone

    6, 7 & 8, include insulation with an R value not less than 1

    (floor system in Zone 6 to be slab on ground).

    Total R-Value means the sum of thermal resistances

    (m2.K/W) of wall components including air spaces and

    associated surface resistances.

    In Specification J1.5Wall Construction, options (a) (b) & (c)

    for concrete masonry give their Total R-values without

    insulation.

    The R-value of the insulation needed to make up the required

    Total R-value for masonry veneer is:

    R1.0 in Climate Zone 2 & 5

    R1.3 in Climate Zone 4 & 6

    R1.5 in Climate Zone 7 and

    R2.4 in Climate Zone 8.

    The insulation is usually placed between the studs.

    For cavity brick, these insulation R-values can be 0.3 lower

    than for brick veneer. The insulation is between battens on

    the inside face, under 10mm plasterboard.

    Minimum masonry thickness is 90mm.

    For 190mm hollow concrete blocks, partially core filled and

    with a bond beam at the top, the insulation R-values can be

    0.1 lower than for brick veneer.

    Options for Increasing R values

    The insulating properties of masonrywalls may be increased

    by the following means:

    The addition of polyester or glasswool insulation betweenstuds for masonry veneer construction.

    The addition of polystyrene sheets between wall ties for

    cavity masonry construction.

    The addition of polyester or glasswool insulation behind

    plasterboard, between battens on inside face of masonry.

    (Battens eliminate the need for chasing for plumbing and

    electrical services).

    Incorporating reflective insulation within the cavity.

    Incorporating foam insulation,pumice orvermiculite within

    the cores of the units or in the cavity.

    Using masonry units with a rough surface. (This traps a

    thicker air film at the surface).

    Using masonryunits made from less dense material. (Tiny

    air pockets within the material disrupt the flow of heat

    energy through the wall).

    Using thicker walls.

  • 8/10/2019 Bor11999 Nsw Manual Bk1 Structural Fire Accustic

    15/72

    BOOK

    PAGE

    1

    Structural Design

    B9

    15.12

    70

    100

    Horizontal

    Bars Vc Mc

    N12 5.1 2.0N16 6.3 2.9

    Vertical

    Bars Vc Mc

    N12 5.1 2.6N16 6.3 2.6

    Cut on-site

    Horizontal

    Bars Vc Mc

    N12 10.2 4.0N16 12.6 4.7

    Vertical

    Bars Vc Mc

    N12 12.5 9.3N16 13.7 16.0

    15.12

    70

    300

    100

    Horizontal

    Bars Vc Mc

    N12 8.2 4.0N16 9.3 6.9N20 10.6 9.9

    129 (N12 bars)127 (N16 bars)125 (N20 bars)

    20.12

    Vertical

    Bars Vc Mc

    N12 7.9 3.6N16 10.2 3.6N20 13.1 3.6

    100

    Horizontal

    Bars Vc Mc

    N12 6.4 2.9N16 7.6 5.0N20 9.1 6.5

    95

    20.12

    Vertical

    Bars Vc Mc

    N12 6.4 2.9N16 7.6 3.6N20 9.1 3.6

    Horizontal

    Bars Vc Mc

    N12 16.4 8.0

    N16 18.6 13.4N20 21.3 17.2

    129 (Y12 bars)127 (Y16 bars)125 (Y20 bars)

    20.20 or20.01 cuton-site

    Vertical

    Bars Vc Mc

    N12 17.9 18.0N16 20.2 30.2N20 23.1 32.2

    300

    20.12

    95

    300

    20.12

    Horizontal

    Bars Vc Mc

    N12 12.9 5.7

    N16 15.2 9.5N20 18.1 9.9

    20.20 or20.01 cuton-site

    Vertical

    Bars Vc Mc

    N12 16.4 9.5N16 17.6 16.6N20 19.0 24.4

    Reinforced Masonry Lintels

    Moment and Shear Capacities for Series 150 Blocks (140mm leaf)

    NOTES

    Vc = Shear capacity (kN)

    Mc = Moment capacity (kNm)

    Mortar type, M3

    Block characteristic compressive strength,

    uc = 15MPa

    Grout compressive strength,

    c = 20MPa

    Cement content min. (Grout) = 300kg/m3

    Moment and Shear Capacities for Series 200 Blocks (190mm leaf)

  • 8/10/2019 Bor11999 Nsw Manual Bk1 Structural Fire Accustic

    16/72

    BOOK

    PAGE

    1

    Structural Design

    B10

    Design of Core Filled &Steel Reinforced MasonryRetaining Walls

    Introduction

    The information presented here is supplied in good faith and

    to the best of our knowledge was accurate at the time of

    preparation. However, from time to time, additional ormodified

    data may be released by the CMAA. Any such information

    will supersede the information presented in this guide.

    This section provides specifications,design tables and typical

    details for a range of reinforced concrete masonry retaining

    walls and their associated reinforced concrete bases. It is

    intended as a general guide for suitably qualified andexperienced professional engineers, who for any particular

    proposed retaining wall, must accept the responsibility for

    carrying out a comprehensive site investigation, determining

    the soil characteristics and other design parameters of the

    particularsite, and fordesigning and detailing the structures.

    It is important forthe professional engineer to determine the

    strength and stability of the foundation material and the

    drainage system required to ensure there will not be a build

    up of hydrostatic pressure behind the wall.

    All designs are based on:

    Reinforced Concrete Masonry Structures AS3700 : 2001

    SA Masonry Code.

    Reinforced Concrete Base AS3600 : 1988 Concrete

    Structures.

    Reinforcement AS1302 : 1982Steel Reinforcing Bars for

    Concrete.

    Concrete Blocks AS4455 : 1997Concrete Masonry Units.

    Wall Types

    Design tables in this section are given for walls up to 3.4

    metres high and for two base types:

    Loading Conditions

    These tables cover:

    Sloping backfill (up to 1 in 4) without any surcharge

    or

    Level backfill with a 5kPa surcharge

    Since typical cases only are presented, these tables may not

    provide an ideal solution for a particular application.

    ConstructionRecommendations

    General

    Recommendations specifically applicable to reinforced

    masonry retaining walls include:

    The provision of clean-out openings in the bottom course

    to permit removal of mortar droppings and other debris

    Boundary

    Backfill

    Ground level

    Foundation

    Base Type 1

    Fig B1 Typical Wall Layout for Base Type 1

    Boundary

    Backfill

    Ground level

    Base Type 2

    Foundation

    Fig B2 Typical Wall Layout for Base Type 2

  • 8/10/2019 Bor11999 Nsw Manual Bk1 Structural Fire Accustic

    17/72

    BOOK

    PAGE

    1

    Structural Design

    B11

    and to allow vertical reinforcement to be positioned and

    tied. These openings should be closed (generallydone with

    formwork) before grouting.

    The use of H blocks above the first course. These blocks

    are easier to fill with grout which provides the required

    continuous protection to the reinforcement. If rebated

    flush-ended blocks are used in lieu of H blocks, they should

    be laid with alternate courses inverted to provide grout

    cover to horizontal reinforcement, which should be

    supported 20mm clear of the webs of flush-ended blocks.

    The forming ofweepholes byleaving out mortarin the vertical

    joints at the required locations. Where H blocks are used,

    and weepholes are required, theymaybe provided byplacing

    25mm diameterPVC pipes through the vertical joint at the

    required locations. Alternatively, flush-ended blocks maybe

    placed on either side of the required weephole location so

    a mortar-free joint may be formed.

    The accurate positioning of reinforcement to give a

    minimum of 55mm of cover to the face of the bar and its

    secure tying before placing concrete or grout.

    The removal of mortar dags protruding into cores before

    grouting.

    The use,wheneveravailable,ofready-mixed groutto workability

    specifications given in AS3700 should be used. Site-mixed

    grout, if used, should be mixed thoroughly in a tilting-drum

    mixer to the same specification as ready-mixed grout.

    The filling of all cores with grout, whether reinforced or

    not. This is essential to bond and protect horizontal

    reinforcement, to provide a full barrier against water

    penetration and to give maximum weight for stability.

    The thorough compaction of the grout so voids are not left.

    Compaction may be achieved with a high-frequency pencil

    vibrator, used carefully. (The main vertical reinforcing barsshould not be used to compact the grout). Control joints

    should be built into the masonry at all points of potential

    cracking.

    Backfill Drainage

    It is essential thatsteps be taken to preventthe backfill behind

    the wall from becoming saturated. These steps should include:

    Sealing Backfill Surface

    To preventsaturation ofbackfill by surface run-off, the surface

    of the backfill should be sealed by covering itwith a compactedlayer of low permeability material. The surface should be

    sloped towards an open drain.

    Continuous Drainage Within the Backfill

    This can be achieved byplacing free-draining gravel orcrushed

    stone to a width of approximately300mm immediatelybehind

    the wall with a continuous agricultural pipe located at the

    base of the wall. The outlets of the pipe must be beyond the

    ends of the wall unless the pipe is connected to a proper

    stormwater drainage system.

    For higher walls, or in cases where excessive groundwater

    exists, it may be necessary to provide another agricultural

    pipe drain at mid-height of the wall.

    Care mustbe taken to ensure that clay and silt do not infiltrate

    the drainage material or agricultural pipe. The use of a

    geofabric envelope around the gravel and/or a geofabric sock

    over the pipe may assist.

    Impermeablelayer slopingto drain

    Drain

    Backfill

    Fig B3 Sealing Backfill Surface

    Continuousagricultural pipedrain surroundedby free-draininggravel or crushedstone

    Vertical layer ofgranular material

    To prevent clay orsilt infiltrating thedrainage system ageofabric materialmay be wrappedaround the graveland/or the pipe

    Fig B4 Continuous Drainage Within the BackfillWalls with Base Type 1

  • 8/10/2019 Bor11999 Nsw Manual Bk1 Structural Fire Accustic

    18/72

    BOOK

    PAGE

    1

    Structural Design

    B12

    Weepholes

    Weepholes should be provided above the finished ground

    level. A drain should be provided in front of the wall to

    prevent saturation of the ground.

    The horizontal spacing of the weepholes depends on the

    provisions made for directing water towards the holes. The

    simplest, but most effective, method is to place one or two

    buckets of free-draining gravel or crushed stone around the

    intake end of each hole. In this case, the horizontal spacing

    should not exceed 1.5 metres. If the layers of draining

    material are continuous for the full length of the wall,

    weephole spacing may be increased to an extent depending

    on the quantity of water expected.

    Note: For walls higher than 2200mm, a second row of

    weepholes may be required. However, staining of the wall

    could result.

    Locate thecontinuous drainat the bottom ofthe base

    Free draininggranular material

    Backfill

    Fig B5 Continuous Drainage Within the BackfillWalls with Base Type 2

    Extraagriculturalpipe drain

    Fig B6 Continuous Drainage for High Wallsand/or Excessive Groundwater

    Free-draininggravel or stone

    Drain

    Weepholesbetweenblocks

    Fig B7 Continuous Drainage Within the BackfillWalls with Base Type 1

    30mm

    Clean-outcourse

    50mm cover to allbase reinforcement

    55mm cover towall reinforcement

    Fig B8 Typical Set-out Detail

    Water Penetration

    If it is considered necessary to reduce the passage of

    moisture through the wall, for aesthetic or other reasons

    such as aggressive groundwater, the earth face of the wall

    should be treated with an appropriate sealer such as water-

    resistant render or water-resistant paint, or by tanking with

    bituminous materials.

    Structural Design Guidelines

    Acceptable Soil Combinations

    For retaining walls founded on sand (Type A soil), the

    retained material must be similar and with a friction angle

    of 38 or greater, eg Type A soil clean sand or gravel.

    For retaining walls founded on other soils, the retained

    material must be a free draining material with a friction

    angle of 27 or greater, eg Type A soil clean sand or gravel,

    Type B soil coarse grained with silt or some clay.

  • 8/10/2019 Bor11999 Nsw Manual Bk1 Structural Fire Accustic

    19/72

    BOOK

    PAGE

    1

    Structural Design

    B13

    190

    400

    230

    B

    B

    250

    550

    330

    300

    600minlap

    H = 1400to 2000

    H = 2200to 3400

    Heightof190mmblocks

    Height of290mmblocks

    450minlap

    Longitudinalreinforcement:N12 inalternatecoursescommencingfrom topcourse. Omiton top ofclean-outblock

    Longitudinal

    reinforcement: N12 inalternate coursescommencing from topcourse. Omit on top ofclean-out block

    Slopingbackfill orsurcharge

    Sloping backfillor surchargeOptional

    capping

    Vertical reinforcement:N12 @400 cts

    N12 @400cts

    N16 @400N16 @400

    V Bars

    X Bars

    V Bars

    X Bars

    K Bars

    Optionalcapping

    290

    190

    140

    350

    180

    B

    200

    450minlap

    H = 800to 1200

    Longitudinal reinforcement:N12 in alternate coursescommencing from top course.Omit on top of clean-out block

    Slopingbackfill orsurcharge

    N12 @400cts

    N12 @400

    V Bars

    X Bars

    Optionalcapping

    Fig B9 Construction Guidelines for Reinforced & Core Filled Retaining Walls with Base Type 1

    Wall Height Reinforcement Base Dimensions

    Total

    Height Height of Blockwork X-Bars Width, B (mm) (mm) 150 200 300 and with following backfill conditions

    H Series Series Series V-Bars K-Bars Level Max 1 in 4 Slope

    800 800 N12 at 400 800 1000

    1000 1000 N12 at 400 1000 1200

    1200 1200 N12 at 400 1100 1500

    1400 1400 N12 at 400 1300 1700

    1600 1600 N16 at 400 1400 2000

    1800 1800 N16 at 400 1600 2200

    2000 2000 N16 at 200 1700 2500

    2200 1400 800 N16 at 400 N16 at 400 1900 2800

    2400 1600 800 N16 at 400 N16 at 400 2000 3100

    2600 1600 1000 N20 at 400 N20 at 400 2200 3300

    2800 1800 1000 N20 at 400 N20 at 400 2400 3600

    3000 2000 1000 N16 at 200 N16 at 200 2600 3900

    3200 2000 1200 N20 at 200 N16 at 200 2800 4200

    3400 2000 1400 N20 at 200 N16 at 200 2900 4500

    Table B3 Design Guidelines for Reinforced & Core Filled Retaining Walls with Base Type 1

  • 8/10/2019 Bor11999 Nsw Manual Bk1 Structural Fire Accustic

    20/72

    BOOK

    PAGE

    1

    Structural Design

    B14

    190

    D

    WB B

    250250

    290

    D

    W

    300

    190

    600min.lap

    H = 1400to 2000

    H = 2200to 3400

    Height of190mmblocks

    Height of290mmblocks

    600min.lap

    Longitudinal reinforcement:N12@400

    N16 in top course only

    N16 in topcourse only

    Optionalcapping

    N12@400 cts

    N12@400 cts

    V Bars

    SL72 Fabric

    N16@400N16@400 N16@400

    V Bars

    K Bars

    Optionalcapping

    SL72 Fabric

    140

    D

    WB

    450min.lap

    H = 800to 1200

    [email protected] fromtop course. Omit ontop of clean-outcourse

    Surcharge orsloping backfill(1 in 4 max.)

    Surcharge orsloping backfill(1 in 4 max.)

    Surcharge orsloping backfill(1 in 4 max.)

    N12@400 cts

    V Bars

    SL72 Fabric

    Optionalcapping

    Longitudinal reinforcement2 x N12@400cts. Omit ontop of clean-out course

    LongitudinalreinforcementN12@400 cts.Omit on top ofclean-out course

    N12@400N12@400

    Fig B10 Construction Guidelines for Reinforced & Core Filled Walls with Base Type 2

    Table B4 Design Guidelines for Reinforced & Core Filled Walls with Base Type 2

    Wall Height Reinforcement Base Dimensions

    Max. 1 in 4

    Total Level Backfill Sloping Backfill

    Height Height of Blockwork Heel Width Base Width Heel Depth Base Width Heel Depth

    (mm) 150 200 300 (mm) (mm) (mm) (mm) (mm)

    H Series Series Series V-Bars K-Bars W B D B D 800 800 N12 at 400 450 600 500 800 500

    1000 1000 N12 at 400 450 800 500 1000 500

    1200 1200 N12 at 400 450 1000 500 1200 600

    1400 1400 N16 at 400 450 1200 500 1400 600

    1600 1600 N16 at 400 450 1400 600 1600 700

    1800 1800 N16 at 400 450 1600 700 1800 800

    2000 2000 N16 at 200 600 1800 700 2000 800

    2200 1400 800 N16 at 400 N16 at 400 600 2000 800 2200 900

    2400 1600 800 N16 at 400 N16 at 400 600 2200 900 2400 1000

    2600 1600 1000 N20 at 400 N20 at 400 900 2400 900 2600 1000

    2800 1800 1000 N20 at 400 N20 at 400 900 2600 900 2800 1100

    3000 2000 1000 N16 at 200 N16 at 200 900 2800 1000 3000 1200

    3200 2000 1200 N20 at 200 N16 at 200 900 3000 1100 3200 1300

    3400 2000 1400 N20 at 200 N16 at 200 900 3200 1200 3400 1500

  • 8/10/2019 Bor11999 Nsw Manual Bk1 Structural Fire Accustic

    21/72

    BOOK

    PAGE

    1

    Structural Design

    B15

    200

    55mmcover

    1000

    N16 @400 cts orN12 at 200 ctsN12 @400 cts

    2700 max.

    Floor slabreinforcement

    Floor slab reinforcementN12 at 200 cts

    Ag. drain

    Verticalreinforcement:N16 @400 cts,central

    Tanking to back face of walle.g. Bituminous coating

    Series 200blocks

    Horizontalreinforcement,N12 at 400 cts

    Starter bar to matchwall reinforcementabove

    One-course bond

    beam with N12 bar

    Note:Wall blocks andreinforcement asfor 'Typical Details'

    200

    Drained cavity

    False wall

    Ag. drain

    190

    20.20 knock-out blocksaw-cut at floor soffit level

    Fig B11 Typical Details Fully Propped Wall

    Fig B12 Alternative Details Fully Propped Wall

  • 8/10/2019 Bor11999 Nsw Manual Bk1 Structural Fire Accustic

    22/72

    BOOK

    PAGE

    1

    Structural Design

    B16

    300300

    55mm cover

    1500N16 at 200 ctsN12 at 400 cts

    2700 max.

    1200

    Timber floor

    Ag. drain

    Vertical reinforcementN16 at 400 cts, central

    65mm cover toback face

    65mm coverto back face

    Tanking toback faceof wall

    Series 200blocks

    Horizontal reinforcement,N12 at 400 cts

    Note:Reinforcement asfor Typical Details

    Drained cavity

    False wall

    Ag. drain

    Series 300blocks

    190

    190

    290

    290

    140

    Timber floor

    Pole plate fixedto bond beam

    One-coursebond beam using20.20 knock-out blockwith 1xN12 bar

    or N20 at 400 cts

    Floor slabreinforcement

    Naturalsoil

    Naturalsoil

    Clean-outcourse

    Fig B13 Typical Details Unpropped or Partially Propped Wall

    Fig B14 Alternative Details Unpropped or Partially Propped Wall

    NOTE: Backfill must be completed prior to construction of timber floor.

  • 8/10/2019 Bor11999 Nsw Manual Bk1 Structural Fire Accustic

    23/72

    BOOK

    PAGE

    1

    Structural Design

    B17

    450 min.

    Bars450 lap

    'H' (2200 max.)

    600 min.

    Ag. drain 65mfall at 1:100 tooutlet

    Free-draining gravel

    Note:Footing size andreinforcement to suitsite conditions

    Note:Retaining wall shall be propped prior tobackfilling and remain in place for aminimum of 7 days after placing floor slab

    Verticalreinforcement:N12 at spacing 'S',centrally placed

    Horizontalreinforcement,N12 at 400 cts

    Knock-out blocksaw-cut at floorsoffit level

    Starter bars,N12 @ spacing 'S',centrally placed

    Use Double-U or H

    blocks forsub-floor wallsection

    Clean-out course

    190

    Floor slab reinforcementto suit site conditions

    Vapour barrier andsand bedding under slab

    Natural soil

    450lap

    N12 at same spacing as verticalreinforcement (spacing 'S')lapped 450 in wall and floor

    N12 at same spacing asvertical reinforcement

    Fig B15 Typical Details Subfloor Retaining Walls

    Vertical Reinforcement Spacing

    Height H(mm) Spacing S(mm)

    1500 600

    >1500 2200 400

  • 8/10/2019 Bor11999 Nsw Manual Bk1 Structural Fire Accustic

    24/72

    BOOK

    PAGE

    1

    Structural Design

    B18

    NOTES

  • 8/10/2019 Bor11999 Nsw Manual Bk1 Structural Fire Accustic

    25/72

    1SECTIONC Fire DesignSTRUCTURAL, FIRE & ACOUSTICMasonry Design Guide

    New South Wales

    BOOK

    1

  • 8/10/2019 Bor11999 Nsw Manual Bk1 Structural Fire Accustic

    26/72

    BOOK

    PAGE

    1

    Fire Design

    C2

    Masonry Design forFire Resistance

    Fire Resistance Levels (FRL)

    FRL come from the Building Code of Australias (BCA) tables

    for Type A, B or C construction. The Type of construction

    depends on the Class of building and the number of stories

    or floors.

    There are 3 figures in the Fire Resistance Level.

    eg: FRL 60/120/120 meaning Structural Adequacy for 60

    minutes / Integrity for120 minutes / Insulation for120 minutes.

    Structural Adequacy

    This governs the wall height, length, thickness and restraints.Masonry unit suppliers do not control the wall height, length

    or restraints, therefore do not control Structural Adequacy.

    However, information that is useful in the design of masonry

    walls is the maximum Slenderness ratio (Srf). Boral Masonry

    provides Srfinformation for all of its masonry units, and its

    use is discussed in more detail later.

    Integrity

    This is the resistance to the passage of flame or gas. To

    provide integrity, masonry walls must be structurally

    adequate because cracks that form when it bows can allowflame through the wall. Since the masonryunit supplier does

    not control Structural Adequacy, they cannotcontrol integrity

    either.

    Insulation

    This is resistance to the passage of heat. Insulation is governed

    by the type and thickness of the material used to produce the

    masonry unit. This is controlled by the masonry unit

    manufacturer. In relation to FRL, masonrymustalways provide

    Insulation to an equal or better level than is required for

    Integrity.

    Masonry Design forStructural Adequacy FRL

    Legend for the following formulae

    Srf = the slenderness ratio in design for fire resistance for

    structural adequacy. See table C2 on page C7 for

    maximum Srf.

    avf = 0.75 ifthe memberis laterallysupported along its top edge.

    = 2.0 if the member is not laterally supported along its

    top edge.

    H = the clear height of a memberbetween horizontal lateral

    supports; or

    = for a memberwithouttop horizontal support,the overall

    height from the bottom lateral support.

    t = the overall thickness of the member cross-section

    perpendicular to the principal axis underconsideration;

    for members of cavity wall construction, the wall

    thickness assessed is in accordance with AS3700

    Clause 6.3.2.1(a) and (b).

    ah = 1.0 if the member is laterally supported along both its

    vertical edges.

    = 2.5 if the member is laterally supported along onevertical edge.

    L = The clear length of a wall between vertical lateral

    supports; or

    = for a wall without vertical support at one end or at a

    control joint orforwalls containing openings, the length

    to that unsupported end or control joint or edge of

    opening.

    NOTE: A control joint in a wall, or an edge to an opening in

    a wall, shall be regarded as an unsupported edge to the wallunless specific measures are taken to provide adequate lateral

    support at the edge.

    Structural Adequacy may be overridden by design for

    robustness; wind; live or earthquake loads.

    A fire on one side of a wall will heat that side, making it

    expand and lean towards the fire. When the lean or bow

    reaches half the thickness of the original wall, the wall

    becomes structurally inadequate. The formulae in AS3700,

    Clause 6.3.2.2 limits masonry panel size, depending on its

    restraints and thickness.

  • 8/10/2019 Bor11999 Nsw Manual Bk1 Structural Fire Accustic

    27/72

    BOOK

    PAGE

    1

    Fire Design

    C3

    The Slenderness ratio (Srf) of the proposed wall is calculated

    as per Clause 6.3.2.2. If this value is less than the maximum

    Srf in Table 6.1 [or the Srf calculated from Fire Tests and

    Clause 6.3.3(b)(ii)], then the wall complies. If the Srfof the

    wall is greater than the maximum permissible, it isrecalculated foran increased thickness and/orextra restraints.

    There are 4 formulae for calculating Srf: 6.3.2.2 (1) and (2)

    are the HEIGHT formulae.

    FORMULA 1 and 2 is:

    6.3.2.2 (3) is the PANEL ACTION formula.

    FORMULA 3 is:

    6.3.2.2 (4) is the LENGTH formula.

    FORMULA 4 is:

    The actual Srfis the lesser of the resulting figures.

    Formula (1) and (2) always govern where there is no end

    restraint, and often govern where walls are long, relative to

    their height. Projects with multiple wall lengths (eg: home

    units) can use this formula as a one size fits all method of

    calculating the masonry thickness.

    Formula (3) allows a wall to exceed the height given by formula

    (1) and (2) provided at least one end is restrained as well as

    the top.

    Formula (4) governs the wall length, often where there is no

    top restraint (eg: portal frame factories) and where walls are

    short, relative to their height (eg: a lift well orvent shaft).

    From a suppliers perspective,it is helpful to be able to calculate

    the maximum height* for a given thickness (masonry unit),

    eg:

    and calculate the thickness from a given wall size.

    where t is the OVERALL thickness, whether the units are

    solid or hollow.

    NOTE:* Refer to the Structural Adequacy Selection Graphs

    on pages C9 to C20 for maximum height values.

    t =avfx H

    Srf

    H =Srfx t

    avf

    Srf = ahL

    t

    Srf =0.7

    t

    Srf = avfH

    t

    Forcavitywalls, two thirds of the total thickness can be used

    for t, provided that BOTH leaves are restrained in the same

    positions (eg: external leaf stops at slab also). If the external

    leaf is a veneerto the slab edge,the internal leaf must provide

    the Structural Adequacy FRL on its own.

    For reinforced masonry, the Srf of 36, from Table C2 on

    page C7 may be used. Reinforcement can be horizontal, as

    bond beams when spanning between columns. Reinforcement

    can be vertical, as filled cores when spanning between slabs.

    In either case, reinforcement can be spaced up to 2m apart,

    depending on span. This reinforcement stiffens the masonry

    and resists bowing. Reinforced walls with Srf< 36 have a 240

    minute FRL for Structural Adequacy.

    All calculations should be checked by an engineer. Other

    loads may supersede Structural Adequacy requirements.

    Masonry Design for

    Integrity FRL

    It is impractical to provide test results forall possible masonry

    wall designs,and therefore Integrity mustbe proved in some

    other way. With masonry wall design, the most practical way

    to prove Integrity is to prove Structural Adequacy and

    Insulationequal to orbetterthan the Integrityrequirement.

    (Logically, if the wall is designed to minimise bowing it will

    not crack and therefore resist the passage of flame and gas

    for the specified time).

    This method is also the best way to prove integrity even

    when a wall may not be required to complywith a structural

    adequacyFRLvalue,such as is the case with non loadbearing

    walls. eg: if the BCA requires an FRL of -/90/90,the wall has

    no actual structural adequacy requirement, but to prove

    integrityof 90 minutes, the wall must be structurallyadequate

    for 90 minutes.

    avfH ah L

  • 8/10/2019 Bor11999 Nsw Manual Bk1 Structural Fire Accustic

    28/72

    BOOK

    PAGE

    1

    Fire Design

    C4

    Masonry Design forInsulation FRL

    Insulation is the one FRL component that a masonry unit

    manufacturer does control. It is governed by the type of

    material and the material thickness.

    Material thickness is defined in AS3700, Clause 6.5.2as the

    overall thickness for solid and grouted units and units with

    cores not more than 30% of the units overall volume.

    For hollow units (cores > 30%), the material thickness is the

    net volume divided by the face area.

    For cavitywalls, t = the sum of material thicknesses in both

    leaves, (not two thirds as for the Structural Adequacy FRL).

    Options for Increasing FRLs

    The Structural Adequacy FRL can be increased by adding

    wall stiffeners, byincreasing the overall thickness, byadding

    reinforcement orbyprotecting the wall with Boral Plasterboard

    FireStop board, fixed to furring channels (on both sides of

    the wall if a fire rating is required from both sides).

    IntegrityFRLs are increased by increasing the other two FRL

    values to the required Integrity FRL.

    Insulation FRLs can be increased by core filling, by adding

    another leaf of masonry, by rendering both sides of the wall

    if the fire can come from either side. NOTE: Only ONE

    thickness of render is added to the material thickness and

    that must be on the cold side because the render on the

    exposed face will drop off early in a fire).

    Boral FireStopplasterboard on furring channels can increase

    the Insulation FRL from either side. Unlike render, the Boral

    FireStop and furring system does not drop off the hot side

    so quickly due to the boards fire resistance, the mechanical

    fixing of the board to furring and the furring to the wall.

    Effect of Chases on Fire RatedMasonry

    Structural Adequacy FRL

    To assess the effect of chases on Structural Adequacy FRLs,

    the direction in which the wall spans must be taken into

    account.

    Walls spanning vertically may be chased vertically. The

    horizontal chase is limited to 4 times the wall thickness.

    Walls spanning vertically and horizontally may be chased

    horizontally up to half the wall length. Horizontal chases

    should be kept to a bare minimum. Walls spanning vertically

    and horizontally may be chased vertically up to half the wall

    height.

    If these limits are exceeded, the masonry design thickness

    must be reduced by the depth of the recess or, in the case of

    vertical chases, designed as 2 walls with unsupported ends

    at the chase.

    Integrity and Insulation FRLs

    Maximum depth of recess is 30mm. Maximum area is

    1,000mm2. Total maximum area on both sides of any5m2 of

    wall is 100,000mm2

    If these limits are exceeded, the masonry design thicknessmust be reduced by the depth of the recess.

    Recesses for Services

    Recesses that are less than half of the masonrythickness and

    are less than 10,000mm2 for both sides within any 5m2 of

    the masonry, do not have an effect on fire ratings.

    If these limits are exceeded, the masonry design thickness

    must be reduced by the depth of the recess.

  • 8/10/2019 Bor11999 Nsw Manual Bk1 Structural Fire Accustic

    29/72

    BOOK

    PAGE

    1

    Fire Design

    C5

    Step 1

    Determine required wall FRL from the Building Code

    of Australia (BCA).

    The Building Code of Australia (BCA), Section C defines

    the CLASS and TYPE of building and designates the

    required Fire Resistant Level (FRL) in terms of threecriteria. See adjacent example.

    NOTE: For masonry wall design, the FRL for any given wall

    must comply with:

    Structural Adequacy Integrity Insulation

    Refer to the section Design for Integrity on page C3 for

    additional explanation.

    How to Select Boral Masonry Units for Fire Rated Walls

    All design information, table data and graphs in this guide

    are derived from formulae in AS3700 : 2001 Masonry

    Structures, Part 6.3 for Structural Adequacy Fire ResistanceLevels (FRL) and Part 4.6 for Robustness.

    Tables and graphs assume all walls are built on concrete

    slabs or broad footings and have adequate restraints. Piers,

    cavity walls, freestanding walls, earthquake, wind and otherloads are not addressed in this guide. All fire rated walls

    should be designed by a suitably qualified engineer.

    eg. If the BCA required FRL is: /120/60

    Then the chosen wall design must have anactual FRL of: 120/120/120 or better.

    Example

    eg: 120/60/60

    Insulation

    IntegrityStructural Adequacy

    Worked Example

    A 6m high, 6m long fire rated, non-loadbearing wall in a

    3 storey warehouse. BCA specifies Class 7, Type b

    Construction.

    BCA Section C1.1, Table 4 specifies an FRL 240/240/240.

  • 8/10/2019 Bor11999 Nsw Manual Bk1 Structural Fire Accustic

    30/72

    BOOK

    PAGE

    1

    Fire Design

    C6

    Material Attributes (New South Wales)

    Scoria Blend High Fire Rated Block uc = 4MPa.

    Offers excellentInsulation and Structural AdequacyFRLs forNON-

    LOADBEARING fire rated walls. 10% lighter than Standard Greyunits. Scoria Blend is hard,durable and suitable forpaintorrender.

    Acoustic performance with plasterboard linings is excellent. Acoustic

    performance with render is medium range.

    FireLight (FL) uc = 3MPa

    Insulation FRL of 90 to 120 minutes. High slenderness ratio

    (S rf) for Structural Adequacy FRL. Suitable for NON

    LOADBEARING fire rated walls. Lightweight, 35% lighter than

    Standard Grey units. Acoustic performance with plasterboard

    linings is excellent.

    Basal t (B) uc = 10MPa for blocks and 12MPa

    for bricks

    Offers excellentSrfvalues forStructural AdequacyFRL. Suitable

    for LOADBEARING walls. Acoustic performance with

    plasterboard is excellent. Acoustic performance with render

    is excellent.

    Designer Blockuc = 15MPa.

    Blocks provide a 60 minute Insulation FRL. Suitable for

    LOADBEARING applications.

    Standard Grey Blockuc = 10MPa.

    Suitable for LOADBEARING walls. 60 minute insulation FRL

    as hollow blockwork.

    Reinforced Grout Filled Masonryuc = 15MPa.

    AS3700 allows an Srfvalue of 36 forreinforced masonry. This

    in turn allows for the largestwalls to be built using the thinnest

    masonry option. Suitable for LOADBEARING applications.Grout strength to be 20MPa. 240 minute insulation FRL as

    fully grout filled blockwork.

    Step 2

    Select an appropriate Boral Masonry Unit based on

    the FRL Insulation Requirement.

    The third figure in an FRL rating is the Insulation.

    Table C1 provides the Insulation values for the various

    Boral units.

    Check the Materials Attributes (see notes below the table)

    to ensure the selection is fit for its purpose.

    Worked Example

    From Table C1, the following units all achieve 240 minutes

    FRL for Insulation:

    Scoria Blend 15.401, 20.401, and 11.119F

    Calcium Silicate Basalt 165S119B

    Grouted Masonry (190mm) 20.42and 20.91.

    If the wall is non loadbearing, the use of Scoria Blend may

    be the more cost effective.

    Table C1 FRL Insulation Values for Boral Masonry Units (New South Wales)

    Fire INSULATION FRL (minutes)

    Test 30 60 90 120 180 240 Material Product Code/TypeYes FireBlock/FireBrick (F) Scoria Blend 10.201; 15.201; 20.201; 9.162F

    Yes FireBlock/FireBrick (F) Scoria Blend 10.331; 15.301; 20.301

    Yes FireBlock/FireBrick (F) Scoria Blend 15.401; 20.401; 11.119F

    Yes FireLight (FL) 10.01FL; 15.01 FL: 20.01FL; 9.162FL

    Yes FireLight (FL) 10.119FL; 11.162FL

    d.t.s. Basalt-Concrete (B) 15.01B

    d.t.s. +render Basalt-Concrete (B) 10.01B; 10.31B; 20.01B; 9.162B

    d.t.s. Basalt-Concrete (B) 10.119B

    d.t.s. +render Basalt-Concrete (B) 11.119B + other 110mm cored

    d.t.s. Calcium Silicate Basalt M3H119B; + other 90mm

    d.t.s. Calcium Silicate Basalt S3H119B; + other 110mm

    d.t.s. Calcium Silicate Basalt 140S119B; + other 140mm

    d.t.s. Calcium Silicate Basalt 165S119B

    d.t.s. DesignerBlockand Standard GreyConcrete 15.01.

    d.t.s. +render DesignerBlockand Standard GreyConcrete 10.01; 10.31; 20.01

    d.t.s. +render Grouted Masonry 140mm 15.42; 15.91

    d.t.s. Grouted Masonry 190mm 20.42; 20.91

    d.t.s. deemed to satisfy. +render = 10mm render both faces

    * Product Codes listed are for the Full Size Unit. Fractional size blocks in the same range have the same FRL rating.

  • 8/10/2019 Bor11999 Nsw Manual Bk1 Structural Fire Accustic

    31/72

    BOOK

    PAGE

    1

    Fire Design

    C7

    Step 3

    Check the Structural Adequacy of the selected units.

    The Slenderness ratio (Srf) of a fire rated wall is calculated

    as per AS3700 : 2001, Clause 6.3.2.2, and must not exceedthe Srfvalues given in AS3700 or calculated from Fire Tests.

    Table C2provides the maximum Srfvalues forBoral masonry

    units.

    Worked Example

    The calculated Srfvalue for your wall design MUST NOT

    EXCEED the value from the accompanying table.

    See following page for an explanation on using the BoralSrf graphs to assist preliminary selection.

    eg. Scoria Blend required to provide Structural Adequacy

    for 240 minutes has an Srf= 24. (refer to Table C2 below).

    Also refer to the previous explanation and AS3700 for Srf

    calculation methods.

    In this example, the 6 x 6m wall,with lateral restraint on 4

    sides, 190mm thick has an Srf = 19.2. as per formula

    6.3.2.2 (3).

    Alternative is 20.91 with reinforcement and core filling,

    however,as the wall in this example is non-loadbearing, the

    Scoria Blend 20.401 is the more economical solution.

    SrfValues

    Fire FRL (minutes) for Structural AdequacyTest 30 60 90 120 180 240 Material Condition of use

    Yes 25.9 25.9 25.9 25.9 25.9 24 Scoria Blend (F) FireBrick/FireBlock Non loadbearing ONLY

    Yes 20.4 20.4 20.4 20.4 20.4 20.4 Custom Scoria Blend (S) Loadbg 110mm made to order

    Yes 29 29 26.9 24.9 22.2 20.3 FireLight (FL) Non loadbearing ONLY

    d.t.s. 25 22.5 21 20 18 17 Basalt-Concrete (B) Any

    d.t.s. 25 22.5 21 20 18 17 Calcium Silicate-Basalt Any

    d.t.s. 19.5 18 17 16 15.5 15 Standard Grey and Designer Block Any

    d.t.s. 36 36 36 36 36 36 Reinforced & Grouted Masonry Any

    d.t.s.= deemed to satisfy, as per AS3700 : 2001,Table 6.1.

    Table C2 Maximum Srf Values for Boral Masonry Units

  • 8/10/2019 Bor11999 Nsw Manual Bk1 Structural Fire Accustic

    32/72

    BOOK

    PAGE

    1

    Fire Design

    C8

    IMPORTANT

    The following selection graphs are based on Specific

    Products manufactured at New South Wales BoralPlants. Should these units be sourced from other plants,

    the specification should be checked with the respective

    supply plant.

    To assist with the preliminary selection of Boral masonry

    units for fire rated walls, a graphical selection method based

    on Srfvalues has been developed.

    The following pages provide graphs and tables fora selection

    of Boral masonry units where at least one end of the wall has

    lateral restraint.

    Additional tables are provided forwalls with no end restraint

    and for reinforced/grout filled masonry,following these graphs.

    Boral Structural Adequacy Selection Graphs & Tables

    SUPPORT

    SUPPORT

    SUPPORT

    SUPPORT

    9

    8

    7

    6

    5

    4

    3

    2

    1

    0

    0 1 2 3 4 5 6 7 8 9

    Structural Adequacy240 minutes FRL

    Laterally supported

    both ends and top

    Length of wall between supports (m)

    Heightofwallbetweensu

    pports(m)

    140mm

    190mm

    110mm

    90mm

    LeafThickness

    Worked Example

    1. Select the appropriate masonry unit material.

    2. Select the appropriate page with Structural

    Adequacyforthe required minutes. (240 minutes

    for this example).

    3. Select the appropriate graph for the chosen wall

    restraint (support) criteria. (Support on both sides,

    top and bottom for this example).

    4. Plot the intersection of the Wall Height and the

    Wall Length on the graph. (For this example 6m

    height x 6m length).

    5. The result MUST FALL BELOW the coloured line

    indicated for the chosen masonry unit thickness.

    In this example, the result is above the line for

    140mm units butbelow the line for190mm units.

    Therefore 190mm units would be suitable. (140mm

    units would not be suitable for this example).

    Scoria-Blend

    How to Use the Boral Structural Adequacy FRL Graphs

    Product Group FRL Minutes (Structural Adequacy) Page

    NSW Firebrick/Fireblock Scoria Blend Masonry (F) 60 180 C9

    NSW Firebrick/Fireblock Scoria Blend Masonry (F) 240 C10

    FireLight Brick (FL) 90 C11

    FireLight Brick (FL) 120 C12

    Basalt Concrete Masonry (B) 60 C13

    Basalt Concrete Masonry (B) 90 C14

    Calcium Silicate Basalt Masonry 60 C15

    Calcium Silicate Basalt Masonry 90 C16

    Calcium Silicate Basalt Masonry 120 C17

    Calcium Silicate Basalt Masonry 180 C18

    Standard Grey and Designer Block 60 C19

    Standard Grey and Designer Block 90 C20

    Walls Restrained at Top (Unrestrained Ends) 60 240 C21

    Reinforced Masonry Walls 60 240 C22

    Index to Structural Adequacy FRL Graphs & Tables

  • 8/10/2019 Bor11999 Nsw Manual Bk1 Structural Fire Accustic

    33/72

    BOOK

    PAGE

    1

    Fire Design

    C9

    SUPPORT

    SUPPORT

    SUPPORT

    9

    8

    7

    6

    5

    4

    3

    2

    1

    0

    0 1 2 3 4 5 6 7 8 9

    Structural Adequacy

    60 180 minutes FRL

    Laterally supported

    one end and top

    Length of wall between supports (m)

    Heightofwallbetweensupports(m)

    140mm

    190mm

    110mm

    90mm

    LeafThickness

    100mm

    SUPPORTSUPPORT

    9

    8

    7

    6

    5

    4

    3

    2

    1

    0

    0 1 2 3 4 5 6 7 8 9

    Structural Adequacy

    60 180 minutes FRL

    Laterally supported

    one end top free

    Length of wall between supports (m)

    Heightofwallbetweensupports(m

    )

    140mm190mm

    110mm90/100mm

    LeafThickness

    SUPPORT

    SUPPORT

    SUPPORT

    SUPPORT

    9

    8

    7

    6

    5

    4

    3

    2

    1

    0

    0 1 2 3 4 5 6 7 8 9

    Structural Adequacy

    60 180 minutes FRL

    Laterally supported

    both ends and top

    Length of wall between supports (m)

    Heightofwallbetweensupp

    orts(m)

    140mm

    190mm

    110mm100mm90mm

    LeafThickness

    SUPPORTSUPPORT

    SUPPORT

    9

    8

    7

    6

    5

    4

    3

    2

    1

    0

    0 1 2 3 4 5 6 7 8 9

    Structural Adequacy

    60 180 minutes FRL

    Laterally supported

    both ends, top free

    Length of wall between supports (m)

    Heightofwallbetweensupports(m)

    140mm

    190mm

    110mm100mm90mm

    LeafThickness

    NSW FireBrick/FireBlock Scoria Blend Masonry (F) - Srf = 25.9

    Structural Adequacy for 60-180 minutes Fire Resistant Level (FRL)

  • 8/10/2019 Bor11999 Nsw Manual Bk1 Structural Fire Accustic

    34/72

    BOOK

    PAGE

    1

    Fire Design

    C10

    SUPPORT

    SUPPORT

    SUPPORT

    SUPPORT

    9

    8

    7

    6

    5

    4

    3

    2

    1

    0

    0 1 2 3 4 5 6 7 8 9

    Structural Adequacy

    240 minutes FRL

    Laterally supported

    both ends and top

    Length of wall between supports (m)

    Heightofwallbetweensupp

    orts(m)

    140mm

    190mm

    110mm

    90mm

    LeafThickness

    100mm

    SUPPORTSUPPORT

    SUPPORT

    9

    8

    7

    6

    5

    4

    3

    2

    1

    0

    0 1 2 3 4 5 6 7 8 9

    Structural Adequacy

    240 minutes FRL

    Laterally supported

    both ends, top free

    Length of wall between supports (m)

    Heightofwallbetweensupports(m)

    140mm

    190mm

    110mm

    90mm

    LeafThickness

    100mm

    SUPPORT

    SUPPORT

    SUPPORT

    9

    8

    7

    6

    5

    4

    3

    2

    1

    0

    0 1 2 3 4 5 6 7 8 9

    Structural Adequacy

    240 minutes FRL

    Laterally supported

    one end and top

    Length of wall between supports (m)

    Heightofwallbetweensupports(m)

    140mm

    190mm

    110mm

    90mm

    LeafThickness

    100mm

    SUPPORTSUPPORT

    9

    8

    7

    6

    5

    4

    3

    2

    1

    0

    0 1 2 3 4 5 6 7 8 9

    Structural Adequacy

    240 minutes FRL

    Laterally supported

    one end top free

    Length of wall between supports (m)

    Heightofwallbetweensupports(m

    )

    140mm190mm

    110mm90/100mm

    LeafThickness

    NSW FireBrick/FireBlock Scoria Blend Masonry (F) - Srf = 24

    Structural Adequacy for 240 minutes Fire Resistant Level (FRL)

  • 8/10/2019 Bor11999 Nsw Manual Bk1 Structural Fire Accustic

    35/72

    BOOK

    PAGE

    1

    Fire Design

    C11

    SUPPORT

    SUPPORT

    SUPPORT

    SUPPORT

    9

    8

    7

    6

    5

    4

    3

    2

    1

    0

    0 1 2 3 4 5 6 7 8 9

    Structural Adequacy

    90 minutes FRL

    Laterally supported

    both ends and top

    Length of wall between supports (m)

    Heightofwallbetweensuppo

    rts(m)

    140mm

    190mm

    110mm

    90mm100mm

    LeafThickness

    SUPPORTSUPPORT

    SUPPORT

    9

    8

    7

    6

    5

    4

    3

    2

    1

    0

    0 1 2 3 4 5 6 7 8 9

    Structural Adequacy

    90 minutes FRL

    Laterally supported

    both ends, top free

    Length of wall between supports (m)

    Heightofwallbetweensuppo

    rts(m)

    140mm

    190mm

    110mm

    90mm100mm

    LeafThickness

    SUPPORT

    SUPPORT

    SUPPORT

    9

    8

    7

    6

    5

    4

    3

    2

    1

    0

    0 1 2 3 4 5 6 7 8 9

    Structural Adequacy

    90 minutes FRL

    Laterally supported

    one end and top

    Length of wall between supports (m)

    Heightofwallbetweensupports(m

    )

    140mm

    190mm

    110mm100mm90mm

    LeafThickness

    SUPPORTSUPPORT

    9

    8

    7

    6

    5

    4

    3

    2

    1

    0

    0 1 2 3 4 5 6 7 8 9

    Structural Adequacy

    90 minutes FRL

    Laterally supported

    one end, top free

    Length of wall between supports (m)

    Heightofwallbetweensupports(m

    )

    140mm190mm

    110mm90/100mm

    LeafThickness

    FireLight Bricks (FL) - Srf = 26.9

    Structural Adequacy for 90 minutes Fire Resistant Level (FRL)

  • 8/10/2019 Bor11999 Nsw Manual Bk1 Structural Fire Accustic

    36/72

    BOOK

    PAGE

    1

    Fire Design

    C12

    FireLight Bricks (FL) - Srf = 24.9

    Structural Adequacy for 120 minutes Fire Resistant Level (FRL)

    SUPPORT

    SUPPORT

    SUPPORT

    SUPPORT

    9

    8

    7

    6

    5

    4

    3

    2

    1

    0

    0 1 2 3 4 5 6 7 8 9

    Structural Adequacy

    120 minutes FRL

    Laterally supported

    both ends and top

    Length of wall between supports (m)

    Heightofwallbetweensupports(m)

    140mm

    190mm

    110mm

    100mm90mm

    LeafThickness

    SUPPORTSUPPORT

    SUPPORT

    9

    8

    7

    6

    5

    4

    3

    2

    1

    0

    0 1 2 3 4 5 6 7 8 9

    Structural Adequacy

    120 minutes FRL

    Laterally supported

    both ends, top free

    Length of wall between supports (m)

    Heightofwallbetweensuppo

    rts(m)

    140mm

    190mm

    110mm100mm90mm

    LeafThickness

    SUPPORT

    SUPPORT

    SUPPORT

    9

    8

    7

    6

    5

    4

    3

    2

    1

    0

    0 1 2 3 4 5 6 7 8 9

    Structural Adequacy

    120 minutes FRL

    Laterally supported

    one end and top

    Length of wall between supports (m)

    Heightofwallbetweensupports(m

    )

    140mm

    190mm

    110mm100mm90mm

    LeafThickness

    SUPPORTSUPPORT

    9

    8

    7

    6

    5

    4

    3

    2

    1

    0

    0 1 2 3 4 5 6 7 8 9

    Structural Adequacy

    120 minutes FRL

    Laterally supported

    one end top free

    Length of wall between supports (m)

    Heightofwallbetweensupports(m

    )

    140mm190mm

    110mm90/100mm

    LeafThickness

  • 8/10/2019 Bor11999 Nsw Manual Bk1 Structural Fire Accustic

    37/72

    BOOK

    PAGE

    1

    Fire Design

    C13

    Basalt-Concrete Masonry (B) Srf = 22.5

    Structural Adequacy for 60 minutes Fire Resistant Level (FRL)

    SUPPORT

    SUPPORT

    SUPPORT

    SUPPORT

    9

    8

    7

    6

    5

    4

    3

    2

    1

    0

    0 1 2 3 4 5 6 7 8 9

    Structural Adequacy60 minutes FRL

    Laterally supported

    both ends and top

    Length of wall between supports (m)

    Heightofwallbetweensuppo

    rts(m)

    140mm

    190mm

    110mm100mm90mm

    LeafThickness

    SUPPORTSUPPORT

    SUPPORT

    9

    8

    7

    6

    5

    4

    3

    2

    1

    0

    0 1 2 3 4 5 6 7 8 9

    Structural Adequacy

    60 minutes FRL

    Laterally supported

    both ends, top free

    Length of wall between supports (m)

    Heightofwallbetweensuppo

    rts(m)

    140mm

    190mm

    110mm90mm

    LeafThickness

    SUPPORT

    SUPPORT

    SUPPORT

    9

    8

    7

    6

    5

    4

    3

    2

    1

    0

    0 1 2 3 4 5 6 7 8 9

    Structural Adequacy60 minutes FRL

    Laterally supported

    one end and top

    Length of wall between supports (m)

    Heightofwallbetweensupports(m)

    140mm

    190mm

    110mm100mm90mm

    LeafThickness

    SUPPORTSUPPORT

    9

    8

    7

    6

    5

    4

    3

    2

    1

    0

    0 1 2 3 4 5 6 7 8 9

    Structural Adequacy

    60 minutes FRL

    Laterally supported

    one end, top free

    Length of wall between supports (m)

    Heightofwallbetweensupports(m)

    140mm190mm

    110mm90mm

    LeafThickness

  • 8/10/2019 Bor11999 Nsw Manual Bk1 Structural Fire Accustic

    38/72

    BOOK

    PAGE

    1

    Fire Design

    C14

    Basalt-Concrete Masonry (B) - Srf = 21

    Structural Adequacy for 90 minutes Fire Resistant Level (FRL)

    SUPPORT

    SUPPORT

    SUPPORT

    SUPPORT

    9

    8

    7

    6

    5

    4

    3

    2

    1

    0

    0 1 2 3 4 5 6 7 8 9

    Structural Adequacy

    90 minutes FRL

    Laterally supported

    both ends and top

    Length of wall between supports (m)

    Heightofwallbetweensuppo

    rts(m)

    140mm

    190mm

    110mm100mm90mm

    LeafThickness

    SUPPORTSUPPORT

    SUPPORT

    9

    8

    7

    6

    5

    4

    3

    2

    1

    0

    0 1 2 3 4 5 6 7 8 9

    Structural Adequacy

    90 minutes FRL

    Laterally supported

    both ends, top free

    Length of wall between supports (m)

    Heightofwallbetweensuppo

    rts(m)

    140mm

    190mm

    110mm90mm

    LeafThickness

    SUPPORT

    SUPPORT

    SUPPORT

    9

    8

    7

    6

    5

    4

    3

    2

    1

    0

    0 1 2 3 4 5 6 7 8 9

    Structural Adequacy90 minutes FRL

    Laterally supported

    one end and top

    Length of wall between supports (m)

    Heightofwallbetweensupports(m)

    140mm

    190mm

    110mm100mm90mm

    LeafThickness

    SUPPORTSUPPORT

    9

    8

    7

    6

    5

    4

    3

    2

    1

    0

    0 1 2 3 4 5 6 7 8 9

    Structural Adequacy

    90 minutes FRL

    Laterally supported

    one end, top free

    Length of wall between supports (m)

    Heightofwallbetweensupports(m)

    140mm190mm

    110mm90mm

    LeafThickness

  • 8/10/2019 Bor11999 Nsw Manual Bk1 Structural Fire Accustic

    39/72

    BOOK

    PAGE

    1

    Fire Design

    C15

    SUPPORT

    SUPPORT

    SUPPORT

    SUPPORT

    9

    8

    7

    6

    5

    4

    3

    2

    1

    0

    0 1 2 3 4 5 6 7 8 9

    Structural Adequacy

    60 minutes FRL

    Laterally supported

    both ends and top

    Length of wall between supports (m)

    Heightofwallbetweensupp

    orts(m)

    140mm

    110mm

    90mm

    LeafThickness

    SUPPORTSUPPORT

    SUPPORT

    9

    8

    7

    6

    5

    4

    3

    2

    1

    0

    0 1 2 3 4 5 6 7 8 9

    Structural Adequacy

    60 minutes FRL

    Laterally supported

    both ends, top free

    Length of wall between supports (m)

    Heightofwallbetweensupports(m)

    140mm110mm90mm

    LeafThickness

    SUPPORT

    SUPPORT

    SUPPORT

    9

    8

    7

    6

    5

    4

    3

    2

    1

    0

    0 1 2 3 4 5 6 7 8 9

    Structural Adequacy

    60 minutes FRL

    Laterally supported

    one end and top

    Length of wall between supports (m)

    Heightofwallbetweensupports(m)

    140mm

    110mm

    90mm

    LeafThickness

    SUPPORTSUPPORT

    9

    8

    7

    6

    5

    4

    3

    2

    1

    0

    0 1 2 3 4 5 6 7 8 9

    Structural Adequacy

    60 minutes FRL

    Laterally supported

    one end, top free

    Length of wall between supports (m)

    Heightofwallbetweensupports(m

    )

    140mm110mm90mm

    LeafThickness

    Calcium Silicate-Basalt Masonry (Boral Calsil) - Srf = 22.5

    Structural Adequacy for 60 minutes Fire Resistant Level (FRL)

  • 8/10/2019 Bor11999 Nsw Manual Bk1 Structural Fire Accustic

    40/72

    BOOK

    PAGE

    1

    Fire Design

    C16

    SUPPORT

    SUPPORT

    SUPPORT

    SUPPORT

    9

    8

    7

    6

    5

    4

    3

    2

    1

    0

    0 1 2 3 4 5 6 7 8 9

    Structural Adequacy

    90 minutes FRL

    Laterally supported

    both ends and top

    Length of wall between supports (m)

    Heightofwallbetweensupp

    orts(m)

    140mm

    110mm

    90mm

    LeafThickness

    SUPPORTSUPPORT

    SUPPORT

    9

    8

    7

    6

    5

    4

    3

    2

    1

    0

    0 1 2 3 4 5 6 7 8 9

    Structural Adequacy

    90 minutes FRL

    Laterally supported

    both ends, top free

    Length of wall between supports (m)

    Heightofwallbetweensupports(m)

    140mm110mm90mm

    LeafThickness

    SUPPORT

    SUPPORT

    SUPPORT

    9

    8

    7

    6

    5

    4

    3

    2

    1

    0

    0 1 2 3 4 5 6 7 8 9

    Structural Adequacy

    90 minutes FRL

    Laterally supported

    one end and top

    Length of wall between supports (m)

    Heightofwallbetweensupports(m)

    140mm

    110mm

    90mm

    LeafThickness

    SUPPORTSUPPORT

    9

    8

    7

    6

    5

    4

    3

    2

    1

    0

    0 1 2 3 4 5 6 7 8 9

    Structural Adequacy

    90 minutes FRL

    Laterally supported

    one end, top free

    Length of wall between supports (m)

    Heightofwallbetweensupports(m

    )

    140mm110mm90mm

    LeafThickness

    Calcium Silicate-Basalt Masonry (Boral Calsil) - Srf = 21

    Structural Adequacy for 90 minutes Fire Resistant Level (FRL)

  • 8/10/2019 Bor11999 Nsw Manual Bk1 Structural Fire Accustic

    41/72

    BOOK

    PAGE

    1

    Fire Design

    C17

    SUPPORT

    SUPPORT

    SUPPORT

    SUPPORT

    9

    8

    7

    6

    5

    4

    3

    2

    1

    0

    0 1 2 3 4 5 6 7 8 9

    Structural Adequacy

    120 minutes FRL

    Laterally supported

    both ends and top

    Length of wall between supports (m)

    Heightofwallbetweensupp

    orts(m)

    140mm

    110mm

    LeafThickness

    SUPPORTSUPPORT

    SUPPORT

    9

    8

    7

    6

    5

    4

    3

    2

    1

    0

    0 1 2 3 4 5 6 7 8 9

    Structural Adequacy

    120 minutes FRL

    Laterally supported

    both ends, top free

    Length of wall between supports (m)

    Heightofwallbetweensupports(m)

    140mm110mm

    LeafThickness

    SUPPORT

    SUPPORT

    SUPPORT

    9

    8

    7

    6

    5

    4

    3

    2

    1

    0

    0 1 2 3 4 5 6 7 8 9

    Structural Adequacy

    120 minutes FRL

    Laterally supported

    one end and top

    Length of wall between supports (m)

    Heightofwallbetweensupports(m)

    140mm

    110mm

    LeafThickness

    SUPPORTSUPPORT

    9

    8

    7

    6

    5

    4

    3

    2

    1

    0

    0 1 2 3 4 5 6 7 8 9

    Structural Adequacy

    120 minutes FRL

    Laterally supported

    one end, top free

    Length of wall between supports (m)

    Heightofwallbetweensupports(m

    )

    140mm110mm

    LeafThickness

    Calcium Silicate-Basalt Masonry (Boral Calsil) - Srf = 20

    Structural Adequacy for 120 minutes Fire Resistant Level (FRL)

  • 8/10/2019 Bor11999 Nsw Manual Bk1 Structural Fire Accustic

    42/72

    BOOK

    PAGE

    1

    Fire Design

    C18

    SUPPORT

    S