best practices: installing new radar tank gauging
TRANSCRIPT
Rosemount Tank Radar AB Confidential
Best Practices: Installing New Radar Tank Gauging for level and overfilling on all type of tanks with all type of products
Hans Manner
Nicolas Odru
[File Name or Event] Emerson Confidential 27-Jun-01, Slide 2 Rosemount Tank Radar AB Confidential 2
Best Practices Installing New Radar Tank Gauging
Industry Trends
Engineering standards and guidelines
What equipment do I need?
How do I get it installed on my tank?
How do I get the readings in the control room?
Safety & Overfill Prevention
[File Name or Event] Emerson Confidential 27-Jun-01, Slide 3 Rosemount Tank Radar AB Confidential 3
Complience to Standards
API standards
– 3.1B Automatic Tank Gauging
– 7 Temperature Measurements
– 3.3 LPG measurements
– 3.6 Hybrid Measurements
– 2350 Overfill Protection
[File Name or Event] Emerson Confidential 27-Jun-01, Slide 4 Rosemount Tank Radar AB Confidential 4
Accuracy Performance
Pattern approvals for Custody Transfer Accuracy
OIML R85:2008
International Organization of Legal Metrology
[File Name or Event] Emerson Confidential 27-Jun-01, Slide 5 Rosemount Tank Radar AB Confidential
Industry Trends
Radar
Continuous
Redundancy
Safety
IEC 61508
API 2350
Wireless
Openness
Internet
Mechanical
Point Switch
Closed systems
[File Name or Event] Emerson Confidential 27-Jun-01, Slide 6 Rosemount Tank Radar AB Confidential 6
Tank Equipment
[File Name or Event] Emerson Confidential 27-Jun-01, Slide 7 Rosemount Tank Radar AB Confidential
Tank Equipment
7
[File Name or Event] Emerson Confidential 27-Jun-01, Slide 8 Rosemount Tank Radar AB Confidential
Tank Equipment – Fixed Roof Tank
8
[File Name or Event] Emerson Confidential 27-Jun-01, Slide 9 Rosemount Tank Radar AB Confidential
Tank Equipment – Floating Roof Tank
9
[File Name or Event] Emerson Confidential 27-Jun-01, Slide 10 Rosemount Tank Radar AB Confidential 10
Tank Equipment
[File Name or Event] Emerson Confidential 27-Jun-01, Slide 11 Rosemount Tank Radar AB Confidential
Tank Equipment
11
[File Name or Event] Emerson Confidential 27-Jun-01, Slide 12 Rosemount Tank Radar AB Confidential 12
Where to install the equipment on the tank?
Look for
– Man ways
– Other nozzles
– Gauge hatches
– Still Pipes
[File Name or Event] Emerson Confidential 27-Jun-01, Slide 13 Rosemount Tank Radar AB Confidential 13
Where to install the Tank Equipment?
Manway 20” Nozzle 8”
Nozzles 2”, 4”, 8” Gauge hatch
[File Name or Event] Emerson Confidential 27-Jun-01, Slide 14 Rosemount Tank Radar AB Confidential 14
Where to install the Tank Equipment?
Radar
Temp Sensor
On a 24” Man Way
[File Name or Event] Emerson Confidential 27-Jun-01, Slide 15 Rosemount Tank Radar AB Confidential 15
Use existing still pipes
[File Name or Event] Emerson Confidential 27-Jun-01, Slide 16 Rosemount Tank Radar AB Confidential 16
Use the existing Still Pipe
[File Name or Event] Emerson Confidential 27-Jun-01, Slide 17 Rosemount Tank Radar AB Confidential 17
Don’t worry about dirty and slotted pipes
[File Name or Event] Emerson Confidential 27-Jun-01, Slide 18 Rosemount Tank Radar AB Confidential 18
Where to install the Tank Equipment?
Still Pipes fitted in existing access hatch
[File Name or Event] Emerson Confidential 27-Jun-01, Slide 19 Rosemount Tank Radar AB Confidential 19
Where to install the Tank Equipment?
Still Pipe fitted in existing access hatch
[File Name or Event] Emerson Confidential 27-Jun-01, Slide 20 Rosemount Tank Radar AB Confidential 20
Where to install the Tank Gauge
What does API Ch 3.1B say?
– Roof mounting
• Close to the tank wall to avoid roof flexing influence
– Still pipe
• Slotted
• Fixed at the bottom end
[File Name or Event] Emerson Confidential 27-Jun-01, Slide 21 Rosemount Tank Radar AB Confidential 21
Where to install the Temperature Sensor?
Same location as the Radar
Separate nozzle
Still pipe arrangements
Floating Roof penetration options
The Temp Sensor can be combined with a Water bottom sensor
Transmitter
Temp sensor
[File Name or Event] Emerson Confidential 27-Jun-01, Slide 22 Rosemount Tank Radar AB Confidential 22
Temperature Measurement
What does Standards say?
– Use RTD type of sensor (Pt100)
– Use at least 6 sensors on tanks > 50 ft
[File Name or Event] Emerson Confidential 27-Jun-01, Slide 23 Rosemount Tank Radar AB Confidential 23
Where to install the Temperature Sensor?
Same location as the Radar
Fixed Roof tank
[File Name or Event] Emerson Confidential 27-Jun-01, Slide 24 Rosemount Tank Radar AB Confidential 24
Where to install the Temperature Sensor?
Same location as the Radar
Floating Roof Tank
[File Name or Event] Emerson Confidential 27-Jun-01, Slide 25 Rosemount Tank Radar AB Confidential 25
Where to install the Temperature Sensor?
Floating Roof Tank
Roof
penetration
thru a rubber
gasket
Support and
cabling at the
platform level
[File Name or Event] Emerson Confidential 27-Jun-01, Slide 26 Rosemount Tank Radar AB Confidential 26
Where to install the Pressure Sensor (Density) ?
Lower end of the tank
Existing nozzles
[File Name or Event] Emerson Confidential 27-Jun-01, Slide 27 Rosemount Tank Radar AB Confidential 27
Where to install the Local Readout?
At the gauge hatch
At grade level
By the road side
Or at all of the above
[File Name or Event] Emerson Confidential 27-Jun-01, Slide 28 Rosemount Tank Radar AB Confidential 28
Local Readout
At Grade Level
[File Name or Event] Emerson Confidential 27-Jun-01, Slide 29 Rosemount Tank Radar AB Confidential 29
Local Readout
Back lit
[File Name or Event] Emerson Confidential 27-Jun-01, Slide 30 Rosemount Tank Radar AB Confidential 30
Where to install the Local Readout?
By the road side
Drive-thru readings
Day and night
[File Name or Event] Emerson Confidential 27-Jun-01, Slide 31 Rosemount Tank Radar AB Confidential 31
How to connect a new system to the Control Room
Use existing cabling
Emulation
Minimized conduit free new cabling
Wireless
[File Name or Event] Emerson Confidential 27-Jun-01, Slide 32 Rosemount Tank Radar AB Confidential
32
Emulation: Remove Old, Install New Plug n´ Play
Disconnect the old cabling Remove the old Gauge
Mount the radar antenna Mount the new Gauge
and connect the wiring
Done!
[File Name or Event] Emerson Confidential 27-Jun-01, Slide 33 Rosemount Tank Radar AB Confidential 33
How to connect a new system to the Control Room
OLD NEW
[File Name or Event] Emerson Confidential 27-Jun-01, Slide 34 Rosemount Tank Radar AB Confidential 34
How to connect a new system to the Control Room
Minimized new cabling
Intrinsically Safe
Conduit Free
[File Name or Event] Emerson Confidential 27-Jun-01, Slide 35 Rosemount Tank Radar AB Confidential 35
How to connect a new system to the Control Room
Minimized new cabling
LAX Airport
One pair
cable
Intrinsically
Safe
[File Name or Event] Emerson Confidential 27-Jun-01, Slide 36 Rosemount Tank Radar AB Confidential 36
How to connect a new system to the Control Room
Wireless
[File Name or Event] Emerson Confidential 27-Jun-01, Slide 37 Rosemount Tank Radar AB Confidential 37
How to connect a new system to the Control Room
Wireless
[File Name or Event] Emerson Confidential 27-Jun-01, Slide 38 Rosemount Tank Radar AB Confidential 38
How to connect a new system to the Control Room
Wireless
[File Name or Event] Emerson Confidential 27-Jun-01, Slide 39 Rosemount Tank Radar AB Confidential 39
How to connect a new system to the Control Room
Wireless
Well proven
On 2500+ tanks
Robust
Safe
IEC 62591 standard
[File Name or Event] Emerson Confidential 27-Jun-01, Slide 40 Rosemount Tank Radar AB Confidential
Overfill Protection with Rosemount 2160 Wireless Vibrating Forks LeveL Switch
No wires No moving parts
No re-calibration Long power module life
Self Checking
condition monitoring
Virtually unaffected by
process conditions
9 years at 1 minute update rate
Min update rate of 1s for control
Steam,
vapors, dust
Density
changes
Temperature
changes
[File Name or Event] Emerson Confidential 27-Jun-01, Slide 41 Rosemount Tank Radar AB Confidential
Instrument Advanced Diagnostics- Health/Self Check Diagnostics The 2160 continuously performs instrument health diagnostics to self-
check the condition of the fork and sensor
Control room can be alerted to emerging issues allowing preventative maintenance to be scheduled- avoid process down-time
2160 Frequency Monitoring : interface detection between oil/water, wet sand/liquid...
Fault conditions detected Standard Enhanced
Process memory failure
External damage to fork
Internal wire disconnect or break
Internal damage to sensor
Excessive corrosion to fork
[File Name or Event] Emerson Confidential 27-Jun-01, Slide 42 Rosemount Tank Radar AB Confidential
Overfill Protection with Rosemount 3308 Wireless Guided Wave Radar
No wires No moving parts
No re-calibration Long power module life
Single probe handles
coating better
Virtually unaffected by
process conditions
9 years at 1 minute update rate
Steam,
vapors, dust
Density
changes
Temperature
changes
[File Name or Event] Emerson Confidential 27-Jun-01, Slide 43 Rosemount Tank Radar AB Confidential
Proactive Maintenance with Advanced Diagnostics Signal Quality Metrics alerts potential measurement
problems, e.g. caused by probe coating
Field
Time
Sig
nal Q
ualit
y
Control room
Level PV
Signal quality
Low
High
[File Name or Event] Emerson Confidential 27-Jun-01, Slide 44 Rosemount Tank Radar AB Confidential
Rosemount Level Wireless 2160 Fork Switch & 3308 Guided Wave Radar
Inaccessible or uneconomic alarms:
– Fast installation of additional instruments
Gain access to advanced diagnostics:
– Self Check Diagnostics
– Signal Quality Metrics
Integrate more information into any control room host without new I/O:
– Eliminate costly cable runs
– System integration
[File Name or Event] Emerson Confidential 27-Jun-01, Slide 45 Rosemount Tank Radar AB Confidential 45
Readout
[File Name or Event] Emerson Confidential 27-Jun-01, Slide 46 Rosemount Tank Radar AB Confidential 46
Readout
[File Name or Event] Emerson Confidential 27-Jun-01, Slide 47 Rosemount Tank Radar AB Confidential 47
Extended Readout
Intranet
Internet
Portable devices
[File Name or Event] Emerson Confidential 27-Jun-01, Slide 48 Rosemount Tank Radar AB Confidential 48
Get Tank info distributed
Open protocols
OPC
Modbus
WebServer
[File Name or Event] Emerson Confidential 27-Jun-01, Slide 49 Rosemount Tank Radar AB Confidential 49
Overfill Safety – Tank Gauging plays an important part
Passive protection layer
Emergency response layer
Process control layer Process
Shutdown
Active protection layer
Process
Value Process control layer
Safety layer Emergency
Shut Down
Time In Use
[File Name or Event] Emerson Confidential 27-Jun-01, Slide 50
Why overfill prevention is important for Industry ? EU Safety and Environmental directives
are more and more restrictive :
– Member States are obliged to transpose it into a national law within the set deadline
– Directive 96/61/EC on integrated pollution prevention and control
– Directive 96/82/EC on the control of major accident hazards involving dangerous substance
Tank overfill is an important concern :
– Industry have to improve the Safety of their sites to reduce pollution risks
Industrial requests for overfill
prevention device applications
have risen in recent years
[File Name or Event] Emerson Confidential 27-Jun-01, Slide 51
Buncefield oil storage, UK Dec. 2005
Overfill of fuel storage tank
Bad configuration and faulty independent high level switch on floating roof
20 large storage fuel tanks took fire
Over 40 people injured
UK Health and safety Executive investigation resulted in 25 recommendations on fuel storage sites
[File Name or Event] Emerson Confidential 27-Jun-01, Slide 52
Tank Overfill Prevention : Key Points
Detection should be independant of the primary level measurement device and separate failure alarm is preferable
Proof testing is required : manual test or internal diagnostics can be used
Redundancy with different technologies is a common strategy for critical level detection
[File Name or Event] Emerson Confidential 27-Jun-01, Slide 53
Tank Overfill Prevention : Customer challenge
Customers need to increase the Safety of their existing installation :
– More information needed for continual supervision in the control room (less operators round)
– Additional independent high level alarm on your primary level measurement
– Remote tank locations / No local power supply
[File Name or Event] Emerson Confidential 27-Jun-01, Slide 54
Single Point for Overfill Protection
Advantages :
Independent safety system
Not affected by process changes
Different types of on/off alarm output available
Functionality is less dependant on configuration, mechanical installation and start up
To be considered :
≈ One device for each level alarm
≈ Power supply needed for electronics
≈ No separate fault signal output
Vibrating Forks is one of the most common technology used in process industry
[File Name or Event] Emerson Confidential 27-Jun-01, Slide 55
Rosemount Vibrating Forks Portfolio
OEM Core Premier
Advanced Health Diagnostic
PlantWeb alerts
Direct load,
PNP,
DPDT Relay, 8/16
IS NAMUR
Direct Load,
PNP/PLC
Direct load,
PNP, 12V
Relay, 8/16
IS NAMUR
Wireless HART
-70 +260°C
SIL 2 High & Low Level
-70 +260°C
Diagnostic
Diagnostic
-40 +180°C
-40 +150°C
-40 +150°C
[File Name or Event] Emerson Confidential 27-Jun-01, Slide 56
Basic or Advanced : What is the difference ?
Forks
Frequency Circuit
Output Circuit
Forks
Frequency Circuit
Output Circuit
Self Check Diagnostics
[File Name or Event] Emerson Confidential 27-Jun-01, Slide 57
The frequency band below show the six sensors states of the 2130 switching bands divided into three groups :
Valid sensor frequency : Wet or Dry
Fault Sensor frequency :
Too Wet : broken wire to the cassette, over-temperature, build-up
Too Dry : sensor body lost mass due to damage to sensor, corrosion
Zero Frequency
2130/2160 Sensor States
*DFF : Dry Forks Frequency Sensor switching limits are percentage of the calibrated frequency
Wet Dry Too Dry
Frequency Switching Bands
Too Wet
0HZ DFF – 28% DFF + 4.5%
DFF* 1400 Hz
[File Name or Event] Emerson Confidential 27-Jun-01, Slide 58
Direct Load
PNP
Relay
Namur
8-16mA*
Fault Relay*
2130 – Self Check available on all Cassettes :
*Provide
Separate fault signal output
[File Name or Event] Emerson Confidential 27-Jun-01, Slide 59
Electrical Installation of the 2130
8-16mA – High Level Alarm
PSU
Hazardous Area Safe Area
Dry = On
Heartbeat LED On
+
- ION = 15...17 mA
PE
(Ground)
U = 24 Vdc Nominal
Drives 4-20 mA Analog Intput
+
-
Compatible with NAMUR NE43
[File Name or Event] Emerson Confidential 27-Jun-01, Slide 60
Electrical Installation of the 2130
8-16mA – High Level Alarm
PSU
Hazardous Area Safe Area
Dry = On
+
-
PE
(Ground)
U = 24 Vdc Nominal
Drives 4-20 mA Analog Intput
+
-
Heartbeat LED Flashing
1Hz
IOFF = 7.5...8.5 mA
Compatible with NAMUR NE43
[File Name or Event] Emerson Confidential 27-Jun-01, Slide 61
Electrical Installation of the 2130
8-16mA – Fault Conditions
PSU
Hazardous Area Safe Area
Dry = On
+
-
PE
(Ground)
U = 24 Vdc Nominal
Drives 4-20 mA Analog Intput
+
-
Heartbeat LED Pulsed
IFAULT < 3.7 mA
Compatible with NAMUR NE43
[File Name or Event] Emerson Confidential 27-Jun-01, Slide 62 Rosemount Tank Radar AB Confidential
Overfill Safety – Tank Gauge Redundancy
[File Name or Event] Emerson Confidential 27-Jun-01, Slide 63 Rosemount Tank Radar AB Confidential
Overfill Safety – Tank Gauge Redundancy
[File Name or Event] Emerson Confidential 27-Jun-01, Slide 64 Rosemount Tank Radar AB Confidential
Overfill Safety – Tank Gauge Redundancy
Level & Roof Gauging
[File Name or Event] Emerson Confidential 27-Jun-01, Slide 65 Rosemount Tank Radar AB Confidential
Overfill Safety
Level & Roof Gauging
[File Name or Event] Emerson Confidential 27-Jun-01, Slide 66 Rosemount Tank Radar AB Confidential
Common Situation: Only One Tank Opening
Need for two Radars but only one opening available
What to do?
66
I want two Radars
on one nozzle!
[File Name or Event] Emerson Confidential 27-Jun-01, Slide 67 Rosemount Tank Radar AB Confidential 67
2 Radar in 1
Only one tank opening
Easy installation
Total electric separation
Operates in parallel
Put 2 Radar in 1 On-Tank Redundancy Made Easy
[File Name or Event] Emerson Confidential 27-Jun-01, Slide 68 Rosemount Tank Radar AB Confidential 68
2-in-1 Radar On-Tank Redundancy Made Easy
Redundancy
Dual operation
Gauging
Overfill Alarm
Separated
”Built in Spare”
[File Name or Event] Emerson Confidential 27-Jun-01, Slide 69 Rosemount Tank Radar AB Confidential 69
Safety Standard Compliant
[File Name or Event] Emerson Confidential 27-Jun-01, Slide 70 Rosemount Tank Radar AB Confidential 70
Safety Standard Compliant
API 2350 compliant
IEC 61508 certified
Certified SIL2
Certified SIL3
TÜV, (WHG) certified
[File Name or Event] Emerson Confidential 27-Jun-01, Slide 71 Rosemount Tank Radar AB Confidential 71
Summary
Its easy to install new Tank Gauging
Minimum Wiring
Wireless
Use existing tank opening
Use exisiting Still Pipes
Easy to connect to other systems
Get Overfil Protection at the same time
[File Name or Event] Emerson Confidential 27-Jun-01, Slide 72 Rosemount Tank Radar AB Confidential
Rosemount Raptor System
5900S Radar
Level Gauge
2410 Tank Hub
2240S Multi-input
Temperature
Transmitter
2120/2160
Liquid Level switch
2230 Graphical
Field Display
5300/5400
Radar Level
Transmitter
375 /475 Field
Communicator
Smart Wireless
THUM Adapter
644 Temperature
Transmitter with Single
Point Temperature Sensor
3051S Pressure
Transmitter
2160/65/75 Field
Communication Unit
2180 Field Bus
Modem
TankMater PC
Workstation in
Network
Smart Wireless
Gateway
2410 2410 2410
2410
2230
5900S
THUM 5900S 2240S
5900S 2240S 5400
5300
644
3051S
TankMaster.net
644
5400
[File Name or Event] Emerson Confidential 27-Jun-01, Slide 73 Rosemount Tank Radar AB Confidential 73
Typical instruments on LNG storage tanks
[File Name or Event] Emerson Confidential 27-Jun-01, Slide 74 Rosemount Tank Radar AB Confidential 74
Raptor 5900S radar for LNG Radar replacing servo in almost all
applications
Primary, secondary and HLA measurement using only radar
Highest accuracy over full range
Advanced signal processing
– FMCW @ 10 GHz
– High sensitivity for long range
Digital accuracy reference
– No aging or temperature effects
Verification during operation
SIL 2 and SIL 3 certified
Unique 2-in-1 redundancy
[File Name or Event] Emerson Confidential 27-Jun-01, Slide 75 Rosemount Tank Radar AB Confidential 75
Antenna – 5900S LPG/LNG
Designed for
– Liquefied gas in LPG/LNG tanks
– 4 in still-pipes sch 10 or 40
– 100 mm still-pipes
Quartz/Ceramic window as pressure sealing
Verification pin function
Optional
– Ball valve, fire-proof
– Rosemount 2051 Pressure sensor
Flange available in six versions
– 4 in. class 150, class 300
– 6 in. class 150, class 300
– 8 in. class 150, class 300
New Adapter Seal & ball
valve
[File Name or Event] Emerson Confidential 27-Jun-01, Slide 76 Rosemount Tank Radar AB Confidential
-0.001
0
0.001
0 5 10 15 20 25 30
Downwards manual log
Upwards manual log
Downwards autolog
Upwards autolog
76
Level Accuracy: 5900S exceeds OIML R85:2008
4
-4
2
-2
0
Old (R85:1998)
New (R85:2008)
(mm
)
3
1
-1
-3
Old (R85:1998)
New (R85:2008)
[File Name or Event] Emerson Confidential 27-Jun-01, Slide 77 Rosemount Tank Radar AB Confidential 77
Verification of Level measurement
On-line verification during normal operation
Verification is made inside the tank
Tank remains closed and no valves need to be maneuvered
A reference pin is mounted inside the still-pipe for level verification
A bottom reflection ring mounted at the end of the pipe is used for zero verification
Photos
[File Name or Event] Emerson Confidential 27-Jun-01, Slide 78 Rosemount Tank Radar AB Confidential 78
Raptor – SIL 2 and 3 Certified
[File Name or Event] Emerson Confidential 27-Jun-01, Slide 79 Rosemount Tank Radar AB Confidential 79
Built In Proof Testing
The two Radars will constantly ”safety-check” each other
Long time between manual Proof Testing
”No man on the tank”
Saves $$$
Avoid Manual Proof Testing
[File Name or Event] Emerson Confidential 27-Jun-01, Slide 80 Rosemount Tank Radar AB Confidential 80
Online proof-testing
-check
Blue and Red lines separated for visibility.
An alarm is given if the exceeds a defined limit
[File Name or Event] Emerson Confidential 27-Jun-01, Slide 81 Rosemount Tank Radar AB Confidential
2-in-1 Radar
81
Radar #1 Radar #2 High Level of Safety
SIL3 Rated
Low Cost Installation
On Tank Redundancy
High Availability
Less Proof Testing
Less Verification
Saves $$$ in many ways
[File Name or Event] Emerson Confidential 27-Jun-01, Slide 82 Rosemount Tank Radar AB Confidential
2x Radars on the same tank - well proven
[File Name or Event] Emerson Confidential 27-Jun-01, Slide 83 Rosemount Tank Radar AB Confidential 83
Some LNG sites using radar from Emerson:
Radar gauges have been used for more than 10 years to measure level at several LNG import terminals in Japan. So far 15+ tanks.
Trunkline LNG Co. – Terminal, Lake Charles, USA
Gaz de France – Terminal, Fos Cavaou, France
– Complete Emerson system solution
CPC Taiwan - Receiving terminal, Northern Taiwan
Qatargas II - Production site, 5 new tanks,
– Complete Emerson system solution
– Radar for all Level measurements (primary, secondary, HLA)
Freeport – Quintana Island - Receiving terminal, Texas, USA
Recent projects system solutions, Rex radar gauges combined with Whessoe LTDs
Cheniere - Sabine Pass – Receiving terminal, Louisiana, US. 5 tanks
Fluxys - Zeebrügge - Existing receiving terminal, Belgium
Exxon - Golden Pass LNG – Receiving terminal, Texas US. 5 tanks
Woodside - Pluto LNG – New export terminal. 2 tanks in Ph I.
PTT LNG – Map Ta Put – New receiving terminal
AGA – Nynashamn LNG – New receiving terminal. 1 tk Ph. 1
Chevron - Gorgon – New tanks at export site, 2 LNG + 4 Condensate tanks. Totally 24
radars
Polskie LNG – New receiving terminal, 2 tks.
[File Name or Event] Emerson Confidential 27-Jun-01, Slide 84 Rosemount Tank Radar AB Confidential 84
Rosemount LNG Radar Benefits
No moving parts
No re-calibration
No maintenance
SIL2 / SIL3 safety functions
Built in High Alarm
On-Line verification during operation inside the tank
Custody Transfer Accuracy
Conformance to API, OIML, ISO and other standards
Proven Technology
Many excellent references on LNG and LPG
Anything for a single gauge to a complete LNG Management System
[File Name or Event] Emerson Confidential 27-Jun-01, Slide 85 Rosemount Tank Radar AB Confidential 85
Emerson and Wärtsilä (Whessoe)
Combining the skills and experience from two organizations into an LNG storage management solution provider
Rosemount Tank Gauging
– Rosemount is the measurement division within Emerson
– Focus on high accuracy radar level gauges and supporting instruments for temperature and pressure
– System supplier, incl project management
Wärtsilä Calais (Whessoe product name)
– Focus on LTD gauges and LNG management software
[File Name or Event] Emerson Confidential 27-Jun-01, Slide 86 Rosemount Tank Radar AB Confidential 86
Loop 1
Loop 2
5900S +
2410
Hi-Hi alarm
5900S LNG + 2410
Secondary level 1146 LTD
Total LNG Tank Instrumentation Solution
TANK
N°1
Level alarms to ESD
5900S LNG + 2410
Primary level
2240S and 566
multiple spot
temp
2240S and 566
multiple spot
temp
[File Name or Event] Emerson Confidential 27-Jun-01, Slide 87 Rosemount Tank Radar AB Confidential 87
TANK N°2
Loop 2
TANK N°1
Total LNG Tank Instrumentation Solution
9510
20 mA loop / RS232C
9510
20 mA loop / RS232C
Loop 1
Loop 2
Loop 1
LNG Manager
LNG Manager
DCS
LNG Roll-Over
Predictor
Serial link
Serial link
Serial link
Serial link
TRL2 bus for Raptor
/2410 if not using
WM660
FCU 2160
[File Name or Event] Emerson Confidential 27-Jun-01, Slide 89 Rosemount Tank Radar AB Confidential 89
Tank detail (Roll-Over)
[File Name or Event] Emerson Confidential 27-Jun-01, Slide 90 Rosemount Tank Radar AB Confidential 90
Sample of project awards Combined Emerson / Rosemount Tank Radar and Whessoe LTD
- recent projects realized at LNG terminals or production sites :
Cheniere’s Sabine Pass
Exxon’s Golden Pass
Fluxys (Zeebrugge, Belgium)
Pluto LNG Australia
Nynashamn Sweden
PTT LNG Map Ta Put Thailand
Sonatrach Skikda LNG Algeria
Gorgon Australia
Polskie LNG
Many new projects to be decided shortly
[File Name or Event] Emerson Confidential 27-Jun-01, Slide 93 Rosemount Tank Radar AB Confidential 93
LNG references (continued)
Golden Pass LNG - new receiving terminal in Texas; Five tanks. Installation 2008.
– CB&I US is the main EPC for the complete project
– Whessoe LTD + software (Wärtsilä)
– Emerson partner to Wärtsilä and supplied:
• 5 x Radar Rex 3960
• 5 x SDAU
• 5 x MST Cryo
• 2 x FCU 2160