bengaluru - southern regional power committee - govt of … · level substations (for power supply...
TRANSCRIPT
SOUTHERN REGIONAL POWER COMMITTEE
BENGALURU
Agenda for the 52
nd Meeting of Protection Coordination Sub-Committee of
SRPC to be held on 30.03.2016 (Wednesday)
1. Introduction
2. Confirmation of Minutes of last PCSC meeting
Confirmation of minutes of 51st
Protection Coordination Sub-Committee meeting held
on 25.02.2016.
3. Grid Occurrences
3.1 Grid Disturbance (GD), Grid Incidences (GI), and trippings due to failure of Auto-
reclosing (A/R), and Mal-operation of PLCC equipment that occurred during the period February - March, 2016 given at Annexure-I would be discussed in the
PCSC meeting
Constituents are requested to furnish the following information in respect of the
above grid occurrences to have fruitful discussions in the PCSC forum.
(a) Single line diagram of the station with switching devices, CT, PT and relay
details.
(b) Cause of the tripping & Remedial Action taken
(c) Relay setting details
(d) Deficiencies / Observations as perceived by the Utility which needs PCSC’s
intervention.
Constituents are requested to bring/ give full particulars of the tripping events
pertaining to their system.
3.2 In compliance of Regulations 5.2 (r) of IEGC, the Constituents are required to
furnish the following information in respect of Grid Occurrences:
(a) First Information Report (FIR)
(b) Event Logger (EL) output
(c) Disturbance Recorder (DR) output
(d) Trip event analysis report (with pre and post fault system conditions)
Non-furnishing of tripping details including Disturbance Recorder/Sequential
Event logger output has been brought to Constituents attention vide SRPC letter
No. SRPC/ SE-III/ PCSC-50/ 2016/1504-16 dated 08-03-2016. The non-
compliance in this regard would be discussed in the meeting.
4. Submission of reports/compliance by Constituents
4.1 Status of pending Protection Coordination Sub-Committee (PCSC)
Recommendations
Status of the pending PCSC recommendations (from 30th
PCSC to 51st PCSC)
given at Annexure-II may please be sent latest by 25.03.2016.
Agenda for the 52nd Protection Coordination Sub Committee Meeting to be held on 30-03-2016 Page 2
4.2 Remedial measures for "Transmission Line under Forced Outage"
The constituents are requested to send the remedial measures/ actions taken by them for the tripping events as circulated vide our emails. (Annexure-III)
The trip events are based on the daily reports at SRLDC website
http://srldc.in/DailyReport.aspx under the menu: Reports->Daily-> "TL under
Forced Outage")
4.3 Certificate for Healthiness of Batteries
As per the MoP direction given in pursuant to recommendations of the
Enquiry Committee (NEW grid disturbance on 30th
& 31st July, 2012), RPC’s
are required to obtain from their respective Constituents the monthly
certificate for healthiness of batteries, installed at 220 KV and above voltage
level Substations (for power supply to Relays, RTUs and PLCC equipment)
and furnish the same to CEA/ MoP.
With reference to above, the Constituents are requested to submit the
certificate on healthiness of batteries on monthly basis (i.e. on 7th
day of the
month) to SRPC.
The sought status for the month of February, 2016 is still awaited from the
following SR-Constituents:
APGENCO(Thermal),APTRANSCO,TSTRANSCO,KPCL,KPTCL,
TANGEDCO,PED,NTECL,UPCL,NTPL,CEPL,SEL,MEPL,TPCIL
5. Review of Islanding Schemes for Southern Region
With the addition of new generators & transmission elements in the Southern Region
(SR), the existing islanding schemes of SR have been reviewed, and the modified
Islands incorporating these new elements were discussed in the 51st meeting of PCSC
held on 25.02.2016.
It was highlighted that as per the current scenario (January, 2016), Load Generation
Balance of Hyderabad and Chennai Islands had not been achieved. In this regard, the
Constituents were requested to kindly furnish the details of (i) load relief from df/dt
and AUFR relays, (ii) participating generators, and (iii) participating loads to be
considered in various Islanding Schemes latest by 25.03.2016 so as to finalize the
revised Islanding Schemes in the 52nd
PCSC meeting.
The issue would be discussed in the meeting.
6. Over Voltage Relay Grading for 765 kV lines in the Southern Region
In the recent past trippings of 765 kV lines have been observed in the Southern Region.
To contain these trippings on Over Voltage, studies relating to Over voltage Relay
grading for 765 kV lines have been carried out. Based on the study results, it is
proposed to adopt the following gradings for 765 kV lines in the Southern region.
Agenda for the 52nd Protection Coordination Sub Committee Meeting to be held on 30-03-2016 Page 3
1. 765 kV Network of Southern Region:
2. Voltage- Time Grading Matrix
Order of tripping Category Rating Time
Delay in Sec
8 A 109 9
7 B1 109 8
6 B2 109 7
5 B3 109 6
4 C1 108 8
3 C2 108 7
2 C3 108 6
1 D 108 5
3. OVR Gradings for 765 kV lines
From
Bus
Number
From Bus Name To Bus
Number To Bus Name
Ckt
Id
Length,
km
OVR
Grading
337004 SHOLAPUR 765.00 437001 RCHR-NEW 765.00 1 208
337004 SHOLAPUR 765.00 437001 RCHR-NEW 765.00 2 208
417001 KRNL-NEW 765.00 417002 NLR-PS 765.00 1 302 C2
417001 KRNL-NEW 765.00 417002 NLR-PS 765.00 2 302 B1
417001 KRNL-NEW 765.00 437001 RCHR-NEW 765.00 1 118.42 B3
417001 KRNL-NEW 765.00 437001 RCHR-NEW 765.00 2 120.48 A
417001 KRNL-NEW 765.00 447002 TRVLM 765.00 1 355 D
417001 KRNL-NEW 765.00 447002 TRVLM 765.00 2 355 B2
417002 NLR-PS 765.00 417001 KRNL-NEW 765.00 1 302 C2
417002 NLR-PS 765.00 417001 KRNL-NEW 765.00 2 302 B1
437001 RCHR-NEW 765.00 337004 SHOLAPUR 765.00 1 208 B3
437001 RCHR-NEW 765.00 337004 SHOLAPUR 765.00 2 208 A
Agenda for the 52nd Protection Coordination Sub Committee Meeting to be held on 30-03-2016 Page 4
437001 RCHR-NEW 765.00 417001 KRNL-NEW 765.00 1 118.42 C1
437001 RCHR-NEW 765.00 417001 KRNL-NEW 765.00 2 120.48 B1
447002 TRVLM 765.00 417001 KRNL-NEW 765.00 1 355 D
447002 TRVLM 765.00 417001 KRNL-NEW 765.00 2 355 B2
7. TANTRANSCO Agenda Points
TANTRANSCO vide their letter No. CE/P&C/SE/D/EEPC 4/AEE 3/F.SRPC/D. 42
/16 dated 05.03.2016(Annexure–IV) requested to review earlier PCSC
recommendation regarding using different make relays at their Alamathy and SV
Chatram substations. The issue is proposed to be discussed in the meeting.
8. KSEB Agenda Points
KSEB vide their mail dated 29.02.2016 requested to discuss certain issues regarding
implementing Ramakrishna commission report based settings in 220KV feeders. The
issues given at Annexure–V would be discussed in the meeting.
9. Network Configuration changes
The network configuration changes (additions/ deletions/ modifications of transmission
elements) that took place in the southern grid during the period December, 2015 -
February, 2016 were intimated vide PCSC-51 minutes circulated vide SRPC letter dated
16-03-2016.
10. Compliance of Hon’ble CERC Orders.
10.1 Petition No. 146/MP/2013 with I.A. 36/2013: Order dated 20.02.2014
Compliance of Regulations 5.2 (r) of the Grid Code: Issue regarding non-
furnishing of FIR / Trip Analysis Report, EL, DR, etc. was also
highlighted. It is pointed out that the above reports are to be submitted /
uploaded on SRLDC web application within 24 hours as mandated under
IEGC / CEA Regulations.
Implementation of Phase-I and Phase-II of Protection Audit
Recommendations: All the constituents are requested to submit the updated
status of the compliance (those who have not completed recommendations
mentioned in the Phase I and Phase II) to SRPC Secretariat at the earliest.
Compliance of Regulations 5.2 (e) & 5.2 (l) of the Grid Code and Regulation
3(1)(e) of CEA Grid Standards: The constituents are requested to strictly
comply with these provisions by ensuring standard protections systems having
the reliability, selectivity, speed and sensitivity to isolate the faulty equipment
and protect all components from any type of faults, within the specified fault
clearance time and providing protection coordination
Ensuring proper maintenance of transmission lines and adopting best O&M
practices: The constituents are requested to conduct line patrolling regularly
as per the SRPC transmission line patrolling guidelines (available under the
menu item "All Uploads Operation Miscellaneous Transmission Line
Patrolling Protocol / Guidelines for Southern Region" on SRPC website).
(http://www.srpc.kar.nic.in/website/2014/operation/patrolling.pdf).
Agenda for the 52nd Protection Coordination Sub Committee Meeting to be held on 30-03-2016 Page 5
10.2 Petition No. 167/Suo- Motu/2012: Order dated 22.02.2014
The Constituents are requested to follow approved protection philosophy
ISTS licensees are requested to submit details of updated distance protection relay
setting of all inter-regional lines to POSOCO & RPCs.
All SLDCs are requested to install/activate sound recording system in their control
rooms within three months from the date of issue of this order.
The Constituents are requested to submit the progress of implementation to
SRPC and SRLDC as specified in the Hon'ble CERC Order.
10.3 Petition No. 263/MP/2012: Order dated 19.12.2013
Constituents are requested to implement the quantum of relief by AUFR and df/dt
relays by identifying additional feeders and keep them functional within one month
of issuing this order.
SLDCs are also requested to map these relays on their respective SCADA
system within three months of issuance of this order.
The Constituents are requested to submit the progress of implementation to
SRPC and SRLDC as specified in the Hon'ble CERC Order.
10.4 APTRANSCO’s Petition No.95/MP/2015: Date of hearing 09-04-2015
It was noted in the Analysis and Decision part of the Order that:
“8. Noting the submissions of the petitioner, SRPC and SRLDC and activities
initiated by the petitioner for procurement of materials required for
implementation of the remarks of protecting audit, we allow time to the
petitioner till 31.12.2015 for completion of our directions in Order dated
19.12.2013 in Petition No. 146/MP/2013.”
“9. SRPC is directed to monitor the status of completion of works relating to
protection audit remarks in respect of 7 nos 400 kV sub-stations and 11 nos
220 kV sub-stations of APTRANSCO, protection audit remarks in Protection
Coordination Sub-Committee (PCSC) meetings and coordinate the periodic
protection audit to be carried out in Southern Region after deliberation in
SRPC and submit bi-monthly report to the Commission.”
10.5 TSTRANSCO’s Petition No.83/MP/2015: Order dated 14-05-2015
It was noted in the Order that:
“12. Noting the submission of the petitioner, SRLDC and SRPC and
considering the actions already initiated by the petitioner for implementation
of works relating to protection audit, we allow time till 31.10.2015 and
31.8.2016 for implementation of Phase-I and Phase -II works respectively.
The petitioner is directed to submit affidavit confirming the completion of
Phase I of protection audit remarks by 31.10.2015 and Phase-II of protection
audit remarks by 31.8.2016.
13. SRPC is directed to monitor the status of completion of remarks in these
substations vis-à-vis protection audit remarks in Protection Coordination Sub
Committee (PCSC) meetings. SRPC is further directed to coordinate the
periodic protection audit to be carried out in Southern Region after
deliberation in SRPC.”
10.6 Order in Petition No. 86/MP/2014 and 374/MP/2014: Order dated 18-08-2015
Agenda for the 52nd Protection Coordination Sub Committee Meeting to be held on 30-03-2016 Page 6
The time-lines given to the various SR-Constituents for completion of Phase-I and
Phase-II activities of Protection Audit Recommendations are given below:
(A) KSEBL:
18. Noting the submission of KSEBL, SRLDC and SRPC and considering the actions
already initiated by KSEBL for implementation of remarks of protection audit, we
allow time till 31.12.2015 and 31.3.2016 for implementation of Phase-II works
and R&M works at Idduki HEP respectively.
(B) TANTRANSCO: 21. After considering the submissions of TANTRANSCO, SRLDC and SRPC, it is noted
that TANTRANSCO`s request for time till 31.5.2015 for implementation of Phase–I
activities of providing numerical relays for feeder protection and Auto transformer
protection is already over. We allow time till 30.6.2016 for other Phase-I activities
such as provision of line VT, 5 core CT, Time synchronizing with GPS, Disturbance
recorder & event logger and Phase-II activities. According to SRLDC, total
implementation period is 15 to 16 months for items which involve major
procurement, design changes with major site modification/civil activities.
Accordingly, we allow 16 months time i.e up to 30.11.2016, for Renovation and
Modernization of Singarpet, Singaperumalkoil, Salem and Tondiarpet 230 kV sub-
stations from the issue of the order.
(C) NLC:
22. NLC has sought time upto 31.12.2014 and 31.3.2015 for completion of Phase-I work
of Numerical Relay Retrofitting and for Phase-II works of providing second battery
bank of PLCC respectively. It is noted that the completion dates for Phase-I and
Phase-II of protection audit remarks as requested by NLC are already over.
Therefore, no direction is required in this regard. However, we direct NLC to file a
confirmation report regarding completion of protection audit works for Phase-I and
Phase-II.
(D) KPTCL:
23. …
…
Considering the submission of KPTCL and SRLDC, we allow time to KPTCL time till
15.01.2016 for completion of Phase-I and Phase-II of protection audit remarks. No
further extension shall be granted in this regard.
(E) KPCL:
24. …
… Considering the submission of KPCL and SRLDC, we allow time to KPCL till
31.10.2015 and 31.12.2015 for completion of Phase-I for Phase-II of protection
audit remarks respectively. No further extension shall be granted in this regard.
26. We direct SRPC to (a) submit status of protection audit remarks in respect of
APGENCO, NTPC (SR), Talcher, Puducherry, PGCIL (SRTS I & II), MAPS and
TANGEDCO, (b) monitor the status of completion of remarks of protection audit in
respect of all constituents of Southern Region in Protection Coordination Sub-
Committee (PCSC) meetings, and (c) to coordinate periodic protection audit to be
carried out in Southern Region after deliberation in SRPC. All the constituents of
Southern Region are directed to file their status with SRPC on regular basis to
facilitate proper monitoring in PCSC meetings. SRPC is directed to submit bi-
annually status report to the Commission confirming the completion of Phase-I,
Agenda for the 52nd Protection Coordination Sub Committee Meeting to be held on 30-03-2016 Page 7
Phase-II and R&M works of protection audit remarks of the constituents of Southern
Region.
11. Other Protection Issues, if any, with the permission of the Chair
12. Sending Agenda items for the PCSC meetings
As per the Guidelines of CEA/MOP, it has been decided to conduct the PCSC
meetings on monthly basis. It is requested that Agenda Items for the PCSC meetings,
if any, may please be sent latest by 5th
working day of the month to SRPC Secretariat to
compile and circulate the same so as to have fruitful discussions in the PCSC
meetings.
13. Date of next PCSC meeting
The 53d PCSC meeting would be conducted on 28.04.2016 (Thursday) at SRPC,
Bengaluru.
*******
Page 1 of 3
Grid Occurrences
For all tripping events involving failure of substation equipment, Constituents are
requested to kindly furnish the SLD or equivalent pictorial representation showing
(i) Location of the fault, and (ii) Bus-bar arrangement/ Configuration of feeders and
other connected equipment with proper CB positions (OPEN/ CLOSE) at the time of
occurrence of the fault.
1. Details of Grid Disturbances:
Sr. No.
Details of Event Date & Time
Reason Remarks Category
1
Complete outage of
230kV Thiruvelam
substation of
TANTRANSCO
10-2-2016 at
15:42hrs
Mal-operation of 230 KV Bus
Bar protection relayat 230 KV
Thiruvalam Substation led to
tripping of all 230 kV feeders
and resulting in total supply
failure
GD-1
2
Complete outage of
220kV Yerraguntla
substation and
running of tripping
units at
Rayalaseema TPS
21-02-2016
at 10:39 hrs
HV B-Ph Current transformer of
100MVA Power Transformer -1
failed resulting into a bus fault
on 220KV Bus-1. Unit-1 and
Unit-5 at RYTPS tripped during
the fault at Yerraguntla
substation
GD-1
3
Complete outage of
220kV Shimoga
substation
22-02-2016
at 15:03 hrs
220kV Bus Bar protection
operated during failure of R
phase CT in DVG-2 line bay.
GD-1
4
Complete outage of
NTPL power
station
02-03-2017
at 7:20 hrs
400kV Coastal-NTPL, 400kB
NTPL-Tuticorin PS and running
units at NTPL tripped during the
incident. LBB prorection got
operated at NTPL
GD-1
5
Complete outage of
220kV Regulapadu
substation of
APTRANSCO
02.03.2016 at
14:32 hrs
220KV R-ph Metering PT failed
at 220KV Ragulapadu
Substation.
GD-1
6
Complete outage of
220kV
Malyalapalli station
of TSTRANSCO
10-03-2016at
18:41 Hrs
CT failure occurred in 220kV
Ramagundam-Malyalapalli line-
1. The CT failure resulted into a
Bus fault. All 220kV lines and
transformers at Malyalapalli
station tripped during the
incident.
GD-1
Annexure- I
Page 1 of 3
Page 2 of 3
7
Complete outage of
220kV Srisailam
right bank station
11-03-2016
at 14:36 hrs LBB Protection of 220KV Srisailam-BilakalaGudur feedergot operated resulting in tripping of both Bus-I and Bus-II
GD-1
2. Details of Grid incidents:
Sr. No.
Details of Event Date & Time
Reason Remarks Category
1
Tripping of 400kV
Chitoor-
Sriperambadur line 01-02-2016
at 9:55 hrs
line tripped on operation of line
reactor protection at
Sriperambadur end and direct trip
was sent to Chitoor. Buchholz
relay of line reactor of 400kV
Chitoor-Sriperambadur got
operated at Sriperabadur end.
2
Tripping of
400/220kV ICT-3 at
Raichur TPS 05-02-2016
at 3:01 hrs
ICT-3 tripped on operation of
Stub protection due to
malfunction of Contact multiplier
of Line isolator
3
Tripping of
400/220kV ICT-2 at
Hoody substation
11-02-2016
at 15:54 hrs Fuse Failure relay burnt out and
Back up overcurrent trip relay got
operated
12-02-2016
at 16:42 hrs ICT tripped while testing/
replacing of PT Fuse failure relay
5 Tripping of HVDC
Talcher-Kolar pole-1
20-02-2016
at 18:22 Hrs HVDC Talcher-Kolar Pole-1
tripped due to Valve cooling
problem at Kolar end
21-02-2016
at 16:46 Hrs
HVDC Talcher-Kolar Pole-1
tripped due to Valve cooling
problem at Kolar end
6
Tripping of HVDC
Pole – 1 at
Gazuwaka
23-02-2016
at 10:13 hrs Failure of thyristors
7 Tripping of ICT-2 at
Cudappah substation
25-02-2016
at 14:23 hrs
ICT-2 tripped on operation of
directional over current. At the
same time B-phase to earth fault
had occurred in 400kV Cudappah-
Kolar line
8 Tripping of ICT-3 at
Talaguppa station
27-02-2016
at 17:33 hrs
Tripped on operation of OCR- Y
Phase (400KV SIDE)
9 Tripping of ICT-1 at
Hoody substation
29-02-2016
at 17:43 hrs
LV side Breaker Tripped due to
problem in lock out trip circuit
contactor
10 Tripping of HVDC
Talcher-Kolar
pole-1 at 1:29
hrs and Pole-
2 at 5:44 hrs
on 08-03-
2016
Pole-1 Tripped after receiving
ESOF from Talcher end. Pole-2
tripped on operation of Bridge
Differential Protection Delta
winding Stage-2 of convertor
transformer
Annexure- I
Page 2 of 3
Page 3 of 3
11
Tripping of 400kV
Jeypore-Gazuwaka
line-1&2 and HVDC
Gajuwaka pole-1&2
10-03-2016at
12:31 Hrs
Disturbance in South Odisha
system GI-2
3. Failure or non-operation of Auto reclose during transient fault
Sr. No.
Element Date & Time
Reason
1
Tripping of 400kV
Vijayawada-Nellore line-2
01-02-2016 at 6:30
hrs
Line tripped on a Y-phase to earth
fault. Line auto-reclosed at
Vijayawada end and failed to
auto-reclose at Nellore end
2
Tripping of 220kV Idukki-
Udumalpet line 03-02-2016at 11:54
hrs line tripped on operation of Y
phase to earth fault. Line auto-
reclosed at udumalpet end and did
not reclose at idukki end. 06-03-2016 at 4:28
hrs
B-phase to earth fault occurred in
line. auto reclosed at Udumalpet
end and did not reclose at Idukki
end
3 Tripping of 400kV Hyderabad-
Kurnool line
22-02-2016 at
06:48 hrs
line tripped on a R-phase to earth
fault and line did not auto-reclose.
4
Tripping of 220kV Chikodi-Taladage line
25-02-2016 at 17:44 hrs and 26-02-2016
at 19:24 hrs
Line tripped at Talandage end only on both the days
4. Lines tripping due to tripping at one end/PLCC mal-operation
Sr. No.
Details of Event Date & Time
Reason Remarks Category
1
Tripping of 400kV
Guttur-Narendra
line-2 01-02-2016
at 12:06 hrs Line got tripped at Guttur end
only
2 400kV Vemagiri-
GVK line-1
07-02-2016
at 21:20hrs
line tripped at Vemagiri end only
on receipt of Direct Trip signal
from GVK
3
Tripping of 400kV
Vemagiri-GMR line-
2
09-02-2016at
12:57 hrs
tripped at GMR end only and line
is in service from Vemagiri
4
Tripping of 765kV
Solapur-Raichur
line-1
10-02-2016at
12:45 hrs
line tripped on direct trip receive
from Solapur end
5
Tripping of 400kV
Hassan-
Neelamangala line
07-03-2016
at 14:55 hrs
line tripped on operation of B-
phase to earth fault. at Hassan
sensed fault in Zone-2 and breaker
tripped after zone-2 time. PLCC
carrier signal not sent from
Neelamangala
*****
Annexure- I
Page 3 of 3
Meet
ing
No /
Index
Details of
Event
Date Reason PCSC Recommendations Utility
Responsible
for
implementa
tion
Status of Recommendations
as on 15-03-2016
Remarks
49/II/1
3
Tripping of
running Units 1
& 3 at
Rayalaseema
TPS of
APGENCO
31-10-2015
at 03:30 hrs
While synchronizing Unit-5 with grid, Bus bar
protection of 220kV Bus-1 operated which
resulted in de-energization of 220kV Bus-1.
This resulted in tripping of running Unit-
1&Unit-3, 220kV lines Pulivedula-1,
Yeralaguntla-1, Chinakampalli-1, Timmapura
In view of the availability of 25AX, APGENCO shall keep
synchronizing facility in auto-mode after getting it’s
operation verified by its OEM, M/s BHEL.
APGENCO Yet to be informed Pending
49/III/
4
Tripping of
400kV
Krishnapatnam-
Chittoor line-1
19-10-2015
at 07:49 hrs
R-phase to earth fault had occurred in line.
Chittoor end tried for auto-reclose. However,
due to persistent fault, breaker at Chittoor end
tripped. Krishnapatnam end relay did not try
for auto-reclose and gave a 3 phase trip as
observed from D.R
• APGENCO to make A/R functional on all lines emanating
from Krishnapatnam TPS by 10th December, 2015.
APGENCO Yet to be informed Pending
44/III/
2
Tripping of
400kV
Ghanapur-
Mamidapalli
line
15-04-2015
at 2:03 hrs
Line tripped at Mamidapalli end only and was
holding at Ghanapur. Overvoltage protection
had operated at Mamidapalli
TSTRANSCO to make DR
functional at Mamidipalli
TSTRANSCO TSTRANSCO informed vide their mail dated 24.06.15 that the existing relays
would be replaced with numerical relays in DPR works.
Pending
During testing of DC earth leakage, DC got
extended to bus bar protection relay. Hence bus
bar protection operated and tripped the 220KV
BUS connected transformers and feeders.
18-11-2015
at 11:20 hrs
Tripping of
220kV
Chittoor-
Tiruvalam
50/II/1
4
Pending Implementation of PCSC Recommendations (30th to 51st)
Andhra Pradesh42/II/3 Outage at
Regulapadu
station of
APTRANSCO
21-02-2015
at
00:49 hrs
Y-Ph Metering PT failed at 220KV
Ragulapadu Substation. Fault got cleared
by tripping of lines from remote ends.
APTRANSCO to furnish the remedial measures taken in
consequent to the tripping
incident along with the status of bus bar protection and bus
coupler at Regulapadu S/s.
A/R feature to be enabled on Regulapadu – Alipuira 220
kV inter-state line.
APTRANSC
O
Mail recieved on 22-08-2015:
APTRANSCOhas planned to commission ABB make ETL-41 type PLCC
terminal along with NSD-50 type protection coupler at Ragulapadu end towards
Alipura. vide our Ltr Dt 23-07-2015, it is requested KPTCL to arrange ABB
make ETL-41 cabinet with NSD-50 type protection coupler for establishing PLC
communication between Alipura- Ragulapadu.
KPTCL Mail recieved on 23-01-2016:
KPTCL is ready with ETL-41 cabinet with NSD-50 type protection coupler at
Alipur end.
APTRANSCO mail received on 24-02-2016:
Protection coupler equipment is ready at Ragulapadu end. Wave trap errection is
pending at Ragulapadu end. To maintain the ground clearenace structural
modification works are going on for errection of wave trap.
Pending
Telangana
PendingAPTRANSCO mail received on 24-02-2016:
220KV chittoor substation is a old 220KV substation with single bus operation.
Bus bar protection has both main & checkzone are in service.
APTRANSC
O
1.APTRANSCO to furnish SLD of 220/132 kV Chittoor
SS,
2. APTRANSCO to confirm whether 220 kV side is on
single-bus operation with only one main-zone. If so,
APTRANSCO shall examine the feasibility of providing
split-bus operation or multiple main-zones for bus bar
protection, and take necessary steps to implement it.
Annexure- II
Page 1 of 20
48/II/5 Tripping of
400kV
Nagarjunsagar-
Mahboobnagar
line
07-09-2015
at 2:58 hrs
Line tripped on operation of over-voltage
protection at Mahboobnagar and direct trip
received at N’sagar station. DT receive was
observed in DR and EL of N’sagar station.
D.R/EL of Mahboobnagar was not furnished to
validate the overvoltage tripping
TSTRANSCO to furnish a detailed report on the tripping
event along with remedial measures taken to PCSC forum.
TSTRANSCO Yet to be informed Pending
48/III/
4
Tripping of
220kV Gajwel-
Shankarapally
line
20-09-2015
at 2:24 hrs
line tripped at Gajwel end on R-Phase to
ground fault. Reason for non-auto reclose
could be established as DR and EL of both
ends were not furnished
• TSTRANSCO to furnish a detailed report on the tripping
event along with remedial measures taken to PCSC forum.
TSTRANSCO Yet to be informed Pending
51/IV/
1
Tripping of
400kV Gajwel-
Hyderabad
29-12-2015
at 6:11 hrs
and 7:11 hrs
Line tripped at Gajwel end only due to
suspected PLCC mal-operation at Gajwel end
TSTRANSCO to check the integrity of all DR’s and EL’s,
and sort out communication related issues at 400 kV Gajwel
SS.
TSTRANSCO Yet to be informed Pending
Karnataka30/I/A RTPS
Tripping
incidents and
the Spl meeting
held
at RTPS on
13th and 14th
March 2014
Mar-14 Spl meeting held at RTPS on 13th
and 14th
March 2014
The PCSC forum recommended for replacement of
existing electromechanical relays with Numerical relays.
KPCL Mail recieved on 21-10-2015 and 23-11-2015:
1) Replacement of Old electromagnetic relays with Numerical relays has been
completed for RTPS-BTPS line & commissioned on 18.03.2014.
Raichur-PG1 & Raichur-PG2 lines have already retrofitted with numerical
relays.
The retrofitting of electromechanical relays with Numerical version for the
following lines/ICTs have been completed/commissioned as follows:
a) ICT-2 –Commissioned on 01-08-2015
b) ICT-1 ---Commissioned on 08-08-2015
c) Munirabad line--- Commissioned on 16-08-2015.
d) Mehaboobnagar line-- Commissioned on 09-09-2015.
2. Job order placed on 26.06.2015 on M/s Alstom T&D India Ltd. Chennai for
retrofitting of relays for all 220kV lines at RTPS.
3. Retrofit of existing bus bar(CAG-34) with numerical version– Budgetary
offers obtained and is under process.
Pending
47/II/6 Tripping of
400kV
Khammam-
KTPS line-2
30-07-2015
at 6:08 hrs
Y-phase to earth fault had occurred in line.
From Khammam end DR it was
observed that the relay after dead time tried for
auto-reclose. The fault was
persisting and relay gave a single phase trip
instead of a 3 phase trip after 1.25sec. R& B
pole voltage dip after 2 sec
possibly due to operation of pole discrepancy.
Auto-reclose close command observed after
2.5 seconds and all poles got closed.
1. TSGENCO to check the reclaim time of A/R and set it at
25 sec at KTPS.
2. TSGENCO to carry out PLCC end-to-end testing in
coordination with PGCIL (SR-I) for KTPS – Khammam
line-2; retrofitting of Protection Coupler may be carried out
based on the test results.
TSGENCO Yet to be informed Pending
Annexure- II
Page 2 of 20
38/G
D/3.2
GD-1 at Guttur
Substation of
KPTCL
05-11-2014
at 11:42 hrs
Circuit breaker of 400kV Guttur-Hiriyur
line-1 failed at Guttur end while availing
shutdown for replacement of CVT. The
failure of breaker caused bus fault at Guttur.
KPTCL was requested to expedite the early implementation
of pending recommendations of:
1. Protection Audit (Phase-I & Phase-II)
2. PSAG-4, PSAG-5, and PSAG-8
KPTCL KPTCL mail received on 23-01-2016:
'The following works are attended at 400kV Guttur SS :
1. Replacement of Hiriyur-1 line, Bus Coupler, Tie Bus coupler breakers by new
Alstom make breakers (3 new CBs commissioned) recently.
2. New CVTs provided for 400kV Hiriyur line-1 and commissioned on
21.01.2016
Pending
39/I/5 Tripping of
400/220kV
ICT-2 at
Hoody
substation of
KPTCL
01-12-2014 Suspected mal-operation of 220kV side
Rphase
over current relay
1. PCSC forum recommended KPTCL to replace the relay
with a different make.
2. KPTCL was also requested to train the O&M personnel
adequately before performing any maintenance works to
avoid such unwanted trippings.
KPTCL Mail received on 27-05-2015 & 29-07-2015:
C&R panels of 500MVA ICT 1&2 will be replaced under scheduled R&M
works. O&M personnel are instructed to take sufficient care in order to avoid
unwarrented trippings.
KPTCL mail received on 23-01-2016:
New C&R panels(with numerical relays) erected for 500MVA ICT-1 &2 under
R&M work, which will be commissioned shortly.
Pending
16-07-2014 As reported directional over current relay of
ICT’s operated due to snapping of line
jumper in 220kV Lingapur line.
1. Bus bar protection shall be provided by asset owner (
i.e KPTCL).
2. Settings for main distance protection & Overcurrent
protection shall be examined and reviewed.
3. Time synchronization of the Substation shall be
ensured.
4. Correct DR shall be submitted to the SRLDC for trip
analysis.
KPTCL
38/G
D/3.5
GD-1 at Kadra
and Kodasalli
hydro power
station
13-11-2014
at 19:31hrs
A fault had occurred in 220 kV Kadra and
Kodasalli. As A result, de-energization of
220kV bus occurred at Kadra and
Kodasalli.
1. The PCSC forum requested KPCL to speed up the
installation of Numerical Distance Protection relay in
Kadra –Kaiga and Kodasalli –Kaiga.
2. The PCSC forum requested KPCL to submit the
implementation status of PSAG-10 recommendations within
a week’s time.
KPCL Mail recieved on 21-10-2015:
NIT floated on 5.5.15 through e-portal. Bid evaluation completed. LOA's issued
to M/s Schneider Electric Infrastructure Ltd. on 08.10.2015.
Mail recieved on 23-11-2015:
LOA's issued to M/s Schneider Electric Infrastructure Ltd. on 08.10.2015.
Engineering work is in progress.
Pending
34/III/
1
400kV
Raichur-BTPS
line
26-06-2014 Transient fault in R-phase.
Line did not auto reclose
A/R at BTPS end to be made operational within one
month
KPCL 1. A/R for 220kV lines enabled already.
2. Shut down of lines availed to commission the auto reclosing schme for 400
kV line at BTPS.
Mail recieved on 21-10-2015:
Timer relays have been received at site. A letter has been addressed to M/s
Alstom to complete the work on priority basis.
Mail recieved on 23-11-2015:
Commissioning of Autorecloser planned on 14, 15 & 16th of Dec-2015 subject
to availability of LC.
Pending
Mail recieved on 27-05-2015 (KPTCL):
1. KPTCL has taken action to provide bus bar protection to 220kV buses.
2. Over current relay Settings of ICTs to be reviewed by PGCIL.
Mail received on 29-07-2015 (KPTCL):
Initial Tendering stage
KPTCL Mail recieved on 23-01-2016:
Detailed estimate prepared for taking up the work. CEE, Transmission Zone,
Gulbarga will take up necessary procurement and further execution.
Pending
38/G
D/3.1
GD-1 at
Mahalingapura
Substation of
KPTCL
25-10-2014 Fault had occurred in 220kV
Mahalingapura-Narendra line-2. Due to the
failure of relay operation at Mahalingapura,
breakers at remote end tripped which
resulted in bus dead condition.
1. PCSC forum recommended KPTCL to replace the old
static distance protection relays with numerical relays.
2. PCSC forum also requested KPTCL to provide a broken
conductor alarm indication in Control Room.
3. Standing instruction needed to be given to the all
substation personnel for not changing the relay settings
without approval of RT/MRT wing.
KPTCL Mail received on 27-05-2015 (KPTCL) & 29-07-2015:
1.Existing Back up relays will be replaced by numerical type distance
relays.Procurement is in tendering stage. Remaining observations were
attended.
KPTCL Mail recieved on 23-01-2016:
Existing back up relays will be replaced by Main-2 protection. LOI issued M/s
Alstom for taking up the works.Remaining observations were attended.
Pending
34/I/6 400/220 kV
ICT-1 & 2 at
MUNIRABA
D
Annexure- II
Page 3 of 20
40/IV/
1
220kV Sedam-
Tandur line
20-12-2014
at 22:20 hrs
Line tripped on Yphase to earth fault from both
the ends
KPTCL was requested to explore the possibility of
providing A/R feature to this line and submit the remedial
measures to the PCSC forum.
KPTCL KPTCL mail recieved on 23-01-2016:
Carrier protection is being restored for 220kV Sedam-Tandoor line at Sedam
end. After restoring the carrier protection , AR will be enabled.
Pending
42/I/1
(GD)
Complete
outage of
220kV Sedam
substation of
KPTCL
15-02-2015
at 14:24 hrs
Fault occurred in 220kV Sedam-Shahpur line 1. KPTCL to provide Bus Bar protection and LBB
protection at Sedam S/s and furnish
the status of their implementation to PCSC forum.
2. KPTCL to implement A/R feature on 220 kV Sedam-
Tandur inter-state line.
KPTCL Mail received on 29-07-2015:
1. Procurement of Bus bar and LBB protection is in the final tendering stage.
2. Action is being taken to restore the carrier protection for 220kV Sedam-
Tandoor line. AR will be enabled after restoration of PLCC.
Pending
42/I/2
(GD)
Complete
outage of
220kV
Ambewadi
substation of
KPTCL
12-03-2015
at 7:51 hrs
Fault in 220kV Ambewadi-Nagjheri line-2 1. KPTCL shall provide A/R feature on Ambewadi – Ponda
220 kV D/C inter-state line.
2. Till the completion of R&M works for bus bar and LBB
protection, KPTCL shall explore
the possibility of having split bus operation at Ambewadi
and submit the details of the
same to PCSC forum.
KPTCL Mail received on 29-07-2015:
1. Procurement of Bus bar and LBB protection is in the final tendering stage.
2. Action is being taken to restore the carrier protection for 220kV Sedam-
Tandoor line. AR will be enabled after restoration of PLCC.
Pending
41/I/1 GD-1 at 220kV
Kadra power
Station of
KPCL
16-02-2015
at 12:56 hrs
Triggering incident was B-phase to earth fault
had occurred in 220kV Kadra-Kodasalli line.
Line tripped from Kodasalli end only. 220kV
Kaiga-Kadra tripped in Zone-3 from Kaiga
end. Tripping of evacuating lines caused bus
shut down at Kadra hydro station.
1. KPCL to make functional the Main2 (EPAC) relay
with the help of KPTCL at the earliest.
2. KPCL to investigate the reason for DC fuse fail
during transient fault in 220kV Kadra-Kodasalli line
including the testing/ checking of DC supply cables, breaker
control cables, and trip coils.
3. KPCL to ensure supply for Main-1& Main-2
protections, Trip Coils (TC1, TC2) from separate battery
banks.
KPCL
40/I/1 GD-1 at 220kV
Ambewadi
Station of
KPTCL
22-12-2014
at 21:22 hrs
Triggering incident was B-phase to earth fault
in 220kV Ambewadi- Nagzari line-1. B-pole
of breaker did not open at Ambewadi end.
LBB protection not available at Ambewadi
end. All elements tripped on Zone-2 from
remote ends.
1. Till the completion of R&M works for bus bar and LBB
protection, KPTCL shall explore the possibility of having
split bus operation at Ambewadi and submit the details of
the same to PCSC forum.
2. KPTCL shall provide the details of the tripping of Supa
hydro station connected downstream from 110 kV bus.
KPTCL Mail recieved on 29-07-2015:
Action is being taken by KPTCL for operating Ambewadi in split bus mode.
Problem in bus coupler breaker is attended.Isolator overhaulling work is
completed.PTs are already provided to 220kV Bus-II. After commissioning of
Bus-II PTs, Ambewadi can be operated in split bus mode. Pending works will
be completed within a months time.
KPTCL mail recieved on 23-01-2016:
Bus-II PTs yet to be commissioned.Planned to complete before end of April-
2016.
Pending
Mail received on 28-05-2015:
1. Main-2 relays already installed and commissioned.
2. DC fuses are intact. Till date no such incidence occurred.
3. Possibility of DC-1 & DC-2 arrangement and splitting of DC will be
reviewed.
Mail received on 07-07-2015 , 21-10-2015 and 23-11-2015:
1. Completed.
2. Completed.
3. Possibility of DC-1 & DC-2 arrangement and splitting of DC will be
reviewed.
Pending
KPTCL mail received on 23-01-2016:
1. Bus bar protection panels pocured and erected at Sedam. Wiring , testing
,commissioning is being taken up.Planned to complete by April 2016.
2. Action is being taken to restore the carrier protection for 220kV Sedam-
Tandoor line. AR will be enabled after restoration of PLCC.
Pending41/I/4 Complete
outage at
220kV Sedam
Substation of
KPTCL (GD-
1)
27-01-2015
at 8.00 hrs
R-Phase to ground fault occurred on 220kV
Sedam-Shahpur line. Fault not cleared from
Sedam end due to stuck-breaker condition.
While the Sedam- Sahapur line tripped from
Shahapur end in Zone-1, the other 220 kv lines
from Sedam tripped at remote ends in Zone-2.
This caused complete outage of 220kV Sedam
substation.
1. KPTCL to provide Bus bar and LBB protections for
220 kV bus at Sedam S/s.
2. KPTCL to implement A/R feature on 220 kV Sedam-
Tandur inter-state line.
KPTCL
Annexure- II
Page 4 of 20
43/II/1
4
Tripping of
400/220kV
ICT-1 at
BTPS
14-01-2015
at 1:09
hrs
ICT tripped due to operation of Over current
and Earth fault relay
KPCL to check the possibility of providing line differential
protection between RTPS and Yermarus stations.
KPCL Mail received on 07-09-2015 , 21-10-2015 and 23-11-2015:
Revised relay settings are awaited from KPTCL.
Revised relay settings furnished by KPTCL will be incorporated in co-ordination
with KPTCL shortly.
Pending
45/III/
12
Tripping of
400kV Raichur-
BTPS line
01-06-2015
at 01:02 hrs
line tripped on R-phase to earth fault. Line did
not auto-reclose
KPCL to make A/R operational on 400 kV RTPS – BTPS
S/C line at both ends.
KPCL Mail recieved on 23-11-2015:
Completed at RTPS end.
Pending at
BTPS end.
42/II/2 Tripping of
220kV
Chikodi-
Talandage and
220kV Chikodi-
Mudshingi line
20-02-2015
at
06:40 hrs
Lines tripped during test charging 220kV
Chikodi-Belgaum line-2 from Chikodi
end.
1. KPTCL to provide A/R feature on the 220 kV Chikkodi –
Talandage, and 220 kV Chikkodi –Mudashinge inter-state
lines.
2. KPTCL to carry out E/F relay coordination for Chikkodi -
Talandage and Chikkodi –
Mudashinge lines in coordination with Maharashtra.
KPTCL KPTCL mail received on 23-01-2016:
1) Replaced existing VXL by ABB make C&R panel for both interstate lines on
21.04.2015. The ABB Engineer visited 220KV Chikodi on 05.11.2015 for
enabling AR system to existing ABB make REL511 relay for both interstate
line, but AR system not enable due to internal cards faulty. Hence action is being
taken to replace the ABB,REL511 distance relays within a months time.
Pending
46/II/2
1
Trippings at
220kV Raichur
TPS
07-06-2015
at 01:35 hrs
1. KPCL to check the operation of anti-pumping relay on
220 kV side and keep it in healthy condition.
2. KPCL to provide manual reset to the 220 kV side master
trip relay.
3. KPCL to use both the 220 kV buses as main buses under
normal operation, and should go for single bus operation
only during emergencies.
KPCL Mail recieved on 23-11-2015:
1) Completed
2) Completed.
3) Two bus operation for 220kV buses : In place of existing CT switching relays,
High speed manual heavy duty change over switch of sufficient current capacity
will be retrofitted to all feeders at 220kV station and same will be operated
manually during changeover of feeder by one bus to the other and this
arrangement may facilitate to put both buses in service. Time required for this
retrofit is around 90days . However, this work will be taken up only after
retrofitting of electromagnetic relays with numerical relays for Main-2 protection
of all 220kV lines, for which work is in progress.
Pending
44/II/3 Tripping of
220kV
Kaiga-
Kodasalli
and 220kV
Kodasalli-
Nagjheri line- 1
22-04-2015
at
20:28 hrs
220kV Kodasalli-Nagjheri line-1 tripped from
Kodasalli end on operation of
distance protection, zone-2.
220kV Kodasalli-Nagjheri line-1&2 is kept
opened from Nagjheri end, hence fault
could not be cleared with carrier aided
protection. Backup earth fault relay at
Kaiga end got operated during the event and
resulted in tripping of 220kV Kaiga-
Kodasalli line from Kaiga end.
1. KPCL to check the possibility of implementing
Permissive Over Reach (POR) with Echo feature at
Kodasally end.
2. If the above is not possible, KPCL shall check the
possibility of keeping the 220kV
Kodasalli-Nagjheri lines OPEN at Kodasalli end and idle-
charged at Nagjheri end, and
implement the same.
KPCL Mail received on 07.07.2015:
The matter had been discussed with KPTCL. KPTCL recommended to keep
Zone-2 time lever to zero. If this is acceptable, then the same shall be
incorporated immediately.
Mail received on 07-09-2015 , 21-10-2015 and 23-11-2015:
The matter has been discussed with KPTCL. KPTCL recommended to keep
Zone-2 time lever to zero.
If this is acceptable to SRLDC, then the same shall be incorporated
immediately.Reply from SRLDC is awaited.
Pending
Annexure- II
Page 5 of 20
47/III/
8
Tripping of
220kV
Ambewadi-
Ponda line-2
02-08-2015
at 13:20 hrs
Line tripped on a transient fault in B-phase.
There is no
provision for auto reclose.
47/III/
10
Tripping of
220kV
Ambewadi-
Ponda line-1
08-08-2015
at 10:51
hrs and 09-08-
2015 at
11:15 hrs
Line tripped on a B-phase to earth fault. Line
tripped as there is no provision for auto-reclose
47/III/
12
Tripping of
220kV
Ambewadi-
Ponda line-1
17-08-2015
at 13:20 hrs
Line tripped on a transient fault . There is no
provision for Auto reclose.
Till A/R is put into service on Ambewadi-Ponda line-1,
KPTCL to reduce Zone-2 time setting to zero sec. at
Ambewadi end.
KPTCL Yet to be informed Pending
PendingYet to be informedKPTCL KPTCL to revise distance relay settings at Nelamangala
end for 220 kV Nelamangala – Hebbal - Peenya line – 1 for
the effective line length of 17 km. These new settings can be
appropriately reviewed as and when the tie-arrangement at
Hebbal is done away with.
All connected 220kV lines and transformers
were taken on 220kV North bus as South bus
was under shut down for conversion of strung
bus to rigid bus and isolator replacement under
R&M works. Failure of HV side Y phase CT
of 150MVA Transformer-3 occurred at Peenya
Substation which resulted in operation of
Differential and HV REF protection. The
failure of CT also resulted in a 220kV bus fault
in North Bus.
27-09-2015
at 4:23:17 hrs
Complete
outage of
220kV Peenya
Substation in
Karnataka
48/I/2
(GD)
PendingYet to be informedKPTCLKPTCL to activate non-directional Over Current protection
with a time delay of 600-800 msec for Fuse
failure condition at Lingasugur.
220kV RTPS-Lingasugur line-2 tripped at
TPS end on operation of distance
protection zone-1. 400/220kV ICT-2 got
tripped on operation of earth fault
protection. 220kV RTPS-Lingasugur line-
1&3 tripped on distance protection
zone-2 and zone-3 respectively. Due to
tripping of ICT-2, the running units got
overloaded and it was mentioned that
under frequency occurred as units are
on load control. The Units got tripped
on under frequency.
06-08-2015
at 4:51 hrs
47/II/1
3
Tripping of
Unit-1&2
along with
400/220kV
ICT-2 at
Raichur TPS
Annexure- II
Page 6 of 20
48/I/3
(GD)
Outage of
220kV
Ambewadi
station in
Karnataka
30-09-2015
at 10:41 hrs
220kV Ambewadi-Nagjheri line-2 tripped on B-
phase to earth fault. This resulted in loss of
supply to 220kV Ambewadi bus. 220kV
Ambewadi-Ponda line-1&2 were hand tripped
after deenergization of bus at Ambewadi.
KPTCL to fast-track providing A/R on all 220 kV lines
emanating from Ambewadi SS to prevent Station shut-down
on temporary faults.
KPTCL KPTCL mail received on 23-01-2016:
Will be complied in a months time.
Pending
48/I/4
(GD)
Complete
outage of 220
kV HSR
substation of
Karnataka
06-10-2015
at 16:32 hrs
All connected 220kV lines at 220kV HSR
substation i.e. Somanahalli, EPIP, Hoody and
Nagnathapura tripped during the incident.
Triggering incident was fault in 220kV HSR-
EPIP line
KPTCL to review distance relay settings at Naganathpura
SS in view of LILO arrangement at HSR Lay-out.
KPTCL KPTCL mail received on 23-01-2016:
ABB make REL 670 type distance relays provided to Somanahalli and hoody
lines. Planned to commission within 10 days.
Pending
49/II/1
5
Trippings at
Raichur TPS
12-11-2015
at 00:30 hrs
Running Unit-4, 5 and Unit-8 and 400kV
RTPS-Yeramaras TPS feeder got tripped due
to de-energization of both 400kV Bus-1&2 at
Raichur TPS
1. KPCL to carry out hot-line washing of RTPS-connected
lines regularly to avoid trippings due to fog and dust.
2. KPCL may see the feasibility of providing breaker
flashover protection at RTPS, and implement the same if
possible.
KPCL Yet to be informed Pending
220kV Nagjheri-Ambewadi line-1 tripped at
13:33 hrs due to B phase to earth fault.
Ambewadi was radially fed from Nagjheri
power station through 220kV Nagjheri-
Ambewadi line-2. Tripping of this line caused
220kV Bus shut down at Ambewadi and
remaining lines and transformers were hand
tripped
49/I/1.
3
(GD)
Complete
outage of
220kV
Ambewadi
Substation of
KPTCL
29.10.2015 at
14:34 hrs
PendingYet to be informedKPTCL1. KPCL to provide A/R on all 220 kV lines emanating from
Nagjheri PH.
2. KPTCL to provide A/R on all 220 kV lines emanating
from Ambewadi SS.
Annexure- II
Page 7 of 20
17-01-2016
at 18:53 hrs
Multiple
tripping at
400kV Guttur
sub-station
51/II/2
1
PendingYet to be informedKPCL/
KPTCL
1. To avoid tripping of transmission lines on transient faults,
KPCL/ KPTCL is recommended to carry out periodic
patrolling of lines, and ensure their proper maintenance by
carrying out jungle/ bushing clearance and trimming of tree
branches within the RoW of transmission lines as per the
SRPC transmission line patrolling guidelines (available
under the menu item "All Uploads Operation
Miscellaneous Transmission Line Patrolling Protocol /
Guidelines for Southern Region" on SRPC website).
2. KPCL/ KPTCL to review operation of SPS at NPH for
functionality (reduction of generation with tripping of
evacuating lines) and healthiness.
3. KPCL to put 220 kV Kodasalli - Nagjheri D/C lines into
service if more than 200 MW generation from Kali Complex
(with Nagheri Contribution not less than 50 MW) is ensured
on sustained basis.
220kV lines from Nagjheri power house started
tripping from 11:00 hrs due to fault in lines.
The sequence of tripping is shown in SOE list.
At 12:33 hrs, 220kV Narendra-Ambewadi
lines-1&2 got tripped which resulted in loss of
evacuation path to Nagjheri station resulting in
tripping of running Units and complete outage
at Nagjhheri power station. 220kV Ambewadi
station also got de-energized due to tripping of
source feeders i.e. 220kV Narendra-Ambewadi-
1&2 and 220kV Nagjheri-Ambewadi-1&2.
22-02-2016
at 12:36 hrs
Complete
outage of
220kV
Nagjheri power
station and
220kV
Ambewadi
substation of
KPTCL
51/I/3
(GD)
PendingYet to be informedKPTCL 1. KPTCL to configure all DR’s and EL’s at 400 kV Guttur
SS so that they will also get triggered for BBP operation.
2. KPTCL to ensure time-synchronization of all DR’s and
EL’s with GPS at their 400 kV Guttur SS.
Failure of Lightning Arrestor of Y-phase Line
Reactor of 400kV Guttur-Hiriyur line-1 and
line tripped on distance protection Zone-1. Bus-
bar protection of 400kV Bus-2 at Guttur
substation also got operated during the event
sensing this through fault. 400/220 kV ICT-1
& 2 at Guttur, 400kV Kaiga-Guttur-2, 400kV
Guttur-Narendra-2, 400kV Guttur-Hiriyur-2
and 400kV Guttur-Munirabad which are on
400kV Bus-2 got tripped during the incident.
400kV Guttur-Narendra-1 which was on Bus-1
also tripped at the same time.
Annexure- II
Page 8 of 20
48/I/1
(GD)
Disturbance in
220kV
Tamilnadu
system
05-09-2015
at 14:04 hrs
Complete outage of 230kV Palladam, 230 kV
Othakalmandapam S/s, 230 kV Coimbatore
S/s, 230 kV Thudialur and 230 kV
Sadayapalayam S/s
TANTRANSCO to take suitable measures like installing
more stub-towers along 230 kV OK Mandapam – Myvady
line to avoid excessive sag due to over-loading.
TANTRANS
CO
TANTRANSCO Mail received on 19-02-2016:
230kV Othakalmandapam - Myvadi feeder will be made LILO at Kongal Nagar.
Line restringing will be carried out along with the above proposal.
Pending
43/II/5 Tripping of
400kV
Alamathy-
SVChatram
line-1&2
and 400/230kV
ICT
at S.V.Chatram
29-03-2015
at
15:29 hrs
Tamil NaduLine-2 tripped on R-phase to earth fault.
Line autoreclosed at SVChatram end and failed
to reclose at Alamathy end. Bphase to earth
fault in line-1. Line tried for A/r but due to
permanent fault line did not reclose. ICT
tripped on operation of over flux protection.
PendingTANTRANSCO vide their mail dated 24.06.15 informed that different relays in
Main-I & Main-II would be ensured at the earliest.
Mail recieved on 24-07-2015:
Different relays in Main-I & Main-II will be ensured.
TANTRANS
CO
TANTRANSCO was requested to swap the relays between
two stations, so that
Main-1 and Main-2 will be of different make at each station.
Annexure- II
Page 9 of 20
50/II/2 Tripping of
400kV
Alamathy-
S.V.Chatram
line-2
08-11-2015
at 10:48 hrs
Line tripped on D.T. receive on CHANNEL-2
at SV.Chatram end when the operator at
ALAMATHY S/S end tried to close Alamathy-
SVChatram-1&2 Feeder Tie Breaker.
Suspected DC earth fault had caused the
initiation of direct trip.
TANTRANSCO to provide A/R for 400 kV bay Tie-CB’s
at Alamathy SS and SV Chatram SS.
TANTRANS
CO
TANTRANSCO Mail received on 19-02-2016:
Instruction has been issued to enable Auto Reclosure feature in 400kV Tie
Breakers. The same will be informed to SRPC after completion.
Pending
49/I/1.
5
(GD)
Complete
outage of
S.P.Koil
station of
TANTRANSC
O and
generation loss
at MAPS
09-11-2015at
09:33 hrs
Fault had occurred in 230kV MAPS-S.P.Koil
feeder-1. LBB protection got operated as
breaker of this feeder was under lockout and
resulted in tripping of 230kV bus at S.P.Koil.
Unit-1&2 at MAPS due to loss of evacuating
feeders i.e. 230kV MAPS-S.P.Koil feeder-1&2
1. TANTRANSCO to ensure correctness of operation of
LBB relays at SP Koil.
2. TANTRANSCO & MAPS to furnish their respective
compliance report of the recommendations of to-be-
conducted PSAG-14 meeting at MAPS, Kalapakkam.
TANTRANS
CO
TANTRANSCO Mail received on 19-02-2016:
LBB scheme will be checked to ensure correctness of operation while availing
Line Clear.
TANTRANSCO and MAPS mail received on 25-01-2016:
Complaince report was submitted with respect to the recommendations given in
the Minutes of PSAG-14 Meeting.
Pending
50/I/3
(GD)
Complete
outage of
230kV
Mywadi station
of
TANTRANSC
O
21-12-2015
at 6:28 hrs
Busbar protection got operated for a fault in
230kV Mywadi-Anaikadavu line
1. TANTRANSCO to examine the feasibility of providing
two main-zone operation for bus bar protection by exploring
various alternatives like replacing existing bus-coupler CB
with a hybrid bus-coupler CB that comes with inbuilt CT,
replacing existing BBP relay with another suitable relay that
supports two main-zone operation, and implement the same.
TANTRANS
CO
TANTRANSCO Mail received on 19-02-2016:
Revision of Bus Bar Protection setting was carried out. The stabilizing voltage
setting was raised from 410 to 450 volts. After completing the necessary test, the
bus bar protection put in to service on 29.12.2015.
Pending
Annexure- II
Page 10 of 20
50/II/1
7
Tripping of
400/230kV
Myvadi ICT-3
27-11-2015
at 17:26 hrs
400/230kV Myvadi ICT-3 tripped due to the
operation of 230 kV CB LBB protection at 230
KV bus (TNEB) of Myvadi station.
TANTRANSCO to check the LBB scheme for LV-3, and
furnish the remedial measures taken to PCSC forum.
TANTRANS
CO
TANTRANSCO Mail received on 19-02-2016:
LBB scheme will be tested while availing Line Clear.
Pending
PendingYet to be informedTANGEDCO NTECL, Vallur to furnish a report detailing the reasons for
mal-operation of Vallur end relays for a fault on Alamathy-
Tiruvalam line-1, and remedial measures taken to PCSC
forum. In the report, their preparedness for implementing
line differential protection on Vallur-Alamathy lines may
also be indicated.
400kV Vallur-Alamathy Line-2 got tripped
from Vallur end during failure of Y-phase LA
in 400kV Alamathy-Tiruvalam line. Protection
at Vallur end tried for an auto-reclose and gave
a 3 phase trip.
13-12-2015
at 22:42 hrs
Tripping of
400kV
Alamathy-
Tiruvalam line-
1 and 400kV
Alamathy-
Vallur line-2
51/II/4
PendingYet to be informedTANTRANS
CO
1. TANTRANSCO to provide split-bus operation with bus
sectionalizer CB for their 230 kV Madurai (Chekanurani)
SS.
2. TANTRANSCO to provide two main-zone operation for
the numerical BBP that is being commissioned.
3. TANTRANSCO to examine the feasibility of providing
Re-Trip feature for the LBB protection, and accordingly take
steps for implementing the same.
Fault had occurred in 230kV Madurai-
Sembatty line. Trip from distance relay was not
extended to breaker due to protection DC fail.
LBB protection got operated resulting in a
busbar trip at 230kV Madurai substation. All
elements got tripped as there is a single bus
operation at 230kV Madurai S/s
19-01-2016
at 11:56 hrs
Complete
outage of
230kV
Madurai S/s
(Chekanaurani)
of
TANTRANSC
O
51/I/1
(GD)
50/II/1
6
Kerala44/I/1
(GD)
Complete
outage of
Idukki Hydro
Power Station
(GD-1)
28-04-2015
at 12:30 Hrs
220 kV breaker of unit-3 at Idukki Power
house flashed and bus differential protection
acted. All Generators (6Nos.) along with all
220 kV feeders tripped during the incident.
1. KSEB to reduce sensitivity of REF protection
appropriately at Idukki PH.
2. KSEB to replace/ repair the faulty breaker.
3. KSEB to check the PLCC equipment at New Pallam and
inform the remedial measures taken to PCSC forum.
KSEB Mail recieved on 30-10-2015:
1. Purchase procedures is still in progress.
2. Replaced.
3. PLCC equipment Tested and found OK.
Mail recieved on 03-03-2016:
1. Even though repeated plans to have a joint inspection with M/s.ABB who is
the OEM of the relay panel for replacing the relays with numerical ones, the
same could not become successful. Finally, the inspection has been fixed on
15.03.2016. It has been planned to replace existing REF protection with low
impedance ones after retrofitting the numerical ones of OEM.
Pending
(Recomme
ndation
No.1)
PendingTANTRANSCO Mail received on 19-02-2016:
400kV S.V.Chatram - Alamathy -1 feeder 'C' phase jumper cut at Loc.No.178
from Alamathy end and created temporary fault with 400kV S.V.Chatram -
Alamathy -2 feeder 'A' phase jumper. Both feeders runs on the same tower.
PUTT Trip and AR successful at S.V.Chatram end. AR lockout at Alamathy
end. Direct Trip received at S.V.Chatram end due to wrong operation of TNC
switch at Alamathy end.
TANTRANS
CO
TANTRANSCO to check and ensure the healthiness of
A/R scheme at Alamathy end on 400 kV Alamathy – SV
Chatram line – 2.
400KV Aalmathy-S.V.Chatram line-1 tripped
on B-phase to earth fault. Line auto reclosed
and at both end subsequently A/R locked out
due to permanent fault.
400KV Alamathy-S.V.Chatram line-2 Line
tripped on R-phase to earth fault. Line
autoreclosed at S.V.Chatram and failed to auto-
reclose at S.V.Chatram end.
27-11-2015
at 15:35 hrs
Tripping of
400kV
Alamathy-
S.V.Chatram
lines - 1&2
Annexure- II
Page 11 of 20
42/II/2
3
Tripping of
HVDC
Bhadravathi
Pole-1
18-03-2015
at
13:55 hrs
Pole tripped due to failure of auxiliary supply PGCIL (SR-I) to submit the compliance report on PSAG-11
recommendations to PCSC
forum.
PGCIL Reply received during 46th PCSC meeting:
Tertiary Transformer charged and auxiliary power for HVDC is being availed
from tertiary widings of ICT.
Pending
Yet to be informed Pending42/II/7 Tripping of
400kV
Jeypore-
Gazuwaka line-
1&2 and
tripping of
HVDC back to
back pole-
1&2 at
Gazuwaka
23-02-2015
at
13:34 hrs
HVDC pole-1 got tripped due to failure
of 4 no. power supply card. HVDC
pole-2 tripped on DC low voltage trip.
400kV Jeypore-Gazuwaka line-1&2
tripped due to operation of Over voltage
protection at Gazuwaka end.
PGCIL (SR-II) to submit the report of M/s ABB’s on
preventing supply card failures.
PGCIL
PGCIL34/I/7 HVDC
BHADRAVA
THI POLE 2
18-07-2014 As reported pole-2 tripped due on 5th
harmonic alarm.
1. Complete analysis of the faults and rectification/remedial
action taken to avert similar occurrence in the HVDC Back
to Back station shall be submitted.
2. The PCSC forum recommended PGCIL, SRTS-I take up
the issue with WRTS to submit the report as per IEGC
guidelines.
3. SRLDC is also requested to send a letter to WRLDC to
submit the reports to SR also.
4. Based on the SRTS/SRLDC correspondences, SRPC
would take it up with WR and PGCIL if the issue is not
getting resolved.
PGCIL Reply received during 46th PCSC meeting:
Being pursued with POWERGRID, WR-1
Pending
PGCIL Mail received on 02-09-2015:
The scheme was tested thoroughly found normal.
Pending to
check the
possibility
of re-trip
feature
PendingReply received during 46th PCSC meeting:
Operation is in-order as per OEM manual (ABB HVDC)
PGCILPGCIL (SR-I) to furnish the reasons for Converter
Transformer differential protection
operation for Pole-2 along with the remedial measures taken.
HVDC Pole-1 at Gazuwaka tripped due to
tripping of filter banks and Pole-2 tripped
due to operation of differential protection.
400kV Jeypore-Gazuwaka line-1 tripped
on over-voltage from Gazuwaka end.
14-03-2015
at
17:12 hrs
Tripping of
HVDC pole-
1&2
at Gazuwaka
and
400kV 400kV
Jeypore
Gajuwaka
line -1
42/II/2
2
43/II/2 Multiple
tripping
at 400/230kV
Hosur
substation
of Powergrid
26-03-2015
at 15:40 hrs
230kV Bus-2 at Hosur (PG) got
tripped as spurious initiation got
extended to LBB relay of 230kV
Hosur-Hosur(PG) line at Hosur(PG)
end due to shorting of contacts in
lockout relay. 400/230kV ICT-2, ICT-
3, 230kV Hosur-Vinnamangalam,
230kV Hosur(PG)-Hosur which were
connected to Bus-2 got tripped along
with bus coupler breaker
PGCIL (SR-II) to check the possibility of providing re-trip
feature in LBB relay.
Annexure- II
Page 12 of 20
44/I/3
(GD)
765 kV
Raichur-
Sholapur line 1
&
2 tripped
24-05-2015
at 19:19 hrs
Tripped on Overload. 1. PGCIL to provide the status of healthiness of SPS contact
logic in SRLDC’s SCADA.
2. PGCIL to furnish the details of the implemented SPS-7
scheme including logic diagram to PCSC forum.
PGCIL Yet to be informed Pending
44/II/4 Tripping of
400kV
Ramagundam-
Hyderabad line-
3,
400kV
Hyderabad-
Malkaram line-
1 and 400kV
Bus-1
at Hyderabad
23-04-2015
at
15:11 hrs
400kV Ramagundam-Hyderabad line-3 at
ramagundam end only due to DT receive.
400kV Hyderabad-Malkaram line-1
tripped at Hyderbad end only and was
holding from Malkaram end. 400kV Bus-1 at
Hyderabad due to operation of bus
bar protection.
PendingYet to be informedPGCILPGCIL (SR-I) to check healthiness of PLCC panels at
Hyderabad SS, and repair/ replace
them, if necessary.
Annexure- II
Page 13 of 20
44/II/6 Multiple
tripping at
Vemagiri
substation of
APTRANSCO
25-04-2015
at 10:04
hrs
400kV Vemagiri-Vijayawada line-1&3, 400kV
Vemagiri-Goutami line-2, 400kV Vemagiri-
Konaseema line-2 and 400/220kV ICT-2 at
Vemagiri tripped
during the incident. Triggering incident
was failure of B-phase L.A in 400kV
Vijayawada-Vemagiri line-1 at Vemagiri.
1. PGCIL (SR-I) to enable Auto reclosure feature at
Vijayawada end.
2. PGCIL (SR-I) to check distance relay settings for
Vijayawada – Vemagiri line 3, and
furnish a compliance report to PCSC forum.
PGCIL Yet to be informed Pending
44/II/8 Tripping of
400kV
Gooty-NPS
line-2
26-04-2015
at 13:16
hrs
R-phase to earth fault had occurred in
line. Lines auto-reclosed at gooty end
and later tripped due to DT receive from
NPS end.
PGCIL (SR-I) to coordinate STUB protection settings with
the distance protection time
settings at NPS.
PGCIL Yet to be informed Pending
45/II/2
1
Tripping of
400/220kV
ICT-1 at Gooty
Substation
03-06-2015
at 12:30 hrs
ICT tripped due to mal-operation of
differential relay
1. PGCIL to follow IS and CEA regulations while carrying
out maintenance work.
2. PGCIL to furnish a report on what caused the ICT-1
tripping including remedial measures.
PGCIL Yet to be informed Pending
46/II/1 Tripping of
400/220kV
ICT-2 at
Nagarjunsagar
Station
16-06-2015
at 18:12 hrs&
19:18 hrs
ICT-2 tripped due to mal-operation of 86B
relay due to suspected DC earth fault.
PGCIL (SR-I) to furnish a detailed report on ICT-2& Bus II
outage at 19.18 hrs on 16.06.2015 along with the remedial
measures taken.
PGCIL Yet to be informed Pending
46/II/4 Tripping of
400/220kV
ICT-2 at Gooty
substation
22-06-2015
at 13:06 hrs
At 220kV Gooty Switching Station, 220KV
Gooty Receiving Station feeder line side Y-
Phase jumper connected between line isolator
to boom resulting in a 220kV Bus fault. This
resulted in tripping of ICT-2 and 220kV
feeders connected to 220KV BUS-II.
PGCIL (SR-I) to furnish a detailed report as to what caused
LBB operation at 400 kV Gooty SS along with the remedial
measures taken.
PGCIL Yet to be informed Pending
45/II/1
5
Tripping of
765kV Raichur-
Solapur line-
1&2
03-05-2015
at 4:13 hrs
Lines tripped on transient fault. Auto reclose
was un-successful. SR &NEW grid separated
due to tripping of 765kV lines
To avoid tripping of transmission lines on transient faults,
PGCIL is recommended to carry out periodic patrolling of
lines, and ensure their proper maintenance by carrying out
jungle/ bushing clearance and trimming of tree branches
within the RoW of transmission lines as per the SRPC
transmission line patrolling guidelines (available under the
menu item "All Uploads Operation Miscellaneous
Transmission Line Patrolling Protocol / Guidelines for
Southern Region" on SRPC website).
PGCIL Yet to be informed Pending
PendingYet to be informedPGCIL1. PGCIL (SR-I) to submit the action taken report on the
measures suggested by their OEM.
2. PGCIL (SR-I) to check for the availability of Chatter
Disable feature in P141 and
configure it appropriately to block operation of REF
protection on DC fluctuations.
REF protection of Line reactor of
Nellore-1&2 and Tiruvalam line-1 maloperated
due to DC earth fault
25-04-2015
at
18:10 hrs
Tripping of
765kV
Kurnool-
Tiruvalam line-
1
and 765kV
Kurnool-
NPS-1
44/II/7
Annexure- II
Page 14 of 20
47/II/1
1
Tripping of
HVDC
Bhadrawati
Pole-1
05-08-2015
at 10:53 hrs
Main pump-2 of valve cooling got
tripped during dip in 33kV auxiliary bus
voltage. Valve cooling flow got reduced
due to tripping of pump and resulting in
tripping of pole-1
PGCIL (SR-I) to furnish compliance report on PSAG-11
recommendations without further delay to PCSC
forum.
PGCIL Yet to be informed Pending
765 kV
RAICHUR -
SHOLAPUR 1
and 2
04-09-2015
at
19:25 hrs
Sholapur -1 and 2 Feeder got tripped at
Raichur end on operation of over current
protection in Main-1 distance relay and
holding from Solapur end on 04.09.2015 at
19:24:42 Hrs
765 KV
RAICHUR –
KURNOOL 2
04-09-2015
at
19:25 hrs
Kurnool -II Feeder got tripped on B-N fault
and holding from Kurnool end (successfully
auto-reclosed at Kurnool end) subsequently
tripped at other end on operation of Over
Voltage stg-1 protection at Raichur end on
04.09.2015 at 19:24 Hrs
49/II/4 Tripping of
400kV Gooty-
NPS line-1
13-10-2015at
10:15 hrs
Direct Trip was sent to NPS end of line-1
during opening of Main CB of Gooty-NPS line-
2 at Gooty end. This resulted in tripping of line-
1 at NPS and line was holding from Gooty.
Over voltage protection got operated at NPS
end and resulted in tripping of line
1. PGCIL (SR-I) to configure time scale resolution in Event
Logger to msec. at Nelllore PS (NPS) and furnish DR
corresponding to OVR, Stag-I operation at NPS end during
the tripping event.
2. PGCIL (SR-I) to ensure time-sync of DR’s and EL’s with
GPS at Gooty and NPS.
PGCIL Yet to be informed Pending
1. PGCIL (SR-I) to furnish a report detailing the sequence of
events including the remedial measures taken to PCSC
forum.
2. PGCIL (SR-I) to verify and ensure time-synchronizationof
DR& EL with GPS at both Gooty and NPS.
3. PGCIL (SR-I) to check and resolve,in co-ordination with
APTRANSCO, the professed Phase-Discrepancy that is
found to be occurring between 400 kV Gooty (PG) SS and
the surrounding 220 kV network of APTRANSCO in the
event of a fault.
Breaker at NPS end tripped on Direct Trip
receipt from NPS end. After 4 seconds, over
voltage protection operated at NPS end as
observed from EL, and direct trip was sent to
Gooty.
01-07-2015
at 09:59 hrs
Tripping of
400kV Gooty-
NPS line-1
46/II/1
3
28-07-2015
at 11.52.22
hrs.
Separation of
SR-grid and
NEW-grid
46/II/2
2
47/II/1
8
1. PGCIL (SR-I) to check the A/R scheme implemented
through BCU’s at all its GIS/ SAS substations for correct
operation.
2. PGCIL (SR-I) to ensure time-synchronization of DR &
EL of 765 kV Kurnool SS with GPS.
3. PGCIL (SR-I) to sort out the LEGEND ISSUE related to
tripping of the lines in the Event Logger of Raichur.
4. PGCIL (SR-I) to check & ensure the functionality &
healthiness of synchronization facility at Raichur end at the
earliest opportune time.
PGCIL Yet to be informed Pending
PendingYet to be informedPGCIL
PendingYet to be informedPGCIL1. PGCIL (SR-I) to obtain from PGCIL (WR-l) the reasons
for DT receipt from Sholapur end and furnish thesame along
with the remedial measures taken to PCSC forum.
2. PGClL (SR-I) to verify the logic implemented of SPS-1
and SPS-7 for the 76S kV Raichur - Sholapur link
byavailing the line shutdown at the earliest opportune time.
3. PGCIL (SR-I) to furnishthe details of the implemented
SPS-1 and SPS-7 schemes including their logicdiagrams to
PCSC forum.
Annexure- II
Page 15 of 20
51/II/2
2
Tripping of
400/220kV
ICT-1 at
Munirabad
18-01-2016
at 12:46 hrs
ICT-1 tripped during operation of tie bay
breaker
1. PGCIL (SR-I) to configure Event Logger (s) at
Munirabad to record event at msec level.
2. PGCIL (SR-I) to set right Time and Field Time values
being shown in EL to proper values.
PGCIL Yet to be informed Pending
51/III/
1
Tripping of
400kV
Vijayawada-
Nellore line-2
31-12-2015
at 12:02 hrs
Line tripped on Y phase to earth fault. Attempt
for auto-reclose / Un-successful auto-reclose
could not be established from the furnished
DR/ EL.
PGCIL (SR-I) to furnish a report bringing out the reasons
for non-operation of A/R during the tripping event, along
with remedial taken, to PCSC forum.
PGCIL Yet to be informed Pending
51/III/
2
Tripping of
400kV
Vijayawada-
Gajuwaka line-
1
05-01-2016
at 04:18 hrs
line tripped on a R-phase to earth fault. Line
auto-reclosed at Gajuwaka end and tripped
from Vijayawada end.
PGCIL (SR-I) to furnish a report bringing out the reasons
for non-operation of A/R during the tripping event, along
with remedial taken, to PCSC forum.
PGCIL Yet to be informed Pending
41/II/1
2
Tripping of
400KV Coastal-
NTPL line
13-02-2015
at 22:54 hrs
Line tripped B-phase to earth fault and later
tripped on R-Y phase fault. From Coastal end
D.R, Y & B poles of breaker opened first and
R-pole appears to be opened on Pole
discrepancy.
CEPL to check A/R scheme at their end. CEPL Yet to be informed Pending
41/IV/
2
400kV
Tuticorin PS-
NTPL line
09-02-2015
at 03:17 hrs
Y-phase to earth fault had occurred in line.
Line auto reclosed at Tuticorin PS end and
failed to reclose at NTPL end.
NTPL to check A/R scheme at their end. NTPL Yet to be informed Pending
44/III/
4
Tripping of
400kV
Coastal
(CEPL)-
Tuticorin
pooling
station
20-04-2015
at 12:35 hrs
Line tripped at Coastal energen end only and
was holding from TTRNPS
CEPL to furnish a detailed report on this trip event to PCSC
forum.
CEPL Yet to be informed Pending
Others
50/I/2
(GD)
Complete
outage of
TPCIL power
station
30-12-2015
at 06:02hrs
Running units at Thermal Powertech power
Station tripped due to tripping of 400kV
Nellore pooling station (NPS)-TPCIL line and
400kV Nellore pooling station (NPS)-ECC line
1.PGCIL (SR-I) to furnish Action Taken Report on the
findings of OEM on relay mal-operation at NPS end on 400
kV NPS – NCCK line to PCSC forum.
2. PGCIL (SR-I) to appropriately configure Station Event
Logger at NPS to record events at msec interval.
3. PGCIL (SR-I) to carry out PLCC end-to-end testing in
coordination with TPCIL for 400 kV NPS –TPCIL line.
4.PGCIL (SR-I), MEPL, SEL, TPCIL & NCC to take steps
to provide line differential protection at their respective ends
on all 400 kV lines (except Gooty line) emanating from
Nellore Pooling Station, and furnish an action plan to
implement the same.
PGCIL Yet to be informed Pending
Annexure- II
Page 16 of 20
46/II/3 Tripping of
400kV
Ramagundam-
Dichipalli line
21-06-2015
at 03:27 hrs
Line tripped on operation of overvoltage
protection at Ramagundam end and direct trip
was received at Dichipalli. Over-voltage
operation could not be established with D.R &
E.L submitted by Ramagundam station.
1. NTPC, Ramagundam to investigate the reasons for Over
Voltage alongside checking the drop off- to- pick-up ratio of
the OV relay.
2. The tripping is not as per the grading adopted for
Overvoltage, Stage-I protection (Grading is C2: 110% and 6
sec time delay) at Ramagundam. NTPC, Ramagundam to
check up the same.
NTPC Yet to be informed Pending
47/III/
2
Tripping of
400kV
Vemagiri –
GVK (JPD)
line-2
16-07-2015
at 17:02 hrs
R-phase to earth fault had occurred in line.
Line auto reclosed at Vemagiri end and failed
to reclose at GVK end.
GVK to put A/R into service at GVK Jegurupadu end on
400 kV GVK (Jegurupadu) – Vemagiri line-2.
GVK Yet to be informed Pending
48/II/1
6
Tripping of
400 kV Hassan
-Udupi line-1
05-10-2015
at 13:33
Line tripped due to B-E fault in Z2. Main 1
relay tripped in Z2. Three phase trip operated
at Hassan. Auto-reclose successful at other end
and line was charging from other end. Then
OV stage 1 picked up in Main2 relay and
operated in OV after the time delay
UPCL to furnish reasons for delayed operation of distance
relay in Zone-1 at their end, and the remedial measures
taken, if any.
UPCL Mail recieved on 19-11-2015 (UPCL):
The fault was of resistive nature, was sensed from Hassan end in Zone-2 reach.
The DR from UPCL indicates resistive high current prior to operation of Zone-1
in C Phase. This is seen as development of Zero sequence voltage and current
prior to Zone -1 operation.
The operation of single phase Z1 from UPCL end was correct followed by
successful AR operation.
Pending
51/II/7 Tripping of
400 kV
Vemagiri-
Gauthami-2
26-12-2015
at 00:01 hrs
Line tripped on operation of over voltage
protection at Gauthami end and direct trip was
received at Vemagiri. FIR, DR and EL of
Gouthami end was not available to validate the
over voltage tripping.
1. GVK Gautami to adjust drop-off to pick-up ratio to >
98% for the Over Voltage relays at Gautami end on 400 kV
Gautami – Vemagiri lines.
2. GVK Gautami to ensure time-sync of all DR’s & EL’s at
Gautami Station with GPS
GVK
Gautami
Yet to be informed Pending
PendingYet to be informedUPCL 1. UPCL to provide different make relays for Main-1 &
Main-2 at UPCL end on 400 kV UPCL – Hassan lines – 1 &
2.
2. UPCL to make GPS functional at their Station and ensure
time-sync of various DR’s and EL’s with GPS.
400kV Hassan-Udupi line-2 tripped on
Directional earth fault protection with Y-E
fault and direct trip was sent to Udupi end.
Directional Earth fault feature of Main-2 relay
at Hassan gave 3-ph trip after 2.6 seconds and
fault current in Y-phase was 1.1 kA. The
distance as well as DEF protection for 400kV
UPCL-Hassan line-2 at UPCL end did not
sense the fault. The generator transformer
backup earth fault protection (51N) had sensed
the fault and tripped both the running units at
UPCL leading to generation loss at UPCL
power station. Back up directional earth fault
protection at 220kV side of 400/220kV ICT’s
at UPCL did not sense the high resistance fault
in line-2
30-11-2015
at 17:22 hrs
Tripping of
400kV UPCL-
Hassan line-2
and running
Units-1&2 at
Udupi power
station
50/II/1
8
Annexure- II
Page 17 of 20
36/II/8 400kV
Raichur-
Munirabad line
07-09-2014 B-phase to earth fault had occurred in line.
Line auto reclosed at Munirabad end and failed
to reclose at Raichur end.
KPTCL:
PD (pole discrepancy) time delay would be changed.
PGCIL /
KPTCL
Yet to be informed Pending
38/II/5 400kV
Ramagundam-
Hyderabad line-
4
27-10-2014 Line tripped on Bphase
to earth fault.
Line did not auto
reclose at Hyderabad
end due to
PLCCmal-operation.
Planned to replace the PLCC system within a week's time at
both the ends during the shutdown.
NTPC/
PGCIL
Yet to be informed. Pending
40/II/3 Tripping of
400
kV
TALAGUPPA
– HASSAN
line
01-01-2015
at
13:38 hrs
On account of R-phase to earth fault, line
tripped at Hassan end due to operation of
distance Zone-2 and non-receipt of
carrier. From D.R of Talaguppa end it is
observed that fault had occurred in Yphase.
1. PGCIL and KPTCL to ascertain the reason for the
phase discrepancy in the relay operation and take suitable
remedial measures.
2. KPTCL to check the PLCC operation at Talaguppa
end and submit the report to the PCSC forum.
PGCIL/
KPTCL
Mail received on 27-05-2015 (KPTCL) & 29-07-2015:
End to end testing of PLCC has been done and problem in the PLCC is
atttended. Phase discripancy in the relay operation is to be checked jointly.
Mail recieved on 02-09-2015:
Problem is in identification of phases at Talguppa end. To be rectified by M/s
KPTCL.
Pending
42/II/1 Tripping of
400kV Coastal-
Tuticorin PS
line
19-02-2015
at
16:37 hrs
Line tripped at Coastal end only
due to suspected PLCC maloperation
and was holding from
Tuticorin PS end. Running Unit at
Coastal energen also got tripped
during the event.
PLCC end-to-end testing shall be carried out by CEPL and
Tuticorin PS (PGCIL-SR II) by
06.04.2015.
CEPL/
PGCIL(SR-II)
Mail received on 02-09-2015 and 25-11-2015:
On 11.06.2015 PLCC testing carried out by M/s ABB Engineer. ABB suspects
that the problem is with frequency interference related issue, and suggested to
change to new frequecies.
Pending
with CEPL
Miscellaneous
39/I/2 Tripping of
400Kv
Ghanapur-
Mamidipally
line
22-12-14
at 10:52 hrs,
24-12-14 at
11:32
hrs,
24-12-14 at
16:16 hrs
Due to PLCC Mal-operation at HYD S/S end,
DT received at MMPLY end and line got
tripped.
PGCIL is requested check up with the manufacturer to
resolve the issue and submit remedial measures to PCSC
forum.
PGCIL/
TSTRANSCO
Mail received on 26-05-2015 from TSTRANSCO:
On 27-12-2014 PGCIL requested to arrange services of OEM(Manufacturer)for
identifying the problem. TSTRANSCO arranged the same on 06-01-2015 and
the manufacturer testing and concluded that the problem in not in the newly
erected digital protection coupler at both ends and the issue is related to relay
panel at Ghanapur. [OEM minutes enclosed]
Pending
42/II/1
8
Multiple
tripping at
Raichur
thermal
power station
of
KPCL
09-03-2015
at
06:36 hrs
400kV Raichur TPS-Raichur(PG) line-
1&2, 400kV Raichur-Mahboobnagar,
Unit#7 and ICT-2 at RTPS tripped
during the incident. B phase to earth
fault had occurred in 400kV Raichur
TPS-Raichur line-1
1. KPCL to review REF setting (DMT or IDMTL) for unit-7
by first week of April, 2015 and
inform the same to PCSC forum.
2. TSTRANSCO to furnish Mehaboobnagar’s DR and EL
and the reasons for distance relay
operation at their end within a week’s time.
3. PGCIL (SR-I) to rectify the issues relating to A/R
operation, relay reach (Z2), reverse reach
(Z4) and SOTF auxiliary contacts within a week’s time, and
submit the actions taken to
PCSC forum.
KPCL/TSTR
ANSCO/PGC
IL (SR-I)
Mail received on 26-05-2015 from TSTRANSCO:
It is found that the main-2 ABB make REL316 type distance relay was
defective and same was replaced with MICOM P444 by M/s.PGCIL on 23.04-
2015. After replacement of main-II, DR can be extracted from this relay. For EL
in to service, some field winding is pending which is being taken up in this
month.
Pending
Annexure- II
Page 18 of 20
43/II/1
2
Multiple
tripping at
400kV
Raichur(PG)
and RTPS of
KPCL
11-04-2015at
18:04 hrs
400kV Raichur(PG)-Gooty line-2,
400kV Raichur TPS-Raichur(PG)
line-1&2, 400kV Raichur-
Mahboobnagar, Unit#5 at RTPS
tripped during the incident
KPCL, KPTCL and PGCIL (SR-I) to furnish the action
taken report on the
recommendations given by PSAG members held at Raichur
on 22-04-2015 and
23-04-2015.
KPCL/KPTC
L/ PGCIL(SR-
I)
Yet to be informed Pending
Tripping of
Unit 1 at
NCTPS
24-05-2015
at 19:13 hrs
ID Fan trip
Tripping of
Unit 1 at
MEPL
24-05-2015
at 19:13 hrs
Coal Mill tripped
Tripping of
Unit 1 at
Krishnapatnam
24-05-2015
at 19:17 hrs
Generator Protection operated
Tripping of
Unit-8 at RTPS
24-05-2015
at 19:19 hrs
Tripped on Overvoltage.
Complete
outage of
MEPL power
station
45/I/2
(GD)
PendingYet to be informedAPGENCO/
PGCIL (SR-I)
1. APGENCO to furnish to PCSC forum (i) A3-size Single
Line Diagram of SDSTPS, and (ii) the sequence of
events with time stamp showing the protection that opened
Tie-CB (405) at SDSTPS.
2. APGENCO to review STUB/TEED protection in all dias
at SDSTPS and ensure that they are configured
for instantaneous operation.
3. APGENCO to properly configure the STATE of the
tripping events so that they get recorded
appropriately like TRIP/ OPERATED in their corresponding
Event Loggers.
4. APGENCO to ensure time sync of all DR’s and EL’s at
SDSTPS.
5. PGCIL (SR-I) to provide line differential protection for
400 kV NPS –Nellore-PG lines 1 & 2.
44/I/3
(GD)
1. All Tripped units, viz., Krishnapatinam, MEPL, Raichur,
NCTPS to submit a detailed report
on this event including the remedial measures taken to PCSC
forum.
2. KPCL to check the excitation system of Unit 8 of RTPS,
and submit the remedial measures
taken to PCSC forum.
KPCL/
MEPL/
APGENCO/
TNEB
TANGEDCO vide their mail dated 07.07.2015 informed that as per the
discussion and recommendation of 44th meeting of PCSC held on 28.05.2015, a
time delay of 2 Sec had been introduced for the above tripping for all the ID
fans at NCTPS-II.
MEPL vide their mail dated 14.09.2015 informed that they have implemented 2
seconds delay for under voltage tripping of all Drag Chain Feeder Conveyors.
And this has been done for both the Units.
Pending
with
KPCL,
APGENC
O
PendingMEPL vide their mail dated 14.09.2015: informed the following
1. Tan Delta Testing of winding and DGA of Insulating Oil for all CTs was
carried out and normal.
2. Could not find any problem during internal checks hence we are in touch with
ABB for rectification work. Will be done by the end of 15th Oct'15
3. End to end testing of Carrier signals was carried out and found them healthy.
MEPL/
PGCIL(SR-I)/
SEL
1. MEPL to ensure healthiness of all CT’s by carrying out
Tan Delta and DGA tests wherever necessary.
2. MEPL to take suitable action to correct the operation of
tie-CB Bay Control Unit that caused LBB/ BBP operation.
3. PGCIL (SR-1) to carry out end-to-end PLCC testing in
coordination with MEPL and ensure that carrier-aided
protection on MEPL – NPS line is in healthy condition.
4. SEL to properly time-coordinate their Over Current
phase and Earth fault relays in consultation with MEPL.
Y phase CT failure at MEPL led to tripping of
400kV NPS-MEPL, 400kV SEPL-MEPL line
and Unit-2 at MEPL. Uni-1 was not in service
at the time of tripping
20-05-2015
at 20:38 hrs
As per FIR submitted, CT damage observed in
Chitoor-Main bay (404). Main breakers
connected to bus-1 (401, 404, 407, 410) got
tripped on operation of bus bar protection. Unit-
1 tripped on operation of MFT. Unit-2 was not
in service
08-09-2015
at 18:20 hrs
Complete
outage of
Krishnapatnam
TPS
47/I/2
(GD)
Annexure- II
Page 19 of 20
47/II/9 Tripping of
400kV Coastal-
NTPL line and
running units
at NTPL
03-08-2015
at
15:43 hrs
R-phase to earth fault had occurred in 400 kV
Coastal NTPL line. Line autoreclosed at NTPL
end and failed to reclose at Coatal end. Auto
reclose block was persisting due to PLCC
channel fail. Also running Units-1&2 at NTPL
tripped on operation of GT differential
protection.
1. NTPL to ensure (i) proper DATE settings, and (ii) time-
sync with GPS for DR and EL at NTPL.
2. CEPL to furnish remedial measures taken regarding
PLCC channel failure.
NTPL/ CEPL Yet to be informed Pending
50/II/1
1
Tripping of
400kV Neyveli
TS2-Pugalur
line
14-11-2015
at 4:01 hrs
Line tripped on operation of over voltage
protection at Pugalur end. However from DR it
was observed that the voltages were below the
O/v stg-1 threshold limits
NLC to configure DT receipt event from Pugalur for
triggering DR and EL at NLC TPS II.
PGCIL (SR-II) to check drop-off to pick-up ratio of OVR
relay at Pugalur and configure its operation as per SRPC
provided OVR gradings.
NLC / PGCIL
(SR-II)
Yet to be informed Pending
51/II/6 Tripping of
400kV
Sattenapalli-
Vijayawada
line
25-12-2015
at 3:01 hrs
Line tripped due to operation of over voltage
protection at Vijayawada end and Direct Trip
was received at Sattenapalli end
1. PGCIL (SR-I), in co-ordination with APTRANSCO, to
address the problem with CB at the earliest opportune time.
2. APTRANSCO to take steps to replace the faulty Event
Logger at Vijayawada (Nunna) SS.
PGCIL (SR-
I)/
APTRANSC
O
Yet to be informed Pending
PendingYet to be informedKPTCL/
KPCL/
NPCIL
1. KPTCL/ KPCL to see the possibility of implementing
Weak Infeed logic with Echo feature enabled by Under
Voltage (27) element on Kadra-Karwar lines 1 &2, and
implement the same if feasible.
2. NPCIL to time-coordinate Kaiga’s DEFR settings with (i)
Zone-2 settings at Kaiga, and (ii) primary protections of the
lines emanating from Kadra and Kodasalli.
3. KPCL to ensure time-sync of EL’s, and healthiness of the
Fault Locators at Kadra.
220kV KAdra-Karwar lines-1&2 tripped
on earth fault in B-phase in zone-2.
Kaiga-Kadra line tripped at Kaiga end
only on operation of directional eath
fault protection.
31-07-2015
at
11:44 hrs
Tripping of
220kV Kadra-
Karwar line-
1&2 and
220kV
Kaiga-Kadra
line
47/II/7
Yet to be informedPGCIL (SR-I)
/ KPTCL
1. For Gooty –Nelamangala line, PGCIL (SR-I) and
KPTCL to provide 3-ph trip logic at their respective ends
upon detection of PLCC link failure during dead-time of
A/R operation.
2. PGCIL (SR-I) to make GPS functional at Gooty SS, and
ensure time-sync of various DR’s and EL’s with it (GPS).
3. PGCIL (SR-I) /KPTCL to furnish reason for the operation
of Backup impedance protection of the line reactor at
Nelamangala end and the remedial measures taken to PCSC
forum.
R-phase to earth fault had occurred in Line.
Line did not auto-reclose from both ends. It
was mentioned that Y&B pole breakers at
Neelamangala tripped on operation of pole
discrepancy and backup impedence protection
for line reactor got operated.
12-11-2015
at 00:20 hrs
Tripping of
400kV Gooty-
Nelamangala
line
50/II/8 Pending
49/II/1
1
Tripping of
400/220 kV
ICT-2 at
Kurnool
Substation and
400kV
Kurnool-
Srisailam line
26-10-2015
at 14:31 hrs
400kV Kurnool-Srisailam line - distance
protection zone-2 had operated at Srisailam
end. However from DR, R-phase to earth fault
and zone-2 start were observed. Breakers at
Kurnool end tripped on direct trip receive from
Srisailam end.
ICT-2 Main-CB tripped due to operation of
bus bar protection, and Tie-CB tripped due to
DT receipt from Srisailam
1.TSGENCO in coordination with APTRANSCO to carry
out end-to-end testing of PLCC channels by 15.12.2015 on
400 kV Srisailam – Kurnool S/C line and 400 kV Srisailam
– Sattenapalli D/C line.
2. TSGENCO and APTRANSCO to make A/R functional
on 400 kV Srisailam – Kurnool line.
3. TSGENCO to resolve configuration problems with the
newly commissioned relays at Srisailam LB so that
unwarranted DT sending to remote ends is addressed.
TSGENCO/
APTRANSC
O
Yet to be informed Pending
Annexure- II
Page 20 of 20
Sl.No. Element NameOutage
date/time
Revival
date/time
Reason for
OutageSender/ Receiver Remedial Measures/ Actions taken
1400 Kv GAJWEL -
SHANKARPALLY 1
02-11-
2015/12:22:
00
02-11-
2015/14:40:
00
R - N FAULT TSTRANSCO To-be-discussed
2400 Kv GAJWEL -
SHANKARPALLY 1
02-11-
2015/11:33:
00
02-11-
2015/11:59:
00
R-N FAULT TSTRANSCO To-be-discussed
3765 KV RAICHUR -
SHOLAPUR 2
02-01-
2016/10:46:
00
CONDUCTER
SNAPPING
PGCIL (SR-I) / PGCIL
(WR-I)To-be-discussed
4400 Kv SHANKARPALLY-
MAMIDIPALLY
25-01-
2016/13:56:
00
25-01-
2016/16:00:
00
DT RECEIVED
TRIPPED AT
SKPLY END
TSTRANSCO To-be-discussed
5400 kV MYSORE -
KOZHIKODE 1
28-01-
2016/12:53:
00
28-01-
2016/13:18:
00
B - N FAULT PGCIL (SR-II)
PGCIL(SR-II): Tripped on B-N fault
during liveline OPGW stringing
works.
6220 kV AMBEWADI -
PONDA 2
28-01-
2016/14:01:
00
28-01-
2016/19:20:
00
DISTANCE
PROTECTIONKPTCL / GOA To-be-discussed
7400 Kv VTPS - MALKARAM
2
31-01-
2016/14:23:
00
R-N FAULTAPGENCO /
TSTRANSCOTo-be-discussed
Pending Remedial Measures/ Actions taken
for the Critical Tripping Incidents (as on 15-03-2016)
Annexure- III
Page 1 of 8
8 400 kV CHITTOOR - SPDR
01-02-
2016/09:55:
00
01-02-
2016/10:40:
00
L/R
PROTECTION
OPERATED
APTRANSCO / PGCIL
(SR-II)
PGCIL (SR-II): Tripped on operation
of L/R Buchholz protection.
APTRANSCO: Tripped at chittoor end
on receipt of direct trip signal from
SPDR. Protection is in order at
APTRANSCO.
9400 kV VIJAYAWADA -
NELLORE 1
01-02-
2016/12:57:
00
01-02-
2016/18:49:
00
TRIPPED ON
Y_N FAULT 257
KM FROM VJA
PGCIL (SR-I) To-be-discussed
10400 kV VIJAYAWADA -
NELLORE 2
01-02-
2016/06:30:
00
01-02-
2016/06:32:
00
TRANSIENT
FAULTPGCIL (SR-I) To-be-discussed
Annexure- III
Page 2 of 8
11220 kV IDUKKI -
UDUMALPET
03-02-
2016/11:54:
00
03-02-
2016/12:19:
00
TRIPPED ON B-
PH FAULTKSEB / TANTRANSCO
TANTRANSCO: AR successful at
Udumalpet end. Feeder tied at Idukki
end on 03.02.2016 at 12:19 hrs.
KSEB: IDUD feeder tripped on zone 1
at Udumal pet end and carrier was sent
from that end. But the carrier was not
received at Moolamattom end due to
the problems with wiring to the relay.
Therefore, the relay at Moolamattom
end tripped in Zone 2. This happened
when wiring modifications were made
for new numerical relay in place of old
L3WYAS electro mechanical relay.
The rectification work is pending
which will be resolved soon.
12400 kV MYSORE -
KOZHIKODE 2
04-02-
2016/12:24:
00
04-02-
2016/13:07:
00
TRIPPED WHILE
CARRYING
OPGW WORKS
PGCIL (SR-II)
PGCIL(SR-II): Tripped on B-N fault
during liveline OPGW stringing
works. Construction Staff/Gangs has
been adviced to take all precautions
while OPGW stringing.
13400/220 kV ICT-3 AT
RAICHUR
05-02-
2016/03:01:
00
05-02-
2016/05:24:
00
TRIPPED DUE
TO TRIPPING OF
RCR-SEDAM
LINE
KPCL To-be-discussed
Annexure- III
Page 3 of 8
14 400 Kv NTPL - TTRNPS
05-02-
2016/11:47:
00
05-02-
2016/13:05:
00
HOT SPOT @
NTPL ENDNTPL / PGCIL (SR-II) To-be-discussed
15765 KV KURNOOL -
THIRUVALLM 1
11-02-
2016/14:30:
00
11-02-
2016/19:56:
00
D/T RECIEVED
AT KURNOOL
END
PGCIL (SR-I) / PGCIL
(SR-II)To-be-discussed
16 GOOTY-SOMANAHALLI
18-02-
2016/14:16:
00
18-02-
2016/15:03:
00
BY PASSED DUE
TO FAULT ON
LIE SIDE
KPTCL / PGCIL (SR-II) To-be-discussed
17 400 Kv HASSAN - UPCL 1
18-02-
2016/11:30:
00
18-02-
2016/11:45:
00
B-N FAULT PGCIL (SR-II) / UPCL To-be-discussed
18HVDC TALCHER - KOLAR
POLE
20-02-
2016/18:22:
00
20-02-
2016/19:15:
00
VALVE
COOLING
PROBLEM
PGCIL (SR-II) To-be-discussed
19HVDC TALCHER - KOLAR
POLE
21-02-
2016/16:46:
00
21-02-
2016/21:36:
00
VALVE
COOLING
PROBLEM
PGCIL (SR-II) To-be-discussed
20 400 kV CUDDAPPA - KOLAR
22-02-
2016/08:39:
00
22-02-
2016/10:32:
00
B - N FAULTPGCIL (SR-I) / PGCIL
(SR-II)To-be-discussed
21400 kV HYDERABAD -
KURNOOL
22-02-
2016/06:48:
00
22-02-
2016/07:18:
00
TRIPPED ON R-N
FAULT
PGCIL (SR-I) /
APTRANSCOTo-be-discussed
22400 kV PUGALUR -
KALAIVANTHAPATTU 2
22-02-
2016/13:53:
00
Y PHASE FAULT PGCIL (SR-II) To-be-discussed
23 400 kV CUDDAPPA - KOLAR
25-02-
2016/14:23:
00
25-02-
2016/17:05:
00
B-N FAULTPGCIL (SR-I) / PGCIL
(SR-II)To-be-discussed
24400/220 kV ICT-2 AT
CUDDAPAH
25-02-
2016/14:23:
00
25-02-
2016/14:36:
00
OVERCURRENT
TRIPPGCIL (SR-II) To-be-discussed
Annexure- III
Page 4 of 8
25220 Kv CHIKKODI -
TALANDGE
25-02-
2016/17:44:
00
25-02-
2016/18:22:
00
OVERCURRENT
TRIPKPTCL To-be-discussed
26220 Kv CHIKKODI -
TALANDGE
26-02-
2016/19:24:
00
26-02-
2016/20:23:
00
TRIPPED AT
TALANDGEKPTCL To-be-discussed
27400/220 kV ICT-3 AT
TALAGUPPA
27-02-
2016/17:33:
00
27-02-
2016/18:11:
00
RELAY
MALOPERATIO
N
KPTCL To-be-discussed
28220 kV IDUKKI -
UDUMALPET
28-02-
2016/13:40:
00
28-02-
2016/14:17:
00
PHASE TO
PHASE FAULTKSEB/ TANTRANSCO
KSEB: On 28.02.2016, IDUD feeder
tripped on zone 1 at both end. At
Idukki end tripped, reclosed and
tripped. The tripping was normal. The
carrier receive at Idukki end was not
functional due to the wiring problem
of the relay. The relay is new, hence
the DR to be fine-tuned for getting
clarity for the wave form. The problem
will be solved as early as possible.
TANTRANSCO: Temporary fault. AR
lock out at Udumalpet end. Feeder
charged from Udumalpet end and tied
at Idukki end on 28.02.2016 at 14:17
hrs.
29 400/220 kV ICT-1 AT HOODY
29-02-
2016/17:43:
00
29-02-
2016/17:49:
00
TRIPPED AT 220
KV SIDEKPTCL To-be-discussed
Annexure- III
Page 5 of 8
30400 kV NEYVELI TS2-
NEYVELI TS-2
29-02-
2016/12:08:
00
29-02-
2016/12:34:
00
PLCC
MALOPERATIO
N
NLC To-be-discussed
31 220 kV SEDAM - TANDUR
29-02-
2016/18:14:
00
29-02-
2016/22:23:
00
DISTANCE
PROTECTION
OPERATED
KPTCL/ TSTRANSCO To-be-discussed
32400 kV KHAMMAM -
KALPAKKA 1
01-03-
2016/05:35:
00
R-N FAULTPGCIL (SR-I) /
APTRANSCOTo-be-discussed
33400 Kv KUDGI- KOLHAPUR-
2
04-03-
2016/07:18:
00
04-03-
2016/07:38:
00
DT RECEIVED
AT KUDGI END.
PGCIL (SR-II) / PGCIL
(WR-I)To-be-discussed
34400 kV NEYVELI TS 2 -
NEYVELI TS2
04-03-
2016/11:22:
00
04-03-
2016/17:07:
00
TRIPPED AT
NLCTS2 ENDNLC To-be-discussed
35220 kV AMBEWADI -
PONDA 1
05-03-
2016/14:32:
00
05-03-
2016/17:50:
00
DISTANCE
PROTECTIONKPTCL / GOA To-be-discussed
36220 kV KANIAMPET -
KADAKOLA
05-03-
2016/13:29:
00
05-03-
2016/14:02:
00
DISTANCE
PROTECTIONKSEB / KPTCL To-be-discussed
37220 kV IDUKKI -
UDUMALPET
06-03-
2016/04:28:
00
06-03-2016/TRIPPED ON B-N
FAULTKSEB/ TANTRANSCO
TANTRANSCO: Temporary fault. AR
successful at Udumalpet end. Tx
incremented by 1. Feeder tied at
Idukki end on 06.03.2016 at 05:32 hrs.
38400 kV HASSAN -
NEELAMANGALA
07-03-
2016/14:55:
00
07-03-
2016/16:17:
00
B - N FAULT KPTCL To-be-discussed
39400 kV RAMAGUNDAM -
CHANDRAPUR 2
07-03-
2016/19:39:
00
07-03-
2016/20:50:
00
R - B FAULTNTPC / PGCIL (WR-I) /
PGCIL (SR-I)To-be-discussed
40400 kV RAMAGUNDAM -
CHANDRAPUR 2
08-03-
2016/23:55:
00
09-03-
2016/01:01:
00
TRIPPED ON R-B
FAULT
NTPC / PGCIL (WR-I) /
PGCIL (SR-I)To-be-discussed
Annexure- III
Page 6 of 8
41HVDC TALCHER - KOLAR
POLE
08-03-
2016/01:29:
00
08-03-
2016/02:12:
00
VALVE
COOLING
PROBLEM
PGCIL (SR-II) To-be-discussed
42 400 Kv NELLORE - SPDR 2
09-03-
2016/17:20:
00
09-03-
2016/19:34:
00
ISO. PROBLEMAPTRANSCO /
TANTRANSCOTo-be-discussed
43220 kV IDUKKI -
UDUMALPET
12-03-
2016/02:32:
00
12-03-
2016/15:44:
00
R -N FAULT KSEB/ TANTRANSCO To-be-discussed
44 220 kV SABARGIRI - THENI
12-03-
2016/13:55:
00
12-03-
2016/14:35:
00
R-N FAULT KSEB/ TANTRANSCO To-be-discussed
45400 kV N'SAGAR -
CUDDAPPA 1
12-03-
2016/12:13:
00
12-03-
2016/13:23:
00
Y-N FAULT PGCIL (SR-I) To-be-discussed
46 400 Kv COASTAL - NTPL
14-03-
2016/01:36:
00
14-03-
2016/02:36:
00
TRIPPED
REASON
AWAITED
CEPL / NTPL To-be-discussed
47 400 Kv NTPL - TTRNPS
14-03-
2016/02:59:
00
14-03-
2016/08:57:
00
TRIPPED ON Y-N
FAULTNTPL / PGCIL (SR-II) To-be-discussed
48220 kV AMBEWADI -
PONDA 1
14-03-
2016/03:44:
00
14-03-
2016/10:50:
00
B-N FAULT KPTCL / GOA To-be-discussed
49 400 Kv NTPL - TTRNPS
14-03-
2016/01:36:
00
14-03-
2016/02:21:
00
TRIPPED
REASON
AWAITED
NTPL / PGCIL (SR-II) To-be-discussed
50 400 Kv NTPL - TTRNPS
14-03-
2016/01:12:
00
14-03-
2016/01:36:
00
TRIPPED ON
R_N FAULT AT
NTPL END
ONLY HOLDING
AT TTCRN
NTPL / PGCIL (SR-II) To-be-discussed
51 400 Kv COASTAL - TTRNPS
14-03-
2016/01:36:
00
14-03-
2016/03:04:
00
TRIPPED
REASON
AWAITED
CEPL / PGCIL (SR-II) To-be-discussed
Annexure- III
Page 7 of 8
52 400 Kv COASTAL - NTPL
14-03-
2016/03:04:
00
14-03-
2016/20:28:
00
TRIPPED
REASON
AWAITED
CEPL / NTPL To-be-discussed
53220 kV AMBEWADI -
PONDA 1
14-03-
2016/03:44:
00
B-N FAULT KPTCL / GOA To-be-discussed
54 400 Kv NTPL - TTRNPS
14-03-
2016/02:59:
00
TRIPPED ON Y-N
FAULTNTPL / PGCIL (SR-II) To-be-discussed
55 400 Kv COASTAL - NTPL
14-03-
2016/03:04:
00
TRIPPED
REASON
AWAITED
CEPL / NTPL To-be-discussed
56 400 Kv NTPL - TTRNPS
14-03-
2016/01:36:
00
14-03-
2016/02:21:
00
TRIPPED
REASON
AWAITED
NTPL / PGCIL (SR-II) To-be-discussed
57 400 Kv NTPL - TTRNPS
14-03-
2016/01:12:
00
14-03-
2016/01:36:
00
TRIPPED ON
R_N FAULT AT
NTPL END
ONLY HOLDING
AT TTCRN
NTPL / PGCIL (SR-II) To-be-discussed
58 400 Kv COASTAL - NTPL
14-03-
2016/01:36:
00
14-03-
2016/02:36:
00
TRIPPED
REASON
AWAITED
CEPL / NTPL To-be-discussed
59 400 Kv COASTAL - TTRNPS
14-03-
2016/01:36:
00
14-03-
2016/03:04:
00
TRIPPED
REASON
AWAITED
CEPL / PGCIL (SR-II) To-be-discussed
60 400 Kv NTPL - TTRNPS
15-03-
2016/02:02:
00
15-03-
2016/03:51:
00
R -N FAULT NTPL / PGCIL (SR-II) To-be-discussed
61220 kV IDUKKI -
UDUMALPET
15-03-
2016/02:09:
00
15-03-
2016/02:51:
00
R-N FAULT KSEB/ TANTRANSCO To-be-discussed
Annexure- III
Page 8 of 8
I__________...__..1.. . . J
TANTRANSCOi-F rom-- ----------·---------r ro-- _._----_._-------------------_._---.i Er. J. Rexline Terese, M.E., i The Member Secretary,I Chief Engineer, i Southern Regional Power Committee,i Protection and Communication, 29, Race Course Cross Road,i TANTRANSCO, Bangalore - 560 009.[ 5B Block, First floor,! TNEB complex,i 144, Anna Salai,L~hennai=-_~gO 002.
Lr.No. CE/P&C/SE/D/EEPC 4/AEE 3/F.5RPC/D. 4-2 /16, dated 05.03.2016.
Sir,Sub: TANTRANSCO - PCSC Recommendations - Issue to be included in
Agenda for 52nd PCSC meeting - Requested - Reg.
*** * ***During the review of the tripp ing of 400kV Alamathy-S.V.Chatram Line-1 & 2
on 29.03.2015 at 15:29 hrs., PCSC Forum recommended to swap the Distance
Protection relays between two stations so that Main-1 and Main-2 will be of different
make at each Sub-station.
With reference to the above, the following issue may please be included in
the agenda for 52nd PCSC meeting:
1. In the Sub-stations with established Sub-station Automation System (SAS),
the integration of another make relay in SAS attracts additional expenditu re
which is many times the panel cost. It requires wiring modifications &
updation and the technical hitches are also to be attended.
2. Hence, it is requested that the forum may recommend to drop the protection
audit remarks and to continue with the present arrangement for the existing
Substations. However, different make Distance Protection relays will be
provided in the upcoming 230kV and above level Sub-stations.
Af- \~~Chief EngineerjP&C
Copy submitted to the Managing DirectorjTANTRANSCO.Copy submitted to the DirectorjOperationjTANTRANSCO.
Annexure- IV
Page 1 of 1
Some notes regarding implementing Ramakrishna commission report based
settings in 220KV feeders.
(JAYARAJAN.C.N. EXECUTIVE ENGINEER, KERALA STATE ELECTRICITY BOARD)
1. Reverse Zone delay:
Case: In 220KV feeder relays, the delay is recommended as 0.5 seconds.
Issue: For long lines following short lines, the zone 2 delay is selected as 0.5 seconds. Often the
delay of zone 2 has to be increased from 0.35 seconds to 0.5 seconds especially in the case of
double circuits followed by short line. It has been observed that the lines like 220KV Sabarigiri-
Edamon which is passing through thick forests, trips in zone 2 (or zone 3) due to high resistance
faults. Resistive reach of reverse zone is selected as resistive reach of Zone 3. In such cases, reverse
zone in other feeders may operate before the tripping of faulty feeder.
Solution: a. Increase the resistive reach of zone 2 of protected feeder equal to zone 3 to get
maximum resistive reach.
b. Set Reverse zone time delay = zone 2 delay + breaker tripping time + relay reset time+
safety margin.
Recommended: It is safer to select delay of Zone 3 delay plus breaker tripping
time plus relay reset time = Zone 3 delay plus 200 ms. It may be noted that reverse zone is intended
to protect as back up to bus bar protection only and not for feeder protecton.
2. Power Swing Blocking and Load encroachment inhibit:
Case: Setting of Power swing blocking is based on minmum source impedance and initial swing
frequency as 1.5Hz.
Issue: a.The setting of power swing blocking in REL 670 is very difficult and different from other
relays. There is no common approach.
b. Selection of initial frequency as 1.5 Hz has not been verified by system studies.
c. The setting of Load Encroachment Inhibit feature in REL 670 relay is influenced by
setting of power swing blocking. Often load encroachment inhibit feature is extended to zone 2
reach. Load encroachment occurs in feeders with heavy overload which may increase sag of lines
leading to arcing to ground reulting high resistance fault. But Load encroachment inhibit feature
will block operation of the distance relay at this time even though there is a good chance for
occurrence of such fault. Directional earth fault protection has to take care of it.
Solution: a. Detailed discussion is required exclusively in setting of Power Swing Blocking and
Load encroachment inhibit.
b. Common approach in all relays is to be developed in the setting of Power swing
blocking and load encroachment inhibit.
c. Studies are to be carried out and values of initial and following power swing frequencies are to be
identified by system adminstrators.
3. Zone 3 delay:
Case: Zone 3 delay in 220KV feeders are suggested as 800ms.
Issue: Often zone 2 delay of distance relay in any of feeders from adjacent station may be 0.5
seconds. If the breaker of that feeder from adjacent station fails to operate for a fault in zone 2
reach, LBB protection of that particular breaker has to act before zone 3 operation of lines from
Annexure- V
Page 1 of 3
remote ends. Present zone 3 delay is not having sufficient margin with zone 2 of 0.5 seconds and
LBB delay of 0.2 seconds.
Solution: Increase Zone 3 delay has to be increased to at least 1 second in order to ensure security.
4. Grading of Zone 3 delay with protectons of transformer and its downstream side in the adjacent
station:
Case: Zone 3 delay of relay in a feeder has to be coordinated with protections in transformer and its
downstream side in adjacent station.
Issue and solutions:
(See the brief note given below regarding issues with Zone 3 reach.)
Zone 3 settings: Issues and suggestions – A brief note
Zone 3 settings are provided not for the protection of the feeder on which the relay is provided.
Zone 3 protection is supposed to act as back up to the protection provided in the feeders from
adjacent station.
However, in practice, it seen that it is very difficult to set Zone3 values. And it has been experienced
in India and aborad that Zone 3 protection has acted for heavy over loads during disturbed system
conditions which again worsened and collapsed the system.
Some examples:
a. On 30th
, July, 2012, the tripping of 400KV Bina-Gwalior 1 with Zone 3 indications led to
serious collapses. Actually, there was no fault in any of the line from adjacent station. However, it
was reported that system voltages were reduced and currents were increased due to overloading.
Similar incident was repeated on next day.
b. On 2nd
,July, 1996, the tripping of Mill Creek -Antellope of WSCC (Wersten North America) line
tripped undesirably on Zone 3 leading to cascaded tripping in many areas in Canada, Mexico,
California, Arizona etc. affecting two million people.
In such cases as above, the reason for maloperation of Zone 3 is due to stressed overloading and
stressed voltage conditions.
Therefore following points need attention:
1. Zone 3 operation makes maloperation than real operation.
2. The chances of operation of Zone 3 is very less except in the cases of high resistance fault
conditons which would otherwise would be sensed by directional earth fault (DEF) protection.
3. For avoiding maloperation load encroachment, Load Encroachment Inhibit feature may be
enabled for those ones having that feature. However, in relays like ABB's REL 670, it completely
blocks operation of distance protection even if high resistance earth faults may be developed as part
of severe overloading and due to conductor sagging. Operation of Directional earth fault becomes
critical then.
4. Extending reach of Zone 3 covering transformer impedance worsen security again. Following
points are to be noted in this case:
a. An earth fault on the downstream side is sometimes cleared by directional earth fault relay in the
feeder on the downstream side of the transformer in case of line faults or by transformer earth fault
Annexure- V
Page 2 of 3
relay. However, the time of operation inversely depends upon the magnitude of current which may
vary according to the resistance of earth fault path, source impedance etc. If Zone 3 is extended
upto downstream side, it is very difficult to grade with IDMT characterstics of earth fault relays in
feeders in downstream side and in transformer protection panels.
b. For solid fault in the downstream side of transformer, there will be significant infeed from
upstream side to the fault. This will under reach Zone 3 reach leading to non operation of Zone 3
protection. This shows that further delaying of Zone 3 in the name of coordinating with downstream
side earth fault or phase fault protection is of no use.
5. It is not practical to provide multipliers as much high as to compensate under reaching effect due
to heavy infeed in the case of Zone3. Because, the fault and system conditions are varying and this
may lead to expansion of Zone reach during low fault levels threating system security.
6. For 220KV and above systems, two redundant distance protections are used. Zone 2 protection is
set as 120 percent or 150 percent of the impedance of the protected line for ensuring 100 percent
feeder protection. Besides this, LBB protection will be in service in every such substations, which
trips all feeders and trasformers connected to the bus in case of breaker failure. Therefore, there is
practically no chance for Zone 3 protection to act for any fault in any of the lines from adjacent
station.
Considering the above facts, following steps can be taken as optimum solution:
1. Restrict Zone 3 protection reach upto longest line end from adjacent station. The equation: Zone
3 = 1.2* (impedance of protected line + impedance of longest line from adjacent station) is
acceptable. The multiplier 1.2 can be increased if only there is heavy infeed through out in service
duration.
2. Enable Directional overcurrent protection inside the distance protection and set the same in such
way to coordinate the same with transformer overcurrent protection in the adjacent station.
Similarly, set the pick up value of directional earth fault relay in the protected line to sense the
lowest earth fault current in the downstream side of the transformer. It may please be noted that
these protections are supposed only to ensure tripping and fault isolation in the extreme cases.
3. Set time delay of Zone 3 to 1 second or in extreme cases to 1.5 seconds. In KSEB, back up
impedance setting of generators are set at 2.5 seconds to act as back up to all protections in the
downstream side. Therefore, Zone 3 delay can not be increased too much which may lead to
generator tripping.
Presently KSEB is following the procedure similar to the above suggestion to a good extent.
This is forwarded for favour of information and further necessary action. Please note that these are
only suggestions to be discussed and to be corrected and modified, if necessary.
Annexure- V
Page 3 of 3
SOUTHERN REGIONAL POWER COMMITTEE
BENGALURU
Additional Agenda for the 52
nd Meeting of Protection Coordination
Sub-Committee of SRPC to be held on 30.03.2016 (Wednesday)
1. Grid Occurrences
The following Grid Disturbances (GD) would be discussed in the PCSC meeting:
Sl. No.
Details of Event Date & Time
Reason Remarks Category
1
Complete
outage of
NTPL station
14-03-2016
at 01:36 hrs
Running Units at NTPL and
Coastal Energen power station
got tripped due to tripping of
evacuating lines.
Generation loss : 1430 MW GD-1
2
Complete
outage of
NTPL station
15-03-2016
at 03:39 hrs
Running Units at NTPL power
station got tripped due to
tripping of evacuating lines.
Generation loss : 415 MW GD-1
Constituents are requested to bring/ give full particulars of the tripping events
pertaining to their system.
2. Non- furnishing of Tripping Details
The members were intimated about non- furnishing of tripping details for the grid
incidents that occurred during the period 1st - 15
th March, 2016 vide SRPC letter no:
SRPC/SE-III/PCSC-52/1801-16 dated 23.03.2016. The issue would be discussed in the
meeting.
3. Over Voltage Relay Grading for 765 kV lines of the Southern Region
With regard to the Over Voltage Grading for 765 kV lines of the Southern Region made
available to the Constituents vide PCSC-52 Agenda, comments/ suggestions of NLDC,
SRLDC and PGCIL have been sought. Considering their suggestions and the various
standards/ guidelines available in this regard, viz., CEA Standards, CBIP Guidelines,
Ramakrishna Committee Guidelines, OVR Grading for 765 kV transmission lines of SR
(existing as on date) has been redone, and the new OVR Gradings proposed to be adopted
for these lines (along with study results) are given at Annexure-VI for kind reference.
4. Over Voltage Relay Grading for 400 kV lines of the Southern Region
Members are aware that it has been more than one year since the OVR Grading Exercise
for 400 kV lines in the Southern Region (SR) has been undertaken. It is also a fact that a
number of 400 kV lines have been added to SR-Grid in addition to reconfiguration
(including LILO) works of the existing 400 kV lines in the past one year.
Additional Agenda for the 52nd Protection Coordination Sub Committee Meeting to be held on 30-03-2016Page 2
In this regard, a comprehensive exercise for OVR grading 400 kV transmission lines of
SR (existing as on date) has been done, and the new OVR Gradings proposed to be
adopted for these lines (along with study results) are given at Annexure-VII for kind
reference.
5. Model Tender Document for Protection Management Suite (PMS)
Constituents are kindly aware that in pursuance with the decision taken in 26th
SRPC
meeting, steps had been initiated to procure Protection Suite (Protection Management
Suite or PMS) that comprises web-based management software and protection setting
calculation tool through PSDF funding.
In this regard, a model PMS Tender Document proposed to be bid out is enclosed at
Annexure-VIII for kind information.
6. PGCIL (SR-II) Agenda Items
PGCIL (SR-II) vide their mail dated 26-03-2016 requested to include the communication
from TANTRANSCO (Annexure-IX) regarding Implementation of SPS for averting ICT
loading at Arasur SS. The issue would be discussed in the meeting.
*****
Voltage Setting
(% of Nominal Voltage)
Time
Setting
(Sec)
OVR
Grading
Order of
Tripping
109 10 A 8
109 9 B 7
109 8 C 6
109 7 D 5
108 7 E 4
108 6 F 3
107 6 G 2
107 5 H 1
1. Voltage - Time (OVR) Grading Matrix:
2. OVR-Graded 765 kV Network of the Southern Region:
OVR Grading for 765 kV Transmission Lines of the Southern Region
Annexure-VI
1 of 2
From Bus
NumberFrom Bus Name
To Bus
NumberTo Bus Name Ckt Id
Length,
km
Charging
B (pu)
Q' from
Line (B/2)
[= Q1]
Q' from
Line
Reactor [=
Q2]
Net 'Q' from
Line [= Q1 + Q2]
Power
Flow, MW
Order as per
Criticality
OVR
Grading
337004 SHOLAPUR 765.00 437001 RCHR-NEW 765.00 1 208 4.992 2.496 -2.4 0.096 1109.3
337004 SHOLAPUR 765.00 437001 RCHR-NEW 765.00 2 208 4.992 2.496 -2.4 0.096 1109.3
417001 KRNL-NEW 765.00 417002 NLR-PS 765.00 1 302 8.0386 4.0193 -2.4 1.6193 -62 5 B
417001 KRNL-NEW 765.00 417002 NLR-PS 765.00 2 302 8.0386 4.0193 -2.4 1.6193 -62 2 G
417001 KRNL-NEW 765.00 437001 RCHR-NEW 765.00 1 118.42 2.78294 1.39147 0 1.39147 -727.3 6 A
417001 KRNL-NEW 765.00 437001 RCHR-NEW 765.00 2 120.48 2.83133 1.415665 -2.4 -0.984335 -714.9 3 F
417001 KRNL-NEW 765.00 447002 TRVLM 765.00 1 355 9.443 4.7215 -2.4 2.3215 342.5 4 E
417001 KRNL-NEW 765.00 447002 TRVLM 765.00 2 355 9.443 4.7215 -2.4 2.3215 342.5 1 H
417002 NLR-PS 765.00 417001 KRNL-NEW 765.00 1 302 8.0386 4.0193 -2.4 1.6193 62 2 B
417002 NLR-PS 765.00 417001 KRNL-NEW 765.00 2 302 8.0386 4.0193 -2.4 1.6193 62 1 G
437001 RCHR-NEW 765.00 337004 SHOLAPUR 765.00 1 208 4.992 2.496 -2.4 0.096 -1103.8 4 A
437001 RCHR-NEW 765.00 337004 SHOLAPUR 765.00 2 208 4.992 2.496 -2.4 0.096 -1103.8 2 C
437001 RCHR-NEW 765.00 417001 KRNL-NEW 765.00 1 118.42 2.78294 1.39147 0 1.39147 728.8 3 B
437001 RCHR-NEW 765.00 417001 KRNL-NEW 765.00 2 120.48 2.83133 1.415665 0 1.415665 716.4 1 E
447002 TRVLM 765.00 417001 KRNL-NEW 765.00 1 355 9.443 4.7215 -2.4 2.3215 -341.6 2 E
447002 TRVLM 765.00 417001 KRNL-NEW 765.00 2 355 9.443 4.7215 -2.4 2.3215 -341.6 1 H
3. OVR Grading for 765 kV Transmission Lines of the Southern Region:
Annexure-VI
2 of 2
Voltage Setting
(% of Nominal
Voltage)
Time Setting (Sec)OVR Grading
(NEW)Order of tripping
Voltage Setting
(% OF Nominal
Votlage)
Time Setting
(Sec)
OVR
Grading
(OLD)
Order of
tripping
110 10 A 8 110 10 A 7
110 9 B 7 110 9 B1 6
110 8 C 6 110 8 B2 5
110 7 D 5 110 7 C1 4
109 7 E 4 110 6 C2 3
109 6 F 3 109 5 D 2
109 5 G 2 109 4 D2 1
109 4 H 1
From Bus
NumberFrom Bus Name To Bus Number To Bus Name
Ckt
Id
Length,
km
Charging B
(pu)
Q' from Line
(B/2) [= Q1]
Q' from Line
Reactor
[= Q2]
Net 'Q' from
Line
[= Q1 + Q2]
Power Flow,
MW
Old OVR
Grading
Order as
per
Criticality
New OVR
Grading
414001 GOOTY 400.00 414010 KURNOOL 400.00 1 84.19 0.4695 0.23475 0 0.23475 -58.2 C1 5 C
414001 GOOTY 400.00 414023 NLR-PS 400.00 1 289 2.118 1.059 -0.5714 0.4876 -140.6 D2 6 B
414001 GOOTY 400.00 414023 NLR-PS 400.00 2 289 2.1183 1.05915 -0.5714 0.48775 -140.6 B2 3 E
414001 GOOTY 400.00 414031 KRNL-PG 400.00 1 112.5 0.62437 0.312185 -0.4535 -0.141315 -69 B1 7 A
414001 GOOTY 400.00 414032 GTYN-FSC 400.00 1 0 0 0 0 0 406.7 ** **
414001 GOOTY 400.00 414033 GTYS-FSC 400.00 1 0 0 0 -0.5714 -0.5714 342.7 ** **
414001 GOOTY 400.00 434008 TUMKUR 400.00 1 208.62 1.25589 0.627945 0 0.627945 0 A 2 F
414001 GOOTY 400.00 434008 TUMKUR 400.00 2 208.62 1.25589 0.627945 0 0.627945 D 1 G
414001 GOOTY 400.00 434009 RCHR-NEW 400.00 1 128.6 0.95104 0.47552 0 0.47552 -298.3 A 8 A
414001 GOOTY 400.00 434009 RCHR-NEW 400.00 2 128.6 0.95104 0.47552 0 0.47552 -298.3 B1 4 D
414002 CHITOOR 400.00 414004 CHNKMPLY 400.00 1 147.14 0.81663 0.408315 0 0.408315 42.2 C2 2 E
414002 CHITOOR 400.00 414030 SDSTPS 400.00 1 189.07 1.38588 0.69294 0 0.69294 -362.4 D2 6 A
414002 CHITOOR 400.00 414030 SDSTPS 400.00 2 189.07 1.38588 0.69294 0 0.69294 -362.4 1 G
414002 CHITOOR 400.00 444001 SRPRMBDR 400.00 1 95.14 0.52803 0.264015 0 0.264015 159.2 B1 4 C
414002 CHITOOR 400.00 444024 TRVLM 400.00 1 21.02 0.15409 0.077045 0 0.077045 100.8 C 5 B
414002 CHITOOR 400.00 444024 TRVLM 400.00 2 21.02 0.15409 0.077045 0 0.077045 100.8 D 3 D
414003 NLR-PG 400.00 414008 NUNNA 400.00 1 340.64 1.89057 0.945285 -0.45351 0.491775 19.8 B2 4 D
414003 NLR-PG 400.00 414008 NUNNA 400.00 2 340.64 1.89057 0.945285 -0.45351 0.491775 19.8 A 2 F
1. Voltage-Time (OVR) Grading Matrix:
2. OVR Grading for 400 kV Transmission Lines of the Southern Region:
Over Voltage Grading for 400 kV Lines of the Southern Region
Annexure-VII
1 of 11
414003 NLR-PG 400.00 414023 NLR-PS 400.00 1 6.35 0.04648 0.02324 0 0.02324 -793.7 A 8 A
414003 NLR-PG 400.00 414023 NLR-PS 400.00 2 6.35 0.04655 0.023275 0 0.023275 -793.7 A 6 B
414003 NLR-PG 400.00 444001 SRPRMBDR 400.00 1 189 1.04895 0.524475 0 0.524475 279.7 B2 5 C
414003 NLR-PG 400.00 444001 SRPRMBDR 400.00 2 189 1.04895 0.524475 0 0.524475 279.7 1 G
414003 NLR-PG 400.00 444024 TRVLM 400.00 1 172.96 1.2678 0.6339 -0.453 0.1809 308.1 D2 7 A
414003 NLR-PG 400.00 444024 TRVLM 400.00 2 172.96 1.2678 0.6339 -0.453 0.1809 308.1 C1 3 E
414004 CHNKMPLY 400.00 414005 CNP-FSC1 400.00 C 0 0 0 0 0 -79.3 ** **
414004 CHNKMPLY 400.00 414006 CNP-FSC2 400.00 C 0 0 0 0 0 -78.9 ** **
414004 CHNKMPLY 400.00 434010 KOLAR-PG 400.00 1 174 0.96611 0.483055 0 0.483055 154.5 B2 2 B
414004 CHNKMPLY 400.00 414002 CHITOOR 400.00 1 147.14 0.81663 0.408315 0 0.408315 -42.2 D 1 E
414005 CNP-FSC1 400.00 414007 TALPALLI 400.00 1 277.33 1.53915 0.769575 0 0.769575 -79.3 A 1 A
414005 CNP-FSC1 400.00 414004 CHNKMPLY 400.00 C 0 0 0 -0.4535 -0.4535 79.3 ** **
414006 CNP-FSC2 400.00 414007 TALPALLI 400.00 1 278.66 1.54659 0.773295 0 0.773295 -78.9 D 1 C
414006 CNP-FSC2 400.00 414004 CHNKMPLY 400.00 C 0 0 0 -0.4535 -0.4535 78.9 ** **
414007 TALPALLI 400.00 414031 KRNL-PG 400.00 1 264.5 1.46798 0.73399 -0.4535 0.28049 -51 D 3 F
414007 TALPALLI 400.00 424001 MAHBBNGR 400.00 1 184.53 1.02342 0.51171 -0.5714 -0.05969 29.6 C2 7 B
414007 TALPALLI 400.00 424002 RGM-NTPC 400.00 1 267.2 1.48296 0.74148 -0.4535 0.28798 -181.7 A 9 A
414007 TALPALLI 400.00 424002 RGM-NTPC 400.00 2 267.2 1.48296 0.74148 -0.4535 0.28798 -181.7 B2 5 D
414007 TALPALLI 400.00 424003 GHANAPUR 400.00 1 155.26 0.86172 0.43086 0 0.43086 98.3 A 4 E
414007 TALPALLI 400.00 424004 KHAMMAM 400.00 1 144.58 0.80242 0.40121 0 0.40121 -97.8 B2 8 B
414007 TALPALLI 400.00 424004 KHAMMAM 400.00 2 144.58 0.869384 0.434692 0 0.434692 -105.5 6 C
414007 TALPALLI 400.00 424004 KHAMMAM 400.00 3 144.58 0.869384 0.434692 0 0.434692 -105.5 2 G
414007 TALPALLI 400.00 414005 CNP-FSC1 400.00 1 277.33 1.53915 0.769575 0 0.769575 79.6 A 1 H
414007 TALPALLI 400.00 414006 CNP-FSC2 400.00 1 278.66 1.54659 0.773295 0 0.773295 79.2 D 10 A
414008 NUNNA 400.00 414009 GAZUWAKA 400.00 1 316.9 1.75879 0.879395 -0.5714 0.307995 -155.3 B1 10 B
414008 NUNNA 400.00 414013 VTS-IV 400.00 1 18.66 0.10315 0.051575 0 0.051575 252.7 B1 12 A
414008 NUNNA 400.00 414014 VEMAGIRI 400.00 1 192.34 0.13472 0.06736 0 0.06736 -153.8 A 9 B
414008 NUNNA 400.00 414014 VEMAGIRI 400.00 2 192.34 0.13472 0.06736 0 0.06736 -153.8 D 6 D
414008 NUNNA 400.00 414014 VEMAGIRI 400.00 3 195.21 1.08779 0.543895 -0.45351 0.090385 -99.3 C1 3 F
414008 NUNNA 400.00 414019 LANCO 400.00 1 22 0.1221 0.06105 0 0.06105 -164.8 B2 8 C
414008 NUNNA 400.00 414019 LANCO 400.00 2 22 0.1221 0.06105 0 0.06105 -164.8 C2 4 E
414008 NUNNA 400.00 414021 STNPLLI 400.00 1 115.89 0.69766 0.34883 0 0.34883 162.5 5 D
414008 NUNNA 400.00 414029 NLR-AP 400.00 1 348.2 1.93251 0.966255 0 0.966255 -19.4 1 H
414008 NUNNA 400.00 424004 KHAMMAM 400.00 1 114.78 0.637 0.3185 0 0.3185 104.3 C2 11 A
414008 NUNNA 400.00 414003 NLR-PG 400.00 1 340.64 1.89057 0.945285 -0.4535 0.491785 -19.8 A 7 C
414008 NUNNA 400.00 414003 NLR-PG 400.00 2 340.64 1.89057 0.945285 -0.4535 0.491785 -19.8 B2 2 G
414009 GAZUWAKA 400.00 414011 KALPAKKA 400.00 1 3.39 0.02061 0.010305 0 0.010305 61 A 4 B
414009 GAZUWAKA 400.00 414011 KALPAKKA 400.00 2 3.39 0.02061 0.010305 0 0.010305 61 B2 1 E
414009 GAZUWAKA 400.00 414020 SMHDRI-2 400.00 1 14.1 0.07825 0.039125 -0.57143 -0.532305 -71.5 A 5 A
414009 GAZUWAKA 400.00 414020 SMHDRI-2 400.00 2 14.1 0.07825 0.039125 -0.57143 -0.532305 -71.5 B2 2 D
414009 GAZUWAKA 400.00 414008 NUNNA 400.00 1 316.9 1.75879 0.879395 -0.5714 0.307995 156.8 B1 3 C
414010 KURNOOL 400.00 414031 KRNL-PG 400.00 1 9.88 0.07243 0.036215 0 0.036215 -379.4 A 5 A
414010 KURNOOL 400.00 414031 KRNL-PG 400.00 2 9.88 0.07243 0.036215 0 0.036215 -379.4 B1 3 C
414010 KURNOOL 400.00 424003 GHANAPUR 400.00 1 226.5 1.2571 0.62855 0 0.62855 114.4 D 1 E
414010 KURNOOL 400.00 424005 SRLMLB 400.00 1 104.9 0.5749 0.28745 0 0.28745 156.1 A 2 D
414010 KURNOOL 400.00 414001 GOOTY 400.00 1 84.19 0.4695 0.23475 0 0.23475 58.3 B1 4 B
414011 KALPAKKA 400.00 414012 SIMHADRI 400.00 1 3.72 0.02256 0.01128 0 0.01128 -360.3 A 12 A
Annexure-VII
2 of 11
414011 KALPAKKA 400.00 414012 SIMHADRI 400.00 2 3.72 0.02256 0.01128 0 0.01128 -360.3 B2 7 C
414011 KALPAKKA 400.00 414012 SIMHADRI 400.00 3 3.72 0.02256 0.01128 0 0.01128 -360.3 D 4 E
414011 KALPAKKA 400.00 414012 SIMHADRI 400.00 4 3.72 0.02256 0.01128 0 0.01128 -360.3 C1 2 G
414011 KALPAKKA 400.00 414014 VEMAGIRI 400.00 1 166.93 1.0124 0.5062 0 0.5062 200.4 A 10 B
414011 KALPAKKA 400.00 414014 VEMAGIRI 400.00 2 166.93 1.0124 0.5062 0 0.5062 200.4 D 1 H
414011 KALPAKKA 400.00 414027 HINDUJA 400.00 1 7.35 0.04425 0.022125 0 0.022125 0 A 8 C
414011 KALPAKKA 400.00 414027 HINDUJA 400.00 2 7.35 0.044247 0.0221235 0 0.0221235 0 B2 5 D
414011 KALPAKKA 400.00 424004 KHAMMAM 400.00 1 364 2.2076 1.1038 -0.5714 0.5324 186.4 A 11 A
414011 KALPAKKA 400.00 424004 KHAMMAM 400.00 2 364 2.2076 1.1038 -0.5714 0.5324 186.4 C1 3 F
414011 KALPAKKA 400.00 414009 GAZUWAKA 400.00 1 3.39 0.02061 0.010305 0 0.010305 -61 A 9 B
414011 KALPAKKA 400.00 414009 GAZUWAKA 400.00 2 3.39 0.02061 0.010305 0 0.010305 -61 B2 6 D
414012 SIMHADRI 400.00 414011 KALPAKKA 400.00 1 3.72 0.02256 0.01128 0 0.01128 360.4 A 4 A
414012 SIMHADRI 400.00 414011 KALPAKKA 400.00 2 3.72 0.02256 0.01128 0 0.01128 360.4 B2 3 B
414012 SIMHADRI 400.00 414011 KALPAKKA 400.00 3 3.72 0.02256 0.01128 0 0.01128 360.4 C1 2 C
414012 SIMHADRI 400.00 414011 KALPAKKA 400.00 4 3.72 0.02256 0.01128 0 0.01128 360.4 C2 1 D
414013 VTS-IV 400.00 414021 STNPLLI 400.00 1 115 0.63825 0.319125 0 0.319125 111.7 D2 5 B
414013 VTS-IV 400.00 414021 STNPLLI 400.00 2 115 0.63825 0.319125 0 0.319125 111.7 D 3 D
414013 VTS-IV 400.00 414029 NLR-AP 400.00 1 330.8 1.83594 0.91797 0 0.91797 -34.4 1 G
414013 VTS-IV 400.00 424011 MALKARAM 400.00 1 261.9 1.4529 0.72645 0 0.72645 146.1 D 4 C
414013 VTS-IV 400.00 424011 MALKARAM 400.00 2 261.9 1.4529 0.72645 0 0.72645 146.1 C1 2 E
414013 VTS-IV 400.00 414008 NUNNA 400.00 1 18.66 0.10315 0.051575 0 0.051575 -252.4 B1 6 A
414014 VEMAGIRI 400.00 414015 GMR 400.00 1 1.76 0.00973 0.004865 0 0.004865 -100 B2 9 C
414014 VEMAGIRI 400.00 414015 GMR 400.00 2 1.76 0.00973 0.004865 0 0.004865 -100 C2 6 D
414014 VEMAGIRI 400.00 414016 GAUTAMI 400.00 1 40 0.2764 0.1382 0 0.1382 -249.4 B2 10 B
414014 VEMAGIRI 400.00 414016 GAUTAMI 400.00 2 40 0.2764 0.1382 0 0.1382 D 3 F
414014 VEMAGIRI 400.00 414017 KONSEEMA 400.00 1 26.16 0.14462 0.07231 0 0.07231 B2 11 B
414014 VEMAGIRI 400.00 414017 KONSEEMA 400.00 2 26.16 0.14462 0.07231 0 0.07231 0 C2 4 E
414014 VEMAGIRI 400.00 414018 GVK-II 400.00 1 6.5 0.03593 0.017965 0 0.017965 A 12 B
414014 VEMAGIRI 400.00 414018 GVK-II 400.00 2 6.5 0.03593 0.017965 0 0.017965 0 B1 5 E
414014 VEMAGIRI 400.00 414020 SMHDRI-2 400.00 1 194.48 1.0796 0.5398 0 0.5398 -161.1 B2 15 A
414014 VEMAGIRI 400.00 414020 SMHDRI-2 400.00 2 194.48 1.0796 0.5398 0 0.5398 -161.1 C2 7 D
414014 VEMAGIRI 400.00 414021 STNPLLI 400.00 1 244.85 1.474 0.737 0 0.737 164.1 8 C
414014 VEMAGIRI 400.00 414008 NUNNA 400.00 1 192.34 0.13472 0.06736 0 0.06736 154.5 A 16 A
414014 VEMAGIRI 400.00 414008 NUNNA 400.00 2 192.34 0.13472 0.06736 0 0.06736 154.5 B2 13 A
414014 VEMAGIRI 400.00 414008 NUNNA 400.00 3 195.21 1.08779 0.543895 0 0.543895 99.7 C1 1 H
414014 VEMAGIRI 400.00 414011 KALPAKKA 400.00 1 166.93 1.0124 0.5062 0 0.5062 -198.9 A 14 A
414014 VEMAGIRI 400.00 414011 KALPAKKA 400.00 2 166.93 1.0124 0.5062 0 0.5062 -198.9 D 2 G
414015 GMR 400.00 414014 VEMAGIRI 400.00 1 1.76 0.00973 0.004865 0 0.004865 100 B2 2 B
414015 GMR 400.00 414014 VEMAGIRI 400.00 2 1.76 0.00973 0.004865 0 0.004865 100 C2 1 F
414016 GAUTAMI 400.00 414014 VEMAGIRI 400.00 1 40 0.2764 0.1382 0 0.1382 250 B2 2 B
414016 GAUTAMI 400.00 414014 VEMAGIRI 400.00 2 40 0.2764 0.1382 0 0.1382 D 1 F
414017 KONSEEMA 400.00 414014 VEMAGIRI 400.00 1 26.16 0.14462 0.07231 0 0.07231 B2 2 B
414017 KONSEEMA 400.00 414014 VEMAGIRI 400.00 2 26.16 0.14462 0.07231 0 0.07231 0 C2 1 F
414018 GVK-II 400.00 414014 VEMAGIRI 400.00 1 6.5 0.03593 0.017965 0 0.017965 B2 2 B
414018 GVK-II 400.00 414014 VEMAGIRI 400.00 2 6.5 0.03593 0.017965 0 0.017965 0 C2 1 F
414019 LANCO 400.00 414008 NUNNA 400.00 1 22 0.1221 0.06105 0 0.06105 165 B2 2 B
414019 LANCO 400.00 414008 NUNNA 400.00 2 22 0.1221 0.06105 0 0.06105 165 C2 1 F
414020 SMHDRI-2 400.00 414009 GAZUWAKA 400.00 1 14.1 0.07825 0.039125 0 0.039125 71.6 A 4 A
414020 SMHDRI-2 400.00 414009 GAZUWAKA 400.00 2 14.1 0.07825 0.039125 0 0.039125 71.6 B2 2 C
Annexure-VII
3 of 11
414020 SMHDRI-2 400.00 414014 VEMAGIRI 400.00 1 194.48 1.0796 0.5398 0 0.5398 162.2 B2 3 B
414020 SMHDRI-2 400.00 414014 VEMAGIRI 400.00 2 194.48 1.0796 0.5398 0 0.5398 162.2 D 1 D
414021 STNPLLI 400.00 424005 SRLMLB 400.00 1 160.65 0.8916 0.4458 0 0.4458 89.1 B1 4 C
414021 STNPLLI 400.00 424005 SRLMLB 400.00 2 160.65 0.8916 0.4458 0 0.4458 89.1 D 1 G
414021 STNPLLI 400.00 414008 NUNNA 400.00 1 115.89 0.69766 0.34883 0 0.34883 -161.9 5 B
414021 STNPLLI 400.00 414013 VTS-IV 400.00 1 115 0.63825 0.319125 0 0.319125 -111.4 A 6 A
414021 STNPLLI 400.00 414013 VTS-IV 400.00 2 115 0.63825 0.319125 0 0.319125 -111.4 C1 2 E
414021 STNPLLI 400.00 414014 VEMAGIRI 400.00 1 244.85 1.474 0.737 0 0.737 -162.9 3 D
414022 SMHPURI 400.00 414023 NLR-PS 400.00 1 26.88 0.19674 0.09837 0 0.09837 416.4 B2 1 D
414022 SMHPURI 400.00 414026 MNAKSHI 400.00 1 5 0.03698 0.01849 0 0.01849 123.6 A 2 A
414023 NLR-PS 400.00 414026 MNAKSHI 400.00 1 26.88 0.197 0.0985 0 0.0985 -393.1 C2 3 E
414023 NLR-PS 400.00 414034 THPTECH 400.00 1 32.5 0.2379 0.11895 0 0.11895 -642 7 A
414023 NLR-PS 400.00 414035 NCC 400.00 1 33 0.24156 0.12078 0 0.12078 -543.5 4 D
414023 NLR-PS 400.00 414001 GOOTY 400.00 1 289 2.118 1.059 -0.4535 0.6055 141.1 D 2 F
414023 NLR-PS 400.00 414001 GOOTY 400.00 2 289 2.1183 1.05915 -0.4535 0.60565 141.1 C2 1 G
414023 NLR-PS 400.00 414003 NLR-PG 400.00 1 6.35 0.04648 0.02324 0 0.02324 794.1 A 8 A
414023 NLR-PS 400.00 414003 NLR-PG 400.00 2 6.35 0.04655 0.023275 0 0.023275 794.1 A 6 B
414023 NLR-PS 400.00 414022 SMHPURI 400.00 1 26.88 0.19674 0.09837 0 0.09837 -416 B2 5 C
414026 MNAKSHI 400.00 414022 SMHPURI 400.00 1 5 0.03698 0.01849 0 0.01849 -123.5 A 2 A
414026 MNAKSHI 400.00 414023 NLR-PS 400.00 1 26.88 0.197 0.0985 0 0.0985 393.5 C2 1 C
414027 HINDUJA 400.00 414011 KALPAKKA 400.00 1 7.35 0.04425 0.022125 0 0.022125 0 A 3 A
414027 HINDUJA 400.00 414011 KALPAKKA 400.00 2 7.35 0.044247 0.0221235 0 0.0221235 0 C2 1 D
414027 HINDUJA 400.00 414014 VEMAGIRI 400.00 1 40 0.222 0.111 0 0.111 B1 2 B
414029 NLR-AP 400.00 414030 SDSTPS 400.00 1 68.1 0.49917 0.249585 0 0.249585 -259.9 A 4 A
414029 NLR-AP 400.00 414030 SDSTPS 400.00 2 68.1 0.49917 0.249585 0 0.249585 -259.9 3 B
414029 NLR-AP 400.00 414008 NUNNA 400.00 1 348.2 1.93251 0.966255 -0.5714 0.394855 19.4 1 E
414029 NLR-AP 400.00 414013 VTS-IV 400.00 1 330.8 1.83594 0.91797 -0.5714 0.34657 34.5 2 D
414030 SDSTPS 400.00 414002 CHITOOR 400.00 1 189.07 1.38588 0.69294 0 0.69294 364.7 C1 4 A
414030 SDSTPS 400.00 414002 CHITOOR 400.00 2 189.07 1.38588 0.69294 0 0.69294 364.7 1 E
414030 SDSTPS 400.00 414029 NLR-AP 400.00 1 68.1 0.49917 0.249585 0 0.249585 260.3 A 3 B
414030 SDSTPS 400.00 414029 NLR-AP 400.00 2 68.1 0.49917 0.249585 0 0.249585 260.3 2 D
414031 KRNL-PG 400.00 414001 GOOTY 400.00 1 112.5 0.62437 0.312185 0 0.312185 69.1 C1 2 C
414031 KRNL-PG 400.00 414007 TALPALLI 400.00 1 264.5 1.46798 0.73399 0 0.73399 51.1 B2 1 D
414031 KRNL-PG 400.00 414010 KURNOOL 400.00 1 9.88 0.07243 0.036215 0 0.036215 379.5 A 4 A
414031 KRNL-PG 400.00 414010 KURNOOL 400.00 2 9.88 0.07243 0.036215 0 0.036215 379.5 B1 3 B
414032 GTYN-FSC 400.00 434004 NLMMGLA 400.00 1 256.13 1.42152 0.71076 0 0.71076 406.7 A 1 A
414032 GTYN-FSC 400.00 414001 GOOTY 400.00 1 0 0 0 0 0 -406.7 ** **
414033 GTYS-FSC 400.00 434005 SMNHLLY 400.00 1 301 1.6705 0.83525 0 0.83525 342.7 C1 1 C
414033 GTYS-FSC 400.00 414001 GOOTY 400.00 1 0 0 0 0 0 -342.7 ** **
414034 THPTECH 400.00 414035 NCC 400.00 1 5.4 0.03953 0.019765 0 0.019765 544.6 2 A
414034 THPTECH 400.00 414023 NLR-PS 400.00 1 32.5 0.2379 0.11895 0 0.11895 643.4 1 C
414035 NCC 400.00 414023 NLR-PS 400.00 1 33 0.24156 0.12078 0 0.12078 544.5 1 C
414035 NCC 400.00 414034 THPTECH 400.00 1 5.4 0.03953 0.019765 0 0.019765 -544.5 2 A
424001 MAHBBNGR 400.00 434006 RCHR-TPS 400.00 1 73.68 0.40892 0.20446 0 0.20446 -506.5 D 2 B
424001 MAHBBNGR 400.00 414007 TALPALLI 400.00 1 184.53 1.02342 0.51171 0 0.51171 -29.4 B1 1 E
424002 RGM-NTPC 400.00 424003 GHANAPUR 400.00 1 201.25 1.11694 0.55847 0 0.55847 315.7 A 9 A
424002 RGM-NTPC 400.00 424003 GHANAPUR 400.00 2 201.25 1.11694 0.55847 0 0.55847 315.7 D 1 H
424002 RGM-NTPC 400.00 424007 DICHIPLY 400.00 1 147.98 0.82139 0.410695 0 0.410695 285.4 C2 4 E
424002 RGM-NTPC 400.00 424008 GAJWEL 400.00 1 135 0.74924 0.37462 0 0.37462 446.5 B1 5 D
Annexure-VII
4 of 11
424002 RGM-NTPC 400.00 424010 WARANGAL 400.00 1 98.8 0.54836 0.27418 0 0.27418 314.5 D 6 C
424002 RGM-NTPC 400.00 424011 MALKARAM 400.00 2 194 1.0724 0.5362 0 0.5362 340.1 B2 2 G
424002 RGM-NTPC 400.00 424014 BDRAWATHI 400.00 1 177.61 0.98571 0.492855 0 0.492855 -488.9 B2 10 A
424002 RGM-NTPC 400.00 424014 BDRAWATHI 400.00 2 177.61 0.98571 0.492855 0 0.492855 -488.9 A 8 B
424002 RGM-NTPC 400.00 414007 TALPALLI 400.00 1 267.2 1.48296 0.74148 -0.4535 0.28798 183.5 A 7 B
424002 RGM-NTPC 400.00 414007 TALPALLI 400.00 2 267.2 1.48296 0.74148 -0.4535 0.28798 183.5 B2 3 F
424003 GHANAPUR 400.00 424006 MMDPALLI 400.00 1 46 0.2553 0.12765 0 0.12765 248.5 B1 6 A
424003 GHANAPUR 400.00 424008 GAJWEL 400.00 1 72.95 0.40403 0.202015 -0.45351 -0.251495 -53.6 C1 3 D
424003 GHANAPUR 400.00 424011 MALKARAM 400.00 1 54.9 0.31111 0.155555 -0.4535 -0.297945 26.5 C2 2 E
424003 GHANAPUR 400.00 414007 TALPALLI 400.00 1 155.26 0.86172 0.43086 0 0.43086 -98 A 4 C
424003 GHANAPUR 400.00 414010 KURNOOL 400.00 1 226.5 1.2571 0.62855 0 0.62855 -113.9 D 1 G
424003 GHANAPUR 400.00 424002 RGM-NTPC 400.00 1 201.25 1.11694 0.55847 0 0.55847 -312 A 7 A
424003 GHANAPUR 400.00 424002 RGM-NTPC 400.00 2 201.25 1.11694 0.55847 0 0.55847 -312 B2 5 B
424004 KHAMMAM 400.00 424006 MMDPALLI 400.00 1 198 1.2008 0.6004 0 0.6004 228.9 C1 8 B
424004 KHAMMAM 400.00 424006 MMDPALLI 400.00 2 198 1.2008 0.6004 0 0.6004 228.9 D2 1 H
424004 KHAMMAM 400.00 424010 WARANGAL 400.00 1 117.09 0.64985 0.324925 -0.4535 -0.128575 -32 B2 5 D
424004 KHAMMAM 400.00 424012 KTPS 400.00 1 67.76 0.37606 0.18803 0 0.18803 -224.9 B2 11 A
424004 KHAMMAM 400.00 424012 KTPS 400.00 2 67.76 0.37606 0.18803 0 0.18803 -224.9 C2 7 C
424004 KHAMMAM 400.00 414007 TALPALLI 400.00 1 144.58 0.80242 0.40121 0 0.40121 98 A 10 A
424004 KHAMMAM 400.00 414007 TALPALLI 400.00 2 144.58 0.869384 0.434692 0 0.434692 105.8 6 C
424004 KHAMMAM 400.00 414007 TALPALLI 400.00 3 144.58 0.869384 0.434692 0 0.434692 105.8 2 G
424004 KHAMMAM 400.00 414008 NUNNA 400.00 1 114.78 0.637 0.3185 0 0.3185 -104 D 4 E
424004 KHAMMAM 400.00 414011 KALPAKKA 400.00 1 364 2.2076 1.1038 -0.5714 0.5324 -183.9 A 9 B
424004 KHAMMAM 400.00 414011 KALPAKKA 400.00 2 364 2.2076 1.1038 -0.5714 0.5324 -183.9 C1 3 F
424005 SRLMLB 400.00 424006 MMDPALLI 400.00 1 147 0.8126 0.4063 0 0.4063 151.8 B1 3 C
424005 SRLMLB 400.00 424013 SNKRPLLI 400.00 1 128.5 0.71323 0.356615 0 0.356615 181.5 5 A
424005 SRLMLB 400.00 414010 KURNOOL 400.00 1 104.9 0.5749 0.28745 0 0.28745 -155.6 D 2 D
424005 SRLMLB 400.00 414021 STNPLLI 400.00 1 160.65 0.8916 0.4458 0 0.4458 -88.8 B1 4 B
424005 SRLMLB 400.00 414021 STNPLLI 400.00 2 160.65 0.8916 0.4458 0 0.4458 -88.8 D2 1 E
424006 MMDPALLI 400.00 424003 GHANAPUR 400.00 1 46 0.2553 0.12765 0 0.12765 -248 B1 4 A
424006 MMDPALLI 400.00 424004 KHAMMAM 400.00 1 198 1.2008 0.6004 0 0.6004 -226.9 C1 3 B
424006 MMDPALLI 400.00 424004 KHAMMAM 400.00 2 198 1.2008 0.6004 0 0.6004 -226.9 D 1 D
424006 MMDPALLI 400.00 424005 SRLMLB 400.00 1 147 0.8126 0.4063 0 0.4063 -151.1 B1 2 C
424007 DICHIPLY 400.00 424002 RGM-NTPC 400.00 1 147.98 0.82139 0.410695 0 0.410695 -283.2 C1 1 C
424008 GAJWEL 400.00 424009 KKTYATPS 400.00 1 131 0.72705 0.363525 0 0.363525 -216.6 A 7 A
424008 GAJWEL 400.00 424009 KKTYATPS 400.00 2 131 0.72705 0.363525 0 0.363525 -216.6 C1 3 E
424008 GAJWEL 400.00 424013 SNKRPLLI 400.00 1 105 0.58275 0.291375 0 0.291375 159.7 D 6 B
424008 GAJWEL 400.00 424013 SNKRPLLI 400.00 2 105 0.58275 0.291375 0 0.291375 159.7 C1 2 F
424008 GAJWEL 400.00 424015 JAIPUR 400.00 1 163.242 1.19656 0.59828 0 0.59828 0.1 4 D
424008 GAJWEL 400.00 424015 JAIPUR 400.00 2 163.242 1.19656 0.59828 0 0.59828 0.1 1 G
424008 GAJWEL 400.00 424002 RGM-NTPC 400.00 1 135 0.74924 0.37462 0 0.37462 -441.3 B1 8 B
424008 GAJWEL 400.00 424003 GHANAPUR 400.00 1 72.95 0.40403 0.202015 0 0.202015 53.6 A 5 C
424009 KKTYATPS 400.00 424010 WARANGAL 400.00 1 46 0.27647 0.138235 0 0.138235 -13.8 A 4 A
424009 KKTYATPS 400.00 424010 WARANGAL 400.00 2 46 0.27647 0.138235 0 0.138235 -13.8 C2 2 C
424009 KKTYATPS 400.00 424008 GAJWEL 400.00 1 131 0.72705 0.363525 0 0.363525 217.8 A 3 B
424009 KKTYATPS 400.00 424008 GAJWEL 400.00 2 131 0.72705 0.363525 0 0.363525 217.8 D 1 E
424010 WARANGAL 400.00 424002 RGM-NTPC 400.00 1 98.8 0.54836 0.27418 -0.4535 -0.17932 -312.6 C1 3 B
424010 WARANGAL 400.00 424004 KHAMMAM 400.00 1 117.09 0.64985 0.324925 0 0.324925 32 B2 1 D
424010 WARANGAL 400.00 424009 KKTYATPS 400.00 1 46 0.27647 0.138235 0 0.138235 13.8 B1 4 A
Annexure-VII
5 of 11
424010 WARANGAL 400.00 424009 KKTYATPS 400.00 2 46 0.27647 0.138235 0 0.138235 13.8 C1 2 C
424011 MALKARAM 400.00 414013 VTS-IV 400.00 1 261.9 1.4529 0.72645 0 0.72645 -145.1 B1 3 B
424011 MALKARAM 400.00 414013 VTS-IV 400.00 2 261.9 1.4529 0.72645 0 0.72645 -145.1 D 1 E
424011 MALKARAM 400.00 424002 RGM-NTPC 400.00 2 194 1.0724 0.5362 0 0.5362 -335.8 B2 4 A
424011 MALKARAM 400.00 424003 GHANAPUR 400.00 1 54.9 0.31111 0.155555 0 0.155555 -26.5 C2 2 C
424012 KTPS 400.00 424004 KHAMMAM 400.00 1 67.76 0.37606 0.18803 0 0.18803 225.6 B2 2 A
424012 KTPS 400.00 424004 KHAMMAM 400.00 2 67.76 0.37606 0.18803 0 0.18803 225.6 C2 1 C
424013 SNKRPLLI 400.00 424005 SRLMLB 400.00 1 128.5 0.71323 0.356615 0 0.356615 -180.7 2 C
424013 SNKRPLLI 400.00 424006 MMDPALLI 400.00 1 17.8 0.09884 0.04942 0 0.04942 -74.7 4 A
424013 SNKRPLLI 400.00 424008 GAJWEL 400.00 1 105 0.58275 0.291375 0 0.291375 -159.2 B1 3 B
424013 SNKRPLLI 400.00 424008 GAJWEL 400.00 2 105 0.58275 0.291375 0 0.291375 -159.2 D 1 D
424014 BDRAWATHI 400.00 424002 RGM-NTPC 400.00 1 177.61 0.98571 0.492855 0 0.492855 497 A 2 A
424014 BDRAWATHI 400.00 424002 RGM-NTPC 400.00 2 177.61 0.98571 0.492855 0 0.492855 497 C2 1 C
424015 JAIPUR 400.00 424008 GAJWEL 400.00 1 163.242 1.19656 0.59828 0 0.59828 0 2 B
424015 JAIPUR 400.00 424008 GAJWEL 400.00 2 163.242 1.19656 0.59828 0 0.59828 0 1 D
434003 HOODY 400.00 434004 NLMMGLA 400.00 1 45 0.24975 0.124875 0 0.124875 54.6 D 3 B
434003 HOODY 400.00 434004 NLMMGLA 400.00 2 45 0.24975 0.124875 0 0.124875 54.6 B2 1 D
434003 HOODY 400.00 434010 KOLAR-PG 400.00 1 51.07 0.3811 0.19055 0 0.19055 -460.3 C1 4 A
434003 HOODY 400.00 434010 KOLAR-PG 400.00 2 51.07 0.3811 0.19055 0 0.19055 -460.3 A 2 C
434004 NLMMGLA 400.00 434007 BIDADI 400.00 1 34.75 0.19286 0.09643 0 0.09643 186 B2 9 B
434004 NLMMGLA 400.00 434007 BIDADI 400.00 2 34.75 0.19286 0.09643 0 0.09643 186 A 5 D
434004 NLMMGLA 400.00 434013 HASSAN 400.00 1 265 1.47075 0.735375 0 0.735375 -41.8 A 3 F
434004 NLMMGLA 400.00 434018 TALAGUPA 400.00 1 354 1.96469 0.982345 0 0.982345 -178.3 D 1 H
434004 NLMMGLA 400.00 434019 HIRIYUR 400.00 1 160 0.888 0.444 0 0.444 -409.8 B2 11 A
434004 NLMMGLA 400.00 434019 HIRIYUR 400.00 2 160 0.888 0.444 0 0.444 -409.8 A 8 B
434004 NLMMGLA 400.00 434020 MYSORE 400.00 1 132.9 0.73758 0.36879 0 0.36879 100.3 C1 6 C
434004 NLMMGLA 400.00 434020 MYSORE 400.00 2 132.9 0.73758 0.36879 0 0.36879 100.3 B1 2 G
434004 NLMMGLA 400.00 414032 GTYN-FSC 400.00 1 256.13 1.42152 0.71076 -0.4535 0.25726 -398.5 A 10 A
434004 NLMMGLA 400.00 434003 HOODY 400.00 1 45 0.24975 0.124875 0 0.124875 -54.5 C2 7 C
434004 NLMMGLA 400.00 434003 HOODY 400.00 2 45 0.24975 0.124875 0 0.124875 -54.5 B2 4 E
434005 SMNHLLY 400.00 434007 BIDADI 400.00 1 16.97 0.09418 0.04709 0 0.04709 8.7 C1 4 B
434005 SMNHLLY 400.00 434007 BIDADI 400.00 2 16.97 0.09418 0.04709 0 0.04709 8.7 A 3 C
434005 SMNHLLY 400.00 434010 KOLAR-PG 400.00 1 97.39 0.54052 0.27026 -0.4535 -0.18324 -270.7 A 5 A
434005 SMNHLLY 400.00 444006 HOSUR 400.00 1 79.75 0.44265 0.221325 0 0.221325 -12.9 A 1 E
434005 SMNHLLY 400.00 414033 GTYS-FSC 400.00 1 301 1.6705 0.83525 -0.5714 0.26385 -335.8 D2 2 D
434006 RCHR-TPS 400.00 434009 RCHR-NEW 400.00 1 22.3 0.16465 0.082325 0 0.082325 -81.1 B1 5 A
434006 RCHR-TPS 400.00 434009 RCHR-NEW 400.00 2 22.3 0.16465 0.082325 0 0.082325 -81.1 A 4 B
434006 RCHR-TPS 400.00 434011 BTPS 400.00 1 151.4 0.83249 0.416245 0 0.416245 -178.9 C1 2 D
434006 RCHR-TPS 400.00 434016 MUNRABAD 400.00 1 172.45 0.95707 0.478535 0 0.478535 90.6 D 1 E
434006 RCHR-TPS 400.00 424001 MAHBBNGR 400.00 1 73.68 0.40892 0.20446 0 0.20446 510.1 C2 3 C
434007 BIDADI 400.00 434004 NLMMGLA 400.00 1 34.75 0.19286 0.09643 0 0.09643 -185.6 D 3 B
434007 BIDADI 400.00 434004 NLMMGLA 400.00 2 34.75 0.19286 0.09643 0 0.09643 -185.6 A 1 D
434007 BIDADI 400.00 434005 SMNHLLY 400.00 1 16.97 0.09418 0.04709 0 0.04709 -8.7 C2 4 A
434007 BIDADI 400.00 434005 SMNHLLY 400.00 2 16.97 0.09418 0.04709 0 0.04709 -8.7 A 2 C
434008 TUMKUR 400.00 414001 GOOTY 400.00 1 208.62 1.25589 0.627945 0 0.627945 0 B1 2 B
434008 TUMKUR 400.00 414001 GOOTY 400.00 2 208.62 1.25589 0.627945 0 0.627945 D 1 D
434009 RCHR-NEW 400.00 414001 GOOTY 400.00 1 128.6 0.95104 0.47552 0 0.47552 299.4 D 3 B
434009 RCHR-NEW 400.00 414001 GOOTY 400.00 2 128.6 0.95104 0.47552 0 0.47552 299.4 A 1 E
434009 RCHR-NEW 400.00 434006 RCHR-TPS 400.00 1 22.3 0.16465 0.082325 0 0.082325 81.2 A 4 A
Annexure-VII
6 of 11
434009 RCHR-NEW 400.00 434006 RCHR-TPS 400.00 2 22.3 0.16465 0.082325 0 0.082325 81.2 C2 2 C
434010 KOLAR-PG 400.00 444006 HOSUR 400.00 1 69 0.38295 0.191475 0 0.191475 374.8 A 7 A
434010 KOLAR-PG 400.00 444006 HOSUR 400.00 2 69 0.38295 0.191475 0 0.191475 374.8 B2 5 B
434010 KOLAR-PG 400.00 444024 TRVLM 400.00 1 153.19 0.8502 0.4251 0 0.4251 -202.1 D2 3 D
434010 KOLAR-PG 400.00 414004 CHNKMPLY 400.00 1 174 0.96611 0.483055 0 0.483055 -153.7 B2 1 G
434010 KOLAR-PG 400.00 434003 HOODY 400.00 1 51.07 0.3811 0.19055 0 0.19055 461.6 C2 6 A
434010 KOLAR-PG 400.00 434003 HOODY 400.00 2 51.07 0.3811 0.19055 0 0.19055 461.6 B2 4 C
434010 KOLAR-PG 400.00 434005 SMNHLLY 400.00 1 97.39 0.54052 0.27026 0 0.27026 272.6 A 2 E
434011 BTPS 400.00 434014 JINDAL 400.00 1 8 0.04399 0.021995 0 0.021995 -421.1 A 4 A
434011 BTPS 400.00 434019 HIRIYUR 400.00 1 156 0.8658 0.4329 0 0.4329 370.6 C2 3 B
434011 BTPS 400.00 434019 HIRIYUR 400.00 2 156 0.8658 0.4329 0 0.4329 370.6 B2 1 D
434011 BTPS 400.00 434006 RCHR-TPS 400.00 1 151.4 0.83249 0.416245 0 0.416245 179.8 B1 2 C
434012 GUTTUR 400.00 434014 JINDAL 400.00 1 142.5 0.78355 0.391775 0 0.391775 -322.5 A 8 A
434012 GUTTUR 400.00 434015 KAIGA 400.00 1 163 0.90465 0.452325 0 0.452325 -136.1 C1 6 B
434012 GUTTUR 400.00 434015 KAIGA 400.00 2 163 0.90462 0.45231 0 0.45231 -136.2 D 4 D
434012 GUTTUR 400.00 434016 MUNRABAD 400.00 1 118.3 0.65656 0.32828 0 0.32828 1.1 C2 2 F
434012 GUTTUR 400.00 434017 NARENDRA 400.00 1 156.5 0.8769 0.43845 0 0.43845 -33 D 3 E
434012 GUTTUR 400.00 434017 NARENDRA 400.00 2 156.5 0.8769 0.43845 0 0.43845 -33 C2 1 G
434012 GUTTUR 400.00 434019 HIRIYUR 400.00 1 100 0.555 0.2775 0 0.2775 194.6 B1 7 A
434012 GUTTUR 400.00 434019 HIRIYUR 400.00 2 100 0.555 0.2775 0 0.2775 194.6 C1 5 C
434013 HASSAN 400.00 434018 TALAGUPA 400.00 1 260 1.443 0.7215 0 0.7215 -205.5 C2 2 E
434013 HASSAN 400.00 434020 MYSORE 400.00 1 97 0.5383 0.26915 0 0.26915 237.4 D 5 B
434013 HASSAN 400.00 434020 MYSORE 400.00 2 97 0.5383 0.26915 0 0.26915 237.4 A 3 D
434013 HASSAN 400.00 434021 UPCL 400.00 1 178 1.31657 0.658285 0 0.658285 -291.1 A 6 A
434013 HASSAN 400.00 434021 UPCL 400.00 2 178 1.31657 0.658285 0 0.658285 -291.1 B1 4 C
434013 HASSAN 400.00 434004 NLMMGLA 400.00 1 265 1.47075 0.735375 0 0.735375 41.7 D2 1 G
434014 JINDAL 400.00 434011 BTPS 400.00 1 8 0.04399 0.021995 0 0.021995 421.3 A 2 C
434014 JINDAL 400.00 434012 GUTTUR 400.00 1 142.5 0.78355 0.391775 0 0.391775 325.3 C2 1 A
434015 KAIGA 400.00 434017 NARENDRA 400.00 1 107 0.61044 0.30522 0 0.30522 160.1 D 4 A
434015 KAIGA 400.00 434017 NARENDRA 400.00 2 107 0.61044 0.30522 0 0.30522 160.1 B2 2 C
434015 KAIGA 400.00 434012 GUTTUR 400.00 1 163 0.90465 0.452325 0 0.452325 136.7 C1 3 B
434015 KAIGA 400.00 434012 GUTTUR 400.00 2 163 0.90462 0.45231 0 0.45231 136.8 D 1 E
434016 MUNRABAD 400.00 434006 RCHR-TPS 400.00 1 172.45 0.95707 0.478535 -0.5714 -0.092865 -90.3 C2 2 B
434016 MUNRABAD 400.00 434012 GUTTUR 400.00 1 118.3 0.65656 0.32828 0 0.32828 -1.1 D 1 D
434017 NARENDRA 400.00 434023 NARENDRA-NEW400.00 1 176.13 1.29105 0.645525 0 0.645525 20.2 3 D
434017 NARENDRA 400.00 434023 NARENDRA-NEW400.00 2 176.13 1.29105 0.645525 0 0.645525 20.2 1 G
434017 NARENDRA 400.00 434012 GUTTUR 400.00 1 156.5 0.8769 0.43845 0 0.43845 33 D 5 B
434017 NARENDRA 400.00 434012 GUTTUR 400.00 2 156.5 0.8769 0.43845 0 0.43845 33 C2 2 E
434017 NARENDRA 400.00 434015 KAIGA 400.00 1 107 0.61044 0.30522 0 0.30522 -159.6 D 6 A
434017 NARENDRA 400.00 434015 KAIGA 400.00 2 107 0.61044 0.30522 0 0.30522 -159.6 B2 4 C
434018 TALAGUPA 400.00 434004 NLMMGLA 400.00 1 354 1.96469 0.982345 0 0.982345 179.1 D 1 D
434018 TALAGUPA 400.00 434013 HASSAN 400.00 1 260 1.443 0.7215 0 0.7215 206.7 C2 2 B
434019 HIRIYUR 400.00 434004 NLMMGLA 400.00 1 160 0.888 0.444 0 0.444 416.4 A 6 A
434019 HIRIYUR 400.00 434004 NLMMGLA 400.00 2 160 0.888 0.444 0 0.444 416.4 B2 3 D
434019 HIRIYUR 400.00 434011 BTPS 400.00 1 156 0.8658 0.4329 0 0.4329 -366.6 A 5 B
434019 HIRIYUR 400.00 434011 BTPS 400.00 2 156 0.8658 0.4329 0 0.4329 -366.6 B2 2 E
434019 HIRIYUR 400.00 434012 GUTTUR 400.00 1 100 0.555 0.2775 0 0.2775 -194.2 B1 4 C
434019 HIRIYUR 400.00 434012 GUTTUR 400.00 2 100 0.555 0.2775 0 0.2775 -194.2 D 1 G
434020 MYSORE 400.00 454008 KOZKODE 400.00 1 203 1.12667 0.563335 0 0.563335 125.6 A 4 C
Annexure-VII
7 of 11
434020 MYSORE 400.00 454008 KOZKODE 400.00 2 203 1.12667 0.563335 0 0.563335 125.6 D 1 G
434020 MYSORE 400.00 434004 NLMMGLA 400.00 1 132.9 0.73758 0.36879 0 0.36879 -100.3 B1 5 B
434020 MYSORE 400.00 434004 NLMMGLA 400.00 2 132.9 0.73758 0.36879 0 0.36879 -100.3 D 2 E
434020 MYSORE 400.00 434013 HASSAN 400.00 1 97 0.5383 0.26915 0 0.26915 -236.3 D 6 A
434020 MYSORE 400.00 434013 HASSAN 400.00 2 97 0.5383 0.26915 0 0.26915 -236.3 A 3 D
434021 UPCL 400.00 434013 HASSAN 400.00 1 178 1.31657 0.658285 0 0.658285 292.5 A 2 A
434021 UPCL 400.00 434013 HASSAN 400.00 2 178 1.31657 0.658285 0 0.658285 292.5 B2 1 B
434023 NARENDRA-NEW400.00 434024 KUDGI-NTPC 400.00 1 8.8 0.06448 0.03224 0 0.03224 0 8 A
434023 NARENDRA-NEW400.00 434024 KUDGI-NTPC 400.00 2 8.8 0.06448 0.03224 0 0.03224 5 C
434023 NARENDRA-NEW400.00 434024 KUDGI-NTPC 400.00 3 8.8 0.06448 0.03224 0 0.03224 4 D
434023 NARENDRA-NEW400.00 434024 KUDGI-NTPC 400.00 4 8.8 0.06448 0.03224 0 0.03224 3 E
434023 NARENDRA-NEW400.00 334058 KOLHAPUR-PG 400.00 1 191.17 1.36721 0.683605 0 0.683605 20.1 6 B
434023 NARENDRA-NEW400.00 334058 KOLHAPUR-PG 400.00 2 191.17 1.36721 0.683605 0 0.683605 20.1 1 G
434023 NARENDRA-NEW400.00 434017 NARENDRA 400.00 1 176.13 1.29105 0.645525 0 0.645525 -20.2 7 A
434023 NARENDRA-NEW400.00 434017 NARENDRA 400.00 2 176.13 1.29105 0.645525 0 0.645525 -20.2 2 F
434024 KUDGI-NTPC 400.00 434023 NARENDRA-NEW400.00 1 8.8 0.06448 0.03224 0 0.03224 0 4 A
434024 KUDGI-NTPC 400.00 434023 NARENDRA-NEW400.00 2 8.8 0.06448 0.03224 0 0.03224 3 B
434024 KUDGI-NTPC 400.00 434023 NARENDRA-NEW400.00 3 8.8 0.06448 0.03224 0 0.03224 2 C
434024 KUDGI-NTPC 400.00 434023 NARENDRA-NEW400.00 4 8.8 0.06448 0.03224 0 0.03224 1 D
444001 SRPRMBDR 400.00 444018 SVCHTRM 400.00 1 17.9 0.00702 0.00351 0 0.00351 -267.2 A 5 A
444001 SRPRMBDR 400.00 444024 TRVLM 400.00 1 85.04 0.47197 0.235985 0 0.235985 -158.7 C1 4 B
444001 SRPRMBDR 400.00 414002 CHITOOR 400.00 1 95.14 0.52803 0.264015 0 0.264015 -158.4 D2 2 D
444001 SRPRMBDR 400.00 414003 NLR-PG 400.00 1 189 1.04895 0.524475 0 0.524475 -276.9 C2 3 C
444001 SRPRMBDR 400.00 414003 NLR-PG 400.00 2 189 1.04895 0.524475 0 0.524475 -276.9 1 E
444002 ALAMATTY 400.00 444018 SVCHTRM 400.00 1 94 0.5217 0.26085 0 0.26085 126.4 D 6 B
444002 ALAMATTY 400.00 444018 SVCHTRM 400.00 2 94 0.5217 0.26085 0 0.26085 126.4 B1 2 F
444002 ALAMATTY 400.00 444019 VALLUR 400.00 1 37.32 0.20535 0.102675 0 0.102675 -463.4 A 8 A
444002 ALAMATTY 400.00 444019 VALLUR 400.00 2 37.32 0.20535 0.102675 0 0.102675 -463.4 C2 5 C
444002 ALAMATTY 400.00 444022 NCTPS-II 400.00 1 84 0.4662 0.2331 0 0.2331 -216.8 A 7 A
444002 ALAMATTY 400.00 444022 NCTPS-II 400.00 2 84 0.4662 0.2331 0 0.2331 -216.8 C1 3 E
444002 ALAMATTY 400.00 444031 TRVLM-TN 400.00 1 112.3 0.67605 0.338025 0 0.338025 50.4 4 D
444002 ALAMATTY 400.00 444031 TRVLM-TN 400.00 2 112.3 0.67605 0.338025 0 0.338025 50.4 1 G
444003 SALEM 400.00 444004 MYWADI 400.00 1 150.4 0.83551 0.417755 0 0.417755 136.7 A 4 C
444003 SALEM 400.00 444004 MYWADI 400.00 2 137.91 0.7654 0.3827 0 0.3827 149.3 C1 2 E
444003 SALEM 400.00 444006 HOSUR 400.00 1 127.06 0.70518 0.35259 0 0.35259 -90.4 C1 3 D
444003 SALEM 400.00 444006 HOSUR 400.00 2 125.32 0.69555 0.347775 -0.4535 -0.105725 -91.6 A 5 B
444003 SALEM 400.00 444014 NLC2 400.00 1 174.95 0.97097 0.485485 -0.4535 0.031985 -378.1 B1 6 A
444003 SALEM 400.00 444014 NLC2 400.00 2 178.72 0.9919 0.49595 0 0.49595 -370.2 D 1 G
444004 MYWADI 400.00 444005 TRNLVLLI 400.00 1 264.99 1.47068 0.73534 -0.5714 0.16394 -154.2 B1 5 C
444004 MYWADI 400.00 444005 TRNLVLLI 400.00 2 264.99 1.47068 0.73534 -0.5714 0.16394 -154.2 D 3 E
444004 MYWADI 400.00 444010 CHKNRANI 400.00 1 127.13 0.70614 0.35307 0 0.35307 -457.7 A 9 A
444004 MYWADI 400.00 444011 ARASUR 400.00 1 65 0.444 0.222 0 0.222 -41.5 B1 4 D
444004 MYWADI 400.00 444011 ARASUR 400.00 2 65 0.444 0.222 0 0.222 -41.5 C2 2 F
444004 MYWADI 400.00 454005 PALAKD 400.00 1 90 0.4995 0.24975 0 0.24975 424.7 A 8 A
444004 MYWADI 400.00 454005 PALAKD 400.00 2 90 0.4995 0.24975 0 0.24975 424.7 B1 6 B
444004 MYWADI 400.00 444003 SALEM 400.00 1 150.4 0.83551 0.417755 -0.4535 -0.035745 -136.2 A 7 B
444004 MYWADI 400.00 444003 SALEM 400.00 2 137.91 0.7654 0.3827 0 0.3827 -148.6 B2 1 G
444005 TRNLVLLI 400.00 444010 CHKNRANI 400.00 1 161.7 0.89744 0.44872 0 0.44872 -110.5 A 1 G
444005 TRNLVLLI 400.00 444017 KKNPP 400.00 2 72 0.52776 0.26388 0 0.26388 -319.1 C2 8 A
Annexure-VII
8 of 11
444005 TRNLVLLI 400.00 444017 KKNPP 400.00 3 79.2 0.58053 0.290265 0 0.290265 -290.3 A 7 A
444005 TRNLVLLI 400.00 444017 KKNPP 400.00 4 79.2 0.58053 0.290265 0 0.290265 -290.3 D2 4 D
444005 TRNLVLLI 400.00 454002 TRIVNDRM 400.00 1 160.4 0.89022 0.44511 0 0.44511 231 A 6 B
444005 TRNLVLLI 400.00 454002 TRIVNDRM 400.00 2 160.4 0.89022 0.44511 0 0.44511 231 B2 2 F
444005 TRNLVLLI 400.00 444004 MYWADI 400.00 1 264.99 1.47068 0.73534 -0.5714 0.16394 155.5 B2 5 C
444005 TRNLVLLI 400.00 444004 MYWADI 400.00 2 264.99 1.47068 0.73534 -0.5714 0.16394 155.5 D 3 E
444006 HOSUR 400.00 434005 SMNHLLY 400.00 1 79.75 0.44265 0.221325 0 0.221325 13 B1 2 D
444006 HOSUR 400.00 434010 KOLAR-PG 400.00 1 69 0.38295 0.191475 0 0.191475 -372.7 A 5 A
444006 HOSUR 400.00 434010 KOLAR-PG 400.00 2 69 0.38295 0.191475 0 0.191475 -372.7 C2 3 C
444006 HOSUR 400.00 444003 SALEM 400.00 1 127.06 0.70518 0.35259 0 0.35259 90.6 D 1 E
444006 HOSUR 400.00 444003 SALEM 400.00 2 125.32 0.69555 0.347775 0 0.347775 91.8 A 4 B
444007 KVPATTU 400.00 444015 PUGALUR 400.00 1 362 2.65346 1.32673 -0.4535 0.87323 98.9 B1 4 C
444007 KVPATTU 400.00 444015 PUGALUR 400.00 2 362 2.65346 1.32673 -0.4535 0.87323 98.9 C2 1 G
444007 KVPATTU 400.00 444019 VALLUR 400.00 1 133.9 0.80608 0.40304 0 0.40304 -263.3 B2 6 A
444007 KVPATTU 400.00 444019 VALLUR 400.00 2 133.9 0.80608 0.40304 0 0.40304 -263.3 C2 2 E
444007 KVPATTU 400.00 444024 TRVLM 400.00 1 113.92 0.63226 0.31613 0 0.31613 -90.6 D 5 B
444007 KVPATTU 400.00 444024 TRVLM 400.00 2 113.92 0.63226 0.31613 0 0.31613 -90.6 C1 3 D
444009 ALUNDUR 400.00 444010 CHKNRANI 400.00 1 130 0.7242 0.3621 0 0.3621 -97.2 B1 2 C
444009 ALUNDUR 400.00 444012 KRAIKUDI 400.00 1 97.7 0.49949 0.249745 0 0.249745 46.2 C1 3 B
444009 ALUNDUR 400.00 444034 NGPTNMPS 400.00 1 160.07 0.88078 0.44039 0 0.44039 -276.1 B1 4 A
444009 ALUNDUR 400.00 444034 NGPTNMPS 400.00 2 160.07 0.88078 0.44039 0 0.44039 -276.1 D 1 E
444010 CHKNRANI 400.00 444012 KRAIKUDI 400.00 1 129.76 0.49949 0.249745 0 0.249745 189.3 C2 3 E
444010 CHKNRANI 400.00 444015 PUGALUR 400.00 1 123.64 0.68265 0.341325 0 0.341325 51.2 B1 5 C
444010 CHKNRANI 400.00 444015 PUGALUR 400.00 2 123.64 0.68265 0.341325 0 0.341325 51.2 D 2 F
444010 CHKNRANI 400.00 444028 TUTCRNPS 400.00 1 94.8 0.69394 0.34697 0 0.34697 -668.8 B2 9 A
444010 CHKNRANI 400.00 444028 TUTCRNPS 400.00 2 94.8 0.69394 0.34697 0 0.34697 -668.8 C2 7 B
444010 CHKNRANI 400.00 444029 TNVL-TIE 400.00 1 161.7 0.89744 0.44872 0 0.44872 1.6 1 G
444010 CHKNRANI 400.00 444004 MYWADI 400.00 1 127.13 0.70614 0.35307 0 0.35307 463 A 8 A
444010 CHKNRANI 400.00 444005 TRNLVLLI 400.00 1 161.7 0.89744 0.44872 0 0.44872 110.9 D 4 D
444010 CHKNRANI 400.00 444009 ALUNDUR 400.00 1 130 0.7242 0.3621 -0.4535 -0.0914 97.4 A 6 B
444011 ARASUR 400.00 444020 METR-III 400.00 1 140 0.777 0.3885 0 0.3885 -153.5 B2 3 B
444011 ARASUR 400.00 444020 METR-III 400.00 2 140 0.777 0.3885 0 0.3885 -153.5 C2 1 D
444011 ARASUR 400.00 444004 MYWADI 400.00 1 65 0.444 0.222 0 0.222 41.6 B1 4 A
444011 ARASUR 400.00 444004 MYWADI 400.00 2 65 0.444 0.222 0 0.222 41.6 C1 2 C
444012 KRAIKUDI 400.00 444015 PUGALUR 400.00 1 160 1.1728 0.5864 0 0.5864 -88.4 5 B
444012 KRAIKUDI 400.00 444015 PUGALUR 400.00 2 160 1.1728 0.5864 0 0.5864 -88.4 2 E
444012 KRAIKUDI 400.00 444030 KAYATHAR 400.00 1 195 1.42935 0.714675 0 0.714675 15.3 C1 4 C
444012 KRAIKUDI 400.00 444030 KAYATHAR 400.00 2 195 1.42935 0.714675 0 0.714675 15.3 B1 1 G
444012 KRAIKUDI 400.00 444009 ALUNDUR 400.00 1 97.7 0.49949 0.249745 0 0.249745 -46.1 A 6 A
444012 KRAIKUDI 400.00 444010 CHKNRANI 400.00 1 129.76 0.49949 0.249745 0 0.249745 -188.7 D 3 D
444013 NLC1EXP 400.00 444014 NLC2 400.00 1 13.94 0.07736 0.03868 0 0.03868 326.9 A 2 A
444013 NLC1EXP 400.00 444034 NGPTNMPS 400.00 1 57.1 0.31594 0.15797 0 0.15797 51.1 B2 1 B
444014 NLC2 400.00 444015 PUGALUR 400.00 1 198.05 1.09916 0.54958 0 0.54958 184.6 C1 1 G
444014 NLC2 400.00 444016 NLC2EXP 400.00 1 1.35 0.00751 0.003755 0 0.003755 -264.9 A 7 A
444014 NLC2 400.00 444034 NGPTNMPS 400.00 1 56.92 0.27315 0.136575 0 0.136575 -33.5 C2 3 D
444014 NLC2 400.00 464001 PONDY 400.00 1 67.88 0.2775 0.13875 0 0.13875 340.9 B2 6 A
444014 NLC2 400.00 444003 SALEM 400.00 1 174.95 0.97097 0.485485 0 0.485485 383.1 A 5 B
444014 NLC2 400.00 444003 SALEM 400.00 2 178.72 0.9919 0.49595 0 0.49595 375.1 D2 2 E
444014 NLC2 400.00 444013 NLC1EXP 400.00 1 13.94 0.07736 0.03868 0 0.03868 -326.7 C1 4 C
Annexure-VII
9 of 11
444015 PUGALUR 400.00 444016 NLC2EXP 400.00 1 199.54 1.10743 0.553715 0 0.553715 -183.8 C2 3 E
444015 PUGALUR 400.00 444007 KVPATTU 400.00 1 362 2.65346 1.32673 -0.4535 0.87323 -98.6 C2 4 D
444015 PUGALUR 400.00 444007 KVPATTU 400.00 2 362 2.65346 1.32673 -0.4535 0.87323 -98.6 B2 1 G
444015 PUGALUR 400.00 444010 CHKNRANI 400.00 1 123.64 0.68265 0.341325 0 0.341325 -51.1 B1 7 A
444015 PUGALUR 400.00 444010 CHKNRANI 400.00 2 123.64 0.68265 0.341325 0 0.341325 -51.1 D 6 B
444015 PUGALUR 400.00 444012 KRAIKUDI 400.00 1 160 1.1728 0.5864 0 0.5864 88.5 5 C
444015 PUGALUR 400.00 444012 KRAIKUDI 400.00 2 160 1.1728 0.5864 0 0.5864 88.5 2 F
444015 PUGALUR 400.00 444014 NLC2 400.00 1 198.05 1.09916 0.54958 -0.4535 0.09608 -183.4 C1 8 A
444016 NLC2EXP 400.00 444014 NLC2 400.00 1 1.35 0.00751 0.003755 0 0.003755 264.9 A 2 A
444016 NLC2EXP 400.00 444015 PUGALUR 400.00 1 199.54 1.10743 0.553715 0 0.553715 185.1 B1 1 B
444017 KKNPP 400.00 444029 TNVL-TIE 400.00 1 72 0.52776 0.26388 0 0.26388 -1.6 B2 4 A
444017 KKNPP 400.00 444005 TRNLVLLI 400.00 2 72 0.52776 0.26388 0 0.26388 319.8 C2 2 C
444017 KKNPP 400.00 444005 TRNLVLLI 400.00 3 79.2 0.58053 0.290265 0 0.290265 290.9 A 3 B
444017 KKNPP 400.00 444005 TRNLVLLI 400.00 4 79.2 0.58053 0.290265 0 0.290265 290.9 D2 1 E
444018 SVCHTRM 400.00 444022 NCTPS-II 400.00 1 95 0.52725 0.263625 0 0.263625 -314.7 A 4 C
444018 SVCHTRM 400.00 444022 NCTPS-II 400.00 2 95 0.52725 0.263625 0 0.263625 -314.7 B1 1 G
444018 SVCHTRM 400.00 464001 PONDY 400.00 1 136.42 0.0535 0.02675 0 0.02675 58.3 B1 3 D
444018 SVCHTRM 400.00 444001 SRPRMBDR 400.00 1 17.9 0.00702 0.00351 0 0.00351 267.5 B1 6 A
444018 SVCHTRM 400.00 444002 ALAMATTY 400.00 1 94 0.5217 0.26085 0 0.26085 -126.1 A 5 B
444018 SVCHTRM 400.00 444002 ALAMATTY 400.00 2 94 0.5217 0.26085 0 0.26085 -126.1 D 2 E
444019 VALLUR 400.00 444022 NCTPS-II 400.00 1 3.5 0.01942 0.00971 0 0.00971 -30.9 B2 4 C
444019 VALLUR 400.00 444022 NCTPS-II 400.00 2 3.5 0.01942 0.00971 0 0.00971 -30.9 C2 2 E
444019 VALLUR 400.00 444002 ALAMATTY 400.00 1 37.32 0.20535 0.102675 0 0.102675 464.9 B1 6 A
444019 VALLUR 400.00 444002 ALAMATTY 400.00 2 37.32 0.20535 0.102675 0 0.102675 464.9 C1 3 D
444019 VALLUR 400.00 444007 KVPATTU 400.00 1 133.9 0.80608 0.40304 0 0.40304 265 B1 5 B
444019 VALLUR 400.00 444007 KVPATTU 400.00 2 133.9 0.80608 0.40304 0 0.40304 265 D 1 G
444020 METR-III 400.00 444031 TRVLM-TN 400.00 1 270 1.9764 0.9882 -0.5714 0.4168 -312.9 3 B
444020 METR-III 400.00 444031 TRVLM-TN 400.00 2 270 1.9764 0.9882 -0.5714 0.4168 -312.9 1 D
444020 METR-III 400.00 444011 ARASUR 400.00 1 140 0.777 0.3885 0 0.3885 154.2 B2 4 A
444020 METR-III 400.00 444011 ARASUR 400.00 2 140 0.777 0.3885 0 0.3885 154.2 D 2 C
444021 TUTCRNJV 400.00 444023 CENERGY 400.00 1 47.29 0.34664 0.17332 0 0.17332 304.6 A 2 A
444021 TUTCRNJV 400.00 444028 TUTCRNPS 400.00 1 61.58 0.45077 0.225385 0 0.225385 645.4 B1 1 B
444022 NCTPS-II 400.00 444002 ALAMATTY 400.00 1 84 0.4662 0.2331 0 0.2331 217.6 B1 4 C
444022 NCTPS-II 400.00 444002 ALAMATTY 400.00 2 84 0.4662 0.2331 0 0.2331 217.6 C1 2 E
444022 NCTPS-II 400.00 444018 SVCHTRM 400.00 1 95 0.52725 0.263625 0 0.263625 316.5 B2 5 B
444022 NCTPS-II 400.00 444018 SVCHTRM 400.00 2 95 0.52725 0.263625 0 0.263625 316.5 D 1 G
444022 NCTPS-II 400.00 444019 VALLUR 400.00 1 3.5 0.01942 0.00971 0 0.00971 30.9 B2 6 A
444022 NCTPS-II 400.00 444019 VALLUR 400.00 2 3.5 0.01942 0.00971 0 0.00971 30.9 C2 3 D
444023 CENERGY 400.00 444028 TUTCRNPS 400.00 1 13 0.26388 0.13194 0 0.13194 704.2 A 2 A
444023 CENERGY 400.00 444021 TUTCRNJV 400.00 1 47.29 0.34664 0.17332 0 0.17332 -304.2 C1 1 C
444024 TRVLM 400.00 414002 CHITOOR 400.00 1 21.02 0.15409 0.077045 0 0.077045 -100.8 A 8 A
444024 TRVLM 400.00 414002 CHITOOR 400.00 2 21.02 0.15409 0.077045 0 0.077045 -100.8 B1 7 A
444024 TRVLM 400.00 414003 NLR-PG 400.00 1 172.96 1.2678 0.6339 -0.453 0.1809 -306.6 D 6 B
444024 TRVLM 400.00 414003 NLR-PG 400.00 2 172.96 1.2678 0.6339 -0.453 0.1809 -306.6 B1 4 D
444024 TRVLM 400.00 434010 KOLAR-PG 400.00 1 153.19 0.8502 0.4251 0 0.4251 203.3 C2 1 G
444024 TRVLM 400.00 444001 SRPRMBDR 400.00 1 85.04 0.47197 0.235985 0 0.235985 159.5 B1 3 E
444024 TRVLM 400.00 444007 KVPATTU 400.00 1 113.92 0.63226 0.31613 0 0.31613 90.8 B2 5 C
444024 TRVLM 400.00 444007 KVPATTU 400.00 2 113.92 0.63226 0.31613 0 0.31613 90.8 B1 2 F
444028 TUTCRNPS 400.00 444010 CHKNRANI 400.00 1 94.8 0.69394 0.34697 0 0.34697 672.8 D 3 B
Annexure-VII
10 of 11
444028 TUTCRNPS 400.00 444010 CHKNRANI 400.00 2 94.8 0.69394 0.34697 0 0.34697 672.8 B1 1 E
444028 TUTCRNPS 400.00 444021 TUTCRNJV 400.00 1 61.58 0.45077 0.225385 0 0.225385 -643.1 B2 2 C
444028 TUTCRNPS 400.00 444023 CENERGY 400.00 1 13 0.26388 0.13194 0 0.13194 -702.5 A 4 A
444029 TNVL-TIE 400.00 444010 CHKNRANI 400.00 1 161.7 0.89744 0.44872 0 0.44872 -1.6 B1 1 B
444029 TNVL-TIE 400.00 444017 KKNPP 400.00 1 72 0.52776 0.26388 0 0.26388 1.6 A 2 A
444030 KAYATHAR 400.00 444012 KRAIKUDI 400.00 1 195 1.42935 0.714675 -0.5713 0.143375 -15.3 A 2 B
444030 KAYATHAR 400.00 444012 KRAIKUDI 400.00 2 195 1.42935 0.714675 -0.5713 0.143375 -15.3 D 1 D
444031 TRVLM-TN 400.00 444002 ALAMATTY 400.00 1 112.3 0.67605 0.338025 0 0.338025 -50.2 3 B
444031 TRVLM-TN 400.00 444002 ALAMATTY 400.00 2 112.3 0.67605 0.338025 0 0.338025 -50.2 2 C
444031 TRVLM-TN 400.00 444020 METR-III 400.00 1 270 1.9764 0.9882 -0.5714 0.4168 315.4 4 A
444031 TRVLM-TN 400.00 444020 METR-III 400.00 2 270 1.9764 0.9882 -0.5714 0.4168 315.4 1 D
444032 ILFS 400.00 444034 NGPTNMPS 400.00 1 13.94 0.33818 0.16909 0 0.16909 270 A 2 A
444032 ILFS 400.00 444034 NGPTNMPS 400.00 2 13.94 0.33818 0.16909 0 0.16909 270 C1 1 C
444034 NGPTNMPS 400.00 444009 ALUNDUR 400.00 1 160.07 0.88078 0.44039 0 0.44039 278.4 A 4 C
444034 NGPTNMPS 400.00 444009 ALUNDUR 400.00 2 160.07 0.88078 0.44039 0 0.44039 278.4 D 1 G
444034 NGPTNMPS 400.00 444013 NLC1EXP 400.00 1 57.1 0.31594 0.15797 0 0.15797 -51 A 3 D
444034 NGPTNMPS 400.00 444014 NLC2 400.00 1 56.92 0.27315 0.136575 0 0.136575 33.5 D 5 B
444034 NGPTNMPS 400.00 444032 ILFS 400.00 1 13.94 0.33818 0.16909 0 0.16909 -269.7 A 6 A
444034 NGPTNMPS 400.00 444032 ILFS 400.00 2 13.94 0.33818 0.16909 0 0.16909 -269.7 C1 2 E
454001 TRICHUR 400.00 454004 COCHIN 400.00 1 78.2 0.5783 0.28915 0 0.28915 22.6 A 3 B
454001 TRICHUR 400.00 454004 COCHIN 400.00 2 78.2 0.5783 0.28915 0 0.28915 22.6 D 1 E
454001 TRICHUR 400.00 454005 PALAKD 400.00 1 90 0.4995 0.24975 0 0.24975 -245.1 A 4 A
454001 TRICHUR 400.00 454005 PALAKD 400.00 2 90 0.4995 0.24975 0 0.24975 -245.1 C1 2 C
454002 TRIVNDRM 400.00 444005 TRNLVLLI 400.00 1 160.4 0.89022 0.44511 0 0.44511 -229.3 A 4 A
454002 TRIVNDRM 400.00 444005 TRNLVLLI 400.00 2 160.4 0.89022 0.44511 0 0.44511 -229.3 D 1 E
454004 COCHIN 400.00 454001 TRICHUR 400.00 1 78.2 0.5783 0.28915 0 0.28915 -22.6 D 3 B
454004 COCHIN 400.00 454001 TRICHUR 400.00 2 78.2 0.5783 0.28915 0 0.28915 -22.6 B2 2 C
454005 PALAKD 400.00 444004 MYWADI 400.00 1 90 0.4995 0.24975 0 0.24975 -421.4 A 4 A
454005 PALAKD 400.00 444004 MYWADI 400.00 2 90 0.4995 0.24975 0 0.24975 -421.4 B2 2 C
454005 PALAKD 400.00 454001 TRICHUR 400.00 1 90 0.4995 0.24975 0 0.24975 246.2 A 3 B
454005 PALAKD 400.00 454001 TRICHUR 400.00 2 90 0.4995 0.24975 0 0.24975 246.2 D 1 E
454008 KOZKODE 400.00 434020 MYSORE 400.00 1 203 1.12667 0.563335 -0.5714 -0.008065 -124.9 A 2 A
454008 KOZKODE 400.00 434020 MYSORE 400.00 2 203 1.12667 0.563335 -0.5714 -0.008065 -124.9 D 1 E
464001 PONDY 400.00 444014 NLC2 400.00 1 67.88 0.2775 0.13875 0 0.13875 -339.7 B1 2 B
464001 PONDY 400.00 444018 SVCHTRM 400.00 1 136.42 0.0535 0.02675 0 0.02675 -58.2 C1 1 D
Annexure-VII
11 of 11
Page 1 of 61
FileNo: SRPC/SE-III/PMS/2016/
TENDER DOCUMENT
FOR
Creation and maintaining a web based Protection Database
and desktop based Protection settings calculation tool for
Southern Regional Grid
Last Date of Receipt of Bids AAAAA up to 14:00 Hrs
Date of Tender Opening AAAAA at 14:30 Hrs
Annexure-VIII
Page 2 of 61
No- SRPC/SE-III/PMS/2016/BBBBB Dated-CCCCC
Notice Inviting Quotations for Creation and maintenance of web based Protection Database and
desktop based Protection Settings Calculation tool for Southern Regional Grid
Sealed quotations/ offers are invited on behalf of SRPC Constituents from eligible and reputed agency for
providing services for implementation of “Creation and maintenance of web based Protection Database and
desktop based Protection Settings Calculation tool for Southern Regional Grid” under Single Stage-two
packet/envelope system.
The validity of the offer should be at least 90 days from the date of opening of this tender. The
technical bid and Price bids shall be enclosed in separate sealed envelopes marked with Tender Reference,
Tender Id “Technical/Price bid”as applicable and Tender Name. EMD and copy of receipt of tender fees paid
shall be provided in the Technical bid envelope.
Technical bid envelope and price bid envelope should been enclosed in a separate sealed envelope
superscripted Tender ID, Tender Reference and Tender Name, date and time of opening.
Sealed tenders must reach SRPC not later than AAAAA at 14:00 hrs at the following address:
Member Secretary,
Southern Regional Power Committee,
Central Electricity Authority,
No. 29, Race Course Cross Road
Bengaluru - 560 009
(S. R. BHAT)
Member Secretary
Annexure-VIII
Page 3 of 61
TENDER SCHEDULE:
Tender Name
Creation and maintenance of web based
Protection Database and desktop based
Protection Settings Calculation tool for Southern
Regional Grid.
Tender Reference
Tender Id
SRPC/SE-III/PMS/2016/BBBBB Dated: CCCCC
DDDDD
Type of Tender Single Stage-Two Packet/Envelope System
Last Date and Time for receipt of
sealed tender offers
AAAAA (14:00 Hrs.) (In case this date is declared a
public holiday then the next working day shall be the last
date)
Time and Date of Opening of
sealed technical bids
AAAAA (14:30 Hrs) (In case this date is declared a public
holiday then the next working day shall be the tender
opening date)
Time and Date of Opening of
sealed financial bids To be intimated in due course.
Place of Opening tender offers SRPC, Bangalore
Address of Communication
S R Bhat, Member Secretary,
Southern Regional Power Committee,
Central Electricity Authority,
#29, Race Course Cross Road,
Bengaluru – 560 009
Email:[email protected]
Email:[email protected]
Contact Telephone Numbers
Website
Phone: 080-22259343, 22287205, 22282516
http://www.srpc.kar.nic.in
Annexure-VIII
Page 4 of 61
SECTION A: DEFINITIONS AND ABBREVIATIONS
The following words and expressions shall have the meanings hereby assigned to them:
(a) “Act” shall mean the Electricity Act 2003 unless otherwise specified.
(b) “Agency” shall mean the bidder
(c) "Applicable Law" means the laws and any other instruments having the force of law in India, as they may be issued
and in force from time to time; (d) “Bank” or “Banks”, refers to all scheduled Indian Banks as per the RBI current list (Schedule-II) (e) “Buyer” means the Purchaser calling for BID
(f) “Contract” means the Agreement entered into between the Purchaser and the Agency, together with the Contract
Documents referred to therein, including all attachments, appendices, annexure and all documents incorporated by
reference therein. (g) “Contract Documents” shall mean the following documents listed, including any amendments thereto be read and
construed as part of this Agreement, viz.:
i. All provisions of Tender vide Reference No: SRPC/SE-III/ PMS/ 2016/BBBBB dated CCCCC, Tender ID- DDDDD Tender Name: Creation and maintenance of web based Protection Database and desktop based Protection Settings Calculation tool for Southern Regional Grid including all Annexures/Appendices;
ii. Vendor’s response (proposal) to the NIQ, including the Bid Submission Sheet and the Price Schedules
Cost of Bid Document
Rs.XXXXX/- (Rupess XXXXX in words only) by
demand draft/bankers cheque on a scheduled
commercial bank in favour of “SRPC
Establishment Fund”. Document can be
downloaded for viewing only from,
www.srpc.kar.nic.in, www.eprocure.gov.in,
www.tenders.gov.in
Last date for Purchase of Bid
Documents EEEEE at 15:00 hrs.
EMD
Rs. XXXXX/- (Rupees XXXXX in words only)
payable as A/c payee Demand draft on any
scheduled commercial Indian bank in favor of
“SRPC Establishment Fund”.
Tender Submission mode Manual/post or by courier at SRPC, No. 29, Race Course
Cross Road, Bangalore - 560 009
Tender Value (Ex-Taxes) Rs. XXXXX/- (Rupees XXXXX in words only)
Annexure-VIII
Page 5 of 61
submitted by the Supplier; iii. The Purchaser’s Notification to the Supplier for Letter of Intent;
iv. Acceptance of purchaser’s notification v. The Purchaser’s Notification to the Supplier for Letter of Award;
(h) “Contract Price” means the price payable to the Supplier as specified in the Agreement, subject to such adjustments
thereto, as may be made pursuant to the Contract. (i) “Day” means calendar day. (j) “Delivery” means the transfer of the Goods and/or Services from the Supplier to the Purchaser in accordance with the
terms and conditions set forth in the Contract.
(k) “Completion” shall mean the completion of the Related Services by the Supplier in accordance with the terms and
conditions set forth in the Contract.
(l) "Effective Date" means the date on which this Contract comes into force and effect pursuant to Clause 8 of GCC; (m) “SRPC” Shall mean Southern Regional Power Committee with responsibilities and functions as provided in the Act.
(n) “GCC” mean the General Conditions of Contract.
(o) “Goods” means all hardware, software, networking equipment and/or other equipment accessories and materials
that the Supplier is required to supply to the Purchaser under the Contract. (p) “Go Live” means the date from which the project is implemented with all functionality as envisaged in the scope of
work. Thereafter, support period shall begin.
(q) “Government” means the Government of India or any state government of India unless the context implies
otherwise.
(r) “Intellectual Property Rights” means any patent, copyright, trademark, trade name, service marks, brands, propriety
information, whether arising before or after the execution of this Contract and the right to ownership and registration of
these rights (s) "Party" means the Purchaser or the Agency, as the case may be;
(t) “Personnel" means persons hired by the Agency as employees and assigned to the performance of the Services or any
part thereof; "Foreign Personnel" means such persons who at the time of being so hired had their domicile outside the
Government's country; and "Local Personnel" means such persons who at the time of being so hired had their domicile
inside the Government's country; (u) "Project" means all Activities covered under present contract
(v) “Purchaser’s Country” shall mean India.
(w) “Purchaser” means the SRPC. It has been used to mean Owner or Purchaser in this document.
(x) “Related Services” means the services to be provided as per the requirements / conditions specified in the Contract.
In addition to this, the definition would also include other related/ancillary services that may be required to execute this
Contract. (y) “RPC” shall mean Regional Power Committee
(z) "Starting Date" means the date referred to in Clause 8 of GCC;
Annexure-VIII
Page 6 of 61
(aa) "Services" means the work to be performed by the Agency pursuant to this Contract for the purposes of the Project,
as described in the Scope of Work hereto; (bb) “Subcontractor” means any natural person, private or government entity, or a combination of the above, including its
legal successors or permitted assigns, to whom any part of the Goods to be supplied or execution of any part of the
Services is subcontracted by the Supplier. Agency shall not sub-contract any part of its obligation under the present
contract. (cc) “Supplier” means the natural person, private or government entity, or a combination of the above, whose bid to
perform the Contract has been accepted by the Purchaser and is named as such in the Agreement, and includes the legal
successors or permitted assigns of the Supplier. Supplier has been used to mean Agency in this document. (dd) “The MoP” is the Ministry of Power, Government of India.
(ee) “The Site,” shall mean all identified locations within the SRPC jurisdiction, where the Supplier carries out any
installation of Goods or is required to provide any Services. (ff) "Third Party" means any person or entity other than the Government, the Purchaser, the Agency or any other party
as implied by the usage and context
(gg) “OEM” means the Original Equipment Manufacturer of any equipment / system / software / product. (hh) “Owner” means the “Purchaser” calling for BID
(ii) “in writing” means communicated in written form with proof of receipt
Annexure-VIII
Page 7 of 61
SECTION B: INTRODUCTION
SRPC Secretariat on behalf of all the constituents of Southern Region requires the services of eligible and well qualified Firms/agencies for Creation and maintenance of web based Protection Database and desktop based Protection Settings Calculation tool for Southern Regional Grid. The detailed scope of the project is at Section-E.
The work shall broadly include the following deliverables which are detailed subsequently:
Database building activities Protection Setting Calculation Tool Protection Database Management System The vendor should develop and maintain a hardware setup and software package capable of meeting
the following objectives; but not limited to:
Classified database of all bay equipment and the protection system details of all bays 220kV/230kV and above for Southern Regional power system
A user friendly interface for browsing and editing the contents of the database
Tool for simulating the performance/ behavior of the protection system under all possible normal and abnormal operating conditions of the power system, including effect of changing one or more parameter setting of the relays
Diagnostics for verifying proper coordination among various protective relays
Generation of useful reports Five-Year Support Period
Need for implementation:
Southern Regional Grid comprises the electrical system of the states of Andhra Pradesh, Karnataka, Kerala, Tamil Nadu, Telangana and Union Territory of Pondicherry. System security is a critical element of power system operations and management. Having an updated information system including an up to date web based protection database and the ability to remotely run various relevant studies on it, is necessary to ensure that the protective relays will function correctly with proper discrimination to provide the requisite reliable, sensitive and selective isolation of faulty power system equipment. The ‘Task Force on Power System Analysis under Contingencies’ constituted in December 2012 on the backdrop of the 30-31.07.2012 black outs strongly recommended creation & maintenance of protection data base under RPCs. In various Protection Co-ordination Sub- Committee (PCSC) meetings of SRPC, it was also felt that a protection data base for transmission system of Southern Region is urgently needed. This tender is being called to implement the protection database system in SRPC.
Objective:
1. To build the centralized web based Protection database of the Southern region transmission system and
continuously update the same
2. To create facility to store all types of relay settings in one system irrespective of the manufacturer
3. To capture the life cycle of protection settings and template
4. To create an interface with Relay Setting Calculation engine and compute the relay settings (distance,
over current, Generator/EF/unit protection, etc...) for the different operating conditions.
5. Perform of post-mortem analysis of the faults/disturbances in the region in a quicker time as most of the
information is centrally available.
6. Establishing the system which is remotely accessible to common stake holders and having transparency
of operation.
7. To create a system where there is a provision of hierarchical Role based access control and have
reporting procedures.
Annexure-VIII
Page 8 of 61
SECTION C: Instruction to Bidders
1. The Address for all communication with the purchaser shall be Member Secretary, SRPC, Bengaluru.
2. Request for clarifications if any with regard to the provisions of NIQ may be forwarded to the mssrpc-
[email protected] and [email protected] by FFFFF 15:00 Hrs.
3. Single Stage – Two Envelope Procedure: Bidders should submit two sealed envelopes simultaneously,
one containing the Technical Proposal and the other the Price Proposal, enclosed together in an outer
single envelope. The envelopes should be superscripted with Tender Name, Tender Id, Tender Reference,
Technical bid/Price bid as applicable and date and time of opening of tender.
4. Constituents: Constituent for this tender shall mean the electrical systems of the electricity utilities of the
states of Andhra Pradesh, Telangana, Karnataka, Kerala, Tamil Nadu, and Union Territory of
Puducherry, NTPC, NPCIL and NLC generating Stations of SR and PGCIL Southern regional transmission
system, SRLDC and SRPC.
5. Project completion time: scheduled implementation of all functionality as per the scope of works shall be
18 months from date of award. Thereafter there shall be a support period of 5 years from the date of Go
Live. In case services are required beyond support period the same shall be with mutual agreement
between buyer and agency.
6. Exchange Rate: For any financial figure in other than Indian rupees the exchange rate as on the date of transaction shall be considered for conversion to Indian rupee value.
7. Milestones for the project shall be as under (all from date of award): a. Submission of High level design documents for the protection software implementation:
one month from issue of letter of Award b. Delivery of 35 No base license of protection calculation engine: 2 months from
acceptance of High level design document c. Completion of Training program on the protection setting calculation software, building
the network data for load flow and fault calculation: 15 months d. Protection database and substation SLD preparation for protection study: 2 months e. Delivery of required hardware: 2 months f. Delivery of web based database management system: 2 months g. Site Acceptance Test(SAT) with one pilot state system: 6 months h. Go live with all SRPC constituent data: last 1 month i. Continuation of support activities: up to 5 years from Go Live.
8. Cancellation of contract: The period of contract is subject to cancellation of appointment due to any of
the reasons mentioned hereunder.
• If the Agency is found to have submitted false particulars / fake documents for securing empanelment as Agency or for the award of assignment.
• The Agency’s performance on the job will be constantly monitored for quality, commitment to
delivery period mentioned in contract with the Purchaser, adherence to the guidelines, Statutory regulations, Conduct / Discipline etc., while executing jobs. Any deviations from stated conditions can lead to appropriate deterrent action as deemed fit by Purchaser.
• If the Agency refuses to execute the job at his agreed scope/quoted rates, after the purchaser issue the letter of intent (LoI)
• Manipulation of rates by cartelization shall be viewed very seriously by the Purchaser. If such a situation comes to the notice of the Purchaser and/or there are reasons / circumstances for the Purchaser to believe so, the concerned Agency will be called in to give justification of proposal/rates quoted by them. If they are not able to give a proper or satisfactory justification of their quoted proposal/rates, their appointment is liable to be cancelled.
• Any other reason deemed fit by the competent authority/purchaser for cancellation • Such Agency’s, whose appointment is cancelled due to any of the above reasons, will not be
considered for subsequent assignments for a period of Five years.
9. Language of BID: The language of the bid shall be English
Annexure-VIII
Page 9 of 61
10. Number of Copies of BID: Two nos of Hardcopies (one marked as “original” and one marked as “Copy”
and 1 Softcopy in CD should be submitted. Each technical proposal should be marked "Original" or "Copy" as appropriate. If there are any discrepancies between the original and the copies of the Proposal, the original governs. In the event of any discrepancy between the hard copy and soft copy, the hard copy shall prevail.
11. Purchase of BID:A demand draft amounting to INR Rs XXXXX/- ( Rupees XXXXX in words only) in favor of “SRPC Establishment Fund” payable at Bangalore as cost of the printing, binding, etc. of the document shall be furnished at the time of purchase of document and receipt enclosed in Technical Bid envelope.
12. Eligible Bidders: Bidders must be registered under Indian business laws. The entire work has to be
undertaken by a single agency. No consortium/ Joint Venture/Association or outsourcing shall be allowed.
13. Conflict Of Interest: The Purchaser considers a conflict of interest to be a situation in which a party has interests that could improperly influence that party’s performance of official duties or responsibilities, contractual obligations, or compliance with applicable laws and regulations, and that such conflict of interest may contribute to or constitute a prohibited corrupt practice. This may include but not limited to circumstances leading to:-
Relationship with Purchaser’s staff: Agency’s (including their personnel) that have a business or family relationship with a member of the Purchaser’s staff who are directly or indirectly involved in any part of: (i) the preparation of the TOR of the contract, (ii) the selection process for such contract, or (iii) supervision of such contract may not be awarded a contract, unless the conflict stemming from this relationship has been resolved in a manner acceptable to the purchaser throughout the selection process and the execution of the contract.
14. Subcontracting: The Agency shall not be permitted to sub-contract any part of its obligations under the
Contract with the purchaser.
15. Corrigendum: Should the Purchaser deem it necessary to amend the BID Document, it shall do so by
uploading the corrigendum in the website(s). At any time prior to the deadline for submission of the BID,
the Purchaser may amend the BID Document by issuing corrigenda. In order to provide prospective
Bidders reasonable time in which to take the amendment into account in preparing their bids, the
Purchaser may, at its discretion, extend the last date for the receipt of BIDs. Any corrigendum issued shall
be part of the BID Document and shall be communicated in writing through registered letter and/ or
Email to all who have obtained the BID Document directly from the Purchaser.
16. Cost of preparation of BID: The Bidder shall bear all costs associated with the preparation and submission
of its BID and the Purchaser shall not be responsible or liable for those costs, regardless of the conduct or outcome of the BID process.
17. Submission of BID: The Bidder shall submit the BID using the appropriate Submission Sheets provided in
the Annexures. These forms must be completed without any alterations to their format, and no substitutes shall be accepted. All blank spaces shall be filled in with the information requested.
18. BID Opening: The Purchaser shall conduct the opening of BIDs in the presence of Bidders‟
representatives who choose to attend, at the address, date and time specified in this document. All other envelopes holding the BID shall be opened one at a time, and the following read out and recorded:
(a) the name of the Bidder; (b) any other details as the Purchaser may consider appropriate.
Only BIDs read out and recorded at opening stage shall be considered for evaluation. Late bids or bids not accompanied with proof of having purchased the document shall be rejected out rightly. Bids shall be
Annexure-VIII
Page 10 of 61
opened at SRPC, Bangalore.
19. Rights of Use: All rights of use of any process, product, service or facility developed or any other task
performed by the Agency during execution of the engagement for the Purchaser would lie exclusively with the Purchaser in perpetuity free from all liens, encumbrances and other third party rights and the Agency shall, wherever required, take all steps that may be necessary to ensure the transfer of such ownership in favor of the Purchaser.
20. Intellectual Property: The purchaser shall own and have a right in perpetuity to use all newly created
Intellectual Property Rights which have been developed solely during execution of the contract, including
all templates, reports, designs, records, application configurations, data and written material,
specifications, drawings and other documents which have been newly created and developed by the
Agency solely during the performance of Related Services and for the purposes of inter-alia use or sub-
license of such Services under this Contract. The Agency should undertake to disclose all such Intellectual
Property Rights arising in performance of the Related Services to the Purchaser and execute all such
agreements/documents and file all relevant applications, effect transfers and obtain all permits and
approvals that may be necessary in this regard to effectively transfer and conserve the Intellectual
Property Rights of the Purchaser. To the extent that Intellectual Property Rights are unable by law to so
vest, the Agency assigns those Intellectual Property Rights to Purchaser on creation.
The Agency shall be obliged to ensure that all approvals, registrations, licenses, permits and rights etc. which are inter-alia necessary for use of the goods supplied / service provided by the Agency, the same shall be acquired in the name of the Purchaser, and the same may be assigned by the Purchaser to the Agency solely for the purpose of execution of any of its obligations under the terms of the Contract. However, subsequent to the term of the Contract, such approvals, registrations, licenses, permits and rights etc. shall endure to the exclusive benefit of the Purchaser. The Agency shall ensure that while it uses any software, hardware, processes, document or material in the course of performing the Services, it does not infringe the Intellectual Property Rights of any person and the Agency shall keep the Purchaser indemnified against all costs, expenses and liabilities howsoever, arising out of any illegal or unauthorized use (piracy) or in connection with any claim or proceedings relating to any breach or violation of any permission/license terms or infringement of any Intellectual Property Rights by the Agency or its personnel during the course of performance of the Related Services. In case of any infringement by the Agency, the Agency shall have sole control of the defence and all related settlement negotiations. Subject to above sub-clauses on intellectual property, the Agency shall retain exclusive ownership of all methods, concepts, algorithms, trade secrets, software documentation, other intellectual property or other information belonging to the Agency that existed before the effective date of the contract.
21. Area of Work: The Agency may be required to work anywhere in the state or union territory of India
within the concerned area of the Purchaser.
22. Confidentiality: The Agency and the personnel of any of them shall not either during the term or within
two (2) years after the expiration of this contract, disclose any proprietary or confidential information relating to the Project, the Services, this Contract or the Owner’s business or operations without the prior written consent of the owner. Purchaser will ensure confidentiality of the bids submitted.
23. Bid Security / Earnest Money Deposit (EMD): The Bidder shall furnish as part of its Technical Proposal, a
Bid Security in original form and in the amount and currency specified below. The EMD shall be payable in form of Demand Draft in favor of “SRPC Establishment Fund” payable at Bangalore drawn on any scheduled commercial bank. Earnest Money Deposit for the tender shall be Rs. XXXXX (Rupees XXXXX in words only). Earnest Money will not fetch any interest. The EMD made by the bidder will be forfeited if:
i. The bidder withdraws his tender before processing of the same. ii. The bidder withdraws his tender after processing but before acceptance of “Letter of award”
issued by SRPC. iii. The selected bidder withdraws his tender before furnishing an unconditional and irrevocable
Performance Security Deposit.
Annexure-VIII
Page 11 of 61
iv. The bidder violates any of the provisions of the terms and conditions of this tender specification.
The EMD will be refunded subject to:
i. To the successful bidder, only after furnishing an unconditional and irrevocable Performance Security Deposit for 5% of the contract price.
ii. To the successful bidder if for any reasons beyond the control of the purchaser, the purchaser fails to award LOI within one month of the date of acceptance of tender by the agency.
iii. To the unsuccessful bidders, after acceptance of the “Letter of Award” by the selected bidder.
24. Price Offer:The Bidder may provide ONLY ONE Price bid. In case of more than one price bid, the submission will be considered non-responsive. Prices will be firm and inclusive of all cost minus taxes and no change alternate/conditional price offers shall be allowed. The price offer shall be firm and no escalation would be allowed
25. Performance Security: Within twenty-eight (28) days of the issue of Letter of Intent from the Purchaser,
the successful Bidder shall furnish the Performance Security in accordance as provided below. The value
of Performance Security would be 5% of the bid value/contract price.
The successful bidder will have to furnish a Performance Security Guarantee Deposit @ 5% of the bid
value/contract price in form of an irrevocable bank guarantee as per format at Annexure G from a
scheduled commercial bank within 28 days after the issue of Letter of Intent (LoI).
This guarantee will be for faithful performance of the contract in accordance with the terms and
conditions and technical specification specified in the contract bid documents. The purchaser shall be at
liberty to deduct appropriately from the Performance Security Deposit such sums as are due and payable
to the agency by purchaser as may be determined in terms of the contract.
The performance guarantee shall remain valid for a period of 60 days beyond the support period of five
years from the date of project ‘go live’ and shall be renewed for a further period, if required so by the
purchaser. Performance Security Guarantee in form of bank guarantee will be discharged and returned
to the successful bidder after satisfactory performance of all the terms and conditions of contract.
26. Bid Validity Period: Bid should be valid for a period of 90 days from the date of opening of proposal.
27. Acceptable Banks: All bank related documents should be submitted only from a bank listed in Schedule-2 of Reserve Bank of India (RBI).
28. Currency of Contract: The currency of contract shall be Indian Rupees only.
29. SRPC shall mean the Southern Regional Power Committee as defined under the Electricity Act, 2003 and
having its secretariat at No. 29, Race Course Cross Road, Bangalore - 560 009and headed by Member Secretary.
30. The website of SRPC is at www.srpc.kar.nic.in
31. Purchaser/owner shall mean the SRPC.
32. The competent Authority for this Tender shall be The Member Secretary, SRPC.
33. The competent Authority reserves to cancel this tender without assigning any reason whatever.
34. Part bids, incomplete bids will not be accepted. No part of this tender may be outsourced under any circumstances.
Annexure-VIII
Page 12 of 61
35. The competent authority reserves the right to postpone and/or extend the date of receipt of tender or to withdraw the tender notice without assigning any reasons thereof. In such an event, bidders shall not be entitled to any compensation, in any form whatsoever.
36. Terms and Conditions described in this NIQ shall be binding on all bidders. 37. All entries in the tender forms should be legible and filled clearly. If the space for furnishing information
is insufficient, a separate sheet duly signed by the authorized signatory may be attached. 38. Each page of this tender document/NIQ should be signed by the bidder or by the authorized signatories
with seal of the agency and require to be enclosed with the technical bid. Signing each page of this document will be implied as its acceptance in unequivocal manner with clear understanding and interpretations.
39. All pages in technical and commercial bid/response documents shall be stamped with the official company seal and duly signed by the authorized signatory.
40. The offer shall be of single stage-two packet/envelope type, containing Technical and Price offers. Two separate sealed envelopes containing the Technical and Price offers separately should be enclosed together in a large envelop, sealed and superscripted with the Tender Reference Number, Tender ID, Tender Name, Name and address of the Bidder. Tender Offer without separate envelops for technical offer and price offer will be rejected outright.
41. Even if the tender document is downloaded from the website, the tender must necessarily be purchased by the last date of purchase of bid documents.
42. Late bids: Any bid received by courier/post/by hand after the deadline for submission of bids prescribed, shall not be accepted.
43. The envelope shall be sealed by signing across all joints & pasting good quality transparent adhesive tape on top of such joints & signatures with company seal. Proposals sent through telex/telegrams/fax/e-mail shall not be accepted. SRPC shall not be responsible for delay on account of delivery by the postal authorities as well as courier companies. Such delivery shall be at the risk and cost of the bidder. If the envelopes are not sealed and marked as required above, SRPC shall assume no responsibility for the proposal’s misplacement or premature opening.
44. Bidder is expected to examine all instructions, forms, terms and requirement in the bid document. The invitation to bid together with all its attachment thereto shall be considered to be read, understood and accepted by the bidder in full and binding manner. Failure to furnish all information required by the bid document or a bid not substantially responsive to the bid document in every respect may result in rejection of the bid.
45. The language of the bid shall be English. All documents enclosed should also be in English language. In case the original document is in a different language, a certified true translation in English language must be furnished, in which case, for purposes of interpretation of the bid, the translation shall govern. All such translated documents should bear the signature and stamp of the authorized signatory of the bidder signing the document, as a token of authentication of the same.
46. The bidders will have to accept unconditionally all the Terms and Conditions of NIT along with an undertaking in support of the authenticity of the declarations regarding the facts, figures, information and documents furnished by the Bidder in order to become an eligible bidder. Conditional bids against the terms of the bid may be rejected upon sole discretion of purchaser.
47. Based on undertaking furnished by the bidder, as per format given at Annexure-E, certifying the authenticity and statement made in the bid,If any information or document submitted by the bidder is found to be false/incorrect, the offer shall be considered absolutely null and void and penal action as deemed fit shall be taken against the bidder which may include termination of contract / forfeiture of all dues including EMD/ Security Deposit / banning of the firm along with all partners of the firm as per provisions of law. Further, suitable action shall be taken for claiming damages from the bidder.
48. SRPC reserves the right to accept or reject any or all offers in part or not to make any procurement against this tender, without assigning any reasons. No dispute of any kind can be raised against this right of the SRPC in any court of law or elsewhere.
49. No deviation from the terms and conditions mentioned in this tender shall be accepted.
50. The purchaser shall be entitled and it shall be lawful on his part to forfeit the amount of Performance Security in whole or in part in the event of any default, failure or neglect on part of the agency in
Annexure-VIII
Page 13 of 61
fulfillment or performance of the contract under reference in all respects to the satisfaction of the purchaser. The purchaser shall be entitled to deduct from the amount of Performance Security any loss or damage which the purchaser may suffer due to any act or default of the Agency as per stipulations of the contract.
51. In the event of termination of agreement for any reasons, or in the event the successful bidder is discharged of its obligations clauses 36-39 of GCC shall be applicable
52. Tender documents are not transferable. Bidders must buy the tender documents in their own name.
53. A tender offer determined as not substantially responsive will be rejected by the purchaser and the price
bid for such Bidder will not be opened.
54. The Purchaser may waive any minor infirmity or irregularity in a Tender offer, which does not constitute a material deviation. This shall be binding on all Bidders and the Purchaser reserves the right of such waivers.
55. After award and before starting of work the selected agency shall give a presentation detailing the proposed architecture and their work plan, support services required and deliverables.
56. The Bidder will be responsible for sizing the hardware to support the scalability and performance requirements of the protection database application. The Bidder shall ensure that the servers are sized adequately and redundancy is built into the architecture required to meet the service levels mentioned in the NIQ.
57. The IT Infrastructure proposed should be compatible with infrastructure at SRPC and constituents. 58. The Bidder will be responsible for providing all the details of the Bill of Material (BoM) and specifications
of the IT Infrastructure proposed, specifications of the system software, all other equipment proposed as part of its Technical Proposal. The price quote submitted by the Bidder should include costs for these.
59. After completion of the 5-year support period the successful agency will provide a proposal for AMC which may be accepted /declined by the purchaser.
SECTION D: SCHEDULE OF REQUIREMENTS
1. Deliverables: j. High level design documents for the protection software implementation. k. Web based database management tool-1 License l. Protection calculation & Analysis tool with laptop computers - 35 Licenses m. User Manuals- 35 sets n. Associated servers for installation and Deployment of application and database software
along with standard Operating System -8 Nos. (communication is excluded in the scope) o. Training for 5 days at SRPC/SRLDC premise and 5 days at each Constituent premise
including printed reading material/soft files. p. 5 year comprehensive Support including incorporation of any new network configuration,
addition of new substation, change of relays, settings, CT/PT, support for database software, web access and various analysis engines.
2. Minimum Hardware BOQ and Specifications:
Sl No Hardware Description Qty Required
1
Application server with following configuration: Quad Core 3.06 GHz X 2, 64 GB RAM, 500 GB HDD, 4 USB port, 18.5” monitor supporting 1024 X 1024, Standard Key Board & Mouse, Windows Server 2012 R2 Operating System
2 No
Main and backup
2
Database server with following configuration: Quad Core 3.06 GHz X 2, 64/128 GB RAM, 1 TB HDD, 4 USB port, 18.5” monitor supporting 1024 X 1024, Standard Key Board & Mouse, Windows Server 2012 R2 Operating System
2 No
Main and backup
Annexure-VIII
Page 14 of 61
3
Database Historian server with following configuration: Quad Core 3.06 GHz X 2, 64 GB RAM, 8 TB HDD, 4 USB port, 18.5” monitor supporting 1024 X 1024, Standard Key Board & Mouse, Windows Server 2012 R2 Operating System,
2 No
4
Web server: Quad Core 3.06 GHz X 2, 64 GB RAM, 500 GB HDD, 4 USB port, 18.5” monitor supporting 1024 X 1024, Standard Key Board & Mouse, Windows Server 2012 R2 Operating System
2 No
5 The database license with Oracle 11G and above. Enterprise
license.
6
Laptop systems (intel core i5-4210U processor 4GB RAM 500 GB HDD, 14’ LED, Win 8 Pro, Minimum 2 USB Ports) along with three year Antivirus for the SRPC constituent member for installation of protection setting calculation tool
35 No Total
7 Protection setting calculation tool to be installed in the laptop
35 Licenses
8 Web based database management tool 1 License
9. Hardware and Software Firewall As applicable
10. Support for the period for the components supplied including hardware and software.
As detailed in E.5
SECTION E: DETAILED SCOPE OF WORK
Bidder should supply Protection Analysis Software Package with following requirements but not limited to the
following modules for the supply of Software and Database building activities:-
Broad scope of supply includes following.
1. Database building activities
2. Protection Setting Calculation Tool
3. Protection Database Management System
4. The vendor should develop and maintain a hardware setup and software package capable of meeting the
following objectives; but not limited to:
Classified database of all bay equipment and the protection system details of all bays 220kV/230kV and
above for Southern Regional power system
A user friendly interface for browsing and editing the contents of the database
Tool for simulating the performance/ behavior of the protection system under all possible normal and
abnormal operating conditions of the power system, including effect of changing one or more parameter
setting of the relays
Diagnostics for verifying proper coordination among various protective relays
Generation of useful reports
5. Five Year Support Period
E.1 Database building activities:
One time power system network model building for the Load-flow, Short circuit and dynamic simulations of entire Southern region with Indian national grid transmission network model.
Data collected from respective substations to be validated before populating the same in the database.
Annexure-VIII
Page 15 of 61
Complete modeling of SR transmission network for 220 kV/ 230 kV and above including HVDC systems connected with SR, with relevant system parameters collecting from the field like transmission lines, generators, transformers, reactors, substation layouts, and associated protective relays in the substations. The model should include CT, PT, Isolator, Breaker and other bay equipment’s ratings along with rating of the BUS and the type of conductor used for the BUS. The modeling should be done as per bus-breaker philosophy instead if node oriented model.
Building of network Database and populations of relay data for all existing substations of 220 kV / 230 kV and above voltage level, of Southern region including Generating station switchyards as well as the Generators.
Prepared network should be ready for base case load flow analysis and the same has to be verified with field engineers of SR constituents. Both MW and MVAR flow should be computed and Voltage Level at different Buses should be ascertained along with suggestive conditions to reduce or enhance Bus voltage.
Short circuit, transient stability and contingency analysis have to be simulated and the results have to be demonstrated to the SR constituents for approval. There should be features to study low frequency oscillations, 3
rd zone tripping, PSS tuning support and Voltage collapse prediction feature.
Transient stability and grid disturbance simulation studies for the southern region database and performing the com-trade file analysis.
Over current and distance relay coordination settings have to be calculated and coordination curves should match the existing protection schemes of the substations. Some critical contingencies have to be discussed with SR constituents and the same has to be simulated and results to be demonstrated.
Computation of critical clearing time for the most of the voltage level and critical stations.
Review of the unit protection like Generators, GT’S, Unit transformers, Station transformers), ICTs, Main power transformers, Reactors, Dynamic and Static Compensators, bus-bars and other differential protection relays.
Following are estimated details of the existing sub-station in the SRPC region and same should be modeled in the software with all details. However, actual number may vary within close limits and has to be considered by the bidder in his proposal.
No. of 765 kV sub-station
No. of 400 kV sub-station
No. of 220/230 kV sub-station
6 111 478
Capacity building and training at SRPC office and each state.
E.2 Protection Setting Calculation Tool
This module gives new relay settings for improved performance and computes panel settings for type of distance/over
current/EF/differential/line/transformer protection relays. Relay co-ordination will be conducted for relays of all make
and with user defined characteristics for over current and distance relays in line with the protection philosophy,
followed by SRPC.
The practice of protection engineering involves fault studies followed by relay setting, checking and co-ordination
studies. These studies are necessary in order to ensure that the wide variety of protective relays function correctly
with proper discrimination to provide the required reliable, sensitive and selective isolation of faulty power system
equipment.
Relay co-ordination for radial and interconnected power system networks for over current relays.
Primary/back-up relay pairs generation.
Fault calculation will be a part of relay co-ordination program.
Transparent Fault calculation results.
Built with standard relays library data for different manufacturers, including but not restricted to the
following protection features
i. Line protection: Distance, over current, earth fault, over voltage
ii. Line Differential protection
Annexure-VIII
Page 16 of 61
iii. Transformer Differential Protection
iv. Transformer Over fluxing Protection
v. Transformer Thermal Overload Protection
vi. Transformer Low Impedance Restricted Earth Fault Protection and High Impedance Restricted Earth
Fault Protection
vii. Generator Overall, Generator Transformer and Unit Differential Protection
viii. Generator Inter – Turn Differential Protection (ix) Generator Transformer Low Impedance and High
Impedance Restricted Earth Fault Protection
ix. Generator Stator Earth Fault Protection ( Both 95% and 100% protection)
x. Generator Rotor Earth Fault Protection
xi. Generator Loss of Excitation Protection(Field Failure) ( with and without Under voltage)
xii. Generator Forward Power and Reverse Power Protection
xiii. Generator Back-Up Impedance protection
xiv. Generator Inadvertent energization
xv. Generator Negative Sequence Protection,
xvi. Generator Pole Slip Protection
xvii. Generator Thermal Overload Protection
xviii. Feeders Directional and Non-Directional Over current and Earth Fault Protection with standard and
nonstandard curves (User defined curves).
Plotting Log-Log grid and graphs.
Option to check existing relay settings as per the field or vice versa.
Unit protection settings computation for Generators/ line/transformer / breaker /reactor/ busbar etc.
Computation of Out of Step Tripping Protection Settings.
Display of sequence operation of relays with respect to tripping time.
Switching status for all relays elements from the screen.
Association of relays to power system elements.
Co-ordination check can be conducted for relays of all make and with user defined characteristics for over
current and distance relays.
Disturbance analysis can be done with single click on mapping of disturbances files with corresponding relay.
It has standard power system components and relay symbols.
Phase and Earth relay co-ordination. Co-ordination between Normal, Non - Directional Earth Fault and
Common Earth Fault should be provided.
Instantaneous setting for relays.
Automatic computation of zone setting.
Feature for viewing existing and newly computed relay settings simultaneously.
Pre-loaded standard relay curves.
Directional and non-directional feature for relays.
Overload factor, unbalance factor and discrimination time (user defined/selectable) for each relay.
Inbuilt discrimination time calculator.
Facility to model the back-up protection settings of generating units / GTs connected to the grid at 230 kV/
220 kV and above level, with the exception where the generator is connected to the lower voltage network
which will be considered so that coordination between power plant and transmission system protections may
also be tested / verified.
E.3 Protection Database Management System:
Web-based Enterprise license of Database tool and populating of all the relay templates and also relay field data into
the software and customizing the approval procedures.
Protection data management system is an asset management tool for maintaining information on relay attributes and
settings. The software should be capable of maintaining the entire data belonging to all relays. Once data fits in the
Annexure-VIII
Page 17 of 61
software it should be capable of porting the data to any third party application for analysis and also various reports
generated. The data would be accessed over web for use in protection calculation tool.
The Protection database management system has following capabilities
1. Web based System.
2. Role based access control
3. Flexible customization of user roles, grants, actions from Master control panel
4. User Access Monitor
5. Relay Template Management
6. Create\Edit\Delete relay templates
7. Viewing relay template
8. Locking and Unlocking templates
9. Copy & Edit templates from the existing template
10. Import and Export templates
11. Relay Data management
12. Create\Edit\Delete relay data
13. Viewing relay data
14. Locking and Unlocking relay data
15. Copy & Edit relay data from the existing data
16. Import and Export relay data
17. Configuration management : Should have option to configure user defined levels for generating relay indexing
18. Work flow Management
19. Relay template life cycle management
20. Relay data life cycle management
21. Reports :
a. Possible to generate report as per user requirement
b. User can generate report in standard format like .xls, .pdf.
c. History logger: All user activities including user operations, data management, template management,
configuration management and workflow can be logged to track the user activities over a period of time
d. Import and Export: There is an option to import template and data from any third party application in
standard formats like xml and .xls format
e. Option to integrate any third party application to share data between protection database management
software and calculation engine\tool and vice versa.
f. Relay characteristics curve can be drawn from the setting data.
g. Provision to attach documents to relay template and relay data can be made available.
h. Option to accept setting data as per the audit and verify/compare the field setting with protection
database setting and generate error report.
i. Provision to store and retrieve audit reports
j. Provision to store and retrieve relay tripping incidence report
k. Facility to store and retrieve setting guidelines as per various committees.
l. Automatic Reconciliation Tool is available which will generate automatic reconciliation requests for relay
settings in the database and in the relay hardware.
m. Up-to-date application guides and user manuals of all relays is a part of the relay library.
n. Web-based Checklist for protection audit is available
Annexure-VIII
Page 18 of 61
E.4 Technical Specification of Software
There must be an integration of setting calculation and database management system.
Description
General/Graphical User Interface
1. Windows based state-of the-art Graphical User Interface(GUI)
2. User friendly screens with integrated help
3. Compatible with latest Operating systems Windows 95, Windows 98, Windows 98 SE, Windows NT 4.0, Windows 2000, Windows XP, Windows 2003, Windows 2007, Windows Vista, 7, 8 and above.
4. Support for both RDBMS & ASCII data
5. Self-contained Graphic editor for generation single line diagrams that does not depend on any other drafting package such as AutoCAD.
6. Provision for exporting the Single Line diagram to AutoCAD
7. Software based on standards (IEEE/ANSI…) that are widely acceptable by national and international community.
8. Single line diagram (SLD) / Network Creation with detailed modeling of all the network elements/equipment and interfaced with relational database.
9. Module for creating SLD has advanced features as in a professional drafting / drawing package like AutoCAD. For e.g. layering, panning, zooming, real-time zoom, scaling to fit any paper size (A5toA0), printing / plotting of full diagram, selected window, current window, copy and paste options etc.
10. Different views of the same network. Meaning, there is a provision to display /print /plot SLD showing only system topology / with load flow results / with fault study results /others.
11. SLD to .PDF conversion, scaling to fit any paper size (A5toA0)
12. Flexibility in modeling the system. Meaning there is provision for
SLD-Database integrated mode for network creation
Independently draft the SLD using IEC or ANSI symbols
Data entry using interactive forms without SLD
Associate any SLD with any database at any point of time
Create input data in ASCII files
13 Automatically generates SLD from given system connectivity data
14. Different ways of executing analysis
Run any analysis directly from graphic editor
Run while interactively entering data through forms
Run studies using ASCII input files
15 User defined reports including MIS information of the system under study.
16 Reports in Standard and IEEE Formats
17 Generate reports in .csv, html format as well
18. Should have inbuilt library of all major power system equipment like Generators, lines, cables, transformers, Reactors both Line and Bus, Dynamic and Static Compensators, relays etc. The libraries have all the equipment that is widely in use by Indian Utilities and industries.
19 User friendly GUI for entering new equipment into library.
20. Software supports modeling of unlimited buses and unlimited number of other power system equipments like transformers, lines, Generators etc...
21 Provision for importing of GPS points and generating the network.
22. Performing the analysis of the single file com-trade file for the associated relay through the network element modeled.
Annexure-VIII
Page 19 of 61
Software Licensing/Commercials
23. Software License is such that it can be loaded in any number of PC’s. The dongle/ hardware lock required for the functioning of the software would then be attached to which ever PC the software is required to run
24. There is a provision for further extending the license in future if required.
25. Any software upgrade within the AMC period should be free of cost
Power Flow Analysis
27. Solution methods - Gauss-Seidel, Newton-Raphson, Fast-DeCoupled, current Injection
28. Zone / Area wise modeling & control, islanding.
29. Simulating the study mode in dynamic changes in the network
30. Modeling loads as constant power, constant current, constant impedance or any combination of these.
31. Determine MVAR Compensation.
32. Contingency analysis ranking.
33. Slack Bus Concept uses Gauss - Seidel, Newton - Raphson, Fast-DeCoupled techniques.
34. Frequency dependent Load flow uses Fast-DeCoupled technique. The options available are
Flat Tie-Line Control
Flat Frequency Control
35. Optimal load flow uses Fast-DeCoupled technique. The different optimizations available are
P - Optimization
Q - Optimization
P & Q Optimization.
36. AC-DC load flow - this shall be in built feature of load flow program
37. Possible to simulate Looped and radial systems.
38. Possible to simulate Multiple Islanded systems.
39. Transmission line can be opened at one or both sides.
40. Possible to Model HVDC systems.
41. Computation of Total Transfer Capability (TTC) and Available Transfer Capability (ATC) between two Buses/Areas/Zones and estimation of Loop flows.
42. Sub Station wise load flow for utilities.
43. Simple and Detailed Wind Turbine Model considering all the four IEEE/WECC generic wind turbines
models (WT1 to WT4)
44. IEEE/WECC standard models for performing Grid Interconnection Studies, Studying Wind Plant behavior, etc. are included
45. Modeling suitable for individual Solar plant, Wind Turbine and Wind Farm (Group of Wind Turbines)
46. Provision to enter user specific Wind Power curves in various formats.
47. FACTS devices namely – SVC, STATCOM, TCSC, SPS and UPFC are modeled
48. Modeling of two and three winding transformers with auto tap, off nominal fixed tap and phase shift.
49. The real and reactive power load values, scheduled generation, reactor and capacitor values can be changed globally or zone wise using reduction factors.
50. Generator Q - check limit violations after a specified number of iterations.
51. Changing the load model from the given type to impedance type automatically, when the voltage magnitude at load bus goes below specified value to have better and realistic convergence.
52. Load shedding during under frequency to maintain the frequency at desired value.
53. Efficient memory management by using sparsity technique.
Annexure-VIII
Page 20 of 61
54. Estimation of Inter regional load flow on various corridors by proper modeling of other regions of the country including all scenarios of peak/off peak, seasonal, etc.
Short Circuit Analysis
55. The module shall Compute fault level for both symmetrical and asymmetrical faults.
56. Report post-fault bus voltages, currents and impedances as seen at relay. Also fault MVA and current, Peak / crest asymmetrical and symmetrical components at fault busses.
57. Open conductor faults, traveling shunt fault simulations.
58. Option of running fault studies taking initial conditions from load flow results or flat-start.
59. Shall comply with IEC 363 & IEC 909 Fault analysis.
60. Simulation of number of faults one at a time at various buses in a single execution.
61. Computation of fault contributions from adjacent/next adjacent/all buses in the neighborhood of fault and from the user defined nodes.
62. While computing the program shall take Transformer vector groups, earthing of transformer and generator neutrals.
63. HVDC system contribution to faults.
64. Zero sequence, mutual coupling values will be taken from element modeling However, provision for
multiplication factors for the calculation of unknown zero-sequence impedance/admittance of lines/transformers, negative/zero sequence resistance/reactance of generators, negative/zero sequence impedance of loads and zero sequence impedance of series reactors/shunt reactors are there.
65. Fault MVA and current, Peak/Crest asymmetrical current and symmetrical components at the fault bus are reported.
66. Wind Turbines contribution to Faults for all the four IEEE/WECC generic wind turbines models (WT1 to WT4)
Transient Stability Studies
67. Study of system stability for various faults and disturbances.
68. Study the effects of sudden load / generation variations.
69. Modeling of cyclic loads and different types of synchronous machine.
70. User defined modeling of loads such as constant power / current / impedance or as any combination of the three
71. Motor starting analysis is inbuilt.
72. Built in standard IEEE type voltages regulators, AVR, governors, static VAR compensators, power system stabilizers
73. Support for user defined control system
74. Reports critical fault clearing time to aid in deciding rating of various equipment’s.
75. Study of machine swing curves at various machines and its states
76. Simulation of user-specified number of disturbances.
77. Disturbances that can be simulated are listed below:
1. Change in transformer parameters (for changing number of transformers in parallel, tripping and reconnecting transformer)
2. Change in transmission line parameters (for changing the number of circuits, tripping and reconnecting transmission line)
3. Change in real and reactive power of the load.
4. Change in shunt impedance
5. Change in load model
6. Change in number of generator sets.
7. Total generation outage.
8. Single line to ground fault with pole reclosure.
Annexure-VIII
Page 21 of 61
9. Three phase to ground fault with auto-reclosure.
10. Loss of excitation
11. Motor starting studies
78. Possible to simulate Load shedding schemes.
79. Simulation of operation of voltage/current/frequency relays and distance relays.
80. Load modeling according to user-defined load characteristics as a constant power / current / impedance or as a combination of all the three.
81. Simulation of over/under frequency and df/dt relays for different levels of load shedding at three setting levels of load frequencies.
82. Simulation of over/under voltage relays.
83. Possible to plot Linear graph of absolute/relative swing curves for various machines.
84. Power swing curves of transmission lines and distance relay performance verification.
85. Wind Turbine behavior considering all the four IEEE/WECC generic wind turbines models (WT1 to WT4)
Over current & Distance Co-ordination Studies
86. Software shall support Standard Power System components and Relay symbols.
87. Software should have Inbuilt library of all widely used relays / fuses used in Indian scenario.
88. Software shall Co-ordinate the over current, earth fault relays, distance relays
89. Fault calculation will be inbuilt in the relay co-ordination program
90. Primary and backup relay pairs will be automatically generated.
91. There shall be a provision for manual selection of primary and backup relays.
92. Shall Consider thermal curve of all equipments
93. Simulation of relay responses for Existing settings of the relays
94. Relay co-ordination for radial and interconnected power system networks for over current relays.
95. Motor hot and cold curves.
96. Plotting Characteristic Curves on Log-Log grid.
97. Option to check existing relay settings as per the site.
98. Switching status for all Relay elements from the screen.
Highlighting of Relay Operational Sequence after the analysis.
99. Display of Sequence Operation of Relays with respect to tripping time.
100. Display of Fault on the SLD with standard notation after fault creation.
101. Disturbance Analysis with single click on mapping of disturbance files with corresponding relay.
102. Possible to model Transformer Differential Protection
103. Possible to model Restricted Earth Fault Protection
104. Possible to model Line Pilot Protection
105. Possible to model Bus Bar Differential Protection
106. Possible to model Line/Cable Differential Protection
107. Transformer over fluxing computations
108. Specific Features of Over Current Relay Coordination:
1. Phase Relay Coordination
2. Earth Relay Coordination (Co-ordination between Normal Non - Directional Earth Fault and Common Earth Fault should be provided.)
3. Standby Earth Fault
4. Partial Bus-bar Protection Simulation
5. Fuse Coordination
Annexure-VIII
Page 22 of 61
6. Instantaneous Setting for Relays
7. Directional and Non-directional Feature for Relays
8. Pre-loaded Standard Relay Curves
9. Normalized Curve and Fault Line Feature
10. View existing and newly computed relay settings simultaneously
11. Partial Analysis for selected relays
12. Quick Solve
109. Specific Features of Distance Relay Coordination:
1. Automatic computation of zone setting in terms of Primary and Secondary for the standard make Relays. It will be the approved database (along with facility to update) for all types of conductors (for example from Dog to Quad Moose, Cables etc.)datai.e.R1/X1/Z1R0/X0/Z0,Zero Sequence Impedance angle etc. for computing the Line impedances. For Zone 2 and Zone 3, Zone 4 setting it has the facility to check whether the setting is not covering the next voltage level (considering the Transformer impedances from the Percentage impedances data).
2. Recommended Arc Resistance, Tower footing Resistance for different voltage level
3. Standard Relay Characteristics (example: mho, circular, quadrilateral, user defined etc.).
4. View existing and newly computed relay settings simultaneously
5. Impedance seen by the relay for faults
6. Quick Solve
Unit Protection/ Equipment Protection
110. Specific Features of Transformer Differential Protection:
1. Choice of relay library based on the manufacturer.
2. User defined bias slope setting
3. Provision to enter CT details for 2 winding and 3 winding Transformers &Single Phase Transformer for Railway Application.
4. Provision to enter existing relay settings.
5. Program Computed Transformer differential settings.
6. Program Computed Operating Time
111. Specific Features of Restricted Earth Fault Relay:
1. Choice of relay library based on the manufacturer.
2. User choice of Current or voltage setting
3. Provision to enter current setting range details like minimum, Maximum and step Sensitive or
Normal selection will be from the REF data.
4. User choice of voltage setting details in % or volts.
5. Choice of continuous, uniform or discrete voltage setting variation.
6. Provision to add and delete voltage setting records.
7. User defined bias slope setting for Low Impedance RE/F application
8. Provision to enter CT details for 2 winding and 3 winding Transformers along with Neutral CT details.
9. Provision to enter existing relay settings.
10. Program Computed Restricted Earth Fault settings.
11. Program Computed Operating Time
112. Specific Features Line Pilot Relay
1. User defined Line Pilot relay characteristics
2. Choice of pilot wire voltage (either 5 or 15 kV)
3. Choice of Loop Resistance between measured and computed data
4. Provision to input isolation transformer data
5. Provision to input CT data
6. Padding resistance as a computed output.
113. Specific Features Bus Bar Differential:
Annexure-VIII
Page 23 of 61
1. Provision to enter relay details like max, min and step values of current in %.
2. Provision to enter relay details like max, min and step values of alarm in %.
3. Provision to enter relay details like max, min and step values of time in seconds.
4. Variable resistor Values: Enter Minimum, Maximum and step values
5. Provision to input Pick up Characteristics data for minimum, maximum and step details for over current setting in %, Stabilizing factor (selective), stabilizing factor (check zone) and Time in ms.
6. Provision to view computed and existing stabilizing resistance simultaneously
Specific Features Line/Cable Differential:
1. User defined values for minimum, maximum and step values in % for differential set, switch on, high set and 2nd harmonic restraint.
2. Provision to view computed and existing settings simultaneously.
114. Specific Features of Generator Overall, Generator Transformer and Unit Differential Protection
o Choice of relay library based on the manufacturer.
o User defined bias slope setting
o Provision to enter CT details for 2 and 3 and Multiple winding (for Overall differential)
Transformers
o Provision to enter existing relay settings.
o Program Computed Transformer differential settings.
o Program Computed Operating Time.
115. Specific Features of Generator Inter-turn Differential Protection.
i. Choice of relay library based on the manufacturer.
ii. User choice of Current or voltage setting
iii. Provision to enter current setting range details
iv. User choice of voltage setting details in % or volts.
v. Provision to enter CT details
vi. Provision to enter existing relay settings.
vii. Program Computed Generator Inter-turn Differential Protection settings.
viii. Program Computed Operating Time
116. Specific Features of Generator Stator Earth Fault Protection (Both 95% and 100% protection).
Choice of relay library based on the manufacturer.
User choice of Selection of 100% Generator Stator Earth Fault Protection ( 20Hz or Third Harmonic Principle)
Provision to enter Voltage setting range details
User choice of voltage setting details in % or volts.
Provision to enter CT details ( for 20Hz Principle)
Provision to enter existing relay settings.
Program Computed 95% and 100% Stator Earth Fault Protection settings.
Program Computed Operating Time.
117. Specific Features of Generator Rotor Earth Fault Protection
1. Choice of relay library based on the manufacturer.
2. User choice of Selection of Rotor Earth Fault Protection
3. Provision to enter Voltage & Ohms setting range details
4. User choice of voltage setting details in % or volts.
5. Provision to enter existing relay settings.
6. Program Computed Rotor Fault Protection settings.
7. Program Computed Operating Time.
118. Specific Features of Generator Loss of Excitation Protection(Field Failure) ( with and without Under voltage)
1. Automatic computation of Different Stages of Loss of Excitation
Annexure-VIII
Page 24 of 61
2. Standard Relay Characteristics
3. View existing and newly computed relay settings simultaneously
4. Impedance seen by the relay.
5. Provision to enter existing relay settings.
6. Program Computed Rotor Fault Protection settings.
7. Program Computed Operating Time
119. Specific Features of Forward Power and Reverse Power Protection
Automatic computation of Different Stages of Power Protection.
View existing and newly computed relay settings simultaneously
Provision to enter existing relay settings.
Program Computed Power Relay settings.
Program Computed Operating Time
120. Specific Features of Back-Up Impedance protection
Automatic computation of zone setting
Standard Relay Characteristics (example: mho, circular etc.
View existing and newly computed relay settings simultaneously
Impedance seen by the relay for faults
Quick Solve
121. Specific Features of Generator Inadvertent energisation
1. Choice of relay library based on the manufacturer.
2. User choice of Selection of Generator Inadvertent energisation.
3. Provision to enter Voltage & current setting range details
4. User choice of voltage setting details in % or volts.
5. Provision to enter existing relay settings.
6. Program Computed Generator Inadvertent energisation settings.
7. Program Computed Operating Time.
122. Specific Features of Generator Negative Sequence Protection
1. Choice of relay library based on the manufacturer.
2. User choice of Selection of Generator Negative Sequence.
3. Provision to enter Voltage & current setting range details
4. Provision to enter existing relay settings.
5. Program Computed Generator Negative sequence settings.
6. Program Computed Operating Time.
123. Specific Features of Generator Thermal Overload Protection
1. Choice of relay library based on the manufacturer.
2. User choice of voltage setting details in % or volts and necessary curves.
3. Choice of continuous, uniform or discrete voltage setting variation.
4. Provision to enter existing relay settings.
5. Program Computed Generator Thermal Overload Relay settings.
6. Program Computed Operating Time
COMTRADE Viewer
124. Viewing of Analog and Digital plots of disturbance files stored in the relay
125. Computation of harmonics in the wave forms of analog channels
126. Harmonics up to the order of N/2 Hz (N-> Sampling Frequency)
127. Harmonics view in Tabular form /bar graphs
128. Saving of the analyzed file in Image format
129. Summary of the report includes
Annexure-VIII
Page 25 of 61
1. File Information
2. Summary of Analog Channels
3. Digital channel data
4. Digital channel sequence events
5. Images of analog, digital and phasor section
6. Report types: Multiple
130. Merging of two existing COMTRADE files received from disturbance recorder can be edited or modified by removing unwanted channels and create a new COMTRADE file for further processing.
131. Comparison of 2 or more channels on the same screen
132. Computational View
133. Export to Excel, jpeg
134. Customized Printing: Printing of only required area on the viewer
Network Reduction Module
135. Used defined number of cases is possible
136. Static and dynamic equivalents (equivalent inertia constant) for the power system
137. Initial system condition will be taken from load flow
138. It is possible to select the busses to be retained, individually or zone/area wise.
139. Output of network reduction will give output for both Ybus and Zbus matrices for the reduced system.
140. Network reduction module will give impedance values of additional series and shunt connections arising out of network reduction.
141. Output of network reduction includes equivalent generator's inertia, power, voltage and impedance.
142. The reduced network database and diagram will be created automatically.
Electro-Magnetic Transient Analysis
143. Programiscapableofmodelingoftransmissionline(bothshortandlong),seriesreactor, seriescapacitor,synchronousmachines,inductionmotors,transformerwithmagnetizing component,shuntreactor(includingsaturation),shuntcapacitor,instantaneousvoltageand currentsources,RMSvoltageandcurrentsources,lightningarrestors,Instrument Transformers such as VT, CT&CVT.
It is possible to obtain the statistical analysis of breaker closing and opening.
Facility to create both symmetrical and asymmetrical faults with varying fault impedance.
It is possible to model the time varying resistor.
Impulse voltage/current can be injected at a bus as disturbance.
It has facility to incorporate user defined filters.
The module will generate the following results
Instantaneous voltage/current waveforms for three phases.
COMTRADE file generation.
Average power & energy output waveforms.
Electrical machines speed, angle, torque etc. waveforms
Protection Database Management system
144. Protection data management system is an asset management tool for maintaining information on relay attributes and settings. The software is capable of maintaining the entire data belonging to all relays. Once data fits in the software it will be capable of porting the data to any third party application for analysis and also various reports generated.
145. Web based software and Remotely accessible
146. Role based access control and user control
147. Customization of user roles, grants, actions
Annexure-VIII
Page 26 of 61
148. User Access Monitor
149. Relay Template management
i. Create\Edit\Delete relay templates
ii. Viewing relay template
iii. Locking and Unlocking templates
iv. Copy & Edit templates from the existing template
v. Important Export templates
150. Relay Data management
a. Create\Edit\Delete relay data
b. Viewing relay data
c. Locking and Unlocking relay data
d. Copy & Edit relay data from the existing data
e. Import and Export relay data
151. Configuration management : It has option to configure user defined levels for generating relay indexing
152. Work flow Management
a) Relay template life cycle management
b) Relay data life cycle management.
153. History Logger : All user activities including user operations, data management, template management, configuration management and workflow should be logged to track the user activities over a period of time
154. Import and Export : It has an option to import template and data from any third party application in standard formats like xml and xls format
155. There is an option to integrate any third party application to share data between protection database management software and calculation engine\tool and vice versa.
156. Able to draw the relay characteristic curve from the setting data.
157. Provision to attach documents to relay template and relay data will be available.
158. There is option to accept setting data as per the audit and verify\compare the field setting with protection database setting and generate error report
159. Provision to store and retrieve relay tripping incidence report
160. There is facility to store and retrieve setting guidelines as per various committees.
161. Capturing the History of Protection audit of the sub-stations and reports are available each region-wise.
162. Reports:
Possible to generate reports as per user requirement
User can export generated report to the standard format like .xls, pdf, .doc.
Tripping Incidence Analysis Report
Sequence of Events Operation as viewed from SLDC Operation
Sequence of Breakers Tripped as viewed from Substation
Relays operated on each element-wise
Distance relay operation with different characteristics modeling
Security and data back up
163. Latest software and hardware firewalls to be installed for security of the database from hacking or other malicious manipulation.
Use should be made of 128 bit SSL protocol to encrypt the channel between a client and server to protect data during transit
164. All settings data, SLD, configuration data, hierarchy controls, etc. will be backed up by Network Data Management Protocol (NDMP) for faster disaster recovery. All hardware, software for such backup
Annexure-VIII
Page 27 of 61
creation shall be deemed to be considered part of the project.
Reconciliation Tool
165. The package will contain an automatic reconciliation tool which would generate requests for reconciliation of substation wise data present on-site, which is obtained by audit and present in the database on a periodical basis. There is no direct communication with Relay is envisaged here. All constituents will be able to see a red colored buzzer on the dashboard informing them of the pending reconciliation. On clicking the buzzer, the constituent will be able to see the list of its substation where reconciliation is pending.
The administrator/SRPC Secretariat and SRLDC should be able to see the pending reconciliation status on constituent wise/substation wise report format. After reconciliation, the administrator shall be able to disengage the buzzer
Disaster recovery/Backup
166. The database has automatic backup/failsafe mechanisms to prevent loss of data with at least two separate storages.
E.5 Five Year Support Period
The following are the broad activities envisaged during the five year support period for this project.
Support period shall be for a period of 5 years beyond the date of Go Live.
Technical support for the protection setting computational tool and training programs on every quarterly
basis.
Updating and entering the protection and network database of the SR region for the next five years on
regular/daily basis which shall include changes in system configuration, addition of new substations,
generators, etc.
Bug fixing and free updation of the software release during the support period.
Performing the grid disturbance simulation for the events occurring in the system on daily basis.
Deployment of two qualified protection engineers for the support period. The engineers shall be available
for the technical support during official working hours.
Providing the expert technical advisory from the protection expert on the grid disturbance and simulation
studies in the events of faults
E.6 Exclusions:
Except the following exclusions all requirements for successful completion of the project shall be deemed to be the responsibility of the successful bidder.
The communication infrastructure/facility is not part of this scope.
The civil building infrastructure for the Hardware and software is not included. The control room Air-
conditioner and electrical power supply is not part of this scope.
This scope of work does not include online real time communication with any of the remote substation
equipment like relays, DR’s etc. It is to be noted that such a facility will call for providing necessary
communication infrastructure and special devices\tools to communicate with various makes\brand\versions
of equipment’s\protocols.
SECTION F: Bid Evaluation and Selection of Agency and Award of Work
The following is the Bid process/ evaluation methodology that will be adapted by purchaser for appointment of Agency.
1. Single Stage – Two packet/Envelope Procedure: Bidders should submit two sealed envelopes simultaneously, one containing the Technical Proposal (marked with Tender ID, Tender Name and “Technical Bid”) and the
Annexure-VIII
Page 28 of 61
other the Price Proposal (marked with Tender ID, Tender Name and “Price Bid”), enclosed together in an outer single envelope (marked with Tender ID, Tender Reference, Tender Name and date of opening). Initially, only the Technical Proposals will be opened at the date and time advised in the Bidding Document. The Price Proposals remain sealed and are held in custody by the purchaser. The Technical Proposals are evaluated by the purchaser. No amendments or changes to the Technical Proposals are permitted. The objective of the exercise is to allow the purchaser to evaluate the Technical Proposals without reference to price for transparency.
2. Following the approval of the technical evaluation, and at an address, date and time advised by the purchaser, the Price Proposals will be opened for technically approved bidders. The Price Proposals are evaluated and, following approval of the price evaluation, the Contract is awarded to the Bidder who’s Bid has been determined to be successful based lowest quote.
3. Alternate bids will not be allowed. Alternate technical modules, methodologies, approach, project plan or timelines that deviate from the defined scope and the SRS document will be considered as alternate bid and will be considered as non responsive.
4. Preliminary Evaluation: The technical proposals will be reviewed for deviations, acceptance of terms and
conditions, adherence to scope of work, formats required, purchase of bid document etc. along with the demonstration during bid evaluation. In case of non compliance on any of the above, bids will be considered as technically non-responsive.
5. MANDATORY QUALIFYING REQUIREMENTS FOR TECHNICAL EVALUATION:
i. The Tenderer must have the complete knowledge of the protection system data base modeling and analysis for a big transmission utility. They should have completed at least ONE Job with the protection modeling, database building, simulations and protection setting calculation to a large transmission utility with more-than 150 sub-stations with the voltage level of 400kV to 132kV in the last seven years ending 31.03.2016. The documentary evidence for the same shall be submitted in the form of documents like PO/WO/Completion Letter/Reference letter/Payment received should be submitted along with the bid.
ii. The proposed Protection analysis software must be in use for at least 7 years ending 31.03.2016 in any Indian State Electricity Boards /transmission companies. Proof of the same like PO/WO/Completion Letter/ Reference letter/Payment received should be submitted along with the bid
iii. Tenderer must have software development center, technical and support team for support in India. Details such as address, phone no and name of relevant personnel along with their designation should be provided.
iv. Bidder must have at least Rs. XXXXX Crores (Rupees XXXXX in words) each year average turnover for the past three financial years that is from 01.04.2013 to 31.03.2016. Certificate from CA is to be submitted.
v. The bidder must have completed at least THREE works of not less than Rs. XXXXX Crores each OR at least TWO works of not less than Rs. XXXXX Crores each OR ONE work of not less than Rs. XXXXX Crores for power system analysis software development/supply for electrical utility in the last seven financial years that is from 01.04.2009 to31.03.2016. Proof of the same like PO/WO/Completion Letter/ Reference letter/Payment received should be submitted along with the bid (Except Hardware and before taxes and not including any AMC component)
Annexure-VIII
Page 29 of 61
vi. The bidder must have completed at least THREE works of not less than Rs. XXXXX Crores each or at least TWO workS not less than Rs. XXXXX Crores OR at least ONE work of not less than Rs. XXXXX Crores for protection system modeling database building and maintenance along with supply of software in power sector in the last seven financial years that is from 01.04.2009 to 31.03.2016. Proof of the same like PO/WO/Completion Letter/ Reference letter/Payment received should be submitted along with the bid (Except hardware and before taxes and not containing any AMC component)
vii. The bidder must submit banker’s solvency certificate for at least Rs. XXXXX Crores.
viii. Tenderer must have the web based protection database software which can be customized to SRPC requirement and will be able to build/model the different manufactures relays.
ix. Key protection simulation functionality as at Annexure-A (Technical bid) shall be complied and confirmation documents shall be submitted along-with the bid. The same shall be demonstrated for the technical evaluation committee of SRPC.
x. The bidder must be able to assign minimum 20(Twenty) number of power system & protection engineer on his role full time with Electrical Engineering degree for the works involved in the project as detailed in Annexure-B.
xi. Tenderer should have an office set up for technical support in the Southern region.
xii. The company should practice ISO industry standard Quality process and systems for the software development and activities. The company should have a relevant ISO 9001 certificate for the software development and power system consultancy and the same should be submitted along with the bid.
xiii. No part of the work can be outsourced to other third parties. All works including collection of data, preparation of Database and integration of analysis tools shall be done by the bidder in house utilizing its own resources. Proprietary third party software available in the market/open source, if required may be purchased with the license in favor of SRPC.
xiv. Tenderer should not be in blacklist of any department of Government in India and Abroad. Submit undertaking in Annexure E
xv. Should have worked with at least one power utility company in India in providing IT consulting (power system analysis software tool development/supply, data collection and database building/maintenance work/consultancy), in the last three financial years.
xvi. Should have positive net worth in the last three audited financial years that is from 01.04.2013 to 31.03.2016.
6. Documents comprising the Technical bid: Technical bids and shall contain no prices or price schedules.
Technical bids containing such price information will be rejected. Attachments to the Technical bid:
Each Bidder shall submit with its First Stage bid the following attachments:
a. EMD b. Power of Attorney c. Bidder’s Eligibility and Qualifications as per Mandatory Qualifying Requirements d. The bidder should submit a statement informing the detailed methodology for executing
the complete assignment along with key points. Work completion schedule, deliverables and detailed technical specifications of hardware and software proposed to be supplied.
e. Tender document signed and sealed on all pages as an unequivocal acceptance of terms and conditions.
Annexure-VIII
Page 30 of 61
f. Manpower deployment schedule with CV’s. g. Manufacturer’s Authorization Form h. Additional Information which bidder intends to submit along with the tender like quality
certifications etc. i. Technical bid form Annexure-A j. Receipt of tender fees k. All other enclosures required to be submitted as per Technical Specification at Annexures
7. Technical Bid Form: The Bidder shall complete the Technical Bid Format Annexure A in the manner and
details indicated therein and submit the same with its first stage bid. 8. Technically qualified bidder: The technical bids shall be opened by a Tender Evaluation Committee (TEC)
formed for this purpose. The Qualifying Criteria & Technical bid shall be analyzed first. TEC will scrutinize the offer to determine whether the offer is complete, whether required technical documentation have been furnished, whether the documents have been properly signed, whether the bidder has made successful demonstration and whether the offer is in order.The decision of the Evaluation Committee in the evaluation of the Qualification criteria and Price bids shall be final and binding.
9. Price bid: The Price bids may be opened on the same day o r at a later date to be intimated on the same day based on the number of bids received. The Price bid of only those bidders would be opened who have qualified the mandatory qualifying requirements. All figures in financial bids shall be in Indian currency only. The financial bid must be submitted in format at Annexure C only. Validity of the Price bids shall be 90 days from the date of opening of financial bid. Selection of Successful bidder: The L1 bidder among technically qualified bidders will be awarded the work after recommendation of TEC.
10. Notification of Award and Initiation of Contract: The Bidder, whose Bid has been accepted, will be notified of the award by SRPC prior to expiry of the Bid validity period by cable, e-mail, or facsimile confirmed by registered letter/speed post. This letter (hereinafter and in the Conditions of Contract called the "Letter of Intent"(LOI)) will state the sum that purchaser will pay the Agency in consideration of the execution, completion and maintenance of the Works by the Agency, as prescribed by the Contract (hereinafter and in the Contract called "the Contract Price").
11. The successful qualified Bidder(s) will confirm acceptance of LOI through ‘Letter of Acceptance’ within seven days from the date of issue of LOI along with the Performance Security Guarantee.
12. Award of work: Thereafter “Letter of Award” shall be issued after receipt of ‘Letter of Acceptance’ and submission of Performance Security.
13. Upon the furnishing of Performance Security Guarantee Deposit by the successful Bidder and receipt of “Letter of Acceptance” SRPC will promptly notify the other Bidder(s) that their Bids have been unsuccessful and refund the Bid Security/Earnest Money Deposit as promptly as possible.
Annexure-VIII
Page 31 of 61
Section G: General Conditions of Contract
1. Contract Documents 1.1 All documents forming the Contract (and all parts thereof) are intended to be
correlative, complementary, and mutually explanatory.
2. Corrupt Practices
The bidder shall not have been blacklisted by any State/Central Government or PSU
Organization or bilateral/multilateral funding agencies for breach of ethical conduct
or fraudulent practices as on date of submission of the proposal. There should be no
investigations pending/proceedings contemplated against the bidder by any
government agency.
1.2 The Purchaser requires bidders, suppliers, and contractors to observe
the highest standard of ethics during the execution of such contracts.
(a) The following definitions apply:
“corrupt practice” means the offering, giving receiving, or soliciting, directly or
indirectly, of anything of value to influence the action of any party in the
procurement process or the execution of a contract;
“fraudulent practice” means a misrepresentation or omission of facts in order to
influence a procurement process or the execution of a contract;
“collusive practices” means a scheme or arrangement between two or more
bidders, with or without the knowledge of the SRPC,- designed to influence the
action of any party in a procurement process or the execution of a contract;
“coercive practices” means harming or threatening to harm, directly or indirectly,
persons, or their property to influence their participation in a procurement process,
or affect the execution of a contract;
(b) The Purchaser will reject a proposal for award if it determines that the bidder
recommended for award has, directly or through an agent, engaged in corrupt,
fraudulent, collusive, or coercive practices in competing for the Contract.
Annexure-VIII
Page 32 of 61
3. Interpretation 1.3 In this Contract unless a contrary intention is evident:
(a) the clause headings are for convenient reference only and do not form
part of this Contract. The headings shall not limit, alter or affect the meaning of this
Contract;
(b) unless otherwise specified a reference to a clause number is a reference to all of
its sub-clauses;
(c) unless otherwise specified a reference to a clause, sub-clause or section is a
reference to a clause, sub-clause or section of this Contract including any
amendments or modifications to the same from time to time;
(d) a word in the singular includes the plural and a word in the plural includes the
singular;
(e) a word imparting a gender includes any other gender;
(f) a reference to a person includes a body corporate;
(g) a reference to legislation includes legislation repealing, replacing or amending
that legislation;
(h) where a word or phrase is given a particular meaning it includes the appropriate
grammatical forms of that word or phrase which have corresponding meanings;
(i) in the event of an inconsistency between the terms of this Contract and the
proposal, the terms of this contract hereof shall prevail.
1.4 Entire Agreement
The Contract constitutes the entire agreement between the Purchaser and the
Supplier and supersedes all communications, negotiations and agreements
(whether written or oral) of parties with respect there to made prior to the date of
Contract.
1.5 Amendment
No amendment or other variation of the Contract shall be valid unless it is in writing,
is dated, expressly refers to the Contract, and is signed by a duly authorized
representative of each party thereto.
1.6 Non-waiver
(a) Subject to GCC Clauses 32 and 34 below, no relaxation, forbearance, delay, or
indulgence by either party in enforcing any of the terms and conditions of the
Contract or the granting of time by either party to the other shall prejudice, affect,
or restrict the rights of that party under the Contract, neither shall any waiver by
either party of any breach of Contract operate as waiver of any subsequent or
continuing breach of Contract.
Any waiver of a party’s rights, powers, or remedies under the Contract must be in
writing, dated, and signed by an authorized representative of the party granting
such waiver, and must specify the right and the extent to which it is being waived.
1.7 Severability
If any provision or condition of the Contract is prohibited or rendered invalid or
unenforceable, such prohibition, invalidity or unenforceability shall not affect the
validity or enforceability of any other provisions and conditions of the Contract.
4. Language 1.8 The Contract as well as all correspondence and documents relating to the
Contract exchanged by the Agency and the Purchaser, shall be written in English.
Supporting documents and printed literature that are part of the Contract may be in
another language provided they are accompanied by an accurate translation of the
relevant passages in English, in which case, for purposes of interpretation of the
Contract, this translation shall govern.
1.9 The Agency shall bear all costs of translation to English and all risks of the
accuracy of such translation.
5.Joint
Venture/Consortium/Association
1.10 No Joint venture/Consortium/Association is allowed to participate in this
tender. All works envisaged in the scope of work are to be undertaken by the bidder
with manpower on its own rolls.
Annexure-VIII
Page 33 of 61
6. Eligibility 1.11 Eligibility criteria shall be as per the Technical bid evaluation criteria
7.Location 1.12 The Services shall be performed at the area under the jurisdiction of SRPC
, or at such location required by SRPC.
8.Effectiveness of Contract 1.13 This Contract shall come into force and effect on the date of award
(the“Effective Date") of the Purchaser’s notice to the Agency confirming that the
following conditions have been met:
a) This Contract has been approved by Purchaser
b) Requisite Performance Bank Guarantee has been submitted.
9. Warranty/ Licenses and Annual
Maintenance Contract (AMC)
1.14 Server, storage hardware and Laptops supplied in the contract shall be covered
under warranty for at least five year onsite manufacturer's warranty.
Warranty period for the all other hardware shall be on site for twelve months or as
per manufacturer standard warranty whichever is higher.
All warranties and licenses for hardware and software shall be in favor of purchaser.
10.Authorized Representatives 1.15 Any action required or permitted to be taken, and any document
required or permitted to be executed under this Contract, may be taken or
executed:
a) on behalf of the Purchaser by competent authority or his designated
representative;
b) on behalf of the Agency by PoA or his designated representative.
11. Relation between the Parties 1.16 Nothing contained herein shall be construed as establishing a relation of
master and servant or of agent and principal as between the Purchaser and the
Agency. The Agency, subject to this Contract, has complete charge of Personnel
performing the Services and shall be fully responsible for the Services performed by
them or on their behalf hereunder.
12. Notices 1.17 Any Notice given by one party to the other pursuant to the Contract shall be in
writing. The term “in writing” means communicated in written form with proof of
receipt.
1.18 Any such notice, request or consent shall be deemed to have been given or
made when delivered in person to an authorized representative of the Party to
whom the communication is addressed, or when sent by registered post, telex,
telegram, email or facsimile to such Party at the following address:
1.19 For the Owner: Member Secretary, SRPC
Email: [email protected] and [email protected] Telephone: 22287205,
26682396
1.20 For the Agency: (pl.fill up)__________________
Attention: ___________________ Telegram: ___________________
Facsimile: ___________________
1.21 Notice will be deemed to be effective as follows:
(a) in the case of personal delivery or registered mail, on delivery;
(b) in the case of email twenty four(24) hours following confirmed transmission.
(c) in the case of facsimiles, twenty four(24) hours following confirmed transmission
1.22 A Party may change its address for notice hereunder by giving the
other Party notice of such change pursuant to this Clause.
13. Governing Law 1.23 The Contract shall be governed by and interpreted in accordance with the laws
of the India. The Courts in Bangalore shall have exclusive jurisdiction with respect of
the tendering process, award of Contract and execution of the Contract.
Annexure-VIII
Page 34 of 61
14.Settlement of Disputes 1.24 The Purchaser and the Supplier shall make every effort to resolve amicably by
direct informal negotiation any disagreement or dispute arising between them
under or in connection with the Contract.
1.25 If the parties fail to resolve such a dispute or difference by mutual consultation
within twenty-eight (28) days from the commencement of such consultation, either
party may require that the dispute be referred for resolution to the formal
mechanisms specified below:
If the parties fail to resolve such a dispute or difference by mutual consultation
within twenty-eight (28) days from the commencement of such dispute and
difference, either party may require that the dispute be referred for resolution to
the formal mechanisms, described below (The date of commencement of the
dispute shall be taken from the date when this clause reference is quoted by either
party in a formal communication clearly mentioning existence of dispute or as
mutually agreed) :
a. The mechanism for resolution of disputes for bidders shall be in accordance with
the Indian Arbitration and Conciliation Act of 1996 as amended from time to time.
The Arbitral Tribunal shall consist of 3 (Three) Arbitrators. Each Party shall nominate
an Arbitrator and the two nominated Arbitrators shall mutually agree and nominate
a third Presiding Arbitrator. b. The place for arbitration shall be Bangalore
15. Scope of Work 1.26 The services to be rendered by Agency shall be as per scope of work (Given in
the Section E-Scope of Work). At the time of awarding the contract, the Purchaser
shall specify any change in the Scope of Work. Such changes may be due to increase
or decrease in the scope of work at the time of award.
1.27 Unless otherwise stipulated in the Contract, the Scope of Work shall include all
such items not specifically mentioned in the Contract but that can be reasonably
inferred from the Contract as being required for attaining Delivery and Completion
of Related Services as if such items were expressly mentioned in the Contract.
16.Commencement of Services 1.28 The Agency shall begin carrying out the Services immediately viz. from the date
of issue of Letter of Award (the "Starting Date"), or on such date as the Parties may
agree in writing.
17. Delivery 1.29 The Delivery of services and Completion of the Related Services shall be in
accordance with the milestones specified in the Section E, Scope of Work and
acceptance of the services rendered by the Purchaser.
1.30 The Agency, in relation to its deliverables, shall provide any supporting data or
information required by the Purchaser.
18.Agency Responsibilities 1.31 The Agency shall provide the services mentioned in the Scope of Work and the
Delivery and Completion Schedule, as per Section–E-Scope of Work.
19.Purchaser’s Responsibilities 1.32 For successful completion of the assignment, as and when required by the
Agency, the Purchaser shall provide data and support based on availability of the
same and without prejudice. In the event that the purchaser is unable to provide the
required data or support for a requirement which the Agency cannot be reasonably
expected to procure on its own or from alternate sources, the Agency’s failure to
deliver shall not be held against it.
1.33 The Agency shall bear all costs involved in the performance of
its responsibilities, in accordance with GCC Clause 20.
1.34 The Competent authority of Purchaser shall act as the nodal point for
implementation of the contract and for issuing necessary instructions, approvals,
commissioning, acceptance certificates, payments etc. to the Agency.
1.35 The Competent authority of Purchaser shall approve all such documents within
30 working days.
1.36 Purchaser may provide on Supplier’s request, particulars/information / or
Annexure-VIII
Page 35 of 61
documentation that may be required by the Supplier for proper planning and
execution of Scope of Work under this contract.
1.37 Purchaser shall provide to the Supplier sitting space and infrastructure and
utilities, in the Purchaser’s offices at such location as may be mutually decided by
the Parties.
20. Contract Price 1.38 The Contract Price shall be as specified in the Agreement subject to any
additions and adjustments thereto, or deductions there from, as maybe made
pursuant to the Contract.
1.39 Prices charged by the agency for the service provided under the Contract shall
not vary from the prices quoted by the Agency in its Bid (bid value).
21. Terms of Payment 1.40 The Contract Price shall be paid in the manner specified in the Payment
Schedule GCC 51. No invoice for extra work/change order on account of change
order will be submitted by the Supplier unless the said extra work /change order has
been authorized/approved by the Purchaser in writing. , as appropriate, Services
provided, accompanied by the documents submitted pursuant to GCC Clause 17.
The Agency shall submit the bills in triplicate to the concerned purchaser.
1.42 Payments shall be made promptly by the Purchaser, not later than sixty (60)
days after submission of an invoice along with supporting documents or request for
payment by the Supplier, and the Purchaser has accepted it. But if the progress is
not satisfactory and according to agreed work program/schedule the payment may
be withheld.
1.43 The final payment under this Clause shall be made only after satisfactory
completion of the activities mentioned in the Scope of Work.
1.44 If any excess payment has been made by the Purchaser due to difference in
quoted price in proposal and Supplier’s invoice, the purchaser may without
prejudice to its rights recover such amounts by other means after notifying the
Supplier or deduct such excess payment from any payment subsequently falling due
to the Agency.
22. Taxes and Duties 1.45 The Agency and the personnel shall pay the taxes, duties, fees, levies and other
impositions levied under the existing, amended or enacted laws during life of this
contract.
The purchaser shall reimburse all applicable taxes such as VAT and Service Tax
directly related to the execution of the works to the agency and the purchaser shall
perform such duties in regard to the deduction of such tax as may be lawfully
imposed.
Payment of taxes/duties shall not be made separately in any case.
For goods/services supplied from outside the Purchaser’s country, the Supplier shall
be entirely responsible for all taxes, duties, stamp duties, license fees, and other
such levies imposed outside the Purchaser’s country.
23. Performance Security 1.48 The Supplier shall, within twenty eight (28) days of the issue of Letter of Intent,
provide a Performance Security for the due performance of the Contract in the
amounts and currencies specified below:
The successful bidder will have to furnish a Performance Security Guarantee
Deposit @ 5% of the bid value/contract price in form of an irrevocable bank
guarantee as per format at Annexure G from a scheduled commercial bank within
28 days after the issue of letter of intent (LoI).
Annexure-VIII
Page 36 of 61
The performance guarantee shall remain valid for a period of 60 days beyond the
support period of five years from the date of project ‘go live’ and shall be
renewed for a further period, if required so. Performance Security Guarantee in
form of bank guarantee will be discharged and returned to the successful bidder
after satisfactory performance of all the terms and conditions of contract.
This guarantee will be for faithful performance of the contract in accordance with
the terms and conditions and technical specification specified in the contract bid
documents.
1.49 The Purchaser shall at its sole discretion invoke the Performance Security and
appropriate the amount secured there-under, in the event that the Supplier
commits any delay or default in Services rendered or commits any breach of the
terms and conditions of the Contract.
1.50 The Performance Security shall be denominated in the currencies of the
Contract, and shall be in one of the forms stipulated by the Purchaser in Annexure
G.
1.51 The Performance Security shall be discharged by the Purchaser and
returned to the Agency not later than sixty (60) days following the date of
completion of the Supplier’s performance obligations under the Contract, unless
specified.
24. Intellectual Property 1.52 Purchaser shall own and have a right in perpetuity to use all newly created
Intellectual Property Rights which have been developed solely during execution of
this Contract, including all records, reports, designs, application configurations, data
and written material, specifications, reports, drawings and other documents which
have been newly created and developed by the Supplier solely during the
performance of Related Services and for the purposes of inter-alia use or sub-license
of such Services under this Contract. The Supplier undertakes to disclose all such
Intellectual Property Rights arising in performance of the Related Services to the
Purchaser and execute all such agreements/documents and file all relevant
applications, effect transfers and obtain all permits and approvals that may be
necessary in this regard to effectively transfer and conserve the Intellectual Property
Rights of the Purchaser. To the extent that Intellectual Property Rights are unable,
by law, to so vest, the Supplier assigns those Intellectual Property Rights to
Purchaser on creation.
1.53 The Supplier shall be obliged to ensure that all approvals, registrations,
licenses, permits and rights etc. which are inter-alia necessary for use of the goods
supplied / installed by the Supplier (if any),as part of the service obligations under
the present contract, shall be acquired in the name of the Purchaser, and the same
may be assigned by the Purchaser to the Supplier solely for the purpose of
execution of any of its obligations under the terms of this Contract. However,
subsequent to the term of this Contract, such approvals, registrations, licenses,
permits and rights etc. shall endure to the exclusive benefit of the Purchaser
1.54 The Supplier shall ensure that while it uses any software, hardware, processes,
document or material in the course of performing the Services, it does not infringe
the Intellectual Property Rights of any person and the Supplier shall keep the
Purchaser indemnified against all costs, expenses and liabilities howsoever, arising
out any illegal or unauthorized use(piracy) or in connection with any claim or
proceedings relating to any breach or violation of any permission/license terms or
infringement of any Intellectual Property Rights by the Supplier or its personnel
during the course of performance of the Related Services. In case of any
Annexure-VIII
Page 37 of 61
infringement by the Supplier, the Supplier shall have sole control of the defense and
all related settlement negotiations
1.55 Subject to sub-clauses 1.52 to 1.54, the Supplier shall retain exclusive
ownership of all methods, concepts, algorithms, trade secrets, software
documentation, other intellectual property or other information belonging to the
Supplier that existed before the effective date of the contract.
25. Confidential Information 1.56 The Agency/Consortium and the personnel of any of them shall not either
during the term or within two (2) years after the expiration of this contract, disclose
any proprietary or confidential information relating to the Project, the Services, this
Contract or the Owner’s business or operations without the prior written consent of
the owner.
1.57 The Purchaser shall not use such documents, data, and other information
received from the Supplier for any purposes unrelated to the Contract. Similarly, the
Supplier shall not use such documents, data, and other information received from
the Purchaser for any purpose other than the design, procurement, or other work
and Services required for the performance of the Contract.
1.58 The obligation of a party under this clause, however, shall not apply to
information that:
(a) the Purchaser or Agency need to share with the institutions participating in the
financing of the Contract;
(b) now or hereafter enters the public domain through no fault of that party;
(c) can be proven to have been possessed by that party at the time of disclosure and
which was not previously obtained, directly or indirectly from the other party; or
(d) Otherwise lawfully becomes available to that party from a third party that has no
obligation of confidentiality.
1.59 The above provisions of GCC Clause 25 shall not in any way modify any
undertaking of confidentiality given by either of the parties hereto prior to the date
of the Contract in respect of the Supply or any part thereof.
1.60 The provisions of GCC Clause 25 shall survive completion or termination, for
whatever reason, of the Contract.
26. Subcontracting 1.61 The Agency shall not be permitted to sub-contract any part of its obligations
under the Contract with the utilities.
Neither the contract nor any rights granted under the contract may be sold,
leased/sublet, assigned, or otherwise transferred, in whole or in part, by the
agency., and any such attempted sale, lease, assignment or otherwise transfer shall
be void and of no effect without the advance written consent of the purchaser .
27. Service Quality 1.62 The Purchaser may reject any Service rendered or any part thereof
that fail to conform to the specifications. The Supplier shall take measures
necessary to meet the specifications at no cost to the Purchaser.
28.Liquidated Damages and Penalty 1.63 Except as provided under GCC Clause 32, if the Supplier fails to perform any or
all of the Services within the period specified in the Contract, the Purchaser may
without prejudice to all its other remedies under the Contract, deduct from the
Contract Price, as liquidated damages,
a)sum equivalent to 0.5% of the value of the Services, supplied beyond stipulated
delivery schedule for each week or part thereof of delay until actual performance,
subject to a maximum of 10% of value of such services.
b) To obtain services from elsewhere, after due notice to the successful bidder on
Annexure-VIII
Page 38 of 61
the account and at the risk of the defaulting service provider.
c) To cancel the work order or a portion thereof and if so desired to get the services
at the risk and cost of the defaulting supplier and also,
d) To extend the period of delivery with or without penalty as may be considered fit
and proper, the penalty, if imposed shall not be more than the agreed liquidated
damages referred to in clause (a) above.
e) To forfeit the security deposit fully or partly.
f) Whenever, under this contract, a sum of money is recoverable from and payable
by the Service Provider, purchaser shall be entitled to recover such sum by
appropriation in part or in whole by deducting any sum or which at any time
thereafter may become due to the successful bidder in this or any contract should
this sum be not sufficient to cover the full amount recoverable, the successful
bidder shall pay purchaser on demand the remaining amount. The supplier shall not
be entitled to any gain on any such purchase.
The bidder shall not be in any manner liable for any delay arising out of purchaser’s
inability to make the site ready within the stipulated period.
29.Liability/ Indemnity 1.64 The Supplier hereby agrees to indemnify the Purchaser, for all conditions and
situations mentioned in this clause, in a form and manner acceptable to the
Purchaser. The supplier agrees to indemnify the Purchaser and its officers, servants,
agents (“ Purchaser Indemnified Persons”) from and against any costs, loss,
damages, expense, claims including those from third parties or liabilities of any kind
howsoever suffered, arising or incurred inter alia during and after the Contract
period out of:
(a) any negligence or wrongful act or omission by the Supplier or its agents or
employees or any third party associated with Supplier in connection with or
incidental to this Contract; or
(b) any infringement of patent, trademark/copyright or industrial design rights
arising from the use of the supplied Goods and Services or any part thereof.
1.65 The Supplier shall also indemnify the Purchaser against any privilege, claim or
assertion made by third party with respect to right or interest in, ownership,
mortgage or disposal of any asset, property, movable or immovable as mentioned in
any Intellectual Property Rights, licenses and permits
1.66 Without limiting the generality of the provisions of this article 1.67and 1.68,
the Supplier shall fully indemnify, hold harmless and defend the Purchaser
Indemnified Persons from and against any and all suits, proceedings, actions, claims,
demands, liabilities and damages which the Purchaser Indemnified Persons may
hereafter suffer, or pay by reason of any demands, claims, suits or proceedings
arising out of claims of infringement of any domestic or foreign patent rights,
copyrights or other intellectual property, proprietary or confidentiality rights with
respect to any Goods, Services, information, design or process supplied or used by
the Supplier in performing the Supplier’s obligations or in any way
incorporated in or related to the Project. If in any such suit, action, claim or
proceedings, a temporary restraint order or preliminary injunction is granted, the
Supplier shall make every reasonable effort, by giving a satisfactory bond or
otherwise, to secure the suspension of the injunction or restraint order. If, in any
such suit, action, claim or proceedings, the Goods or Services, or any part thereof or
comprised therein, is held to constitute an infringement and its use is permanently
enjoined, the Supplier shall promptly make every reasonable effort to secure for the
Purchaser a license, at no cost to the Purchaser, authorizing continued use of the
infringing work. If the Supplier is unable to secure such license within a reasonable
time, the Supplier shall, at its own expense, and without impairing the specifications
and standards, either replace the affected work, or part, or process thereof with
Annexure-VIII
Page 39 of 61
non-infringing work or part or process, or modify the same so that it becomes non-
infringing. Survival on Termination The provisions of this Clause 29 shall survive
Termination.
1.67 Defense of Claims:
If any proceedings are brought or any claim is made against the Purchaser arising
out of the matters referred to in GCC Sub-Clause 1.67, 1.68, or 1.69the Purchaser
shall promptly give the Supplier a notice thereof, and the Supplier may at its own
expense and in the Purchaser’s name conduct such proceedings or claim and any
negotiations for the settlement of any such proceedings or claim.
1.68 If the Supplier fails to notify the Purchaser within twenty-eight (28)days after
receipt of such notice that it intends to conduct any such proceedings or claim, then
the Purchaser shall be free to conduct the same on its own behalf.
1.69 The Purchaser shall, at the Supplier’s request, afford all available assistance to
the Supplier in conducting such proceedings or claim, and shall be reimbursed by
the Supplier for all reasonable expenses incurred in so doing.
30. Limitation of Liability 1.70 Except in cases of gross negligence or willful misconduct :
(a) neither party shall be liable to the other party for any indirect or consequential
loss or damage, loss of use, loss of production, or loss of profits or interest costs,
provided that this exclusion shall not apply to any obligation of the Supplier to pay
liquidated damages to the Purchaser; and(b) the aggregate liability of the Supplier
to the Purchaser, whether under the Contract, in tort, or otherwise, shall not exceed
the amount specified in the Contract Price. Provided that this limitation shall not
apply to the cost of repairing or replacing defective equipment, or to any obligation
of the Supplier to indemnify the Purchaser with respect to patent infringement.
31. Change in Laws and Regulations 1.71 Unless otherwise specified in the Contract, if after the date of the Invitation for
Bids, any law, regulation, ordinance, order or bylaw having the force of law is
enacted, promulgated, abrogated, or changed in the place of the Purchaser’s
country where the Site / area of work is located(which shall be deemed to include
any change in interpretation or application by the competent authorities) that
subsequently affects the Delivery Date, then such Delivery Date shall be
correspondingly increased or decreased, to the extent that the Supplier has thereby
been affected in the performance of any of its obligations under the Contract.
32. Force Majeure If the execution of the contract is delayed beyond the period stipulated in the
contract as a result of outbreak of hostilities, declaration of an embargo or blockage
or fire, flood, acts of nature or any other contingency beyond the supplier’s control
due to act of God, then purchaser may allow such additional time by extending the
delivery period as it considers to be justified by the circumstances of the case and
the decision of the purchaser in this regard shall be final.
If and when additional time is granted by the purchaser, the contract shall be read
and understood as if it had contained from its inception the delivery date as
extended subject to the following conditions. Power failure will not be considered as
a force majeure conditions.
1.75 A Party affected by an event of Force Majeure shall take all reasonable
measures to remove such Party's inability to fulfill its obligations hereunder with a
minimum of delay.
1.76 A Party affected by an event of Force Majeure shall notify the other Party of
such event as soon as possible, and in any event not later than fourteen (14) days
following the occurrence of such event, providing evidence of the nature and cause
of such event, and shall similarly give notice of the restoration of normal conditions
as soon as possible.
1.77 The Parties shall take all reasonable measures to minimize the consequences of
any event of Force Majeure.
1.78 The decision of the Purchaser with regard to the occurrence, continuation,
Annexure-VIII
Page 40 of 61
period or extent of Force Majeure shall be final and binding on the Supplier.
1.79 Any period within which a Party shall, pursuant to this Contract, complete any
action or task, shall be extended for a period equal to the time during which such
Party was unable to perform such action as a result of Force Majeure.
1.80 Not later than thirty (30) days after the agency, as the result of an event of
Force Majeure, have become unable to perform a material portion of the Services,
the Parties shall consult with each other with a view to agreeing on appropriate
measures to be taken in the circumstances.
33. Change Orders and Contract
Amendments
1.81 The Purchaser may at any time order the Agency through Notice in accordance
GCC Clause 12, to make changes within the terms and conditions of this Contract,
including any modification of the scope of the Services.
1.82 If any such Change Order causes an increase or decrease in the cost of, or the
time required for, the Supplier’s performance of any provisions under the Contract,
an equitable adjustment shall be made in the Contract Price or in the Delivery and
Completion Schedule, or both, and the Contract shall accordingly be amended. Any
claims by the Agency for adjustment under this Clause must be asserted within
twenty-eight (28)days from the date of the Supplier’s receipt of the Purchaser’s
Change Order.
1.83 No variation or modification of the terms of the contract shall be made except
by written amendment signed by the parties.
34. Extensions of Time 1.84 If at any time during performance of the Contract, the Supplier should
encounter conditions impeding timely completion of Services pursuant to GCC
Section-E, the Supplier shall promptly notify the Purchaser in writing of the delay, its
likely duration, and its cause. As soon as practicable after receipt of the Supplier’s
notice, the Purchaser shall evaluate the situation and may at its discretion extend
the Supplier’s time for performance, in which case the extension shall be ratified by
the parties by amendment of the Contract.
1.85 Except in case of Force Majeure, as provided under GCC Clause 32 or where the
delay in delivery of the Goods or completion of Services is caused due to any delay
or default of the Purchaser, any extension granted under clause 34 shall not absolve
the Supplier from its liability to the pay of liquidated damages pursuant to GCC
Clause 28.
35. Suspension 1.86 The Purchaser may, by written notice of suspension to the Agency, suspend all
payments to the Agency hereunder if the Agency fail to perform any of their
obligations under this Contract, including the carrying out of the Services as per
schedule, provided that such notice of suspension (i) shall specify the nature of the
failure, and (ii) shall request the Agency to remedy such failure within a period not
exceeding Seven (7) days after receipt by the Agency of such notice of suspension
and shall invoke contract performance guarantee.
36. Termination 1.87 Termination of Contract for Failure to Become Effective
(a) If the purchaser fails to issue letter of intent (LoI) within 90 days of the date of
opening of bids for whatever reasons, either Party may, by not less than two weeks
(2) weeks' written notice to the other Party, declare this Contract to be null and
void, and in the event of such a declaration by either Party, neither Party shall have
any claim against the other Party with respect hereto.
1.88 Termination for Default
(a) The Purchaser may, without prejudice to any other remedy for breach of
Contract, by Notice of default sent to the Agency terminate the Contract in whole or
in part:
(i) if the Agency fails to provide acceptable quality of Services within the period
specified in the Contract, or within any extension thereof granted by the Purchaser
pursuant to GCC Clause34; or
(ii) if the Agency, in the judgment of the Purchaser has engaged in corrupt,
Annexure-VIII
Page 41 of 61
fraudulent, collusive, or coercive practices, as defined in GCC Clause 2, in competing
for or in executing the Contract; or
Any representation made by the bidder in the proposal is found to be false or
misleading if the Agency commits any breach of the Contract and fails to remedy or
rectify the same within the period of two weeks (or such longer period as the
Purchaser in its absolute discretion decide) provided in a notice in this behalf from
the Purchaser.
If the Agency fail to comply with any final decision reached as a result of arbitration
proceedings.
If, as the result of Force Majeure, the Agency is unable to perform a material portion
of the Services for a period of not less than sixty (60) days.
If the Agency has been blacklisted by the any government agency due to misconduct
etc.
In the event the Purchaser terminates the Contract in whole or in part, pursuant to
GCC Clause36, the Purchaser may procure, upon such terms and in such manner as
it deems appropriate, Goods or Services similar to those undelivered or not
performed, and the Agency shall be liable to the Purchaser for any additional costs
for such similar Goods or Services. However, the Supplier shall continue
performance of the Contract to the extent not terminated.
1.89 Termination for Insolvency
The Purchaser may at any time terminate the Contract by giving Notice to the
Agency if the Supplier becomes bankrupt or otherwise insolvent. In such event,
termination will be without compensation to the Agency, provided that such
termination will not prejudice or affect any right of action or remedy that has
accrued or will accrue thereafter to the Purchaser
1.90 Termination for Convenience
The Purchaser, by Notice sent to the Agency, may terminate the Contract, in whole
or in part, at any time for its convenience. The Notice of termination shall specify
that termination is for the Purchaser’s convenience, the extent to which
performance of the Agency under the Contract is terminated, and the date upon
which such termination becomes effective.
1.91 Consequences of Termination
Upon Termination of the Contract, the Agency shall:
Prepare and present a detailed exit plan within five calendar days of termination
notice receipt to the competent authority of Purchaser (“Exit Plan”).
The competent authority and along with designated team will review the Exit plan. If
approved, Supplier shall start working on the same immediately. If the plan is
rejected, Agency shall prepare alternate plan within two calendar days. If the
second plan is also rejected, competent authority will provide a plan for Supplier
and it should be adhered by in totality.
The Exit Plan should cover at least the following :-
Annexure-VIII
Page 42 of 61
Execute all documents that may be necessary to effectively transfer the ownership
and title, including OEM warranties in respect of all leased equipment;
(ii) Handover all developed codes, related documentation and other Configurable
Items, if any in his possession;
(iii) Handover the list of all IT Assets, passwords at all locations to the Purchaser.
37. Cessation of Rights & Obligations 1.92 Upon termination of this Contract pursuant to Clause 36 hereof, or upon
expiration of this Contract pursuant to Clause 49 hereof, all rights and obligations of
the Parties hereunder shall cease, except
a) Such rights and obligations as may have accrued on the date of termination or
expiration,
b) The obligation of confidentiality set forth in Clause 25 hereof,
c) Any right which a Party may have under the Applicable Law.
38. Cessation of Services 1.93 Upon termination of this Contract by notice to pursuant to Clause 36hereof,
the Agency shall, immediately upon dispatch or receipt of such notice, take all
necessary steps as provided in Clause 36 hereof, to bring the Services to a close in a
prompt and orderly manner and shall make every reasonable effort to keep
expenditures for this purpose to a minimum.
39. Payment upon Termination 1.94 Upon termination of this Contract pursuant to Clause 36 hereof, the
Purchaser shall make the following payments to the Agency:
a) Remuneration pursuant “Payment Schedule” GCC 51 for Services satisfactorily
performed prior to the effective date of termination;
b) Reimbursable expenditures pursuant to “Terms of Payment” GCC 51 for
expenditures actually incurred prior to the effective date of termination; and
c) Except in the case of termination pursuant failure to perform, insolvency of the
Agency, deliberate false submission by the Agency or for failure to comply with the
final decision of an arbitration process, reimbursement of any reasonable cost
incident to the prompt and orderly termination of the Contract.
40. Assignment 1.95 The Agency shall not assign to any other party, in whole or in part, their
obligations under this Contract.
41. Disclaimer 1.96 Purchaser reserves the right to share, with any agency of its choosing, any
resultant Proposals in order to secure expert opinion.
1.97 Purchaser reserves the right to accept or reject any proposal deemed to be in
the best interest of the SRPC
42. Public Disclosure 1.98 All materials provided to the Purchaser by bidder are subject to Country public
disclosure laws such as RTI etc.
1.99 The Vendor shall not make or permit to be made a public announcement or
media release about any aspect of this Contract unless the Purchaser first gives the
Vendor its written consent.
43. Adherence to safety procedures,
rules regulations and restriction
1.100 Agency shall comply with the provision of all laws including labor laws, rules,
regulations and notifications issued there under from time to time. All safety and
labour laws enforced by statutory agencies and by Purchaser shall be applicable in
the performance of this Contract and Vendor’s Team shall abide by these laws.
1.101 The Agency shall take all measures necessary or proper to protect the
personnel, work and facilities and shall observe all reasonable safety rules and
instructions. Supplier’s Team shall adhere to all security requirement/regulations of
the Purchaser during the execution of the work. Purchaser’s employee also shall
comply with safety procedures/policy.
1.102 The Supplier shall report as soon as possible any evidence, which may indicate
or is likely to lead to an abnormal or dangerous situation and shall take all necessary
emergency control steps to avoid such abnormal ituations.
1.103 The Purchaser will be indemnified for all the situations mentioned
Annexure-VIII
Page 43 of 61
44. Removal and/or Replacement of
Personnel
1.104 Except as the appropriate Purchaser may otherwise agree, no changes shall be
made in the Personnel. If, for any reason beyond the reasonable control of the
Agency, it becomes necessary to replace any of the Personnel, the Agency shall
forthwith provide as a replacement a person of equivalent or better qualifications.
If the Purchaser:
a) Finds that any of the Personnel has committed serious misconduct or has been
charged with having committed a criminal action, OR
b) Has reasonable cause to be dissatisfied with the performance of any of the
Personnel, then the Agency shall, at the Purchaser’s written request specifying the
grounds therefore, forthwith provide as a replacement a person with qualifications
and experience acceptable to the Purchaser.
1.105 The Agency shall bear all additional travel and other costs arising out of or
incidental to any removal and/or replacement, and
1.106 No extra payment is to be made to the agency due to such replacement of
personnel.
45. Fairness & Good Faith 1.107 The Parties undertake to act in good faith with respect to each other's rights
under this Contract and to adopt all reasonable measures to ensure the realization
of the objectives of this Contract.
1.108 Operation of the Contract: The Parties recognize that it is impractical in this
Contract to provide for every contingency which may arise during the life of the
Contract, and the Parties hereby agree that it is their intention that this Contract
shall operate fairly as between them, and without detriment to the interest of either
of them, and that, if during the term of this Contract either Party believes that this
Contract is operating unfairly, the Parties will use their best efforts to agree on such
action as may be necessary to remove the cause or causes of such unfairness, but no
failure to agree on any action pursuant to this Clause shall give rise to a dispute
subject to arbitration in accordance with Clause 14 hereof.
46. Insurance 1.109 The Agency shall take and maintain at their own cost, insurance coverage
against the risks to their personnel and properties relating to this assignment.
47. Conflict of Interest 1.110 The Process Agency shall not engage, and shall cause their Personnel not to
engage, either directly or indirectly, in any business or professional activities which
would conflict with the activities assigned to them under this Contract.
1.111 The Purchaser considers a conflict of interest to be a situation in which a party
has interests that could improperly influence that party’s performance of official
duties or responsibilities, contractual obligations, or compliance with applicable
laws and regulations, and that such conflict of interest may contribute to or
constitute a prohibited corrupt practice.
1.112 If the Agency is found to be involved in a conflict of interest situation with
regard to the present assignment, the Purchaser may choose to terminate this
contract as per Clause 36 of GCC.
48. Standard of Performance 1.113 The Agency shall perform the Services and carry out their obligations
hereunder with all due diligence, efficiency and economy, in accordance with
generally accepted techniques and practices used with professional engineering and
consulting standards recognized by professional bodies, and shall observe sound
management, and technical and engineering practices, and employ appropriate
advanced technology and safe and effective equipment, machinery, materials and
methods. The Agency shall always act, in respect of any matter relating to this
Contract or to the Services, as faithful advisers to the Owner.
49. Expiration of Contract 1.114 Unless terminated earlier pursuant to Clause 36 hereof, this Contract shall
terminate when, pursuant to the provisions hereof, the Services have been
completed and the payments of remuneration and reimbursable expenditures have
been made.
Annexure-VIII
Page 44 of 61
50. Risk Purchase Clause
1.115 In the event of failure of the agency to provide service under this contract
within the stipulated date/period of the order, or in the event of breach of any of
the terms and conditions mentioned in the order, purchaser shall have the right to
procure such service from elsewhere after due notice to the defaulting agency at
the risk and cost of the defaulting agency. In the event of failure of the agency as
detailed above, the cost as per risk purchase exercise may be recovered from the
bills against any other contracts pending in purchaser.
51. Payment Schedule 1.116 The bidders may please note that the prices are Firm. All statutory taxes,
levies, duties, etc. shall be paid on actual.
Payment Terms:
The bidder shall quote VAT TIN, Service Tax Registration No. and PAN No. in the
offer.
Payment would be released via account payee cheque after deduction of statutory
dues such as TDS/eSTDS, etc.
Rates quoted shall remain firm till the completion of work. Rates are not subject to
revision under any circumstances.
Payment will be released on presentation of bills in triplicate via account payee
cheques/RTGS/NEFT within 60 days after completion of milestones and the same
being certified by the competent authority as per the following schedule.
For payment against Part A price(see price bid)
10% on submission of High level design document for implementation of
web based protection management system to SRPC.
25 % of the order value on delivery of 35 No of base license of protection
calculation engine along with laptops
5 % of the order value after completion of Training program on the desktop
based protection setting calculation software.
10 % of the order value after Building the network data for operational load
flow and fault calculation
15 % of the order value on completion of Protection database and
substation SLD preparation for protection study
10 % of the order value on delivery of required server hardware
10 % of the order value on delivery of web based database management
system
5 % of the order value on completion of Site Acceptance Tests with one pilot
state system
10 % of the order value after uploading all SRPC constituent data along with
SLD and Go Live.
For payment against Part B price(see price bid)
20% on completion of each annual support period.
The Certificate of Completion in respect of the works referred to in 1.116 above
shall not absolve the Agency from its liability to make good any defects
imperfections, shrinkages or faults which may appear during the period of
maintenance specified in the tender arising in the opinion of the Engineer from
materials or workmanship not in accordance with the drawings or specifications or
instruction of the Engineer, which defects, imperfections, shrinkages or faults shall
upon the direction in writing of the Engineer be amended and made good by the
Agency at his own cost; and in case of default on the part of Agency, the Engineer
may employ labour and materials or appoint another Agency to amend and make
good such defects, imperfections, shrinkages and faults and all expenses
Annexure-VIII
Page 45 of 61
consequent thereon and incidental thereto shall be borne by the Agency and shall
be recoverable from any moneys due to him under the contract.
52. Monitoring Mechanism 1.117 Competent Authority shall nominate a monitoring committee for certification
of completion of milestones. No payment shall be released unless the competent
authority is satisfied with the completion of works envisaged as per the milestones.
The competent authority may design acceptance tests for some or all of the
milestones envisaged in the project within the overall scope of works and the
agency shall satisfy the competent authority with regard to the correctness of
response /performance of the system. The competent authority may choose to be
advised by technical experts from relevant field with respect to the design of
acceptance tests.
53. Acceptance Tests: 1.118 A list of the various planned tests and a brief explanation follows below:
Functionality Testing-Execute each function, using valid & invalid data to verify
the following: The expected result occurs when valid data used. The
appropriate error / warning messages are displayed when invalid data is used.
Integration Testing-Integration testing ensure that interface of coupling
between the module is working fine. The goal here is to see if the modules can
be integrated properly. Hence the emphasis is on testing interface between
modules.
System Testing- The System tests will focus on the behavior of the application.
Conditions specified in Software Requirement Specification will be executed
against the system and error message testing. Overall, the system tests will test
the system testing and verify that it meets the requirements defined in the
requirements document.
User Acceptance Testing-The purpose of these tests is to confirm that the
system is developed according to the specified user requirements and is ready
for operational use. Acceptance Testing checks the system against the
"Requirements". It is similar to systems testing in that the whole system is
checked but the important difference is the change in focus.
54. Guaranteed Availability and
Penalty
1.119 The supplier shall ensure that the Guaranteed Availability of the application
system shall not be less than 95% (Ninety five percent) during the period of 5 years
from the date of ‘go live’ on quarterly basis.
The following calculation shall determine the availability of the total system:
Scheduled Available Time – Downtime
% Availability = -------------------------------------------------------------------X 100
Scheduled Available Time
Scheduled Available time shall equate to 24 hours x 7 days per week.
In the event that the application system fails to achieve the guaranteed availability
as mentioned above, aggregated over the quarter, during 5 years period from the
date of ‘go live, SRPC shall be at liberty of deducting 1% contract value for every
percent reduction in availability from the agency’s bills/performance security as
penalty.
Annexure-VIII
Page 46 of 61
Annexure-A
From: <Bidder> (On official letterhead)
To: The Member Secretary, SRPC, No. 29 Race Course Cross Road Bangalore-560 009 Sir, I/we ____________________________________Consultant / Developer Firm herewith enclose our bid for
appointment of my/our firm as the agency for implementation of________________. I/We hereby accept and abide by the
scope & terms and conditions of NIQ document unconditionally.
Yours faithfully,
Signature: _________________ Full Name: _________________ Address: _________________
Annexure-VIII
Page 47 of 61
A. Proforma for Submission of Technical bid for Creation and maintaining a Protection Database and desktop based Protection Settings calculation tool for Southern Regional Grid
1 Name of Agency
2 Profile of the agency(in brief)
3 Name of proprietor/Director of the Agency
4 Full Address of Registered Office
a. Telephone No.
b. Fax No.
c. E-Mail address
5 Full Address of Local Office (ER)
6 a. Telephone No.
b. Fax No.
c. E-mail Address
7 All necessary supporting documents as mentioned in the technical qualification criteria as per
checklist
B.CHECK LIST for documents (to be self attested) to be enclosed with Technical Bid:
Sl.No Documentary proof of Attached (Y/N)
1. Completed at least ONE Job with the protection modeling, database building, simulations and setting calculation to a large transmission purchaser with more-than 150 plus sub-stations with the voltage level of 400kV to 132kV in the last 7(seven) years ending 31.03.2016. PO/WO/Completion Letter/Reference letter/Payment received
2. The proposed Protection analysis software must be in use for at least seven (7 ) years ending 31.03.2016 in any Indian State Electricity Boards /transmission companies. PO/WO/Completion Letter/Reference letter/Payment received
3. Details of software development center, technical and support team for support in India such as address, phone no and name of relevant personnel along with their designation should be provided
4. Average turnover for the past three financial years that is
Annexure-VIII
Page 48 of 61
from 01.04.2013 to 31.03.2016 at least Rs. XXXXX/- Crores (Rupees XXXXX in words). Certificate from CA is to be submitted.
5. Tenderer must have the web based protection database software which can be customized to SRPC requirement and will be able to build/model the different manufactures relays. The software must have been in use for at elast last 7 years ending 31.03.2016. Copy of PO/WO/Completion Letter/Reference letter/Payment received
6. The tenderer must be able to assign minimum 20 number of power system & protection engineer on his role full time with Electrical Engineering degree for the works involved in the project. Attach Resume (Annexure B) with proposed work allocation such as data collection, update of database, database engineer, power system engineer, etc
7. The tenderer should have an office set up for technical support in the Southern region. Provide full address, telephone, fax, email address and contact personnel.
8. Whether work is proposed to be outsourced?
9. Has the bidder been blacklisted by any Government organization? If no then give declaration as per Annexure E
10. The bidder must have completed at least THREE works of not less than Rs. XXXXX/- Crores each OR at least TWO works of not less than Rs. XXXXX/- Crores each OR ONE work of not less than Rs. XXXXX/- Crores for power system analysis software development/supply for electrical utility in the last seven financial years that is from 01.04.2009 to 31.03.2016. Proof of the same like PO/WO/Completion Letter/ Reference letter/Payment received should be submitted along with the bid (cost should not include Hardware cost, taxes and not including any AMC component)
11. The bidder must have completed at least THREE works of not less than Rs. XXXXX/- Crores each OR at least TWO works not less than Rs. XXXXX/- Crores OR at least ONE work of not less than Rs. XXXXX/- Crores for protection system modeling database building and maintenance along with supply of software in power sector in the last seven financial years that is from 01.04.2009 to31.03.2016. Proof of the same like PO/WO/Completion Letter/ Reference letter/Payment received should be submitted along with the bid (Except hardware and before taxes and not containing any AMC component)
12.
The bidder must submit banker’s solvency certificate for at least Rs. XXXXX Crores (Rupees XXXXX in words only). Submit certificate from bank.
Annexure-VIII
Page 49 of 61
13. Should have worked with at least one power utility in India for providing IT consulting (power system analysis software tool development/supply, data collection and database building activities) , in the last three financial years from 01.04.2013-31.03.2016.
14. Should have positive net worth in the last three audited financial years ended 31.03.2016. Submit certificate from CA
15. Power of Attorney as per format in Annexure
16. Manufacturer’s Authorization Form
17. Additional Information, if any which bidder intends to submit along with the tender like quality certifications
18. VAT/CST of the bidder. Please enclose copies
19. EMD draft. Please Enclose
20. Brief note on the work as understood by the bidder including a plan of action along with pert chart and proposed system architecture including details of hardware and software proposed with their technical specifications. Detailed methodology for executing the complete assignment along with key points. Deliverables and detailed technical specifications
21. Copies of latest service tax and income tax returns. Please submit return for last three years ending 31.03.2016.
22. Copy of PAN card, service tax registration certificate, VAT TIN registration certificate (if applicable)
23. Copy of registration certificate of the company of bidder/lead bidder
24. Turn-over certificate and P&L statement of past three financial years certified by CA.
25. Copies of ISO 9001 certification for software development and consultancy
26. Listing with NIC documentary evidence copy thereof in respect of bidder/lead bidder
27. Copy of the tender document signed on all the pages. Enclose copy
28. Receipt of tender fees to be enclosed.
C. Demonstration during Technical Evaluation:
Sl. No.
Key Functionality Availability
Yes No
01
Protection database software demonstration-it should be able to produce SLDs showing key protection elements along with the CT, PT, and different type of Relays modeled, run a sample base case LF on data provided, add/update various relay setting in the database and show their operation by simulating a fault.
Annexure-VIII
Page 50 of 61
02
Key protection simulation functionality as at Annexure-A (Technical bid) shall be complied and confirmation documents shall be submitted along-with the bid. The same shall be demonstrated for the technical evaluation committee of SRPC.
03 Web Based Protection Database Management System with User Role management and tracking the details
04 Enhanced database creation including detailed modeling of all relay elements with standard libraries
05 Possible to create user defined Relay template and life cycle management of the relay
06 Possible to reduce Regional/ Bigger Transmission Network to equivalent network and to perform EMTP Simulation
07 Distance Relay simulation and showing the zone of Operation in the graph of R/X plot
08 Relay co-ordination can be conducted for relays of all make and with user defined characteristics for over current and earth fault relays.
09 Automatic / Interactive / Manual Primary-back-up relay pairs generation
10 Simulation of relay responses for the program Computed & Existing Field settings of the relays
11 Highlighting of Relay Operational Sequence after the analysis.
12 Fault simulation and relay trip currents plotted on the SLD for different type of fault currents including user defined fault current.
13 Fault Simulation and Relay trip sequence on the SLD and showing the sequence of relay pick-up.
14 Unit protection of Transformers/lines
15 Attaching the COMTRADE file to the Relay for analysis.
16 Performing the analysis of the single file COMTRADE file for the associated relay through the network element modeled.
17 Viewing of Analog and Digital plots of disturbance files stored in the relay using the COMTRADE Viewer.
18 Merging of two existing COMTRADE files received from disturbance recorder and removing unwanted channels and storing as a new COMTRADE file for further processing.
19 EMTP analysis for the given network and generating COMTRADE files to match with the disturbance records as part of the Post-mortem analysis.
20 Under frequency and df/dt relay modeling and simulation of load shedding schemes.
21 Possible to model user defined control block for simulation of AVR, Governor and special protection schemes.
Annexure-VIII
Page 51 of 61
Annexure B
The following are the minimum Human Resource requirements to be deployed for the execution of the
tender(CV of the personnel proposed to be entrusted to be enclosed with detailed experience)
Key Personnel Qualifications/Experience No
Power System Advisors and Team Leader
He/ She should be Ph.D holder in power systems domain with 20 years of power system and protection field. He/ She should have advised several projects in protection and one project for complete modeling of network with protection elements and database modeling
2
Senior Power System Consultants
He/ She should be Bachelor/ Master’s Degree with more than 10 years of experience in transmission system protection analysis and studies.
2
Software Consultants/Experts
He/ She should be Bachelor/Master’s Degree with more than 7 years’ of experience in designing database concepts for power system products. He/she should have experience in handling data base structures for any reputed power system domain applications. He/ She should have successfully completed the implementation of database structure design for any power system application under reputed projects of India in the past 3 years.
2
Power System Engineers
He/She should be Bachelor /Master’s Degree holder in Electrical Engineering and should have minimum 3 years’ experience in power system consulting services and protection system
20
The format for submission of CVs is the following:
………………………………………………………………………………………………………………………………………………………………………
1. Name: __________________________________________________________
2. Profession / Present Designation: ____________________________________
3. Years with firm: ____________________Nationality: ____________
4. Area of Specialization: ___________________________________________
5. Proposed Position on Team: ______________________________________
6. Key Qualification/Experience: (Under this heading give outline of staff members experience and training most pertinent to assigned work on proposed team. Describe degree of responsibility held by staff member on relevant previous assignments and give dates and locations. Use up to half-a-page.)
7. Education: (Under this heading, summarize college/ university and other specialized education of staff member, giving names of colleges, dates and degrees obtained. Use up to quarter page.)
8. Experience: (Under this heading, list of positions held by staff member since graduation, giving dates, names of employing organization, title of positions held and location of assignments. For experience in last ten years also give types of activities performed and Owner references, where appropriate. Use up to three quarters of a page.
9. Language: (Indicate proficiency in speaking, reading and writing of each language by “excellent‟,
Annexure-VIII
Page 52 of 61
“good‟ or “poor‟).
Signature : _________________
Full Name : _________________ Address : _________________
Date : _________________
Kindly ensure that the relevant work experience and its applicability to the present assignment are clearly articulated. The CVs should not be longer than 4 type-written pages.
Signature : _________________ Seal:
Full Name : _________________ Address : _________________
………………………………………………………………………………………………
Annexure-VIII
Page 53 of 61
Annexure C
PROFORMA FOR PRICE BID TO BE SUBMITTED BY BIDDER
Creation and maintaining a web based Protection Database and desktop based Protection settings calculation tool for Southern Regional Grid
Sl No Item Price Quote
Part A. Price for completion of High level design, Web based database management tool-1 License, desktop based Protection settings calculation & Analysis tool with laptop computers - 35 Licenses, User Manuals- 35 sets, Associated servers for installation and Deployment of application and database software along with standard Operating, Training for 5 days at SRPC/SRLDC premise and 5 days at each constituent premises including printed reading material/soft files and all activities up to Go Live.
Part B 5 year comprehensive Support after Go Live including incorporation of any new network configuration, addition of new substation, change of relays, settings, CT/PT, support for database software, setting calculation tool and various analysis engines updates.
Total contract price* to be considered for determination of L1 party (Part A+PartB):
Part C
Taxes as applicable (estimated)
Part D
Grand Total (Part A+ Part B + Part C):
Date:.................... (Signature).................................
Place:.....................
Name.....................
Designation......…...
(Common Seal)
*The agency shall not be entitled to any other payments other than contract price and statutory taxes as applicable.
**The prices shall remain FIRM till completion of the Assignment.
Annexure-VIII
Page 54 of 61
Annexure-D
Guarantee Declaration by Bidder
Bidder’s Name and Address: To: The Member Secretary
Southern Regional Power Committee,
No. 29, Race Course Cross Road,
Bengaluru-560 009
Dear Sir,
1. We confirm that the services offered including all hardware, software and database building works shall have minimum performance specified in Technical Specification.
2. We further guarantee the performance/efficiency of all hardware, software and database building
works in response to the Technical Specifications.
Date:.................... (Signature).................................
Place:.....................
Name.....................
Designation......…...
(Common Seal)
Annexure-VIII
Page 55 of 61
Annexure-E
UNDERTAKING BY BIDDER
1. I,Son/Daughter/WifeofShri……………….…………..………………………………………………………,Proprietor/Director/authorizedsignatoryof………………………………..,is competent to sign this declaration and execute this tender document;
2. I, have carefully read and understood all the terms and conditions of the tender and undertake
to abide by them.
3. The information/documents furnished along with the above application are true and
authentic to the best of my knowledge and belief. I/we, am/are well aware o f the fact that furnishing of any false information/ fabricated document would lead to rejection of my tender at any stage besides liabilities towards prosecution under appropriate law.
4 Certified that no investigations is pending/legal action contemplated against
…………………………………….(name of agency) by any government authority to the best of my knowledge and belief.
5. Certified that the agency has not been blacklisted/ security deposit has not been forfeited in
case of the agency during the last five years.
Date:.................... (Signature).................................
Place:.....................
Name.....................
Designation......…...
(Common Seal)
Annexure-VIII
Page 56 of 61
Annexure-F MANDATE FORM ELECTRONIC FUND TRANSFER/ RTGS TRANSFER
To The Member Secretary, Southern Regional Power Committee No. 29 Race Course Cross Road Bangalore-560 009 Sub: Authorization for release of payment / dues from Southern Regional Power Committee, Bangalore through Electronic Fund Transfer / RTGS Transfer:
1. Name of the Party / Firm/ Company/ Institute:
2. Address of the Party: City _________________________________ Pin code _________________ E-mail ID _____________________________ Mob No: _________________ Permanent Account Number _______________________________________
3. Particulars of Bank
Bank Name Branch Name
Branch Place Branch City
Pin Code Branch Code
MICR No
(9 Digit number appearing on the MICR Bank of the Cheque supplied by the Bank, Please attach a Xerox copy of a cheque of your bank for ensuring accuracy of the bank name , branch name and code number)
IFS Code: (11 digit alpha numeric code)
Account Type Savings Current Cash Credit
Account Number
DECLARATION I hereby declare that the particulars given above are correct and complete. If any transaction delayed and not effected for reasons of incomplete or incorrect information I shall not hold, Southern Regional Power Committee, Bangalore responsible. I also undertake to advise any change in the particulars of my account to facilitate updating of records for purpose of credit of amount through NEFT/ RTGS Transfer. Place: _____________________ Date: _____________________ Signature & Seal of the Authorized Signatory of he Party
Certified that particulars furnished above are correct as per our records. Bankers Stamp: Date: Signature of the Authorized Official from the Bank N.B: Please fill in the information in CAPITAL LETTERS, computer typed; please Tick wherever it is applicable.
Annexure-VIII
Page 57 of 61
Annexure-G BANK GUARANTEE FORMAT FOR PERFORMANCE SECURITY
To The Member Secretary, Southern Regional Power Committee No. 29 Race Course Cross Road Bangalore-560 009. WHEREAS M/s _________________________ having its office at _______________________________ (hereinafter referred to as the “ Supplier”) which expression shall repugnant to the context or meaning thereof, include its successors, administrators, executors and assigns), in pursuance of the Work Order/LOA No. ____________________ dated __________________________ has undertaken for execution of ___________________________ (hereinafter referred to as the “ Contract”) on behalf of Southern Regional Power Committee, Bangalore ( hereinafter referred to as the “ Purchaser”) AND WHEREAS it has been stipulated by you in the said contract that the “ Supplier” shall furnish you with a irrevocable bank guarantee by a Scheduled Commercial Bank for the sum specified therein as security for compliance with its obligations in accordance with the contract: AND WHEREAS we have agreed to give the “ Supplier” such a bank guarantee NOW THEREFORE we hereby affirm that we are guarantors and responsible to you, on behalf of the Supplier and we undertake to pay you, upon your first written demand declaring the “Supplier” to be in default under the contract and without cavil or argument, any sum or sums within the limits of (Rupees ____________________ as aforesaid, without your needing to prove or to show grounds or reasons for your demand or the sum specified therein. We hereby waive the necessity of your demanding the said debt from the Supplier before presenting us with the demand. We further agree that no change or addition to or other modification of the terms of the contract to be performed there under or of any of the contract documents which may be made between you and the Supplier shall in any way release us from any liability under this guarantee and we hereby waive notice of any such change, addition or modification. This guarantee shall be valid until the (Signature of the authorized officer of the Bank) .................................................................................. Name and Designation of the Officer …………………………………………………………………………….. Seal,name& address of the Bank and Address of the Branch.
Note:
1. The stamp papers of appropriate value shall be purchased in the name of bank who issues the `Bank Guarantee‟.
2. PBG should remain valid for a period of sixty days beyond the end of support period. 3. PBG Should be from a schedule commercial bank operating in India as approved by RBI. 4. It should be send directly by the banker of the vendor to Member Secretary, Southern Regional
Power Committee, Bangalore.
Annexure-VIII
Page 58 of 61
Annexure-H
MANUFACTURER’S AUTHORIZATION FORM
The Bidder shall require the Manufacturer to fill in this Form in accordance with the instructions indicated. This letter of authorization should be on the letterhead of the Manufacture and should be signed by a person with the proper authority to sign documents that are binding on the Manufacturer. Date: [ insert date (as day, month and year) of Bid submission] Tender No. [ insert number from Invitation For Bids] To: [ insert complete name and address of Purchaser] WHEREAS We [ insert complete name of Manufacturer] who are official manufacturers of [insert type of goods manufactured], having factories at [insert full address of Manufacturer’s factories], do hereby authorize [insert complete name of Bidder] to submit a bid the purpose of which is to provide the following Goods, manufactured by us [insert name and or brief description of the Goods] and to subsequently negotiate and sign the Contract. We hereby extend our full guarantee and warranty in accordance with the General Conditions of Contract, with respect to the Goods offered by the above firm. Signed:[ insert signature(s) of authorized representatives(s) of the Manufacturer] Name:[ insert complete name(s) of authorized representative(s) of the Manufacturer] Title: [insert title] Duly authorized to sign this Authorization on behalf of : [insert complete name of Bidder] Dated on ___________________ day of _______________________ , _____________ [insert date of signing]
Annexure-VIII
Page 59 of 61
Annexure-I
Agreement (On Non-Judicial Stamp Paper of appropriate value to be arranged by the agency)
THIS AGREEMENT is made this ________ day of ________________________, _____, between Southern Regional Power Committee (hereinafter called “SRPC”/”Purchaser”/”Owner”), of the one part, and __________________________________ of ______________________________ (hereinafter called “THE
Agency”/”Supplier”), of the other part: AND WHERAS the Purchaser invited bids for Related Services, viz.,
____________________________________________________________________ and has accepted a Bid
by the Consultant for the supply of those Related Services in the sum of ________________________________________________________ (hereinafter Called “the Contract Price”). NOW THIS AGREEMENT WITNESSETH AS FOLLOWS:
2. In this Agreement words and expressions shall have the same meanings as are respectively assigned to them in the Contract referred to.
3. The following documents (collectively referred to as “Contract Documents”) shall be deemed to form and be read and construed as part of this Agreement, viz.:
i. All provisions of Tender vide Reference No- Tender ID- Tender Name
including all Annexures/Appendices; ii. Vendor’s response (proposal) to the RFP, including the Bid Submission Sheet and the
Price Schedules submitted by the Supplier; i. The Purchaser’s Notification to the Supplier for Letter of Intent;
ii. Acceptance of purchaser’s notification iii. The Purchaser’s Notification to the Supplier for Letter of Award;
3. In consideration of the payments to be made by the Purchaser to the Agency as indicated in this Agreement, the Agency hereby covenants with the Purchaser to provide the Related Services and to remedy defects therein in conformity in all respects with the provisions of the Contract.
4. The Purchaser hereby covenants to pay the Consultant in consideration of the provision of the Goods and Related Services and the remedying of defects therein, the
Contract Price or such other sum as may become payable under the provisions of the Contract at the times
and in the manner prescribed by the Contract. IN WITNESS whereof the parties hereto have caused this
Agreement to be executed in accordance with the laws of ________________________ on the day, month
and year indicated above.
Signed by __________________________________________ (Authorized official on behalf of purchaser)
Signed by ___________________________________________(Authorized official on behalf of Supplier)
Annexure-VIII
Page 60 of 61
Annexure-J
CERTIFICATE AS TO CORPORATE PRINCIPAL
(To be signed by any of Board Directors or Company Secretary)
I _______________________ certify that I am _________________ of the Company under the laws of
_____________________ and that __________________ who signed the above tender is authorized to bind the Company
/ Firm by authority of its governing body.
Signature : _________________ Seal: Full Name : _________________ Address : _________________
Annexure-VIII
Page 61 of 61
Annexure-K
Approach and Methodology
Please provide details of methodology to be followed for successful implementation of the project. Please provide the details of the following:
a. UNDERSTANDING OF THE UTILITY AND ITS REQUIREMENTS (Also provide Prior interaction with Utility, if any) b. DETAILS OF METHODOLOGY c. PROJECT MANAGEMENT OFFICE STRUCTURE d. RESOURCE PLANNING AND ESTIMATION INCLUDING HARDWARE AND SOFTWARE
PROPOSED TO BE SUPPLIED e. RISK MANAGEMENT*
*Kindly provide a detailed list of all risks envisaged during the execution of the assignment and specify how the firm/consortium plans to mitigate each of them. Please also indicate the seriousness of each risk envisaged on a scale of 1 to 5 with 1 being “Not Serious‟ and 5 being “Very Serious‟.
Signature : _________________ Seal: Full Name : _________________ Address : _________________
Annexure-VIII