basic tests for transformers

Upload: hoosman-monroy-rojas

Post on 04-Apr-2018

220 views

Category:

Documents


0 download

TRANSCRIPT

  • 7/29/2019 Basic Tests for Transformers

    1/4

    POWER ELECTRONICS

    BASIC TESTS FOR TRANSFORMERS

    Mario Alejandro Chaparro

    Hoosman Monroy

    OBJECTIVES:

    Understand the operation of a

    transformer and introduce in the technical

    language used in the rules.

    Based on the Colombian technicalregulations do various tests required for

    optimal performance and characteristics

    of transformers.

    As the NTC 380 tests carried out to

    demonstrate compliance with specific

    requirements that are not covered by

    routine tests.

    Given the NTC 375: 2000 take the

    measurement of the resistance of thewindings in transformers used in practice.

    Using the provisions of NTC 471, check

    the transformer turns ratio.

    I. THEORETICAL

    FRAMEWORK.

    a. TRANSFORMER

    The transformer is an electrical device

    using the physical properties of

    electromagnetic induction is able to raise

    and lower the voltage, convert the

    frequency (Hz), balanced or unbalanced

    circuits as needed and the specific case.

    Transporting electricity from power

    generating electricity to domestic

    residences, businesses and industries.

    Said device is also electrical circuits

    capable of isolating circuitry AC current.

    b. Measure the resistance of the

    windings. NTC375

    According to the NTC 375.

    Measuring the resistance of the

    transformer windings, is used inter alia, to

    check the connections and determine if

    an open circuit condition or the existence

    of a high resistance connection

    conductors arranged in parallel.

    Applicable to distribution transformers

    and power.

    This trial is of fundamental importance to

    Calculate the losses ^ 2 * R

    Control and field maintenance.

    Comparison of phases.

    Detect problems circuital partial short.

  • 7/29/2019 Basic Tests for Transformers

    2/4

    POWER ELECTRONICS

    Check the operation of the tap changer

    perfect.

    METHOD.

    Method voltage ohmmeter or bridge:

    The instructions are performed following

    the manual instructions in order to select

    the most appropriate ranges. Wheatstone

    bridge, wherein R, R1 and RX R2son

    known resistances and represents the

    winding resistance which the

    measurement is made.

    The resistance of each winding, the

    terminals between which is measured

    and the temperature of the windings to be

    recorded. The measurement is done with

    direct current. All resistance

    measurements inductive effects should

    be minimized.

    c. Measurement of the ratio, and

    polarity verification phase

    relationship. NTC 471

    Voltmeter Method

    It consists in applying a sinusoidal

    alternating voltage of known value to the

    higher voltage winding, measuring this

    voltage and which appears in the other

    winding by means of appropriate

    transformers and voltmeters. The ratio ofthe two voltages measured will be the

    transformation ratio. The voltmeter

    should read simultaneously. It should be

    a second reading voltmeters exchange,

    will take the average of the two readings

    to compensate for instrument error.

    Transformer Method pattern

    Consists in comparing the voltage of the

    transformer under test with the calibrationpattern of a transformer, whose

    relationship is adjustable in small steps.

    With this method, the transformer and the

    test pattern are connected in parallel and

    voltage is applied to its high-voltage

    windings, while the lower windings are

    connected to a sensitive detector which

    takes zero indication transformer ratio

    adjusting pattern . At this point, the

    relationship of both transformers are

    equal.

    d. PROCEDURE FOR THE

    DETERMINATION OF NO LOAD

    LOSSES

  • 7/29/2019 Basic Tests for Transformers

    3/4

    POWER ELECTRONICS

    The maximum flux density corresponds

    to the absolute average value of the

    voltage (NAM effective value rms) and

    therefore, if the average value of the

    voltage is set to quesea equal to the

    average value of the sinusoidal wavevoltage and maintains the desired

    appropriate frequency, the hysteresis

    loss should be corresponding to the

    desired sinusoidal waveform.

    II. Calculations and operations

    Turns ratio

    Connecting a laboratory autotransformer

    (variac) to the transformer primary, a

    voltmeter measuring the voltage at the

    primary and secondary induced voltage,

    as shown in the circuit of Figure.

    Turns ratio of the transformer

    a

    N

    V1 1

    N2 V2

    V1 V2

    119.8 29.9

    Table 1. Measurements of the voltage

    ratio.

    As the turns ratio of the primary to the

    secondary of the transformer

    corresponds to 4

    Number of turns of the primary

    The procedure consists of applying the

    nominal voltage corresponding to the

    winding for measuring the voltage

    induced in one or several turns of wire

    previously wound on the transformer

    windings. The ratio of voltage and power

    (s) return (s) sets the number of turns of

    winding. This test rolled

    four turns through the window of the

    transformer.

    Number of turns of the primary

    V1 V4vueltas

    119.8 0.8858

    Table 2. Measuring the number of

    primary turns.

    IDENTIFICATION OF THE POLARITY

    To perform this test is fed to the

    transformer primary with nominal voltage,

    previously connected with one terminal of

    the primary side as shown in Figure 10.

    Connect a voltmeter between the primary

    and secondary terminals that are

    available. If the reading obtained is the

  • 7/29/2019 Basic Tests for Transformers

    4/4

    POWER ELECTRONICS

    remainder of the primary voltage and

    secondary marks are placed on the

    terminals where the voltmeter is

    connected. If the reading is the sum, the

    polarity must be one in the terminal

    where the voltmeter and the other in theterminal where he joined the primary and

    the secondary.

    Identification of the polarity markings.

    WINDING RESISTANCES

    Measure the resistance of each winding,

    previously with a multimeter to be a

    reference to its value. Then applied volt-

    ammeter method feeding a direct current

    source such that the winding rated

    current flow. Applying Ohm's law relate

    measurements voltmeter and ammeter

    and determined resistance. This process

    must be performed for both windings.

    V I

    2.5708 V 0.2588 A

    TEST SHORTED

    This test is performed at rated current,

    connect the low side short and gradually

    increased from zero the voltage fed to the

    primary. In this test, the core losses are

    neglected because the voltage is too low.

    Connecting the short circuit test.

    V IRetraso de corriente

    5.528 V 0.255 A 2.1 ms

    Table. Measurements of short-circuit

    proof.

    CONCLUSIONS

    En el presente informe se presenta en forma

    integral las etapas de medicin de un

    transformador de pequea capacidad,

    adems de establecer las pruebas fsicas y

    elctricas estndar de los transformadores.

    REFERENCES

    [1] Mark N. Horesntein. Microelectronics

    circuit and processors. 2 edition p. 125 to

    130

    [2]

    http://www.labc.usb.ve/gfernandez/Ec_38

    81/webs/Enero_Marzo_2006/diagrama_b

    loque.pdf