basic tests for transformers
TRANSCRIPT
-
7/29/2019 Basic Tests for Transformers
1/4
POWER ELECTRONICS
BASIC TESTS FOR TRANSFORMERS
Mario Alejandro Chaparro
Hoosman Monroy
OBJECTIVES:
Understand the operation of a
transformer and introduce in the technical
language used in the rules.
Based on the Colombian technicalregulations do various tests required for
optimal performance and characteristics
of transformers.
As the NTC 380 tests carried out to
demonstrate compliance with specific
requirements that are not covered by
routine tests.
Given the NTC 375: 2000 take the
measurement of the resistance of thewindings in transformers used in practice.
Using the provisions of NTC 471, check
the transformer turns ratio.
I. THEORETICAL
FRAMEWORK.
a. TRANSFORMER
The transformer is an electrical device
using the physical properties of
electromagnetic induction is able to raise
and lower the voltage, convert the
frequency (Hz), balanced or unbalanced
circuits as needed and the specific case.
Transporting electricity from power
generating electricity to domestic
residences, businesses and industries.
Said device is also electrical circuits
capable of isolating circuitry AC current.
b. Measure the resistance of the
windings. NTC375
According to the NTC 375.
Measuring the resistance of the
transformer windings, is used inter alia, to
check the connections and determine if
an open circuit condition or the existence
of a high resistance connection
conductors arranged in parallel.
Applicable to distribution transformers
and power.
This trial is of fundamental importance to
Calculate the losses ^ 2 * R
Control and field maintenance.
Comparison of phases.
Detect problems circuital partial short.
-
7/29/2019 Basic Tests for Transformers
2/4
POWER ELECTRONICS
Check the operation of the tap changer
perfect.
METHOD.
Method voltage ohmmeter or bridge:
The instructions are performed following
the manual instructions in order to select
the most appropriate ranges. Wheatstone
bridge, wherein R, R1 and RX R2son
known resistances and represents the
winding resistance which the
measurement is made.
The resistance of each winding, the
terminals between which is measured
and the temperature of the windings to be
recorded. The measurement is done with
direct current. All resistance
measurements inductive effects should
be minimized.
c. Measurement of the ratio, and
polarity verification phase
relationship. NTC 471
Voltmeter Method
It consists in applying a sinusoidal
alternating voltage of known value to the
higher voltage winding, measuring this
voltage and which appears in the other
winding by means of appropriate
transformers and voltmeters. The ratio ofthe two voltages measured will be the
transformation ratio. The voltmeter
should read simultaneously. It should be
a second reading voltmeters exchange,
will take the average of the two readings
to compensate for instrument error.
Transformer Method pattern
Consists in comparing the voltage of the
transformer under test with the calibrationpattern of a transformer, whose
relationship is adjustable in small steps.
With this method, the transformer and the
test pattern are connected in parallel and
voltage is applied to its high-voltage
windings, while the lower windings are
connected to a sensitive detector which
takes zero indication transformer ratio
adjusting pattern . At this point, the
relationship of both transformers are
equal.
d. PROCEDURE FOR THE
DETERMINATION OF NO LOAD
LOSSES
-
7/29/2019 Basic Tests for Transformers
3/4
POWER ELECTRONICS
The maximum flux density corresponds
to the absolute average value of the
voltage (NAM effective value rms) and
therefore, if the average value of the
voltage is set to quesea equal to the
average value of the sinusoidal wavevoltage and maintains the desired
appropriate frequency, the hysteresis
loss should be corresponding to the
desired sinusoidal waveform.
II. Calculations and operations
Turns ratio
Connecting a laboratory autotransformer
(variac) to the transformer primary, a
voltmeter measuring the voltage at the
primary and secondary induced voltage,
as shown in the circuit of Figure.
Turns ratio of the transformer
a
N
V1 1
N2 V2
V1 V2
119.8 29.9
Table 1. Measurements of the voltage
ratio.
As the turns ratio of the primary to the
secondary of the transformer
corresponds to 4
Number of turns of the primary
The procedure consists of applying the
nominal voltage corresponding to the
winding for measuring the voltage
induced in one or several turns of wire
previously wound on the transformer
windings. The ratio of voltage and power
(s) return (s) sets the number of turns of
winding. This test rolled
four turns through the window of the
transformer.
Number of turns of the primary
V1 V4vueltas
119.8 0.8858
Table 2. Measuring the number of
primary turns.
IDENTIFICATION OF THE POLARITY
To perform this test is fed to the
transformer primary with nominal voltage,
previously connected with one terminal of
the primary side as shown in Figure 10.
Connect a voltmeter between the primary
and secondary terminals that are
available. If the reading obtained is the
-
7/29/2019 Basic Tests for Transformers
4/4
POWER ELECTRONICS
remainder of the primary voltage and
secondary marks are placed on the
terminals where the voltmeter is
connected. If the reading is the sum, the
polarity must be one in the terminal
where the voltmeter and the other in theterminal where he joined the primary and
the secondary.
Identification of the polarity markings.
WINDING RESISTANCES
Measure the resistance of each winding,
previously with a multimeter to be a
reference to its value. Then applied volt-
ammeter method feeding a direct current
source such that the winding rated
current flow. Applying Ohm's law relate
measurements voltmeter and ammeter
and determined resistance. This process
must be performed for both windings.
V I
2.5708 V 0.2588 A
TEST SHORTED
This test is performed at rated current,
connect the low side short and gradually
increased from zero the voltage fed to the
primary. In this test, the core losses are
neglected because the voltage is too low.
Connecting the short circuit test.
V IRetraso de corriente
5.528 V 0.255 A 2.1 ms
Table. Measurements of short-circuit
proof.
CONCLUSIONS
En el presente informe se presenta en forma
integral las etapas de medicin de un
transformador de pequea capacidad,
adems de establecer las pruebas fsicas y
elctricas estndar de los transformadores.
REFERENCES
[1] Mark N. Horesntein. Microelectronics
circuit and processors. 2 edition p. 125 to
130
[2]
http://www.labc.usb.ve/gfernandez/Ec_38
81/webs/Enero_Marzo_2006/diagrama_b
loque.pdf