base column connections eng

Upload: hsbasavaraj

Post on 10-Apr-2018

235 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/8/2019 Base Column Connections Eng

    1/14

  • 8/8/2019 Base Column Connections Eng

    2/14

    820 L. Di Sarno et al. / Journal of Constructional Steel Research 63 (2007) 819832

    steel base plate connection. The latter was designed in

    compliance with the rules utilized for the composite frame

    tested at JRC Ispra laboratory [3,14]. Several tests under either

    monotonic or cyclic lateral loads and different levels of axial

    loads were performed. This work focuses on the response

    of composite columns under monotonic regime, i.e. pushover

    tests. The results of the experiments carried out on specimenswith welded base steel plate (traditional) and socket-type joints

    are discussed. It is found that for the traditional connections,

    concentrations of inelastic demand occur in the anchorage

    bolts and relies chiefly on bond type mechanisms. This type

    of structural response is assessed with a simplified fibre-

    based numerical model. The latter allows the evaluation of the

    different contributions of the lateral deformation at the top of

    the column specimens. Such model points out the large inelastic

    demand imposed on the anchorage bolts of the steel end

    plate in traditional base column connections. Conversely, the

    socket-type system, derived from precast reinforced concrete

    structures, leads to large energy dissipation. Plastic hinges form

    at column base and the strength capacity is not lowered even atlarge lateral drifts (greater than 5%6%). As a consequence,

    socket-type foundations may be reliably utilized for steel

    and composite steelconcrete framed structures, especially in

    regions with moderate-to-high seismicity, to achieve adequate

    seismic structural performance.

    2. Experimental program and test set-up

    Several research programmes were recently launched in

    Europe, the US and Japan to investigate the inelastic response

    of bare steel and composite steel and concrete composite

    structures and/or their subassemblages, both for new andexisting buildings (e.g. [22,7], among others). In Italy, a number

    of experimental programmes were funded through national

    and European grants to provide technical support for the

    implementation and improvement of seismic provisions and

    guidelines (e.g. [4,20,11]). These test programmes included

    the assessment of the seismic response of composite slabs,

    beamcolumns and connections, either beam-to-column or

    base columns. In particular, the authors of the present work

    investigated the inelastic static and dynamic (seismic) response

    of base column connections. In so doing, a number of partial

    encased column specimens, with different base joints, were

    tested in the laboratory of the Department of Structural

    Analysis & Design (DAPS, University of Naples, Italy).The sample specimens included monotonic and cyclic tests;

    different levels of axial loads were considered during the

    tests to simulate the seismic load combinations implemented

    in European standards [11] for composite building structures.

    These axial loads were computed with regard to the exterior and

    interior composite steelconcrete columns frame tested at JRC

    Ispra laboratory [3,14], as shown in Fig. 1. In addition, pull-

    out tests were carried out to define the forceslip relationships

    of the hooked anchorage bolts; the results of the pull-out

    tests were utilized to investigate the deformation capacity of

    the base column traditional joint. In this work the results of

    the monotonic (pushover) tests are discussed in details. The

    experiments were carried out on two types of partially encased

    composite columns: HEB260 and HEB280 (see Fig. 1). The

    test specimens employed two layouts for the base column

    joints as per Fig. 2: traditional (bolted steel base plate) and

    innovative (socket-type) joints. The former consist of tapered

    steel plates welded onto base plates and anchored to the

    foundation block through steel bolted bars (see also [14]). Thelatter is an alternative and innovative socket type joint in which

    the column is fixed to the foundation block utilizing a special

    concrete filler; such joint was developed and designed to benefit

    of composite action. Socket type connections are generally

    utilized in precast reinforced concrete systems for residential,

    office and industrial framed structures.

    The first set of specimens (traditional base column

    connections) correspond to the columns and base joints

    designed in compliance with the guidelines of European

    standards [911] and used for the full-scale composite frame

    tested in ISPRA [3]; the layout of the latter is pictorially

    displayed in Fig. 1. The socket-type foundation was designed

    in compliance with Eurocode 2 [8] using strut-and-ties design

    approach.

    In the experimental tests, the lateral loads were applied

    at two different locations along the height of the column,

    namely at 1.6 m (traditional joint) and 1.7 m (socket type)

    above the foundation block to account for the different location

    of the restraint. Traditional base plates are generally placed

    at floor level, conversely socket type solution enables to use

    pavings that cover the foundation block. The horizontal load T,

    simulating the earthquake loading, was applied by means of a

    500 kN-hydraulic jack; the test was under displacement control.

    As a consequence, the maximum flexural moments M, located

    at the base connection, was increased until failure occurred. The

    displacement controlled loading regime allowed the softening

    branch of the response (capacity) curve to be investigated. The

    connection of the jack to the column is ensured by two steel

    plates 30 mm thick bolted on two opposite faces of the column.

    The reaction wall for the horizontal load is a stiff tapered

    cantilever bolted to a steel system; its layout is shown in Fig. 3

    along with the test set-up. The cantilever system is connected to

    the laboratory floor slab (strong floor) by means of large steel

    rebars crossing the slab and the steel elements. These rebars are

    loaded in tension to prestress the connection. The vertical load

    N is applied by two hydraulic jacks connected with two bars

    at the hinges placed at the foundation level. The axial load Nacts along the column centroid axis. The reaction system for

    N consists of a steel plate located under the foundation block

    and connected to the hinges. This layout ensures that the load

    remains along the member axis during the column deformation.

    The transversal beam, at the column top, is connected to the

    jack by means of large stiffeners. An adequate lateral restraint

    along four prestressing bars at the corners were used to prevent

    slip and rocking of the foundation block and to guarantee the

    transfer of the shear forces to the strong floor level.

    The investigation of the interface behaviour between anchor-

    age bolts and concrete block was carried out by means of pull-

    out tests; the set-up employed to perform the tests is provided

  • 8/8/2019 Base Column Connections Eng

    3/14

    L. Di Sarno et al. / Journal of Constructional Steel Research 63 (2007) 819832 821

    Fig. 1. Geometry of the full-scale composite frame tested at Ispra.

    in Fig. 4. It consists of a rigid steel frame, designed to prevent

    the onset of local buckling. The jack is bolted at the horizon-

    tal beam of the frame and the anchoring device is gripped with

    a tension bar. The anchoring devices were instrumented with a

    transducer and strain gauges. It is instructive to note that the use

    of strain gauges may, however, modify the mechanism associ-

    ated to bond and influence significantly the results due to local

    stresses acting on the device.

    3. Test specimens

    The experimental programme carried out at the laboratory

    of DAPS, in Naples, focused on two sample partially encased

    composite steel and concrete columns: HEB260 and HEB280

    (see also Fig. 1). The sample specimens tested were cantilever

    systems summarised as below (Table 1): partially encased

    columns with a steel HEB 260 member and traditional

  • 8/8/2019 Base Column Connections Eng

    4/14

    822 L. Di Sarno et al. / Journal of Constructional Steel Research 63 (2007) 819832

    Fig. 2. Layout of the sample base column connection: traditional (left) and socket-type (right).

    Table 1

    Sample column specimens

    Specimen Axial load (kN) Loading type Connection

    HEB260 330 Monotonic Traditional

    HEB260 170 Monotonic TraditionalHEB260 330 Monotonic Socket

    HEB280 520 Monotonic Socket

    connection to foundation (stiffening plates and anchoring

    devices) and innovative socket-type system; HEB280 with

    socket-type foundation. The specimens were instrumented in

    a refined fashion to characterize reliably the concentration of

    inelastic demand at the base column. Fig. 5 provides a close-up

    view of the displacement transducers (LVDTs) located at the

    base of the partially encased columns with either traditional or

    innovative joints.

    The values of axial load N used in the tests were equal to170 kN, 330 kN and 520 kN. The latter values correspond to

    the axial loads of the design load combinations of the full-

    scale composite framed building tested in the ELSA laboratory

    of JRC in Ispra [3]. The grade of the structural steel of the

    specimens was S235; the reinforcing bars grade was B450-

    C and the concrete was class C25/30. Actual values of the

    mechanical properties of steel and concrete were estimated

    from tensile (for steel) and compression (for concrete) tests.

    The values computed for the column members are summarized

    in Table 2. The width-to-thickness ratios of the sample columns

    (b/tf = 20.8 for HEB260 and b/tf = 21.5 for HEB280)

    fulfil the limit (b/tf = 44) given in European standards [10]

    to prevent local buckling in partially-encased I-sections madeof steel grade S253. Further details on the results of such tests

    can be found in [3]. The values of material overstrength ( fu/fy)

    relative to the element flange are on average higher than those in

    the webs. This result is in agreement with similar experimental

    data for steel members produced in Europe (e.g. [2]).

    The details of the foundation system are shown in Fig. 2. The

    design of such foundation block was based on the ultimate limit

    state corresponding to the stress values and distribution at the

    column failure. The layout of the composite column specimen

    employing HEB 260 steel section and traditional base joint is

    provided in Fig. 6, while the specimen HEB260 with socket

    type connection is provided in Fig. 7. The thicknesses of the

    Table 2

    Mechanical properties of the sample columns

    Property HEB260 HEB280

    Web Flange Web Flange

    fy (MPa) 406 341 341 300fu (MPa) 480 449 450 430

    fu/fy 1.18 1.32 1.32 1.43

    u (%) 31.8 35.7 34.5 37.1

    base of the socket is equal to 300 mm, while the walls of the

    socket are 250 mm thick. The total height of the foundation

    is 1050 mm. The values of the internal actions, i.e. axial load

    NSd,j , flexural moment MSd,j and shear VSd,j used for the

    design are NSd,j = 308 kN, MSd,j = 906 kN m and VSd,j =

    444 kN. These values were derived from the ultimate flexural

    capacity of the HEB 280; the evaluation of the resistance was

    based on conservative assumptions. In fact, for the above cross-

    section, the ultimate bending moment is MRd,col = 755 kN m;

    note that the design value MSd,j accounts for the overstrength

    ( fu/fy = 1.20) at the base column connection.

    For each foundation block, two anchoring devices were

    embedded in addition to the ones used for the base column joint

    details (Fig. 8). These embedded elements were instrumented

    with transducers and were utilized for pull-out tests. Thus,

    forceslip relationships were estimated for each anchorage

    bolts; these relationships were then utilized to compute the

    momentcurvature relationship of the base column section,

    as discussed in Section 5. The results of the experimental

    tests carried out on composite columns employing innovative

    (socket-type) are discussed below.

    4. Test results

    The test results of the partially encased composite columns

    were computed in terms of both local (momentcurvature

    M and momentrotation M ) and global (lateral loadtop

    displacement, F) response parameters. The capacity curves

    of the specimens HEB260 with axial load N = 330 kN, both

    traditional and innovative base connections, are provided in

    Fig. 9. Such curves are expressed in terms of lateral force

    (F)-drift (d/H), where H is the distance of the centreline

    of the hydraulic jack from the foundation and d the total

  • 8/8/2019 Base Column Connections Eng

    5/14

    L. Di Sarno et al. / Journal of Constructional Steel Research 63 (2007) 819832 823

    Fig. 3. Layout of the test set-up (top) and reaction wall (bottom).

    horizontal displacement at the jack height. It is observed that

    the traditional connection layout exhibits higher lateral strength

    (600 kN m vs. 510 kN m) due to the steel stiffeners used

    at the base of the column and to overstrength for seismic

    design. Conversely, the ultimate deformation capacity of the

    socket type connection is about 75% higher than the counterpart

    traditional (about 0.05 rad vs. 0.09 rad); in both cases the

    threshold value of 35 m rad given by Eurocode 8 [11] is

    exceeded. The latter limit value is more stringent than the 3%

    drift, which is assumed as the onset of the ultimate limit state in

    steel and composite frames in the US practice [16]. Furthermore

    the failure mode of the specimen with steel end plate is related

    to anchorage bolt fracture (Fig. 10), while in the case of the

    socket type a very ductile mechanism is observed (Fig. 11).

    At serviceability, the stiffness of the traditional connection

    is slightly higher than that of the socket connection. It can

  • 8/8/2019 Base Column Connections Eng

    6/14

    824 L. Di Sarno et al. / Journal of Constructional Steel Research 63 (2007) 819832

    Fig. 4. Set-up of pull-out tests: layout (left) and actual system (right).

    Fig. 5. Close-up view of the electrical displacement transducers (LVDTs): traditional (left) and innovative (right) joint.

    thus be argued that the experimental tests carried out both

    on traditional bolted steel end plate and innovative socket-

    type connections demonstrate that the former experience brittle

    failure modes. Rupture of anchorage bolts as per Fig. 10 was

    observed for traditional connections. The composite partially

    encased columns with traditional joint yield at about 310 kN,

    which corresponds to a lateral drift of 26 mm (d/h 1.65%).

    The maximum force is equal to 375 kN for HEB260 with axial

  • 8/8/2019 Base Column Connections Eng

    7/14

    L. Di Sarno et al. / Journal of Constructional Steel Research 63 (2007) 819832 825

    Fig. 6. Traditional base column joint.

    loads N = 330 kN and 340 kN for N = 170 kN. The lower

    value found in the second specimen (340 kN) is related to

    the premature rupture of the base joint, probably caused by

    technological defects of the threaded bars. In both specimens,

    i.e. with N = 170 kN and N = 330 kN, under monotonic

    regime, the column strength and energy dissipation do not

    exhibit significant loss for drift d/h 5%6%. The thick steel

    plate and the stiffeners used at the column base ensure that

    the end section of the column remains plane (rigid rotation).

    Additional tests carried out by the authors under cyclic loads

    have demonstrated that the crushed concrete and the inelastic

    deformations in the steel components (anchorages), both at

  • 8/8/2019 Base Column Connections Eng

    8/14

    826 L. Di Sarno et al. / Journal of Constructional Steel Research 63 (2007) 819832

    Fig. 7. Socket-type base column joint.

    the column base, endanger the global lateral stiffness of

    the composite column [15]. Bond-related phenomena give

    rise to degrading effects, especially at large drifts, thus

    reducing significantly the energy dissipation capacity of the

    member. These findings point out that traditional connections

    are not fully satisfactory, especially when the contribution

    of reinforced concrete component increases, i.e. due to

    cross section dimensions. Conversely, innovative socket-type

    connections possess adequate ductility. Under monotonic load

    conditions, the test results show strain hardening of the base

    column equal to 1.32. This is due chiefly to the material

    overstrength of structural steel (compare, for instance, values of

  • 8/8/2019 Base Column Connections Eng

    9/14

    L. Di Sarno et al. / Journal of Constructional Steel Research 63 (2007) 819832 827

    Fig. 8. Steel reinforcement used for the traditional base column joint and layout of the additional anchorage bolts for pull-out tests.

    Fig. 9. Capacity curves for the traditional and socket-type connections for

    HEB260 (N= 330 kN).

    fu/fy of the member flange in Table 2). The contribution of the

    hardening of the longitudinal reinforcement bars is in fact very

    small (1.13 vs. 1.32). The tests carried out on the specimens

    employing the socket joint do not exhibit strength deterioration

    even at large lateral drifts, e.g. d/h > 0.040.05 rad. The

    formation of the plastic hinge occurs at the base column, as

    observed during the tests. Fig. 11 shows the occurrence of

    inelastic deformations at the base column during the test on the

    HEB 260 with N= 330 kN; the spreading of such inelasticity is

    also evident. At very large drifts, the flange plate of the column

    tends to bend outwards and the bond between the inner concrete

    and the exterior steel plate is broken as demonstrated by the

    close-up view of the Fig. 11, without any relevant effect on

    the global response. The tensile resistance of the concrete is

    exceeded and inclined (flexural) cracks initiate and propagate

    above the foundation block.

    To shed light on the structural performance of the sample

    columns with either traditional or innovative socket-type

    Table 3

    Material mechanical properties used to computed the interaction curves

    Property Design Yield Collapse

    fcd (MPa) 14.2 21.3 38.0

    fsd (MPa) 391.3 450.0 450.0

    fad (MPa) 213.6 235.0 450.0

    c 1.50 1.00 1.00

    s 1.15 1.00 1.00

    a 1.10 1.00 1.00

    Key: fcd = concrete compression strength at yield ( f c); fsd = compres-

    sion/tensile strength of reinforcement steel (bars); fad = compression/tensile

    strength of reinforcement steel (profiles); c = partial safety factor for con-

    crete; s = partial safety factor for steel (bars); a = partial safety factor for

    steel (profiles).

    member-to-foundation joint, the bendingaxial load MN

    interaction curves (Fig. 12) were computed for the specimens

    HEB 260 and HEB 280. These MN curves were derived

    in compliance with the simplified method of design for

    doubly symmetric and uniform cross-section over the member

    length with rolled steel sections implemented in the European

    standards for composite steel and concrete structures [10]. Theresistance of the cross-section to combined compression and

    bending is calculated assuming stress blocks (plastic stress

    distribution); the tensile strength of the concrete is neglected

    and the interaction curve is replaced by a polygonal diagram

    (the dashed line in Fig. 12). The material mechanical properties

    used to derive the simplified interaction curves are provided in

    Table 3. The values of the simplified M N interaction curves

    for the test with HEB260 (N= 170 kN and N= 330 kN) and

    HEB280 (N = 330 kN and N = 520 kN) estimated at yield

    and collapse are summarized in Tables 4 and 5, respectively.

    The computed values of the MN curves demonstrate that

    the failure mechanism is controlled in the case of traditional

  • 8/8/2019 Base Column Connections Eng

    10/14

    828 L. Di Sarno et al. / Journal of Constructional Steel Research 63 (2007) 819832

    Fig. 10. Close-up view of the deformations of the specimen HEB260 with N= 330 kN (traditional connection).

    Table 4

    Values of interaction curves for the test with HEB260 (N= 170 kN and N= 330 kN) and traditional joint at different performance state

    Yield Collapse Test

    M (kN m) N (kN) M (kN m) N (kN) M (kN m) N (kN)

    Section above stiffening plate 343 330 633 330 488 330

    339 170 628 170 433 170

    Column base connection 440 330 550 330 596 330

    395 170 510 170 530 170

    Table 5

    Values of interaction curves for the test with HEB280 (N = 330 kN and

    N = 520 kN) and socket-type joint at different performance state (at column

    base connection)

    Yield Collapse Test

    M (kN m) N (kN) M (kN m) N (kN) M (kN m) N (kN)

    390 330 740 330 608 330

    420 520 750 520 762 520

    joint by the base column component. By contrast, for socket-

    type connections, the failure mode is due to the formation of

    the plastic hinges in the columns (see also Fig. 11, where the

    spreading of inelasticity due to flexure is evident).

    The inelastic response of the critical region of the specimens

    with socket-type joints was monitored carefully through six

    electrical displacement transducers located at the column base

    as displayed in Fig. 5. These LVDTs record the lateral

    displacement of several points of the column flanges in

    order to define reliably the various inelastic phenomena,e.g. yielding, local buckling, fracture initiation, occurring

    at those locations during the tests. Fig. 13 provides force-

    rotation curves computed at the base column of the socket-

    type connection under monitonic loads. All monitored sections

    shows significant nonlinear response as the deformations

    increase; this behaviour characterizes also the cyclic tests [15].

    Comparison between total cord rotation and the base column

    one derived from LVDT #6 measures enable to recognise that

    the higher is the drift, the higher is the contribution to the total

    drift given by the deformation of the socket type connection.

    Furthermore, due to the location of LVDT #1, 45.0 cm far

    from the foundation, the socket type shows a yielding spreading

  • 8/8/2019 Base Column Connections Eng

    11/14

    L. Di Sarno et al. / Journal of Constructional Steel Research 63 (2007) 819832 829

    Fig. 11. Close-up view of the deformations of the specimen HEB260 with N= 330 kN (socket-type connection).

    Fig. 12. Simplified interaction curve for combined axial loaduniaxial bending

    moment (NM).

    that is nearly twice the width of the section (45.0 cm vs.

    52.0 cm). As far as seismic design is concerned, the longer

    the spreading of inelasticity the higher the energy dissipation.

    By contrast, traditional connection systems, employing bolted

    steel end-plate generate high concentrated inelastic demand on

    the anchorage bolts, which fail prematurely in a brittle manner.

    Fig. 13. Forcerotation of the base column of the socket-type connection:

    LVDTs #1 to LVDT #6.

    5. Numerical simulations

    Numerical simulations of the pushover tests were carried out

    through a fibre-based model, which may accommodate both

  • 8/8/2019 Base Column Connections Eng

    12/14

    830 L. Di Sarno et al. / Journal of Constructional Steel Research 63 (2007) 819832

    Fig. 14. Evaluation of fixed end rotation: system response (top-left), cross-section response (top-right) and computational model (bottom).

    Fig. 15. Momentcurvature of the columns and the base joints: HEB260 with N= 330 kN (left) and N= 170 kN (right).

    mechanical (material nonlinearity and residual stresses) andgeometrical (P effects) nonlinearities. The effects of the

    fixed end rotations are also accounted for; the computational

    model is pictorially shown in Fig. 14. The constitutive

    relationships employed in the numerical simulations were

    based on experimental tests carried out on structural steel

    and reinforcement bars (see Table 2); concrete stress strain

    including size effect was used to simulate behaviour of

    concrete. The collapse of the sample columns was caused

    by base column joint failure in the case of the traditional

    connection as shown in Fig. 10. The ultimate resistance of

    the columns is thus controlled by this failure mechanism.

    Consequently, the ultimate bending moment of the base

    joint was computed for purpose of comparisons. Themomentcurvature relationship of the base column was derived

    through the constitutive relationship of anchorage bolts and the

    Manders model for unconfined concrete for the high strength

    material which supports the rigid steel end-plate. The peak

    of resistance for concrete ( fc = 70 MPa) is assumed at

    c = 0.002, which corresponds to the upper bound of the

    compressive strength estimated via experimental tests. The

    actual yield and ultimate strengths of the bolts are equal to

    400 MPa and 570 MPa, respectively; the strain hardening

    starts at sh = 0.01. Fig. 15 provides the momentcurvature

    curves of the columns and the base joints for the sample

    specimens HEB260 with both N = 170 kN and N = 330 kN.

  • 8/8/2019 Base Column Connections Eng

    13/14

    L. Di Sarno et al. / Journal of Constructional Steel Research 63 (2007) 819832 831

    Fig. 16. Pull-out tests for anchorage bolts used for HEB260 with N= 330 kN (left) and N= 170 kN (right).

    Reference lines relative to the onset of the yield in the base

    joint and the column are also plotted in Fig. 15. For both

    specimens HEB 260, the former component yields at a value of

    about 300 kN m, while the column elastic threshold is higher

    (452 kN m and 475 kN m for HEB260 with N = 330 kNand N = 170 kN, respectively). The total deformation of the

    columns were computed by integrating the momentcurvature

    along the member. This relationship was derived by assuming

    that member cross-sections remain plane and slip between

    steel and concrete does not take place (ideal bond); the

    computational model employed for the numerical simulation

    is outlined in Fig. 14. The fixed end rotation was estimated

    through the momentcurvature of the base joint ( position of

    neutral axis) and a fitting curve of experimental bond-slip

    constitutive relationships provided in Fig. 16 (slip effects).

    Comparisons between numerical simulations and experi-

    mental test are provided in Fig. 17 for the sample column HEB

    260 with N = 330 kN; results for traditional and socket-type

    joints are displayed. For the former, it may be observed that the

    value of the yield of the base joint is close to the elastic thresh-

    old measured during the experiment, thus demonstrating that

    the failure of the base column controls the global response of

    the composite steel and concrete column. This behaviour was

    also experienced by the sample HEB 260 with N = 170 kN.

    Forcedeformation curves of the tested columns are also shown

    in the same figure. The total lateral deformations and the con-

    tributions caused by the fixed-end rotation and the column flex-

    ibility are included. The deformation of the column was esti-

    mated with respect to the length of 1310 mm, i.e. the distance

    between the column tip and the steel stiffening end plate atthe base. The comparison between experimental and numerical

    simulation of the socket-type joint provided in Fig. 17 demon-

    strates that also for this type of connection layout the fixed

    end rotation can be significant. However, the contribution of

    the end rotation to the overall lateral displacement of the spec-

    imen with socket-type joint tends to be lower than in the case

    of the traditional bolted base plate connection. The end rotation

    in the case of socket joints is caused by concretesteel interface

    mechanisms that occur within the socket, i.e. slip in the embed-

    ded length. This slip is a function of the concrete strength, the

    number and configuration of studs, if any, welded on the col-

    umn web. Moreover, for socket-type connections the bending

    Fig. 17. Comparisons between numerical simulations and experimental test for

    HEB260 with N = 330 kN for traditional (H = 1310 mm) (top) and socket

    type (H= 1700 mm) (bottom) joints.

    moment computed through the numerical simulation of the can-tilever column with height of 1700 mm is smaller than the value

    estimated experimentally; the difference between these bending

    moments is about 25%. Similarly, Fig. 17 shows that the yieldof the sample column evaluated numerically is higher than thatmeasured experimentally. The latter may be caused by the inter-

    action between the composite column and the surrounding con-

    crete. It is observed that for the socket type connection the fixity

    of the column is not located at the interface between the end-plate and the foundation block, but it penetrates in the socket,

    as proved by the profile of the lateral displacement determined

    by means of the LVDTs shown in Fig. 5.

    6. Conclusions

    Experimental tests carried out on composite steel and

    concrete columns were presented in this paper. Two layouts

  • 8/8/2019 Base Column Connections Eng

    14/14

    832 L. Di Sarno et al. / Journal of Constructional Steel Research 63 (2007) 819832

    for the base column connections were assessed: the traditional

    system employing the bolted steel end plate and the innovative

    socket type. The experimental results demonstrate that the

    socket system is beneficial for the spreading of inelasticity

    at the base of the composite columns. To assess the

    inelastic structural performance, the composite specimens

    were subjected to monotonic loads at increasing lateral drifts(pushover experimental tests). It was found that the maximum

    drift of the socket-type connection is nearly 75% higher than the

    traditional bolted steel end plate. Traditional base connections

    fail in a less ductile fashion because of the fracture of the

    anchorage bolts. Conversely, socket connections exhibit a

    ductile response due the formation of the plastic hinge at the

    base of the column, which extends over a length much higher

    than the cross section depth. As a result, socket-type joints can

    be reliably used for design of structures which may experience

    significant inelastic excursions, such as those in earthquake

    prone regions.

    Acknowledgements

    The present work was funded by the Italian Ministry

    of Research, through the grant PRIN-COFIN04 (Composite

    steel and concrete earthquake-resistant frames: advanced

    dissipative joint systems, methods for damage assessment and

    seismic design guidelines); the financial support is gratefully

    acknowledged.

    References

    [1] Broderick BM, Elnashai AS. Seismic response of composite frames-I.

    Response criteria and input motion. Engineering Structures 1996;18(9):

    696706.

    [2] Byfield MP, Nethercot DA. Material and geometric properties of

    structural steel for use in design. The Structural Engineer, Journal of the

    Institution of Structural Engineers 1997;75(21):3637.

    [3] Bursi OS, Caramelli S, Fabbrocino G, Molina J, Salvatore W, Taucer F.

    3D Full-scale seismic testing of a steelconcrete composite building at

    ELSA. contr. no. HPR-CT-1999-00059. European Community; 2004.

    [4] CNR 10016. Composite steel and concrete structures. Guidelines for

    applications in construction. CNR bulletin n. 192. Rome (Italy); 1999 [in

    Italian].

    [5] Cosenza E, Pecce MR. Le colonne composte acciaio-calcestruzzo: Analisi

    sperimentali, modelli di calcolo, indicazioni normative. Costruzioni

    Metalliche 2001;10(2):4960 [in Italian].

    [6] Cosenza E, Zandonini R. Composite construction. In: Chen WF, editor.

    Handbook of structural engineering. Boca Raton (USA): CRC; 1997.[7] Di Sarno L, Elnashai AS. Seismic retrofitting of steel and composite

    building structures. Mid-America earthquake center report, CD Release

    02-01. IL (USA): University of Illinois at Urbana-Champaign; 2002.

    [8] Eurocode 2. Design of concrete structures. Part 1.1: General rules and

    rules for buildings. Brussels (Belgium): Eur. Comm. for Stand.; 2004.

    [9] Eurocode 3. Design of steel structures. Part 1.1: General rules and rules

    for buildings. Brussels (Belgium): Eur. Comm. for Stand.; 2004.

    [10] Eurocode 4. Design of composite steel and concrete structures. Part 1.1:

    General rules and rules for buildings. Brussels (Belgium): Eur. Comm. for

    Stand.; 2004.

    [11] Eurocode 8. Design provisions for earthquake resistance of structures.

    Part 1.3: General rules. Specific rules for various materials and elements.

    Brussels (Belgium): Eur. Comm. for Stand; 2004.

    [12] Elnashai AS, Elghazouli Y. Performance of composite steelconcrete

    members under earthquake loading, part 2: Parametric studies and design

    considerations. Earthquake Engineering and Structural Dynamics 1993;

    22(4):34768.

    [13] Fabbrocino G, Manfredi G, Cosenza E, Pecce MR. Some remarks on

    deformation capacity of composite frames in seismic areas. In: Proc. of

    the 1st international conference on steel and composite structures. 2001.

    [14] Fabbrocino G, Pecce MR, Di Sarno L. Inelastic response of steel and

    concrete columns. In: Proc. of the fourth international conference on steel

    and composite structures. 2004. CD-ROM.

    [15] Fabbrocino G, Pecce MR, Di Sarno L. Inelastic response of steel and

    concrete columns. In: Proc. of the fourth international conference on

    advances in steel sructures. vol. I. 2005. p. 7938.

    [16] Federal Emergency Management Agency. Prestandard and commentary

    for the seismic rehabilitation of buildings. FEMA report no. 356.

    Washington DC (USA); 2000.

    [17] Hajjar JF. Composite steel and concrete structural systems for seismic

    engineering. Journal of Constructional Steel Research 2002;58(58):

    70223.

    [18] Lee TKL, Pan ADE. Analysis of composite beamcolumns under lateral

    cyclic loading. Journal of Structural Engineering, ASCE 2001;127(2):

    18693.

    [19] Mazzolani FM. Steel and composite structures in European seismic areas:

    Research, codification, design and applications. Earthquake Spectra 2003;

    19(2):41552.

    [20] OPCM. General criteria for new seismic zonation in Italy and seismicstandards. Rome (Italy): Department of National Emergency Agency;

    2003 [in Italian].

    [21] Ricles JM, Paboojian SD. Seismic performance of steel-encased

    composite columns. Journal of Structural Engineering, ASCE 1994;

    120(8):247494.

    [22] Roeder CW. Overview of hybrid and composite systems for seismic

    design in the United States. Engineering Structures 1998;20(46):35563.

    [23] Shanmugam NE, Lakshmi B. State of art report on steelconcrete

    composite columns. Journal of Constructional Steel Research 2001;

    57(10):104180.

    [24] Spacone E, El-Tawil S. Nonlinear analysis of steelconcrete composite

    structures: State of the art. Journal of Structural Engineering, ASCE 2004;

    130(2):15968.

    [25] Thermou GE, Elnashai AS, Plumier A, Doneux C. Seismic design

    and performance of composite frames. Journal of Constructional SteelResearch 2004;60(1):3157.