IMPORTANT• Completeallformsunderthisappendixforeach
unitandemail,faxormailtoVenmarCESimme-diatelyafterstart-uptovalidatewarrantyandtoprovidevaluableinformationforpersonnelperform-ingfuturemaintenanceorforfactoryassistancetoaddressbelow.
• ReadtheInstallation,OperationandMaintenanceInstructionManualandtheVenmarCESControlSystemKeypadOperationGuideandtheSequenceofOperationbeforeproceeding.
• Leaveacopyofthisreportwiththeownerandattheunitforfuturereferenceandpermanentrecord.
• Toensureproperoperationofeachunit,qualifiedpersonnelshouldperformthestart-up,completethechecklistandreport.
• Allunitsarefunctionallytestedexceptwhenshippedinmultiplepieces.Start-upadjustmentsmayberequired.Iftheunitisshippedasasinglepiece,blowers,enthalpywheelandcompressors(ifequipped)aresetuptoruncorrectlywhenpowerisconnected.Ifanyblowerisrunningbackwardsorcompressorismakingloudnoises,disconnectpowerandswitchtwoleads(onthree-phasepower)toensureproperrotationandavoiddamage.
• Ifunitsareequippedwithcompressors,powermustbeturnedonfor24 hours prior to a callforcool-ing,forthecompressorcrankcaseheaterstobeenergizingtopreventpossibledamage.
• TheBacviewkeypadlocatedatthecontrolpanelwillallowformanualoverrideforstart-up,modeofoperationselectionandincludesaninternaltimeclockifremoteinterlocksarenotprovided.
VCES-ASTON-SF-1B – EnergyPack, ERV5000–10000, HRV3000–10000 Start-up Form January2014
EnergyPack®, ERV5000–10000(i/e) and HRV3000–10000(i/e) Start-up Form and Checklist
Venmar CES Inc.200RueCarterSt.Léonardd’Aston,QCCanadaJ0C1M0
Emailtotechsupport:[email protected]:899-319-2612Phone:1-866-4-VENMAR
Unit Identification InformationProject____________________________________________JobName_________________________________________JobAddress______________________________________________________________________________________________________________________________________________________ModelNumber_____________________________________SerialNumber______________________________________Tag ______________________________________________JobsiteContact ____________________________________Email_____________________________________________Telephone_________________________________________
SerialNumber:_____________________________________
Table E1: Pre Start-up ChecklistChecklist Item Check √ N/A
1 Checktheelectricaldisconnectsettothe‘Off’position.
2 Checkthesplitsectionjointsareproperlyinstalledonmulti-sectionalunits.
3CheckthatallholesthathavebeenmadebytheInstallingContractorafterreceivingtheunitinthecasing,partitionsorfloorhavebeenwellsealedtopreventairand/orwaterinfiltration.
4Checktheunitforobstructivepackaging,objectsnearorinfans,dampers,energyrecoverywheel,etc.
a. Checkthattheinsideofunithasbeencleanedofalldebris.
5
Removeallretainingboltsonfanisolationbases.
a. Checkthatthefanimpellersarerotatingfreely.
b. Checkfanimpellersanddrivesetscrews.Tightenifrequired.
c. Checkthefanbearingsetscrewsorlockingcollars.Tightifrequired.
d. Checkfanbeltalignmentandtension.
e. Checkthefanflexiblejointconnectionsarewellattached.
6
Checkthattheairfiltersareinstalledandclean.Replaceifnecessary.SeeAppendixFforoptionaldownstreamhighefficiencyHEPAfilterinstallation(ifsupplied).a. Checkallfacemountedfiltersareattachedwithfourclipseach.
b. Checkeachslidingfilterhasaretainerattheendtrackandwellattachedblank-offs.c. Checkthefilterpressuredifferentialgauges,switchesorsensorsarefreeofdirtandsetata
valuesatisfactorytotheendusertotriggerafilterchange.
7
Checkcoilsiffinshavebeendamagedinshipping,installationorbuildingconstructionandareclean.Straightenfinswithafincombandcleancoilifrequired.a. Checkallpipeconnectionsaretightandthatnodamagehasoccurredduringshippingorinstallation.b. CheckthatthepipingtothecoilsandWSHPhavebeencompleted,pipinglineshavebeen
flushed,filled,ventedandtestedat1.2timestheoperatingpressure.RefertoAppendixB.
8
ScrollcompressorRISvibrationisolatorboltsarefactorytightenedtothecorrecttorquesettingforoperationanddonotrequirefieldadjustment.a. Checktherefrigerantcomponentsandpipingareingoodconditionandhavenodamageor
leaksfromshippingorinstallation.b. Checkthattherefrigerantlinesarespacedatleast1”apartandfromthecompressoraftership-
pingandinstallation.c. Checkthattherefrigerantlineclampsarestillsecureandhavetheirrubberlining.d. Checkthattheclearancearoundtheaircooledcondenseriswithinminimumclearanceandthe
dischargeisnotblocked.
9Checkmotorizeddampercontrolarms,controlrodsandshaftsfortightness.
a. Checkthatnonmotorizeddampersrotatefreely.
10
Checktheenergyrecoverywheelmediaforanydefectsfromshippingorinstallation.SeeMainte-nancesectionfordetails.a. Greasebothpillowblockbearingsonthewheel(s)whengreasenipplesprovided.
b. Checkthatthewheel(s)areturningfreelybyhandanddonotbind.c. Visuallyinspectthewheel(s)toensureitiscenteredanddoesnottilt.Ifthereisanyindicationof
aproblemcallVenmarCESTechSupportat1-866-4-VENMAR.d. Checkthatthewheelsealsareproperlypositionedfromthefaceofthewheel.
e. Checkthatthewheelpurge(ifpresent)issettothedefaultangleasspecifiedinthesubmittal.
f. Checkthemountingfastenersonthewheel(s)motorandgearreduceraretight.
g. Checkthebeltandpulleyonthewheeldriveforcorrectalignment,tensionandsetscrewtightness.
11 Checktheplatemediaforanydefectsfromshippingorinstallation.
VCES-ASTON-SF-1B – EnergyPack, ERV5000–10000, HRV3000–10000 Start-up Form January2014
Table E1: Pre Start-up ChecklistChecklist Item Check √ N/A
12
Checktheheatpipefinsforanyfindefectsfromshippingorinstallation.
a. Removeretainingboltsonheatpipetiltmechanism.
b. Checktheheatpipeflexibleconnectionisproperlyattachedandsealedontiltmechanism.
c. Checktheactuatorcontrolarmandlinkagesaretightontiltmechanism.
13 Checkthatductworkisconnected,completeandfreeofobstructions.
14 Checkthatcondensatedrainconnectionshavebeentrapped,installedcorrectlyandfilled.
15Checkatallunitsplitsectionsthatallfactoryinternalhighandlowvoltagewiringconnectionshavebeenproperlyre-connected.
16 Checkthatallshippedlooseorfieldsuppliedcomponentshavebeencorrectlyinstalledandwired.
17 Checkthatthewiringdiagramhasbeenmarkedupaccordinglyandleftwiththeunit.
18CheckthatallpowersuppliesandcontrolwiringhavebeeninspectedandapprovedbytheLocalAuthoritieshavingjurisdiction.
19 Checkallfactoryandfieldwiringconnectionsfortightness.Tightenifnecessary.
20 Checkthatallfusesareproperlyinstalledinholders.
21Checkthevoltageatthedisconnectswitchagainstthenameplateandagainstphase-to-phasereadingsonthree-phase.Ifthevoltageisnotwithin10%ofratedor2%ofphasetophase,havetheconditioncorrectedbeforecontinuingstart-up.
22Checkthatallfieldpipingandventinginstallationandconnectionsforheatingandcoolingoptionshavebeencompletedandtested.
23 Settheheatingandcoolingenableswitchestothe‘Off’position.
24RefertoAppendixDforgas-firedfurnacemoduleandAppendixGforelectriccoilinstallationandmaintenanceandcheckthattheinstallationiscompleted.Performallgas-firedfurnaceandelectriccoilprestart-upchecks.
25 Checkthatallsafetyswitches,overloadsorothermanualresetdevicesarereset.
26Iftheunitisequippedwithcompressors,powermustbeturnedonwiththeunitin‘Off’modefor24hoursbeforestart-up.Thiswillenergizecrankcaseheatersandassurenoliquidrefrigerantispresentwhichcouldcausecompressordamageorfailure.Checkthatthishasbeencompleted.
Table E2: Start-up ChecklistChecklist Item Check √ N/A
1 Beforeproceeding,completetheprestart-upchecklist.
2 Checkthatallaccesspanelsordoorsareclosed.
3
Ifunitsareequippedwithcompressors,feelthecompressorcrankcases.Theyshouldbewarmifthedisconnecthasbeen‘On’foratleast24hours.Thiswillassurethatnorefrigerantliquidispresentinthecrankcasewhichcouldcausecompressordamageorfailuretooccuronstart-up.Otherwise,turnthemaindisconnecttothe‘On’position.
4
TheunitcanbestartedbyusingthekeypadandselectingthemodeofoperationfromtheKeypadOperationGuideandtheSequenceofOperation.Disabletheheatingandcoolingfunctionsandsettheunittotheoccupiedmodetobumpstartthefanwheel(s)andenergyrecoverywheel(s)tochecktheiroperation.
5 Checkthatdampersareoperatingproperly.
6 Checkthatthefanwheel(s)andenergyrecoverywheel(s)arerotatinginthecorrectdirection.
7 AdjustthefanmotorVFD(s)tothecorrectairvolume/Hertz.
8Foroccupiedrecirculationmode,adjustoutside,exhaustandmixedorrecirculationairdamperpositionerstoachievetherequiredairvolumes.
9CheckamperagedrawtoeachmotoroneachphaseagainstmotornameplateFLA.Ifsignificantlydifferent,checkductworkstaticand/ortakecorrectiveaction.
SerialNumber:_____________________________________
VCES-ASTON-SF-1B – EnergyPack, ERV5000–10000, HRV3000–10000 Start-up Form January2014
Table E2: Start-up ChecklistChecklist Item Check √ N/A
10Recheckthevoltageatthedisconnectswitchagainstthenameplateandagainstphase-to-phasereadingsonthree-phasewithallblowersoperating.Ifthevoltageisnotwithin10%ofratedor2%ofphase-to-phasehavetheconditioncorrectedbeforecontinuingstart-up.
11BeforeactivatingthecompressoronWSHPunits,checkthatthewatershut-offvalvesareopenandwateriscirculatingthroughthewater-to-refrigerantheatexchanger.Checktheincominglinewaterpressuretoensureiswithindesignandacceptablelimits.
12Enablethecoolingmodeofoperation.Checkifthesoundofthecompressorisnormalorifthereisexcessivevibration.
13Onunitswithintegratedaircooledcondenserscheckcondenserfansarerotatinginthecorrectdirection.
14 Checkallfieldandfactoryrefrigerantandwaterpipingconnectionsforleaksandcorrect.
15
Operatetherefrigerantsystemnearfullloadconditionsinbothheatingandcoolingmodesandchecksub-coolingandsuperheatagainstvaluesinAppendixP,TableP1.Ifreadingsdonotmatch,adjusttherefrigerantcharge.RefertoAppendixPforinformationonadjustingtherefrigerationcharge.
16
OnunitswithWSHP,afterafewminutesofoperation:a. Checkthesupplydischargetemperaturestatusonthekeypadforcoolingairdelivery.Measure
thetemperaturedifferencebetweenenteringandleavingwater.Incoolingmode,thetempera-turedifferenceshouldbeapproximately1.5timesgreaterthantheheatingmodetemperaturedifference.Forexample,ifthecoolingtemperaturedifferenceis15°F[8.3°C],theheatingtemperaturedifferenceshouldbeapproximately7°Fto10°F[3.9°Cto5.6°C].Alternatively,ifaflowmeasuringvalveorpressuregaugeconnectionsareincluded,taketheflowreadingorpres-suredropcomparedtothesubmittalinformationandadjusttheshut-off/balancingvalveinthereturnlinetothecorrectflow/pressuredropreading.
b. Measurethetemperaturedifferencebetweenenteringandleavingairandenteringandleavingwater.Withenteringwaterof60°Fto80°F[15.6°Cto26.7°C],leavingtemperatureshouldrisethroughtheunit.Shouldnotexceed35°F[19.4°C].Iftheairtemperatureexceeds35°F[19.4°C],thenthewaterflowrateisinadequateortheairflowratemaybelowandasecondcheckmayberequiredafterairflowbalancing.
17Onunitswithgas-firedfurnacemoduleorelectricheatingcoils,checksupplyairprovinginterlockswitchsettingtoensureminimumsupplyairflowpriortoburneroperation.Settheswitchtoopenbelowtheminimumsupplyairflowonthefurnaceratingplate.
18Enableheatingoptions,seestart-upandcheckoutinstructionsinAppendixDforgas-firedfurnacemoduleandAppendixGforelectriccoilandcomplete.
19Forelectricheatingcoiloptionchecktheampdrawoneachstage,theoperationofthesequenceorSCRcontrollerandthecoilforanyhotspots.
20 Checktheoperationofthecontroloptionsprovidedontheunit.
21 CheckthesetpointsontheDDCPointsReference,adjustandrecordchangesasrequired.
22 Hasairbalancingbeencompletedforbothoccupiedandunoccupiedoperation?
23
Whenunithasachievedsteadystate,takemeasurementsandcompleteStart-upReadingsportionoftheStart-upReportandChecklistinAppendixE.SendacopyofthecompletedStart-upReportandChecklisttoVenmarCEStovalidatewarranty.Maintainacopyofthereportattheunitforfuturereference.
24Oncecompleted,returnsetpointstooriginalorrequiredvalues,returntheunittothecorrectmodeofoperationandadjustthetimeclockifrequired.
SerialNumber:_____________________________________
VCES-ASTON-SF-1B – EnergyPack, ERV5000–10000, HRV3000–10000 Start-up Form January2014
Start-up Readings• Allowunittoreachsteadystatebeforetakingreadings.• Completebasedonoptionsincludedwithunit
Nameplatevoltage
Inputvoltage L1–L2 L2–L3 L1–L3
Table E3: Start-up Readings – Supply Fan
Rotation Correct
Full Load Amps (Nameplate Amps)
Amp Draw O/L Amp Setting
Hertz RPML1 L2 L3
Fan1
Fan2
Fan3
Fan4
Fan5
Fan6
Fan7
Fan8
Fan9
Fan10
Fan11
Fan12
Table E4: Start-up Readings – Exhaust Fan
Rotation Correct
Full Load Amps (Nameplate Amps)
Amp Draw O/L Amp Setting
Hertz RPML1 L2 L3
Fan1
Fan2
Fan3
Fan4
Fan5
Fan6
Fan7
Fan8
Fan9
Fan10
Fan11
Fan12
SerialNumber:_____________________________________
VCES-ASTON-SF-1B – EnergyPack, ERV5000–10000, HRV3000–10000 Start-up Form January2014
SerialNumber:_____________________________________
Table E6: Start-up Readings – Compressors
Full Load Amps
(Nameplate Amps)
Amp DrawAfter compressor has been running for 15 minutes check the
following:
Suction Pressure
Discharge Pressure
SuperheatLiquid
Subcooling
Hot Gas Bypass
Functioning
Outdoor Ambient Temp.
During AC Cooling
Start-up (°F/°C)
L1 L2 L3
Compressor1
Compressor2
Compressor3
Compressor4
Compressor5
Compressor6
Compressor7
Compressor8
Compressor9
Compressor10
Compressor11
Compressor12
Compressor13
Compressor14
Compressor15
Compressor16
Table E5: Start-up Readings – Condenser Fan
Rotation CorrectFull Load Amps
(Nameplate Amps)Amp Draw
O/L Amp SettingL1 L2 L3
Fan1
Fan2
Fan3
Fan4
Fan5
Fan6
Fan7
Fan8
Fan9
Fan10
Fan11
Fan12
Fan13
Fan14
Fan15
Fan16
VCES-ASTON-SF-1B – EnergyPack, ERV5000–10000, HRV3000–10000 Start-up Form January2014
Table E7: Start-up Readings – WSHPWaterside Cooling Mode Waterside Heating Mode
Entering Temp. (°F/°C)
Leaving Temp. (°F/°C)
Temp. Difference
(°F/°C)
Entering Temp. (°F/°C)
Leaving Temp. (°F/°C)
Temp. Difference
(°F/°C)
Entering Pressure
(PSI)
Leaving Pressure
(PSI)US GPM
Condenser1
Condenser2
Condenser3
Condenser4
Condenser5
Condenser6
Condenser7
Condenser8
Condenser9
Condenser10
Condenser11
Condenser12
Condenser13
Condenser14
Condenser15
Condenser16
SerialNumber:_____________________________________
Table E8: Start-up Readings – Electric Heating CoilStage L1 Amps L2 Amps L3 Amps Check for Hot Pots
1
2
3
4
5
6
Table E9: Start-up Readings – Energy Recovery Wheel (ERW)
Full Load Amps (Nameplate Amps)
Amp DrawO/L Amp Setting
L1 L2 L3
ERW1
ERW2
ERW3
ERW4
VCES-ASTON-SF-1B – EnergyPack, ERV5000–10000, HRV3000–10000 Start-up Form January2014
SerialNumber:_____________________________________
Thisunithasbeencheckedoutandstartedaccordingwiththeaboveproceduresandcompletedformsandisoperatingsatisfactorily.After24hoursofsatisfactoryop-erationshutdowntheunitandcheckallfoundationbolts,shaftbearings,drivesetscrews,valvetrainandterminals.Tightenwhererequired.
AdditionalComments:______________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________
Start-upBy________________________________________________CompanyName____________________________________Date______________________________________________Email_____________________________________________Telephone_________________________________________
Emailtotechsupport:[email protected]:819-399-2612.
Table E10: Start-up Readings – Gas-fired Duct FurnaceFuel Natural Gas Propane Furnace #1 Furnace #2
Combustionairfan
Rotationcorrect2
Fullloadamps(nameplateamps)2
AmpdrawL1/L2/L32
O/Lampsetting2
Induceddraftfanmotor
RotationcorrectFullloadamps(nameplateamps)AmpdrawL1/L2/L3O/Lampsetting
Lowfire
Inletgaspressure–”w.c.Regulatoroutletpressure–”w.c.Manifoldpress–”w.c.StackCO2–%2
StackO2–%2
Netstacktemperature–°F/°C2
Efficiency–%2
Flamesignal–mA/VDCSupplyairinlettemperature–°F/°CSupplyairdischargetemperature–°F/°C1
Supplyairtemperaturerise–°F/°C
Highfire
Inletgaspressure–”w.c.Regulatoroutletpressure–”w.c.2
Manifoldpress–”w.c.StackCO2–%2
StackO2–%2
Netstacktemperature–°F/°C2
Efficiency–%2
Flamesignal–mA/VDCSupplyairinlettemperature–°F/°CSupplyairdischargetemperature–°F/°C1
Supplyairtemperaturerise–°F/°C1.Measuredownstreamwheretemperatureiseveninduct.2.ForIGseriesdrumandtubegas-firedductfurnacemodelsonly.
VCES-ASTON-SF-1B – EnergyPack, ERV5000–10000, HRV3000–10000 Start-up Form January2014