aston-built products start-up form and · pdf filecheck the belt and pulley on the wheel drive...

8
IMPORTANT Complete all forms under this appendix for each unit and email, fax or mail to Venmar CES imme- diately after start-up to validate warranty and to provide valuable information for personnel perform- ing future maintenance or for factory assistance to address below. Read the Installation, Operation and Maintenance Instruction Manual and the Venmar CES Control System Keypad Operation Guide and the Sequence of Operation before proceeding. Leave a copy of this report with the owner and at the unit for future reference and permanent record. To ensure proper operation of each unit, qualified personnel should perform the start-up, complete the checklist and report. All units are functionally tested except when shipped in multiple pieces. Start-up adjustments may be required. If the unit is shipped as a single piece, blowers, enthalpy wheel and compressors (if equipped) are set up to run correctly when power is connected. If any blower is running backwards or compressor is making loud noises, disconnect power and switch two leads (on three-phase power) to ensure proper rotation and avoid damage. If units are equipped with compressors, power must be turned on for 24 hours prior to a call for cool- ing, for the compressor crank case heaters to be energizing to prevent possible damage. The Bacview keypad located at the control panel will allow for manual override for start-up, mode of operation selection and includes an internal time clock if remote interlocks are not provided. VCES-ASTON-SF-1B – EnergyPack, ERV5000–10000, HRV3000–10000 Start-up Form January 2014 EnergyPack ® , ERV5000–10000(i/e) and HRV3000–10000(i/e) Start-up Form and Checklist Venmar CES Inc. 200 Rue Carter St. Léonard d’Aston, QC Canada J0C 1M0 Email to tech support: [email protected] Fax: 899-319-2612 Phone: 1-866-4-VENMAR Unit Identification Information Project ____________________________________________ Job Name _________________________________________ Job Address __________________________________________________ __________________________________________________ __________________________________________________ Model Number_____________________________________ Serial Number______________________________________ Tag ______________________________________________ Jobsite Contact ____________________________________ Email _____________________________________________ Telephone_________________________________________

Upload: lamkhanh

Post on 13-Mar-2018

215 views

Category:

Documents


2 download

TRANSCRIPT

Page 1: Aston-built Products Start-up Form and · PDF fileCheck the belt and pulley on the wheel drive for correct alignment ... and adjust the shut-off/balancing valve ... Aston-built Products

IMPORTANT• Completeallformsunderthisappendixforeach

unitandemail,faxormailtoVenmarCESimme-diatelyafterstart-uptovalidatewarrantyandtoprovidevaluableinformationforpersonnelperform-ingfuturemaintenanceorforfactoryassistancetoaddressbelow.

• ReadtheInstallation,OperationandMaintenanceInstructionManualandtheVenmarCESControlSystemKeypadOperationGuideandtheSequenceofOperationbeforeproceeding.

• Leaveacopyofthisreportwiththeownerandattheunitforfuturereferenceandpermanentrecord.

• Toensureproperoperationofeachunit,qualifiedpersonnelshouldperformthestart-up,completethechecklistandreport.

• Allunitsarefunctionallytestedexceptwhenshippedinmultiplepieces.Start-upadjustmentsmayberequired.Iftheunitisshippedasasinglepiece,blowers,enthalpywheelandcompressors(ifequipped)aresetuptoruncorrectlywhenpowerisconnected.Ifanyblowerisrunningbackwardsorcompressorismakingloudnoises,disconnectpowerandswitchtwoleads(onthree-phasepower)toensureproperrotationandavoiddamage.

• Ifunitsareequippedwithcompressors,powermustbeturnedonfor24 hours prior to a callforcool-ing,forthecompressorcrankcaseheaterstobeenergizingtopreventpossibledamage.

• TheBacviewkeypadlocatedatthecontrolpanelwillallowformanualoverrideforstart-up,modeofoperationselectionandincludesaninternaltimeclockifremoteinterlocksarenotprovided.

VCES-ASTON-SF-1B – EnergyPack, ERV5000–10000, HRV3000–10000 Start-up Form January2014

EnergyPack®, ERV5000–10000(i/e) and HRV3000–10000(i/e) Start-up Form and Checklist

Venmar CES Inc.200RueCarterSt.Léonardd’Aston,QCCanadaJ0C1M0

Emailtotechsupport:[email protected]:899-319-2612Phone:1-866-4-VENMAR

Unit Identification InformationProject____________________________________________JobName_________________________________________JobAddress______________________________________________________________________________________________________________________________________________________ModelNumber_____________________________________SerialNumber______________________________________Tag ______________________________________________JobsiteContact ____________________________________Email_____________________________________________Telephone_________________________________________

Page 2: Aston-built Products Start-up Form and · PDF fileCheck the belt and pulley on the wheel drive for correct alignment ... and adjust the shut-off/balancing valve ... Aston-built Products

SerialNumber:_____________________________________

Table E1: Pre Start-up ChecklistChecklist Item Check √ N/A

1 Checktheelectricaldisconnectsettothe‘Off’position.

2 Checkthesplitsectionjointsareproperlyinstalledonmulti-sectionalunits.

3CheckthatallholesthathavebeenmadebytheInstallingContractorafterreceivingtheunitinthecasing,partitionsorfloorhavebeenwellsealedtopreventairand/orwaterinfiltration.

4Checktheunitforobstructivepackaging,objectsnearorinfans,dampers,energyrecoverywheel,etc.

a. Checkthattheinsideofunithasbeencleanedofalldebris.

5

Removeallretainingboltsonfanisolationbases.

a. Checkthatthefanimpellersarerotatingfreely.

b. Checkfanimpellersanddrivesetscrews.Tightenifrequired.

c. Checkthefanbearingsetscrewsorlockingcollars.Tightifrequired.

d. Checkfanbeltalignmentandtension.

e. Checkthefanflexiblejointconnectionsarewellattached.

6

Checkthattheairfiltersareinstalledandclean.Replaceifnecessary.SeeAppendixFforoptionaldownstreamhighefficiencyHEPAfilterinstallation(ifsupplied).a. Checkallfacemountedfiltersareattachedwithfourclipseach.

b. Checkeachslidingfilterhasaretainerattheendtrackandwellattachedblank-offs.c. Checkthefilterpressuredifferentialgauges,switchesorsensorsarefreeofdirtandsetata

valuesatisfactorytotheendusertotriggerafilterchange.

7

Checkcoilsiffinshavebeendamagedinshipping,installationorbuildingconstructionandareclean.Straightenfinswithafincombandcleancoilifrequired.a. Checkallpipeconnectionsaretightandthatnodamagehasoccurredduringshippingorinstallation.b. CheckthatthepipingtothecoilsandWSHPhavebeencompleted,pipinglineshavebeen

flushed,filled,ventedandtestedat1.2timestheoperatingpressure.RefertoAppendixB.

8

ScrollcompressorRISvibrationisolatorboltsarefactorytightenedtothecorrecttorquesettingforoperationanddonotrequirefieldadjustment.a. Checktherefrigerantcomponentsandpipingareingoodconditionandhavenodamageor

leaksfromshippingorinstallation.b. Checkthattherefrigerantlinesarespacedatleast1”apartandfromthecompressoraftership-

pingandinstallation.c. Checkthattherefrigerantlineclampsarestillsecureandhavetheirrubberlining.d. Checkthattheclearancearoundtheaircooledcondenseriswithinminimumclearanceandthe

dischargeisnotblocked.

9Checkmotorizeddampercontrolarms,controlrodsandshaftsfortightness.

a. Checkthatnonmotorizeddampersrotatefreely.

10

Checktheenergyrecoverywheelmediaforanydefectsfromshippingorinstallation.SeeMainte-nancesectionfordetails.a. Greasebothpillowblockbearingsonthewheel(s)whengreasenipplesprovided.

b. Checkthatthewheel(s)areturningfreelybyhandanddonotbind.c. Visuallyinspectthewheel(s)toensureitiscenteredanddoesnottilt.Ifthereisanyindicationof

aproblemcallVenmarCESTechSupportat1-866-4-VENMAR.d. Checkthatthewheelsealsareproperlypositionedfromthefaceofthewheel.

e. Checkthatthewheelpurge(ifpresent)issettothedefaultangleasspecifiedinthesubmittal.

f. Checkthemountingfastenersonthewheel(s)motorandgearreduceraretight.

g. Checkthebeltandpulleyonthewheeldriveforcorrectalignment,tensionandsetscrewtightness.

11 Checktheplatemediaforanydefectsfromshippingorinstallation.

VCES-ASTON-SF-1B – EnergyPack, ERV5000–10000, HRV3000–10000 Start-up Form January2014

Page 3: Aston-built Products Start-up Form and · PDF fileCheck the belt and pulley on the wheel drive for correct alignment ... and adjust the shut-off/balancing valve ... Aston-built Products

Table E1: Pre Start-up ChecklistChecklist Item Check √ N/A

12

Checktheheatpipefinsforanyfindefectsfromshippingorinstallation.

a. Removeretainingboltsonheatpipetiltmechanism.

b. Checktheheatpipeflexibleconnectionisproperlyattachedandsealedontiltmechanism.

c. Checktheactuatorcontrolarmandlinkagesaretightontiltmechanism.

13 Checkthatductworkisconnected,completeandfreeofobstructions.

14 Checkthatcondensatedrainconnectionshavebeentrapped,installedcorrectlyandfilled.

15Checkatallunitsplitsectionsthatallfactoryinternalhighandlowvoltagewiringconnectionshavebeenproperlyre-connected.

16 Checkthatallshippedlooseorfieldsuppliedcomponentshavebeencorrectlyinstalledandwired.

17 Checkthatthewiringdiagramhasbeenmarkedupaccordinglyandleftwiththeunit.

18CheckthatallpowersuppliesandcontrolwiringhavebeeninspectedandapprovedbytheLocalAuthoritieshavingjurisdiction.

19 Checkallfactoryandfieldwiringconnectionsfortightness.Tightenifnecessary.

20 Checkthatallfusesareproperlyinstalledinholders.

21Checkthevoltageatthedisconnectswitchagainstthenameplateandagainstphase-to-phasereadingsonthree-phase.Ifthevoltageisnotwithin10%ofratedor2%ofphasetophase,havetheconditioncorrectedbeforecontinuingstart-up.

22Checkthatallfieldpipingandventinginstallationandconnectionsforheatingandcoolingoptionshavebeencompletedandtested.

23 Settheheatingandcoolingenableswitchestothe‘Off’position.

24RefertoAppendixDforgas-firedfurnacemoduleandAppendixGforelectriccoilinstallationandmaintenanceandcheckthattheinstallationiscompleted.Performallgas-firedfurnaceandelectriccoilprestart-upchecks.

25 Checkthatallsafetyswitches,overloadsorothermanualresetdevicesarereset.

26Iftheunitisequippedwithcompressors,powermustbeturnedonwiththeunitin‘Off’modefor24hoursbeforestart-up.Thiswillenergizecrankcaseheatersandassurenoliquidrefrigerantispresentwhichcouldcausecompressordamageorfailure.Checkthatthishasbeencompleted.

Table E2: Start-up ChecklistChecklist Item Check √ N/A

1 Beforeproceeding,completetheprestart-upchecklist.

2 Checkthatallaccesspanelsordoorsareclosed.

3

Ifunitsareequippedwithcompressors,feelthecompressorcrankcases.Theyshouldbewarmifthedisconnecthasbeen‘On’foratleast24hours.Thiswillassurethatnorefrigerantliquidispresentinthecrankcasewhichcouldcausecompressordamageorfailuretooccuronstart-up.Otherwise,turnthemaindisconnecttothe‘On’position.

4

TheunitcanbestartedbyusingthekeypadandselectingthemodeofoperationfromtheKeypadOperationGuideandtheSequenceofOperation.Disabletheheatingandcoolingfunctionsandsettheunittotheoccupiedmodetobumpstartthefanwheel(s)andenergyrecoverywheel(s)tochecktheiroperation.

5 Checkthatdampersareoperatingproperly.

6 Checkthatthefanwheel(s)andenergyrecoverywheel(s)arerotatinginthecorrectdirection.

7 AdjustthefanmotorVFD(s)tothecorrectairvolume/Hertz.

8Foroccupiedrecirculationmode,adjustoutside,exhaustandmixedorrecirculationairdamperpositionerstoachievetherequiredairvolumes.

9CheckamperagedrawtoeachmotoroneachphaseagainstmotornameplateFLA.Ifsignificantlydifferent,checkductworkstaticand/ortakecorrectiveaction.

SerialNumber:_____________________________________

VCES-ASTON-SF-1B – EnergyPack, ERV5000–10000, HRV3000–10000 Start-up Form January2014

Page 4: Aston-built Products Start-up Form and · PDF fileCheck the belt and pulley on the wheel drive for correct alignment ... and adjust the shut-off/balancing valve ... Aston-built Products

Table E2: Start-up ChecklistChecklist Item Check √ N/A

10Recheckthevoltageatthedisconnectswitchagainstthenameplateandagainstphase-to-phasereadingsonthree-phasewithallblowersoperating.Ifthevoltageisnotwithin10%ofratedor2%ofphase-to-phasehavetheconditioncorrectedbeforecontinuingstart-up.

11BeforeactivatingthecompressoronWSHPunits,checkthatthewatershut-offvalvesareopenandwateriscirculatingthroughthewater-to-refrigerantheatexchanger.Checktheincominglinewaterpressuretoensureiswithindesignandacceptablelimits.

12Enablethecoolingmodeofoperation.Checkifthesoundofthecompressorisnormalorifthereisexcessivevibration.

13Onunitswithintegratedaircooledcondenserscheckcondenserfansarerotatinginthecorrectdirection.

14 Checkallfieldandfactoryrefrigerantandwaterpipingconnectionsforleaksandcorrect.

15

Operatetherefrigerantsystemnearfullloadconditionsinbothheatingandcoolingmodesandchecksub-coolingandsuperheatagainstvaluesinAppendixP,TableP1.Ifreadingsdonotmatch,adjusttherefrigerantcharge.RefertoAppendixPforinformationonadjustingtherefrigerationcharge.

16

OnunitswithWSHP,afterafewminutesofoperation:a. Checkthesupplydischargetemperaturestatusonthekeypadforcoolingairdelivery.Measure

thetemperaturedifferencebetweenenteringandleavingwater.Incoolingmode,thetempera-turedifferenceshouldbeapproximately1.5timesgreaterthantheheatingmodetemperaturedifference.Forexample,ifthecoolingtemperaturedifferenceis15°F[8.3°C],theheatingtemperaturedifferenceshouldbeapproximately7°Fto10°F[3.9°Cto5.6°C].Alternatively,ifaflowmeasuringvalveorpressuregaugeconnectionsareincluded,taketheflowreadingorpres-suredropcomparedtothesubmittalinformationandadjusttheshut-off/balancingvalveinthereturnlinetothecorrectflow/pressuredropreading.

b. Measurethetemperaturedifferencebetweenenteringandleavingairandenteringandleavingwater.Withenteringwaterof60°Fto80°F[15.6°Cto26.7°C],leavingtemperatureshouldrisethroughtheunit.Shouldnotexceed35°F[19.4°C].Iftheairtemperatureexceeds35°F[19.4°C],thenthewaterflowrateisinadequateortheairflowratemaybelowandasecondcheckmayberequiredafterairflowbalancing.

17Onunitswithgas-firedfurnacemoduleorelectricheatingcoils,checksupplyairprovinginterlockswitchsettingtoensureminimumsupplyairflowpriortoburneroperation.Settheswitchtoopenbelowtheminimumsupplyairflowonthefurnaceratingplate.

18Enableheatingoptions,seestart-upandcheckoutinstructionsinAppendixDforgas-firedfurnacemoduleandAppendixGforelectriccoilandcomplete.

19Forelectricheatingcoiloptionchecktheampdrawoneachstage,theoperationofthesequenceorSCRcontrollerandthecoilforanyhotspots.

20 Checktheoperationofthecontroloptionsprovidedontheunit.

21 CheckthesetpointsontheDDCPointsReference,adjustandrecordchangesasrequired.

22 Hasairbalancingbeencompletedforbothoccupiedandunoccupiedoperation?

23

Whenunithasachievedsteadystate,takemeasurementsandcompleteStart-upReadingsportionoftheStart-upReportandChecklistinAppendixE.SendacopyofthecompletedStart-upReportandChecklisttoVenmarCEStovalidatewarranty.Maintainacopyofthereportattheunitforfuturereference.

24Oncecompleted,returnsetpointstooriginalorrequiredvalues,returntheunittothecorrectmodeofoperationandadjustthetimeclockifrequired.

SerialNumber:_____________________________________

VCES-ASTON-SF-1B – EnergyPack, ERV5000–10000, HRV3000–10000 Start-up Form January2014

Page 5: Aston-built Products Start-up Form and · PDF fileCheck the belt and pulley on the wheel drive for correct alignment ... and adjust the shut-off/balancing valve ... Aston-built Products

Start-up Readings• Allowunittoreachsteadystatebeforetakingreadings.• Completebasedonoptionsincludedwithunit

Nameplatevoltage

Inputvoltage L1–L2 L2–L3 L1–L3

Table E3: Start-up Readings – Supply Fan

Rotation Correct

Full Load Amps (Nameplate Amps)

Amp Draw O/L Amp Setting

Hertz RPML1 L2 L3

Fan1

Fan2

Fan3

Fan4

Fan5

Fan6

Fan7

Fan8

Fan9

Fan10

Fan11

Fan12

Table E4: Start-up Readings – Exhaust Fan

Rotation Correct

Full Load Amps (Nameplate Amps)

Amp Draw O/L Amp Setting

Hertz RPML1 L2 L3

Fan1

Fan2

Fan3

Fan4

Fan5

Fan6

Fan7

Fan8

Fan9

Fan10

Fan11

Fan12

SerialNumber:_____________________________________

VCES-ASTON-SF-1B – EnergyPack, ERV5000–10000, HRV3000–10000 Start-up Form January2014

Page 6: Aston-built Products Start-up Form and · PDF fileCheck the belt and pulley on the wheel drive for correct alignment ... and adjust the shut-off/balancing valve ... Aston-built Products

SerialNumber:_____________________________________

Table E6: Start-up Readings – Compressors

Full Load Amps

(Nameplate Amps)

Amp DrawAfter compressor has been running for 15 minutes check the

following:

Suction Pressure

Discharge Pressure

SuperheatLiquid

Subcooling

Hot Gas Bypass

Functioning

Outdoor Ambient Temp.

During AC Cooling

Start-up (°F/°C)

L1 L2 L3

Compressor1

Compressor2

Compressor3

Compressor4

Compressor5

Compressor6

Compressor7

Compressor8

Compressor9

Compressor10

Compressor11

Compressor12

Compressor13

Compressor14

Compressor15

Compressor16

Table E5: Start-up Readings – Condenser Fan

Rotation CorrectFull Load Amps

(Nameplate Amps)Amp Draw

O/L Amp SettingL1 L2 L3

Fan1

Fan2

Fan3

Fan4

Fan5

Fan6

Fan7

Fan8

Fan9

Fan10

Fan11

Fan12

Fan13

Fan14

Fan15

Fan16

VCES-ASTON-SF-1B – EnergyPack, ERV5000–10000, HRV3000–10000 Start-up Form January2014

Page 7: Aston-built Products Start-up Form and · PDF fileCheck the belt and pulley on the wheel drive for correct alignment ... and adjust the shut-off/balancing valve ... Aston-built Products

Table E7: Start-up Readings – WSHPWaterside Cooling Mode Waterside Heating Mode

Entering Temp. (°F/°C)

Leaving Temp. (°F/°C)

Temp. Difference

(°F/°C)

Entering Temp. (°F/°C)

Leaving Temp. (°F/°C)

Temp. Difference

(°F/°C)

Entering Pressure

(PSI)

Leaving Pressure

(PSI)US GPM

Condenser1

Condenser2

Condenser3

Condenser4

Condenser5

Condenser6

Condenser7

Condenser8

Condenser9

Condenser10

Condenser11

Condenser12

Condenser13

Condenser14

Condenser15

Condenser16

SerialNumber:_____________________________________

Table E8: Start-up Readings – Electric Heating CoilStage L1 Amps L2 Amps L3 Amps Check for Hot Pots

1

2

3

4

5

6

Table E9: Start-up Readings – Energy Recovery Wheel (ERW)

Full Load Amps (Nameplate Amps)

Amp DrawO/L Amp Setting

L1 L2 L3

ERW1

ERW2

ERW3

ERW4

VCES-ASTON-SF-1B – EnergyPack, ERV5000–10000, HRV3000–10000 Start-up Form January2014

Page 8: Aston-built Products Start-up Form and · PDF fileCheck the belt and pulley on the wheel drive for correct alignment ... and adjust the shut-off/balancing valve ... Aston-built Products

SerialNumber:_____________________________________

Thisunithasbeencheckedoutandstartedaccordingwiththeaboveproceduresandcompletedformsandisoperatingsatisfactorily.After24hoursofsatisfactoryop-erationshutdowntheunitandcheckallfoundationbolts,shaftbearings,drivesetscrews,valvetrainandterminals.Tightenwhererequired.

AdditionalComments:______________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________

Start-upBy________________________________________________CompanyName____________________________________Date______________________________________________Email_____________________________________________Telephone_________________________________________

Emailtotechsupport:[email protected]:819-399-2612.

Table E10: Start-up Readings – Gas-fired Duct FurnaceFuel Natural Gas Propane Furnace #1 Furnace #2

Combustionairfan

Rotationcorrect2

Fullloadamps(nameplateamps)2

AmpdrawL1/L2/L32

O/Lampsetting2

Induceddraftfanmotor

RotationcorrectFullloadamps(nameplateamps)AmpdrawL1/L2/L3O/Lampsetting

Lowfire

Inletgaspressure–”w.c.Regulatoroutletpressure–”w.c.Manifoldpress–”w.c.StackCO2–%2

StackO2–%2

Netstacktemperature–°F/°C2

Efficiency–%2

Flamesignal–mA/VDCSupplyairinlettemperature–°F/°CSupplyairdischargetemperature–°F/°C1

Supplyairtemperaturerise–°F/°C

Highfire

Inletgaspressure–”w.c.Regulatoroutletpressure–”w.c.2

Manifoldpress–”w.c.StackCO2–%2

StackO2–%2

Netstacktemperature–°F/°C2

Efficiency–%2

Flamesignal–mA/VDCSupplyairinlettemperature–°F/°CSupplyairdischargetemperature–°F/°C1

Supplyairtemperaturerise–°F/°C1.Measuredownstreamwheretemperatureiseveninduct.2.ForIGseriesdrumandtubegas-firedductfurnacemodelsonly.

VCES-ASTON-SF-1B – EnergyPack, ERV5000–10000, HRV3000–10000 Start-up Form January2014