Bock Compressor FK40
Assembly instructions
2 0971
6-04
.201
2-DG
bFEI
TrCn
D
GB
F
E
I
TR
CN
1 Safety 4 1.1 Identificationofsafetyinstructions 1.2 Qualificationsrequiredofpersonnel 1.3 Generalsafetyinstructions 1.4 Intendeduse 2 Product description 6 2.1 Briefdescription 2.2 Nameplate 2.3 Typekey 3 Areas of application 8 3.1 Refrigerants 3.2 Oilcharge 3.3 Limitsofapplication 3.4 NandKversions 3.4.1 LimitsofapplicationR134a 3.4.2 LimitsofapplicationR407C 3.5 TKversion 3.5.1 LimitsofapplicationR404A/R507 3.5.2 LimitsofapplicationR22 4 Compressor assembly 11 4.1 Settingup 4.2 Maximumpermissibleinclination 4.3 V-beltdrive 4.4 Mainbearingload 4.5 Electromagneticcouplingassembly 4.6 Pipeconnections 4.7 Pipes 4.8 Operatingtheshut-offvalves 4.9 Operatingmodeofthelockableserviceconnections 5 Commissioning 15 5.1 Preparationsforstart-up 5.2 Pressurestrengthtest 5.3 Leaktest 5.4 Evacuation 5.5 Refrigerantcharge 5.6 Oillevelcheck 5.7 Shaftseal 5.8 Shaftseal,emptyingtheoilreservoir 5.9 Avoidingliquidshocks 6 Maintenance 18 6.1 Preparation 6.2 Worktobecarriedout 6.3 Recommendedspareparts 6.4 Integrateddecompressionvalve 6.5 Extractfromthelubricantstable 6.6 Decommissioning 7 Accessories 20 7.1 Capacityregulator 7.2 Thermalprotectionthermostat 8 Technical data 21 9 Dimensions and connections 22 10 Installationcertificate 24 11 Service 25
About these instructionsReadtheseinstructionsbeforeassemblyandbeforeusingthecompressor.Thiswillavoidmisunder-standings andpreventdamage.Improperassemblyanduseofthecompressorcanleadtoseriousorfatalinjury.Observethesafetyinstructionscontainedintheseinstructions.Theseinstructionsmustbepassedontotheendcustomeralongwiththeunitinwhichthecompres-sorisinstalled.
GEABockGmbH
72636Frickenhausen
GEABockGmbH
Benzstraße7
72636Frickenhausen
Germany
Telephone +49702294540
Fax +4970229454-137
www.bock.de
Manufacturer
Contact
30971
6-04
.201
2-DG
bFEI
TrCn
D
GB
F
E
I
TR
CN
Contents Page
1 Safety 4 1.1 Identificationofsafetyinstructions 1.2 Qualificationsrequiredofpersonnel 1.3 Generalsafetyinstructions 1.4 Intendeduse 2 Product description 6 2.1 Briefdescription 2.2 Nameplate 2.3 Typekey 3 Areas of application 8 3.1 Refrigerants 3.2 Oilcharge 3.3 Limitsofapplication 3.4 NandKversions 3.4.1 LimitsofapplicationR134a 3.4.2 LimitsofapplicationR407C 3.5 TKversion 3.5.1 LimitsofapplicationR404A/R507 3.5.2 LimitsofapplicationR22 4 Compressor assembly 11 4.1 Settingup 4.2 Maximumpermissibleinclination 4.3 V-beltdrive 4.4 Mainbearingload 4.5 Electromagneticcouplingassembly 4.6 Pipeconnections 4.7 Pipes 4.8 Operatingtheshut-offvalves 4.9 Operatingmodeofthelockableserviceconnections 5 Commissioning 15 5.1 Preparationsforstart-up 5.2 Pressurestrengthtest 5.3 Leaktest 5.4 Evacuation 5.5 Refrigerantcharge 5.6 Oillevelcheck 5.7 Shaftseal 5.8 Shaftseal,emptyingtheoilreservoir 5.9 Avoidingliquidshocks 6 Maintenance 18 6.1 Preparation 6.2 Worktobecarriedout 6.3 Recommendedspareparts 6.4 Integrateddecompressionvalve 6.5 Extractfromthelubricantstable 6.6 Decommissioning 7 Accessories 20 7.1 Capacityregulator 7.2 Thermalprotectionthermostat 8 Technical data 21 9 Dimensions and connections 22 10 Installationcertificate 24 11 Service 25
4 0971
6-04
.201
2-DG
bFEI
TrCn
D
GB
F
E
I
TR
CN
1.1 Identificationofsafetyinstructions:
DANGER!
WARNING!
CAUTION!
ATTENTION!
INFO!
Indicates a dangerous situation which, if not avoided, will cause immediate fatal or serious injury.
Indicates a dangerous situation which, if not avoided, may cause fatal or serious injury.
Indicates a dangerous situation which, if not avoided, may cause fairly severe or minor injury.
Indicates a situation which, if not avoided, may cause property damage.
Important information or tips on simplifying work.
1| Safety
1.2 Qualificationsrequiredofpersonnel
1.3 General safety instructions
DANGER! •Refrigerating compressors are pressurised machines and as such call for heightened caution and care in handling.
The maximum permissible overpressure must not be exceeded, even for testing purposes.
WARNING! •Risk of burns! Depending on the operating conditions, surface temperatures of over 60°C on the discharge side or below 0°C on the suction side can be reached.
WARNING! Inadequately qualified personnel poses the risk of accidents, the consequencebeingseriousorfatalinjury.Workoncompressorsis therefore reserved for personnel with the qualifications listed below: •For example, a refrigeration technician, refrigeration mechatronic engineer. As well as professions with comparable training, which enables personnel to assemble, install,maintain and repair refrigeration and air-conditioningsystems.Personnelmustbecapableofassessingthe worktobecarriedoutandrecognisinganypotentialdangers.
50971
6-04
.201
2-DG
bFEI
TrCn
D
GB
F
E
I
TR
CN
1| Safety
These assembly instructions describe the standard version of the FK40 manufac-tured by Bock. The compressor is intended for use in refrigeration systems in compliancewith the operating limits. Only the refrigerant specified in these instructions may be used. Any other use of the compressor is prohibited!
TheBockrefrigeratingcompressornamedinthetitleisintendedforinstallationinamachine(withintheEUaccordingtotheEUDirectives2006/42/ECMachineryDirective,97/23/ECPressureEquipmentDirective).Commissioningispermissibleonlyifthecompressorhasbeeninstalledinaccordancewiththeseas-semblyinstructionsandtheentiresystemintowhichitisintegratedhasbeeninspectedandapprovedinaccordancewithlegalregulations.
1.4 Intended use
6 0971
6-04
.201
2-DG
bFEI
TrCn
D
GB
F
E
I
TR
CN
2| Product description
Threedifferentdesignsareavailableforvariousrangesofapplication:> for air-conditioning the K Design> for air-conditioning or normal cooling the N Design> for deep freezing the TK DesignThedifferencesliemainlyinthevalveplatetoolingwhichisadaptedtoeachapplicationrangewhereoperationalsafetyandefficiencyareconcerned.
CompactfourcylindercompressorinVdesign. Fourcapacityranges. Lightweightaluminumdesign. Lubricatingoilpumpwithoilpressurereliefvalveindependentofrotationaldirection. Variablearrangementoftheshut-offvalves.
Nameplate
Fig.1
2.1 Brief description
Fig.2
Oilsightglass
Valveplate
Cylindercover
Dischargeshut-offvalve
Shaftend
Shaftseal
Suctionshut-offvalve
Oilpump
DimensionandconnectionvaluescanbefoundinChapter9
Eyebolt
Oilsightglass
Leakoiltrappingdevicewithoilreservoir
Leakoil drainhose
70971
6-04
.201
2-DG
bFEI
TrCn
D
GB
F
E
I
TR
CN
2| Product description
/FK 04 655 NX
1 Typedesignation2 Displacementat1450rpm3 LP:Max.permissibleoperatingpressure
(g)Lowpressureside HP:Max.permissibleoperatingpressure
(g)Highpressureside
4 Machinenumber5 Factory-filledoiltype
Fig.3
2.2 Name plate (example)
2.3 Type key (example)
¹)K- speciallyforair-conditioning
N- speciallyforair-conditioningornormalcooling
TK-speciallyfordeepfreezing
²)X- Esteroilcharging(HFCrefrigerant,e.g.R134a,R407C)
Designs¹)
Sweptvolume
Size
Esteroilcharging²)
Series
1
2
3
4
5
AS12345A020
19/28bar
Observe the limits of application diagrams!}
GEA Bock GmbH72636 Frickenhausen, Germany
8 0971
6-04
.201
2-DG
bFEI
TrCn
D
GB
F
E
I
TR
CN
3| Areas of application
ATTENTION! Compressor operation is possible within the limits of application showninthediagrams.Pleasenotethesignificanceoftheshadedareas. The limits of application must be observed. Thresholds should not be selected as design or continuous operating points.
-Max.permissibledischargeendtemperature:140°C -Max.permissibleambienttemperature:100°C -Max.permissibleswitchingfrequency:12x/h -Aminimum running time of 2min. at equilibrium (continuous operation) must be achieved.
Avoid continuous operation near the threshold. Should the com-pressor happen to be used near the thresholds, we recommend the useofathermalprotectionthermostat(Accessories,Chap.7).
When capacity regulators are used, the limits of application can move.
When operating in the vacuum range, there is a danger of air en-tering on the suction side. This can cause chemical reactions, a pressure rise in the condenser and an elevated compressed-gas temperature. Prevent the ingress of air at all costs!
Thecompressorsarefactory-filledwiththefollowingoiltype:-forR134a,R404A/R507,R407C FUCHSRenisoTritonSE55 -forR22 FUCHSRenisoSP46Compressorswithesteroilcharge(FUCHSRenisoTritonSE55)aremarkedwithanXinthetypedesignation (e.g.FKX40/655N).
3.1 Refrigerants• HFKW/HFC: R134a,R404A/R507,R407C• (H)FCKW/(H)CFC: R22
3.2 Oil charge
3.3 Limits of application
INFO! Forrecharging,werecommendtheaboveoiltypes.Alternativesare: see lubricants table, Chapter 6.5.
90971
6-04
.201
2-DG
bFEI
TrCn
D
GB
F
E
I
TR
CN
3| Areas of application
Designforotherrangesonrequest
Max. permissible operating pressure(g)onthehigh-pressureside(HP):28bar
Max. permissible operating pressure(g)onthehigh-pressureside(HP):28bar
Unrestrictedapplicationrange
Unrestrictedapplicationrange
reducedsuctiongastemperature
reducedsuctiongastemperature
Evaporatingtemperature(°C)
Evaporatingtemperature(°C)
Condensingtemperature(°C)
Condensingtemperature(°C)
Suctiongassuperheat(K)
Suctiongassuperheat(K)
Suctiongastemperature(°C)
Suctiongastemperature(°C)
Fig.4
Fig.5
20
30
50
70
80
-20 -10 100 20 30 t (°C)o
t (°C)c
82
-30
40
60
90
t + 25 °Coh
< ? toh 20 K
R134a
20
30
50
-20 -10 100 20 t (°C)o
t (°C)c
61
-30
40
60
-25
< ? toh 20 K
t + 25 °Coh
R407C
3.4.1LimitsofapplicationR134a(NandKversions)
3.4 N and K versionsModelsavailable:
•FKX40/390N •FKX40/470N •FKX40/560N•FKX40/655N •FKX40/390K •FKX40/470K •FKX40/560K•FKX40/655K
Permissiblerotationspeeds:
NDesign:500-3000¹/rpm(maxrotationspeed3500rpm)KDesign:500-3500¹/rpm
3.4.2LimitsofapplicationR407C(NandKversions)
Permissiblerotationspeeds:
NDesign:500-2600¹/rpmKDesign:500-3500¹/rpm
10 0971
6-04
.201
2-DG
bFEI
TrCn
D
GB
F
E
I
TR
CN
3| Areas of application
3.5 TK version
Modelsavailable:
•FK40/390TK •FK40/470TK •FK40/560TK •FK40/655TK•FKX40/390TK •FKX40/470TK •FKX40/560TK •FKX40/655TK
3.5.1LimitsofapplicationR404A/R507(TKversion)
3.5.2LimitsofapplicationR22(TKversion)
Permissiblerotationspeeds:
TKdesign:500-2600¹/rpm
Permissiblerotationspeeds:
TKdesign:500-2600¹/rpm
FK
100-10-20-30-40-5020
30
40
50
60
70
t (°C)o
t (°C)c
Dtoh<20K
t +20°Coh
58
-45
R404A/R507
R404A/R507 TK
t c
t 0
toh
Dt oh
Verdampfungstemperatur (°C)
Verflüssigungstemperatur (°C)
Sauggasüberhitzung (K)
Sauggastemperatur (°C)
UneingeschränkterAnwendungsbereich
reduzierte Sauggastemperatur
FK
R22
t c
t 0
toh
Dt oh
Verdampfungstemperatur (°C)
Verflüssigungstemperatur (°C)
Sauggasüberhitzung (K)
Sauggastemperatur (°C)
UneingeschränkterAnwendungsbereich
reduzierte Sauggastemperatur
R22 TK
100-10-20-30-40-5020
30
40
50
60
70
t (°C)o
t (°C)c
Dtoh<20K
t +25°Coh
66
-45
Max. permissible operating pressure(g)onthehigh-pressureside(HP):28bar
Unrestrictedapplicationrange
reducedsuctiongastemperature
Evaporatingtemperature(°C)
Condensingtemperature(°C)
Suctiongassuperheat(K)
Suctiongastemperature(°C)
Fig.6
R404A/R507
R22
Max. permissible operating pressure(g)onthehigh-pressureside(HP):28bar
Unrestrictedapplicationrange
reducedsuctiongastemperature
Evaporatingtemperature(°C)
Condensingtemperature(°C)
Suctiongassuperheat(K)
Suctiongastemperature(°C)
Designforotherrangesonrequest
Fig.7
110971
6-04
.201
2-DG
bFEI
TrCn
D
GB
F
E
I
TR
CN
4| Compressor assembly
4.1 Setting up
4.2 Maximum permissible inclination
A max.30°, max.2minutes
a max.15°,continuousoperation
ATTENTION! Poor lubrication can damage the compressor. Respect the stated values.
INFO! Newcompressorsarefactory-filledwithinertgas(3barnitrogen).Leave this service charge in the compressor for as long as possible and prevent the ingress of air.
Check the compressor for transport damage before starting any work.
Fig.8 Fig.9
Transportandsuspensionunitontheeyebolt(Fig.8)ordirectonthedischargelinevalve (Fig.9).
Fittings (e.g. pipe holders, additional units etc.) on the compressor are permissible onlyfollowingconsultationwithBock.
Setuponanevensurfaceorframewithsufficientload-bearingcapacity.Useall4fasteningpoints.
Correctsetupofthecompressorandmountingofthebeltdrivearedecisiveforrunningcomfort,operatingsafetyandtheservicelifeofthecompressor.
Aa
Aa
WARNING! Movecompressorsonlywithhoiststhathaveadequateload-bearingcapacity.
Aa
Aa
Fig.10
12 0971
6-04
.201
2-DG
bFEI
TrCn
D
GB
F
E
I
TR
CN
4| Compressor assembly
Duringoperationwith capacity controllers (Accessories,Chap.7), the changing load can causeincreasedrunningnoisesandbeltdrivevibrations.
4.3 V-belt drive
4.4 Main bearing load
4.5 Electromagnetic clutch assembly
ATTENTION! Inappropriately designed belt drives, especially belt knocking or excessive tensioning forces can cause compressor damage! Make sure that the drive belt is designed correctly, e.g. by using tensionersandselectingthebeltprofileandthebeltlength.
Thefollowingdescriptionappliesforanelectromagneticclutchsecuredtoashaft. Toabsorbthemagneticfieldof theelectromagneticclutch, thefrontbearingflangehasasnugfitØ148h8(seeFig.12).
Toconnectthemagneticfield,loosenthe4cheeseheadscrewsM8onthebearingflange(seeFig.12).
Slidethemagneticfieldtoasnugfitandre-attachusingthefourcheeseheadscrewsM8(Fig.13).Screwtorque=34Nm.
Furtherassemblyoftheelectromagneticclutchaccordingtotheclutchmanufacturer.
Fig.12
Bearingflange,front
Magneticfield
Fig.13148h8
Toprevent thebeltdriveoverloadingthecompressormainbearing,ensurethat:
The forceappliedat the forceengagement forceby thebelttension(seeFig.11)mustnotexceedFmax=2750N.
Iftheforceengagementpointshiftsforwards(seeFig.11,smallpoint),theforceFmaxreducesasperthefollowingformula:
Fmax=245kNmm
(90mm+L1[mm])
Fmax= 2750 NMbmax= 245kNmm
L1 (mm)
Fig.11
130971
6-04
.201
2-DG
bFEI
TrCn
D
GB
F
E
I
TR
CN
4| Compressor assembly
4.7 Pipes
Pipesandsystemcomponentsmustbecleananddryinsideandfreeofscale,swarfandlayersofrustandphosphate.Onlyuseair-tightparts.
Laypipescorrectly.Suitablevibrationcompensatorsmustbeprovidedtopreventpipesbeingcrackedandbrokenbyseverevibrations.
Ensureaproperoilreturn. Keeppressurelossestoanabsoluteminimum.
ATTENTION! Overheating can damage the valve. Therefore, remove the pipe supports from the valve before soldering.
Solderonlyusinginertgastoinhibitoxidationproducts(scale).
Thepipe connectionshavesteppedinternaldiameterssothatpipeswithstandardmillimetreandinchdimensionscanbeused. The connection diameters of the shut-off valves are designed for maximum compressor output.The required pipe cross-sectionmust be matched to the capacity. The same applies for non-return valves.
Fig.14:Steppedinternaldiameters
4.6 Pipe connections
Valve spindle seal
4.8 Operating the shut-off valves
Beforeopeningorclosingtheshut-offvalve,releasethevalvespindlesealbyapprox.¼ofaturncounter-clockwise.
Afteractivatingtheshut-offvalve,re-tightentheadjustablevalvespindlesealclockwise.
Fig.15 Fig.16
Release
Tighten
Therequiredtighteningtorquefortheflangeconnectionis60Nm.
14 0971
6-04
.201
2-DG
bFEI
TrCn
D
GB
F
E
I
TR
CN
4| Compressor assembly
4.9 Operating mode of the lockable service connections
1
1
3
3
Pipeconnection
Pipeconnection
2
2
Fig.17
Openingtheshut-offvalve:a) Spindle1:turntotheleft(counter-clockwise)asfarasitwillgo. —>Shut-offvalvefullyopened/serviceconnection2closed.
Fig.18
Openingtheserviceconnection(2):b) Spindle1:Turn½-1rotationtotheright. —>Serviceconnection2opened/shut-offvalveopened. Connection3isprovidedforsafetydevicesandisnotlockable.
150971
6-04
.201
2-DG
bFEI
TrCn
D
GB
F
E
I
TR
CN
5| Commissioning
5.2 Pressure strength test
DANGER! Risk of bursting! The compressor must never be pressurised using oxygen or other technical gases!
The maximum permissible overpressure of the compressor must not beexceededatanytimeduringthetestingprocess(seenameplatedata)!Donotmixanyrefrigerantwiththetestingmedium(N2), as this could cause the ignition limit to shift into the critical range.
5.1 Preparations for start-up
Thecompressorhasbeenfactory-testedforpressureresistance.Thefollowingmustbeobservediftheentireplantissubjectedtoanadditionalpressurestrengthtest:
TesttherefrigerationcircuitaccordingtoEN378-2oracorrespondingsafetystandard. Thepressurestrengthtestisbestcarriedoutusingdrynitrogen(N2).
5.3 Leak test
5.4 Evacuation
Firstevacuatethesystem andthenincludethe compressor in the evacuation process. Relievethecompressorpressure. Openthesuctionanddischargelinevalves. Evacuatethesuctionanddischargepressuresidesusingthevacuumpump. Attheendoftheevacuationprocess,thevacuumshouldbe<1.5mbarwhenthepumpisswitchedoff. Repeattheprocessasoftenasisrequired.
INFO! To protect the compressor against inadmissible operating conditions, high-pressure and low-pressure pressostats are mandatory on the installation side.
Thecompressorhasundergonetrialsinthefactoryandallfunctionshavebeentested.Therearethereforenospecialrunning-ininstructions.
Check the compressor for transport damage!
DANGER! Risk of bursting! Do not mix any refrigerant with the testing medium (N2), as this could cause the ignition limit to shift into the critical range.
CarryouttheleaktestoftherefrigeratingsysteminaccordancewithEN378-2oracorresponding safetystandardwithout including the compressor.
16 0971
6-04
.201
2-DG
bFEI
TrCn
D
GB
F
E
I
TR
CN
5| Commissioning
CAUTION! Wear personal protective clothing such as goggles and protective gloves!
Makesurethatthesuctionanddischargelinevalvesareopen.
Withthecompressorswitchedoff,addtheliquidrefrigerantdirectlytothecondenserorreceiver,breakingthevacuum.
Iftherefrigerantneedstoppingupafterstartingthecompressor,itcanbetoppedupinvapourformonthesuctionside,or,takingsuitableprecautions,alsoinliquidformattheinlettotheevaporator.
Afterstarting,checkthecompressor'soillevel. Drivemotorinoperatingcondition"Highidle". Compressorruntimemin.10minutes. Thesystemshouldhavereachedoperatingpoints. Checkoillevel.Astheinstallationlocationofthecompressorcandifferinpractice(inclinations),it
isrecommendedthattheoillevelischeckedinbothsightglasses.Theoillevelmustbevisibleinatleastonesightglass.
ATTENTION! Avoidoverfillingthesystemwithrefrigerant! Toavoidshiftsinconcentration,zeotropicrefrigerantblends(e.g.
R407C)mustalwaysbeaddedtotherefrigeratingplantinliquid form.
Donotpourliquidrefrigerantthroughthesuctionlinevalveonthe compressor.
It is not permissible to mix additives with the oil and refrigerant.
5.5 Refrigerant charge
5.6 Oil level check
5.7 Shaft seal
ATTENTION! Failure to observe the following instructions can cause loss of refrigerant and damage to the shaft seal!
INFO! The shaft seal seals and lubricates with oil. An oil leakage of 0.05 ml per operating hour is therefore normal. This applies particularlyduringtherun-inphase(200-300h).
Totrapandcollectleakedoil,theFK40isfittedwithanintegratedleakoiltrappingdevicewithoilreservoir(P.6,Fig.1).
ATTENTION! After a compressor is replaced, the oil level must be checked again. If the level is too high, oil must be drained off (riskofoil impact, reduced performance of the air-conditioning system).
170971
6-04
.201
2-DG
bFEI
TrCn
D
GB
F
E
I
TR
CN
5| Commissioning
Aschangingtheshaftseal involvesopeningtherefrigerantcircuit,thisisrecommendedonlyifthesealislosingrefriger-ant.Replacingtheshaftseal isdescribed in thesparepartkitconcerned.Emptyingtheoilreservoir:Theoilreservoircanbeemptiedverysimplewithouthavingtodismantlethecouplingand/orbeltdrive. It isrecommendedthatthis isdoneatthesametimeastheair-conditioningmaintenanceandmotorservice.Toproceed,detachtheoilhosefromthebracket,removethesealingpluganddrain theoil intoacollectingvessel.Afteremptying,resealtheoilhoseandclampit intothebracket. Dispose of the used oil in accordance with national regulations.
Thecompressorshaft issealedtooutsideusingashaftseal.Thesealingelementrotateswiththeshaft.Thefollowingisespeciallyimportanttoensuringfault-freeoperation: Thecompleterefrigerantcircuitmustbecorrectlyexecutedandcleaninside. Heavyshocksandvibrationstotheshaftaswellascontinuouscyclicoperationaretobeavoided. Thesealingsurfacescansticktogetherduringprolongeddowntimes(e.g.winter).Therefore,run
thesystemevery4weeksfor10minutes.
5.8 Shaft seal, emptying the oil reservoir
5.9 Avoidingliquidshocks
ATTENTION! Slugging can damage the compressor and cause refrigerant to leak.
Toavoidliquidshocks,thefollowingpointsshouldbeobserved: Thecompleterefrigerationplantmustbecorrectlydesignedandexecuted. The capacities of all componentsmust be compatible (particularly evaporator and expansion
valve). Suctiongassuperheatingattheevaporatoroutputshouldbeatleast7–10K(checksettingof
theexpansionvalve). Thesystemmustreachastateofequilibrium. Particularly in critical systems (e.g. several evaporator points), suitablemeasures, e.g. use of
liquidtraps,solenoidvalveintheliquidline,etc.arerecommended.
Fig.19
18 0971
6-04
.201
2-DG
bFEI
TrCn
D
GB
F
E
I
TR
CN
6.1 Preparation
6.2 Work to be carried out
6| Maintenance
Oilchange:Inprinciple,anoilchangeisnotmandatoryifthesystemiscorrectlymanufactured andoperated.However, basedondecadesof experiencewe recommend that the followingoilchange/serviceworkiscarriedout:
- Firstoilchangeduringthefirstmaintenanceofthevehicle. - Thenafterevery5,000operatinghours,thoughnomorethan3years,cleantheoilstrainer
atthesametime.Ifnecessary,alsoemptytheoilreservoirattheshaftseal.
Annualchecks:Oil level, tightnessof thecompressor, runningnoise,pressures, temperatures,functionofauxiliarydevicessuchascheckingthecapacitycontrol.
Thevalveismaintenancefree.
However,constant leakagecanoccurafterblowingoffduetoabnormaloperatingconditions.Thisleadstoreducedperformanceandincreasesthecompressedgastemperature.Inthiscasecheckthevalveandreplaceasnecessary.
6.4 Integrated decompression valve
Only use genuine Bock spare parts!
6.3 Recommended spare parts
WARNING! Beforestartinganyworkonthecompressor: Switch off the compressor and secure it to prevent a restart. Relieve compressor of system pressure. Preventairfrominfiltratingthesystem! Aftermaintenancehasbeenperformed: Connect safety switch. Evacuate compressor. Release switch lock.
FK40 / ... 390 N470 N
560 N655 N
390K470K560K655K
390TK470TK
560TK655TK
Designation Art.-Nr. Art.-Nr. Art.-Nr. Art.-Nr. Art.-Nr.
Setofgaskets 80230 80001 80230
Valveplatekit 80240 80241 80010 80240 80241
Setofshaftseals 80023
OilSP46,1Ltr. 02279
OilSE55,1Ltr. 02282
190971
6-04
.201
2-DG
bFEI
TrCn
D
GB
F
E
I
TR
CN
6.6 Decommissioning
Closetheshut-offvalveonthecompressor.Draintherefrigerant(itmustnotbedischargeddirectlyintotheenvironment)anddisposeofitaccordingtotheregulations.Whenthecompressorisdepres-surised,undothefasteningscrewsoftheshut-offvalves.Removethecompressorusinganappropri-atehoist.Disposeoftheoilinsideinaccordancewiththevalidnationalregulations.
6| Maintenance
6.5 Extract from the lubricants table
Theoiltypechargedasstandardinthefactoryismarkedonthename plate. This oil type should be used as a preference.Alternativesarestatedintheextractfromourlubricantstablebelow.
Refrigerant Bock standard oil grade Recommendedalternatives
HFC(e.g.R134a,R407,R404A)
Fuchs Reniso Triton SE 55(seealsochap.6.3)
FuchsSEZ32/68/80ICIEmkarateRL46SMobilArcticEAL46ShellClavusR46
HCFC(e.g.R22) Fuchs Reniso SP 46(seealsochap.6.3)
MobilSHC425ShellClavusSD22-12SunoilSuniso4GSTexacoCapellaWF46
20 0971
6-04
.201
2-DG
bFEI
TrCn
D
GB
F
E
I
TR
CN
7| Accessories
7.1 Capacity regulation
Foradescription,seetechnicalinformation"Capacityregulation"(ItemNo.09900)
Ifthecapacityregulatorisfactory-fitted,itisintegratedintoanextra,dedicatedcylindercover.Forretrofits,itissuppliedwiththecylindercover.Theregulatorclosesonecylinderbank(capacityregula-tionapprox.50%).
A screw-in option is provided for the sensor element on the hot gas side of the compressor housing(seeChap.9).Connectthethermalprotectionthermostatinserieswiththecontrolline.
TechnicalData:
Switchingvoltagemax. : 24VDCSwitchingcurrentmax. : 2.5Aat24VDCSwitch-offtemperature: 145°C±5KSwitch-ontemperature : approx.115°C
7.2 Thermalprotectionthermostat(ItemNo.07595)
FK40 / ... ... N + TK ... K
Designation Art.-Nr. Art.-Nr.
Specialaccessory12V 08703 08708
Specialaccessory24V 08704 08709
ATTENTION! Capacity-regulated operation alters the gas speeds and pressure ratiosoftherefrigeratingplant:Adjustthesuctionlineroutingand dimensioning accordingly, do not set the control intervals too close and donotletthesystemswitchmorethan12timesperhour(refriger-atingplantmusthavereachedastateofequilibrium).Continuousoperation in the control stage is not recommended as the gas velocity in the plant system under certain circumstances does not guaranteesufficientoil return to thecompressorwithactivated capacity regulator for a compressor speed below 1200 - 1500 rpm.
Werecommendswitchingtounregulatedoperation(100%capacity) for at least 5 minutes per capacity-regulated operating hour. An assuredoilreturncanalsoberealisedbya100%capacityrequire- ment after each compressor restart as otherwise the compressor can also be shut down in the regulated operating time by the thermostat. Electricalactuationofthesolenoidvalve:Normallyopen,(corre-
spondsto100%compressorcapacity). Cylinder covers for capacity regulation are marked with the
designation"CR"(CapacityRegulator).
210971
6-04
.201
2-DG
bFEI
TrCn
D
GB
F
E
I
TR
CN
8| Technical dataTy
peNr
. of
Cyl.
Disp
lace
-m
ent
cm3
Swep
t vo
lum
e(145
0 rpm)
m3 /h
Wei
ght
kg
Disc
harg
e
line
DV
mm/inch
Suct
ion
line
SV
mm/inch
Oil
char
ge
Ltr.
Iner
tia
mom
ent
of th
e dr
ivin
g un
it[kgm
2 ]
Lubr
i-ca
tion
Oil p
ump
FK40
/390
4
385
33.5
34.0
22 /7/ 8
28 /1
1/ 8
2.0
0.00
43Forced
lubrication
Rotatio
n-inde
pend
ent
FK40
/470
466
40.5
33.0
28 /1
1/ 8
35 /1
3/ 8
FK40
/560
554
48.3
33.0
28 /1
1/ 8
35 /1
3/ 8
FK40
/655
650
56.6
31.0
35 /1
3/ 8
35 /1
3/ 8
Conn
ectio
ns
Thetech
nicald
ataforthe
differen
tdesignsK,N
and
TKareiden
tical.
Thecompressortypeda
tath
ereforedo
notm
entio
nthesead
ditio
ns.
22 0971
6-04
.201
2-DG
bFEI
TrCn
D
GB
F
E
I
TR
CN
9| Dimensions and connections
Dimensionsin()=K-Design
Shaft end
Centreofgravity
Dimensionsinmm
Dimensionsinmm
Fig.20
Fig.21
169ca.110
ca.1
70
M
SV
A
SV1
A1C/E
G
13
232210
145
329
ca.3
70
4x
ca.320 (325)
F
DV B B1
L
H
K
D
Y
109130
170
4xM
10 L
K
253
344ca.385
Leakoildrainhose
230971
6-04
.201
2-DG
bFEI
TrCn
D
GB
F
E
I
TR
CN
9| Dimensions and connections
1)=Noconnectionavailableasstandard.Availableonrequest(ConnectionM22x1,5)
SVDV
SuctionlineDischargelineseetechnicaldata,Chapter8
A Connectionsuctionside,notlockable 1/8"NPTF
A1 Connectionsuctionside,lockable 7/16"UNF
B Connectiondischargeside,notlockable 1/8"NPTF
B1 Connectiondischargeside,lockable 7/16"UNF
C ConnectionoilpressuresafetyswitchOIL 1/8"NPTF
D ConnectionoilpressuresafetyswitchLP 1/8"NPTF
E Connectionoilpressuregauge 1/8"NPTF
F Oildrain 1/4"NPTF
G Opt.connectionforoilsumpheating 1)
H Oilchargeplug 1/4"NPTF
K Sightglass 2x11/8"-18UNEF
L Connectionthermalprotectionthermostat 1/8"NPTF
M Oilstrainer M22x1.5
SV1 Opt.connectionforsuctionlinevalve - -
24 0971
6-04
.201
2-DG
bFEI
TrCn
D
GB
F
E
I
TR
CN
10| Installation certificate
INSTALLATION CERTIFICATE
forusingthecompressorswithintheEuropeanUnion(inaccordancewithMachineryDirective2006/42/EC)
Themanufacturer: GEABockGmbH,Benzstraße7 D-72636Frickenhausen,Tel.:07022/9454-0
herebydeclaresthattherefrigeratingcompressor FK40conformstotheessentialrequirementsofAnnexII1BoftheMachineryDirective2006/42/EC. Thefollowingharmonisedstandardshavebeenapplied:
EN ISO 12100-1EN ISO 12100-2 EN 12693 EN 349
Apartlycompletedmachinemayonlybeputintooperationwhenithasbeenestablishedthatthemachine,intowhichthepartlycompletedmachineistobeinstalled,conformstotheregulationsoftheMachineryDirective(2006/42/EC).
Themanufacturerundertakestotransmitelectronicallythespecialdocumentationrequired byindividualstatesforpartlycompletedmachineryuponrequest.
Thespecialtechnicaldocumentationrequiredforpartlycompletedmachineryhasbeencreated inaccordancewithAnnexVIIPartB.
Personresponsiblefordocumentationis: WolfgangSandkötter,Benzstraße7,72636Frickenhausen.
Frickenhausen,01.11.2011 ppa.WolfgangSandkötter,ChiefDevelopmentOfficer
250971
6-04
.201
2-DG
bFEI
TrCn
D
GB
F
E
I
TR
CN
Dearcustomer,
Bockcompressorsaretop-quality,reliableandservice-friendlyproducts.Ifyouhaveanyquestionsaboutinstallation,operationandaccessories,pleasecontactourtechnicalserviceorspecialistwhole-salerand/orourrepresentative.TheBockserviceteamcanbecontacted
bytelephone: +49 7022 9454-0 viae-mail: [email protected] orontheInternetat:www.bock.de
In addition, for German-speaking countries we have set up a toll-free Bock hotline 00800/80000088fromMondaytoSaturdaybetween8amand9pm.
Anysuggestionsyoumayhaveregardingtheon-goingdevelopmentofourcompressor,equipmentandsparepartsrangearewelcomeatanytime.
Yours
11| Service
GEABockGmbH
Benzstraße 7
72636 Frickenhausen
Germany
WealsoprovideinformationontheInternetatwww.bock.de. Forexample,underthe"Documentation"linkyouwillfind:
-Technicalinformation-Productinformation-Productbrochures-andmuchmore
10| Installation certificate
- Änderungen vorbehalten -
Sehr geehrter Kunde,Bock-Verdichter sind hochwertige, zuverlässige und servicefreundliche Qualitätsprodukte. Um alle Vorteile in vollem Umfange und über den gesamten Einsatzzeitraum Ihrer Kälteanlage nutzen zu können, beachten Sie unbedingt die folgenden Bedienungs- und Wartungshinweise. Bei Fragen zu Montage, Betrieb und Zubehör wenden Sie sich bitte an unsere Anwendungstechnik oder an den Kältefachgroßhandel bzw. unsere Vertretung. Das Bock-Serviceteam erreichen Sie direkt unter Tel.: +49 7022 9454-0, via e-mail: [email protected] oder im Internet: www.bock.de. Für den deutschspra-chigen Raum steht darüber hinaus die kostenlose Bock-Hotline 00 800 / 800 000 88 von montags bis samstags zwischen 8 und 21 Uhr zur Verfügung. Für Anregungen zur Weiterentwicklung unseres Verdichter-, Ausrüstungs- und Ersatzteilprogramms sind wir Ihnen jederzeit sehr dankbar.
Bock Kältemaschinen GmbHPostfach 11 61D-72632 FrickenhausenBenzstr. 7D-72636 FrickenhausenFon: +49 7022 9454-0Fax: +49 7022 [email protected]
Lesen Sie vor Arbeitsbeginn die in dieser Betriebsanlei-tung für Sie zusammengefassten Informationen.Es werden wichtige Hinweise zur Sicherheit, Montage, Inbe-triebnahme und Bedienung gegeben. Darüber hinaus fi nden Sie Informationen zu Wartung, Ersatzteilen und Zubehör.Einige Hinweise sind besonders gekennzeichnet:
WARNUNG! Dieses Symbol weist darauf hin, dass ungenaues Befolgen oder Nichtbefolgen von Anweisungen zu Schäden an Personen, am Verdichter oder an der Kälteanlage führen kann.GEFAHR! Dieses Symbol weist auf Anweisun-gen hin, um unmittelbare schwere Gefährdun-gen von Personen zu vermeiden.GEFAHR! Dieses Symbol weist auf Anweisun-gen hin, um unmittelbare schwere Gefähr-dungen von Personen oder Anlagen durch elektrischen Strom zu vermeiden.Dieses Symbol verweist auf wichtige Zusatz-hinweise, die bei der Arbeit unbedingt zu berücksichtigen sind.
Das hohe Qualitätsniveau der Bock-Verdichter wird durch die ständige Weiterentwicklung der Konstruktion, der Ausstat-tung und des Zubehörs gewährleistet. Daraus können sich Abweichungen zwischen der vorliegenden Betriebsanleitung und Ihrem Verdichter ergeben. Haben Sie bitte Verständnis, dass deshalb aus den Angaben, Abbildungen und Beschrei-bungen keine Ansprüche abgeleitet werden können.
Ihr Team derBock Kältemaschinen GmbH
26 0971
6-04
.201
2-DG
bFEI
TrCn
D
GB
F
E
I
TR
CN
Excellence Passion Integrity Responsibility GEA-versity
GEA Group is a global mechanical engineering company with multi-billion euro sales and operations in more than 50 countries. Founded in 1881, the company is one of the largest providers of innovative equipment and process technology. GEA Group is listed in the STOXX Europe 600 Index.
GEA Refrigeration TechnologiesGEA Bock GmbH
Benzstraße 7, 72636 Frickenhausen, GermanyTelephone: +49 7022 9454-0, Fax: +49 7022 [email protected], www.bock.de 09