ASPIRATING SMOKE

DETECTION SYSTEMS

Page 2: ASPIRATING SMOKE DETECTION SYSTEMS - SMS Fire · smoke detection with advanced algorithms to detect a wide range of fire types while maintaining enhanced immunity to nuisance particulates

Aspirating Smoke Detection

FAAST LT-200 (Standalone)Fire Alarm Aspirating Sensing Technology®

The FAAST LT-200 Aspirating Smoke Detector is designed with the installer and end user

in mind. It serves the wide variety of Class C applications where maintenance is difficult,

where traditional smoke detection methods are inappropriate or prone to fail due to harsh

environments or areas where aesthetics matter. It is also suitable for smaller mission critical

applications where very early warning - Class A or B detection is required.

FAAST LT-200 combines proven aspirating detection technologies to deliver reliable smoke

detection and efficient installation and maintenance. The device comprises innovative and

intelligent internal design features designed to protect vulnerable components. These include

a high sensitivity LED detection chamber (featuring a high power output IR LED and high gain IR

receiver amplifier), along with ultrasonic flow sensors.

The device is fast to install and easy to commission thanks to Pipe-IQ pipe design and

configuration software, which is included with the product as standard.

FAAST LT-200 stand alone devices are available as single channel and dual channel devices,

offering flexibility for different detection strategies. A range of customisable settings are geared

towards maximising device performance and meeting different application needs.

The device also includes pre-alarm functionality for graduated alarm thresholds.

The FAAST LT-200 provides alarm and fault relays with auxiliary events relay as an option.

These can be set as latched or non-latched. To accommodate local installation standards or

environments, flow and general fault delays can also be set.

F E AT U R E S

• High sensitivity LED Detection Chamber specially designed to cover Class C. Includes a high power output IR LED and high gain IR receiver amplifier

• Single & Dual channel versions with independent channels including fan, sensor and flow monitoring

• Provides pre-alarm functionality for graduated alarm thresholds

• Ultrasonic airflow sensing with expanded monitoring range

• A single device covers up to 2,000m2 according to national design regulations

• Pipe-IQ™ software provides intuitive system layout and configuration all in one package

• Whisper-quiet 26db(A) fan; ideal for discrete detection monitorng

• Multiple event logging up to 2244 events

• User friendly air flow pendulum graph for verification of pipe network functionality

• Easily replaceable and reusable filter without affecting the rest of the device

• Protected electronics from air flow and accidental damage during installation or maintenance

• Designed for efficient wiring and installation: cable gland holes, easy access to the wiring area and no special tools required

• Easy access to parts requiring routine maintenance: filter(s) and sensor(s)

• IP65 enclosure

LT-200

Page 3: ASPIRATING SMOKE DETECTION SYSTEMS - SMS Fire · smoke detection with advanced algorithms to detect a wide range of fire types while maintaining enhanced immunity to nuisance particulates

FAAST LT-200 (Standalone) ARCHITECT / ENGINEERING SPECIFICATION

Honeywell140 Waterside Road

Hamilton Industrial Park

Leicester

LE5 1TN

Tel: +44 (0) 203 409 1779

Email: [email protected]

All technical data is correct at the time of publication and is subjectto changes without notice. All trademarks acknowledged.Installation information: In order to ensure full functionality,refer to the installation instructions as supplied.DSFL-HS-UK-18 | HON© 2018 Honeywell International Inc.

PHYSICAL SPECIFICATION

HEIGHT 403mm (inc. inlets and outlets)

WIDTH 356mm

DEPTH 135mm

CABLE ACCESS 3 x M20 gland holes pre-drilled on top and bottom of the FAAST LT-200 unit

WIRE GUAGE Min. 0.5mm2 – max. 2.0mm2

MAX. SINGLE PIPE LENGTH 100m

MAX. TOTAL BRANCHED PIPE LENGTH

160m (per channel)

MAXIMUM AIR INLET HOLES 18 (per channel)

OUTSIDE PIPE DIAMETER 25mm or 27mm

INTERNAL PIPE DIAMETER 15-21mm

SENSITIVITY RANGE 0.07 - 0.66% obs/m (Alarm level 1-5)

RELAYS 3 (1 Alarm, 1 Fault, 1 Pre-Alarm) x per channel

SOUNDER OUTPUTS 1 per channel

SOUND PERFORMANCE As low as 26db(A)

EVENT LOG 2,244 events

INTERFACES Terminal blocks: power supply, relays, sounder outputs, external input; Loop Connection, USB port; Buttons (Test, Reset, Disable)

POWER SUPPLY & RELAYS CONNECTIONS

Max. 2mm2

USB Standard USB cable for Type B USB connection

SHIPPING WEIGHT -INC. PACKAGING MATERIAL

6.5kg (dual channel)

FLOW MONITORING & REPORTING

High and low according to EN54-20

FILTRATION Replacement filter

ELECTRICAL SPECIFICATIONS

SMOKE SENSORS High sensitivity LED Detection Chamber

EXTERNAL SUPPLY VOLTAGE 18.5-31.5 V

REMOTE RESET TIME 2s

POWER RESET 0.5s

OPERATING CURRENT1 CHANNEL DEVICE

170mA @ 24 VDC (excluding sounders)

2 CHANNEL DEVICE 270mA @ 24 VDC (excluding sounders)

MAX. ALARM CURRENT

1 CHANNEL DEVICE 360mA @24 VDC (excluding sounders)

2 CHANNEL DEVICE 570mA @24 VDC (excluding sounders)

RELAY CONTACT RATINGS 2.0 A @ 30 VDC, 0.5A @ 30 VAC)

ENVIRONMENTAL SPECIFICATIONS

OPERATING TEMPERATURE -10°C to 55°C

HUMIDITY RANGE 10% to 93% (non condensing)

IP RANGE 65

COVERAGE AREA Up to 2,000m3 according to national design regulations

ORDERING INFORMATION

PART NUMBER DESCRIPTION

FL0122E-HS-EB Standalone Dual Channel Detector

FL0112E-HS-EB Standalone Single Channel Dual Detector

FL0111E-HS-EB

ACCESSORIES

Standalone Single Channel Detector

F-LT-EB Earth Bar

FL-IF-6 FAAST LT-200 Integral Filter (6 filters)

Pipe and Fittings Please see Aspirating Accessories Brochure

F-SEN-SSE Replacement detector head

FLT-AB-SA1 FAAST LT SA 1-Ch Accessories Box

FLT-AB-SA2 FAAST LT SA 2-Ch Accessories Box

F-INF-25 External Pipe Filter

F-INF-25-RF External Filter replacement filter pack

LISTINGS & APPROVALS

LPCB

EN54-20: (holes per channel) Class A - 3 holes

Class B - 6 holes

User Interface Display

The front panel will be different depending on which of the 3 loop models is being installed.

The following display information is possible:

• Alarm level; Alarm, Pre-Alarm

• Particulate Levels: 1-5

• Fault Status

• Flow Level

• Test, Reset and Disable Buttons

367mm

3 x cable gland plug

3 x M20 gland holes pre-drilled on top

3 x M20 gland holes pre-drilled on bottom

Page 4: ASPIRATING SMOKE DETECTION SYSTEMS - SMS Fire · smoke detection with advanced algorithms to detect a wide range of fire types while maintaining enhanced immunity to nuisance particulates

The FAAST™ Aspirating smoke detector combines dual source (blue LED and infra-red laser) optical smoke detection with advanced algorithms to detect a wide range of fire types while maintaining enhanced immunity to nuisance particulates. This enables FAAST™ to accurately detect incipient fire conditions as early as 30 minutes before a fire actually starts in Class A and Class B fire detection.

Key Features• Detection as precise as 0.0015%/m obscuration

• Integral Ethernet interface enables remote monitoring and e-mail status updates

• Patented particle separator and field-replaceable filter remove contaminants from the system

• Five alarm levels & two sensitivity modes

• Dual flow detection including both ultrasonic and electronic sensing for pipe and chamber air flow measurement

• Protects up to 2,000 square metres

• Advanced detection algorithms reject common nuisance conditions

• PipeIQ™ software provides intuitive system layout, configuration, and monitoring all in one package

• Fault indictors covering a broad spectrum of events

• Unique air flow pendulum graph verifies pipe network functionality

• Particulate graph displays subtle environmental changes for early problem indications

FAASTTM 8100EFAAST is a ground breaking aspirating solution designed to deliver highly accurate and discreet early warning fire detection.

Aspirating Smoke Detection

Page 5: ASPIRATING SMOKE DETECTION SYSTEMS - SMS Fire · smoke detection with advanced algorithms to detect a wide range of fire types while maintaining enhanced immunity to nuisance particulates

Dimensions FAAST™ User Interface Display

MECHANICAL SPECIFICATION ELECTRICAL

FAAST™ 8110EHeight 337 mm External Supply Voltage 18-30 VDC

Width 330 mmRemote Reset Time

External monitor must be pulled low for a minimum of 100 msDepth 127 mm

Cable Access 2.54 cm cable entry holes on top and bottom of unit

Power Reset 1 sec.

Wire Gauge max. min.

2.0 mm 0.5 mm

Avg. Operating Current 500 mA @ 24 VDC

Maximum Single Pipe Length 120m

Alarm650 mA – All relays active, all alarm levels displayed. Voltage @ 24 VDC

Maximum Total Branched Pipe Length 320m

Maximum Air Inlet Holes 36 holes

Network Outside Pipe Diameter 25 mm Maximum Current Draw 650 mA Voltage at 18 VDC

Internal Pipe Diameter 15-21 mm ENVIRONMENTAL

Relays8 changeover contacts, 3 AMP, latching or non-latching

Operating Temperature 0°C to 38°C

Sampled Air Temperature -20°C to 60°C

Event Log 18,000 events stored Humidity Range 10 to 95% (non-condensing)

Sensitivity Range (obscuration)0.0015%/m. obs - 20.5%/m obs

IP Rating IP30

Communication NetworkEthernet monitoring, 6 e-mail address alerts

Coverage Area Up to 2000sq. m

The User Interface consists of 5 Alarm levels Alert, Action 1, Action 2, Fire 1, and Fire 2, 10 Particulate levels, 10 Bi-colour Flow and Fault graph

330 mm 127 mm

337

mm

FAAST 8100E TECHNICAL SPECIFICATION

Page 6: ASPIRATING SMOKE DETECTION SYSTEMS - SMS Fire · smoke detection with advanced algorithms to detect a wide range of fire types while maintaining enhanced immunity to nuisance particulates

HoneywellTel: +44 (0) 116 246 2000Fax: +44 (0) 116 246 2300Email: [email protected] Waterside RoadHamilton Industrial ParkLeicesterLE5 1TN

November 2014© 2014 Honeywell International Inc.

For a full range of filters, pipework and accessories please refer to your price list.uide

Product Range

DESCRIPTION ORDER CODES

FAAST high sensitivity laser aspirating unit. Includes built in replaceable filter. 8100E

FAAST specific accessories

FAAST Replacement internal filter F-A3384-000

Page 7: ASPIRATING SMOKE DETECTION SYSTEMS - SMS Fire · smoke detection with advanced algorithms to detect a wide range of fire types while maintaining enhanced immunity to nuisance particulates

FAAST XS (Model 7100XE)FAAST™ Fire Alarm Aspiration Sensing Technology

FAAST XS aspirating smoke detectors deliver highly accurate Very Early

Warning Fire Detection for the smaller applications and offer extensive

communication capabilities.

DescriptionThe FAAST XS aspirating smoke detector combines advanced particle

separation with unique dual source optical smoke detection technology

to provide highly sensitive Very Early Warning Fire Detection while

providing enhanced immunity to false alarms. This technology enables

FAAST XS to accurately detect incipient fire conditions up to Class A

(according to EN54-20), in applications ranging from mission critical to

harsh and extreme environments.

An installed FAAST XS device can administrate up to 170 m pipe length

in standard coverage type applications and can be monitored in several

different ways, including: Serial or TCP Modbus, Ethernet over a LAN or a

direct connection, or via FAAST XS’s onboard USB.

When connected to a LAN, FAAST XS’s email server can provide

email event notification to appropriate personnel. FAAST XS also

communicates alarm and notifications via relays.

PipeIQ® is FAAST XS’s intuitive design,

configuration, and monitoring software. The

all-in-one program can be used to create a

pipe network tailored to meet site specific

requirements, configure a FAAST XS device,

and monitor an installed device - including live

trending and reading of historic reports.

A complimentary download of PipeIQ is available at

www.faast-detection.com.

F E AT U R E S

• Approved for use in Class A, B and C, according to EN54-20

• Provides Very Early Warning Fire Detection, as precise as 0.00095%/m obscuration

• Three alarm levels and three sensitivity modes provide application flexibility

• User configurable 3-speed fan, allowing for maximum coverage area or minimizing on current consumption

• Ultrasonic flow sensing and chamber airflow monitoring for precise system health information

• Dual source optical detection chamber with enhanced algorithms provide high sensitivity with greater immunity to nuisance conditions

• Patented particle separator removes large, non-fire particulate, ensuring chamber health and extending the life of the field-replaceable filter

• TCP and Serial Modbus for easy integration with building management systems

• Easy configuration via USB interface, no external power needed

• Onboard Ethernet interface enables remote monitoring, configuration, web server and e-mail notifications

• Multilingual LCD user interface allows for detailed device information and interaction such as: Active faults, precise airflow monitoring, reset of airflow baseline, test/reset/isolate and more

• Configurable air flow fault thresholds and verification period

• Convenient wiring compartment

• Status-at-a-glance provides immediate alarm, fault and airflow status

Agency Listings (pending). Pending

Aspirating Smoke Detection

Page 8: ASPIRATING SMOKE DETECTION SYSTEMS - SMS Fire · smoke detection with advanced algorithms to detect a wide range of fire types while maintaining enhanced immunity to nuisance particulates

FAAST XS (Model 7100XE) Product Specifications

PHYSICAL SPECIFICATION

HEIGHT 279 mm

WIDTH 229 mm

DEPTH 159 mm

WEIGHT 4 Kg

CABLE ACCESS 2.54 cm cable entry holes on top and back of the unit

WIRE GAUGE Minimum 0.5 mm - 2.0 mm maximum

TOTAL PIPE LENGTH 170 m (all designs must be verified within PipeIQ software)

TOTAL HOLE NUMBERS Class A: 16 holes / Class B: 20 holes / Class C: 20 holes (all designs must be verified within PipeIQ software)

OUTSIDE PIPE DIAMETER 25 mm

INTERNAL PIPE DIAMETER 15-21 mm

RELAYS 5 changeover , programmable latching or non-latchingAlert, Fire (2), Fault, Isolated

OPERATING SPECIFICATION

OPERATING TEMPERATURE 0°C to 38°C; Factory Tested to 55°C

SAMPLED AIR TEMPERATURE -20°C to 60°C

HUMIDITY 10 to 95% (non-condensing)

SENSITIVITY RANGE 0.00095% Obs/m to 20.5% Obs/m

IP RATING IP30

COVERAGE AREA Up to 2,000 m2 (please consider regional standards and guidelines)

AIR MOVEMENT 0-1,219m/min

DIAGNOSTIC SPECIFICATION

EVENT LOG 18,000 events stored

TREND DATA LOG configurable sampling period 1 minute to 1 day

SERVICE LOG 300 customer user entries

NETWORKING SPECIFICATION

COMMUNICATION NETWORK Ethernet monitoring, 6 email address alerts, TCP and Serial Modbus

NETWORK SERVICES DHCP, SMTP, HTTP, MODBUS/TCP, AutoIP, NetBIOS-NS, Serial MODBUS

ETHERNET 10/100 Mbps, MDI-X

MODBUS TCP or Serial RS-485

EMAIL 6 recipients, selectable notifications

WEBSERVER Read Configuration, Live View, Logs

ELECTRICAL SPECIFICATION

EXTERNAL SUPPLY VOLTAGE 18-30 VDC

REMOTE RESET TIME External monitor must be pulled low for a minimum of 100 ms

POWER RESET 1 sec.

OPERATING CURRENT Fan High - 200mA, 4.8W; Fan Med - 151mA, 3.7W;Fan Low - 120mA, 2.1W

ALARM CURRENT Fan High - 230mA, 5.6W; Fan Med - 172mA, 4.2W;Fan Low - 142mA, 3.5W

RELAY CONTACT RATINGS 3.0 A @ 30 VDC, 0.5 A @ 125 VAC

INTERFACE SPECIFICATION

PIPEIQ USB or Ethernet

MODBUS Ethernet or RS-485

ORDERING INFORMATION

PART NO 7100XE

DESCRIPTION FAAST XS HIGH SENSITIVITY LASER

ACCESSORIES † Various accessories are available upon request

† Additional accessory information, including part numbers,can be accessed at systemsensor.com/faast

229 mm

279 mm

159 mm

FAAST XS User Interface Display

The User Interface consists of 3 Alarm levels -

Alert, Fire 1, and Fire 2, 10 Particulate levels, 10

Airflow indicators, 4 Fault indicators, LCD.

All technical data is correct at the time of publication and is subject to changes without notice. All trademarks acknowledged.Installation information: In order to ensure full functionality, refer to the installation instructions as supplied.

DS9400XE-16 | 2 | 03/17© 2017 Honeywell International Inc.

Honeywell 140 Waterside Road

Hamilton Industrial Park

Leicester

LE5 1TN

Tel: +44 (0) 116 246 2000

Fax: +44 (0) 116 246 2300

Email: [email protected]

Page 9: ASPIRATING SMOKE DETECTION SYSTEMS - SMS Fire · smoke detection with advanced algorithms to detect a wide range of fire types while maintaining enhanced immunity to nuisance particulates

Automatic Purging Unit: F-BO-AFE70-2FAAST™ Fire Alarm Aspiration Sensing Technology

OverviewThe FAAST Automatic Purging Unit provides a fully integrated

and compact solution with user-selectable preventative or event

triggered purging programs. An intelligent and installation-

friendly design ensures AFE70-2 is a cost effective and reliable

means of preventing pipe network contaminant blockages.

DescriptionASD systems continuously monitor the air in a

protected environment, potentially subjecting

the system to contamination over time. In order

to prevent the build up of pipe or aspiration hole

contaminates, regular ASD system purging with

compressed air is essential.

In contrast to conventional purging

systems,Honeywell’s compact and user-friendly

AFE70-2 unit features a single built- in Solenoid

valve, which initiates the release of air into the

ASD system. This valve also increases reliability

by protecting the unit from any compressed air

damage and can be accessed through a control

board that is integrated into the housing.

Installation time is greatly reduced, thanks to a

compact and fully integrated design, removing

the need for mechanical and electrical control

devices. Further cost savings can be leveraged

by a reduced need for cabling and pipe work to

commission the system.

With user-definable purging processes and

customisable program features, AFE70-2

delivers continuous and uninterrupted air flow

and is also optimised to assist with benchmark

preventative maintenance regimes, through

automatic purging processes that can be set

up at specific times. These purging processes

are independent of any fault-initiated purging

procedures performed by the system.

Designed with the engineer in mind, the system

offers excellent flexibility; external devices -

such as a push- button or a central timer – can

be connected to an input to allow initiation of

additional manual or automatic activations of

the purging process.

F E AT U R E S

• A fully integrated and compact system, designed for larger pipe networks

• Designed for use in Honeywell Aspiration Smoke Detection ( ASD) systems

• Patented design without air resistance (as defined by EN 54-20)

• 6 user selectable preventive or event-triggered purging programs - Short or long purging cycle options

• Internal clock or external clock timer can be connected

• Several systems can be coupled in Master-Slave mode

• Manual control via external push-button

• Automatic initiation if a fault message is received from the ASD system (activating through FACP only)

• Easy commissioning without software tools

• Multicolored LED indicates the system condition

Page 10: ASPIRATING SMOKE DETECTION SYSTEMS - SMS Fire · smoke detection with advanced algorithms to detect a wide range of fire types while maintaining enhanced immunity to nuisance particulates

Honeywell 140 Waterside Road

Hamilton Industrial Park

Leicester

LE5 1TN

Tel: +44 (0) 116 246 2000

Fax: +44 (0) 116 246 2300

Email: [email protected]

All technical data is correct at the time of publication and is subject to changes without notice. All trademarks acknowledged.Installation information: In order to ensure full functionality, refer to the installation instructions as supplied.

DSF-PSU-2405 | 07/17© 2017 Honeywell International Inc.

F-BO-AFE70-2 Architect/Engineer Specifications

PURGING UNIT

HEIGHT 68 mm

WIDTH 204 mm

DEPTH 160 mm

HOUSING COVER COLOUR Grey white, RAL 9002

WEIGHT 3.2kg (approx.)

PATENT NUMBER AT 514912

ENVIRONMENT

OPERATING TEMPERATURE +5°C to +50°C

IP RATING IP20D

RELATIVE HUMIDITY Max. 95% at 40°C

COMPRESSED AIR CONNECTION

MAX. PERMISSIBLE OVERPRESSURE

0.7MPa (7.0bar)

RECOMMENDED MINIMUM PRESSURE

0.2MPa (2.0bar)

FLOW RATE SOLENOID VALVE 0.2MPa: typ. 1,300 l/min

0.4MPa: typ. 2,300 l/min

0.6MPa: typ. 3,200 l/min

0.7MPa: typ. 3,700 l/min

ORDERING INFORMATION

DESCRIPTION PART NUMBER

Purging Unit / AFE70-2 F-BO-AFE70-2

Non-return valve for pipework RSV-R25

ELECTRICAL SPECIFICATION

SUPPLY VOLTAGE 21.6 – 30 VDC

CURRENT CONSUMPTION @ 24V

8mA (normal condition)

300mA (solenoid valve energised)

System Configuration

RSV-R25 non return valvePipe Network

Page 11: ASPIRATING SMOKE DETECTION SYSTEMS - SMS Fire · smoke detection with advanced algorithms to detect a wide range of fire types while maintaining enhanced immunity to nuisance particulates

Aspirating Smoke Detection in Cold Environments & Freezers

Aspirating Smoke Detection Applications Guide

Security and Fire

FAAST™

Page 12: ASPIRATING SMOKE DETECTION SYSTEMS - SMS Fire · smoke detection with advanced algorithms to detect a wide range of fire types while maintaining enhanced immunity to nuisance particulates

2

Cold storage & freezer application monitoring

Aspirating Smoke Detection (ASD) technology is ideal for installation in cold environments where traditional point or beam detection is unsuitable, due to high levels of moisture and ice particles in the atmosphere. FAAST LTTM combines the most advanced ASD technology and flexible pipe network design to deliver the earliest, most accurate smoke detection with false alarm immunity. Typical cold storage and freezer applications include:

• Pharmaceutical & medical stores

• Food/drink produce stores

• Leasire centres e.g. ice rinks

There are a number of factors that make many traditional fire detection systems unsuitable for cold environments:

• Temperatures from -45°C to +8°C / -49°F to 46°F

• Heavy condensation

• Water vapour clouds

• High airflows diluting smoke

• Poor smoke transport due to low thermal conductivity

• Inaccessibility for installation, maintenance, testing and

replacement

Fire risks in these applications are considerable and include:

• Electrical or mechanical faults in conveyors and transport

equipment

• Electrical equipment and wiring (in the environment or

housed in the roof space)

• Lighting systems

• Hot spots resulting from maintenance operations

• Discarded cigarette butts

• Arson

Typical areas where an ASD fire detection system provides an effective alternative to traditional detection methods include:

• Food processing plants

• Retail food distribution

• Ambient stores (pharmaceutical)

Cold environment challenges and risks

Page 13: ASPIRATING SMOKE DETECTION SYSTEMS - SMS Fire · smoke detection with advanced algorithms to detect a wide range of fire types while maintaining enhanced immunity to nuisance particulates

3

FAAST Fire Alarm Aspiration Sensing Technology®

Sampling pipe network

Achieving optimum performance, accuracy and reliability depends upon correct installation of both the device and the sampling pipe network. It is essential to ensure the unit is protected from any contamination and the following recommendations should be considered in order to leverage the full performance capability of the system.

Pipe installation considerations

PipeIQTM three-in-one design, configuration and monitoring software is provided as standard with FAAST LTTM. During the planning stage, PipeIQTM

will provide an isometric design of the pipework system and may not take into consideration the following factors that may impact final correct design:

• Environment• Feeder pipe run• Offsets• Obstructions

Environmental considerations

Environmental conditions can affect installation, operation and maintenance of the system, so please consider the following factors when designing the sampling pipe network:

• Temperature: from ambientto operational temperature; large fluctuationsoccur when doors are open/closed duringloading/unloading

• Humidity: High levels of humidity fog areprevalent during loading/unloading activities

• External influence: Internal trafficmovement, lorries, forklifts, conveyors,mechanical shovels and accumulative dirtbuild-up

Pipework application

Installation of the sampling pipe network

Most installations will use ABS Red or White sampling pipe work; this is approved and tested for FAAST LTTM. Optimum system design requires as much straight pipe work as possible. However, in reality bends and offsets will be required to create most application designs.

It is recommended to use the preferred fittings (shown in Figure 1 a-f below), designed for use with FAAST LTTM. Please note: 90° elbow bends (Figure 1a), should not be used.

Accessories image descriptions:

a. DO NOT USE a 90° elbow bendb. Standard pipe clipc. Girder clip for fitting standard pipe clip*d. Sweep bende. 45° elbow bendf. Flexible connector

* Please note: fixings and hangers are availablefrom a variety of manufacturers.

Figure 1.

a. b.

c. d.

e. f.

Page 14: ASPIRATING SMOKE DETECTION SYSTEMS - SMS Fire · smoke detection with advanced algorithms to detect a wide range of fire types while maintaining enhanced immunity to nuisance particulates

4

In all cases, the correct pipe clip should be used to accommodate for pipe slippage in the event of expansion and contraction from temperature fluctuations. Most pipes are affected by temperature fluctuations; the amount of expansion is generally 0.1mm / m for every 10°C / 50°F increase above installation temperature.

Using the appropriate clips allows expansion and contraction to occur naturally. However, positioning the pipe up against a wall or obstruction such as a girder (see Figure 2 below), can prevent expansion/contraction.

Expansion clip Flexible connector

Support clips need to be spaced as detailed in the table below.

Pipe Size Bracket spacing in metres

25mm 20°C / 68°F1m

30°C / 86°F0.95m

40°C / 104°F0.85m

50°C / 122°F0.75m

60°C / 140°F0.70m

70°C / 158°F0.60m

In cold environments where high water/humidity are expected, additional ASD pipe network protection is required.

A water trap can be fitted to the pipe network to ensure that water droplets do not enter the ASD unit; moisture simply falls into the trap and can be flushed out of the system during routine maintenance checks (see Figure 3 below).

Preventing water and high humidity detection issues

Figure 2.

Water trap

Gradient of pipe system aprox. 1-1.5%

Please note: No offsets around obstructions in pipework, clear line of site to water trap

Figure 3.

Temperature impact on pipes

Page 15: ASPIRATING SMOKE DETECTION SYSTEMS - SMS Fire · smoke detection with advanced algorithms to detect a wide range of fire types while maintaining enhanced immunity to nuisance particulates

5

FAAST Fire Alarm Aspiration Sensing Technology®

Added system protection can be achieved by offsetting the sampling points. This prevents sample point

blockages from large water droplets and also prevents airflow faults from occurring.

Installing pipework on a slight gradient towards the ASD detection unit also encourages any moisture build-up

in the pipe network to flow towards the water trap. Please note: the offset must be towards the water trap.

FAAST LTTM is ideal for cold stores and freezer room monitoring, because the unit can be mounted outside of the protected area. To ensure correct system operation and performance, please consider the following guidance:

Cold stores and freezer monitoring considerations

Air return

It is important that the air sampled from the protected area is returned to prevent condensation build-up in and around the exhaust of the unit and to alleviate any flow monitoring issues that could arise from pressure differentials between the protected area and the unit position (see Figure 5 below).

Figure 5.

Pipe with hole in the bottom: risk of condensation blocking the aspiration hole and humidity is sucked in.

Pipe with hole at an angle: 30º angle allows condensation to drop down.

Aprox. 30º angle

Figure 4.

For additional protection, the aspiration hole can be situated at a 30º angle (see Figure 4 below); this prevents

water ingress into the pipe network, preventing the need for subsequent flushing during routine maintenance.

Page 16: ASPIRATING SMOKE DETECTION SYSTEMS - SMS Fire · smoke detection with advanced algorithms to detect a wide range of fire types while maintaining enhanced immunity to nuisance particulates

6

Electronics protection

Protection of the ASD unit electronics is essential in the coldest environments. This can be achieved by installing a length of pipe between the FAAST LTTM device and the inlet to the protected area.

The pipe length allows cold air taken from the protected area to warm up, preventing damage to the FAAST LT unit (see Figure 6 below). The following pipe length specification is recommended:

• Down to -20°C / -4°F environment: 5 m pipe length minimum• Below -20°C / -4°F environment: 15 m pipe length minimum

Please note: This guidance is based on a normal ambient temperature (~22°C / 71°F), outside of the protected cold area.

Figure 6.

Pipe lagging and insulation

Where build-up of condensation is an issue, lagging the inlet pipe from the protected area to the ASD unit should always be considered to avoid condensation or frosting of the pipe network. In extreme conditions,

extensive insulation / lagging of the pipe network is recommended (see Figure 5 below).

Figure 7.

Page 17: ASPIRATING SMOKE DETECTION SYSTEMS - SMS Fire · smoke detection with advanced algorithms to detect a wide range of fire types while maintaining enhanced immunity to nuisance particulates

7

FAAST Fire Alarm Aspiration Sensing Technology®

Manual blow through

A manual blow through system is recommended in a cold store, and should be used with a closed end-cap, removing the pressure relief valve

(see Figure 8 to the right). External in-line filter

Safety valve: close before blowing the compressed air into the pipeline

Compressed air inlet: e.g. snap-on fitting

Sampling points

It’s important to ensure sampling points are not sit-uated near entrance doors to the cold store, freezer or the blast chillers.

These locations are the most likely for high condensation and ice crystal formation on the

sampling points (see Figure 9 to the left).

FAAST LT Accessories

Please find below information on the FAAST LT accessories discussed in this guide.

Copyright © 2018 Honeywell All rights reserved. All technical data is correct at time of publication and is

subject to change without notice. All trademarks acknowledged. Installation information: in order to ensure full functionality, refer to the installation instructions as supplied.

Figure 8.

Accessories image descriptions:

a. Plastic clip for airflow reducersb. Water/steam trapc. 3-way ball valved. Manual blow through set

a. b. c. d.

Figure 9.

Page 18: ASPIRATING SMOKE DETECTION SYSTEMS - SMS Fire · smoke detection with advanced algorithms to detect a wide range of fire types while maintaining enhanced immunity to nuisance particulates

Honeywell

Tel: +44 (0)203 409 1779

Email: [email protected]

140 Waterside Road

Hamilton Industrial Park

LeicesterLE5 1TN, UK

Page 19: ASPIRATING SMOKE DETECTION SYSTEMS - SMS Fire · smoke detection with advanced algorithms to detect a wide range of fire types while maintaining enhanced immunity to nuisance particulates

Overview

The Honeywell Refrigerated Storage Sampling Kit provides

a standardised method of smoke sampling for Refrigerated

Storage facilities in a considerably improved manner

allowing simplified installation with reduced maintenance,

thus promoting more reliable and hassle-free operation.

The Honeywell Refrigerated Storage Sampling Kit has

been designed to replace standard cone-shaped sampling

nozzles installed at the ceiling in existing or new Refrigerated

Storage facilities. This kit can be installed in the entire facility

or combined with standard sampling points if required. The

aim here is to reduce direct ice blockage of the sampling

points hence this kit is recommended for installation in

areas where higher humidity is likely to occur as a result of

vehicle and pedestrian traffic (e.g. areas close to doorways or

perimeter of the facility).

This kit is treated as a standard sampling hole in the

Honeywell ASD system design, in terms of system

parameters (e.g. sampling hole location, hole size, transport

time, sampling hole sensitivity)

Description

The sampling kit consists of outer and inner parts with

the sampling pipe penetrating the Refrigerated Storage

sandwich panel. The sampling pipe through the sandwich

panel and inner parts are made of ABS plastic which is

suitable for low temperatures down to -40 °C (-40 °F). The kit

comprises a restriction assembly, placed above the sandwich

Refrigerated Storage SamplingVSP-860

F E AT U R E S

panel, which consists of a sampling orifice within a socket

union.

Detectors Supported

• All Honeywell detectors installed with large bore pipe

networks.

• Enables the ASD pipe to be installed, inspected and maintained

outside the Refrigerated Storage facility hence enabling fire

contractors to work in ambient conditions most of the time

• Suited for facilities with and without ceiling cavities

• Eliminates the need for expensive HDPE (high density polyethylen

pipe inside the Refrigerated Storage facility

• Eliminates the need for costly access equipment hire for on-going

service/maintenance

• Eliminates the need for heat tracing

• Less prone to blockage due to icing

• Provides a generally more robust ASD installation for these unique

environments

• Provides considerably improved aesthetics

• Minimises the need for “Back Flush” systems

• Offers all round cost savings

Aspirating Smoke Detection

Page 20: ASPIRATING SMOKE DETECTION SYSTEMS - SMS Fire · smoke detection with advanced algorithms to detect a wide range of fire types while maintaining enhanced immunity to nuisance particulates

Honeywell140 Waterside Road

Hamilton Industrial Park

Leicester

LE5 1TN

Tel: +44 (0) 203 409 1779

Email: [email protected] | 10/18© 2018 Honeywell International Inc.

a

b

c

Cold Store Insulation Material

i

g

d

f

g

e

h

ITEM NO DESCRIPTION

a Inlet Funnel

b Inner Flange

c Outer Flange

d Screw self-tapping

e Tube-lower

fSocket Union-including Flow Restrictor and Seal

g Tube-Upper

h Flexible Pipe

i US Pipe Adaptor

All technical data is correct at the time of publication and is subject to changes without notice. All trademarks acknowledged. Installation information: In order to ensure full functionality, refer to the installation instructions as supplied.

VSP-860 Dimensions

280 mm

Flexible pipe length approximately 72 cm

100 mm

40 mm

34 mm

100 mm

* Please ensure a suitable T-junction is used.

ORDER CODES

DESCRIPTION PART NUMBER

Refrigerated Storage Sampling Kit* VSP-860

Page 21: ASPIRATING SMOKE DETECTION SYSTEMS - SMS Fire · smoke detection with advanced algorithms to detect a wide range of fire types while maintaining enhanced immunity to nuisance particulates

A S P I R AT I N G S M O K E D E T E C T I O N S Y S T E M S

EN54-4 APPROVED POWER

SUPPLY UNITS

Power supply Units fully certified to EN54-4 provide a stable and fully regulated, true 24V output

for fire alarm system applications under all power conditions. The unique regulation techniques

ensure that even when running on standby batteries, a stable 24V supply is available to all parts

of the system ensuring that all 24V powered devices connected are supplied with optimum

power. The powerful onboard micro-controller ensures that all battery types are conditioned with

optimum, temperature compensated charging algorithms to maximise battery life and maintain

batteries in top condition. The EN54-4 compliant power supplies can be fitted with an optional

dual fused output monitoring module to ensure compliance with European standards when

supplying fire control panels with an external power supply.

DIMENSIONS (mm)

355 117

500

ORDER CODES

EN54 2.5A Power Supply

able to charge up to 12Ah

batteries (500 x 355 x 117mm) ASD-PSU25

EN54 5.25 Amp Power

Supply able to charge up

to 12Ah batteries (with Dual

Output Board) 4I0AC 05214-24-EN

l 2.5A and 5.25A versions

l Enclosure mounted with battery space

l 110V or 230V input, Regulated true 24V output

l Intelligent battery charging and temperature compensation

l Houses up to 12Ah batteries

l Status indicators for monitored faults

l Fully enclosed and robust construction

Page 22: ASPIRATING SMOKE DETECTION SYSTEMS - SMS Fire · smoke detection with advanced algorithms to detect a wide range of fire types while maintaining enhanced immunity to nuisance particulates

A S P I R AT I N G S M O K E D E T E C T I O N S Y S T E M S

EN54-4 APPROVED POWER

SUPPLY UNITS

TECHNICAL SPECIFICATION

Construction 1.2mm mild sheet steel

Finish Epoxy powder coated

Colour – lid & box BS 00 A 05 grey – fine texture

Mains input supply voltage 230V AC 50/60Hz or 11 0V AC 50/60Hz (link selectable)

Mains supply fuse 250V, 3A, SB, 5mm x 20mm

Load output voltage 19-30V DC +/- 1%

Maximum load current – 05214-24-EN models

5.25 Amps continuous with maximum battery charge output of 1.25A

Maximum load current – ASD-PSU25

2.5 Amps continuous with maximum battery charge output of 1.0A

Maximum ripple 200 milliamps

Load fuse 5 Amp, self resetting Polyfuse

Maximum current draw from batteries

5 Amps

Battery charge output voltage 27.4V DC nominal at 20ºC

Battery charge current 2 stage, constant voltage 1.25 Amps maximum

Deep discharge prevention Battery disconnects at 1 9V

Compatible batteriesYuasa – NP7-1 2, NP1 2-12, NP1 7-12, NP24-1 2 Powersonic – PS-1270, PS-12120, PS-12170, PS12260

Operating temperature -5ºC to +45ºC

Common fault output Normally energised volt free changeover relay – 30V DC 1 Amp

Battery disconnected output Open collector 50 milliamps

Battery low output Open collector 50 milliamps

Charger fault output Open collector 50 milliamps

Earth fault output Open collector 50 milliamps

Mains failed output Open collector 50 milliamps

Fault output connector 14 way DIL header 0.1" spacing

Mains connector 3 way terminal, 7.62mm spacing, 2.5mm maximum cable size

Load connector 2 way terminal, 7.62mm spacing, 2.5mm maximum cable size

Battery connector 2 way terminal, 7.62mm spacing, 2.5mm maximum cable size

Front panel Power On indicator Green LED

Front panel Fault indicator Yellow LED

Power outputDual 24V supply terminals with EN54-4 clause 6.4 interface (When fitted with optional dual fused output monitoring module)