ashrae presentation
TRANSCRIPT
ASHRAE 90.1 - 2010
Presented by
Ryan Kopko, PE BEMP, BEAP, LEED AP
March, 7th 2012
Presentation Overview
• ASHRAE 90.1 Overview and History
• Heating, Cooling, and Ventilation
Section Updates/Changes
• Lighting Section Updates/Changes
• Building Envelope Section
Updates/Changes
• ASHRAE, LEED, and Beyond!
ASHRAE 90.1 - Overview & History
• It supersedes ANSI/ASHRAE/IESNA Standard 90.1-2007 by adding 60 Addenda
• It will become the reference standard for the 2012 IECC
• It is the professional “standard of care” for energy efficiency set by ASHRAE Consensus
• Format: Structured like a code document, with a consistent numbering scheme
• Climate Zones: – Defined geographically by county lines,
not by individual city or climatic Degree Days
– Metropolitan areas kept together.
ASHRAE 90.1 - Overview & History
• Purpose of the Standard
– The purpose of this standard is to provide
minimum requirements for the energy-
efficient design of buildings except low-rise
residential buildings for:
1) design, construction, and plan for O&M**, and
2) Utilization of on-site, renewable energy sources
** Note: This portion is new in 2010
ASHRAE 90.1 - Overview & History
90.1 - 1975
• Standard First
issued
90.1 - 1980
• First Update to
Standard
90.1 – 1989
• Second Update
90.1 – 1999
• Major Rewrite of
the Standard
90.1 – 2001
• Minor Revisions
90.1 – 2004
• Improved on 2001
by ~10%
90.1 – 2007
• Improved on 2004
by ~25%
90.1 – 2010
• Improved on 2007
by ~5%
ASHRAE 90.1 - Overview & History
State Adoption as of
November 1, 2011
ASHRAE 90.1 - Overview & History
ASHRAE 90.1 – 2010 Structure
Sections in the Document 1. Purpose
2. Scope
3. Definitions, Abbrev. & Acronyms
4. Administration and Enforcement
5. Building Envelope
6. HVAC
7. SWH
8. Power
9. Lighting
10. Other Equipment
11. Energy Cost Budget (ECB)
12. Normative References Appendices A-G
Technical Sections Outline x.1 General – Scope & Conditions
x.2 Compliance Paths
x.3 Simplified Building (Note 1)
x.4 Mandatory Provisions
x.5 Prescriptive Compliance Path
x.6 Alternative Compliance Path (Note 2)
x.7 Submittals – Drawings, manuals, labeling, etc
x.8 Product Information – Equipment efficiency, installation requirements, etc.
Notes:
1. Only used in HVAC
2. Only in Section 5 and 9
ASHRAE 90.1 – 2010 HVAC
• Airside Energy Recovery
• Chiller Minimum Efficiency Changes
• Economizer Exemptions
• Single Zone VAV
• Load Calculations
• Appendix G
• Damper/Duct Leakage Requirements
• Part Load Fan Power
• Garage Ventilation Requirements
ASHRAE 90.1 – 2010 HVAC
Airside Energy Recovery
Table 6.5.6.1 Exhaust Air Energy Recovery Requirements
Climate
Zone
% Outdoor Air at Full Design Airflow Rate
30~40% 40~50% 50~60% 60~70% 70~80% > 80%
Design Supply Fan Airflow Rate (cfm)
3b,3c,4b,4c,5b NR NR NR NR ≥ 5,000 ≥ 5,000
1b,2b,5c NR NR ≥ 26,000 ≥ 12,000 ≥ 5,000 ≥ 4,000
6b ≥ 11,000 ≥ 5,500 ≥ 4,500 ≥ 3,500 ≥ 2,500 ≥ 1,500
1a,2a,3a,4a,5a,
6a ≥ 5,500 ≥ 4,500 ≥ 3,500 ≥ 2,000 ≥ 1,000 > 0
7,8 ≥ 2,500 ≥ 1,000 > 0 > 0 > 0 > 0
• Incorporate exhaust air
energy recovery system
with at least 50%
enthalpy energy recovery.
• 2004 was ≥5000 cfm and ≥70% OA
ASHRAE 90.1 – 2010 HVAC
Chiller Efficiencies
Equipmen
t Type
Size
Category
(Tons) Units
Before 1/1/2010
As of 1/1/2010
Path A Path B
Full Load IPLV Full Load IPLV Full Load IPLV
Air
Cooled < 150 EER ≥9.562 ≥10.416 ≥9.562 ≥12.5 NA NA
≥150 EER ≥9.562 ≥10.416 ≥9.562 ≥12.75 NA NA
Water
Cooled
Electricall
y
Operated
Positive
Disp.
<75 kW/Ton ≤0.790 ≤0.676
≤0.780 ≤0.630 ≤0.800 ≤0.600
≥75 to <150 kW/Ton ≤0.775 ≤0.615 ≤0.790 ≤0.586
≥150 to <300
kW/Ton ≤0.717 ≤0.627 ≤0.680 ≤0.580 ≤0.718 ≤0.540
≥300 kW/Ton ≤0.639 ≤0.571 ≤0.620 ≤0.540 ≤0.639 ≤0.490
Table 6.8.1C Water Chilling Packages – Efficiency Rqmts
• On 1/1/2010, the HCFC (R-22) refrigerants were eliminated and HFC’s (R-
134a, R-410a) must be used. This table shows the EER and kW/ton
requirements for chillers before and after January 2010.
• The Standard also provides guidance for chiller efficiencies at Nonstandard
Conditions (Section 6.4.1.2)
ASHRAE 90.1 – 2010 HVAC
Economizer Exemptions Climate Zone Efficiency Improvement 1
2a 17%
2b 21%
3a 27%
3b 32%
3c 65%
4a 42%
4b 49%
4c 64%
5a 49%
5b 59%
5c 74%
6a 56%
6b 65%
7 72%
8 77%
• Economizer required on all
equipment 4.5 tons and above.
2004 was 11.25 Tons
• Table 6.3.2 (on the left) lists
efficiency improvement requirement
needed to not use economizer.
• Computer Rooms have a number of
exemptions and still undergoing
discussion.
• The table used to be based strictly
on specific EER or SEER
improvements not a percentage. 1) If a unit is rated with an IPLV, IEER, or SEER then to
eliminate the required air or water economizer, the minimum
cooling efficiency of the HVAC unit must be increased by the
percentage shown. If the HVAC unit is only rated with a full
load metric like EER then these must be increased by the
percentage shown.
ASHRAE 90.1 – 2010 HVAC
Single Zone VAV Control
HVAC Systems shall have variable
airflow controls
• Chilled water
– Motor power 5 Hp and greater
– Reduce airflow by 50% or to
minimum OA per 62.1
• Direct Expansion
– 110,000 btuh (9.2 Tons) and
greater
– Reduce airflow by 33% or to
minimum OA per 62.1
• Either can be accomplished with
2 speed motors or VFD Control
Section 6.4.3.10
ASHRAE 90.1 – 2010 HVAC
Load Calculations
• 90.1 - 2004 – Heating and cooling system design loads for the purpose of
sizing systems and equipment shall be determined in
accordance with generally accepted engineering standards and
handbooks acceptable to the adopting authority.
• 90.1 – 2010 – Heating and cooling system design loads for the purpose of
sizing systems and equipment shall be determined in
accordance with ANSI/ASHRAE/ACCA Standard 183, Peak
Cooling and Heating Load Calculations in Buildings Except
Low-Rise Residential Buildings.
ASHRAE 90.1 – 2010 HVAC
Appendix G
• Normative Appendix G in 2010
• Provides specific rules for determining
Degree of Improvement over 90.1
• Responding to demand by LEED
designers
• Distinct from Energy Cost Budget
Compliance Method in Section 11
ASHRAE 90.1 – 2010 HVAC
Damper/Duct Leakage
• Damper Leakage (Section 6.4.3.4.3) – OA Supply and Exhaust/relief Dampers
– Shall have maximum leakage rate per Table 6.4.3.4.3
• Permitted Duct Leakage (Section 6.4.4.2.2) – Maximum permitted duct leakage shall be:
𝐿𝑚𝑎𝑥 = 𝐶𝐿𝑃0.65
𝐿𝑚𝑎𝑥 = 𝑚𝑎𝑥𝑖𝑚𝑢𝑚 𝑝𝑒𝑟𝑚𝑖𝑡𝑒𝑑 𝑙𝑒𝑎𝑘𝑎𝑔𝑒 𝑖𝑛 𝑐𝑓𝑚 𝑝𝑒𝑟 100 𝑠𝑞𝑓𝑡 𝑑𝑢𝑐𝑡 𝑠𝑢𝑟𝑓𝑎𝑐𝑒 𝑎𝑟𝑒𝑎
𝐶𝐿 = 𝑙𝑒𝑎𝑘𝑎𝑔𝑒 𝑐𝑙𝑎𝑠𝑠, 𝑐𝑓𝑚 𝑝𝑒𝑟 100 𝑠𝑞𝑓𝑡 @ 1" 𝑤. 𝑐. 𝑃 = 𝑇𝑒𝑠𝑡 𝐷𝑒𝑠𝑖𝑔𝑛 𝑝𝑟𝑒𝑠𝑠𝑢𝑟𝑒, 𝑖𝑛 𝑤. 𝑐.
ASHRAE 90.1 – 2010 HVAC
Part Load Fan Power Limitation
• Individual VAV fans with motors ≥10 hp
– Shall have VSD, or
– Shall be vane-axial w/variable pitch blades, or
– Shall have other controls and devices to result in fan motor demand ≤30% of design wattage at 50% of design air volume when static
pressure set point = 1/3 of total design static pressure.
Was 30 hp in 90.1-2001 and 15 hp in 90.1 2004
ASHRAE 90.1 – 2010 HVAC
Ventilation Control
• High Occupancy Areas – DCV required for spaces >500 sqft and > 40 people/1000
sqft that are served by any of these: • Air-side economizer
• Auto modulation of OA damper
• Design OA airflow > 3000 CFM
(Must maintain minimum rates per ASHRAE Standard 62.1)
– Exceptions • Exhaust energy recovery system per section 6.5.6.1
• Multiple-zone systems w/o DDC of individual zones
• Design OA < 1200 cfm
• Where supply air – make up air < 1200 cfm
* CO2 Sensor Control Considered the BEST Method
ASHRAE 90.1 – 2010 HVAC
Ventilation Control
• Enclosed Parking Garage Ventilation
– Parking garage ventilation systems shall automatically detect
contaminant levels and stage/modulate fans of 50% (or
less) of design capacity provided acceptable contaminant
levels are maintained.
ASHRAE 90.1 – 2010 HVAC
Other Items
• AC and Condensing Unit Efficiency Requirements
increased
• VRF Efficiency requirements
• Closed Circuit Cooling Tower Performance
Requirements
• Pipe Insulation Requirements Changed
• Commissioning of HVAC Systems
ASHRAE 90.1 – 2010 Lighting
• Lighting provided the largest energy
savings in the new version of ASHRAE
90.1-2010 with reduced Lighting
Power Density allowances and emphasis
on daylighting!
ASHRAE 90.1 – 2010 Lighting Luminaire Wattage Determination
• Luminaires w/o ballasts = maximum
labeled wattage of the luminaire
• Luminaires with ballasts = wattage of
the lamp/ballast combination
• Line-voltage track = minimum 30 W
per foot or wattage of circuit breaker
or other current-limiting device(s)
• Low-voltage track = transformer
wattage
• All other misc lighting equipment, as
specified.
ASHRAE 90.1 – 2010 Lighting
Lighting Power Density (LPD)
• Addendum “by” changes:
– For most building types, the
LPDs are reduced.
• Average LPDs: – 90.1–2007 ……Ave = 1.09 w/sqft
– 90.1-2010……Ave = 0.906 w/sqft
Difference of -16.9%
• Lighting Controls Update
– Occupancy, Daylighting with
photosensor, Scheduling
Building Area Type
LPD
(W/sqft)
Automotive Facility 0.9 0.82
Convention Center 1.2 1.08
Courthouse 1.2 1.05
Dining: Bar/Leisure 1.3 0.99
Dining: Cafeteria/fast
food
1.4 0.9
Dining: Family 1.6 0.89
Dormitory 1.0 0.61
Exercise Center 1.0 0.88
Gymnasium 1.1 1.0
Health-care Clinic 1.0 0.87
Office 1.0 0.9
ASHRAE 90.1 – 2010 Lighting
Lighting Control
• Daylighting Controls for Sidelighting
– When daylight sidelighted area exceeds 250 sqft, the lighting should be separately controlled by at least on multi-level photocontrol with these features: • Light Sensor for the photocontrol shall be remote from where the
calibration adjustments are made,
• The calibration adjustments shall be readily accessible, and
• Multilevel photocontrol shall reduce the electric lighting in response to available daylight with at least one control step between 50% and 70% of design lighting power and another control step that is ≤ 35% (including off) of design power.
– Exceptions • Tops of adjacent structures are twice as high above the windows as
their distance from the window.
• Sidelighting effective aperture (EA) < 10%
• Retail spaces
ASHRAE 90.1 – 2010 Lighting
Lighting Control • Daylighting Controls for Toplighting (Skylight or
Monitors)
– When daylight toplighted area exceeds 900 sqft, the
lamps for general lighting shall be separately
controlled by at least one multilevel photocontrol
with these features: • SEE PREVIOUS SLIDES REQUIREMENTS!
– Exceptions
• Adjacent structures block direct beam sunlight for more than
1500 hours per year between 8 am and 4 pm
• Skylight effective aperture (EA) < 0.6%
• Buildings with daylighted spaces <1500 sqft in CZ 8
ASHRAE 90.1 – 2010 Lighting
Lighting Control
“Daylight from Sidelights”
ASHRAE 90.1 – 2010 Lighting
Lighting Control
“Daylight Area Under Skylights”
ASHRAE 90.1 – 2010 Lighting
Lighting Control
“Daylight Area Under Monitors”
ASHRAE 90.1 – 2010 Envelope
The new standard includes a number of
updates that address the Envelope of
the building including these major
changes:
- Continuous Air Barrier Required
- Skylights are required
- U Factors are lowered
- Changes to Fenestration Requirements
ASHRAE 90.1 – 2010 Envelope
Continuous Air Barrier
• Entire building envelope to be designed and constructed with a continuous Air Barrier. – It should extend over all surfaces of the building.
• All air barrier components shall be clearly identified and detailed on the design drawings.
• If the air barrier is not detailed then building leakage has to be determined through testing.
ASHRAE 90.1 – 2010 Envelope
Skylights are Required
• Required in any enclosed
space that is four stories
or less that is:
– ≥5000 sqft and,
– Directly under a roof with ceiling height ≥15ft, and
– Is a office, lobby, atrium, concourse, corridor, etc.
• A number of exemptions exist
ASHRAE 90.1 – 2010 Envelope
U Factors
• Fenestration U Factor requirements in
90.1 – 2007 are 38% lower than those
in 2004
• Roof with attics and above deck insulation
have U-factor requirements that are 20
to 24% lower.
ASHRAE 90.1 – 2010 Envelope
Fenestration Orientation
The vertical fenestration area shall meet the
following requirement:
AS ≥ AW and AS ≥ AE
Where:
AS = south oriented vertical fenestration area
AN = north oriented vertical fenestration area
AW = west oriented vertical fenestration area
AE = east oriented vertical fenestration area
(this is for northern hemisphere)
ASHRAE Resources
Advanced Energy Design Guides
• Provide a guide to
energy savings.
• Adding new facility
types as they are
completed.
• Free for download at
ashrae.org. http://www.ashrae.org/standards-
research--technology/advanced-energy-
design-guides
30%
Design
Guide
over
1999
50%
Design
Guide
over
2004
ASHRAE, LEED, and Beyond!
Standard 189.1 – Design of High-
Performance Green Buildings • Compliments 90.1-2010
• Provides guidance on
• Photovoltaic Usage
• Site Selection
• Water Reduction
• Etc, etc
LEED 2009/2013 • Utilizes 90.1-2007 (Soon to be 2010) as
baseline
• Increase efficiency above the Standard
• Sustainable Design Guide
ASHRAE, LEED, and Beyond!
Questions?