as3740-2004-waterproofing in wet areas

48
AS 3740—2004 Australian Standard Waterproofing of wet areas within residential buildings AS 3740

Upload: cc01111

Post on 24-Apr-2015

1.326 views

Category:

Documents


45 download

TRANSCRIPT

Page 1: AS3740-2004-Waterproofing in Wet Areas

AS 3740—2004

Australian Standard™

Waterproofing of wet areas within residential buildings

AS

3740

Page 2: AS3740-2004-Waterproofing in Wet Areas

This Australian Standard was prepared by Committee BD-038, Wet Areas in Buildings. It was approved on behalf of the Council of Standards Australia on 20 February 2004 and published on 15 April 2004.

The following are represented on Committee BD-038:

Architectural Aluminium Fabricators Association (NSW)

Australian Building Codes Board

Australian Chamber of Commerce and Industry

Australian Consumers Association

Australian Institute of Building Surveyors

Building Industry Authority NZ

Business New Zealand

CSIRO Manufacturing and Infrastructure Technology

Housing Industry Association

Importers, Distributors and Sealants Manufacturers Association of Australia

Institute of Materials Engineering Australasia

Master Builders Australia

Planning South Australia

South Australian Housing Trust

TAFE NSW

Keeping Standards up-to-date

Standards are living documents which reflect progress in science, technology and systems. To maintain their currency, all Standards are periodically reviewed, and new editions are published. Between editions, amendments may be issued. Standards may also be withdrawn. It is important that readers assure themselves they are using a current Standard, which should include any amendments which may have been published since the Standard was purchased.

Detailed information about Standards can be found by visiting the Standards Web Shop at www.standards.com.au and looking up the relevant Standard in the on-line catalogue.

Alternatively, the printed Catalogue provides information current at 1 January each year, and the monthly magazine, The Global Standard, has a full listing of revisions and amendments published each month.

Australian StandardsTM and other products and services developed by Standards Australia are published and distributed under contract by SAI Global, which operates the Standards Web Shop.

We also welcome suggestions for improvement in our Standards, and especially encourage readers to notify us immediately of any apparent inaccuracies or ambiguities. Contact us via email at [email protected], or write to the Chief Executive, Standards Australia International Ltd, GPO Box 5420, Sydney, NSW 2001.

This Standard was issued in draft form for comment as DR 02124.

Page 3: AS3740-2004-Waterproofing in Wet Areas

AS 3740—2004

Australian Standard™

Waterproofing of wet areas within residential buildings

Originated as AS 3740—1989. Previous edition 1994. Third edition 2004.

COPYRIGHT

© Standards Australia International

All rights are reserved. No part of this work may be reproduced or copied in any form or by any means, electronic or mechanical, including photocopying, without the written permission of the publisher.

Published by Standards Australia International Ltd GPO Box 5420, Sydney, NSW 2001, Australia

ISBN 0 7337 5870 3

Page 4: AS3740-2004-Waterproofing in Wet Areas

AS 3740—2004 2

PREFACE

This Standard was prepared by the Standards Australia Committee BD-038, Wet Areas in

Buildings, to supersede AS 3740—1994.

The objective of this Standard is to set out the criteria for wet areas within residential

buildings. It gives minimum requirements for materials, designs and installations. It is

noted however, that other forms of construction may be equally satisfactory, providing they

demonstrate equivalence with the criteria set out in the Standard.

This Standard will be referenced in the Building Code of Australia in BCA 2004 to be

published in May 2004.

Additional requirements may need to be considered for wet areas intended for use by people

with disabilities.

The term ‘informative’ has been used in this Standard to define the application of the

appendix to which it applies. An ‘informative’ appendix is only for information and

guidance.

Statements expressed in mandatory terms in notes to tables and figures are deemed to be

requirements of this Standard.

Page 5: AS3740-2004-Waterproofing in Wet Areas

3 AS 3740—2004

CONTENTS

Page

FOREWORD.............................................................................................................................. 5

SECTION 1 SCOPE AND APPLICATION

1.1 SCOPE ........................................................................................................................ 6

1.2 APPLICATION ........................................................................................................... 6

1.3 NEW MATERIALS AND METHODS ....................................................................... 6

1.4 REFERENCED DOCUMENTS .................................................................................. 6

1.5 DEFINITIONS ............................................................................................................ 7

SECTION 2 MATERIALS, DESIGN AND INSTALLATION CRITERIA

2.1 SCOPE OF SECTION ............................................................................................... 10

2.2 MATERIALS ............................................................................................................ 10

2.3 DESIGN AND INSTALLATION.............................................................................. 10

2.4 MOVEMENT JOINTS .............................................................................................. 10

SECTION 3 MATERIALS

3.1 SCOPE OF SECTION ............................................................................................... 12

3.2 MATERIALS ............................................................................................................ 12

3.3 PREFORMED SHOWER BASES AND ENCLOSURES.......................................... 13

3.4 SEALANTS............................................................................................................... 13

3.5 ADHESIVES............................................................................................................. 13

3.6 SHEET FASTENINGS.............................................................................................. 13

3.7 OTHER MATERIALS .............................................................................................. 13

SECTION 4 DESIGN

4.1 SCOPE OF SECTION .............................................................................................. 14

4.2 DESIGN .................................................................................................................... 14

4.3 FALLS IN FLOOR FINISHES.................................................................................. 14

SECTION 5 INSTALLATION

5.1 SCOPE OF SECTION ............................................................................................... 22

5.2 GENERAL ................................................................................................................ 22

5.3 ALTERNATE INSTALLATION TECHNIQUES ..................................................... 22

5.4 CURING OF MATERIALS....................................................................................... 22

5.5 PREFORMED SHOWER BASES............................................................................. 22

5.6 BATHS AND SPAS .................................................................................................. 23

5.7 FLASHINGS ............................................................................................................. 25

5.8 PENETRATIONS...................................................................................................... 27

5.9 WET AREA FLOORS............................................................................................... 27

5.10 WALL SHEETING OR RENDER............................................................................. 27

5.11 GENERAL SHOWER AREA REQUIREMENTS..................................................... 27

5.12 MEMBRANE TO DRAINAGE CONNECTION....................................................... 32

5.13 INSTALLATION OF AN INTERNAL MEMBRANE .............................................. 33

5.14 INSTALLATION OF AN EXTERNAL MEMBRANE ............................................. 36

5.15 DOORJAMBS AND ARCHITRAVES...................................................................... 37

5.16 SHOWER SCREENS ................................................................................................ 37

Page 6: AS3740-2004-Waterproofing in Wet Areas

AS 3740—2004 4

Page

APPENDICES

A GUIDE FOR COMPLIANCE WITH THIS STANDARD......................................... 38

B DESIGN CONSIDERATIONS IN WET-AREA WATERPROOFING ..................... 39

C FALLS IN FLOOR FINISHES.................................................................................. 42

Page 7: AS3740-2004-Waterproofing in Wet Areas

5 AS 3740—2004

FOREWORD

Since the last edition of this Standard was published in 1994, it has become increasingly

apparent that various methods for design and installation of waterproofing systems outlined

in the document no longer represent minimum acceptable standards and a further review

was required. In this document the Committee has attempted to address these shortcomings.

The topics that have been addressed include the following:

(a) Risk levels of different areas.

(b) Appropriate details for various risk levels.

(c) Clarification of usage definitions.

(d) Increased ease of reference for varying conditions.

(e) Revised design and installation techniques.

This revision is intended to cover the treatment of wet areas within residential buildings in

a form that makes the application of accepted methods more relevant to the various risk

levels, while presenting typical detail diagrams relevant to those applications.

Problems with waterproofing defects relate to a number of fundamentals, including the

following:

(i) Workmanship.

(ii) Understanding of material technology/properties.

(iii) Applicator skills and competence.

(iv) Application to a variety of use situations.

(v) Changes in design trends.

(vi) Quality control including supervision, inspection and testing.

(vii) Maintenance of waterproofing medium when disturbed.

(viii) Fixture of fittings after waterproofing and tiling.

(ix) Professional attitude and a desire to continuously improve without compromising

quality, performance and contractual obligations (where they exceed minimum

requirements).

Page 8: AS3740-2004-Waterproofing in Wet Areas

AS 3740—2004 6

Standards Australia www.standards.com.au

STANDARDS AUSTRALIA

Australian Standard

Waterproofing of wet areas within residential buildings

S E C T I O N 1 S C O P E A N D A P P L I C A T I O N

1.1 SCOPE

This Standard sets out requirements for materials and minimum design and installation

criteria for the waterproofing of wet areas within residential buildings. It includes typical

details of construction materials and methods. It does not cover situations where flooding of

the wet areas occurs through overflowing of vessels and showers or plumbing failures.

NOTES:

1 Appendix A provides guidance on means for compliance with this Standard.

2 Appendix B provides design considerations for wet area waterproofing.

1.2 APPLICATION

This Standard applies to all residential buildings and is intended for use by building

regulators, designers, builders, waterproofing contractors and associated trades.

NOTE: This Standard may also apply to other buildings where the use of wet areas is similar to

that in residential buildings.

1.3 NEW MATERIALS AND METHODS

This Standard shall not be interpreted as preventing the use of materials, systems or

methods that meet the design and installation criteria set out in the Standard, but are not

specifically referred to herein.

1.4 REFERENCED DOCUMENTS

The following documents are referred to in this Standard:

AS

1566 Copper and copper alloys—Rolled flat products

1684 Residential timber-framed construction

1684.2 Part 2: Non-cyclonic areas

1684.3 Part 3: Cyclonic areas

1684.4 Part 4: Simplified—Non-cyclonic areas

1860 Installation of particleboard flooring

2334 Steel nails—Metric series

2870 Residential slabs and footings—Construction

2924 High pressure decorative laminates—Sheets made from thermosetting resins

2924.1 Part 1: Classification and specifications

3566 Self-drilling screws for the building and construction industries

3566.1 Part 1: General requirements and mechanical properties

3566.2 Part 2: Corrosion resistance

3600 Concrete structures

3700 Masonry in buildings

Page 9: AS3740-2004-Waterproofing in Wet Areas

7 AS 3740—2004

www.standards.com.au Standards Australia

AS

3958 Ceramic tiles

3958.1 Part 1: Guide to the installation of ceramic tiles

CA 27 Code of recommended practice for internal plastering on solid backgrounds

AS/NZS

1170 Structural design actions

1170.1 Part 1: Permanent, imposed and other actions

1170.2 Part 2: Wind actions

1860 Particleboard flooring

1860.1 Part 1: Specifications

2269 Plywood—Structural

2588 Gypsum plasterboard

2908 Cellulose-cement products

2908.2 Part 2: Flat sheets

4858 Wet area membranes

ASTM

C630 Standard Specification for water-resistant gypsum backing board

1.5 DEFINITIONS

For the purpose of this Standard, the definitions below apply.

1.5.1 Bond breaker

A system that prevents the membrane bonding to the substrate, bedding or lining.

1.5.2 Drainage flange

A flange connected to a waste pipe, at the point at which it passes through the floor

substrate, to prevent leakage and which enables tile bed drainage into the waste pipe.

1.5.3 Drainage riser

A waste pipe between the floor waste and the drainage system.

1.5.4 Enclosed shower

A shower designed and installed to control the spread of water from the shower enclosure.

1.5.5 Flashing

A strip or sleeve of impervious material dressed, fitted or built-in, or a liquid-applied

product, to provide a barrier to moisture movement, or to divert the travel of moisture, or to

cover a joint where water would otherwise penetrate.

1.5.6 Flashing, perimeter

A flashing used at the floor-wall junction.

1.5.7 Flashing, vertical

A flashing used at wall junctions within shower areas.

1.5.8 Floor waste

A grated inlet within a graded floor intended to drain the floor surface.

1.5.9 Hob

The upstand at the perimeter to a shower area.

Page 10: AS3740-2004-Waterproofing in Wet Areas

AS 3740—2004 8

Standards Australia www.standards.com.au

1.5.10 Insert bath

A bath, where the bath lip is installed onto a horizontal plinth or surface.

1.5.11 Maximum retained water level

The point where surface water will start to overflow out of the shower area.

1.5.12 Membrane

A barrier impervious to moisture.

NOTE: A barrier may be a single or multi-part system.

1.5.13 Membrane, external

A membrane that is installed behind the wall sheeting or render. Usually external

membranes are preformed trays or sheet material systems.

1.5.14 Membrane, internal

A membrane that is installed to the face of the wall sheeting or render. Usually internal

membranes are liquid systems applied in situ.

1.5.15 Prefinished wall panels

Predecorated sheets or thermosetting laminated sheets that are designed for use as the final

wall finish of the wet area.

1.5.16 Residential building

A class 1, 2, 3 or 4 building, as referenced in the Building Code of Australia.

1.5.17 Shower base

A preformed, prefinished vessel installed as the finished floor of a shower compartment,

and which is provided with a connection point to a sanitary drainage system. Shower bases

are commonly made of plastics, composite materials, vitreous enamelled pressed steel, or

stainless steel.

1.5.18 Shower screen

The panels, doors or windows enclosing or partially enclosing a shower area.

1.5.19 Shower tray

An internal or external liquid or sheet membrane system used to waterproof the floor and

the wall/floor junctions of a shower area.

1.5.20 Shower area

The area affected by water from a shower, including a shower over a bath.

1.5.21 Shower area, enclosed

The area enclosed by walls or screens including hinged or sliding doors that control the

spread of water to within the enclosure.

NOTE: For the purposes of this Standard a shower fitted with a frameless glass shower screen, or

a screen over a bath less than 1500 mm long, is not an enclosed shower.

1.5.22 Shower area, unenclosed

The area that is open on one or more sides, extending in an arc on the open sides, 1500 mm

from the shower connection at the wall.

1.5.23 Vessel

An open, pre-formed, pre-finished concave receptacle capable of holding water for

residential use, usually for the purpose of washing, e.g., basin, sink, bath, laundry tub.

Page 11: AS3740-2004-Waterproofing in Wet Areas

9 AS 3740—2004

www.standards.com.au Standards Australia

1.5.24 Waterproof (WP)

The property of a material that does not allow moisture to penetrate through it when tested

in accordance with AS/NZS 4858.

NOTE: For the purposes of this Standard, see Clause 3.2.1 for materials deemed to be waterproof

and suitable for including in a waterproofing system.

1.5.25 Waterproofing system

A combination of elements that are required to achieve a waterproof barrier as required by

this Standard, e.g., substrate, membrane, bond breakers, sealants, and finishes.

NOTE: A waterproofing system for a bathroom floor may include lining it with a material in

accordance with Clause 3.2.1(a), (b) or (d) or by using a waterproof flexible sheet flooring

material in accordance with Clause 3.2.1(c).

1.5.26 Water resistant (WR)

The property of a system or material that restricts moisture movement and will not degrade

under conditions of moisture.

1.5.27 Waterstop

A vertical extension of the waterproofing system forming a barrier to prevent the passage of

moisture in the floor.

1.5.28 Wet area

An area within a building supplied with water from a water supply system and includes

bathrooms, showers, laundries and sanitary compartments. Excludes kitchens, bar areas,

kitchenettes or domestic food and beverage preparation areas.

Page 12: AS3740-2004-Waterproofing in Wet Areas

AS 3740—2004 10

Standards Australia www.standards.com.au

S E C T I O N 2 M A T E R I A L S , D E S I G N A N D

I N S T A L L A T I O N C R I T E R I A

2.1 SCOPE OF SECTION

This Section sets out the criteria for the materials, design and installation of wet area

waterproofing systems.

2.2 MATERIALS

Materials for use in waterproofing of wet areas shall be either waterproof or water resistant

as set out in Table 2.1.

2.3 DESIGN AND INSTALLATION

Waterproofing systems and their installation details shall be suitable for the intended

application and shall be waterproof or water resistant as set out by Table 2.1.

In addition, waterproofing systems and their installation details shall be compatible and

shall resist the following:

(a) Differential movement due to—

(i) loadings as defined in AS/NZS 1170.1 and AS/NZS 1170.2;

(ii) shrinkage and expansion of substrate materials, framing and finishes;

(iii) temperature variations from −5°C to 50°C; and

(iv) movements tolerances as defined in AS 2870.

(b) Exposure to—

(i) cleaning chemicals (such as detergents, sodium hypochlorite (bleach) and

ammonia), as required by AS/NZS 4858; and

(ii) alkalis from cement mortar as required by AS/NZS 4858.

2.4 MOVEMENT JOINTS

The waterproofing system shall accommodate the expected movement at movement joints

in the substrate.

Page 13: AS3740-2004-Waterproofing in Wet Areas

11 AS 3740—2004

www.standards.com.au Standards Australia

TABLE 2.1

DESIGN AND INSTALLATION CRITERIA FOR WET AREA WATERPROOFING

Design and installation criteria Vessels or area where

the fixture is installed

Level of

risk Floor Walls Junctions Penetrations

Shower area High Waterproofed

and drained

Water-

resistant

Waterproof Waterproof*

Concrete and

compressed

fibre cement

sheet flooring

Water resistant‡

N/A Waterproof† N/A Bathrooms Medium

Timber floors

including

particleboard

plywood and

other materials

Waterproof

N/A Waterproof† N/A

Concrete and

compressed

fibre cement

sheet flooring

Water resistant‡

Water-

resistant§

Waterproof Horizontal surface

Waterproof*

Vertical surface

water-resistant

Areas adjacent to baths

and spas§ (applies to

all rooms in which a

bath or spa is installed)

Medium

Timber floors

including

particleboard,

plywood and

other materials

Waterproof

Water-

resistant§

Waterproof Horizontal surface

Waterproof*

Vertical surface

water-resistant

Walls adjoining other

vessels

(e.g., sink, basin or

laundry tubs)

Low N/A Water-

resistant

Waterproof Horizontal surface

Waterproof*

Vertical surface

water-resistant

Laundries and WCs Low Water resistant‡ N/A Water-resistant† N/A

Bathrooms and

laundries requiring a

floor waste in

accordance with

Volume One of the BCA

High Waterproofed

and drained

N/A Waterproof† Waterproof where

through the floor,

otherwise N/A

LEGEND:

N/A = not applicable

* Including mechanical fixings or fastenings through surface materials

† Wall/floor junctions only

‡ Where a floor waste is provided the floor shall be graded to the waste

§ If a shower is included in a bath, include the requirements for shower area walls

Page 14: AS3740-2004-Waterproofing in Wet Areas

AS 3740—2004 12

Standards Australia www.standards.com.au

S E C T I O N 3 M A T E R I A L S

3.1 SCOPE OF SECTION

This Section sets out requirements for acceptable materials for use in the waterproofing of

wet areas.

3.2 MATERIALS

3.2.1 Waterproof

For the purposes of this Standard, the following materials used in waterproofing systems

are deemed to be waterproof:

(a) Stainless steel.

(b) Copper, Material not less than 99.9% copper, complying with the requirements for

material designation 110 or 122 given in AS 1566.

(c) Waterproof flexible sheet flooring material with sealed joints.

(d) Membranes meeting the requirements of AS/NZS 4858.

NOTE: For the design and installation criteria of waterproofing systems see Clause 2.3 and

Clause 2.4.

3.2.2 Water-resistant substrates

For the purposes of this Standard, the following materials used in waterproofing systems, in

conjunction with water resistant surface materials in accordance with Clause 3.2.3, are

deemed to be water resistant:

(a) Walls:

(i) Concrete in accordance with AS 3600, treated to resist moisture movement.

(ii) Cement render treated to resist moisture movement.

NOTE: For recommended practice, see CA 27.

(iii) Fibre cement sheeting manufactured in accordance with AS 2908.2.

(iv) Water-resistant plasterboard sheeting manufactured in accordance with

AS 2588 and complying with the performance criteria of ASTM C630.

(v) Masonry in accordance with AS 3700, treated to resist moisture movement.

(b) Floors:

(i) Concrete in accordance with AS 3600 and AS 2870.

(ii) Compressed fibre cement sheeting manufactured in accordance with AS 2908.2.

(iii) Fibre cement sheeting manufactured in accordance with AS 2908.2, and

supported on a structural floor.

(iv) Flooring grade particleboard sheeting manufactured in accordance with

AS/NZS 1860.1, and installed in accordance with AS 1860.

(v) Structural plywood manufactured in accordance with AS/NZS 2269, and

installed in accordance with AS 1684.2, AS 1684.3 and AS 1684.4.

Page 15: AS3740-2004-Waterproofing in Wet Areas

13 AS 3740—2004

www.standards.com.au Standards Australia

3.2.3 Water-resistant surface materials

For the purposes of this Standard, the following surface materials are deemed to be water

resistant for the locations listed:

(a) Walls:

(i) Thermosetting laminated sheet manufactured in accordance with AS 2924.1.

(ii) Pre-decorated fibre cement sheeting manufactured in accordance with

AS 2908.2.

(iii) Tiles when used in conjunction with a substrate listed in Clause 3.2.2.

(iv) Water-resistant flexible sheet wall material with sealed joints, e.g., sheet vinyl

or linoleum, when used in conjunction with a substrate listed in Clause 3.2.2.

(v) Sanitary grade acrylic wall linings.

(b) Floors, when used in conjunction with a substrate listed in Clause 3.2.2:

(i) Tiles.

(ii) Water-resistant flexible sheet flooring material with sealed joints, e.g., sheet

vinyl and linoleum.

3.3 PREFORMED SHOWER BASES AND ENCLOSURES

Materials used in the manufacture of preformed shower bases and enclosures shall be such

that the finished product is waterproof.

3.4 SEALANTS

For the purposes of this Standard, all sealants shall be—

(a) waterproof;

(b) flexible;

(c) mould-resistant; and

(d) compatible with adjacent materials.

3.5 ADHESIVES

Adhesives used in a waterproofing system shall be—

(a) waterproof, where used to adhere other waterproof materials; and

(b) compatible with the materials to which it is adhered.

3.6 SHEET FASTENINGS

Fastenings for sheet materials shall be in accordance with AS 2334 or AS 3566.1.

3.7 OTHER MATERIALS

Materials used in a waterproofing system, which are not mentioned in Section 3, shall be

deemed waterproof or water resistant where it can be shown they meet the criteria set out in

Section 2.

Page 16: AS3740-2004-Waterproofing in Wet Areas

AS 3740—2004 14

Standards Australia www.standards.com.au

S E C T I O N 4 D E S I G N

4.1 SCOPE OF SECTION

This Section sets out design requirements for the waterproofing of wet areas and includes

extent of application of the requirements of Section 2.

NOTE: Additional design considerations for waterproofing of wet areas are given in Appendix B.

4.2 DESIGN

Waterproofing materials and systems shall be designed in accordance with the requirements

of Table 2.1 and Table 4.1. Where Table 4.1 provides additional information on the extent

of applying the requirements of Table 2.1.

4.3 FALLS IN FLOOR FINISHES

Where required, falls in floor finishes shall allow all surface water to drain without

ponding. There shall be no sharp edges or significant lipping in floor tiling.

NOTES:

1 For additional information on falls in floor finishes, see Appendix C.

2 For information on the laying of tiles to enable them to drain without ponding, see AS 3958.1.

4.3.1 SHOWER FLOORS

Falls in shower floors shall be sufficient to prevent water from ponding within the shower

area and shall prevent water from discharging outside the shower area.

NOTE: For recommended ratio of fall, see Paragraph C3, Appendix C.

Page 17: AS3740-2004-Waterproofing in Wet Areas

15

ww

w.s

tan

da

rds.c

om

.au

S

tan

da

rd

s A

ustra

lia

AS

37

40

—2

00

4

TABLE 4.1

GENERAL REQUIREMENTS FOR EXTENT OF APPLICATION

Requirements for elements Vessels or area where the fixture

is installed Floors and horizontal surfaces Walls Wall junctions and joints Penetrations

Shower area

Enclosed and hobbed Waterproof entire enclosed

shower area, including hob (see

Figure 4.3(a))

Waterproof to 150 mm min. above the

shower floor substrate or 25 mm min.

above the maximum retained water

level and the remainder to be water

resistant to a height of 1800 mm min.

from finished floor level (see

Figure 4.3(a))

Enclosed and hobless Waterproof entire enclosed

shower area including water stop

Waterproof to 150 mm min. above the

shower floor substrate and the

remainder to be water resistant to a

height of 1800 mm min. from finished

floor level (see Figure 4.3(a))

Enclosed and stepped down Waterproof entire enclosed

shower area including the

stepdown

Waterproof to 150 mm min. above the

shower floor substrate or 25 mm min.

above the maximum retained water

level and the remainder to be water

resistant to a height of 1800 mm min.

from finished floor level (see

Figure 4.3(a))

Waterproof internal and external

corners and horizontal joints within

a minimum height of 1800 mm.

above the floor level with a

minimum width of 40 mm either

side of junction (see Figure 4.3(a))

Seal all penetrations (see

Clause 5.8.1)

Enclosed and preformed

shower base

N/A Water resistant to a height of

1800 mm min. from finished floor

level (see Figure 4.3(a))

Waterproof internal and external

corners and horizontal joints to a

minimum height of 1800 mm. above

the floor level with a minimum

width of 40 mm either side of

junction (see Figure 4.3(a))

Seal all penetrations (see

Clause 5.8.1)

(continued)

Page 18: AS3740-2004-Waterproofing in Wet Areas

16

S

tan

da

rd

s A

ustra

lia

w

ww

.sta

nd

ard

s.c

om

.au

AS

37

40

—2

00

4

Requirements for elements Vessels or area where the fixture

is installed Floors and horizontal surfaces Walls Wall junctions and joints Penetrations

Unenclosed Waterproof entire shower area

(see Figure 4.3(b))

Waterproof to 150 mm min. above the

shower floor substrate or 25 mm min.

above the maximum retained water

level and the remainder to be water

resistant to a height of 1800 mm min.

from finished floor level (see

Figure 4.3(b))

Waterproof internal and external

corners and horizontal joints to a

minimum height of 1800 mm. above

the floor level with a minimum

width of 40 mm either side of

junction (see Figure 4.3(b))

Seal all penetrations (see

Clause 5.8.1)

Areas outside the shower area for

concrete and compressed fibre

cement sheet flooring

Water resistant to entire floor N/A Waterproof all wall to floor

junctions, where a flashing is used

the horizontal leg shall be a

minimum of 40 mm

N/A

Areas outside the shower area for

timber floors including

particleboard, plywood and other

flooring materials

Waterproof entire floor N/A Waterproof all wall to floor

junctions, where a flashing is used

the horizontal leg shall be a

minimum of 40 mm

N/A

Areas adjacent to baths and

spas*† for concrete and

compressed fibre cement sheet

flooring

Water resistant to entire floor Water resistant to a height of 150 mm

min. above vessel and exposed

surfaces below vessel lip to floor

level* (see Figure 4.1)

Seal edges for extent of vessel and

junction of bath enclosure with

floor. Where the lip of the bath is

supported by a horizontal surface

this area shall be waterproof for

showers over bath and water resist

for all other cases (see Figure 4.1)

Seal all tap and spout

penetrations where they

occur in a horizontal

surface

Areas adjacent to baths and

spas*† for timber floors including

particleboard, plywood and other

flooring materials

Waterproof entire floor Water resistant to a height of 150 mm

min. above vessel and exposed

surfaces below vessel lip to floor

level*(see Figure 4.2)

Seal edges for extent of vessel and

junction of bath enclosure with

floor. Where the lip of the bath is

supported by a horizontal surface

this area shall be waterproof for

showers over bath and water resist

for all other cases (see Figure 4.2)

Seal all tap and spout

penetrations where they

occur in a horizontal

surface

(continued)

TABLE 4.1 (continued)

Page 19: AS3740-2004-Waterproofing in Wet Areas

17

ww

w.s

tan

da

rds.c

om

.au

S

tan

da

rd

s A

ustra

lia

AS

37

40

—2

00

4

Requirements for elements Vessels or area where the fixture

is installed Floors and horizontal surfaces Walls Wall junctions and joints Penetrations

Insert baths N/A for floor under the bath

Waterproof entire shelf area,

incorporating a waterstop under

the bath lip and project a

minimum of 5 mm above the tile

surface (see Figure 5.2(c))

N/A for wall under the bath

Waterproof to 150 mm min. above the

lip of the bath*

N/A for wall under the bath* Seal all tap and spout

penetrations where they

occur in a horizontal

surface

Walls adjoining other vessels

(e.g., sink, basin or laundry tub)

N/A Water resistant to a height of 150 mm

min. above vessel if the vessel is

within 75 mm min. of the wall (see

Figure 4.4)

Where the vessel is fixed to a wall,

seal edges for extent of vessel

Seal all tap and spout

penetrations where they

occur in a horizontal

surface

Laundries and WCs Water resistant to entire floor Seal all wall to floor junctions with a

skirting or flashing to 25 mm min.

above the finished floor level, sealed

to the floor

Waterproof all wall to floor

junctions, where a flashing is used

the horizontal leg shall be a

minimum of 40 mm

N/A

Bathrooms and laundries

requiring a floor waste in

accordance with Volume One of

the BCA

Waterproof and drain entire floor N/A Seal all wall to floor junctions with

a skirting or flashing to 25 mm min.

above the finished floor level, sealed

to the floor

Waterproof where through

the floor, otherwise N/A

LEGEND:

N/A = not applicable

* If a shower is included in a bath refer to the requirements for shower area walls and penetrations

† Does not apply to joinery fittings such as vanities

TABLE 4.1 (continued)

Page 20: AS3740-2004-Waterproofing in Wet Areas

AS 3740—2004 18

Standards Australia www.standards.com.au

DIMENSIONS IN MILLIMETRES

FIGURE 4.1 EXTENT OF TREATMENT FOR WET AREAS—SHOWER AREA-OVER-

BATH—UNENCLOSED SHOWER—FOR CONCRETE AND COMPRESSED FIBRE

CEMENT SHEET FLOORING

Page 21: AS3740-2004-Waterproofing in Wet Areas

19 AS 3740—2004

www.standards.com.au Standards Australia

DIMENSIONS IN MILLIMETRES

FIGURE 4.2 EXTENT OF TREATMENT FOR WET AREAS—SHOWER AREA-OVER-

BATH—UNENCLOSED SHOWER—FOR TIMBER FLOORS INCLUDING

PARTICLEBOARD, PLYWOOD AND OTHER FLOORING MATERIALS

Page 22: AS3740-2004-Waterproofing in Wet Areas

AS 3740—2004 20

Standards Australia www.standards.com.au

DIMENSIONS IN MILLIMETRES

FIGURE 4.3 EXTENT OF TREATMENT FOR SHOWER AREAS—CONCRETE AND

COMPRESSED FIBRE CEMENT SHEET FLOORS

Page 23: AS3740-2004-Waterproofing in Wet Areas

21 AS 3740—2004

www.standards.com.au Standards Australia

FIGURE 4.4 SECTION THROUGH BATH EXTENT OF TREATMENT

FOR WET AREAS —BATHS AND OTHER VESSELS

Page 24: AS3740-2004-Waterproofing in Wet Areas

AS 3740—2004 22

Standards Australia www.standards.com.au

S E C T I O N 5 I N S T A L L A T I O N

5.1 SCOPE OF SECTION

This Section sets out installation requirements for wet area construction.

5.2 GENERAL

Where a tile bed is used, the waterproof membrane shall be installed above or below the tile

bed.

NOTES:

1 For the purposes of this Standard, the figures given in this Section illustrate the membrane

below the tile bed; however, where applicable, the membrane may be installed above the tile

bed.

2 See Table 4.1 for a cross-reference for the relevant installation clauses and the typical detail

drawings.

5.3 ALTERNATE INSTALLATION TECHNIQUES

Installation techniques not covered by this Section shall demonstrate compliance with the

criteria of Section 2.

5.4 CURING OF MATERIALS

Where required by the manufacturer, materials shall be cured in accordance with the

manufacturer’s instructions.

5.5 PREFORMED SHOWER BASES

Preformed shower bases shall be supported to prevent distortion or cracking, and shall be

sufficiently recessed into the wall to allow the water-resistant surface materials to pass

down inside the perimeter rebate of the shower base (see Figure 5.1(a) and (b)).

When installing preformed shower bases, the integrity of the structure shall be maintained.

Page 25: AS3740-2004-Waterproofing in Wet Areas

23 AS 3740—2004

www.standards.com.au Standards Australia

FIGURE 5.1 TYPICAL PREFORMED SHOWER BASE JUNCTIONS

5.6 BATHS AND SPAS

Baths and spas shall be supported to prevent distortion and cracking. Baths and spas

recessed into the wall shall be installed to allow the water-resistant surface materials of the

wall to pass down inside the rim of the bath or spa (see Figures 5.2(a) and 5.2(b)).

When installing baths and spas, the integrity of the structure shall be maintained.

Page 26: AS3740-2004-Waterproofing in Wet Areas

AS 3740—2004 24

Standards Australia www.standards.com.au

FIGURE 5.2 TYPICAL BATH JUNCTION

Page 27: AS3740-2004-Waterproofing in Wet Areas

25 AS 3740—2004

www.standards.com.au Standards Australia

5.7 FLASHINGS

5.7.1 Location

Flashings shall be installed in accordance with the requirements of Table 4.1.

5.7.2 Perimeter flashing

5.7.2.1 General

Perimeter flashing to wall/floor junctions shall have a vertical leg of a minimum of 25 mm

above the finished floor level, except across doorways, and the horizontal leg shall be a

minimum width of 50 mm.

Where a water-resistant substrate is used in conjunction with a water-resistant surface

material to at least 100 mm high above the finished floor level, a sealant shall be used at

wall/floor junctions. This sealant shall be installed after the surface finishes have been

applied.

5.7.2.2 Perimeter flashing at floor level openings

The following applies:

(a) For whole wet area floor waterproofing A waterstop that has a vertical leg finishing

flush with the top of the finished floor level shall be installed at floor level openings.

The floor membrane shall be terminated to create a waterproof seal to the waterstop

and to the perimeter flashing (see Figures 5.3(a) and 5.3(b)).

(b) For other than whole wet area floor waterproofing A waterstop that has a vertical

leg finishing flush with the top of the finished floor level shall be installed at floor

level openings, and shall be waterproofed to the perimeter flashing.

Page 28: AS3740-2004-Waterproofing in Wet Areas

AS 3740—2004 26

Standards Australia www.standards.com.au

FIGURE 5.3 TYPICAL BATHROOM DOOR DETAIL FOR WHOLE

BATHROOM WATERPROOFING

Page 29: AS3740-2004-Waterproofing in Wet Areas

27 AS 3740—2004

www.standards.com.au Standards Australia

5.7.3 Vertical flashing

Vertical flashing may be external or internal and shall terminate a minimum of 1800 mm

above the finished floor level. Vertical flashings may be used as follows:

(a) External vertical flashing may be used with external membranes systems and installed

behind the wall sheeting or render provided they have legs of sufficient width to

allow the wall sheeting or render to overlap by a minimum of 32 mm.

(b) Internal vertical flashing may be used with both external and internal membrane

systems, provided each leg has a minimum overlap of 40 mm to the wall sheeting or

render and where used with—

(i) internal membranes, each leg extends vertically from within the shower tray;

(ii) external membranes, each leg overlaps the top edge of the floor waterproofing

system, by a minimum 20 mm; and

(iii) preformed shower bases or baths, each leg extends to the bottom edge of the

wall sheeting or render.

5.8 PENETRATIONS

5.8.1 Shower areas

Penetrations for taps, shower nozzles and the like shall be waterproofed by sealing with

proprietary flange systems or a sealant. When sealing the tap body to the wall the spindle

housing shall be able to be removed to enable the replacement of the washer without

damaging the seal. Any penetrations of mechanical fixings or fastenings through surface

materials shall be waterproofed.

5.8.2 Other areas

Tap penetrations on horizontal surfaces surrounding baths and spas shall be waterproofed

by sealing with proprietary flange systems or by sealing the tap body to the substrate.

5.9 WET AREA FLOORS

The floor shall be finished with a water-resistant surface material as listed in Clause 3.2.3.

Where there is a waste, the floor finish shall be constructed so that water flows to the waste,

without ponding.

NOTE: For additional information on floor gradients, see Appendix C.

5.10 WALL SHEETING OR RENDER

Where wall sheeting or render is used with an external membrane system in a shower area,

it shall—

(a) not extend into the floor tile bed; or

(b) be waterproofed to prevent moisture movement by capillary action or wicking.

For water-resistant plasterboard sheeting, all cut edges that have the potential to be affected

by moisture shall be waterproofed, including the bottom edge over a preformed shower

base.

5.11 GENERAL SHOWER AREA REQUIREMENTS

5.11.1 Substrate surface preparation for application of a membrane

The area shall be cleaned and dust free. Indentations and imperfections shall be kept to a

minimum and repaired where necessary.

Page 30: AS3740-2004-Waterproofing in Wet Areas

AS 3740—2004 28

Standards Australia www.standards.com.au

5.11.2 Stepdown showers

The highest finished floor level of the shower area shall be stepped down a minimum of

25 mm lower than the finished floor level outside the shower (see Figures 5.4(a), (b), (c)

and (d)).

(a) Enclosed shower—Membrane below tile bed

(b) Enclosed shower—Membrane above tile bed

FIGURE 5.4 (in part) TYPICAL STEPPED DOWN SHOWER CONSTRUCTION

Page 31: AS3740-2004-Waterproofing in Wet Areas

29 AS 3740—2004

www.standards.com.au Standards Australia

(c) Unenclosed shower—Membrane below tile bed

(d) Unenclosed shower—Membrane above tile bed

FIGURE 5.4 (in part) TYPICAL STEPPED DOWN SHOWER CONSTRUCTION

5.11.3 Falls in floor finishes

The entire shower area shall be constructed so that water flows to a waste, without ponding.

NOTE: For additional information on floor gradients, see Appendix C.

5.11.4 Additional requirements for bath end walls abutting a shower

Where a bath end wall is within a shower area, it shall be treated as a shower area wall.

Page 32: AS3740-2004-Waterproofing in Wet Areas

AS 3740—2004 30

Standards Australia www.standards.com.au

5.11.5 Bond breaker installation for bonded membranes

Bond breakers are required at all wall/floor, hob/wall junctions and at movement joints

where the membrane is bonded to the substrate. Bond breakers shall be of the type

compatible with the flexibility class of the membrane to be used (see AS/NZS 4858 and

Table 5.2). Typical details for bond breaker types are given in Figures 5.5, 5.6 and 5.7.

NOTE: For further information about bond breaker action, see Paragraph B3.5.4, Appendix B.

TABLE 5.2

APPROPRIATE BOND BREAKER

Membrane Class Elongation at break Minimum bond breaker/tape width to

bridge joints opening up by 5 mm

I <60% 75 mm with backing rod

II 60% to 300% 35 mm

III >300% 12 mm

NOTE: For example, for a Class II membrane, a 35 mm wide bond breaker/tape should be applied over a

joint to accommodate the joint opening up by up to 5 mm.

FIGURE 5.5 TYPICAL BOND BREAKER DETAIL FOR CLASS I MEMBRANES

FIGURE 5.6 TYPICAL BOND BREAKER DETAIL FOR CLASS II MEMBRANES

Page 33: AS3740-2004-Waterproofing in Wet Areas

31 AS 3740—2004

www.standards.com.au Standards Australia

FIGURE 5.7 TYPICAL BOND BREAKER DETAIL FOR CLASS III MEMBRANES

NOTES TO FIGURES 5.5, 5.6 AND 5.7:

1 Bond breakers for Class I membranes (low extensibility) allow the membrane to flex rather

than stretch.

2 Bond breakers for Class II membranes (medium extensibility) allow the membrane to stretch.

If a tape is used as a bond breaker, either the membrane shall not bond to the tape or the tape

shall have elastic properties similar to the membrane.

3 Bond breakers for Class III membranes (high extensibility) allow the membrane to have even

thickness.

5.11.6 Vertical membrane termination

The membrane shall be applied over the floor substrate and up the vertical face of the wall

as follows:

(a) For showers with hobs and stepdowns, a minimum height of 150 mm above the

finished tile level of the floor or 25 mm above the maximum retained water level,

whichever is the greater.

(b) For hobless showers, a minimum height of 150 mm above the finished tile level of the

floor.

(c) For vertical flashing in shower areas see Clause 5.7.3.

5.11.7 Hob construction

Hobs shall be constructed of masonry, concrete or similar material. Autoclaved aerated

concrete may be used for internal membrane systems but shall not be used for external

membrane systems. Where used, autoclaved aerated concrete shall be primed. All gaps,

joints and intersections of the hob substrate shall be made flush before application of the

membrane. The hobs shall be adequately secured to the floor and sealed against the wall

prior to applying an internal membrane.

Timber shall not be used for hob construction.

5.11.8 Enclosed showers without hobs or set downs

For the purposes of this Standard a shower fitted with a frameless glass shower screen is not

an enclosed shower (see Clause 5.11.9).

At the extremity of the shower area (see Figure 4.3)—

(a) a waterstop shall be positioned so that its vertical leg will finish a minimum of 5 mm

above the finished floor level, where a shower screen is to be installed (see

Figure 5.8); and

(b) where the waterstop intersects with a wall or is joined, the junction shall be

waterproof.

Page 34: AS3740-2004-Waterproofing in Wet Areas

AS 3740—2004 32

Standards Australia www.standards.com.au

FIGURE 5.8 TYPICAL HOBLESS CONSTRUCTION

5.11.9 Unenclosed showers including showers with frameless glass screens

At the extremity of the shower area (see Figure 4.3)—

(a) a waterstop shall be positioned so that its vertical leg will finish flush with the

finished floor level (see Figure 5.9); and

(b) where the waterstop intersects with a wall or is joined, the junction shall be

waterproof.

Alternatively, the whole wet area floor may be waterproofed and drained to a floor waste as

for shower areas (see Figure 5.3(a) and (b)). At doorways, where the height of the tiling

angle needs to be adjusted for tiling finishing purposes, the angle shall be fixed with a

sealant compatible with the waterproofing membrane without damaging the waterproofing

system.

FIGURE 5.9 TYPICAL TERMINATION OF MEMBRANE AT EXTENT OF SHOWER AREA

5.12 MEMBRANE TO DRAINAGE CONNECTION

5.12.1 Concrete Floors

For membrane drainage connections in concrete floors, any one of the following shall

apply:

(a) The drainage riser shall be trimmed to the floor level of the concrete substrate or

screed with all internal burrs removed and the waterproofing membrane terminated a

minimum of 20 mm into the riser.

Page 35: AS3740-2004-Waterproofing in Wet Areas

33 AS 3740—2004

www.standards.com.au Standards Australia

(b) A drainage flange shall be installed with the waterproofing membrane terminated

at/in the drainage flange to provide a waterproof connection.

NOTE: Drainage flanges may be either cast into the concrete slab or fixed to the top surface

of the concrete slab or tile bed.

(c) Where a prefabricated shower tray is used, provision shall be made to drain the tile

bed and provide a waterproof connection to the drain.

5.12.2 Other floors

For membrane drainage connections in other floors, any one of the following shall apply:

(a) The drainage riser shall be fixed to the floor substrate and the waterproofing

membrane terminated a minimum of 20 mm into the riser.

(b) A drainage flange shall be installed with the waterproofing membrane terminated

at/in the drainage flange to provide a waterproof connection (see Figure 5.10).

NOTE: Drainage flanges may be set into the floor or fixed to the top surface of the floor

substrate or tile bed.

(c) Where a prefabricated shower tray is used, provision shall be made to drain the tile

bed and provide a waterproof connection to the drain.

FIGURE 5.10 TYPICAL MEMBRANE TERMINATION AT DRAINAGE OUTLET

5.12.3 Floor waste

The floor waste shall be of sufficient height to suit the thickness of the tile and tile bed at

the outlet position. Provision shall be incorporated to drain the tile bed unless the floor

waste is incorporated as part of the drainage flange, in which case the drainage flange/floor

waste shall drain the tile bed where the waterproof membrane is below the tile bed.

5.13 INSTALLATION OF AN INTERNAL MEMBRANE

5.13.1 Membrane application

5.13.1.1 General

In addition to the requirements of Clauses 5.11 and 5.12, the requirements of this Clause

shall apply also for internal membranes.

Page 36: AS3740-2004-Waterproofing in Wet Areas

AS 3740—2004 34

Standards Australia www.standards.com.au

5.13.1.2 Termination of membranes at showers with hobs

The membrane shall be brought up over the top of the hob, down the outside face and

terminate a minimum 50 mm onto the floor (see Figure 5.11).

Figure 5.12(b) shows the extent of the membrane for an internal shower tray.

FIGURE 5.11 TYPICAL HOB CONSTRUCTION—INTERNAL MEMBRANE

Page 37: AS3740-2004-Waterproofing in Wet Areas

35 AS 3740—2004

www.standards.com.au Standards Australia

FIGURE 5.12 TYPICAL SHOWER CONSTRUCTION

Page 38: AS3740-2004-Waterproofing in Wet Areas

AS 3740—2004 36

Standards Australia www.standards.com.au

5.13.1.3 Showers with water-stops

The membrane shall be brought to the top of the floor finish, except where it is under a

shower screen where it shall terminate a minimum of 5 mm above the finished tile surface

(see Figures 5.8 and 5.9).

5.14 INSTALLATION OF AN EXTERNAL MEMBRANE

5.14.1 Membrane application

5.14.1.1 General

Where the membrane is fabricated from a flexible material, the top edges shall be fixed to

the wall. Fixing penetrations shall be a minimum of 100 mm above the finished tile level of

the shower area. All fixings shall be compatible with the membrane and be non-corrosive.

5.14.1.2 Showers with hobs

The hob shall be included within the finished size of the shower membrane and the

membrane shall finish at the underside of the tile that forms the top of the hob (see

Figure 5.13).

Figure 5.12(a) shows the extent of the membrane for an external shower tray.

FIGURE 5.13 TYPICAL HOB CONSTRUCTION—EXTERNAL (PREFORMED)

MEMBRANE

5.14.2 Base termination of vertical flashing

Vertical flashings in internal corners shall overlap the membrane or extended into the tray

by a minimum of 25 mm.

Page 39: AS3740-2004-Waterproofing in Wet Areas

37 AS 3740—2004

www.standards.com.au Standards Australia

5.14.3 Drainage riser connection

5.14.3.1 Preformed trays

The drainage riser shall be connected to the tray with a waterproof joint.

5.14.3.2 Made in situ shower trays

The membrane shall extend not less than 20 mm into the drainage riser or drainage flange.

The membrane shall be able to form a permanent waterproof seal to the drainage riser or

drainage flange (see Figure 5.10).

5.15 DOORJAMBS AND ARCHITRAVES

Where the bottom of doorjambs and architraves do not finish above the floor tiling, the

portion of the doorframes and architraves below the floor tiling shall be waterproofed to

provide a continuous seal between the perimeter flashing and the waterstop (see

Figure 5.3(a)).

NOTE: Where possible, the doorjambs and architraves should be installed above the floor tiling.

5.16 SHOWER SCREENS

5.16.1 General

For an enclosed shower, the shower screen shall be designed and installed to prevent water

escaping from the shower enclosure.

NOTE: For the purposes of this Standard, a shower fitted with a frameless glass shower screen is

not an enclosed shower (see Clause 5.11.9).

5.16.2 Shower screen placement

5.16.2.1 Showers with hobs

The shower screen shall be installed so as to be flush with the shower area side of the hob

or overhanging into the shower area.

NOTE: A self-draining sub-sill is considered to be a part of the shower screen.

5.16.2.2 Showers with stepdowns

The shower screen shall be installed so as to be flush with the finished vertical surface of

the stepdown of the shower area.

5.16.2.3 Showers without hobs or stepdowns

The shower screen shall incorporate or be mounted on an inverted channel, positioned over

the top of the waterstop that defines the shower area (see Figure 5.8).

5.16.2.4 Bath end walls and dividing walls abutting a shower

The shower screen shall be positioned so that the bottom edge within the shower area is

either flush with the outside edge of the bath or overhanging into the shower area.

NOTE: A self-draining sub-sill is considered to be a part of the shower screen.

Page 40: AS3740-2004-Waterproofing in Wet Areas

AS 3740—2004 38

Standards Australia www.standards.com.au

APPENDIX A

GUIDE FOR COMPLIANCE WITH THIS STANDARD

(Informative)

This Standard reflects traditional designs, materials and installations for waterproofing of

wet areas. The materials, design and installation criteria have been included to quantify the

level of performance expected of new and innovative products and methods that are not

covered by this Standard.

Compliance with this Standard may be achieved by either—

(a) achieving the design and installation criteria specified in Section 2; or

(b) meeting the requirements for materials, design and installation contained in

Sections 3, 4 and 5.

The flow chart outlining the procedure for compliance with this Standard is illustrated in

Figure A1.

FIGURE A1 FLOW CHART OUTLINING COMPLIANCE PROCEDURE

Page 41: AS3740-2004-Waterproofing in Wet Areas

39 AS 3740—2004

www.standards.com.au Standards Australia

APPENDIX B

DESIGN CONSIDERATIONS IN WET-AREA WATERPROOFING

(Informative)

B1 SCOPE

This Appendix provides information that should be considered when designing

waterproofing systems for wet areas in residential buildings and includes guidelines for

dealing with the degree of risk, the types of materials used and their locations in the

construction. Most of these situations are covered in this Appendix.

B2 LEAKAGE THROUGH FINISHES

Water may penetrate wall and floor finishes in wet areas, depending on the frequency, the

intensity and the length of time these surfaces are exposed to water. If not intercepted, this

water may damage the moisture-sensitive materials lying beneath, and sometimes reach

adjoining rooms and their finishes. Consequently, careful attention should be paid to the

design and installation of all materials and components and systems to prevent damage by

water.

Water penetration mainly occurs at joints. Grouted joints, in particular, will often shrink

producing cracks that allow water to pass through. At floor and wall junctions these cracks

can be caused or enlarged by movement of the structure, substrate or finishes.

B3 MOVEMENT AND WATERPROOFING

B3.1 General

Movement in the wall and floor structure is often caused by contraction, expansion or

settlement. Users of this Standard should be aware of the need for waterproofing materials

or system to accommodate the expected movement of the structure.

B3.2 Structure movement

B3.2.1 Frame movement

Potential movement of corner studs is restricted if the studs are fastened to intermediate

blocking pieces. Where the framing is constructed of metal or seasoned timber, blocking is

generally a provision to restrict structural deflection.

Unseasoned timber requires additional consideration for movement and its subsequent

effects upon the waterproofing system.

B3.2.2 Masonry movement

Masonry products such as clay-based materials, cement-based materials, and autoclaved

aerated materials may be subject to specific movement characteristics depending on the

material used. These products also require consideration for movement and its subsequent

effects upon the waterproofing system.

B3.2.3 Panel movement

Panel products are also subject to movement particularly at joints, such products also

require consideration for movement and its subsequent effects upon the waterproofing

system.

Page 42: AS3740-2004-Waterproofing in Wet Areas

AS 3740—2004 40

Standards Australia www.standards.com.au

B3.3 Wall linings under tiles in shower areas

While it is considered that the faces of the nominated linings are impervious enough to

shield wall framing against damage from water that penetrates tiled finishes in wet areas,

the joints between lining sheets and their junctions with other materials may require special

attention to intercept or stop the natural paths of water through them.

Of major concern are the vertical corner joints and the perimeter joints where the potential

for shrinkage and structural movement of the framing is greatest. Vertical corner joints

should, therefore, be provided with flashing angles and sealant for surface finishes.

B3.4 Prefinished wall panels

Vertical joints between panels and their horizontal junctions with other materials should be

carefully considered, as the panels are the only barrier between the water and the framing

beneath. All joints between panels should be either flashed or waterproofed with a sealant

and the bottoms of panels installed to overlap adjoining materials.

B3.5 Floors

B3.5.1 General

Waterproof barriers are required to prevent downward or sideways movement of water into

adjoining construction or rooms.

Water naturally penetrates tiled floor finishes more readily than wall finishes. Where a tile

bed is used, a waterproof membrane may be installed above or below the tile bed. Where a

membrane is installed above a tile bed, it is essential that the tile adhesive be compatible

with the membrane.

Where the membrane is under the tile bed, the tile bed tends to become a reservoir of

moisture.

A drainage system should be provided within the tile bed, over an in situ membrane. This

allows the reservoir of moisture to discharge into the waste fitting or pipe (see Figure 5.10).

B3.5.2 General requirements of barriers

In order to maintain waterproofing integrity, trays or flashing angles should be installed in a

manner that allows for the expected movements of the supporting structure. In situ

membranes and flashings should be able to cover floor-to-wall and wall-to-wall joints

without tearing or breaking under the forces exerted on them when movement occurs in the

adjacent elements to which they are fixed.

For framed construction, prefabricated flashing angles should be adhered only to the floor

allowing the sides of the vertical legs to accommodate the differential movement between

walls and floors.

B3.5.3 In situ barriers (properties and installation)

Some of the materials specified for in situ membranes or flashings are not considered

sufficiently elastic to stretch without tearing, or flexible enough to bend without breaking

when subjected to joint movement. Such barriers should, therefore, not be applied directly

across the joint, and should be completely bonded to both adjacent surfaces. The correct

approach is to first install a ‘bond-breaker’ at the wall/floor junction. This bond-breaker

may consist of any of the following:

(a) A flexible foam-backing rod combined with a suitable bond-breaker tape.

(b) A suitable sealant.

(c) Bond-breaker tape.

Page 43: AS3740-2004-Waterproofing in Wet Areas

41 AS 3740—2004

www.standards.com.au Standards Australia

The method used should be directly related to the type of membrane installed. More rigid

membrane and flashing materials, which bend rather than stretch, are better suited for use

with a backing rod and bond-breaker tape (see Figures 5.5, 5.6 and 5.7).

B3.5.4 Setdowns

Vertical edges of the setdowns should align flush with the wall substrate to avoid creating

voids, cavities or protrusions. They should be repaired prior to installation of a

waterproofing system, as they are the cause of many waterproofing problems.

B3.5.5 Tiles within shower area

Small dimension tiles used in shower areas enable the tiler to achieve the necessary fall to

the waste. Adequate falls become more difficult to achieve as the size of the tiles used

increase.

Page 44: AS3740-2004-Waterproofing in Wet Areas

AS 3740—2004 42

Standards Australia www.standards.com.au

APPENDIX C

FALLS IN FLOOR FINISHES

(Informative)

C1 GENERAL

The primary consideration for falls in floor finishes is to ensure water does not remain on

the finished floor in a manner that can adversely affect the health or amenity of the

occupants or deteriorate building elements.

Falls in floor finishes should ensure water exits the area at the floor waste or doorway if

that is the designed exit point, e.g., laundry door to exterior. Water should not pond on the

floor, with the exception of residual water remaining due to surface tension.

C2 FACTORS AFFECTING FALLS

The ratio of fall achieved in a floor may vary depending upon the—

(a) finished height requirements at doorways;

(b) height of fixtures or fittings;

(c) dimensions of the tiles used, adequate falls become more difficult to achieve as the

size of the tiles used increase;

(d) area of the floor to be drained; and

(e) requirements of persons with disabilities.

C3 FALL RATIOS

The recommended ratio of fall within a shower area is between 1:60 and 1:80.

The recommended ratio of fall in other wet areas is between 1:80 and 1:100.

In some circumstances, the fall in the floor finishes in the same area may vary.

Where falls steeper than 1:100 are not achievable, the effectiveness of the floor drainage

should be confirmed to ensure it meets the primary consideration set down in Paragraph C1

above.

C4 DIAGONAL CUTTING OF TILES

Tiles may require diagonal cutting in the area around the waste to achieve the required falls,

sufficient drainage and to ensure lipping is kept within the guidelines of AS 3958.1.

Page 45: AS3740-2004-Waterproofing in Wet Areas

43 AS 3740—2004

NOTES

Page 46: AS3740-2004-Waterproofing in Wet Areas

AS 3740—2004 44

NOTES

Page 47: AS3740-2004-Waterproofing in Wet Areas

Standards Australia

Standards Australia is an independent company, limited by guarantee, which prepares and publishes

most of the voluntary technical and commercial standards used in Australia. These standards are

developed through an open process of consultation and consensus, in which all interested parties are

invited to participate. Through a Memorandum of Understanding with the Commonwealth government,

Standards Australia is recognized as Australia’s peak national standards body. For further information

on Standards Australia visit us at

www.standards.org.au

Australian Standards

Australian Standards are prepared by committees of experts from industry, governments, consumers

and other relevant sectors. The requirements or recommendations contained in published Standards are

a consensus of the views of representative interests and also take account of comments received from

other sources. They reflect the latest scientific and industry experience. Australian Standards are kept

under continuous review after publication and are updated regularly to take account of changing

technology.

International Involvement

Standards Australia is responsible for ensuring that the Australian viewpoint is considered in the

formulation of international Standards and that the latest international experience is incorporated in

national Standards. This role is vital in assisting local industry to compete in international markets.

Standards Australia represents Australia at both ISO (The International Organization

for Standardization) and the International Electrotechnical Commission (IEC).

Electronic Standards

All Australian Standards are available in electronic editions, either downloaded individually from our web

site, or via On-Line and DVD subscription services. For more information phone 1300 65 46 46 or visit

Standards Web Shop at

www.standards.com.au

Page 48: AS3740-2004-Waterproofing in Wet Areas