as-10.20.007_tms50-eb
TRANSCRIPT
![Page 1: AS-10.20.007_TMS50-eb](https://reader033.vdocuments.mx/reader033/viewer/2022060206/577c7a1c1a28abe054943d1f/html5/thumbnails/1.jpg)
7/26/2019 AS-10.20.007_TMS50-eb
http://slidepdf.com/reader/full/as-1020007tms50-eb 1/52
AS-10.20.7
Page: 1
SERVICE INSTRUCTION
TMS50eb SERVICE INSTRUCTION
TABLE OF CONTENTS
1 BUILT IN FUSES, BUTTONS AND SWITCHES. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
2 REQUIREMENTS FOR ALLOWING A NORMAL START . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
3 SUPERVISIONS IN TMS50eb SOFTWARE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
3.1 Drive time supervision. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
3.2 DIP switch check for drive type failed . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
3.3 Brake supervision . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
3.4 Anti creep device in . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
3.5 Anti creep device out . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
3.6 Safety circuit broken. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
3.7 Shaft door contact open during drive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
3.8 Car door contact open during drive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
3.9 Lock contact open during drive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
3.10 Start permit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
3.11 Fault from drive system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
3.12 Phase supervision . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
3.13 Car light supervision. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
3.14 Thermistor hot . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73.15 Shaft door contact open longer than 10 minutes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
3.16 Lock input not made for starting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
3.17 Swing door contact and concealed door contacts do not match. . . . . . . . . . . . . . . . . . . . . . 7
3.18 Reopen request active longer than 5 minutes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
3.19 Both synchronization switches ( 136 or 77 ) activated . . . . . . . . . . . . . . . . . . . . . . . . . . 7
3.20 Stuck car/landing call button . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
3.21 Safety ray broken . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
3.22 Cylinder limit drive for hydraulic elevators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
3.23 ADO/ACL Supervision . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
3.24 Synchronization failed three times . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
3.25 Overspeed supervision (only with BAR) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
3.26 BAR supervision. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
4 DISPLAY FUNCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
4.1 Self test errors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
4.2 Display functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
4.3 Run time errors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
5 DETAILED RUN TIME ERROR CODES ON DISPLAY. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
01 DRIVE TIME SUPERVISION ELAPSED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
02 DIP SWITCH CHECK FOR DRIVE TYPE FAILED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
03 OVERSPEED (Only with BAR). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
04 SYNCHRONIZATION FAILED THREE TIMES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
05 BRAKE FAULT ON 2 CONSECUTIVE STARTS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3311 DIP SWITCH CHANGED DURING OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
12 ANTICREEP IN FAULT ON 2 CONSECUTIVE DRIVES . . . . . . . . . . . . . . . . . . . . . . . . . . 34
13 ANTICREEP OUT FAULT ON 2 CONSECUTIVE DRIVES . . . . . . . . . . . . . . . . . . . . . . . . . 34
Compiled by: HEC/Sirpa Riikonen Date: 2.4.1996 Issue: A - 27.9.1996
Changed by: HEC/Ari Salonen © KONE Corporation No of Pages: 52
Checked by: HEC/Aki Tamminen\ Product code: TMS50eb BALTIC Language: en
Approved by: HES/Jari Reilio\ Drawing no: SW: FM 4.0 Win
![Page 2: AS-10.20.007_TMS50-eb](https://reader033.vdocuments.mx/reader033/viewer/2022060206/577c7a1c1a28abe054943d1f/html5/thumbnails/2.jpg)
7/26/2019 AS-10.20.007_TMS50-eb
http://slidepdf.com/reader/full/as-1020007tms50-eb 2/52
AS-10.20.7Page: 2
SERVICE INSTRUCTION
14 ADO/ACL PERMIT INPUT (XM17/1) NOT RELEASED. . . . . . . . . . . . . . . . . . . . . . . . . . . 34
15 ADO/ACL PERMIT INPUT (XM17/1) NOT ACTIVATED. . . . . . . . . . . . . . . . . . . . . . . . . . 35
18 PULSE TABLES NOT VALID, NEW SETUP DRIVE REQUIRED (Only with BAR). . . . . . . . . . . . 35
19 CYLINDER LIMIT DRIVE FOR HYDRAULIC ELEVATOR . . . . . . . . . . . . . . . . . . . . . . . . 35
21 SAFETY CIRCUIT BROKEN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
22 SHAFT DOOR CONTACT BROKEN DURING DRIVE . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
23 CAR DOOR CONTACT BROKEN DURING DRIVE. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3624 LOCK CONTACT BROKEN DURING DRIVE. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
25 START PERMIT FAULT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
26 FAULT FROM QUATTRONIC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
26 FAULT FROM V3F-10 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
27 BRAKE FAULT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
28 SAFETY RAY BROKEN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
29 PHASE SUPERVISION FAULT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
30 SAFETY RAY DEVICE BROKEN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
42 CAR LIGHT SUPERVISION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
43 THERMISTOR HOT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
44 DOOR CLOSING FAULT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
45 SHAFT DOOR CONTACT OPEN LONGER THAN 10 MINUTES . . . . . . . . . . . . . . . . . . . . . 3846 LOCK CONTACT NOT MADE FOR STARTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
47 SWING AND CONCEALED DOOR CONTACT DO NOT MATCH . . . . . . . . . . . . . . . . . . . . . 39
48 REOPEN LONGER THAN 5 MINUTES ACTIVE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
50 ANTICREEP FAULT FIRST TIME . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
51 START FAILED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
52 BOTH SYNCHRONISATION SWITCHES ACTIVE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
71 DOOR ZONE SIGNAL IS MISSING. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
72 VANE SIGNAL 61:U IS MISSING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
73 VANE SIGNAL 61:N IS MISSING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
77 DOOR OPENING FAULT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
78 STUCK CAR CALL BUTTON . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
79 STUCK LANDING CALL BUTTON. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
80 FULL LOAD IS ACTIVE CONTINUOUSLY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
81 RELEVELLING HAS BEEN FAILED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
86 START PERMIT CONTINUOUSLY ACTIVE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
90 BAR FLOOR SELECTOR CPU FAILURE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
91 BAR ChA, ChB or ChC FAILURE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
92 ChA AND ChB WIRING CROSSED OR WRONG 77 / 136-POLARITY . . . . . . . . . . . . . . . . . . 42
93 INCORRECT NUMBER OF DOOR ZONE FLAGS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
94 DECELERATION DISTANCE TOO LONG . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
6 TMS50eb EMERGENCY BATTERY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
6.1 TMS50eb Emergency Battery circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
6.2 Trouble shooting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
7 REPLACING TMS50eb MODULE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
7.1 Mechanical change of the module. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
7.2 Commissioning of new module in case of BAR floor selector. . . . . . . . . . . . . . . . . . . . . . . 47
7.3 Commissioning of module in case of drive system changes. . . . . . . . . . . . . . . . . . . . . . . . 47
8 REPLACING OTHER THAN TMS50eb MODULES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
8.1 TMS50e module withTMS50eb module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
8.2 TMS50 module with TMS50eb module. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
8.3 TMS50 module with TMS50eb module, if floor extension module is used . . . . . . . . . . . . . . . 50
![Page 3: AS-10.20.007_TMS50-eb](https://reader033.vdocuments.mx/reader033/viewer/2022060206/577c7a1c1a28abe054943d1f/html5/thumbnails/3.jpg)
7/26/2019 AS-10.20.007_TMS50-eb
http://slidepdf.com/reader/full/as-1020007tms50-eb 3/52
AS-10.20.7Page: 3
SERVICE INSTRUCTION
1 BUILT IN FUSES, BUTTONS AND SWITCHES
The TMS50eb has five built in fuses (slow type) for:
– Car and shaft voltage 2 AT (ceramic) T5x20 mm
– TMS50eb module and
battery charger 4 AT (ceramic) T5x20 mm– Retiring ramp 4 AT (ceramic) T5x20 mm
– Brake/Anti creep device 4 AT (ceramic) T5x20 mm
– Control voltage 1 AT (ceramic) T5x20 mm
Extension module 1 AT (ceramic) T5x20 mm
The TMS50eb houses five push buttons:
– ALARM RESET
– FUNCTION MODE
– ACCEPT/NEXT
– CAR CALL TOPMOST FLOOR
– CAR CALL BOTTOM FLOOR
The ALARM RESET in red colour is used for resetting a stored alarm. Transmit alarm delay
can be adjusted from approx. 2 to 13 seconds. The FUNCTION MODE and ACCEPT NEXT
buttons are used to manipulate the function display. With the CAR CALL buttons it is possible
to drive the elevator for test purpose. Note: An emergency stop situation can not be reset with
these car call buttons.
The TMS50eb has two built in switches:
– INHIBIT LANDING CALLS (261)– INHIBIT DOOR OPENING (263)
With the INHIBIT LANDING CALLS switch all given landing calls can be cancelled and new
landing calls are not accepted. A red LED illuminates when this switch is put to active position.
With the INHIBIT DOOR OPENING switch the door opening is cancelled. An open door will
start closing and a closed door will not open again. A red LED illuminates when this switch is
put to active position. With swing door, the retiring ramp remains energized.
![Page 4: AS-10.20.007_TMS50-eb](https://reader033.vdocuments.mx/reader033/viewer/2022060206/577c7a1c1a28abe054943d1f/html5/thumbnails/4.jpg)
7/26/2019 AS-10.20.007_TMS50-eb
http://slidepdf.com/reader/full/as-1020007tms50-eb 4/52
AS-10.20.7Page: 4
SERVICE INSTRUCTION
2 REQUIREMENTS FOR ALLOWING A NORMAL START
Green indications:
– CPU OK indicates that TMS50eb module and Battery charger is correct and software is
running.
– Phase OK indicates that the 3 phase mains supply has correct voltage and phase rotation.
– Car light voltage OK indicates that there is voltage for the car light. Note, if the car light isswitched, the car light will only be on when the lift is used.
– Thermistor must be green to indicate that the motor is in normal temperature.
– Safety circuit must be green to indicate that no safety devices are activated.
Yellow indications:
– A car or landing call must be present.
– Safety input 2, safety input 3 and safety input 4 must be lit.
– If synchronization switch up is lit the lift can not start in the up direction. Vice versa for
synchronization switch down.
– Start permit must be yellow indicating that all contactors are dropped.
Red indications:
– No red indications must be lit ( BATTERY OK. excluded ).
Car light voltage OK
(green)
Safety circuit (green)
Safety input 2 (yellow)
Safety input 3 (yellow)
Safety input 4 (yellow)
M A X 4 A T
375 Microcomputer
Safetycircuit
DRIVE
MODULE
SIGNALS
Safetyinput 3
Safetyinput 4
8765 Car calls/
4 Carcallsindicator3
2
1
39
765Landing calls/ 4Landing calls
indicator3
2
1
8
7
65 position
4 indicator
3
2
1
Car
Inuselight
Steppingup
Doorzone30
Steppingdown
Inspectiondrive
Anticreepcontact
Switchedcarfan/light
CarlightvoltageOK
Reopenrequest
Opendoor
Closedoor
Startpermit
Thermistor/Oil contact
Alarmreset
Functionmode
Accept/ next
CarcallTopfloor
Emergencyalarm
BatteryOK
CPUOK
PhaseOK
Inhibitlandingcalls
Inhibitdooropening
31:8
31:7
31:631:531:431:3
31:2
31:1
96/ 176
263
261
Carcallbottomfloor
91:U
91:N
161
61:U
61:N
30
42:DS42:U42:N
136:U
136:N
99
35
59
58
67
73:K
43
44
AlarmDelaytime
8
BrakeSupervision
X M 3 1
X M 3 2 3
1
1
4
1 1
8 8
1
X C 1
X H1
3
1 2
X H 3
1
X C
3
1 2
1
X H 4
1 0
X H 5
1
X C 4
1 0
X H 6
2
X C 5
X M 3 3
X C 6
1
X
C 8
8
5 5
X C 9
1
4
X C 1 0
1
3
X M 1
X M 3
X M 6
X M 5
5
1
4
C O N T R O L
V O L T A G E
B A T T E R Y C H A R G E R
T
B R A K E
A N T I C R E E P
R E T I R I N G
R A M P
X
M 7
X M 1
5
X M 9
X M 1 2
X
M 8
X M 1 1
X M 1
3
X M 1
4
X M 1
6
X M 1
7
X M 1
8
X M 2
0
X M 1
9
X C2
1
8 1
8
1
8
1
1
1
2 2
1 1
4
3
3 1
1
5 5 1 1
1
1
5 2
1
2
X M 4
1
4
1
2
1
6
1
1
1
7
1
1
Directionarrowup
Directionarrowdown
88 TMS50eb
Nudging
Prioritycarcallswitch
Firerecall
Retiringramp/cardoorlock
Emergencylight
A B C D F G HE
J K L M P QN
Running
EPDReturned
Runpermit
Safetyray2/Doorclosebutton/DriveOK
Emerg.PowerDrive
Inspectiondrivedown
Inspectiondriveup
Overload
Fullload
Synchonizationswitchup
Synchronizationswitchdown
SafetyraysupervisionSafetyray
Overloadindication
Hydraulicovertravel
Outofservice
M a x . 4 A T
M a x . 4 A T
M a x . 4 A T
M a x . 1 A T
44:E
Safetyinput 2
DoorzoneB30B30
V O L T A G E
M a x . 2 A T
T M S 5 0 e b M O D U L E A N D
R
C A R A N D S H A F T
ADO/ACLspeed
CPU OK (green)
Phase OK (green)
Start permit (yellow)
Thermistor/Oilcontact
(green)
h10207a.eps
![Page 5: AS-10.20.007_TMS50-eb](https://reader033.vdocuments.mx/reader033/viewer/2022060206/577c7a1c1a28abe054943d1f/html5/thumbnails/5.jpg)
7/26/2019 AS-10.20.007_TMS50-eb
http://slidepdf.com/reader/full/as-1020007tms50-eb 5/52
AS-10.20.7Page: 5
SERVICE INSTRUCTION
3 SUPERVISIONS IN TMS50EB SOFTWARE
3.1 Drive time supervision
This supervision is not operative during service drive. Also not operative in downwards drive
with hydraulic elevators.
Counting of drive time starts, when the main contactors are energized (input START PERMIT).
There is adjustable time to spend between two floors. This time can be selected by a dip switch
(Q3) as follows:
Rope lifts: 20 / 40 seconds
Hydraulics: 30 / 60 seconds
This is a fatal error and requires power off for resuming.
3.2 DIP switch check for drive type failed
In each power up situation, the software checks, that the drive module corresponds to dip switch
settings. This is made by energizing drive outputs and checking the state of START PERMIT
input. Before the check is allowed, safety circuit must be closed. This means in normal drive,
that the door(s) must be closed and in inspection drive, that one of the inspection drive direction
buttons must be pressed. For each drive type, there is a predefined sequence to check the drive
module type.
3.3 Brake supervision
This supervision is not activated with hydraulic elevators.
This supervision checks, that there is a voltage for the brake during a drive. This check is made
by checking the state of input BRAKE SUPERVISION. When the main and brake contactors
are energized, there is a maximum time of 400 ms to get the voltage for the brake. If there is no
voltage, start trial will be cancelled and after ca. 2 seconds, the second trial is performed. Two
trials are allowed. If both of them are failed, the elevator is out of service and requires a power
off to resume.
3.4 Anti creep device in
Before start, there is a maximum time of 3 seconds to get the anticreep device in. If the anticreep device is not in, the elevator starts upwards and drives to the next floor ( if already stand-
ing at floor, no drives needed). If the anti creep device is still out, when the elevator arrives to
the floor, the elevator is set out of service. Power off required to resume.
3.5 Anti creep device out
After stop, there is a maximum time of 4 seconds to get the anti creep device out ( after emer-
gency stop, there is a delay of 600 ms before releasing the device, to ensure that the elevator is
stopped ). If the anti creep device is still in after the delay, the elevator will be returned to the
bottom floor and set out of service. Power off required to resume.
![Page 6: AS-10.20.007_TMS50-eb](https://reader033.vdocuments.mx/reader033/viewer/2022060206/577c7a1c1a28abe054943d1f/html5/thumbnails/6.jpg)
7/26/2019 AS-10.20.007_TMS50-eb
http://slidepdf.com/reader/full/as-1020007tms50-eb 6/52
AS-10.20.7Page: 6
SERVICE INSTRUCTION
3.6 Safety circuit broken
If the stop button in car is pressed, the elevator will stop immediately. Car calls are cancelled or
not, according to dip switch selection. If the emergency stop memory is not selected by the dip
switch, all car calls will be canceled and to resume from this, the elevator needs:
1 new car call pressed (if car calls cancelled) OR2 inspection drive turned on OR
3 opening of the door at door zone
If the elevator stands at floor, automatic door will be opened depending on DIP switch setting
(P7). If the elevator is passing the floor and door opening is not allowed by a dip switch, the
door remains closed and retiring ramp energized. Also the car door lock remains active with
ADX/ADF door.
3.7 Shaft door contact open during drive
If the shaft door contact SAFETY INPUT 2 opens during a drive, the elevator will stop immedi-
ately. It continues directly, when the door contact is closed again. Note: for ADX/ADF safety
input 2 is car door contact.
3.8 Car door contact open during drive
If the car door contact SAFETY INPUT 3 opens during a drive, the elevator will stop immedi-
ately. It continues directly, when the door contact is closed again. NOTE: for ADX /ADF safety
input 3 is car door lock.
3.9 Lock contact open during drive
If the lock contact SAFETY INPUT 4 opens during a drive, the elevator will stop immediately.
It continues, when the lock contact is closed again.
3.10 Start permit
Checks, that the main contactors are not stuck. This is made by checking the input START
PERMIT. If there is a stuck contactor, start is not allowed. Resumes to normal use, as soon as
the contactor is ok. The input is also supervised to get pass during a drive.
3.11 Fault from drive system
There is a supervision for Quattronic, and V3F-10 drives. If the drive unit releases main contac-
tors or mechanical brake by itself, the elevator will stop immediately. This supervision checks
the state of inputs MAIN CONTACTORS and MECHANICAL BRAKE from the drive unit
during a drive. Also ALARM signal from V3F-10 drive unit will cause this fault. Resumes to
normal service if a new call is given and with V3F-10, ALARM signal has disappeared.
3.12 Phase supervision
Checks the state of input PHASE OK. If this input is passive for more than 1 second, the eleva-
tor stops immediately. All calls will be canceled and new ones are not accepted. Resumes to
normal operation 10 seconds after the input gets active.
![Page 7: AS-10.20.007_TMS50-eb](https://reader033.vdocuments.mx/reader033/viewer/2022060206/577c7a1c1a28abe054943d1f/html5/thumbnails/7.jpg)
7/26/2019 AS-10.20.007_TMS50-eb
http://slidepdf.com/reader/full/as-1020007tms50-eb 7/52
AS-10.20.7Page: 7
SERVICE INSTRUCTION
3.13 Car light supervision
Inoperative during inspection drive.
Checks the input CAR LIGHT VOLTAGE OK. If the input gets passive, the elevator drives to
destination and stays there with open doors. All calls will be canceled and new ones are notaccepted. Resumes to normal operation as soon as the input gets active or the elevator is turned
to inspection drive.
3.14 Thermistor hot
Checks the input THERMISTOR/OIL CONTACT. If the input gets active (= HIGH IMPED-
ANCE) in inspection, the elevator stops immediately. In normal service, there is a dip switch
selection to stop immediately or drive to the next floor and stay there with door(s) opened. All
calls will be cancelled and new ones are not accepted. Hydraulic elevator will be returned to the
lowest floor. Resumes to normal operation 2 minutes after the input gets passive.
3.15 Shaft door contact open longer than 10 minutes
If swing door is selected by dip switches, this supervision checks the input SAFETY INPUT 2.
If the contact is open longer than 10 minutes, all calls will be cancelled. Resumes normal
operation as soon as the door contact is closed.
3.16 Lock input not made for starting
There is a delay of 3 second for the lock contact to get active after the retiring ramp is ener-
gized. This check is done by reading the input SAFETY INPUT 4. If the lock contact is notmade, start trial will be canceled and tried again. Maximum amount of trials is 5.
3.17 Swing door contact and concealed door contacts do not match
This supervision is activated only, if swing door is selected.
There is a delay of 2 seconds for the concealed door contact to get the same state as swing door
contact. If the state is different, start is not allowed. Resumes to normal operation as soon as the
contacts make in the correct sequence. This check is done by comparing the state of input
SAFETY INPUT 2 to the input SAFETY INPUT 3.
3.18 Reopen request active longer than 5 minutes
This supervision is done by checking the input DOOR REOPEN REQUEST. If the input is
active longer than 5 minutes, the error code will be shown on the display. Returns to normal
operation as soon as the input gets passive.
3.19 Both synchronization switches ( 136 or 77 ) activated
If both inputs SYNCHRONIZATION SWITCH UP and SYNCHRONIZATION SWITCH
DOWN are activated at the same time, all drives are prohibited. If the elevators runs, it will stop
at next floor. Synchronization drive will be done after resuming.
![Page 8: AS-10.20.007_TMS50-eb](https://reader033.vdocuments.mx/reader033/viewer/2022060206/577c7a1c1a28abe054943d1f/html5/thumbnails/8.jpg)
7/26/2019 AS-10.20.007_TMS50-eb
http://slidepdf.com/reader/full/as-1020007tms50-eb 8/52
AS-10.20.7Page: 8
SERVICE INSTRUCTION
3.20 Stuck car/landing call button
A call is set as a stuck call, if it's not possible to cancel it within one minute after arriving to the
floor.
3.21 Safety ray broken
This supervision is available only with swing door and can be selected by a dip switch. The
supervision sets the output SAFETY RAY SUPERVISION together with the retiring ramp. Via
this output the safety ray device gets activated. If the SAFETY RAY is cut during a drive, the
elevator will stop immediately, cancels all car calls and returns to normal service by a new car
call or opening of the door at door zone. Supervision is disabled at door zone, if the elevator is
going to stop to this floor. The condition of safety ray device is also checked in every stop via
input SAFETY RAY 2. If the device is broken, new start is not allowed. This supervision is
selected always together with the safety ray supervision.
3.22 Cylinder limit drive for hydraulic elevators
This supervision reads the state of the input HYDRAULIC OVER TRAVEL. All calls will be
canceled and new ones are not accepted. When the safety circuit is made again, the elevator
returns to the bottom floor, if relevelling with open door is selected by a dip switch. If anticreep
device is selected, the elevator sinks down to the anticreep device and stays there until power off
comes. If the elevator is returned to the bottom floor, it returns to the normal service by service
drive or power off.
3.23 ADO/ACL Supervision
Selectable with a dip switch.
Checks the input ADO/ACL PERMIT. This supervision is done in two phases. The first phase
checks, that the contactor 485 is not stuck. This supervision is done while driving full speed or
relevelling. The other phase checks, that the contactor 485 is able to energize. This phase is
done when starting to relevelling or decelerating to a floor at door zone. If 485 fails, advance
door opening and relevelling with door opened are prohibited. The elevator stops normally,
opens the door(s) and makes a synchronization drive. In synchronization drive, 485 is checked
again via the input. If it still fails, the elevator will be taken out of use, otherwise the elevator
remains to normal service.
3.24 Synchronization failed three times
This supervision is activated in each synchronization drive. If the elevator is not able to syn-
chronize to the terminal floor, a new trial to the other end is done. If the elevator fails 3 times
consecutively, it will be returned to the bottom floor and taken out of use. Power off is required
to resume.
![Page 9: AS-10.20.007_TMS50-eb](https://reader033.vdocuments.mx/reader033/viewer/2022060206/577c7a1c1a28abe054943d1f/html5/thumbnails/9.jpg)
7/26/2019 AS-10.20.007_TMS50-eb
http://slidepdf.com/reader/full/as-1020007tms50-eb 9/52
AS-10.20.7Page: 9
SERVICE INSTRUCTION
3.25 Overspeed supervision (only with BAR)
If an overspeed of greater than 10% of the setup drive (H1) or learning drive (H3) speed is
detected, the elevator is stopped. Find the reason for the overspeed. If any particular reason for
the overspeed cannot be found, it is possible that the elevator has come a little bit faster due to
normal guide rail and gear adapting. New higher speed can be learnt by using BAR function H3.The fault is reset by switching off the power.
3.26 BAR supervision
The communication between BAR and TMS50 microcomputers is supervised.
The system checks that it gets correct information from the BAR.
4 DISPLAY FUNCTIONS
4.1 Self test errors
In the POWER-UP phase a selftest of the computer is performed.
If there is an error detected, the lift is not able to start the operation. An error code is displayed
to indicate this situation. The following selftest errors are possible:
E0 RAM failure
E1 EPROM failure
WHAT TO DO:
– Switch off the main power and change the TMS50eb unit.
After this test is passed, there are two possibilities:
1 There is no error. The system goes automatically into FUNCTION 0 (display car position).
2 There is an error. The error code is flashing. If there are more than one error, the one with
the lowest error number ( highest priority) is shown. See FUNCTION 1 for details.
![Page 10: AS-10.20.007_TMS50-eb](https://reader033.vdocuments.mx/reader033/viewer/2022060206/577c7a1c1a28abe054943d1f/html5/thumbnails/10.jpg)
7/26/2019 AS-10.20.007_TMS50-eb
http://slidepdf.com/reader/full/as-1020007tms50-eb 10/52
AS-10.20.7Page: 10
SERVICE INSTRUCTION
4.2 Display functions
There are different kind of functions for the seven segment display. These functions are:
F0 Car position H0 Return to the F-functions
F1 Current error code H1 Setup drive
F2 Stored error codes, 50 latest H2 Speed monitorF3 Drive reference counter H3 Drive learning
F4 Door reference counter H4 Fine floor level adjustment
F5 Rotary and DIP switch settings H5 Synchronization magnet positions
F6 Software version number H6 Flag position check
F7 Give car calls (1 to top floor) H7 Learning drive - moved flags
F8 Give up calls (1 to top floor-1)
F9 Give down calls (2 to top floor)
FL Number of elevators in group
FH Entry to the BAR functions
The" Function Mode" button is used to select the desired kind of function. After that the"Accept/Next" button is used to scroll through these functions.
TMS Functions BAR Functions
FH
F1F2
F6
F7F9
F0
H6
H7
H0
H1
H2H3
H4
H5
Car Position
Function
Accept/
F3
F4
F5
F8
FL
ModeFunction
Mode
FunctionMode
Next
Accept/ Next
Accept/ Next
![Page 11: AS-10.20.007_TMS50-eb](https://reader033.vdocuments.mx/reader033/viewer/2022060206/577c7a1c1a28abe054943d1f/html5/thumbnails/11.jpg)
7/26/2019 AS-10.20.007_TMS50-eb
http://slidepdf.com/reader/full/as-1020007tms50-eb 11/52
AS-10.20.7Page: 11
SERVICE INSTRUCTION
FUNCTION F0: Car position
DESCRIPTION:
The F0 function shows the car position on display.
It indicates also a position lost mode.
HOW TO ENTER THIS FUNCTION:
There are three ways:
1 Automatically after power on. The current car position will be displayed if it passes selftest
and there is no current error code.
2 If display was used for another function:
Press the FUNCTION BUTTON until the F0 is shown on display.
Then enter with ACCEPT/NEXT BUTTON.
3 No button was pressed for 2 minutes (timeout).
The system returns automatically into the FUNCTION F0.
WHAT INFORMATION IS GIVEN AND HOW:
The car position is indicated by numbers from 01 to 16.
The lowest floor is 01.
There are some special indications as follows:
_ _ = Position lost
Example: Display shows
IMPORTANT! PRIORITY OF CAR POSITION INDICATION
The normal state for the display is to indicate the car position.
There is a timeout from all functions except the flashing error codes.
Two minutes after entering the last button, the system will automatically
change back to FUNCTION F0.
This is done to ensure that the elevator will not remain in another function.
The elevator is at 3rd floor
Position lost
![Page 12: AS-10.20.007_TMS50-eb](https://reader033.vdocuments.mx/reader033/viewer/2022060206/577c7a1c1a28abe054943d1f/html5/thumbnails/12.jpg)
7/26/2019 AS-10.20.007_TMS50-eb
http://slidepdf.com/reader/full/as-1020007tms50-eb 12/52
AS-10.20.7Page: 12
SERVICE INSTRUCTION
FUNCTION F1: Current error code
DESCRIPTION:
The function F1 causes the display to show the errors which are logged at the present moment.
This table can store max. 10 errors. The error shown first has happenedlast. The error is copied into the stored errors F2.
HOW TO ENTER THIS FUNCTION:
Press the FUNCTION BUTTON until the F1 is shown on display.
Then enter with ACCEPT/NEXT BUTTON.
WHAT INFORMATION IS GIVEN AND HOW:
See list of error numbers for detailed error codes on page 30.
When the display shows F1 and the ACCEPT/NEXT BUTTON is pressed,
the first error will be shown. By pressing ACCEPT/NEXT again the second
error number will be shown. In this way up to 10 errors can be shown. An 00
indicates that there is no error. When scanning through all the errors, the system
returns itself after the first 00 (no error) to the beginning of the table. This is
indicated by the F1 again.
Example:
Press: Display shows:
IMPORTANT! FLASHING ERROR CODE
The current error code has, after the selftest, the highest priority in the display
software. This means whenever an error occurs, the display changes to the
current error code. This is indicated by FLASHING numbers. The error with
the highest priority is shown, if more errors occur at the same time.
If the display is indicating an error code by flashing numbers, it can be used for
getting more information.
By pressing the FUNCTION BUTTON the display shows F0 and can be used
with the buttons in the normal way for maximum two minutes. After this timethe display goes back to the flashing mode if the fault remains. Pressing the
button again gives another two minutes.
Safety circuit broken
No other current errors
FUNCTIONMODE
ACCEPTNEXT
ACCEPTNEXT
![Page 13: AS-10.20.007_TMS50-eb](https://reader033.vdocuments.mx/reader033/viewer/2022060206/577c7a1c1a28abe054943d1f/html5/thumbnails/13.jpg)
7/26/2019 AS-10.20.007_TMS50-eb
http://slidepdf.com/reader/full/as-1020007tms50-eb 13/52
AS-10.20.7Page: 13
SERVICE INSTRUCTION
FUNCTION F2: Stored error codes
DESCRIPTION:
The function F2 causes that the errors from function F1 are written into the error table. This
table is stored in abattery backup RAM. In this way, the data is not lost when the power is
switched off. This error table can handle up to 50 errors.
The latest error is shown first. If the table is full and a new error is stored,
the oldest error information will be lost.
HOW TO ENTER THIS FUNCTION:
By pressing the FUNCTION BUTTON until the F2 is shown on display. Then
enter with ACCEPT/NEXT BUTTON.
WHAT INFORMATION IS GIVEN AND HOW:
See list of error numbers for detailed error codes on page 30.
When the display shows F2 and the ACCEPT/NEXT BUTTON is pressed, the
error which happened last, will be shown.
By pressing ACCEPT/NEXT again the second error number can be seen. In
this way up to 50 errors can be shown.
An 00 indicates that there is no error.
When scrolling through the whole error table, the system returns afterthe first 00 (no error) or after 50 errors to the beginning of the table, which is
indicated by F2.
Example:
Press: Display shows:
HOW TO ERASE THE STORED ERRORS:
The error table is erased when the FUNCTION BUTTON is pressed
during the power on phase.The door counter and the drive counter are erased at the same time.
It might be useful to write down the actual date and the data from functions F2,
F3 and F4 before erasing the codes, to save this information.
FUNCTIONMODE
ACCEPTNEXT
ACCEPTNEXT
ACCEPTNEXT Safety circuit broken
Car light supervision
No other stored errors
![Page 14: AS-10.20.007_TMS50-eb](https://reader033.vdocuments.mx/reader033/viewer/2022060206/577c7a1c1a28abe054943d1f/html5/thumbnails/14.jpg)
7/26/2019 AS-10.20.007_TMS50-eb
http://slidepdf.com/reader/full/as-1020007tms50-eb 14/52
AS-10.20.7Page: 14
SERVICE INSTRUCTION
FUNCTION F3: Drive reference counter
DESCRIPTION:
The drive counter (F3) counts the number of starts. All starts are counted (relevelling, service
drive etc.). The data is stored in a battery backup RAM.
HOW TO ENTER THIS FUNCTION:
Press the FUNCTION BUTTON until the F3 is shown on display. Then
enter with ACCEPT/NEXT BUTTON.
WHAT INFORMATION IS GIVEN AND HOW:
This counter consists of 6 digits. The two highest ones are shown first. By
pressing ACCEPT/NEXT again the middle section is shown and by pressing it
the third time the lower ones.
If the ACCEPT/NEXT button is pressed again it will show F3 to indicate
the beginning of this block. The maximum for this counter is 99 99 99, then it
starts again from 00 00 00.
Example:
Press: Display shows:
This example shows that 23,962 drives have happened after last erase.
HOW TO ERASE THE DRIVE COUNTER:
This drive counter is erased when the FUNCTION BUTTON is pressed
during the power on phase. The stored error code and the door counter are
erased at the same time. It might be useful to write down the actual date and
the data from functions F2, F3 and F4 before erasing the codes, to save this
information.
FUNCTIONMODE
ACCEPTNEXT
ACCEPTNEXT
ACCEPTNEXT
Highest part
Middle part
Lowest part
![Page 15: AS-10.20.007_TMS50-eb](https://reader033.vdocuments.mx/reader033/viewer/2022060206/577c7a1c1a28abe054943d1f/html5/thumbnails/15.jpg)
7/26/2019 AS-10.20.007_TMS50-eb
http://slidepdf.com/reader/full/as-1020007tms50-eb 15/52
AS-10.20.7Page: 15
SERVICE INSTRUCTION
FUNCTION F4: Door reference counter
DESCRIPTION:
The door counter (F4) counts the number of door operations. The data is stored in
a battery backup RAM.
HOW TO ENTER THIS FUNCTION:
Press the FUNCTION BUTTON until the F4 is shown on display.
Then enter with ACCEPT/NEXT BUTTON.
WHAT INFORMATION IS GIVEN AND HOW:
The door counter consists of 6 digits. The highest ones are shown first. By pressing
ACCEPT/NEXT again the middle section is shown and by pressing it the third
time the lower ones.
If the ACCEPT/NEXT button is pressed again it will show the F4 to indicate
the beginning of this block. The maximum for this counter is 99 99 99, then it
starts again from 00 00 00.
Example:
Press: Display shows:
This example shows that the door had opened and closed 3904 times after last erase.
HOW TO ERASE THE DOOR COUNTER:
This door counter is erased when the FUNCTION BUTTON is pressed during
the power on phase. The stored error code and the drive counter are erased at
the same time. It might be useful to write down the actual date and the data
from functions F2, F3 and F4 before erasing the codes, to save this information.
FUNCTIONMODE
ACCEPTNEXT
ACCEPTNEXT
ACCEPTNEXT
Highest part
Middle part
Lowest part
![Page 16: AS-10.20.007_TMS50-eb](https://reader033.vdocuments.mx/reader033/viewer/2022060206/577c7a1c1a28abe054943d1f/html5/thumbnails/16.jpg)
7/26/2019 AS-10.20.007_TMS50-eb
http://slidepdf.com/reader/full/as-1020007tms50-eb 16/52
AS-10.20.7Page: 16
SERVICE INSTRUCTION
FUNCTION F5: Rotary and DIP switch settings
DESCRIPTION:
Rotary and DIP switch settings (F5) are made for easily checking which parameters are selected
and valid for the software.It might be easier to see the selected value from this function, than from the
DIP switches themselves.
HOW TO ENTER THIS FUNCTION:
Press the FUNCTION BUTTON until the F5 is shown on display.
Then enter with ACCEPT/NEXT BUTTON.
WHAT INFORMATION IS GIVEN AND HOW:
The values of the rotary and DIP switches are shown in the same way as they
are located physically on the board. This function indicates first the order
number, by showing a NUMBER WITH DOT. The order number can be
scrolled by pressing the ACCEPT/NEXT BUTTON continuously, and releasing it
when the number is shown. After that the value is shown until button is
pressed again.
Example:
Press: Display shows:
Rotary and DIP switch settings
1 Number of floors 02 - 16
2 Main floor 01 - 09
3 Door open time
Setting 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
Seconds 2 3 4 5 6 7 8 9 10 12 15 18 21 24 28 32
FUNCTIONMODE
ACCEPTNEXT
ACCEPTNEXT
first switch settingnumber of floors=6
second switch settingmain floor is 3rd floor
![Page 17: AS-10.20.007_TMS50-eb](https://reader033.vdocuments.mx/reader033/viewer/2022060206/577c7a1c1a28abe054943d1f/html5/thumbnails/17.jpg)
7/26/2019 AS-10.20.007_TMS50-eb
http://slidepdf.com/reader/full/as-1020007tms50-eb 17/52
AS-10.20.7Page: 17
SERVICE INSTRUCTION
4 Buffer time/ Star/delta time
Setting 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
TAC-M ms- 20 40 60 80 100 120 140 160 180 200 220 240 260 280 300
HYDRO sec- .1 .2 .3 .4 .5 .6 .7 .8 1.0 1.4 1.8 2.2 2.6 3.0 3.2
2-SPD sec- .3 .6 1.0 1.3 1.6 2.0 3.0 - 1.0 .8 .7 .6 .5 .3 .15
5 Drive type
00 1-speed
01 2-speed
02 TAC-M
03 Quattronic
04 Beringer
05 Hydro
06 V3F-10
6 Maintenance speed
00 Low speed
01 High speed
7 Door types
00 Swing door, swing door opener
01 Automatic door ADM or equal
02 Swing door and automatic door at the same side03 Automatic door ADX or equal
8 Position indicator type
00 Decimal
01 Binary code (for DOT MATRIX)
02 Seven segment
9 Control mode
00 Push button01 Single button collective
02 Down collective
03 Full collective
10 Anticreep device or relevelling (for hydraulic only)
00 Anticreep device
01 Relevelling
11 Service drive stop
00 At 136:U/N
01 At level in terminal floors
![Page 18: AS-10.20.007_TMS50-eb](https://reader033.vdocuments.mx/reader033/viewer/2022060206/577c7a1c1a28abe054943d1f/html5/thumbnails/18.jpg)
7/26/2019 AS-10.20.007_TMS50-eb
http://slidepdf.com/reader/full/as-1020007tms50-eb 18/52
AS-10.20.7Page: 18
SERVICE INSTRUCTION
12 Advance door opening
00 Normal opening
01 Advance door opening
13 Oscillator lines
00 2 lines (61:U, 61:N)
01 3 lines (61:U, 61:N, 30)
14 Emergency stop
00 Doors are not allowed to open
01 Doors are allowed to open
15 Emergency stop
00 No memory (cancel car calls)
01 With memory
16 Parking at main floor
00 No main floor parking
01 Parking immediately when vacant
02 Parking after 60 seconds vacant
03 Parking after 15 minutes vacant
17 Door position during main floor parking
00 Door closed
01 Door opened
18 Door reopen time
00 3 seconds
01 75% of the door open time
19 Quick close with new car call
00 No quick close
01 Shortening the door time to ca 2 seconds
20 Direction of synchronization drive
00 Downwards
01 Upwards
![Page 19: AS-10.20.007_TMS50-eb](https://reader033.vdocuments.mx/reader033/viewer/2022060206/577c7a1c1a28abe054943d1f/html5/thumbnails/19.jpg)
7/26/2019 AS-10.20.007_TMS50-eb
http://slidepdf.com/reader/full/as-1020007tms50-eb 19/52
AS-10.20.7Page: 19
SERVICE INSTRUCTION
21 Releasing of retiring ramp with semiautomatic door
00 Immediately after the elevator has stopped
01 After the car door is fully open
22 Car calls behind accepted
00 Not accepted
01 Accepted
23 Safety ray / Light ray in car
00 Swing door: Safety ray not connected
Automatic door: Photocell not separately connected
01 Swing door: Emergency stop by safety ray
Automatic door: Photo cell separately connected
24 VOK mode
00 Not in VOK mode
01 VOK mode
25 Fire recall floor01 - 09
00 = Topmost floor
26 Emergency power drive (EPD)/Out of service (OSS) recall floor 01 - 09
00 = Nearest floor
27 Lowest floor 01 - 06
28 Spare
29 Fireman type (FRD)
00 No FRD
01 FRD NL02 FRD DE
03 FRD S UK
04 not used
05 not used
06 not used
07 not used
30 Spare
![Page 20: AS-10.20.007_TMS50-eb](https://reader033.vdocuments.mx/reader033/viewer/2022060206/577c7a1c1a28abe054943d1f/html5/thumbnails/20.jpg)
7/26/2019 AS-10.20.007_TMS50-eb
http://slidepdf.com/reader/full/as-1020007tms50-eb 20/52
AS-10.20.7Page: 20
SERVICE INSTRUCTION
31 Fire detection (FID)
00 No detection selected
01 Detection selected
32 Door position during fire detection (FID)
00 Door closed
01 Door opened
33 Door position after emergency drive (EPD)/ Out of service mode (OSS)
00 Door closed
01 Door opened
34 False car call cancelling (FCC C)
00 No cancelling
01 Cancelling selected
35 Lanterns and gong (other than full collective)
00 Not used
01 Located to 371:1
36 Phase supervision
00 Continuously active
01 Active only when standing
37 Door open limit
00 Door open limit is not connected to TMS50e
01 Door open limit is connected to TMS50e
38 Thermistor hot
00 Drives to next floor, automatic reset01 Stops immediately, version 0,01 -> 0,03 manual reset required
1,00-> automatic reset
39 Emergency power drive (EPD)/ out of service mode (OSS)
00 Emergency power drive
01 Out of service mode
40 Emergency stop by safety ray
00 EMO S (with supervision)
01 EMO AT (for Austria)
A
![Page 21: AS-10.20.007_TMS50-eb](https://reader033.vdocuments.mx/reader033/viewer/2022060206/577c7a1c1a28abe054943d1f/html5/thumbnails/21.jpg)
7/26/2019 AS-10.20.007_TMS50-eb
http://slidepdf.com/reader/full/as-1020007tms50-eb 21/52
AS-10.20.7Page: 21
SERVICE INSTRUCTION
41 Door movement if safety circuit breaks at door zone
00 Opens the door
01 Stop door movement
42 Landing call cross coupling time (LCC)
00 No time
01 2 seconds time
43 Correction drive (COD)
00 No correction drive
01 Correction drive selected
44 ARH disabled (only with anticreep device)
00 Return after 2 hours
01 No returning
45 Drive time supervision
00 Rope elevators: 20 seconds
Hydraulic elevators: 60 seconds
01 Rope elevators: 40 seconds
Hydraulic elevators: 30 seconds
46 Shortening of door open time by photocell
00 Door open time shortened
01 Door open time not shortened
47 Spare
48 ADO/ACL Supervision
00 no supervision
01 ADO/ACL permission supervised
49 Floor selector type
00 Impulse vanes
01 Band Reader
50 Elevator identification number in group
00 Elevator 1
01 Elevator 2
A
![Page 22: AS-10.20.007_TMS50-eb](https://reader033.vdocuments.mx/reader033/viewer/2022060206/577c7a1c1a28abe054943d1f/html5/thumbnails/22.jpg)
7/26/2019 AS-10.20.007_TMS50-eb
http://slidepdf.com/reader/full/as-1020007tms50-eb 22/52
AS-10.20.7Page: 22
SERVICE INSTRUCTION
FUNCTION F6: Software version number
DESCRIPTION:
The Number of the software version and revision can be shown with the software version
number (F6). If there are some problems with the elevator, it is important to provide this infor-mation when calling for some assistance!
HOW TO ENTER THIS FUNCTION:
Press the FUNCTION BUTTON until the F6 is shown on display. Then
enter with ACCEPT/NEXT BUTTON.
WHAT INFORMATION IS GIVEN AND HOW:
First the version number is shown. This is indicated also with the dot.
By pressing ACCEPT/NEXT again, the revision number is shown.
Example:
Press: Display shows:
The software number for this elevator is 1.02.
FUNCTIONMODE
ACCEPTNEXT
ACCEPTNEXT
Revision number
Version number
![Page 23: AS-10.20.007_TMS50-eb](https://reader033.vdocuments.mx/reader033/viewer/2022060206/577c7a1c1a28abe054943d1f/html5/thumbnails/23.jpg)
7/26/2019 AS-10.20.007_TMS50-eb
http://slidepdf.com/reader/full/as-1020007tms50-eb 23/52
AS-10.20.7Page: 23
SERVICE INSTRUCTION
FUNCTION F7: Give car calls
DESCRIPTION:
The Give car calls (F7) -function allows a car call to be made from the 1st up to the top floor.
This function assists during servicing the elevator, like adjusting the drive system.
HOW TO ENTER THIS FUNCTION:
Press the FUNCTION BUTTON until the F7 is shown on display. Then
enter with ACCEPT/NEXT BUTTON. The display shows C1 for CALL TO
FLOOR 1 on the display.
The display is now in the call giving mode. Press the ACCEPT/NEXT
BUTTON again until the floor number which the car should serve is on the
display. The elevator will start to this floor 3 seconds after releasing the
ACCEPT/NEXT BUTTON.
After this call is accepted, the display is ready for the next call.
Example:
Press: Display shows:
There is a timeout for the Give car calls -function. Two minutes after the button was pressed
last time, the display returns into FUNCTION 0 (Floor indication).
FUNCTIONMODE
ACCEPTNEXT
ACCEPTNEXT
ACCEPTNEXT
Release the button and wait for 3 seconds
Release the button and wait for 3 seconds
Call 3 is set
Call 4 is set
ACCEPTNEXT
![Page 24: AS-10.20.007_TMS50-eb](https://reader033.vdocuments.mx/reader033/viewer/2022060206/577c7a1c1a28abe054943d1f/html5/thumbnails/24.jpg)
7/26/2019 AS-10.20.007_TMS50-eb
http://slidepdf.com/reader/full/as-1020007tms50-eb 24/52
AS-10.20.7Page: 24
SERVICE INSTRUCTION
FUNCTION F8: Give up calls
DESCRIPTION:
The Give up calls (F8) -function allows an up call to be made from the 1st up to the top floor -1.
This function assists during servicing the elevator, like adjusting the drive system.
HOW TO ENTER THIS FUNCTION:
Press the FUNCTION BUTTON until the F8 is shown on display. Then
enter with ACCEPT/NEXT BUTTON. The display shows u1 for CALL TO
FLOOR 1 on the display.
The display is now in the call giving mode. Press the ACCEPT/NEXT
BUTTON again until the floor number which the car should serve is on the
display. The elevator will start to this floor 3 seconds after releasing the
ACCEPT/NEXT BUTTON.
After this call is accepted, the display is ready for the next call.
Example:
Press: Display shows:
There is a timeout for the Give up call -function. Two minutes after the button was pressed
last time, the display returns into FUNCTION 0 (Floor indication).
FUNCTIONMODE
ACCEPTNEXT
ACCEPTNEXT
ACCEPTNEXT
Release the button and wait for 3 seconds
Release the button and wait for 3 seconds
ACCEPTNEXT
Call 3 is set
Call 4 is set
![Page 25: AS-10.20.007_TMS50-eb](https://reader033.vdocuments.mx/reader033/viewer/2022060206/577c7a1c1a28abe054943d1f/html5/thumbnails/25.jpg)
7/26/2019 AS-10.20.007_TMS50-eb
http://slidepdf.com/reader/full/as-1020007tms50-eb 25/52
AS-10.20.7Page: 25
SERVICE INSTRUCTION
FUNCTION F9: Give down calls
DESCRIPTION
The Give down calls (F9) -function allows down calls to be made from the 2nd up to the top
floor. This function assists during servicing the elevator, like adjusting the drive system.
HOW TO ENTER THIS FUNCTION:
Press the FUNCTION BUTTON until the F9 is shown on display. Then
enter with ACCEPT/NEXT BUTTON. The display shows n1 for CALL TO
FLOOR 1 on the display.
The display is now in the call giving mode. Press the ACCEPT/NEXT
BUTTON again until the floor number which the car should serve is on the
display. The elevator will start to this floor 3 seconds after releasing the
ACCEPT/NEXT BUTTON.
After this call is accepted, the display is ready for the next call.
Example:
Press: Display shows:
There is a timeout for the Give down calls -function. Two minutes after the button was pressed
last time, the display returns into FUNCTION 0 (Floor indication).
FUNCTIONMODE
ACCEPTNEXT
ACCEPTNEXT
ACCEPTNEXT
Release the button and wait for 3 seconds
Release the button and wait for 3 seconds
ACCEPTNEXT
Call 4 is set
Call 5 is set
![Page 26: AS-10.20.007_TMS50-eb](https://reader033.vdocuments.mx/reader033/viewer/2022060206/577c7a1c1a28abe054943d1f/html5/thumbnails/26.jpg)
7/26/2019 AS-10.20.007_TMS50-eb
http://slidepdf.com/reader/full/as-1020007tms50-eb 26/52
AS-10.20.7Page: 26
SERVICE INSTRUCTION
FUNCTION FL: Number of elevators in group
DESCRIPTION:
The function FL shows the number of elevators in group.
HOW TO ENTER THIS FUNCTION:
Press the FUNCTION BUTTON until FL is shown on display.
Then enter ACCEPT/NEXT BUTTON. The display shows the number of elevators
in group. (01=simplex, 02=duplex)
Example:
Press: Display shows:
FUNCTIONMODE
ACCEPTNEXT Simplex
![Page 27: AS-10.20.007_TMS50-eb](https://reader033.vdocuments.mx/reader033/viewer/2022060206/577c7a1c1a28abe054943d1f/html5/thumbnails/27.jpg)
7/26/2019 AS-10.20.007_TMS50-eb
http://slidepdf.com/reader/full/as-1020007tms50-eb 27/52
AS-10.20.7Page: 27
SERVICE INSTRUCTION
FH Entry to the BAR-functions.
Available only if BAR floor selector is selected by DIP-switch Q7. When FH is on display
and ‘Accept/Next’ button is pressed then display goes to the BAR-menu (H0-H7).
H0 Return to the F-functions.
When H0 on display and ‘Accept/Next’ is pressed then display returns to F0.
H1 Setup drive. Only with the BAR floor selector.
Purpose of the H1 function is to measure distances between each floor and create picture of
the shaft to the computer memory. After H1, computer have default deceleration and stop-
ping distances for each floor. All previous H3 and H4 adjustments will be resetted during
H1.
How to perform H1:
Move the elevator to the bottom or top floor with inspection drive or manually. LED “Door
zone 30” or “Door zone B30” and the corresponding synchronization switch 77 ( LED
136:U or 136:N) must be ON.
Press “Function Mode” until “FH” is shown on the display. Press “Accept/Next” to access
the H-menu. “H0” is displayed. Press “Function Mode” to scroll to H1.
Activate Function H1 by pressing “Accept/Next”. Display should alternate between termi-
nal floor number e.g 01 and “H1”. If there is a problem, ChC or 77 (136) switch signal is
missing from the controller, display will show “_ _”.
Start the learning drive by pressing top and bottom car call buttons simultaneously. The
floor numbers will scroll while the elevator is moving. When stopped, displays “= =” if
learning drive is O.K.
If the elevator reached the terminal floor but “= =” is not displayed, check that the control-
ler floor number parameter is the same as the number of flags installed. Include floor zonemagnets for floors with B-door only in the flag count.
H2 Speed monitor. Only with the BAR floor selector.
Purpose of the H2 speed monitor is to use it as a speed measuring tool. It can be used eg.
for car balancing and hydraulic valve adjustments.
How to perform H2:
Scroll to “H2” by pressing “Function Mode”. Displays “H2”. Activate Function H2 by
pressing “Accept/Next”. Display alternates between “00” , the elevator speed and H2 while
standing. The speed in cm/s is shown when the elevator is moving
H3 Drive learning. Only with the BAR floor selector.
Purpose of the H3 drive learning is to optimise deceleration and stopping distances of the
elevator. During H3, computer will measure deceleration and stopping distances and it
automatically adjusts corresponding deceleration and stopping points to have good drive.
H3 can be performed several times. Always when the drive unit of the elevator is adjusted
man can use H3 to learn new distances.
How to perform H3:
Press “Function Mode” to scroll to H3. Displays “H3”. Activate function H3 by pressing
“Accept/Next”. Display alternates between floor number where elevator is standing and
“H3”.
Run the elevator (2 runs at least) in both directions until the car stops in the door zone area
with a good deceleration curve. The runs must be done preferably between two floors in the
![Page 28: AS-10.20.007_TMS50-eb](https://reader033.vdocuments.mx/reader033/viewer/2022060206/577c7a1c1a28abe054943d1f/html5/thumbnails/28.jpg)
7/26/2019 AS-10.20.007_TMS50-eb
http://slidepdf.com/reader/full/as-1020007tms50-eb 28/52
AS-10.20.7Page: 28
SERVICE INSTRUCTION
middle of the shaft because deceleration switch 77 can disturb learning. The elevator must
reach top speed during each run.
Learning is O.K when the elevator stops at the same point for up and down drives to the
same floor. Marks on the ropes can be used for checking.
H4 Fine floor level adjustment. Only with the BAR floor selector.Purpose of the H4 fine floor level adjustment is to tell to the computer where exactly floor
level is. Top and bottom car call buttons are used to describe how elevator has been stopped
to the floor. Before H4 can be performed successful the elevator must stop to the same posi-
tion when driving to the floor from up and down direction.
How to perform H4:
The elevator should be on Normal Drive. Press “Function Mode” to scroll to H4. Displays
“H4”. Activate function H4 by pressing “Accept/Next”. Display alternates between floor
number where elevator is standing and “H4” every 2 seconds.
Landing calls are now ignored and the elevator only answers car calls one at a time. The
elevator will park with its doors open. The fine floor levels are now set from inside the car.
The elevator is driven to each floor and the inaccuracy of the level measured. Note that only
one drive direction to each floor is needed.
Go inside the car and perform the steps as in following diagram. When finished, press both
buttons to close the doors and return to the machine room.
1
54
32
1
• Press the next floor call
• OK
• Check
1
5 43
2
2
• Press bottom call button
• Each press = 5mm
1
5 43
2
2
• Press top call button• Each press = 5mm
1
54
32
2
• Store floor level.
• Doors close.
Press top and bottom callbuttons together
•TOO HIGH •TOO LOW
Repeat for
floor level
Note 1.
If floor level is correct,
remember to store this by
pressing both buttons before
pressing a call
button for the next floor.
Note 2
If a mistake is made, (e.g pushed too
many times) corrections can be made
by
pushing the opposite push.
each floor
Note 2. Note 2.
START
![Page 29: AS-10.20.007_TMS50-eb](https://reader033.vdocuments.mx/reader033/viewer/2022060206/577c7a1c1a28abe054943d1f/html5/thumbnails/29.jpg)
7/26/2019 AS-10.20.007_TMS50-eb
http://slidepdf.com/reader/full/as-1020007tms50-eb 29/52
AS-10.20.7Page: 29
SERVICE INSTRUCTION
H5 Synchronization magnet positions. Only with the BAR floor selector.
Purpose of the H5 deceleration switch magnet distance function is to adjust terminal floor
deceleration switch magnets to the correct position after learning drive. Correct position for
the magnets can be asked from the computer.
How to perform H5:Press “Function Mode” to scroll to H5. Displays “H5”.
Activate function H5 by pressing “Accept/Next”. Displays “u”corresponding to 77:U. Press
“Accept/Next” to display distance in meters. Press “Accept/Next” to display distance in
centimeters.
Press “Accept/Next”. Displays “n"corresponding to 77:N. Press “Accept/Next” to displaydistance in meters. Press “Accept/Next” to display distance in centimeters.
In this example the 77:U magnet must be positioned 128 cm from the centre of the top floor
flag and 77:N must be positioned 88 cm from the centre of bottom floor flag.
H6 Flag position check. Only with the BAR floor selector.Purpose of the H6 flag position check is to check that all door zone flags are mounted in
accepted +/- 30 mm accuracy compared to the fine floor level which was adjusted during
H4.
How to perform H6:
Press “Function Mode” to scroll to H6. Displays “H6”. Activate function H6 by pressing
“Accept/Next”. Displays “==” if all flags are within acceptable distance.
Or displays first flag number to be moved. Press “Accept/Next”. Displays distance in cen-
timeters how mush flag have to be moved. Positive distance means upwards and negative
number means downwards.
H7 Learning drive - moved flags. Only with the BAR floor selector.
Purpose of the H7 function is to learn new positions of the door zone flags if any of them
have been moved. If door zone flags have been modified man can start from the beginning
and perform steps H1, H3 and H4 or man can use H7 just to learn new flag positions. H7 do
not reset H3 and H4 adjustments like H1 does.
How to perform H7:
Move the elevator to the bottom or top floor. LED “Door zone 30” or “Door zone B30” and
the corresponding Synchronization switch LED (136:U or 136:N) must be ON.
Press “Function Mode” to scroll to H7. Displays “H7”. Activate Function H7 by pressing
“Accept/Next”. Display should alternate between terminal floor number e.g 01 and “H7”. If
there is a problem, ChC or 77 (136) switch signal is missing from the controller, display
will show “_ _”.
77:U Meters Centimeters
77:N Meters Centimeters
![Page 30: AS-10.20.007_TMS50-eb](https://reader033.vdocuments.mx/reader033/viewer/2022060206/577c7a1c1a28abe054943d1f/html5/thumbnails/30.jpg)
7/26/2019 AS-10.20.007_TMS50-eb
http://slidepdf.com/reader/full/as-1020007tms50-eb 30/52
AS-10.20.7Page: 30
SERVICE INSTRUCTION
Start the learning drive by pressing top and bottom car call buttons simultaneously. The
floor numbers will scroll while the elevator is moving.
4.3 Run time errors
1 Stop the elevator immediately, power off required
01 Drive time supervision elapsed
02 DIP switch check for DRIVE TYPE failed
03 Overspeed (only with BAR)
04 Synchronization failed three times
05 Brake fault on 2 consecutive starts
2 Continue this drive, power off required
11 DIP switch changed during operation
12 ANTICREEP IN fault on 2 consecutive drives
13 ANTICREEP OUT fault on 2 consecutive drives
14 ADO/ACL permit input (XM17/1) not released
15 ADO/ACL permit input (XM17/1) not activated18 Pulse tables not valid, new setup drive required (only with BAR)
19 Cylinder limit drive for hydraulic elevators
3 Stop the elevator immediately, next drive when fault disappears
21 Safety circuit broken
22 Shaft door contact broken during drive
23 Car door contact broken during drive
24 Lock contact broken during drive
25 Start permit fault
26 Fault from drive system
27 Brake fault28 Safety ray broken ( swing door )
29 Phase supervision fault
30 Safety ray device broken
– When stopped, displays “==” if learning drive
was O.K or
– Displays “ “ if flag is still not at acceptable
distance.
Repeat functions H6 and H7.
OR
![Page 31: AS-10.20.007_TMS50-eb](https://reader033.vdocuments.mx/reader033/viewer/2022060206/577c7a1c1a28abe054943d1f/html5/thumbnails/31.jpg)
7/26/2019 AS-10.20.007_TMS50-eb
http://slidepdf.com/reader/full/as-1020007tms50-eb 31/52
AS-10.20.7Page: 31
SERVICE INSTRUCTION
4 Not able to start, next drive when fault disappears
41 Not used
42 Car light supervision
43 Thermistor hot
44 Door closing fault
45 Shaft door contact open longer than 10 minutes46 Lock contact not made for starting
47 Swing door and concealed door contacts do not match
48 REOPEN longer than 5 minutes active
49 Not used
50 Anticreep fault first time
51 Start failed
52 Both synchronisation switches active
5 Fault registered, the elevator is able to drive
71 Door zone signal is missing
72 Vane signal 61:U is missing
73 Vane signal 61:N is missing
74 Not used
75 Not used
76 Not used
77 Door opening fault
78 Stuck car call button
79 Stuck landing call button
80 Full load is active continuously
81 Relevelling has been failed
86 Start permit continuously active
6 Continue this drive, power off required
90 BAR floor selector CPU failure
91 BAR ChA, ChB or ChC failure
92 ChA and ChB wiring crossed or 77 / 136 wrong polarity
7 Fault registered, the elevator is able to drive
93 Incorrect number of door zone flags
94 Deceleration distance too long
![Page 32: AS-10.20.007_TMS50-eb](https://reader033.vdocuments.mx/reader033/viewer/2022060206/577c7a1c1a28abe054943d1f/html5/thumbnails/32.jpg)
7/26/2019 AS-10.20.007_TMS50-eb
http://slidepdf.com/reader/full/as-1020007tms50-eb 32/52
AS-10.20.7Page: 32
SERVICE INSTRUCTION
5 DETAILED RUN TIME ERROR CODES ON DISPLAY
Table 1: Detailed run time error codes on display
Error
code
Failure Indication
Item
Description
(What has happened?)
Corrective action
(What to do?)
(How to continue?)
01 DRIVE TIME
SUPERVISION
ELAPSED
The car position information
has not changed after a certain
time period.
( 20/40 seconds for rope eleva-
tors )
( 30/60 seconds for hydro ele-
vators)This means in shafts with door
zone information ( 30 ) that
this input has not got active
and passive state.
In shafts with 61:U and 61:N
oscillators only one of them is
missing.
• Check if other errors appeared,
like 71, 72, 73 or 81.
• Verify shaft arrangement and
wiring of oscillators.
• When the elevator is standing
at level, it might not have
started at all. Check the contac-tor wiring.
• This is a FATAL ERROR. It is
needed to switch the POWER
OFF to restart the elevator.
02 DIP SWITCH
CHECK FOR
DRIVE TYPEFAILED
There is a check that the drive
type which is chosen by DIP
switches E1, E2 and E3matches the con-
nected drive type. ( See picture
A on page 44)
This is done after power on, as
soon as safety chain is made
and doors are closed.
By activating outputs, reading
input start permit and resetting
outputs.
The outputs are checked one
by one.
• Check the DIP SWITCH set-
tings from picture B on page
44. If they are set in the rightway, then verify with TEST
FUNCTION F5 that the setting
was read correctly.
• If the function shows a correct
value, then check the wiring
and plugging of the drive mod-
ule.
• Switch power-off and make the
correct setting if that was
wrong or correct the drivemodule.
• When the test is passed, the
elevator resumes normal oper-
ation.
![Page 33: AS-10.20.007_TMS50-eb](https://reader033.vdocuments.mx/reader033/viewer/2022060206/577c7a1c1a28abe054943d1f/html5/thumbnails/33.jpg)
7/26/2019 AS-10.20.007_TMS50-eb
http://slidepdf.com/reader/full/as-1020007tms50-eb 33/52
AS-10.20.7Page: 33
SERVICE INSTRUCTION
03 OVERSPEED
(Only with BAR)
If an overspeed of greater than
10% of the setup drive (H1) or
learning drive (H3) speed is
detected, the elevator is
stopped.
• Find the reason for the over-
speed. If any particular reason
for the overspeed cannot be
found, it is possible that the
elevator has come a little bit
faster due to normal guide rail
and gear adapting. New higher
speed can be learnt by using
BAR function H3.
• The fault is reset by switchingoff the power.
04 SYNCHRONIZA-
TION FAILED
THREE TIMES
The system has not seen sig-
nals 136, 61 and 30 after stop-
ping synchronization drive.
This has happened on three
consecutive drives.
• Check that the floor level is
reached ( drive adjustment )
and the LED is mentioned
above lit.
• This is a FATAL ERROR. It is
needed to switch the POWER
OFF to restart the elevator.
05 BRAKE FAULT
ON 2 CONSECU-
TIVE STARTS
There has not been voltage for
the brake during two consecu-
tive starts.
• Check the brake voltage.
• This is a FATAL ERROR. It is
needed to switch the POWER
OFF and on to restart the ele-
vator.
Table 1: Detailed run time error codes on display
Error
code
Failure Indication
Item
Description
(What has happened?)
Corrective action
(What to do?)
(How to continue?)
![Page 34: AS-10.20.007_TMS50-eb](https://reader033.vdocuments.mx/reader033/viewer/2022060206/577c7a1c1a28abe054943d1f/html5/thumbnails/34.jpg)
7/26/2019 AS-10.20.007_TMS50-eb
http://slidepdf.com/reader/full/as-1020007tms50-eb 34/52
AS-10.20.7Page: 34
SERVICE INSTRUCTION
11 DIP SWITCH
CHANGED
DURING OPERA-
TION
The DIP switch setting for:
– Drive type
– Door type
– Position indication
– Control mode
– Anticreep/Relevelling
– Oscillator lines
– Emergency stop memory
– Maintenance speed
– Service stop
– Sync. direction– VOK
– Buffer / Y/D time
– Floor number
– Main floor
– Fireman drive
– Fireman recall floor
– EPD recall floor
– False car call cancelling
– Door open limit
– ADO/ACL supervision
has been changed during
power on.
• Check the DIP switch settings.
• To enter new value of dip
switch settings, turn power off
shortly.
• Correct the DIP switch set-
tings.
12 ANTICREEP IN
FAULT ON 2
CONSECUTIVE
DRIVES
The anticreep device has not
released during two consecu-
tive drives.
• Check the device and wiring.
• The elevator continues the
operation as soon as anticreep
device is working.
13 ANTICREEP
OUT FAULT ON 2CONSECUTIVE
DRIVES
The anticreep device is not
activated during two consecu-tive drives.
• Check the device and wiring.
• The elevator continues the
operation as soon as the
anticreep device is working.
14 ADO/ACL
PERMIT INPUT
(XM17/1) NOT
RELEASED
Contactor 485 has not been
energized to allow advance
door opening and relevelling
with door opened.
• Check the condition of 485 and
ADO/ACL input. Check the
wiring too.
• Resumes to normal service
after power off.
Table 1: Detailed run time error codes on display
Error
code
Failure Indication
Item
Description
(What has happened?)
Corrective action
(What to do?)
(How to continue?)
![Page 35: AS-10.20.007_TMS50-eb](https://reader033.vdocuments.mx/reader033/viewer/2022060206/577c7a1c1a28abe054943d1f/html5/thumbnails/35.jpg)
7/26/2019 AS-10.20.007_TMS50-eb
http://slidepdf.com/reader/full/as-1020007tms50-eb 35/52
AS-10.20.7Page: 35
SERVICE INSTRUCTION
15 ADO/ACL
PERMIT INPUT
(XM17/1) NOT
ACTIVATED
Contactor 485 is stuck. • Check the condition of 485 and
ADO/ACL input.
• Resumes to normal service
after power off.
18 PULSE TABLES
NOT VALID, NEW
SETUP DRIVE
REQUIRED
(Only with BAR)
Setup drive H1 has never been
performed with this computer
unit or check sum of floor
tables in EEPROM memory
has been failed.
• Perform BAR functions H1,
H2 and H3 .
• If failure happens second time
to the same computer, EEP-
ROM is broken and TMS50eb
computer module (375) has to
be replaced by new one.
19 CYLINDER
LIMIT DRIVE
FOR HYDRAU-
LIC ELEVATOR
The elevator has passed the top
most floor and drove to the
limit switch 151.
• Check oscillator 61:U, 61:N
and deceleration limit switch
136:U.
• The elevator returns to normal
service by service drive or
power off.
21 SAFETY CIR-
CUIT BROKEN
The safety input SAFETY
CIRCUIT lost the voltage. A
typical reason is that the car
EMERGENCY STOP BUT-
TON was activated. The eleva-
tor is stopped immediately.
Depending on the emergency
stop memory selection, the car
calls are cancelled or not.
• NOTE: The SAFETY CIR-
CUIT is also opened when
switched to inspection drive.
Check, that the red LED
INSPECTION DRIVE is OFF.
• The emergency stop situation is
reset if:
– NEW CAR CALL is given in
car
– the elevator is switched to
INSPECTION DRIVE mode
– the DOOR HAS OPENED
at door zone
22 SHAFT DOOR
CONTACT BRO-
KEN DURING
DRIVE
The safety input 2 has lost the
voltage during a drive.
Reasons could be that the serv-
ice man opened the door or
that the door contact was not
properly made. In the case of
ADX/ADF the car door con-
tact has been broken.
• Check that the door contacts
and the wiring are properly
made if the reason is unknown.
• The elevator resumes normal
operation as soon as the safety
input 2 is active ( LED is ON).
Table 1: Detailed run time error codes on display
Error
code
Failure Indication
Item
Description
(What has happened?)
Corrective action
(What to do?)
(How to continue?)
![Page 36: AS-10.20.007_TMS50-eb](https://reader033.vdocuments.mx/reader033/viewer/2022060206/577c7a1c1a28abe054943d1f/html5/thumbnails/36.jpg)
7/26/2019 AS-10.20.007_TMS50-eb
http://slidepdf.com/reader/full/as-1020007tms50-eb 36/52
AS-10.20.7Page: 36
SERVICE INSTRUCTION
23 CAR DOOR CON-
TACT BROKEN
DURING DRIVE
The safety input 3 was lost the
voltage during a drive.
• Check if:
– Car door contact not prop-
erly made
– Power supply for door
motor lost (fuses in door
module )
– Loose wires
– Car door opened by hand
• The elevator continues with
normal operation when thesafety input 3 is active ( LED is
ON ).
24 LOCK CONTACT
BROKEN
DURING DRIVE
The safety input 4 has lost the
voltage during a drive.
• Check if:
– Service man opened the
lock for service purpose
– Lock contacts not properly
made
– Loose wire
• The elevator resumes normaloperation when the safety input
4 is active ( LED is ON ).
25 START PERMIT
FAULT
The contactors have not
released after the elevator
stopped.
• Check the wiring of start per-
mit circuit, to main contactors.
• The elevator is ready for next
start as soon as start permit is
made ( LED is ON ).
26FAULT FROM
QUATTRONIC
Quattronic drive unit has
released the main contactors
and closed the brake, or sent
the FAULT information.
• Check the wiring from tachom-
eter and drive system.
• The elevator continues with
normal operation when the
inputs MAIN CONTACTORS,
MECHANICAL BRAKE from
the drive unit are working
properly and a call is given.
The FAULT led is litting, when
there is a fault in Quattronic.
Table 1: Detailed run time error codes on display
Error
code
Failure Indication
Item
Description
(What has happened?)
Corrective action
(What to do?)
(How to continue?)
![Page 37: AS-10.20.007_TMS50-eb](https://reader033.vdocuments.mx/reader033/viewer/2022060206/577c7a1c1a28abe054943d1f/html5/thumbnails/37.jpg)
7/26/2019 AS-10.20.007_TMS50-eb
http://slidepdf.com/reader/full/as-1020007tms50-eb 37/52
AS-10.20.7Page: 37
SERVICE INSTRUCTION
26 FAULT FROM
V3F-10
V3F-10 drive unit has released
the main contactors and closed
the brake or sent the ALARM
information.
• Check the wiring and the drive
system.
• The elevator continues with
normal operation when the
inputs MAIN CONTACTORS,
MECHANICAL BRAKE and
ALARM from the drive unit are
working properly and a call is
given. The ALARM led is lit-
ting, when the there is a fault inV3F-10.
27 BRAKE FAULT The brake has lost the voltage. • Check the voltage of the brake.
• The elevator resumes once, the
second time will cause FATAL
ERROR 05. Led brake supervi-
sion is ON.
28 SAFETY RAY
BROKEN
Safety ray has been cut with
swing door.
• Check the safety ray and wir-
ing.
• The elevator continues by
pressing a car call or open the
door at floor.
29 PHASE SUPERVI-
SION FAULT
The build-in PHASE SUPER-
VISION has detected a wrong
phase rotation a missing phase
or a voltage drop.
• Measure that all three phases
are connected correctly.
• The elevator continues with
normal operation after 10 sec-
onds when LED phase ok is
ON.
30 SAFETY RAY
DEVICE BRO-
KEN
Input safety ray 2 has changed
the state.
• Check the safety ray device.
• The elevator continue when the
input safety ray 2 is in correct
state.
Table 1: Detailed run time error codes on display
Error
code
Failure Indication
Item
Description
(What has happened?)
Corrective action
(What to do?)
(How to continue?)
![Page 38: AS-10.20.007_TMS50-eb](https://reader033.vdocuments.mx/reader033/viewer/2022060206/577c7a1c1a28abe054943d1f/html5/thumbnails/38.jpg)
7/26/2019 AS-10.20.007_TMS50-eb
http://slidepdf.com/reader/full/as-1020007tms50-eb 38/52
AS-10.20.7Page: 38
SERVICE INSTRUCTION
42 CAR LIGHT
SUPERVISION
The car light voltage is not
OK.
This error is also shown, if the
switch CAR LIGHT/EMER-
GENCY CALL in machine
room is switched
off.
• Make sure that the car light is
switched on ( if there is a
switch for that ).
• A new start is allowed as soon
as the car light voltage is ok
( LED car light voltage ok is
ON ).
43 THERMISTOR
HOT
The resistance of the thermis-
tors is too high. This means
that the motor is too hot. Typi-
cal reason for this error is a
long drive with slow speed (
service drive ).
• Check the connections.
• Make sure that the motor fan
runs whenever a rope elevator
drives.
• New drive is allowed after 2
minutes from resuming( LED is
GREEN).
44 DOOR CLOSING
FAULT
The safety input 2 or 3 have no
voltage.
• See car door contact not
made. Error no. 23
• See shaft door contact not
made. Error no. 22
• The elevator resumes normal
as soon as inputs are made.
45 SHAFT DOOR
CONTACT OPEN
LONGER THAN
10 MINUTES
Shaft door contact has been
open more than 10 minutes.
• Check that the door is really
closed.
• Check the door wiring and
mechanics.
• The elevator resumes normal
operation as soon as safety
input 2 signal is made.
46 LOCK CONTACT
NOT MADE FOR
STARTING
The safety input 4 has 3 sec-
onds time to get active after
energizing the retiring ramp
output.
• Check that the retiring ramp
energizes and lock contact
operates. In elevators with no
retiring ramp, check that there
is a connection to XH1/8.
• The elevator resumes normal
operation as soon as safety
input 4 is made.
Table 1: Detailed run time error codes on display
Error
code
Failure Indication
Item
Description
(What has happened?)
Corrective action
(What to do?)
(How to continue?)
![Page 39: AS-10.20.007_TMS50-eb](https://reader033.vdocuments.mx/reader033/viewer/2022060206/577c7a1c1a28abe054943d1f/html5/thumbnails/39.jpg)
7/26/2019 AS-10.20.007_TMS50-eb
http://slidepdf.com/reader/full/as-1020007tms50-eb 39/52
AS-10.20.7Page: 39
SERVICE INSTRUCTION
47 SWING AND
CONCEALED
DOOR CONTACT
DO NOT MATCH
Swing door contact and con-
cealed door contact are in dif-
ferent state.
• Check the wiring and mechan-
ics.
• The elevator continues with
normal position as soon as the
contacts are in the same state.
48 REOPEN
LONGER THAN
5 MINUTES
ACTIVE
One or more of the door safety
devices have been active more
than 5 minutes.
• Check following:
– reopen button in car
– door safety devices
- safety edge
- pressure limiter
• The elevator resumes normal
operation as soon as the reo-
pen request input disappears
(LED is OFF).
50 ANTICREEP
FAULT FIRST
TIME
Anticreep contact did not work
correctly.
• Check the anticreep device.
• Elevator remains operative. If
this fault happens again, fault
code 12 or 13 appears.
51 START FAILED V3F-10 drive unit has not
replied to the start request.
• Check the wiring of signal
MECHANICAL BRAKE and
the condition of the drive unit.
• The elevator resumes to nor-
mal service as soon as the sig-
nal is received.
Table 1: Detailed run time error codes on display
Error
code
Failure Indication
Item
Description
(What has happened?)
Corrective action
(What to do?)
(How to continue?)
![Page 40: AS-10.20.007_TMS50-eb](https://reader033.vdocuments.mx/reader033/viewer/2022060206/577c7a1c1a28abe054943d1f/html5/thumbnails/40.jpg)
7/26/2019 AS-10.20.007_TMS50-eb
http://slidepdf.com/reader/full/as-1020007tms50-eb 40/52
AS-10.20.7Page: 40
SERVICE INSTRUCTION
52 BOTH SYN-
CHRONISATION
SWITCHES
ACTIVE
Both synchronisation switches
77 ( 136 ) are active at the
same time.
Synchronization switch up
and down leds are ON.
• Check the polarities from the
DIP switch H3. DIP switch sets
input signal for normally open
or normally closed synchroni-
zation switch.
• Check the synchronization
switches.
• A typical reason for this error
code is that a fuse of 1A ( con-
trol voltage ) is blown.
• The elevator resumes normal
operation when one of the syn-
chronization switch signal
have disappeared.
• Synchronization drive is per-
formed automatically.
See picture C on page 44.
71 DOOR ZONE SIG-
NAL IS MISSING
Door zone signal "Door zone
30" or “Door zone B30” is
missing at the door zone inquestion.
• Check the door zone vanes and
oscillators.
• The elevator resumes normal
operation as soon as door zone
information exists again.
72 VANE SIGNAL
61:U IS MISSING
Vane signal "Stepping up" is
missing.
• Check the vanes and connec-
tions of oscillators.
• The elevator resumes normal
operation when the vane infor-
mation is ok.
73 VANE SIGNAL
61:N IS MISSING
Vane signal "Stepping down"
is missing.
• Check the vanes and connec-
tions of oscillators.
• The elevator resumes normal
operation when the vane infor-
mation is ok.
Table 1: Detailed run time error codes on display
Error
code
Failure Indication
Item
Description
(What has happened?)
Corrective action
(What to do?)
(How to continue?)
![Page 41: AS-10.20.007_TMS50-eb](https://reader033.vdocuments.mx/reader033/viewer/2022060206/577c7a1c1a28abe054943d1f/html5/thumbnails/41.jpg)
7/26/2019 AS-10.20.007_TMS50-eb
http://slidepdf.com/reader/full/as-1020007tms50-eb 41/52
AS-10.20.7Page: 41
SERVICE INSTRUCTION
77 DOOR OPENING
FAULT
Door open limit function is
selected by a dip switch, but
the input state is not changing.
• Check the wiring and door
opening limit switch.
• The elevator works normally,
except the door opening time is
long. Door opening time
resumes to normal as soon as
the input state changes.
78 STUCK CAR
CALL BUTTON
The controller tried to cancel a
car call after the call was
served. The input for this call
was still
active ( connected to -/24 V ).
• Check with the LEDs, which
button is stuck.
• The elevator is ignoring this
call and continuing with serv-
ing the other calls. This call
will be served again, immedi-
ately after the input was pas-
sive.
79 STUCK LAND-
ING CALL BUT-
TON
The controller tried to cancel a
landing call after the call was
served. The input for this call
was still active ( connected to -
/24 V ).
• Check with the LEDs which
button is stuck.
• The elevator is ignoring this
call and continuing with serv-
ing the other calls. This call
will be served again, immedi-
ately after the input was pas-
sive.
80 FULL LOAD IS
ACTIVE CON-
TINUOUSLY
When the elevator is free 5
minutes and full load is valid
all the time a conclusion is
made that the full
load weighing device has been
stuck.
• Check the function and con-
nections of the full load weigh-
ing device.
• The elevator resumes normal
operation taking the full load
weighing device into account.
81 RELEVELLING
HAS BEEN
FAILED
Relevelling for hydraulic ele-
vator has failed to reach the
floor level within drive time
supervision time. Elevator has
been returned to the lowest
floor and switched out of use.
Blinking fault code on the dis-
play is 01 and fault code 81 is
in fault memory (function F1).
• Check the adjustment of valves
and the vanes at the floor level
in question.
• See error 01. Check relevelling
function.
Table 1: Detailed run time error codes on display
Error
code
Failure Indication
Item
Description
(What has happened?)
Corrective action
(What to do?)
(How to continue?)
![Page 42: AS-10.20.007_TMS50-eb](https://reader033.vdocuments.mx/reader033/viewer/2022060206/577c7a1c1a28abe054943d1f/html5/thumbnails/42.jpg)
7/26/2019 AS-10.20.007_TMS50-eb
http://slidepdf.com/reader/full/as-1020007tms50-eb 42/52
AS-10.20.7Page: 42
SERVICE INSTRUCTION
86 START PERMIT
CONTINUOUSLY
ACTIVE
Start permit input has been in
incorrect state during drive.
• Check the start permit chain.
• Requires power OFF.
90 BAR FLOOR
SELECTOR CPU
FAILURE
TMS50eb module internal fail-
ure.
• Change TMS50eb module.
• Run setup procedure functions
H1, H3 and H4 with new mod-
ule.
91 BAR ChA, ChB or
ChC FAILURE
Pulses from car top band
reader are not coming correctlyto the TMS50eb module.
Elevator drives to the final
limit switch.
• Check alignment of the band
inside reader fork.• Check that band is clean. Holes
are not filled by dust.
• Check that ChA and ChB leds
are blinking when driving serv-
ice drive from car top.
• Check door zone flags
mounted on the band.
• Check that ChC and Chd leds
are lit while door zone flag is
inside the reader fork. And
ChC and ChD leds are not lit
when the lift is between floor
levels.
• Check wiring from the reader
to the control panel and to the
XC5 connector.
• This is a FATAL ERROR. It is
needed to switch the POWER
OFF to restart the elevator.
92 ChA AND ChB
WIRING
CROSSED OR
WRONG 77 / 136-
POLARITY
Pulses from car top band
reader are going to the wrong
direction when passing 77-
deceleration switch or 77-
deceleration switch polarity is
wrong.
There could be wiring mistake
or 77-switch magnet is wrong
way round or DIP switch H3 is
UP. Elevator drives to the final
limit switch.
• Check that DIP H3 is down.
• Check both terminal floors that
corresponding 136 LED is on
and other 136 LED is off. If not
ok then check bistable 77-
switches on the car roof.
• Swap ChA and ChB wires
from XC5/1 and XC5/2 termi-
nals.
• This is a FATAL ERROR. It isneeded to switch the POWER
OFF to restart the elevator.
Table 1: Detailed run time error codes on display
Error
code
Failure Indication
Item
Description
(What has happened?)
Corrective action
(What to do?)
(How to continue?)
![Page 43: AS-10.20.007_TMS50-eb](https://reader033.vdocuments.mx/reader033/viewer/2022060206/577c7a1c1a28abe054943d1f/html5/thumbnails/43.jpg)
7/26/2019 AS-10.20.007_TMS50-eb
http://slidepdf.com/reader/full/as-1020007tms50-eb 43/52
AS-10.20.7Page: 43
SERVICE INSTRUCTION
93 INCORRECT
NUMBER OF
DOOR ZONE
FLAGS
During setup drive H1 the
number of door zones are cal-
culated and compared to the
rotary switch A setting. Com-
parison has given different
value.
• Check that rotary switch A is
correct and all the flags are
correctly mounted on the band.
Check bistable switch for rear
side if exists.
• Put lift to the terminal floor
and perform H1 again.
94 DECELERATION
DISTANCE TOO
LONG
Only with TAC-M and Quat-
tronic drives.
BAR-function H3 has meas-
ured deceleration distance
which is longer than shortest
floor to floor distance.
• Use function H5 to check
deceleration distance. Deceler-
ation distance is displayed
77:U magnet distance -7 cm.
• Do functions H1 and H3 once
again. If still failure exists, try
to adjust deceleration distance
shorter. Then use H3 to learn
new shorter deceleration dis-
tance.
Table 1: Detailed run time error codes on display
Error
code
Failure Indication
Item
Description
(What has happened?)
Corrective action
(What to do?)
(How to continue?)
![Page 44: AS-10.20.007_TMS50-eb](https://reader033.vdocuments.mx/reader033/viewer/2022060206/577c7a1c1a28abe054943d1f/html5/thumbnails/44.jpg)
7/26/2019 AS-10.20.007_TMS50-eb
http://slidepdf.com/reader/full/as-1020007tms50-eb 44/52
AS-10.20.7Page: 44
SERVICE INSTRUCTION
pict. A
pict. B
1-speed
2-speed
TAC-M
Q10
Beringer
Hydronic
V3F - 10
Not used
A B C D E F G H
H3
A B C D E F G H
pict. C
![Page 45: AS-10.20.007_TMS50-eb](https://reader033.vdocuments.mx/reader033/viewer/2022060206/577c7a1c1a28abe054943d1f/html5/thumbnails/45.jpg)
7/26/2019 AS-10.20.007_TMS50-eb
http://slidepdf.com/reader/full/as-1020007tms50-eb 45/52
AS-10.20.7Page: 45
SERVICE INSTRUCTION
6 TMS50EB EMERGENCY BATTERY
6.1 TMS50eb Emergency Battery circuit
The TMS50eb contains:
1- Battery charger for 12 V battery2- Charge level supervision
3- Over current protection
4- Over voltage protection
5- Supply to 12 V emergency bell
6- Emergency car light supply
7- Emergency alarm circuit
6.1.1 Battery charger for 12 V battery
The built-in charger is charging the battery with constant voltage. Maximum current is limited
to 500-550 mA.
6.1.2 Charge level supervision
Battery will be load tested automatically after power up (reset) of computer and then once in 24
hours. Load test is done by 11 ohm resistor for 10 seconds time. If battery voltage drops below
10.5 V during test then Battery OK led lits red, otherwise it lits green.
Lower 9.4V limit is used for battery deep discharge protection. While TMS50eb module and
battery charger supply is off then all load will be disconnected from battery is voltage drops
below 9.4V. The green LED for the "Battery OK" goes red.
6.1.3 Over current protection
In series with the battery connection (terminal XM6) is a thermal 4 A fuse. The fuse
disconnects the load from the battery. If the fuse trips, the load has to be off for at least 5 min-
utes before resuming normal operation.
6.1.4 Voltage protection
XM6 has overvoltage protection for 24 V.
6.1.5 Supply to 12 V emergency bell
On terminal XC5/6 and XH5/6 there is a fused 12 V/500 mA supply to emergency bell or
alarm. A 12 V line regulator ensures, that the emergency devices are always operative, when the
power is ON.
6.1.6 Emergency car light supply
Terminal XC5/7 supplies 12 V to the car emergency light if the car light supply is off (and there
is a battery connected). The activation of the emergency car light function is shown by a yellow
"Emergency light" indicator on the TMS50eb unit.
![Page 46: AS-10.20.007_TMS50-eb](https://reader033.vdocuments.mx/reader033/viewer/2022060206/577c7a1c1a28abe054943d1f/html5/thumbnails/46.jpg)
7/26/2019 AS-10.20.007_TMS50-eb
http://slidepdf.com/reader/full/as-1020007tms50-eb 46/52
AS-10.20.7Page: 46
SERVICE INSTRUCTION
6.1.7 Emergency alarm circuit
The internal emergency alarm will be activated if +12 VDC is applied to XC3/9 or XH3/9.
There is a about 2-13 second adjustable delay (potentiometer on TMS50eb unit) during which
the signal has to be active. The alarm activates a red light ("Emergency alarm") and the
"Transmit output relay". The relay has one uncommitted switch over contact at XM21/3-5 andone closing contact at XM21/1-2.
The emergency alarm is reset by pushing the red reset button on the TMS50eb unit or by
connecting XM21/6 to C-.
6.2 Trouble shooting
6.2.1 Normal state
In normal operation the following state is observed;
– "Battery OK" LED should be lit green.
– "Emergency light" and alarm LED should be off.
– + 12...13.5 VDC on the XM6/1 (versus C-, XM6/2), on XC5/6 and on XH5/6
6.2.2 No voltage on XC5/6 and XH5/6 ( power off situation )
If voltage on XM6 and "Battery OK" LED is green, then the internal thermal 4 A current
protection has tripped. Disconnect the load at XH5/6 and XC5/6 and wait at least 5 minutes for
the protection device to cool.
If "Battery OK" is red, the undervoltage protection has disconnect the load to protect thebattery. Ensure there is no load on XC5/6 or XH5/6 and the battery will be recharged during
normal lift operation (>10 hours).
6.2.3 No voltage on XM6/1
If no +12 V voltage on XM6/1, the battery is damaged and needs replacing. If the voltage is not
recovering, the charging circuit in the TMS50eb is damaged. Replace the TMS50eb unit.
![Page 47: AS-10.20.007_TMS50-eb](https://reader033.vdocuments.mx/reader033/viewer/2022060206/577c7a1c1a28abe054943d1f/html5/thumbnails/47.jpg)
7/26/2019 AS-10.20.007_TMS50-eb
http://slidepdf.com/reader/full/as-1020007tms50-eb 47/52
AS-10.20.7Page: 47
SERVICE INSTRUCTION
7 REPLACING TMS50EB MODULE
7.1 Mechanical change of the module
– Switch main power supply and possible car light supply off.
– Pull out connectors and unscrew four fixing screws.
– Pull out possible extension module flat cable.
– Remove TMS50eb module from control panel.
– Set DIP and ROTARY switches of new module similar than they are in old one.
– Transfer drive signal plate from old module to new module.
– In case of Duplex: Transfer Duplex serial module from old module to new module. Verify
new and old module software number. If it is not the same, change also the software
EPROM.
– Install new module to control panel.
– Tighten four fixing screws. Right lower screw should made earthing.
– Put back cables and connectors.
7.2 Commissioning of new module in case of BAR floor selector.
If BAR floor selector is used then setup and learning drives has to be done. Computer in
TMS50eb module must know floor positions, speed and deceleration curve of the elevator.
– Perform BAR function H1 Setup drive. Details at page 27.
– Perform BAR function H3 Drive learning. Details at page 27.
– Perform BAR function H4 Fine floor level adjustment. Details at page 28.
BAR functions H2, H5, H6 and H7 should not be needed because speed and deceleration dis-tance of the drive system remains the same.
7.3 Commissioning of module in case of drive system changes.
If BAR floor selector is used and nominal speed, creeping speed or deceleration distance of the
drive system is changed then learning drives has to be done again. Computer in TMS50eb mod-
ule must know speed and deceleration curve of the elevator.
– Perform BAR function H3 Drive learning. Details at page 27.
– Perform BAR function H5 Deceleration switch magnet distance. Details at page 29.
BAR functions H1, H2, H4, H6 and H7 should not be needed because exact floor positions of
the elevator remains the same.
![Page 48: AS-10.20.007_TMS50-eb](https://reader033.vdocuments.mx/reader033/viewer/2022060206/577c7a1c1a28abe054943d1f/html5/thumbnails/48.jpg)
7/26/2019 AS-10.20.007_TMS50-eb
http://slidepdf.com/reader/full/as-1020007tms50-eb 48/52
AS-10.20.7Page: 48
SERVICE INSTRUCTION
8 REPLACING OTHER THAN TMS50EB MODULES
8.1 TMS50e module withTMS50eb module
Follow the instructions for replacing a TMS50e module:
1 Turn the main and possible car light switch OFF. Ensure that there is no voltage!
2 In case of duplex disconnect the serial communication cable.
3 Disconnect all Phoenix plugs.
4 Loose the 4 fixing screws.
5 Take the TMS50e module out of the panel.
6 Change the additional Phoenix plugs (if used) to the new module.
7 Place the new TMS50eb module and screw it tight. Watch especially that the lower right
screw is tightend together with a dented washer, which puts disturbance signals to earth.
8 Set all the Rotary and DIP switches exactly according to the old one.
9 Change in a duplex case the additionally screwed serial module to the new microcomputer
module.
10 Change the drive plate with the signal names depending on the drive type to the new mod-
ule.
11 Connect all the Phoenix plugs and the group cable, if exists.
12 Turn ON the main and the possible car light switch
13 Reset the fault log of the microcomputer module. This can be done by keeping the Func-
tion button on TMS50eb pressed during the 3-phase automat 286 is switched OFF and ON
again.
14 Make a functional test of the lift.
![Page 49: AS-10.20.007_TMS50-eb](https://reader033.vdocuments.mx/reader033/viewer/2022060206/577c7a1c1a28abe054943d1f/html5/thumbnails/49.jpg)
7/26/2019 AS-10.20.007_TMS50-eb
http://slidepdf.com/reader/full/as-1020007tms50-eb 49/52
AS-10.20.7Page: 49
SERVICE INSTRUCTION
8.2 TMS50 module with TMS50eb module
The new TMS50eb microcomputer module can be used to substitute an older TMS50 module.
The connections are exactly the same.
For replacing a TMS50 with a new TMS50eb module follow the steps:1 Turn the main and possible car light switch OFF. Ensure that there is no voltage !
2 Disconnect all Phoenix plugs.
3 Loose the 4 fixing screws.
4 Take the TMS50 module out of the panel.
5 Change the additional Phoenix plugs (if used) to the new module.
6 Place the new TMS50eb module and screw it tight. Watch especially that the lower rightscrew is tightend together with a dented washer, which puts disturbance signals to earth.
7 Set all the rotary and DIP switches of the lower row exactly according to the old one. In the
additional row of the new module, all rotary switches must be set to ´0´ and all DIP
switches to the ´DOWN´ position to get the TMS50 functions (and no others).
8 Change the drive plate with the signal names depending on the drive type to the new mod-
ule.
9 Connect all the Phoenix plugs.
10 Turn ON the main and the possible car light switch.
11 Reset the fault log of the microcomputer module. This can be done by keeping the Func-
tion button on TMS50eb pressed during the 3-phase automat 286 is switched OFF and ON
again.
12 Make a functional test of the lift.
Additional wire needed with Quattronic drives !
If the lift has a Quattronic drive system, a wire for a new signal needs to be added. It is the´FAULT´ signal and prevents a start trial of the TMS50eb as long as the fault exists.
Add the following wire: TMS50eb / XM17/2 -- Quattronic / 18
.
Add this wire into the circuit diagramsas well (circuit diagram page 4) TMS50eb Quattronic
h10207b.wmf
![Page 50: AS-10.20.007_TMS50-eb](https://reader033.vdocuments.mx/reader033/viewer/2022060206/577c7a1c1a28abe054943d1f/html5/thumbnails/50.jpg)
7/26/2019 AS-10.20.007_TMS50-eb
http://slidepdf.com/reader/full/as-1020007tms50-eb 50/52
AS-10.20.7Page: 50
SERVICE INSTRUCTION
8.3 TMS50 module with TMS50eb module, if floor extension module is used
In case of 9 to 16 floors, a TMS50 floor extension module is used. This module can not be con-
nected to the TMS50eb microcomputer module. It is not compatible.
There is the possibility to replace the needed module by one of the same type, which means
TMS50 microcomputer or floor extension. If they are not available it is required to use aTMS50eb microcomputer module and a TMS50e extension module. This requires some addi-
tional wiring as well.
You need: 1 TMS50eb microcomputer module
1 Extension module (490478G01)
1 Plastic cover for extension module 1.DC9-16 (491130G01)
For replacing the TMS50 microcomputer module and TMS50 floor extension follow the steps:
1 Turn the main and possible car light switch OFF. Ensure that there is no voltage !
2 Disconnect all Phoenix plugs.
3 Loose the 2 fixing screws of the floor extension and the flat cable between the modules and
put it out of the panel.
4 Loose the 4 fixing screws of the microcomputer module and take it out.
5 Change the additional Phoenix plugs (if used) to the new module.
6 Place the new TMS50eb module and screw it tight. Watch especially that the lower right
screw is tightend together with a dented washer, which grounds the module.
7 Set all the rotary and DIP switches of the lower row exactly according to the old one. In the
additional row of the new module, all rotary switches must be set to ´0´ and all DIP
switches to the ´DOWN´ position to get the TMS50 functions (and no others).
8 Change the drive plate with the signal names depending on the drive type to the new mod-
ule.
9 Place the TMS50eb extension module in, connect the flat cable and screw it tight.
10 Connect all the Phoenix plugs.
![Page 51: AS-10.20.007_TMS50-eb](https://reader033.vdocuments.mx/reader033/viewer/2022060206/577c7a1c1a28abe054943d1f/html5/thumbnails/51.jpg)
7/26/2019 AS-10.20.007_TMS50-eb
http://slidepdf.com/reader/full/as-1020007tms50-eb 51/52
AS-10.20.7Page: 51
SERVICE INSTRUCTION
11 Add the following wiring:
12 Turn ON the main and the possible car light switch.
13 Reset the fault log of the microcomputer module. This can be done by keeping the Func-
tion button on TMS50eb pressed during the 3-phase automat 286 is switched OFF and ON
again.
14 Make a functional test of the lift.
NOTE: POWER SUPPLY
Additional load is connected to thetransformer.
Check, that the transformer can handleit. The AC voltage should be 18 - 21V.
h10207c.wmf
![Page 52: AS-10.20.007_TMS50-eb](https://reader033.vdocuments.mx/reader033/viewer/2022060206/577c7a1c1a28abe054943d1f/html5/thumbnails/52.jpg)
7/26/2019 AS-10.20.007_TMS50-eb
http://slidepdf.com/reader/full/as-1020007tms50-eb 52/52
AS-10.20.7Page: 52
SERVICE INSTRUCTION
This page has been added to make double-sided printing easier.