argus manual
DESCRIPTION
manual argusTRANSCRIPT
-
TsRKF 656437.019 OM. 1
BORETS COMPANY LLC
BORETS RESEARH & DEVELOPMENT CENTER
VARIABLE SPEED DRIVE CONTROLLER "ARGUS"
OPERATING MANUAL
2013
-
TsRKF 656437.019 OM. 2
The following abbreviations are used throughout the document:
AR - Automatic restart
SCADA - Automated control system
LAU - Lightning arrester unit
Commissioning - Commissioning
LCD - Liquid crystal display
UL - Trip on underload
OL - Overload protection
UFCC
LLC -
Universal frequency converter controller
(Low level controller)
ARGUS - Variable speed drive controller
Tubing - Tubing
FC - Frequency converter
motor - Induction motor
PMM - Permanent magnet motor
AOM - Alarm operation mode
VSD - Variable speed drive
SCADA - Upper level system
DHG - Telemetry system
Step-up
transformer - Step-up transformer
ESP system - Electric submersible pump system
OGPD - Oil and Gas Production Department
ESP - Electric submersible pump
-
TsRKF 656437.019 OM. 3
1.1 Controller's functions
VSD and motor operation modes control and protection functions are carried out by the software
of the variable speed drive ARGUS controller (ARGUS).
ARGUS controller is the upper level controller, it sets operation modes, carries out certain
protection functions, and provides interface with operator, LLC controller, integrated auxiliary equipment
and external automated control system (SCADA).
Detailed list of parameters, commands and settings, the structure of on-screen menu of the
ARGUS controller are described in Sections 2, 3, 4.
1.1.1 Motor operation control functions:
Controller provides:
- operation with induction and permanent magnet motor;
- motor switching on and tripping in manual control mode by the
operator or in automated control mode (including, using the program with preset motor
operation / shutdown time intervals);
- remote motor switching on and tripping on SCADA command;
- automated and manual control of motor speed using the ARGUS
keypad without tripping the VSD and remote control on SCADA commands;
- operation using the program with individually preset motor operation
and shutdown time intervals;
- automatic motor switching on with adjustable delay time when voltage
is supplied or when voltage is recovered in accordance with the standard;
- smooth acceleration and braking of motor with the set rate;
- acceleration with omission of resonant frequencies when changing
ESP system frequency (operation with the set minimum frequency and frequency hopping
bandwidth);
- changing of the motor rotation direction (reversal), also without VSD
tripping by smooth deceleration to zero and smooth acceleration up to the set frequency;
- motor braking with backspin with its further startup for direct rotation
(backspin picking up mode);
- automatic frequency shift at the output depending on the analog input
signal;
- automated maintaining of the set motor current value by changing the
output frequency with possibility of motor current control;
- automated current optimization when reaching the set frequency
(selection of optimum voltage after ESP system has reached the steady state mode);
- automated system unlocking mode using jogging mode ("heavy" and
reverse startup);
- system running up mode with heavy motor startup using jogging mode
with the set "jogging" frequency;
- "stirring" mode (to prevent depositions on pump stages);
1.1.2 Protective functions
1.1.2.1 motor tripping with automatic restarting (AR):
-
TsRKF 656437.019 OM. 4
- when underloading in-phase current component of any phase with
selection of the minimum phase current;
- when overloading any phase with selection of the maximum phase
current in accordance with the adjustable time-current characteristic via separate selection of the
desired current settings and overload time;
- when supply voltage is above or below the set values;
- when the selected motor current imbalance setting is exceeded;
- when the selected voltage imbalance setting is exceeded;
1.1.2.2 When variable speed drive is provided with surface telemetry units of the sensor system,
the controller shall support motor tripping with AR:
- on DHG signal indicating that the set motor temperature value is
exceeded;
- on DHG signal indicating that pump intake pressure is above or below
the set value;
- on DHG signal indicating that motor vibration acceleration is above
the set level;
- when communication with DHG is lost.
1.1.2.3 motor tripping and startup locking:
- in case of unauthorized access to the power box of the cabinet;
- on EXTERNAL LOCKING signal;
- on signal from contact pressure gauge;
- on reduction of insulation resistance of the Step-up transformercable
motor circuit below the set value (recommended 30 kOhm).
Note. ESP system may be allowed to operate with insulation resistance reduction below the
setting, provided that the response speed of the current overload protection trip is automatically increased.
1.1.2.4 motor startup locking:
- in case of voltage recovery with incorrect phase sequence;
- in case of backspinning with selection of the frequency exceeding the
allowable value.
1.1.2.5 Each protection is provided with:
- selection of active (ON) and inactive (OFF ) condition;
- adjustable delay time of protection activation after its operation;
- adjustable delay time for protection activation (except for low
insulation resistance protection, door opening protection);
- separately adjustable delay time for tripping immediately after startup
(except for low insulation resistance protection, door opening protection);
- selection of protection mode (except for protections for maximum
current load, low insulation resistance, contact pressure gauge) with restart (AR), and AR
locking or without AR;
1.1.2.6 AR function is provided with:
- selection of active (ON, LOCKED) and inactive (OFF ) condition;
- adjustable AR delay time;
- selection of restarts number;
- interlocking of AR when the set number of allowed restarts is
exceeded;
- manual unlocking of VSD tripping.
-
TsRKF 656437.019 OM. 5
1.1.2.7 Prevention of operation modes switching, protections switching on / off and changing of
settings without entering password.
1.1.3 Monitoring and information functions
1.1.3.1 Monitoring and display of current values of parameters and characteristics on ARGUS
display:
- supply voltages of three phases and their imbalance;
- currents of three motor phases and their imbalance;
- motor rotation speed;
- insulation resistance of the Step-up transformer submersible cable
motor circuit;
- heat sink temperature;
- phase sequence at the VSD input;
- phase sequence at the VSD output;
- current value of the power factor (cos );
- current value of actual motor load in per cent of active current rated
value;
- motor condition (on - off) using DHG;
- condition of the VSD with indication of the reason for this condition,
uptime from the moment of the last startup in hours and minutes or time remaining to the
startup in minutes and seconds, when operating in the automated control mode;
- operation of specific protections;
- opening of the power box doors (in case of unauthorized access);
- current date and time.
1.1.3.2 Monitoring and display of the preset and the current values of parameters on ARGUS
display in VSD, equipped with surface DHG units:
- motor winding temperature;
- formation temperature;
- pressure at the pump intake and discharge;
- motor vibration level at the axes and Y.
1.1.3.3 Monitoring and display on electric meter display and ARGUS display in VSD, provided
with electric meter:
- active energy in conducting direction with accrued total;
- reactive energy with accrued total;
- total energy in conducting direction with accrued total;
- instantaneous values:
linear voltage,
active power (total and of each phase),
reactive power (total and of each phase),
apparent power (total and of each phase),
power factor (total and of each phase),
Unified Power Quality Index;
- current time and current date (on electric meter display);
- daily and monthly maximum power;
- event log with daily (00-00 to 24-00) recording of power consumption
(active and apparent power) and uptime per day, registered by VSD controller and transmission
to the upper level.
-
TsRKF 656437.019 OM. 6
1.1.3.4 VSD controller provides display and chronological recording of 50000 last changes of
ESP system condition. In real time with adjustable time interval a recording is made in a memory unit,
containing information on motor switching on and tripping reasons:
- total ESP system run life;
- total number of ESP system starts;
- current date and time;
- parameter, which value entered the zone that triggered a protection
function;
- power up and power off time;
- current values of supply voltage;
- current values of motor current;
- current load values;
- current power factor values;
- pump system parameters (if sensor system is used);
- date and time, when setting was changes, number of the changed
setting, old and new value of changed setting.
Set operation parameters and accumulated information are stored, when no power is supplied.
1.1.3.5 Real time clock operate autonomously, when no external power supply source is
available, during 360 days, clock adjustment is provided, including remote adjustment using SCADA
command.
1.1.4 Information reading and transmission functions
- transmission of the set operation parameters, current and accumulated
information into the SCADA system using the RS-485 interface;
- transmission of accumulated information to PC via -port using
the RS-232 interface;
- transmission of accumulated information to the USB reader device, the
information can further be converted on PC into Microsoft Office Excel format using a USB
port.
1.1.5 Process parameters settings
- well number;
- well pad number;
- oil and gas field (OGF) number;
- ESP system running depth, m;
- Step-up transformer voltage, V;
- recording step, min;
- rotation speed measurement unit;
- current consumption of DHG, mA;
- VSD type;
- motor type;
- ESP system capacity, m3/day;
- ESP system head, m;
- DHG type;
- number, type, manufacturer, date of manufacture of ARGUS;
- number, type, manufacturer, date of manufacture of VSD;
-
TsRKF 656437.019 OM. 7
- feeder number.
1.1.6 Functions of intelligent control system
1.1.6.1 Automated startup of ESP system in accordance with the pre-set program, including
"sparing commissioning" with minimum possible pump flow rate, sufficient to cool the motor.
1.1.6.2 Mode for surveying / scanning of well inflow the mode for determining the maximum
possible well production rate at the current moment of time and adjustment of the ESP system for the
maximum production rate.
1.1.6.3 Efficient power consumption (automated optimization of power consumption) in all
operation modes.
1.1.6.4 Avoiding emergency operation modes of ESP system.
1.1.6.5 Pump operation on the boundary of pump underload (prevention of tripping due to pump
underload in terms of head, pump underload in terms of gas etc.);
1.1.6.6 Cyclic operation mode of the ESP system.
Automatic switching over from cyclic operation mode into continuous operation mode, provided that the
appropriate conditions for continuous operation mode are available.
2 Controller
2.1 General provisions
Variable speed drive controller (ARGUS) provides:
- implementation of various motor control algorithms;
- browsing of current values of operating parameters of motor and VSD;
- reprogramming of ARGUS and LLC without VSD tripping;
- reading of ESP system operation history.
In terms of design, ARGUS is a complete system, front panel of operator's interface is installed
on the VSD front door.
All information required for operator is shown on LCD display on the front panel in text format.
Data entry is carried out with keypad using menus.
ARGUS software allows using several types of menu, both those already used in serial VSD
manufactured by BORETS COMPANY, and other menus, made to specific customer's requirements.
ARGUS controller is used as standard. Other controller modifications may be manufactured,
provided that the software continuity is preserved. ARGUS controller description is provided in TsRKF
... Description of its front panel is given below.
-
TsRKF 656437.019 OM. 8
2.2 Front panel of ARGUS controller
Front panel of ARGUS controller is shown in Figure 1.
Figure 1 Front panel of ARGUS controller
The ARGUS controller front panel is provided with:
- four line liquid crystal display, 20 characters in each line, which displays information in text
format;
- ten digital buttons of membrane keypad ("0" "9");
- four keypad control buttons "ENTER", "CANCEL", "ALT", "HELP";
- LED display "ALT";
- two VSD control buttons "START", "STOP";
- LED indicator "PREHEATING";
- 15 pin connector "PORT", with two interfaces connected to it: RS232 and USB to connect with
SCADA system and reading of accumulated information from the controller.
-
TsRKF 656437.019 OM. 9
3 ARGUS controller menu Controller menu provides established operator's access to viewing equipment condition, setting
system operating modes, protection parameters. ARGUS software supports various types of menu,
meeting the specific requirements of the customers and allowing it use in serial VSD manufactured by
BORETS COMPANY.
All the messages related to ESP system operation are shown on LCD display in text format.
Information is displayed in 4 lines, hereinafter referred to as "window". All operations on data entry into
controller are carried out using its keypad.
Controller menu provides access to the parameters via multilevel structure of subfolders (as in
controller "Borets PMM"). Menu contains 15 items at the 1-st level, which may have nested menus of
the 2-nd, 3-rd and 4-th level. Menu structure is given in Table 3.1. The complete list of menu parameters
is given in Table 1 A (see Appendix A).
The columns of each of the tables of the list provides the following information:
- the list of parameters having the same designations, as they are shown on LCD display,
- parameter appearance (parameter, setting, command)
- measurement unit,
- explanation of abbreviations and brief description of the parameter,
- range of possible values,
- factory setting of the parameter's value,
- reference to a more detailed description of the parameter.
The "Reference" column of each of the table of the list provides reference to the comment clause
in Section 8 "Description of the displayed parameters and system operation modes"
The complete list of parameters, commands and settings, used in operation with submersible
system, there are parameters, applicable only for specific configuration and execution of the equipment,
depending on the type of VSD, LLC, motor, auxiliary equipment. Menu is made in a way that, when
entering specific equipment configuration, display shows the parameters, applicable only to the selected
configuration.
3.1 Controller menu
3.1.1 Menu structure
Menu structure is given in Table 3.1.
Table 3.1
Name of subfolders
Reference to
the parameters
list 9
Current parameters 9
Settings 9.1
Settings I 9.1.1
Settings U 9.1.2
Other settings 9.1.3
DHG settings 9.1.4
Analog inputs settings 9.1.5
REG settings 9.1.6
-
TsRKF 656437.019 OM. 10
External devices 9.2
Settings 9.3
Measurement units 0
Date and time 9.5
Configuration of VSD 0
Settings of motor 0
Settings of SS 0
VSD technical data sheet 0
DHG technical data sheet 0
SDHG 0
SurfDHG 0
DHG configuration 0
Commands 9.7
Change password 9.7.1
Calibration 9.8
SCADA 9.9
Language 0
LCD 0
Electric meter 9.12
Readings 0
Current day 0
Previous day 9.12.1.2
Current month 9.12.1.3
Previous month 9.12.1.4
Current year 9.12.1.5
Previous year 9.12.1.6
Total 9.12.1.7
Quadrants 0
Current day 0
Previous day 0
Current month 0
Previous month 0
Current year 0
Previous year 0
Total 0
Settings 9.12.3
Information 0
Parameters 9.12.5
Basic 0
Power 0
Other 0
Commissioning parameters 9.13
-
TsRKF 656437.019 OM. 11
Intelligence 9.14
Parameters 0
Commissioning Error!
Reference
source not
found.
Optimization 9.14.3
Gas lock 0
Pulses 0
Working submergence 0
Deposits Error!
Reference
source not
found.
Intelligence 0
Service 9.15
Variable speed drive 0
Settings 9.15.1.1
Coefficients 0
Analog inputs 0
Condition 9.15.1.2
Parameters 9.15.1.3
Motor 0
LL controller 0
Parameters 0
Condition 0
Autonomous operation 0
aut.op,min 0
DHG 0
Adjustment settings 0
Condition 0
Parameters 0
RS DHG 0
USB stick 9.16
Read history 0
ARGUS programming 0
FCC programming 0
Accept settings 0
-
TsRKF 656437.019 OM. 12
3.1.2 Buttons function in the menu
3.1.2.1 Buttons functions are changed depending on the type of operations with the menu. There
are four types of operations with the menu:
- viewing of lists of parameters, settings and system operation history;
- editing of settings;
- performance of commands from submenu "Commands";
- calibration of the insulation resistance measurement channel.
Buttons functions depending on the type of operations are given in Table 2.
Table 2
Button
Operation type
Viewing Editing Execution of
commands Calibration
09 Digit entry
Cursor movement
one line up
- Changing of parameters values.
- Changing of the current symbol to the
next value
Cursor movement
one line up
Cursor movement
one line down
Cursor movement
one line down
Moving to the
next window
Moving one character
to the right
Moving to the
next window
Moving to the
previous window
Moving one character
to the left
Moving to the
previous window
ENTER
Moving to the
next menu level
Exit from editing,
saving the entered
value
Execution of
command
Moving to the
next calibration
step
CANCEL
Moving to the
previous menu
level
Exit from editing,
without saving the
entered value
Moving to the
previous menu
level
Calibration exit
without saving
the results
Alt
Switching from the
digit entry mode to the
arrows navigation
mode
Help
Display of
parameter
reference
information for 2
seconds
Moving one character
to the left
START MOTOR STARTUP (if no wafer type switch is available)
STOP MOTOR SHUTDOWN (if no wafer type switch is available)
3.1.2.2 In "viewing" mode operator can view elements lists in menu windows. Use ENTER
button to switching from the last level viewing mode to editing of parameters and settings
3.1.2.3 Editing mode allows changing settings values within the given ranges. Switching to
editing mode is possible only after password entry, if the password was not cancelled. To cancel the
password, change the password to 0000. If the value of the entered setting is beyond the possible range,
then, while still in editing mode, operator is suggested possible limiting values.
-
TsRKF 656437.019 OM. 13
3.1.3 Entry into the 1 type menu
3.1.3.1 When powering the controller, its booting is started (it takes about 2 minutes), after that,
the main window is displayed on LCD.
The first three line of the main window display the parameters:
- "No., rpm" rotation speed;
- "I PMM, A" motor current;
- "R,kOhm" insulation resistance;
- the fourth line is the status bar.
Status bar displays current date and time or current condition (reason for drive start failure, if
yellow lamp is constantly on).
The main window is different from other menu windows, since it has additional indications on
the right side of the window.
Additional indications area may display the following information symbols.
3.1.3.2 Line "No., rpm" may display the following symbols: "", "", "~", "^".
Symbol "", "" indicates that the Step-up transformer voltage is not optimum. If the voltage is
higher, variable speed drive is running at the increased frequency converter current; if lower variable
speed drive can not reach the required rotation speed, due to undervoltage.
Symbol "~" indicates that variable speed drive is operating in motor acceleration or deceleration
mode.
Symbol "^" indicates that motor is running at increased speed to remove gas locks.
3.1.3.3 Line "IPMM, A" may display symbol "", which indicates undercurrent. This happens:
- when Step-up transformer transformer stage voltage is set high above the required value,
- when incorrectly selected configuration of the drive engineering package is lacking power for
the variable speed drive provide the required rotation speed of motor.
3.1.3.4 Line "R, kOhm" may display symbol "", appearance of which shows that insulation
resistance is below the set value.
3.1.3.5 The lower line may show the following symbols:
- "DHG" indicating that the variable speed drive operates with the telemetry system;
- "DOOR" indicating that the VSD door is open;
- "MAN","AUT","PRG" indicates VSD operation mode;
- "REL" indicates that independent automatic circuit breaker QF5 release has operated;
- ">>>" or "" indicates that the VSD is in standby mode for automatic startup;
- " ", " " or " !! " accordingly indicate that decrease of the rotation speed or sudden
decrease of the dynamic level of the formation fluid in the well in auto adaptation mode.
3.1.3.6 The list of the current parameters may be viewed in the main window.
3.1.3.7 Moving from the current parameters window to other menu windows is carried out by
pressing the "ENTER" button.
3.1.3.8 LCD displays only the information applicable to the selected equipment.
-
TsRKF 656437.019 OM. 14
4.1 Preparing VSD for switching on
- enter ESP system equipment parameters into ARGUS in accordance with Table 4.1. If required, check the compliance of the existing settings with the factory settings or enter "Restore factory settings"
command.
Table 4.1. Equipment parameters, entered in ARGUS
Parameter name Navigation in menu
Menu appearance Service | VSD | Settings | Menu appearance
Restore factory settings Commands |
Unlocking Commands |
Nominal mains voltage, V Service | VSD | Settings | U mains|
Field number Settings | Field No. |
Well pad number Settings | Well pad No. |
Well number Settings | Well No. |
Nominal pump capacity DEP configuration | ESP|
Pump head, m; DEP configuration | Head|
Installation depth, m Settings | Lrunning|
Cable cross section, mm Settings | Cross section mm2 |
VSD type DEP configuration | VSD type |
Operating mode Settings | Other settings | Mode |
Input filter Service | VSD | Settings | Inp. filter |
Rotary switch Service | VSD | Settings | Rotary switch|
motor type DEP configuration | motor type |
motor nominal power, kW DEP configuration | Pnom.| |
motor nominal current, A DEP configuration | Inom. |
motor nominal voltage, V DEP configuration | Unom. |
motor idle current, A, DEP configuration | Ixx|
Nominal power factor of motor DEP configuration | motor settings| COSnom. |
motor rotation speed Settings | Other settings | No. rpm |
motor rotation direction Settings | Other settings | Rotation dir.|
Step-up transformer nominal power, kVA Settings | nom. Step-up transformer, kVA|
Primary voltage of Step-up transformer
transformer, V
Settings | Uprim.trans.,V |
Voltage of Step-up transformer secondary
winding tap, V1)
Settings | Usec.trans.,V |
Total voltage of motor and cable (Umotor +
Ucab.)
DEP configuration | motor settings| Umotor + Ucab. |
- Procedure for calculation of the secondary winding tap of the Step-up transformer transformer
is described in Appendix B.
-
TsRKF 656437.019 OM. 15
-
TsRKF 656437.019 OM. 16
4.2 Description of the displayed parameters and operation modes of the system
Detailed description of the parameters and operation modes of the submersible system, displayed
on the LCD of the ARGUS controller.
8.1 VSD equipment configuration
ARGUS software is designed for controller operation with various types of VSD, LLC and
motor.
During manufacturing or service maintenance of VSD, settings and technical data sheet
information is entered into its memory:
- type, manufacturer (manufacturer's code), serial number, date of manufacture of VSD; - type, manufacturer, serial number, date of manufacture of ARGUS; - type, manufacturer, serial number, date of manufacture of LLC;
Software data: version, LLC firmware installation date and version, generation date, date of
ARGUS "protection" firmware installation in the appropriate software, this information is shown on
display as parameters.
When preparing the system for start, settings applicable to the specific configuration of the
equipment is entered into ARGUS and LLC.
8.1.1 VSD type is selected from the list:
Borets VD80 Borets VD500 Borets VD105
Borets VD40 Borets VD160 Borets15-400
Borets VD250 Borets VD300
Borets VD50
8.1.2 LLC type is selected from the list:
- Direct start - FC FCC controller or UFCC - Drivers controller - Rockwell - Smooth start
8.1.3 motor type is selected from the list, which is determined by the selected VSD:
Borets VD40 Borets VD50 Borets VD80 Borets VD250
1VEDBT-117 1VEDBT-117 1VEDBT-117 1VEDBT-117
2VEDBT-117 2VEDBT-117 2VEDBT-117 2VEDBT-117
11VEDBT-103
11VEDBT-103
11VEDBT-103
2VEDBT-117
11VEDBT-130
11VEDBT-130
11VEDBT-130
11VEDBT-103
PVEDN-1170 PVEDN-1170 PVEDN-1170 11VEDBT-130
5VEDBT-117 5VEDBT-117 5VEDBT-117 PVEDN-1170
12VEDBT-117
12VEDBT-117
12VEDBT-117
5VEDBT-117
-
TsRKF 656437.019 OM. 17
12VEDBT-117
Borets VD105 Borets VD160 Borets VD300 Borets VD500
1VEDBT-117 1VEDBT-117 1VEDBT-117 1VEDBT-117
2VEDBT-117 2VEDBT-117 2VEDBT-117 2VEDBT-117
11VEDBT-103
11VEDBT-103
11VEDBT-103
11VEDBT-103
11VEDBT-130
11VEDBT-130
11VEDBT-130
11VEDBT-130
PVEDN-117 PVEDN-117 PVEDN-117 PVEDN-1170
5VEDBT-117 5VEDBT-117 5VEDBT-117 5VEDBT-117
12VEDBT-117
12VEDBT-117
12VEDBT-117
12VEDBT-117
Borets15-400
motor
The following motor technical data sheet settings are entered while preparing for startup:
- type; - nominal power, nominal power factor (for induction motor only); - nominal current, nominal voltage, idle current.
8.1.4 DHG type is selected from the list:
DHG - none DHG SKAD DHG Elekton-3
DHG SPT-2 DHG BST5 DHG TT37
DHG SPT-1 DHG SPT1_25
DHG Elekton DHG ViewPoint
DHG BST1 DHG Novomet
DHG Weatherford DHG IR-2
Name plate data about manufacturer, date of manufacture, serial numbers of surface and
submersible parts of DHG, sensors configurations, and technical data and data on design features and
version of "protection" software in DHG software, these data may be shown on the display as parameters
in accordance with the selected DHG type. These data are given in sufficient detail in the menu tables
(see Appendix A and B).
8.2 Mains parameters
Description of parameters and related settings is given below
8.2.1 Input voltage.
Current value of the input voltage is changed in UFCC, transmitted via internal interface into
ARGUS and shown on display as an average three phase linear voltage value Umains
=(Uab+Ubc+Uac)/3.
Mains voltage and frequency are selectable.
-
TsRKF 656437.019 OM. 18
UFCC contains the parameters, and the following protection settings are entered to provide
operation of protection functions depending on the mains voltage:
- selection of the mains voltage and frequency 380 V /50 Hz or 480 V /60 Hz - hardware protection on exceeding the maximum linear voltage
Umains max=542 V,
- protection on exceeding the threshold 25% from the nominal value, - protection on reduction by more than 25% from the nominal value, - protection with variable threshold within 15% from the nominal.
The following can also be entered:
- protection operation mode, - delay time of switching on / tripping of the VSD after operation of protection, after startup or in
case of alternative automatic restarting after power loss,
- compensation factors of the measured voltage, (in UFCC correction is not provided, since precision is ensured by hardware).
8.2.2 Input voltage imbalance.
The following are entered as settings:
- threshold value of imbalance in % from the nominal voltage, - operation mode of protection on exceeding the threshold, - switching on / tripping time after operation of protection.
8.2.3 Phase sequence of mains voltage
Monitoring of phase sequence is carried out in ARGUS using the signals from the phase
sequence indication unit PSIU. Information about this parameter is relevant for VSD with smooth starter,
during startup after maintenance and repair work
8.2.4 Power consumption
VSD versions, equipped with standard electric meters, all the mains parameters, including:
- active power consumption, - power consumption, - power factor
are transmitted from the meter to the ARGUS using internal interface RS485
Meter type is selected from the list:
SET Merkuriy Energomera
8.3 VSD output voltage
Current value of the output voltage is measured in UFCC and shown on the display.
8.3.1 Procedure for VSD output voltage generation
The procedure is selected in ARGUS menu, depending on the selected types of motor, VSD and
LLC, from the following:
- "6 step" commutation producing trapezoidal form of output voltage. The procedure is implemented in PMM VSD with UFCC. Adjustment of output voltage to control permanent magnet motor is
carried out by PWM converter under control of UFCC in accordance with the voltage in DC buses or output
current (depending on the setting or by automatic selection).
- "Sine" and "Sine+" modulation of output voltage. The procedure is implemented in PMM VSD with UFCC. Adjustment of output voltage to control induction motor is carried out by PWM converter the
-
TsRKF 656437.019 OM. 19
same as in 6-clock commutation. Software used for this procedure carries out continuous harmonic analysis
of the output current (1, 5 and 7 harmonics), which is used to calculate motor consumption parameters.
- "Sine PWM" modulation of output voltage. Implemented in PWM VSD with UFCC with built in output filter (VSD Borets-15-400). Adjustment of induction motor speed is carried out using output voltage
or current.
8.3.2 Current value of the output linear voltage
8.3.2.1 In PMM VSD with UFCC with "6 step" commutation is calculated using the formula:
Uuv=Uvw=Uwu=Udc*0.74,
where: - Udc average voltage in the VSD direct current bus for the period,
- 0.74 factor of the form of the linear output voltage.
8.3.2.2 With "Sine" and "Sine+" commutation, the DC bus voltage is measured. Using the value
measured during the period in 128 points, and the known PWM modulation factor, output voltage is
calculated for the given point.
8.3.2.3 With "Sine PWM" modulation, output voltage is calculated using the DC bus voltage
with frequency of 45-50 kHz with account of the current PWM conversion factor.
8.3.3 Output voltage protection settings:
- linear output voltages Uuv,Uvw,Uwu; - hardware protection on exceeding voltage in DC buses Umax.dc=765 V, is implemented in
UFCC.
8.3.4 Output voltage imbalance
The menu has the following settings
- Selection of the operation mode for the output voltage imbalance protection, - output voltage imbalance protection threshold in % from the nominal value, - tripping and AR delay time in case of output voltage imbalance.
8.4 Output current
Current value of the VSD output current is measured in UFCC and shown on the display.
Output current is measured using the signals from the current sensors, installed on the direct
current bus and output buses.
8.4.1 Current value of the output current
8.4.1.1 In PMM VSD with UFCC with "6 clock" commutation is calculated using the formula:
Iu=Iv=Iw=Idc*0.816,
where: Idc current amplitude in the direct current loop, averaged for the commutation time of the
measured current,
0.816 factor of the output current form.
8.4.1.2 With "Sine" and "Sine+" commutation, the current value of the output current is
calculated using the formula:
Iout=Iu (v,w)=SUM(In2/N)
where: In instantaneous current,
N=256 number of measurements per period.
8.4.1.3 With "Sine PWM" modulation, the calculations are made using the formula in 0, with
measurement rate of instantaneous output current of 45-50 kHz.
8.4.2 Output current protection settings
-
TsRKF 656437.019 OM. 20
- Hardware protection from exceeding the maximum allowed value of output phase current. Protection operates with Imax =(1,2 - 1,7) I nom, depending on VSD power.
8.5 VSD output power
VSD output power is calculated using the formula:
out = 3*Uuv (vw, wu)*Iu (v,w)
where: - Uuv (vw, wu) current value of the linear output voltage (8.3)
- Iu (v,w) current value of output current (8.4),
8.6 Step-up transformer parameters
Menu contains the settings, corresponding to the technical data sheet value of Step-up
transformer parameters:
- apparent nominal power of Step-up transformer. - Step-up transformer primary voltage,
and:
- Step-up transformer secondary winding tap voltage, which is calculated or selected from the table with account of the cable length and nominal parameters of motor: voltage, current, power (Appendix B)
8.7 Cable parameters
8.7.1 Cable insulation resistance
In the menu, the current parameters display the cable insulation resistance value Rins., which
can be measured by VSD using two methods: VSD hardware or DHG equipment.
8.7.2 Cable insulation resistance protection
Condition menu displays the following Rins. protection functions:
- reduction of Rins. down to minimum allowable value Rins. min=20-35 kOhm, - no calibration is carried out for the insulation resistance measurement channel in ARGUS, - failure of the current sensor Rins. in the submersible DHG unit.
8.8 motor parameters
8.8.1 motor phase current
The displayed motor phase current is calculated using the following formula:
Imot = Iout / avot
where: Iout- VSD output current,
avot = U2avot / U1avot multiplying transformation ratio of Step-up transformer.
where: U1avot, U2avot voltages of the primary and the secondary Step-up transformer
windings, correspondingly
With "Sine" and "Sine +" commutation, Imot calculation accounts for losses in Step-up
transformer and cable, which are calculated by the software on the basis of the corresponding technical
data sheet data.
Compensation factors settings for the measured voltage, (in UFCC correction is not provided,
since precision is ensured by hardware).
8.8.2 Motor current protection settings:
-
TsRKF 656437.019 OM. 21
The menu provides for two types of motor current protections, which cause equipment
breakdown: overload protection (OL) and underload protection (trip on underload UL). In case of motor
overload, motor current exceed the maximum nominal current, which causes overheating of winding. In
case of underload, motor current is below the nominal value, pump stops pumping the fluid, motor and
pump are not cooled, which may lead to motor overheating, burning of cable, motor seal failure.
The following settings are made for operation of the protection functions:
- selection of the protection operation mode in case of overload (underload); - motor current value, determining the protection threshold, in % from the nominal current; - tripping delay time at overload (underload); - tripping delay time at overload (underload) after startup; - AR delay time at overload (underload); - number of AR on OL and UL.
8.8.3 Motor currents imbalance
The following protection settings are available in the menu:
- motor current imbalance protection threshold in % from the nominal value, - selection of the operation mode for the motor current imbalance protection; - imbalance trip delay time; - imbalance trip delay time after startup; - AR delay time with motor current imbalance;
8.8.4 motor operation modes
Motor control in steady state mode implies maintenance of the set motor rotation speed No. rpm.
Current value No. rpm is displayed
The menu provides entry of the following rpm settings:
- rotation speed setting number of rpm in the steady state mode, - acceleration time time required for motor to reach the set values of steady state mode, - Initial acceleration speed speed setting for normal acceleration, which is the starting point for
reaching the steady state mode.
- rotation direction symbol on display indicates the current forward or inverse phase sequence of the output voltage, which may be changed.
8.8.5 motor load
Motor "Load" parameters is displayed in the current mode and is calculated using the following
formulae,
8.8.5.1 In permanent magnet motor cos is taken equal to 1 and
PMM load =(Imot / Imot.nom)*100 [%]
where: Imot.nom. motor nominal current is entered using the setting from the technical data sheet
(8.1.3),
Imot. current value of the motor phase current (8.8).
8.8.5.2 When controlling induction motor using "Sine" and "Sine +" procedures and "Sine
PWM" modulation, load is calculated using the formula:
motor load =(Imot* cos mot / Imot.nom* cos nom)*100 [%]
where: cos nom =0.98 for motor nominal current.
Imot with "Sine" and "Sine+", the current value is calculated with account of the 5th and the 7th
harmonics, cos mot is calculated using the 1-st harmonics.
-
TsRKF 656437.019 OM. 22
With "Sine PWM" modulation in PWM VSD with output filter, harmonic current components
are negligible and are not accounted for
8.8.5.3 In idle mode, load is determined as:
Load min=(1.3*I*0.35/ Imot.nom)*100 [%]
where: I motor idle current,
1.3 factor, accounting for minimum mechanical load on motor shaft,
0.35 cos with minimum mechanical load on motor shaft,
8.9 Energy consumption parameters with load applied
The following parameters are displayed:
act.cons.=3*Iout*Uout*cos active power consumption,
Fp= Imot 1 / Imot power factor,
cons.=act.cons.* consumed active energy.
where: out vsd
Table 8.1 contains formulae for the implemented output voltage generation procedures
Table 8.1. Formulae for calculation of energy parameters of ESP system
Commutation method act.cons. Fp cons.
"6 step"
(PMM VSD, PMM
motor)
3*Iout*Uout
close to 1 act.cons.*
"Sine" and "Sine+" 3*Iout*Uout*cos Imot1 / Iout
"Sine PWM" cos
where: Iout,Uout see 8.3, 8.4,
Imot1 -1-st current harmonic,
8.10 DHG parameters
8.10.1 Information
The menu contains the following information:
- DHG condition: "DHG failure" - SDHG technical data sheet, containing the information about the submersible unit - SurfDHG technical data sheet, containing information about the surface unit - DHG configuration, displaying TSM sensors configuration
8.10.2 Current parameters
The menu displays the following current parameters of DHG operation:
- pressure at pump intake and discharge - vibration in three space axes - temperature at pump intake and discharge - motor winding temperature.
8.10.3 DHG protection settings
The following protection settings are entered in the menu:
- selection of the protection operation mode (on|off); - protection on maximum and minimum pressure at the pump intake - protection on motor maximum winding temperature
-
TsRKF 656437.019 OM. 23
- protection on minimum insulation resistance in the cable - delay time for tripping on operation of protection for allowable pressure, motor temperature,
vibration,
- delay time for AR on low pressure, motor winding temperature, allowable vibration.
8.11 Adjustment settings
Provisions are made for entry of settings, adjusting allowable changes of parameters when
controlling the production process:
- deviation of pressure from the set value - rpm increase, when adjusting rotation speed - time interval of adjustment - pressure change rate when performing pressure adjustment
8.12 SCADA settings
The following settings are made in the menu:
- SCADA type from the list, suggested in the menu: 1. No SCADA
2. SCADA Surgut NG N3
3. SCADA Region - 2000
4. GPRS modem
5. SCADA MODBUS2
6. SCADA MODBUS3
7. SCADA Lukoil-3S
- SCADA address in the telemetry system - data exchange rate 1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200 - switching on of recording in SCADA
8.13 Service settings
Service settings include the settings providing convenient operator's interface environment:
- setting of the display parameters input language, brightness, contrast, - selection of units for parameters display pressure, frequency, temperature - selection of the menu type, - calibration corrections
8.14 Additional inputs
When using additional analog inputs, the following settings are made in the menu:
- protections operation modes on signals from analog inputs, - delay time for protective trips and AR - maximum and minimum protection levels, - maximum and minimum physical signal levels for automatic setting of the appropriate
measurement range,
8.15 Operating technical data sheet
Technical data sheet data for the well pad, well, cable for identification of information, read
from ARGUS (see cl. 9)
8.16 VSD operation time counters
This group includes displayed information parameters indicating continuous operation of the
system: number of VSD trips on protection operation, number of starts, total operating time and idle time.
-
TsRKF 656437.019 OM. 24
8.17 Operating modes
The settings for the following operating modes are entered in the ARGUS menu: "Startup",
"Shutdown", "Acceleration and braking", "Jogging mode", "Startup with backspin", "Gas locks
removal", "Stirring", "Maintenance of one of the set parameters", "Intelligent mode".
8.17.1 Startup
Operator's actions to startup the system are allowed only after the VSD and the controllers have
reached the allowable temperature range (see cl.). The next step is selection of the menu type and entry
of the settings required for the startup and normal operation in manual, automatic or program mode.
Availability of settings depends on the selected equipment type.
8.17.1.1 The algorithm for PMM startup by PMM VSD with "6 step" commutation is as follows.
On STARTUP command, the PMM rotation condition diagnostics is carried out. If PMM is
rotating in the direction reverse to the set direction, with the speed, exceeding the allowable for startup
with backspin, it is prohibited to carry out the startup.
If PMM is at a standstill, which is indicated by static condition of comparator unit of UFCC,
which are used to determine the condition of PMM rotor rotation, voltage is generated at the VSD
output, which with the set rate creates rotating magnetic field in the PMM (six positions per period) and
the torque with the set current. PMM rotor is started from the initial position and accelerates to the set
rotation speed
If PMM did not start rotating during the time, set by the time current characteristic, which is
possible at increased load, then the current is automatically, in 3-4 stages, increased until PMM starts
rotating. Threshold value is limited with maximum current hardware protection, operation of which
disables the startup mode.
8.17.1.2 Induction motor startup algorithm with "Sine" and "Sine +" commutation is as follows.
Starting torque of motor with this commutation type (PMM VSD, UFCC) is set by the initial
voltage setting, which is changed by voltage / rotation speed ratio, and starting current. Current increase
is monitored and limited in the same way as it is done for VSD startup.
8.17.1.3 Induction motor startup algorithm with "Sine PWM" commutation is similar to that
described for "Sine" and "Sine+" with the difference that, total acceleration time and maximum jamming
time at the startup are set.
8.17.2 Jogging mode
Motor jogging startup mode (or "Unlock" mode for PMM) is used when the system is jammed.
In this mode the startup is carried out by programmed reversing of rotation direction with the set torque.
The following settings are made: jogging mode time, number of jogs, current protection values,
phase sequence, parameters, setting the maximum jog current values. With "Sine PWM" commutation,
the values of the prohibited frequency range are additionally entered.
8.17.3 Acceleration and braking
-
TsRKF 656437.019 OM. 25
To change the current rotation speed, operator enters new speed setting value and time for
reaching the new value. VSD uses the entered value to generate time distributed sequence of rotation
speed settings for LLC controller and monitors their observance.
8.17.4 Startup with backspin
Motor backspin may occur, when operating ESP system is tripped. Startup from the backspin
condition is carried out when reverse rotation speed is decreased to the set minimum. This condition may
arise either with complete draining of the fluid column above the pump or by braking motor backspin.
PMM and motor braking techniques are different.
PMM VSD when braking PMM, the energy generated by PMM is dissipated either in the
connected braking resistors unit (in PMM VSD for cavity pumps) or in submersible cable (in PMM VSD
for ESP pumps). The latter is implemented by short circuiting output phases of VSD using frequency
converter keys. Monitoring of the startup condition occurrence is carried out by rotation speed or output
current, accordingly. When startup conditions occurs, frequency and phase synchronization of the motor
rotation speeds and commutation of output phases is carried out, the startup mode is then switched on.
The settings specify the mode and the values of the rotation speed and startup current with backspin.
With motor backspin, no energy is produced, and braking is carried out in rotation speed pickup
mode with further switching over to the normal mode. The settings specify the mode and the values of
the startup rotation speed with backspin.
8.17.5 Gas locks removal
When enabling UL protection (trip on underload), motor rotation speed increases by the set
value and is maintained during the specified time. If during this time, UL condition persist, increased
rpm remain constant, until UL protection operates. If UL conditions no longer exist, rpm is reduced to
the initial value.
The following settings are made for the mode:
- Enabling of the mode, - rotation speed change value, - gas lock removal time
8.17.6 Shaking
"Shaking" mode is used to clean the motor from deposits by sudden decrease of its rotation
speed with further recovery of the rotation speed. The following settings are made for the mode:
- Enabling of the mode, - shaking intervals, - number of shakes, - two values of rotation speed change (can not exceed the value, specified by the setting) and the
appropriate rates of the change.
8.17.7 Maintenance of one of the parameters
In this mode, the setting allows selecting one of the parameters, which is used for automatic
control of:
-
TsRKF 656437.019 OM. 26
- rotation speed, - pump intake pressure, - motor current, - in intelligent control mode.
In rotation speed maintenance mode, automatic adjustment of output current and voltage of VSD
are carried out, the current value of which is measured by LLC.
In current maintenance mode, when it is increased or decreased due to load variations, motor
rpm are automatically, accordingly, decreased or increased until the current reaches the set value. When
this value is reached, motor returns to the reached speed. If rotation speed has reached the maximum,
specified by the setting, and the current did not increase to the setting value, UL protection is triggered.
Minimum rotation speed is set in pressure maintenance mode.
Intellectual control mode implies entry of the settings for factors for static and dynamic
parameter deviations during control, which are selected by operator or automatically per the specified
criteria: prevention of underload, head maintenance, optimum power consumption, allowable load on
motor etc. Changing of factors settings may be carried out without VSD tripping.
Maintenance of the selected parameter is interrupted when acceleration and braking mode is
enabled, or gas locks removal mode is required, until operation in these modes is completed.
8.18 Protection settings
The menu provides two types of protection operation modes settings: "On/Off" and
"Off/Lock/AR", where:
- Off protection disabled, - On" protection enabled, - AR protection enabled with restart of VSD specified number of times (from 1 to 5) after
protection operation,
- Lock interlocking of restart for protection functions, supporting AR mode. If protection is enabled, after its operation (with AR operation after the last startup) VSD
startup is interlocked and in order to restart it, "Unlocking" command need to be entered.
8.19 Commands
"Test" command, the command allows testing indicator lamps and fan operation. When it is
executed:
- the controller successively displays indication symbols, - fan is switched on, - green, red and yellow lamps are successively switched on on the door.
The test ends in a minute after it was started or by pressing the "Cancel" button.
8.20 Event log (history)
When this menu is selected, VSD operation events history may be viewed on the display.
History limits are marked by the words: "Beginning of the history", "End of the history".
8.21 USB stick
This menu allows selecting commands for the operations with the USB stick.
- Read history event log history is read.
-
TsRKF 656437.019 OM. 27
- ARGUS programming, FCC programming using USB stick are selected to install ARGUS or FCC firmware version, accordingly.
- Accept settings settings are read from the USB stick
8.22 Condition of equipment
Menu Condition of VSD, ARGUS, DHG contains the list of protections against electrical
parameters exceeding the allowable limits (including those caused by the equipment malfunction).
However, there are protections, which are related only to the units and elements, included in the VSD.
This clause provides description of these protections, shown on the display. Possible protections
operation reasons are provided.
8.22.1 "Ipwm sens. fail." failure of PWM current sensor. PWM modulation circuit is used to
change output voltage in PMM VSD. A current sensor is used in this circuit, readings of which are used
for adjustments. Protection operates when the sensor, its power circuits are faulty or sensor's signal path is
damaged.
8.22.2 "THYR protection" failure of thyristors of power rectifier, TCB board, TCB power
circuit. At that, if any thyristor module is not switched on when control command is sent, the appropriate
LED indicator lights up on the TCB board.
8.22.3 "SWB protection" failure of IGBT modules in the switchboard, PdRK driver board,
short circuit of the switchboard power circuit. In case of short circuit in the power circuit or overload on
PdRK board, the appropriate LED indicator lights up.
8.22.4 "I GND Protection" operates when the difference between the VSD output currents
exceeds 10% from the nominal current I nom. Protection operates in case of failure of any current sensors
in output circuits of VSD, their power circuits, ground fault of any of the VSD output phases.
8.22.5 "Overheat" protection operates, when the frequency converter heat sink temperature
exceeds 95 according to the measurements of at least one of the two temperature sensors installed on the
heat sink.
8.22.6 "Temp. sens. 1 failure", "Temp. sens. 2 failure" multiple failure of temperature
sensor 1 or 2, accordingly, of power circuits and signals paths of these sensors.
8.22.7 "H. brige failure" failure of IGBT module in switchboard or short circuit in the
switchboard power circuits. Registered, when "SWB protection" signal recurs (8.22.1)
8.22.8 "Choke failure" short circuit of choke coil in PWM circuit, choke inductance loss,
failure of UFCC board, Measuring resistors board in PMM VSD.
8.22.9 "Phase break" main voltage phase break. Main voltage is measured by UFCC
controller.
8.22.10 "No protocol" no record of VSD parameters measurement is kept. Appears in case of
record ROM failure in UFCC.
8.22.11 "Comp. conf.error" FCC comparator unit condition failure. Appears during
automatic testing of VSD before startup due to UFCC failure or when mains voltage range is exceeded.
8.22.12 "motor conn. err." the output current value at VSD startup is not increased,
approaches zero in the current parameters of current value. It means that load (motor) is not connected.
8.22.13 "Rins. sens. failure" failure of insulation resistance measurement channel.
Determined in VSD, if insulation resistance between any of the output phases and cable sheath is below
the acceptable value (35 kOhm).
-
TsRKF 656437.019 OM. 28
8.22.14 "Rins. cal. fail." VSD insulation resistance measurement channel was not calibrated.
8.22.15 "Dig. FCC failure" failure of digital analog section of FCC controllers. Occurs when
UFCC board is faulty, when digital devices on the board do not respond when they are addressed via
internal I2C interface.
8.22.16 "Analog FCC failure" failure of analog paths for normalization and conversion in
UFCC board.
8.22.17 "I2Cpot failure" no communication via I2C line in UFCC board with any of the
integrated circuits of digital potentiometers.
8.22.18 "FCC fault" restarting of FCC processors with 40 seconds interval, without
determining its cause.
8.22.19 "FC RS timeout" timeout on exchange line LLC and ARGUS longer than 8 minutes
(PMM VSD and longer than 15 min in series 15 VSD)
8.22.20 "LLC failure" fault in exchange between ARGUS and LLC in series 15 VSD.
8.22.21 "Rect. RS failure" fault in exchange between ARGUS and SCADA.
8.22.22 "WAFF failure" failure of VSD operation modes waffer type switch on the front
door.
8.22.23 "LCD failure" failure of ARGUS liquid crystal display. Occurs when connection with
the LCD driver is lost.
-
TsRKF 656437.019 OM. 29
9 Menu parameters list Table 9.1 contains the menu parameters list. Parameters format in column Menu item short name corresponds to that of LCD display; the number
of symbols preceding the name stands for the number of jumps to the next menu level (from 1 to 4) before opening the list of parameters, settings and
commands; symbol * is related to the protection setting with an option to select an operation mode (Off/Interlock/AR), and the settings given below in
the list (up to the next asterisk) enable setting of the protection.
Table 9.1.
Menu item short name Parameter Measure
ment unit Menu item full name
Minimum
value
Maximum
value
Factory
setting Reference
9 0
Speed Parameter Rpm/H
z motor rotation speed 0 65535 0
Nturb.,rpm Parameter rpm motor backspin speed 0 3500 0
Rins.,kOhm Parameter kOhm Insulation resistance 0 65535 9999
Imotor, Parameter A motor current 0 150 0
Date Parameter Current date 01.01.2001 01.01.2001 01.01.2001
U in,V Parameter V Linear network voltage 0 480 380
Mode end time, min Parameter min Mode end time 0 65535 0
Number of starts Parameter Number of starts 0 65535 0
Load, % Parameter % motor load 0 65535 0
P,kW Parameter kW Power consumption 0 65535 0 8.2.4
motor run life, h Parameter h motor run life 0 65535 0
W,MW`h Parameter MWh Power consumption 0 65535 0
Software version Parameter ARGUS software version 1 99,99 1407
Ainp.1 Parameter V Analog input 1 voltage 0 10 0
Ainp.2 Parameter V Analog input 2 voltage 0 10 0
I imbal., % Parameter % Current imbalance 0 100 0
Uin. imbal., % Parameter % Network voltage imbalance 0 100 0
-
TsRKF 656437.019 OM. 30
Uout. imbal., % Parameter % Output voltage imbalance 0 100 0
UL number Parameter Number of UL shutdown time intervals 0 65535 0
OL number Parameter Number of OL shutdown time intervals 0 65535 0
Misc. protections number Parameter Number of miscellaneous protections shutdown time
intervals 0 65535 0
Startup run life, min Parameter min motor run life after the last startup 0 600000 0
VSD run life, h Parameter h motor idle time 0 65535 0
Ileak,mA Parameter mA Current leakage 0 99,999 0
SS version Parameter SS version 0 65535 0
ESP, m3/day Parameter m
3/day ESP system capacity 0 65535 0
os Parameter os 0 0.999 0.98
Pi,atm Parameter atm Pump intake pressure 0 1000 0
Pd.,atm Parameter atm Pump discharge pressure 0 999.99 0
Tm,C Parameter C motor temperature -300 300 0
Td, Parameter Pump discharge fluid temperature -32768 32768 0
oil, Parameter Oil temperature -80 32000 0
Ti, Parameter Pump intake fluid temperature -80 300 0
Vibr. X,g Parameter g Vibration along axis X 0 99.99 0
Vibr. XY,g Parameter g Root-mean-square vibration along axes X and Y 0 99.99 0
Vibr. Y,g Parameter g Vibration along axis Y 0 99.99 0
Vibr. Z,g Parameter g Vibration along axis Z 0 99.99 0
Phase seq. Parameter Phase sequence /
9.1 1
9.1.1 1.1
*OL Setting motor overload protection Off/Interlock/AR AR
I OL, A Setting motor overload current 0 9999
OL dl.t.trip,s Setting A motor overload delay time for tripping 0 120 20
AR dl.t. OL, min Setting s motor overload AR delay time 0 3000 5
OL AR number Setting min Number of OL AR 1 3000 5
*UL Setting motor underloading protection switching on Off/Interlock/AR Off
I UL, A Setting motor underloading motor current 0 9999
-
TsRKF 656437.019 OM. 31
UL dl.t.trip,s Setting A motor underloading delay time for tripping 0 600 40
AR dl.t. UL, min Setting s motor underloading AR delay time 0 3000 60
UL AR number Setting min Number of UL AR 1 21 3
*I imbal.pr. Setting Current imbalance protection Off/Interlock/AR AR
I imbal.,% Setting Current imbalance 0 25 25
I imbal.dl.t.trip, s Setting s Current imbalance delay time for tripping 0 60 5
I imbal.AR dl.t., min Setting min Current imbalance AR delay time 0 300 5
I imbal.dl.t., s Setting s
Current imbalance delay time for tripping after
motor start 0 3600 15
OL dl.t., s Setting s Overload delay time for tripping after motor start 0 3600 5
UL dl.t., s Setting s
Underloading delay time for tripping after motor
start 0 3600 5
*GasLck removal Setting Gas locks removal mode Off/On Off
dNgas,rpm Setting rpm motor rotation speed change value 50 500 100
Ngas dl.t.,s Setting s motor high rotation speed keeping delay time 1 600 5
9.1.2 1.2
Umax dl.t.,s Setting s Umax protection delay time for tripping after start 0 3600 5
*Umin prot. Setting Protection switching on at low network voltage Off/Interlock/AR AR
Umin,% Setting % Minimum network voltage 0 100 75
Umin dl.t.trip,s Setting s Umin protection delay time for tripping 0 60 5
*Umax prot. Setting Protection switching on at high network voltage Off/Interlock/AR AR
Umax, % Setting % Maximum network voltage 100 125 110
Umax dl.t.trip,s Setting s Umax protection delay time for tripping 0 60 5
*Uinp. imbal. prot. Setting Network voltage imbalance protection Off/Interlock/AR AR
Uinp. imbal., % Setting % Network voltage imbalance 0 20 20
Uinp.imbal.dl.t.trip,s Setting s Network U imbalance delay time for tripping 0 60 5
*Uout. imbal. prot. Setting Output voltage imbalance protection Off/Interlock/AR AR
Uout. imbal., % Setting % Output voltage imbalance 0 20 20
Uout.imbal.dl.t.trip,s Setting s Uout. imbalance delay time for tripping 0 60 5
Uout.imbal.AR dl.t., min Setting min AR delay time at Uout. imbalance 0 300 5
Umin dl.t.,s Setting s Umin protection delay time for tripping after start 0 3600 15
Uinp.imbal.dl.t.,s Setting s Network voltage imbalance delay time for 0 3600 5
-
TsRKF 656437.019 OM. 32
tripping after start
9.1.3 1.3
Speed Setting
Rpm/H
z Rotation speed setting in rpm 250 4200 1000
Accel. Time, min Setting min
Time to reach preset rotation speed at
acceleration 0 1000 0
Rot.dir. Setting Rotation direction >>>
Mode Setting Operating mode MAN/AUT MAN
*Rins. prot. Setting Insulation resistance protection Off/On On
Rins.min,kOhm Setting kOhm Insulation resistance setting 30 500 50
*CPGP Setting Contact pressure gauge protection Off/Interlock/AR Off
CPG dl.t.trip,s Setting s Contact pressure gauge delay time for tripping 0 999 0
CPG AR dl.t., min Setting min
AR delay time by a signal from the contact
pressure gauge 0 300 60
CPG dl.t.,s Setting s
Contact pressure gauge delay time for tripping
after start 0 999 15
Misc. protections AR number Setting
AR number at miscellaneous protections
operation 0 9999 5
AR zer.time, min Setting min Time to zero AR number meters 0 9999 5
*PRG Setting Program mode enabling Off/On Off
Oper. PRG, min Setting min Program operation time 1 9999 1
Pause PRG, min Setting min Program operation pause 1 9999 1
Sw on dl.t., min Setting min Alternative start time 1 60 1
*D PROT. Setting Door protection Off/On On
*Instab. prot. Setting Instability protection Off/Interlock/AR Off
N init. accel.,rpm Setting rpm Initial rotation speed at controlled acceleration 500 4200 1500
*Imax prot.overload. Setting Imax protection or PMM has not accelerated Interlock/AR AR
AR dl.t. Imax,min Setting min Imax AR delay time and PMM has not
accelerated 1 600 15
AR number Imax Setting Imax AR number and PMM has not accelerated 0 25 5
-
TsRKF 656437.019 OM. 33
*Backsp. prot. Setting Backspin protection Off/On On
*Backsp.decel. Setting Backspin protection Off/On Off
Ibacksp., Setting Start current at backspin below which start is
permitted 0 24.99 0
Nturb.,rpm Setting rpm
Backspin rotation speed below which start is
permitted 0 3000 0
*Ext.lock. Setting External operation locking Off/On On
Ctrl. Setting Control by I/by U by I
dNstirr.,rpm Setting rpm Rotation speed change value at stirring 60 1800 500
*Stirr. Setting Mode "Stirring" enabling Off/On Off
Tstirr.,min Setting h Mode "Stirring" time 1 99 1
Stirr.number Setting Number of stirrings 1 9 1
F1stirr., Hz Setting Hz The first stirring frequency 30 200 50
F2stirr., Hz Setting Hz The second stirring frequency 30 200 50
V1stirr.,Hz/s Setting Hz/s The first stirring rotation speed 1 15 5
V2stirr.,Hz/s Setting Hz/s The second stirring rotation speed 1 15 5
9.1.4 1.4
*Vibr.prot.,g Setting Vibration protection Off/Interlock/AR Off
Vibr,g Setting g Maximum vibration 0 9999,00 0.1
Vibr. dl.t.trip,s Setting s
Delay time for tripping at too high maximum
vibration 0 60 5
Vibr. AR dl.t., min Setting min AR delay time at too high maximum vibration 0 300 60
*motor prot. Setting Motor temperature protection Off/Interlock/AR Off
Tmotor,C Setting C Maximum motor temperature 0 160 125
motor dl.t.trip,s Setting s Delay time for tripping at maximum motor
temperature 0 60 5
motor AR dl.t., min Setting min AR delay time at maximum motor temperature 0 300 60
*Pmin prot. Setting low pump intake pressure protection Off/Interlock/AR Off
min,atm Setting atm Minimum pump intake pressure 0 299.99 40
max,atm Setting atm Maximum pump intake pressure for startup 0 299.99 80
Pmin dl.t.trip,s Setting s Delay time for tripping at minimum pressure 0 60 5
-
TsRKF 656437.019 OM. 34
Pmin AR dl.t., min Setting min AR delay time at low pump intake pressure 0 3000 60
Pmin dl.t.,s Setting s
Delay time for tripping at minimum pressure after
motor start 0 3600 5
motorMin, C Setting C motor minimum temperature enabling startup 0 160 120
Tmax dl.t.,s Setting s
motor delay time for tripping at maximum motor
temperature after motor start 0 3600 5
Vibr.dl.t.,s Setting s Delay time for tripping at vibration after motor start 0 3600 5
9.1.5 1.5
*Uan.inp.1 prot. Setting Protection by a signal from analog input 1 Off/Interlock/AR Off
An.inp.1max,% Setting V
Maximum level of protection actuation by analog
input 1 0 9999 0
UAn.inp.1dl.t.trip,s Setting s Delay time for tripping by analog input 1 0 120 5
UAn.inp.1 AR dl.t., min Setting min AR delay time for tripping by analog input 1 0 300 1
UAn.inp.1 AR number Setting AR number by analog input 1 protection 0 9999 5
UAn.inp.1 dl.t., s Setting s
Delay time for tripping by analog input 1 after
start 0 60 15
*UAn.inp.2 prot. Setting Protection by a signal from analog input 2 Off/Interlock/AR Off
An.inp.2max,% Setting V
Maximum level of protection actuation by analog
input 2 -9999 99999 0
UAn.inp.2dl.t.trip,s Setting s Delay time for tripping by analog input 2 0 120 5
UAn.inp.2 AR dl.t., min Setting min AR delay time for tripping by analog input 2 0 300 1
UAn.inp.2 AR number Setting AR number by analog input 2 protection 0 9999 5
UAn.inp.2 dl.t., s Setting s
Delay time for tripping by analog input 2 after
start 0 60 15
An.inp.1min,% Setting %
Minimum level of protection actuation by analog
input 1 0 9999 0
An.inp.2min,% Setting %
Minimum level of protection actuation by analog
input 2 0 9999 0
An.inp.1nom Setting V Nominal level by analog input 1 0 9999 0
An.inp.2nom Setting V Nominal level by analog input 2 0 9999 0
-
TsRKF 656437.019 OM. 35
9.1.6 1.6
*Adj. Setting Automatic adjustment enabling Parameters list
by
rotation
speed
See the
item
Ppump Adj.,atm Setting atm Required pump intake pressure 0 299.99 90
Nmax adj., rpm Setting rpm motor maximum rotation speed at adjustment 500 4200 1500
Nmin adj., rpm Setting rpm motor minimum rotation speed at adjustment 500 4200 1500
Iadj., Setting Current in current adjustment mode 0 999.99 5
9.2 2
Electric meter Setting Electric meter availability Meter types list type
See the
item
EFC availability Parameter External frequency converter availability No/Yes No
SS availability Parameter Soft starter availability No/Yes No
Radio channel Parameter Radio channel availability No/Yes No
ESU availability Setting External sensor unit availability No/Yes No
?Polyans
k
An. input 1 Parameter Analog input 1 availability No/Yes No
An. input 2 Parameter Analog input 2 availability No/Yes No
Communications module Parameter Communications module No/Yes No
CPG availability Setting Contact pressure gauge availability No/Yes No
DHG type Parameter DHG type Current selection
9.3 3
Well No. Setting Well number 0 65535 0
Well pad No. Setting Well pad number 1 65535 1
Field No. Setting Field number 1 65535 1
Lrunning, m Setting m Installation depth 0 9999 0
Usec.trans.,V Setting V Transformer secondary winding voltage 380 5000 983
Recording step, min Setting min Parameter recording step 0 9999 120
-
TsRKF 656437.019 OM. 36
DHG Icons., mA Setting mA Leak current measured by Zenith type DHG 8 12 10
Uprim.trans.,V Setting V Transformer primary winding voltage 380 700 380
PnomStep-up transformer,
kVA Setting kVA Step-up transformer transformer nominal power 0 2000 0
Cross section, mm2 Setting mm
2 Cable cross section 1 200 1
9.4 Measurement units 3.1
N meas. unit Setting motor rotation speed measurement units rpm/Hz rpm
I meas.unit Setting Current protection measurement units / % %
An.inp.meas. unit Setting Analog input protection measurement units V / % %
P meas.unit Setting Pressure measurement units atm / psi / MPa atm
T meas.unit Setting Temperature measurement units / F
9.5 4
Date Setting Current date 01.01.2001 01.01.2029
Time Setting Current time 00:00:00 23:59:59
Summer time/winter time Setting Daylight saving enabling Off/On Off
9.6 Drive engineering package configuration 5
VSD type Setting Variable speed drive controller type Types list
See the
item
Motor type Setting Motor type Motors list
See the
item
ESP, m3/day Setting m
3/day ESP system capacity 0 2000 0
ESP head, m Setting m ESP head 0 5000 0
DHG type Setting DHG type DHG types list
See the
item
Unom.,V Setting V motor nominal voltage 100 4000 380
Inom., Setting motor nominal current 10 1500 18
Pnom.,kW Setting kW motor nominal power 1 500 8
-
TsRKF 656437.019 OM. 37
Iidle curr.,A Setting A Idle current 0 99.99 0.1
9.6.1 Induction motor settings 5.1
I1 off,% Setting % Ampere-second, cutoff current I1 characteristics 50 250 120
T1off,s Setting s
Ampere-second, delay time for tripping 1 characteristics 1 60 20
I2 off,% Setting % Ampere-second, cutoff current I2 characteristics 50 250 150
T2off,s Setting s
Ampere-second, delay time for tripping 2 characteristics 1 60 4
I3 off,% Setting % Ampere-second, cutoff current I3 characteristics 50 250 200
T3off,s Setting s
Ampere-second, delay time for tripping 3 characteristics 1 60 1
Fnom.,Hz Setting Hz motor nominal frequency 50/60 50
Umotor+Ucab.,V Setting V Umotor+Ucable,V 100 4000 380
COSnom. Setting Power factor 0 1 0.82
Istart,% Setting % Starting current level 50 350 100
Tjamm.,s Setting s Maximum jamming time, s 1 20 5
Ustart,% Setting % Starting voltage level 50 200 100
Fstart,Hz Setting Hz motor start frequency 2 24 03
*Jog Setting PMM start mode ?
IFF/RIFF/Pfreq./Freq.
/Off IFF see
Tjog,s Setting s Jog mode time 1 20 10
Jog numb. Setting Number of jogs 1 15 4
accel.,s Setting s Acceleration time 5 125 30
Decel. Setting s Deceleration time ? ? ?
Uwaveform Setting Voltage waveform 6clock/Sin/Sin+ Sin+
*Iaccel. Prot. Setting Current limiting in acceleration mode Off/On On
motor Fnom.,Hz Setting Hz motor nominal frequency 0 200 50
VSD Uinp., V
Setting V VSD input voltage 1 500 380
Pole pair numb. Setting Number of pole pairs 1 15 2
Fproh.zone, Hz Setting Hz Prohibited zone frequency 3 100 30
-
TsRKF 656437.019 OM. 38
Wproh.zone, Hz Setting Hz Prohibited zone width 0 6 0.1
Pumping type Setting Power key modulation waveform
sine/6clock/6clock+/tr
apez. Sine
Ustart,% Setting % Starting voltage level 70/80/90/100/105/112/120 70
*Jog Setting motor start mode
Common/direct/revers
e/swing/push Common see
F PWM, kHz Setting kHz PWM frequency 1 3 1
Fnetwork,Hz Setting Hz Network frequency 50/60 50
Fpickup Setting Initial frequency after power off 3 30 5
*Netw. Prot.tripping Setting Protective tripping function Off/On Off
Uswitch init., V Setting V Switchboard initial voltage 10 600 100
Upulse, V Setting V Voltage ripple threshold on diode bridge 10 99 20
Uswitch ref., V Setting V Switchboard reference voltage 0 500 200
Phase seq. Setting Phase sequence /
9.6.2 Soft starter settings 5.2
SS mode Setting Soft starter operation mode 1 3 1
Start.moment, % Setting % SS starting moment 2 99 2
Accel.time, s Setting s SS acceleration time 1 30 2
Boost, ms Setting ms SS boost, ms 2 200 20
Jamm. time, s Setting s SS jamming 1 8 2
Ijamm.,% Setting % Motor overloading by jamming 100 500 150
Imax.start., % Setting % Maximum starting current 70 130 80
9.6.3 Technical data sheet 5.3
ARGUS No. Parameter ARGUS serial number 0 9999999 0
ARGUS type Parameter Variable speed drive controller type 0 9999 0
ARGUS manuf. Parameter ARGUS manufacturer's code 0 9999 2
ARGUS date Parameter ARGUS date of manufacture 01.01.200 31.12.20 01.01.201
VSD No. Parameter Variable speed drive serial number 0 9999999 0
-
TsRKF 656437.019 OM. 39
VSD type Parameter VSD type as per the manufacturers classification 0 9999 0
VSD manuf. Parameter VSD manufacturer's code 0 9999 2
VSD date Parameter VSD date of manufacture 01.01.200 31.12.20 01.01.201
Note Parameter Note 0 9999999
9.6.4 DHG technical data sheet 5.4
9.6.4.1 Information on DHG submersible part 5.5
Vibr.max,g Parameter g Maximum vibration measured by DHG 0 99.99 0
SDHG manuf. Parameter DHG submersible unit manufacturer's code Manufacturers list 2
See the
item
SDHG date Parameter SDHG date of manufacture 01.01.2001 31.12.2029
SDHG pr. No. Parameter
DHG submersible part data exchange protocol
number 1 255 0
SDHG design Parameter DHG submersible part design type code 1 255 0
SDHG software No. Parameter Software version for DHG submersible part 0 65535 0
PpumpMax,atm Parameter atm
Maximum pump intake pressure that can be
measured by DHG 0 65535 0
TmotorMax, C Parameter Maximum motor temperature that can be
measured by DHG -32768 32768 0
Tfluid Max, Parameter Maximum pump intake fluid temperature that can
be measured by DHG -32768 32768 0
SDHG No. Parameter DHG submersible part number 0 9999999 0
9.6.4.2 Information on DHG surface part 5.6
Pdisch.Max,atm Parameter atm Maximum pump discharge pressure 0 999.99 0
ESPmax, m3/s Parameter m
3/day
Maximum ESP capacity, that can be measured by
flow meter 0 65535 0
ESPmin, m3/s Parameter m
3/day
Minimum ESP capacity, that can be measured by
flow meter 0 65535 0
SurfDHG manuf. Parameter DHG surface unit manufacturer's code 0 3 0 See the
-
TsRKF 656437.019 OM. 40
item
SurfDHG No. Parameter DHG surface part number 0 9999999 0
SurfDHG date Parameter SurfDHG date of manufacture 01.01.2001 31.12.2029 ?
SurfDHG pr. No. Parameter DHG surface part data exchange protocol number 1 255 0
SurfDHG design Parameter DHG surface part design type code 1 255 0
SurfDHG software No. Parameter Software version for DHG surface part 0 65535 0
T bit, ms Parameter ms Single bit transmission period 0 65535 0
meas. Rins.,s Parameter s Insulation resistance measurement time 0 65535 0
T par. meas., ms Parameter ms DHG parameters measurement time 0 65535 0
TmodeRins., ms Parameter ms
Time to switch to insulation resistance
measurement mode 0 65535 0
Tfluid disch. Max, Parameter Maximum pump discharge fluid temperature that
can be measured by DHG -32768 32768 0
9.6.4.3 DHG sensors configuration 5.7
Ppump sensor Parameter
Availability of pressure sensor on the pump
intake
Tmotor sensor Parameter Availability of motor temperature sensor
Tfluid pump sensor Parameter
Availability of pump intake fluid temperature
sensor
Vibr. X sensor Parameter Availability of the sensor. Vibration along axis X
Vibr. Y sensor Parameter Availability of the sensor. Vibration along axis Y
Flow sensor Parameter Availability of the fluid flow sensor
Pdisch. sensor Parameter
Availability of the sensor The pump discharge
pressure
Tfluid pump discharge sensor Parameter
Availability of the sensor. Pump intake/discharge
fluid temperature
Vibr. Z sensor Parameter Availability of the sensor. Vibration along axis Z
Vibr. XY sensor Parameter
Availability of the sensor. Root-mean-square
vibration along axes X and Y
Rins. sensor Parameter Availability of the insulation resistance sensor
-
TsRKF 656437.019 OM. 41
Ileak sensor Parameter Availability of leak current sensor
Toil sensor Parameter Availability of oil temperature sensor
9.7 6
Delete the history Command Delete the history
Unlocking Command Unlocking
Factory settings Command Factory settings restoration
Test Command VSD test
Meters reset Command All meters reset
Phasing Command Testing phase sequence on VSD output
Record Startup Command Record Startup
Command Change password
9.7.1 6.1
Password 1 Setting Operator password 0 9999 0
Password 2 Setting Engineer password 0 9999 0
9.8 7
Rins. Parameter kOhm Insulation resistance 0 9999
Correction, kOhm Setting kOhm Rinsulation correction, kOhm 0 9999
9.9 8
SCADA type Setting SCADA type SCADA list
See the
item
SCADA address Setting
Variable speed drive address in the telemetry
system SCADA address list 0
See the
item
Baud-rate Setting baud Data exchange rate Rate list 4
See the
item
Protocol # Setting Data exchange protocol number in the telemetry Protocols list 3 See the
-
TsRKF 656437.019 OM. 42
system 255 item
Recording from SCADA Setting Recording from SCADA Off/On On
9.10 Language selection on LCD 9
Russian Parameter Russian-language menu selection
English Parameter English-language menu selection
9.11 ARGUS LCD 10
Brightness Setting Indicator brightness 0 255 70
Contrast Setting Indicator contrast 0 255 100
9.12 11
9.12.1 Main readings of electric meter 11.1
9.12.1.1 Electric meter data on current day 11.1.1
Wa+d,kWA*h Parameter
kWA*
h
Current day. Active energy. Conducting
direction. 0 999999 0
Wa-d,kWA*h Parameter
kWA*
h Current day. Active energy. Reverse. 0 999999 0
W+d,kVr*h Parameter kVrA*
h
Current day. Reactive energy. Conducting
direction. 0 999999 0
W-d,kVr*h Parameter kVrA*
h Current day. Reactive energy. Reverse. 0 999999 0
9.12.1.2
-
TsRKF 656437.019 OM. 43
Wa-pd,kWA*h Parameter
kWA*
h Previous day. Active energy. Reverse. 0 999999 0
W+pd,kVr*h Parameter kVrA*
h
Previous day. Reactive energy. Conducting
direction. 0 999999 0
W-pd,kVr*h Parameter kVrA*
h Previous day. Reactive energy. Reverse. 0 999999 0
9.12.1.3 11.1.3
Wa+m,MWA*h Parameter MWA*h
Current month. Active energy. Conducting
direction. 0 65535 0
Wa-m,MWA*h Parameter MWA*h Current month. Active energy. Reverse. 0 65535 0
W+m,MVr*h Parameter MVrA*h Current month. Reactive energy. Conducting
direction. 0 65535 0
W-m,MVr*h Parameter MVrA*h Current month. Reactive energy. Reverse. 0 65535 0
9.12.1.4 11.1.4
Wa+pm,MWA*h Parameter MWA*h
Previous month. Active energy. Conducting
direction. 0 65535 0
Wa-pm,MWA*h Parameter MWA*h Previous month. Active energy. Reverse. 0 65535 0
W+pm,MVr*h Parameter MVrA*h Previous month. Reactive energy. Conducting
direction. 0 65535 0
W-pm,MVr*h Parameter MVrA*h Previous month. Reactive energy. Reverse. 0 65535 0
9.12.1.5 11.1.5
Wa+y,MWA*h Parameter MWA*h
Current year. Active energy. Conducting
direction. 0 65535 0
Wa-y,MWA*h Parameter MWA*h Current year. Active energy. Reverse. 0 65535 0
W+y,MVr*h Parameter MVrA*h Current year. Reactive energy. Conducting
direction. 0 65535 0
W-y,MVr*h Parameter MVrA*h Current year. Reactive energy. Reverse. 0 65535 0
-
TsRKF 656437.019 OM. 44
9.12.1.6 11.1.6
Wa+py,MWA*h Parameter MWA*h
Previous year. Active energy. Conducting
direction. 0 65535 0
Wa-py,MWA*h Parameter MWA*h Previous year. Active energy. Reverse. 0 65535 0
W+py,MVr*h Parameter MVrA*h Previous year. Reactive energy. Conducting
direction. 0 65535 0
W-py,MVr*h Parameter MVrA*h Previous year. Reactive energy. Reverse. 0 65535 0
9.12.1.7 11.1.7
9.12.2 Electric meter quadrants 11.2
9.12.2.1 Electric meter data on current day 11.2.1
WdI,kVA*h Parameter kVA*h Current day. Reactive energy.
Quadrant I. 0 0 0
WdII,kVA*h Parameter kVA*h Current day. Reactive energy.
Quadrant II. 0 0 0
WdIII,kVA*h Parameter kVA*h Current day. Reactive energy.
Quadrant III. 0 0 0
WdIV,kVA*h Parameter kVA*h Current day. Reactive energy.
Quadrant IV. 0 0 0
9.12.2.2 Electric meter data on previous day 11.2.2
WpdI,kVA*h Parameter kVA*h Previous day. Reactive energy. Quadrant I. 0 0 0
WpdII,kVA*h Parameter kVA*h Previous day. Reactive energy. Quadrant II. 0 0 0
WpdIII,kVA*h Parameter kVA*h Previous day. Reactive energy. Quadrant III. 0 0 0
WpdIV,kVA*h Parameter kVA*h Previous day. Reactive energy. Quadrant IV. 0 0 0
9.12.2.3 Electric meter data on current month 11.2.3
-
TsRKF 656437.019 OM. 45
WmI,MVA*h Parameter MVA*
h
Current month. Reactive energy.
Quadrant I. 0 600000 0
WmII,MVA*h Parameter MVA*
h
Current month. Reactive energy.
Quadrant II. 0 600000 0
WmIII,MVA*h Parameter MVA*h Current month. Reactive energy.
Quadrant III. 0 600000 0
WmIV,MVA*h Parameter MVA*h Current month. Reactive energy.
Quadrant IV. 0 600000 0
9.12.2.4 Electric meter data on previous month 11.2.4
WpmI,MVA*h Parameter MVA*h Previous month. Reactive energy. Quadrant I. 0 600000 0
WpmIII,MVA*h Parameter MVA*h Previous month. Reactive energy. Quadrant II. 0 600000 0