Arc Flash Fundamentals & Compliance MARTA Training Part I , July 16, 2015

Upload: others

Post on 24-Oct-2019

1 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Arc Flash Fundamentals & Compliance · © ABB Group Month DD, Year | Slide 5 Human Reaction to Current • 10 mA Let Go Current • 30 mA Stop Breathing • 75 mA FibrillationThreshold

Arc Flash Fundamentals & Compliance

MARTA Training Part I , July 16, 2015

Page 2: Arc Flash Fundamentals & Compliance · © ABB Group Month DD, Year | Slide 5 Human Reaction to Current • 10 mA Let Go Current • 30 mA Stop Breathing • 75 mA FibrillationThreshold

© ABB GroupMonth DD, Year | Slide 2

Classification of Electric Power By User Class

Residential Commercial Industrial Utilities

Page 3: Arc Flash Fundamentals & Compliance · © ABB Group Month DD, Year | Slide 5 Human Reaction to Current • 10 mA Let Go Current • 30 mA Stop Breathing • 75 mA FibrillationThreshold

© ABB GroupMonth DD, Year | Slide 3

What are Watts?

• Amps

• Volts

• Watts = Amps x Volts

• Watt Hour (Energy) = Amps x Volt x Hours

Page 4: Arc Flash Fundamentals & Compliance · © ABB Group Month DD, Year | Slide 5 Human Reaction to Current • 10 mA Let Go Current • 30 mA Stop Breathing • 75 mA FibrillationThreshold

Electric Systems NormalOperations, Short Circuit, and

Arcing Currents

© ABB GroupMonth DD, Year | Slide 9

Page 5: Arc Flash Fundamentals & Compliance · © ABB Group Month DD, Year | Slide 5 Human Reaction to Current • 10 mA Let Go Current • 30 mA Stop Breathing • 75 mA FibrillationThreshold

© ABB GroupMonth DD, Year | Slide 5

Human Reaction to Current

• 10 mA Let Go Current• 30 mA Stop Breathing• 75 mA Fibrillation Threshold

(Stops the Heart)• >5 A Tissue Burning• 12 A Your Hair Dryer

Page 6: Arc Flash Fundamentals & Compliance · © ABB Group Month DD, Year | Slide 5 Human Reaction to Current • 10 mA Let Go Current • 30 mA Stop Breathing • 75 mA FibrillationThreshold

© ABB GroupMonth DD, Year | Slide 6

Annual Electrical Burn Statistics Department of Labor

• 4000+ Admissions to burn centers with severe Arc Flash Burns

• 3600 Disabling injuries

• 400 – 600 Deaths

Page 7: Arc Flash Fundamentals & Compliance · © ABB Group Month DD, Year | Slide 5 Human Reaction to Current • 10 mA Let Go Current • 30 mA Stop Breathing • 75 mA FibrillationThreshold

© ABB GroupMonth DD, Year | Slide 7

Electrical Injuries by Percentage

• 77% Electrical Arc Injuries

• 21% Permanent Disabilities

• 3% Death

Page 8: Arc Flash Fundamentals & Compliance · © ABB Group Month DD, Year | Slide 5 Human Reaction to Current • 10 mA Let Go Current • 30 mA Stop Breathing • 75 mA FibrillationThreshold

HOW FAR CAN YOU GO?

Fatal burns do occur at >10 feet.

© ABB GroupMonth DD, Year | Slide 13

Page 9: Arc Flash Fundamentals & Compliance · © ABB Group Month DD, Year | Slide 5 Human Reaction to Current • 10 mA Let Go Current • 30 mA Stop Breathing • 75 mA FibrillationThreshold

© ABB GroupMonth DD, Year | Slide 9

Arc Flash Incident

• A dangerous release of energy created by an electric short circuit

• Energy is released in the following forms:– Arc Blast: 35,000o F (Sun surface is 9,000o F)– Thermal Radiation: Blinding light– Pressure Wave: Ear drum rupture at 720 lbs/sq ft– Debris / Projectiles / Molten Material: Inhaling debris

Page 10: Arc Flash Fundamentals & Compliance · © ABB Group Month DD, Year | Slide 5 Human Reaction to Current • 10 mA Let Go Current • 30 mA Stop Breathing • 75 mA FibrillationThreshold

© ABB GroupMonth DD, Year | Slide 10

Threshold ofSecond & Third Degree Burns

• Second Degree Burns – Just curable, skin bubbles at 1.2 cal/cm2, 176o F for 0.1 sec.

• Third Degree Burns – Complete destruction of skin, needs grafting, 205o F, for 0.1 sec.

One calorie = 4.184 Joules = 1.163 X 10-6 KWH = 0.003964 BTU

Page 11: Arc Flash Fundamentals & Compliance · © ABB Group Month DD, Year | Slide 5 Human Reaction to Current • 10 mA Let Go Current • 30 mA Stop Breathing • 75 mA FibrillationThreshold

Fundamentals of ElectricSystem Protection

© ABB GroupMonth DD, Year | Slide 21

Page 12: Arc Flash Fundamentals & Compliance · © ABB Group Month DD, Year | Slide 5 Human Reaction to Current • 10 mA Let Go Current • 30 mA Stop Breathing • 75 mA FibrillationThreshold

© ABB GroupMonth DD, Year | Slide 12

Protective Device Clearing Time

• Current Limiting Fuse < ½ cycle(1/60 sec)

• Low Voltage Breaker 1-6 cycles (with instantaneous element)

• Low Voltage Breaker 30 cycles (without instantaneous element)

• Medium Voltage Breaker 8 cycles +relay time

Page 13: Arc Flash Fundamentals & Compliance · © ABB Group Month DD, Year | Slide 5 Human Reaction to Current • 10 mA Let Go Current • 30 mA Stop Breathing • 75 mA FibrillationThreshold

© ABB GroupMonth DD, Year | Slide 13

Switchgear

Page 14: Arc Flash Fundamentals & Compliance · © ABB Group Month DD, Year | Slide 5 Human Reaction to Current • 10 mA Let Go Current • 30 mA Stop Breathing • 75 mA FibrillationThreshold

© ABB GroupMonth DD, Year | Slide 14

Overcurrent and Instantaneous Protection

Time

Current

Page 15: Arc Flash Fundamentals & Compliance · © ABB Group Month DD, Year | Slide 5 Human Reaction to Current • 10 mA Let Go Current • 30 mA Stop Breathing • 75 mA FibrillationThreshold

© ABB GroupMonth DD, Year | Slide 15

Protective Devices Coordination (1 of 2)

The main mission is to isolate the smallest portion of the faulted distribution system.

Page 16: Arc Flash Fundamentals & Compliance · © ABB Group Month DD, Year | Slide 5 Human Reaction to Current • 10 mA Let Go Current • 30 mA Stop Breathing • 75 mA FibrillationThreshold

© ABB GroupMonth DD, Year | Slide 16

Protective Device Coordination (2 of 2)

• Reliability versus Safety

• Arcing Current < Bolted Short Circuit Current

Page 17: Arc Flash Fundamentals & Compliance · © ABB Group Month DD, Year | Slide 5 Human Reaction to Current • 10 mA Let Go Current • 30 mA Stop Breathing • 75 mA FibrillationThreshold

© ABB GroupMonth DD, Year | Slide 17

How Do Regulations Stack?

OSHA - Federal Regulations

NESC - Electric Utilities NFPA 70E – General Industry

IEEE 1584Arc Flash Hazard Calculations

Page 18: Arc Flash Fundamentals & Compliance · © ABB Group Month DD, Year | Slide 5 Human Reaction to Current • 10 mA Let Go Current • 30 mA Stop Breathing • 75 mA FibrillationThreshold

IV Calculations Based onIEEE 1584

How do you purchase a size 11 black shoe?

© ABB GroupMonth DD, Year | Slide 44

Page 19: Arc Flash Fundamentals & Compliance · © ABB Group Month DD, Year | Slide 5 Human Reaction to Current • 10 mA Let Go Current • 30 mA Stop Breathing • 75 mA FibrillationThreshold

© ABB GroupMonth DD, Year | Slide 19

Personal Protective Equipment

• Determine incident energy based on short circuit current and overcurrent deviceclearing time.

• Then select the appropriate PPE.

Page 20: Arc Flash Fundamentals & Compliance · © ABB Group Month DD, Year | Slide 5 Human Reaction to Current • 10 mA Let Go Current • 30 mA Stop Breathing • 75 mA FibrillationThreshold

Hazard/Risk Category (HRC) Classification

Required Minimum Arc

Rating (cal/cm2)

HRC Components

4 1 FR shirt and FR pants or FR Coveralls

8 2 FR shirt and FR pants or FR Coveralls

25 3 FR shirt and FR pants or FR Coveralls and arc flash suit selected so the system arc rating meets the required minimum

40 4 FR shirt and FR pants or FR Coveralls and arc flash suit selected so the system arc rating meets the required minimum

>40 Don’t be a dead hero! Work de-energized.

© ABB Group

Month DD, Year | Slide 47

Page 21: Arc Flash Fundamentals & Compliance · © ABB Group Month DD, Year | Slide 5 Human Reaction to Current • 10 mA Let Go Current • 30 mA Stop Breathing • 75 mA FibrillationThreshold

© ABB GroupMonth DD, Year | Slide 21

Level 1 PPE

• Level 1 PPE

Level 1 PPE must provide protection to 5 calories/cm2 from potential Arc Flash Thermal Energy. Level 1 PPE total clothing weight usually is 4.5 oz/yd2 to 8 oz/yd2

and may consist of:– FR long sleeve shirt and FR long pants, FR Coveralls or 50” FR smock;– Safety glasses with side shields and electrically non-conductive frames;– Polycarbonate or propionate goggles, if goggles are required;– Electrically-rated safety shoes;– Electrically non-conductive hardhat; and– Arc Flash Hazard rated gloves shall be worn to protect against the Arc Flash Hazard energy

for this level of PPE.

Page 22: Arc Flash Fundamentals & Compliance · © ABB Group Month DD, Year | Slide 5 Human Reaction to Current • 10 mA Let Go Current • 30 mA Stop Breathing • 75 mA FibrillationThreshold

© ABB GroupMonth DD, Year | Slide 22

Level 2 PPE• Level 2 PPE

Level 2 PPE must provide protection to 8 calories/cm2 from potential Arc Thermal Energy, Level 2 PPE total clothing weight of all layers usually is 9 oz/yd2 to 12 oz/yd2 and may consist of:

First Layer • 100% cotton underwear, including short sleeve shirt

Second Layer •FR long sleeve shirt and FR long Pants, FR Coveralls or 50” smock.

Other PPE: •Safety glasses with side shield and electronically non-conductive.• Electrically non-conductive hardhat.• Hearing protection.•Arc Flash rated gloves shall be worn to protect against the Arc Flash Hazard energy for this level PPE.

Page 23: Arc Flash Fundamentals & Compliance · © ABB Group Month DD, Year | Slide 5 Human Reaction to Current • 10 mA Let Go Current • 30 mA Stop Breathing • 75 mA FibrillationThreshold

© ABB GroupMonth DD, Year | Slide 23

Level 3 PPE• Level 3 PPE

Level 3 PPE must provide protection to 25 calories/cm2 frompotential Arc Thermal Energy, Level 3 PPE total clothing weight of all layers usually is 16 oz/yd2 to 20 oz/yd2 and may consist of:

First Layer • 100% cotton underwear, including short sleeve shirt

Second Layer •FR long sleeve shirt and FR long Pants, FR Coveralls or 50” smock.

Third Layer • Single layer Nomex 50” length smock or coveralls.• Nomex hood or hood cape.• Wrap around arc rated face shied.

Other PPE: •Safety glasses with side shield and electronically non-conductive.• Electrically non-conductive hardhat.• Electrically rated safety shoes.• Polycarbonate or propionate goggles, if goggles are required.• Hearing protection.•Arc Flash rated gloves shall be worn to protect against the Arc Flash Hazard energy for this level PPE.

Page 24: Arc Flash Fundamentals & Compliance · © ABB Group Month DD, Year | Slide 5 Human Reaction to Current • 10 mA Let Go Current • 30 mA Stop Breathing • 75 mA FibrillationThreshold

© ABB GroupMonth DD, Year | Slide 24

Level 4 PPE• Level 4 PPE

Level 4 PPE must provide protection to 40 calories/cm2 from potential ArcThermal Energy, Level 4 PPE total clothing weight of all layers usually is 24 oz/yd2 to 30 oz/yd2 and may consist of:

First Layer • 100% cotton underwear, including short sleeve shirt

Second Layer • FR long sleeve shirt and FR long Pants, FR Coveralls or 50” smock.

Third Layer • Multi0ply Nomex III 50” length switcher’s coat.• Nomex switcher’s hood with wrap around arc rated face shied.

Other PPE: •Safety glasses with side shield and electronically non-conductive.• Electrically non-conductive hardhat.• Electrically rated safety shoes.• Polycarbonate or propionate goggles, if goggles are required.• Hearing protection.•Arc Flash rated gloves shall be worn to protect against the Arc Flash Hazard energy for this level PPE.

Page 25: Arc Flash Fundamentals & Compliance · © ABB Group Month DD, Year | Slide 5 Human Reaction to Current • 10 mA Let Go Current • 30 mA Stop Breathing • 75 mA FibrillationThreshold

© ABB GroupMonth DD, Year | Slide 25

Questions and Comments

Page 26: Arc Flash Fundamentals & Compliance · © ABB Group Month DD, Year | Slide 5 Human Reaction to Current • 10 mA Let Go Current • 30 mA Stop Breathing • 75 mA FibrillationThreshold

© ABB GroupMonth DD, Year | Slide 26

WHY NFPA 70E?

1. OSHA tells you what to do.

2. NFPA 70E tells you how to do it.

3. NFPA 70E is revised every three years.

4. NFPA 70E 2015 became effective on August, 2014 and often is cross-referenced as part of OSHA.

Page 27: Arc Flash Fundamentals & Compliance · © ABB Group Month DD, Year | Slide 5 Human Reaction to Current • 10 mA Let Go Current • 30 mA Stop Breathing • 75 mA FibrillationThreshold

© ABB GroupMonth DD, Year | Slide 27

NFPA 70E 2015 UPDATE (1 of 3)

1. Hazard Risk Category (HRC) is replaced by PPE level or arc-rated PPE.

2. Elimination of Hazard Risk Category 0.

3. Elimination of Shock Prohibited ApproachBoundaries.

Page 28: Arc Flash Fundamentals & Compliance · © ABB Group Month DD, Year | Slide 5 Human Reaction to Current • 10 mA Let Go Current • 30 mA Stop Breathing • 75 mA FibrillationThreshold

© ABB GroupMonth DD, Year | Slide 28

NFPA 70E 2015 UPDATE (2 of 3)

4. Arc flash study must be performed byApril 1, 2015 and every 3-5 yearsthereafter.

5. Risk assessment replaced hazard analysis.

Page 29: Arc Flash Fundamentals & Compliance · © ABB Group Month DD, Year | Slide 5 Human Reaction to Current • 10 mA Let Go Current • 30 mA Stop Breathing • 75 mA FibrillationThreshold

© ABB GroupMonth DD, Year | Slide 29

6. Arc flash PPE table was replaced by two tables.

a. Table 130.7 (C) (15)(a) determines existence of arc flash hazard.

b. Table 130.7 (C) (15)(b) recommendsclothing and PPE.

NFPA 70E 2015 UPDATE (3 of 3)

Page 30: Arc Flash Fundamentals & Compliance · © ABB Group Month DD, Year | Slide 5 Human Reaction to Current • 10 mA Let Go Current • 30 mA Stop Breathing • 75 mA FibrillationThreshold

© ABB GroupMonth DD, Year | Slide 30

ELIMINATION OF PPE for CLOSED DOOR OPERATIONS

Under the following conditions:

- Equipment properly installed and maintained.

- Covers for all other equipment are secured.

- No evidence of impending failure.