approval sheet specifications of hermetic scroll …
TRANSCRIPT
No. :WXXS-000-GGSY-14
NO. DATE PAGE SANYO SIGNED CLIENT SIGNED
USER:DALIAN SANYO COMPRESSOR CO., LTD.
LEADER TECHNICALMANAGER APPROVED CHECKED SUBMITTED
MANUFACTURER:
PURCHASINGMANAGER
SPECIFICATIONS OF HERMETIC SCROLL COMPRESSOR
C-SCP270H38A
REVISION RECORD
REVISION DETAILS
APPROVAL SHEET
MODEL
1
Phase
Rated Voltage
Rated Frequency
Motor Type
Number of Poles
Electrical Insulation
Nominal Revolution
Locked Rotor Ampere
Suction Line (O.D.)
Discharge Line (O.D.)
Notes
1 Voltage range is applied at standard rating conditions.
2 Motor specifications in the table are the average values for your reference.
3 ( ): All units with parentheses are reference values.
Expiration of Specification
Expiration of this specification shall be effected until issuing a notice with indication of the expiration date from the
issued date . In case of improvement or elimination of this specification , it shall be handled by the revision record
based on agreement between both sides.
Compressor Model — C-SCP270H38A
Black Paint
min-1 —
A 106/111
U-W 1.373
Connection Tube
U-V 1.308
mm (in) 25.4 (1.000)
mm (in) 19.05 (0.750)
V-W 1.351
ml (fl oz) 2800 (94.7)
Displacement cm3 (in3) /rev 89.2(5.44)
— R410A
Oil Type — FV68S or Equivalent
Refrigerant
V 342~456/396~484
kg (lb) 66.5(146.6)
— Natural Cooling
Power Source
— 3
V 380-415/440
Hz 50/60
Compressor Cooling Type
°C (°F) -15~12 (5~54)
— Hermetic Scroll Compressor
— High Back Pressure
Content Unit Specification
Section 1. General Specifications
Voltage Range
Weight (Including Oil)
Oil Charge
Type
Application
Evap. Temp. Range
E
— 3-PH Induction Motor
— 2
Class
Compressor Surface Paint —
Motor
Winding Resistance[at 25°C (77°F)] Ω
2
Hz 50 60
V 380 440
W 22,400 27,200 ±5%
(BTU/hr) 76,429 92,806 reference
W 7,400 8,900 ±5%
A 13.1 13.4 ±5%
Standard Rating Conditions
°C (°F)
°C (°F)
°C (°F)
°C (°F)
°C (°F)
Hz 50
V 380
dB(A) 72Max.
Notes
1 The operating conditions are the same as 2.1.
2 MIC location is the distance of 1m (3.28feet) from the compressor.
3 Sound Level is an average sound pressure level in four directions.
Hz 50
V 304
Conditions
°C (°F)
°C (°F)
MPa(G)/psig
MPa(G)/psig
UnitL.P. S. MPa(G)/psigH. P. S. MPa(G)/psig
MΩ
V
mgNote:
1. The insulation resistance be measured with a DC500V megohm tester.
0.9(130.5)
2.3 Minimum Starting Voltage
2.2 Sound Level
10~60(50~140)
10~40(50~105)
3.25(471)
7.2( 45 )
Remark
2.1 Performance
Section 2. Performance Warranty
Power Source (3PH)
54.4(130)
Capacity
2.21(320)
2.4 OthersContent Specification
Residual Moisture
Insulation Resistance
Dielectric Strength
Design Pressure4.15(602)
100 (without refrigerant)
2300 (1 second)
400
Input Power
Current
Condensing Temp.
Evaporating Temp.
Suction Gas Temp.
Liquid Temp.
Ambient Temp.
Power Source (3PH)
Ambient Temp.
High Pressure
Low Pressure
Sound Level
Power Source (3PH)
Minimum Starting Voltage
Compressor Temp.
18.3( 65 )
46.1(111)
35.0( 95 )
352
60
440
74Max.
60
3
3.1 Accessories List
Parts Name Qty Parts code Revision No. Note
Terminal Box Cover 1 A-0101-DSB 0 Installed on Compressor
Terminal Box Clip 1 A-0201-DSB 0 Installed on Compressor
Insulating Grommet 1 A-0301-DSB 0 Installed on Compressor
Gasket Terminal 1 A-0401-DSC 0 Installed on Compressor
Mounting Grommet 4 M-0101-DSC 0 Included with Compressor
Mounting Sleeve 4 M-0201-DSC 0 Included with Compressor
3.2 The Drawing for Reference
Revision No.
0
0
0
0
3. 3 Inernal Motor Protector (in compressor)
Parts Name
Trip Temprature
Reset Temprature
Trip Current
Inernal Motor Protector 70±10
Parts Code
D-0105-DSC
D-0201-DSC
Specification
66A / 3~10s
165±5
E-0910-DSC
Section 3. Standard Accessories
Wiring Diagram
Compressor Outline Drawing
Parts Name
Mounting Parts Listing
Packing Dimensions
M-5102-DSC
4
4.1 Protection Required but not Included with compressor
Protection Device Items
Features
Rated Voltage
Crankcase Heater Rated Power
Mounting Position
Trip Temperature
Reset Temperature
High Pressure Switch Setting
Low Pressure Switch Setting
4.2 Position of the Protection and Refrigerant Charging
135±5(275 ±10 °F)
Section 4. Compressor Protection
Specifications
Cut-out seting no lower than 0.15MPa(G)
AC380VReversal Defensible Relay
To protect the compressor from reverse rotation
Cut-out seting no higher than 4.15MPa(G)
86±15 (187 ± 27 °F)
Discharge Thermostat
88 Watts
Located in the well pipe of top shell
HIGH PRESSURE
SWITCH
COMPRESSOR
LOW PRESSURE
SWITCH
CRANKCASE HEATER
DISCHARGE THERMOSTAT
OUTDOOR HEAT
EXCHANGER
INDOOR HEAT
EXCHANGER
ACCUMULATOR
FOR LIQUID REFRIGERANT
CHARGING
FOR GAS REFRIGERANT
CHARGING
CAPILLARY
LIQUID LINE SERVICE
VALVE
GAS LINE SERVICE VALVEREVERSING
VALVE
5
6
Section 5. Operating Envelope
10
20
30
40
50
60
70
-30 -25 -20 -15 -10 -5 0 5 10 15 20
Evaporating Temperature()
Con
dens
ing
Tem
pera
ture(
)
Suction Gas Superhea : 11.1K.Refrigerant : R410A.
Transient Operation
Normal Operation
The following requirements apply to vertical type hermetic scroll compressors:
No. Item Note
1 Refrigerant
4 Compression Ratio
5 Winding Temp.
8 Suction Gas Temp.
It should meet therequirement of item 5, 6,7 and 14 within 30cm ofthe suction fitting.
12 Refrigerant Charge Specific gravity of theOil:0.94
13 Life Time
By high pressure switch
By low pressure switch
16 System MoistureLevel
18 Tilt
Operation beyond the above limits must be approved by Dalian SANYO Compressor Co., Ltd. (G): Gauge Pressure
Voltage at compressorterminals.
Single Phase Models: 90% of the rated voltage min.
For at least 7 minutes -on/3 minutes-off isrecommendable.
On Period: Until the oil level returns to the center of the lower bearing
Off Period: Until balance of high and low pressure is obtained
Voltage at compressorterminals.
24 hrs. after vacuuming:1.01kPa Max.
Condensing Temp.
Discharge GasTemp.
11 On/Off Cycling
6 Shell Bottom Temp.
2 ~ 6 8
Limit: Applicable to transitional brief period of time, such as start-up and beginning of defrost mode.
90(194 °F) Max.
Evaporating Temp.+12(21 °F) Min.
Ambient Temp.+11(20 °F) Min.
115(240 °F) Max. 125(257 °F)
14 Minimum Oil Level
Section 6. Application Standard & Limit
2 Evaporating Temp.
Standard Limit
R410A
Standard: Applicable to ordinary conditions in Japan JIS B8616 or standards relative to JIS B8616, such as standard ratingconditions, maximum operating conditions, low temperature conditions, etc.
17SystemUncondensable GasLevel
Abnormal PressureRise/Drop15
9 Running Voltage
200ppm Max.
No excessive noiseSuperheat: 5K(10 °F)Min.
Within ±10% of the rated voltage
oil/refrigerant(wt.)≥0.35
Pressure Drop: 0.15MPa(G) (22psig) Min.
10 Starting Voltage
5。Deg.Max.
200,000 cycle
Residual Oxygen 0.1 Vol.% Max.
1 Vol.% Max.
Pressure Rise: 4.15MPa(G) (602psig) Max.
C-SC:No less than 70% of the initial oil charge
C-SB: Center of the lower bearing C-SB:Bottom of the lower bearing
115(240 °F) Max.
C-SB:130( 266°F) Max.
C-SC:135( 275°F) Max.
Three Phase Models: 85% of the rated voltage min.
7
-15~12(5~54 °F) -25~15(-13~59 °F)
0.38~1.06MPa(G)(55~154psig) 0.23~1.16MPa(G)(33~168psig)
30~60(86~140 °F) 65(149 °F)
4.18MPa(G)(606psig)1.80~3.75MPa(G)(261~544psig)3
7
1 Installation should be completed within 15 minutes after removing the rubber plugs.
2 Do not use the compressor to compress air.
5 Do not tilt over the compressor while carrying it.
6 Do not remove the paint.
9 Do not operate compressor in reverse rotational direction.
11 Copper Piping Stress Start/Shutdown 34.32 N/mm2 Max.
Run 12.26 N/mm2 Max.
10 Suction strainers are recommended for all applications.
3 Do not energize the compressor under vacuumed conditon.
Notes
4 Evacuation and Refrigerant charge : Evacuate internal section in the refrigeration system from high and low pressuresides and charge liquid refrigerant from condenser outlet side. Additional charge shall be done with gas condition fromlow side.
7 Crankcase heater is required when the oil sump temperature is too low to meet the requirement of item 6 on page7.
8 Voltage fluctuation between compressor terminals, during operation, shall be within 2% of the rated voltage.
8
Voltage drop may occur due to the large current draw during compressor starting.
We recommend selecting the wire size from the table below.
7.1 Type of Unit7.1.1 Window & Commercial Type Unit
7.1.2 Split Type(Separate Type)
7.2 Size Table of Electrical Wire
Remark③(heat-resistance Temperature:120°C(248°F) min.)
5m max. 10m max. 15m max. 20m max. 30m max. 50m max. 1m max.
20max. 2.0 2.0 2.0 3.5 5.5 8.0 2.0
30max. ↑ ↑ 3.5 5.5 ↑ 14.0 ↑
40max. ↑ 3.5 5.5 ↑ 8.0 ↑ ↑
50max. ↑ ↑ ↑ 8.0 14.0 22.0 ↑
60max. ↑ 5.5 ↑ ↑ ↑ ↑ ↑
70max. 3.5 ↑ 8.0 14.0 ↑ ↑ 3.5
80max. ↑ ↑ ↑ ↑ 22.0 30.0 ↑
90max. ↑ ↑ 14.0 ↑ ↑ ↑ ↑
100max. ↑ 8.0 ↑ ↑ ↑ 38.0 ↑
110max. ↑ ↑ ↑ ↑ ↑ ↑ ↑
120max. 5.5 ↑ ↑ 22.0 30.0 ↑ ↑
140max. ↑ 14.0 ↑ ↑ ↑ 50.0 5.5
160max. ↑ ↑ 22.0 ↑ ↑ ↑ ↑
180max. ↑ ↑ ↑ ↑ 38.0 60.0 8.0
200max. 8.0 ↑ ↑ 30.0 ↑ ↑ ↑
220max. ↑ ↑ ↑ ↑ 50.0 80.0 ↑
240max. ↑ ↑ ↑ ↑ ↑ ↑ 14.0
The internal motor protector does not protect the compressor against all possible conditions.
Please be sure that the system utilizes the ground connection when installed in the field.
Section 7. Selection of Electrical Wire
7.3 Caution of Ground
Starting current(A)
Size of electrical wire(mm2)
Remark ① or Remark ①+②(heat-resistance Temperature: 60°C(140°F) min.)
①power source
terminal plate compressor
indoor
outdoor
②
①powersource
terminalplate
compressorindoor
outdoor
② ③
9
TAPPING SCREWS M4
77.2
TERMINAL
U
V
W
68.2
COMP. CODE A B C D E809 28* 8*809 18* 8*809 29* 8*809 19* 8*809 20* 8*809 10* 8*809 22* 8*809 12* 8*C-SCP270,315,360,400
538[21.18]
284[11.18]
486[19.13]
7.9[0.31]
289[11.38]
553[21.77]
299[11.77]
501[19.21]
9[0.35]
304[11.97]
Part CodeD-0105-DSC D-0105-DSC
Name Compressor Outline Drawing
10
COMP. CODE A B C D E809 28* 8*809 18* 8*809 29* 8*809 19* 8*809 20* 8*809 10* 8*809 22* 8*809 12* 8*C-SCP270,315,360,400
538[21.18]
284[11.18]
486[19.13]
7.9[0.31]
289[11.38]
553[21.77]
299[11.77]
501[19.21]
9[0.35]
304[11.97]
No. Part QTY Name1 M-0101-DSC 4 Mounting Grommet2 M-0202-DSC 4 Mounting Sleeve
11
Part Code M-5102-DSC Name Mounting Parts Listing
1
`
Compressor Model AC-SCP270H38*C-SCP315H38*C-SCP360H38*C-SCP400H38*
Part Code
D-0201-DSC
Name Packing Dimensions
12
697 [27.441]
E-0910-DSCName
13
Part Code
Wiring Diagram
POWER SUPPLY50Hz 220V
DISCHARGE GAS TEMP. SENSOR
W
V
U
POWER SUPPLY50Hz 380~415V
14
11
12
A
B
C
T
S
R
CRANKCASE HEATER
REVERSAL DEFENSIBLE RELAY
MAGNETIC SWITCH
COMPRESSOR
INTERNAL PROTECTOR
SWITCH
TERMINAL
PERFORMANCE DATA (PRELIMINARY DATA)C-SCP270H38A
Power Source 3PH 50Hz 380~415VSuction Gas Superheat(K) 11.1Sub Cooling(K) 8.3Compressor Cooling Natural CoolingRefrigerant R410A
CAPACITY(W)CondensingTemperature() -15 -10 -5 0 5 10 15
35.0 13,083 15,487 18,376 21,834 25,940 30,77840.0 12,376 14,656 17,385 20,644 24,515 29,081 34,42245.0 11,741 13,898 16,465 19,527 23,163 27,456 32,48850.0 11,179 13,212 15,619 18,482 21,883 25,904 30,62655.0 12,599 14,845 17,510 20,676 24,424 28,83760.0 14,144 16,611 19,541 23,017 27,12065.0 15,784 18,479 21,683 25,477
POWER(W)CondensingTemperature() -15 -10 -5 0 5 10 15
35.0 5,712 5,345 5,077 4,899 4,802 4,77840.0 5,963 5,711 5,532 5,415 5,353 5,337 5,35845.0 6,296 6,159 6,068 6,013 5,986 5,978 5,98150.0 6,711 6,690 6,686 6,693 6,701 6,701 6,68655.0 7,302 7,387 7,456 7,498 7,507 7,47360.0 8,171 8,300 8,378 8,395 8,34365.0 9,227 9,340 9,365 9,295
CURRENT(A) @380VCondensingTemperature() -15 -10 -5 0 5 10 15
35.0 10.2 9.8 9.5 9.3 9.2 9.140.0 10.7 10.4 10.2 10.1 10.0 10.0 10.045.0 11.3 11.2 11.1 11.0 11.0 11.0 11.050.0 11.9 12.0 12.0 12.0 12.1 12.1 12.055.0 12.9 13.0 13.2 13.2 13.3 13.260.0 14.2 14.4 14.5 14.5 14.565.0 15.7 15.9 15.9 15.8
NOTE:* The performance values subject to change without notice.
Compressor Model
Evaporating Temperature()
Evaporating Temperature()
Evaporating Temperature()
C-SCP270H38APower Source 3PH 50Hz 380~415VCompressor Model(Code)
0
5,000
10,000
15,000
20,000
25,000
30,000
35,000
40,000
‐15 ‐10 ‐5 0 5 10 15
CAPA
CITY
(W)
Evap. Temp. ()
CAPACITY Cond.Temp.
35.040.545.050.054.460.065.0
6.0
8.0
10.0
12.0
14.0
16.0
18.0
‐15 ‐10 ‐5 0 5 10
CURR
ENT (A)
Evap. Temp. ()
CURRENT @ 380V Cond.Temp.
65.060.054.450.045.040.535.0
COEFFICIENTS OF PERFORMANCE CURVES
Compressor Model C-SCP270H38APower Source 3PH 50Hz 380~415VSuction Gas Superheat (K) 11.1Sub Cooling (K) 8.3Compressor Cooling Natural CoolingRefrigerant R410A
X——CAPACITY(W) OR POWER(W) OR CURRENT(A) OR FLOW(kg/h)S——EVAPORATING TEMP, °CD——CONDENSING TEMP, °C
380V-50HzC1C2C3C4C5C6C7C8C9
C10
Note:The polynomial coefficients subject to change without notice.
X=C1+C2*(S)+C3*D+C4*(S2)+C5*(S*D)+C6*(D2)+C7*(S3)+C8*(D*S2)+C9*(S*D2) +C10*(D3)
CAPACITY (W) POWER (W) CURRENT (A)3.219596E+04 3.593062E+03 6.370747E+00
1.056983E+03 -9.479755E+01 -1.256042E-01
-3.469117E+02 -2.027454E+01 1.274237E-02
1.819444E+01 5.358398E+00 6.906110E-03
1.645550E+00 2.015232E-03
1.089955E-01 -1.132851E-02 -1.130512E-05
-3.344003E-06 -1.454315E-06 -1.630045E-09
-1.487040E-01 -1.066712E-01 -1.433611E-04
5.563710E-07 -6.273563E-07
-8.665679E+00 1.930288E+00 2.638099E-03
-7.456751E-10
1.452823E+00