applications for daa data beyond transformer load management

Upload: pinkesh-parekh

Post on 14-Apr-2018

224 views

Category:

Documents


0 download

TRANSCRIPT

  • 7/30/2019 Applications for DAA Data Beyond Transformer Load Management

    1/14

    Applications For DAA DataBeyond Transformer Load

    Management

    Presented by: Donald J. Kane P.E.

    Asset Systems Program Manager

    Connecticut Light & Power

    October 19, 2010

  • 7/30/2019 Applications for DAA Data Beyond Transformer Load Management

    2/14

    CL&P A subsidiary ofNortheast Utilities

  • 7/30/2019 Applications for DAA Data Beyond Transformer Load Management

    3/14

    CL&P

    4 Divisions

    13 Districts

    235 Substations

    1,085 FeedersMGY, UGY, and DeltaVoltages from 2.4kv to34.5kv

    40 Circuit

    Owners plus 6staff engineers

  • 7/30/2019 Applications for DAA Data Beyond Transformer Load Management

    4/14

    2003 Review several TLM products,

    including ITRONs DAO/DAA

    2004 ITRON selected, plans for

    implementation begin (late 2005 start)

    2007 Implemented DAA (without On-Demand), and trained 40 users by ITRON

    at NUhalf day sessions.

    2009 Updated with 2008 Summer loads.

    DAA Implementation History

  • 7/30/2019 Applications for DAA Data Beyond Transformer Load Management

    5/14

    General Issues and ChallengesData Source Changes

    New CS system implemented in 2009

    New MDM implementation ongoing (2011 completion)

    GIS Details and Error CorrectionTransformer sizes and phasing

    Customer to Transformer ConnectivityUsing OMS for this relationship presently

    Plans to use GIS eventuallySome difficulties maintaining accuracy

    Feeding the BeastAHuge amounts of data, even without smartmeters

    ANo concrete plans for on demand updates yet

  • 7/30/2019 Applications for DAA Data Beyond Transformer Load Management

    6/14

    Transformer Load ManagementFind overloaded transformers before they fail

    Too many false positives-big problem

    Looking for ways to minimize false positivesDatafeed for Loadflow Applications

    Estimate errors not as big a problem

    Just need to weed out extreme errors (very large load estimates)

    Much better to use than connected KVA

    Operations/New Service ReferenceCasual or emergency transformer load lookup

    For transformer trip/failure-Reset or replace/upgrade?

    For new service-Place on existing transformer or upgrade size?

    Distribution PlanningASignificant load additions Can upstream devices handle the load? Whatphase to use?

    AOverload checks for major devices (S/S transformers, step transformers,regulators, reclosers, etc)

    A

    Substation meter error checking

    Potential Applications for DAA Results

  • 7/30/2019 Applications for DAA Data Beyond Transformer Load Management

    7/14

    Load Estimates from

    DAA in loadflow models

  • 7/30/2019 Applications for DAA Data Beyond Transformer Load Management

    8/14

    Web Tool to manage follow-up work from

    identifying overloaded transformers.

  • 7/30/2019 Applications for DAA Data Beyond Transformer Load Management

    9/14

    Also used to look up transformer loads for routine or emergency queries.

  • 7/30/2019 Applications for DAA Data Beyond Transformer Load Management

    10/14

    and to verify/correct customer to transformer connectivity

  • 7/30/2019 Applications for DAA Data Beyond Transformer Load Management

    11/14

    Check % loading and

    customer counts onupstream devices to

    determine potential

    problems for new load

    connections.

  • 7/30/2019 Applications for DAA Data Beyond Transformer Load Management

    12/14

    Check phase balance on

    upstream devices, forselection of what phase to

    use for new single phase

    loads.

  • 7/30/2019 Applications for DAA Data Beyond Transformer Load Management

    13/14

    Measured load (from station meter) diverges from

    predicted model - indicates a possible switching

    event where this substation bank picked up some

    load.

  • 7/30/2019 Applications for DAA Data Beyond Transformer Load Management

    14/14

    A view of the chart from another substation nearby

    indicates a matching divergence between the

    measured load and the predicted profile