apfc analog thesis

Upload: pandyamech

Post on 14-Apr-2018

232 views

Category:

Documents


0 download

TRANSCRIPT

  • 7/27/2019 Apfc Analog Thesis

    1/40

    ABSTRACT

    This project discusses the design, implementation and analysis of a single phase

    (240V, 50Hz) capacitor bank controller unit. Power factor control using capacitor

    banks reduces reactive power consumption which will lead to minimization of losses

    and at the same time increases the electrical systems efficiency. Power saving issues

    and reactive power management has brought to the creation of single phase capacitor

    banks for domestic applications. The development of this project is to enhance and

    upgrade the operation of single phase capacitor banks by developing a micro-

    processor based control system. The control unit will be able to control capacitor

    bank operating steps based on the varying load current. Current transformer is used to

    measure the load current for sampling purposes. Fluorescent lamp will be use as

    loads in this single phase capacitor bank developments. That fluorescent lamp shall

    be divided into different load value to enable capacitor bank model is controlled

    systematically.

    1 | P a g e

  • 7/27/2019 Apfc Analog Thesis

    2/40

    Unit -01

    INTRODUCTION

    &

    PROBLEM IDENTIFICATION

    2 | P a g e

  • 7/27/2019 Apfc Analog Thesis

    3/40

    1.1 INTRODUCTION

    Electrical energy efficiency is of prime importance to industrial and commercial

    companies operating in today's competitive markets. Optimum use of plant and

    equipment is one of the main concerns that industry tries to balance with energy

    efficiency, for both economical and environmental reasons. As society becomes

    increasingly conscious of its impact on the environment, reduced energy consumption

    becomes more desirable, which, is an achievable goal for everyone. Through the use

    of measures such as power factor control, electricity consumption is optimized, which

    ultimately leads to reduced energy consumption and reduced CO2 greenhouse gas

    emissions.

    Within a cost conscious market, payback considerations are also important. This

    report identifies the most appropriate application for power factor control based on

    energy consumption, tariff metering, cost payback and emission reduction. Power

    factor control is an appropriate means by which to improve the power quality of an

    installation. Its application is dependent though on the size of the installation and the

    extent that power factor control needs to be applied. The opportunity however exists

    to make a significant environmental contribution whilst simultaneously providing

    economic benefit.

    3 | P a g e

  • 7/27/2019 Apfc Analog Thesis

    4/40

    Currently, the effective of the capacitor bank as power factor control device was

    produced a capacitor bank to domestic use. Also known as energy stability, it will

    correct power factor base capacitor concept as compensator reactive current in the

    single phase electric circuit. However, this device is less efficiency because the static

    operation and did not control load change. The project titled Automatic Power

    Factor Control was developed to enable operation single phase capacitor bank to

    control follow load change. The operation of present single phase capacitor bank was

    not able to operate base of current change according the increase or reduction load.

    Because the present system could not detect load rating that changed, the operation

    inefficient and power factor control not be optimum. This project is using fluorescent

    magnetic ballast as the load.

    1.2 Problem Identification

    This project developed to improve the weakness of static capacitor bank. Static

    capacitor bank is a traditional method was used to improve the power factor by using

    capacitor banks. In the configuration of static capacitor bank, the value of capacitor

    was fixed and cannot to control. The weakness of the static capacitor bank, which the

    operations:

    i. Capacitive compensation does not change according to increase or reduction in

    loads.

    ii. Could not detect load rating that change inefficiency

    iii. Operation and power factor control not optimized.

    4 | P a g e

  • 7/27/2019 Apfc Analog Thesis

    5/40

    CUR RENT WAVEFOR MS WITH AND WITH OUT P FC:

    Input Voltage

    0

    DC Bus Output Voltage

    Without

    PFC

    0

    Input Curren

    5 | P a g e

    With

    PFC

  • 7/27/2019 Apfc Analog Thesis

    6/40

    1.3 Target and Objectives of the Project

    There are four objectives of this project, which is stated in the following

    texts:

    i. To learn the way of power factor control in power systems.

    ii. To learn and identify methods to control capacitor banks.

    iii. Identify one method of power factor control with the low cost and

    practical.

    iv. To provide an automatically controlled PFC unit that will bring the

    power factor to as near to unity as practical (typically 0.9) and have

    sufficient capacity for future PFC requirements or expansion.

  • 7/27/2019 Apfc Analog Thesis

    7/40

    Unit-02

    LITERATURE REVIEW

  • 7/27/2019 Apfc Analog Thesis

    8/40

    POWER FACTOR:

    Power factor is the ration between the KW and the KVA drawn by an

    electrical load where the KW is the actual load power and the KVA is the

    apparent load power. It is a measure of how effectively the current is being

    converted into useful work output and more particularly is a good indicator

    of the effect of the load current on the efficiency of the supply system.

    APPARENT POWER REACTIVE POWER

    ACTIVE POWER

    Fig 2.1

    All current will cause losses in the supply and distribution system. A load

    with a power factor of 1.0 result in the most efficient loading of the supply

    and a load with a power factor of 0.5 will result in much higher losses in the

    supply system.

    A poor power factor can be the result of either a significant phase difference

    between the voltage and current at the load terminals, or it can be due to a

    high harmonic content or distorted/discontinuous current waveform. Poor

  • 7/27/2019 Apfc Analog Thesis

    9/40

    load current phase angle is generally the result of an inductive load such as

    an induction motor, power transformer, lighting ballasts, welder or induction

    furnace. A distorted current waveform can be the result of a rectifier,

    variable speed drive, switched mode power supply, discharge lighting or

    other electronic load.

    A poor power factor due to an inductive load can be improved by the

    addition of power factor correction, but, a poor power factor due to a

    distorted current waveform requires a change in equipment design or

    expensive harmonic filters to gain an appreciable improvement. Many

    inverters are quoted as having a power factor of better than 0.95 when in

    reality, the true power factor is between 0.5 and 0.75. The figure of 0.95 is

    based on the Cosine of the angle between the voltage and current but does

    not take into account that the current waveform is discontinuous and

    therefore contributes to increased losses on the supply.

    POWER FACTOR CORRECTION:

    Capacitive Power Factor correction is applied to circuits which include

    induction motors as a means of reducing the inductive component of the

    current and thereby reduce the losses in the supply. There should be no

    effect on the operation of the motor itself.

  • 7/27/2019 Apfc Analog Thesis

    10/40

    An induction motor draws current from the supply that is made up of

    resistive components and inductive components.

    The resistive components are:

    (i)Load current (ii) Loss current

    The inductive components are:

    (i)Leakage reactance (ii) Magnetizing current

    Fig 2.2

    The current due to the leakage reactance is dependent on the total current

    drawn by the motor, but the magnetizing current is independent of the load

    on the motor. The magnetizing current will typically be between20% and

    60% of the rated full load current of the motor. The magnetizing current is

    the current that establishes the flux in the iron and is very necessary if the

    motor is going to operate. The magnetizing current

  • 7/27/2019 Apfc Analog Thesis

    11/40

    does not actually contribute to the actual work output of the motor. It is the

    catalyst that allows the motor to work properly. The magnetizing current and

    the leakage reactance can be considered passenger components of current

    that will not affect the power drawn by the motor, but will contribute to the

    power dissipated in the supply and distribution system.

    Taking an example, a motor with a current draw of 100 Amps and a power

    factor of 0.75 the resistive component of the current is 75 Amps and this is

    what the KWh meter measures. The higher current will result in an increase

    in the distribution losses of (100 x 100) / (75 x 75) = 1.777 or a 78%

    increase in the supply losses.

    In the interest of reducing the losses in the distribution system, power factor

    correction is added to neutralize a portion of the magnetizing current of the

    motor. Typically, the corrected power factor will be 0.92 - 0.95 some power

    retailers offer incentives for operating with a power factor of better than 0.9,

    while others penalize consumers with a poor power factor. There are many

    ways that this is metered, but the net result is that in order to reduce wasted

    energy in the distribution system, the consumer will be encouraged to apply

    power factor correction.

  • 7/27/2019 Apfc Analog Thesis

    12/40

    Fig 2.3

    Power factor correction is achieved by the addition of capacitors in parallel

    with the connected motor circuits and can be applied at the starter, or applied

    at the switchboard or distribution panel. The resulting capacitive current is

    leading current and is used to cancel the lagging inductive current flowing

    from the supply.

    Capacitors connected at each starter and controlled by each starter are

    known as "Static Power Factor Correction".

  • 7/27/2019 Apfc Analog Thesis

    13/40

    STATIC CORRECTION:

    As a large proportion of the inductive or lagging current on the supply is due

    to the magnetizing current of induction motors, it is easy to correct each

    individual motor by connecting the correction capacitors to the motor

    starters. With static correction, it is important that the capacitive current is

    less than the inductive magnetizing current of the induction motor. In many

    installations employing static power factor correction, the correction

    capacitors are connected directly in parallel with the motor windings. When

    the motor is Off Line, the capacitors are also Off Line. When the motor is

    connected to the supply, the capacitors are also connected providing

    correction at all times that the motor is connected to the supply. This

    removes the requirement for any expensive power factor monitoring and

    control equipment. In this situation, the capacitors remain connected to the

    motor terminals as the motor slows down. An induction motor, while

    connected to the supply, is driven by a rotating magnetic field in the stator

    which induces current into the rotor. When the motor is disconnected from

    the supply, there is for a period of time, a magnetic field associated with the

    rotor. As the motor decelerates, it generates voltage out its terminals at a

    frequency which is related to its speed. The capacitors connected across the

    motor terminals, form a resonant circuit with the motor inductance. If the

  • 7/27/2019 Apfc Analog Thesis

    14/40

    motor is critically corrected, (corrected to a power factor of 1.0) the

    inductive reactance equals the capacitive reactance at the line frequency and

    therefore the resonant frequency is equal to the line frequency. If the motor

    is over corrected, the resonant frequency will be below the line frequency. If

    the frequency of the voltage generated by the decelerating motor passes

    through the resonant frequency of the corrected motor, there will be high

    currents and voltages around the motor/capacitor circuit. This can result in

    severe damage to the capacitors and motor. It is imperative that motors are

    never over corrected or critically corrected when static correction is

    employed.

    Static power factor correction should provide capacitive current equal to

    80% of the magnetizing current, which is essentially the open shaft current

    of the motor.

    The magnetizing current for induction motors can vary considerably.

    Typically, magnetizing currents for large two pole machines can be as low

    as 20% of the rated current of the motor while smaller low speed motors can

    have a magnetizing current as high as 60% of the rated full load current of

    the motor. It is not practical to use a "Standard table" for the correction of

    induction motors giving optimum correction on all motors. Tables result in

    under correction on most motors but can result in over correction in some

    cases. Where the open shaft current cannot be measured, and the

  • 7/27/2019 Apfc Analog Thesis

    15/40

    magnetizing current is not quoted, an approximate level for the maximum

    correction that can be applied can be calculated from the half load

    characteristics of the motor.

    Fig 2.4

    It is dangerous to base correction on the full load characteristics of the motor

    as in some cases, motors can exhibit a high leakage reactance and correction

    to 0.95 at full load will result in over correction under no load, or

    disconnected conditions.

    Static correction is commonly applied by using one contactor to control both

    the motor and the capacitors. It is better practice to use two contactors, one

  • 7/27/2019 Apfc Analog Thesis

    16/40

    for the motor and one for the capacitors. Where one contactor is employed, it

    should be up sized for the capacitive load. The use of a second contactor

    eliminates the problems of resonance between the motor and the capacitors.

    SUPPLY HARMONICS

    Harmonics on the supply cause a higher current to flow in the capacitors.

    This is because the impedance of the capacitors goes down as the frequency

    goes up. This increase in current flow through the capacitor will result in

    additional heating of the capacitor and reduce its life.

    The harmonics are caused by many non-linear loads; the most common in

    the industrial market today, are the variable speed controllers and switch

    mode power supplies. Harmonic voltages can be reduced by the use of a

    harmonic compensator, which is essentially a large inverter that cancels out

    the harmonics. This is an expensive option. Passive harmonic filters

    comprising resistors, inductors and capacitors can also be used to reduce

    harmonic voltages. This is also an expensive exercise. In order to reduce the

    damage caused to the capacitors by the harmonic currents, it is becoming

    common today to install detuning reactors in series with the power factor

    correction capacitors. These reactors are designed to make the correction

    circuit inductive to the higher frequency harmonics. Typically, a reactor

  • 7/27/2019 Apfc Analog Thesis

    17/40

    would be designed to create a resonant circuit with the capacitors above the

    third harmonic, but sometimes it is below.

    Adding the inductance in series with the capacitors will reduce their

    effective capacitance at the supply frequency. Reducing the resonant or

    tuned frequency will reduce the effective capacitance further. The object is

    to make the circuit look as inductive as possible at the 5th harmonic and

    higher, but as capacitive as possible at the fundamental frequency. Detuning

    reactors will also reduce the chance of the tuned circuit formed by the

    capacitors and the inductive supply being resonant on a supply harmonic

    frequency, thereby reducing damage due to supply resonance amplifying

    harmonic voltages caused by non-linear loads.

    SUPPLY RESONANCE:

    Capacitive Power factor correction connected to a supply causes resonance

    between the supply and the capacitors. If the fault current of the supply is

    very high, the effect of the resonance will be minimal, however in a rural

  • 7/27/2019 Apfc Analog Thesis

    18/40

    installation where the supply is very inductive and can be high impedance,

    the resonance can be very severe resulting in major damage to plant and

    equipment.

    To minimize supply resonance problems, there are a few steps that can be

    taken, but they do need to be taken by all on the particular supply.

    1) Minimize the amount of power factor correction, particularly when the

    load is light. The power factor correction minimizes losses in the supply.

    When the supply is lightly loaded, this is not such a problem.

    2) Minimize switching transients. Eliminate open transition switching -

    usually associated with generator plants and alternative supply switching,

    and with some electromechanical starters such as the star/delta starter.

    3) Switch capacitors on to the supply in lots of small steps rather than a few

    large steps.

    4) Switch capacitors on o the supply after the load has been applied and

    switch off the supply before or with the load removal.

    Harmonic Power Factor correction is not applied to circuits that draw either

    discontinuous or distorted current waveforms.

    Most electronic equipment includes a means of creating a DC supply. This

    involves rectifying the AC voltage, causing harmonic currents. In some

    cases, these harmonic currents are insignificant relative to the total load

    current drawn, but in many installations, a large proportion of the current

  • 7/27/2019 Apfc Analog Thesis

    19/40

    drawn is rich in harmonics. If the total harmonic current is large enough,

    there will be a resultant distortion of the supply waveform which can

    interfere with the correct operation of other equipment. The addition of

    harmonic currents results in increased losses in the supply.

    Power factor correction for distorted supplies cannot be achieved by the

    addition of capacitors. The harmonics can be reduced by designing the

    equipment using active rectifiers, by the addition of passive filters (LCR) or

    by the addition of electronic power factor correction inverters which restore

    the waveform back to its undistorted state. This is a specialist area requiring

    either major design changes, or specialized equipment to be used.

  • 7/27/2019 Apfc Analog Thesis

    20/40

    UNIT-3

    WORKING METHODOLOGY

    3.1 BLOCK DIAGRAM

  • 7/27/2019 Apfc Analog Thesis

    21/40

    FIG 3.1

    3.2 CIRCUIT DIAGRAM

  • 7/27/2019 Apfc Analog Thesis

    22/40

    FIG 3.2

  • 7/27/2019 Apfc Analog Thesis

    23/40

    3.3 COMPONENT DESCRIPTION

    CURRENT TRANSFORMERS

    Principle of operation of CT:

    A current transformer is defined as as an instrument transformer

    in which the secondary current is substantially proportional to the

    primary current (under normal conditions of operation) and differs

    in phase from it by an angle which is approximately zero for an

    appropriate direction of the connections.

    Current transformers are usually either measuring or

    protective types.

  • 7/27/2019 Apfc Analog Thesis

    24/40

    FIG 3.3

  • 7/27/2019 Apfc Analog Thesis

    25/40

    Related Terms:

    1) Rated primary current:

    The value of primary current which appears in the designation of the

    transformer and on which the performance of the current transformer

    is based.

    2) Rated secondary current:

    The value of secondary current which appears in the designation of

    the transformer and on which the performance of the current

    transformer is based.

    Typical values of secondary current are 1 A or 5 A. In the case of

    transformer differential protection, secondary currents of 1/ root 3 A

    and 5/ root 3 A are also specified.

    3) Rated output:

    The value of the apparent power (in volt-amperes at a specified power

    (factor) which the current transformer is intended to supply to the

    secondary circuit at the rated secondary current and with rated burden

    connected to it.

  • 7/27/2019 Apfc Analog Thesis

    26/40

    12-0-12 Transformer

    Transformers are composed of a laminated iron core with one or more

    windings of wire. They are called transformers because they transform

    voltage and current from one level to another. An alternating current

    flowing through one coil of wire, the primary, induces a voltage in one or

    more other coils of wire, the secondary coils. It is the changing voltage

    of AC current that induces voltage in the other coils through the changing

    magnetic field. DC voltage such as from a battery or DC power supply

    will not work in a transformer. Only AC makes a transformer work. The

    magnetic field flows through the iron core. The faster the voltage

    changes, the higher the frequency.

    The lower the frequency, the more iron is required in the core for the

    efficient transfer of power. In the USA, the line frequency is 60 Hertz

    with a nominal voltage of 110 volts. Other countries use 50 Hertz, 220

    volts. Transformers made for 50 Hertz must be a little heavier than ones

    made for 60 Hertz because they must have more iron in the core. Line

    voltage can vary a little and usually runs between 110 volts and 120 volts

    or between 220 and 240 volts depending on country or power

    connections. A house in the USA has 220 volts coming in but is split to

    two legs of 110V by grounding the centre tap.

  • 7/27/2019 Apfc Analog Thesis

    27/40

    The ratio of input voltage to output voltage is equal to the ratio of turns

    of wire around the core on the input side to the output side. A coil of

    wire on the input side is called the primary and on the output side is

    called the secondary. There can be multiple primary and secondary coils.

    The current ratio is opposite the voltage ratio. When the output voltage is

    lower than the input voltage, the output current will be higher than the

    input current. If there is 10 times the number of turns of wire on the

    primary than the secondary and you put 120 volts on the primary, you

    will get 12 volts out on the secondary. If you pull 2 amps out from the

    secondary, you will only be using 0.2 amps or 200 milliamps going into

    the primary.

    Transformers can be built so they have the same number of windings on

    primary and secondary or different numbers of windings on each. If they

    are the same, the input and output voltage are the same and the

    transformer is just used for isolation so there is no direct electrical

    connection (they are only linked through the common magnetic field). If

    there are more windings on the primary side than the secondary side, then

    it is a step down transformer. If there are more windings on the primary

    side, then it is a step up transformer.

    A transformer can actually be used in reverse and will work fine. For

    example, if you have a step up transformer built for transforming 120

  • 7/27/2019 Apfc Analog Thesis

    28/40

    volts to 240 volts, you can also use it for a step down transformer by

    putting 240 volts into the secondary side and you will get 120 volts on

    the primary side. Effectively, the secondary becomes the primary and

    vice versa.

    Transformer Power Ratings

    Voltage is measured in volts, current is measured in amps, and the unit of

    measure for power is watts. Watts is equal to the volts times the amps.

    There is a little loss of power in a transformer due to the combination of

    resistance and reactance. Reactance is similar to resistance except it is the

    resistance to an AC current or more technically, the resistance to change

    in a change in current due to the change in the field created. This heat is

    what limits the amount of current or power a transformer can handle. The

    higher the current, the more heat is produced. When the wires get too

    hot, the insulation breaks down and shorts with adjacent wires which

    cause more heat which eventually melts wires and ruins the transformer.

    A basic transformer has no additional components and so nothing to

    protect it from overloading. If you were to connect the two output wires

    directly together, that will constitute a short circuit and cause far too

    much current to flow in both the primary and secondary and you will

    burn out the transformer. In the same way, if you use the transformer to

    power a hot wire foam cutter and you are using a wire with too little

  • 7/27/2019 Apfc Analog Thesis

    29/40

    resistance for your foam cutter, you will burn out your transformer if you

    don't have it protected by a proper value fuse or breaker. It has to be

    made sure that the wire resistance, in other words, the gage or diameter,

    and the length is correct to limit the amount of current to under the rating

    of the transformer.

    The higher the current, the larger the wires need to be that carry that

    current. When the wires are larger, there is less resistance and so less

    heat. The power that is changed to heat and lost can be calculated as

    P=I2R. That means that if you double the current, the power lost to heat

    increases by four times. If the transformer is a step down transformer,

    then there will be more current on the output and so the wire in the

    secondary windings will be heavier than the primary. The reverse is true

    for a step up transformer.

    A transformer may be rated in Amps, Volt-Amps (VA), or Watts (W).

    For small transformers, VA and Watts is the same thing for all practical

    purposes. In large industrial transformers, power factors get involved

    and the two can be different. If the transformer is rated in amps, it

    usually says X amps at X volts and is rated on the output or secondary

    side. A 120V transformer with 24V out rated at 2 amps means that you

    can only safely pull 2 amps from the secondary side. You can find the

  • 7/27/2019 Apfc Analog Thesis

    30/40

    power rating of the transformer by multiplying the rated amps times the

    output voltage so 2 X 24 = 48 watts.

    If the transformer is rated in VA or watts, you can calculate the

    maximum allowable output current by dividing the VA or watts by the

    output voltage. So if the transformer is rated at 48 VA with 24 volts

    output, the allowable output current is 48 / 24 = 2 amps.

    Transformer Configurations

    A 120 volt transformer with two wires in and two wires out is very

    simple. You hook up the two wires on the primary side, the 120V side,

    to a wall outlet and your output voltage is on the two wires coming from

    the secondary side.

    When a transformer is shown in an electronic circuit, it is shown as a

    diagram like shown here. The parallel lines represent the laminated iron

    core, the curved lines represent the primary and secondary windings, the

    circles represent the terminations whether terminals or short wires.

    Centre Tap

    A common configuration is a centre tap or CT. The secondary side has

    three wires out. The middle wire on the output side is attached to the

  • 7/27/2019 Apfc Analog Thesis

    31/40

    secondary coil, usually at the middle. If the winding ratio is 5 to 1, then

    with 120V input, you get 24 volts output on the two outside wires but if

    you connect an outside wire and the centre wire, you get 12 volts because

    you are using only half the secondary winding making the connection a

    10 to 1 ratio. If the transformer is rated at 2 amps, you still can only use

    2 amps output whether you use 12 volts or 24 volts. Often the centre tap

    is grounded so you then have two 12 volt sources that can be used to

    make + and - 12V DC after running through a converter (rectifier and

    filter).

    Power Supply Diagram

    ELECTRO MAGNETIC RELAY:

  • 7/27/2019 Apfc Analog Thesis

    32/40

    These are varying much reliable devices and widely used on field. The

    operating frequency of these devices are minimum 10-20ms.That is 50Hz

    100Hz.The relay which is used here can care 25mA currents continuously.

    The electromagnetic relay operates on the principle magnetism. When the

    base voltage appears at the relay driver section, the driver transistor will be

    driver transistor will be

  • 7/27/2019 Apfc Analog Thesis

    33/40

    driven into saturation and allow to flow current in the coil of the relay,

    Which in turn create a magnetic field and the magnetic force produced

    due to that will act against the spring tension and close the contact coil.

    Whenever the base voltage is withdrawn the transistor goes to cutoff .So

    no current flow in the coil of the relay. Hence the magnetic field

    disappears so the contact point breaks automatically due to spring

    tension. Those contact points are isolated from the low voltage supply, so

    a high voltage switching is possible by the help of electromagnetic relays.

    The electromagnetic relays normally having 2 contact points. Named as

    normally closes (NC) , normally open (NO). Normally closed points will

    so a short CKT path when the relay is off. Normally open points will so a

    short CKT path when the relay is energized.

  • 7/27/2019 Apfc Analog Thesis

    34/40

    2.5UF 400V 450VAC CBB60A CAPACITOR:

    2.5UF 400V 450VAC CBB60A Motor Run Capacitors takes heavy-edge

    metalized Al/Zn PP film or web-like fuse film as dielectric. Its

    components are sealed with flame-retardant epoxy resin. It has cylindrical

    outline with high reliability and stability.CBB60 capacitor has features of

    small size, light weight, small tangent in waste angle, and good self-

    concrescence. Applicable to start and operation with 50/60Hz. A. C

    single motor, specially suit for micro pump, baric pump, micro motor and

    so on.

  • 7/27/2019 Apfc Analog Thesis

    35/40

    Transistor SL100:

    SL100 is a general purpose, medium power NPN transistor. It is mostly

    used as switch in common emitter configuration. The transistor terminals

    require a fixed DC voltage to operate in the desired region of its

    characteristic curves. This is known as the biasing. For switching

    applications, SL100 is biased in such a way that it remains fully on if

    there is a signal at its base. In the absence of base signal, it gets turned off

    completely.

    The emitter leg of SL100 is indicated by a protruding edge in the

    transistor case. The base is nearest to the emitter while collector lies at

    other extreme of the casing.

    Rated Capacitance Motor Run Capacitor

    Tolerance 2.5uF

    Rated Voltage 5%

    Brand 400/450VAC

    Housing Material Cinco or Custom-made

    Housing Shape Plastic

    Terminal Round

    Dielectric Material 2+2 6.35mmx0.8 pins

    Operating Temperature Metallised Polypropylene Film

    Frequency 25/70/21

    explosion-proof Class 50/60Hz

    P0

  • 7/27/2019 Apfc Analog Thesis

    36/40

  • 7/27/2019 Apfc Analog Thesis

    37/40

    UNIT-4

    CONCLUSION

    &

    RESULT

    CONCLUSION:

    It can be concluded that power factor correction techniques can be

    applied to the industries, power systems and also households to make

    them stable and due to that the system becomes stable and efficiency of

    the system as well as the apparatus increases. The use of microcontroller

  • 7/27/2019 Apfc Analog Thesis

    38/40

    reduces the costs. Due to use of microcontroller multiple parameters can

    be controlled and the use of extra hard wares such as timer, RAM, ROM

    and input output ports reduces. Care should be taken for overcorrection

    otherwise the voltage and current becomes more due to which the power

    system or machine becomes unstable and the life of capacitor banks

    reduces.

    ADVANTAGES OF IMPROVED POWER FACTOR:

    Reactive power decreases

    Avoid poor voltage regulation

    Overloading is avoided

    Copper loss decreases

    Transmission loss decreases

    Improved voltage control

    Efficiency of supply system and apparatus increases

    ADVERSE EFFECT OF OVER CORRECTION:

    Power system becomes unstable

    Resonant frequency is below the line frequency

    Current and voltage increases

  • 7/27/2019 Apfc Analog Thesis

    39/40

    REFERENCES:

    P. N. Enjeti and R martinez, A high performance si ngle phase

    rectifier with input power factor correction ,IEEE Trans. Power

    Electron..vol.11,No.2,Mar.2003.pp 311-317

    J.G. Cho,J.W. Won,H.S. Lee , Reduced conduction lo ss zero-

  • 7/27/2019 Apfc Analog Thesis

    40/40

    voltage-transition power factor correction converter with low cost,IEEE

    Trans.Industrial Electron..vol. 45,no 3,Jun. 2000,pp395-400

    The 8051 Microcontroller and Embedded Systems by

    Muhammad Ali Mazidi and Janice Gillispie Mazidi

    8052 simulator for windows version 3.604

    25Jun1999,[email protected]

    www.fsinc.com

    www.keil.com

    Eleectric power industry reconstructing in India,Present scenario

    and future prospects,S.N. Singh ,senior member,IEEE and S.C.

    Srivastava,Senior Member,IEEE

    Power factror correction, Reference design from Freescale

    http://www.freescale.com