\J; CITY OF SANTA ROSA , IMPROVEMENT PLANS FOR STATION 2 EMERGENCY GENERATOR REPLACEMENT AND STATION 3 POWER FILTER INSTALLATION RECORD PLAN DATA . PROJECT END ----.----·---.. ·-··· ··-----·---·-······---------------·-------·------- -- -- -- - -------- --------··--------- ------------ --- _ __ _________ ___ ··- ... ____ _ Sl)PERINTEN[lENT; UNDERGROUND FOREMAN Si;\llJER_!'l!'E.D'.!'E: ....... -.. -·-- -··--···-·· ·---··-·· -·-···--·--- . !\.'lANl.lFACTURER· SEWER FITTINGS M_A_NUF_ACTi,JRf;_F?;: __ _____________ .. ______________________ -----·--·--·-·---------- .. WAT.ER .PWE.Tl.P.E: Ml\Nufl\C_TV""IL ...... . WATER VALVE "1ANUFA(;Tl)R.ER• ........ . WATER FITTINGS Ml\NV.El\GT.i,IRf'.R: .. MAN_l!EAQTURER .. ___ . FIRE H)'DRANT TYPE f>Al\N1'EAGTliRER; .. IN§!'E_CTOR ............. . CONSTRUCTION M.ANt\G_t;_f?.;. -"-· .. REQQBQ.!'LAN-8 BY• -- r - N I :::u '! '-- I .----- 1 ----- - -- - ----··-· ---- CONTRACT No. C02150 SEPTEMBER, 2018 ··a! I \..._; I '• . -- ·-- ---- -' .. --··---· .. : .... "" - LOCATION MAP NOT TO SCALE i '. \ \ PS 53 Location 3503 Thomas Lake Harris Dr ---- --- -, ' - ---- - . PS 52 Location 1395 Fountaingrove · · ······ - ··-- ·- -- ·· Parkway INDEX TO SHEETS STATION 2 EMERGENCY GENERATOR REPLACEMENT PREPARED BY WEST YOST ASSSOCIATES 1 TITLE SHEET, LOCATION MAP, INDEX OF DRAWINGS 2 LEGEND, GENERAL NOTES & ABSREVIA TIONS 3 DEMOLITION PLAN 4 SITE & MECHANICAL PLAN 5 ELECTRICAL SYMBOLS & ABBREVIATIONS, E1 6 EXISTING MOD & MCC ONE LINE DIAGRAM, E2 7 BUILDING ELECTRICAL PLANS, E3 8 EXAMPLE INTERCONNECT DIAGRAM, E10 9 TYPICAL ELECTRICAL DETAILS N0.1, E11 10 INSTRUMENTATION SYMBOLS & ABBREVIATIONS, 11 11 AUXILIARY SYSTEMS P&ID, 12 STATION 3 POWER FlLTER INSTALLATION PREPARED BY BRELJE & RACE CONSULTtNG ENGINEERS 12 13 POWER FILTER, ABBREVIATIONS, LEGEND, NOTES POWER FILTER ELECTRICAL PLANS BEFORE EXCAVATING CALL U.S.A. UNDERGROUND SERVICE ALERT 814 TWO WORKING DAYS BEFORE ALL PLANNED WORK OPERATIONS WEST YOST ASSOCIATES 2020 ·Research ?ark Drive Suite 100 Davis, CaHfomia 95618 -- ----------------------------------- (530) 756-5905 FAX (530) 756-5991 r . J _,_: <-' ' l ,_i ' 1_} i : ·-··; ---· !l.L -, ' ,-, >·, c.J ' ,-, , f·· .. <l ']' C- " I ..... ·_,_, i <.L: ' ; . ' _\ __ i , : I ,__ ! l..L;: (/) ,c .. :; ! i :.t;:. ; - . ' . L __ ; ' ,-,-, -,-, -- - -- - . , .. r ··, T '\ !--\ r_:· - ',·\ "<\/'

Upload: others

Post on 28-Dec-2021

2 views

Category:

Documents


0 download

TRANSCRIPT

\J;

~ CITY OF SANTA ROSA , IMPROVEMENT PLANS FOR

STATION 2 EMERGENCY GENERATOR REPLACEMENT AND STATION 3 POWER FILTER INSTALLATION

RECORD PLAN DATA PR()_J~C::I§Il\RL . PROJECT END ----.----·---.. ·-··· ··-----·---·-······---------------·-------·------- -- -- -- - -------- --------··--------- ------------ ---

Cl.~_N. l:;(lNIRJl<::TQR~_ _ __ _________ ___ ··- ... ____ _ Sl)PERINTEN[lENT; UNDERGROUND ~QNTR_A_9T.9R: FOREMAN

Si;\llJER_!'l!'E.D'.!'E: ....... -.. -·-- -··--···-·· ·---··-·· -·-···--·--- . !\.'lANl.lFACTURER·

SEWER FITTINGS M_A_NUF_ACTi,JRf;_F?;: __ MJj_._Ji'16JS.1JE8Q.I.t,,JJ~J;J~~-- _____________ .. ______________________ -----·--·--·-·---------- .. WAT.ER .PWE.Tl.P.E: Ml\Nufl\C_TV""IL ...... . WATER VALVE "1ANUFA(;Tl)R.ER• ........ . WATER FITTINGS Ml\NV.El\GT.i,IRf'.R: ..

MAN_l!EAQTURER .. -· ___ . FIRE H)'DRANT TYPE f>Al\N1'EAGTliRER; .. IN§!'E_CTOR ............. . CONSTRUCTION M.ANt\G_t;_f?.;. -"-· .. REQQBQ.!'LAN-8 BY•

-- r -

N

I

:::u '! .~>

'-- I .----- 1

----- - -- - ----··-· ----

CONTRACT No. C02150

SEPTEMBER, 2018

··a! ,~-- I

\..._;

I '• .

-- ·-- ---- - ' .. --··---· .. : .... ~. "" -

LOCATION MAP NOT TO SCALE

i '.

2~ \ \ ~:'

'-)~;

PS 53 Location 3503 Thomas Lake Harris Dr ---- --- -,

' ----- ~ -.

PS 52 Location 1395 Fountaingrove · · ······ - ··-- ·- -- ·· Parkway

INDEX TO SHEETS STATION 2 EMERGENCY GENERA TOR REPLACEMENT PREPARED BY WEST YOST ASSSOCIATES

1 TITLE SHEET, LOCATION MAP, INDEX OF DRAWINGS

2 LEGEND, GENERAL NOTES & ABSREVIA TIONS

3 DEMOLITION PLAN

4 SITE & MECHANICAL PLAN

5 ELECTRICAL SYMBOLS & ABBREVIATIONS, E1

6 EXISTING MOD & MCC ONE LINE DIAGRAM, E2

7 BUILDING ELECTRICAL PLANS, E3

8 EXAMPLE INTERCONNECT DIAGRAM, E10

9 TYPICAL ELECTRICAL DETAILS N0.1, E11

10 INSTRUMENTATION SYMBOLS & ABBREVIATIONS, 11

11 AUXILIARY SYSTEMS P&ID, 12

STATION 3 POWER FlLTER INSTALLATION PREPARED BY BRELJE & RACE CONSUL TtNG ENGINEERS

12

13

POWER FILTER, ABBREVIATIONS, LEGEND, NOTES

POWER FILTER ELECTRICAL PLANS

BEFORE EXCAVATING CALL U.S.A.

UNDERGROUND SERVICE ALERT 814

TWO WORKING DAYS BEFORE ALL PLANNED WORK OPERATIONS

WEST YOST

ASSOCIATES

2020 ·Research ?ark Drive Suite 100 Davis, CaHfomia 95618 -- -----------------------------------

(530) 756-5905 FAX (530) 756-5991

r

. J

_,_: <-' ' l ,_i ' 1_} i

: ·-··; ---· !l.L

-, ' ,-, >·, c.J

'

,-, L.~ , ~'-~

f·· .. <l

']'

C-" I .....

·_,_, i

<.L:

' ; . ' _\ __ i

, : I

,__ !

~--!

l..L;:

(/) ,c .. :; ! i :.t;:. ,_-~ ;

--~-

- .

'

.

L __ ; ' ,-,-,

-,-,

-- - -- - . , .. r ··, !\~ T '\ !--\ r_:· ~· - ',·\

"<\/'

(])

~I ·-2 CL

m

" N

IX)

0 N ....___ n ....___ m

CJ' 3: u N 0 O· I

<D L')

I CD

I

""

I

" -./ 0 Ul 0

a:: 0 ~

c 0

CJ)

u <D 0

"" ./ 8 c (j)

u ./ z

LEGEND - CIVIL

·~"0("0(~:e«"0("0(v ::C.7~7~7~7~~7~/~/' NATURAL GROUND OR GRADE x73.s EXISTING SPOT ELEVATION 4 •.. :J CONCRETE

.__ ______ ....__.]_." SECTION

~w;~w~~1 1 1:~;1 1 11 1 1W;-,-;Lll COMPACTED SOIL ~ FINISH GRADE SPOT ELEVATION

EXISTING FENCE 8HV11 TEMPORARY SURVEY MONUMENT

EXiSTING GRADE CONTOURS PERMANENT SURVEY MONUMENT

EXISTING PIPELINE

--( 12" ML )i--- NEW PIPELINE EXISTING FACILITY

NEW FACILITY ~- - - - - NEW PIPELINE UNDER CONCRETE

EXISTING ELECTRICAL CENTERLINE

- / / / / / l / l l / II DEMOLISH ·· · ·· · ···· EXISTING TELEPHONE

PROPERTY LINE -0~--·-0------ IRON FENCE

---------- EASEMENT LINE x CHAIN LINK FENCE

--·- SWALE SLOPE

LEGEND - PIPING

SINGLE LINE DOUBLE LINE SINGLE LINE DOUBLE LINE SINGLE LINE DOUBLE LINE

E:m 3 FLANGED JOINT

F----fi-= PLAIN OR GROOVED END ---~ MECHANICAL COUPLING

'=--= ~ PUSH ON, MECHP..NICAL OR "--- Q.:=::;1-~ BALL & SOCKET JOINT

E::- f ~ WELDED JOINT

~~ SLEEVE TYPE MECHANICAL ~COUPLING

.,_+RESTRAINED SLEEVE TYPE MECHANICAL COUPLING

f!li ~ FLANGED COUPLING ~lf.::::11- ADAPTER

C+-

GATE VALVE (NORMALLY OPEN)

-l'-f- BUTTERFLY VALVE

GATE VALVE (NORMALLY CLOSED)

PLUG VALVE (NORMALLY OPEN)

PLUG VALVE (NORMALLY CLOSED)

BALL VALVE (NORMALLY OPEN)

BALL VALVE (NORMALLY CLOSED)

--1)(1-

-i'/1-~

~!-

~-~

--!-

GLOBE VALVE

CHECK VALVE

BALL CHECK VALVE

SOLENOID VALVE

DIAPHRAGM OPERATED VAL VE

MOTOR OPERATED VALVE

SECTION & DETAIL DESIGNATIONS -----------~c_;;,;_;o__;;...c....;.;_-"-'-.;._;;;__:_;:_:=_ _____ -·--·--

SECTION CUT ON DWG 21 ~SECTION LETTER

~- DRAWING WHERE SECTION APPEARS

ON DWG 2.3 THIS IS IDENTIFIED AS:

SECTION ®=-- SECTION NUMBER 21

- DRAWING FROM WHICH SECTION WAS TAKEN

DETAILS ARE CROSS REFERENCED IN A SIMILAR MANNER, EXCEPT THAT DETAILS ARE IDENTiFIED BY NUMBER RATHER THAN LETTER

PIPING DESIGNATIONS

NEVI PIPING ( 4" w)

PIPE SIZj l._ PIPING SYSTEM ABBREVIATION

EXISTING PIPING FUTURE PIPING

~4"' Vi -·- .,

-J- RESTRAINED FLANGED COUPLING ADAPTER

E Ill =--:;!-GROOVED END Ill ADAPTER FLANGE

£----~ UNION

~ .. ELASTOMER & FABRIC ~-EXPANSION JOINT

~ELBOW UP

~ELBOW DOWN

--i0t-- ~TEE UP

1:1 c:msm=a TEE DOWN

-+-Of-- t=-;J)IB:3 LATERAL UP

!Cl-~ ~LATERAL DOWN

_______N__ .~ CONCENTRIC ----vr-- ~--REDUCER

"I -~ ECCENTRIC ~REDUCER

BASIS OF BEA.:.:...R=IN.:.-=G=S'-----· NORTH 68' 50' 49" EAST BETWEEN CITY OF SANTA ROSA HORIZONTAL CONTROL NETWORK COORDINATE MONUMENTS G-453 & G-1 004_ NAD83 - ZONE 2 - EPOCH 2010.00

BENCHMARK CITY OF SANTA ROSA SURVEY CONTROL POINT #4, AS REFERENCED IN CITY OF SANTA ROSA FIELDBOOK 179, PAGE 03.

ABBREVIATIONS ·------AB AC AFF AL, ALUM APPROX ARV ASPH BC BF BTW BV, BFV CL, (t_ CLR CL.SM

co CONC CMU CV CY DI DIA, 'Ii DIP DTL DWG EA EF EJF EL ELEC EP EQUIP EW EX (E) EXP FF FH FCA

FCO FD FL, If. FLG FO FRP

FOC FT, , GA CALV GB GS GSP GV HC HP

HPI

HORZ IE IJTS

IN, " INV LAT LF

AGGREGATE BASE ASPHALT CONCRETE ABOVE FINISH FLOOR ALUMINUM APPROXIMATE AIR RELIEF VALVE ASPHALT BEGIN CURVE BLIND FLANGE BETWEEN BUTTERFLY VALVE CENTER LINE CLEAR CONTROL LOW STRENGTH MATERIAL CLEAN OUT CONCRETE CONCRETE MASONRY UNIT CHECK VALVE CUBIC YARDS DRAIN INLET DIAMETER DUCTILE IRON PIPE DETAIL DRAWING EACH EACH FACE EXPANSION JOINT FILLER ELEVATION ELECTRIC EDGE OF PAVEMENT EQUIPMENT EACH WAY EXISTING EXPANSION FINISHED FLOOR FIRE HYDRANT FLANGED COUPUNG ADAPTER FLOOR CLEANOUT FLOOR DRAIN FLOW LINE FLANGE FIBER OPTIC FIBERGLASS REINFORCED PLASTIC FACE OF CURB FEET, FOOT GAUGE GALVANIZED GRADE BREAK GROUND SURFACE GALVANIZED STEEL PIPE GATE VALVE HANDICAPPED HIGH POINT IN PVMT, HIGH PRESSURE HORIZONTAL POINT OF INFLECTION HORIZONTAL INVERT ELEVATION INSULATING JOINT TEST STATION INCH INVERT LATERAL LINEAL FEET

MAX MIN MH MJ MON MOV (N), N NJ.A. No., # NTS oc OD OF OH PD PE PL, Ii'. PSV PRV PSF PSI PG PV PVC PVM'T QRC R RCP REQ'D REV RR R/W s SCH SD SDMH SPD SQ SS SSB SSMH SST STA ST STD STL SVC SW T T&B TOC TOS

TYP UG UPRR VAR VTR w W/ W/O ws WSP WWF WV

PIPING SYSTEM ABBREVIATIONS

BD BUILDING DRAIN CS CHLORINE SOLUTION D DRAIN IRR IRRIGATION PTW PUMP TO WASTE RW RAW WATER SD STORM DRAIN

MAXIMUM MINIMUM MANHOLE MECHANICAL JOINT MONUMENT, MONITORING MOTOR OPERATED VALVE NEW, NORTH NOT IN CONTRACT NUMBER NOT TO SCALE ON CENTER OUTSIDE DIAMETER OVERFLOW OVERHEAD PULSATION DAMPENER PLAIN END PLATE, PROPERTY LINE PRESSURE RELIEF VALVE PRESSURE REDUCING VALVE POUNDS PER SQUARE FOOT POUNDS PER SQUARE INCH PRESSURE GAUGE PLUG VALVE POLYVINYL CHLORIDE PIPE PAVEMENT QUICK RELEASE COUPLING RADIUS REINFORCED CONC PIPE REQUIRED REVISION RAILROAD. RIGHT OF WAY SOUTH, SLOPE SCHEDULE STORM DRAIN STORM DRAIN MANHOLE SUMP PUMP DISCHARGE SQUARE SANITARY SEWER STAINLESS STEEL BOLT SANITARY SEWER MANHOLE STAINLESS STEEL STATION STREET STANDARD STEEL SERVICE SIDEWALK TELEPHONE TOP & BOTTOM TOP OF CONCRETE TOP OF STEEL OR TOP OF STRUCTURAL FRAME TYPICAL UNDERGROUND UNION PACIFIC RAILROAD VARIOUS VENT THROUGH ROOF WEST WITH WITHOUT WATER SURFACE WELDED STEEL PIPE WELDED WIRE FP.BRIC WATER VALVE

SL SAMPLE LINE SS SANITARY SEWER TW TREATED WATER W WATER

GENERAL NOTES

1. ALL WORKMANSHIP, MATERIALS AND CONSTRUCTION SHALL CONFORM TO THE CITY OF SANTA ROSA DESIGN AND CONSTRUCTION STANDARDS, THE SPECIAL PROVISIONS FOR THIS PROJECT AND THE STATE STANDARD SPECIFICATIONS AND STANDARD PLANS. THE CONTRACTOR IS RESPONSIBLE FOR UNDERSTANDING ALL STANDARDS PERTAINING TO THIS PROJECT.

2. THE LOCATIONS OF UNDERGROUND UTILITIES SHOWN ON THE PLANS ARE BASED ON THE BEST AVAILABLE INFORMATION. THE CONTRACTOR SHALL POTHOLE AND DETERMINE THE EXACT LOCATION OF ALL EXISTING UTILITIES IN ACCORDANCE WITH THE SPECIAL PROVISIONS.

3. ALL WORK AND EQUIPMENT SHALL COMPLY WITH FEDERAL AND STATE OCCUPATIONAL HEALTH AND SAFETY ADMINISTRATION (OSHA) REQUIREMENTS_

4. DAMAGE TO CITY OR PRIVATE PROPERTY CAUSED BY THE CONTRACTOR 'S OPERATIONS SHALL BE REPAIRED OR REPLACED AT THE CONTRACTOR 'S EXPENSE AND TO THE SATISFACTION OF THE ENGINEER.

5. THE CONTRACTOR SHALL PROTECT AND PRESERVE CITY MONUMENTS WHEREVER POSSIBLE. THE CONTRACTOR SHALL COORDINATE WITH THE PROJECT INSPECTOR 10 WORKING DAYS (MIN.) PRIOR TO DISTURBING ANY MONUMENT.

6. OVERHEAD UTILITY SERVICE DROPS ARE NOT SHOWN ON THE PLANS. THE CONTRACTOR SHALL INVESTIGATE THE SITE PRIOR TO CONSTRUCTION AND BE AWARE OF LIMITED OVERHEAD CLEARANCES.

7_ THE CONTRACTOR SHALL REMOVE AND REPLACE SIDEWALK AND CONCRETE PLANTER STRIPS TO THE NEAREST TRANSVERSE SCORE MARK ON BOTH SIDES OF NEW SEWER LATERALS, WATER SERVICES AND FIRE HYDRANT INSTALLATIONS.

8. THE CONTRACTOR IS CAUTIONED THAT THE LOCATIONS OF UNDERGROUND OBSTRUCTIONS SHOWN ON THE PLANS ARE APPROXIMATE ONLY AND SHOULD NOT BE TAKEN AS FINAL OR COMPLETE. THE CONTRACTOR IS CAUTIONED THAT THE C!TY OF SANTA ROSA AND THE ENGINEER ASSUME NO RESPONSIBILITY FOR OBSTRUCTIONS THAT MAY BE ENCOUNTERED.

SITE SPECIFIC SEISMIC CRITERIA

1. RISK CATEGORY: Iii

2. SITE-SPECIFIC SPECTRAL RESPONSE COEFFICIENTS:

I SHORT PERIOD MAPPED MAXIMUM CONSIDERED EAfHHQUAKE, 5 PERCENT DAMPED: SS = 2.466G i .I

i 1 SECOND PERIOD MAPPED MAXIMUM CONSIDERED EARTHQUAKE, 5 PERCENT DAMPED: S1 = L022G J I SHORT PERIOD DESiGN SPECTRAL RESPONSE ACCELERATION, 5 PERCENT DAMPED: sos - 1.644G :

I 1 SECOND PERIOD DESIGN SPECTRAL RESPONSE ACCELERATION, 5 PERCENT DAMPED: SD1 = 1.022G l l'-------------------------------..L------j

3. SITE CLASS: D

4. SEISMIC DESIGN CATEGORY: D, UNLESS NOTED OTHERWISE

5. COMPONENT IMPORTANCE FACTOR, IP: MECHANICAL AND ELECTRICAL EQUIPMENT: USE 1.5

6. DO NOT USE MORE THAN 60 PERCENT OF THE WEIGHT OF MECHANICAL AND ELECTRICAL EQUIPMENT FOR DESIGNING ANCHORS FOR RESISTING OVERTURNING DUE TO SEISMIC FORCES

,_ "' I.LI

CONTRACT NO. C02150

u 0 Vl Vl <(

>­ro

w ,_ <IC o.

0 z

SHEET 2 of 13

FILE NO. 2018-0004

-0 n I

({) L')

I ({)

-I U)

0

"' / c 0

c:; () :0 TI 0 L

Q / 0 <(

11 -"'. c 0

f--

Q:'.

lD

Q:'.

<( (5)

Q:'.

Ul Ul I

<D

I

"' / 'a

"' 0 Q:'.

0 ~

c 0

(/) -0

0

u / z

I

I .;O;:-

co

I I w

/

I

/

-(E) FLOW METER

VAULT I I

:r====lT I I c;:! 11 I

z I I

I ;i I :

I Q . I > '1

' ~ jt ' I.' v I

(E) CONCRETE ~L':::i ==-=-- 1

J1

RETAINING WALL. 7,,.::i, ~ ty I

""

(E) CHAIN LINK FENCE/

0 3

SCALE IN }'EET

I

I I

I

l_.

(E) WATER

(E) ELECTRICAL VAULTS-

(E) PUMP ROOM AND ELECTRICAL ROOM

REMOVE AND DISPOSE OF (E) NATURAL GAS PIPE

. I

I I I i ' ,.....J

w

// /

NOTES:

1. COORDINATE DEMOLITION PLAN WITH CITY WATER DEPARTMENT.

2. REMOVE EXISTING LOUVERS DURING CONSTRUCTION. REINSTALL AFTER INSTALLATION OF NEW GENERATOR. MAINTAIN BUILDING SECURITY DURING CONSTRUCTION BY SECURING OPENING OUTSIDE OF WORKING HOURS.

3. REMOVE AND DISPOSE OF EXISTING MUFFLER ON ROOF. SEE DETAIL 1/- AND 2/-.

4. REMOVE AND DISPOSE OF EXISTING SUPPLY FAN AND CABINET ON ROOF. SEE DETAIL 1 /­AND 2/-.

5. AFTER REMOVAL OF EXISTING MUFFLER AND SUPPLY FAN FROM ROOF, WEATHER PROTECT AND SECURE OPENINGS UNTIL NEW MUFFLER AND SUPPLY FAN ARE INSTALLED. MAINTAIN BUil.DiNG SECURITY DURING CONSTRUCTION BY SECURING OPENINGS OUTSIDE OF WORKING OURS

/ (E) EDGE OF PAVEMENT,

I

6. CITY HAS CONTACTED PG&E FOR REMOVAL OF GAS METER. CONTRACTOR TO VERIFY GAS METER/SERVICE REMOVAL PRIOR TO CONSTRUCTION.

/

(E) ELECTRICAL VAULT, PROTECT IN PLACE

REMOVE AND DISPOSE OF (E) NATURAL GAS METER, VALVE & ASSY, & CAP (E) NATURAL GAS PIPE, SEE NOTE 5 r-01t t. NOTE 2

±

REMOVE (E) METAL VENT HOOD

L _ _.,,... ___ J CUT (E) CONDUIT FLUSH AND FILL WiTH NON-SHRINK GROUT

.

(E)

I

I 11

I

I

I

I . ·. I

-- __ , __ · - -·-- ~

/

i I '

I

REMOVE AND DISPOSE ' , OF {t:) CABINET AND VAf'ORIZORS ··

, ... (E) OPENINGS TO. BE REUSED FOR (N) FUEL LINES

/ REMOVE AND DISPOSE OF (E) GENERATOR, !ff SUPPORT RAILS AND AFTE~,,e:QOLER PUMP SYSTEM,·' .

/ /

~/

(E) OPENING )fO BE REUSED FOR (N) µ:ECTRICAL CONDUIT, SEE SHJ/7 /

/ /

/

/

EXISTING MUFFLER, SUPPLY FAN AND CABINET

DETAIL0 NOT TO SCALE

COORDINATE EVACUATION OF ,/' (E) PROPANE GAS & REMOVE &//

DISPOSE OF (E) PROPANE JANK

~ . /' ~:: i j

//

,,.,-/--

SUPPLY FAN

/''- -

EXISTING MUFFLER AND SUPPLY FAN

DETAILS NOT TO SCALE

,._ "'

CONTRACT NO. C02150

-,.,.

SHEET 3 OF 13

FILE NO. 2018-0004

u 0 Vl

"' <(

c:i z

00 -0 N

' ,,,.

'n lD I

'° i ,,,.

/ 0 U)

0 O'.:

0 ~· c 0

(/)

' ' NOTES:

1. CONTRACTOR TO FIELD-VERIFY EXACT LOCATION. DIMENSIONS ARE APPROXIMATE. CONDUITS TO BE iNSTALLED OVERHEAD. COORDINATE CONDUIT LOCATIONS WITH SELECTED GENERATOR.

2. RADIATOR TO BE CENTER-LINED WITH THE OPENING.

3. 1" PE DOUBLE CONTAINED PIPING SYSTEM. CONTRACTOR TO FIELD-RUN, EXACT LOCATIONS OF PIPES WITH ENGINEER'S APPROVAi.. PIPE TO BE INSTALLED ABOVE GRADE.

4. INSTALL NEW CRITICAL GRADE SILENCER ON ROOF. GREENHECK MODEL 1860 VRS 8 51 BY HARCO ENGINE PRODUCTS, OR EQUAL. /

/

/ ,~,

5. INSTALL NEW GRAVITY VENTILl\TOR ON ROOF. MODEL WIH, 56.5"x56.5"x38.5" WITH BIRD AND INSECT SCREEN, OR EQUAL.

L.i.J (i ~-- v EB INSTALL REMOVABLE //

BOLLARDS PER DETAIL·- / /

//

//Y (,N) 500-GALLON FUEL STORAGE

.TANK BY CONVAULT, OR EQUAL WITH EARTHQUAKE RESTRAINTS 6. INSTALL SEISMIC-CERTIFIED GENERATOR WITH VIBRATION ISOLATORS, 250KW, CATERPILLAR C9, OR

EQUAL.

7. INSTALL FUEL LINES THROUGH (E) ±3/4" WALL PENETRATIONS ±4' AFF. EXPAND PENETRATIONS AS NEEDED TO ACCOMMODATE (N) 1" FUEL LINES. SEAL AROUND FUEL LINES WITH FLEXIBLE SEALANT. LOCATE FUEL LINES OVERHEAD WITHIN GENERATOR ROOM. INSTALL PIPE SUPPORTS AT MAXIMUM 5' INTERVALS PER DETAIL 3/-.

METER

'

\ I

(E) CHAIN J: LINK FENCE_/ ;

I () \ l

i .

~ j l ,;, '.:;.: ,; '

·~· '"·- ---·--·-1 l k-'

\'> . ~I

j '

' j .. j );·

t .. ~ -I '

'

I '

I ,, !''

. ;;.·

' (•

(E) WATER VAULT~

"

(E) (E)

(E)

I EDGE OF PAVEMENT

I ASPHALT CURB/

FUEL INLET LINE, SEE NOTE .3-,

(E) TELEPHONE BOX

CONSTRUCT (N) SHEET METAL '·· CONNECTION FROM GENERATOR

RADIATOR TO LOUVER

EXISTING CONCRETE PAD--.. I r ! 1

NEW GEN SET~

' FUEL RETURN LINE,

__ J~(E) ELECtRIC:LEE NOTE 3

7'-0"

RADIATOR, SEE NOTE 2

VAULT

-··•"";'' '"-~··--\/~"··- .. ---w- '""" .,---~-~'ie~'~-•~-~-•••

. .• ·v !

I , 1-, I'

I ' !-·

. I

!

'

I ) l

NEW ELECTRICAL CONDUITS, SEE NOTE 1. f. i

COORDINATE W/ELEC PLANS. COORDINATE , , I i. GENERATOR

SEE NOTE 6

CONDUIT LOCATIONS W/SELECTED GENERATOR---...-h-+--

1 ·, --- • PUMP ROOM AND ELECTRICAL ROOM

i., i1 '•-I~. ·~-------LJt, 'b l . I i i "I h:

I• rl ·~-3'_-_6'_' --ilL'. _____ 1::.'. ______ : ------ -~J--~

v. " . 14' ;,.,

' "

' 'i,

: ! - l

' . :-

'

:;.> ''"'"-·:"":·- --- '' "'"fl'"•-~-,, ~-----·-:-~· --~-,.·~-:,·---~"· '-~------·--" --- . --~~~:------~-----1,::--,,---~--~_.., ... ~- ~-~-'°'." --·

~-'} !!- t> pt. t-ti- J. '" 'vj " ,, ~--

-~--«~.!

0 3

SCALE IN FEET

/>'.

• 4-' -o" 4 • -0 1' /' 4 -o"

~ -~ I ·I ""'° EOU,PMEN'

r·1

I I \;:­

,...--;-...,,.,I I ......... --11

(:->: (/~,)

I -

I I LJ

. . ··:.·

':-.

oi l)- •

- - -~- ... -~~ ..

INSTAl;)( FUEL Lll'jES' THROUGH (E) WAL~/ PENETRATIONS. SEE NOTE 7

,...-..., (E) STACKED I (N) 500-GALLON FUEL

"'l • CONVAULT, OR EQUAL BLOCK WALL~ STORAGE TANK BY

~ I

n I I

© i I LI

·• ..•. A. ..

. (

' I I

: (N) #4 @ 12" OCEW, TOP & SODOM I

: (N) 8' -o"x2' -O"x12"

. .3/4" CHAMFER, TYP

..... VJ

0 >-

-<..'Cl.\t 1 I /AY~ (E) TANK

«~"-;, 1 SLAB\

~ I

I SLAB EXTENSION

'----------~--------- MP.TCH 0 (E) GRADE l-"-r-J....F-l..-.!.-J.-1..Z-1

~~~" ~ ~~ 4. " ••

·~~ ' "

~~ ;·. • 'c ""·it" ~·, ~'~ ~ __._ ~~~~~ INSTALL EARTHQUAKE RESTRAINTS

PER TANK MANUFACTURER RECOMMENDATIONS

DRILL 5/8"¢x6" MIN DEEP HOLE, BLOW CLEAN AND EPOXY DOWEL IN PLACE,

TYP AT ALL (N) #4 DOWELS

TANK SLAB EXTENSION

DETAIL® SCALE: 1"=1 '-0"

L

• 4

• 4

4.

..;.; -a" CLASS 2 AB !;;:

@ 90% AC o

* ELEVATION OF AC BERM RELATIVE TO TANK PAD VARIES

END CAP 4" GALV. MALLEABLE IRON THREADED (SCREWED)

NOTE:

FRAMING CHANNEL 1-%" SQ X 12 GAGE MIN. TYPE 304 SST (LENGTH AS REQUIRED)

PIPE CLAMP--FRAMING CHANNEL TYPE 304 SST

1-%" SST EXPANSION ANCHOR EACH SIDE

ALL COMPONENTS SHALL BE TYPE 304 SST UNLESS OTHERWISE NOTED.

SAFETY LOCK

PREP SURFACE AND APPLY TWO

COATS HIGH GLOSS WHITE PAINT

SEE DETAIL "A"

CUT FROM 1/2"X 6" GAL V. STEEL EYE BOLT

EYE BOLT 2"x 6" GALV. STEEL (TO BE INSTALLED PARALLEL TO EDGE OF PAD)

DETAIL "A"

' ro ...

HANDLES

_.---3-TWO INCH WIDE -- RETROREFLECTIVE

.. ,· • .... •• "<; ......

YELLOW STRIPES

(HORIZONTALLY PLACED)

POST 4" GALV. STEEL PIPE STD SCH. NO. 40

WITH SLEEVE 5" GALV. STEEL PIPE 36" LONG STD SCH. NO. 40

CONCRETE FOOTING

;A </.,<., •. ;.: -THREADED """' ... : ...... -'---1_,...-'-'-'.-'-'"-l COUPLING

15"

CONTRACT NO.

C02150 PIPE SUPPORT 3/8" THROUGH 8" PIPE

DETAIL EB REMOVABLE BOLLARD DETAIL

DETAIL© SHEET 4 OF 13

SCALE: NTS SCALE: NTS FILE NO. 2018-0004

2 w w ~ 2 ll.

Ol 0

" OCJ

0 0

" u n 0 <D

/ u n 0 <D

/ <D

0 N / Cl

& @

A AC AFF Al AIC ALT AM AO AWG B BC BKR c CAP CB CKT COAX COMM CPT CR CT CTQ CTR cu DC DET DI DIAG DISC DO DPDT DWG ELEV EMT ETM (E) F FC FCS FLA FLP FO FLEX FS FV, FVNR FVR FWD (F) G CALV GFI GND CRS GRS-PVC GS HI HIM HOA HP HS HTR HZ HZD I 1/0 !CR INCAN INST ISC ISR J K LA LC LEL LO LOS LPU LR LS M MAX MCC MCM MCP MD MH MIN MINS MNFR MODEM MOV MTR N NC NIC

MISCELLANEOUS ELECTRICAL & AND AT AMBER, AMPERES ALTERNATING CURRENT ABOVE FINISHED FLOOR ANALOG INPUT AMP INTERRUPTING CAPACITY SYMMETRICAL ALTERNATOR AMMETER ANALOG OUTPUT AMERICAN WIRE GAUGE BLUE BARE COPPER CIRCUIT BREAKER CONDUIT CAPACITOR CIRCUIT GREAKER CIRCUIT COAXIAL CABLE COMMUNICATION PORT CONTROL POWER TRANSFORMER CONTROL RELAY CURRENT TRANSFORMER CONSTANT TORQUE CYCLE COUNTER COPPER DIRECT CURRENT DETAIL DIGITAL INPUT DIAGRAM DISCONNECT DIGITAL OUTPUT DOUBLE POLE DOUBLE THROW DRAWING ELEVATION ELECTRICAL METALLIC TUBING ELAPSED TIME METER EXISTING FRAME FAIL CLOSED FIELD CONTROL STATION FULL LOAD AMPS FAIL LAST POSITION FAIL OPEN FLEXIBLE, METAL LIQUID TIGHT CONDUIT FLOW SWITCH OR FULL SPEED FULL VOLTAGE NON-REVERSING FULL VOLTAGE REVERSING FORWARD FUTURE GREEN GALVANIZED GROUND FAULT CIRCUIT INTERRUPTER GROUND GALVANIZED RIGID STEEL CONDUIT PVC COATED GRS CONDUIT GALVANIZED STEEL HIGH HUMAN INTERFACE MODULE HAND-OFF-AUTO HORSEPOWER HAND SWITCH HEATER HERTZ (CYCLES PER SECOND) HAZARDOUS AREA, EXPLOSION PROOF INTERLOCK INPUT/OUTPUT INSTRUMENTATION CONTROL RELAY INCANDESCENT INSTANTANEOUS SHORT CKT INTERRUPTING CURRENT (SYMM) INTRINSICALLY SAFE RELAY JUNCTION BOX KILO, PREFIX LIGHTNING ARRESTOR LIGHTING CONTACTOR LOWER EXPLOSIVE LIMIT LOW LOCK-OUT STOP SWITCH LINE PROTECTION UNIT LATCHING RELAY LEVEL SWITCH MOTOR CONTACTOR MAXIMUM MOTOR CONTROL CENTER THOUSAND CIRCULAR MILS MOTOR CIRCUIT PROTECTOR MOISTURE DETECTION MANHOLE MINIMUM MINUTES MANUFACTURER MODULATOR/DEMODULATOR MOTOR OPERATED VALVE MOTOR NEUTRAL NORMALLY CLOSED NOT IN CONTRACT

25 (916) 457-8144 ~ u @ NOVEMBER2017

INSTRUMENTATION ABBREVIATIONS NL NIGHT LIGHT NO NORMALLY OPEN NP NAMEPLATE NTS NOT TO SCALE N) NEW

oc ON CENTER 01 OPERATOR INTERFACE OL OVERLOAD ORP OXIDATION REDUCTION POTENTIAL p PHASE, POLE PB PUSHBUDON PBX PULL BOX PC 'PERSONAL COMPUTER PF POWER FAIL PFR POWER (PHASE) FAIL RELAY PH HYDROGEN ION CONCENTRATION Pl PULSE INPUT PLC PROGRAMMABLE LOGIC CONTROLLER PMP PUMP PNL PANEL POT POTENTIOMETER PR PAIR, TWISTED & SHIELDED CABLE PRESS PRESSURE PRI PRIMARY PROVIDE FURNISH, INSTALL & CONNECT PRR POWER RELAY PRV PRESSURE REDUCING VALVE PS PRESSURE SWITCH, POWER SUPPLY PT POTENTIAL TRANSFORMER PTT PUSH TO TEST PV PROCESS VARIABLE PVC POLY VINYL CHLORIDE PWR POWER R RED ROT REPEAT CYCLE TIMER REF REFERENCE RFI RADIO FREQUENCY INTERFERENCE RIO REMOTE 1/0 RMS ROOT MEAN SQUARED RT RESET TIMER RTD RESISTANCE TEMPERATURE DETECTOR RTM RUN TIME METER RTU REMOTE TELEMETRY UNIT RVNR REDUCED VOLTAGE NON-REVERSING

I (Rl REWIRE, RELOCATE, REVISE, REUSE s SWITCH SCH SCHEDULE SEC SECONDARY SECS SECONDS SEL SELECTOR SFA SERVICE FACTOR AM PS SP SET POINT SPEC SPECIFICATION SS STAINLESS STEEL SSS SOLID SOFT STARTER SD START STP STOP sv SOLENOID VALVE SW SWITCH SWBD SWITCHBOARD SYMM SYMMETRICAL T TRIP TB TERMINAL BLOCK TC TIME CLOCK TDOD TIME DELAY ON DE-ENERGIZATION TDOE TIME DELAY ON ENERGIZATION TEL TELEMETRY TEL CO TELEPHONE COMPANY TM THERMAL MAGNETIC TEMP TEMPERATURE TR TIME DELAY RELAY TRIAD TWISTED & SHIELDED 3 CONDUCTOR TS TEMPERATURE SWITCH TSPR TWISTED & SHIELDE.D PAIR TYP TYPICAL UG UNDERGROUND UCN UNLESS OTHERWISE NOTED UPS UNINTERRUPTIBLE POWER SUPPLY v VOLTAGE VA VOLT AMPS VAR VOLT AMP REACTIVE voe VOLTAGE DIRECT CURRENT VFD VARIABLE FREQUENCY DRIVE VLV VALVE VM VOLTMETER VTQ VARIABLE TORQUE w WHITE, WADS WHM WAD -HOUR METER WM WADMETER WP WATERPROOF, WEATHER PROOF ws TORQUE SWITCH XFMR TRANSFORMER XS MISCELLANEOUS SWITCH y YELLOW z IMPEDANCE ZS LIMIT SWITCH

SYMBOL DESCRIPTION

SWITCHES - PROCESS FS

~

FS

~

TS

-or TS

~

WS

~0---

FLOW SWITCH -CLOSES UPON INCREASING FLOW

FLOW SWITCH -OPENS UPON INCREASING FLOW

LEVEL SWITCH -CLOSES UPON INCREASING LEVEL

LEVEL SWITCH -OPENS UPON INCREASING LEVEL

PRESSURE SWITCH -CLOSES UPON INCREASING PRESSURE (INCREASING VACUUM)

PRESSURE SWITCH -OPENS UPON INCREASING PRESSURE (INCREASING VACUUM)

TEMPERATURE SWITCH -CLOSES UPON INCREASING TEMPERATURE

TEMPERATURE SWITCH -OPENS UPON INCREASING TEMPERATURE

LIMIT SWITCH -CLOSES AT SET LIMIT

LIMIT SWITCH -OPENS AT SET LIMIT

PROXIMITY SWITCH -CLOSES UPON DECREASING DISTANCE

PROXIMITY SWITCH -OPENS UPON DECREASING DISTANCE

TORQUE SWITCH -CLOSES UPON INCREASING TORQUE

TORQUE SWITCH -OPENS UPON INCREASING TORQUE

SWITCHES OPERATOR

SW

-0~

PB _J_

-0 0--

PB ---OJ..fr--

PB _J_

-o Io--

HO A

~ I I

~

\ \, ' ale

"'1 L~4 -, '

I : --'- '

--< "*-'

2:1/~-2 2-1 1-2 ~ '*"'_e+-

1 I ' I I ; ~~

TOGGLE OR DISCONNECT SWITCH

PUSHBUDON -NORMALLY OPEN, MOMENTARY ACTION

PUSHBUDON -NORMALLY CLOSED, MOMENTARY ACTION

PUSHBUTTON, MECHANICALLY INTERLOCKED, DOUBLE CIRCUIT -NORMALLY CLOSED AND NORMALLY OPEN, MAINTAINED ACTION

SELECTOR SWITCH, 3 POSITION -CONTACT STATUS SHOWN EXISTS AT POSITION OF H-HAND, 0-0FF, OR A-AUTO

SELECTOR SWITCH, 2 POSITION -CONTACT STATUS SHOWN EXISTS AT POSITION AS SHOWN

SYMBOL DESCRIPTION

DEVICES - RELAY

~ 1 28, JJJ

TDOE TDOD

SV -of\ro-

CR1 --11--­

(105)

CR1 --tt--

TR2

~

TR2

~

CONTROL RELAY CR1 WITH NORMALLY OPEN CONTACT ON LINE 28 & NORMALLY CLOSED CONTACT ON LINE 111

TIME DELAY RELAY TR2 -ADJUSTABLE TIME DELAY RANGE & SETTING AS SHOWN

TIME DELAY ON ENERGIZATION TIME DELAY ON DE-ENERGIZATION

CONTACTOR OR STARTER M1

SOLENOID

NORMALLY OPEN, RELAY CONTACT -ACTUATED BY RELAY CR1 COIL LOCATED ON LINE 1 05

NORMALLY CLOSED, RELAY CONTACT -ACTUATED BY RELAY CR1

NORMALLY OPEN, TIME DELAY RELAY CONTACT -CONTACT CLOSES AFTER TR2 IS ENERGIZED

NORMALLY CLOSED, TIME DELAY RELAY CONTACT -CONTACT OPENS AFTER TR2 IS ENERGIZED

NORMALLY OPEN, TIME DELAY RELAY CONTACT -CONTACT OPENS AFTER TR2 IS DE-ENERGIZED

NORMALLY CLOSED, TIME DELAY RELAY CONTACT -CONTACT CLOSES AFTER TR2 IS DE-ENERGIZED

CONTACT OPENS AND CLOSES IN A TIMED REPEAT CYCLE

DEVICES - FRONT PANEL

INDICATINC LIGHT, LETTER "X" INDICATES COLOR: R=RED G=GREEN, A=AMBER, W=WHITE Y=YELLOW, B=BLUE

INDICATING LIGHT, PUSH TO TEST

AMP METER

VOLT METER

ELAPSED TIME METER

RUN TIME METER

MULTI-POSITION SWITCH WHERE LEITER "X" IS FUNCTION: A=AMP, \/=VOLT

SYMBOL DESCRIPTION

COMPONENTS

..,I

DEVICES

RESISTOR

POTENTIOMETER

CAPACITOR, FIXED

CAPACITOR, ADJUSTABLE

DIODE

DIODE, ZENER

VARISTOR TRANSIENT VOLTAGE SUPPRESSOR

VOLTAGE SURGE SUPPRESSOR, AC

LIGHT EMITTING DIODE

TRANSISTOR

RESISTANCE TEMPERATURE DETECTOR (RTD)

THERMOCOUPLE (T/C)

THERMISTOR

MISCELLANEOUS

AUDIBLE ALARM

TACHOMETER GENERATOR

BATTERY

HEATER

3 PHASE HEATER

3 PHASE MOTOR # = MOTOR HP

SINGLE PHASE MOTOR

TRANSFORMER

DEVICES - PROTECTIVE

~ --o Io--

1

~ -o Io---

1

~ --0 0----

OL --tt--

DISCONNECT, 3 POLE

CIRCUIT BREAKER, 3 POLE THERMAL MAGNETIC (TM) OR MOTOR CIRCUIT PROTECT (MCP)

THERMAL OVERLOAD CONTACT

THERMAL OVERLOAD ELEMENT

FUSE WITH BLOWN FUSE INDICATING LIGHT

FUSE

SYMBOL

WIRING

/

®~

OD

'-'- ~ --( SHIELD~

--- CONDUCTOR

DESCRIPTION

CONNECTIONS

PANEL OR EQUIPMENT WIRING

FIELD WlRING

CONDUCTORS -NOT CONNECTED

CONDUCTORS -CONNECTED

GROUND

CHASSIS OR FRAME GROUND

PLUG AND RECEPTACLE

INCOMING LINE

TERMINAL BLOCKS

TERMINALS

SHIELDED CABLE

PLAN - SYMBOLS

l

I I

--)--

-G-

-

# $ ~

CD

CONDUIT, EXPOSED

CONDUIT, IN SLAB OR BELOW GRAD£

CONDUIT STUBBED OUT & CAPPED

CONDU1T BENDS TOWARD OBSERVER

CONDUIT BENDS AWAY FROM OBSERVER

CONDUIT ENDS

CONDUIT CHANGE IN ELEVATION

BARE COPPER GROUND WIRE

GROUND CONNECTION BOLTED TYPE

GROUND CONNECTION EXOTHERMIC WELD TYPE

DISCONNECT SWITCH

FIELD CONTROL STATION WITH JUNCTION BOX

FIELD CONTROL STATION WITH #AMP DISCONNECT SWITCH

FIELD MOUNTED DEVICE

SPECIAL RECEPTACLE

JUNCTION BOX

THERMOSTAT

LIGHTING, FANS, HEATERS # - CIRCUIT BREAKER NUMBER A - FIXTURE SCHEDULE REF, a - CONTROL SWITCH REFERENCE

DUPLEX RECEPTACLE # - CIRCUIT BREAKER NUMBER

TOGGLE SWITCH # - CIRCUIT BREAKER NUMBER SUBSCRIPT - CIRCUIT CONTROLLED SUPERSCRIPT - BLANK = 1 POLE

CONDUIT #

2 = 2 POLE 3 = 3 WAY

9/14/2018

(()

0 N

w z => ,

z ;;;; 0 :r: If)

'{}_

w __J <( u If)

)-' m z ~ 0

V>

0 >-I­

V> LU

CONTRACT NO. C02150

SHEET 5 OF 13

V> LU I­<(

u 0 VJ

V> <(

>­OJ

z 0 (/)

> w Ct'

~ <( 0

0 z

? ATEEM ENGINEERING FILE NO, 2018-0004 Nl_~A=L:L~R=IG~H~T=S~R:E:S:ER~V~E=D'.__ ________________________________________________________________________________________________________________________________ -'--------~

ro 0 ('J

' N

O'

" -0

N 0 0

Q)

CJ n 0 co

/ -0 n 0 <D

/ <D

0 N / 0 3 0 0 <{ 0

5 N

MMS/MCC

LOAD CALCULATIONS UTILITY GENERATOR SERVICE SERVICE

LOAD QTY LOAD RUN QTY RUN QTY RUN HP DESCRIPTION AMPS LOAD VA AMPS RUN VA RUN VA

100 BOOSTER PUMP 124 4 412,367 3 309,275 2 206, 1113

HEATER 6.0 5,000 5,000 5,000

SUPPLY FAN 3.4 1 2,827 1 2,827 1 2,827

PANEL LP 10.1 8,401 8,401 11,401

SUBTOTAL 516 428,594 325,502 222,411 DIVERSITY FACTOR 76 % GEN

100 HP SIZE Largest motor @ 25% additional 124 0.25 25,773 2511 KW

313 KVA TOTAL 351,275 376 AMPS

AMPS• 266 I 480 V, 3 Phase, 4 Wire, Service Amps= 423 Amps

1.25 Multiplier KVA= 222 Service Size = 528 Amps

Feeder Breaker Size = 400 Amps %GEN

% Feeder Breaker Load = 132.0% LOA[)oo 71.2%

AUTOMATIC MMS TRANSFER SWITCH MCC

'

IDWGREF: E2

NAMEPLATE: PANELA : LOCATION: MCC

MOUNTING: FLUSH VOLTS: 120 I PHASE: 3

200 BUS AMPS: 100A

MAIN BKR: MLO KAIC RATING: ?

ENTRY: BOTIOM

NEMA: 1

BKR LOAD LOAD

NO. DESCRIPTION VA 1 SPARE ,0

3 RECEPTACLES 540

5 SPARE ----- -~0---

7 LIGHTS - PUMP ROOM 500

9 DCU-LIQ 5 '500

11 UPS/120V CONTROLS

13 EXHAUST FAN

15 SUPPLY FAN CONTROLS 100

17 100

PHASE A B C

L~~~~~:~!---j~t~J-: i]f j,& TOTAL KVA, 9.33

TOTAL AMPS@ 208V, 3P' 25.9

DIVERSITY FACTOR ,. 0.90

LOAD KVA L__ __ _.::,8·:..:,40::.J

WIRE: 4

BKR

AMP/ BKR POLE NO. PHASE

20/1

20/1

20/1

20/1

15/1

20/1

1511

60/2

3

5

7

9

11

13

15

17

A

B

c A

B

c A

B

c

( B- HIGH LEG)

[NEUTRAL J !GROUND

BKR

BKR AMP/

NO. POLE

2

4

14

16

18

SPD: NO

LOAD LOAD BKR

~V_A_~--------~D~ES_C_Rl_PT_l~N NO. 0 SPARE 2

650 RECEPTACLES 4

500 IG TS - GEN ROOM 6

1,442 GEN JACKET HEATERS

1,442

500 BATTERY CHARGER

RECEPTACLES GEN ROOM 14

EXTERIOR LIGHT 16

SPARE 18

350 B C PHASE ~-------

15 22 8 RIGHT SIDE AMPS f---------1---~----4 REPLACE

CIRCUIT BREAKER 1.80 2.59' 1.00 RIGHT SIDE KVA

1.70 1.14 1.10'LEFT SIDE KVA , _____________ -~-i- ... -_ ---

3.50 3.73 2.10 TOTAL PHASE KVA

29 31' 18'TOTALPHASEAMPS 1--------1---+---

113 120 67,%0FAVERAGE 1----~--+--~

NOTES: 1. MEANS OF WIRE COLOR CODING SHALL BE POSTED ON PANELBOARD PER NEC 210.5

2. ( G) INDICATES GFI BREAKER REQUIRED WITH 30 MA SENSITIVITY.

3. ( H) INDICATES HACR RATED BREAKER.

4. ( L ) PROVIDE PADLOCKING PROVISION IN ORDER TO LOCK BREAKER IN THE OFF POSITION.

- NEW WORK

1------T----i~=-=~-~--+----~-----~=--=-----------------------~ --- ------------------~ -3:. ~A~ ~O~R -H~~;A~ ~ ~;E~ -K~1c-- - - ,-- - - -- - - -- - - -- - - -- - -,- - ---i----1------r--1 : M~i~~i:c : 8 400

A : : !-------<l i00:Ts > ~ -~-) 1~:A/3PI----,-) 175A;3:i-- ) 1;5A/3Pl---I) ,,,:1::r-J-) ,w~,l~) ;w"rf) ;,:1J- ··f) 1:~:----1----1-----1 -----1---TEST

BLOCKS

l : l TM I l TM I I TM I l TM I ? TM I ? TM I TM I I/ TM I I I I I I I I I I I I I ~480V PRI I I I I

i I ss - - I ] ~ - -ss - 1 ! [ - ss ~ ] [ - - ss - - -[ ] ] ! ] 1 1~ili~~:,, ] ~~~~~ ] R;ig~g~R ] 's\~f i' ] DCU SECTION >-------

I

POWER-l---­BLOCKS I

TERMINATION 1

I ,,l-----_.,,.._~N=E~U~R~A~L"-' I'

ISOLATED BUS

NEUTRAL LINK

GROUND BUS

UTILITY TRANSFORMER

I I I I I I I I I I

~

~ I I I

A 480 VAC, 3 PHASE, 4 WIRE

480/277 v UTILITY SERVICE

ON TRANSFORMER SECONDARY

(916) 457-8144

© NOVEMBER2017 ATEEM ENGINEERING ALL RIGHTS RESERVED

I &-------,

~ ~ UFER

GROUND GROUND

ROD

NEW WORK

Vi (E) 4" ( 4#500 KCMIL I - - - - - -I I 1- - - - - -I I I - - - - - -I I 1- - - - - -I I I i I ) ¢~A/3P I I I I & #3 GND) L---,----_J L---,-----1 I L---,-----1 I L __ , ___ I I I I -------

1 I 1 I I LINE I I I I

LL -------------------------1

-- - _ l _ ---1

- - -- _ l __ -_ L __ _j_ _ -__ j_ -- -_[_ -_ l _ ~ ---_Li_ -__ _j_MONITO: _ J _ -=-----_ i _ --- _l __ -_ j _ ----_ L _ -__ __J

I 400A

+ TERMINATION 1 , PANEL

~ TRANSFER SWITCH PEDESTAL NEMA 12 : ~S------------L~;D BANK--~

i I 8i<,f< _ - l:'l_ECH _l_NTERLOCK - - - ~R I I 1 1 480V, 3¢, 3 WIRE, 400A, 1 I 1 ~ COPPER BUS RATED 65 KAIC ~

L _____ l_4o~A/3P l l 40~A/3P

4::A/3P )_l_NT~~tcicK -) 400A/3:M

POSl-LOK (TYP)

I TM 9 TM PORTABLE I STATION

1 GENERATOR : GENERATOR

L BKR I BKR 1

I

________ l ________ _J I

400A, 480V ~ 400A, 480V GENERATOR ~ LOAD BANK

RECEPTACLES 1 RECEPTACLES

1--r---1 I ) 400AT I

600AF I 3P,@ I I LSI I I r;::\ I I ~ I L ______ _J

GENERATOR

(R) ( GEN0201 ) 250 KW 313 KVA 376 A

480/277 VAC, 3 PHASE, 4 WIRE

I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I

e 124 FLA e 124 FLA @ 124 FLA @ 124 FLA 0 0 143 SFA 143 SFA 143 SFA 143 SFA

PUMP PUMP 2 PUMP 3

('-_P_1~) ( P2 > ( P3 PUMP 4

) ( P4

HEATER

)

SUPPLY FAN

-=E .;:__;_x -=--=-' S_.:_T ,;_;_I N.:.._:::Gc,__,:_:_M::..=E:__:_T =-:E R'-'--/./--'M-'-'-"A--'--'1-'--'-N ~s w I T c H B 0 A R D (MMS) & MOTOR CONTROL CENTER (MCC) NOTES: CD BOND NEUTRAL TO GROUND PER GENERATOR

MANUFACTURER INSTRUCTIONS.

0 BREAKER TO HAVE LONG, SHORT AND INSTANTANEOUS (LSI) ADJUSTABLE TRIP UNITS.

PANEL A

ONE LINE DIAGRAM

9/14/2018

ro 0 N

w __J <{ 0 (j)

> "' N

>-' OJ

z 3 0

,_ (/')

0 >-

0 w > 0 CL CL CL <(

Q) ~

0 0

CONTRACT NO. C02150

SHEET 6 OF 13

FILE NO, 2018-0004

(/')

LU

I­<(

u 0

"' "' <(

>­CD

z 0 V> > w ()'.'.

w f­<C 0

0 z

w CL

'C 0

__J

/ w 0 N / 0 s: 0 0 <(

Sf --:: N

0 3

SCALE IN FEET

(E) MMS

'' '' Ii

NOTES:

{916) 457-8144

@ NOVEMBER 2017 ATEEM ENGINEERING ALL RIGHTS RESERVED

6

CD 0

0

(E) ATS

(E) 4" CONDUIT WITH 4#500 KCMIL & #3 GND

(E) MCC

I

I

C0201A

... . - - . ··- -

C0201C

400A TERMINATION

PANEL

(j)

L 112A

/

CONDUIT & WIRE ROUTING SCHEDULE REF

DWG

E3

E3

E3

E3

E3

E3

E3

E3

E3

GENERATOR

(R) ( GEN0201 )

P0201B

CONDUIT

NO.

c 0201

c 0201

c 0201

c 0255

L 112

L 112

p 0201

p 0201

XA 0255

C0201B L112B

TRANSFER SWITCH PEDESTAL

A

B

c

A

A

B

A

B

FROM

MCC/ATS

JB

FCS0201

GEN0201

MCCIATS

JS

400A TERMINATION PNL

TRANSFER SWITCH PED

BLDGJB

/

/ /

/ / ,/

TO

JB

GEN0201

GEN0201

LSH/UX0255

JB

GEN0201

TRANSFER SWITCH PED

GEN0201

FUEL TANKJB

,., ' ' ' ' ' ' ' ' I I ' ' ' ' ' '

QTY SIZE TYPE

1 ? EXISilNG

1 1" GRS

1 314" GRS

1 1" GRS-PVC

1 ? EXISTING

1 1" GRS

1 4" GRS

1 4" GRS

1 1-112" GRS-PVC

FUEL TANK

( TNK0255 )

-- -------v:~~;~=----- J WP ' 1,, ··-· .. -· ~,., . , ···--. . -... ,, ....... ,,,

/i l ~/ i l

I I I I I I I I I I I I I I I I I I I I I I I I I I I

XA0255

C0255A

t

60"

--- . - . ..__,_

ATS o DISCONNECT o

LOAD BANK o D1SCONNECT 0

r------------------, I r---------------, I I I

i WWW c I

I ! L---------------_._I L------------------_._I r------------------1 ! r---------------, I I I

i wwf!J c i I I ) L----------------_._I L------------------J

FRONT ELEV. OUTER DOOR REMOVED

,., ' ' ' ' ! t

' ' ' ' ' ' ' ' ! I ' ' ' ' ' ' ' ' ! ! ' ' I l ,_,

PWR GND CONTROL SIGNAL QTY SIZE SIZE QTY

---

-4

4

4

4

-

- #12

- #12

- #12

- #12

#10 #10

#10 #10

#500 kcmil #3

#500 kcmil #3

- -

\i

EQUIPMENT NAMEPLATE WITH 1/4" LETIERING (TYP)

PORTABLE o GENERATOR o

DISCONNECT

STANDBY o GENERATOR o

DISCONNECT

LOAD BANK o RECEPTACLES o

480 VAC, 400A

~LOAD BANK POSl-LOK (MALE)

GENERATOR o RECEPTACLES o

480 VAC, 400A

COVER ON OUTER DOOR (TYP)

GENERATOR POSl-LOK (FEMALE)

16

16

4

12

-

-

-

--

SIZE QTY SIZE

#14 -#14 -#14 -#14 -- -

- -- -

- -- -

BACKUP 0 GENERATOR 0 & LOAD BANK

SECTION

THREE POINT LATCHING

MECHANISM WITH PADLOCKABLE

HASP (TYP)

-

-

-

------

NOTES

REPLACE WIRES

GRS Inside BLDG

REPLACE WJRES

PULL ROPE

ENCLOSURE NAMEPLATE WITH 1/2" LETIERING (TYP)

SIDE ELEV.

ELECTRICAL OVERALL SITE PLAN CD000 ..=c..=..c="--CC.-.'--'-'-'-"'-'--"-'=-~-=-~--"---~~"--'=-~-=--'---'--'=-~'--~~~

TRANSFER PEDESTAL ELEVATION CD0 SWITCH NOT TO SCALE

EXPOSED CONDUITS PER DWG E11, DETAIL "A",

HAND DIG CONDUIT TRENCH IN EXISTING AREA EXISTING UNDERGROUND SERVICES ARE NOT SHOWN & SHALL BE PROTECTED FROM DAMAGE, UNDERGROUNO CONDUITS PER DWG E11, DETAIL "B",

UNDERGROUND CONDUIT TRANSITIONS PER DWG E11, DETAIL "c",

®

NOT ALL EXISTING CONDulTS SHOWN. CONDUITS SHOWN ARE THOSE ASSOCIATED WITH NEW WORK.

CORE DRILL CONDUIT OPENINGS, PATCH WITH NON-SHRINK GOUT TO SEAL AROUND CONDUITS AND PAINT TO MATCH EXISTING SURFACE.

INSTALL NEW WEATHERPROOF TRANSITION JUNCTION BOX,

®

0

REPLACE (E) JUNCTION BOX WITH NEW 400A TERMINATION PANEL WITH POWER TERMINATION BLOCKS AND PIANO HINGES TO INTERCEPT EXISTING CONDUIT AND WIRES. COORDINATE WITH CITY TO DETERMINE HEIGHT OF PANEL.

EXISTING CONDUITS TO BE RESCHEDULED, SEE CONDUIT SCHEDULE FOR DETAILS,

MAINTAIN CLEARANCE IN FRONT OF TRANSFER SWITCH PEDESTAL, INSTALL GENERATOR CONTROLS AND BREAKERS FACING AWAY PEDESTAL,

NOTES1 CD 0

ITEMS DRAWN IN DASHED LINES ARE TO BE LOCATED BEHINO DEADFRONT OOORS, OUTER DOORS ARE NOT SHOWN FOR ELEVATION CLARITY,

EACH BREAKER SHALL HAVE PADLOCKING PROVISION TO LOCK BREAKER IN THE OFF POSITION,

FABRICATION METHODS

1, NEMA 12 ENCLOSURE. 2. ALL OUTER DOORS SEALED WITH PERMANENT TYPE CASKETING, 3. EXTERIOR FABRICATED FROM HOT DIPPED GALVANIZED SHEET STEEL. 4, 12 GAUGE EXTERIOR AND 14 GAUGE INTERIOR 5, ALL SEAMS CONTINUOUS WELDED, 6, OUTER DOORS TO BE PAOLOCKABLE WITH HEAVY DUTY 3 POINT LATCHES, 7, DOOR HINGES AND PINS SHALL BE 316 STAINLESS STEEL. 8, NO SCREWS, RIVETS , OR BOLTS SHALL PROTRUDE EXTERNALLY, 9, INTERNAL SCREWS, RIVETS, BOLTS, AND NUTS

SHALL BE STAINLESS STEEL. 10. PEDESTAL SHALL BE UL LABELEO,

11. EXTERIOR PANEL COLOR: DESERT TAN (SUBMIT COLOR SAMPLE TO OWNER FOR APPROVAL).

12. INTERIOR DEADFRONT DOOR COLOR: WHITE. 13. PHENOLIC SCREW MOUNTED NAMEPLATES SHALL BE PROVIDED

FOR ALL DEVICES ON DEAOFRONT. 14. FABRICATION AND WIRING SHALL CONFORM TO U,L. 508 AND NEMA STANDARDS, 15. ALL WIRING SHALL BE PERMANENTLY LABELEO WITH

WIRE MARKERS ON BOTH ENDS. 1 6. WIRING DIAGRAMS SHALL BE PLACED IN A DRAWING HOLDER

PERMANENTLY ATIACHED TO THE INSIDE OF THE FRONT DOOR 17, AS - BUILT WIRING DIAGRAMS SHALL BE SHIPPED WITH EQUIPMENT,

9/1412018

co 0 N

w z :::> ..,,

z s: 0 :r: (j)

~

w __J <( (_) (j)

> "" N

"' 0 >-I­

"' UJ

CONTRACT NO, C02150

SHEET 7 OF 13

FILE NO. 2018-0004

"' LU

I­<(

u 0 V)

V)

<(

>­CD

z 0 l/)

G:1 O'.: I

w I­<( 0

0 z

I

0 N :;:-

~

0 (I)

-0 n 0

"' / -0 n 0

"' ~

0 N / 0 s 0 0 <(

5 N

(916) 457-8144

@ NOVEMBER 2017 ATEEM ENGINEERING ALL RIGHTS RESERVED

CONDUIT

1 5/6" x 1 5/8" (,;\ STEEL CHANNEL \}:_,;

CONDUIT CLAMP

CONDUIT SUPPORT

PIPE STRAP MOUNTING A NOT TO SCALE DETAIL E 11

NOTES:CD THIS DETAIL TYPICAL FOR BOTH VERTICAL AND HORIZONTAL MOUNTING.

0 CHANNEL AND ALL SUPPORT DEVICES TO BE NEMA RATED PER AREA CLASSIFICATION. FIELD ALL CUTS, ETC. TO MATCH.

CHANNELS TO BE SPACED 5' MAXIMUM.

GRS INDOORS AND GRS-PVC OUTDOORS

COAT

4 .

·2 ·4 GROUT CURB AROUND ALL SIDES OF CONDUIT WITH BEVELLED CORNERS

3 1/2" HEIGHT

2 1 /2" (MIN) ---...i AROUND CONDUIT

GRS-PVC COATED COUPLING

GRS-PVC COATED

GRS-PVC CONDUIT

ADAPTOR COUPLING

CONDUIT PER CONDUIT SCHEDULE

EXPOSED CONDUIT TRANSITION c NOT TO SCALE DETAIL E 11

DEVICE NAMEPLATE WITH 3/16" LETTERS

(TYP)

INSTALL 3" WIDE RED WARNING TAPE LABELED "ELECTRICAL"

FOR ALL CONDUIT RUNS 1 00' & GREATER

24" (MIN)

12"

2" SEPARATION 0 (MIN)

CD CONDUITS QUANTITY & TYPE PER CONDUIT SCHEDULE

NOTES:

4" SAND ALL AROUND

#2/0 CONTINUOUS BARE COPPER GROUND

UNDERGROUND CONDUITS NOT TO SCALE D ET Al L

CD

0

PLACE CONDUIT RUNS OF 4 CONDUITS OR GREATER IN PLASTIC SPACERS (RATED FOR DIRECT BURIAL) EVERY 5' ALONG LENGTH OF RUN.

PROVIDE 12" (MIN) SEPARATION BETWEEN "A, C, D & M" TYPE GROUP AND "E, L & P" TYPE GROUP CONDUITS.

TRENCHING & COMPACTED BACKFILL PER SPECIFICATIONS & CITY'S STANDARD 215.

GENERATOR O EMERGENCY

-- 1 /2" WHITE LETTERS STOP

E-STOP

(HC)

ON RED PHENOLIC NAMEPLATE ATTACHED WITH STAINLESS STEEL SCREWS

DEVICE BOX

TWO POSITION PUSH-PULL LATCHED RED MUSHROOM SWITCH OPERATOR

HC

3

TERMINAL BLOCKS INSIDE

ENCLOSURE (TYP)

E-STOP FCS ELEMENTARY & ELEVATION o NOT TO SCALE DETAIL E 11

2 TO GENERATOR

4 SPARE

9/14/2018

'

ro ~

0 N

w z ::,) -,

w ~ 0

z s 0 :r: (f'J

(f'J <(

w _J <( u (/)

<( en 0 a:: ;:!: z <( r.n u.. 0 >-I-(.)

y: :;;; (f'J

;;.: m

"' :r: u

> "' N

;;.: m z 5:: 0

('\I

z 0 i=

,_ Vl

0 >-

"' UJ

;:: I-(/) z ow z ::2 <(~ 6:5 - Q._

~Ml <;! a:: I- 0

~~ 0:: w w ffi !:i (!)

u:: >-a:: (.) wZ :sw fr~

LU <') ::l1! Z LU 0 s (J)

CONTRACT NO. C02150

SHEET 9 OF 13

I FILE NO. 2018-0004

"' UJ f­<(

u 0

"' Vl <(

>­m

z 0 VJ

> w Ct:

w I­<( 0

0 z

0 Q u n 0 CD

/ u n 0 CD

/ CD

0 N / ('.)

~ (916) 457-8144 0

C"i @ NOVEMBER 2017 :_> ATEEM ENGINEERING N ALL RIGHTS RESERVED

SYMBOL DESCRIPTION

P & I DIAGRAM SYMBOLS

® ® @

® @

0 DWG

@ @

® ® ocf%t

% +/-

a IR#-C#I

( xxxxx ) ZS: v .... v

<a I xxxx I lxxxxla)

( P-X (

2:P-X)

#

FIELD MOUNTED INSTRUMENT

FACE MOUNTED INSTRUMENT ON LOCAL PANEL, OPERATOR ACCESSIBLE

FACE MOUNTED INSTRUMENT ON FIELD PANEL, OPERATOR ACCESSIBLE

INSTRUMENT MOUNTED IN LOCAL PANEL, OPERATOR INACCESSIBLE

INSTRUMENT MOUNTED IN FIELD PANEL, OPERATOR INACESSIBLE

OPERATION PERFORMED WITH LOGIC OR HARDWIRED DEVICES

- REFERENCE ELEMENTARY DWG. #

"'LC OR COMPUTER FUNCTION PERFORMING OPERATION WITH VISUAL INDICATION

PLC OR COMPUTER FUNCTION PERFORMING OPERATION WITH VISUAL ALARM INDICATION

PLC OR COMPUTER PERFORMING INTERNAL OPERATION

PLC OR COMPUTER PERFORMING INTERNAL ALARM OPERATION

?ROPORTIONAL, INTEGRAL, AND DIFFERENTIAL PARAMETERS

RATIO AND BIAS PARAMETERS

AUDIBLE ALARM (BUZZER OR HORN)

ANNUNCIATOR WINDOW R - ROW # C - COLUMN #

LAMP INDICATION (STATUS OR ALARM)

DISCRETE INPUT

DISCRETE OUTPUT

ANALOG INPUT

ANALOG OUTPUT JUMP TAG FROM ONE AREA TO ANOTHER AREA OF DRAWING "a" TAG CONNECT POINT ON EACH DRAWING

CONTINUED ON DWG P-X

AUTODIALER PRIORITY # PC BASED SOFTWARE

I

SYMBOL

p & OPEN CLOSED

~ ~

lOi ii 0 * FlJ ~

~ H N

~

G? 8 ~

CJ [:j ~

I xx xx I

( xxxxx >

------

- - -

.. ,,

)( )(

. " c

ES AS

0 -0

0

"'

E

SA ,.,

IA)

LO

I

DESCRIPTION

DIAGRAM

GATE VALVE

PLUG VALVE

BALL VALVE

BUTTERFLY VALVE

GATE (GENERAL)

CHECK VALVE (GENERAL)

SYMBOLS

PRESSURE RELIEF VALVE

PUMP (GENERAL)

PROGRESSIVE CAVITY PUMP

DIAPHRAGM PUMP

ROTARY SCREW PUMP

BLOWER (GENERAL)

VALVE/GATE NUMBER

EQUIPMENT NUMBER

ELECTRIC SIGNAL

LOGIC OR DATA SIGNAL

PNEUMATIC SIGNAL

CAPILLARY TUBING (FILLED SYSTEM)

HYDRAULIC SIGNAL

SONIC OR ELECTROMAGNETIC SIGNAL

ELECTRIC SUPPLY

SERVICE AIR

INSTRUMENT AIR

DISCONNECT SWITCH

INSTRUMENT IDENTIFICATION LETTERS FIRST LETTER

MEASURED OF INITIATING MODIFIER VARIABLE

A ANALYSIS B BURNER,

COMBUSTION c CONDUCTIVITY D DENSITY DIFFERENTIAL E VOLTAGE

F FLOW RATE RATIO (FRACTION) G GENERAL

~ -H HAND I CURRENT

(ELEC.) J POWER SCAN K TIME. TIME RATE

TIME SCHEDULE OF CHANGE L LEVEL M MOISTURE MOMENTARY N STATUS 0 OPERATOR

P PRESSURE, VACUUM

Q QUANTITY INTEGRATE. TOTALIZE

R RESET S SPEED, SAFETY

FREQUENCY T TEMPERATURE U MULTIVARIABLE V VIBRATION,

MECH. ANALYSIS W WEIGHT, FORCE X SWITCH X AXIS Y EVENT, STATE Y AXIS

OR PRESENCE POSITION

Z DIMENSION Z AXIS

SUCCEEDING - LETTER READOU I OUTPUT PASSIVE FUNCTION

FUNCTION ALARM USER'S USER'S CHOICE CHOICE

CONTROLLER

SENSOR, PRIMARY ELEMENT

GLASS VIEWING DEVICE

INDICATING, INDICATOR

CONTROL STATION

LIGHT

STATUS USER'S CHOICE ORIFICE, RESTRICTION POINT (TEST) CONNECTION

RECORD SWITCH

TRANSMITIER MULTIFUNCTION MULTIFUNCTION

VALVE, DAMPER LOUVER

WELL UNCLASSIFIED UNCLASSIFIED

RELAY, COMPUTER, CONVERTOR DRIVER, ACTUATOR, UNCLASSEIFIED FINAL CONTROL ELEMENT

--- FIRST LffiER F - FLOW RATE

--- SUCCEEDING LETTERS I - INDICATING

'----- SEQUENCE DESCRIPTION

MODIFIER

USER'S CHOICE

HIGH, OPENED

LOW, CLOSED MIDDLE USER'S CHOICE

TEST MULTIFUNCTION

UNCLASSIFIED

7 - 70 SERIES - FLOW DEVICES 1 - INDIVIDUAL ITEMS

REPRESENTS AREA NUMBER

P&ID INSTRUMENT IDENTIFICATION EXAMPLE

ANALOG RECORDER

( ~PUT ) ~FIR • I

I I I I I 2500 I

1-5 voe t L---~~s!T~~---J t I I I

l t 4-20 mA

SIGNAL

1-5 voe

ANALOG INPUT

( F ) • ! 11-5 voe : 2500 1 RESISTER

op

! I 4-20 mA l

SAMPLER i.----------J~) ISOLATOR

4-20 mA \-,

l t 4-20 mA

SIGNAL

TYPICAL SIGNAL FLOWS

NUMBERING SEQUENCE

SEQUENCE DESCRIPTION NUMBER

00 COMMON ALARM

01-09 INDIVIDUAL ITEMS

1 0 MECHANICAL

20 MECHANICAL

30 MECHANICAL

40 MECHANICAL

50 LEVEL DEVICES

60 PRESSURE DEVICES

70 FLOW DEVICES

80 ANALYTICAL DEVICES

90 SAFETY & SECURITY DEVICES

OC!

0 N

w z ::J .,

w ~ 0

z 3; 0 I (/)

(/) q

w _, q (.) (/)

U3 ~ <( I-z <( 00 I.I,,. 0

~ (3

~ ::;; (fl

;;.: CD

""" I 0

> "" N

;;.: CD

z $ 0

N z 0 f'.=

,_

"' 0 >-

1-U')

UJ

~ I-Cl) z ow z ::;;; <( w z~ 0 0,,.

5~ ~ 0:: I-~ ~~ 0::: LU wZ I- w ::! ~ u.. >-0:: u LU Z s: w oe:i 0... 0::

LU "'~ zw 0

~ U)

9/14/2018

CJ) ,, -,.., .s; . ': .... "' '·._$''¢"~ '" .s \} ---,,, tn ,,

c5 ([) ~

0 0 ....

D ~

(j

"' ·"' Q\ . "" \ ) ':; ) 2- ' Cl ,~ tn

'""~ .s ~ '· (j

"( ~ \

0 \~ ~ ~{:·, 0 x

,. Q_ Q_ q

"" ro

fl) ...J 0 00 ---

u 0

"' "' <(

>­m

z 0 U)

> w 0::

w c--<{

0

0 z

w Q_

d ([)

c 0 n ~

::::i

·c: 0 _,

:E ~

>- fl)

UJ z z 0 ..... 0 ~ -s -> w z rt w m :! al

<( :;:) IX ~ .... UJ z -

CONTRACT NO. C02150

SHEET 10 OF 13

FILE NO. 2018-0004

AUTODIALER (E) ~ (E) AUTODIALER L_ ! _ ...... _ ...... _ ...... -- ...... _ ..... _ ...... _ ...... _ ...... - ...... - ...... _ ...... -- ...... - ...... _ ...... _ .... ,._ ...... _ ...... _ ...... - ...... - .... ---J C---""'"'_ ...... - ...... - ...... _ ..... ,,_ ...... - ...... - ...... _.,. .. - ...... _ ...... ._ ...... _ ...... _. ...... _ .................... _. .... .,_ ...... _ ...... _ ...... _ ...... _ ...... _ ...... _ ...... _ ...... - ....... - ...... - ...... - ...... - .... ..,__, ...... _ ...... - ....... - ...... _ ...... ._ ....... - ...... _ ...... - ...... _ .. ., .. _ ...... _ ...... _ ...... _ ...... _...... --i:

OPERATOR ~ INTERFACE ~ 01 DISPLAY (E) t

PROGRAMMABLE LOGIC CONTROLLER PLC (E) ~ - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -

MOTOR CONTROL CENTER MCC (E) t-----

FIELD CONTROL STATION FCS

- - - - - - -·- - - - -·- -·- - -·-·- - -·-·- - ...... - - - - - - -·- r,_._ -I E-STOP

@ 1 DWG V E1 ': -D

FCS

I

·-·· GENERATOR

RUN ALARM AUTO

~~4'~1 ) _(uszo1) ~Y?!1 )-, I I I I I I I I I I I I I I I I I I I I I I I I I I I I I

• + + I I I I

I I I I I

I A I

Ti I

I I I

I : I

I : I I

*

I I I I I I I I I I A I --·-T--1 I I I I I I I I I I

i

I I I I I I I I I I

t -1·-

I I I I I I I I I I I

~

-·- - - - - - -·-·- - -·-·- - - -

(E) 01 DISPLAY -(

(E) PLC - - - -2

(E) MCC ----------------------------~

FCS t·- - - - - - -·- - - - - -·- - - - ....... ......,. - - _,_ -·- -·- ....... - -·-·- _, ___ -·-

I 0201 L-- 1- - .._ .L """'" .... - - ....... I.- - -·-·- - -·- - ....... - - ....... - - -·- - - - -·- ~·- -·-·- - - -·-·-·- -·- - -·- -·- - - -·-·- - ~

FIELD

i

(916) 457-8144 @ NOVEMBER 2017 ATEEM ENGINEERING ALL RIGHTS RESERVED

ATS (E)( ATS0201 )

I I I I

I I I I I I I I I I I I I I I I I L ______ _

I I I I I I I I I I

I I I I I I I I I I

I I I I I I I I I I I

I I I I I I _____ _J

L----------- GENERATOR ~--------~- (R)< GEN0201 )

NOTES: CD

0

0

t

FUEL TANK < TNK0255 )

3

LSX LEAK ~55

AUXILIARY SYSTEMSCD0

CONTRACTOR TO MAKE NEEDED UPDATES TO CITY SCADA SYSTEM AS REQUIRED.

CONTRACTOR SHALL INCLUDE ALL NECESSARY MODIFICATIONS AND TESTING TO THE CITY SCADA SYSTEM.

DOUBLE WALLED ABOVE GROUND FUEL TANK WITH FUEL FLOAT SWITCHES.

FIELD

~

NEW WORK

AREA PREFIX

0 2""

OJ ~

0 N

w z => -,

w I-<( 0

z 5: 0

"' ~ (!)

;.: m

"' I ()

>­V)

0 >-,_

"' u.J

I > (!) "' N

N

i5 i= ~ I-(/) z Cl UJ z :i: <( ~

< z :5 (f) 0 c. 0 5~ 0:: <( ...J 0:: I- ~ ~ z (/) ~ <( z Cl) 0:: w LL wZ 0 I- w ~

...J Cl IJ.. >-0:: (.) 0 wz $: w 0 (!)

0.. ffi ("):ii z UJ 0

~ (/)

N --~ c .... ~ a.. U)

:ii!: w I-U)

> UJ > a: <( ..... ....I -)( ;:) <(

CONTRACT NO. C02150

SHEET 11 OF 13

FILE NO. 2018·0004

u 0 V)

"' <(

>­co

z 0 Ul

> w Ct:

w I­<( 0

0 z

-

"' w b z D w _J w I

N

'" i N 0

ABBREVIATIONS A AMPERE AC ALTERNATING CURRENT A/C AIR CONDITIONING AF AMPERE FRAME, CKT. BKR, RATING AFF ABOVE FINISHED FLOOR AH AMP HOUR AHU AIR HANDLING UNIT AL ALUMINUM Al ANALOG IN AIT CHLORINE RESIDUAL ANALYZER AM AMMETER ANN ANNUNCIATOR AMP AMPERES, AMPERAGE AO ANALOG OUT APC AMERICAN POWER CORP, APPD APPROVED AS AMMETER SWITCH AT AMPERE TRIP ATS AUTOMATIC TRANSFER SWITCH AUTO AUTOMATIC AUX AUXILIARY AWG AMERICAN WIRE GAUGE BATI BATIERY BKR BREAKER BLDG c CAB CB CKT CL co COM COM PT COM PR COND CP CPT CR CT cu DC DH DI DIC O!SC DISTR DPDT DWG (E) EF EHU ELEV EM ERG EMT ENCL EQPT ER EP ETM EXH EXIST

FDR FLEX FLUOR FUT FVR FVNR FWD GALV GEN GND H HH HID HG HGA HMI HOA HP HPS HT TR HTR HVAC HZ IMC INCAND IND 1/0 INST INSTR !NVT JB J BOX KVA KW KWH KCM L LC LC8 LCP LOC LO LOS LS LT LTG LTS M mA MAN MAG MAX MCC MCB MCP MD

BUILDING CONDUIT CABINET CIRCUIT BREAKER CIRCUIT CIRCUIT CONDUIT ONLY COMMON COMPARTMENT COMPRESSOR CONDUIT CONTROL PANEL CONTROL POWER TRANSFORMER CONTROL RELAY CURRENT TRANSFORMER COPPER DIRECT CURRENT DATA HIGHWAY DIGITAL IN DIGITAL IN OUTPUT DISCONNECT DISTRIBUTION DOUBLE POLE DOUBLE THROW DRAWING EXISTING EXHAUST FAN ELECTRIC HEATING UNIT ELEVATION EMERGENCY ELECTRICAL METALLIC TUBING EMC.LOSURE EQUIPMENT CONDUCTANCE RELAY EXPLOSION PROOF ElAPSED TIME METER EXHAUST EXISTING

FEEDER FLEXIBLE FLUORESCENT FUTURE FULL VOLTAGE REVERSING FULL VOLTAGE NON-REVERSING FORWARD GALVANIZED GENERATOR GROUND HOT CONDUCTOR HAND HOLE HIGH INTENSITY DISCHARGE MERCURY HARMONIC GUARD ACTIVE Fil TER HUMAN MACHINE INTERFACE HAND-OFF-AUTOMATIC HORSEPOWER HIGH PRESSURE SODIUM HEAT TRACED HEATER HEATING, VENTILATING, A/C HERTZ - CYCLES PER SECOND INTERMEDIATE METAL CONDUIT INCANDESCENT INDICATION, INDICATING INPUT/OUTPUT INSTANTANEOUS INSTRUMENT INVERT JUNCTION BOX JUNCTION BOX KILO VOLT AMPERES KILOWATIS KiLOWATT HOUR 1,000 CIRCULAR MILS LINE POWER LIGHTING CONTACTDR LOCAL CONTROL BOARD LOCAL CONTROL PANEL LOCAL LOCKOUT LOCKOUT STOP LEVEL SWITCH LIGHT LIGHTING LIGHTS MOTOR CONTACTOR COIL M!LLIAMPS MANUAL MAGNETIC MAXIMUM MOTOR CONTROL CENTER MAIN CONTROL BOARD MOTOR CIRCUIT PROTECTOR MOTORIZED DAMPER

MDR

MH MTG MIN MLO MDV MS MMS MTD MTR MTS MUX N NA NC NO NO NOS NP (N) NTS 0 oc cc OL osc p

PB PCM PCP PF PH,¢ Pl PL PLC PNL PNLBD POS PQM PDT PRI P/S PS PT PVC REC RECPTS REQ'D REV RGS RTU RVNR RVSS SC SCH SEC SECT SS SEQ SHLD

SHT SIG SP SPDT SPECS SP HTR SPST SS ST STA STD STL STR sov SW SYS SYM TB TC TACH TEMP TERM T'STAT TR TD TS TSP TVSS 1YP UG UH UI UON UPS v VAR VFD VP vs w WHD WHM WP x

MANUFACTLRERS DESIGNATION FOR SPECIFIC POWER SUPPLY

MANHOLE MOUNTING MINIMUM, MINUTES MAIN LUGS ONLY MOTOR OPERATED VALVE MOTOR STARTER MANUAL MOTOR STARTER MOUNTED MOTOR MANUAL TRANSFER SWITCH MULTIPLEXING PANEL NEUTRAL NON·-AUTOMATIC NORMALLY CLOSED NORMALLY OPEN NUMBER NUMBERS NAMEPLATE NEW OR PROPOSED NOT TO SCALE OPEN ON CENTER CENTER TO CENTER OVERLOAD RELAY OSCILLATION POLE PUSH BUITON PROCESS CONTROL MODULE PROCESS CONTROL PANEL POWER FACTOR PHASE PULSE IN PILOT LIGHT PROGRAMMABLE LOGIC CONTROLLER PANEL PANEL.BOARD POSITION POWER QUALITY MONITOR POTENTIOMETER PRIMARY POWER SUPPLY PRESSURE SWITCH POTENTIAL TRANSFORMER POLYVINYL CHLORIDE RECEPTACLE RECEPTACLES REQUIRED REVERSE RIGID GALVANIZED STEEL REMOTE TERMINAL UNIT REDUCED VOLTAGE NON-REVERSING REDUCED VOLTAGE SOLID STATE SHORT CIRCUIT CURRENT SCHEDULE SECONDARY, SECONDS SECTION SELECTOR SWITCH SEQUENCE SHIELDED

SHEET SIGNAL SPARE SINGLE POLE DOUBLE THROW SPECIFICATIONS SPACE HEATER SINGLE POLE SINGLE THROW SOLID STATE SHUNT TRIP STATION STANDARD STEEL STARTER SOLENOID OPERATED VALVE SWITCH SYSTEM SYMMETRICAL TERMINAL BOX TIME CLOCK TACHOMETER TEMPERATURE TERMINAL THERMOSTAT TIMING RELAY TIME DELAY TEMPERATURE SWITCH lW!STEO SHIELDED P,~IR

TRANSIENT VOLTAGE SURGE SUPPRESSOR IYPICAL UNDERGROUND UNIT HEATER UNIVERSAL !N

UNLESS OTHERWISE NOTED UNINTERRUPTIBLE POWER SUPPLY VOLTAGE, VOLTS VAR METER VARIABLE FREQUENCY DRIVE VAPOR PROOF VOLTMETER SWITCH, VARIABLE SPEED WATTS, WIRE WA TTHOUR DEMAND METER WATTHOUR METER WEATHERPROOF WIRING TERMINAL

TIME DELAY CONTACTS INST. CLOSE TIME OPEN

OFF DELAY TIMER

T INST. OPEN TIME CLOSE ~--~--~~-+-~~~~--~~

TIME CLOSE INST. OPEN ON DELAY

TIMER

c.°1 __ -o__,_ _________ l_:~E OPEN INST. CLOSE

OPERATORS ~ T·---L-0-CK-,O-U_T_ST_O_P_P_US-"H_B_U_TT_O_N ______ _

r-_;: .. ox

.-{') ;;:m «i-0 -o-i """'

PUSHBUTION NORMALLY OPEN

TWO POSITION SELECTOR SWITCH

THREE POSITION SELECTOR SWITCH

X DENOTES CLOSED CONTACT IN

THAT POSITION

TOGGLE SWITCH

PILOT LIGHT -- PUSH TO TEST,

X DENOTES COLOR ----~-----------------~

DRAWING LEGEND .-----~--~-----------------·-

! ----

! l(X)(X

---'0 I !

0

0

c--1 i

!

I

EXISTING EQUIPMENT, WIRING, DEVICES

NEW WORK

DEMOLISH OR REMOVE

CONDUIT TURNING UP

CONDUIT TURNING DOWN

EQUIPMENT OR DEVICE TAG

SHEET NOTE TAG

HVAC/l.IGHTING DEVICE (SEE SCMEDULE)

DUPLEX RECEPTACLE, 20A, 125V, NEMA 5-20R

DOUBLE DUPLEX RECEPTACLE, 20A, 125V,

NEMA 5-20R

FLUORESCENT LIGHTING FIXTLRE

JUNCTION BOX, SIZE PER NEC

WALL MOUNTED LUMINAIRE

LIGHT SWITCH. SUBSCRIPT • a" INDICATES LUMINA RE CONTROLLED, MOUNT AT 48",

3/4" x 10' CU CLAD GROUND ROD.

UNDERGROUND CONDUIT OR DUCTBANK.

f-------+-------~·------------~

!1111 INSTRUMENTATION DEVICE

~------~-------- I i;;s1 MINI-POWER ZONE (COMBINATION TRANSFORMER & ~ PANELBOARD)

L SHORT HASH MARK INDICATES HOT WIRE

111/J '" INDICATES GROUND CONDUCTOR

""'---LONG HASH MARK INDICATES NEUTRAL WIRE

NOTE: NO HASH MARK INDICATES 3/4"C. 2#12+1#12G __J

ELECTRICAL COMPONENTS EARTH GROUND

--·--f-----------------------1 I

rh CHASSIS GROUND

GROUNDED RECEPTACLE

FUSE

B HORN

TRANSFORMER

SOLENOID

OVERLOAD RELAY

~

0 0 CIRCUIT BREAKER

!-----~-------------------------

@ MOTOR (NO. DENOTES HORSEPOWER)

COIL

RELAY CONTACT, N.O.

RELAY CONTACT, N.C.

SHIELDED CABLE

OIOOE, SURGE SUPPRESSOR

SURGE SUPPRESSOR

TERMINAL BLOCK

SEPARABLE CONNECTOR

POTENTIOMETER

CURRENT TRANSFORMER

PRESSURE SWITCHES OPEN - CLOSES ON RISING PRESSURE

CLOSED - CLOSES ON FALLING PRESSURE

OPEN - OPENS ON RJSING PRESSURE

CLOSED - OPENS ON FALLING PRESSURE

LIMIT SWITCHES NORMALLY OPEN

HELD OPEN

NORMALLY CLOSED

LEVEL FLOAT SWITCHES ~ O CLOSES ON RISING LEVEL

°t CLOSES ON FALLING LEVEL I I 6 OPENS ON RISING LEVEL I '

'-~---'---o-PE_N_s_o_N __ FALLl_'_N_G_L_EVE_· _L __________ I

'

GENERAL ELECTRICAL CONSTRUCTION NOTES 1. CONTRACTOR IS RESPONSIBLE FOR VERIFY EXISTING

CONOITIONS AND ROUTE CONDUITS WITHOUT DISTURBING EXISTING UTILITIES. IN ADDITION, CONDUIT ROUTING !£1:il BE APPROVED BY THE ENGINEER. FEASIBILITY OF THE LOCATION OF THE EQUIPMENT SHALL BE FIELD \IERIFlED. COORDINATE WITH ALL TRADES.

2, VERIFY, LOCATE AND PRESERVE ALL UNDERGROUND UTILITIES. REPAIR ALL UTILITIES DAMAGED DURING CONSTRUCTION TO OWNER'S SATISFACTION.

3. MINOR CHANGES IN WORK DUE TO EXISTING CONDITIONS SHALL BE MADE WITHOUT ADDITIONAL COST TO THE OWNER.

4. ELECTRICAL CONTRACTOR SHALL VISIT JOB SITE AND VERIFY EXISTING CONDITIONS BEFORE BIDDING AND SHALL INCLUDE IN HIS BID THE NECESSARY COSTS TO CONSTRUCT THIS PROJECT IN ACCORDANCE WITH THE INTENT OF THE ELECTRICAL DRAW1NGS, SPECIFICATIONS, AND ALL APPLICABLE CODES.

5. THE ELECTRICAL INSTALLATION SHALL COMPLY WITH ALL LOCAL, STATE, AND NATIONAL CODES, LAWS, AND ORDINANCES APPLICABLE TO ELECTRICAL WORK.

6. ALL ELECTRICAL MATERIALS AND EQUIPMENT SHALL BE LISTED BY UNDERWRITERS LABORATORIES.

7. THE WORD PRCViDE AS USED ON THE DRAWINGS SHALL BE DEFINED AS CONTRACTOR FURNISHED AND INSTALLED.

8. AT LEAST TWO WORKING DAYS PRIOR TO ANY EXCAVATION WORK, THE CONTRACTOR SHALL CALL UNDERGROUND SERVICE ALERT AT 1-800-227-2600 FOR LOCATING AND MARKlNG UTILITIES IN THE AREAS OF THE WORK

9. ALL UNDERGROUND CONDUITS SHALL BE PVC, SCHEDULE 40 OR BEITER UNLESS OTHERWISE NOTED.

NOTES RACEWAYS 1. CONDUIT ROUTING SHOWN ON DRAWINGS IS DIAGRAMMATIC

TO ILLUSTRATE DESIGN INTENT. CONTRACTOR SHALL FIELD DETERMINE THE MOST SUITABLE ROUTING TO FACILITATE INSTALLATION.

2. ALL CONDUIT RUNS SHALL BE INSTALLED WITH A MINIMUM NUMBER OF BENDS AND OFFSETS, GENERALLY, A RUN OF CONDUIT CONTAINING LOW VOLTAGE (600 VOLT MAXIMUM) WIRE SHALL HAVE A MAXIMUM PULLING DISTANCE OF 300 FEET AND CONTAIN NO MORE THAN THREE AND ONE-HALF QUARTER BENDS (315 DEGREES TOTAL), INCLUDING OFFSETS AND BENDS LOCATED IMMEDIATELY ADJACENT TO THE PULL LOCATION. ON RUNS OVER 300 FEET THIS SHALL BE REDUCED TO TWO QUARTER BENDS (180 DEGREES TOTAL).

3. CONDUIT UNIONS SHALL BE INSTALLED AT REMOVABLE DEVICES SUCH THAT THE DEVICES CAN BE EASILY AND INDEPENDENTLY REMOVED.

4. NOT ALL FITTINGS REQUIRED FOR A COMPLETE CONDUIT SYSTEM ARE SHOWN ON THE DRAWINGS. IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO INSTALL THE NUMBER AND TYPE OF FITTINGS REQUIRED FOR A COMPLETE CONDUIT SYSTEM WHICH COMPLIES WITH ALL APPLICABLE CODES AND STANDARDS. THE THREADS Of FITIINGS, INCLUDING COVER SCREWS AND SOL TS, SHALL BE COATED WITH A CONDUCTIVE THREAD LUBRICANT PRIOR TO INSTALLATION TO PROTECT AGAINST CORROSION,

5. ALL CONDUIT FITTINGS AND JUNCTION BOXES SHALL BE INSTALLED SO THAT THEIR COVERS ARE EASILY REMOVED.

5. ALL METAWC CONDUIT SHALL BE TERMINATED WITH INSULATED BUSHINGS TO PREVENT DAMAGE TO WIRE DURING PULLING OP£RATIONS, EXCEPT IN ENCLOSURES WHERE HUB DESIGN IS ADEQUATE TO PREVENT INSULATION DAMAGE, GROUNDING CONNECTIONS SHALL BE PROVIDED ON ALL INSTALLED 6USHINGS FOR GROUND CONTINUITY.

7. CONDUITS SHALL NOT BE SUPPORTED FROM EQUIPMENT OR PIPING. CONDUITS SHALL BE SUPPORTED AT INTERVAL AS REQUIRED BY NEC 344.30, 'SECURING AND SUPPORTs" AND TABLE 344.30(8)(2), TO PREVENT NOTICEABLE SAG. NO NOTICEABLE SAG Sf!ALL BE ALLOWED. THE CONTRACTOR SHALL PROVIDE ANY ADDITIONAL SUPPORT REQUIRED TO PREVENT OSJECTIONABLE SAG. IF RIGID ALUMINUM CONDUIT IS USED, THE SUPPORT SYSTEM SHALL BE OF SUITABLE MATERLAL OR CONSTRUCTION TO PREVENT GALVANIC ACTION,

8, LIQUID-TITE FLEXIBLE CONDUIT WITH PVC JACKET SHALL BE USED WHERE VIBRATION IS PRESENT, WHERE FLEXIBILITY IS REQUIRED, AND AT ALL MOTOR CONDUIT BOXES. TERMINATIONS OF FLEXIBLE METALLIC CONDUIT SHALL BE MADE USING LIQUID-TIGHT CONNECTORS WITH INTEGRAL INSULATED BUSHINGS AND POSITIVE GROUND CONNECTIONS. THE MAXIMUM LENGTH OF FLEXIBLE CONDUIT SHALL BE 24 INCH(;S FOR INSTRUMENTS AND EQUIPMENT, 36 INCHES FOR MOTORS, AND 48 INCHES FOR LIGHTING.

9. RUNS OF ABOVE GROUND CONDUIT FOR ANY SERVICE SHALL NOT BE DIRECTLY SUPPORTED FROM OVERHEAD PIPING.

10, ALL ABOVE GROUND, STRAIGHT CONDUIT RUNS OVER ZOO FEET LONG SHALL HAVE EXPANSION FITTINGS, WITH PROVISION FOR 4 INCHES TOTAL EXPANSION, BONDING JUMPERS SHALL BE INSTALLED TO ASSURE GROUNDING CONTINUITY,

11, THREADED JOINTS FOR CONDUITS SHALL BE MADE UP WITH A METAL OXIDE PAINT SUCH AS "T&B" KOPR-SHIELD, BURNDY PENETRDX E OR APPROVED EQUAL,

12. USE CA!lLE PULL!NG LUBRICANT, SUCH AS, POL '!'WATER OR EQUAL FOR CABLE PULLS IN CCNDU!T GREATER THAN 10-FEET,

NOTES - WIRING 1. SINGLE OR MULTICONDUCTOR CABLE MAY BE USED FOR

CONTROL, INSTRUMENT, COMMUNICATION AND SIGNAL CIRCUfTS, SINGLE-CONDUCTOR SHALL #14 AWG MINIMUM; SINGLE PAIRED CABLES SHALL BE 1/18 AWG MfNIMUM; AND MULTICONOUCTOR CABLE SHALL BE #20 AWG MINIMUM. CIRCUITS CLASSIFIED AS CLASS I CIRCUITS BY NEC ARTICLE 725 SHALL BE 1/18 AWG MINIMUM, 600 VOLT INSULATION CLASS,

2. ALL FIELD POWER, CONTROL AND LIGHTING CONDUCTORS SHALL BE COLOR CODED AS FOLLOWS UNLESS OTHERWISE SPECIFIED. • BLACK - ALL UNGROUNDED CONTROL CIRCUIT

CONDUCTORS OPERATING AT THE SUPPLY VOLTAGE,

• RED - UNGROUNDED AC CONTROL CIRCUITS OPERATING AT A VOLTAGE LESS THAN THE SUPPLY VOLTAGE.

• BLUE - UNGROUNDED DC CONTROL CIRCUITS, • YELLOW OR ORANGE - UNGROUNDED CONTROL CIRCUITS

OR OTHER WIRING,

• WHITE - GROUNDED AC CURRENT-CARRYING CONTROL CIRCUIT CONDUCTOR REGARDLESS OF VOLTAGE,

• GRAY - GROUNDED DC CURRENT-·CARRYING CONTROL CIRCUIT CONDUCTOR.

ALL INTERIOR CONTROL PANEL WIRING SHALL BE PER UL 508A, LATEST EDITION.

3. NO MORE THAN lWO CONDUCTORS SHALL BE CON NEC TED TO ANY ONE TERMINAL ON A TERMINAL STRIP, IF MORE THAN TWO CONDUCTORS MUST BE TERMINATED AT THE SAME POINT, THE TERMINATIONS SHALL BE MADE ON AS MANY TERMINALS AS NECESSARY ANO THE TERMINALS INTERCONNECTED WITH JUMPERS. THE JUMPERS SHALL BE PHYSICALLY SEPARATED FROM THE CONDUCTORS,

4, FOR POWER AND LIGHTING CIRCUITS, 600 VOLTS AND BELOW, THE SMALLEST WIRE SHALL BE #12 AWG. EXCEPT THAT #14 AWG SHALL BE USED FOR CONTROLS, WIRES SHALL SE SINGLE CONDUCTOR, COPPER, STRANDED, 500 VOLT HEAT AND MOISTURE RESISTANT THERMOPLASTIC INSULATED TYPE "THHN/fHWN", UNDERGROUND CONDUCTORS MUST BE RHW, UNLESS OTHERWISE NOTED.

5. #10 AWG OR LARGER SHALL BE XHHW UNLESS NOTED OTHERWISE.

6. MOTOR JUNCTION BOX CONNECTIONS SHALL BE CRIMP LUG/60L TED CONNECTIONS WITH 3M MOTOR SPLICE KIT 53.00 SERIES INSULATORS.

NOTES - LABELS 1. PROVIDE LAMINATED PLASTIC EQUIPMENT NAMEPLATE LABELS

AT ALL FIELD DEVICES, DENOTING EQUIPMENT NAME, VOLTAGE AND FEEDER ORIGIN. PLASTIC NAMEPLATES SHALL BE BLACK WITH WHITE LETIERS. ALL EXISTING PANELBOARD CIRCUIT DIRECTORIES SHALL BE UPDATED DENOTING NEW EQUIPMENT LOADS.

2. ALL JUNCTION BOX COVERPLATES SHALL SE LABELED WITH CIRCUIT NUMBERS IT CONTAINS,

3, NAMEPLATES AND TAGS SHALL BE PROVIDED FOR ELECTRICAL EQUIPMENT AND DEVICES, INCLUDING ALL PUSHSun"ONS. SELECTOR SWITCHES, CIRCUIT BREAKERS AND STARTERS. WHERE EQUIPMENT ALSO CAN BE STARTED FROM ANOTHER LOCATION, OR STARTED AUTOMATICALLY, A CAlfflON NAMEPLATE SHALL BE PROVIDED.

4, THE NAMEPLATE DESCRIPTION SHALL SHOW THE EQUIPMENT NUMBER AND SERVICE OF THE CONTROLLED EQUIPMENT, ALL PANELBOARDS SHALL HAVE NAMEPLATES STATING THE APPROPRIATE DESIGNATION, VOLTAGE, CONTINUOUS RATING, AND NUMBER OF PHASES. LIGHTING AND POWER PANELS SHALL BE SUPPLIED WITH COMPLETED CIRCUIT DIRECTORIES.

5. ALL WIRING SHALL BE IDENTIFIED AT EACH TERMINATION WITH PERMANENT, PRINTED, HEAT-SHRINKABLE PIASTIC SLEEVES OR WITH CLEAR, HEAT-SHRINKABLE SLEEVES THAT COVER ADHESIVE WRAP-ON MARKERS, COl'ITRACTOR SHALL USE A 'BRADY' OR EQUAL TYPE WIRE MARKER. THE WIRE IDENTIFICATION NUMBER SHALL INCLUDE THE COMPLETE CIRCUIT OR INSTRUMENT NUMBER. THE WIRE IDENTIFICATION SHALL BE THE IDENTIF1CATION SHOWN ON THE WIRING DIAGRAM. IF NONE IS SHOWN ON A WIRING DIAGRAM, THE OWNERS REPRESENTATIVE SHALL BE CONSULTED FOR PROPER IDENTIFICATION, ELECTRICAL CABLES SHALL BE LABELED WITH THE CIRCUIT NUMBER AND PHASE DESIGNATION AT EACH END OF CABLE. IF THE CABLE IS IN CONDUIT, THE CONDUIT TAG MAY SERVE AS AN INDICATION OF THE CIRCUIT NUMBER FOR POWER CIRCUITS.

NOTES - GROUNDING 1. ALL INSULATED GROUND!NG CONDUCTORS SHALL BE MADE OF

SOFT DRAWN, STRANDED COPPER WIRE, UTILIZING GREEN, FlRE RETARDANT INSULATION. ALL EXPOSED GROUNDING CONDUCTORS SHALL BE MINIMUM 1/2 AWG, RIGIDLY SUPPORTED, AND PROTECTED FROM MECHANICAL INJURY,

2, ALL UN-INSULATED GROUNDING CONDUCTORS (STRANDED OR SOLID) SHALL BE TINNED COPPER

3. ALL CONNECTIONS SHALL BE COATED WITH A CONDUCTIVE. CORROSION PREVENTIVE COMPOUND BEFORE JOINING.

4. ALL GROUND CONNECTIONS SHALL BE EXOTHERMIC.

I

T !

IJ) ..., 0

0

>, ro

>­CD

z 0 (f)

> w a:::

1----l'----'~~--~--~

CONTRACT NO.

C02150

SHEET 12 OF 13

FILE NO. 2018 - 0004