Analog and Digital I/O Conversion Module (Cat 1492-CM1771-LA004) I. Description This I/O Conversion Module provides for the conversion of (1) 1771, 8 Ch Analog I/O module to be converted to (1) or (2) 1756, 6 or 8 Ch Analog I/O module(s) and consists of the following: (1) Conversion Module: 1492-CM1771-LA004 (1) Cable: 1492-CONACAB005F8 or 1492-CONACAB010F8 (1) Conversion Mounting Assembly: 1492-MUA… (Table 1) (1) Conversion Module: 1492-CM1771-LA004 (1) Cable: 1492-CONACAB005K8 or 1492-CONACAB005L8 (1) Conversion Mounting Assembly: 1492-MUA… (Table 1) (1) Conversion Module: 1492-CM1771-LA004 (1) Cable: 1492-CONACAB005F or 1492-CONACAB005K or 1492-CONACAB005L (1) Conversion Mounting Assembly: 1492-MUA… (Table 1) (1) Conversion Module(s): 1492-CM1771-LA004 (1) Cable: 1492-CONACAB005T1 or 1492-CONACAB005T2 (1) Conversion Mounting Assembly: 1492-MUA… (Table 1) This I/O Conversion Module also provides for the conversion of (2) 1771 Digital I/O modules that also use the 1771-WF swing arm. In this case, this I/O conversion modules provide for the conversion of (2) 1771, 8 pt. Digital I/O modules to be converted to (1) 1756, 16 pt. Digital I/O module and consists of the following: (2) 1771 Module (8pt) to (1) 1756 Module (16pt) (2) Conversion Modules: 1492-CM1771-LA004 (1) Cable: 1492-C005005XT (1) Conversion Mounting Assembly: 1492-MUA… (Table 1) These conversions are accomplished without the removal of any field wires from the existing 1771 Swing Arms. The existing 1771 Swing Arms fit directly onto the edge connector of the 1492 Conversion Modules. On one end of the 1492 Cable are (2) connectors for the Conversion Modules and on the other end is (1) Removable Terminal Block (RTB) for the 1756 I/O module. See the photos below. The I/O signals are routed through the 1492 Conversion Module(s) and the 1492 Cable(s) to the appropriate terminals on the 1756 I/O module(s) per the Wiring Diagrams in Section V. As standard, the 1492 Cables are 0.5M long, but we also offer a 1.0M cable length. Refer to the footnotes in Table 2 for further details. De-energize and lockout any and all power to all I/O field devices connected to the A-B 1771 I/O chassis, and the power to the 1771 I/O chassis itself. Ensure all power is de-energized and locked out to any device in the control cabinet where the conversion is to be performed. Ensure work is performed by qualified personnel. WARNING (1) PN-114290 DIR 10000060101 (Version 04) Publication 1492-IN048C-EN-E Printed in U.S.A.

Upload: others

Post on 21-Mar-2022

2 views

Category:

Documents


0 download

TRANSCRIPT

Analog and Digital I/O Conversion Module(Cat 1492-CM1771-LA004)

I. DescriptionThis I/O Conversion Module provides for the conversion of (1) 1771, 8 Ch Analog I/O module to be converted to (1) or (2) 1756, 6 or 8 Ch Analog I/O module(s) and consists of the following:

(1) Conversion Module: 1492-CM1771-LA004 (1) Cable: 1492-CONACAB005F8 or 1492-CONACAB010F8 (1) Conversion Mounting Assembly: 1492-MUA… (Table 1)

(1) Conversion Module: 1492-CM1771-LA004 (1) Cable: 1492-CONACAB005K8 or 1492-CONACAB005L8 (1) Conversion Mounting Assembly: 1492-MUA… (Table 1)

(1) Conversion Module: 1492-CM1771-LA004 (1) Cable: 1492-CONACAB005F or 1492-CONACAB005K or 1492-CONACAB005L (1) Conversion Mounting Assembly: 1492-MUA… (Table 1)

(1) Conversion Module(s): 1492-CM1771-LA004 (1) Cable: 1492-CONACAB005T1 or 1492-CONACAB005T2 (1) Conversion Mounting Assembly: 1492-MUA… (Table 1)

This I/O Conversion Module also provides for the conversion of (2) 1771 Digital I/O modules that also use the 1771-WF swing arm. In this case, this I/O conversion modules provide for the conversion of (2) 1771, 8 pt. Digital I/O modules to be converted to (1) 1756, 16 pt. Digital I/O module and consists of the following:

(2) 1771 Module (8pt) to (1) 1756 Module (16pt)(2) Conversion Modules: 1492-CM1771-LA004 (1) Cable: 1492-C005005XT (1) Conversion Mounting Assembly: 1492-MUA… (Table 1)

These conversions are accomplished without the removal of any field wires from the existing 1771 Swing Arms. The existing 1771 Swing Arms fit directly onto the edge connector of the 1492 Conversion Modules. On one end of the 1492 Cable are (2) connectors for the Conversion Modules and on the other end is (1) Removable Terminal Block (RTB) for the 1756 I/O module. See the photos below.

The I/O signals are routed through the 1492 Conversion Module(s) and the 1492 Cable(s) to the appropriate terminals on the 1756 I/O module(s) per the Wiring Diagrams in Section V. As standard, the 1492 Cables are 0.5M long, but we also offer a 1.0M cable length. Refer to the footnotes in Table 2 for further details.

De-energize and lockout any and all power to all I/O field devices connected to the A-B 1771 I/O chassis, and the power to the 1771 I/O chassis itself. Ensure all power is de-energized and locked out to any device in the control cabinet where the conversion is to be performed. Ensure work is performed by qualified personnel.

WARNING

(1)PN-114290DIR 10000060101 (Version 04)Publication 1492-IN048C-EN-EPrinted in U.S.A.

(2)

Conversion Compatibilityand Product I.D. Label

25-Pin Connector for cable 1492-CONACAB005_

1492-CM1771-LA004 Conversion Module

I. Description (Cont’d)

Conversion Compatibilityand Product I.D. Label

25-Pin Connector for cable1492-CONACAB005T_

Cable1492-CONACAB005T_

ConversionCompatibility andProduct I.D. Label

25-Pin Connectorfor cable1492-C005005XT

PN-114290DIR 10000060101 (Version 04)Publication 1492-IN048C-EN-E

(3)

II. Installation

The 1492 Conversion Modules must be installed in a 1492 Conversion Mounting Assembly (see Table 1 below). A complete System Installation Manual ships with the 1492 Conversion Mounting Assembly.

1) Determine the quantity of each type of 1771 I/O modules used in the 1771 I/O Chassis to be converted.2) Select the applicable 1492 Conversion Modules from Table 2, Section III.3) Review the Max Slots for I/O and Chassis Width data from the Table 1 below.4) Select a 1756 I/O Chassis which has enough I/O Slots.NOTE: (2) I/O slots are required in the 1756 Chassis for conversions where (1) 1771 I/O module converts to (2) 1756 I/O modules.5) Select the 1492 Conversion Mounting Assembly which has enough Conversion Module slots.NOTE: (2) Conversion Module slots are required in the 1492 Conversion Mounting Assembly for conversions where (2) 1771 I/O module convert to (1) 1756 I/O modules.NOTE: The 1492 Conversion Mounting Assembly has the same Height & Width foot-print as the 1771 Chassis and is designed to use the same mounting hardware. The combined Depth of the 1492 Conversion Mounting Assembly with the 1756 Chassis mounted on top is 10.25 inches (Controller w/key) or 10.0 inches (Controller w/o key). Dimension drawings are included in the System Installation Manual that ships with the 1492 Conversion Mounting Assembly.

� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �

� � � � � �

� � �� � � �

� �� � �

� � � � �! �

� � " " � �

� � �! �

� � " " � �

� � � � � �

� � �� � � �

� �� � �

� � � � � � �# � $ � �

� � � � � �

� � � � � � �� �

� � � � � � �� $ � � �

� � � � � � �# � $ � �

� � � % � & ' � ( � ' �� � � � % � � ) & * � ( � � + � �

� � � % � � � & � & *� & * + % � , � � ) % � & % � � & * � ( �

� � � % � � � & � & *� � � � % � + ) - � & � ( � � � � �

� � � % � � ( * � * � ( +� & * + % � , � + ) % � � % � � ( - � & � ( �

� � � % � � ( * � * � ( +� + � * � ( �

� � � % � � ' � + + ' � � �� & * + % � , � ' % � � ( % � � ' � + � * � ( �

� � � % � � ' � + + ' � � �� � � � % � & ) � + & � ( �

� � � % � � � � + * � ( � & * + % � , � & % � � ' % � � � � + & � ( �

1771-A3B is not listed as it is used for 19 inch wide instrumentation panels.

Notice that the 1756 Chassis Width sometimes exceeds the 1771 Chassis Width, with or without the Power Supply. The Cover-Plate of the 1492 Conversion Mounting Assembly allows the 1756 Chassis to be Left justified, Right justified or Centered. A complete System Installation Manual ships with the 1492 Conversion Mounting Assembly.

. / 0 1 2 3 4 5 6 1 1 2 7 8 9 3 : : 3 7 ; 3 : < = > ? / @ @ 8 @ > ; 9 A 2 B @ 8 ; 9

� � � � % � ' ) �

� � � � � � � # � $ � �

PN-114290DIR 10000060101 (Version 04)Publication 1492-IN048C-EN-E

(4)

IV. Conversion Module Specifications

(Operating specifications are when installed in the Conversion System base / cover-plate assembly)

III. Compatibility

Foot Notes:①To understand any issues concerning I/O module compatibility, refer to the Installation Manuals for the specific 1771

and 1756 I/O modules involved.②The 3 numbers indicate the length of the 1492 Cable. Recommended cable lengths of 0.5M are shown. Additional

cable lengths are as follows: 1.0M = 1492-CONACAB010F/8 or 1492-CONACAB010K/8 or 1492-CONACAB010L/81.0M = 1492-CONACAB010T1 or 1492-CONACAB010T2

③The 6 numbers indicate the cable length of each portion of the 1492 Cable. Recommended cable lengths of 0.5M / 0.5M are shown. Additional cable lengths are as follows:1.0M / 1.0M = 1492-C010010XT0.5M / 1.0M = 1492-C005010XT1.0M / 0.5M = 1492-C010005XT

④These cables have a maximum operating voltage of 30VDC, 2A maximum per pin, 12A maximum per cable.

Specification Value Dimensions

Approximate Shipping Weight Storage Temperature -40 to +85 C (-40 to 185° F) Operating Temperature 0 to 60 C (32 to 40° F) Operating Humidity 5 to 95% at 60° C (non-condensing) Shock Non -operating Operating

50g 30g

Operating Vibration 2g at 10 to 500Hz (Agrees with 1756 I/O module specification) Maximum Operating Voltage 30 Vdc Max. Module Operating Current

Per Point: Per Module:

Agency Certifications

UL Classified: Under UL File Number E113724 CSA

CE : compliant for all applicable directives

Pollution Degree 2 Environmental Rating IP20

Refer to the Wiring Diagram(s) for current limits for a specific configura-

NOTICE

2 Amps12 Amps

11.81 in. (height) x 4.38 in. (depth) x 1.5 in. (width)300 mm. (height) x 111.25 mm (depth) x 38.1 mm (width)

250.6 g (0.55 lbs) (includes carton)

PN-114290DIR 10000060101 (Version 04)Publication 1492-IN048C-EN-E

� � � �� � � � � � � � � � � � �

� � � �� � � � � � � � � � � � �

� � � � � � � � � � � � � � � � � � � �

� � � �� � � � � �

� � � � � �� � � � � � �

� � �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

" # # " $ % H " # ' ( $ % H G * % " 5 6 7 $ . 8 " # # " $ & 9 : : 5 " 5 6 7 $ . ; < 9 . 9 = : : ' ) * ? " "" # # " $ % H " # ' ( $ % H ( % " 5 6 7 $ . 8 " # # " $ & 9 : : 5 " 5 6 7 $ . ; < 9 . 9 = : : ' ) ? " 7

" # # " $ ; E + E 3 F 7 4 + I J D J 3 C B 4 " # ' ( $ ; = " ( % " 5 6 7 $ . 8 " # # " $ & 9 : : 5 " 5 6 7 $ . : : ' : : ' K G L " M

(5)

Conversion: 1771-IL(1) to 1756-IF8I (1) (CURRENT)

The 1771-IL input configuration was software configured, as is the 1756-IF8I. Please ensure the correct configuration in the 1756-IF8I.

SHIELD GROUNDING: In some installations, the field wiring shield was grounded on the 1771 chassis. If this was the case, the installer must remove these shield connections from the 1771 chassis and they can be connected to the grounding stud on the 1492-CM1771-LA004 module. The pre-wired cable used between the 1492-CM1771-LA004 module and the 1756-IF8I [1492-CONACAB005K8] provides a shield ground lug to ground the shield at the 1756 ControlLogix chassis, this must be connected. Do NOT connect this ground lug to the conversion module grounding stud.

� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �

Refer to your 1771-IL and 1756-IF8I Installation and User Manuals for additional information concerning comparisons of module wiring, features and configuration details.

WARNING There are several key application considerations and system specifications (bottom of drawing) when usingthese components (conversion module, cable and input module). Read and understand these considerationsbefore installation.

Cables are available in lengths of 0.5M or 1.0M (005=0.5M, 010=1.0M)

18

� � � � � � � � � � � � � � � � �

1716151413121110

987

SH

432

6

1

5

� � � � � ! " # # $ % % & ' (

) * + , - . / 0 . 12 3 4 5 . / 0 . 1

6 * . . , / 2 3 4 5 .7 8 9 . / 2 3 4 5 .

) * + , - . / 7 8 + : ;

0 . 1 / 2 3 4 5 .

7 8 + : ; / 0 . 1

7 8 9 . / 7 8 + : ;7 8 + : ; / 2 3 4 5 .

6 * . . , / 7 8 + : ;

7 8 9 .) * + , - .

0 . 1 / 7 8 + : ;2 3 4 5 . / 7 8 + : ;

18

14131211

8

65

< = = < > ? @ A B C D E F G H@ G I H < = = < > J K

171615

4321

109

7

Channel6 Channel7Channel7

) * + , - .7 8 9 .2 3 4 5 . / 7 8 + : ;

0 . 1 / 7 8 + : ;Channel5 Channel5Channel6

Channel4Channel4

Channel3 Channel3

Channel0

Channel2Channel2

Channel1Channel1

Channel0 TransmitterPower Supply

+

-

4-Wire Transmitter

+ -

2-WireTransmitter

+

-

� L M N O P Q R L M � L S T U O� V W U O X Y Z [ \ ] ^ _ ]

4

3027

11

12

20

3

28

19

5

6

13

14

21

22

29

Iin_CH0RTN_CH0Iin_CH1RTN_CH1Iin_CH2RTN_CH2Iin_CH3RTN_CH3

Iin_CH4RTN_CH4Iin_CH5RTN_CH5Iin_CH6

RTN_CH7Iin_CH7RTN_CH6

2625

32

31

3433

2

1

98

1510

1716

23

18

7

24N.C.

N.C.

N.C.

N.C.

N.C.

N.C.

N.C.

N.C.

N.C.

N.C.

N.C.

N.C.

3635

N.C.

N.C.

N.C.

N.C.

N.C.

N.C.

N.C.

N.C.

V. Wiring Diagrams

PN-114290DIR 10000060101 (Version 04)Publication 1492-IN048C-EN-E

3

(6)

Conversion: 1771-IL (1) to 1756-IF8I (1) (VOLTAGE)

WARNING There are several key application considerations and system specifications (bottom of drawing) when usingthese components (conversion module, cable and input module). Read and understand these considerationsbefore installation.

The 1771-IL input configuration was software configured, as is the 1756-IF8I. Please ensure the correct configuration in the 1756-IF8I.

SHIELD GROUNDING: In some installations, the field wiring shield was grounded on the 1771 chassis. If this was the case, the installer must remove these shield connections from the 1771 chassis and they can be connected to the grounding stud on the 1492-CM1771-LA004 module. The pre-wired cable used between the 1492-CM1771-LA004 module and the 1756-IF8I [1492-CONACAB005L8] provides a shield ground lug to ground the shield at the 1756 ControlLogix chassis, this must be connected. Do NOT connect this ground lug to the conversion module grounding stud.

Refer to your 1771-IL and 1756-IF8I Installation and User Manuals for additional information concerning comparisons of module wiring, features and configuration details.

Conversion Module Installation and Application Considerations Cables are available in lengths of 0.5M or 1.0M (005=0.5M, 010=1.0M)

18

� � � � � � � � � � � � � � �

1716151413121110

987

SH

432

6

1

5

� � � � � � � � � � � � � � � �

� � � � � �� � � � � � �

� � � � � � � � � � � � � � �

� � � � � � � �

� � � � � � �

� � � � � � �

� � � � � � � �� � � � � � � � �

� � � � � � �

� � � � � �

� � � � � � �� � � � � � � � �

18

14131211

8

65

� � � � � � � ! " # $ % & '� & ( ' � � � � � ) *

171615

4321

109

7

TransmitterPower Supply+

-

4-Wire Transmitter

+ -

� + , - . / 0 1 + , � + 2 3 4 .� 5 6 4 .

3

7 8 9 : ; < = > <

2

3025

9

10

18

1

26

17

5

6

13

14

21

22

29

Vout_CH0RTN_CH0Vout_CH1RTN_CH1Vout_CH2RTN_CH2Vout_CH3RTN_CH3

Vout_CH4RTN_CH4Vout_CH5RTN_CH5Vout_CH6

RTN_CH7Vout_CH7RTN_CH6

2724

31

28

3332

4

3

35

8

1211

1615

2019

7

23N.C.

N.C.

N.C.

N.C.

N.C.

N.C.

N.C.

N.C.

N.C.

N.C.

N.C.

N.C.

36

34

N.C.

N.C.

N.C.

N.C.

N.C.

N.C.

N.C.

N.C.

Vout_CH0RTN_CH0Vout_CH1RTN_CH1Vout_CH2RTN_CH2Vout_CH3RTN_CH3

Vout_CH4RTN_CH4Vout_CH5RTN_CH5Vout_CH6

RTN_CH7Vout_CH7RTN_CH6

� � � � � � � � � � � � � � �

� � � � � � �

V. Wiring Diagrams

PN-114290DIR 10000060101 (Version 04)Publication 1492-IN048C-EN-E

(7)

There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and input module). Read and understand these considerations before installation.

WARNING

Conversion Module Installation and Application Considerations Cables are available in lengths of 0.5M or 1.0M (005=0.5M, 010=1.0M)

SHIELD GROUNDING: In some installations, the field wiring shield was grounded on the 1771 chassis. If this was the case, the installer must remove these shield connections from the 1771 chassis and they can be connected to the grounding stud on the 1492-CM1771-LA004 module. The pre-wired cable used between the 1492-CM1771-LA004 module and the 1756-IF6I [1492-CONACAB005K] provides a shield ground lug to ground the shield at the 1756 Control-Logix chassis, this must be connected. Do NOT connect this ground lug to the conversion module grounding stud.

The 1771-IL input configuration was software configured, as is the 1756-IF6I. Please ensure the correct configuration in the 1756-IF6I.

Refer to your 1771-IL and 1756-IF6I Installation and User Manuals for additional information concerning comparisons of module wiring, features and configuration details. [Reference Doc: 41171-030]

1771-WF Swing ArmFrom 1771-IL

Conversion Module1492-CM1771-LA004 Cable

1492-CONACAB005K 1756-IF6I

Conversion: 1771-IL to 1756-IF6I (Current)

181716151413121110

987

SH

432

6

1

5

� � � � � � � � �

� � � � � �

� � � � � � � � �

� � � � � � � �

� � � � � � � � � � � �

� � � � � �

� � � � � � � �

� � � � � � � � � �

� � � � � � � � �

� � � � � � � � � � �

� � � �

� � � � � �

� � � � � � � �

� � � � � � � � �

18

14131211

8

65

171615

4321

109

7

Channel6 Channel7Channel7

� � � � �

� � �

� �

� � � � �

Channel5 Channel5Channel6

Channel4Channel4

Channel3 Channel3

Channel0

Channel2Channel2

Channel1Channel1

Channel0 53

64

119

1210

1917

16152018

1

278

RET-0

IN-0/I

IN-1/V

IN-4/IRET-4IN-5/IRET-5

TransmitterPower Supply+

-

4-Wire Transmitter

+ -

RET-1

IN-1/I

IN-0/V

RET-3

IN-3/I

IN-2/VIN-3/V

RET-2IN-2/I

IN-4/VIN-5/V

2-WireTransmitter

+

-

V. Wiring Diagrams

PN-114290DIR 10000060101 (Version 04)Publication 1492-IN048C-EN-E

(8)

There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and input module). Read and understand these considerations before installation.

WARNING

Conversion: 1771-IL to 1756 -IF6I (Voltage)

Conversion Module Installation and Application Considerations Cables are available in lengths of 0.5M or 1.0M (005=0.5M, 010=1.0M)

SHIELD GROUNDING: In some installations, the field wiring shield was grounded on the 1771 chassis. If this was the case, the installer must remove these shield connections from the 1771 chassis and they can be connected to the grounding stud on the 1492-CM1771-LA004 module. The pre-wired cable used between the 1492-CM1771-LA004 module and the 1756-IF6I [1492-CONACAB005L] provides a shield ground lug to ground the shield at the 1756 Control-Logix chassis, this must be connected. Do NOT connect this ground lug to the conversion module grounding stud.

The 1771-IL input configuration was software configured, as is the 1756-IF6I. Please ensure the correct configuration in the 1756-IF6I.

Refer to your 1771-IL and 1756-IF6I Installation and User Manuals for additional information concerning comparisons of module wiring, features and configuration details. [Reference Doc: 41171-029 ]

1771-WF Swing ArmFrom 1771-IL

Conversion Module1492-CM1771-LA004 Cable

1492-CONACAB005L 1756-IF6I

V. Wiring Diagrams

PN-114290DIR 10000060101 (Version 04)Publication 1492-IN048C-EN-E

181716151413121110

987

SH

432

6

1

5

� � � � � � � � �

� � � � � �

� � � � � � � � �

� � � � � � � �

� � � � � � � � � � � �

� � � � � �

� � � � � � � �

� � � � � � � � � �

� � � � � � � � �

� � � � � � � � � � �

� � � �

� � � � � �

� � � � � � � �

� � � � � � � � �

18

14131211

8

65

171615

4321

109

7

� � � � �

� � �

� �

� � � � �

152

47

118

12

1718

1915

1413

2016

109

RET-0IN-0

RET-1IN-1

RET-2IN-2

RET-3

IN-4RET-4IN-5RET-5

NO CONNECTNO CONNECT

TransmitterPower Supply+

-

2-Wire Transmitter

+ -

IN-3

43 NO CONNECT

NO CONNECTNO CONNECTNO CONNECTNO CONNECTNO CONNECT

Channel6 Channel7Channel7

Channel5 Channel5Channel6

Channel4Channel4

Channel3 Channel3

Channel0

Channel2Channel2

Channel1Channel1

Channel0

(9)

There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and input module). Read and understand these considerations before installation.

WARNING

Conversion Module1492-CM1771-LA004 Cable

1492-CONACAB005T1 1756-IF6I

1756-IF6I

Conversion: 1771-IL (1) to 1756-IF6I (2) (Current)

Conversion Module Installation and Application Considerations Cables are available in lengths of 0.5M or 1.0M (005=0.5M, 010=1.0M)

SHIELD GROUNDING: In some installations, the field wiring shield was grounded on the 1771 chassis. If this was the case, the installer must remove these shield connections from the 1771 chassis and they can be connected to the grounding stud on the 1492-CM1771-LA004 module. The pre-wired cable used between the 1492-CM1771-LA004 module and the 1756-IF6I [1492-CONACAB005T1] provides a shield ground lug to ground the shield at the 1756 ControlLogix chassis, this must be connected. Do NOT connect this ground lug to the conversion module grounding stud.

The 1771-IL input configuration was software configured, as is the 1756-IF6I. Please ensure the correct configuration in the 1756-IF6I.

Refer to your 1771-IL and 1756-IF6I Installation and User Manuals for additional information concerning comparisons of module wiring, features and configuration details.

This configuration uses two (2) 1756-IF6I output modules to replace a single 1771-IL output module. This may require the use of a larger 1756 I/O chassis and conversion mounting assembly. Ensure there is sufficient panel space to allow for this possibility. [Reference Doc: 41171-032]

V. Wiring Diagrams

PN-114290DIR 10000060101 (Version 04)Publication 1492-IN048C-EN-E

TransmitterPower Supply

4-Wire Transmitter

2-WireTransmitter

1771-WF Swing ArmFrom 1771-IL

181716151413121110

987

SH

432

6

1

5

� � � � � � � � �

� � � � � �

� � � � � � � � �

� � � � � � � �

� � � � � � � � � � � �

� � � � � �

� � � � � � � �

� � � � � � � � � �

� � � � � � � � �

� � � � � � � � � � �

� � � �

� � � � � �

� � � � � � � �

� � � � � � � � �

18

14131211

8

65

171615

4321

109

7

Channel6 Channel7Channel7

� � � � �

� � �

� �

� � � � �

Channel5 Channel5Channel6

Channel4Channel4

Channel3 Channel3

Channel0

Channel2Channel2

Channel1Channel1

Channel0 53

64

119

1210

1917

16152018

1

278

RET-0

IN-0/I

IN-1/V

IN-4/IRET-4IN-5/IRET-5

+

-

+ -

RET-1

IN-1/I

IN-0/V

RET-3

IN-3/I

IN-2/VIN-3/V

RET-2IN-2/I

IN-4/VIN-5/V

+

-

53

64

119

1210

1917

16152018

1

278

RET-0

IN-0/I

IN-1/V

IN-4/IRET-4IN-5/IRET-5

RET-1

IN-1/I

IN-0/V

RET-3

IN-3/I

IN-2/VIN-3/V

RET-2IN-2/I

IN-4/VIN-5/V

(10)

There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and input module). Read and understand these considerations before installation.

WARNING

Conversion Module1492-CM1771-LA004 Cable

1492-CONACAB005T2 1756-IF6I

1756-IF6I

Conversion: 1771-IL (1) to 1756-IF6I (2) (Voltage)

Conversion Module Installation and Application Considerations Cables are available in lengths of 0.5M or 1.0M (005=0.5M, 010=1.0M).

SHIELD GROUNDING: In some installations, the field wiring shield was grounded on the 1771 chassis. If this was the case, the installer must remove these shield connections from the 1771 chassis and they can be connected to the grounding stud on the 1492-CM1771-LA004 module. The pre-wired cable used between the 1492-CM1771-LA004 module and the 1756-IF6I [1492-CONACAB005T2] provides a shield ground lug to ground the shield at the 1756 ControlLogix chassis, this must be connected. Do NOT connect this ground lug to the conversion module grounding stud.

The 1771-IL input configuration was software configured, as is the 1756-IF6I. Please ensure the correct configuration in the 1756-IF6I.

Refer to your 1771-IL and 1756-IF6I Installation and User Manuals for additional information concerning comparisons of module wiring, features and configuration details.

This configuration uses two (2) 1756-IF6I output modules to replace a single 1771-IL output module. This may require the use of a larger 1756 I/O chassis and conversion mounting assembly. Ensure there is sufficient panel space to allow for this possibility. [Reference Doc: 41171-031]

V. Wiring Diagrams

PN-114290DIR 10000060101 (Version 04)Publication 1492-IN048C-EN-E

1771-WF Swing ArmFrom 1771-IL

181716151413121110

987

SH

432

6

1

5

� � � � � � � � �

� � � � � �

� � � � � � � � �

� � � � � � � �

� � � � � � � � � � � �

� � � � � �

� � � � � � � �

� � � � � � � � � �

� � � � � � � � �

� � � � � � � � � � �

� � � �

� � � � � �

� � � � � � � �

� � � � � � � � �

18

14131211

8

65

171615

4321

109

7

� � � � �

� � �

� �

� � � � �

152

67

118

12

1718

1915

1413

2016

109

RET-0IN-0

RET-1IN-1

RET-2IN-2

RET-3

IN-4RET-4IN-5RET-5

NO CONNECTNO CONNECT

TransmitterPower Supply+

-

4-Wire Transmitter

+ -

IN-3

43 NO CONNECT

NO CONNECTNO CONNECTNO CONNECTNO CONNECTNO CONNECT

Channel6 Channel7Channel7

Channel5 Channel5Channel6

Channel4Channel4

Channel3 Channel3

Channel2Channel2

Channel1Channel1

Channel0 Channel0

152

47

118

12

1718

1915

1413

2016

109

RET-0IN-0

RET-1IN-1

RET-2IN-2

RET-3

IN-4RET-4IN-5RET-5

NO CONNECTNO CONNECT

IN-3

43 NO CONNECT

NO CONNECTNO CONNECTNO CONNECTNO CONNECTNO CONNECT

2-WireTransmitter

+

-

(11)

PN-114290DIR 10000060101 (Version 04)Publication 1492-IN048C-EN-E

18

� � � � � � � � � � � � � � �

1716151413121110

987

SH

432

6

1

5

� � � � � � � � �� � � � � � � � �

� � � � � � � � � �� � � � � � � � � �

� � � � � � � � � � �

� � � � � � � � �

� � � � � � � � �

� � � � � � � � � �� � � � � � � � � � �

� � � � � � � � � �

� � � �� � � � �

� � � � � � � � �� � � � � � � � � � �

18

14131211

8

65

171615

4321

109

7

Channel6 - CChannel6 - BChannel6 - A

643

10

87

1412

1811

2022

1516

19262423

3-Wire RTD

2-Wire RTD

� � � � �� � � � �

� � �� � � �

Channel5 - CChannel5 - BChannel5 - A

Channel4 - C

Channel4 - BChannel4 - A

Channel3 - CChannel3 - B

Channel3 - A

Channel2 - C

Channel2 - BChannel2 - A

Channel1 - CChannel1 - B

Channel1 - A

WARNING There are several key application considerations and system sp cations (bottom of drawing) when usingthese components (conversion module, cable and output module). Read and understand these considerationsbefore installation.

� ! " # $ % & ' $

IN_0/RTD C

IN_1/RTD C

IN_1(-)/B

IN_1(+)/A

IN_2/RTD C

IN_2(-)/B

IN_2(+)/A

IN_3/RTD C

IN_3(-)/B

IN_3(+)/A

IN_4/RTD C

IN_4(-)/B

IN_4(+)/A

IN_5(+)/A

IN_5(-)/B

IN_5/RTD C

3130

33

32

3534

2

1

139

2117

2725

28

5

29N.C.

N.C.

N.C.

N.C.

N.C.

N.C.

N.C.

N.C.

N.C.

N.C.

N.C.

36

N.C.

N.C.

N.C.

N.C.

N.C.

N.C.

N.C.

IN_0(+)AIN_0(-)/B

Conversion Module Installation and Application Considerations Cables are available in lengths of 0.5M or 1.0M (005=0.5M, 010=1.0M)

shield connections from the 1771 chassis and they can be connected to the grounding stud on the 1492-CM1771-LA004 module. The pre-wired cable used between the 1492-CM1771-LA004 module and the 1756-IRT8I [1492-CONACAB005F8] provides a shield ground lug to ground the shield at the 1756 ControlLogix chassis, this must be connected. Do NOT connect this ground lug to the conversion module grounding stud.

Refer to your 1771-IR and 1756-IRT8I Installation and User Manuals for additional information concerning comparisons of module wiring, features and

Cable( ) * + , - . / 0 - 0 1 2 2 3 4 5

V. Wiring Diagrams

� 6 7 8 9 : ; < 6 7 � 6 = > ? 9

[Reference Doc: 10002306208]

Conversion Module Installation and Application Considerations Cables are available in lengths of 0.5M or 1.0M (005=0.5M, 010=1.0M).

SHIELD GROUNDING: In some installations, the field wiring shield was grounded on the 1771 chassis. If this was the case, the installer must remove these shield connections from the 1771 chassis and they can be connected to the grounding stud on the 1492-CM1771-LA004 module. The pre-wired cable used between the 1492-CM1771-LA004 module and the 1756-IR6I [1492-CONACAB005F] provides a shield ground lug to ground the shield at the 1756 Control-Logix chassis, this must be connected. Do NOT connect this ground lug to the conversion module grounding stud.

The 1771-IR input configuration was software configured, as is the 1756-IR6I. Please ensure the correct configuration in the 1756-IR6I.

Refer to your 1771-IR and 1756-IR6I Installation and User Manuals for additional information concerning comparisons of module wiring, features and configuration details. [Reference Doc: 41170-950]

There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and input module). Read and understand these considerations before installation.

WARNING

Conversion Module1492-CM1771-LA004

1771-WF Swing ArmFrom 1771-IR

Cable1492-CONACAB005F 1756-IR6I

Conversion: 1771-IR to 1756-IR6IV. Wiring Diagrams

PN-114290DIR 10000060101 (Version 04)Publication 1492-IN048C-EN-E

(12)

181716151413121110

987

SH

432

6

1

5

� � � � � � � � �

� � � � � �

� � � � � � � � �

� � � � � � � �

� � � � � � � � � � � �

� � � � � �

� � � � � � � �

� � � � � � � � � �

� � � � � � � � �

� � � � � � � � � � �

� � � �

� � � � � �

� � � � � � � �

� � � � � � � � �

18

14131211

8

65

171615

4321

109

7

Channel6 - CChannel6 - BChannel6 - A

5

IN-0/A

RTN-0/C3

IN-1/A

1

RTN-1/C6

IN-2/A

4

RTN-2/C

2

IN-3/A

11

RTN-3/C

9

RTN-4/C

12

IN-4/A

7

IN-0/B

17

IN-3/B

19

RTN-5/C

8

IN-5/A

10

IN-1/B

15

IN-2/B

20

IN-4/B

18IN-5/B

16

3-Wire RTD

2-Wire RTD

� � � � �

� � �

� �

� � � � �

Channel5 - CChannel5 - BChannel5 - A

Channel4 - C

Channel4 - BChannel4 - A

Channel3 - CChannel3 - B

Channel3 - A

Channel2 - C

Channel2 - BChannel2 - A

Channel1 - CChannel1 - B

Channel1 - A

There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and input module). Read and understand these considerations before installation.

WARNING

Conversion Module1492-CM1771-LA004

Conversion Module1492-CM1771-LA004

1771-WF Swing ArmFrom 1771-OQ

1771-WF Swing ArmFrom 1771-OQ

Cable1492-C005005XT 1756-OB16I

Conversion: 1771-OQ (2) to 1756-OB16I (1)V. Wiring Diagrams

PN-114290DIR 10000060101 (Version 04)Publication 1492-IN048C-EN-E

181716151413121110

987

432

6

1

5

� � � � � � � � �

� � � � � �

� � � � � � � � �

� � � � � � � �

� � � � � � � � � � � �

� � � � � �

� � � � � � � �

� � � � � � � � � �

� � � � � � � � �

� � � � � � � � � � �

� � � �

� � � � � �

� � � � � � � �

� � � � � � � � �

18

14131211

8

65

171615

4321

109

7

� � � � �

� � �

� �

� � � � �

214

3

10

14

13

DC-1OUTPUT-0

OUTPUT 1

DC-2

OUTPUT 2

DC-2

6

8

12

5

9

7

11

15

OUTPUT 3

DC-3

DC-3

DC-4

16DC-4

DC-1

OUTPUT-4

OUTPUT 5OUTPUT 6

OUTPUT 7

LOAD

+

-

LOAD

181716151413121110

987

432

6

1

5

� � � � � � � � �

� � � � � �

� � � � � � � � �

� � � � � � � �

� � � � � � � � � � � �

� � � � � �

� � � � � � � �

� � � � � � � � � �

� � � � � � � � �

� � � � � � � � � � �

� � � �

� � � � � �

� � � � � � � �

� � � � � � � � �

18

14131211

8

65

171615

4321

109

7

� � � � �

� � �

� �

� � � � �

181720

19

26

30

29

DC-1OUTPUT-8

OUTPUT 9

DC-2

OUTPUT 10

DC-2

22

24

28

21

25

23

27

31

OUTPUT 11

DC-3

DC-3

DC-4

32DC-4

DC-1

OUTPUT-12

OUTPUT 13OUTPUT 14

OUTPUT 15

LOAD

+

-

LOAD

NOT USED33343536

NOT USEDNOT USEDNOT USED

Cable “B”

Cable “A”DC-1

OUTPUT-0

OUTPUT 1

DC-2OUTPUT 2

DC-2OUTPUT 3

DC-3

DC-3

DC-4

DC-4

DC-1

OUTPUT-4

OUTPUT 5

OUTPUT 6

OUTPUT 7

Not Used

Not Used

DC-1OUTPUT-8

OUTPUT 9

DC-2OUTPUT 10

DC-2OUTPUT 11

DC-3

DC-3

DC-4

DC-4

DC-1

OUTPUT-12

OUTPUT 13

OUTPUT 14

OUTPUT 15

Not Used

Not Used

Conversion Module Installation and Application Considerations This Bul. 1492 cable consists of 2 separate cables (cable “A” and cable “B”) wired to one 1756-OB16I RTB. Each cable can be either

0.5M or 1.0M (005=0.5M, 010=1.0M). Ensure that cable A and cable B are connected to the correct module in the conversion

The 1771-OQ module output resistive current limits versus 1756-OB16I limits are as follows: 1771-OQ 1756-OB16I w/ 1492-C005005XT a) Current/Point 2.25A 2A b) Current/Module 9A 8A c) Surge Current/Point 4A for 10ms 4A for 10ms

The 1771-OQ is rated 10V to 32V DC. The 1756-OB16I is rated 10V to 30V DC.

Refer to your 1771-OQ and 1756-OB16I Installation Manual wiring schematics and diagrams for more details. Ensure 1756 output module ratings are not exceeded. [Reference Doc: 41171-033]

PN-114290DIR 10000060101 (Version 04)Publication 1492-IN048C-EN-E

(14)

PN-114290

FrontPage 13

BackPage 14

FrontPage 9

BackPage 10

FrontPage 7

BackPage 8

FrontPage 1

BackPage 2

FrontPage 3

BackPage 4

FrontPage 5

BackPage 6

8-1/2" W x 11" H(7 SHEETS) 4-1/4" W x 11" H

Stapled

CONFIDENTIAL AND PROPRIETARY INFORMATION. THIS DOCUMENT CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF

ROCKWELL AUTOMATION, INC. AND MAY NOT BE USED, COPIED OR DISCLOSED TO OTHERS, EXCEPT WITH THE AUTHORIZED WRITTEN

PERMISSION OF ROCKWELL AUTOMATION, INC.

Sheet

Size Ver

Of 11

B 00Dr. DateJ. MEREDIG 01-04-2018

SPECIFICATIONS FOR14 PAGE INSTRUCTION SHEET7 SHEETS STAPLED 4-1/4" W x 11" H - FINAL FOLD 10003661523

MATERIALSIZE

FOLD

TWO SIDES PRINTEDBODY STOCK WHITE

BODY INK BLACK7 SHEETS STAPLED - UPPER LEFT CORNER

FLAT

Final Fold

4-1/4”

11”

PN-123456DIR 10000000000 (Version 00)Printed in U.S.A.

BARCODE

Note: After folding---Printed in (Country where printed*), part number(s) and barcode (when used) should be visible.

* The printing vendor may change the instruction sheet files to show the correct country.

FrontPage 11

BackPage 12