Structure
The Building Regulations 2000
A A1 Loading A2 Ground movement
A3 Disproportionate collapse
APPROVED DOCUMENT
-
8/20/2019 Uk Building Regulations-A Must Know for All Devwlopers
2/47
Contents
PAGE
Use of guidance 3
Loading and Ground MovementThe Requirements A1/2 5
Guidance 6
Introduction 6
Section 1: Codes, standards and
references for all building types 7Introduction 7
References 7
Loading 7
Structural work of timber 7
Structural work of masonry 7
Structural work of reinforced,pre-stressed or plain concrete 7
Structural work of steel 7
Structural work of aluminium 7
Foundations 7
Ground movement (Requirement A2b) 8
Existing buildings 8
Section 2: Sizes of structural elementsfor certain residential buildings and othersmall buildings of traditional construction 9
General 9
Definitions 9
Section 2A: Basic requirements for stability 10
Section 2B: Sizes of certain timbermembers in floors and roofs for dwellings. Areas at risk from house longhorn beetle 11
Sizing of members 11
House longhorn beetle 11
S ti 2C Thi k f ll i t i
Construction ma
Loading on walls
End restraint
Openings, recess
Lateral support b
Interruption of lat
Small single-storeand annexes
Section 2D: Proportchimneys above the
Height to width r
Section 2E: Founda
Conditions relatin
Design provision
Minimum width o
Minimum depth o
Section 3: Wall clad
General
Technical approa
Loading
Fixings
Further guidance
Section 4: Roof cov
Materials
Re-covering of ro
Disproportionate CThe Requirement A
Guidance
Performance
-
8/20/2019 Uk Building Regulations-A Must Know for All Devwlopers
3/47
PAGE
DIAGRAMS
1. Size and proportion of residentialbuildings of not more than three storeys 13
2. Size and proportion of non-residentialbuildings and annexes 14
3. Determination of wall thickness 15
4. Parapet walls: height 16
5. Maximum floor area enclosed bystructural walls 17
6. Map showing wind speed in m/s formaximum height of buildings 18
7. Maximum height of buildings 19
8. Measuring storey and wall heights 20
9. Declared compressive strength of masonry units 22
10. Maximum span of floors 23
11. Differences in ground levels 24
12. Openings in a buttressing wall 25
13. Buttressing 26
14. Sizes of openings and recesses 27
15. Lateral support by floors 28
16. Lateral support at roof level 29
17. Size and location of openings 3018. Wall thickness 31
19. Lateral restraint at roof level 32
20. Proportions for masonry chimneys 33
21. Elevation of stepped foundation 34
22. Piers and chimneys 34
23. Foundation dimensions 34
24. Area at risk of collapse in the event of an accident 43
TABLES
1. Areas at risk from holonghorn beetle
2. Wall types considere
3. Minimum thickness oexternal walls, compaand separating walls
4. Imposed loads
5. Cavity wall ties
6. Declared compressivmasonry units complBS EN 771-1 to -5
7. Normalised compresmasonry units of claysilicate blocks complBS EN 771-1 and -2
8. Value of Factor ‘X’
9. Lateral support for w
10. Minimum width of str
11. Building classes
A CONTENTS
-
8/20/2019 Uk Building Regulations-A Must Know for All Devwlopers
4/47
THE APPROVED DOCUMENTS
This document is one of a series that has beenapproved by the First Secretary of State for thepurpose of providing practical guidance withrespect to the requirements of Schedule 1 to andRegulation 7 of the Building Regulations 2000 (SI2000/2531) for England and Wales. SI 2000/2531 has been amended by the Building (Amendment)Regulations 2001 (SI 2001/3335 ), by the Building(Amendment) Regulations 2002 (SI 2002/440), by
the Building (Amendment) (No. 2) Regulations2002 (SI 2001/2871), by the Building (Amendment) Regulations 2003 (SI 2003/2692) and by the Building (Amendment) Regulations 2004 (SI 2004/1465).
At the back of this document is a list of all thedocuments that have been approved and issuedby the Secretary of State for this purpose.
Approved Documents are intended to provideguidance for some of the more common
building situations. However, there may well bealternative ways of achieving compliance withthe requirements. Thus there is no obligation toadopt any particular solution contained in an Approved Document if you prefer to meet therelevant requirement in some other way.
Other requirements
The guidance contained in an Approved
Document relates only to the particularrequirements of the Regulations which thatdocument addresses. The building work willalso have to comply with the requirements ofany other relevant paragraphs in Schedule 1to the Regulations.
There are Approved Documents which giveguidance on each of the parts of Schedule 1and on Regulation 7.
LIMITATION ON REQUIREMENTS
In accordance with regulation 8, the requirementsin Parts A to K and N of Schedule 1 to theBuilding Regulations do not require anythingto be done except for the purpose of securing
product complying wspecification (as defia British Standard, otechnical specificatiocontracting party to which, in use, is equby a national or Euroa European Technicaand the conditions othe terms of the certguidance in the Appr
Regulation 7 on mat
Independent c
There are many UK pschemes. Such schewith the requirementwhich is appropriatematerial is to be usecertified may still con
Many certification boschemes are accred
Technical spec
Building Regulationspurposes: health andand the welfare and people. Standards arelevant guidance toto these consideratioaddress other aspecserviceability, or asprelate to health and sthe Regulations.
When an Approved Dto a named standardthe standard is the opublication. Howeverevised or updated bbody, the new versioof guidance providedrelevant requirement
The appropriate use with a European Tec
C
Use of guidance
http://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=251188REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=251188REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=254415REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=254415REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=254415REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=256378REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=256378REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=261853REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=261853REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=264861REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=264861REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=266712REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=266712REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=266712REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=266712REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=264861REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=264861REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=261853REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=261853REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=256378REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=256378REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=254415REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=254415REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=251188REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=251188REG
-
8/20/2019 Uk Building Regulations-A Must Know for All Devwlopers
5/47
THE WORKPLACE (HEALTH,
SAFETY AND WELFARE)
REGULATIONS 1992
The Workplace (Health, Safety and Welfare)Regulations 1992 contain some requirementswhich affect building design. The mainrequirements are now covered by the BuildingRegulations, but for further information see:Workplace health, safety and welfare, TheWorkplace (Health, Safety and Welfare)Regulations 1992, Approved Code of Practice and Guidance; The Health and Safety
Commission, L24; Published by HMSO 1992;ISBN 0 11886 333 9.
The Workplace (Health, Safety and Welfare)Regulations 1992 apply to the common partsof flats and similar buildings if people such ascleaners and caretakers are employed to workin these common parts. Where the requirementsof the Building Regulations that are covered bythis Part do not apply to dwellings, the provisions
may still be required in the situations describedabove in order to satisfy the Workplace Regulations.
OTHER FORMS OF HOUSE
CONSTRUCTION
This Approved Document includes guidance onstructural elements of residential buildings oftraditional masonry construction. It is recognised,
however, that there are other suitable forms ofconstruction in use in the housing sector some ofwhich (e.g. timber framed) have been in commonuse for a number of years and have demonstratedan adequate performance in compliance with the A1 requirement. Such alternative forms includeprefabricated timber, light steel and precastconcrete framed construction.
A number of guidance documents relating to
these alternative forms are presently beingdeveloped by industry. The intention is toreference these in this Approved Documentas soon as they become available and areapproved by the Secretary of State.
EUROCODES
A USE OF GUIDANCE
http://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=70459REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=70459REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=70459REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=70459REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=70459REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=70459REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=70459REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=70459REG
-
8/20/2019 Uk Building Regulations-A Must Know for All Devwlopers
6/47
The Requirements
This Approved Document deals with the followingRequirements which are contained in the BuildingRegulations 2000 (as amended by SI 2001/3335,SI 2002/440, SI 2002/2871 and SI 2003/2692).
Requirement Limits on application
Loading
A1. (1) The building shall be constructed so that the combined dead,
imposed and wind loads are sustained and transmitted by it to the
ground:
(a) safely; and
(b) without causing such deflection or deformation of any
part of the building, or such movement of the ground, as will impair
the stability of any part of another building.
(2) In assessing whether a building complies with sub paragraph
(1) regard shall be had to the imposed and wind loads to which it islikely to be subjected in the ordinary course of its use for the purpose
for which it is intended.
Ground movement
A2. The building shall be constructed so that ground movement
caused by:
(a) swelling, shrinkage or freezing of the subsoil; or
(b) land-slip or subsidence (other than subsidence arising from
shrinkage, in so far as the risk can be reasonably foreseen), will notimpair the stability of any part of the building.
LOADING AND GROUND MOVEMENT
http://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=254415REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=256378REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=261853REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=264861REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=264861REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=261853REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=256378REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=254415REG
-
8/20/2019 Uk Building Regulations-A Must Know for All Devwlopers
7/47
Introduction
0.1 In the Secretary of State’s view therequirements of A1 and A2 will be met byfollowing the recommendations given in thedocuments listed in Section 1 or by adoptingthe guidance in Sections 2-4:
a. Section 1 is relevant to all building typesand lists Codes, Standards and otherreferences for structural design andconstruction but, where they do not give
precise guidance, consideration shouldbe given to paragraph 0.2.
b. Section 2 give sizes of structural elementsfor certain residential buildings and othersmall buildings of traditional construction.
c. Section 3 gives guidance on the supportand fixing of wall cladding.
d. Section 4 gives guidance where roofs are
to be re-covered as a material alteration asdefined in the Regulations.
0.2 The safety of a structure depends on thesuccessful combination of design and completedconstruction, particularly:
a. The design should be based on identificationof the hazards to which the structure is likelyto be subjected and assessment of the risks.
The selection of relevant critical situationsfor design should be made reflecting theconditions that can reasonably be foreseenduring future use.
b. Loading. Dead load, imposed load and windload should be in accordance with the currentCodes of Practice referred to in Section 1 ofthis document.
c. Properties of materials.
d. Detailed design and assembly ofthe structure.
e. Safety factors.
f. Workmanship.
The numeric values of safety factors, whether
Interim guidance on the des may be found in ‘Dynamic p requirements for permanentto crowd action, Interim Gui and design’ published by thStructural Engineers, Novem
Supplementary advice on thof grandstands and seating published in an Advisory Noof Structural Engineers, Jun
Guidance A1/2
http://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=260233REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=260233REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=260233REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=260233REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=262605REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=262605REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=260233REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=260233REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=260233REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=260233REG
-
8/20/2019 Uk Building Regulations-A Must Know for All Devwlopers
8/47
Introduction
1.1 This section is relevant to all building typesand lists codes, standards and other referencesfor structural design and construction.
References
1.2 Loading:
a. Dead and imposed loadsBS 6399-1:1996 Loading for buildings. Code ofpractice for dead and imposed loads.
b. Wind loads
BS 6399-2:1997 Loading for buildings. Codeof practice for wind loads
BRE digest 436 Parts 1, 2 and 3 (Brief guidance
for using BS 6399-2:1996).c. Imposed roof loads
BS 6399-3:1998 Loading for buildings. Code ofpractice for imposed roof loads.
1.3 Structural work of timber:
BS 5268-2:2002 Structural use of timber. Code ofpractice for permissible stress design, materialsand workmanship.
BS 5268-3:1998 Structural use of timber. Code ofpractice for trussed rafter roofs.
BS 8103-3:1996 Structural design of low-risebuildings. Code of practice for timber floors androofs for housing.
1.4 Structural work of masonry:
BS 5628-1:1992 Code of practice for use of
masonry. Structural use of unreinforced masonry.
BS 5628-2:2000 Code of practice for use ofmasonry. Structural use of reinforced andpre-stressed masonry.
BS 5628-3:2001 Code of practice for use ofmasonry. Materials and components, design
BS 8110-3:1985 StruDesign charts for sinreinforced beams an
BS 8103-4:1995 Strubuildings. Code of pconcrete floors for ho
1.6 Structural wo
BS 5950-1:2000 Strubuilding. Code of praand continuous conswelded sections.
BS 5950-2:2001 Strubuilding. Specificatioand erection, hot roll
BS 5950-3-1:1990 Sbuilding. Design in c
of practice for desigcomposite beams.
BS 5950-4:1994 Struin building. Code of composite slabs with
BS 5950-5:1998 Codof cold formed thin g
BRE Digest 437 Indu
mezzanine and raise
1.7 Structural wo
BS 8118-1:1991 StruCode of practice for
BS 8118-2:1991 StruSpecification for matand protection.
1.8 Foundations:
BS 8002:1994 Coderetaining structures.
BS 8004:1986 Code
Section 1: Codes, standards andfor all building types
-
8/20/2019 Uk Building Regulations-A Must Know for All Devwlopers
9/47
Ground movement
(Requirement A2b)
1.9 There may be known or recorded
conditions of ground instability, such as thatarising from landslides, disused mines orunstable strata which, if ignored, can have adevastating effect on the safety of a buildingand its environs. Such conditions should betaken into account in the design of the buildingand its foundations. Attention is drawn to DOEPlanning Policy Guidance Note 14 Developmenton unstable land (obtainable from The StationeryOffice), which sets out the broad planning andtechnical issues relating to development onunstable land.
The Department has also sponsored a seriesof reviews aimed at determining the scale andnature of problems arising from mining instability,natural underground cavities and adversefoundation conditions. Databases of bothsubsidence incidents and subsidence potentialproduced from these reviews are available fromthe following licence holders:
British Geological Survey, Sir Kingsley DunhamCentre, Keyworth, Nottingham NG12 5GG.
Landmark, 7 Abbey Court, Eagle Way, Exeter,Devon EX2 7HY.
Peter Brett Associates, 16 Westcote Road,Reading, Berkshire RG20 2DE.
Catalytic Data Ltd, The Spinney, 19 WoodlandsRoad, Bickley, Kent BRI 2AD.
The reports from these reviews, which include1:250,000 scale maps showing the distributionof the physical constraints, are available from thefollowing organisations:
Arup Geotechnics, 1991. Review of mininginstability in Great Britain.
Obtainable from Arup Geotechnics, Bede House, All Saints, Newcastle-upon-Tyne NE1 2EB.
Applied Geology Ltd, 1994. Review of instabilitydue to natural underground cavities in GreatBritain.
Obtainable from Kennedy & Donkin Ltd,
Existing buildings
1.10 Compliance with Parrequired in certain classes obuilding, subject to the contand 6. Guidance relevant torelated to ‘change of use’ isdocuments:
a. BRE Digest 366: StructuExisting Buildings for Ch
b. The Institution of Structu Appraisal of Existing Str
Note: With reference to the in the above mentioned InstEngineers report the choicefactors should be made to scircumstances of each case
A1/2 CODES, STANDARDS AND REFERENCES FOR ALL B
http://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=85652REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=85652REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=17006REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=201727REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=201727REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=201727REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=201727REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=17006REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=85652REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=85652REG
-
8/20/2019 Uk Building Regulations-A Must Know for All Devwlopers
10/47
Section 2: Sizes of structural elecertain residential buildings and
buildings of traditional constructGeneral
2.1 This section is presented as follows:
Section 2A
Basic requirements for stability.
Section 2BSizes of certain timber members in floors androofs for dwellings.
Areas at risk from house longhorn beetle.
Section 2C
Thickness of masonry walls in certain residentialbuildings of not more than three storeys, small
single-storey non-residential buildings and annexes.Section 2D
Proportions for masonry chimneys.
Section 2E
Foundations of plain concrete.
2.2 Section 2A gives general rules which mustbe observed in following Sections 2B and 2C.
Sections 2B to 2E may be used independentlyof each other.
Throughout this section the diagrams are onlyillustrative and do not show all the details ofconstruction.
Definitions
2.3 The following meanings apply to terms
throughout this section:Buttressing wall A wall designed andconstructed to afford lateral support to anotherwall perpendicular to it, support being providedfrom the base to the top of the wall.
Cavity width The horizontal distance betweenth t l f it ll
Pier A member whicof a wall, in the formintervals along the wsupport to the wall tosecurely tied.
Separating wall A w
common to adjoiningto meet the requirem
Spacing The distanccentres of any two athe same type, measceiling or roof structu
Span The distance mline of a member betadjacent bearings or
Supported wall A wafforded by a combipiers or chimneys acfloor(s) or roof.
Wind load The load pressure or suction.
-
8/20/2019 Uk Building Regulations-A Must Know for All Devwlopers
11/47
Section 2A: Basic requirements for
2A1 This section must be used in conjunctionwith sections 2B and 2C and its principles relate
to all forms of low-rise residential buildings.
2A2 Adequate provision shall be made toensure that the building is stable under the likelyimposed and wind loading conditions. This willcommonly necessitate meeting the followingrequirements:
a. That the overall size and proportioningof the building are limited in accordance
with the specific guidance for each form ofconstruction.
b. That a suitable layout of walls (both internaland external) forming a robust 3 dimensionalbox structure in plan is constructed withrestriction on the maximum size of cellsmeasured in accordance with the specificguidance for each form of construction.
c. That the internal and external walls are
adequately connected either by masonrybonding or by using mechanical connections.
d. That the intermediate floors and roof are ofsuch construction and interconnection withthe walls that they provide local supportto the walls and also act as horizontaldiaphragms capable of transferring the windforces to buttressing elements of the building.
Note: A traditional cut timber roof (i.e. usingrafters, purlins and ceiling joists) generally hassufficient built in resistance to instability andwind forces (e.g. from hipped ends, tiling battens,rigid sarking or the like). However, the needfor diagonal rafter bracing equivalent to thatrecommended in BS 5268-3:1998 or Annex H ofBS 8103-3:1996 for trussed rafter roofs shouldbe considered especially for single-hipped andnon-hipped roofs of greater than 40° pitch to
detached houses.
A1/2
http://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=201392REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=86711REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=86711REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=201392REG
-
8/20/2019 Uk Building Regulations-A Must Know for All Devwlopers
12/47
Sizing of members
2B1 Guidance on the sizing of certain membersin floors and roofs is given in ‘Span tables forsolid timber members in floors, ceilings and roofs(excluding trussed rafter roofs) for dwellings’,published by TRADA, available from Chiltern
House, Stocking Lane, Hughenden Valley, HighWycombe, Bucks HP14 4ND.
Alternative guidance is available in BS 5268-2:2002 Code of practice for permissible stress design,materials and workmanship, BS 5268-3:1998,Code of practice for trussed rafter roofs andBS 8103-3:1996 Structural design of low-risebuildings, Code of Practice for timber floors androofs for dwellings.
Table 1 Areas at risk from house longhorn beetle
Geographical area
In the Borough of Bracknell Forest the parishes of Sandhurst and Crowthorne.
The Borough of Elmbridge
In the District of Hart, the parishes of Hawley and Yateley
The District of Runnymede
The Borough of Spelthorne
The Borough of Surrey Heath
In the Borough of Rushmoor, the area of the former district of Farnborough
The Borough of Woking
House longhor
2B2 In the geograpTable 1, softwood timor fixed in the roof spwithin the void spaceadequately treated to
house longhorn beetGuidance on suitableis given within the BrDamp-Proofing Assorevision), available fr Vernongate, South S
Section 2B: Sizes of certain timbin floors and roofs for dwellings.
risk from house longhorn beetle
http://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=256380REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=201392REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=86711REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=86711REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=201392REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=256380REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=REG
-
8/20/2019 Uk Building Regulations-A Must Know for All Devwlopers
13/47
Section 2C: Thickness of walls in cesmall buildings
Application2C1 This section applies to the followingbuilding types:
a. residential buildings of not more thanthree storeys;
b. small single-storey non-residentialbuildings;
c. small buildings forming annexes toresidential buildings (including garagesand outbuildings).
Wall types
2C2 Only the types of wall given in Table 2,which must extend to the full storey height, andparapet walls are considered in this section.
The use of this section2C3 When using this section it should benoted that:
a. this section must be used in conjunctionwith Section 2A;
b. if wall thickness is to be determinedaccording to paragraphs 2C5 to 2C13, allappropriate design conditions given in this
section must be satisfied;
c. walls should comply with the relevantrequirements of BS 5628: Part 3: 2001, exceptas regards the conditions given in paragraphs2C4 and 2C14 to 2C38;
d. in formulating the guidance of this section theworst combination of circumstances likely toarise was taken into account. If a requirement
of this part is considered too onerous in aparticular case it may be appropriate toconsider a minor departure on the basisof judgement and experience, or to showadequacy by calculation in respect of theaspect of the wall which is subject to thedeparture rather than for the entire wall;
e. the guidance given is bacompressive strengths obeing not less than indica
BS 5628-1:1992 gives desigwhere the suitability for use other compressive strength
Conditions relating
of which the wall fo2C4 This Section applies having proportions within thparameters (see Diagrams 1
a. residential buildings ofthree storeys:
i. the maximum heightmeasured from the lo
level adjoining the bupoint of any wall or rgreater than 15m, suof paragraph 2C16;
ii. the height of the builexceed twice the leabuilding W1;
iii. the height of the winexceed twice the leaW2 where the projecthe width W2;
b. small single-storey nonheight H should not excthe greatest length or wshould not exceed 9m (ssubject to the limits of p
A1/2
http://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=254037REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=260482REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=260482REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=260482REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=254037REG
-
8/20/2019 Uk Building Regulations-A Must Know for All Devwlopers
14/47
c. annexes: height H as variously indicated inDiagram 2 should not exceed 3m, subject tothe limits of paragraph 2C16.
Thickness of walls
2C5 General wall thickness may be determinedaccording to this section provided:
a. conditions relating to the building of whichthe wall forms part (see paragraphs 2C4,2C14 to 2C16, 2C38 ); and
b. conditions relating to the wall (see paragraphs2C17 to 2C37 ) are met. (See Diagram 3.)
wide. The wall ties sspacing of 900mm a450mm, which is equmetre. Wall ties shounot more than 300mdistance of 225mm fopenings, movemen
selection of wall tieswidths refer to Tablewall ties refer to para
For external walls, coseparating walls in ccombined thickness should not be less th
THICKNESS OF WALLS IN CERTAIN SMALL BUILDING
Diagram 1 Size and proportion of residential buildings of not m
See para 2C4
-
8/20/2019 Uk Building Regulations-A Must Know for All Devwlopers
15/47
A1/2 THICKNESS OF WALLS IN CERTAIN SMALL BUILDI
Diagram 2 Size and proportion of non-residential buildings and ann
See paras 2C4b and 2C4c
-
8/20/2019 Uk Building Regulations-A Must Know for All Devwlopers
16/47
Table 3 Minimum thickness of certain external walls, comparseparating walls
Height of wall Length of wall
Not exceeding 3 5m Not exceeding 12m
THICKNESS OF WALLS IN CERTAIN SMALL BUILDING
Diagram 3 Determination of wall thickness
See para 2C5
-
8/20/2019 Uk Building Regulations-A Must Know for All Devwlopers
17/47
except for a wall in the lowest storey of a threestorey building, carrying load from both upper
storeys, which should have a thickness asdetermined by the equation or 140mm whicheveris the greatest.
2C11 Parapet walls: The minimum thicknessand maximum height of parapet walls should beas given in Diagram 4.
2C14 Maximum floor areathis section assumes that no
structural walls on all sides that no floor without a strucexceeds 36m2. (See Diagram
2C15 Imposed loads on roceilings: The design considthis section are intended to imposed loads given in Tabl
A1/2 THICKNESS OF WALLS IN CERTAIN SMALL BUILDI
Diagram 4 Parapet walls: height
See para 2C11
-
8/20/2019 Uk Building Regulations-A Must Know for All Devwlopers
18/47
Table 4 Imposed loads
Element Loading
Distributed loadsRoof 1.00kN/m² for spans not exceeding 12m 1.5kN/m² for spans not exceeding 6m Floors Distributed load: 2.00kN/m² Ceilings Distributed load: 0.25kN/m² together with concentrated load: 0.9kN
2C18 Rules of measurement for heights ofwalls and storeys: The height of a wall or astorey should be measured in accordance with
2C20 Masonry unitbonded and solidly pconstructed of maso
a. clay bricks or bloBS 6649:1985 or
b. calcium silicate bBS 6649:1985 or
c. concrete bricks oor BS EN 771-3 o
d. square dressed nrequirements desBS 5628-3:2001;
e. manufactured stoBS EN 771 5
THICKNESS OF WALLS IN CERTAIN SMALL BUILDING
Diagram 5 Maximum floor area enclosed by structural walls
See para 2C14
A1/2
http://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=12910REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=12910REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=266032REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=254037REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=266033REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=266033REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=254037REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=266032REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=12910REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=12910REG
-
8/20/2019 Uk Building Regulations-A Must Know for All Devwlopers
19/47
A1/2 THICKNESS OF WALLS IN CERTAIN SMALL BUILDI
Diagram 6 Map showing wind speeds in m/s for maximum height o
See para 2C16
-
8/20/2019 Uk Building Regulations-A Must Know for All Devwlopers
20/47
THICKNESS OF WALLS IN CERTAIN SMALL BUILDING
Diagram 7 Maximum height of buildings
See para 2C16
A1/2 THICKNESS OF WALLS IN CERTAIN SMALL BUILDI
-
8/20/2019 Uk Building Regulations-A Must Know for All Devwlopers
21/47
A1/2 THICKNESS OF WALLS IN CERTAIN SMALL BUILDI
Diagram 8 Measuring storey and wall heights
See para 2C18
THICKNESS OF WALLS IN CERTAIN SMALL BUILDING
-
8/20/2019 Uk Building Regulations-A Must Know for All Devwlopers
22/47
THICKNESS OF WALLS IN CERTAIN SMALL BUILDING
Table 5 Cavity wall ties
Nominal cavity width mm
(Note 1)
50 to 75
76 to 90
91 to 100
101 to 125
126 to 150
151 to 175
176 to 300
Tie length mm
(Note 2)
200
225
225
250
275
300
(See Note 2)
Permissible type of tie
Tie shape in accordance
with BS 1243*
Butterfly, double triangle or vertical twist
Double triangle or vertical twist
Double triangle (Note 3) or vertical twist
Vertical twist
Vertical twist
Vertical twist
Vertical twist style
Typeselec
load
*Although BSwithdrawn on(types) given
document ca
Notes:
1. Where face insulated blocks are used the cavity width should be measured from the face of the masonry u
2. The embedment depth of the tie should not be less than 50mm in both leaves. For cavities wider than 180cavity width plus 125mm and select the nearest stock length.
3. Double triangle ties of this shape having a strength to satisfy Type 2 of DD 140-2* are manufactured. Specconsulted if 225mm long double triangle format ties are needed for 91 to 100mm cavities.
4. Where BS EN 845-1 ties are used reference needs to be made additionally to DD 140-2* for the selection to the performance levels given in DD 140-2.
Table 6 Declared compressive strength of masonry units comBS EN 771-1 to -5 (N/mm2 )
Masonry unit Clay masonry units to Calcium silicate masonry Aggrega BS EN 771-1 units to BS EN 771-2 concre mason units t BS EN 77
Condition A (See Diagram 9)
Brick Group 1 Group 2 Group 1 Group 2 6.0 6.0 9.0 6.0 9.0
Block See Table 7 See Table 7 See Table 7 See Table 7 2.9*
Condition B (See Diagram 9)
Brick Group 1 Group 2 Group 1 Group 2 9.0 9.0 13.0 9.0 13.0
Block See Table 7 See Table 7 See Table 7 See Table 7 7.3* Condition C (See Diagram 9)
Brick Group 1 Group 2 Group 1 Group 2 18.0 18.0 25.0 18.0 25.0
Block See Table 7 See Table 7 See Table 7 See Table 7 7.3*
A1/2 THICKNESS OF WALLS IN CERTAIN SMALL BUILDI
-
8/20/2019 Uk Building Regulations-A Must Know for All Devwlopers
23/47
A1/2 THICKNESS OF WALLS IN CERTAIN SMALL BUILDI
Diagram 9 Declared compressive strength of masonry units
See para 2C21
THICKNESS OF WALLS IN CERTAIN SMALL BUILDING
-
8/20/2019 Uk Building Regulations-A Must Know for All Devwlopers
24/47
THICKNESS OF WALLS IN CERTAIN SMALL BUILDING
Table 7 Normalised compressive strength of masonry units osilicate blocks complying with BS EN 771-1 and 2 (N/
Standard
Clay masonry units to BS EN 771-1Calcium silicate masonry units toBS EN 771-2
Condition (See Diagram 9)
A
B
C
Group 1 masonry unit
5.0
7.5
15.0
Notes:
1. Values in this table are normalised compressive strengths (N/mm²). Compressive strengths of masonry units
2. The table applies to clay and calcium silicate block masonry units where the work size exceeds 337.5mm
3. Group 1 masonry units have not more than 25% formed voids (20% for frogged bricks). Group 2 masonry
25%, but not more than 55%.
2C22 Mortar: Mortar should be:
a.
i. Mortar designation (iii) according toBS BS 5628-3:2001.
ii. Strength class M4 according to
BS EN 998-2.
iii. 1:1:5 or 6 CEM 1, lime and fine aggregatemeasured by volume of dry materials, or
b. of equivalent or greater strength anddurability to the specification in a. above.
Loading on walls
2C23 Maximum span of floors: The maximum
span for any floor supported by a wall is 6mwhere the span is measured centre to centre ofbearing (see Diagram 10).
2C24 Other loading conditions:
a. Vertical loading on walls should be distributed.This may be assumed for concrete floorslabs, precast concrete floors, and timberfloors designed in accordance with section
2B, and where the bearing length for lintels is150mm or greater. Where a lintel has a clearspan of 1200mm or less the bearing lengthmay be reduced to 100mm.
b. Differences in level of ground or other solidconstruction between one side of the walland the other should be less than 4 times the
End restraint
2C25 Vertical Later
The ends of every wotherwise securely ti
Diagram 10 Max
See para 2C23
A1/2 THICKNESS OF WALLS IN CERTAIN SMALL BUILDI
http://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=254037REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=256415REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=256415REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=254037REG
-
8/20/2019 Uk Building Regulations-A Must Know for All Devwlopers
25/47
A1/2 THICKNESS OF WALLS IN CERTAIN SMALL BUILDI
Diagram 11 Differences in ground levels
See para 2C24b
THICKNESS OF WALLS IN CERTAIN SMALL BUILDING
-
8/20/2019 Uk Building Regulations-A Must Know for All Devwlopers
26/47
THICKNESS OF WALLS IN CERTAIN SMALL BUILDING
a. half the thickness required by this section foran external or separating wall of similar heightand length less 5mm; or
b. 75mm if the wall forms part of a dwellinghouse and does not exceed 6m in total heightand 10m in length; and
to the wall. Piers width of 190mm
b. the sectional are(excluding openishould be not lesfor a pier in the s
Diagram 12 Openings in a buttressing wall
See para 2C26
A1/2 THICKNESS OF WALLS IN CERTAIN SMALL BUILDI
-
8/20/2019 Uk Building Regulations-A Must Know for All Devwlopers
27/47
2C29 Dimensional criteria for openings andrecesses:
The dimensional criteria are given in Diagram 14and Table 8.
No openings should be provided in walls belowground floor except for small holes for servicesand ventilation, etc. which should be limitedto a maximum area of 0.1m² at not less than2m centres.
2C30 Chases:
Lateral support by r
2C32 A wall in each storey extend to the full height of thorizontal lateral supports to
of the wall at right angles to2C33 Floors and roofs sh
a. act to transfer lateral forbuttressing walls, piers o
b. be secured to the suppo
A1/2 THICKNESS OF WALLS IN CERTAIN SMALL BUILDI
Diagram 13 Buttressing
See para 2C27
THICKNESS OF WALLS IN CERTAIN SMALL BUILDING
-
8/20/2019 Uk Building Regulations-A Must Know for All Devwlopers
28/47
Diagram 14 Sizes of openings and recesses
See para 2C29
Table 8 Value of Factor ‘X’ (see Diagram 14)
Span of timber floor into wall Span of floor Minimum is parallel max maNature of Maximum thickness of to wall 4.5m 6.0roof span roof span (m) wall inner (mm)
Value of f Roof spans Not 100 6 6 6parallel to wall applicable 90 6 6 6
Timber roof 9 100 6 6 5
A1/2 THICKNESS OF WALLS IN CERTAIN SMALL BUILDI
-
8/20/2019 Uk Building Regulations-A Must Know for All Devwlopers
29/47
specifications including material references 1 or3 (austenitic stainless steel). The declared tensilestrength of tension straps should not be less
than 8kN.
Tension straps need not be provided:
a. in the longitudinal direction of joists in housesof not more than 2 storeys, if the joists areat not more than 1.2m centres and have atl t 90 b i th t d ll
d. where floors are at or abon each side of a suppocontact between the floo
continuous or at intervalWhere contact is intermcontact should be in lineplan (see Diagram 15(e))
2C36 Gable walls should bshown in Diagram 16(a) and
Diagram 15 Lateral support by floors
See para 2C35
THICKNESS OF WALLS IN CERTAIN SMALL BUILDING
-
8/20/2019 Uk Building Regulations-A Must Know for All Devwlopers
30/47
Interruption of lateral support
2C37 Where an opening in a floor or roof for a
stairway or the like adjoins a supported wall andinterrupts the continuity of lateral support, thefollowing conditions should be satisfied for thepurposes of Section 2C:
a. the maximum permitted length of the openingis to be 3m, measured parallel to the supported
Small single-st
buildings and a
2C38 Size and prop
i. General
The guidance given circumstances:
Diagram 16 Lateral support at roof level
See para 2C36
A1/2 THICKNESS OF WALLS IN CERTAIN SMALL BUILDI
-
8/20/2019 Uk Building Regulations-A Must Know for All Devwlopers
31/47
Diagram 17 Size and location of openings
See para 2C38
THICKNESS OF WALLS IN CERTAIN SMALL BUILDING
-
8/20/2019 Uk Building Regulations-A Must Know for All Devwlopers
32/47
Diagram 18 Wall thickness
See para 2C38
A1/2 THICKNESS OF WALLS IN CERTAIN SMALL BUILDI
-
8/20/2019 Uk Building Regulations-A Must Know for All Devwlopers
33/47
Walls which do not contain a major openingbut exceed 2.5m in length or height should bebonded or tied to piers for their full height at notmore than 3m centres as shown in Diagram 18a.Walls which contain one or two major openings
(iv) Horizontal lateral re
Walls should be tied horizon2m centres to the roof strucbase of gables and along roin Diagram 19 with straps fix
Diagram 19 Lateral restraint at roof level
See para 2C38
A1/2
S ti 2D P ti f
-
8/20/2019 Uk Building Regulations-A Must Know for All Devwlopers
34/47
Section 2D: Proportions for maschimneys above the roof surface
Height to width relationship2D1 Where a chimney is not adequatelysupported by ties or securely restrained in anyway, its height if measured from the highest pointof intersection with the roof surface, gutter, etc.should not exceed 4.5W, provided the density ofthe masonry is greater than 1500kg/m3, where:
W is the least horizontal dimension of the
chimney measured at the same point ofintersection, and
H is measured to the top of any chimney pot orother flue terminal (see Diagram 20).
Diagram 20 Proportions for masonrychimneys
See para 2D1
S ti 2E F d ti f l i A1/2
-
8/20/2019 Uk Building Regulations-A Must Know for All Devwlopers
35/47
Conditions relating to the ground
2E1 There should not be:
a. non-engineered fill (as described in BREDigest 427 ) or wide variation in groundconditions within the loaded area; nor
b. weaker or more compressible ground atsuch a depth below the foundation as couldimpair the stability of the structure.
Design provisions
2E2 The following design provisions relate tofoundations:
a. the foundations should be situated centrallyunder the wall;
b. for foundations in chemically aggressivesoil conditions guidance in BS 8500-1 andBRE Special Digest 1 should be followed.In non-aggressive soils, concrete should
be composed of Portland cement to BS EN197-1 and -2 and fine and coarse aggregateconforming to BS EN 12620 and the mixshould comply with one of the followingrecommendations:
i. in proportion of 50kg of Portland cementto not more than 200kg (0.1m3 ) of fineaggregate and 400kg (0.2m3 ) of coarseaggregate; or
ii. grade ST2 or grade GEN I concrete toBS 8500-2;
c. minimum thickness T of concrete foundationshould be 150mm or P, whichever is thegreater where P is derived using Table 10and Diagram 23. Trench fill foundations maybe used as an acceptable alternative to stripfoundations;
d. foundations stepped on elevation shouldoverlap by twice the height of the step, bythe thickness of the foundation, or 300mm,whichever is greater (see Diagram 21).
For trench fill foundations the overlap shouldbe twice the height of the step or 1m,
Section 2E: Foundations of plain co
Diagram 21 Elevation
foundationSee paras 2E2d and e
Diagram 22 Piers and
See para 2E2f
Diagram 23 Foundatio
See para 2E2c
FOUNDATIONS OF PLAIN CONCRETE
http://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=200216REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=200216REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=264682REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=262440REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=266916REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=266916REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=250766REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=267344REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=264683REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=264683REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=267344REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=250766REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=266916REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=266916REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=262440REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=264682REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=200216REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=200216REG
-
8/20/2019 Uk Building Regulations-A Must Know for All Devwlopers
36/47
Table 10 Minimum width of strip footings
Total load of loa(
Type of ground 20 30 (including Condition Field testengineered fill) of ground applicable Minimum wid
I Not inferior to Requires at least a pneumatic In each casRock sandstone, limestone or other mechanically operated or firm chalk pick for excavation
II Requires pick for excavation. 250 300 Gravel or sand Medium dense Wooden peg 50mm square in cross section hard to drive beyond 150mm
III Can be indented slightly by thumb 250 300 Clay StiffSandy clay Stiff
IV Thumb makes impression easily 300 350 Clay FirmSandy clay Firm V Can be excavated with a spade. 400 600Sand Loose Wooden peg 50mm square inSilty sand Loose cross section can be easily driven
Clayey sand Loose VI Finger pushed in up to 10mm 450 650 Silt Soft Clay SoftSandy clay SoftClay or silt Soft
VII Finger easily pushed in up to 25mm RefeSilt Very softClay Very softSandy clay Very softClay or silt Very soft
The table is applicable only within the strict termsof the criteria described within it.
Minimum depth of strip
foundations
2E4 Except where strip foundations arefounded on rock, the strip foundations shouldhave a minimum depth of 0.45m to theirunderside to avoid the action of frost. This depth,however, will commonly need to be increased inareas subject to long periods of frost or in order
f h l di i f d
Section 3: Wall cladding A1/2
-
8/20/2019 Uk Building Regulations-A Must Know for All Devwlopers
37/47
General
3.1 Wall cladding presents a hazard if itbecomes detached from the building. Thissection provides guidance on the supportand fixing of wall cladding. An acceptablelevel of safety can be achieved by differentmeans depending on the type and location ofthe cladding. The guidance given relates toall forms of cladding, including curtain wallingand glass facades. It is not intended to provideguidance concerning the weather resistance
of wall cladding which is included in ApprovedDocument C, Site preparation and resistance tomoisture, or guidance on resistance to spread offire which is included in Approved Document B,Fire safety, or guidance in relation to soundinsulation, which is included in ApprovedDocument E, Resistance to the passageof sound.
Technical approach
3.2 The cladding will meet the safetyrequirement if:
a. the cladding is capable of safely sustainingand transmitting to the supporting structureof the building all dead, imposed and windloads, and
b. the cladding is securely fixed to andsupported by the structure of the building.This shall comprise both vertical supportand horizontal restraint, and
c. provision is made, where necessary, toaccommodate differential movement of thecladding and the supporting structure of thebuilding, and
d. the cladding and its fixings (includingany support components) are of durable
materials; the design life of the fixings beingnot less than that of the cladding. Fixingsshall be corrosion resistant and of a materialtype appropriate for the local environment.
Loading
3.5 Where the wall claddfunction as pedestrian guard
vertical drops of 600mm or vehicle barrier, then accounthe additional imposed load Approved Document K, Procollision and impact.
3.6 Where the wall claddsafely withstand lateral presan appropriate design loadi6399 Part 1 and the Guide t
Grounds (4th Edition, 1997)
Fixings
3.7 The selection of fixingcladding should be determinconsideration of the proven fixing and the risks associatapplication. In this regard apdesignated as being either n
the failure of a single fixing cdetachment of the cladding)failure or excessive movemeresults in load sharing by adthe required reliability of theaccordingly.
Note: Attention is drawn to tof anchors with an ETA (Eur Approval) gained in accorda
requirements of ETAG 001 GEuropean Technical Approvfor use in Concrete Parts 1-redundant and non-redundaPart 6 which covers ‘Anchoin non-structural applicationeffectively be regarded as cuse. The UK definition of ‘mcontained in an annexe to this framed in such a way that
be validated as to whether othis category without calculmay be downloaded in Engli
3.8 The strength of fixingfrom tests using materials rematerial into which the fixing
Section 3: Wall cladding
WALL CLADDING
http://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=261432REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=98685REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=98685REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=98685REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=98685REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=261432REG
-
8/20/2019 Uk Building Regulations-A Must Know for All Devwlopers
38/47
in ‘Use of anchors with European Technical Approvals. UK Guidance – Distinctionbetween cracked and non-cracked concrete’.This is available on the BBA websitewww.bbacerts.co.uk click tab ‘ETA’.
Further guidance
3.9 The use of large panels of glass incladding of walls and roofs where the claddingis not divided into small areas by load-bearingframing requires special consideration. Guidanceis given in the following documents:
The Institution of Structural Engineers’ Report on
‘Structural use of glass in buildings’ dated 1999,available from 11 Upper Belgrave Street, LondonSW1X 8BH.
‘Nickel sulfide in toughened glass’ published bythe Centre for Window Cladding and Technologydated 2000.
3.10 Further guidance on cladding is given inthe following documents:
The Institution of Structural Engineers’ Report on‘ Aspects of Cladding’ dated 1995.
The Institution of Structural Engineers’ Reporton ‘Guide to the structural use of adhesives’dated 1999.
BS 8297:2000 Code of practice for the designand installation of non-load-bearing pre-castconcrete cladding.
BS 8298:1994 Code of practice for the design andinstallation of natural stone cladding and lining.
3.11 Additional guidance on fixings is given inthe following documents:
ETAG No. 001 1997 Guideline for EuropeanTechnical Approvals of Metal Anchors for use inConcrete, European Organisation for Technical Approvals (EOTA), Brussels. All EOTA parts maybe downloaded in English from www.eota.be.
English version published by the British Boardof Agreement, PO Box 195, Bucknalls Lane,Garston, Watford, Hertfordshire WD25 9BA.
Part 1 Anchors in general.
Part 2 Torque controlled anchors.
Guidance notes pubFixings Association, Technology, Henry SSouth Yorks S3 7EQ
Guidance Note: ProcConstruction Fixings
Guidance Note: Eurofor Construction Fixi
Guidance Note: Anc
Guidance Note: Fixin
Guidance Note: Anc
Guidance Note: Bon
Guidance Note: Hea Anchors (1997).
Guidance Note: FixinBlockwork (1997).
Guidance Note: Und
Guidance Note: Fixin
Section 4: Roof covering A1/2
http://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=86727REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=247903REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=251584REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=98906REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=98906REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=251584REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=247903REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=86727REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=REG
-
8/20/2019 Uk Building Regulations-A Must Know for All Devwlopers
39/47
Materials
4.1 All materials used to cover roofs,
including transparent or translucent materials,but excluding windows of glass in residentialbuildings with roof pitches of not less than15°, shall be capable of safely withstandingthe concentrated imposed loads upon roofsspecified in BS 6399: Part 3.
Re-covering of roofs
4.2 The re-covering of roofs is commonlyundertaken to extend the useful life of buildings.Roof structures may be required to carryunderdrawing or insulation provided at a timelater than their initial construction. This sectionprovides guidance on determining whether suchwork to a roof constitutes a material alterationunder the Building Regulations.
4.3 Where the work involves a significantchange in the applied loading the structuralintegrity of the roof structure and the supportingstructure should be checked to ensure thatupon completion of the work the building is notless compliant with Requirement A1 than theoriginal building.
4.4 A significant change in roof loading iswhen the loading upon the roof is increased bymore than 15%.
4.5 Where such checking of the existing roofstructure indicates that the construction is unableto sustain any proposed increase in loading (e.g.due to overstressed members or unacceptabledeflection leading to ponding), appropriatestrengthening work or replacement of roofingmembers should be undertaken. This is classifiedas a material alteration.
4.6 In carrying out the checks mentioned in
paragraph 4.3 an increase of stress in a structuralmember arising from increased loading doesnot necessarily indicate that the roof structure isless compliant than the original roof provided anadequate factor of safety is maintained.
4.7 Where work will significantly decrease
Section 4: Roof covering
DISPROPORTIONATE COLLAPSE
The Requirement
http://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=99729REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=99729REG
-
8/20/2019 Uk Building Regulations-A Must Know for All Devwlopers
40/47
This Approved Document deals with the followingRequirements which are contained in the Building
Regulations 2000 (as amended by SI 2001/3335,SI 2002/440, SI 2002/2871 and SI 2003/2692 ).
Requirement Limits on application
Disproportionate collapse
A3. The building shall be constructed so that in the event of an accidentthe building will not suffer collapse to an extent disproportionate to
the cause.
The Requirement
Guidance A3
http://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=251188REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=251188REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=254415REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=256378REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=261853REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=264861REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=264861REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=261853REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=256378REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=254415REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=251188REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=251188REG
-
8/20/2019 Uk Building Regulations-A Must Know for All Devwlopers
41/47
Performance
In the Secretary of State’s view the Requirement
of A3 will be met by an appropriate choiceof measures to reduce the sensitivity of abuilding to disproportionate collapse shouldan accident occur.
Introduction
0.1 The guidance in Section 5 deals with themeans of meeting this performance criterion.
Guidance
Section 5: Reducing the sensitiv
-
8/20/2019 Uk Building Regulations-A Must Know for All Devwlopers
42/47
Section 5: Reducing the sensitivbuilding to disproportionate coll
event of an accident5.1 The requirement will be met byadopting the following approach for ensuringthat the building is sufficiently robust tosustain a limited extent of damage or failure,depending on the class of the building,without collapse.
a. Determine the building class from Table 11.
b. For Class 1 buildings – Provided thebuilding has been designed and constructedin accordance with the rules given in this Approved Document, or other guidancereferenced under Section 1, for meetingcompliance with requirement A1 and A2 innormal use, no additional measures are likelyto be necessary.
Table 11 Building classes
Classes Building type and occupancy 1 Houses not exceeding 4 storeys
Agricultural buildings
Buildings into which people rarely go, provided no part of the building is closer to anodo go, than a distance of 1.5 times the building height
2A 5 storey single occupancy houses
Hotels not exceeding 4 storeys
Flats, apartments and other residential buildings not exceeding 4 storeys
Offices not exceeding 4 storeys
Industrial buildings not exceeding 3 storeys
Retailing premises not exceeding 3 storeys of less than 2000m² floor area in each sto
Single-storey educational buildings
All buildings not exceeding 2 storeys to which members of the public are admitted anexceeding 2000m² at each storey
2B Hotels, flats, apartments and other residential buildings greater than 4 storeys but no
Educational buildings greater than 1 storey but not exceeding 15 storeys
Retailing premises greater than 3 storeys but not exceeding 15 storeys
Hospitals not exceeding 3 storeys
c. For Class 2A buhorizontal ties, osuspended floorsin the Codes andparagraph 5.2 fowall constructionparagraph 5.3 be
d. For Class 2B buhorizontal ties, asStandards listed uand load-bearingbeing defined in pwith effective verCodes and Stand5.2, in all suppor
Alternatively, check that upon the notional Key elements
REDUCING THE SENSITIVITY OF THE BUILDING TO A3 DISPROPORTIONATE COLLAPSE IN THE EVENT OF
-
8/20/2019 Uk Building Regulations-A Must Know for All Devwlopers
43/47
Alternatively, check that upon the notionalremoval of each supporting column and eachbeam supporting one or more columns, or anynominal length of load-bearing wall (one at atime in each storey of the building), the building
remains stable and that the area of floor at anystorey at risk of collapse does not exceed 15%of the floor area of that storey or 70m2, whicheveris smaller, and does not extend further than theimmediate adjacent storeys (see Diagram 24).
Where the notional removal of such columnsand lengths of walls would result in an extent ofdamage in excess of the above limit, then suchelements should be designed as a ‘key element’
as defined in paragraph 5.3 below.e. For Class 3 buildings – A systematic
risk assessment of the building should beundertaken taking into account all the normalhazards that may reasonably be foreseen,together with any abnormal hazards.
Critical situations for design should be selectedthat reflect the conditions that can reasonablybe foreseen as possible during the life of thebuilding. The structural form and concept andany protective measures should then be chosenand the detailed design of the structure andits elements undertaken in accordance withthe recommendations given in the Codes andStandards given in paragraph 5.2.
5.2 Details of the effective horizontal andvertical ties, together with the design approachesfor checking the integrity of the building followingthe notional removal of vertical members andthe design of key elements, are available in thefollowing Codes and Standards:
BS 5628-1:1992 Structural use of unreinforcedmasonry. Code of practice for use of masonry.
BS 5950-1:2000 Structural use of steelworkin building. Code of practice for design. Rolledand welded sections.
BS 8110-1:1997 Structural use of concrete. Code of practice for design and construction.
BS 8110-2:1985 Structural use of concrete. Codeof practice for special circumstances.
5 3 Definitions
Key elements
A ‘key element’, as referred should be capable of sustaidesign loading of 34kN/m2 ahorizontal and vertical direcat a time) to the member ancomponents (e.g. cladding eto the ultimate strength of sand their connections. Suchloading should be assumedwith 1/3 of all normal characwind and imposed loading).
Load-bearing construction
For the purposes of this Gu‘load-bearing wall constructmasonry cross-wall construcomprising close centred timsteel section studs.
Alternative approac
5.4 Alternatively, for any does not fall into the classe
11 or for which the consequmay warrant particular examinvolved, the performance mrecommendations given in t
‘Guidance on Robustness a Accidental Actions’ dated J
‘Calibration of Proposed Remeeting Compliance with th
Building Regulation Part A3 Allott and Lomax proposalsNo. 205966.
Both of the above documenon the following ODPM webhttp://www.odpm.gov.uk
Diagram 24 Area at risk of collapse in the e ent of an acciden
REDUCING THE SENSITIVITY OF THE BUILDING TODISPROPORTIONATE COLLAPSE IN THE EVENT OF AN
http://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=260482REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=252984REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=257098REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=257098REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=253667REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=267193REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=267193REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=267214REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=267214REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=267214REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=267214REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=267214REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=267214REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=267193REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=267193REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=253667REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=257098REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=257098REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=252984REGhttp://www.thebuildingregs.com/RefDocs/CIS/Lookup.asp?AccessionNo=260482REG
-
8/20/2019 Uk Building Regulations-A Must Know for All Devwlopers
44/47
Diagram 24 Area at risk of collapse in the event of an acciden
See para 5.1d
A
Standards referred to
-
8/20/2019 Uk Building Regulations-A Must Know for All Devwlopers
45/47
A1/2
BS 187:1978
Specification for calcium silicate (sandlime andflintlime) bricks. AMD 5427 1987.
BS 1243:1978Specification for metal ties for cavity wallconstruction. AMD 3651 1981, AMD 4024 1982.(Withdrawn and superseded by BS EN 845-1:2003Specification for ancillary components for masonry.Ties, tension straps, hangers and brackets. AMD 14736 2003.)
BS 5080-1:1993Structural fixings in concrete and masonry.Method of test for tensile loading.
BS 5268-2:2002Structural use of timber. Code of practicefor permissible stress design, materials andworkmanship.
BS 5268-3:1998
Structural use of timber. Code of practice fortrussed rafter roofs.
BS 5628-1:1992Code of practice for use of masonry. Structuraluse of unreinforced masonry. AMD 7745 1993, AMD 13680 2002.(Withdrawn and superseded by BS 5628-1:2005Code of practice for the use of masonry. Structuraluse of reinforced masonry.)
BS 5628-2:2000Code of practice for use of masonry. Structuraluse of reinforced and prestressed masonry.(Withdrawn and superseded by BS 5628-2:2005Code of practice for the use of masonry. Structuraluse of reinforced and prestressed masonry.)
BS 5628-3:2001Code of practice for use of masonry. Materials
and components, design and workmanship.(Withdrawn and superseded by BS 5628-3:2005Code of practice for the use of masonry. Materialsand components, design and workmanship.)
BS 5950-1:2000Structural use of steelwork in building. Code of
BS 5950-5:1998Structural use of steelwork of practice for design of colgauge sections.
BS 6399-1:1996Loading for buildings. Codeand imposed loads. AMD 13
BS 6399-2:1997Loading for buildings. Codeloads. AMD 13392 2002, AM
BS 6399-3:1998Loading for buildings. Codeimposed roof loads. AMD 61996, AMD 9452 1997.
BS 8002:1994Code of practice for earth re AMD 8851 1995, AMD 1206 AMD 13386 2001.
BS 8004:1986
Code of practice for foundaBS 8103-1:1995Structural design of low-riseof practice for stability, site foundations and ground floo AMD 8980 1995.
BS 8103-2:1996Structural design of low-risepractice for masonry walls f(Superseded but remains currStructural design of low riseof practice for masonry walremains current.)
BS 8103-3:1996Structural design of low-risepractice for timber floors an
BS 8103-4:1995
Structural design of low-risepractice for suspended conc
BS 8110-1:1997Structural use of concrete. Cfor design and constructionAMD 13468 2002.
STANDARDS REFERRED TO
BS 8297:2000C d f ti f d i d i t ll ti
BS EN 845-2:2001S ifi ti f
-
8/20/2019 Uk Building Regulations-A Must Know for All Devwlopers
46/47
Code of practice for design and installationof non-loadbearing precast concrete cladding. AMD 11064 2000, AMD 13018 2000.
BS 8298:1994
Code of practice for design and installation ofnatural stone cladding and lining.
BS 8500-1:2002Concrete. Complementary British Standard toBS EN 206-1. Method of specifying and guidancefor the specifier. AMD 14639 2003.
BS 8500-2:2002Concrete. Complementary British Standard to
BS EN 206-1. Specification for constituentmaterials and concrete. AMD 14640 2003.
BS EN 197-1:2000Cement. Composition, specifications andconformity criteria for common elements. AMD 15209 2004.
BS EN 197-2:2000Cement. Conformity evaluation.
BS EN 771-1:2003Specification for masonry units. Clay masonryunits. AMD 15998 2005.
BS EN 771-2:2001Specification for masonry units. Calciumsilicate masonry units.(Withdrawn and superseded by BS EN 771-2:2003Specification for masonry units. Calcium silicatemasonry units. AMD 15974 2005.)
BS EN 771-3:2003Specification for masonry units. Aggregateconcrete masonry units (dense and light-weightaggregates).
BS EN 771-4:2001Specification for masonry units. Autoclavedaerated concrete masonry units.(Withdrawn and superseded by BS EN 771-4:2003Specification for masonry units. Autoclaved
aerated concrete masonry units. AMD 16000 2005.)
BS EN 771-5:2003Specification for masonry units. Manufacturedstone masonry units. AMD 15999 2005.
BS EN 771-6:2001
Specification for ancmasonry. Lintels.(Withdrawn and supeSpecification for anc
masonry. Lintels.)BS EN 845-3:2001Specification for ancilBed joint reinforcem(Withdrawn and supeSpecification for ancilBed joint reinforcem
BS EN 998-2:2002Specification for mor
Masonry mortar.(Withdrawn and supeSpecification for morMasonry mortar.)
BS EN 12620:2002 Aggregates for conc
DD 140-1:1986Wall ties. Method of
timber frame connec(Withdrawn and supeSpecification for ancilTies, tension straps, AMD 14736 2003.)
DD 140-2:1987Wall ties. Recommenties. AMD 7971 1994
A3BS 5628-1:1992Code of practice for use of unreinforced m AMD 13680 2002.(Partially supersededMethod of test for mcompressive strengthby BS 5628-1:2005 C
of masonry. StructuraBS 5950-1:2000Structural use of stepractice for design. R AMD 13199 2001.
BS 8110 1 1997
B ui l d i n g
Published by NBS, part of RIBA Enterprises Ltd, and available from:
RIBA Bookshops Mail Order
-
8/20/2019 Uk Building Regulations-A Must Know for All Devwlopers
47/47
g
R e g ul at i on s
2 0 0 0
A P P R OV E DD O
C UME NT A
S t r u c
t ur e
15 Bonhill Street
London EC2P 2EA
Telephone orders/General enquiries: 020 7256 7222
Fax orders: 020 7374 2737
Email orders: sales@ribabookshops.com
Or order online at:www.thebuildingregs.com
www.thenbs.com
© Crown copyright 2006
The Approved Documents are published by NBS for the Office of the Deputy Prime Minister.
This publication has been approved by Ministers and has official status. Copyright in thecontents, the cover, the design and the typographical arrangement of this publication restswith the Crown unless otherwise stated. The contents of this publication may be reproducedfree of charge in any format or medium for the purposes of private research and studyor for internal circulation within an organisation. This is subject to the contents beingreproduced accurately and not in a way that implies official status. Any publisher wishingto reproduce the content of this publication must not use or replicate the ODPM crestor replicate the official version’s style and appearance, including the cover design, andmust not present their publication as being an official publication as this may confuse thepublic. The reproduced material must be acknowledged as Crown Copyright and the titleof the publication specified. The Office of the Deputy Prime Minister does not accept anyresponsibility for the accuracy and comprehensiveness of any other versions.
Any other use of the contents of this publication would require a copyright licence. Pleaseapply for a licence by writing to the Office of Public Sector Information, Information Policy Team,St Clements House, 2-16 Colegate, Norwich NR3 1BQ. Fax 01603 723000 or emailHMSOlicensing@cabinet-office.x.gsi.gov.uk. Further information can be obtained fromwww.opsi.gov.uk.
ISBN-10 1 85946 200 6ISBN-13 978 1 85946 200 3
Stock code 56653
RIBA Bookshops
66 Portland Place, London W1B 1AD. Telephone 020 7256 7222.
113-115 Portland Street, Manchester M1 6DW. Telephone 0161 236 7691.
Birmingham & Midland Institute, Margaret Street, Birmingham B3 3SP. Telephone 0121 233 2321.
RSUA, 2 Mount Charles, Belfast BT7 1NZ. Telephone 028 9032 3760.
Renew Rooms, 82 Wood Street, Liverpool L1 4DQ. Telephone 0151 707 4380.
top related