io and fpga soultion - alphitech.com
Post on 01-Feb-2022
3 Views
Preview:
TRANSCRIPT
IO And FPGA RT Solutions Page 1
INDEX
S. N Contents PageNo.
System Level FPGA Solutions 2 I Core and Enhanced DAS Module features 3 1.1 Strain/Pressure Modules 4 1.2 Thermocouple/RTD Module 5 1.3 Voltage Module 6 1.4 Vibration (IEPE) Module 7
II System and Enclosures 8 III DAS Software 9-12 IV. Accessories 13 V Configuration list. 14
IO And FPGA RT Solutions Page 2
I/O and FPGA RT DAS Solutions
1. Index
I. Core and Enhanced DAS (PXI/CPCIs/VPX) Solutions. Strain/Pressure Modules Voltage Modules Thermocouple Modules RTD (2-wire, 3 wire, 4 wire) Modules IEPE Vibration Module LVDT Module
II. System and Enclosures
2 U/4U/6U/9U PXI/CPCI/VPX Enclosure Portable Enclosures Rugged Enclosures
III. Software
DAS system Software Customized application Development
IV. Accessories
IO Cable IO connector Systems Connector panels Rack
IO And FPGA RT Solutions Page 3
I. Core and Enhanced DAS Module features
SN Main Features Strain /Pressure IEPE Thermocouple/RTD Voltage
1 No Of channels 8/16
2 Amplifier Gain 0-5000 Programable
3 Per channel 24 Bit ADC
4 Voltage Excitation (0-12V Programable) Excitation voltage
23V (Minimum) - -
5 Type of bridge ½, ¼ & Full Bridge Programable -
J, K, E, T, N, B, R, S, C type Thermocouple, PT-100, PT-500, PT-
1000
Differential/Single ended
6 Sampling rate Up to 250 KSPS
7
Filter Software selectable Digital Low pass
Filter 1Hz to 30KHz
User selectable User selectable User selectable User selectable
8 Isolation Input/output/Power
Available in Enhanced IO Module
Available in Enhanced IO Module
Available in Enhanced IO Module
Available in Enhanced IO Module
9 Common Mode
voltage >300V
Available in Enhanced IO Module
Available in Enhanced IO Module
Available in Enhanced IO Module
Available in Enhanced IO Module
10 Analog Dual output Available in Enhanced IO Module
Available in Enhanced IO Module
Available in Enhanced IO Module
Available in Enhanced IO Module
11 Size 3U/6U 3U/6U 3U/6U 3U/6U
12 Form factor PXI/PXIe/CPCI/VPX PXI/PXIe/CPCI/VPX PXI/PXIe/CPCI/VPX PXI/PXIe/CPCI/VPX
All the modules are pluggable mezzanine modules that can be hosted by any carrier modules to suite various buses - PXI/PXIe/CPCI/VPXetc and a wide
range of application demands.
IO And FPGA RT Solutions Page 4
1.1 Strain/Pressure Modules Overview The PXI/CPCIs-Stra16-A0 module offers a complete solution for High Performance data Acquisition applications.Both the A/D and D/A offers 5us converters. The input instrumentation amplifiers provide differential inputs, buffering and gain. A/D operations can be triggered internally or externally through the front panel.Each D/A offers 2 output simultaneously for monitoring and control.A PXI/CPCIs bus connector provides the interface to the host computer with x1 Lane PCI express. Main features
• 16 Channels per board • 24 Bits Delta Sigma A/D • Sampling rate: 5 SPS to 250 kSPS • Overvoltage protected up to ±30 V • Input range: ±2mV to 10V • Programmable Gain up to
1,10,100,1000,2000,5000 with 0.05% accuracy and Linearity 0.02%
• Low pass FIR Filter with programmable up to 5kHz cut off (-3dB)
• TEDS support • Types of Strain Input bridges:
Quarter, Half and Full bridges • Strain Gauge Bridge resistances:
350 Ω and 120 Ω • Isolation (Input/output/Power) ** • 300V or better Common Mode voltage ** • Dual analog Outputs ** • Dual +/- 10V AO outputs ** • Short circuit protection on Analog Outputs • Output Current: 40 mA
Software Drivers
• C library DLL’s • Linux drivers • Window drivers • Lab View • VxWorks drive •
Datasheet
Ordering Information PXI-Stra16 6U PXI 16 Ch A/D125kSPS PXI-Stra16-A0* 6U PXI 16 Ch with AO A/D125kSPS CPCI-Stra16 6U CPCI 16 Ch A/D125kSPS CPCI-Stra16-A0* 6U CPCI 16 Ch with AO A/D125kSPS
Optional AccessoriesCBL-HDR-50 50-pin IDC cable only
TB-50-HDR 50-pin Header terminals block and 3 feet Flat Ribbon Cable
XMC or PMC Carrier board
All the modules are pluggable mezzanine modules that can be hosted by any carrier modules to suite various buses - PXI/PXIe/CPCI/VPX etc and a wide range of
application demands.
Mezzaninemodule CH 1- 8
TR1 TR2
Mezzaninemodule CH 9- 16
TR1 TR2
IO And FPGA RT Solutions Page 5
2.2 Thermocouple/RTD Module Overview The PXI/CPCIs-RTD SC module offers a complete solution for Thermocouple Solution. It offers 24 bits precision temperature measurement, with fixed and optional programmable current source. Each of the 16-temperature measurement channels has its own A/D converter with two matched 200 µA current sources.The Board also features 16 single-ended high impedance analog inputs. Also, a 16-bit A/D converter with 16 channels multiplexed allows measurement of input voltage in excess of +/- 20 volts. Main features • 6U high Compact PCIs module • 16 Channels 4 Wires RTD or 20 Channels 2
or 3 wires RTD • J, K, E, T, N, B, R, S, C type Thermocouple • Automatic CJC Cold Junction
Compensation • Built-In Standard and User-Programmable
Coefficients for Thermocouples, RTDs and Thermistors
• Negative Thermocouple Voltages support • Automatic Short-Circuit & Fault Detection • Support most RTD:PT-10, PT-50, PT-100,
PT-200, PT-500, PT-1000, and NI-120 • Input impedance of 1MΩ • 24 Bits Delta Sigma A/D • Sampling rateUp to 250 KSPS • High CMRR: 120 dB • Isolation (Input/output/Power) ** • 300V or better Common Mode voltage ** • +/- 10V Dual analog Outputs ** • Short circuit protectionon Analog Outputs • 0.1°C accuracy and 0.001°C resolution
Software Drivers
• Linux drivers • C library DLL’s • Window drivers • LabView • VxWorks drive
Datasheet
Ordering Information PXI-TC16 6U PXI 16 Ch Thermo Couple, Commercial 0 – 70Deg C PXI-TC16 with AO* PXI-RTD16 6U PXI 16 Ch RTD Commercial 0 – 70 Deg C PXI-RTD 16 With AO* CPCI-TC16 6U CPCIs, 16 Ch Thermo Couple Industrial -40 to 85 CCPCIs TC 16 With AO* CPCI-RTD16 6U CPCIs, 16 Ch RTD -40 to 85 C CPCIs RTD 16 with AO*
Optional Accessories
CBL-HDR-50 50-pin IDC cable only TB-50-HDR 50-pin Header terminals block and 3 feet Flat Ribbon Cable
2X50
IDC
DDR64MB
DMA
FPGA
scan clock internalclock
PCIe
X 1
serialnvRAM
D/A
external
Ain1+Ain1-
RTD1200uA
2.5VREFIN+
REFIN-
RTD2200uA
R Ref
AGND
T
D/A
24- bit A/D
X 4
24- bit A/D
24- bit A/D
MUX
21:6
Ch 4
Ch 20
Ch 1
XMC/PMC Carrier
board
Mezzanine module CH 1- 8
TR1 TR2
Mezzanine module CH 9- 16
TR1 TR2
All the modules are pluggable mezzanine modules that can be hosted by any carrier modules to suite various buses - PXI/PXIe/CPCI/VPX etc and a wide
range of application demands.
IO And FPGA RT Solutions Page 6
2.3 Voltage Module
Overview
The PXI/CPCIs-VOLT SC module offers a complete solution for High Performance data Acquisition applications. Both the A/D and D/A offers 5 us converters. The input instrumentation amplifiers provide differential input buffering and gain. A/D operations can be triggered internally or externally through the front panel. Each D/A offers 2 output simultaneously for monitoring and control. A CPCI subs connector provides the interface to the host computer with x1 Lane PCI express
Main features • 6U PXI/CPCI voltage input Module • 32 SE/16 DIFF x 24-bits Σ-Δ AD • Input range settable +/-10V • Per channel configurability—up to sixteen
different setups can be defined. • 24 Bits Delta Sigma A/D • Sampling rate: 5 SPS to 250 kSPS • Giga ohm (GΩ) input impedance or better • Isolation (Input/output/Power) ** • 300V or better Common Mode voltage ** • +/- 10VDual buffer analog Outputs ** • Short circuit protected Analog Outputs • Output Current: 50 mA min
Software Drivers
• Windows drivers • C library DLL’s • LabView
Datasheet
Ordering Information
CPCIs-VOLT SC6U CPCIs, 8/16 Ch A/D250kSPS Commercial 0 – 70Deg C CPCIs-VOLT SC with AO * 6U CPCIs, 8/16 Ch A/D250kSPS, 8/16 Ch D/A 5us, with AO * PXI-VOLT SC 6U CPCIs, 8/16 Ch A/D 250 kSPS Commercial 0 – 70 Deg C PXI-VOLT SC-with AO 6U CPCIs, 8/16 Ch A/D 250 kSPS, 8/16 Ch D/A 5 us, with AO *
Optional Accessories CBL-HDR-50 50-pin IDC cable only TB-50-HDR 50-pin Header terminals block and 3 feet Flat Ribbon Cable
2X50
IDC
DDR64MB
24- bit A/D
DMA
FPGA
scan clock internalclock
controllogic
Eth
1GB
PCIe
X 1
serialnvRAM
8 inputs
16- bit D/A
external
X 8 channels A/DVoltage Input +/
Ain1+Ain1-
-
X 8 channels
D/A with Dual Ouput
OU1A
OU1B
XMC/PMC Carrier board
Mezzanine module CH 1- 8
TR1 TR2
Mezzanine module CH 9- 16
TR1 TR2
All the modules are pluggable mezzanine modules that can be hosted by any carrier modules to suite various buses - PXI/PXIe/CPCI/VPX etc and a wide range of
application demands.
IO And FPGA RT Solutions Page 7
2.4 Vibration (IEPE) Module
Overview The PXI-IEPE-6U module offers a complete single board IEPE sensor Analog Input.This design is intended for use with a high-end single-channel IEPE sensor interface. A 24-bit conversion at maximum sampling speeds reaching up to 256 KSPS establishes this design at the leading edge of the existing product range. The design targets an input bandwidth of 20 kHZ and a programmable gain between –12 dB to 18 dB. A programmable excitation current of 2 mA to 20 mA as well as a programmable sampling speed down to 32 kSPS means that this design can accommodate different sensor cable distances and different back-end DAQ capabilities. Wire-break and short-circuit detection ensure safe and reliable operation of the sensor interface Main features • 6U high PXI/CPCI-6U module • 16 x Channels IEPE Sensor Analog
Input • Programmable Data Rate: up to 256
kSPS, • SNR 100dB • Programmable Excitation Current: 2
mA to 20 mA (8 bits of resolution) • Excitation voltage 23V (Minimum) • ±10-V AC Input, 250-kΩ Input
Impedance • Diagnostics: Wire-Break, Short-Circuit
Detection, and Short-Circuit Protection
• 24 Bits Delta Sigma A/D • High Pass Filter/low pass filter • Giga ohm (GΩ) input impedance • Isolation (Input/output/Power) ** • 300V or better Common Mode voltage ** • +/- 10V Dual analog Outputs **
Datasheet Available Software Drivers and Software Tools:
• C library DLL’s Linux drivers • Window drivers • LabView • VxWorks drivers •
Ordering Information
PXI-IEPE-6U 6U PXI 16 Ch IEPE Sensor Input Commercial 0 – 70Deg C PXI-IEPE—6U-with AO* 6U PXI 16 Ch IEPE Sensor Input Industrial -40 to 85 C CPCIs-IEPE-6U 6U CPCI, 16 Ch IEPE Sensor Input Commercial 0 – 70Deg C CPCIs-IEPE—6U-with AO 6U CPCI, 16 Ch IEPE Sensor Input Industrial -40 to 85 C
Optional Accessories SMC-BNC- XXX SMB Blug to BNC RG233 Coax cable only XXX Desired length: 36, 48, 60, 72
DDR64MB
24 bit A/D
DMA
FPGA
scan clock internalclock
control
logic
CPCI
serialnvRAM
external
clock
Atten
IEPE1Vcom
Gain
MFB LPF3rd Order
DAC PGMCurrent
0- 20maIEPE Sensor
24 bit A/D
Atten
Sensors
Vcom
Gain
MFB LPF3rd Order
DAC PGMCurrent
0- 20maIEPE Sensor
X 6 Channel
Ext Connector
IEPE6
DAC
DAC
DAOut1
DAOut2
XMC/PMC Carrier board
Mezzanine module CH 1- 8
TR1 TR2
Mezzanine module CH 9- 16
TR1 TR2
All the modules are pluggable mezzanine modules that can be hosted by any carrier modules to suite various buses - PXI/PXIe/CPCI/VPX etc and a wide
range of application demands.
IO And FPGA RT Solutions Page 8
3 Systems and Enclosure Rack Mount 2U/4U/6U/9U 4/6/9/20 Slot Chassis
• Advanced EMC shielded 19“chassis, powder-coated black (RAL 9005) • Applicable for Compact PCI, PICMG 2.16, VME bus and VME64x backplanes • Horizontal backplane, 4 slots • System platform for horizontal boards (6 U) • Card cage front: 160 mm • Card cage rear I/O: 80 mm • ON/OFF switch: rear • Fan speed controlled by Fan Con in order to min. noise • Ambient temperature: 0 °C to +50 °C operation; –40 °C to +80 °C storage • Humidity: 30 % – 80 %, non-condensing • Form factor PXI/CPCI/VPX
Rugged Chassis
• Modular, Rugged COTs design • VPX, PXI, PXIe,cPCI and MicroTCA compatible • 19" rack mount per IEC60297 (slide mounting optional) • 8U H x standard depths: 22" and 25" • 12-21 card slots, front access • Optional shock isolated cards cage and device mounting • Front to rear evacuative cooling (350 LFM @ .1" H20) • Custom rear I/O patch panel (rear I/O cards optional) • MIL grade components • 500 to 1200-watt PSU options • Input options: 90-264VAC Fixed PSU, 47-500 Hz, 28/48VDC • Designed to meet: MIL-STD-5400, MIL-STD-810F, MIL-STD-46IE, MIL-STD-704E, MIL-STD-1275A, MIL-STD-167,
MIL-STD-901 Portable Chassis
• 4U Portable tower fully compliant to IEEE 1101.10/.11 • 3, 4, or 6 slot, 6U x 160mm boards • PICMG: 2.0, 2.16, 2.17, 2.20 backplanes (H.110 optional) • Cooling front to rear (1 x 90 CFM), plug removable • Advanced EMC shielding to meet CE and FCC • Wide range of PSU inputs (90 - 264 VAC, 48VDC) • Wide range of PSU options: fix mount, plug in, N+1 • Ready to run - turnkey solution
4 slot Chassis WITH PSW
14/21 Slot Chassis
Rugged Chassis
PortableChassis
SBC & backplanes
IO And FPGA RT Solution Page 9
4 Application development environmental platform:
• We shall provide Lab view Runtime platform on Lab view development environment for developing the real
tome software and real time simulation • We shall provide BSP, library, API & test applications for the I/O models to test and clear the ATP of
installation
The Lab view Run-Time Platform from Lab VIEW-built applications relates to the concept of component-based software development and distribution. The world of software today is a component-based world. No longer do we develop and deploy monolithic applications. Rather, we develop software that reuses common components as often as possible. When we deploy this software, more than a single file is almost always required. Applications that use the same components are then able to use the same common files, resulting in smaller disk usage than if each application included all required components. Perhaps even more importantly, developing component-based software allows us to update individual components separately from the software that uses those components.
The principal complaints about LabVIEW applications were their large size. A contributing factor to the size of LabVIEW applications was that the Application Builder includes a copy of the LabVIEW Run-Time Engine in every application. Using the principles of component-based software, one way to solve this problem was to separate out the common component, the LabVIEW Run-Time Engine, so that all LabVIEW-built applications on a system could use the component.
Many of the technologies that we use in LabVIEW today are available only as components. Examples include Data Socket, NI-Reports, and the Mesa graphics library for displaying three-dimensional controls and indicators.
IO And FPGA RT Solution Page 12
Lab view development environment With the Lab VIEW Embedded Model for Blackfin Processors, domain
experts can develop their applications from algorithm design and prototyping to deployment and test – all using one platform. The graphical software includes more than 140 Blackfin-specific, hand-optimized math, analysis, and signal processing functions • High-performance execution with compiled code optimized for the execution target • Rapid prototyping and development with graphical programming • Integrated debugging and system analysis tools • Add-on models to deploy code to real-time and FPGA targets
Integrated I/O such as audio and video DACs, ADCs and CODECs; and on-chip debugging, as well as easy graphical interconnection via Ethernet. The LabVIEW Embedded Model for Black fin Processors includes the fully featured and accessible ADI VisualDSP++ C development and debugging environment for low-level access and real-time, interactive debugging and deployment directly to Black fin. Engineers and scientists can debug code graphically in LabVIEW or simultaneously debug both the graphical code and generated C source code. The new model is shipped with examples for applications including audio, control, power monitoring, and communications. It also provides easy connectivity to the extensive range of NI test and measurement hardware for deploying external simulation and test methodologies early in the development process
SOFTDAQ Software Includes following Modules
• Setup Configuration Module • Online Display Module • Calibration Module • Lab sensitivity • Field Calibration • Internal shunt Calibration • External shunt Calibration • Offline Analysis
IO And FPGA RT Solution Page 14
VI. Accessories
1. Instrumentation Rack, Cables, Connectors panels
• 42U Smart Rack enclosure with doors and side panels • Adjustable mounting rails with easy-view depth index and toolless
mounting slots for PDUs and vertical cable managers. Locking, removable, reversible front and rear doors
• EMC/EMI Standards
D Sub Connectors MIL- Connectors BNC Connectors
Dual Buffer & Isolator
Customized Connector panel
IO And FPGA RT Solution Page 15
V. Configuration List Description Model No. Remarks
Strain
PXI-Stra16 6U PXI 16 Ch A/D125kSPS PXI-Stra16 with AO* 6U PXI 16 Ch with AO A/D125kSPS
CPCI-Stra16 6U CPCI 16 Ch A/D125kSPS CPCI-Stra16-A0* 6U CPCI 16 Ch with AO A/D125kSPS
Thermocouple
PXI-TC16 6U PXI 16 Ch Thermo Couple, Commercial 0 – 70 Deg C PXI-TC16 with AO*
CPCI-TC1 6U CPCIs, 16 Ch Thermo Couple Industrial -40 to 85 C CPCIs TC 16 With AO*
RTD
PXI-RTD16 6U PXI 16 Ch RTD Commercial 0 – 70 Deg C PXI-RTD 16 With AO*
CPCI-RTD16 6U CPCIs, 16 Ch RTD -40 to 85 C CPCIs RTD 16 with AO*
IEPE
PXI-IEPE-6U 6U PXI 16 Ch IEPE Sensor Input Commercial 0 – 70 Deg C
PXI-IEPE—6U-with A 6U PXI 16 Ch IEPE Sensor Input CPCIs-IEPE- 6U CPCI, 16 Ch IEPE Sensor Input
Commercial 0 – 70 Deg C CPCIs-IEPE—6U-with AO 6U CPCI, 16 Ch IEPE Sensor Input
Voltage
CPCIs-VOLT SC 6U CPCIs, 8/16 Ch A/D 250 kSPS Commercial 0 – 70 Deg C
CPCIs-VOLT SC with AO * 6U CPCIs, 8/16 Ch A/D 250 kSPS, 8/16 Ch D/A 5 us, with AO *
PXI-VOLT 6U CPCIs, 8/16 Ch A/D 250 kSPS Commercial 0 – 70 Deg C
PXI-VOLT SC-with AO 6U CPCIs, 8/16 Ch A/D 250 kSPS, 8/16 Ch D/A 5 us, with AO *
LVDT VDSP31-SC-LVDT LVDT INPUT MODULE Software Application development Kit
accessories Optional Transition Modules
top related