Designing to Prevent Disasters: Mechanical System Failures and Physical Plant Design. Bill Zavatkay PE, LEED AP BD+C – HDR Mechanical Engineering Section Manager. Introduction Disasters Regulatory Requirements Physical Plant. A. - PowerPoint PPT Presentation

TRANSCRIPT

Designing to Prevent Disasters: Mechanical System Failures

and Physical Plant Design

Bill Zavatkay PE, LEED AP BD+C – HDRMechanical Engineering Section Manager

A

Click icon to add picture

Introduction

Disasters

Regulatory Requirements

Physical Plant

2014 ACLAM FORUM: Coeur d’Alene, Idaho

By definition, a disaster is, "an occurrence causing

widespread destruction and distress, a grave

misfortune, a total failure..." A disaster is often

further defined as being either a man-made or

natural event that results in death, injury, and

property damage which cannot be managed

through normal, routine channels.(Source: Google…Author not indicated).

B

Click icon to add picture

Introduction

Disasters

Regulatory Requirements

Physical Plant

2014 ACLAM FORUM: Coeur d’Alene, Idaho

What we typically think of as a Disaster?

2014 ACLAM FORUM: Coeur d’Alene, Idaho

Widespread flooding from levee breaches and storm surge

2014 ACLAM FORUM: Coeur d’Alene, Idaho

Widespread flooding from levee breaches and storm surge

2014 ACLAM FORUM: Coeur d’Alene, Idaho

Wind and flood damage

2014 ACLAM FORUM: Coeur d’Alene, Idaho

Wind damage to buildings

2014 ACLAM FORUM: Coeur d’Alene, Idaho

Tree damage to buildings

2014 ACLAM FORUM: Coeur d’Alene, Idaho

Impassable roads

2014 ACLAM FORUM: Coeur d’Alene, Idaho

Natural disasters occur and make big headlines, but more likely events include:

• Facility Failures

• Operational Issues

• Power Outages

2014 ACLAM FORUM: Coeur d’Alene, Idaho

Broken Pipes

FiresFailed Equipment

C

Click icon to add picture

Introduction

Disasters

Regulatory Requirements

Physical Plant

2014 ACLAM FORUM: Coeur d’Alene, Idaho

REGULATORY REQUIREMENTS

Green / Sustainable / LEED / Energy Star / ASHRAE 90.1 =

Building codes / GUIDE / BMBL / WHO / NIH DRM / AALAC / USDA =

• Safety for building occupants as well as “the public”

• Minimum exhaust stack velocities (vs energy savings)• Redundant equipment (increased electrical load)

• Spare capacity (effects on operation energy use)

“SAVE THE PLANET”

“Safety”

Combined equals your Project

2014 ACLAM FORUM: Coeur d’Alene, Idaho

THE GUIDE – BASIC HVAC REQUIREMENTS

» Performance Based Approach• Temperature and humidity control to minimize variations.• Pressurization Control – Directional Airflow• HVAC system to be designed for reliability, ease of

maintenance and energy conservation.• Temperature: 68-79 deg F, maintain +\- 2 degrees F (varies

based on species)• Maintain Humidity 30-70% year round.• Redundancy • Temperature control for each holding space.• Emergency power for critical services (HVAC, freezers,

ventilated racks, isolators)

2014 ACLAM FORUM: Coeur d’Alene, Idaho

NIH DRM - BASIC HVAC REQUIREMENTS

» Prescriptive Based Approach• Animal Facilities shall meet the requirements of “The Guide”• Laboratory Spaces shall meet the requirements of the

BMBL.• Design conditions: ASHRAE 0.4% summer, 99.6% winter• Equipment sized for 20% future expansion.• 15 ACH Small Animal Static Rack/Large Animal• 10 ACH Small Animal Ventilated Rack• Exhaust fans on emergency power.• Dedicated Air Systems

» Non-Research Function» Animal Areas» Lab General Research.

• N+1 Redundancy Required.• Emergency Power Required; AHU’s, EF, chillers, boilers,

pumps, etc.

2014 ACLAM FORUM: Coeur d’Alene, Idaho

THE GUIDE – PAGE 35

Animal facilities may be subject to unexpected conditions that result in the catastrophic failure of critical systems or significant personnel absenteeism, or other unexpected events that severely compromise ongoing animal care and well-being (ILAR 2010). Facilities must therefore have a disaster plan. The plan should define the actions necessary to prevent animal pain, distress, and deaths due to loss of systems such as those that control ventilation, cooling, heating, or provision of potable water. If possible the plan should describe how the facility will preserve animals that are necessary for critical research activities or the irreplaceable. Knowledge of the geographic locale may provide guidance as to the probability of a particular type of disaster.

2014 ACLAM FORUM: Coeur d’Alene, Idaho

NIH GUIDELINES

» “Spare” Capacity Issues• Different than redundancy or reliability• Owner driven (program revisions)• NIH DRM requirements for 20% spare capacity• Process loads (large % of total load)• Major equipment turndown Issues

» Chillers» Boilers» AHU Components

• Coils• Filters• Fans• Humidifiers• Airflow Stations

» Exhaust fans

n+1 + 20% =

Potential Loss of

EfficiencyUntil Used

D

Click icon to add picture

Introduction

Disaster Preparedness

Regulatory Requirements

Physical Plant

2014 ACLAM FORUM: Coeur d’Alene, Idaho

• Every system will fail at the least opportunistic time.

• Design, plan, educate and train to eliminate or provide redundancy for every critical system.

“SINGLE POINT OF FAILURE”

2014 ACLAM FORUM: Coeur d’Alene, Idaho

Identify all Critical systems:

MEP Systems:

• Air Handling Units • Exhaust Fans• Cooling • Heating• Controls• Potable Water• Power

“SINGLE POINT OF FAILURE”

2014 ACLAM FORUM: Coeur d’Alene, Idaho

MEP Critical systems:

• Need Redundancy• Need Spare Parts• Need Maintenance Staff to Install

Spare Parts

“SINGLE POINT OF FAILURE”

2014 ACLAM FORUM: Coeur d’Alene, Idaho

PHYSICAL PLANT Reliability is a measure of probability that the environmental systems will be operational at the time that it is required.

Redundancy is a subset of reliability and can be achieved by the engineering systems, or a combination of engineering systems and protocols

2 at 50%

3 at 33%

4 at 25%

2014 ACLAM FORUM: Coeur d’Alene, Idaho

PHYSICAL PLANT

No redundancy Scenario One AHU and one EF serves each zone

Lab Zone

Lab Zone

2014 ACLAM FORUM: Coeur d’Alene, Idaho

PHYSICAL PLANT

Partial Redundancy Scenario Requires ductwork and control dampers to allow

interconnection of air systems Requires extensive ceiling space Reduces quantity of equipment to provide

redundancy

Lab Zone

Lab Zone

2014 ACLAM FORUM: Coeur d’Alene, Idaho

PHYSICAL PLANT

Lab Zone

Lab Zone

Fully Redundant Scenario – 2N or 2@50% Greater equipment requirements Automatic Operation Less dependency upon other systems

2014 ACLAM FORUM: Coeur d’Alene, Idaho

Reliability & Redundancy•independent systems•N+1 (100%) back-up capability

desirable•Less than N+1 with load shedding•consider utilizing systems adjacent to

vivarium spaces as an alternate means to provide redundancy

PHYSICAL PLANT

2014 ACLAM FORUM: Coeur d’Alene, Idaho

PHYSICAL PLANT

AHU fan redundancy options Fan Wall Dual Fans

2014 ACLAM FORUM: Coeur d’Alene, Idaho

Failure Protection - Automation•normal operation•exhaust failure – supply reacts•supply failure – exhaust reacts•BAS controls & interlocks•maintain directional airflow (positive or

negative pressurization)•consider ‘load shedding’ strategies

PHYSICAL PLANT

2014 ACLAM FORUM: Coeur d’Alene, Idaho

Central Utilities (Campus Scenario- Issues)

•Large Chiller Plants typically not on emergency power backup

•Large Boiler Plants typically not on emergency power backup

PHYSICAL PLANT

2014 ACLAM FORUM: Coeur d’Alene, Idaho

Central Utilities (Campus Scenario-Resolutions)

•Consider providing small backup air cooled chiller and pumps for critical cooling.

•Consider providing small backup boiler and pumps for critical heating

PHYSICAL PLANT

2014 ACLAM FORUM: Coeur d’Alene, Idaho

Potable Water

•Consider providing potable water backup storage tank if water outage typical.•Provide maintenance staff on hand to repair pipe leaks.•Ensure shut-off valves are in place in case of emergency.•Periodically exercise valves to ensure they will be operational when required.

PHYSICAL PLANT

2014 ACLAM FORUM: Coeur d’Alene, Idaho

Normal Power•Redundant Feeders to a double ended substation•Redundancy and independent

electric services•Should come from two separate

utility generating stations (Or from two separate substations on a campus configuration)

•Feeders should be in separate duct banks and routing.

•Provides redundancy in feeders and in services to building.

PHYSICAL PLANT - POWER

2014 ACLAM FORUM: Coeur d’Alene, Idaho

EM Power•Generators•Serve critical equipment•Supply air handlers•Exhaust fans•Caging systems (IVCs)•Heating & Cooling systems•Distribution pumps•BAS system controllers

UPS•BAS control panels to keep from resetting controls to minimize downtime under any failure scenario

PHYSICAL PLANT - POWER

2014 ACLAM FORUM: Coeur d’Alene, Idaho

PHYSICAL PLANT…

Locate vivarium above flood elevation levels – New facilities

» Flood gates or retaining walls around existing facilities

Locate physical plant above flood elevation levels

Locate electrical switchgear above floor elevation levels

2014 ACLAM FORUM: Coeur d’Alene, Idaho

PHYSICAL PLANT…

Provide adequate level of redundancy

Provide automated control

Provide Emergency Power Backup

Locate generators above flood elevation level

Provide “enough” fuel capacity for sustained duration for outage based on risk assessment

2014 ACLAM FORUM: Coeur d’Alene, Idaho

PHYSICAL PLANT… Fail closed reheat coil valves

Fail open AHU preheat valve

Fail open AHU cooling coil valves

Interlock AHU’s with EF’s

Interlock supply and exhaust air valves

Security systems to prevent unwanted entry

Seismic reinforcement

2014 ACLAM FORUM: Coeur d’Alene, Idaho

PHYSICAL PLANT…

Snowfall issues and AHU shutdowns

2014 ACLAM FORUM: Coeur d’Alene, Idaho

PHYSICAL PLANT…

Provide snow melt device such as MISTOP Snostop

Provide bypass damper across filters that opens on high filter delta P

Remove AHU pre-filters before snow occurrences

2014 ACLAM FORUM: Coeur d’Alene, Idaho

PHYSICAL PLANT – MAINTENANCE

• Access Outside Vivarium

• Locate Equipment where it is accessible

• Routine Inspection

• Preventative Maintenance

• Minimize Impact on Science

• High Tech vs. Low Tech

2014 ACLAM FORUM: Coeur d’Alene, Idaho

THE BIODESIGN INSTITUTE AT ASU

2014 ACLAM FORUM: Coeur d’Alene, Idaho

2014 ACLAM FORUM: Coeur d’Alene, Idaho

PHYSICAL PLANT

2014 ACLAM FORUM: Coeur d’Alene, Idaho

PHYSICAL PLANT

2014 ACLAM FORUM: Coeur d’Alene, Idaho

PHYSICAL PLANT

2014 ACLAM FORUM: Coeur d’Alene, Idaho

PHYSICAL PLANT

2014 ACLAM FORUM: Coeur d’Alene, Idaho

PHYSICAL PLANT

2014 ACLAM FORUM: Coeur d’Alene, Idaho

Questions?