CONCEPT OF SYMMETRICAL COMPONENT AS A TECHNIQUE FOR ANALYSIS OF FAULT AND IMPROVEMENT OF OVERCURRENT PROTECTION SCHEME

TRANSCRIPT

1

A SEMINAR PRESENTATION ON

“CONCEPT OF SYMMETRICAL COMPONENT AS A TECHNIQUE FOR ANALYSIS OF FAULT AND IMPROVEMENT OF OVERCURRENT PROTECTION SCHEME”

Submitted to: Submitted by:

Mr. Ankush Tandon Saurabh Varshney

Mrs. Deepti Arela (10ESKEE106)

2

CONTENT

INTRODUCTION PROTECTION SYSTEM SYMMETRICAL COMPONENT FAULT OVERCURRENT RELAY ALGORITHM SIMULATION DISTRIBUTION SYSTEM RESULTS CONCLUSION

3

INTRODUCTION

Aim of my seminar topic is better understanding the concept of symmetrical components for enhancing protection scheme by providing a practical technology for understanding and analyzing power system operation during unbalanced condition.

4

PROTECTION SYSTEMWhat is need of protective system ? In order to maintain steady state of power system by

taking correct and quick remedial action during any faulty condition.

Properties of a good protective systemAutomaticQuickMinimum amount of disruption

5

SYMMETRICAL COMPONENT

Unbalanced systems are difficult to handle. It provide balanced analysis of an unbalanced

system The unbalanced three phase system can be

transformed into three balanced phasorsPositive SequenceNegative SequenceZero Sequence

6

POSITIVE PHASE SEQUENCE

Each have the same magnitude.

Each positive sequence voltage or

current quantity is displaced 120°

from one another.

The positive sequence quantities

have a-b-c, counter clock-wise,

phase rotation.

7

NEGATIVE PHASE SEQUENCE

Each have the same magnitude.

Each negative sequence voltage

or current quantity is displaced 120°

from one another.

The negative sequence quantities

have a-c-b, counter clock-wise,

phase rotation.

8

ZERO PHASE SEQUENCE

Each zero sequence quantity has the same magnitude.

All three phasor with no angular

displacement between them, all in phase.

9

FAULT

o General Causes of faultFault due to lightningTree limbs falling on the lineWind damage

Effects of faultFlow of excessive currentAbnormal voltagesInduces over voltages on neighbouring equipments. Hazards to human, equipment and animals

10

TYPES OF FAULTS• Balanced Faults :

– Three-phase fault

• Unbalanced Faults :– Single line to ground fault– Line to line fault– Double line to ground fault

11

UNBALANCED FAULTS

12

SINGLE LINE TO GROUND FAULT

The most common type of fault is the single line to ground fault:

13

The SLG fault can be described by the following voltage and current relationship: Ib=0 & Ic=0

Va=IaZf

The Sequence current can be given as:

14

LINE TO LINE FAULT

It occurs when two conductors are short circuited.

There is no zero sequence component due to absence of ground return path.

The positive and negative sequence components are connected in parallel.

15

DOUBLE LINE TO GROUND FAULT

In double line to ground fault two line conductors come in contact with each other and ground .

The networks are connected in parallel.

For the zero sequence component it requires to add an external impedance of Zf+3Zg

16

OVER CURRENT RELAY Short-circuit currents are generally several times (5 to 20)

full load current. Hence fast fault clearance is always desirable on short circuits.

A relay that operates or picks up when it’s current exceeds a predetermined value (setting value) is called Over current Relay.

Over current includes short-circuit protection, and short circuits can be: Phase faults Earth faults Winding faults

17

TYPES OF OVER CURRENT RELAY

I. Instantaneous Over current (Definite Current) Relay

II. Definite Time Over current Relay

III. Inverse Time Over current Relay (IDMT Relay)

i. Moderately Inverse

ii. Very Inverse Time

iii. Extremely Inverse

IV. Directional over current Relay

18

ALGORITHM The criterion function for discriminating fault

from non fault switching is defined as follows :

R= |I1|-|I2| / |I1|+|I2|

19

SIMULATED DISTRIBUTION SYSTEM

20

RESULTSSeveral non faults events are applied to

this system along with some short circuit events a different time.

The discrimination of fault from a non fault event could be done by representing two cases Transformer energizingFault

21

TRANSFORMER ENERGIZING Various inrush current condition were simulated. Various parameters which have considerable effect

on the characteristic of the current signal were changed and was analysed.

FAULT In this case a single line to ground fault occurs.

22

NON FAULT CONDITION

WHEN VALUE OF R>=.35s

FAULTY CONDITION WHEN VALUE OF R<.35s

23

THREE PHASE CURRENT BEFORE FAULT

THREE PHASE CURRENT AFTER FAULT

24

CONCLUSION Simple method of improving over current relays

operation by algorithm, based on different behaviour of the current amplitudes. Based on the differences, a criterion function R is defined such that undesirable operation of the over current relays to the switching is prevented.

25

THANK YOU

ANY QUERIES?