ee 340 symmetrical faultseebag/symmetrical faults.pdf · ac and dc components just after the fault...

31
1 EE 340 EE 340 Symmetrical Faults Symmetrical Faults

Upload: halien

Post on 13-Apr-2018

235 views

Category:

Documents


7 download

TRANSCRIPT

Page 1: EE 340 Symmetrical Faultseebag/Symmetrical faults.pdf · AC and DC components just after the fault ... a symmetrical 3 phase fault occurs on that bus. 20 Fault current calculations

1

EE 340EE 340Symmetrical FaultsSymmetrical Faults

Page 2: EE 340 Symmetrical Faultseebag/Symmetrical faults.pdf · AC and DC components just after the fault ... a symmetrical 3 phase fault occurs on that bus. 20 Fault current calculations

2

IntroductionIntroduction

A A faultfault in a circuit is any failure that in a circuit is any failure that interferes with the normal system interferes with the normal system operation. operation. Lighting strokes cause most faults on Lighting strokes cause most faults on highhigh--voltage transmission lines voltage transmission lines producing a very high transient that producing a very high transient that greatly exceeds the rated voltage of greatly exceeds the rated voltage of the line. the line. This voltage usually causes flashover This voltage usually causes flashover between the phases and/or the ground between the phases and/or the ground creating an arc. creating an arc. Since the impedance of this new path Since the impedance of this new path is usually low, an excessive current is usually low, an excessive current may flow.may flow.Faults involving ionized current paths Faults involving ionized current paths are also called transient faults. They are also called transient faults. They usually clear if power is removed from usually clear if power is removed from the line for a short time and then the line for a short time and then restored.restored.

Page 3: EE 340 Symmetrical Faultseebag/Symmetrical faults.pdf · AC and DC components just after the fault ... a symmetrical 3 phase fault occurs on that bus. 20 Fault current calculations

3

IntroductionIntroduction• If one, or two, or all three phases break or

if insulators break due to fatigue or inclement weather This fault is called a permanent fault since it will remain after a quick power removing.

• Approximately 75% of all faults in power systems are transient in nature.

• Selecting an appropriate circuit breaker (type, size, etc.) is important…

Page 4: EE 340 Symmetrical Faultseebag/Symmetrical faults.pdf · AC and DC components just after the fault ... a symmetrical 3 phase fault occurs on that bus. 20 Fault current calculations

4

33--Phase fault current transients in Phase fault current transients in synchronous generatorssynchronous generators

When a symmetrical 3-phase fault occurs at the terminals of a synchronous generator, the resulting current flow in the phases of the generator can appear as shown.The current can be represented as a transient DC component added on top of a symmetrical AC component.Therefore, while before the fault, only AC voltages and currents were present within the generator, immediately after the fault, both AC and DC currents are present.

Page 5: EE 340 Symmetrical Faultseebag/Symmetrical faults.pdf · AC and DC components just after the fault ... a symmetrical 3 phase fault occurs on that bus. 20 Fault current calculations

5

Fault current transients in machinesFault current transients in machines

When the fault occurs, the AC component When the fault occurs, the AC component of current jumps to a very large value, but of current jumps to a very large value, but the total current cannot change instantly the total current cannot change instantly since the series inductance of the machine since the series inductance of the machine will prevent this from happening. will prevent this from happening. The transient DC component of current is The transient DC component of current is just large enough such that the sum of the just large enough such that the sum of the AC and DC components just AC and DC components just afterafter the fault the fault equals the AC current just equals the AC current just beforebefore the fault. the fault. Since the instantaneous values of current Since the instantaneous values of current at the moment of the fault are different in at the moment of the fault are different in each phase, the magnitude of DC each phase, the magnitude of DC components will be different in different components will be different in different phases.phases.Th DC t d f i lTh DC t d f i l

Page 6: EE 340 Symmetrical Faultseebag/Symmetrical faults.pdf · AC and DC components just after the fault ... a symmetrical 3 phase fault occurs on that bus. 20 Fault current calculations

6

Symmetrical AC component of the fault current:Symmetrical AC component of the fault current:

There are three periods of time:There are three periods of time:SubSub--transient period: first cycle or so after the fault transient period: first cycle or so after the fault –– AC current is very AC current is very large and falls rapidly;large and falls rapidly;Transient period: current falls at a slower rate;Transient period: current falls at a slower rate;SteadySteady--state period: current reaches its steady value.state period: current reaches its steady value.

It is possible to determine the time constants for the subIt is possible to determine the time constants for the sub--transient transient and transient periods .and transient periods .

Page 7: EE 340 Symmetrical Faultseebag/Symmetrical faults.pdf · AC and DC components just after the fault ... a symmetrical 3 phase fault occurs on that bus. 20 Fault current calculations

7

Fault current transients in machinesFault current transients in machines

The AC current flowing in the generator during the subThe AC current flowing in the generator during the sub--transient period is called the subtransient period is called the sub--transient current and is transient current and is denoted by denoted by II””.. The time constantThe time constant of the subof the sub--transient current is transient current is denoted by denoted by TT”” and it can be determined from the slope. This and it can be determined from the slope. This current may be 10 times the steadycurrent may be 10 times the steady--state fault current.state fault current.The AC current flowing in the generator during the transient The AC current flowing in the generator during the transient period is called the transient current and is denoted by period is called the transient current and is denoted by II’’. The . The time constanttime constant of the transient current is denoted by of the transient current is denoted by TT’’. This . This current is often as much as 5 times the steadycurrent is often as much as 5 times the steady--state fault state fault current.current.After the transient period, the fault current reaches a steadyAfter the transient period, the fault current reaches a steady--state condition state condition IIssss. . This current is obtained by dividing the This current is obtained by dividing the induced voltage by the synchronous reactance:induced voltage by the synchronous reactance:

Ass

s

EIX

=

Page 8: EE 340 Symmetrical Faultseebag/Symmetrical faults.pdf · AC and DC components just after the fault ... a symmetrical 3 phase fault occurs on that bus. 20 Fault current calculations

8

Fault current transients in machinesFault current transients in machines

The The rmsrms magnitude of the AC fault current in a magnitude of the AC fault current in a synchronous generator varies over time assynchronous generator varies over time as

The subThe sub--transient and transient transient and transient reactancesreactances are defined as are defined as the ratio of the internal generated voltage to the subthe ratio of the internal generated voltage to the sub--transient and transient current components:transient and transient current components:

""AEX

I=

( ) ( ) ( )" '" ' 't T t Tss ssI t I I e I I e I− −= − + − +

''AEX

I=

s

As I

EX =

Page 9: EE 340 Symmetrical Faultseebag/Symmetrical faults.pdf · AC and DC components just after the fault ... a symmetrical 3 phase fault occurs on that bus. 20 Fault current calculations

9

Fault current transientsFault current transients

Example 12-1: A 100 MVA, 13.8 kV, Y-connected, 3 phase 60 Hz synchronous generator is operating at the rated voltage and no load when a 3 phase fault occurs at its terminals. Its reactances per unit to the machine’s own base are

1.00 ' 0.25 " 0.12sX X X= = =

and the time constants are

' 1.10 " 0.04T s T s= = The initial DC component in this machine averages 50 percent of the initial AC component.

a)What is the AC component of current in this generator the instant after the fault?

b)What is the total current (AC + DC) in the generator right after the fault occurs?

c)What will the AC component of the current be after 2 cycles? After 5 s?

Page 10: EE 340 Symmetrical Faultseebag/Symmetrical faults.pdf · AC and DC components just after the fault ... a symmetrical 3 phase fault occurs on that bus. 20 Fault current calculations

10

Fault current transientsFault current transients

The base current of the generator can be computed as

,,

100,000,000 4,1843 3 13,800

baseL base

L base

SI AV

= = = ⋅

The subtransient, transient, and steady-state currents are (per-unit and Amps)

1.0" 8.333 34,900" 0.12

1.0' 4 ,700' 0.25

1.0 1 4,1841.0

A

A

Ass

s

EI pu AXEI pu AXEI pu AX

= = = =

= = = = 16

= = = =

Page 11: EE 340 Symmetrical Faultseebag/Symmetrical faults.pdf · AC and DC components just after the fault ... a symmetrical 3 phase fault occurs on that bus. 20 Fault current calculations

11

Fault current transientsFault current transients

a) The initial AC component of current is I” = 34,900 A.

b) The total current (AC and DC) at the beginning of the fault is

1.5 " 52,350totI I A= = c) The AC component of current as a function of time is

( ) ( ) ( ) 0.04 1.1" '" ' ' 18,200 12,516 4,184t tt t

T Tss ssI t I I e I I e I e e A

− − − − = − + − + = ⋅ + ⋅ +

After 2 cycles t = 1/30 s and the total AC current is1 7,910 12,142 4,184 24,23630

I A⎛ ⎞ = + + = ⎜ ⎟⎝ ⎠

At 5 s, the current reduces to

( )5 0 133 4,184 4,317I A= + + =

Page 12: EE 340 Symmetrical Faultseebag/Symmetrical faults.pdf · AC and DC components just after the fault ... a symmetrical 3 phase fault occurs on that bus. 20 Fault current calculations

12

Fault current transientsFault current transients

Example 12-2: Two generators are connected in parallel to the low-voltage side of a transformer. Generators G1 and G2 are each rated at 50 MVA, 13.8 kV, with a subtransient resistance of 0.2 pu. Transformer T1 is rated at 100 MVA, 13.8/115 kV with a series reactance of 0.08 pu and negligible resistance.

Assume that initially the voltage on the high side of the transformer is 120 kV, that the transformer is unloaded, and that there are no circulating currents between the generators.

Calculate the subtransient fault current that will flow if a 3 phase fault occurs at the high-voltage side of transformer.

Page 13: EE 340 Symmetrical Faultseebag/Symmetrical faults.pdf · AC and DC components just after the fault ... a symmetrical 3 phase fault occurs on that bus. 20 Fault current calculations

13

Fault current transientsFault current transients

Let choose the per-unit base values for this power system to be 100 MVA and 115 kV at the high-voltage side and 13.8 kV at the low-voltage side of the transformer.

The subtransient reactance of the two generators to the system base is2

given newnew given

new given

V SZ ZV S

⎛ ⎞⎛ ⎞= ⎜ ⎟⎜ ⎟ ⎜ ⎟⎝ ⎠ ⎝ ⎠

The reactance of the transformer is already given on the system base, it will not change

2" "1 2

13,800 100,0000.2 0.413,800 50,000

X X pu⎛ ⎞ ⎛ ⎞= = ⋅ = ⎜ ⎟ ⎜ ⎟⎝ ⎠ ⎝ ⎠

0.08TX pu=

Therefore:

Page 14: EE 340 Symmetrical Faultseebag/Symmetrical faults.pdf · AC and DC components just after the fault ... a symmetrical 3 phase fault occurs on that bus. 20 Fault current calculations

14

Fault current transientsFault current transients

The per-unit voltage on the high-voltage side of the transformer is

120,000 1.044115,000pu

actual valueV pubase value

= = =

Since there is no load on the system, the voltage at the terminals of each generator, and the internal generated voltage of each generator must also be 1.044 pu. The per-phase per-unit equivalent circuit of the system is

We observe that the phases of internal generated voltages are arbitrarily chosen as 00. The phase angles of both voltages must be the same since the generators were working in parallel.

Page 15: EE 340 Symmetrical Faultseebag/Symmetrical faults.pdf · AC and DC components just after the fault ... a symmetrical 3 phase fault occurs on that bus. 20 Fault current calculations

15

Fault current transientsFault current transients

To find the subtransient fault current, we need to solve for the voltage at the bus 1 of the system. To find this voltage, we must convert first the per-unit impedances to admittances, and the voltage sources to equivalent current sources. The Thevenin impedance of each generator is ZTh = j0.4, so the short-circuit current of each generator is

1.044 0 2.61 9004

ocsc

th

VIZ j

∠ °= = = ∠ − °

The equivalent circuit

Page 16: EE 340 Symmetrical Faultseebag/Symmetrical faults.pdf · AC and DC components just after the fault ... a symmetrical 3 phase fault occurs on that bus. 20 Fault current calculations

16

Fault current transientsFault current transients

Then the node equation for voltage V1

( ) ( ) ( )1 1 1

1

2.5 2.5 12.5 2.61 90 2.61 905.22 90 0.298 0

17.5

V j V j V j

Vj

− + − + − = ∠ − ° + ∠ − °

∠ °= = ∠ °

−Therefore, the subtransient current in the fault is

( )1 12.5 3.729 90FI V j pu= − = ∠ − °

Since the base current at the high-voltage side of the transformer is3 ,

,

100,000,000 5023 3 115,000

basebase

LL base

SI A

Vφ= = =

, 3.729 502 1,872F F pu baseI I I A= = ⋅ =

the subtransient fault current will be

Page 17: EE 340 Symmetrical Faultseebag/Symmetrical faults.pdf · AC and DC components just after the fault ... a symmetrical 3 phase fault occurs on that bus. 20 Fault current calculations

17

Fault current calculations using the bus Fault current calculations using the bus impedance matriximpedance matrix

So far, we considered simple circuits. To So far, we considered simple circuits. To determine the fault current in a system:determine the fault current in a system:

Create a perCreate a per--phase perphase per--unit equivalent circuit of the power unit equivalent circuit of the power system using either subsystem using either sub--transient transient reactancesreactances (if (if subtransientsubtransientcurrents are needed) or transient currents are needed) or transient reactancesreactances (if transient (if transient currents are needed).currents are needed).Add a short circuit between one node of the equivalent circuit Add a short circuit between one node of the equivalent circuit and the neutral and calculate the current flow through that shorand the neutral and calculate the current flow through that short t by standard analysis.by standard analysis.

This approach always works but can get This approach always works but can get complex while dealing with complex complex while dealing with complex systems. Therefore, a nodal analysis systems. Therefore, a nodal analysis technique will be used.technique will be used.We introduce a new voltage sourceWe introduce a new voltage source in the in the system to represent the effects of a fault system to represent the effects of a fault at a bus. By solving for the currents at a bus. By solving for the currents i t d d b thi dditi l lti t d d b thi dditi l lt

Page 18: EE 340 Symmetrical Faultseebag/Symmetrical faults.pdf · AC and DC components just after the fault ... a symmetrical 3 phase fault occurs on that bus. 20 Fault current calculations

18

Fault current calculations using the Fault current calculations using the impedance matriximpedance matrix

Let us consider a power system shown.

Assuming that we need to find the sub-transient fault current at some node in the system, we need to create a per-phase, per-unit equivalent circuit using sub-transient reactancesX”. Additionally, we assume that the system is initially unloaded, making the voltages behind sub-transient reactances

1

2

"

"

1 0

1 0A

A

E pu

E pu

= ∠ °

= ∠ °

Page 19: EE 340 Symmetrical Faultseebag/Symmetrical faults.pdf · AC and DC components just after the fault ... a symmetrical 3 phase fault occurs on that bus. 20 Fault current calculations

19

Fault current calculations using the Fault current calculations using the impedance matriximpedance matrix

The resulting equivalent circuit is shown.

Suppose that we need to determine the sub-transient fault current at bus 2 when a symmetrical 3 phase fault occurs on that bus.

Page 20: EE 340 Symmetrical Faultseebag/Symmetrical faults.pdf · AC and DC components just after the fault ... a symmetrical 3 phase fault occurs on that bus. 20 Fault current calculations

20

Fault current calculations using the Fault current calculations using the impedance matriximpedance matrix

Before the fault, the voltage on bus 2 was Vf. If we introduce a voltage source of value Vf between bus 2 and the neutral, nothing will change in the system.

Since the system operates normally before the fault, there will be no current If” through that source.

Page 21: EE 340 Symmetrical Faultseebag/Symmetrical faults.pdf · AC and DC components just after the fault ... a symmetrical 3 phase fault occurs on that bus. 20 Fault current calculations

21

Fault current calculations using the Fault current calculations using the impedance matriximpedance matrix

Assume that we create a short circuit on bus 2, which forces the voltage on bus 2 to 0. This is the same as inserting an additional voltage source of value -Vf in series with the existing voltage source. This make the total voltage at bus 2 equal to 0.

With this additional voltage source, there will be a fault current If”, which is entirely due to the insertion of the new voltage source to the system. Therefore, we can use superposition to analyze the effects of the new voltage source on the system.

The resulting current If” will be the current for the entire power system, since the other sources in the system produced a net zero current.

Page 22: EE 340 Symmetrical Faultseebag/Symmetrical faults.pdf · AC and DC components just after the fault ... a symmetrical 3 phase fault occurs on that bus. 20 Fault current calculations

22

Fault current calculations using the Fault current calculations using the impedance matriximpedance matrix

If all voltage sources except –Vf” are set to zero and the impedances are converted to admittances, the power system appears as shown.

For this system, we can construct the bus admittance matrix as discussed previously:

16.212 5.0 0 6.6675.0 12.5 5.0 2.50 5.0 13.333 5.0

6.667 2.5 5.0 14.167

bus

j j jj j j j

Yj j j

j j j j

−⎡ ⎤⎢ ⎥−⎢ ⎥=⎢ ⎥−⎢ ⎥−⎣ ⎦

The nodal equation describing this power system is

busY V = I

Page 23: EE 340 Symmetrical Faultseebag/Symmetrical faults.pdf · AC and DC components just after the fault ... a symmetrical 3 phase fault occurs on that bus. 20 Fault current calculations

23

Fault current calculations using the Fault current calculations using the impedance matriximpedance matrix

With all other voltage sources set to zero, the voltage at bus 2 is –Vf, and the current entering the bus 2 is –If”. Therefore, the nodal equation becomes

11 12 13 14 1"

21 22 23 24

31 32 33 34 3

41 42 43 44 4

0

00

f f

Y Y Y Y VY Y Y Y V IY Y Y Y VY Y Y Y V

Δ⎡ ⎤ ⎡ ⎤ ⎡ ⎤⎢ ⎥ ⎢ ⎥ ⎢ ⎥− −⎢ ⎥ ⎢ ⎥ ⎢ ⎥=⎢ ⎥ ⎢ ⎥ ⎢ ⎥Δ⎢ ⎥ ⎢ ⎥ ⎢ ⎥Δ ⎣ ⎦⎣ ⎦⎣ ⎦

where ΔV1, ΔV3, and ΔV4 are the changes in the voltages at those busses due to the current –If” injected at bus 2 by the fault.

The solution to is found as-1bus busV = Y I = Z I

Page 24: EE 340 Symmetrical Faultseebag/Symmetrical faults.pdf · AC and DC components just after the fault ... a symmetrical 3 phase fault occurs on that bus. 20 Fault current calculations

24

Fault current calculations using the Fault current calculations using the impedance matriximpedance matrix

11 12 13 141"

21 22 23 24

31 32 33 343

41 42 43 444

0

00

f f

Z Z Z ZVZ Z Z ZV IZ Z Z ZVZ Z Z ZV

Δ ⎡ ⎤⎡ ⎤ ⎡ ⎤⎢ ⎥⎢ ⎥ ⎢ ⎥− −⎢ ⎥⎢ ⎥ ⎢ ⎥=⎢ ⎥⎢ ⎥ ⎢ ⎥Δ⎢ ⎥⎢ ⎥ ⎢ ⎥Δ ⎣ ⎦⎣ ⎦ ⎣ ⎦

where Zbus = Ybus-1. Since only bus 2 has current injected at it, the

system reduces to

"

"1 12

"3 32

"

2

4

2

42

Which, in the case considered, is

f

f

f

f f

V Z I

V Z I

V

I

Z I

V Z

= −

= −

= −

− = −

Page 25: EE 340 Symmetrical Faultseebag/Symmetrical faults.pdf · AC and DC components just after the fault ... a symmetrical 3 phase fault occurs on that bus. 20 Fault current calculations

25

Fault current calculations using the Fault current calculations using the impedance matriximpedance matrix

Therefore, the fault current at bus 2 is just the prefault voltage Vf at bus 2 divided by Z22, the driving point impedance at bus 2.

"

22

ff

VI

Z=

The voltage differences at each of the nodes due to the fault current can be calculated by

" 121 12

22

2

" 323 32

22

" 424 42

22

f f

f f

f f

f f

ZV Z I VZ

V V V

ZV Z I VZZV Z I VZ

= − = −

= − = −

= − = −

= − = −

Page 26: EE 340 Symmetrical Faultseebag/Symmetrical faults.pdf · AC and DC components just after the fault ... a symmetrical 3 phase fault occurs on that bus. 20 Fault current calculations

26

Fault current calculations using the ZFault current calculations using the Z--bus matrixbus matrixAssuming that the power system was running at no load conditionsbefore the fault, it is easy to calculate the voltages at every bus during the fault. At no load, the voltage will be the same on every bus in the power system, so the voltage on every bus in the system is Vf. The change in voltage on every bus caused by the fault current–If” is specified , so the total voltage during the fault is

12

22

12

221

232

322

4

1

232

322

44 42

22

2

22

1

0

1

1

f

f ff

f f

ff f

f f

f

f

Z VZ

V VVVV VV

Z VV VVZ

V

ZZ

VV

VZV

ZV

ZZ

VVZ VZ

⎡ ⎤−⎢ ⎥⎢ ⎥Δ⎡ ⎤ ⎡ ⎤⎡ ⎤

−⎢ ⎥⎢ ⎥ ⎢ ⎥⎢ ⎥Δ ⎢ ⎥⎢ ⎥ ⎢ ⎥⎢ ⎥=

⎡ ⎤−⎢ ⎥⎢ ⎥⎡ ⎤⎢ ⎥⎢ ⎥⎢ ⎥⎢ ⎥ = ⎢ ⎥−⎢ ⎥⎢ ⎥⎢ ⎥⎢ ⎥⎣ ⎦⎢ ⎥−⎢ ⎥⎣

+ = + ⎢ ⎥⎢ ⎥ ⎢ ⎥ −⎢ ⎥Δ⎢ ⎥⎢ ⎥ ⎢ ⎥⎢ ⎥Δ ⎢ ⎥⎢ ⎥ ⎢ ⎥⎣ ⎦⎣ ⎦ ⎣ ⎦⎢ ⎥−⎢ ⎥⎣ ⎦ ⎦

Therefore, we can calculate the voltage at every bus in the power system during the fault from a knowledge of the pre-fault voltage at the faulted bus and the bus impedance matrix!

Page 27: EE 340 Symmetrical Faultseebag/Symmetrical faults.pdf · AC and DC components just after the fault ... a symmetrical 3 phase fault occurs on that bus. 20 Fault current calculations

27

Fault current calculations using the ZFault current calculations using the Z--bus matrixbus matrixOnce these bus voltages are known, we can calculate the fault Once these bus voltages are known, we can calculate the fault current flowing in the transmission line using bus voltages and current flowing in the transmission line using bus voltages and the bus admittance matrix.the bus admittance matrix.The general procedure for finding the bus voltages and line The general procedure for finding the bus voltages and line currents during a symmetrical 3 phase fault is as follows:currents during a symmetrical 3 phase fault is as follows:

Create a perCreate a per--unit equivalent circuit of the power system. Include unit equivalent circuit of the power system. Include subtransientsubtransient reactancesreactances of each synchronous and induction of each synchronous and induction machine when looking for machine when looking for subtransientsubtransient fault currents; include fault currents; include transient transient reactancesreactances of each synchronous machine when looking of each synchronous machine when looking for transient fault currents.for transient fault currents.Calculate the bus admittance matrix. Include the admittances of Calculate the bus admittance matrix. Include the admittances of all transmission lines, transformers, etc. between busses includall transmission lines, transformers, etc. between busses including ing the admittances of the loads or generators themselves at each the admittances of the loads or generators themselves at each bus.bus.Calculate the bus impedance matrix Calculate the bus impedance matrix ZbusZbus as inverse of the bus as inverse of the bus admittance matrix.admittance matrix.Assume that the power system is at no load and determine the Assume that the power system is at no load and determine the voltage at every bus, which will be the same for every bus and tvoltage at every bus, which will be the same for every bus and the he same as the internal voltage of the generators in the system. Thsame as the internal voltage of the generators in the system. This is is the preis the pre--fault voltage fault voltage VfVf..

Page 28: EE 340 Symmetrical Faultseebag/Symmetrical faults.pdf · AC and DC components just after the fault ... a symmetrical 3 phase fault occurs on that bus. 20 Fault current calculations

28

Fault current calculations using the ZFault current calculations using the Z--bus matrixbus matrix

5. Calculate the current at the faulted bus i as

",

ff i

ii

VI

Z=

6. Calculate the voltages at each bus during the fault. The voltage at bus j during a symmetrical 3 phase fault at the bus i is found as

1 jij f

ii

ZV V

Z⎛ ⎞

= −⎜ ⎟⎝ ⎠

7. Calculate the currents in any desired transmission line during the fault. The current through a line between bus i and bus j is found as

( )ij ij i jI Y V V= − −

Page 29: EE 340 Symmetrical Faultseebag/Symmetrical faults.pdf · AC and DC components just after the fault ... a symmetrical 3 phase fault occurs on that bus. 20 Fault current calculations

29

Fault current calculations using the ZFault current calculations using the Z--bus matrixbus matrix

•Example 12-4: The previous power system is working at no load when a symmetrical 3 phase fault is developed on bus 2. a) Calculate the per-unit subtransient fault current If” at bus 2. b) Calculate the per-unit voltage at every bus in the system during the subtransient period. c) Calculate the per-unit current I1 flowing in line 1 during the subtransient period of the fault.

Following the 7 steps discussed before, we write:

1.The per-phase per-unit equivalent circuit was shown earlier.

2.The bus admittance matrix was previously calculated as

16.212 5.0 0 6.6675.0 12.5 5.0 2.50 5.0 13.333 5.0

6.667 2.5 5.0 14.167

bus

j j jj j j j

Yj j j

j j j j

−⎡ ⎤⎢ ⎥−⎢ ⎥=⎢ ⎥−⎢ ⎥−⎣ ⎦

Page 30: EE 340 Symmetrical Faultseebag/Symmetrical faults.pdf · AC and DC components just after the fault ... a symmetrical 3 phase fault occurs on that bus. 20 Fault current calculations

30

Fault current calculations using the ZFault current calculations using the Z--bus matrixbus matrix

3. The bus impedance matrix calculated using Matlab as the inverse of Ybus is

0 0.1515 0 0.1232 0 0.0934 0 0.12600 0.1232 0 0.2104 0 0.1321 0 0.14170 0.0934 0 0.1321 0 0.1726 0 0.12820 0.1260 0 0.1417 0 0.1282 0 0.2001

bus

j j j jj j j j

Zj j j jj j j j

+ + + +⎡ ⎤⎢ ⎥+ + + +⎢ ⎥=⎢ ⎥+ + + +⎢ ⎥+ + + +⎣ ⎦

4. For the given power system, the no-load voltage at every bus is equal to the pre-fault voltage at the bus that is

1.00 0fV pu= ∠ °

5. The current at the faulted bus is computed as

",2

22

1.00 0 4.753 900.2104

ff

VI pu

Z j∠ °

= = = ∠ − °

Page 31: EE 340 Symmetrical Faultseebag/Symmetrical faults.pdf · AC and DC components just after the fault ... a symmetrical 3 phase fault occurs on that bus. 20 Fault current calculations

31

Fault current calculations using the ZFault current calculations using the Z--bus matrixbus matrix

6. The voltage at bus j during a symmetrical 3 phase fault at bus Ican be found as

121

22

2

323

22

424

22

0.12321 1 1.0 0 0.414 00.2104

0.0 0

0.13211 1 1.0 0 0.372 00.2104

0.14171 1 1.0 0 0.327 00.2104

f

f

f

Z jV V puZ j

V pu

Z jV V puZ j

Z jV V puZ j

⎛ ⎞ ⎛ ⎞= − = − ⋅ ∠ ° = ∠ ° ⎜ ⎟ ⎜ ⎟

⎝ ⎠⎝ ⎠= ∠ °

⎛ ⎞ ⎛ ⎞= − = − ⋅ ∠ ° = ∠ ° ⎜ ⎟ ⎜ ⎟

⎝ ⎠⎝ ⎠⎛ ⎞ ⎛ ⎞

= − = − ⋅ ∠ ° = ∠ ° ⎜ ⎟ ⎜ ⎟⎝ ⎠⎝ ⎠

7. The current through the transmission line 1 is computed as

( ) ( )12 12 1 2 0.414 0 0.0 0 5.0 2.07 90I Y V V j pu= − − = ∠ ° − ∠ ° ⋅ = ∠ °

That’s it!