alternator e1x13m d/2 - linz electric
TRANSCRIPT
ALTERNATOR E1X13M D/2
three-phase brushless synchronous alternator with AVR - 2 poles
Technical Data Sheet
Document: E1X13M D-2
Date: 12/11/2014
COMMON DATA
kVA
kVA
°C
rpm
REGULATION DATA
Rated Power at 50Hz
Sustained Short Circuit
Protection
Maximum Overspeed
Rated Power Factor
Regulation Type
Insulation Class
Sensing
Voltage Regulation
brushless
AVR
H
Control System
Execution
R.F.I. Suppression
E1X13M D/2
16
Air Flow Requirement m3/min
110% of rated power for one hour in a cycle of 6 hours
Rated Power at 60Hz 19.5
40
0.8
self excited
Nominal Temperature
Overload
IP21
4500
9.6 at 60Hz8 at 50Hz
AVR
Standard EN55011
HVR11
single-phase
HVR30
three-phase
±1% ±1%
> 300% of rated current
2/7
WINDING DATA
Adc
Adc
STANDARD
16.5 at 20°C
1.06
EN60034-1 ISO8528-3 EN55011
<3%
Exciter Stator Resistance
Exciter Rotor Resistance
THD at full load
Excitation at full load
2.15 at 20°C
<3%
12 at 20°C
THD at no load
Excitation at no load
Rotor Winding Resistance
12Number of Leads of Stator
with damping cage
Stator Winding Resistance
Rotor Winding
0.43 at 20°C
2/3
Double layer with auxiliary windingStator Winding
Winding Pitch
References
0.14
2/7
Document: E1X13M D-2
Date: 12/11/2014
ELECTRICAL DATA
V
kVA
kW
kVA
kW
kVA
kW
kVA
kW
EFFICIENCY IN CL. H
REACTANCES AND TIME CONSTANTS
14.4
12.8
21
17.6
14.7Rated Power in Class F
(105°C/40°C) 9.6 12.4 14.413.92
16.4
17.6
14.7 12
11.04
15.2
15.5
14.4 13.6
13.8 18.2
19
14.7 17.4
11.76 11.76 11.76
17.4
18
85.5%4/4
11.36
17.4 17.4
14.4
21Rated Power Standby
(150°C/40°C)
Rated Power Standby
(163°C/27°C)
16.8
18 18 17 14.2
16.8
14.56
21
13.92 13.92 13.92
415/240 440/254
60Hz - 3600rpm
380/220 400/230 415/240
50Hz - 3000rpm
460/266 480/277
E1X13M D/2
Voltage Series Star
Frequency
Rated Power in Class H
(125°C/40°C) 15.6 15.6
19.5 19.516 13 17 19
12.8
16 16
12.8 10.4 13.6 15.2
440/254
18
16.8
2222
20.5
1/4
85.3%3/4
2/4
77.3%
85.0%
81.6% 80.2%
76.3%
85.7%
3/7
Xd
X'd
X''d
Xq
T'do
T'dT''d
MECHANICAL DATA
kg
kg
kg
in B2
in B3/B14
ρcc 0.42
- dir. axis synchronous
- dir. axis transient
- dir. axis subtransient
- quad. axis reactance 230%
30.0%
259% 449% 446%427% 385% 358%
6.7% 11.7%
230%
419% 385%
33.2% 30.0% 27.9% 20.1% 35.0% 34.8% 32.7%
10.9% 10.0%
255% 250%
11.1% 10.0% 9.3% 11.6%
214% 154% 268% 267%
Weight of
generatorin B3/B9 \
- O.C. field time constant
- Transient time constant
- Sub-transient time constant 8.8ms
30ms
390ms
6305-2Z-C3Bearing non drive end
Bearing drive end (B3/B14 form) 6208-2Z-C3
90
85.9
3/7
Document: E1X13M D-2
Date: 12/11/2014
MOMENT OF INERZIA
kg·m2
kg·m2
kg·m2
POWER VARIATION ACCORDING TO TEMPERATURE AND ALTITUDE
WIRING DIAGRAM
Ambient temperature
0.85 0.81 0.78 0.76
< 1000m 1.09 1 0.96 0.93 0.91
0.87 0.84 0.83
2000m - 3000m 0.9
0.081B2
55°C
1000m - 1500m 1.01 0.96 0.92 0.89 0.87
Altitude 25°C 40°C 45°C 50°C
1500m - 2000m 0.96 0.91
SAE 7½
B3/B9 \
E1X13M D/2
0.088
4/74/7
Document: E1X13M D-2
Date: 12/11/2014
TRANSIENT VOLTAGE VARIATION 50Hz
TRANSIENT VOLTAGE VARIATION 60Hz
E1X13M D/2
0
5
10
15
20
25
30
35
0 5 10 15 20 25 30 35
Vo
lta
ge
dip
%
Load [kVA]
Transient Voltage Variation @ 50Hz
P.F. 0
P.F. 0.8
P.F. 1
30
Transient Voltage Variation @ 60Hz
5/7
0
5
10
15
20
25
30
0 10 20 30 40 50
Vo
lta
ge
dip
%
Load [kVA]
Transient Voltage Variation @ 60Hz
P.F. 0
P.F. 0.8
P.F. 1
5/7
Document: E1X13M D-2
Date: 12/11/2014
EFFICIENCY 50Hz
EFFICIENCY 60Hz
E1X13M D/2
85.0%85.3%
81.6%
77.3%
88.2%88.4%
85.4%
81.8%
76.0%
78.0%
80.0%
82.0%
84.0%
86.0%
88.0%
90.0%
0 5 10 15 20
Eff
icie
ncy
%
Load [kVA]
Three Phase Efficiency Curves @ 50Hz
P.F. 0.8
P.F. 1
88.6%88.7%
84.2%85.0%
90.0%
Eff
icie
ncy
%
Three Phase Efficiency Curves @ 60Hz
6/7
85.5%85.7%
80.2%
76.3%
84.2%
80.9%
75.0%
80.0%
85.0%
0 5 10 15 20 25
Eff
icie
ncy
%
Load [kVA]
P.F. 0.8
P.F. 1
6/7
Document: E1X13M D-2
Date: 12/11/2014
E1X13M D/2
7/7
Linz Electric S.p.a. Viale del lavoro, 30 – 37040 Arcole (VR) Italy – T +39 045 763 92 01 – F +39 045 763 92 02
[email protected] – www.linzelectric.com
7/7