alphagaz clma1

22
ALPHAGAZ ML - ML1 - CLSA1 User Manual www.airliquide.com

Upload: mpica

Post on 15-Nov-2015

372 views

Category:

Documents


44 download

DESCRIPTION

Estaciones de gases Alphagaz. Airliquid

TRANSCRIPT

  • ALPHAGAZ ML - ML1 - CLSA1

    User Manualwww.airliquide.com

  • EN

    OP 206 ML-ML1-CLSA1 08/2013 v.1.0 1

    WarningTo preserve the quality of our product throughout its usage in the best safety conditions, please read this manual carefully and strictly follow the instructionsthat it contains. Non-compliance with these instructions or modification of the product may result in serious accidents or bodily injuries. AIR LIQUIDEshall not be held responsible in case of non approved usage of the product.Air Liquide reserves the right to make all necessary modifications to the specifications described hereafter without notice.

  • OP 206 ML-ML1-CLSA1 08/2013 v.1.0

    ML1300-16-8

    ML1300-10-50

    ML200-200-30

    CLSA1

  • EN

    OP 206 ML-ML1-CLSA1 08/2013 v.1.0 3

    Contents

    1. Domain of usage and Characteristics............................. 41.1 Functions..............................................................................................41.2 Technical characteristics....................................................................... 41.3 Gas compatibiliy table.......................................................................... 4

    2. AIR LIQUIDE commitments............................................ 72.1 Conformity ...........................................................................................72.2 Cleaning .............................................................................................. 72.3 Inspections ..........................................................................................72.4 Warranty ..............................................................................................7

    3. Assembly - Activation.................................................... 83.1 Safety................................................................................................... 83.2 Precautions before assembly................................................................83.3 Assembly..............................................................................................83.4 Options.................................................................................................93.5 Checking the tightness of connections................................................. 93.6 Activation............................................................................................10

    4. Usage...........................................................................114.1 Use.....................................................................................................114.2 Cylinders or Bundles change .............................................................114.3 After use.............................................................................................11

    5. Maintenance.................................................................125.1 Troubleshooting.................................................................................. 125.2 Maintenance....................................................................................... 135.3 Spare parts.........................................................................................14

  • OP 206 ML-ML1-CLSA1 08/2013 v.1.04

    1. Domain of usage and Characteristics

    1.1 Functions

    The ML1 & CLSA1 gas manifolds are used to:

    connect one or several cylinders or bundles topipe network,

    reduce a high-pressure conditioned gas (200 or300 bar at 15C) in cylinder or bundle.

    ModelConnection on

    Cylinders / BundlesContinued

    supply

    Continuouslycylinderschange

    Adjustableoutlet

    pressure

    Gas panel ML - ML1 1x1 1x2 no no yes

    Automatic changeover with reset

    CLSA 1 2x1 2x2 yes yes no

    The operation of the CLSA1 automatic change-over with reset is based on the assembly of twoopposing pressure regulators connected to twogas sources and adjusted to obtain a slightlydifferent pressure between the pressure regulatorinto operation and pressure regulator in the reserve.Since these two reducers have a commonoutlet, only the regulator set to the higher

    pressure delivers gas to flow. When the source inservice is nearing exhaustion, the pressure dropcauses the commissioning of the second regulatorautomatically.The technician operates to switch the lever towardsthe new source to restore full operating pressure(hence the term "automatic with reset "), and thento replace the empty cylinders or bundles.

    1.2 Technical characteristics

    Operating temperature : -20C to + 50C

    Leakage rate (Int/Ext.) : < 10-7 mbar.l/s helium.

    1.3 Gas compatibiliy table

    The gas manifold are mainly designed for theimplementation of pure gases and mixtures withpurity < N50 thus ALPHAGAZ 1.

    IMPERATIVE: check the gasescompatibility of this equipment byreferring to the "Gas CompatibilityTable".

    Legend :Suitable up to a working pressure of XXXbar at 15C.Not suitable.

    * 1,013 bar at 15C, according to ISO 2503P1 Inlet = 2(P2 Outlet) + 1 bar

  • EN

    OP 206 ML-ML1-CLSA1 08/2013 v.1.0 5

    Par

    amet

    ers

    Mai

    n g

    ases

    :

    Outlet pressure(bar)

    Pressure of gasin reserve supply

    (bar)

    Nominal nitrogenflow rate*(Nm3/h)

    Calibration of reliefvalve (Bar)

    Inerts, Nitrogen

    CO2**

    CO

    Breathable air

    Air

    Oxygen

    Nitrous oxide

    Hydrogen

    Acetylene

    Propane

    Propylene

    Ethylene

    Methane

    Ammonia

    Fo

    r b

    reat

    hab

    le o

    xyg

    en, c

    orr

    osi

    ve g

    ases

    , oth

    er g

    ases

    and

    mix

    ture

    s : P

    leas

    e co

    ntac

    t A

    IR L

    IQU

    IDE

    .M

    L -

    ML1

    Gas

    pan

    els

    ML1

    300

    -16

    -8

    168

    30

    050

    300

    300

    4430

    0

    ML1

    300

    -10

    -50

    1050

    30

    050

    300

    300

    4430

    0

    ML

    200-

    200-

    3020

    030

    20

    050

    200

    200

    4420

    0

    CLS

    A1

    Sem

    i-au

    tom

    atic

    cha

    nge

    ove

    rsC

    LSA

    1 20

    0-10

    -10

    10

    1015

    200

    50

    200

    200

    4420

    0

    CLS

    A1

    200-

    10-

    5010

    5015

    200

    5020

    020

    044

    200

    CLS

    A1

    200-

    20-

    5020

    50

    25

    200

    5020

    020

    044

    20

    0

  • OP 206 ML-ML1-CLSA1 08/2013 v.1.06

    Material in contact with gas :

    CLSA1CLSA1

    200-10-10CLSA1

    200-10-50CLSA1

    200-20-50

    Valve block / Purge Regulators

    Body Nickel Plated Brass Nickel Plated Brass

    Seat PTFCE Brass

    Valve / SpringBrass / PA

    Brass / SS 301 Brass + PTFCE / SS

    Diaphragm SS 304 Hastelloy

    Piston

    Filter Bronze Monel Bronze

    Pressure gauge Copper Alloy Copper Alloy

    Relief valve SS / NBR Brass / NBR

    Seal EPDM / PA 6.6 EPDM / PA 6.6 / PTFCE

    ML/ML1 ML1 300-16-8 ML1 300-10-50 ML 200-200-30

    Valve block / Purge Regulators

    BodyNickel Plated Brass Nickel Plated Brass

    ChroniumPlated Brass

    Seat PTFCE Brass

    Valve / Spring Brass / PABrass / Bronze

    BrassPTFCE / Bronze

    Brass PTFCE

    Diaphragm Hastelloy

    Piston SS

    Filter Bronze Monel Bronze

    Pressure gauge Copper Alloy Copper Alloy

    Relief valve Brass / NBR Brass / NBR Brass / NBR

    Seal EPDM / PA 6.6 EPDM / PA 6.6

    NBR / PTFCE /Copper

    Seat diameter :

    ModelsSeat diameter

    (Equivalentdiameter in mm)

    ModelsSeat diameter

    (Equivalentdiameter in mm)

    ML1 300-16-8 1,73 CLSA1 200-10-10 1,73

    ML1 300-10-50 3,57 CLSA1 200-10-50 4,67

    ML 200-200-30 1,73 CLSA1 200-20-50 4,67

  • EN

    OP 206 ML-ML1-CLSA1 08/2013 v.1.0 7

    2. AIR LIQUIDE commitments

    2.1 Conformity

    AIR LIQUIDE certifies that the equipment ismanufactured, tested and controlled, in accordancewith the technical specifications described in thespecifications of AIR LIQUIDE.In addition to technical specifications, a degreasingprocess consistant with oxygen service is applied.It is the responsibility of the end user to ensurethat such equipment are installed and used inaccordance with the current regulations.

    2.1.1 Directive 97/23/EC: Pressurisedequipment (PED)

    AIR LIQUIDE equipment of DN < 25 (e.g. pressureregulators, valves, non return valves) satisfy torequirement of article 33 of 97/23/EC directiveand at the state of the art. Consequently, theseequipments shall not be "CE" marked as definedin article 15.By design, these equipment may integrate pressurerelief valves or burst disks. In this case, those onesshall neither be CE marked according to paragraph2 of annex II.In other case, pressure relief valves and burst disksshall be CE marked.

    2.1.2 Directive 94/9/EC ATEX: Explosiveatmospheres

    The ML, ML1 & CLSA1 gas manifolds do nothave their own source of ignition. Consequently,they are excluded from field of application of theATEX 94/9/CE directive and shall not be CEmarked.They can be used in zone 2, according to ATEX1999/92/EC pending on up to date regulations,rules, operating instruction and state of the art arefollowed during installation and use.Every installation including one of those equipmentsin ATEX zone shall comply to the ATEX directive andbe certified. Remark: It belongs to the end user todefine the ATEX zone.

    2.2 Cleaning

    Each equipment is subject to a grease removal anda high quality cleaning to preserve the purity of gasin the equipment as well as for use with oxygen incompatible equipment.A suitable packaging protects the equipmentagainst exterior pollutions during storage andtransport.Take care to avoid polluting the equipmentduring usage.

    2.3 Inspections

    Each equipment is inspected and has undergonea leak test (with helium) before packing.

    2.4 Warranty

    The warranty period for equipment supplied by AIRLIQUIDE is one year, covering faulty material andworkmanship during manufacture. The warrantydoes not cover packing and return transport costs.Excluded from warranty: seals and relief valves.These components are subjected to a natural wear.Warranty is not valid on deterioration resulting fromincorrect or improper use, use of spare parts whichare not marked AIR LIQUIDE or from the nonerespect of this operating instruction.For more information, refer to the general salesconditions of AIR LIQUIDE.

  • OP 206 ML-ML1-CLSA1 08/2013 v.1.08

    3. Assembly - Activation

    3.1 Safety

    First of all, read and respectIMPERATIVELY the safety instructionsdescribed in the document GeneralSafety Instructions delivered with theproduct.

    3.2 Precautions before assembly

    After opening the packaging, check that theequipment is not damaged and that the contentscorrespond to the delivery notes accompanying theequipment. During assembly, it is important to take extreme

    care to ensure cleanliness and avoid pollution. To install the equipment, select a ventilated area,

    protected from the effects of bad weather.

    3.3 Assembly

    3.3.1 Assembly of the gas manifold

    Set the manifold (see drawing) The surface on which the manifold will be mounted,must be flat. Any deformation of the plate couldaffect the proper operation of the equipment. Depending of the case, mount and connect the

    extension ramps (Options) Fix the racks (in case of cylinder use). Attach the panels "Cylinders/bundles change

    procedure" and the "Safety precautions"corresponding to the gas used. They have to bevisible and in close range.

    Mount the anti-flapping connectors. Warning!They must be imperatively mounted in a verticalposition. Unused ports must be sealed with blindplugs provided for that purpose.

    Place the cylinders in their racks with their safetychains.

    Connect the flexible hoses or pigtails as specifiedin their operating instructions.

    Attach the safety cables. Use the holes for thatpurpose on the manifold. In case of bundles,attach the anchor cable to a solid anchor point.

    In case of CLSA1 used with hydrogen or Helium,install at the outlet the calibrated orifice adaptedto the gas used and delivered with the equipment.

    Connect the outlet of the manifold to the pipenetwork.

    Install a shut-off valve between the manifold andthe pipeline:-At a distance equal to 20 x internal diameter of

    the pipe when used with breathable air. CheckThe compatibility of the seals.

    -EFP9 shut-off valve for oxygen (> 20 bar) andhydrogen use

    If continuous supply is required, even during themaintenance, install back up cross downstreamthe manifold

    If necessary, collect the purges and the reliefvalve (particularly for the combustible gases) andconnect them to exhaust pipes to secure theinstallation. Height > 2,5m.

    In case of combustible gases, connect the manifoldto the ground and check the electrical continuitybetween the different components.

    3.3.2 Assembly of a compression fitting

    Check dimensions and respect materialcompatibility between connection and pipe :Connection and pipe must always be made from thesame material, example: Stainless steel connectionfor stainless steel pipe < Rockwell hardness B90(exception : brass connection with copper pipe).

  • EN

    OP 206 ML-ML1-CLSA1 08/2013 v.1.0 9

    Connector pre-assembled by hand. After cutting, de-burring and blowing on the tube

    (use preferably a tube cutter), pre assemble thenut and the ferrules, following the order and thedirection indicated in the figure.

    Introduce the tube inside the connector up to thestop limit on the body.

    Clamp the nut completely by hand. Complete the clamping using a wrench by turning

    the nut at a 1 1/4 turn.

    3.4 Options

    To choose the appropriate option, pleaseconsult the AIR LIQUIDE "Product sheet" inmyCatalogue.

    For the options assembly, refer to Assembly - Activation chapter of the operating instructions delivered with the options.

    3.5 Checking the tightness ofconnections

    Even though the different components of theequipment have been carefully checked in thefactory, it is nevertheless necessary to make averification of the sealing of the mounted assemblybefore commissioning .

    -Close the outlet valve.-Verify that the HP shut-off valves (2) and the

    purge valves (3) are closed.-Open and then close gradually all valves of

    cylinders or bundles (1). The cylinder pressureis read on the high pressure gauges (5).

    -Verify that the value indicated on the highpressure gauge does not vary over a sufficientlylong period. Otherwise, there is leakage ona connection. Identify it by using a leakdetector such as the Mille Bulles from AIR

    LIQUIDE. After locating the leakage, purge theinstallation, check the state of seals and of theseats of seals, and retighten the connectorsagain.

    Always turn valves GRADUALLY.Never retighten a fitting under gaspressure.

    In the same way, during the pressurization of theinstallation, check also the tightness of the outputconnections.

  • OP 206 ML-ML1-CLSA1 08/2013 v.1.010

    3.6 Activation

    Never use the purge valves to purgethe pipeline connected downstreamof the gas manifold (risk polluting theregulators).

    3.6.1 1st stage: Flexible hoses purging.

    Initial stage: Closed HP shut-off valves (2) and purge valves

    (3). Closed low-pressure outlet shut-off valve.Purge all flexible hoses or pigtails, by at leastof 3 compressions-reductions cycles, ie: openthe cylinder/bundle valves (1) and close it beforereaching the pressure of the cylinder (high pressuregauge (5)), wait 1 minute, slowly open the purgevalve (3) and then close it before falling toatmospheric pressure.

    3.6.2 2nd stage: function control

    Initial stage: Closed cylinder/bundle valves, Closed HP shut-off valves (2) and purge valves (3) Closed low pressure outlet shut-off valve.Indicate the main gas source to use first by usingthe lever (4). (In case of CLSA1): On the right: lever downwards On the left: lever upwards Slowly open all cylinder/bundle valves (1). Slowly open the HP shut-off valves (2) on the mainsource.Note the outlet pressure of the low pressure gauge(6). Adjust the pressure with the handwheel (exceptCLSA1: not adjustable).

    Slowly open the HP shut-off valve on the 2nd gassource (In case of CLSA1).Slowly open the outlet shut-off valve.Let the gas flow normally through the manifold andpurge all pipes.Limit the outlet flow during the filling of the pipenetwork to avoid vibrations. Respect the nominalflow.

    If necessary, adjuste the outlet pressure (Except withCLSA1: non-adjustable).

    3.6.3 3rd stage: verification of theautomatic switchover (In case of CLSA1only)

    Close the cylinder/bundle valves of the main gassource in service, the high pressure gauge (5)decreases.When the HP pressure falls below 2 times theworking pressure, the source in reserve must entergradually in service. The LP pressure gauge (6)indicates the pressure of the gas source in reserve.Change the position of the lever, the initial outletpressure is now restored. The previous gas sourcein reserve becames the main gas source inservice.Repeat in reverse the operation, to check that theautomatic switchover works well in both directions.Remark: if during the switchover, the pressuredifference "deltaP" is too disturbing for the user, itis recommended to install one 2nd stage pressureregulator at the outlet.

    3.6.4 4th stage: setting in flow

    The tested equipment is now ready to use.Slowly open the shut-off valve at the outlet.In the case of the CLSA1, when the gas source inservice is empty, the switchover to the gas sourcein reserve will be automatic. It will be sufficient toswitch over the position of the lever so that the gassource initially in reserve will be in service, at therequired working pressure.Change the empty cylinders or bundles which willbe automatically in reserve.The gas source in service is indicated by the positionof the lever. The arrow on the lever indicates themain source.

    Open always the cylinder (orbundle) valves slowly andgradually.

  • EN

    OP 206 ML-ML1-CLSA1 08/2013 v.1.0 11

    4. Usage

    4.1 Use

    Adjust the outlet pressure according toyour need with the handwheel (ML1 gas panel only).

    4.2 Cylinders or Bundles change

    Identify the empty cylinders or bundles.

    -1. Push the handle (4) (for semi-automatic gasmanifold only):-Downwards: if empty cylinders are on the

    left.-Upwards : if empty cylinders are on the right.

    Change of empty cylinders or bundles.

    -2. Close the High Pressure shut off valve(2) (empty side) on the gas panel or on theconnection point (in case of use of more than2 bundels).

    -3. Close the cylinder or bundle valves (1).-4. Slowly open the purge valve (3) and release

    the pressure, then close the valve.The pressuregauge must indicate 0 bar.

    -5. Disconnect the flexible hoses or the pigtailsfrom the cylinders or the bundles.

    -6. Replace the empty cylinders or bundles andsafely store.

    -7. Verify the cleanliness of the cylinders' orbundles' valve outlet.

    -8. Connect the flexible hoses or the pigtailsafter change the seals. Do not forget toremount the Safety cable.

    -9. Slowly open the cylinder or bundel valves(1) and close them again before to reach themaximum pressure.

    -10. Wait about 1 minute..-11. Slowly open the purge valve (3) and

    close it again before to reach the atmosphericpressure.

    -12. Start twice this cycle from point (9) to (11).(4 to 6 times in case of pure gases).

    -13. Slowly open the cylinder or bundel valves(1) at least 2 turns.

    -14. Slowly open the High Pressure shut offvalve (2).

    Do not allow a flexible hoses to rub against theground or a wall.Fix the chain holding the cylinders in the racks. Inthe case of bundles, make sure that they are onhorizontal surface.All flexible hoses or pigtails must be connectedand safety cables hooked up before opening thecylinders or bundles.In case of combustible gases, make sure that thebundles are connected to the ground, before toconnect them to the gas manifold.* Different positions according to models

    4.3 After use

    Close all of shut-off valves and cylinder (or bundle)valves.

    Open the purge valves, purge the installation andthe flexible hoses (or pigtails). The gauges shallindicate "0".

    Close the purge valves again. Dismantle and store carefully the flexible hoses

    or the pigtails. Store safely from dust and ofmoisture.

    Screw the blind plugs on the "High Pressure" inletports.

  • OP 206 ML-ML1-CLSA1 08/2013 v.1.012

    5. Maintenance

    5.1 Troubleshooting

    FAULT CAUSE REMEDYImpossible assembly of theconnections

    Verify the compatibility with gases,inlet and outlet

    Impossible assembly

    Dammaged connection Change the connectionCross section passage limited bya valve.

    Open the valve

    Insufficient filled or empty cylinder Change the cylinderNot operating valve Change the cylinderUnder-dimensioned equipment Contact AIR LIQUIDE

    Insufficient output of gas

    Equipment in output notoperational

    Change the equipment

    Occasional over consumption Replace by an equipment with alower output

    Leakage check out the gas tightness

    The gas source in reserve drainswithout being used (Change overonly)

    Leakage at the main valve of theregulator

    Replace the main valve* or theregulator,

    At the same pressure and outputentry, the outlet pressure is notthe same which side you areusing

    Disturb regulators Adjust the regulators

    Leakage at the flap of theregulator

    Replace the regulatorGas comes out of the relief valve

    defect relief valve Replace the relief valveToo low working pressure Close the cylinder valve.

    Increase the temperature of theequipment above 0C

    Frosting

    The used gas is argon (Ar),carbon dioxide (CO2) or nitrousoxide (N2O)

    Mount an heater at the inlet

    The outlet pressure decreases Output flow too high

    Respect the regulator flow. Limitthe flow by using a valve or acalibrated orifice.

    Vibrations

    Presence of a valve with rapidopening on the outlet pipe.

    Limit the flow by using a valve or acalibrated orifice.

  • EN

    OP 206 ML-ML1-CLSA1 08/2013 v.1.0 13

    5.2 Maintenance

    Even though the equipment is reliable, it mustbe checked periodically. Since this task requiressome precautions, it must be done exclusively by aqualified technician.

    The periodicity of this verification dependsessentially on the usage of the equipment (intensive,moderate, occasional). It can be performed annuallyby AIR LIQUIDE under a maintenance contract(SERVIGAZ).The period will in no case exceed 5years.

    Legend Periodically Once a yearEvery

    3 years

    We suggest the use of the following table toensure an optimum usage of your equipment

    V : to verify

    C : to change Leakage

    Operation

    condition of threads

    Sealing of closure

    Fastening

    Appearance

    Setting

    Safety

    Cleanliness

    Labelling

    Seal

    Setting

    Filter

    Electrical continuity

    Flexible hoses / Pigtails V V V V V V C V CSafety cable V V CRacks V VChain V V

    Cylinder/Manifoldconnection

    Fittings / Filters V V V CSupport plate V V V V VHP Valves V V VRegulators V V V V V VLP Valves V V VRelief valves V V C

    Manifold

    Pressure Gauges V V V

    2nd Stage reducer V V V C V CMonitoring system V V V Others

    Pipe network V V V V V V C V

    In case of operating accident (insufficient output,leakage, opening of the relief valve or accidentaldamage) : Contact AIR LIQUIDE.

    Use only original parts and do not modify theequipment,

    Never dismantle any of the equipmentscomponents.

    Defective reassembly may causebursting, malfunctioning and/or an

    increasing output pressure, which isdangerous for your safety.

  • OP 206 ML-ML1-CLSA1 08/2013 v.1.014

    5.3 Spare parts

    ManifoldInlet

    pressuregauge (5)

    Outletpressuregauge (6)

    Reliefvalve (7)

    Regulator(8)

    Shut-off/purge

    valvesblock (9)

    Designation Code

    ML1 300-16-8 16004 152809

    ML1 300-10-50 151821

    18554

    ML 200-200-30 15337 15969 15653

    CLSA1 200-10-10 15209 16003 15481

    CLSA1 200-10-50 15228

    17076

    CLSA1 200-20-50 15247

    15970

    18544

    16188

    Spare part seals (package of ten):

    Designation Code

    O-Ring EPDM R6 PC851 for inlet port 16x1,336 SI 17129

    Flat seal PTFCE (Kel-F) 14,5x10x2 for outlet port G3/8 AL 17141

    Flat seal Alu/ARCAP for gauge M10x1 (Kit of seals, Alu:8,5x5x1, ARCAP:8,5x5x0,3) 17084

    Flat seal PA 6.6 for gauge G1/4 151862

    Flat seal annealed copper for intet fitting 16x1,336 SI 137203

  • EN

    OP 206 ML-ML1-CLSA1 08/2013 v.1.0 15

    Other spare parts

    Dsignation Code

    Plug for orifice 16x1,336 SI in stainless steel 16597

    Plug for orifice G 3/8 in stainless steel 16596

    Plug for orifice M10x1 in stainless steel 16598

    Fitting with non-flapping valve brass/EPDM + filter 16x1,336 SI M - M20x1,5 M 16413

    Fitting with non-flapping valve brass/EPDM + filter 16x1,336 SI M - CF10MM 151804

    Plastic cover for central 83401

    Cylinder/Bundle Change Procedure Panel for CLSA/ML 152662

    Multilingual stickers Change procedure for cylinders or bundles CLSA/ML 153663

    Hazard panel Oxygen - Nitrous oxide 153687

    Hazard panel Combustible Gases 155103

    Hazard panel Inert Gases 153689

    Choice of the calibrated orifice :

    Nitrogen N2 Helium He Hydrogen H2Code Change over Orifice

    mmCode

    Orifice mm

    Code Orifice mm

    Code

    15209 CLSA1 200-10-10 1,5 155748 0,9 155743 0,8 155742

    15228 CLSA1 200-10-50 3,8 155761 2,3 155755 2,0 155752

    15247 CLSA1 200-20-50 2,2 155754 1,3 155746 1,1 155745

  • OP 206 ML-ML1-CLSA1 08/2013 v.1.016

    1. Drawings

    1.1 Dimensions

    ML - ML1

    L: 135 mmH: 115 mmP: 112 mmWeight: 7-7,5 Kg

    CLSA1

    L: 530 mmH: 115 mmP: 112 mmWeight: 12,5 Kg

  • FR

    OP 206 ML-ML1-CLSA1 08/2013 v.1.0 17

    1.2 CLSA1

  • OP 206 ML-ML1-CLSA1 08/2013 v.1.018

    1.3 ML-ML1

  • We are present in more than 80 countries.

    Contact:AIR LIQUIDEEuropean Platform and ServicesTour Kupka C92039 Paris La Dfense Cedex, Francewww.airliquide.com

    www.ai r l iqu ide.com

    Air Liquide is the world leader in gases for industry, health and the environment, and is present in 80 countries serving over 2 million customers.Its Industrial Merchant Business Line plays a vital role in helping Air Liquide achieve its goals. We are a network of over 20,000 open-mindedpeople working at 500 facilities, each one committed to inventiveness in moving our customers businesses forward. This means always beingready to adapt, to understand, to recognise opportunities and to innovate, in order to drive long-term performance at every stage of your growth.

    OP

    206

    ML-

    ML1

    -C

    LSA

    1 08

    /201

    3 v.

    1.0

    A

    IR L

    IQU

    IDE

    , G B

    oula

    y