Addressing Defective Cathodic Protection Systems On Above Grade Storage Tanks

NISTM-2013 Ralph Eichlin Corrosion Control Incorporated

Page 2: Addressing Defective Cathodic Protection Systems On … 1/Eichlin.pdf · Cathodic Protection Systems Cathodic protection is used to control corrosion on the underside (soil side)

Cathodic Protection Systems

Cathodic protection is used to control corrosion on the underside (soil side) of above grade petro-chemical tanks

Effective cathodic protection will increase reliability and reduce costs associated with maintenance and inspection

Several states, the DOT and the DoD require the use of cathodic protection to reduce product release

Page 3: Addressing Defective Cathodic Protection Systems On … 1/Eichlin.pdf · Cathodic Protection Systems Cathodic protection is used to control corrosion on the underside (soil side)

Cathodic Protection Types

Galvanic

Impressed Current

Page 4: Addressing Defective Cathodic Protection Systems On … 1/Eichlin.pdf · Cathodic Protection Systems Cathodic protection is used to control corrosion on the underside (soil side)

Single Bottom Storage Tanks

(-) (+)

Protective Current

Tank

Anode

Foundation

Rectifier

Page 5: Addressing Defective Cathodic Protection Systems On … 1/Eichlin.pdf · Cathodic Protection Systems Cathodic protection is used to control corrosion on the underside (soil side)

Cathodic Protection Arrangement

Many above grade tanks are equipped with under floor containment liners

The type of liner used will determine the anode placement

Page 6: Addressing Defective Cathodic Protection Systems On … 1/Eichlin.pdf · Cathodic Protection Systems Cathodic protection is used to control corrosion on the underside (soil side)

Clay Fabric Containment Liner

Tank

(-)

(+)

Anode

Rectifier

Clay Fabric Liner

Soil

• Current passes through liner • Anodes can be placed below liner or around tank • Replacement anodes can be placed around tank

Page 7: Addressing Defective Cathodic Protection Systems On … 1/Eichlin.pdf · Cathodic Protection Systems Cathodic protection is used to control corrosion on the underside (soil side)

Non-Conductive Liner

Tank

(-)

(+)

Anode

Rectifier

Plastic Liner Current will not pass through liner

Sand

Tank Floor

• Containment liner blocks current from reaching tank bottom • Cathodic protection readings around tank give indication of

effective corrosion control • Tank bottom subject to corrosion above liner

Page 8: Addressing Defective Cathodic Protection Systems On … 1/Eichlin.pdf · Cathodic Protection Systems Cathodic protection is used to control corrosion on the underside (soil side)
Page 9: Addressing Defective Cathodic Protection Systems On … 1/Eichlin.pdf · Cathodic Protection Systems Cathodic protection is used to control corrosion on the underside (soil side)

Cathodic Protection – Plastic Liner

• Anodes are placed in sand between liner and tank bottom • Anodes can not come in contact with tank bottom • Distance between anode and floor determines current distribution

Anode

Shell

Bottom

Foundation Sand

Liner

Tank

Page 10: Addressing Defective Cathodic Protection Systems On … 1/Eichlin.pdf · Cathodic Protection Systems Cathodic protection is used to control corrosion on the underside (soil side)

Galvanic Ribbon Systems

Spacing between ribbons must adequate to provide current distribution

Sand fill can not be corrosive, and must remain relatively dry

When moisture enters the sand, most galvanic systems continue to protect the tank bottom but a shorter anode service life may result.

Some early galvanic ribbon systems were actually used to detect leaks

Page 11: Addressing Defective Cathodic Protection Systems On … 1/Eichlin.pdf · Cathodic Protection Systems Cathodic protection is used to control corrosion on the underside (soil side)

Zinc Anode Ribbons

36 to 60 inches

Cable Connections

Tank Shell

Zinc ribbon

Test Box

Page 12: Addressing Defective Cathodic Protection Systems On … 1/Eichlin.pdf · Cathodic Protection Systems Cathodic protection is used to control corrosion on the underside (soil side)

Magnesium Anode Ribbons

Magnesium Ribbons

Permanent reference cell centered between ribbons

#10 RHW-USE

Tank Shell

Splice Test Box

24” Centers

Page 13: Addressing Defective Cathodic Protection Systems On … 1/Eichlin.pdf · Cathodic Protection Systems Cathodic protection is used to control corrosion on the underside (soil side)

Galvanic Anode Splice

To Next Anode

Mastic Patch

Exposed Steel Core

Solid Copper Crimp To Next Anode

#10 RHW-USE

Magnesium Ribbon

Page 14: Addressing Defective Cathodic Protection Systems On … 1/Eichlin.pdf · Cathodic Protection Systems Cathodic protection is used to control corrosion on the underside (soil side)

Galvanic Test Box

Live Shell

Sand

New Floor

Reference Cells

Test Box

Liner Seal

Anode Ribbon Grade

Couple

Seal off

1 ½” dia. conduit

Page 15: Addressing Defective Cathodic Protection Systems On … 1/Eichlin.pdf · Cathodic Protection Systems Cathodic protection is used to control corrosion on the underside (soil side)
Page 16: Addressing Defective Cathodic Protection Systems On … 1/Eichlin.pdf · Cathodic Protection Systems Cathodic protection is used to control corrosion on the underside (soil side)

Current Flow

• Current flows off magnesium anode into sand • Current flows through sand and onto underside of floor • Current returns in steel and cable to anode

Live Shell

Sand Protective current flow

Newer Tank Floor

To next anode

Test Box Weld

Liner Seal

Cable

Anode

New Floor

Old Floor

Cable connection to tank

Current return in cable

Page 17: Addressing Defective Cathodic Protection Systems On … 1/Eichlin.pdf · Cathodic Protection Systems Cathodic protection is used to control corrosion on the underside (soil side)

Sand Contamination

Rain water enters at leak detection tubes

Rain water enters at chime (new floor to old shell)

Water bottoms seep through flaws in welds or floor plates

Page 18: Addressing Defective Cathodic Protection Systems On … 1/Eichlin.pdf · Cathodic Protection Systems Cathodic protection is used to control corrosion on the underside (soil side)

Water Entering Sand

Live Shell

New Floor

Dead Shell

Leak detection port not sealed

Sand

Old Floor

Water entering sand

Chime

Lack of seal weld

Weld defect Defect in plate

Page 19: Addressing Defective Cathodic Protection Systems On … 1/Eichlin.pdf · Cathodic Protection Systems Cathodic protection is used to control corrosion on the underside (soil side)

Impressed Current

• Rectifier supplies current to anodes in sand • Anodes deliver current to floor which is returned to rectifier • Reference cells are used to monitor protection levels

Anode

Shell

Floor

Foundation

Liner Reference Cells

Sand

Rectifier Negative Connection

Test Box

Page 20: Addressing Defective Cathodic Protection Systems On … 1/Eichlin.pdf · Cathodic Protection Systems Cathodic protection is used to control corrosion on the underside (soil side)
Page 21: Addressing Defective Cathodic Protection Systems On … 1/Eichlin.pdf · Cathodic Protection Systems Cathodic protection is used to control corrosion on the underside (soil side)

Galvanic System Deficiencies

Anode ribbons are too far apart

Anode ribbons do not deliver sufficient current

Sand used as fill is conductive and corrosive

Water enters sand causing it to become corrosive

Galvanic anode ribbons are depleted

Reference cells are inaccurate or inoperable

Page 22: Addressing Defective Cathodic Protection Systems On … 1/Eichlin.pdf · Cathodic Protection Systems Cathodic protection is used to control corrosion on the underside (soil side)

Impressed Current Deficiencies

Rectifier inoperable or not properly adjusted

Cables between rectifier and anode box are severed

Anodes are spaced too far apart

Anode ratings are too low

Anodes are grounded to tank bottom

Reference cells are inacurate or inoperable

Positive and negative cables are connected with the wrong polarity

Sand is too dry

Page 23: Addressing Defective Cathodic Protection Systems On … 1/Eichlin.pdf · Cathodic Protection Systems Cathodic protection is used to control corrosion on the underside (soil side)
Page 24: Addressing Defective Cathodic Protection Systems On … 1/Eichlin.pdf · Cathodic Protection Systems Cathodic protection is used to control corrosion on the underside (soil side)

The CP System Doesn’t Work. Now What ?

Monitor tank bottom using API-653 inspection code, take action if corrosion losses are significant

Lift the tank or remove the floor and replace the cathodic protection system

Attempt to insert anodes between liner and floor through holes cored in ringwall

Inject inhibitors into sand in place of cathodic protection

Page 25: Addressing Defective Cathodic Protection Systems On … 1/Eichlin.pdf · Cathodic Protection Systems Cathodic protection is used to control corrosion on the underside (soil side)
Page 26: Addressing Defective Cathodic Protection Systems On … 1/Eichlin.pdf · Cathodic Protection Systems Cathodic protection is used to control corrosion on the underside (soil side)

Retrofit Inserted Anode

Shell

Ringwall

Floor

Sand Cable Splice Box

Containment Liner Inserted Anode

Page 27: Addressing Defective Cathodic Protection Systems On … 1/Eichlin.pdf · Cathodic Protection Systems Cathodic protection is used to control corrosion on the underside (soil side)

Inject Water Based Inhibitor

Shell

Inject Water Based Inhibitor

Electrical resistance probe or coupon

Monitor Discharge

Page 28: Addressing Defective Cathodic Protection Systems On … 1/Eichlin.pdf · Cathodic Protection Systems Cathodic protection is used to control corrosion on the underside (soil side)

Conclusions

Best solution is to avoid the problem to start with; specific requirements for construction

Monitor tank floor using API-653 inspection code, take action based on inspection results

Inhibitor inject shows promise, concerns are accuracy of corrosion monitoring and life cycle of inhibitor

Inserting anodes between liners and floors is not practical in most applications

Lift tank/remove floor – be sure any replacement systems are design and installed to provide long term service