additional installation manual

22
Additional installation manual

Upload: others

Post on 16-Oct-2021

5 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Additional installation manual

Additional installation manual

Page 2: Additional installation manual

2

Summary

Recommendations for implementation ....................................................................................... 3

DHW Heat Pump nomenclature .................................................................................................... 4

Siting the DHW heat pump ............................................................................................................ 5

Conversion to outdoor air mode ................................................................................................... 6

Converting the top panel ............................................................................................................................................. 6

Fitting the air intake/air discharge ductwork ........................................................................................................ 8

Connecting the condensate drain ............................................................................................... 10

Connections on the DHW side ..................................................................................................... 11

Adjusting the draw-off rate ......................................................................................................... 12

Electrical connections ................................................................................................................... 12

Connecting the premium/economy tariff function .................................................................. 13

Filling the DHW cylinder on the DHW side ............................................................................... 13

Installation parameters settings .................................................................................................. 14

Troubleshooting ........................................................................................................................... 15

Connecting photovoltaic modules to GSE THERMO'SYSTEM ...................................................................... 16

Connections configurations of modules to GSE THERMO’SYSTEM ............................................................. 16

Connecting the existing CMV to GSE THERMO'SYSTEM .......................................................... 18

Kit’s nomenclature for CMV connection to GSE THERMO’SYSTEM ............................................................ 18

Connecting the Elios4You ............................................................................................................ 19

Electric diagram ............................................................................................................................................................ 19

Elios4You installation steps ...................................................................................................................................... 19

Elios4You configuration ............................................................................................................................................. 21

Troubleshooting ............................................................................................................................................................ 22

Page 3: Additional installation manual

3

Recommendations for implementation

• For horizontal transport of the DHW heat pump, it must be lying on the face indicated on

the packaging.

• Don’t tilt the DHW heat pump more than 45° during transport and installation.

• The installation room must be dry and free from the risk of frost.

• The intake air must be kept free from dust, grease and/or contamination.

• A separately fused standard power socket must be available.

• A condensate drain pipe must be available.

• Always maintain the minimum clearances for service and maintenance work.

• Leave the DHW heat pump upright in the planned installation placement for at least 24

hours before start it, in order to allow the entire refrigerant to set properly.

Implementation schemes of configurations:

Recirculation air mode Recirculation air mode with air discharge

to the outside

Outdoor air mode

Page 4: Additional installation manual

4

DHW Heat Pump nomenclature

A: Programming unit

B: Heat pump control unit

C: Sensor well for draw-off profile L

D: Sensor well for draw-off profile XL

E: Inspection port, magnesium anode, immersion heater

F: Air discharge

G: Air intake

H: Cold water/drain outlet R 1

N: DHW circulation R ¾

O: DHW R ¾

P: Condensate Ø20 mm

R: Power cable, length 3m

Page 5: Additional installation manual

5

Siting the DHW heat pump

• Never drill into the sheet steel

casing of the DHW heat pump.

• Never use the connectors as a

transport aid.

• Carefully remove the DHW heat

pump from the pallet. The EPS

padding underneath can be

removed for this.

• Do not exceed 35 mm height

from flat surface, measuring to

the bottom end of the DHW

heat pump as shown in the

figure.

Page 6: Additional installation manual

6

Conversion to outdoor air mode

Converting the top panel

Note:

The air discharge aperture is converted for recirculation air mode with air discharge to the

outside.

Page 7: Additional installation manual

7

Note:

If the top panel is not sealed tightly, indoor air will be drawn in. This causes negative

pressure inside the room.

A Air discharge cover grid

B Air intake cover grid

Page 8: Additional installation manual

8

Fitting the air intake/air discharge ductwork

• Never operate the DHW heat pump simultaneously with open flue combustion equipment

(e.g. an open fireplace).

• Be careful that no drilling swarf fall into the DHW heat pump air intake aperture or air

discharge aperture.

• For outdoor air mode, always route the ducts for air intake and air discharge with a 2-3° fall,

so that rain and condensate can drain away.

Connections and installation options which are not permissible:

• Connection of kitchen extractor hoods to the ductwork

• Installation of a DHW heat pump with recirculation air mode in a heated room

• Connection of the air intake duct to a mechanical ventilation system

• Connection of the air intake duct to an air/geothermal heat exchanger

• Connection of the air intake duct to a tumble dryer

• Reversed connections (air intake to the outside and air discharge to the inside)

• Installation of the DHW heat pump in an attic

• Installation of the DHW heat pump in dusty rooms

• Operation of the DHW heat pump in conjunction with an open flue boiler

Notes:

• In recirculation air mode with air discharge to the outside, ensure an adequate supply of fresh

air to the installation room (on site), e.g. via separate vents (min. DN 160).

• Ducts, wall outlets and connections to the DHW heat pump can be installed using anti-

vibration insulation to reduce noise (see below).

Page 9: Additional installation manual

9

Ductwork DN [mm]

1 Bend 90° 160

45° 160

2 Folded spiral-seam tube or flexible

pipe

Length 3.0 m 160

3 Outdoor air intake grid as air

s discharge duct wall outlet

160

4 Exhaust air roof outlet Round, with protective grid and insulation

sleeve, for air discharge duct

160

5 Vent Wall/external connection, for air intake

duct

160

6 Check valve (on site)

A: DHW heat pump

B: Flexible hydraulic connections

C: EPP insulated plastic pipes or insulated flexible pipes (min. DN 160) for air

intake/air discharge ductwork

D: Anti-vibration insulation for wall outlet

E: Anti-vibration bracket for air intake duct

F: Air intake silencer

G: Air discharge silencer

H: Anti-vibration bracket for air discharge duct

K: Anti-vibration insulation for air discharge duct wall outlet

L: Anti-vibration insulation for floor

M: Adjustable feet

A : Supply air

B : Exhaust air

1. Join individual duct sections together with connection

pieces or female connections (see system diagram on

page 16).

2. Secure joints with self-tapping screws or blind rivets

and make an airtight seal using shrink tape.

Page 10: Additional installation manual

10

When the intake and discharge are both sheathed on the outside, make sure to respect the

following distances :

Through the wall Through the roof

Measures for minimizing the pressure drop:

• Use as few bends as possible..

• Route the air intake duct above the air discharge duct if possible.

Connecting the condensate drain

• To prevent water leakage, never twist the condensate drain connector on the appliance.

• Route the condensate hose as a U-bend and connect with a constant fall and a pipe vent

to the public sewage system or a neutralising system. If necessary, connect to an on-site

trap. Ensure that the trap is connected securely.

• Connecting the condensate drain to rainwater downpipes is not permissible.

• Should the condensate drain run partially through unheated rooms, provide thermal

insulation or a ribbon heater around the condensate drain on site..

A : Air intake

B : Air discharge

Condensate drain via water seal Condensate drain via trap

Page 11: Additional installation manual

11

Connections on the DHW side

Connect all pipework with detachable fittings.

Note: The safety assembly to DIN 1988 is available as an accessory. The safety assembly contains

the following components:

• Shut-off valve

• Diaphragm safety valve

• Non-return valve and test connector

• Pressure gauge connector

A: DHW

B: DHW circulation pipe

If no DHW circulation pipe is connected, seal the

aperture provided for this purpose.

C: DHW circulation pump

D: Spring-loaded check valve

E: Visible discharge pipe outlet point (tundish)

F: Safety valve

G: Shut-off valve

H: Flow regulating valve

K: Pressure gauge connection

L: Non-return valve

M: Drain valve

N: Cold water

O: Drinking water filter

P: Pressure reducer

R: Non-return valve/pipe separator

S: Expansion vessel, suitable for potable

T: Automatic thermostatic mixing valve (on site)

Equip the DHW circulation pipe with a

DHW circulation pump, check valve and

time switch. Gravity operation is possible

only to a limited extent.

Page 12: Additional installation manual

12

Adjusting the draw-off rate

If there is high demand for DHW, it is possible to change the draw-off profile from L to XL.

To do this, the cylinder temperature sensor fitted at the factory is removed from sensor well A

and fitted in sensor well B, taking care not to bend or damage this sensor.

Note: The high limit safety cut-out for the DHW heat pump must also be refitted.

Electrical connections

The DHW heat pump is fully wired with a 3-core power cable:

▪ H05VV-F 3G 1.5

▪ Color: White

▪ Cores:

o L1: Brown

o N: Blue

o PE: Green/Yellow

A separately fused standard socket is required for the power supply:

▪ 230 V/50 Hz

▪ Max. fuse rating 10 A

Maximum fuse protection 10A

Sensor well for draw-off profile L (basic state)

Sensor well for draw-off profile XL

Page 13: Additional installation manual

13

Connecting the premium/economy

tariff function

In case of installation of the GSE THERMO'SYSTEM, the day/night contactor of the

conventional hot water tank must be removed. The terminals C1 and C2 of the heat pump control

module located under the front cover of the GSE THERMO'SYSTEM, must be connected to C1 and

C2 terminals of the electric meter:

Filling the DHW cylinder on

the DHW side

1. Completely fill the DHW cylinder. Open the highest hot water draw-off point. Leave it

open (under supervision) until only water is flowing out.

2. Check the fittings for leaks and tighten if necessary.

Page 14: Additional installation manual

14

Commissioning

Calling up installation menu "INST"

1. Press and hold and − simultaneously for 3 seconds. « INST » appears on the display.

2. Press the button once to access « I » parameters.

3. Set the four « I » parameters according to the table on the next page by selecting the

parameter with + / − and set its value with the « OK » button.

4. Then press the button twice to pass « T » and « t’ » parameters. « SAVE » appears on the

display.

Installation parameters settings

Parameter Delivered condition Setting range Unit Function

« I1 » 1 1 or 2 - - 1: Installation for recirculation air mode

- 2: Installation for outdoor air mode or

recirculation air mode with air discharge to the

outside

« I2 » 0 0 or 1 - - 0: Installation without premium/economy tariffs

- 1: Installation with premium/economy tariffs

Note: The (230 V) signal cable for premium/

economy tariffs must be connected.

« I3 » 0 (OFF) 0 to 20 min - 0: Installation without PV system

- 1 to 20: Installation with PV system : The set

temperature is raised after the multifunctional relay

contact (on site) has been closed for between 1

and 20 minutes.

Recommended setting: 5 minutes

« I4 » 0 0 or 1 - "Increased DHW hygiene" function

- 0 : Function disabled

- 1 : Function enabled:

The DHW cylinder is automatically heated

to 60 °C every 22 days

Page 15: Additional installation manual

15

Troubleshooting

Message Cause Action

"ER 1"

Safety high pressure switch has

responded. Overpressure in the

heat pump circuit.

Switch power supply OFF and

ON again.

OR

Acknowledge message. See the

following chapter.

"ER 2"

High limit safety cut-out has

responded. Overheating of the

DHW cylinder.

Ensure DHW is being drawn.

Reset high limit safety cut-out.

"ER 3" Short circuit/lead break in lower

cylinder temperature sensor.

Check resistance value and

replace sensor if necessary. "ER 4"

Short circuit/lead break in air

intake temperature sensor.

"ER 5" Short circuit/lead break in

evaporator temperature sensor.

"ER 8"

Communication problem

between programming unit and

heat pump control unit.

Check connections and cables.

Acknowledging messages

Press and hold and OK simultaneously for 3 seconds to clear a message and resume

standard operation.

Page 16: Additional installation manual

16

Connecting photovoltaic

modules to GSE THERMO'SYSTEM

Connections configurations of modules to GSE THERMO’SYSTEM

In both cases, to connect photovoltaic modules to GSE THERMO'SYSTEM:

- Make the modification for outdoor air mode as indicated in page 7.

- Connect a Ø160mm duct between the delta collector output and the air intake of the

DHW heat pump as in the layouts above.

- Connect a Ø160mm duct extraction between the air discharge of the GSE

THERMO’SYSTEM and the outside extraction as indicated in page 11, through the wall

or through the roof according to the configuration of the house.

1. PV Modules

+ GSE THERMO’SYSTEM

2. PV Modules

+ GSE THERMO’SYSTEM

+ GSE AIR’SYSTEM

Page 17: Additional installation manual

17

Nomenclature of kits

KIT PRODUCTS QUANTITY

GSE AIR'SYSTEM FRAME 8

ELBOW CONNECTOR 75 8

O-RING JOINT 16

DUCT AIR'SYSTEM 75 25

ISULATOR DUCT 14 22,8

DELTA C 160 1

DUCT AIR'SYSTEM 160 10

ADJUSTABLE SEAL 2

GSE AIR'SYSTEM FRAME 16

ELBOW CONNECTOR 75 16

O-RING JOINT 32

DUCT AIR'SYSTEM 75 50

ISULATOR DUCT 14 40,8

DELTA C 160 2

DUCT AIR'SYSTEM 160 10

GALVANIZED CONNECTION 160 2

ADJUSTABLE SEAL 6

4 TO 8 PANELS CONNECTION KIT

9 TO 16 PANELS CONNECTION KIT

Page 18: Additional installation manual

18

Connecting the existing CMV to GSE

THERMO'SYSTEM

Kit’s nomenclature for CMV connection to GSE THERMO’SYSTEM

Note: For connection from the discharge of the DHW heat pump to the roof, an optional roof cap

can be supplied.

PRODUCTS QUANTITY

GSE THERMO'SYSTEM 1

OUTDOOR AIR MODE KIT 1

DELTA C 160/160/160 1

INSULTED DUCT 160 1

ADJUSTABLE SEAL 6

CONNECTION BALLON + VMC KIT

Page 19: Additional installation manual

19

Connecting the Elios4You

Electric diagram

Elios4You installation steps

1. Set the device in the customer's electrical panel.

WARNING: If no sufficient space is available in the main electrical panel, install it in an additional

electrical panel.

2. Connect the yellow main current transformer to terminals 10 and 12 of Elios4You, and then

clamp it to the main meter phase.

3. Connect the white main current transformer to terminals 7 and 9 of Elios4You, and then clamp

it to the generation meter phase.

Page 20: Additional installation manual

20

WARNING: place the current transformer ensuring that the green point and the direction of the

arrow points to the main circuit breaker.

4. After removing the cover on the front side of the DHW heat pump, connect the white and

yellow unconnected cables of the heat pump module to terminals 13 and 14 of Elios4You.

5. Supply the Elios4You by connecting the neutral of the power supply to terminal 1 and the

phase to terminal 2.

WARNING: Elios4You power supply must be protected via a 1A fuse.

6. Check the LED on the Elios4you panel.

WARNING: Some errors can be detected through LED blinking:

• If the generation energy LED does not blink when the PV installation is producing

energy, it is necessary to invert the Generation CT orientation by inverting the connection of

the wires of Elios4you (terminals 7 and 9).

• If the exchange LEDs and detect the wrong energy flow (“sold” energy is

indicated when it should be reporting a situation of “purchased” energy or vice versa), it is

necessary to invert the main CT (yellow label) by inverting the connection of the wires of

Elios4you (terminals 10 and 12).

• If the generation and exchange values are incorrect, reverse the power supply terminals.

Page 21: Additional installation manual

21

Elios4You configuration

1. After device installation and after having it powered on, download the free App Elios4you on

your own device (smartphone or tablet) from Play Store (Android) or App Store (iOS).

2. Open the App, start the wizard, and follow the steps indicated on your smartphone/tablet (read

the Elios4you APP Quick Guide for further information).

3. Set the correct parameters for your PV system and your energy provider using the App menu:

- Press « Menu » button

- Select « Parameter Settings»

- Press « Relay Management », and then on « EDIT » in front of « Auto »

- Adjust settings « Enable the relay when … » and « Disable the relay when … » as shown

below:

Page 22: Additional installation manual

22

Troubleshooting

Problem Solutions

1. I cannot see my PV system energy generation

in the App’s home Page

a. Change current clamp (CT) orientation (white

label) by inverting the green dot or the inside

current clamp arrow position.

b. Check that inside the current clamp there is the

PV Line cable only (not the Neutral as well).

c. Check that the current clamp core is not

broken or cracked inside.

2. The energy generation visible on the App is

definitely less than the value read from the

inverter

a. Make sure that the Elios4you is powered from

the same line of the 2 current clamps.

b. Make sure that the current clamp (white label)

is perfectly closed: no strong pressure is required

to clamp the cable properly.

3. Consumption graph has the same shape as the

production graph line

a. Make sure that the main CT (yellow label) is

clamping all the lines coming from the Mains

Meter: if not, it is possible that the meter is

measuring the consumption only.

b. Check that both current clamps are not broken

or cracked inside.

4. It seems that consumption values are shown in

the “grid” icon

a. Make sure that the main CT (yellow label) is

clamping all the lines coming from the Mains

Meter: if not, it is possible that the meter is

measuring the consumption only.

5. I can never see purchased energy in my system

a. Make sure that the main CT (yellow label) is

clamping all the coming from the Mains Meter: if

not, it is possible that the meter is measuring the

consumption only.

6. During the night, the consumption is zero,

while during the day, it is always more than

expected normal value

a. Reverse CT (yellow label) current clamp

position, by inverting the green dot or the inside

arrow position.

7. In the App I can see high consumption levels,

while the real time consumption is very low

a. Reverse CT (yellow label) current clamp

position, by inverting the green dot or the inside

arrow position.

b. Make sure that the main CT (yellow label) is

clamping all the coming from the Mains Meter: if

not, it is possible that the meter is measuring the

consumption only.