ADDENDUM NO. CC-1 CC-1 - 1
ADDENDUM NO. CC-1 PLATTVIEW JR & SR HIGH SCHOOL RENOVATIONS SPRINGFIELD PLATTEVIEW COMMUNITY SCHOOLS SPRINGFIELD, NEBRASKA DLR GROUP PROJECT NO. 10-13125-30 COMBINED CONTRACT September 13, 2017 NOTICE TO BIDDERS: Amend the Project Manual and Drawings to the above referenced project as follows:
PROJECT MANUAL ITEM NO. 1 SECTION 000110 TABLE OF CONTENTS – VOLUME I
A. Under Division 05 Metals, add the following Section:
“054000 Cold-Formed Metal Framing”
B. Under Division 06 Wood, Plastics and Composites, add the following Section:
“066400 Plastic Paneling”
ITEM NO.2 SECTION 054000 COLD-FORMED METAL FRAMING
A. Add new Section 054000 Cold-Formed Metal Framing as shown on Attachment No. 1. ITEM NO. 3 SECTION 066400 PLASTIC PANELING
A. Add new Section 066400 Plastic Paneling as shown on Attachment No. 2. ITEM NO. 4 SECTION 072119 FOAMED-IN-PLACE INSULATION
A. Subparagraph 2.1A.1 Add the following;
“g. Accella Polyurethane Systems; Bayseal OC or Foamsulate 50. h. Quadrant Urethane Technologies; QuadFoam 500.”
ITEM NO. 5 SECTION 087100 DOOR HARDWARE
A. Article 3.3. Delete Hardware Sets, No.01, 04, 05, 07, 08 and 09 and substitute the following;
“HW SET NO. 01
FOR USE ON MARK/DOOR #(S): F124 Qty Description Catalog Number Finish Mfr
2 EA CONT. HINGE 224XY 313AN IVE
Architecture Engineering Planning Interiors
6457 Frances Street, Suite 200 Omaha, NE 68106
tel 402/393-4100 fax 402/393-8747
www.dlrgroup.com
PLATTVIEW JR & SR HIGH SCHOOL RENOVATIONS 10-13125-30 SPRINGFIELD PLATTEVIEW COMMUNITY SCHOOLS SPRINGFIELD, NEBRASKA
ADDENDUM NO. CC-1 CC-1 - 2
1 EA KEYED REMOVABLE MULLION
KR4954XP-STAB-SEC-MT54 SP313 VON
1 EA PANIC HARDWARE LD-XP-99-DT 313 VON 1 EA PANIC HARDWARE LD-XP-99-NL 313 VON 1 EA RIM CYLINDER 20-057-ICX 643e SCH 1 EA MORTISE CYLINDER 26-091-ICX 643e SCH 1 EA FSIC CORE 23-030 606 SCH 2 EA OH STOP 100S 695 GLY 2 EA SURFACE CLOSER 4040XP EDA 695 LCN 2 EA BLADE STOP SPACER 4040XP-61 695 LCN 1 EA MULLION SEAL 8780N N ZER 2 EA DOOR SWEEP 39D D ZER 1 EA THRESHOLD 545D-MSLA-10 D ZER 1 EA WEATHERSTRIP BY DOOR/FRAME MANUFACTURER
PERIMETER GASKETING BY DOOR MANUFACTURER.
HW SET NO. 04
FOR USE ON MARK/DOOR #(S): F201 F236 Qty Description Catalog Number Finish Mfr
2 EA CONT. HINGE 224XY EPT 313AN IVE 2 EA POWER TRANSFER EPT10 695 VON 1 EA KEYED REMOVABLE
MULLION KR4954XP-STAB-SEC-MT54 SP313 VON
1 EA ELEC PANIC HARDWARE
RX-LC-QEL-99-DT 313 VON
1 EA ELEC PANIC HARDWARE
RX-LC-QEL-99-NL 313 VON
1 EA RIM CYLINDER 20-057-ICX 643e SCH 1 EA MORTISE CYLINDER 26-091-ICX 643e SCH 2 EA FSIC CORE 23-030 606 SCH 1 EA OH STOP 100S
(SAME LEAF AS AUTO OPERATOR) 695 GLY
1 EA SURFACE CLOSER 4040XP EDA 695 LCN 1 EA SURF. AUTO
OPERATOR 4642 WMS (RHR LEAF)
695 LCN
1 EA BLADE STOP SPACER 4040XP-61 695 LCN 2 EA ACTUATOR KIT WALL
MT 8310-3853TWS 630 LCN
2 EA RECEIVER 8310-865 BLU LCN 1 EA WALL STOP WS406/407CCV 613 IVE 2 EA DOOR SWEEP 39D D ZER 1 EA THRESHOLD 545D-MSLA-10 D ZER 1 EA MULTITECH READER BY ACCESS CONTROL BLK SCE 2 EA DOOR CONTACT 7764 628 SCE 1 EA POWER SUPPLY PS904 900-2RS 900-4RL LGR SCE 1 EA WEATHERSTRIP BY DOOR/FRAME MANUFACTURER
OPERATION: DOORS NORMALLY CLOSED AND LOCKED. ENTRY GRANTED BY EXTERIOR CARD READER, WHICH MOMENTARILY RETRACTS EXIT DEVICE LATCHES. INSIDE PUSH PADS ALWAYS FREE
PLATTVIEW JR & SR HIGH SCHOOL RENOVATIONS 10-13125-30 SPRINGFIELD PLATTEVIEW COMMUNITY SCHOOLS SPRINGFIELD, NEBRASKA
ADDENDUM NO. CC-1 CC-1 - 3
EGRESS. AUTOMATED INGRESS ON RHR LEAF BY PRESSING EXTERIOR ACTUATOR WHEN DOORS ARE DOGGED, OR AFTER VALID CARD READ. AUTOMATED EGRESS BY PRESSING INTERIOR ACTUATOR. WHEN DOORS ARE LATCHED, PRESSING INTERIOR ACTUATOR FIRST RETRACTS EXIT DEVICE LATCH, THEN INITIATES AUTO OPERATOR CYCLE.
HW SET NO. 05
FOR USE ON MARK/DOOR #(S): F121 Qty Description Catalog Number Finish Mfr
2 EA CONT. HINGE 224XY 313AN IVE 2 EA DUMMY PUSH BAR 330-DT-990 313 VON 2 EA SURFACE CLOSER 4040XP EDA 695 LCN 2 EA BLADE STOP SPACER 4040XP-61 695 LCN 2 EA WALL STOP WS406/407CCV 613 IVE 1 EA WEATHERSTRIP BY DOOR/FRAME MANUFACTURER
HW SET NO. 07
FOR USE ON MARK/DOOR #(S): F212 Qty Description Catalog Number Finish Mfr
2 EA CONT. HINGE 224XY 313AN IVE 2 EA DUMMY PUSH BAR 330-DT-990 313 VON 2 EA OH STOP 100S 695 GLY 2 EA SURFACE CLOSER 4040XP EDA 695 LCN 1 EA SURF. AUTO
OPERATOR 4642 WMS 695 LCN
2 EA BLADE STOP SPACER 4040XP-61 695 LCN 2 EA ACTUATOR KIT WALL
MT 8310-3853TWS 630 LCN
2 EA RECEIVER 8310-865 BLU LCN 1 EA WEATHERSTRIP BY DOOR/FRAME MANUFACTURER
PLATTVIEW JR & SR HIGH SCHOOL RENOVATIONS 10-13125-30 SPRINGFIELD PLATTEVIEW COMMUNITY SCHOOLS SPRINGFIELD, NEBRASKA
ADDENDUM NO. CC-1 CC-1 - 4
HW SET NO. 08
FOR USE ON MARK/DOOR #(S): F107 F116 F219 F227 Qty Description Catalog Number Finish Mfr
1 EA CONT. HINGE 224XY 313AN IVE 1 EA PANIC HARDWARE LD-XP-99-EO-990 313 VON 1 EA OH STOP 100S 695 GLY 1 EA SURFACE CLOSER 4040XP EDA 695 LCN 1 EA BLADE STOP SPACER 4040XP-61 695 LCN 1 EA DOOR SWEEP 39D D ZER 1 EA THRESHOLD 545D-MSLA-10 D ZER 1 EA WEATHERSTRIP BY DOOR/FRAME MANUFACTURER
PERIMETER GASKETING BY DOOR MANUFACTURE.
HW SET NO. 09
FOR USE ON MARK/DOOR #(S): F203 Qty Description Catalog Number Finish Mfr
1 EA CONT. HINGE 224XY 313AN IVE 1 EA PANIC HARDWARE LD-XP-99-NL 313 VON 1 EA RIM CYLINDER 20-057-ICX 643e SCH 1 EA MORTISE CYLINDER 26-091-ICX XQ11-948 643e SCH 1 EA FSIC CORE 23-030 606 SCH 1 EA OH STOP 100S 695 GLY 1 EA SURFACE CLOSER 4040XP EDA 695 LCN 1 EA BLADE STOP SPACER 4040XP-61 695 LCN 1 EA DOOR SWEEP 39D D ZER 1 EA THRESHOLD 545D-MSLA-10 D ZER 1 EA WEATHERSTRIP BY DOOR/FRAME MANUFACTURER
ITEM NO. 6 SECTION 087100 DOOR HARDWARE
A. 3.3 Door Hardware Schedule add the following Hardware Set No. 38;
“HW SET NO. 38
FOR USE ON MARK/DOOR #(S): C229 C233
B. Qty Description Catalog Number Finish Mfr
6 EA HW HINGE 5BB1HW NRP 630 IVE 1 EA KEYED FIRE RATED
REMOVABLE MULLION KR9954-STAB-MT54 689 VON
2 EA FIRE EXIT HARDWARE 99-L-F-2SI-06 626 VON
PLATTVIEW JR & SR HIGH SCHOOL RENOVATIONS 10-13125-30 SPRINGFIELD PLATTEVIEW COMMUNITY SCHOOLS SPRINGFIELD, NEBRASKA
ADDENDUM NO. CC-1 CC-1 - 5
4 EA RIM CYLINDER 20-057-ICX 626 SCH 1 EA MORTISE CYLINDER 26-091-ICX 626 SCH 5 EA FSIC CORE 23-030 626 SCH 2 EA SURFACE CLOSER 4040XP EDA
(SCUSH AT LHR LEAF OF C229) 689 LCN
2 EA KICK PLATE 8400 10" X 2" LDW B4E CS 630 IVE 2 EA WALL STOP WS406/407CCV 630 IVE 1 EA GASKETING 488S-BK S-Bk ZER 1 EA MULLION SEAL 8780N N ZER 1 EA ASTRAGAL SET 8193AA AA ZER”
ITEM NO. 7 SECTION 092216 NON-STRUCTURAL METAL FRAMING
A. Subparagraph 2.2.B.1.a. Add the following;
“7) ClarkDietrich Building Systems.
8) MarionWare”
B. 2.2.C.2.a. Add the following;
“7) MarionWare”
ITEM NO. 8 SPECIFICATION SECTION 224000 – PLUMBING FIXTURES
A. Modify heading as shown on Attachment No.3.
PLATTVIEW JR & SR HIGH SCHOOL RENOVATIONS 10-13125-30 SPRINGFIELD PLATTEVIEW COMMUNITY SCHOOLS SPRINGFIELD, NEBRASKA
ADDENDUM NO. CC-1 CC-1 - 6
DRAWINGS ITEM NO. 1 DRAWING A1.1F – FLOOR PLAN, LOWER LEVEL – AREA F
A. Modify drawing as shown on Attachment A1.1F-1.
ITEM NO. 2 DRAWING A5.1 – EXTERIOR ELEVATIONS
A. Modify drawing as shown on Attachment A5.1-1.
ITEM NO. 3 DRAWING A9.1 – DOOR AND FRAME SCHEDULE
A. Modify drawing as shown on Attachment A9.1-1.
ITEM NO. 4 DRAWING A10.2 – GENERAL BUILDING DETAILS
A. Modify drawing as shown on Attachment A10.2-1.
ITEM NO. 5 DRAWING M1.1F – HVAC PLAN, LOWER LEVEL – AREA F
A. Modify drawing as shown on Attachment M1.1F-1.
ITEM NO. 6 DRAWING M1.2F – HVAC PLAN, MAIN LEVEL – AREA F
A. Modify drawing as shown on Attachment M1.2F-1.
ITEM NO. 7 DRAWING M2.1F – HVAC PIPING PLAN, LOWER LEVEL – AREA F
A. Modify drawing as shown on Attachment M2.1F-1.
ITEM NO. 8 DRAWING M2.2F – HVAC PIPING PLAN, MAIN LEVEL – AREA F
A. Modify drawing as shown on Attachment M2.2F-1.
ITEM NO. 9 DRAWING E2.1F – POWER PLAN, LOWER LEVEL – AREA F
A. Modify drawing as shown on Attachment E2.1F-1.
ITEM NO. 10 DRAWING E2.2F – POWER PLAN, MAIN LEVEL – AREA F
A. Modify drawing s shown on Attachment E2.2F-1.
ITEM NO. 11 DRAWING E3.1F – SPECIAL SYSTEMS PLAN, LOWER LEVEL – AREA F
A. Modify drawing as shown on Attachment E3.1F-1.
PLATTVIEW JR & SR HIGH SCHOOL RENOVATIONS 10-13125-30 SPRINGFIELD PLATTEVIEW COMMUNITY SCHOOLS SPRINGFIELD, NEBRASKA
ADDENDUM NO. CC-1 CC-1 - 7
ITEM NO. 12 DRAWING E3.2F – SPECIAL SYSTEMS PLAN, MAIN LEVEL – AREA F
A. Modify drawing as shown on Attachment E3.2F-1.
ITEM NO. 13 PRE-BID CONFERENCE SIGN-IN SHEET
A. Add Pre-Bid Conference Sign-In Sheet as shown on Attachment No. 4.
END OF ADDENDUM
PLATTEVIEW JR HIGH & HIGH SCHOOL RENOVATIONS 10-13125-30
SPRINGFIELD PLATTEVIEW COMMUNITY SCHOOLS BID SET
SPRINGFIELD, NEBRASKA
COLD-FORMED METAL FRAMING 054000 - 1
SECTION 054000 - COLD-FORMED METAL FRAMING
PART 1 - GENERAL
1.1 RELATED DOCUMENTS
A. Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
1.2 SUMMARY
A. Section Includes:
1. Load-bearing wall framing.
B. Related Requirements:
1. Section 055000 "Metal Fabrications" for miscellaneous steel shapes, masonry shelf
angles, and connections used with cold-formed metal framing.
2. Section 092116.23 "Gypsum Board Shaft Wall Assemblies" for interior non-load-
bearing, metal-stud-framed, shaft-wall assemblies, with height limitations.
3. Section 092216 "Non-Structural Metal Framing" for standard, interior non-load-bearing,
metal-stud framing, with height limitations and ceiling-suspension assemblies.
1.3 PREINSTALLATION MEETINGS
A. Preinstallation Conference: Conduct conference at Project site.
1.4 ACTION SUBMITTALS
A. Product Data: For each type of product.
B. Shop Drawings:
1. Include layout, spacings, sizes, thicknesses, and types of cold-formed steel framing;
fabrication; and fastening and anchorage details, including mechanical fasteners.
2. Indicate reinforcing channels, opening framing, supplemental framing, strapping,
bracing, bridging, splices, accessories, connection details, and attachment to adjoining
work.
C. Delegated-Design Submittal: For cold-formed steel framing.
Attachment No. 1, dated 09/13/17 for
Addendum CC-1
PLATTEVIEW JR HIGH & HIGH SCHOOL RENOVATIONS 10-13125-30
SPRINGFIELD PLATTEVIEW COMMUNITY SCHOOLS BID SET
SPRINGFIELD, NEBRASKA
COLD-FORMED METAL FRAMING 054000 - 2
1.5 INFORMATIONAL SUBMITTALS
A. Qualification Data: For testing agency.
B. Welding certificates.
C. Product Certificates: For each type of code-compliance certification for studs and tracks.
D. Product Test Reports: For each listed product, for tests performed by manufacturer and
witnessed by a qualified testing agency.
1. Steel sheet.
2. Expansion anchors.
3. Power-actuated anchors.
4. Mechanical fasteners.
5. Vertical deflection clips.
6. Horizontal drift deflection clips
7. Miscellaneous structural clips and accessories.
E. Evaluation Reports: For nonstandard cold-formed steel framing post-installed anchors and
power-actuated fasteners, from ICC-ES or other qualified testing agency acceptable to
authorities having jurisdiction.
1.6 QUALITY ASSURANCE
A. Testing Agency Qualifications: Qualified according to ASTM E 329 for testing indicated.
B. Product Tests: Mill certificates or data from a qualified independent testing agency indicating
steel sheet complies with requirements, including base-metal thickness, yield strength, tensile
strength, total elongation, chemical requirements, and metallic-coating thickness.
C. Welding Qualifications: Qualify procedures and personnel according to the following:
1. AWS D1.1/D1.1M, "Structural Welding Code - Steel."
2. AWS D1.3/D1.3M, "Structural Welding Code - Sheet Steel."
1.7 DELIVERY, STORAGE, AND HANDLING
A. Protect cold-formed steel framing from corrosion, moisture staining, deformation, and other
damage during delivery, storage, and handling.
B. Store cold-formed metal framing, protect with a waterproof covering, and ventilate to avoid
condensation.
PLATTEVIEW JR HIGH & HIGH SCHOOL RENOVATIONS 10-13125-30
SPRINGFIELD PLATTEVIEW COMMUNITY SCHOOLS BID SET
SPRINGFIELD, NEBRASKA
COLD-FORMED METAL FRAMING 054000 - 3
PART 2 - PRODUCTS
2.1 MANUFACTURERS
A. Manufacturers: Subject to compliance with requirements, provide products by one of the
following;
1. AllSteel & Gypsum Products, Inc.
2. ClarkDietrich Building Systems.
3. Consolidated Fabricators Corp.; Building Products Division.
4. Custom Stud Inc.
5. Formetal Co. Inc
6. Marino\WARE.
7. Steel Construction Systems
8. Steeler, Inc
9. Super Stud Building Products Inc.
10. United Metal Products, Inc
2.2 PERFORMANCE REQUIREMENTS
A. Delegated Design: Engage a qualified professional engineer, as defined in Section 014000
"Quality Requirements," to design cold-formed steel framing.
B. Structural Performance: Provide cold-formed steel framing capable of withstanding design
loads within limits and under conditions indicated.
1. Design Loads: As indicated.
2. Deflection Limits: Design framing systems to withstand design loads without deflections
greater than the following:
a. Interior Load-Bearing Wall Framing: Horizontal deflection of 1/360 of the wall
height under a horizontal load of 5 lbf/sq. ft. (239 Pa).
b. Floor Joist Framing: Vertical deflection of 1/360 for live loads and l/240 for total
loads of the span.
3. Design framing systems to provide for movement of framing members located outside
the insulated building envelope without damage or overstressing, sheathing failure,
connection failure, undue strain on fasteners and anchors, or other detrimental effects
when subject to a maximum ambient temperature change of 120 deg F (67 deg C).
C. Cold-Formed Steel Framing Standards: Unless more stringent requirements are indicated,
framing shall comply with AISI S100, AISI S200, and the following:
1. Floor and Roof Systems: AISI S210.
2. Lateral Design: AISI S213.
PLATTEVIEW JR HIGH & HIGH SCHOOL RENOVATIONS 10-13125-30
SPRINGFIELD PLATTEVIEW COMMUNITY SCHOOLS BID SET
SPRINGFIELD, NEBRASKA
COLD-FORMED METAL FRAMING 054000 - 4
2.3 COLD-FORMED STEEL FRAMING MATERIALS
A. Steel Sheet: ASTM A 1003/A 1003M, Structural Grade, Type H, metallic coated, of grade and
coating designation as follows:
1. Grade: As required by structural performance.
2. Coating: G90 (Z275) or equivalent.
2.4 INTERIOR LOAD-BEARING WALL FRAMING
A. Steel Studs: Manufacturer's standard C-shaped steel studs, of web depths indicated, punched,
with stiffened flanges, and as follows:
1. Minimum Base-Metal Thickness: 0.0428 inch (1.09 mm).
2. Flange Width: 1-5/8 inches (41 mm).
B. Steel Track: Manufacturer's standard U-shaped steel track, of web depths indicated, unpunched,
with straight flanges, and as follows:
1. Minimum Base-Metal Thickness: Matching steel studs.
2. Flange Width: .
C. Steel Box or Back-to-Back Headers: Manufacturer's standard C-shapes used to form header
beams, of web depths indicated, unpunched, with stiffened flanges, and as follows:
1. Minimum Base-Metal Thickness: 0.0428 inch (1.09 mm).
2. Flange Width: 1-5/8 inches (41 mm).
2.5 FLOOR JOIST FRAMING
A. Steel Joists: Manufacturer's standard C-shaped steel joists, of web depths indicated, punched
with standard holes, with stiffened flanges, and as follows:
1. Minimum Base-Metal Thickness: 0.0428 inch (1.09 mm).
2. Flange Width: 1-5/8 inches (41 mm), minimum.
B. Steel Joist Track: Manufacturer's standard U-shaped steel joist track, of web depths indicated,
unpunched, with unstiffened flanges, and as follows:
1. Minimum Base-Metal Thickness: Matching steel joists.
2. Flange Width: 1-1/4 inches (32 mm), minimum.
2.6 FRAMING ACCESSORIES
A. Fabricate steel-framing accessories from ASTM A 1003/A 1003M, Structural Grade, Type H,
metallic coated steel sheet, of same grade and coating designation used for framing members.
PLATTEVIEW JR HIGH & HIGH SCHOOL RENOVATIONS 10-13125-30
SPRINGFIELD PLATTEVIEW COMMUNITY SCHOOLS BID SET
SPRINGFIELD, NEBRASKA
COLD-FORMED METAL FRAMING 054000 - 5
B. Provide accessories of manufacturer's standard thickness and configuration, unless otherwise
indicated, as follows:
1. Supplementary framing.
2. Bracing, bridging, and solid blocking.
3. Web stiffeners.
4. Anchor clips.
5. End clips.
6. Foundation clips.
7. Gusset plates.
Stud kickers and knee braces.
2.7 ANCHORS, CLIPS, AND FASTENERS
A. Steel Shapes and Clips: ASTM A 36/A 36M, zinc coated by hot-dip process according to
ASTM A 123/A 123M.
B. Post-Installed Anchors: Fastener systems with bolts of same basic metal as fastened metal, if
visible, unless otherwise indicated; with working capacity greater than or equal to the design
load, according to an evaluation report acceptable to authorities having jurisdiction, based on
ICC-ES AC58 or ICC-ES AC308 as appropriate for the substrate.
1. Uses: Securing cold-formed steel framing to structure.
2. Type: adhesive anchor.
3. Material for Interior Locations: Carbon-steel components zinc plated to comply with
ASTM B 633 or ASTM F 1941 (ASTM F 1941M), Class Fe/Zn 5, unless otherwise
indicated.
4. Material for Exterior or Interior Locations and Where Stainless Steel Is Indicated: Alloy
Group 1 (A1) stainless-steel bolts, ASTM F 593 (ASTM F 738M), and nuts,
ASTM F 594 (ASTM F 836M).
C. Power-Actuated Anchors: Fastener systems with working capacity greater than or equal to the
design load, according to an evaluation report acceptable to authorities having jurisdiction,
based on ICC-ES AC70.
D. Mechanical Fasteners: ASTM C 1513, corrosion-resistant-coated, self-drilling, self-tapping,
steel drill screws.
1. Head Type: Low-profile head beneath sheathing; manufacturer's standard elsewhere.
E. Welding Electrodes: Comply with AWS standards.
2.8 MISCELLANEOUS MATERIALS
A. Galvanizing Repair Paint: ASTM A 780/A 780M.
PLATTEVIEW JR HIGH & HIGH SCHOOL RENOVATIONS 10-13125-30
SPRINGFIELD PLATTEVIEW COMMUNITY SCHOOLS BID SET
SPRINGFIELD, NEBRASKA
COLD-FORMED METAL FRAMING 054000 - 6
B. Cement Grout: Portland cement, ASTM C 150/C 150M, Type I; and clean, natural sand,
ASTM C 404. Mix at ratio of 1 part cement to 2-1/2 parts sand, by volume, with minimum
water required for placement and hydration.
C. Nonmetallic, Nonshrink Grout: Factory-packaged, nonmetallic, noncorrosive, nonstaining
grout, complying with ASTM C 1107/C 1107M, and with a fluid consistency and 30-minute
working time.
D. Shims: Load-bearing, high-density, multimonomer, nonleaching plastic; or cold-formed steel of
same grade and metallic coating as framing members supported by shims.
E. Sealer Gaskets: Closed-cell neoprene foam, 1/4 inch (6 mm) thick, selected from manufacturer's
standard widths to match width of bottom track or rim track members as required.
PART 3 - EXECUTION
3.1 EXAMINATION
A. Examine substrates, areas, conditions, and abutting structural framing for compliance with
requirements for installation tolerances and other conditions affecting performance of the Work.
B. Proceed with installation only after unsatisfactory conditions have been corrected.
3.2 PREPARATION
A. Install load-bearing shims or grout between the underside of load-bearing wall bottom track and
the top of foundation wall or slab at locations with a gap larger than 1/4 inch (6 mm) to ensure a
uniform bearing surface on supporting concrete or masonry construction.
B. Install sealer gaskets at the underside of wall bottom track or rim track and at the top of
foundation wall or slab at stud or joist locations.
3.3 INSTALLATION, GENERAL
A. Cold-formed steel framing may be shop or field fabricated for installation, or it may be field
assembled.
B. Install cold-formed steel framing according to AISI S200, AISI S202, and manufacturer's
written instructions unless more stringent requirements are indicated.
C. Install shop- or field-fabricated, cold-formed framing and securely anchor to supporting
structure.
1. Screw, bolt, or weld wall panels at horizontal and vertical junctures to produce flush,
even, true-to-line joints with maximum variation in plane and true position between
fabricated panels not exceeding 1/16 inch (1.6 mm).
PLATTEVIEW JR HIGH & HIGH SCHOOL RENOVATIONS 10-13125-30
SPRINGFIELD PLATTEVIEW COMMUNITY SCHOOLS BID SET
SPRINGFIELD, NEBRASKA
COLD-FORMED METAL FRAMING 054000 - 7
D. Install cold-formed steel framing and accessories plumb, square, and true to line, and with
connections securely fastened.
1. Cut framing members by sawing or shearing; do not torch cut.
2. Fasten cold-formed steel framing members by welding, screw fastening, clinch fastening,
or riveting. Wire tying of framing members is not permitted.
a. Comply with AWS D1.3/D1.3M requirements and procedures for welding,
appearance and quality of welds, and methods used in correcting welding work.
b. Locate mechanical fasteners, install according to Shop Drawings, and comply with
requirements for spacing, edge distances, and screw penetration.
E. Install framing members in one-piece lengths unless splice connections are indicated for track
or tension members.
F. Install temporary bracing and supports to secure framing and support loads equal to those for
which structure was designed. Maintain braces and supports in place, undisturbed, until entire
integrated supporting structure has been completed and permanent connections to framing are
secured.
G. Do not bridge building expansion joints with cold-formed steel framing. Independently frame
both sides of joints.
H. Fasten hole-reinforcing plate over web penetrations that exceed size of manufacturer's approved
or standard punched openings.
3.4 LOAD-BEARING INTERIOR WALL INSTALLATION
A. Install continuous top and bottom tracks sized to match studs. Align tracks accurately and
securely anchor at corners and ends, and at spacings as follows:
1. Anchor Spacing: As shown on Shop Drawings.
B. Squarely seat studs against top and bottom tracks, with gap not exceeding 1/8 inch (3 mm)
between the end of wall-framing member and the web of track. Fasten both flanges of studs to
top and bottom tracks. Space studs as follows:
1. Stud Spacing: 16 inches (406 mm).
C. Set studs plumb, except as needed for diagonal bracing or required for nonplumb walls or
warped surfaces and similar configurations.
D. Align studs vertically where floor framing interrupts wall-framing continuity. Where studs
cannot be aligned, continuously reinforce track to transfer loads.
E. Align floor and roof framing over studs according to AISI S200, Section C1. Where framing
cannot be aligned, continuously reinforce track to transfer loads.
PLATTEVIEW JR HIGH & HIGH SCHOOL RENOVATIONS 10-13125-30
SPRINGFIELD PLATTEVIEW COMMUNITY SCHOOLS BID SET
SPRINGFIELD, NEBRASKA
COLD-FORMED METAL FRAMING 054000 - 8
F. Anchor studs abutting structural columns or walls, including masonry walls, to supporting
structure.
G. Install headers over wall openings wider than stud spacing. Locate headers above openings.
Fabricate headers of compound shapes indicated or required to transfer load to supporting studs,
complete with clip-angle connectors, web stiffeners, or gusset plates.
1. Frame wall openings with not less than a double stud at each jamb of frame. Fasten jamb
members together to uniformly distribute loads.
2. Install tracks and jack studs above and below wall openings. Anchor tracks to jamb studs
with clip angles or by welding, and space jack studs same as full-height wall studs.
H. Install supplementary framing, blocking, and bracing in stud framing indicated to support
fixtures, equipment, services, casework, heavy trim, furnishings, and similar work requiring
attachment to framing.
1. If type of supplementary support is not indicated, comply with stud manufacturer's
written recommendations and industry standards in each case, considering weight or load
resulting from item supported.
I. Install horizontal bridging in stud system, spaced vertically as indicated on Shop Drawings.
Fasten at each stud intersection.
1. Channel Bridging: Cold-rolled steel channel, welded or mechanically fastened to webs of
punched studs with a minimum of two screws into each flange of the clip angle for
framing members up to 6 inches (150 mm) deep.
2. Strap Bridging: Combination of flat, taut, steel sheet straps of width and thickness
indicated and stud-track solid blocking of width and thickness to match studs. Fasten flat
straps to stud flanges, and secure solid blocking to stud webs or flanges.
3. Bar Bridging: Proprietary bridging bars installed according to manufacturer's written
instructions.
J. Install miscellaneous framing and connections, including supplementary framing, web
stiffeners, clip angles, continuous angles, anchors, and fasteners, to provide a complete and
stable wall-framing system.
3.5 ERECTION TOLERANCES
A. Install cold-formed steel framing level, plumb, and true to line to a maximum allowable
tolerance variation of 1/8 inch in 10 feet (1:960) and as follows:
1. Space individual framing members no more than plus or minus 1/8 inch (3 mm) from
plan location. Cumulative error shall not exceed minimum fastening requirements of
sheathing or other finishing materials.
PLATTEVIEW JR HIGH & HIGH SCHOOL RENOVATIONS 10-13125-30
SPRINGFIELD PLATTEVIEW COMMUNITY SCHOOLS BID SET
SPRINGFIELD, NEBRASKA
COLD-FORMED METAL FRAMING 054000 - 9
3.6 FIELD QUALITY CONTROL
A. Testing: Owner will engage a qualified independent testing and inspecting agency to perform
field tests and inspections and prepare test reports.
B. Field and shop welds will be subject to testing and inspecting.
C. Testing agency will report test results promptly and in writing to Contractor and Architect.
D. Cold-formed steel framing will be considered defective if it does not pass tests and inspections.
E. Additional testing and inspecting, at Contractor's expense, will be performed to determine
compliance of replaced or additional work with specified requirements.
3.7 REPAIRS AND PROTECTION
A. Galvanizing Repairs: Prepare and repair damaged galvanized coatings on fabricated and
installed cold-formed steel framing with galvanized repair paint according to
ASTM A 780/A 780M and manufacturer's written instructions.
B. Provide final protection and maintain conditions, in a manner acceptable to manufacturer and
Installer, that ensure that cold-formed steel framing is without damage or deterioration at time
of Substantial Completion.
END OF SECTION 054000
PLATTEVIEW JR HIGH & HIGH SCHOOL RENOVATIONS 10-13125-30
SPRINGFIELD PLATTEVIEW COMMUNITY SCHOOLS BID SET
SPRINGFIELD, NEBRASKA
PLASTIC PANELING 066400 - 1
SECTION 066400 - PLASTIC PANELING
PART 1 - GENERAL
1.1 RELATED DOCUMENTS
A. Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
1.2 SUMMARY
A. Section Includes:
1. Plastic sheet paneling.
B. Related Requirements:
1. Section 061053 “Miscellaneous Rough Carpentry” for wood furring for installing plastic
paneling.
1.3 ACTION SUBMITTALS
A. Product Data: For each type of product.
B. Samples: For plastic paneling and trim accessories, in manufacturer's standard sizes.
1.4 QUALITY ASSURANCE
A. Testing Agency: FM Approvals.
1.5 PROJECT CONDITIONS
A. Environmental Limitations: Do not deliver or install plastic paneling until spaces are enclosed
and weathertight and temporary HVAC system is operating and maintaining ambient
temperature and humidity conditions at occupancy levels during the remainder of the
construction period.
PART 2 - PRODUCTS
2.1 MANUFACTURERS
A. Source Limitations: Obtain plastic paneling and trim accessories from single manufacturer.
Attachment No. 2, dated 09/13/17 for
Addendum No. CC-1
PLATTEVIEW JR HIGH & HIGH SCHOOL RENOVATIONS 10-13125-30
SPRINGFIELD PLATTEVIEW COMMUNITY SCHOOLS BID SET
SPRINGFIELD, NEBRASKA
PLASTIC PANELING 066400 - 2
2.2 PLASTIC SHEET PANELING
A. Glass-Fiber-Reinforced Plastic Paneling: Gelcoat-finished, glass-fiber-reinforced plastic panels
complying with ASTM D 5319.
1. One of the following manufactures or equal
a. Crane Composites, Inc: Sequentia Flat, basis of specification
b. Glasteel
c. Marlite
d. Newcout, Inc
e. Nudo Products, Inc
f. Parkland Plastics
2. Surface-Burning Characteristics: As follows when tested by a qualified testing agency
according to ASTM E 84. Identify products with appropriate markings of applicable
testing agency.
a. Flame-Spread Index: 25 or less.
b. Smoke-Developed Index: 450 or less.
3. Nominal Thickness: Not less than 0.09 inch (2.3 mm).
4. Surface Finish: Molded pebble texture.
5. Color: White.
2.3 ACCESSORIES
A. Trim Accessories: Manufacturer's standard one-piece vinyl extrusions designed to retain and
cover edges of panels. Provide division bars, inside corners, outside corners, and caps as needed
to conceal edges.
1. Color: Match panels.
B. Exposed Fasteners: Nylon drive rivets recommended by panel manufacturer.
C. Concealed Mounting Splines: Continuous, H-shaped aluminum extrusions designed to fit into
grooves routed in edges of factory-laminated panels and to be fastened to substrate.
D. Adhesive: As recommended by plastic paneling manufacturer.
E. Sealant: Mildew-resistant, single-component, neutral-curing silicone sealant recommended by
plastic paneling manufacturer and complying with requirements in Section 079200 "Joint
Sealants."
PLATTEVIEW JR HIGH & HIGH SCHOOL RENOVATIONS 10-13125-30
SPRINGFIELD PLATTEVIEW COMMUNITY SCHOOLS BID SET
SPRINGFIELD, NEBRASKA
PLASTIC PANELING 066400 - 3
PART 3 - EXECUTION
3.1 EXAMINATION
A. Examine substrates and conditions, with Installer present, for compliance with requirements for
installation tolerances and other conditions affecting performance of the Work.
B. Proceed with installation only after unsatisfactory conditions have been corrected.
3.2 PREPARATION
A. Remove wallpaper, vinyl wall covering, loose or soluble paint, and other materials that might
interfere with adhesive bond.
B. Prepare substrate by sanding high spots and filling low spots as needed to provide flat, even
surface for panel installation.
C. Clean substrates of substances that could impair adhesive bond, including oil, grease, dirt, and
dust.
D. Condition panels by unpacking and placing in installation space before installation according to
manufacturer's written recommendations.
E. Lay out paneling before installing. Locate panel joints to provide equal panels at ends of walls
not less than half the width of full panels.
1. Mark plumb lines on substrate at trim accessory locations for accurate installation.
2. Locate trim accessories to allow clearance at panel edges according to manufacturer's
written instructions.
3.3 INSTALLATION
A. Install plastic paneling according to manufacturer's written instructions.
B. Install panels in a full spread of adhesive.
C. Install panels with fasteners. Layout fastener locations and mark on face of panels so that
fasteners are accurately aligned.
1. Drill oversized fastener holes in panels and center fasteners in holes.
2. Apply sealant to fastener holes before installing fasteners.
D. Install factory-laminated panels using concealed mounting splines in panel joints.
E. Install trim accessories with adhesive.
F. Fill grooves in trim accessories with sealant before installing panels, and bed inside corner trim
in a bead of sealant.
PLATTEVIEW JR HIGH & HIGH SCHOOL RENOVATIONS 10-13125-30
SPRINGFIELD PLATTEVIEW COMMUNITY SCHOOLS BID SET
SPRINGFIELD, NEBRASKA
PLASTIC PANELING 066400 - 4
G. Maintain uniform space between panels and wall fixtures. Fill space with sealant.
H. Maintain uniform space between adjacent panels and between panels and floors, ceilings, and
fixtures. Fill space with sealant.
I. Remove excess sealant and smears as paneling is installed. Clean with solvent recommended by
sealant manufacturer and then wipe with clean dry cloths until no residue remains.
END OF SECTION 066400
PLATTEVIEW JR HIGH & HIGH SCHOOL RENOVATIONS 10-13125-30
SPRINGFIELD PLATTEVIEW COMMUNITY SCHOOLS BID SET
SPRINGFIELD, NEBRASKA
PLUMBING FIXTURES 224000 - 1
ECTION 224000 - PLUMBING FIXTURES
PART 1 - GENERAL
1.1 RELATED DOCUMENTS
A. Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
1.2 SUMMARY
A. This Section includes the following conventional plumbing fixtures and related components:
1. Faucets for lavatories showers and sinks.
2. Flushometers.
3. Toilet seats.
4. Protective shielding guards.
5. Fixture supports.
6. Water closets.
7. Urinals.
8. Lavatories.
9. Commercial sinks.
10. Service basins.
11. Emergency Plumbing Fixtures.
12. Wash fountains.
B. Related Sections include the following:
1. Division 22 Section "Domestic Water Piping Specialties" for backflow preventers, floor
drains, and specialty fixtures not included in this Section.
2. Division 22 Section "Drinking Fountains and Water Coolers."
1.3 DEFINITIONS
A. Accessible Fixture: Plumbing fixture that can be approached, entered, and used by people with
disabilities.
B. Cast Polymer: Cast-filled-polymer-plastic material. This material includes cultured-marble and
solid-surface materials.
C. Cultured Marble: Cast-filled-polymer-plastic material with surface coating.
PLATTEVIEW JR HIGH & HIGH SCHOOL RENOVATIONS 10-13125-30
SPRINGFIELD PLATTEVIEW COMMUNITY SCHOOLS BID SET
SPRINGFIELD, NEBRASKA
PLUMBING FIXTURES 224000 - 2
D. Fitting: Device that controls the flow of water into or out of the plumbing fixture. Fittings
specified in this Section include supplies and stops, faucets and spouts, shower heads, drains
and tailpieces, and traps and waste pipes. Piping and general-duty valves are included where
indicated.
E. PVC: Polyvinyl chloride plastic.
F. Solid Surface: Nonporous, homogeneous, cast-polymer-plastic material with heat-, impact-,
scratch-, and stain-resistance qualities.
1.4 SUBMITTALS
A. Product Data: For each type of plumbing fixture indicated. Include selected fixture and trim,
fittings, accessories, appliances, appurtenances, equipment, and supports. Indicate materials
and finishes, dimensions, construction details, and flow-control rates.
B. Shop Drawings: Diagram power, signal, and control wiring.
C. Operation and Maintenance Data: For plumbing fixtures to include in emergency, operation,
and maintenance manuals.
D. Warranty: Special warranty specified in this Section.
1.5 QUALITY ASSURANCE
A. Source Limitations: Obtain plumbing fixtures, faucets, and other components of each category
through one source from a single manufacturer.
1. Exception: If fixtures, faucets, or other components are not available from a single
manufacturer, obtain similar products from other manufacturers specified for that
category.
B. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70,
Article 100, by a testing agency acceptable to authorities having jurisdiction, and marked for
intended use.
C. Regulatory Requirements: Comply with requirements in ICC A117.1, "Accessible and Usable
Buildings and Facilities"; Public Law 90-480, "Architectural Barriers Act"; and Public
Law 101-336, "Americans with Disabilities Act"; for plumbing fixtures for people with
disabilities.
D. Regulatory Requirements: Comply with requirements in Public Law 102-486, "Energy Policy
Act," about water flow and consumption rates for plumbing fixtures unless the requirements of
this specification are more restrictive.
E. NSF Standard: Comply with NSF 61, "Drinking Water System Components--Health Effects,"
for fixture materials that will be in contact with potable water.
PLATTEVIEW JR HIGH & HIGH SCHOOL RENOVATIONS 10-13125-30
SPRINGFIELD PLATTEVIEW COMMUNITY SCHOOLS BID SET
SPRINGFIELD, NEBRASKA
PLUMBING FIXTURES 224000 - 3
F. Select combinations of fixtures and trim, faucets, fittings, and other components that are
compatible.
G. Comply with the following applicable standards and other requirements specified for plumbing
fixtures:
1. Stainless-Steel Commercial, Handwash Sinks: NSF 2 construction.
2. Vitreous-China Fixtures: ASME A112.19.2M.
3. Water-Closet, Flush Valve, Tank Trim: ASME A112.19.5.
4. LEAD FREE: The wetted surfaces of potable / domestic water valves shall contain no
more than 0.25% lead by weighted average to comply with CA AB1953, VT Act 193,
MD HB372, LA HB471 and Federal Public Law 111-380.
a. All potable water products shall comply with the Federal Safe Drinking Water Act
– Public Law No. 111-380 and shall be ANSI 3rd Party Certified Lead Free.
b. All potable water products shall comply with NSF/ANSI Standard 372 (Drinking
Water System Components, Lead Content).
H. Comply with the following applicable standards and other requirements specified for lavatory
and sink faucets:
1. Backflow Protection Devices for Faucets with Hose-Thread Outlet: ASME A112.18.3M.
2. Diverter Valves for Faucets with Hose Spray: ASSE 1025.
3. Faucets: ASME A112.18.1.
4. Hose-Connection Vacuum Breakers: ASSE 1011.
5. Hose-Coupling Threads: ASME B1.20.7.
6. Integral, Atmospheric Vacuum Breakers: ASSE 1001.
7. NSF Potable-Water Materials: NSF 61.
8. Pipe Threads: ASME B1.20.1.
9. Sensor-Actuated Faucets and Electrical Devices: UL 1951.
10. Supply Fittings: ASME A112.18.1.
11. Brass Waste Fittings: ASME A112.18.2.
I. Comply with the following applicable standards and other requirements specified for shower
faucets:
1. Backflow Protection Devices for Hand-Held Showers: ASME A112.18.3M.
2. Combination, Pressure-Equalizing and Thermostatic-Control Antiscald Faucets:
ASSE 1016.
3. Faucets: ASME A112.18.1.
4. Hand-Held Showers: ASSE 1014.
5. High-Temperature-Limit Controls for Thermal-Shock-Preventing Devices: ASTM F 445.
6. Hose-Coupling Threads: ASME B1.20.7.
7. Pipe Threads: ASME B1.20.1.
8. Pressure-Equalizing-Control Antiscald Faucets: ASTM F 444 and ASSE 1016.
9. Thermostatic-Control Antiscald Faucets: ASTM F 444 and ASSE 1016.
PLATTEVIEW JR HIGH & HIGH SCHOOL RENOVATIONS 10-13125-30
SPRINGFIELD PLATTEVIEW COMMUNITY SCHOOLS BID SET
SPRINGFIELD, NEBRASKA
PLUMBING FIXTURES 224000 - 4
J. Comply with the following applicable standards and other requirements specified for
miscellaneous fittings:
1. Atmospheric Vacuum Breakers: ASSE 1001.
2. Brass and Copper Lead free supplies: ASME A112.18.1.
3. Brass Waste Fittings: ASME A112.18.2.
4. Sensor-Operation Flushometers: ASSE 1037 and UL 1951.
K. Comply with the following applicable standards and other requirements specified for
miscellaneous components:
1. Flexible Water Connectors: ASME A112.18.6.
2. Floor Drains: ASME A112.6.3.
3. Hose-Coupling Threads: ASME B1.20.7.
4. Off-Floor Fixture Supports: ASME A112.6.1M.
5. Pipe Threads: ASME B1.20.1.
6. Plastic Toilet Seats: ANSI Z124.5.
7. Supply and Drain Protective Shielding Guards: ICC A117.1.
1.6 WARRANTY
A. Warranty Period for Commercial Applications: One year from date of Substantial Completion.
PART 2 - PRODUCTS
2.1 LAVATORY FAUCETS
A. Manufacturers: Subject to compliance with requirements, provide products by one of the
following:
1. American Standard Companies, Inc.
2. Chicago Faucets.
3. Kohler Co.
4. Moen, Inc.
5. Symmons Industries, Incorporated.
B. Description: Single-control mixing or two-handle mixing valve. Include hot- and cold-water
indicators; coordinate faucet inlets with supplies and fixture holes; coordinate outlet with spout
and fixture receptor.
1. Provide lavatory faucets as specified with lavatories in this Section.
2.2 INDIVIDUAL SHOWER VALVES
A. Manufacturers Shower Valves: Subject to compliance with requirements, provide products by
one of the following:
PLATTEVIEW JR HIGH & HIGH SCHOOL RENOVATIONS 10-13125-30
SPRINGFIELD PLATTEVIEW COMMUNITY SCHOOLS BID SET
SPRINGFIELD, NEBRASKA
PLUMBING FIXTURES 224000 - 5
1. American Standard Companies, Inc.
2. Eljer.
3. Kohler Co.
4. Moen, Inc.
5. Lawler Manufacturing Company Incorporated.
6. Symmons Industries, Inc.
7. Zurn Plumbing Products Group; AquaSpec Commercial Faucet Operation.
8. Powers, a Division of Watts Water Technologies, Inc.
B. Description, SH-1: Individual Adjustable Showerhead and Valve.
1. Shower Valve: Chrome finish, Symmons Model S-9601-P-X-CHKS-1.5-VP, "Temptrol"
pressure balancing mixing valve with lever handle and hand shower.
a. Provide with integral service stops (-X) and check stops (-CHKS) with integral
volume control.
2. Showerhead: Symmons Clear-Flo with 1.5 gpm (5.7 L/min) flow rate restrictor.
3. Lead free supplies: NPS 1/2 (DN 15) copper tubing.
4. Maximum Flow Rate: 1.5 gpm.
5. Diverter Valve: Not Applicable.
6. Mounting: Concealed.
7. Antiscald Device: Integral with mixing valve.
8. Check Stops: Check-valve type, integral with or attached to body; on hot- and cold-water
supply connections.
C. Description, SH-2: Individual Adjustable Showerhead and Valve, ADA Compliant.
1. Shower Valve: Chrome finish, Symmons Model 9605-PLR-X-CHKS-1.5-VP,
"Temptrol" pressure balancing mixing valve with lever handle and hand shower.
a. Provide with integral service stops (-X) and check stops (-CHKS) with integral
volume control.
2. Provide a hand held shower spray with 60-inch stainless steel flexible hose and 30 inch
spray adjusting slide bar.
3. Showerhead: Symmons EF-101 hand shower wand with 1.5 gpm (5.7 L/min) flow rate
restrictor.
4. Provide with inline backflow preventer with quick disconnect.
5. Lead free supplies: NPS 1/2 (DN 15) copper tubing.
6. Maximum Flow Rate: 1.5 gpm.
7. Diverter Valve: Separate two function valve.
8. Mounting: Concealed.
9. Antiscald Device: Integral with mixing valve.
10. Check Stops: Check-valve type, integral with or attached to body; on hot- and cold-water
supply connections.
PLATTEVIEW JR HIGH & HIGH SCHOOL RENOVATIONS 10-13125-30
SPRINGFIELD PLATTEVIEW COMMUNITY SCHOOLS BID SET
SPRINGFIELD, NEBRASKA
PLUMBING FIXTURES 224000 - 6
2.3 SINK FAUCETS
A. Manufacturers: Subject to compliance with requirements, provide products by one of the
following:
1. American Standard Companies, Inc.
2. Chicago Faucets.
3. Kohler Co.
4. Moen, Inc.
5. Symmons Industries, Inc.
B. Provide faucets as specified with fixtures in this Section.
2.4 FLUSHOMETERS
A. Manufacturers: Subject to compliance with requirements, provide products by one of the
following:
1. Moen, Inc.
2. Sloan Valve Company.
3. Zurn Plumbing Products Group; Commercial Brass Operation.
B. Provide flushometers as specified with fixtures in this Section.
2.5 TOILET SEATS
A. Manufacturers: Subject to compliance with requirements, provide products by one of the
following:
1. Centoco.
2. Church Seats.
3. Olsonite Corp.
4. Sanderson Plumbing Products, Inc.; Beneke Div.
B. Provide toilet seats as specified with fixtures in this Section.
2.6 PROTECTIVE SHIELDING GUARDS
A. Manufacturers: Subject to compliance with requirements, provide products by one of the
following:
1. Engineered Brass Co.
2. McGuire Manufacturing.
3. Plumberex Specialty Products Inc.
4. TRUEBRO, Inc.
5. Zurn Plumbing Products Group; Tubular Brass Plumbing Products Operation.
PLATTEVIEW JR HIGH & HIGH SCHOOL RENOVATIONS 10-13125-30
SPRINGFIELD PLATTEVIEW COMMUNITY SCHOOLS BID SET
SPRINGFIELD, NEBRASKA
PLUMBING FIXTURES 224000 - 7
B. Description: Manufactured plastic wraps for covering plumbing fixture hot- and cold-water
supplies and trap and drain piping. Comply with Americans with Disabilities Act (ADA)
requirements.
2.7 FIXTURE SUPPORTS
A. Manufacturers: Subject to compliance with requirements, provide products by one of the
following:
1. Josam Company.
2. Smith, Jay R. Mfg. Co.
3. Tyler Pipe; Wade Div.
4. Zurn Plumbing Products Group; Specification Drainage Operation.
B. Provide fixture supports as specified with fixtures in this Section.
2.8 WASTE FITTINGS, SUPPLIES AND STOPS
A. Manufacturers: Subject to compliance with requirements, provide products from the following:
1. Brasscraft.
2. Dearborn.
3. McGuire.
4. Wolverine Brass.
2.9 WATER CLOSETS
A. Manufacturers: Subject to compliance with requirements, provide products by one of the
following:
1. American Standard Companies, Inc.
2. Kohler Co.
3. TOTO USA, Inc.
4. Zurn Industries.
B. Description (WC-1): Wall-mounting, back-outlet, vitreous-china fixture designed for
flushometer valve operation.
1. Bowl Type: Elongated with siphon-jet design.
2. Design Consumption: 1.28 gal./flush (4.8 L/flush).
3. Color: White.
4. Model: American Standard “Afwall FloWise” 3351.001.
5. Flushometer: Sloan Royal Optima Smooth Model 111-1.28.
a. Battery-Operation
b. Mechanical Manual Override
PLATTEVIEW JR HIGH & HIGH SCHOOL RENOVATIONS 10-13125-30
SPRINGFIELD PLATTEVIEW COMMUNITY SCHOOLS BID SET
SPRINGFIELD, NEBRASKA
PLUMBING FIXTURES 224000 - 8
1) Ability to operate without power
6. Toilet Seat: Church 9500SSC, white.
7. Fixture Support: Jay R. Smith 0210Y carrier for single or double horizontal installation;
Jay R. Smith 0230Y, 0240Y or 0250Y carrier for single or double vertical installation;
Jay R. Smith 0209Y carrier for single horizontal back-to-back installation with urinal.
C. Description (WC-2):
1. Same as WC-1, except mounted at ADA height.
D. Description (WC-3):
1. Same as WC-1, except mounted at middle school height.
E. Description (WC-4):
1. Same as WC-1, except mounted at middle school ADA height.
2.10 URINALS
A. Manufacturers: Subject to compliance with requirements, provide products by one of the
following:
1. American Standard Companies, Inc.
2. Kohler Co.
3. TOTO USA, Inc.
4. Zurn Industries.
B. Description (UR-1): Wall-mounting, back-outlet, vitreous-china fixture designed for
flushometer valve operation.
1. Type: Washout flush action.
2. Strainer or Trapway: Integral trap.
3. Design Consumption: 0.125 gal./flush.
4. Color: White.
5. Fixture Model: American Standard “Washbrook FloWise” 6590.001
6. Supply Spud Size: NPS 3/4 (DN 20) Top Spud Inlet.
7. Outlet Size: NPS 2 (DN 50).
8. Flushometer Model: Sloan Royal Optima 186-0.125.
a. Battery-Operated
b. Mechanical Manual Override
1) Ability to operate without power.
9. Fixture Support: Jay R. Smith 0617 carrier.
PLATTEVIEW JR HIGH & HIGH SCHOOL RENOVATIONS 10-13125-30
SPRINGFIELD PLATTEVIEW COMMUNITY SCHOOLS BID SET
SPRINGFIELD, NEBRASKA
PLUMBING FIXTURES 224000 - 9
C. Description (UR-2):
1. Same as UR-1, except mounted at ADA height.
2.11 LAVATORIES
A. Manufacturers: Subject to compliance with requirements, provide products by one of the
following:
1. American Standard Companies, Inc.
2. Briggs Plumbing Products, Inc.
3. Crane Plumbing, L.L.C./Fiat Products.
4. Eljer.
5. Gerber Plumbing Fixtures LLC.
6. Kohler Co.
7. TOTO USA, Inc.
B. Description (L-1): Accessible, wall-mounting, vitreous china fixture.
1. Model: American Standard “Lucerne” 0356.421.
2. Size: 20 by 18 inches.
3. Faucet Hole Punching: Single hole.
4. Color: White.
5. Faucet: Sloan Optima EFX250, deck mounted, sensor activated electronic faucet.
a. 0.5 GPM vandal resistant flow control, below deck mechanical mixing valve.
b. Battery-Operation
c. Above deck control access.
6. Supplies: NPS 1/2 copper pipe with shut-off valves located upstream of thermostatic
mixing valve.
7. Drain: Integral drain, no grid required.
8. Drain Piping: NPS 1-1/4 (DN 32), 17 gauge, chrome-plated, cast-brass P-trap.
a. Truebro or equal protective pipe covers for P-trap, two angle valves and waste arm
tailpiece extensions. White in color.
9. Fixture Supports: Jay R. Smith 0700 carrier.
C. Description (L-2): Accessible, wall-mounting, vitreous-china fixture ADA compliant.
1. Lavatory L-2 shall be identical to L-1 except mounted at ADA height.
D. Description (L-3): Accessible, wall-mounting, vitreous-china fixture ADA compliant.
1. Lavatory L-3 shall be identical to L-1 except mounted at middle school height.
E. Description (L-4): Accessible, wall-mounting, vitreous-china fixture ADA compliant.
PLATTEVIEW JR HIGH & HIGH SCHOOL RENOVATIONS 10-13125-30
SPRINGFIELD PLATTEVIEW COMMUNITY SCHOOLS BID SET
SPRINGFIELD, NEBRASKA
PLUMBING FIXTURES 224000 - 10
1. Lavatory L-4 shall be identical to L-1 except mounted at middle school ADA height.
2.12 COMMERCIAL SINKS
A. COUNTER SINK (SINGLE COMPARTMENT, CAST EPOXY RESIN), CS-1
1. Manufacturer: By casework manufacture, see Section 123210.
2. Model: By casework manufacture, see Section 123210.
3. Size: By casework manufacture, see Section 123210.
4. Color: By casework manufacture, see Section 123210.
5. Trim: By casework manufacture, see Section 123210.
6. Grid strainer by casework manufacture, see Section 123210.
7. Provide 1-1/2-inch acid waste P-trap and tail piece per Section 226650.
8. Lead free supplies: NPS ½ (DN 40) chrome-plated copper with McGuire LFST010LK
½” nom compression x ½” OD compression with loose key.
B. COUNTER SINK (ADA COMPLIANT SINGLE COMPARTMENT, CAST EPOXY RESIN),
CS-2
1. Manufacturer: By casework manufacture, see Section 123210.
2. Model: By casework manufacture, see Section 123210.
3. Size: By casework manufacture, see Section 123210.
4. Color: By casework manufacture, see Section 123210.
5. Trim: By casework manufacture, see Section 123210.
6. Grid strainer by casework manufacture, see Section 123210.
7. Provide 1-1/2-inch acid waste P-trap and tail piece per Section 226650.
8. Lead free supplies: NPS ½ (DN 40) chrome-plated copper with McGuire LFST010LK
½” nom compression x ½” OD compression with loose key.
C. Manufacturers: Subject to compliance with requirements, provide products by one of the
following:
1. Advance Tabco.
2. Elkay Manufacturing Co.
3. Just Manufacturing Company.
4. Moen, Inc.
D. Description, CS-3: ADA compliant, Single compartment, counter-mounting, stainless-steel
commercial sink.
1. Overall Dimensions: 22 inches x 19-1/2 inches x 5-1/2-inch.
2. Metal Thickness: 18 gage.
3. Each Compartment:
a. Dimensions: 18 inches x 14 inches x 5-1/2-inch.
b. Drains: Provide with Elkay LK-99 Type 304 stainless steel body and removable
conical basket strainer with metal ball bearing locking stem and rubber stopper
with NPS 1-1/2 (DN 40) tailpiece.
PLATTEVIEW JR HIGH & HIGH SCHOOL RENOVATIONS 10-13125-30
SPRINGFIELD PLATTEVIEW COMMUNITY SCHOOLS BID SET
SPRINGFIELD, NEBRASKA
PLUMBING FIXTURES 224000 - 11
1) Location: Off-Centered Rear.
c. Sink undercoating to dampen sound and prevent condensation.
4. Faucet: Chicago Faucets model 895-317 RGD 1E35ABCP lead free deck mounted 4-inch
center, two hole, dual handle, top mount commercial faucet with 4 inch indexed wrist
blades handles, 3-1/2 inch rigid gooseneck spout with 1.5 GPM restricted flow aerator.
a. Number Required: One.
b. Mounting: Deck.
5. Lead free supplies: NPS 1/2 (DN 15) chrome-plated copper with McGuire LFST010LK,
½” nom compression x ½” OD compression with loose key.
6. Drain Piping: McGuire 8912. Chrome plated NPS 1-1/2 (DN 40), cast-brass P-trap with
cleanout; end outlet waste connection; 17 gauge tubular brass waste to wall; and wall
escutcheon(s). Drain shall be located off-centered rear.
7. Basis of Design: Elkay LRAD2219 with 2 faucet holes. Provide hole configuration #2 for
the faucet.
2.13 SERVICE BASINS
A. Manufacturers: Subject to compliance with requirements, provide products by one of the
following:
1. Crane Plumbing, L.L.C./Fiat Products.
2. Mustee.
3. Stern-Williams Co., Inc.
B. Description, MS-1: Flush-to-wall, floor-mounting, precast terrazzo fixture with rim guard.
1. Model: Fiat TSB 100 or equal.
2. Shape: Square.
3. Size: 24 by 24 inches (610 by 610 mm).
4. Height: 12 inches (305 mm).
5. Tiling Flange: Not required.
6. Rim Guard: On all top surfaces.
7. Color: Not applicable.
8. Faucet: Lead free polished chrome-plated cast brass 8-inch sink faucet with quarter turn
ceramic disc cartridges, 3/8-inch short swivel inlets providing adjustable centers from 7-
1/4-inch to 8-3/4-inch, integral service stops and a 6-inch centerline cast brass spout with
chemical resistant atmospheric vacuum breaker, 3/4-inch hose threaded outlet, pail hook,
check stops, hot/cold text indexes, wall hook and adjustable wall brace.
a. Basis of Design: Zurn AquaSpec Z843M1-XL-CS-HCT-WHK.
9. Drain: Fiat 1453-BB flat stainless steel strainer with NPS 3 (DN 80) outlet.
10. Accessories: Fiat 832-AA hose and hose bracket.
11. Accessories: Fiat 889 CC - Mop Bracket, 24" long x 3" wide, stainless steel with three
(3) rubber grips.
PLATTEVIEW JR HIGH & HIGH SCHOOL RENOVATIONS 10-13125-30
SPRINGFIELD PLATTEVIEW COMMUNITY SCHOOLS BID SET
SPRINGFIELD, NEBRASKA
PLUMBING FIXTURES 224000 - 12
2.14 COMBINATION EMERGENCY SHOWER & EYEWASH UNITS
A. Manufacturers: Subject to compliance with requirements, provide products by one of the
following:
1. Bradley Corporation.
2. Guardian Equipment Co.
3. Haws Corporation.
4. Speakman Company.
B. Description EEWS-1: Barrier Free Combination shower and eyewash.
1. Basis of Design: Haws Model 8356WCC
2. Construction: 18 Gauge Type 304 Stainless Steel recessed cabinet is a deep-drawn heavy
duty structure with smudge resistant bead blast finish to provide a durable, long lasting
product.
3. Accessibility: Pull-down design accommodates all users including wheelchair
accessibility.
4. Shower Head: AXION MSR stainless steel showerhead uses a hydrodynamic design to
give equal distribution of water throughout the entire footprint of flow.
5. Eye/Face Wash: AXION MSR eye/face wash head uses an inverted directional laminar
flow to sweep contaminants away from the vulnerable nasal cavity.
6. Piping: Unit shall also include brass pipe and fittings, a drain pan, a front-access
maintenance panel, universal sign, 1" NPT(F) inlet and 2" NPT(F) drain. Operating
pressure is 30 - 90 psi (2.1 - 6.2 bar).
7. Options: Provide the following options:
a. Model SP170 waterproof test card.
b. Model SP178LG large vertical universal combination emergency shower and
eyewash sign.
2.15 WASH FOUNTAINS
A. Manufacturers: Subject to compliance with requirements, provide products by one of the
following:
1. Bradley Corporation.
2. Intersan Manufacturing Co.
3. Sloan.
4. Willoughby.
PLATTEVIEW JR HIGH & HIGH SCHOOL RENOVATIONS 10-13125-30
SPRINGFIELD PLATTEVIEW COMMUNITY SCHOOLS BID SET
SPRINGFIELD, NEBRASKA
PLUMBING FIXTURES 224000 - 13
PART 3 - EXECUTION
3.1 EXAMINATION
A. Examine roughing-in of water supply and sanitary drainage and vent piping systems to verify
actual locations of piping connections before plumbing fixture and emergency plumbing fixture
installation.
B. Examine cabinets, counters, floors, and walls for suitable conditions where fixtures will be
installed.
C. Proceed with installation only after unsatisfactory conditions have been corrected.
3.2 INSTALLATION
A. Assemble plumbing fixtures, trim, fittings, and other components according to manufacturers'
written instructions.
B. Install off-floor supports, affixed to building substrate, for wall-mounting fixtures.
1. Use carrier supports with waste fitting and seal for back-outlet fixtures.
2. Use carrier supports without waste fitting for fixtures with tubular waste piping.
3. Use chair-type carrier supports with rectangular steel uprights for accessible fixtures.
C. Install back-outlet, wall-mounting fixtures onto waste fitting seals and attach to supports.
D. Install wall-mounting fixtures with tubular waste piping attached to supports.
E. Install counter-mounting fixtures in and attached to casework.
F. Install fixtures level and plumb according to roughing-in drawings.
G. Install water-supply piping with stop on each supply to each fixture to be connected to water
distribution piping. Attach supplies to supports or substrate within pipe spaces behind fixtures.
Install stops in locations where they can be easily reached for operation.
1. Exception: Use ball, gate, or globe valves if supply stops are not specified with fixture.
Valves are specified in Division 22 Section "General-Duty Valves for Plumbing Piping."
H. Install trap and tubular waste piping on drain outlet of each fixture to be directly connected to
sanitary drainage system.
I. Install tubular waste piping on drain outlet of each fixture to be indirectly connected to drainage
system.
J. Install flushometer valves for accessible water closets and urinals with handle mounted on wide
side of compartment. Install other actuators in locations that are easy for people with
disabilities to reach.
PLATTEVIEW JR HIGH & HIGH SCHOOL RENOVATIONS 10-13125-30
SPRINGFIELD PLATTEVIEW COMMUNITY SCHOOLS BID SET
SPRINGFIELD, NEBRASKA
PLUMBING FIXTURES 224000 - 14
K. Install toilet seats on water closets.
L. Install faucet flow-control fittings with specified flow rates and patterns in faucet spouts if
faucets are not available with required rates and patterns. Include adapters if required.
M. Install shower flow-control fittings with specified maximum flow rates in shower arms.
N. Install traps on fixture outlets.
1. Exception: Omit trap on fixtures with integral traps.
2. Exception: Omit trap on indirect wastes, unless otherwise indicated.
O. Install escutcheons at piping wall ceiling penetrations in exposed, finished locations and within
cabinets and millwork. Use deep-pattern escutcheons if required to conceal protruding fittings.
Escutcheons are specified in Division 22 Section "Escutcheons for Plumbing Piping."
P. Set service basins in leveling bed of cement grout. Grout is specified in Division 22 Section
"Hangers and Supports for Plumbing Piping and Equipment."
Q. Seal joints between fixtures and walls, floors, and countertops using sanitary-type, one-part,
mildew-resistant silicone sealant. Match sealant color to fixture color. Sealants are specified in
Division 07 Section "Interior Joint Sealants."
R. Install sensor operated flush valves per manufacturer’s instructions. Provide required AC
adapters, wire leads, insulation displacement connectors, dual strand 18 ga. wire, wire nuts and
accessories, as needed for a complete and functioning system. Coordinate location of duplex
electrical outlets with electrical contractor.
3.3 EMERGENCY PLUMBING FIXTURE INSTALLATION
A. Assemble emergency plumbing fixture piping, fittings, control valves, and other components.
B. Install fixtures level and plumb.
C. Fasten fixtures to substrate.
D. Install shutoff valves in water-supply piping to fixtures. Use ball, gate, or globe valve if
specific type valve is not indicated. Install valves chained or locked in open position if
permitted. Install valves in locations where they can easily be reached for operation. Comply
with requirements for valves specified in Division 22 Section "General-Duty Valves for
Plumbing Piping."
1. Exception: Omit shutoff valve on supply to emergency equipment if prohibited by
authorities having jurisdiction.
E. Install dielectric fitting in supply piping to emergency equipment if piping and equipment
connections are made of different metals. Comply with requirements for dielectric fittings
specified in Division 22 Section "Domestic Water Piping."
PLATTEVIEW JR HIGH & HIGH SCHOOL RENOVATIONS 10-13125-30
SPRINGFIELD PLATTEVIEW COMMUNITY SCHOOLS BID SET
SPRINGFIELD, NEBRASKA
PLUMBING FIXTURES 224000 - 15
F. Install trap and waste piping on drain outlet of emergency equipment receptors that are
indicated to be directly connected to drainage system. Comply with requirements for waste
piping specified in Division 22 Section "Sanitary Waste and Vent Piping."
G. Install indirect waste piping on drain outlet of emergency equipment receptors that are indicated
to be indirectly connected to drainage system. Comply with requirements for waste piping
specified in Division 22 Section "Sanitary Waste and Vent Piping."
H. Install escutcheons on piping wall and ceiling penetrations in exposed, finished locations.
Comply with requirements for escutcheons specified in Division 22 Section "Escutcheons for
Plumbing Piping."
3.4 CONNECTIONS
A. Piping installation requirements are specified in other Division 22 Sections. Drawings indicate
general arrangement of piping, fittings, and specialties.
B. Connect fixtures with water supplies, stops, and risers, and with traps, soil, waste, and vent
piping. Use size fittings required to match fixtures.
C. Ground equipment according to Division 26 Section "Grounding and Bonding."
D. Connect hot- and cold-water-supply piping to hot- and cold-water, water-tempering equipment.
Connect output from water-tempering equipment to emergency plumbing fixtures. Comply
with requirements for hot- and cold-water piping specified in Division 22 Section "Domestic
Water Piping."
3.5 FIELD QUALITY CONTROL
A. Verify that installed plumbing fixtures are categories and types specified for locations where
installed.
B. Check that plumbing fixtures are complete with trim, faucets, fittings, and other specified
components.
C. Inspect installed plumbing fixtures for damage. Replace damaged fixtures and components.
D. Test installed fixtures after water systems are pressurized for proper operation. Replace
malfunctioning fixtures and components, then retest. Repeat procedure until units operate
properly.
3.6 ADJUSTING
A. Operate and adjust faucets and controls. Replace damaged and malfunctioning fixtures, fittings,
and controls.
B. Adjust water pressure at faucets and flushometer valves to produce proper flow and stream.
PLATTEVIEW JR HIGH & HIGH SCHOOL RENOVATIONS 10-13125-30
SPRINGFIELD PLATTEVIEW COMMUNITY SCHOOLS BID SET
SPRINGFIELD, NEBRASKA
PLUMBING FIXTURES 224000 - 16
C. Replace washers and seals of leaking and dripping faucets and stops.
D. Install fresh batteries in sensor-operated mechanisms.
3.7 CLEANING
A. Clean fixtures, faucets, and other fittings with manufacturers' recommended cleaning methods
and materials. Do the following:
1. Remove faucet spouts and strainers, remove sediment and debris, and reinstall strainers
and spouts.
2. Remove sediment and debris from drains.
B. After completing installation of exposed, factory-finished fixtures, faucets, and fittings, inspect
exposed finishes and repair damaged finishes.
3.8 PROTECTION
A. Provide protective covering for installed fixtures and fittings.
B. Do not allow use of plumbing fixtures for temporary facilities unless approved in writing by
Owner.
END OF SECTION 224000
UP
UP
A5.132
A5.1
A5.1
A5.1
12
52
42
A
A
B
B
C
C
D
D
E
E
F
F
G
G
H
H
J
J
K
K
1
2
3
4 5
6
7
8
9
10
11
BOYS
F105
GIRLS
F106
ELECTRICAL
F104
MECHANICAL
F103
VEST
F124
STORAGE
F122
MEDIA CENTER
F121
COMPUTER LAB
F108
CLASSROOM
F110
CLASSROOM
F120
CLASSROOM
F117
CLASSROOM
F119
CLASSROOM
F118
SCIENCE
F111
CONFERENCEROOM
F115
DATA
F113
CUSTODIAL
F102
STORAGE
F114
SMOKE CURTAIN
STAIR
F1S2
CORRIDOR
F101
CORRIDOR
F116
CORRIDOR
107
F110
F120
F117
F119
F118
F115
F103
F102
F113
F105
F106
F116
F121
A2.1
21
LIFT
8' MMBD
6' MBD 8' MMBD
6' MBD 8' MMBD
8' M
BD
8' M
MB
D
8' M
MB
D8'
MB
D
8' MMBD 4' MBD
8' MBD8' MMBD
4' MBD
6' MBD
4' MBD
CLASSROOM
F109
RAMP/STAIR
F1S1
GREEN ROOM
F123
4' MBD
6' M
BD
6' MBD
8' M
BD
4' MBD 8' MMBD 8' MBD
8' MBD
8' M
BD
4' M
BD
4' M
BD
4' M
BD
4' TBD (NIC)
26/ A11.1
26/ A11.1
26/ A11.1
26/ A11.1
26/ A11.1
A11.1
53
54
A11.1 55
56
A11.1
31
14' -
8"
3' -
4"
1' -
0"
3' -
4"
10' -
8"
6' - 5" 22' - 11 5/8" 22' - 10 3/8" 6' - 5" 27' - 9 1/4"
27' -
10"
14' - 9"
3' - 4"
31' -
8"
36' -
8"
26' -
10"
EWC-1
8' - 0" 12' - 8"
32' -
8"
18' -
4"
2' -
10"
26' -
6 5
/16"
1' -
4"
6' -
4"
24' -
0"
6' -
4"
A11.135 36
11/ A11.2
F108
F109
F122
F123
TV(NIC)
F111
F111A
F114
E
E
F
F
G
G
EWC-2
32
AQUA TANK(NIC)
F107
F124
TYP. FIN. FL.100' - 0"
18' - 4" 4' - 2" 1' - 1" 21' - 1" 1' - 2"
A12.1 11
7' - 4" 23' - 0" 3' - 6"
35
A7.1
2' -
10"
2' - 10" 7' - 4"
1' - 6"
2' -
10"
7' -
0"
4' - 0"
6' M
BD
4' T
BD
4' M
BD
FE
FEC
FEC
FEC
51
A7.1
53
A7.1
C
C
C
C
C
C
C
C
C
C
FD
FD
FD
FD
2' -
2"
A-1
A-1
A-1 A-1
A-1A-1
A
A
A A A A A A A A A A A A A A A A A A A A A A A A A
AAAAAAAAAAAAAAAAAAAAA
A8.1
32
NEW CONCRETETOPPING OVEREXISING STR STOOP
NEW CONCRETETOPPING OVEREXISING STR STOOP
NEW CONCRETETOPPING OVEREXISING STR STOOP
22
A9.2
A9.2
11
A9.2
12
26/ A11.1
3' - 0"
3' -
0"
24"W x 72"H ACCESSPANEL, BOTT 6" AFF
VE
ND
(NIC
)
A10.1
46
A10.1
54
TYP
32
A7.1
33
A7.1
J
F1
F1 F1
F1 F1
F1
J
F1
J
KJ
J
F1
F1
F1
FM B B
M
F1
B
B
B
BB
E
F1
F1
F1
F1
J
F1
N
N
F1
E
N
E1
E1
N
E1
23
A10.2
PRECAST CAP, ALIGN JOINTSWITH GUARDRAIL POST ANDEQ DISTANCE BETWEENGUARDRAIL POST
B
CG
CG
CGCG
CGCG CG CG CG
CGCG CG
CG
CG
CG
J
ALIGN WITH WALLWITH WINDOW JAMB
GOGGLESCABINET
8' - 6"
CANE DETECTION RAILUNDER STAIRS, SEEDETAIL 55/A10.2
FIRE PUMPROOM
F103A
F103A
8' -
0"
8' - 0"
HOUSEKEEPING PADCOORDINATE SIZEWITH MECHANICAL
FD
A
E
E
A10.1
15
TYP
2' - 0"
1' -
9"
Arc
hite
ctu
re E
ngin
eering
P
lan
nin
g In
teriors
©
,
DL
R G
rou
p inc., a
Ne
bra
ska
co
rpo
ratio
n, A
LL
RIG
HT
S R
ES
ER
VE
D
KEY PLAN
A
NO
RT
H
Rev
isio
ns
B
C
D
E
F
9/1
2/2
017 4
:23:2
9 P
M
C:\R
evit\1
0-1
3125-3
0_A
R_2016_C
entr
al_
jlim
bach.r
vt
10-1
3125-3
0
8/2
9/2
017
PLA
TT
EV
IEW
JR
HIG
H &
HIG
H S
CH
OO
L R
EN
OV
AT
ION
S
FLO
OR
PLA
N, LO
WE
R L
EV
EL -
AR
EA
FA1.1F
20
17
SP
RIN
GF
IELD
PLA
TT
EV
IEW
CO
MM
UN
ITY
SC
HO
OLS
NORTHSCALE: 1/8" = 1'-0"
FLOOR PLAN, LOWER LEVEL - AREA F
CC
-19/
13/1
7A
DD
EN
DU
M C
C-1
CC-1
MAIN LEVELEL = 112' - 0"
GYM LEVELEL = 108' - 4"
LOWER LEVELEL = 100' - 0"
E E
EE
F227
G G
G G F124
H J
F244A
NEW METAL PANEL ROOF
NEW METAL WALL PANELS
TUCK POINT FACE BRICK
REMOVE AND REPLACE4 COURSES OF FACEBRICK FOR NEW LINTEL-SEE33/A9.2
REMOVE AND REPLACEFACE BRICK FOR NEW LINTEL
TUCK POINTBRICK
CUT NEW BCJ3/8" DEEP
RE-CAULKEXISTING JOINT
RE-CAULKEXISTING JOINT
CUT NEW BCJ3/8" DEEP
RE-CAULKEXISTING JOINT
NEW SOFT JOINT
ECJ
ECJ
RE-CAULK EXISTINGCONTROL JOINTS, TYP
ECJ
ECJTUCK POINTBRICK
TUCK POINTBRICK
ECJ
WEEPS @ 24" OC12" DOWN FROMTOP OF WALL
WEEPS @ 24" OC4" ABOVE GRADE
WEEPS @ 24" OC4" ABOVE GRADE
A5.1
31
BEYOND
REMOVE SEALANT ATPERIMETER AND REPLACE
DOWNSPOUT -COORDINATEWITH CIVIL
DOWNSPOUT -COORDINATEWITH CIVIL
MAIN LEVELEL = 112' - 0"
GYM LEVELEL = 108' - 4"
L
NEW METAL WALL PANELSFULL DEPTH BRICKCONTROL JOINT, TYP@ "BCJ"
BCJ
BCJ @ 9" FROMEND OF WALL
ECJ RE-CAULK EXISTINGCONTROL JOINTS, TYP
ECJ ECJ
RE-CAULKEXISTINGJOINT
WEEPS @ 24" OC12" DOWN FROMTOP OF WALL
WEEPS @ 24" OC4" ABOVE BOTTOF WALL
WEEPS @ 24" OC12" DOWN FROMTOP OF WALL
WEEPS @ 24" OC4" ABOVE GRADE
ECJ
WEEPS @ 24" OC12" DOWN FROMTOP OF WALL
WEEPS @ 24" OC4" ABOVE GRADE
REMOVE SEALANT ATPERIMETER AND REPLACEAT EXISTING DOOR FRAME
MAIN LEVELEL = 112' - 0"
LOWER LEVELEL = 100' - 0"
F203
F F
F F
F
F124
H
PAINT GUARDRAIL
NEW METAL PANEL ROOF
PRE-MANUFACUTRED METALCANOPY-ALTERNATE CC-2
NEW PRECAST CAP ONEXISTING WALL
NEW METAL WALL PANELS
ECJ
WEEPS @ 24" OC12" DOWN FROMTOP OF WALL
WEEPS @ 24" OC4" ABOVE GRADE
RE-CAULK EXISTINGCONTROL JOINTS, TYP
CUT NEW BCJ3/8" DEEP
RE-CAULKEXISTING JOINT
RE-CAULKEXISTING JOINT
REMOVE AND REPLACE3 COURSES OF FACEBRICK FOR NEW LINTEL
TUCK POINT BRICKUNDER ROWLOCK
ECJFULL DEPTH BRICKCONTROL JOINT, TYP@ "BCJ"
BCJ
BCJ @ 4" FROMEND OF WALL
BCJ @ 4" FROMEND OF WALL
BCJ
CUT NEW BCJ3/8" DEEP
RE-CAULKEXISTING JOINT
RE-CAULKEXISTING JOINT
CUT NEW BCJ3/8" DEEP
RE-CAULKEXISTING JOINT
RE-CAULKEXISTING JOINT
BCJ @ 4" FROMEND OF WALL
BCJ
ECJ ECJ
ECJ
ROOF LADDER
STAIRS, REMOVEDFROM THIS VIEWFOR CLARITY
MAIN LEVELEL = 112' - 0"
K
ADD METAL FLASHING SILL AT WINDOW OPENINGMECHANICAL EQUIPMENT
NEW METAL WALL PANELS BEYOND
ECJECJ
ECJ
ECJ
ECJ
ECJ
ECJECJ
WEEPS @ 24" OC12" DOWN FROMTOP OF WALL
WEEPS @ 24" OC4" ABOVE GRADE
RE-CAULK EXISTINGCONTROL JOINTS, TYP
CONTROL JOINT KEY
ECJ - EXISTING CONTROL JOINT
BCJ - BRICK CONTROL JOINT
REMOVE AND REPLACEFACE BRICK FOR INSTALLATIONOF NEW STAIR
F227
F116
Arc
hite
ctu
re E
ngin
eering
P
lan
nin
g In
teriors
©
,
DL
R G
rou
p inc., a
Ne
bra
ska
co
rpo
ratio
n, A
LL
RIG
HT
S R
ES
ER
VE
D
Rev
isio
ns
9/1
3/2
017 1
1:2
9:0
9 A
M
C:\R
evit\1
0-1
3125-3
0_A
R_2016_C
entr
al_
jlim
bach.r
vt
10-1
3125-3
0
8/2
9/2
017
PLA
TT
EV
IEW
JR
HIG
H &
HIG
H S
CH
OO
L R
EN
OV
AT
ION
S
EX
TE
RIO
R E
LE
VA
TIO
NS
A5.1
20
17
SP
RIN
GF
IELD
PLA
TT
EV
IEW
CO
MM
UN
ITY
SC
HO
OLS
SCALE: 1/8" = 1'-0"A5.1
32 EAST ELEVATION
SCALE: 1/8" = 1'-0"A5.1
12 NORTH ELEVATION
SCALE: 1/8" = 1'-0"A5.1
42 SOUTH ELEVATION
SCALE: 1/8" = 1'-0"A5.1
52 WEST ELEVATION
PAINT EXISTING STEEL STRUCTURE
NEW PRECAST CAPON EXISTING WALL
CC
-19/
13/1
7A
DD
EN
DU
M C
C-1
SCALE: 1/4" = 1'-0"A5.1
31 ELEVATION DETAILCC-1
CC-1
A B C D E
SE
E S
CH
ED
ULE
SCHEDULESEE
SCHEDULESEE
SE
E S
CH
ED
ULE
SE
E S
CH
ED
ULE
SCHEDULESEE
SCHEDULESEE
SCHEDULESEE
SE
E S
CH
ED
ULE
SE
E S
CH
ED
ULE
4" BY DR MFR
3' -
7"
AF
F8"
BY DR MFR BY DR MFR
3' -
7"
AF
F8"
3' -
4"
4"4"
8"1'
- 0
"
BY DR MFR BY DR MFR BY DR MFR BY DR MFR
1' -
0"
8"
2' -
8"
SE
E S
CH
ED
ULE
SCHEDULESEE
F
A B C D E
F G H J
K L
2"3' - 0"
2"
3' - 4"
2" 1' - 6"2"
3' - 0"5"
5' - 3"
2 1/
2"1'
- 0
"1
1/2"
6' -
8"
1 1/2"6' - 0"
1 1/2"6' - 10 3/4"
1 1/2"4' - 10 7/16"
1 1/2"6' - 10 3/4"
1 1/2"
2 1/
2"4'
- 9
"2"
2' -
8 1
/2"
2"
2" 4' - 11" 2"
5' - 3"
8' -
0"
25' - 3 1/2"
8' -
0"
2"8"
2"4'
- 0
"2"
2' -
8"
2"
4"7'
- 0
"
7' -
4"
2"8"
2"4'
- 0
"2"
2' -
6"
4"
2"3' - 10"
2"3' - 0"
2"
8' -
0"
7' - 4"
5"4' - 8"
2"
5' - 3"
4"6'
- 8
"2"
7"3"
8' -
0"
4"2'
- 6
"2"
4' -
0"
2"7"
3"
8' -
0"
2"5'
- 3
"3"
5' -
8"
2" 5' - 0" 2"
5' - 4"
2"5'
- 4
"2"
5' -
8"
2"6' - 11 7/16"
2"5' - 4 5/8"
2"5' - 4 5/8"
2"6' - 11 7/16"
2"
25' - 6"
2"5' - 11 7/16"
2"5' - 4 5/8"
2"5' - 4 5/8"
2"5' - 11 7/16"
2"
23' - 6"
2"5'
- 4
"2"
5' -
8"
2"6' - 3 5/8"
2"6' - 3 5/8"
2"6' - 3 5/8"
2"6' - 3 5/8"
2"6' - 3 5/8"
2"
32' - 6"
3"3'
- 7
"2"
4' -
0"
5" 4' - 11" 2" 5' - 1" 2" 5' - 1" 2" 4' - 11" 5"
21' - 4"
2"1'
- 4
"2"
1' -
8"
M
2" 5' - 0 5/16" 2" 4' - 11 5/16" 2" 5' - 0 5/16" 2" 3' - 0" 2"
18' - 10"2"
8"2"
4' -
0"
2"2'
- 6
"4"
8' -
0"
CTIG CTIG
CTIG
CTIG
CTIG
CTIG
CTIG CTIG
CTIG CTIG
CTIG
CTIG CTIG
CTIG
CTIG
CTIG
CTIG
CTIG
CTIG
CTIG
CTIG
CTIG
CTIG CTIG CTIG CTIG CTIG CTIG CTIG CTIG
CTIG CTIG CTIG CTIG CTIG
CTIG CTIG CTIG CTIG
CTIG
CTIG
CTIG
CTIG
CTIG
CTIG
CTIG CTIG CTIG CTIG
N
1' -
2"
4' -
10"
2"
5' -
0"
2" 3' - 0" 2"
3' - 4"
DOOR AND WINDOW FRAME SCHEDULE GENERAL NOTES
A. ALL HOLLOW METAL FRAMES SHALL BE FILLED WITH MINERALWOOL AT METAL STUD WALLS.
B. INSTALL EXTERIOR FRAMES WITH 1/4 INCH SHIM AND JOINTSEALANT AROUND PERIMETER OF FRAME.
C. MASONRY LINTELS AND STEEL LINTELS ARE INDICATED ONSTRUCTURAL DRAWINGS.
D. GLASS TYPES FOR DOORS MATCH GLAZING INDICATED FORFRAME. INTERIOR DOORS (CTG), EXTERIOR DOORS (CTIG). GLASSTYPES FOR FRAMES ARE INDICATED ON FRAME ELEVATIONS.
E. EXTERIOR WINDOW FRAME TYPES ARE INDICATED ON FLOOR PLANWITH HEXAGON SYMBOL.
F. OVERHEAD COILING DOORS, GRILLES AND SECTIONAL DOORSWIDTH AND HEIGHT DIMENSIONS INDICATED IN DOOR AND FRAMESCHEDULE REPRESENT FURNISHED OPENING SIZE. CONTRACTORTO COORDINATE EXACT SIZE OF DOOR WITH MANUFACTURER.
G. FRAME MANUFACTURER SHALL COORDINATE LOCATIONS OFCONCEALED CONDUIT AND J-BOXES REQUIRED FOR SECURITYSYSTEM HARDWARE PRIOR TO MANUFACTURING OF HOLLOWMETAL FRAMES AND COORDINATE WITH SECURITY HARDWAREAND DEVICES.
H. PROVIDE HEAD RECEIVERS AT ALUMINUM STOREFRONTS ANDCURTAINWALLS AS REQUIRED FOR FRAME AND STRUCTURALDEFLECTION.
I. SEE SPECIFICATIONS 087100 HARDWARE FOR HARDWARE SETNOTED IN DOOR SCHEDULE.
1 2 3 6 7 8 9 10
2" VARIES 2"
2"V
AR
IES
, SE
E S
CH
ED
ULE
2" VARIES 2"
VA
RIE
S, S
EE
SC
HE
DU
LE4"
2" 3' - 0" 2" 1' - 10" 2"
5' - 4"
4"3'
- 0
"2"
3' -
6"
2"
7' -
2"
2" 3' - 0" 2" 1' - 2" 2"
4' - 8"
4"3'
- 0
"2"
3' -
6"
2"8"
2"
8' -
0"
2" 3' - 0" 2"
3' - 4"
7' -
0"
2"8"
2"
8' -
0"
2" 6' - 0" 2"
6' - 4"
6' -
8"
2"4'
- 1
0"2"
11' -
10"
2" 3' - 8" 2" 6' - 0" 2" 3' - 8" 2"
14' - 0"
4"2'
- 1
0"2"
4' -
6"
2"
8' -
0"
2" EQ 2" EQ 2"
9' - 8 3/8"
4"2'
- 6
"2"
4' -
10"
2"
8' -
0"
4 5 11
2" 3' - 0" 2" 2' - 6" 2"
6' - 0"
4"3'
- 0
"2"
3' -
6"
4"
7' -
4"
2" 3' - 0" 2" 2' - 6" 2" 2' - 6" 2"
8' - 8"
3' -
4"
2"3'
- 6
"4"
7' -
4"
2"4'
- 6
"2"
3' -
0"
4' -
10"
2" EQ 2" EQ 2" EQ 2" EQ 2"
30' - 0"
12
7' -
0"
2"1'
- 4
"2"
8' -
8"
2" 6' - 0" 2"
6' - 4"
CTG
CTG
CTG
CTG
CTG CTG
CTG CTG
CTG
CTG
CTGCTG
CTG
CTG
CTG
CTG
CTG
CTG
CTG
CTG
CTG CTG CTG CTG
CTG
Arc
hite
ctu
re E
ngin
eering
P
lan
nin
g In
teriors
©
,
DL
R G
rou
p inc., a
Ne
bra
ska
co
rpo
ratio
n, A
LL
RIG
HT
S R
ES
ER
VE
D
Rev
isio
ns
9/1
2/2
017 4
:23:3
3 P
M
C:\R
evit\1
0-1
3125-3
0_A
R_2016_C
entr
al_
jlim
bach.r
vt
10-1
3125-3
0
8/2
9/2
017
PLA
TT
EV
IEW
JR
HIG
H &
HIG
H S
CH
OO
L R
EN
OV
AT
ION
S
DO
OR
AN
D F
RA
ME
SC
HE
DU
LE
A9.1
20
17
SP
RIN
GF
IELD
PLA
TT
EV
IEW
CO
MM
UN
ITY
SC
HO
OLS
_DOOR AND FRAME SCHEDULE - AREA C_
NUMBER
DOOR PANEL FRAME
FIRE RATING HARDWARE SET
DETAILS
COMMENTSNO. OF PANELS WIDTH HEIGHT THICKNESS MATERIAL GLAZING TYPE DEPTH MATERIAL TYPE HEAD JAMB LEFT JAMB RIGHT SILL
C201 1 3' - 0" 7' - 0" 1 3/4" HM A 5 3/4" HM 2 25 25/A9.2 24/A9.2 24/A9.2
C202 1 3' - 0" 7' - 0" 1 3/4" HM A 5 3/4" HM 2 25 25/A9.2 24/A9.2 24/A9.2
C203 1 3' - 0" 7' - 0" 1 3/4" HM A 5 3/4" HM 2 36 25/A9.2 24/A9.2 24/A9.2
C205 1 3' - 0" 7' - 0" 1 3/4" HM A 5 3/4" HM 2 36 25/A9.2 24/A9.2 24/A9.2
C205A 1 3' - 0" 7' - 0" 1 3/4" HM A 5 3/4" HM 2 36 25/A9.2 24/A9.2 24/A9.2
C206 1 3' - 0" 7' - 0" 1 3/4" HM A 5 3/4" HM 4 28 25/A9.2 24/A9.2 24/A9.2
C206A 1 3' - 0" 7' - 0" 1 3/4" HM C 5 3/4" HM 5 28 25/A9.2 24/A9.2 24/A9.2
C207 1 3' - 0" 7' - 0" 1 3/4" HM A 5 3/4" HM 2 20 25/A9.2 24/A9.2 24/A9.2
C207A 1 3' - 0" 7' - 0" 1 3/4" WD A 5 3/4" HM 2 28 25/A9.2 24/A9.2 24/A9.2
C208 1 3' - 0" 7' - 0" 1 3/4" WD A 5 3/4" HM 2 17 25/A9.2 24/A9.2 24/A9.2
C209 1 3' - 0" 7' - 0" 1 3/4" HM A 5 3/4" HM 2 36 25/A9.2 24/A9.2 24/A9.2
C211 1 3' - 0" 7' - 0" 1 3/4" HM A 5 3/4" HM 2 20 25/A9.2 24/A9.2 24/A9.2
C212 1 3' - 0" 7' - 0" 1 3/4" HM A 5 3/4" HM 2 36 25/A9.2 24/A9.2 24/A9.2
C214 1 3' - 0" 7' - 0" 1 3/4" HM A 5 3/4" HM 2 36 25/A9.2 24/A9.2 24/A9.2
C214A 1 3' - 0" 7' - 0" 1 3/4" HM A 5 3/4" HM 2 36 25/A9.2 24/A9.2 24/A9.2
C215 1 3' - 0" 7' - 0" 1 3/4" HM A 5 3/4" HM 4 28 25/A9.2 24/A9.2 24/A9.2
C215A 1 3' - 0" 7' - 0" 1 3/4" HM C 5 3/4" HM 5 28 25/A9.2 24/A9.2 24/A9.2
C216 1 3' - 0" 7' - 0" 1 3/4" HM A 5 3/4" HM 2 20 25/A9.2 24/A9.2 24/A9.2
C216A 1 3' - 0" 7' - 0" 1 3/4" WD A 5 3/4" HM 2 28 25/A9.2 24/A9.2 24/A9.2
C217 1 3' - 0" 7' - 0" 1 3/4" WD A 5 3/4" HM 2 17 25/A9.2 24/A9.2 24/A9.2
C218 1 3' - 0" 7' - 0" 1 3/4" HM A 5 3/4" HM 2 36 25/A9.2 24/A9.2 24/A9.2
C220 1 3' - 0" 7' - 0" 1 3/4" HM A 5 3/4" HM 2 20 25/A9.2 24/A9.2 24/A9.2
C221 2 3' - 0" 7' - 0" 1 3/4" HM A 5 3/4" HM 2 60 MIN 15 25/A9.2 24/A9.2 24/A9.2 1 HR FIRE-RESISTIVE ASSEMBLY
C227 2 2' - 8" 7' - 0" 1 3/4" HM B 5 3/4" HM 2 30 25/A9.2 24/A9.2 24/A9.2
C228 1 3' - 0" 7' - 0" 1 3/4" HM A 5 3/4" HM 2 21 25/A9.2 24/A9.2 24/A9.2
C229 2 3' - 0" 7' - 0" 1 3/4" HM B 5 3/4" HM 12 38 25/A9.2 24/A9.2 24/A9.2
C230 1 3' - 0" 7' - 0" 1 3/4" HM A 5 3/4" HM 7 24 16/A9.2 16/A9.2 16/A9.2
C232 1 3' - 0" 7' - 0" 1 3/4" HM A 5 3/4" HM 7 24 16/A9.2 16/A9.2 16/A9.2
C233 2 3' - 0" 7' - 0" 1 3/4" HM B 5 3/4" HM 12 38 25/A9.2 24/A9.2 24/A9.2
C301 1 3' - 0" 4' - 8" 1 3/4" HM A 5 3/4" HM N 10 25/A9.2 SIM 24/A9.2 SIM 32/A9.2 4-SIDED HOLLOW METAL FRAME
C302 1 3' - 0" 4' - 8" 1 3/4" HM A 5 3/4" HM N 10 25/A9.2 SIM 24/A9.2 SIM 32/A9.2 4-SIDED HOLLOW METAL FRAME
_WINDOW SCHEDULE_
FRAME
FIRE RATING
DETAILS
COMMENTSNUMBER TYPE MATERIAL DEPTH HEAD JAMB LEFT JAMB RIGHT SILL
E E AL 4 1/2" 44/A9.2 42/A9.2 41/A9.2 53/A9.2
F F AL 4 1/2" 44/A9.2 41/A9.2 43/A9.2 53/A9.2
F202A 10 HM 5 3/4" 45/A9.2 34/A9.2 34/A9.2 55/A9.2
F232 11 HM 8 1/4" 46/A9.2 46/A9.2 46/A9.2 46/A9.2
G G AL 4 1/2" 44/A9.2 43/A9.2 43/A9.2 54/A9.2
H H AL 5 3/4" 44/A9.2 43/A9.2 43/A9.2 54/A9.2
J J AL 5 3/4" 44/A9.2 43/A9.2 43/A9.2 54/A9.2
K K AL 4 1/2" 44/A9.2 43/A9.2 43/A9.2 54/A9.2
L L AL 4 1/2" 44/A9.2 43/A9.2 43/A9.2 54/A9.2
SCALE: 1/4" = 1'-0"
DOOR TYPES
FRAME ELEVATIONS EXTERIOR
_DOOR AND FRAME SCHEDULE - AREA F_
NUMBER
DOOR PANEL FRAME
FIRE RATING HARDWARE SET
DETAILS
COMMENTSNO. OF PANELS WIDTH HEIGHT THICKNESS MATERIAL GLAZING TYPE DEPTH MATERIAL TYPE HEAD JAMB LEFTJAMBRIGHT SILL
F102 1 3' - 0" 7' - 0" 1 3/4" HM A 5 3/4" HM 1 11 16/A9.2 16/A9.2 16/A9.2
F103 1 3' - 0" 7' - 0" 1 3/4" HM A 5 3/4" HM 2 45 MIN 11 25/A9.2 24/A9.2 24/A9.2
F103A 1 3' - 6" 7' - 0" 1 3/4" HM 5 3/4" HM 45 MIN 11 16/A9.2 26/A9.2 26/A9.2 55/A9.2
F105 1 3' - 0" 7' - 0" 1 3/4" WD A 5 3/4" HM 1 35 16/A9.2 16/A9.2 16/A9.2
F106 1 3' - 0" 7' - 0" 1 3/4" WD A 5 3/4" HM 1 35 16/A9.2 16/A9.2 16/A9.2
F107 1 3' - 0" 7' - 0" 1 3/4" ALUM D 4 1/2" ALUM B 8 43/A9.2 44/A9.2 42/A9.2
F108 1 3' - 0" 7' - 0" 1 3/4" WD A 5 3/4" HM 3 26 16/A9.2 16/A9.2 16/A9.2 55/A9.2
F109 1 3' - 0" 7' - 0" 1 3/4" WD A 5 3/4" HM 3 26 16/A9.2 16/A9.2 16/A9.2 55/A9.2
F110 1 3' - 0" 7' - 0" 1 3/4" WD A 5 3/4" HM 3 26 16/A9.2 16/A9.2 16/A9.2 55/A9.2
F111 1 3' - 0" 7' - 0" 1 3/4" WD A 5 3/4" HM 3 12 16/A9.2 16/A9.2 16/A9.2 55/A9.2
F111A 1 3' - 0" 7' - 0" 1 3/4" WD A 5 3/4" HM 3 12 16/A9.2 16/A9.2 16/A9.2 55/A9.2
F113 1 3' - 0" 7' - 0" 1 3/4" WD A 5 3/4" HM 1 20 16/A9.2 16/A9.2 16/A9.2
F114 1 3' - 0" 7' - 0" 1 3/4" WD A 5 3/4" HM 1 20 16/A9.2 16/A9.2 16/A9.2
F115 1 3' - 0" 7' - 0" 1 3/4" WD B 5 3/4" HM 1 31 16/A9.2 16/A9.2 16/A9.2
F116 1 3' - 0" 7' - 0" 1 3/4" ALUM D 4 1/2" ALUM B 8 43/A9.2 44/A9.2 42/A9.2
F117 1 3' - 0" 7' - 0" 1 3/4" WD A 5 3/4" HM 3 26 16/A9.2 16/A9.2 16/A9.2 55/A9.2
F118 1 3' - 0" 7' - 0" 1 3/4" WD A 5 3/4" HM 3 26 16/A9.2 16/A9.2 16/A9.2 55/A9.2
F119 1 3' - 0" 7' - 0" 1 3/4" WD A 5 3/4" HM 3 26 16/A9.2 16/A9.2 16/A9.2 55/A9.2
F120 1 3' - 0" 7' - 0" 1 3/4" WD A 5 3/4" HM 3 27 16/A9.2 26/A9.2 26/A9.2 55/A9.2
F121 2 3' - 0" 6' - 8" 1 3/4" ALUM D 4 1/2" ALUM 8 5 43/A9.2 44/A9.2 42/A9.2 -
F122 1 3' - 0" 7' - 0" 1 3/4" WD A 5 3/4" HM 7 20 16/A9.2 16/A9.2 16/A9.2
F123 1 3' - 0" 7' - 0" 1 3/4" WD B 5 3/4" HM 7 28 16/A9.2 16/A9.2 16/A9.2
F124 2 3' - 0" 6' - 8" 1 3/4" ALUM D 4 1/2" ALUM C 1 43/A9.2 44/A9.2 44/A9.2
F201 2 3' - 0" 7' - 10" 1 3/4" ALUM - 4 1/2" ALUM -- 4 - - - - EXISTING DOOR AND FRAME
F202 1 3' - 0" 7' - 0" 1 3/4" WD A 5 3/4" HM 7 13 16/A9.2 16/A9.2 16/A9.2
F203 1 3' - 0" 7' - 0" 1 3/4" ALUM D 4 1/2" ALUM M 9 44/A9.2 43/A9.2 43/A9.2 52/A9.2
F207 1 3' - 0" 7' - 0" 1 3/4" WD A 5 3/4" HM 3 32 16/A9.2 16/A9.2 16/A9.2 55/A9.2
F208 1 3' - 0" 7' - 0" 1 3/4" WD E 5 3/4" HM 1 32 16/A9.2 16/A9.2 16/A9.2
F209 1 3' - 0" 7' - 0" 1 3/4" WD B 5 3/4" HM 1 33 16/A9.2 16/A9.2 16/A9.2
F210 1 3' - 0" 7' - 0" 1 3/4" WD A 5 3/4" HM 1 34 16/A9.2 16/A9.2 16/A9.2
F212 2 3' - 0" 7' - 10" 1 3/4" ALUM - 4 1/2" ALUM -- 7 33/A9.2 SIM 43/A9.2/SIM 43/A9.2 SIM
F213 1 3' - 0" 7' - 0" 1 3/4" WD A 5 3/4" HM 1 35 16/A9.2 16/A9.2 16/A9.2
F214 1 3' - 0" 7' - 0" 1 3/4" WD A 5 3/4" HM 1 35 16/A9.2 16/A9.2 16/A9.2
F216 1 3' - 0" 7' - 0" 1 3/4" HM A 5 3/4" HM 1 26 16/A9.2 16/A9.2 16/A9.2
F217 1 3' - 0" 7' - 0" 1 3/4" WD A 5 3/4" HM 1 18 16/A9.2 16/A9.2 16/A9.2
F218 1 3' - 0" 7' - 0" 1 3/4" WD A 5 3/4" HM 1 18 16/A9.2 16/A9.2 16/A9.2
F219 1 3' - 0" 7' - 0" 1 3/4" ALUM D 4 1/2" ALUM D 8 43/A9.2 44/A9.2 44/A9.2 52/A9.2
F220 1 3' - 0" 7' - 0" 1 3/4" WD A 5 3/4" HM 3 26 16/A9.2 16/A9.2 16/A9.2 55/A9.2
F221 1 3' - 0" 7' - 0" 1 3/4" WD A 5 3/4" HM 3 26 16/A9.2 16/A9.2 16/A9.2 55/A9.2
F222 1 3' - 0" 7' - 0" 1 3/4" WD A 5 3/4" HM 3 26 16/A9.2 16/A9.2 16/A9.2 55/A9.2
F223 1 3' - 0" 7' - 0" 1 3/4" WD A 5 3/4" HM 3 60 MIN 14 16/A9.2 16/A9.2 16/A9.2 55/A9.2
F223A 1 3' - 0" 7' - 0" 1 3/4" WD A 5 3/4" HM 3 60 MIN 14 16/A9.2 16/A9.2 16/A9.2 55/A9.2
F224 1 3' - 0" 7' - 0" 1 3/4" WD A 5 3/4" HM 1 20 16/A9.2 16/A9.2 16/A9.2
F225 1 3' - 0" 7' - 0" 1 3/4" WD B 5 3/4" HM 1 31 16/A9.2 16/A9.2 16/A9.2
F226 1 3' - 0" 7' - 0" 1 3/4" WD A 5 3/4" HM 1 20 16/A9.2 16/A9.2 16/A9.2
F227 1 3' - 0" 7' - 0" 1 3/4" ALUM D 4 1/2" ALUM B 8 43/A9.2 43/A9.2 42/A9.2
F228 1 3' - 0" 7' - 0" 1 3/4" WD A 5 3/4" HM 3 26 16/A9.2 16/A9.2 16/A9.2 55/A9.2
F229 1 3' - 0" 7' - 0" 1 3/4" WD A 5 3/4" HM 3 26 16/A9.2 16/A9.2 16/A9.2 55/A9.2
F230 1 3' - 0" 7' - 0" 1 3/4" WD A 8 1/4" HM 3 26 16/A9.2 16/A9.2 16/A9.2 55/A9.2
F231 1 3' - 0" 7' - 0" 1 3/4" HM A 5 3/4" HM 1 31 16/A9.2 16/A9.2 16/A9.2
F233 1 3' - 0" 7' - 0" 1 3/4" WD A 5 3/4" HM 3 26 16/A9.2 16/A9.2 16/A9.2 55/A9.2
F233A 1 3' - 0" 7' - 0" 1 3/4" HM B 5 3/4" HM 1 27 16/A9.2 16/A9.2 16/A9.2
F234 1 3' - 0" 7' - 0" 1 3/4" WD E 5 3/4" HM 6 31 16/A9.2 16/A9.2 16/A9.2 55/A9.2
F235 1 3' - 0" 7' - 0" 1 3/4" WD E 5 3/4" HM 6 31 16/A9.2 16/A9.2 16/A9.2 55/A9.2
F236 2 3' - 0" 6' - 8" 1 3/4" ALUM EXISTING 4 1/2" ALUM - 4 - - - - EXISTING DOOR AND FRAME
F237 1 3' - 0" 6' - 8" 1 3/4" HM A 5 3/4" HM 2 20 25/A9.2 24/A9.2 24/A9.2
F238 1 3' - 0" 7' - 0" 1 3/4" HM A 5 3/4" HM 1 20 16/A9.2 16/A9.2 16/A9.2
F239 1 3' - 0" 6' - 8" 1 3/4" HM A 5 3/4" HM 2 23 25/A9.2 24/A9.2 24/A9.2
F239A 1 3' - 0" 6' - 8" 1 3/4" HM A 5 3/4" HM 2 22 25/A9.2 24/A9.2 24/A9.2
F239B 3' - 4" 4' - 4" SS F SS 37 13/A9.2 14/A9.2 14/A9.2 23/A9.2
F239C 1 3' - 0" 6' - 8" 1 3/4" HM A 5 3/4" HM 2 29 25/A9.2 24/A9.2 24/A9.2
F240 1 3' - 0" 6' - 8" 1 3/4" HM A 5 3/4" HM 2 19 25/A9.2 24/A9.2 24/A9.2
F241 2 3' - 4" 6' - 8" 1 3/4" HM B 5 3/4" HM 1 16 16/A9.2 16/A9.2 16/A9.2
F242 1 3' - 0" 6' - 8" 1 3/4" HM A 5 3/4" HM 2 35 25/A9.2 24/A9.2 24/A9.2
F243 1 3' - 0" 6' - 8" 1 3/4" HM A 5 3/4" HM 2 35 25/A9.2 24/A9.2 24/A9.2
F244 1 3' - 6" 6' - 8" 1 3/4" HM A 5 3/4" HM 2 6 25/A9.2 24/A9.2 24/A9.2
F244A 2 3' - 0" 6' - 8" 1 3/4" HM A 5 3/4" EXISTING - 2 - - - - EXISTING FRAME NEW DOOR
F245 1 3' - 0" 7' - 0" 1 3/4" HM A 5 3/4" HM 1 21 16/A9.2 16/A9.2 16/A9.2
F246 1 3' - 0" 7' - 0" 1 3/4" HM A 5 3/4" HM 2 21 25/A9.2 24/A9.2 24/A9.2
F247 1 3' - 6" 6' - 8" 1 3/4" HM A 5 3/4" EXISTING 3 - - - - EXISTING FRAME NEW DOOR
FRAME ELEVATIONS INTERIOR
CC
-19/
13/1
7A
DD
EN
DU
M C
C-1
CC-1
MINIMUM 20 GAUGE SHEET METALSTRAPPING MINIMUM 8" HIGH
#8 SELF TAPPING PAN PHILLIPSSCREW. MINIMUM THREE PER STUD
STEEL STUDS AS SCHEDULED
2 x WOOD BLOCKINGMINIMUM OF 8" HIGH..
NOTE: DIMENSIONAL WOOD AND PLYWOOD BLOCKING MUST BE FIRE-RETARDANT IN CONSTRUCTION TYPES IAND II AND CAN ONLY BE PERMITTED AT NONBEARING PARTITION WALLS WITH A FIRE RATING OF 2 HOURS ORLESS AND AT NONBEARING EXTERIOR WALLS WHERE NO FIRE RATING IS REQUIRED. REFER TO CODE SHEETSFOR CONSTRUCTION TYPE.
#8 X 1" SELF TAPPING PANHEAD SCREW. MINIMUM
THREE PER STUD
KERF BLOCKINGAT STUD RETURN
20 GAUGE GALVANIZED STEELANGLE FULL HEIGHT OF BLOCKING.
ANCHOR TO STUD WITH MINIMUMTHREE #7 FRAMING SCREWS.
ANCHOR BLOCKING TO ANGLE WITHMINIMUM OF THREE #8 X 1" SELF
TAPPING SCREWS
STEEL STUDS ASSCHEDULED
STEEL STUDS AS SCHEDULED
KERF BLOCKINGAT STUD RETURN
20 GAUGE GALVANIZED STEELANGLE FULL HEIGHT OF BLOCKING.
ANCHOR TO STUD WITH MINIMUMTHREE #7 FRAMING SCREWS.
ANCHOR BLOCKING TO ANGLE WITHMINIMUM OF THREE #8 X 5/8" SELF
TAPPING SCREWS
3/4" PLYWOOD BLOCKINGMINIMUM OF 8" HIGH..
USE WOOD BLOCKING AT DOOR STOPS, GRAB BARS, HANDRAILS, WALL HUNG CABINETS, TOILET PARTITIONS
AND/OR OTHER ITEMS WITH A WEIGHT OF 20 LBS OR MORE OR IF ITEM IS CANTILEVERED FROM WALL.
USE SHEET METAL STRAPPING FOR BATHROOM ACCESSORIES, MARKER BOARDS, TACK BOARDS, AND/OR OTHER
THAN GRAB BARS WHERE ITEMS WEIGH LESS THAN 20 LBS
SHEET METAL BACKING
ANCHORS, SEE ADJACENTPLAN VIEW FOR TYPE ANDNUMBER
STEEL STUDS AS SCHEDULED
ANCHOR WOOD BLOCKING TOSTEEL STUDS. SEE ADJACENTPLAN VIEW FOR TYPE AND NUMBER
STEEL STUDS AS SCHEDULED
DIMENSIONAL WOODBLOCKING
STEEL ANGLE, ANCHOR TOSTUDS AS NOTED INADJACENT PLAN VIEW
WA
LL H
EIG
HT
- S
EE
NO
N-B
EA
RIN
G IN
TE
RIO
R W
ALL
FR
AM
ING
TA
BLE
OPENING WIDTH
OPENING WIDTHCONTINUOUS FLOOR RUNNER
CONTINUOUS CEILING RUNNERWITH SLIP TYPE JOINT
BRIDGING
3-5/8" X 25 GAUGE
3-5/8" X 20 GAUGE
6" X 20 GAUGE
8" X 20 GAUGE
13'-8" 12'-5" 10'-10" 350S125-18
STUD SIZE 12 16 24
SPACING IN INCHES
MAXIMUM HEIGHT DESIGNBASED ONSSMA SIZE
362S137-33
6000S137-33
8000S137-33
NON-BEARING INTERIOR WALL FRAMING TABLE
(SSMA - STEEL STUD MANUFACTURER'S ASSOCIATION)
18'-5" 16'-9" 14'-7"
27'-5" 24'-11" 21'-9"
34'-8" 31'-6" 27'-6"
AT SOUNDWALLS
CONTROL JOINT LOCATIONS
SILL STUDS WITH CRIPPLE STUDSBELOW AT WINDOW OPENING
CRIPPLE STUDS ABOVE HEAD RUNNERSEE NOTE BELOW
JAMB STUDS
HEADER STUDS
STIFFENER STUDS
TOP RUNNER
BOTTOM RUNNER
C
TYP. METAL STUD FRAMING AT FRAME OPENINGNO SCALE
B
5/8" GYPSUM WALLBOARD OVER 6"COLD FORM METAL FRAMING
LINE OF GYPSUM WALLBOARDRETURN AT OPENING BELOWOPENING
BELOW
TEAR AWAY 'L' BEAD TRIM NOFASTENERS INTO RUNNER TRACK
SCALE: 1-1/2" = 1'-0"
TYP. VERT. SLIP CONTROL JOINTD
SELF ADHERED AIR BARRIERDESIGNER TO CONFIRM AIRBARRIER TYPE W/ SPECS
SM 'L' TRIM ON VERTICAL SLIP JOINTBOTH SIDES
D
AT EXTERIOR WALL SEE ELEVATIONSFOR LOCATIONS
SPRAY FOAM INSULATION
E/F
OPENING WIDTH
0' TO 5'-0"
10'-1" TO 15'-0"5'-1" TO 10'-0"
INTERIOR HEADER SCHEDULE
FRAMING MEMBERS
TWO - 8" x 20 GATWO - 10" x 20 GA
TWO - 3-5/8" x 20 GA
TRACK (SAME GAUGE AS HEADER)(TYP)
BOX LINTEL (HEADER) SEESCHEDULE BELOW (TYP)
SEE PLAN FOR WALL TYPE (TYP)
#12 SCREWS AT 16" O.C. TYP.
SPAN UP TO 10'-0"
SPAN GREATER THAN 10'-0"
NOTE:1. HEADER SHALL BE UNPUNCHEDAND OF THE SIZE AND GAUGE LISTED.
2. SEE STRUCTURAL DETAILS FOROPENINGS OVER 15'-1".
E
F
TRACK AT TOP AND BOTTOM OFHEADER
CONTROL JOINT LOCATIONS
TOP TRACK
CRIPPLE STUDS ABOVE HEADERTOP TRACK - SEE NOTE BELOW
HEADER STUDS
STIFFENER STUDS - SEE STRUCTURAL
BEARING STUD - SEE STRUCTURAL
BOTTOM TRACK
NOTE: ABOVE HEADER, PROVIDE 1/2"MIN CLEAR SPACE BETWEEN CRIPPLESTUDS AND STIFFENER STUDS BOTHSIDES OF ALL DOOR OPENINGS
TYP METAL STUD FRAMING AT DOOR OPENING
TYP GWB CONTROL JOINT ABOVE
GWB/METAL STUD WALL -SEE PLAN FOR WALL TYPE
DOOR FRAME BELOW
CONTROL JOINT
CRIPPLE STUDS @ 16" OC
STIFFENER STUDS - SEE STRUCTURAL
NOTE:AT DOUBLE LAYER GWB LOCATIONSMAINTAIN 1/2" CLEAR SPACE ATFIRST LAYER AND CONTROL JOINTAT SECOND LAYER
1/2"
SCALE: 1-1/2" = 1'-0"
NO SCALE
C
C
A
E/F
WALL FINISH AS SCHEDULED
(2) #12 FLAT HEAD PHILIPSSTAINLESS STEEL SHEET METALSCREW INTO STUD BLOCKING
GRAB BAR
MOUNTING FLANGE
MOUNTING FLANGE
1 1/2"1 1/4" MIN1 1/2" MAX
ATTACHEMENT PERMANUFACTURERSPECS WITH 1 1/2"MIN. PENETRATIONINTO METAL STUDBLOCKING
ANGLE CLIP ASPER MANUF.
WALL AS SCHEDULED
MARKERBOARD
MARKERBOARD TRAY
2 1/
2"
1 1/2" MIN
COVER PLATE
1 1/4" PIPE ALUMINUMHANDRAIL
WALL TYP PER PLAN
2 ANCHORS PER BRACKET
CONT. WELD
6"
HANDRAIL BRACKET
1 1/4" PIPE ALUMINUMHANDRAIL
WALL PER PLAN
MA
X1/
8"
1 1/
2"
PROVIDE CONT 14 GA X 8" WIDE STLSHEET BACKING IN STUD WALL
35
A10.2
TOP OF WALLEL = VARIES - SEE PLANS
FINISH FLOOREL = 112' - 0"
3"1"
4"
FIELD VERIFY1' - 4"
4" SFCMU
NEW CONCRETE SLAB
EXISTING CONCRETE WALL
PRECAST CAP
DRIP EDGE
EMBEDED FLASHINGWITH SS DRIPS
FIELD INSTALLED FASTNERINTO EXISTING CONCRETE WALL
1/2"1/2"
1/2"1/2"
EXISTING CONCRETE WALL
TOP OF WALLEL = VARIES
FINISH FLOOREL = VARIES - 112' - 0"
EXISTING FACE BRICK TO REMAIN
EXISTING GUARDRAIL TO REMAIN.SCRAPE PAINT AND REMOVE RUST.PREPARE SURFACE FOR NEWPRIMER AND PAINT
3"1"
4"
FIELD VERIFY
PRECAST CAP
DRIP EDGE
EMBEDED FLASHINGWITH SS DRIPS
SEALANT AROUND GUARDRAIL POST
2" 2"
1/2"
1/2"
1/2" 1/2"
FIELD INSTALLED FASTNERINTO EXISTING CONCRETE WALL(BEYOND)
8' -
0"
36" TYPICAL & 60" ADA COMPARTMENTVARIES - SEE PLAN
GWB CEILING
SEE PLAN FOR WALL TYPE
ALUM HEADRAIL
FIXED TRANSOM PANELBY PARTITION MANUFACTURER
74"H x XX"W DOOR PANEL32" WIDE AT ADA COMPARTMENT20" WIDE AT STANDARD COMPARTMENT
1/2" GAP AT TOP ANDBOTTOM OF DOOR
NOTCH DOOR @ 3" HIGHPILASTER SHOES, TYP
1" AIR GAP AT TOP FOR EXHAUSTAIR VENTILATION FROM SHOWERCOMPARTMENT
TOILET SIGN
MAXIMUM OCCUPANCY SIGN
NAME AND NUMBER SIGN
CHANGEABLE INSERT CLASSROOM SIGN
NAME ONLY SIGNE
F
D
4"
1/4"
3/4"
1/4"
1"
3/4"
1/4"
10"
5"5"
A B
C
TACTILE ROOM NUMBER AND NAME3/4" HELVETICA MEDIUM RAISED 1/32"COLOR: WHITE
FIELD COLOR: P-2
TYPE A (SHOWN) - WOMENTYPE B - MEN
ENGRAVED BRAILLE - GRADE II, 24POINT
TACTILE ROOM NAME3/4" HELVETICA MEDIUM RAISED 1/32"COLOR: WHITE
FIELD COLOR: P-5, BLACK
INTERNATIONAL SYMBOL OFACCESSIBILITY
SYMBOL COLOR: WHITE
FIELD COLOR: P-2
3"3"
6"
1/2"
1/2"
3/4" 7/8"
1/2"
9"
5"5"
10"
1/4"
1/2"
1/4"
3/4" 1/
4"
3/4"
3"
9"
5"5"
10"
4 1/
2"
1/4"
3/4"1/4"
1/2"
2"
TACTILE ROOM NAME AND NUMBER3/4" HELVETICA MEDIUM RAISED 1/32"COLOR: WHITE
FIELD COLOR: P-2
ENGRAVED BRAILLE - GRADE II, 24POINT
FIELD COLOR: P-2
CHANGEABLE INSERT FIXTURE
TACTILE ROOM NAME3/4" HELVETICA MEDIUM RAISED 1/32"COLOR: WHITE
FIELD COLOR: P-2
ENGRAVED BRAILLE - GRADE II, 24POINT
CL
1/2"
3/8"
5"
CL
3/4"
CL
CL
1/4" 2
1/4"
2"
1/4" 8 1/2" 1/4"
SEALANT
SEE PLAN FORWALL TYPE
WRAP GWB
EXISTING WALL
CONCRETE RAMP
GUARDRAIL
2' -
0"
TO
P O
F R
AIL
1 1/4" ES STEEL PIPE GUARDRAIL
1 1/4" ES STEEL PIPE POST
EMBEDDED STEEL POST
UTILITY SHELF (US) WITH MOP HOOKS- TYP. AT ALL MOP SINKS
METAL EDGE TRIM
FIBERGLASS REINFORCED PLASTICWALL PANELS AND ACCESSORIES
1'-0"
PROVIDE SEALANT AT PERIMETER OFMOP SINK AND FLOOR
MOP SINK
4'-0
"
Arc
hite
ctu
re E
ngin
eering
P
lan
nin
g In
teriors
©
,
DL
R G
rou
p inc., a
Ne
bra
ska
co
rpo
ratio
n, A
LL
RIG
HT
S R
ES
ER
VE
D
Rev
isio
ns
9/1
2/2
017 4
:23:3
7 P
M
C:\R
evit\1
0-1
3125-3
0_A
R_2016_C
entr
al_
jlim
bach.r
vt
10-1
3125-3
0
8/2
9/2
017
PLA
TT
EV
IEW
JR
HIG
H &
HIG
H S
CH
OO
LR
EN
OV
AT
ION
S
GE
NE
RA
L B
UIL
DIN
G D
ET
AIL
SA10.2
20
17
SP
RIN
GF
IELD
PLA
TT
EV
IEW
CO
MM
UN
ITY
SC
HO
OLS
SCALE: 1 1/2" = 1'-0"A10.2
24 TYPICAL BLOCKING IN FRAME WALLS
SCALE: 1/4" = 1'-0"A10.2
11 NON-LOAD BEARING INTERIOR WALL FRAMING AND SCHEDULE
SCALE: 1 1/2" = 1'-0"A10.2
31 METAL STUD OPENINGS AND CONTROL JOINTS
SCALE: 3" = 1'-0"A10.2
54 GRAB BAR ATTACHMENT DETAIL
SCALE: 3" = 1'-0"A10.2
34 MARKERBOARD ATTACHMENTSCALE: 3" = 1'-0"A10.2
35 HANDRAIL ATTACHMENT AT WALL - SECTIONSCALE: 3" = 1'-0"A10.2
36 HANDRAIL ATTACHMENT AT WALL - PLANSCALE: 1 1/2" = 1'-0"A10.2
33 PRECAST CAP DETAIL
CC
-19/
13/1
7A
DD
EN
DU
M C
C-1
SCALE: 1 1/2" = 1'-0"A10.2
23 PRECAST CAP DETAIL
SCALE: 3/4" = 1'-0"A10.2
51 SHOWER PARTITION ELEVATION
SCALE: 3" = 1'-0"A10.2
45 TYPICAL PANEL SIGNS
SCALE: 1 1/2" = 1'-0"A10.2
56 DETAILSCALE: 1 1/2" = 1'-0"A10.2
55 CANE DETECTION RAIL
SCALE: 3/4" = 1'-0"A10.2
44 MOP SINK DETAIL
CC-1
UP
S
S
S
S
S
FS
S S
S
S
S
S
SS
S
S
S
S
S
S
SS
S
S
S
S
S
A
A
B
B
C
C
D
D
E
E
F
F
G
G
H
H
J
J
K
K
1
2
3
4 5
6
7
8
9
10
11
ELECTRICAL
F104
MECHANICAL
F103
VEST
F124
STORAGE
F122MEDIA CENTER
F121
COMPUTER LAB
F108
CLASSROOM
F109
CLASSROOM
F110
CLASSROOM
F120
CLASSROOM
F117
CLASSROOM
F119
CLASSROOM
F118
SCIENCE
F111 CONFERENCEROOM
F115
DATA
F113
CUSTODIAL
F102
STORAGE
F114
CORRIDOR
107
CORRIDOR
F101
CORRIDOR
F116
RAMP/STAIR
F1S1
GREEN ROOM
F123
8"x10" SA
8" ø130 CFM
D-1
10"x
8" S
A
8" ø130 CFM
D-1
8" ø130 CFM
D-1
8" ø130 CFM
D-1
HP-F05
8" ø130 CFM
D-1
8" ø130 CFM
D-1
6" ø120 CFM
D-1
6" ø120 CFM
D-16" ø
120 CFM
D-1
HP-F03
8" ø225 CFM
D-1
8" ø225 CFM
D-1
8" ø225 CFM
D-1
HP-F02
8" ø130 CFM
D-1
8" ø130 CFM
D-18" ø
130 CFM
D-1
HP-F01
10" ø285 CFM
D-1
10" ø265 CFM
D-1
10" ø265 CFM
D-1
6" ø75 CFM
D-1
10" ø365 CFM
D-110" ø
365 CFM
D-1
10" ø365 CFM
D-1
HP-F06
HP-F08
HP
-F10HP-F09
10" ø250 CFM
D-110" ø
250 CFM
D-1
6" ø500 CFM
D-1
6" ø500 CFM
D-1
HP-F11
6" ø120 CFM
D-1
6" ø120 CFM
D-1
6" ø120 CFM
D-1
HP-F07
HP-F04
8" ø180 CFM
D-1
18"x12" SA10"x12" SA
10"x8" SA
8"x10" SA
12"x
10"
SA
10"x8" SA
10"x
10"
SA
18"x
10"
SA
8" ø245 CFM
D-2
8" ø245 CFM
D-2
8" ø245 CFM
D-2
6"x8
" S
A
200 cfm
375 cfm
380 CFM
140 CFM
350 CFM
430 CFM
430 CFM
430 CFM
475 CFM
440 CFM
440 CFM
UH-F1
GDWH-F103
T-F103
ET-1
TMV-1
FIRE PUMPROOM
F103A
8"x6" EA 10"x10" EA
8"x6
" E
A
10"x
10"
EA
10"ø
OA
14"x
12"
OA
20"x14" OA
12"ø
OA
10"ø
OA
26"x14" OA10
"ø O
A
26"x
14"
OA
30"x
14"
OA
10"ø
OA
8"ø
OA
14"x10" OA
14"ø
SA
SS-F01
34"x
14"
OA
34/14 OA UP
10"ø OA
G-224" x 24"
G-224" x 24"
30"x
14"
OA
10"ø OA
10"ø
OA
G-224" x 14"
G-224" x 24"
14"x12" RA
10"x10" SA
12"x12" TA
12"x12" RA
D-124" x 24"12"x12" TA
12"x12" TA
24"x
12"
RA
G-224" x 24"
10"ø OA
14"x12" RA
G-224" x 24"
12"x12" TA
14"x12" RA
G-224" x 24"
12"x12" TA
20"x16" RA
G-224" x 24"
20"x16" RA
12"x12" TA
12"x12" TA
14"x12" RA
G-224" x 24"12"x12" TA
16"x14" SA
10/10 EA UP
10"x10" EA
24"x14" RA
CC- 1
GENERAL HVAC PLAN NOTES:
1. LIMIT ALL FLEXIBLE DUCT RUNS TO 3 FEET MAXIMUM LENGTH.FLEXIBLE DUCT(S) SHALL BE OF THE SAME SIZE AS THE DIFFUSERNECKS THAT THEY CONNECT TO UNLESS NOTED OTHERWISE.
2. COORDINATE EXACT LOCATIONS OF ALL DIFFUSERS WITHELECTRICAL, FIRE SPRINKLERS, AND GRID CEILINGS.
3. BALANCING DAMPERS SHALL BE LOCATED ABOVE ACCESSIBLE CEILINGS. IF THIS IS NOT POSSIBLE, ACCESS PANELS SHALL BE PROVIDED. ACCESS PANELS SHALL BE TAMPERPROOF
LOCKABLE ACCESS PANLES FOR ACCESS TO CONTROL VALVES,MOTORIZED DAMPERS, SHUT-OFF VALVES, AND SIMILARCOMPONENTS THAT ARE NOT LOCATED OVER AN ACCESSIBLECEILING. VOLUME DAMPERS SHALL BE PROVIDED WITH REMOTEDAMPER OPERATORS WITH ADJUSTABLE COVER IN NON-ACCESSABLE CEILING AREAS. SEE DETAIL 8, SHEET M4.2,"REMOTE VOLUME DAMPER" AND SPECIFICATIONS FORFURTHER INFORMATION.
4. PROVIDE CEILING AND/OR WALL ACCESS DOORS FOR ACCESS TODUCT ACCESS DOORS RELATED TO THE INSPECTION ANDRESETTING OF FIRE DAMPERS AND COMBINATION SMOKE ANDFIRE DAMPERS. PROVIDE MINIMUM 18" X 18" SIZE. CEILINGAND/OR WALL ACCESS DOOR RATING SHALL BE EQUIVALENT TOCEILING AND/OR WALL WHERE DOOR IS TO BE INSTALLED.
5. BRANCH DUCT SIZES SHALL BE THE SAME AS THE NECK SIZE OFTHE DIFFUSERS OR THE CONNECTION SIZE OF THE GRILLES,UNLESS NOTED OTHERWISE.
6. HORIZONTAL HEAT PUMPS:A. MANUFACTURER-RECOMMENDED SERVICE ACCESS AREAS
FOR HORIZONTAL HEAT PUMPS HAVE BEEN SHOWN ON THEPLANS.
B. LOCATE THE HORIZONTAL HEAT PUMP UNITS IN AREAS THATALLOW FOR EASY REMOVAL OF THE FILTER AND EASYACCESS TO HEAT PUMP UNIT ACCESS PANELS. LEAVEENOUGH SPACE FOR SERVICE PERSONNEL TO PERFORMMAINTENANCE OR REPAIR. PROVIDE SUFFICIENT ROOM TOMAKE WATER, ELECTRICAL, DUCT AND CONDENSATE DRAINCONNECTIONS.
C. IF ANY DUCTWORK OR PIPING (DOMESTIC WATER, FIRE,WATER LOOP, CONDENSATE DRAIN, NATURAL GAS,ELECTRICAL CONDUIT, CONTROLS CONDUIT IS RUN WITHINTHE SERVICE AREAS, THE PIPE, CONDUIT OR DUCT SHALL BEREMOVED AND RE-ROUTED IF POSSIBLE SO IT IS NOT WITHINTHE SERVICE AREA.
D. ALLOW ADEQUATE ROOM BELOW THE HEAT PUMP UNIT FORA CONDENSATE TRAP. DO NO LOCATE THE HEAT PUMP UNITABOVE ANY PIPING SYSTEMS WHERE POSSIBLE. EACHHORIZONTAL HEAT PUMP UNIT SHALL BE PROVIDED WITH AFILTER BRACKET FOR SIDE FILTER REMOVAL. THECONTRACTOR MAY CONVERT OR MODIFY THIS FILTERBRACKET TO ALLOW FOR BOTTOM REMOVAL OF THE FILTERIF IT PROVIDES A BETTER, MORE ACCESSIBLE INSTALLATION.
E. GENERALLY SPEAKING, HORIZONTAL HEAT PUMPS ARELOCATED AS HIGH AS POSSIBLE, BUT STILL ACCESSIBLEFROM A LADDER.
7. VERTICAL HEAT PUMPS:A. SEE 'VERTICAL HEAT PUMP INSTALLATION' DETAIL ON SHEET
M4.1 FOR REQUIREMENTS.
8. FOR OUTSIDE AIR SUPPLY DUCTWORK SIZES TO HEAT PUMPS,REFER TO HEAT PUMP SCHEDULE ON SHEET M5.1.
9. GENERALLY SPEAKING, DUCTWORK THROUGHOUT THE BUILDINGWAS LOCATED AS HIGH AS POSSIBLE TO ALLOW ROOM FORFITTINGS DOWN TO DIFFUSERS AND OTHER TRADES.
10. RTU EXHAUST OUT OF CLASSROOMS SHALL EQUAL THE OUTSIDEAIR CFM TO CLASSROOM UNLESS STATED OTHERWISE.
Arc
hite
ctu
re E
ngin
eering
P
lan
nin
g In
teriors
©
,
DL
R G
rou
p inc., a
Ne
bra
ska
co
rpo
ratio
n, A
LL
RIG
HT
S R
ES
ER
VE
D
KEY PLAN
LEGEND NOTESLEGEND NOTES ARE COMMON TO ALLSOME NOTES MAY NOT APPLY TO THIS SHEET
A
NO
RT
H
Rev
isio
ns
B
C
D
E
F
9/1
3/2
017 1
:08:1
5 P
M
C:\R
evit\1
0-1
3125-3
0_M
P_2016_C
entr
al_
mm
art
z.r
vt
10-1
3125-3
0
8/2
9/2
017
PLA
TT
EV
IEW
JR
HIG
H &
HIG
H S
CH
OO
L R
EN
OV
AT
ION
S
HV
AC
PLA
N, LO
WE
R L
EV
EL -
AR
EA
FM1.1F
20
17
SP
RIN
GF
IELD
PLA
TT
EV
IEW
CO
MM
UN
ITY
SC
HO
OLS
NORTHSCALE: 1/8" = 1'-0"
HVAC PLAN, LOWER LEVEL - AREA F
CC
- 1
9/13
/17
AD
DE
ND
UM
CC
-1
DN
FS
S S
FS
S
SS
S
S
S
SS
FS
FS
FS
FS
SS
FS
S
SS
S
S
S
S
S
SS
S
S
S
S H
S
S
S
A B C
D
E F G H J K
1
2
3
4 5
6
7
8
9
10
11
OFFICE
F234
CLASSROOM
F233
VEST
F201
EARLYEDUCATION
F202
EARLYEDUCATION
F203BOYS
F204
GIRLS
F205
BOYS
F213
GIRLS
F214
PRINCIPAL
F207
NURSE
F209WORK ROOM
F211
GUIDANCE
F208
CLASSROOM
F222
CLASSROOM
F221
SPECIAL ED
F230JANITOR
F216
CLASSROOM
F228
TEACHERSLOUNGE
F220
WOMENS
F217
MENS
F218CLASSROOM
F229
SCIENCE
F223
CONFERENCEROOM
F225
ELEC
F224
RECEPTION
F206
CORRIDOR
F212
LEARNINGCOMMONS
F232
TOILET
F210
OFFICE
F235
STORAGE
F226
OFFICE
F231
CORRIDOR
F219
CORRIDOR
F215
COORIDOR
F227
34"x14" RA
HP-F25
HP
-F12
HP
-F24
HP
-F22
HP
-F19
HP
-F20
HP
-F14
HP
-F18
125
CF
M
400CFM
110CFM
500CFM
HP
-F21
HP
-F17
HP
-F16
HP
-F15
12"x8" OA
14"x
8" O
A
14"x8" OA
16"x10" OA
22"x
10"
OA
14"x10" OA
24"x12" OA 16"x12" OA 14"x10" OA
10"x
8" O
A
10"x
8" O
A
10"x
8" O
A
8"x6" EA
8"x6" EA
12"x8" EA
18"x
10"
EA
18"x10" EA
18"x14" EA
22"x
14"
EA
20"x
10"
EA
12"x8" EA
14"x10" EA
20"x6" SA 18"x8" SA 18"x8" SA 18"x8" SA
20"x10" SA
18"x12" SA
12"ø
SA
12" ø565 CFM
D-1
12" ø565 CFM
D-1
24"x10" RA
8"ø OA
14"x10" SA
8" ø175 CFM
D-18" ø
175 CFM
D-1
8" ø175 CFM
D-18" ø
175 CFM
D-1
26"x16" OA
20"x8" RA
G-224" x 24"
14"x10" SA
18"x
8" O
A
8"ø
OA
8"ø OA
34/14 OA DN
8" ø230 CFM
D-1
TYP 2
16"x
10"
SA
8" ø200 CFM
D-18" ø
200 CFM
D-1
8" ø200 CFM
D-1
8" ø200 CFM
D-1
8"x1
0" S
A
G-224" x 24"
22"x22" RA
8"x8" TA
12"x12" TA
R-120" x 6"
400 CFM
R-120" x 6"
350 CFM
R-120" x 6"
350 CFM
R-120" x 6"
350 CFM
R-120" x 6"
350 CFM
30"x8" RA
8"x8" TA
8" ø270 CFM
D-1
12"x12" TA
10"x
8" O
A
14"x
10"
SA
8" ø315 CFM
D-1
8" ø315 CFM
D-16" ø
70 CFM
D-1
12"x12" TA
14"x
10"
SA
10"x10" SA
8" ø230 CFM
D-1
8" ø235 CFM
D-18" ø
235 CFM
D-1
10"x10" SA
8" ø230 CFM
D-1
8" ø235 CFM
D-18" ø
235 CFM
D-1
14"x10" SA
16"x10" OA
10"x10" SA
8" ø235 CFM
D-18" ø
235 CFM
D-1
8" ø230 CFM
D-1
14"x
10"
SA
10"x8" EA
10"x8" EA10"x8" EA
14"x10" SA
8" ø230 CFM
D-1
8" ø235 CFM
D-18" ø
235 CFM
D-1
10"x10" SA
12"x12" TA
10"x8" OA
20"ø SA
16"ø
SA
16"ø
SA
12" ø565 CFM
D-4
TYP 4
10"x10" EA
10/10 EA DN
R-130" x 24"
1250 CFM
30"X12" RA UPTO RTU-F01
20"X20" SA UPTO RTU-F01
G-124" x 24"
12"x12" TA
HP-F23
12"ø SA
8"ø
EA
12"ø SA16
"x14
" S
A
34"x
14"
RA
14"x8" OA
8" ø250 CFM
D-1
8" ø250 CFM
?
8" ø250 CFM
D-1
8" ø250 CFM
D-1
8" ø230 CFM
D-1
8" ø240 CFM
D-1
8" ø230 CFM
D-1
G-224" x 24"
G-224" x 24"
12"x10" SA
12"x12" SA
24"x8" RA
G-224" x 24"
G-112" x 12"100 CFM
12"x12" TA
10" ø325 CFM
D-1
10" ø325 CFM
?
8" ø200 CFM
D-110" ø
275 CFM
D-1
8"x6
" O
A
G-124" x 24"
G-124" x 24"
G-124" x 24"
G-124" x 24"
G-124" x 24"
G-124" x 24"
G-124" x 24"
G-124" x 24"
G-124" x 24"
G-112" x 12"100 CFM
G-112" x 12"100 CFM
G-112" x 12"100 CFM
8"x8" TA
G-112" x 12"
G-112" x 12"
10"x
6" O
A
12"x
8" O
A
G-224"x24"G-2
24"x24"
G-224"x24"
G-224"x24"
G-224"x24"
G-224"x24"
G-224"x24"
G-224"x24"
G-112" x 12"
G-112" x 12"
G-112" x 12"150 CFM
G-112" x 12"150 CFM
CC- 1
GENERAL HVAC PLAN NOTES:
1. LIMIT ALL FLEXIBLE DUCT RUNS TO 3 FEET MAXIMUM LENGTH.FLEXIBLE DUCT(S) SHALL BE OF THE SAME SIZE AS THE DIFFUSERNECKS THAT THEY CONNECT TO UNLESS NOTED OTHERWISE.
2. COORDINATE EXACT LOCATIONS OF ALL DIFFUSERS WITHELECTRICAL, FIRE SPRINKLERS, AND GRID CEILINGS.
3. BALANCING DAMPERS SHALL BE LOCATED ABOVE ACCESSIBLE CEILINGS. IF THIS IS NOT POSSIBLE, ACCESS PANELS SHALL BE PROVIDED. ACCESS PANELS SHALL BE TAMPERPROOF
LOCKABLE ACCESS PANLES FOR ACCESS TO CONTROL VALVES,MOTORIZED DAMPERS, SHUT-OFF VALVES, AND SIMILARCOMPONENTS THAT ARE NOT LOCATED OVER AN ACCESSIBLECEILING. VOLUME DAMPERS SHALL BE PROVIDED WITH REMOTEDAMPER OPERATORS WITH ADJUSTABLE COVER IN NON-ACCESSABLE CEILING AREAS. SEE DETAIL 8, SHEET M4.2,"REMOTE VOLUME DAMPER" AND SPECIFICATIONS FORFURTHER INFORMATION.
4. PROVIDE CEILING AND/OR WALL ACCESS DOORS FOR ACCESS TODUCT ACCESS DOORS RELATED TO THE INSPECTION ANDRESETTING OF FIRE DAMPERS AND COMBINATION SMOKE ANDFIRE DAMPERS. PROVIDE MINIMUM 18" X 18" SIZE. CEILINGAND/OR WALL ACCESS DOOR RATING SHALL BE EQUIVALENT TOCEILING AND/OR WALL WHERE DOOR IS TO BE INSTALLED.
5. BRANCH DUCT SIZES SHALL BE THE SAME AS THE NECK SIZE OFTHE DIFFUSERS OR THE CONNECTION SIZE OF THE GRILLES,UNLESS NOTED OTHERWISE.
6. HORIZONTAL HEAT PUMPS:A. MANUFACTURER-RECOMMENDED SERVICE ACCESS AREAS
FOR HORIZONTAL HEAT PUMPS HAVE BEEN SHOWN ON THEPLANS.
B. LOCATE THE HORIZONTAL HEAT PUMP UNITS IN AREAS THATALLOW FOR EASY REMOVAL OF THE FILTER AND EASYACCESS TO HEAT PUMP UNIT ACCESS PANELS. LEAVEENOUGH SPACE FOR SERVICE PERSONNEL TO PERFORMMAINTENANCE OR REPAIR. PROVIDE SUFFICIENT ROOM TOMAKE WATER, ELECTRICAL, DUCT AND CONDENSATE DRAINCONNECTIONS.
C. IF ANY DUCTWORK OR PIPING (DOMESTIC WATER, FIRE,WATER LOOP, CONDENSATE DRAIN, NATURAL GAS,ELECTRICAL CONDUIT, CONTROLS CONDUIT IS RUN WITHINTHE SERVICE AREAS, THE PIPE, CONDUIT OR DUCT SHALL BEREMOVED AND RE-ROUTED IF POSSIBLE SO IT IS NOT WITHINTHE SERVICE AREA.
D. ALLOW ADEQUATE ROOM BELOW THE HEAT PUMP UNIT FORA CONDENSATE TRAP. DO NO LOCATE THE HEAT PUMP UNITABOVE ANY PIPING SYSTEMS WHERE POSSIBLE. EACHHORIZONTAL HEAT PUMP UNIT SHALL BE PROVIDED WITH AFILTER BRACKET FOR SIDE FILTER REMOVAL. THECONTRACTOR MAY CONVERT OR MODIFY THIS FILTERBRACKET TO ALLOW FOR BOTTOM REMOVAL OF THE FILTERIF IT PROVIDES A BETTER, MORE ACCESSIBLE INSTALLATION.
E. GENERALLY SPEAKING, HORIZONTAL HEAT PUMPS ARELOCATED AS HIGH AS POSSIBLE, BUT STILL ACCESSIBLEFROM A LADDER.
7. VERTICAL HEAT PUMPS:A. SEE 'VERTICAL HEAT PUMP INSTALLATION' DETAIL ON SHEET
M4.1 FOR REQUIREMENTS.
8. FOR OUTSIDE AIR SUPPLY DUCTWORK SIZES TO HEAT PUMPS,REFER TO HEAT PUMP SCHEDULE ON SHEET M5.1.
9. GENERALLY SPEAKING, DUCTWORK THROUGHOUT THE BUILDINGWAS LOCATED AS HIGH AS POSSIBLE TO ALLOW ROOM FORFITTINGS DOWN TO DIFFUSERS AND OTHER TRADES.
10. RTU EXHAUST OUT OF CLASSROOMS SHALL EQUAL THE OUTSIDEAIR CFM TO CLASSROOM UNLESS STATED OTHERWISE.
Arc
hite
ctu
re E
ngin
eering
P
lan
nin
g In
teriors
©
,
DL
R G
rou
p inc., a
Ne
bra
ska
co
rpo
ratio
n, A
LL
RIG
HT
S R
ES
ER
VE
D
KEY PLAN
LEGEND NOTESLEGEND NOTES ARE COMMON TO ALLSOME NOTES MAY NOT APPLY TO THIS SHEET
A
NO
RT
H
Rev
isio
ns
B
C
D
E
F
9/1
3/2
017 1
:08:2
4 P
M
C:\R
evit\1
0-1
3125-3
0_M
P_2016_C
entr
al_
mm
art
z.r
vt
10-1
3125-3
0
8/2
9/2
017
PLA
TT
EV
IEW
JR
HIG
H &
HIG
H S
CH
OO
L R
EN
OV
AT
ION
S
HV
AC
PLA
N, M
AIN
LE
VE
L -
AR
EA
FM1.2F
20
17
SP
RIN
GF
IELD
PLA
TT
EV
IEW
CO
MM
UN
ITY
SC
HO
OLS
NORTHSCALE: 1/8" = 1'-0"
HVAC PLAN, MAIN LEVEL - AREA F
CC
- 1
9/13
/17
AD
DE
ND
UM
CC
-1
UP
SS
S
S
S
S
S
S
SS
S
A
A
B
B
C
C
D
D
E
E
F
F
G
G
H
H
J
J
K
K
1
2
3
4 5
6
7
8
9
10
11
MEDIA CENTER
F121
1601 SF
STORAGE
F122
175 SF
GREEN ROOM
F123
180 SF
CLASSROOM
F120
791 SF
CORRIDOR
F101
947 SF
CLASSROOM
F119
718 SF
CLASSROOM
F118
714 SF
CLASSROOM
F117
725 SF
CLASSROOM
F110
703 SF
CORRIDOR
F116
382 SFCONFERENCE
ROOM
F115
213 SF
DATA
F113
134 SF
STORAGE
F114
59 SF
SCIENCE
F111
999 SF
CORRIDOR
107
453 SF
COMPUTER LAB
F108
747 SF
CLASSROOM
F109
742 SF
GIRLS
F106
163 SF
BOYS
F105
131 SF
CUSTODIAL
F102
207 SF
RAMP/STAIR
F1S1
715 SF
MECHANICAL
F103
583 SF
ELECTRICAL
F104
126 SF
VEST
F124
39 SF
HP-F06
HP-F05
HP-F07
HP-F03
HP
-F04
HP
-F02
HP-F01
HP-F11
HP-F08
HP
-F09
HP
-F10
1"1" CR1"1" CS
1"1" CR
1"1" CS
1 1/2"1 1/2" CS1 1/2"1 1/2" CR
3/4"3/4" CR3/4"3/4" CS
1 1/2"1 1/2" CS
1 1/2"1 1/2" CR
1"1" CR1"1" CS
1 1/2"1 1/2" CS
1 1/2"1 1/2" CR
1"1" CS1"1" CR 1 1/2"1 1/2" CR
1 1/2"1 1/2" CS
1"1" CS
1"1" CR
1"1" CR1"1" CS
1"1" CS1"1" CR
2"2" CS2"2" CR
1"1" CR1"1" CS
1"1" CS1"1" CR
2"2" CS2"2" CR
3/4"3/4" CS3/4"3/4" CR
1 1/4"1 1/4" CS
1 1/4"1 1/4" CR
2 1/2"2 1/2" CR2 1/2"2 1/2" CS
4"4" CR
4"4" CR
CONDESER WATER LINES ROUTEDUNDERGROUND TO GEOTHERMAL VAULT.SEE SITE UTILITY PLAN FOR CONTINUATION
CS/R PIPING UP. SEE SHEETM2.2F FOR CONTINUATION P-F02
P-F01
GENERAL HVAC PIPING PLAN NOTES:
1. VALVES SHALL BE LOCATED ABOVE ACCESSIBLE CEILINGS. IFTHIS IS NOT POSSIBLE, ACCESS PANELS SHALL BE PROVIDED.ACCESS PANELS SHALL BE TAMPERPROOF LOCKABLE PANELSFOR ACCESS TO CONTROL VALVES, MOTORIZED DAMPERS,SHUT-OFF VALVES, VOLUME DAMPERS AND SIMILAR COMPONENTSTHAT ARE NOT LOCATED OVER AN ACCESSIBLE CEILING.
2. GENERALLY SPEAKING, WATER LOOP PIPING SHALL BE RUN ASHIGH AS POSSIBLE, BETWEEN JOISTS AND THROUGH JOISTWEBBING TO PROVIDE MAXIMUM CLEARANCE TO DUCTWORK ANDOTHER TRADES. PIPING SHALL BE AT LOW ENOUGH ELEVATIONTO ALLOW PROPER BRANCH TAPS TO BE MADE (OFF TOP OF MAINS)AND ROUTED TO THEIR ASSOCIATED HEAT PUMPS. STACK PIPINGWHERE REQUIRED.
3. WLS AND WLR PIPING CONNECTIONS TO HEAT PUMPS ARE SIZEDAS SHOWN ON THE HEAT PUMP SCHEDULE. SEE SHEET M5.1.
4. CONDENSATE DRAIN (CD) PIPING IS SIZED AS SHOWN ON THEHEAT PUMP SCHEDULE. SEE SHEET M5.1. WHERE CD IS NOTSHOWN ON THE DRAWINGS, ROUTE TO THE NEAREST FLOORDRAIN.
5. HORIZONTAL HEAT PUMPS:A. MANUFACTURER-RECOMMENDED SERVICE ACCESS AREAS
FOR HORIZONTAL HEAT PUMPS HAVE BEEN SHOWN ON THEPLANS.
B. LOCATE THE HORIZONTAL HEAT PUMP UNITS IN AREAS THATALLOW FOR EASY REMOVAL OF THE FILTER AND EASYACCESS TO HEAT PUMP UNIT ACCESS PANELS. LEAVEENOUGH SPACE FOR SERVICE PERSONNEL TO PERFORMMAINTENANCE OR REPAIR. PROVIDE SUFFICIENT ROOM TOMAKE WATER, ELECTRICAL, DUCT AND CONDENSATE DRAINCONNECTIONS.
C. IF ANY DUCTWORK OR PIPING (DOMESTIC WATER, FIRE,WATER LOOP, CONDENSATE DRAIN, NATURAL GAS,ELECTRICAL CONDUIT, CONTROLS CONDUIT IS RUN WITHINTHE SERVICE AREAS, THE PIPE, CONDUIT OR DUCT SHALL BEREMOVED AND RE-ROUTED IF POSSIBLE SO IT IS NOT WITHINTHE SERVICE AREA.
D. ALLOW ADEQUATE ROOM BELOW THE HEAT PUMP UNIT FORA CONDENSATE TRAP. DO NO LOCATE THE HEAT PUMP UNITABOVE ANY PIPING SYSTEMS WHERE POSSIBLE. EACHHORIZONTAL HEAT PUMP UNIT SHALL BE PROVIDED WITH AFILTER BRACKET FOR SIDE FILTER REMOVAL. THECONTRACTOR MAY CONVERT OR MODIFY THIS FILTERBRACKET TO ALLOW FOR BOTTOM REMOVAL OF THE FILTERIF IT PROVIDES A BETTER, MORE ACCESSIBLE INSTALLATION.
E. GENERALLY SPEAKING, HORIZONTAL HEAT PUMPS ARELOCATED AS HIGH AS POSSIBLE, BUT STILL ACCESSIBLEFROM A LADDER.
6. VERTICAL HEAT PUMPS:A. SEE 'VERTICAL HEAT PUMP INSTALLATION' DETAIL ON SHEET
M4.1 FOR REQUIREMENTS.
7. BRANCH PIPING CONNECTIONS FROM THE PIPING MAINS SHALL BE TAKEN OFF THE TOP OR SIDES OF THE PIPE. BRANCH PIPING OFF THE BOTTOM OF THE WATER LOOP PIPING MAINS IS SPECIFICALLY PROHIBITED UNLESS IT HAS BEEN SPECIFICALLY SHOWN TO BE PIPEDOFF THE BOTTOM OF THE PIPING MAIN.
8. REFRIGERANT PIPE SIZES SHALL BE AS DETERMINED BY THESUCCESSFUL MANUFACTURER.
Arc
hite
ctu
re E
ngin
eering
P
lan
nin
g In
teriors
©
,
DL
R G
rou
p inc., a
Ne
bra
ska
co
rpo
ratio
n, A
LL
RIG
HT
S R
ES
ER
VE
D
KEY PLAN
LEGEND NOTESLEGEND NOTES ARE COMMON TO ALLSOME NOTES MAY NOT APPLY TO THIS SHEET
A
NO
RT
H
Rev
isio
ns
B
C
D
E
F
9/1
3/2
017 1
:08:2
5 P
M
C:\R
evit\1
0-1
3125-3
0_M
P_2016_C
entr
al_
mm
art
z.r
vt
10-1
3125-3
0
8/2
9/2
017
PLA
TT
EV
IEW
JR
HIG
H &
HIG
H S
CH
OO
L R
EN
OV
AT
ION
S
HV
AC
PIP
ING
PLA
N, LO
WE
R L
EV
EL -
AR
EA
FM2.1F
20
17
SP
RIN
GF
IELD
PLA
TT
EV
IEW
CO
MM
UN
ITY
SC
HO
OLS
NORTHSCALE: 1/8" = 1'-0"
HVAC PIPING PLAN, LOWER LEVEL - AREA F
CC
- 1
9/13
/17
AD
DE
ND
UM
CC
-1
CC- 1
DN
UP
S
S
S
S
S
SS
S
S
S
S H
A B C
D
E F G H J K
1
2
3
4 5
6
7
8
9
10
11
GYMNASIUM
F244
2718 SF
STORAGE
F245
159 SF
MECHANICAL
F246
73 SF
OFFICE
F235
64 SF
OFFICE
F234
64 SF
CLASSROOM
F233
922 SF
GIRLS
F243
208 SF
BOYS
F242
184 SF
STORAGE
F240
96 SF
KITCHEN
F239
585 SF
COORIDOR
F241
128 SF
ALCOVE
F236
68 SF
JANITOR
F237
95 SF
ELECTRICAL
F238
98 SF
LEARNINGCOMMONS
F232
1085 SF
RAMP/STAIR
F1S1
715 SF
CORRIDOR
F212
1373 SF
RECEPTION
F206
272 SF
WORK ROOM
F211
149 SFNURSE
F209
118 SF
TOILET
F210
62 SFGUIDANCE
F208
281 SF
PRINCIPAL
F207
244 SF
VEST
F201
126 SF
EARLYEDUCATION
F202
666 SF
EARLYEDUCATION
F203
473 SF
BOYS
F204
20 SF
GIRLS
F205
20 SF
TEACHERSLOUNGE
F220
344 SF
CORRIDOR
F219
203 SF
CLASSROOM
F221
746 SF
CLASSROOM
F222
757 SF
CLASSROOM
F228
725 SF
CLASSROOM
F229
713 SF
SPECIAL ED
F230
642 SF
OFFICE
F231
67 SF
STORAGE
F226
94 SF
CONFERENCEROOM
F225
236 SFSCIENCE
F223
1089 SF
ELEC
F224
65 SF
MENS
F218
63 SF
WOMENS
F217
64 SF
JANITOR
F216
44 SF
GIRLS
F214
163 SF
BOYS
F213
131 SF
CORRIDOR
F215
327 SF
COORIDOR
F227
384 SF
VEST
F247
45 SF
HP
-F22
HP
-F21
HP
-F20
HP
-F19
HP
-F18
HP
-F17
HP
-F16
HP
-F15
HP
-F14
HP
-F13
HP
-F24
HP
-F12
HP-F23
HP-F25
1"1" CR1"1" CS
1 1/4"1 1/4" CR
1 1/4"1 1/4" CS
1 1/2"1 1/2" CS
1 1/2"1 1/2" CR
1"1" CR
1"1" CS
1 1/2"1 1/2" CS
1 1/2"1 1/2" CR
1 1/2"1 1/2" CR1 1/2"1 1/2" CS
1"1" CR1"1" CS 2 1/2"2 1/2" CS
2 1/2"2 1/2" CR
1"1" CR1"1" CS
2 1/2"2 1/2" CS
2 1/2"2 1/2" CR
1"1" CR
1"1" CS
2 1/2"2 1/2" CS
2 1/2"2 1/2" CR
1"1" CR
1"1" CS
2 1/2"2 1/2" CS
2 1/2"2 1/2" CR
1 1/4"1 1/4" CS
1 1/4"1 1/4" CR
1"1" CR1"1" CS
1 1/2"1 1/2" CS
1 1/2"1 1/2" CR
3"3" CR3"3" CS
3"3" CS3"3" CR
1 1/2"1 1/2" CR1 1/2"1 1/2" CS
1"1" CS
1"1" CR
1 1/2"1 1/2" CR
1 1/2"1 1/2" CS
1"1" CS
1"1" CR
1"1" CS
1"1" CR
1 1/4"1 1/4" CS1 1/4"1 1/4" CR
4"4" CS
4"4" CR
P-F01
P-F02
2-1/2" CS/R DOWN TOSERVE LOWER LEVEL
4" CONDENSER WATER THRUWALL TO CEILING PLENUM.ROUTE PIPING TO EXTERIORPLUMBING CHASE.
ROUTE PIPING AS HIGH ASPOSSIBLE IN JOIST SPACEABOVE CORRIDOR.
CC- 1
GENERAL HVAC PIPING PLAN NOTES:
1. VALVES SHALL BE LOCATED ABOVE ACCESSIBLE CEILINGS. IFTHIS IS NOT POSSIBLE, ACCESS PANELS SHALL BE PROVIDED.ACCESS PANELS SHALL BE TAMPERPROOF LOCKABLE PANELSFOR ACCESS TO CONTROL VALVES, MOTORIZED DAMPERS,SHUT-OFF VALVES, VOLUME DAMPERS AND SIMILAR COMPONENTSTHAT ARE NOT LOCATED OVER AN ACCESSIBLE CEILING.
2. GENERALLY SPEAKING, WATER LOOP PIPING SHALL BE RUN ASHIGH AS POSSIBLE, BETWEEN JOISTS AND THROUGH JOISTWEBBING TO PROVIDE MAXIMUM CLEARANCE TO DUCTWORK ANDOTHER TRADES. PIPING SHALL BE AT LOW ENOUGH ELEVATIONTO ALLOW PROPER BRANCH TAPS TO BE MADE (OFF TOP OF MAINS)AND ROUTED TO THEIR ASSOCIATED HEAT PUMPS. STACK PIPINGWHERE REQUIRED.
3. WLS AND WLR PIPING CONNECTIONS TO HEAT PUMPS ARE SIZEDAS SHOWN ON THE HEAT PUMP SCHEDULE. SEE SHEET M5.1.
4. CONDENSATE DRAIN (CD) PIPING IS SIZED AS SHOWN ON THEHEAT PUMP SCHEDULE. SEE SHEET M5.1. WHERE CD IS NOTSHOWN ON THE DRAWINGS, ROUTE TO THE NEAREST FLOORDRAIN.
5. HORIZONTAL HEAT PUMPS:A. MANUFACTURER-RECOMMENDED SERVICE ACCESS AREAS
FOR HORIZONTAL HEAT PUMPS HAVE BEEN SHOWN ON THEPLANS.
B. LOCATE THE HORIZONTAL HEAT PUMP UNITS IN AREAS THATALLOW FOR EASY REMOVAL OF THE FILTER AND EASYACCESS TO HEAT PUMP UNIT ACCESS PANELS. LEAVEENOUGH SPACE FOR SERVICE PERSONNEL TO PERFORMMAINTENANCE OR REPAIR. PROVIDE SUFFICIENT ROOM TOMAKE WATER, ELECTRICAL, DUCT AND CONDENSATE DRAINCONNECTIONS.
C. IF ANY DUCTWORK OR PIPING (DOMESTIC WATER, FIRE,WATER LOOP, CONDENSATE DRAIN, NATURAL GAS,ELECTRICAL CONDUIT, CONTROLS CONDUIT IS RUN WITHINTHE SERVICE AREAS, THE PIPE, CONDUIT OR DUCT SHALL BEREMOVED AND RE-ROUTED IF POSSIBLE SO IT IS NOT WITHINTHE SERVICE AREA.
D. ALLOW ADEQUATE ROOM BELOW THE HEAT PUMP UNIT FORA CONDENSATE TRAP. DO NO LOCATE THE HEAT PUMP UNITABOVE ANY PIPING SYSTEMS WHERE POSSIBLE. EACHHORIZONTAL HEAT PUMP UNIT SHALL BE PROVIDED WITH AFILTER BRACKET FOR SIDE FILTER REMOVAL. THECONTRACTOR MAY CONVERT OR MODIFY THIS FILTERBRACKET TO ALLOW FOR BOTTOM REMOVAL OF THE FILTERIF IT PROVIDES A BETTER, MORE ACCESSIBLE INSTALLATION.
E. GENERALLY SPEAKING, HORIZONTAL HEAT PUMPS ARELOCATED AS HIGH AS POSSIBLE, BUT STILL ACCESSIBLEFROM A LADDER.
6. VERTICAL HEAT PUMPS:A. SEE 'VERTICAL HEAT PUMP INSTALLATION' DETAIL ON SHEET
M4.1 FOR REQUIREMENTS.
7. BRANCH PIPING CONNECTIONS FROM THE PIPING MAINS SHALL BE TAKEN OFF THE TOP OR SIDES OF THE PIPE. BRANCH PIPING OFF THE BOTTOM OF THE WATER LOOP PIPING MAINS IS SPECIFICALLY PROHIBITED UNLESS IT HAS BEEN SPECIFICALLY SHOWN TO BE PIPEDOFF THE BOTTOM OF THE PIPING MAIN.
8. REFRIGERANT PIPE SIZES SHALL BE AS DETERMINED BY THESUCCESSFUL MANUFACTURER.
Arc
hite
ctu
re E
ngin
eering
P
lan
nin
g In
teriors
©
,
DL
R G
rou
p inc., a
Ne
bra
ska
co
rpo
ratio
n, A
LL
RIG
HT
S R
ES
ER
VE
D
KEY PLAN
LEGEND NOTESLEGEND NOTES ARE COMMON TO ALLSOME NOTES MAY NOT APPLY TO THIS SHEET
A
NO
RT
H
Rev
isio
ns
B
C
D
E
F
9/1
3/2
017 1
:08:2
9 P
M
C:\R
evit\1
0-1
3125-3
0_M
P_2016_C
entr
al_
mm
art
z.r
vt
10-1
3125-3
0
8/2
9/2
017
PLA
TT
EV
IEW
JR
HIG
H &
HIG
H S
CH
OO
L R
EN
OV
AT
ION
S
HV
AC
PIP
ING
PLA
N, M
AIN
LE
VE
L -
AR
EA
FM2.2F
20
17
SP
RIN
GF
IELD
PLA
TT
EV
IEW
CO
MM
UN
ITY
SC
HO
OLS
NORTHSCALE: 1/8" = 1'-0"
HVAC PIPING PLAN, MAIN LEVEL - AREA F
CC
- 1
9/13
/17
AD
DE
ND
UM
CC
-1
UP
S
S
S
S
S
FS
S S
S
S
S
S
SS
S
S
S
S
S
S
SS
S
S
S
S
S
P
TW
TW
TW
TW
TW
TW
TW
TW
P
P
P
P
P
P
PTW
M
M
ELECTRICAL
F104
MECHANICAL
F103
CUSTODIAL
F102
BOYS
F105
GIRLS
F106
COMPUTER LAB
F108
CLASSROOM
F109
CLASSROOM
F110
SCIENCE
F111
DATA
F113
CONFERENCEROOM
F115
CLASSROOM
F117
CLASSROOM
F118
CLASSROOM
F119
VEST
F124
MEDIA CENTER
F121
STORAGE
F122
CLASSROOM
F120
GREEN ROOM
F123
CORRIDOR
F101
CORRIDOR
F116
CORRIDOR
107
RAMP/STAIR
F1S1
36"
STORAGE
F114
LS
MSB
DP1
T1
ATS
36"
36"
36"
36"
36"
36"
42"
42"
TVHP-F07
HP-F04
HP-F05
HP-F03
HP-F02
HP-F01
HP-F08
HP-F06
36"
L3 - 1
L3 - 3
L3 - 5
L3 - 7
L3 - 9
L3 - 11
L3 - 13
L3 - 19
L3 - 23
L3 - 29
L3 - 31
L3 - 22
L3 - 24
L3 - 2
L3 - 18
L3 - 20
L3 - 25
L3 - 4
L3 - 6
L3 - 8L3 - 10
L3 - 12
L3 - 14,16
HP-F11
HP-F10
L3 - 28
L2 - 14
L2 - 16L2 - 10
L3 - 37
1
12
22
L3 - 33
DP1 - 13
3
4
4
4
4
4
4
4
4
E2.1F
2
L3 - 27
1
L3 - 26
L3 - 17
L3 - 15
L3 - 35
7DP1 - 1
DP1 - 3
8
L2 - 12
L3 - 21
E6.1
34Sim
1' -
6"
MIN
9
2' - 6" MAX
WP
HP-F09
DP1 - 5
10
11
DP1 - 9
12
12
L3 - 41
WPL3 - 30
13
GDWH-F103
L3 - 64
12
P-F03
P-F04
FIRE PUMP
JOCKEY PUMP
16
78"
FIRE PUMPROOM
F103A
UH-F1
POWER NOTES(TYPICAL ALL POWER SHEETS)
1. MOUNT POWER RECEPTACLES DENOTED 'TV' AT THE SAMEHEIGHT AND WITHIN 8" OF ASSOCIATED TV OUTLET.
2. RECEPTACLES DENOTED 'R' OR 'ROOF' SHALL BE MOUNTED TO AUNISTRUT FRAME ON ROOF, GFCI-TYPE AND MOUNTED IN AWEATHERPROOF BOX WITH WEATHERPROOF IN-USE COVER A MINIMUMOF 18" ABOVE ROOF STRUCTURE.
3. SPECIAL RECEPTACLES: TO ENSURE PROPER INSTALLATION,VERIFY JUNCTION BOX AND WALL PLATE REQUIREMENTS FORSPECIALTY DEVICES PRIOR TO ROUGH-IN.
4. VERIFY OWNER'S PREFERENCE FOR PANEL DIRECTORIES.DIRECTORIES SHALL REFLECT OWNER'S NUMBERING SCHEME ANDNOT THE ARCHITECTURAL NUMBERING SCHEME. OBTAIN REQUIREDINPUT FROM OWNER PRIOR TO FABRICATION OF TYPED PANELDIRECTORIES.
5. PROVIDE MINIMUM OF 24-INCHES SEPARATION BETWEEN BOXESLOCATED BACK-TO-BACK AT ALL FIRE-RATED WALLS.
6. PROVIDE POWER FROM DESIGNATED 20/1P BREAKER IN NEARESTPANEL TO EACH SMOKE DAMPERS IN AREA. WIRE THRU FIRE ALARMSYSTEM RELAYS.
7. SEE SCHEDULE SHEETS FOR CONNECTIONS TO ALL MECHANICALEQUIPMENT, INCLUDING DISCONNECTS & STARTERS PROVIDED BYDIVISION 26. COORDINATE MOUNTING OF DISCONNECTS ANDSTARTERS WITH SURROUNDING EQUIPMENT AND PROVIDE ADEQUATECLEARANCES AS REQUIRED BY NEC.
8. SEE MECHANICAL AND PLUMBING DRAWINGS TO CONFIRMLOCATIONS OF ALL HVAC EQUIPMENT, WATER HEATERS, PUMPS,EXHAUST FANS, DAMPERS, THERMOSTATS, HUMIDISTATS, SENSORS,CONTROL DEVICES, CONTROL PANELS, ETC.
78" 78"78"
78"
78" 78"
L3
DATA
F113
L3 - 43L3 - 45,47
L3 - 49,51,53
5 6
L3 - 57
E6.1
33Sim
T378"
.
14
15
AC-F1
17
Arc
hite
ctu
re E
ngin
eering
P
lan
nin
g In
teriors
©
,
DL
R G
rou
p inc., a
Ne
bra
ska
co
rpo
ratio
n, A
LL
RIG
HT
S R
ES
ER
VE
D
KEY PLAN
A
NO
RT
H
Rev
isio
ns
B
C
D
E
F
9/1
2/2
017 4
:26:3
5 P
M
C:\R
evit\1
0-1
3125-3
0_E
L_2016_C
entr
al_
mw
urs
t.rv
t
10-1
3125-3
0
8/2
9/2
017
PLA
TT
EV
IEW
JR
HIG
H &
HIG
H S
CH
OO
L R
EN
OV
AT
ION
S
PO
WE
R P
LA
N, LO
WE
R L
EV
EL -
AR
EA
FE2.1F
20
17
SP
RIN
GF
IELD
PLA
TT
EV
IEW
CO
MM
UN
ITY
SC
HO
OLS
NORTHSCALE: 1/8" = 1'-0"
POWER PLAN, LOWER LEVEL - AREA F
KEYED NOTES
KEY VALUE KEY TEXT
1 REUSE EXISTING BOX, ROUTE CONDUIT ON BACKSIDE OFWALL.
2 NEW DEVICE ONLY, REUSE EXISTING CIRCUITING.EXISTING CIRCUIT SHOWN FOR REFERENCE,CONTRACTOR TO CONFIRM.
3 MOUNT SURFACE RACEWAY THIS ROOM AT 36 INCHES.
4 PROJECTOR RECEPTACLES SHALL BE INSTALLED FLUSHIN CEILING, POWER TO RECEPTACLE SHALL BE ROUTEDVIA FLEXIBLE METALLIC CONDUIT (W/ 12' SERVICE LOOP)FED FROM A JUNCTION BOX LOCATED 24" ABOVE LAY-INCEILING. JUNCTION BOX SHALL BE DIRECTLY ABOVERECEPTACLE AND RIGIDLY SUPPORTED BY STRUCTUREOR THREADED ROD AND UNISTRUT HUNG FROMSTRUCTURE ABOVE (HIGH STRUCTURE APPLICATIONS).
5 LABEL RECEPTACLES THIS ROOM WITH CIRCUIT NAMEAND NUMBER.
6 ALL WALL-MOUNTED ELECTRICAL DEVICES FLUSHMOUNTED THIS ROOM.
7 POWER FOR SMOKE CURTAIN, PROVIDE MOTOR RATEDSWITCH ABOVE CEILING FOR LOCAL DISCONNECT,CIRCUIT PER MANUFACTURER'S RECOMMENDATIONS.
8 COORDINATE ELECTRICAL CONNECTION FOR LIFT WITHREVIEWED SHOP DRAWINGS. DISCONNECT PROVIDED BYLIFT MANUFACTURER.
9 APPROXIMATE LOCATION OF EXISTING UNDERGROUNDCONDUITS. COORDINATE WITH NEW SWITCHBOARD.LOCATE SWITCHBOARD AS FAR SOUTH AS POSSIBLEWHILE STILL UTILIZING EXISTING SERVICE CONDUITSFROM TRANSFORMER.
10 WATER HEATER POWER, COORDINATE WITH DIVISION 23.
11 EMERGENCY POWER OFF DEVICE CONNECTED TO SHUNTTRIP ACCESSORY IN CIRCUIT BREAKER FOR WATERHEATER. ACTIVATION OF SWITCH SHALL SHUT OFFPOWER TO UNIT.
12 POWER FOR SUMP PUMP, GFCI RECEPTACLE TO BEPROVIDED WITH AUDIBLE ALARM.
13 INSTALL RECEPTACLE IN WELL FIELD VAULT FOR SUMPPUMP. COORDINATE WITH DIVISION 23 AND SITE PLAN.
14 NEMA 4 ENCLOSED CIRCUIT BREAKER.
15 TRANSFORMER T3 CIRCUITED TO EMERGENCYRECEPTACLE FOR DISTRIBUTED ANTENNA SYSTEM (DAS).SEE ONE-LINE DIAGRAM FOR CIRCUIT INFORMATION.LABEL RECEPTACLE WITH CIRCUIT. MOUNTTRANSFORMER AND DISCONNECTING MEANS ON WALL,STACK EQUIPMENT ON WALL TO MINIMIZE WALL AREA.MOTOR RATED TOGGLE FOR PRIMARY DISCONNECT ANDENCLOSED CIRCUIT BREAKER FOR SECONDARYDISCONNECT. ALL EQUIPMENT TO BE NEMA 4, ORINSTALLED IN A NEMA 4 ENCLOSURE.
16 GOGGLE CABINET POWER.
17 INSTALL RECEPTACLE FOR DAS SYSTEM IN NEMA 4ENCLOSURE WITH DAS. COORDINATE INSTALLATION WITHDAS INSTALLER. SEE ONE-LINE FOR CIRCUITINFORMATION.
SCALE: 1/4" = 1'-0"E2.1F
2 F113 - LARGE SCALE POWER PLAN CC
-19/
13/1
7A
DD
EN
DU
M C
C-1
CC-1
CC-1
CC-1
CC-1
DN
UP
FS
S S
FS
S
SS
S
S
SS
SS
FS
FS
FS
FS
SS
FS
S
SS
S
S
S
S
S
SS
S
S
S
S H
S
S
TW
TW
TW
TW
TW
TW
TW
P
P
P
P
P
P
P
TV
TV
TW
TW
M
J J J
J
J J
J
J
J
J
J
J
J
J
GYMNASIUM
F244
KITCHEN
F239
STORAGE
F240
VEST
F247
OFFICE
F234
STORAGE
F245
CLASSROOM
F233
GIRLS
F243BOYS
F242ELECTRICAL
F238
COORIDOR
F241
VEST
F201
EARLYEDUCATION
F202
EARLYEDUCATION
F203BOYS
F204
GIRLS
F205
BOYS
F213
GIRLS
F214
PRINCIPAL
F207
NURSE
F209
WORK ROOM
F211
GUIDANCE
F208
CLASSROOM
F222
CLASSROOM
F221
SPECIAL ED
F230JANITOR
F216
CLASSROOM
F228
TEACHERSLOUNGE
F220
WOMENS
F217
MENS
F218
CLASSROOM
F229
SCIENCE
F223
CONFERENCEROOM
F225
ELEC
F224
RECEPTION
F206
CORRIDOR
F212
LEARNINGCOMMONS
F232
CORRIDOR
F215
CORRIDOR
F219
COORIDOR
F227
OFFICE
F231
JANITOR
F237
TOILET
F210
STORAGE
F226
42"
42"
42"
24" 60"
TV
H1
L1
H2 L2 T2
36"
36"
36"
36"
42"
42"
36"
42"
36"
36"
OFFICE
F235
TV
42"
42"
TR TR
TR
TR
TR
45" 45" 45" 45" 45"
33" 33" 33" 33" 33"
RTU-F01
DOAS-F01
DOAS-F02
42"NEMA 14-30R
42"
1
1
P-F02 P-F01
L2 - 7
L2 - 13
L2 - 15
L2 - 19
L2 - 21
L2 - 23
11
1
1
L2 - 27
L2 - 31
L2 - 37
L2 - 41
L1 - 1
L1 - 3
L1 - 7
L1 - 9
L1 - 11
L1 - 13
L1 - 15L1 - 17
L1 - 21
L1 - 23
L1 - 25
L1 - 27
L1 - 29
L1 - 31
L1 - 33
L1 - 35
L1 - 37
L1 - 39
L1 - 41
L1 - 2
L1 - 8
L1 - 10
L1 - 12
L1 - 20
L1 - 22
L1 - 24
L1 - 18
L1 - 16
L2 - 4,6
L2 - 17
MECHANICAL
F246
26" 26"
L1 - 19
L1 - 5
L2 - 33
L2 - 29
L2 - 25
L1 - 14
L1 - 4
1 1
1
L2 - 9
L1 - 26
42" 42"
2
3
L1 - 6
36"
4
4
4
4
44
4
L2 - 11
L2 - 2
L2 - 39
L2 - 1,3,5
5
6
7
77
8
RAMP/STAIR
F1S1
L2 - 35
L1 - 30
L2 - 8
34"
78"
9
HP-F24
L4
K
L4
10
10
10
HP-F25
HP-F12
?
HP-F14
HP-F20
HP-F19
HP-F22
L1 - 28
R
R
R
11
11
11
12
13
HP-F18
EF-F1EF-F2
L1 - 40
CU-F1
STORAGE
F248
HP-F17
HP-F16
HP-F15
HP-F21
HP-F23
Arc
hite
ctu
re E
ngin
eering
P
lan
nin
g In
teriors
©
,
DL
R G
rou
p inc., a
Ne
bra
ska
co
rpo
ratio
n, A
LL
RIG
HT
S R
ES
ER
VE
D
KEY PLAN
A
NO
RT
H
Rev
isio
ns
B
C
D
E
F
9/1
2/2
017 4
:26:3
6 P
M
C:\R
evit\1
0-1
3125-3
0_E
L_2016_C
entr
al_
mw
urs
t.rv
t
10-1
3125-3
0
8/2
9/2
017
PLA
TT
EV
IEW
JR
HIG
H &
HIG
H S
CH
OO
L R
EN
OV
AT
ION
S
PO
WE
R P
LA
N, M
AIN
LE
VE
L -
AR
EA
FE2.2F
20
17
SP
RIN
GF
IELD
PLA
TT
EV
IEW
CO
MM
UN
ITY
SC
HO
OLS
NORTHSCALE: 1/8" = 1'-0"
POWER PLAN, MAIN LEVEL - AREA F
KEYED NOTES
KEY VALUE KEY TEXT
1 NEW DEVICE ONLY, REUSE EXISTING CIRCUITING.EXISTING CIRCUIT SHOWN FOR REFERENCE,CONTRACTOR TO CONFIRM.
2 GAS EMERGENCY SHUTDOWN PANEL BY DIVISION 23.PROVIDE CONDUIT AND CONNECT PANEL TO REMOTEPANIC ASSEMBLY AND GAS VALVE IN CORRIDOR.COORDINATE EXACT REQUIREMENTS WITH DIVISION 23.
3 SINGLE GANG BOX FOR REMOTE PANIC ASSEMBLY FORGAS EMERGENCY SHUTDOWN BY DIVISION 23.
4 PROJECTOR RECEPTACLES SHALL BE INSTALLED FLUSHIN CEILING, POWER TO RECEPTACLE SHALL BE ROUTEDVIA FLEXIBLE METALLIC CONDUIT (W/ 12' SERVICE LOOP)FED FROM A JUNCTION BOX LOCATED 24" ABOVE LAY-INCEILING. JUNCTION BOX SHALL BE DIRECTLY ABOVERECEPTACLE AND RIGIDLY SUPPORTED BY STRUCTUREOR THREADED ROD AND UNISTRUT HUNG FROMSTRUCTURE ABOVE (HIGH STRUCTURE APPLICATIONS).
5 MOUNT RECEPTACLE IN FUME HOOD. CONNECT LIGHTSWITCH AND LIGHT FIXTURE FURNISHED IN FUME HOODTO RECEPTACLE CIRCUIT.
6 INSTALL DOOR ACTUATOR AND COVER BY DIVISION 8,CONNECT ELECTRIFIED DOOR HARDWARE TO BEACTIVATED BY AUTO OPERATOR. DOOR ACTUATORMOUNTED TO MULLION. COORDINATE ELECTRICALPATHWAY THROUGH MULLION. TYPICAL 2 ACTUATORLOCATIONS THIS ENTRY.
7 CONNECT TO POWER DOOR OPERATOR MOTOR, ALLWIRING BY DIVISION 26.
8 INSTALL DOOR ACTUATOR AND COVER BY DIVISION 8,CONNECT ELECTRIFIED DOOR HARDWARE TO BEACTIVATED BY AUTO OPERATOR. DOOR ACTUATORMOUNTED TO MULLION. COORDINATE ELECTRICALPATHWAY THROUGH MULLION. TYPICAL 4 ACTUATORLOCATIONS THIS ENTRY.
9 GOGGLE CABINET POWER.
10 CONNECT ELECTRIFIED DOOR HARDWARE TO POWERSUPPLY ABOVE CEILING. POWER SUPPLY BY DIVISION 8,ALL WIRING BY DIVISION 26. COORDINATE WITH ACCESSCONTROL BY OWNER.
11 MOUNT RECEPTACLE ON UNISTRUT FRAME ON ROOF.
12 GENERATOR ANNUNCIATOR PANEL, COORDINATEREQUIREMENTS WITH GENERATOR MANUFACTURER.
13 DEEP DRIVEN GROUND ROD IN TEST WELL. COORDINATELOCATION WITH SITE PLAN. SEE GROUNDING DIAGRAM.
CC
-19/
13/1
7A
DD
EN
DU
M C
C-1
CC-1
CC-1
CC-1
CC-1
UP
S
S
S
S
S
FS
S S
S
S
S
S
S
S
S
S
P
AP
F
75
S
TW
TW
TW
TW
TW
TW
TW
TW
P
P
P
P
P
S
S
S
S
S
AP
AP
AP
AP
AP P
S
F
30
F
30
F
75
F
75
F
15
F
30
F
75
F
15
F
75
F
15
F
15
F
15
F
15
F
15
F
15
F
F
F
F
F
15
F
F
15
F
15
P
S
AP
S
AP
S
F
15
TV
S
S
S S
S
S
S
S
S
S
V
S
S
S
S
P
PP
P
P
PP
P
P
P
P
P
P
TW
AP
P
P
S
S P
S
S
F 15
MJ
P
TS FS M
AP
F
110
F
15
F
15
F
15
P
F
75
SP
F
15
M
BOYS
F105
GIRLS
F106
ELECTRICAL
F104
MECHANICAL
F103
VEST
F124
STORAGE
F122
MEDIA CENTER
F121
COMPUTER LAB
F108
CLASSROOM
F109
CLASSROOM
F110
CLASSROOM
F120
CLASSROOM
F117
CLASSROOM
F119
CLASSROOM
F118
SCIENCE
F111 CONFERENCEROOM
F115
DATA
F113
CUSTODIAL
F102CORRIDOR
F101
CORRIDOR
F116
0, 1, 0
E6.1
14Sim
TYPICAL
GREEN ROOM
F123
0, 1, 0
0, 1, 0
0, 1, 0
0, 1, 0
0, 1, 0
STORAGE
F114
0, 1, 0
CORRIDOR
107
RAMP/STAIR
F1S1
1
0, 2, 0
0, 2, 00, 2, 0 0, 2, 0 0, 2, 0
0, 2, 0
0, 2, 0
0, 2, 0
0, 2, 0
0, 2, 0
0, 2, 0
0, 2, 0
0, 1, 0
2
0, 1, 0
0, 2, 0
0, 2, 0
0, 2, 0
0, 2, 0
0, 2, 0
0, 2, 0
0, 2, 0
0, 2, 0
0, 2, 00, 2, 0
E3.1F
3
E3.1F
2
1112
DS
0, 2, 0
13
0, 2, 0
(2) 2" C.
0, 1, 0
14
2, 0, 0
15
FIRE PUMPROOM
F103A
(2) 3" C.(2) 3" C.
(2) 3" C.
SPECIAL SYSTEMS NOTES(TYPICAL ALL SPECIAL SYSTEMS SHEETS)
1. EXISTING SYSTEMS FOR CONNECTION AT THE HIGH SCHOOLLOCATED APPROXIMATELY 160 FEET NORTH IN MAIN OFFICE.
A. NOTIFIER FIRE ALARM CONTROL PANELB. BOGEN INTERCOM SYSTEMC. SYSTIMAX TIME CONTROL CENTER CLOCK SYSTEM
2. SLEEVES FOR LOW VOLTAGE CABLES: PROVIDE SLEEVES PERSECTION 270500. COORDINATE WITH PATH OF DUCTWORK AND PIPESTO ENSURE ACCESSIBILITY. INSTALL ALL SLEEVES 12" ABOVE HIGHERCEILING OF TWO ADJACENT SPACES (REFER TO ROOM FINISHSCHEDULES AND REFLECTED CEILING PLANS FOR CEILING HEIGHTS).STUB SLEEVES INTO JOIST SPACE OF FINISHED ROOMS WITH EXPOSEDSTRUCTURE. PROVIDE INSULATED BUSHINGS ON BOTH ENDS OF EMTSLEEVES, INCLUDING UNUSED SLEEVES. PROVIDE GROUT TO SECURESLEEVES TO WALL. FIRESTOP AT ALL FIRE-RATED WALLS WHEREREQUIRED FOR UL LISTING OF FIRE-RATED WALL CABLE PATHWAYASSEMBLY.
3. INSTALL SLEEVES FOR INSTALLATION OF ALL LOW VOLTAGECABLING. FOLLOW INDUSTRY STANDARDS TO MAINTAIN 40% FILLREQUIREMENTS IN ALL SLEEVES. PROVIDE ADDITIONAL SLEEVES(MEETING REQUIREMENTS) AS REQUIRED.
4. MOUNT TELECOMMUNICATIONS OUTLETS AT THE SAME HEIGHTAND WITHIN 8" OF NEAREST ADJACENT RECEPTACLE UNLESS NOTEDOTHERWISE. DO NOT SCALE OFF OF SPECIAL SYSTEMS PLANS FOREXACT DEVICE LOCATIONS.
5. COMMUNICATIONS OUTLET RACEWAYS SHALL BE ROUTED UP WITHSWEEP BENDS UNLESS SHOWN AS UGC.
6. EXPOSED CABLES IN FINISHED SPACES: PROVIDE 3/4 INCH MINIMUMCONDUIT FOR ALL LOW-VOLTAGE CABLES IN EXPOSED STRUCTUREAREAS ROUTED TO ACCESSIBLE SPACE ABOVE NEAREST LAY-INCEILING. PAINT ALL CONDUIT, BOXES, AND ASSOCIATED MOUNTINGHARDWARE TO MATCH ADJACENT FINISHES.
7. PROVIDE SURFACE MOUNT SPEAKER ENCLOSURES FOR ALLCEILING MOUNTED SPEAKERS IN LOCATIONS WITH NO CEILINGS(EXPOSED STRUCTURE).
8. DO NOT INSTALL CABLES ABOVE STRUCTURAL MEMBERS IN ROOFDECK SPACES.
9. CABLE TRAY AND SLEEVES SHALL BE FIRESTOPPED AND SMOKESTOPPED THROUGH FIRE/SMOKE-RATED WALLS PER MFR'SRECOMMENDATIONS AND MATERIALS SPECIFIED IN DIVISION 7. USEREMOVABLE PILLOWS OR NON-HARDENING PUTTY.
10. S OR FS - SMOKE OR FIRE/SMOKE DAMPER SYMBOL.PROVIDE CONNECTION TO FIRE ALARM SYSTEM. PROVIDE FA RELAYAND DUCT DETECTOR WITH REMOTE INDICATOR LAMP AND TESTSWITCH FOR ACTUATION OF DAMPER. DETECTION AND ACTUATIONSHALL BE COMPLIANT WITH IBC 2006 SECTION 716.3.2.1 TYPICAL FOREACH DAMPER SHOWN.
11. PROVIDE RELAY(S) FOR FAN SHUTDOWN OF COMMON DUCTEDMECHANICAL EQUIPMENT AT EACH MECH UNIT. (REFER TO HVAC PLANSFOR EQUIPMENT LOCATION AND DUCTS). UNITS LISTED ON E7.2MECHANICAL CONNECTION SCHEDULES. COORDINATE EFFORT WITHDIVISION 23. FIRE ALARM SYSTEM SHALL CONNECT DIRECTLY TOMECHANICAL UNITS SHOWN ON SCHEDULE AND SHUT-DOWNCORRESPONDING UNITS UPON ACTIVATION OF COMMON DUCTEDDETECTION AS SPECIFIED.
12. PROVIDE FIRE ALARM MONITORING OF ALL FLOW SWITCHES,TAMPER SWITCHES, AND POST INDICATOR VALVES. COORDINATEQUANTITIES AND LOCATION WITH DIVISION 21 CONTRACTOR.
13. OUTLETS FOR TELECOM, FIRE ALARM, SECURITY, ACCESSCONTROL, AND ALL OTHER LOW VOLTAGE CABLING: PROVIDEINSULATED BUSHINGS ON ALL CONDUIT STUB-UPS, INCLUDING UNUSEDSTUB-UPS OR STUB-UPS INDICATED FOR FUTURE USE.
14. PROJECTORS ARE OWNER FURNISHED, OWNER INSTALLED,SHOWN FOR COORDINATION ONLY.
7
89
10
E6.1
25
DATA
F113
16
3' -
7"
3
45
6
DATA
F113
Arc
hite
ctu
re E
ngin
eering
P
lan
nin
g In
teriors
©
,
DL
R G
rou
p inc., a
Ne
bra
ska
co
rpo
ratio
n, A
LL
RIG
HT
S R
ES
ER
VE
D
KEY PLAN
A
NO
RT
H
Rev
isio
ns
B
C
D
E
F
9/1
2/2
017 4
:26:3
7 P
M
C:\R
evit\1
0-1
3125-3
0_E
L_2016_C
entr
al_
mw
urs
t.rv
t
10-1
3125-3
0
8/2
9/2
017
PLA
TT
EV
IEW
JR
HIG
H &
HIG
H S
CH
OO
L R
EN
OV
AT
ION
S
SP
EC
IAL S
YS
TE
MS
PLA
N, LO
WE
R L
EV
EL -
AR
EA
FE3.1F
20
17
SP
RIN
GF
IELD
PLA
TT
EV
IEW
CO
MM
UN
ITY
SC
HO
OLS
NORTHSCALE: 1/8" = 1'-0"
SPECIAL SYSTEMS PLAN, LOWER LEVEL - AREA F
KEYED NOTES
KEY VALUE KEY TEXT
1 SWEEP BEND (3) - 4 INCH CONDUITS THROUGH WALL ANDUP INTO ELECTRICAL ROOM ABOVE. ROUTE CONDUIT 8FEET UP WALL WITH BUSHINGS ON BOTH ENDS.
2 MOUNT TW DEVICES AT 42" ADJACENT TO ABOVECOUNTER RECEPTACLE THIS ROOM.
3 18 INCH CABLE RUNWAY AT 7'-8".
4 PROVIDE CABLE DROP-OUTS 3'-0" ON CENTER AT WALLFIELD.
5 PROVIDE RADIUS CORNER BRACKETS FOR ALL CABLERUNWAY.
6 PROVIDE CABLE DROP-OUTS AT EACH VERTICAL CABLEMANAGEMENT.
7 FRAMED CABLE ADMINISTRATION DRAWINGS WITHPLEXIGLASS COVER MOUNTED ON WALL.
8 PLYWOOD FROM 0'-4" TO 8'-4" ON ALL 4 WALLS.
9 SLEEVES THROUGH WALL. STACK AND ALIGN WITH CABLERUNWAY. PROVIDE VERTICAL RUNWAY FOR SUPPORT OFCABLES BETWEEN SLEEVES AND CABLE RUNWAY.
10 WALL FIELD LOCATION FOR INTERCOM TERMINATIONS.
11 SMOKE DETECTOR FOR CONTROL OF SMOKE CURTAIN,SMOKE CURTAIN TO DEPLOY UNDER LOCAL DETECTIONONLY. COORDINATE INSTALLATION WITH REVIEWEDSMOKE CURTAIN SHOP DRAWING.
12 TEST DEPLOY SWITCH FOR SMOKE CURTAIN, PROVIDESINGLE GANG BOX AT 42 INCHES. COORDINATEINSTALLATION WITH REVIEWED SMOKE CURTAIN SHOPDRAWING.
13 COORDINATE QUANTITY OF TAMPER AND FLOWSWITCHES FOR FIRE SPRINKLER SYSTEM. PROVIDEMONITOR MODULES AND CONNECT TO FIRE ALARMSYSTEM PER SECTION 283100.
14 (12) STRAND MM OM4 FIBER AND (1) 25 PAIR CAT 3 VOICEIN 3" EMT BETWEEN F113 AND F103. TERMINATE VOICEON EACH END IN NEW 66 BLOCK MOUNTED TO PLYWOOD.TERMINATE FIBER IN RACK MOUNTED HARDWARE PERSPECIFICATION.
15 PHONE LINES FOR LIFT, COORDINATE EXACT LOCATIONWITH LIFT MANUFACTURER.
16 WALL MOUNT DISTRIBUTED ANTENNA SYSTEM (DAS). SEESPECIFICATION FOR DETAILS. MOUNT SYSTEM IN NEMA 4ENCLOSURE CONNECTED TO LIFE SAFETY SYSTEMPOWER PER POWER PLANS.
SCALE: 1/4" = 1'-0"E3.1F
2 F113 - LARGE SCALE SPECIAL SYSTEMS PLAN
SCALE: 1/4" = 1'-0"E3.1F
3 F113 - LARGE SCALE CABLE RUNWAY PLAN
CC
-19/
13/1
7A
DD
EN
DU
M C
C-1
CC-1
CC-1
CC-1
CC-1
DN
UP
FS
S S
FS
S
SS
S
S
SS
SS
FS
FS
FS
FS
SS
FS
S
SS
S
S
S
S
S
SS
S
S
S
S H
S
S
TW
TW
TW
TW
TW
TW
TW
P
P
P
P
P
S
S
S
SAP
AP
AP
AP
AP
F
30
F
15
F
15
F
15F
15
F
15
F
15
F
75
F
75
F
75
F
30
F
30
F
75
F
15F
15
F
75
F
15
F
15
F
15
F
15
F
15
F
15
F
15
F
30
F
15
F
FF
15
F
F
F
F
30
F
75
P
F
15
S
S
S
S
S P
FF
F
F
75
F
75
F
15
F
30
F
30
FACP
FAA
S
S
S
S
S
S
S
S S
S
S
S
S
S
S S
SS
SS
S
S
S
S
S
S
S
S
S
S
S
S
S
S
HH
F
75
F
15
F
15
F
15
F
15
F
15
F
15
F
15
F
15
F
15
F
15
F
15
F
15
F
30
P
P
P
P
P
PP
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P P
M
T
S
F
F
M
TV
TV
TW
TW
AP
AP
AP
AP
AP
AP
AP
AP
S
S
V
V
V
S
P
P P P
S
S
L
K
K
MJ
P
J J J
JJ J
J
J
J
PIV
J
J
J
PD
PD
PD
D
D
D
F15
D
CR
J
D
D
L
L
L
P
P
F
15
F
15
J
P
GYMNASIUM
F244
KITCHEN
F239
STORAGE
F240
VEST
F247
OFFICE
F234STORAGE
F245CLASSROOM
F233
GIRLS
F243
BOYS
F242
ELECTRICAL
F238
COORIDOR
F241
VEST
F201
EARLYEDUCATION
F202
EARLYEDUCATION
F203
BOYS
F204
GIRLS
F205
BOYS
F213
GIRLS
F214
PRINCIPAL
F207
NURSE
F209WORK ROOM
F211
GUIDANCE
F208
CLASSROOM
F222
CLASSROOM
F221
SPECIAL ED
F230
JANITOR
F216
CLASSROOM
F228
TEACHERSLOUNGE
F220
WOMENS
F217
MENS
F218CLASSROOM
F229
SCIENCE
F223
CONFERENCEROOM
F225
RECEPTION
F206
CORRIDOR
F212
COORIDOR
F227
OFFICE
F231
LEARNINGCOMMONS
F232
OFFICE
F235
0, 1, 0
STORAGE
F226
CORRIDOR
F219
CORRIDOR
F215
TOILET
F210
JANITOR
F237
ALCOVE
F236
ELEC
F224
0, 1, 0
0, 1, 0
0, 1, 0
MECHANICAL
F246
0, 1, 0
1
0, 2, 0
0, 1, 0
0, 1, 0
0, 2, 0
0, 2, 0 2
0, 1, 0
0, 1, 0
0, 1, 0
0, 1, 0
0, 1, 0
0, 1, 0
0, 1, 0
0, 1, 0
0, 2, 0
0, 2, 0
0, 2, 0
0, 2, 0
0, 2, 0
0, 2, 0
RAMP/STAIR
F1S1
3
4
5
6 6 6
7
8
D
DS
0, 2, 0
0, 2, 0
0, 2, 0
AC
0, 2, 0
0, 2, 0
0, 2, 0
0, 2, 0
2, 0, 0
9
(2) 3" C.
(2) 2" C.
0, 2, 0
DOAS-F02SUPPLY
DO
AS
-F01
SU
PP
LY
RT
U-F
01S
UP
PLY
10
10
10
7
(2) 3" C.(2) 3" C.
(2) 3" C.
11
STORAGE
F248
Arc
hite
ctu
re E
ngin
eering
P
lan
nin
g In
teriors
©
,
DL
R G
rou
p inc., a
Ne
bra
ska
co
rpo
ratio
n, A
LL
RIG
HT
S R
ES
ER
VE
D
KEY PLAN
A
NO
RT
H
Rev
isio
ns
B
C
D
E
F
9/1
2/2
017 4
:26:3
7 P
M
C:\R
evit\1
0-1
3125-3
0_E
L_2016_C
entr
al_
mw
urs
t.rv
t
10-1
3125-3
0
8/2
9/2
017
PLA
TT
EV
IEW
JR
HIG
H &
HIG
H S
CH
OO
L R
EN
OV
AT
ION
S
SP
EC
IAL S
YS
TE
MS
PLA
N, M
AIN
LE
VE
L -
AR
EA
FE3.2F
20
17
SP
RIN
GF
IELD
PLA
TT
EV
IEW
CO
MM
UN
ITY
SC
HO
OLS
NORTHSCALE: 1/8" = 1'-0"
SPECIAL SYSTEMS PLAN, MAIN LEVEL - AREA F
KEYED NOTES
KEY VALUE KEY TEXT
1 FIRE ALARM RELAY FOR MONITORING EMERGENCY GASSHUT-OFF CONTROLLER FURNISHED BY DIVISION 23.
2 MOUNT TW DEVICES AT 42" ADJACENT TO ABOVECOUNTER RECEPTACLE THIS ROOM.
3 FIRE ALARM BEAM DETECTOR TRANSMITTER. MOUNTWITHIN 3 FEET OF THE EXPOSED ROOF STRUCTURE.COORDINATE LOCATION FOR CLEAR PATH TO MIRRORWITH ALL CEILING DEVICES.
4 FIRE ALARM BEAM DETECTOR MIRROR. COORDINATELOCATION WITH BEAM DETECTOR TRANSMITTER. MOUNTWITHIN 3 FEET OF THE EXPOSED ROOF STRUCTURE.
5 PROVIDE (2) REMOTE TEST SWITCHES MOUNTED INCEILING FOR SMOKE DETECTION OVER STAIR F1S1 ANDLABEL.
6 MOUNT SMOKE DETECTOR AS HIGH IN SKYLIGHT ASPOSSIBLE. COORDINATE LOCATION WITH AHJ AND SKYLIGHT CONSTRUCTION.
7 SMOKE DETECTOR FOR CONTROL OF SMOKE CURTAIN,SMOKE CURTAIN TO DEPLOY UNDER LOCAL DETECTIONONLY. COORDINATE INSTALLATION WITH REVIEWEDSMOKE CURTAIN SHOP DRAWING.
8 TEST DEPLOY SWITCH FOR SMOKE CURTAIN, PROVIDESINGLE GANG BOX AT 42 INCHES. COORDINATEINSTALLATION WITH REVIEWED SMOKE CURTAIN SHOPDRAWING.
9 SEE SITE UTILITIES PLAN FOR LOCATION OF PIV. PROVIDESPD AT ENTRANCE AND CONNECT TO FIRE ALARMSYSTEM.
10 REMOTE INDICATOR/TEST SWITCH FOR ROOF TOP UNITDUCT DETECTOR. MOUNT RECESSED IN WALL 6'-0" AFFAND LABEL.
11 CONDUIT PATHWAY TO DATA ROOM BELOW, STUB UPABOVE FLOOR 8", PROVIDE VERTICAL CABLE RUNWAY ONWALL UP TO 10 FOOT TO SUPPORT CABLES FROM BELOW.SEE LOWER LEVEL FLOOR PLAN FOR PATHWAY DETAILS.
CC
-19/
13/1
7A
DD
EN
DU
M C
C-1
CC-1