active rectifier in microgrid - ntnu · active rectifier in microgrid mini-project 15a 1 table ......

23
03.09.2012 Active Rectifier in Microgrid - Developing a simulation model in SimPower - Dimensioning the filter - Current controller comparison - Calculating average losses in the diodes and transistors Kristiansen Baricuatro Sergey Klyapovskiy Umair Ashraf Emmanuel Omede MSc in Electric Power Engineering TET4190 Power Electronics for Renewable Energy Supervisors: Tore Undeland (NTNU) Roy Nilsen (Wärtsilä) Mini-project 15a Project Group N Faculty of IME

Upload: others

Post on 12-May-2020

4 views

Category:

Documents


0 download

TRANSCRIPT

03.09.2012

Active Rectifier in Microgrid

- Developing a simulation model in SimPower

- Dimensioning the filter

- Current controller comparison

- Calculating average losses in the diodes and transistors

Kristiansen Baricuatro

Sergey Klyapovskiy

Umair Ashraf

Emmanuel Omede

MSc in Electric Power Engineering

TET4190 Power Electronics for Renewable Energy

Supervisors: Tore Undeland (NTNU)

Roy Nilsen (Wärtsilä)

Mini-project 15a

Project Group N

Faculty of IME

PREFACE

This report was written by four students from NTNU, for the mini-project for the course TET4190 Power Electronics for Renewable Energy. The report describes the project’s background, its objectives, the methods used to achieve these objectives and the results of these efforts. We chose this project because it tackles many interesting parts within the power electronic field. In addition to learning more about converters and control methods, the task gave us an opportunity to learn how to use a Simulink toolbox, SimPower. The project is carried out in the period September to October 2012. We wish to thank Wärtsilä and Roy Nilsen for giving us the opportunity to work with them, and be granted the guidance that we needed. At NTNU, we want to thank our supervisor, Professor Tore Undeland for his supervision and guidance during the project.

Trondheim, 03.09.2012

Active Rectifier in Microgrid

Mini-project 15a 1

Table of Contents

1 ABSTRACT ...................................................................................................................... 2

2 INTRODUCTION ............................................................................................................. 3

2.1 Structure and content of the report .................................................................................................................... 3 2.2 Problem formulation ................................................................................................................................................ 3 2.3 Why wartsila wants to work with the problem .............................................................................................. 3 2.4 Objectives of the project .......................................................................................................................................... 3

3 THEORY ......................................................................................................................... 4

3.1 Microgrid ....................................................................................................................................................................... 4 3.2 Inverter .......................................................................................................................................................................... 4 3.3 Current controller analysis .................................................................................................................................... 5

3.3.1 PI PWM Current Controller. ............................................................................................................................................... 5 3.3.2 Hysteresis Current Controller ........................................................................................................................................... 6

3.4 LCL Filter ....................................................................................................................................................................... 6

4 CALCULATIONS .............................................................................................................. 7

4.1 Dimensioning the filter ...................................................................................................................................... 7 4.2 Calculating average power loss in the diodes and the transistors .......................................................... 8

4.2.1 Switching losses ....................................................................................................................................................................... 8 4.2.2 Conduction losses ................................................................................................................................................................... 8

5 SIMULATION ................................................................................................................ 10

5.1 The model ................................................................................................................................................................... 10 5.2 Results .......................................................................................................................................................................... 13

5.2.1 PI PWM Current Controller with fs = 20 kHz ........................................................................................................... 13 5.2.2 Hysteresis Current Controller with fs = 20 kHz ...................................................................................................... 15 5.2.3 Comparisons ........................................................................................................................................................................... 17

6 CONCLUSION ............................................................................................................... 19

7 REFERENCES ................................................................................................................ 20

8 LISTS OF FIGURES, TABLES AND ABBREVIATIONS .......................................................... 20

9 APPENDIX .................................................................................................................... 21

Active Rectifier in Microgrid

Mini-project 15a 2

1 ABSTRACT

Renewable Energy sources are usually to be looked upon as Distributed Energy Resources (DER). They

have to be integrated into a local energy network; the Microgrid. An inverter (DC/AC-converter) is used

to connect this system to the utility grid.

Two simulation models of such an inverter have been made: One with a PI-current controller and the

other with a hysteresis current controller. Both current control techniques had been studied and analyzed

through theory and simulation.

Calculations had been made to dimension a LCL filter for the system and to find the average losses in the

diode and transistors.

Active Rectifier in Microgrid

Mini-project 15a 3

2 INTRODUCTION This chapter will present the objectives and requirements of the project.

2.1 STRUCTURE AND CONTENT OF THE REPORT

The report is based on theoretical presentations and simulations on two different kinds of current controllers. Introductory chapters present the task. Chapter 3 gives a theoretical presentation of inverters and current controllers. Chapter 4 deals with calculations. Chapter 5 deals with the main part of the project which is the simulations. The final chapter is devoted to conclusion. Attached zip-file or CD contains data sheet, simulation results, SimPower models and matlab files.

2.2 PROBLEM FORMULATION The desire for increasing their efficiency and reducing the harmful emissions lead to the widely spreading and applying of small-scale generators, which are commonly called distributed generation (DG) units. The attempt to realize the DG potential has led to the appearance of “Microgrid” concept. The main characteristics of Microgrid concept are: It is a local scale power system with DG units, which produces electrical or thermal energy to the local system demand. It can provide power supplies to the customers with multiple load locations. It creates the possibility of seamless crossing between grid-connected mode and autonomous operation (island mode). It increases the power quality and system reliability. In addition, it provides significant control capabilities over the network operation. Different types of DG units could have different output nature, than the network which they are supposed to work with. Since the existing Microgrids are operating as AC systems, we need to use power electronic interfaces in order to connect DG units.

2.3 WHY WARTSILA WANTS TO WORK WITH THE PROBLEM Wärtsilä is a global leader in complete lifecycle power solutions for the marine and energy

markets. Since Wärtsilä is integrating DG units on ships and their power plants are based on

renewable energy, they need to use power electronics to connect and control DG units.

2.4 OBJECTIVES OF THE PROJECT

During the Miniproject, a simulation model of Inverter for 230 Vac and 20 kW should be created

using SimPower. To keep voltage ripples on acceptable level, the parameters of LCL-filter should

be chosen. The project group will also compare the behavior of a PWM-modulator with a PI-

current controller with the behavior of a hysteresis current-controller and calculate the average

losses in the diode and transistors.

Active Rectifier in Microgrid

Mini-project 15a 4

3 THEORY

3.1 MICROGRID

A microgrid is power supply network which is designed to provide power to a certain area. It also can

provide the power to centralized grid. Generators and loads are connected at low voltage in micro grid.

Sources of power generation related to microgrid are usually renewable energy. The power we get from

the renewable energy sources is mostly DC power, so to operate our load which is AC driven we need

inverters. Inverters are thus essential part to get energy from renewable energy sources.

3.2 INVERTER

Figure 1: Three-phase inverter

Inverters convert DC power into AC power. Conversion of this energy is done with a three-phase full

bridge inverter and for every single switch we need anti parallel diode. The main idea behind an inverter

is to get a pure sinusoidal voltage and current for our AC driven load.

To obtain this pure sine wave, we use different components and control methods in the inverter. The

component characteristics determine the conduction losses, maximum switching frequency, power

handling capability and temperature dependent variables. The control methods will determine the

switching frequency.

Active Rectifier in Microgrid

Mini-project 15a 5

3.3 CURRENT CONTROLLER ANALYSIS

For high performing three phase AC drives, the current controlling technique is of great importance as the characteristics of the inverter such as the switching frequency, level of harmonic distortion and the measure of dynamics in the output response. Two techniques are discussed, PI PWM current controller (linear) and the Hysteresis PWM current controller (non-linear).

Figure 2: PWM Current Controller

3.3.1 PI PWM CURRENT CONTROLLER. This is a linear current controller known as the proportional-integral regulator. In this technique, the phase current is compared to a reference current value and output error compensated through the PI error compensator whose output is further used to modulate the IGBT (inverter switch) or the PWM. The integral part of the PI compensator minimizes errors at low frequency, while proportional gain and zero placement are related to the amount of ripple [1]. The ripple in the output current is amplified by the gain of the compensator, thus influencing the switching frequency of the switches. This technique requires minimal harmonic frequency below the carrier frequency. The disadvantage is in the tracking error of the output current amplitude and phase [1].

Figure 3: PI PWM current controllers

Active Rectifier in Microgrid

Mini-project 15a 6

3.3.2 HYSTERESIS CURRENT CONTROLLER This is one of the mostly used current controller technique because it is very easy to implement as compared to other types. Knowledge of load parameters is not required and its current loop response is faster than others [2]. In the hysteresis technique, actual phase current in a three phase systems is compared with a reference current for the same phase and the error passed through a hysteresis band to generated input pulses to regulate the IGBT for minimal current errors. This is done for three phase currents of the system but with one disadvantage of phase quantity interaction in a three phase system. Each three phase output currents to the load are compared with the respective reference phase currents by three hysteresis comparators for each phase and the output used to activate the inverter switches. But additional circuitry is required since the switching frequency/the ripple current varies at every point of the fundamental frequency.

Figure 4: Hysteresis current controllers

3.4 LCL FILTER

Figure 5: Three-phase inverter with LCL filter

The DC/AC inverter discussed in chapter 3.1 consists of the DC link, three-phase inverter and the filter. To

minimize the current harmonics, we need a bulky inductance in the filter to achieve good performance.

The LCL filter, consisting of two inductors and one capacitor, is a popular choice because of its better

attenuation for switching frequency harmonics and its low cost. However, an LCL filter has its own

drawback. Because of the peak at the resonance frequency, the filter will increase instability of the

system. To counteract this, we use a damping resistor in series with the capacitors.

Active Rectifier in Microgrid

Mini-project 15a 7

4 CALCULATIONS

4.1 DIMENSIONING THE FILTER

When dimensioning the LCL filter, the following should be kept in mind. The total inductance should be

large to have lower harmonic distortion, but it will also slow down the system response. It is also

important to keep in mind that inductance size is proportional to the cost. To have a high power factor,

the capacitor should not be too large since it absorbs reactive power. The damping resistor should not be

too large since it would produce huge power loss.

First a suitable overall inductance value Ls is chosen: [3]

Where Em is the peak voltage of the grid, Im is the peak current of the grid, fsw is the switching frequency,

and iripple is the current ripple. Since we want a low value of Ls for cost reasons, we will use the minimum

boundary.

The capacitance Cf is then chosen: [3]

Where q is the percent reactive power we want absorbed, fn is the grid frequency, En is the rms value of

the phase voltage, and Pn is the rated power produced by the inverter.

The value of the two inductances L1 and L2 is dictated by a ratio r:

The resonance frequency fres should be check if it is suitable:

√( )

Lastly, the damping resistor is calculated: [3]

Active Rectifier in Microgrid

Mini-project 15a 8

4.2 CALCULATING AVERAGE POWER LOSS IN THE DIODES AND THE TRANSISTORS

The IGBT and Diode power losses (Pi), can be divided into two groups: the conduction losses (Pcond) and the switching losses (Psw).

4.2.1 SWITCHING LOSSES The switching losses in the diode and the IGBT are the product of switching energies and the switching frequency: [4]

( )

( )

The turn-on energy losses in the IGBT (EonT) can be calculated as the sum of the switch-on energy without taking the reverse recovery process into account (EonTi) and the switch-on energy caused the reverse-recovery of the free-wheeling (EonTrr). The turn-on energy in the diode consists mostly of the reverse-recovery energy (EonDrr). [4]

∫ ( ) ( )

∫ ( ) ( )

where UDrr is the voltage across the diode during reverse recovery and Qrr is the diode recovery charge. The turn-off energy losses in the IGBT can be calculated in the similar manner. The switch-off losses in the diode are normally neglected. [4]

∫ ( ) ( )

To simplify calculations, typical switching energies given on the data-sheet of the supplier are used.

4.2.2 CONDUCTION LOSSES The instantaneous value of the IGBT and the diode conduction losses are given: [4]

( ) ( ) ( ) ( ) ( )

( ) ( ) ( ) ( ) ( )

The average conduction losses across the switching period (Tsw=1/fsw) are:

( )

∫ ( )

∫ ( ) ( )

( )

∫ ( )

∫ ( ) ( )

The dynamic resistance values for IGBT and diode (rc and rd) can be read from the data-sheet diagram of

the supplier (as shown at the figure below). Since both values are dependent on the junction temperature,

we took into account the worst case scenario which is at Tj =150 C.

Active Rectifier in Microgrid

Mini-project 15a 9

Figure 6: Calculating dynamic resistance values

Active Rectifier in Microgrid

Mini-project 15a 10

5 SIMULATION

5.1 THE MODEL

A simulation model of the specified system was created using SimPower.

Figure 7: Simulation model

It consists of a three phase full bridge inverter for a 230 Vac and 20 kW load. The inverter has a constant

DC voltage source of 680V. An Infineon IGBT with anti-parallel diode IKW40T120 was used. Lastly, a LCL-

filter is connected on the AC side of the inverter to minimize ripples. As

Figure 8: Current Controllers

Two different controllers are used, a hysteresis current-controller and a PWM-modulator with a PI-

current controller.

Active Rectifier in Microgrid

Mini-project 15a 11

Figure 9: Switching frequency checker

To determine the average switching frequency of an inverter with a hysteresis current controller, a

subsystem was created to measure the switching frequency. This is done by counting the number of rises

on a gate signal which basically tells us the number of switches made, and holding the count once the

clock reaches the fundamental period. Dividing the number of switches by the fundamental period then

gives us the switching frequency.

Figure 10: Power loss calculations

A subsystem dedicated for power loss calculations was also created, using the equations discussed at chapter 4.2.

Active Rectifier in Microgrid

Mini-project 15a 12

Figure 11: Conduction loss calculations

Figure 12: Switching loss calculations

The LCL filter values are calculated automatically using the equations discussed at chapter 4.1 through a matlab script each start of a new simulation to accommodate changes in input data.

Active Rectifier in Microgrid

Mini-project 15a 13

5.2 RESULTS

5.2.1 PI PWM CURRENT CONTROLLER WITH FS = 20 KHZ Using 20 kHz switching frequency, and assuming 20% current ripple gave us the following values for the LCL filter:

L1 14,58 mH Cf 22,17 mF L2 10,2 mH

Table 1: LCL Filter for fs = 20 kHz Starting with the PI PWM Current Controller, the scope readings below show us how the PWM controller works. When the PI output which is our control voltage is more than the triangular wave voltage, the upper thyristor TA+ is conducting. When the control voltage is less than the triangular wave voltage, the lower thyristor TA- is conducting.

Figure 13: PI Controller outputs

Active Rectifier in Microgrid

Mini-project 15a 14

The scope readings below shows the effects of the LCL filter.

Figure 14: PI controller ripple and load measurements

This gives us a THD of 8,98 %.

Figure 15: PI Controller THD

This setup gives us average IGBT losses of 1506 W and average diode losses of 73 W, giving a total loss of 1579 W.

Active Rectifier in Microgrid

Mini-project 15a 15

5.2.2 HYSTERESIS CURRENT CONTROLLER WITH FS = 20 KHZ Using the hysteresis current controller and the same LCL filter values, gave us an average switching frequency of 21 kHz. The scope readings below show us how the hysteresis current controller works. If the actual current tries to go beyond the upper tolerance band, TA- is turned on to reduce the current. The opposite switching occurs if the actual current tries to go below the lower tolerance band.

Figure 16: Hysteresis Controller outputs

The scope readings below shows the effects of the LCL filter.

Figure 17: Hysteresis controller ripple and load measurements

Active Rectifier in Microgrid

Mini-project 15a 16

This gives us an acceptable THD of 3 %.

Figure 18: Hysteresis Controller THD

This setup gives us average IGBT losses of 1691 W and average diode losses of 76 W, giving a total loss of 1767 W.

Active Rectifier in Microgrid

Mini-project 15a 17

5.2.3 COMPARISONS The figure below shows the effects of the switching frequency to the filter inductance. It shows that as we

increase the switching frequency, the value that we need for the filter inductance decreases. It is also

important to notice that the hysteresis current controller gives out higher average switching frequency

than the PWM PI current controller at similar filter inductance values.

Figure 19: Filter inductance vs switching frequency

The figure below shows the effects of the switching frequency to the total loss (in the diode and the

transistors).

Figure 20: Switching frequency vs total losses

0

5000

10000

15000

20000

25000

25 28 33 40 50

Swit

chin

g fr

eq

ue

ncy

[H

z]

Filter Inductance Ls [mH]

PWM PI CC

Hysteresis CC

0

200

400

600

800

1000

1200

1400

1600

1800

2000

Tota

l Lo

sse

s (I

GB

T an

d D

iod

e)

[W]

Switching Frequency [Hz]

PWM PI CC

Hysteresis CC

Active Rectifier in Microgrid

Mini-project 15a 18

The figure below shows us the effects of variations in the hysteresis band in a hysteresis current

controller. This shows us that the THD in a hysteresis current controller is mainly dependent on the

hysteresis band. If the hysteresis band increases, THD also increases, but the switching frequency

decreases, which gives less switching losses.

Figure 21: Hysteresis band variation effects

0,00

0,50

1,00

1,50

2,00

2,50

3,00

3,50

4,00

4,50

9,90 14,84 19,80 24,75 29,70

Hysteresis Band [A]

fs [10^4 Hz]

Power loss [kW]

THD [%]

Active Rectifier in Microgrid

Mini-project 15a 19

6 CONCLUSION Current control techniques can be divided into two groups: linear (PI Controller) and non-linear

controllers (Hysteresis CC). The basic principles of these techniques have been described in the report.

Both have its advantages and limitations.

The advantage of the PI controller is that it gives out constant switching frequency, which provides a

stable operation of the inverter. The main disadvantage of this technique is an inherent tracking

(amplitude and phase) error.

The advantage of the hysteresis band controller lies in its simplicity and its providing of excellent

dynamic performance. On the other hand, the disadvantage is that the switching frequency varies,

providing irregular operation of the inverter. As a result the switching losses are increased.

In addition to studying the two current control techniques, the project group also studied how to

dimension a LCL filter and how to calculate power losses in the IGBT and the diode.

Active Rectifier in Microgrid

Mini-project 15a 20

7 REFERENCES

[1] Current Control Techniques for Three-Phase Voltage-Source PWM Converters: A Survey; Kazmierkowski and Malesani

[2] Performance Analysis of Differrent Current Control Techniques for VSI connected to R-L Load;

Ch.Nagarjuna Reddy, B.Vasanth Reddy, B.Chitti Babu

[3] “A method of tracking the peak power points for a variable speed wind energy conversion system,”; Datta and Ranganathan

[4] Power Electronics; Mohan, Undeland and Robbins

8 LISTS OF FIGURES, TABLES AND ABBREVIATIONS

LIST OF FIGURES AND TABLES:

Figure 1 Three-phase inverter p. 4 Figure 2 PWM Current Controller p. 5 Figure 3 PI PWM current controller p. 5 Figure 4 Hysteresis current controller p. 6 Figure 5 Three-phase inverter with LCL filter p. 6 Figure 6 Calculating dynamic resistance values p. 9 Figure 7 Simulation model p. 10 Figure 8 Current controllers p. 10 Figure 9 Switching frequency checker p. 11 Figure 10 Power loss calculations p. 11 Figure 11 Conduction loss calculations p. 12 Figure 12 Switching loss calculations p. 12 Figure 13 PI Controller outputs p. 13 Figure 14 PI controller ripple and load measurements p. 14 Figure 15 PI Controller THD p. 14 Figure 16 Hysteresis Controller outputs p. 15 Figure 17 Hysteresis controller ripple and load measurements p. 15 Figure 18 Hysteresis controller THD p. 16 Figure 19 Filter inductance vs switching frequency p. 17 Figure 20 Switching frequency vs total losses p. 17 Figure 21 Hysteresis band variation effects s. 3 Table 1 LCL Filter for fs = 20 kHz p. 13

LIST OF ABBREVIATIONS

THD: Total Harmonic Distortion IGBT: Insulated Gate Bipolar Transistor fs: switching frequency CC: Current Controller DG: Distributed Generation PWM: Pulse Width Modulation

Active Rectifier in Microgrid

Mini-project 15a 21

9 APPENDIX A: IGBT with anti parallel diode datasheet - Infineon IKW40T120

B: PI CC model (Simulink file)

C: PI CC data inputs for model (Matlab file)

D: Hysteresis CC model (Simulink file)

E: Hysteresis CC data inputs for model (Matlab file)