active chilled beamsdadanco.eu/images/downloads/acb_35_technical_data... · 2019. 12. 3. · the...

12
Technical Data Technical Data Technical Data Technical Data — Concealed Ceiling Concealed Ceiling Concealed Ceiling Concealed Ceiling—Mounted Model Mounted Model Mounted Model Mounted Model With Vertical Coil and Integral Drain Pan With Vertical Coil and Integral Drain Pan With Vertical Coil and Integral Drain Pan With Vertical Coil and Integral Drain Pan Active Chilled Beams ACB35 Concealed Ceiling-Mounted With Vertical Coil and Integral Drain Pan (Vertical down discharge)

Upload: others

Post on 28-Feb-2021

3 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Active Chilled Beamsdadanco.eu/images/downloads/ACB_35_Technical_Data... · 2019. 12. 3. · The general design intent of an Active Chilled Beam system is for the central system to

Technical Data Technical Data Technical Data Technical Data ———— Concealed CeilingConcealed CeilingConcealed CeilingConcealed Ceiling————Mounted Model Mounted Model Mounted Model Mounted Model With Vertical Coil and Integral Drain PanWith Vertical Coil and Integral Drain PanWith Vertical Coil and Integral Drain PanWith Vertical Coil and Integral Drain Pan

Acti

ve C

hil

led

Beam

s

ACB35 Concealed Ceiling-Mounted With Vertical Coil and Integral Drain Pan

(Vertical down discharge)

Page 2: Active Chilled Beamsdadanco.eu/images/downloads/ACB_35_Technical_Data... · 2019. 12. 3. · The general design intent of an Active Chilled Beam system is for the central system to

2

APPLICATION CONSIDERATIONSAPPLICATION CONSIDERATIONSAPPLICATION CONSIDERATIONSAPPLICATION CONSIDERATIONS The general design intent of an Active Chilled Beam system is for the central system to circulate only the amount of primary air needed for ventilation and latent load purposes, with the Active Chilled Beams providing the additional sensible cooling (and heating) and air movement required through the induced room air and secondary water coil. Active Chilled Beam systems transfer a large portion of the cooling (and heating loads) from the less efficient air distribution system (fans and ductwork) to the more efficient water distribution system (pumps and pipes). The net result of this shift in loads is lower energy consumption and operating costs.

Primary Air SystemPrimary Air SystemPrimary Air SystemPrimary Air System There are a number of important issues affected by the primary airflow rates, pressure and temperature chosen in the primary air system design as follows:

• Ventilation Air Requirements

• Primary Air Latent Cooling Capacities

• Risk of Over-cooling/Reheating

• Building Pressurization Control Choosing the primary air flow rates and temperature requires considerable thought and judgment. Decreasing the primary air temperatures offers the opportunity to decrease fan energy consumption (within the limits of the ventilation air requirement) and increasing latent cooling capacities, while potentially increasing the risks of over-cooling/reheating. Other design concerns with the primary air system design include:

• Air Handler/Ductwork Zoning and Resetting of Primary Air Temperatures

• Air Distribution Considerations

• Noise Level Requirements

• Heating

Secondary Water SystemSecondary Water SystemSecondary Water SystemSecondary Water System The chilled water temperature entering the Active Chilled Beam secondary water coils must be at or above the room design dew point temperature to avoid formation of condensate on the coil. Using the room design temperature of 24 ºC db/ 17ºC wb (50% relative humidity), the room air dew point temperature is 12.8 ºC. In this case the minimum entering chilled water temperature to the Active Chilled Beams should be 12.8 ºC or higher (typically around 14-16 ºC is used in Practice). Choosing the secondary chilled water temperature is another area requiring considerable thought and judgment. A higher chilled water temperature will add to the margin of safety relative to condensation concerns and increase the hours when a water-side economizer can be used to serve the active chilled beams, but could have the effect of increasing the fan and pump energy requirements and unit costs.

HeatingHeatingHeatingHeating The suitability of the use of overhead heating from the ceiling in any system (Active Chilled Beam, VAV, etc) is dependent on the extent of heat losses along the perimeter. In general overhead heating is acceptable if the heat losses are less than 384 W/linear meter along the perimeter. The air distribution discharge arrangements employed vary based on the extent of heat losses along the perimeter.

Page 3: Active Chilled Beamsdadanco.eu/images/downloads/ACB_35_Technical_Data... · 2019. 12. 3. · The general design intent of an Active Chilled Beam system is for the central system to

3

UNIT SELECTIONUNIT SELECTIONUNIT SELECTIONUNIT SELECTION There are two methods for selecting DADANCO Active Chilled Beams – a manual method using the enclosed tables and an optimized design method using the DADANCO Specifier™ computerized product selection program. The following will demonstrate the manual selection method using the data from the Quick Selection Capacity and Sound Level tables. For optimized unit selections using the DADANCO Specifier™ computerized product selection program or for special selection assistance, contact Dadanco LLC via phone (413) 564—5657, fax (413) 568—5384 or e-mail at [email protected].

MANUAL SELECTION METHODMANUAL SELECTION METHODMANUAL SELECTION METHODMANUAL SELECTION METHOD

The unit performance data in the Quick Selection Capacity tables in this publication is given for the ACB35 (vertical down discharge) concealed ceiling-mounted model in both 2-pipe and 4-pipe coil configurations. The capacity ratings are based on a “typical” nozzle selections. With the optimized design method using the DADANCO Specifier™ computerized selection program, both the size/number of nozzles will vary and will be optimized to provide the exact performance required.

Ventilation AirVentilation AirVentilation AirVentilation Air To begin your unit selections determine the minimum ventilation air required for each zone (using as a minimum that prescribed by ASHRAE 62). This would be the minimum amount of primary air that could delivered to the Active Chilled Beams in each zone.

Latent Cooling Latent Cooling Latent Cooling Latent Cooling Prior to selecting the Active Chilled Beams the primary air quantity and temperature must be determined to provide for adequate ventilation air, as well as for the latent cooling capacity required. It is very important that both of these requirements are determined and satisfied by the primary air in every zone before selecting the Active Chilled Beams. Using the ventilation air quantity as the primary air quantity, determine the latent cooling being provided by the primary air based on the airflow, room design and primary air temperatures chosen. Compare the latent cooling capacity being provided by the primary air to the latent load in each zone. Often times the primary air quantity and temperature will be driven by the latent cooling loads and more (or preferably colder/drier) primary air will be required than that needed solely for ventilation air purposes to satisfy the zone latent loads. Remember that the latent loads in an Active Chilled Beam system must be fully satisfied by the primary air as insufficient latent cooling capacities can lead to condensation issues.

Active Chilled Beam Unit TypeActive Chilled Beam Unit TypeActive Chilled Beam Unit TypeActive Chilled Beam Unit Type The type of unit (s) to be selected must be chosen. This publication includes data for the concealed ceiling-mounted models.

Quick Selection Cooling and HeatingQuick Selection Cooling and HeatingQuick Selection Cooling and HeatingQuick Selection Cooling and Heating Capacity TablesCapacity TablesCapacity TablesCapacity Tables The performance data in the Quick Selection Capacity tables are based on assumed operating conditions of:

• 125 Pa inlet static pressure

• 24 °C db/17 °C wb room design temperature (50% relative humidity, 0.00925 kg Water/kg Dry Air humidity ratio)

• 12.0 °C db/11.3 °C wb primary air temperature (90% relative humidity, 0.00800 kg Water/kg Dry Air humidity ratio)

• 14.0 °C entering chilled water temperature for cooling

• 50.0 °C entering hot water temperature for heating

• 0.10 L/s water flow rate

• Sea level elevation

The correction factor tables can be used to adjust the cooling and heating capacities shown in the Quick Selection Capacity tables for operating conditions that differ from the above assumptions.

Conceleld Ceiling Conceleld Ceiling Conceleld Ceiling Conceleld Ceiling ----Mounted ModelsMounted ModelsMounted ModelsMounted Models

ModelModelModelModel Air DischargeAir DischargeAir DischargeAir Discharge Coil ConfigurationCoil ConfigurationCoil ConfigurationCoil Configuration

ACB35ACB35ACB35ACB35 Vertical DownVertical DownVertical DownVertical Down 2222----PipePipePipePipe

ACB35ACB35ACB35ACB35 Vertical DownVertical DownVertical DownVertical Down 4444----PipePipePipePipe

Page 4: Active Chilled Beamsdadanco.eu/images/downloads/ACB_35_Technical_Data... · 2019. 12. 3. · The general design intent of an Active Chilled Beam system is for the central system to

4

Sensible CoolingSensible CoolingSensible CoolingSensible Cooling The Quick Selection Cooling Capacity tables show the sensible and latent cooling capacity being provided by the primary air, the sensible cooling capacity being provided by the secondary water coil and the total unit sensible cooling capacity.

Example Assume we want to select an ACB35 2-pipe unit and that the total sensible cooling capacity required was 1,350 W with a minimum primary airflow of 28 L/s. Using the correct Quick Selection Cooling Capacity table on page 7, a total sensible cooling capacity of 1,369 W (412 W from the primary air and 957 W from the secondary water coil) could be provided by a 1500 mm unit using 28 L/s of primary air. Remember this amount of primary air must be sufficient to provide the necessary ventilation air and latent cooling capacities required. The performance data in the Quick Selection Cooling Capacity tables is based on TRA — TPA of 12 °C (24 ºC — 12 ºC). Use the correction factor for primary air temperature less room design temperature differences other than the 12 °C ∆T temperature difference used in the Quick Selection Cooling

Capacity tables.

Example Using the above base unit selection, the sensible cooling being provided by the primary air is 412 W. If the primary air temperature was 11 °C (rather than the 12 º C assumed in the tables), the actual temperature difference is 13 °C (rather than the 12 °C used in the tables). The corrected sensible cooling capacity of the primary air at the 13 °C ∆T is 445 W ( 412 W x 1.08). The performance data in the Quick Selection Cooling Capacity tables is based on a TRA — TCHW of 10 °C ∆T (24 ºC — 14 ºC). Use the correction factor for room design temperature less chilled water temperatures other than the 10 °C ∆T temperature difference used in the Quick Selection Cooling Capacity

tables.

Example Using the above base unit selection, the sensible cooling capacity being provided by the secondary water coil is 957 W. If the chilled water temperature was 15 °C (rather than the 14 ºC assumed in the tables), the actual temperature difference is 9 °C (rather than the 10 °C used in the tables). The corrected sensible cooling capacity of the secondary water coil at the 9°C ∆T is 861 W (957 W x 0.90). Remember that the chilled water temperature must be above the room dew point temperature to avoid condensation issues.

Throw and Sound LevelsThrow and Sound LevelsThrow and Sound LevelsThrow and Sound Levels Consult the Throw and Sound Level tables to ensure proper air distribution and noise levels within each zone. Use conventional air distribution application guidelines when considering placement of the Active Chilled Beams. Throw performance will be determined depending on the supply air outlet diffuser chosen for use with the ACB35.

Primary Air Temperature Correction Factor Primary Air Temperature Correction Factor Primary Air Temperature Correction Factor Primary Air Temperature Correction Factor ———— CoolingCoolingCoolingCooling

Primary AirPrimary AirPrimary AirPrimary Air ∆ ∆ ∆ ∆ TemperatureTemperatureTemperatureTemperature Correction FactorCorrection FactorCorrection FactorCorrection Factor

TemperatureTemperatureTemperatureTemperature Room Air Room Air Room Air Room Air ———— Primary AirPrimary AirPrimary AirPrimary Air Applied to Primary AirApplied to Primary AirApplied to Primary AirApplied to Primary Air

TTTTPAPAPAPA TTTTRA RA RA RA ———— TTTTPAPAPAPA Sensible Cooling CapacitySensible Cooling CapacitySensible Cooling CapacitySensible Cooling Capacity

(º C)(º C)(º C)(º C) (º C)(º C)(º C)(º C) KKKKPAPAPAPA

10101010 14141414 1.171.171.171.17

11111111 13131313 1.081.081.081.08

12121212 12121212 1.001.001.001.00

13131313 11111111 0.920.920.920.92

14141414 10101010 0.830.830.830.83

15151515 9999 0.750.750.750.75

16161616 8888 0.670.670.670.67

17171717 7777 0.580.580.580.58

18181818 6666 0.500.500.500.50

19191919 5555 0.420.420.420.42

Water Temperature Correction Factor Water Temperature Correction Factor Water Temperature Correction Factor Water Temperature Correction Factor ———— CoolingCoolingCoolingCooling

Chilled WaterChilled WaterChilled WaterChilled Water ∆ ∆ ∆ ∆ TemperatureTemperatureTemperatureTemperature Correction FactorCorrection FactorCorrection FactorCorrection Factor

TemperatureTemperatureTemperatureTemperature Room Air Room Air Room Air Room Air ———— Chilled WaterChilled WaterChilled WaterChilled Water Applied to Secondary CoilApplied to Secondary CoilApplied to Secondary CoilApplied to Secondary Coil

TTTTCHWCHWCHWCHW TTTTRA RA RA RA ———— TTTTCHWCHWCHWCHW Sensible Cooling CapacitySensible Cooling CapacitySensible Cooling CapacitySensible Cooling Capacity

(º C)(º C)(º C)(º C) (º C)(º C)(º C)(º C) KKKKCHWCHWCHWCHW

13.513.513.513.5 10.510.510.510.5 1.051.051.051.05

14141414 10101010 1.001.001.001.00

14.514.514.514.5 9.59.59.59.5 0.950.950.950.95

15151515 9999 0.900.900.900.90

15.515.515.515.5 8.58.58.58.5 0.850.850.850.85

Page 5: Active Chilled Beamsdadanco.eu/images/downloads/ACB_35_Technical_Data... · 2019. 12. 3. · The general design intent of an Active Chilled Beam system is for the central system to

5

HeatingHeatingHeatingHeating The Quick Selection Heating Capacity tables show the sensible heating being provided by the primary air, the sensible heating being provided by the secondary water coil and the total unit sensible heating capacity. Remember that if the primary in the heating mode is being delivered at a temperature below the room design temperature, the heating required to bring the primary air up to the room design temperature must be added to the heating load that must be satisfied by the Active Chilled Beam’s secondary water coil.

Example Using the same base unit selection and the correct Quick Selection Capacity table on page 8, the unit would provide a total sensible heating capacity of 2,242 W (-343 W from the primary air and 2,571 W from the secondary water coil) using 28 L/s of primary air (based on the operating condition assumptions used in the Quick Selection Heating Capacity tables). The performance data in the Quick Selection Heating Capacity tables are based on a room design temperature less primary air temperature of 10°C ∆T temperature difference (22 ºC — 12 ºC). For primary air temperatures other than the 12 ºC adjust the amount of heating being provided by the primary air using the formula of:

QPA = 1.226 x PA x (TPA – TRA)

Example Using the above base unit selection, the sensible heating being provided by the primary air is –343 W. If the primary air temperature was 18 °C (rather than the 12 º C assumed in the tables), the corrected sensible heating capacity of the primary air is –137 W. The heating provided by the active chilled beam would increase to 2,434 W (-137 W from the primary air and 2,571 W from the secondary water coil). The performance data in the Quick Selection Heating Capacity tables is based on a THW—TRA of 28 °C (50 ºC — 22 ºC). Use the correction factor for hot water temperature less room design temperature other than the 28 °C ∆T temperature difference used in the Quick Selection Heating Capacity

tables.

Example Using the above base unit selection, the sensible heating being provided by the secondary water coil is 2,571 W. If the hot water temperature was 40 °C (rather than the 50 ºC assumed in the tables), the actual temperature difference is 18 °C (rather than the 28 °C used in the tables). The corrected sensible heating capacity of the secondary water coil at the 18 °C ∆T is 1,645 W (2,571 W x 0.64) and the active chilled beam heating capacity would decrease to 1,302 W (-343 W from the primary air and 1,645 W from the secondary water coil). WATER FLOW RATESWATER FLOW RATESWATER FLOW RATESWATER FLOW RATES The cooling and heating capacities shown in the Quick Selection Capacity tables are based on water flows rates of 0.10 L/s. Use the water flow correction factor for water flow rates other than 0.10 L/s.

Water Temperature Correction Factor Water Temperature Correction Factor Water Temperature Correction Factor Water Temperature Correction Factor ———— HeatingHeatingHeatingHeating

Hot WaterHot WaterHot WaterHot Water ∆ ∆ ∆ ∆ TemperatureTemperatureTemperatureTemperature Correction FactorCorrection FactorCorrection FactorCorrection Factor

TemperatureTemperatureTemperatureTemperature Hot WaterHot WaterHot WaterHot Water————Room AirRoom AirRoom AirRoom Air Applied to Secondary CoilApplied to Secondary CoilApplied to Secondary CoilApplied to Secondary Coil

TTTTHWHWHWHW TTTTHW HW HW HW ———— TTTTRARARARA Heating CapacityHeating CapacityHeating CapacityHeating Capacity

(º C)(º C)(º C)(º C) (º C)(º C)(º C)(º C) KKKKHWHWHWHW

40404040 18181818 0.640.640.640.64

45454545 23232323 0.820.820.820.82

50505050 28282828 1.001.001.001.00

55555555 33333333 1.181.181.181.18

60606060 38383838 1.361.361.361.36

35353535 13131313 0.460.460.460.46

30303030 8888 0.290.290.290.29

Water Flow Capacity Correction Factor Water Flow Capacity Correction Factor Water Flow Capacity Correction Factor Water Flow Capacity Correction Factor ———— Cooling & HeatingCooling & HeatingCooling & HeatingCooling & Heating

Water Flow (L/s)Water Flow (L/s)Water Flow (L/s)Water Flow (L/s) 0.150.150.150.15 0.140.140.140.14 0.130.130.130.13 0.120.120.120.12 0.110.110.110.11 0.100.100.100.10 0.090.090.090.09 0.080.080.080.08 0.070.070.070.07 0.060.060.060.06 0.050.050.050.05 0.040.040.040.04 0.030.030.030.03

600 mm Length600 mm Length600 mm Length600 mm Length 1.021.021.021.02 1.021.021.021.02 1.011.011.011.01 1.011.011.011.01 1.011.011.011.01 1.001.001.001.00 0.990.990.990.99 0.980.980.980.98 0.960.960.960.96 0.960.960.960.96 0.940.940.940.94 0.900.900.900.90 0.850.850.850.85

900 mm Length900 mm Length900 mm Length900 mm Length 1.021.021.021.02 1.021.021.021.02 1.021.021.021.02 1.011.011.011.01 1.011.011.011.01 1.001.001.001.00 0.990.990.990.99 0.980.980.980.98 0.960.960.960.96 0.950.950.950.95 0.930.930.930.93 0.890.890.890.89 0.820.820.820.82

1200 mm Length1200 mm Length1200 mm Length1200 mm Length 1.031.031.031.03 1.031.031.031.03 1.021.021.021.02 1.021.021.021.02 1.011.011.011.01 1.001.001.001.00 0.990.990.990.99 0.980.980.980.98 0.960.960.960.96 0.930.930.930.93 0.900.900.900.90 0.850.850.850.85 0.770.770.770.77

1500 mm Length1500 mm Length1500 mm Length1500 mm Length 1.041.041.041.04 1.031.031.031.03 1.031.031.031.03 1.021.021.021.02 1.011.011.011.01 1.001.001.001.00 0.990.990.990.99 0.970.970.970.97 0.950.950.950.95 0.920.920.920.92 0.880.880.880.88 0.820.820.820.82 0.720.720.720.72

1800 mm Length1800 mm Length1800 mm Length1800 mm Length 1.051.051.051.05 1.041.041.041.04 1.031.031.031.03 1.021.021.021.02 1.011.011.011.01 1.001.001.001.00 .098.098.098.098 0.960.960.960.96 0.940.940.940.94 0.900.900.900.90 0.850.850.850.85 0.780.780.780.78 0.670.670.670.67

Page 6: Active Chilled Beamsdadanco.eu/images/downloads/ACB_35_Technical_Data... · 2019. 12. 3. · The general design intent of an Active Chilled Beam system is for the central system to

6

COMPUTERIZED SELECTION METHODCOMPUTERIZED SELECTION METHODCOMPUTERIZED SELECTION METHODCOMPUTERIZED SELECTION METHOD The Dadanco’s Specifier™ computerized selection program can be accessed on our website (www.dadanco.com). To request a selection, please contact your local sales representative (see our website for a listing of representatives). A list of the typical inputs needed for a unit selection is as follows:

ElevationElevationElevationElevation The performance data in the Quick Selection Capacity tables is based air densities at sea level. Use the correction factor for elevations other than sea level.

Example Using the previous example, the total sensible cooling being provided by the active chilled beam at sea level is 1,369 W. If the installation was at 1,200 meters above sea level, the total unit sensible cooling capacity is 1,177 W (1,369 W x 0.86).

Elevation Correction Factor Elevation Correction Factor Elevation Correction Factor Elevation Correction Factor ———— Cooling & HeatingCooling & HeatingCooling & HeatingCooling & Heating

Elevation AboveElevation AboveElevation AboveElevation Above Correction FactorCorrection FactorCorrection FactorCorrection Factor

Sea LevelSea LevelSea LevelSea Level Applied to CapacitiesApplied to CapacitiesApplied to CapacitiesApplied to Capacities

(Meters)(Meters)(Meters)(Meters) KKKKEEEE

300300300300 0.960.960.960.96

600600600600 0.930.930.930.93

900900900900 0.900.900.900.90

1200120012001200 0.860.860.860.86

1500150015001500 0.830.830.830.83

1800180018001800 0.800.800.800.80

Page 7: Active Chilled Beamsdadanco.eu/images/downloads/ACB_35_Technical_Data... · 2019. 12. 3. · The general design intent of an Active Chilled Beam system is for the central system to

7

Operating ConditionsOperating ConditionsOperating ConditionsOperating Conditions

Room Design Dry Bulb Temperature 24.024.024.024.0 ºCºCºCºC

Room Design Wet Bulb Temperature 17.017.017.017.0 ºCºCºCºC

Room Design Relative Humidity 50.050.050.050.0 %%%%

Room Design Dew Point Temperature 12.9012.9012.9012.90 ºCºCºCºC

Room Design Humidity Ratio 0.009250.009250.009250.00925 kgkgkgkgWaterWaterWaterWater/kg /kg /kg /kg Dry AirDry AirDry AirDry Air

Chilled Water Supply Temperature 14.014.014.014.0 ºCºCºCºC

Chilled Water Flow Rate 0.100.100.100.10 L/sL/sL/sL/s

Primary Air Dry Bulb Supply Temperature 12.012.012.012.0 ºCºCºCºC

Primary Air Wet Bulb Temperature 11.111.111.111.1 ºCºCºCºC

Primary Air Relative Humidity 90.090.090.090.0 %%%%

Primary Air Humidity Ratio 0.008000.008000.008000.00800 kgkgkgkg WaterWaterWaterWater/kg/kg/kg/kgDry AirDry AirDry AirDry Air

Primary Air Static Pressure 125125125125 PaPaPaPa

ACB35 ACB35 ACB35 ACB35 ---- 2222----Pipe Quick Selection Cooling CapacityPipe Quick Selection Cooling CapacityPipe Quick Selection Cooling CapacityPipe Quick Selection Cooling Capacity

Primary Primary Primary Primary Airflow Airflow Airflow Airflow

(L/s)(L/s)(L/s)(L/s)

Primary Air Primary Air Primary Air Primary Air

CoolingCoolingCoolingCooling Sensible Cooling (W)Sensible Cooling (W)Sensible Cooling (W)Sensible Cooling (W)

SensibleSensibleSensibleSensible LatentLatentLatentLatent

Nominal 600 mm Nominal 600 mm Nominal 600 mm Nominal 600 mm

CoilCoilCoilCoil

Nominal 900 mm Nominal 900 mm Nominal 900 mm Nominal 900 mm

Coil Coil Coil Coil

Nominal 1200 Nominal 1200 Nominal 1200 Nominal 1200

mm Coilmm Coilmm Coilmm Coil

Nominal 1500 Nominal 1500 Nominal 1500 Nominal 1500

mm Coilmm Coilmm Coilmm Coil

Nominal 1800 Nominal 1800 Nominal 1800 Nominal 1800

mm Coilmm Coilmm Coilmm Coil

(W)(W)(W)(W) (W)(W)(W)(W) CoilCoilCoilCoil TotalTotalTotalTotal CoilCoilCoilCoil TotalTotalTotalTotal CoilCoilCoilCoil TotalTotalTotalTotal CoilCoilCoilCoil TotalTotalTotalTotal CoilCoilCoilCoil TotalTotalTotalTotal

7777 103103103103 31313131 298298298298 401401401401

9999 137137137137 42424242 347347347347 484484484484 422422422422 559559559559

12121212 172172172172 52525252 386386386386 558558558558 475475475475 646646646646 528528528528 700700700700

14141414 206206206206 62626262 392392392392 598598598598 530530530530 736736736736 581581581581 787787787787

17171717 240240240240 73737373 593593593593 833833833833 633633633633 874874874874 713713713713 953953953953

19191919 275275275275 83838383 616616616616 891891891891 691691691691 966966966966 763763763763 1037103710371037 839839839839 1114111411141114

21212121 309309309309 94949494 629629629629 939939939939 754754754754 1063106310631063 813813813813 1122112211221122 892892892892 1201120112011201

24242424 343343343343 104104104104 626626626626 969969969969 766766766766 1110111011101110 867867867867 1211121112111211 940940940940 1283128312831283

26262626 378378378378 115115115115 782782782782 1159115911591159 924924924924 1301130113011301 983983983983 1361136113611361

28282828 412412412412 125125125125 784784784784 1196119611961196 957957957957 1369136913691369 1036103610361036 1448144814481448

31313131 447447447447 135135135135 984984984984 1431143114311431 1092109210921092 1539153915391539

33333333 481481481481 146146146146 1001100110011001 1482148214821482 1151115111511151 1632163216321632

35353535 515515515515 156156156156 1008100810081008 1523152315231523 1169116911691169 1684168416841684

38383838 550550550550 167167167167 1006100610061006 1555155515551555 1195119511951195 1745174517451745

40404040 584584584584 177177177177 1212121212121212 1796179617961796

42424242 618618618618 187187187187 1222122212221222 1840184018401840

45454545 653653653653 198198198198 1224122412241224 1877187718771877

47474747 687687687687 208208208208 1220122012201220 1907190719071907

Page 8: Active Chilled Beamsdadanco.eu/images/downloads/ACB_35_Technical_Data... · 2019. 12. 3. · The general design intent of an Active Chilled Beam system is for the central system to

8

Operating ConditionsOperating ConditionsOperating ConditionsOperating Conditions

Room Design Dry Bulb Temperature 22.022.022.022.0 ºCºCºCºC

Room Design Wet Bulb Temperature

Room Design Relative Humidity

Room Design Dew Point Temperature

Room Design Humidity Ratio

Hot Water Supply Temperature 50.050.050.050.0 ºCºCºCºC

Hot Water Flow Rate 0.100.100.100.10 L/sL/sL/sL/s

Primary Air Dry Bulb Supply Temperature 12.012.012.012.0 ºCºCºCºC

Primary Air Wet Bulb Temperature

Primary Air Relative Humidity

Primary Air Humidity Ratio

Primary Air Static Pressure 125125125125 PaPaPaPa

ACB35 ACB35 ACB35 ACB35 ---- 2222----Pipe Quick Selection Heating CapacityPipe Quick Selection Heating CapacityPipe Quick Selection Heating CapacityPipe Quick Selection Heating Capacity

Primary Primary Primary Primary Airflow Airflow Airflow Airflow

(L/s)(L/s)(L/s)(L/s)

Primary Air Primary Air Primary Air Primary Air

HeatingHeatingHeatingHeating Sensible Heating (W)Sensible Heating (W)Sensible Heating (W)Sensible Heating (W)

SensibleSensibleSensibleSensible

Nominal 600 mm Nominal 600 mm Nominal 600 mm Nominal 600 mm

CoilCoilCoilCoil

Nominal 900 mm Nominal 900 mm Nominal 900 mm Nominal 900 mm

Coil Coil Coil Coil

Nominal 1200 Nominal 1200 Nominal 1200 Nominal 1200

mm Coilmm Coilmm Coilmm Coil

Nominal 1500 Nominal 1500 Nominal 1500 Nominal 1500

mm Coilmm Coilmm Coilmm Coil

Nominal 1800 Nominal 1800 Nominal 1800 Nominal 1800

mm Coilmm Coilmm Coilmm Coil

(W)(W)(W)(W) CoilCoilCoilCoil TotalTotalTotalTotal CoilCoilCoilCoil TotalTotalTotalTotal CoilCoilCoilCoil TotalTotalTotalTotal CoilCoilCoilCoil TotalTotalTotalTotal CoilCoilCoilCoil TotalTotalTotalTotal

7777 ----86868686 800800800800 718718718718

9999 ----114114114114 932932932932 822822822822 1134113411341134 1024102410241024

12121212 ----143143143143 1039103910391039 901901901901 1276127612761276 1138113811381138 1420142014201420 1282128212821282

14141414 ----172172172172 1054105410541054 889889889889 1425142514251425 1260126012601260 1562156215621562 1397139713971397

17171717 ----200200200200 1593159315931593 1401140114011401 1702170217021702 1510151015101510 1916191619161916 1723172317231723

19191919 ----229229229229 1656165616561656 1437143714371437 1857185718571857 1637163716371637 2050205020502050 1830183018301830 2255225522552255 2035203520352035

21212121 ----258258258258 1692169216921692 1444144414441444 2026202620262026 1779177917791779 2186218621862186 1939193919391939 2397239723972397 2149214921492149

24242424 ----286286286286 1683168316831683 1408140814081408 2060206020602060 1785178517851785 2332233223322332 2057205720572057 2526252625262526 2251225122512251

26262626 ----315315315315 2101210121012101 1799179917991799 2483248324832483 2180218021802180 2642264226422642 2340234023402340

28282828 ----343343343343 2106210621062106 1777177717771777 2571257125712571 2242224222422242 2785278527852785 2456245624562456

31313131 ----372372372372 2646264626462646 2289228922892289 2936293629362936 2579257925792579

33333333 ----401401401401 2692269226922692 2307230723072307 3093309330933093 2709270927092709

35353535 ----429429429429 2710271027102710 2298229822982298 3142314231423142 2730273027302730

38383838 ----458458458458 2704270427042704 2264226422642264 3212321232123212 2773277327732773

40404040 ----487487487487 3259325932593259 2792279227922792

42424242 ----515515515515 3285328532853285 2790279027902790

45454545 ----544544544544 3290329032903290 2768276827682768

47474747 ----572572572572 3278327832783278 2729272927292729

Page 9: Active Chilled Beamsdadanco.eu/images/downloads/ACB_35_Technical_Data... · 2019. 12. 3. · The general design intent of an Active Chilled Beam system is for the central system to

9

Operating ConditionsOperating ConditionsOperating ConditionsOperating Conditions

Room Design Dry Bulb Temperature 24.024.024.024.0 ºCºCºCºC

Room Design Wet Bulb Temperature 17.017.017.017.0 ºCºCºCºC

Room Design Relative Humidity 50.050.050.050.0 %%%%

Room Design Dew Point Temperature 12.9012.9012.9012.90 ºCºCºCºC

Room Design Humidity Ratio 0.009250.009250.009250.00925 kgkgkgkgWaterWaterWaterWater/kg /kg /kg /kg Dry AirDry AirDry AirDry Air

Chilled Water Supply Temperature 14.014.014.014.0 ºCºCºCºC

Chilled Water Flow Rate 0.100.100.100.10 L/sL/sL/sL/s

Primary Air Dry Bulb Supply Temperature 12.012.012.012.0 ºCºCºCºC

Primary Air Wet Bulb Temperature 11.111.111.111.1 ºCºCºCºC

Primary Air Relative Humidity 90.090.090.090.0 %%%%

Primary Air Humidity Ratio 0.008000.008000.008000.00800 kgkgkgkg WaterWaterWaterWater/kg/kg/kg/kgDry AirDry AirDry AirDry Air

Primary Air Static Pressure 125125125125 PaPaPaPa

ACB35 ACB35 ACB35 ACB35 ---- 4444----Pipe Quick Selection Cooling CapacityPipe Quick Selection Cooling CapacityPipe Quick Selection Cooling CapacityPipe Quick Selection Cooling Capacity

Primary Primary Primary Primary Airflow Airflow Airflow Airflow

(L/s)(L/s)(L/s)(L/s)

Primary Air Primary Air Primary Air Primary Air

CoolingCoolingCoolingCooling Sensible Cooling (W)Sensible Cooling (W)Sensible Cooling (W)Sensible Cooling (W)

SensibleSensibleSensibleSensible LatentLatentLatentLatent

Nominal 600 mm Nominal 600 mm Nominal 600 mm Nominal 600 mm

CoilCoilCoilCoil

Nominal 900 mm Nominal 900 mm Nominal 900 mm Nominal 900 mm

Coil Coil Coil Coil

Nominal 1200 Nominal 1200 Nominal 1200 Nominal 1200

mm Coilmm Coilmm Coilmm Coil

Nominal 1500 Nominal 1500 Nominal 1500 Nominal 1500

mm Coilmm Coilmm Coilmm Coil

Nominal 1800 Nominal 1800 Nominal 1800 Nominal 1800

mm Coilmm Coilmm Coilmm Coil

(W)(W)(W)(W) (W)(W)(W)(W) CoilCoilCoilCoil TotalTotalTotalTotal CoilCoilCoilCoil TotalTotalTotalTotal CoilCoilCoilCoil TotalTotalTotalTotal CoilCoilCoilCoil TotalTotalTotalTotal CoilCoilCoilCoil TotalTotalTotalTotal

7777 103103103103 31313131 274274274274 377377377377

9999 137137137137 42424242 316316316316 454454454454 380380380380 518518518518

12121212 172172172172 52525252 349349349349 521521521521 424424424424 596596596596 469469469469 641641641641

14141414 206206206206 62626262 354354354354 560560560560 469469469469 675675675675 512512512512 718718718718

17171717 240240240240 73737373 520520520520 760760760760 553553553553 794794794794 618618618618 858858858858

19191919 275275275275 83838383 538538538538 813813813813 599599599599 874874874874 657657657657 932932932932 718718718718 993993993993

21212121 309309309309 94949494 549549549549 858858858858 648648648648 957957957957 697697697697 1006100610061006 759759759759 1068106810681068

24242424 343343343343 104104104104 546546546546 890890890890 658658658658 1001100110011001 739739739739 1082108210821082 797797797797 1140114011401140

26262626 378378378378 115115115115 670670670670 1048104810481048 782782782782 1160116011601160 830830830830 1208120812081208

28282828 412412412412 125125125125 671671671671 1084108410841084 808808808808 1220122012201220 871871871871 1283128312831283

31313131 447447447447 135135135135 829829829829 1276127612761276 915915915915 1361136113611361

33333333 481481481481 146146146146 842842842842 1323132313231323 960960960960 1441144114411441

35353535 515515515515 156156156156 848848848848 1363136313631363 974974974974 1490149014901490

38383838 550550550550 167167167167 846846846846 1395139513951395 995995995995 1544154415441544

40404040 584584584584 177177177177 1008100810081008 1592159215921592

42424242 618618618618 187187187187 1016101610161016 1634163416341634

45454545 653653653653 198198198198 1017101710171017 1670167016701670

47474747 687687687687 208208208208 1014101410141014 1701170117011701

Page 10: Active Chilled Beamsdadanco.eu/images/downloads/ACB_35_Technical_Data... · 2019. 12. 3. · The general design intent of an Active Chilled Beam system is for the central system to

10

Operating ConditionsOperating ConditionsOperating ConditionsOperating Conditions

Room Design Dry Bulb Temperature 22.022.022.022.0 ºCºCºCºC

Room Design Wet Bulb Temperature

Room Design Relative Humidity

Room Design Dew Point Temperature

Room Design Humidity Ratio

Hot Water Supply Temperature 50.050.050.050.0 ºCºCºCºC

Hot Water Flow Rate 0.100.100.100.10 L/sL/sL/sL/s

Primary Air Dry Bulb Supply Temperature 12.012.012.012.0 ºCºCºCºC

Primary Air Wet Bulb Temperature

Primary Air Relative Humidity

Primary Air Humidity Ratio

Primary Air Static Pressure 125125125125 PaPaPaPa

ACB35 ACB35 ACB35 ACB35 ---- 4444----Pipe Quick Selection Heating CapacityPipe Quick Selection Heating CapacityPipe Quick Selection Heating CapacityPipe Quick Selection Heating Capacity

Primary Primary Primary Primary Airflow Airflow Airflow Airflow

(L/s)(L/s)(L/s)(L/s)

Primary Air Primary Air Primary Air Primary Air

HeatingHeatingHeatingHeating Sensible Heating (W)Sensible Heating (W)Sensible Heating (W)Sensible Heating (W)

SensibleSensibleSensibleSensible

Nominal 600 mm Nominal 600 mm Nominal 600 mm Nominal 600 mm

CoilCoilCoilCoil

Nominal 900 mm Nominal 900 mm Nominal 900 mm Nominal 900 mm

Coil Coil Coil Coil

Nominal 1200 Nominal 1200 Nominal 1200 Nominal 1200

mm Coilmm Coilmm Coilmm Coil

Nominal 1500 Nominal 1500 Nominal 1500 Nominal 1500

mm Coilmm Coilmm Coilmm Coil

Nominal 1800 Nominal 1800 Nominal 1800 Nominal 1800

mm Coilmm Coilmm Coilmm Coil

(W)(W)(W)(W) CoilCoilCoilCoil TotalTotalTotalTotal CoilCoilCoilCoil TotalTotalTotalTotal CoilCoilCoilCoil TotalTotalTotalTotal CoilCoilCoilCoil TotalTotalTotalTotal CoilCoilCoilCoil TotalTotalTotalTotal

7777 ----86868686 667667667667 581581581581

9999 ----114114114114 777777777777 663663663663 945945945945 830830830830

12121212 ----143143143143 865865865865 722722722722 1063106310631063 920920920920 1183118311831183 1040104010401040

14141414 ----172172172172 878878878878 707707707707 1187118711871187 1015101510151015 1301130113011301 1130113011301130

17171717 ----200200200200 1328132813281328 1127112711271127 1419141914191419 1218121812181218 1596159615961596 1396139613961396

19191919 ----229229229229 1380138013801380 1151115111511151 1547154715471547 1318131813181318 1708170817081708 1479147914791479 1879187918791879 1650165016501650

21212121 ----258258258258 1410141014101410 1152115211521152 1688168816881688 1431143114311431 1822182218221822 1564156415641564 1997199719971997 1740174017401740

24242424 ----286286286286 1402140214021402 1116111611161116 1717171717171717 1430143014301430 1943194319431943 1657165716571657 2105210521052105 1819181918191819

26262626 ----315315315315 1751175117511751 1436143614361436 2069206920692069 1754175417541754 2202220222022202 1887188718871887

28282828 ----343343343343 1755175517551755 1412141214121412 2143214321432143 1799179917991799 2321232123212321 1978197819781978

31313131 ----372372372372 2205220522052205 1833183318331833 2447244724472447 2074207420742074

33333333 ----401401401401 2243224322432243 1842184218421842 2578257825782578 2177217721772177

35353535 ----429429429429 2258225822582258 1829182918291829 2619261926192619 2189218921892189

38383838 ----458458458458 2253225322532253 1795179517951795 2677267726772677 2219221922192219

40404040 ----487487487487 2716271627162716 2229222922292229

42424242 ----515515515515 2737273727372737 2222222222222222

45454545 ----544544544544 2742274227422742 2198219821982198

47474747 ----572572572572 2732273227322732 2160216021602160

Page 11: Active Chilled Beamsdadanco.eu/images/downloads/ACB_35_Technical_Data... · 2019. 12. 3. · The general design intent of an Active Chilled Beam system is for the central system to

11

ACB35 ACB35 ACB35 ACB35 ---- 1200 mm Unit Sound Data1200 mm Unit Sound Data1200 mm Unit Sound Data1200 mm Unit Sound Data Primary Primary Primary Primary Airflow Airflow Airflow Airflow

(CFM)(CFM)(CFM)(CFM)

100Pa Inlet Static Pressure100Pa Inlet Static Pressure100Pa Inlet Static Pressure100Pa Inlet Static Pressure 150 Pa Inlet Static Pressure150 Pa Inlet Static Pressure150 Pa Inlet Static Pressure150 Pa Inlet Static Pressure 200 Pa Inlet Static Pressure200 Pa Inlet Static Pressure200 Pa Inlet Static Pressure200 Pa Inlet Static Pressure

NCNCNCNC dB (A)dB (A)dB (A)dB (A) NCNCNCNC dB (A)dB (A)dB (A)dB (A) NCNCNCNC dB (A)dB (A)dB (A)dB (A)

High Nozzle PitchHigh Nozzle PitchHigh Nozzle PitchHigh Nozzle Pitch

30303030 ---- 14141414

35353535 ---- 19191919

40404040 16161616 24242424

Medium Nozzle PitchMedium Nozzle PitchMedium Nozzle PitchMedium Nozzle Pitch

40404040 ---- 16161616

50505050 15151515 22222222

60606060 20202020 26262626

Low Nozzle PitchLow Nozzle PitchLow Nozzle PitchLow Nozzle Pitch

55555555 16161616 23232323

70707070 22222222 27272727

80808080 26262626 31313131

Note: Room Attenuation effect of 10 dB has been applied when calculating NC levels.

Note: While every effort is made to ensure the details contained in this publication are current and up-to-date, in the interest of ongoing product development DADANCO reserves the right to alter the same without notice.

Page 12: Active Chilled Beamsdadanco.eu/images/downloads/ACB_35_Technical_Data... · 2019. 12. 3. · The general design intent of an Active Chilled Beam system is for the central system to

12

®

260 North Elm Street Westfield, MA 01085 Ph: (413) 564 — 5657 Fax: (413) 568 — 5384

www.dadanco.com [email protected]

DADANCO—MESTEK Joint Venture LLC (DADANCO)

is jointly owned by subsidiaries of Dadanco Pty Ltd headquartered in

Adelaide, Australia and Mestek, Inc. headquartered in Westfield, MA.

Mestek is a diversified manufacturer of HVAC products with sales of over

$400m. Mestek’s HVAC companies include Smith Cast Iron Boilers,

Hydrotherm, RBI Boilers & Water Heaters, Sterling, Vulcan, Airtherm,

Applied Air, Anemostat, Air Balance, Arrow United, L. J. Wing, Lockformer

and many others. May 2010