  • 7/25/2019 Accs Test Procedure

    1/12

    0 09/10/2011

    ISSUE DATE CUSTOMER AREVA TD

    Original Issue of test protocol

    DESCRIPTION

    DATE SIGNATURE

    SIZE ISSUE

    A4 (297 x 420 mm) 0

    SEC REFERENCE NO.

    AREVA REFERENCE NO.

    DOCUMENT TITLE

    TEST PROCEDURE FOR ACCS

    PAGES

    10

  • 7/25/2019 Accs Test Procedure

    2/12

    LOCATION : SEP RIYADH ACCS TEST PROCEDURE

    Failed Date Failed PassedDate

    Passe

    PAGE-1 Hardware component identification : C264

    PAGE-2 Validate HMI (LCD Screen)

    PAGE-3 Validate Control and Indication

    PAGE-4 Test General Cases

    PAGE-5 Test Case-1 ( BS-1 & BS-2 are in open position).

    PAGE-6 Test Case-2 (BS-1 in open posi tion &BS-2 in close posi tion).

    PAGE-7 Test Case-3 ( BS-1 in close posi tion & BS-2 in open posi tion).

    PAGE-8 Test Case-4 ( BS-1&BS-2 are in close position ).

    PAGE-9 Test Case-5 ( Irrespective of Bus Sectionaliser Status ).

    PAGE-10 Test Case-6 (Irrespective of Bus Sectionaliser Status ).

    Reference Test Objective

    Test Result

    INDEX

    ACCS TEST PROCEDURE

  • 7/25/2019 Accs Test Procedure

    3/12

    TEST PROCEDURE PAGE 1/1

    IED: C264

    APPLICATION: ACCS ISSUE:

    Test Objective

    Initial conditions Test Tools

    Test conditions Referenced DocumentsAs Follows C264 Technical Manual

    Act ions

    Result:

    Hardware component identification : C264

    Pass

    ed

    Not

    Tested

    Faile

    d RemarkAct ions

    => Note down the serial number of C264.1 ]

    2 ]

    3 ]

    4 ]

    5 ]

    6 ]

    => Check that each DI Card contains 16 Input channels

    => Check that each DO Card contains 10 Output channels

    => Check the presence of 17 LED indicattion lamps.

    => Check for Copper (RJ45) & Fiber Optic (ST) Ports available.

    => Note down the serial number of C264.

    => Identify and note down the number of I/O Cards.

    7 ]

    8 ]

    9 ]

    10 ]

    11 ]

    12 ]

    13 ]

    14 ]

    15 ]

    Software Version : Comments :

    Database version :

    Automation Version :

    Other Version :

    Attached Documents :

    Overall Decision : TESTED BY WITNESSED BY

    : PassedName / Visa Name / Visa

    : Not Completed

    =>

    => Check the front port access.

    =>

    =>

    =>

    =>

    =>

    => Check the Auxilliary power supply of C264

    => Check the Wetting voltage of Digital Input Board of C264

    : FailedDate : Date :

    ACCS TEST PROCEDURE

  • 7/25/2019 Accs Test Procedure

    4/12

    TEST PROCEDURE PAGE 2/1

    IED: C264

    APPLICATION: ACCS ISSUE:

    Test Objective

    Initial conditions Test Tools

    Test conditions Referenced Documents

    Validate HMI (LCD Screen)

    Panel Powered on

    As Follows

    Act ions

    Result:

    Pass

    ed

    Not

    Tested

    Faile

    d RemarkAct ions

    => Check the navigation buttons on front panel of C2641 ]

    2 ]

    3 ]

    4 ]

    5 ]

    6 ]

    => Check the navigation buttons on front panel of C264

    Navigate through the pages on LCD and find display of the following.

    => Details of Firmware and database.

    => Status (Healthy or Faulty) of DI, DO & AI cards.

    => Status (High/Low) of all DI & DO Channels

    => Reading of Analog Value (If Any)

    7 ]

    8 ]

    9 ]

    10 ]

    11 ]

    12 ]

    13 ]

    14 ]

    15 ]

    Software Version : Comments :

    Database version :

    Automation Version :

    Other Version :

    Attached Documents :

    Overall Decision : TESTED BY WITNESSED BY

    : PassedName / Visa Name / Visa

    : Not Completed

    => Check the SLD on LHMI

    => Check the arrangement of equipments on LHMI

    =>

    =>

    =>

    =>

    =>

    =>

    =>

    : FailedDate : Date :

    ACCS TEST PROCEDURE

  • 7/25/2019 Accs Test Procedure

    5/12

    TEST PROCEDURE PAGE 3/1

    IED: C264

    APPLICATION: ACCS ISSUE:

    Test Objective

    Initial conditions Test Tools

    Test conditions Referenced Documents

    Validate control and Indication

    Panel is powered on

    As Follows

    Act ions

    Result:

    Pass

    ed

    Not

    Tested

    Faile

    d RemarkAct ions

    => Download a valid database and check the LED Corresponds to "OPERATIONAL" Glows1 ]

    2 ]

    3 ]

    4 ]

    5 ]

    6 ]

    => Download a valid database and check the LED Corresponds to "OPERATIONAL" Glows

    => When the C264 Auxilliary supply connected, check the LED Corresponds to "POWER" Glows

    => Check when the ACCS is IN SERVICE, corresponding Lamp Glows

    => Check when the ACCS is OUT OF SERVICE, corresponding Lamp Glows

    => Check when the Capacitor Connected to Bus-A is in Discharging mode, corresponding Lamp Glows

    => Check when the Capacitor Connected to Bus-B is in Discharging mode, corresponding Lamp Glows

    7 ]

    8 ]

    9 ]

    10 ]

    11 ]

    12 ]

    13 ]

    14 ]

    15 ]

    Software Version : Comments :

    Database version :

    Automation Version :

    Other Version :

    Attached Documents :

    Overall Decision : TESTED BY WITNESSED BY

    : PassedName / Visa Name / Visa

    : Not Completed

    => Check when the Capacitor Connected to Bus-C is in Discharging mode, corresponding Lamp Glows

    =>

    =>

    =>

    =>

    =>

    : FailedDate : Date :

    ACCS TEST PROCEDURE

  • 7/25/2019 Accs Test Procedure

    6/12

    TEST PROCEDURE PAGE 4/1

    IED: C264

    APPLICATION: ACCS ISSUE:

    Test Objective

    Initial conditions Test Tools

    Test conditions Referenced Documents

    To test ACCS Logic(General Test)

    As Follows

    Digital Simulator kit, Analog Simulation KitC264 is powered up and connected with Simulators

    ACCS Functional & Logic Description

    Act ions

    Result:

    Pass

    ed

    Not

    Tested

    Faile

    d RemarkAct ions

    => Check all the status information are in healthy condition1 ]

    2 ]

    3 ]

    4 ]

    5 ]

    6 ]

    => Validate the reading of GT-1 Reactive power is correct

    => Check the Operation of ACCS IN/OUT or ON/OFF function works correctly.

    => Check the CB of the Capacitor bank once Switched OFF shall not Switch ON within 10 Minutes.

    => Check the ACCS is IN SERVICE.

    => Check all the status information are in healthy condition

    => Validate the reading of GT-2 Reactive power is correct

    7 ]

    8 ]

    9 ]

    10 ]

    11 ]

    12 ]

    13 ]

    14 ]

    15 ]

    Software Version : Comments :

    Database version :

    Automation Version :

    Other Version :

    Attached Documents :

    Overall Decision : TESTED BY WITNESSED BY

    : PassedName / Visa Name / Visa

    : Not Completed

    => Check when the Capacitor Bank is Overloaded, (ie: Overlaod DI signal received) the respective capacitor

    bank trip command issued from ACCS

    => Validate the reading of Bus-C Voltage is correct

    => Validate the reading of GT-3 Reactive power is correct

    =>

    =>

    =>

    =>

    => Validate the reading of Bus-B Voltage is correct

    => Validate the reading of Bus-A Voltage is correct

    : FailedDate : Date :

    ACCS TEST PROCEDURE

  • 7/25/2019 Accs Test Procedure

    7/12

    TEST PROCEDURE PAGE 5/1

    IED: C264

    APPLICATION: ACCS ISSUE:

    Test Objective

    Initial conditions Test Tools

    Test conditions Referenced Documents

    To test ACCS Logic (Test case-1)

    C264 is powered up and connected with Simulators Digital Simulator kit, Analog Simulation Kit

    BS-1 & BS-2 are in open position ACCS Functional & Logic Description

    Act ions

    Result:

    Pass

    ed

    Not

    Tested

    Faile

    d RemarkAct ions

    => Check all the status information are in healthy condition1 ]

    2 ]

    3 ]

    4 ]

    5 ]

    6 ]

    => Check all the status information are in healthy condition

    => Check the ACCS is IN SERVICE.

    => Inject the Reactive Power of Transformer-1 (HV Side) above set value (MVAr-1) for t1 time duration

    => Check the Capacitor -1 is switched ON automatically

    => Inject the Reactive Power of Transformer-1 (HV Side) below set value (MVAr-2) for t2 time duration

    => Check the Capacitor -1 is switched OFF automatically

    7 ]

    8 ]

    9 ]

    10 ]

    11 ]

    12 ]

    13 ]

    14 ]

    15 ]

    Software Version : Comments :

    Database version :

    Automation Version :

    Other Version :

    Attached Documents :

    Overall Decision : TESTED BY WITNESSED BY

    : PassedName / Visa Name / Visa

    : Not Completed

    => Inject the Reactive Power of Transformer-2 (HV Side) above set value (MVAr-1) for t1 time duration

    => Check the Capacitor -2 is switched ON automatically

    =>

    => Inject the Reactive Power of Transformer-2(HV Side) below set value (MVAr-2) for t2 time duration

    => Check the Capacitor -2 is switched OFF automatically

    => Inject the Reactive Power of Transformer-3 (HV Side) above set value (MVAr-1) for t1 time duration

    => Check the Capacitor -3 is switched ON automatically

    => Inject the Reactive Power of Transformer-3 (HV Side) below set value (MVAr-2) for t2 time duration

    => Check the Capacitor -3 is switched OFF automatically

    : FailedDate : Date :

    ACCS TEST PROCEDURE

  • 7/25/2019 Accs Test Procedure

    8/12

    TEST PROCEDURE PAGE 6/1

    IED: C264

    APPLICATION: ACCS ISSUE:

    Test Objective

    Initial conditions Test Tools

    Test conditions Referenced Documents

    To test ACCS Logic (Test case-2)

    C264 is powered up and connected with Simulators Digital Simulator kit, Analog Simulation Kit

    BS-1 in open position &BS-2 in close position ACCS Functional & Logic Description

    Act ions

    Result:

    Pass

    ed

    Not

    Tested

    Faile

    d RemarkAct ions

    => Check all the status information are in healthy condition1 ]

    2 ]

    3 ]

    4 ]

    5 ]

    6 ]

    => Check all the status information are in healthy condition

    => Check the ACCS is IN SERVICE.

    => Inject the Reactive Power of Transformer-1 (HV Side) above set value (MVAr-1) for t1 time duration

    => Check the Capacitor -1 is switched ON automatically

    => Inject the Reactive Power of Transformer-1 (HV Side) below set value (MVAr-2) for t2 time duration

    => Check the Capacitor -1 is switched OFF automatically

    7 ]

    8 ]

    9 ]

    10 ]

    11 ]

    12 ]

    13 ]

    14 ]

    15 ]

    Software Version : Comments :

    Database version :

    Automation Version :

    Other Version :

    Notes: System Allows to Switch ON the Capacitor Bank Attached Documents :

    10 Minutes Af ter Swich OFF

    Overall Decision : TESTED BY WITNESSED BY

    : PassedName / Visa Name / Visa

    : Not Completed

    => Inject the Reactive Power of Transformer-2 & Transformer-3 combinely to come above set value (MVAr-3)

    for t3 time duration

    => Check the Capacitor -2 is switched ON automatically

    =>

    => Inject the Reactive Power of Transformer-2&Transformer-3 combinely to come below set value (MVAr-4) for

    t4 time duration

    => Check the Capacitor -2 is switched OFF automatically

    => Inject the Reactive Power of Transformer-2&Transformer-3 combinely to come above set value (MVAr-5) for

    t5 time duration

    => Check the Capacitor -3 is switched ON automatically

    => Inject the Reactive Power of Transformer-2&Transformer-3 combinely to come below set value (MVAr-6) for

    t6 time duration

    => Check the Capacitor -3 is switched OFF automatically

    : FailedDate : Date :

    ACCS TEST PROCEDURE

  • 7/25/2019 Accs Test Procedure

    9/12

    TEST PROCEDURE PAGE 7/1

    IED: C264

    APPLICATION: ACCS ISSUE:

    Test Objective

    Initial conditions Test Tools

    Test conditions Referenced Documents

    To test ACCS Logic (Test case-3)

    C264 is powered up and connected with Simulators Digital Simulator kit, Analog Simulation Kit

    BS-1 in close position & BS-2 in open position ACCS Functional & Logic Description

    Act ions

    Result:

    Pass

    ed

    Not

    Tested

    Faile

    d RemarkAct ions

    => Check all the status information are in healthy condition1 ]

    2 ]

    3 ]

    4 ]

    5 ]

    6 ]

    => Check all the status information are in healthy condition

    => Check the ACCS is IN SERVICE.

    => Inject the Reactive Power of Transformer-1 & Transformer-2 combinely to come above set value (MVAr-3)

    for t3 time duration

    => Check the Capacitor -1 is switched ON automatically

    => Inject the Reactive Power of Transformer-1&Transformer-2 combinely to come below set value (MVAr-4) for

    t4 time duration

    => Check the Capacitor -1 is switched OFF automatically

    7 ]

    8 ]

    9 ]

    10 ]

    11 ]

    12 ]

    13 ]

    14 ]

    15 ]

    Software Version : Comments :

    Database version :

    Automation Version :

    Other Version :

    Notes: System Allows to Switch ON the Capacitor Bank Attached Documents :

    10 Minutes Af ter Swich OFF

    Overall Decision : TESTED BY WITNESSED BY

    : PassedName / Visa Name / Visa

    : Not Completed

    => Inject the Reactive Power of Transformer-1 & Transformer-2 combinely to come above set value (MVAr-5)

    for t5 time duration

    => Check the Capacitor -2 is switched ON automatically

    =>

    => Inject the Reactive Power of Transformer-1&Transformer-2 combinely to come below set value (MVAr-6) for

    t6 time duration

    => Check the Capacitor -2 is switched OFF automatically

    => Inject the Reactive Power of Transformer-3 above set value (MVAr-1) for t1 time duration

    => Check the Capacitor -3 is switched ON automatically

    => Inject the Reactive Power of Transformer-3 below set value (MVAr-2) for t2 time duration

    => Check the Capacitor -3 is switched OFF automatically

    : FailedDate : Date :

    ACCS TEST PROCEDURE

  • 7/25/2019 Accs Test Procedure

    10/12

    TEST PROCEDURE PAGE 8/1

    IED: C264

    APPLICATION: ACCS ISSUE:

    Test Objective

    Initial conditions Test Tools

    Test conditions Referenced Documents

    To test ACCS Logic (Test case-4)

    C264 is powered up and connected with Simulators Digital Simulator kit, Analog Simulation Kit

    BS-1&BS-2 are in close position ACCS Functional & Logic Description

    Act ions

    Result:

    Pass

    ed

    Not

    Tested

    Faile

    d RemarkAct ions

    => Check all the status information are in healthy condition1 ]

    2 ]

    3 ]

    4 ]

    5 ]

    6 ]

    => Check all the status information are in healthy condition

    => Check the ACCS is IN SERVICE.

    => Inject the Reactive Power of Transformer-1, Transformer-2& Transformer-3 combinely to come above set

    value (MVAr-3) for t3 time duration

    => Check the Capacitor -1 is switched ON automatically

    => Inject the Reactive Power of Transformer-1, Transformer-2 & Transformer-3 combinely to come below set

    value (MVAr-4) for t4 time duration

    => Check the Capacitor -1 is switched OFF automatically

    7 ]

    8 ]

    9 ]

    10 ]

    11 ]

    12 ]

    13 ]

    14 ]

    15 ]

    Software Version : Comments :

    Database version :

    Automation Version :

    Other Version :

    Notes: System Allows to Switch ON the Capacitor Bank Attached Documents :

    10 Minutes Af ter Swich OFF

    Overall Decision : TESTED BY WITNESSED BY

    : PassedName / Visa Name / Visa

    : Not Completed

    => Inject the Reactive Power of Transformer-1 , Transformer-2 & Transformer-3 combinely to come above set

    value (MVAr-5) for t5 time duration

    => Check the Capacitor -2 is switched ON automatically

    =>

    => Inject the Reactive Power of Transformer-1 , Transformer-2 & Transformer-3 combinely to come below set

    value (MVAr-6) for t6 time duration

    => Check the Capacitor -2 is switched OFF automatically

    => Inject the Reactive Power of Transformer-1 , Transformer-2 & Transformer-3 combinely to come above set

    value (MVAr-7) for t7 time duration

    => Check the Capacitor -3 is switched ON automatically

    => Inject the Reactive Power of Transformer-1 , Transformer-2 & Transformer-3 combinely to come below set

    value (MVAr-8) for t8 time duration

    => Check the Capacitor -3 is switched OFF automatically

    : FailedDate : Date :

    ACCS TEST PROCEDURE

  • 7/25/2019 Accs Test Procedure

    11/12

    TEST PROCEDURE PAGE 9/1

    IED: C264

    APPLICATION: ACCS ISSUE:

    Test Objective

    Initial conditions Test Tools

    Test conditions Referenced Documents

    To test ACCS Logic (Test case-5)

    C264 is powered up and connected with Simulators Digital Simulator kit, Analog Simulation Kit

    Irresctive of Bus Sectionalizer (BS) Status. Capacitor Banks are ON ACCS Functional & Logic Description

    Act ions

    Result:

    Pass

    ed

    Not

    Tested

    Faile

    d RemarkAct ions

    => Check all the status information are in healthy condition1 ]

    2 ]

    3 ]

    4 ]

    5 ]

    6 ]

    => Check all the status information are in healthy condition

    => Check the ACCS is IN SERVICE.

    => Inject the Voltage to Bus Section-A (13.8kV Side) above set value (V-1) for t9 time duration

    => Check the Capacitor -1 is switched OFF automatically

    => Check if the Over Voltage Switch OFF Condition Supersedes Conditions of CASE-1 to CASE-4

    => Inject the Voltage to Bus Section-B (13.8kV Side) above set value (V-1) for t9 time duration

    7 ]

    8 ]

    9 ]

    10 ]

    11 ]

    12 ]

    13 ]

    14 ]

    15 ]

    Software Version : Comments :

    Database version :

    Automation Version :

    Other Version :

    Notes: System Allows to Switch ON the Capacitor Bank Attached Documents :

    10 Minutes Af ter Swich OFF

    Overall Decision : TESTED BY WITNESSED BY

    : PassedName / Visa Name / Visa

    : Not Completed

    => Check the Capacitor -2 is switched OFF automatically

    => Check if the Over Voltage Switch OFF Condition Supersedes Conditions of CASE-1 to CASE-4

    =>

    => Inject the Voltage to Bus Section-C (13.8kV Side) above set value (V-1) for t9 time duration

    => Check the Capacitor -3 is switched OFF automatically

    => Check if the Over Voltage Switch OFF Condition Supersedes Conditions of CASE-1 to CASE-4

    =>

    =>

    =>

    : FailedDate : Date :

    ACCS TEST PROCEDURE

  • 7/25/2019 Accs Test Procedure

    12/12

    TEST PROCEDURE PAGE 10/1

    IED: C264

    APPLICATION: ACCS ISSUE:

    Test Objective

    Initial conditions Test Tools

    Test conditions Referenced Documents

    To test ACCS Logic (Test case-6)

    C264 is powered up and connected with Simulators Digital Simulator kit, Analog Simulation Kit

    Irresctive of Bus Sectionalizer (BS) Status. Capacitor Banks are OFF ACCS Functional & Logic Description

    Act ions

    Result:

    Pass

    ed

    Not

    Tested

    Faile

    d RemarkAct ions

    => Check all the status information are in healthy condition1 ]

    2 ]

    3 ]

    4 ]

    5 ]

    6 ]

    => Check all the status information are in healthy condition

    => Check the ACCS is IN SERVICE.

    => Inject the Voltage to Bus Section-A (13.8kV Side) below set value (V-2) for t-10 time duration

    => Check the Capacitor -1 is switched ON automatically

    => Inject the Voltage to Bus Section-B (13.8kV Side) below set value (V-2) for t-10 time duration

    => Check the Capacitor -2 is switched ON automatically

    7 ]

    8 ]

    9 ]

    10 ]

    11 ]

    12 ]

    13 ]

    14 ]

    15 ]

    Software Version : Comments :

    Database version :

    Automation Version :

    Other Version :

    Notes: System Allows to Switch ON the Capacitor Bank Attached Documents :

    10 Minutes Af ter Swich OFF

    Overall Decision : TESTED BY WITNESSED BY

    : PassedName / Visa Name / Visa

    : Not Completed

    => Inject the Voltage to Bus Section-C (13.8kV Side) below set value (V-2) for t-10 time duration

    => Check the Capacitor -3 is switched ON automatically

    =>

    => Check if the Under Voltage Switch ON Condition Supersedes Conditions of CASE-1 to CASE-4

    =>

    =>

    =>

    =>

    =>

    : FailedDate : Date :