access design standards

Upload: gustavo-sevilla

Post on 05-Apr-2018

226 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/2/2019 Access Design Standards

    1/90

    calgary.ca | call 3-1-1

    AccessDesignStandards

    Advisory Committeeon AccessibilityMobility, Vision, Cognitive, Hearing

  • 8/2/2019 Access Design Standards

    2/90

    A c c e s s D e s i g n S t a n d a r d s T h e C i t y o C a l g a r y

    September 2009

    The 2010 edition o The City o Calgary Access Design Standards is largely based on the 2002

    edition. However, we wish to grateully acknowledge the ollowing groups and individuals or theirassistance with developing new and revised content or 2010.

    The City o Calgary committees

    Advisory Committee on Accessibility

    Access Design Sub-Committee

    The City o Calgary business units/divisions

    Calgary Housing Company

    Calgary Transit

    Community & Neighbourhood Services

    Corporate Properties & Buildings

    Development & Building Approvals

    Land Servicing & Housing

    Land Use Planning & Policy

    Recreation

    Roads

    Transportation InrastructureTransportation Planning

    Private industry/not-or proft contributors/individuals

    Accessible Housing Society

    Mark Iantkow

    Editorial team

    Sarah Alexander

    Anna CiarlaUlrik Seward

    Janel Smith

    Acknowledgements

  • 8/2/2019 Access Design Standards

    3/90

    1A c c e s s D e s i g n S t a n d a r d s T h e C i t y o C a l g a r y

    Table o Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1

    Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

    Access design standards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3A. Exterior barrier-ree path o travel . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

    B. Interior barrier-ree path o travel . . . . . . . . . . . . . . . . . . . . . . . . . . 12

    C. Vehicular access. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16

    D. Illumination and acoustics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22

    E. Location o controls, dispensers and receptacles . . . . . . . . . . . . . . . 24

    F. Building entrances, doors and doorways . . . . . . . . . . . . . . . . . . . . . 26

    G. Ramps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31

    H. Stairs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33

    J. Handrails and guards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36

    K. Elevators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38

    L. Public washrooms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41

    M. Recreational and cultural centres . . . . . . . . . . . . . . . . . . . . . . . . . 45

    N. Public acilities . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50

    P. Parks, pathways and playgrounds . . . . . . . . . . . . . . . . . . . . . . . . . . 54

    Q. Patios . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58

    R. Emergency egress, alarms and warning suraces . . . . . . . . . . . . . . . 59

    S. Communications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64

    T. Plus-15 System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70

    U. Public transit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72

    V. Pedestrian crossings and trac signals . . . . . . . . . . . . . . . . . . . . . . 74W. Crime Prevention through Environmental Design (CPTED) . . . . . . 76

    X. Universal Dwelling Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78

    Figure list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84

    Endnotes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87

    Table o Contents

  • 8/2/2019 Access Design Standards

    4/90

    2 A c c e s s D e s i g n S t a n d a r d s T h e C i t y o C a l g a r y

    Today, people with disabilities are in the

    mainstream o society, where opportunities are

    the same or everyone and is enriched by the

    diversity o its active and contributing members.

    It is important that people o all abilities be

    positively supported by their surroundings.

    A well-designed environment is sae,

    convenient, comortable, age-riendly1

    and readily accessible to everyone. Design

    solutions that also respond to the climate

    variations in a winter city, like Calgary, increase

    and enhance the accessibility to the outdoors

    throughout the year.

    The City o Calgary wishes to set an example

    by creating a more livable and accessible

    city. To this end, it established the Advisory

    Committee on Accessibility (ACA) and

    published these Standards.

    The Advisory Committee on Accessibility

    was established by City Council to improve

    access to buildings and other services. The

    committee consists o members with disabilities,

    representatives rom the community, and City o

    Calgary business units. The terms o reerence o

    the ACA are:

    To review and make recommendations

    to City Council through the Standing

    Policy Committee on Community and

    Protective Services on policy issues, the

    accessibility o municipal properties,

    inormation and services or people

    with disabilities, and to be a resource to

    City Council and City Administration in

    addressing accessibility issues.

    Introduction

  • 8/2/2019 Access Design Standards

    5/90

    3A c c e s s D e s i g n S t a n d a r d s T h e C i t y o C a l g a r y

    These Standards represent The City o Calgarys

    approach to a universal built environment.

    They are intended to complement the Alberta

    Building Code. In some cases, these Standardsare intended to enhance accessibility

    by requiring measures that exceed the

    requirements o the Alberta Building Code 2006.

    The contents o these Standards are required to

    be integrated into the design and construction

    o all new City o Calgary owned/operated

    buildings and acilities. The Standards do not

    require retrotting o existing buildings. Theyare not intended to be a set o requirements

    or projects that are not owned or operated by

    The City. However, design proessionals, the

    building industry, government departments

    and the community as a whole are

    encouraged to implement these Standards

    in all projects constructed within the city.

    Generally, these Standards apply within

    the property boundaries o City owned/

    operated buildings and acilities. For

    construction pertaining to regional pathways,

    road right-o-ways and city parks, the

    appropriate City department shall be

    consulted, in addition to these Standards.

    This document is designed both as a

    working tool to provide a common point

    o reerence and as a means to increasethe awareness o the needs o people

    with disabilities, including the elderly.

    Formulation o these Standards has been based

    primarily on:

    1. Experience and knowledge o people with

    disabilities rom the community.2. Expertise acquired by The City o Calgary

    business units through planning and review

    o major projects.

    3. Documentation o standards by other

    authorities, provinces and countries.

    4. Alberta Building Code 2006.

    Questions regarding the content o these

    standards can be directed to:

    Advisory Committee on Accessibility

    Administrative Contact

    Telephone: 3-1-1

    TTY: 403-268-1379

    Email: [email protected]

    These Standards are comprised o 22 Sections.

    Each Section is divided into sub-sections,

    as ollows:

    1. Principle/rationale:

    A statement o the principle/rationale behind

    making a particular area accessible.

    2. Existing regulations:

    Articles o the Alberta Building Code (ABC)

    2006 and other recognized standards, relating

    to each specic area o concern.

    3. Proposed standards:Proposals to improve access and justication or

    those proposals. In some cases, the deciencies

    o existing regulations are highlighted.

    In some sections, graphic illustrations are

    provided as supporting inormation. Please be

    advised, all measurements in illustrations are in

    millimetres, unless otherwise specied.

    Access design standards

  • 8/2/2019 Access Design Standards

    6/90

    4 A c c e s s D e s i g n S t a n d a r d s T h e C i t y o C a l g a r y

    A.1 Principle/rationale

    Everyone wants to be able to move throughout

    a city saely, conveniently and independently.

    Exterior barrier-ree paths o travel, which

    include pathways and sidewalks, can make

    movement dicult i not impossible i obstacles

    or hazards obstruct the path o travel. These

    obstacles and hazards can be weather induced,

    as in the case o snow drits. The placement o

    exterior items must not obstruct the pathway or

    people with visual or mobility impairments.

    Consistent tactile suraces within barrier-ree

    paths o travel prevent conusion and promote

    understanding through textured surace

    indicators. When care is taken in the design o

    the tactile quality o suraces, those suraces

    can support inormation regarding orientation,

    direction and location.

    The City o Calgary Roads, Transportation

    Planning, and Land Use Planning & Policy shall

    be consulted or all matters concerning public

    sidewalks and roads.

    Figure 1. Cane detectable tactile suraces.

    A.2 Existing regulations

    Alberta Building Code 2006 3.8.3.2.

    A.3 Proposed standards

    This section applies to exterior pathways and

    sidewalks on the property o City owned andoperated buildings.

    A.3.1 Suraces and textures

    Since ground and foor suraces are an

    important aspect o access, they shall be

    designed to acilitate sae and easy movement.

    The reeze/thaw cycle and positive drainage

    are an important consideration when designing

    ground suraces.

    A. Exterior barrier-ree path o travel

  • 8/2/2019 Access Design Standards

    7/90

    5A c c e s s D e s i g n S t a n d a r d s T h e C i t y o C a l g a r y

    Throughout these Standards, Five Basic

    Principles or Sae and Eective Environmental

    Design or People with Visual Disabilities

    have been considered. These ve principleswere developed by Mark Iantkow in 2003

    and are best remembered by using the

    acronym CoLATE.

    Co Colour and contrast

    L Lighting

    A Audible cues

    T Tactile cues

    E Ergonomics

    The principle considered in this sub-section and

    other sections in these Standards is T Tactile

    Cues, described by Iantkow as ollows:

    Tactile queues (and cues) are a parallel

    consideration to audible queuing. One might

    align onesel according to the direction o

    a wall, curb or planter i there is someindication that such a tactile entity is used in a

    consistent way within a structure. Tactile cues

    may also be used at decision making points or

    waynding (dierent textures on foor suraces;

    or textures on walls; or signs in relie placed

    consistently next to doorways; or even railings

    with dierent textures when approaching

    changes in elevation).2

    Outdoor ground suraces made o brick or stone

    shall be laid on a rm base, level with adjacent

    suraces and embedded in concrete.

    The City o Calgary is currently researching

    the easibility o developing a system o tactile

    tiles, provisionally known as Urban Braille, or

    use in the citys public sidewalks. These tiles

    assist people with vision loss in negotiating

    public sidewalks.

    Directional tiles are normally thin, linearly

    aligned tiles that contrast with the rest othe sidewalk, helping to direct pedestrian

    trac. Node tiles along the sidewalk act as

    an indicator or deciding to cross a road

    or change direction. Intersection curb tiles

    indicate curb ramps. Crosswalk directional tiles

    are used on crosswalks to direct people saely

    across the road.

    Please contact the Advisory Committeeon Accessibility (ACA) or updates on the

    development o these tactile systems. These

    tiles are not to be applied without prior

    approval, since consistency and standardization

    are necessary or the success o the entire

    system. The City intends to develop these

    standards urther, and such inormation may be

    incorporated into uture editions o the Access

    Design Standards.

  • 8/2/2019 Access Design Standards

    8/90

    6 A c c e s s D e s i g n S t a n d a r d s T h e C i t y o C a l g a r y

    Figure 2. Crosswalk direction tile3. Figure 3. Node tile4.

    Figure 4. Directional tile5. Figure 5. Intersection curb tile.

  • 8/2/2019 Access Design Standards

    9/90

    7A c c e s s D e s i g n S t a n d a r d s T h e C i t y o C a l g a r y

    A.3.2 General requirements

    The placement o lampposts, transormers,

    mailboxes, newspaper boxes, trash containers

    and bus shelters, can obstruct the barrier-ree

    path o travel. They should be placed outside

    the minimum required width o the sidewalk

    or pathway.

    The minimum width o a sidewalk shall be

    1,500 mm (the Transportation Association o

    Canada recommends 2,400 mm).

    Joints in sidewalks or between bricks or stonesshall not exceed 13 mm in width.

    Figure 6. Sidewalk joint.

    Sidewalks shall be designed to drain water toprevent puddles and ice build-up.

    Rest areas shall be located on one side

    o walkways every 30 m. Rest areas shall

    have minimum dimensions o 2,400 mm

    x 2,400 mm. I benches are included in the

    rest areas, they shall conorm with Section P

    o these Standards.

    Figure 7. Obstructions located out o the direct patho travel.

    A.3.3 Obstructions

    The Alberta Building Code requires a

    horizontally projecting obstruction to extend

    within 680 mm above the foor or ground

    surace. People with vision loss nd this height

    to be above cane detection level. Thereore,

    a lower maximum o 200 mm is required toreduce the risk o collision with the obstruction.

    Figure 8. Specication or protruding objects toavoid collision.

  • 8/2/2019 Access Design Standards

    10/90

    8 A c c e s s D e s i g n S t a n d a r d s T h e C i t y o C a l g a r y

    Gratings, manhole covers, electrical vaults and

    other access covers shall be placed adjacent

    to walkways, out o the path o travel, unless

    prevented by site constraints. I placementwithin the path o travel is unavoidable, the

    gratings shall have a maximum clear opening o

    13 mm. Due to ventilation requirements,

    the gratings on electrical vaults may be

    larger (openings no larger than 20 mm wide

    x 90 mm long to meet transormer ventilation

    requirements, as specied by Enmax).

    The long dimension o the openings shalllie perpendicular to the path o travel, and i

    small solid plates (like ootprints) are placed in

    the direction o pedestrian trac and spaced

    to accommodate an average stride, a person

    wearing high heels can cross gratings saely.

    Guy-wires near walkways shall be clearly

    marked to at least 1,980 mm above the ground

    and have a physical barrier beneath or be

    placed out o the path o travel.

    Temporary signs, parked vehicles, or vegetation

    shall not block a path o travel.

    Figure 11. Clearance between overhanging objects andthe ground.

    Figure 9. Requirements or openings in theground surace.

    Figure 10. Placement o gratings.

  • 8/2/2019 Access Design Standards

    11/90

    9A c c e s s D e s i g n S t a n d a r d s T h e C i t y o C a l g a r y

    Figure 12. Proper placement o obstructions.

    A.3.4 Curb ramps

    In Calgary, new sidewalks are constructed with

    curb ramps. Curb ramps are also constructed

    when curb and gutter work is undertaken in

    existing sidewalks or when they are replaced.

    In designing curb ramps, care shall be taken

    to prevent them rom becoming hazardous

    to people with vision loss, who may not

    notice them and walk inadvertently into the

    intersection. Curb ramps located right on

    the corner shall be avoided, because they

    orce people with vision loss, people using

    wheelchairs and people pushing strollers

    into the intersection, rather than the sae area

    o the crosswalk.

    At times, curb radii and trac saety concerns

    preclude the alignment o the curb ramp

    perpendicular to trac. In such cases,

    the curb ramps shall discharge into thepainted crosswalk, as close as possible to a

    perpendicular alignment with trac fow.

    Figure 13. Proper placement o curb ramps.

    A level surace shall be maintained on the

    sidewalk behind the curb ramps or smooth

    pedestrian and wheelchair travel.

    The minimum width o curb ramps, exclusive o

    fared sides, shall be 1,500 mm.

  • 8/2/2019 Access Design Standards

    12/90

    1 0 A c c e s s D e s i g n S t a n d a r d s T h e C i t y o C a l g a r y

    The slope o a curb ramp shall not exceed 1:12

    (eight per cent), and shall be not less than 1:15

    (six per cent) unless sidewalk constraints do not

    allow these ratios.

    Figure 14. Plan view o City standard curb ramp6.

    Figure 15. Section and elevation o curb ramp7.

    The edges shall be curved rather than cut

    sharply, so all the wheels o a wheelchair can

    maintain contact with the ground at all times.

    Suraces o curb ramps shall be slip resistant.

    Curb ramps shall contrast in texture rom the

    surrounding sidewalk and the road, so they can

    be identied by the visually impaired. A raised

    texture is more perceptible.

    Drainage shall be designed to prevent water

    and snow accumulation at the bottom o curb

    ramps. However, catch basins shall not be

    located in ront o the curb ramps.

    Where the widths o sidewalks provide

    adequate space, curb ramps shall be oset rom

    the main fow o pedestrian trac and still bewithin the crosswalk area. The corner curb shall

    be maintained as a clearly dened edge and be

    cane detectable.

    Figure 16. Proper layout o intersections.

  • 8/2/2019 Access Design Standards

    13/90

    1 1A c c e s s D e s i g n S t a n d a r d s T h e C i t y o C a l g a r y

    Medians in crossings shall have curb

    ramps at both sides and a level area no

    less than 1,500 mm long. Where a median

    island is less than 3.6 m wide, the tworamps and the fat area between shall

    all be reduced by an equal amount.

    A.3.5 Snow removal

    Temporary hazards are oten overlooked. For

    example, snow removal oten results in snow

    banks along sidewalks, which block access.

    Snow removal vehicles oten clear the street,but they must also ensure curbs are not blocked

    with snow banks, as it makes it dicult, i not

    impossible, to cross the street.

    Wind buers, such as ences, hedges and trees,

    shall be set back rom the sidewalk so the walk

    will be protected rom winds and snow will be

    deposited next to the walk, rather than coveringthe path.

    Figure 17. Wind buers.

  • 8/2/2019 Access Design Standards

    14/90

    1 2 A c c e s s D e s i g n S t a n d a r d s T h e C i t y o C a l g a r y

    B. Interior barrier-ree path o travel

    B.1 Principle/rationale

    Navigation through interior corridors and

    passageways shall be simple and sae.

    Passageway widths can create barriers, i

    the needs o people with disabilities are not

    considered. Strategic placement o objects in a

    passageway can reduce collisions and acilitate

    cane detection. Surace materials are also an

    important consideration or people with vision

    loss and the elderly, as they can reduce injury

    and disorientation.

    B.2 Existing regulations

    Alberta Building Code 2006 3.3.1.9.

    1) The minimum width o a public corridor shall

    be 1,100 mm.

    2) Except as required by Sentence 3.3.3.3.(2),

    the minimum unobstructed width o a corridor

    used by the public or a corridor serving

    classrooms or patients sleeping rooms shall be

    1,100 mm.

    3) Except as permitted by Sentence (4),

    obstructions located within 1,980 mm o the

    oor shall not project more than 100 mm

    horizontally into an exit passageway, a public

    corridor, a corridor used by the public or a

    corridor serving classrooms or patients sleeping

    rooms in a manner that would create a hazard

    or a person with a visual disability traveling

    adjacent to the walls.

    4) The horizontal projection o an obstruction

    reerred to in Sentence (3) is permitted to be

    more than 100 mm provided the clearance

    between the obstruction and the oor is lessthan 680 mm.

    Figure 18. Proper height requirements or

    protruding objects.

    Alberta Building Code 2006 A-3.3.1.9.

    4) The sweep o a cane used by blind or

    visually impaired persons normally detects

    obstructions that are within 680 mm o the oor.

    Any obstructions above this height would not

    normally be detected and can, thereore, create

    a hazard i it projects more than 100 mm intothe path o travel.

  • 8/2/2019 Access Design Standards

    15/90

    1 3A c c e s s D e s i g n S t a n d a r d s T h e C i t y o C a l g a r y

    Figure 19. Interior passageway.

    B.3 Proposed standards

    B.3.1 General requirements

    The ideal width o an interior corridor is 1,525

    mm. This allows two wheelchairs to pass each

    other without diculty. Additional manoeuvring

    space is necessary at corners and doorways. The

    length o a wheelchair, including ootrest, shallbe considered when determining the turning

    radius. Thereore, at corners and doorways, or

    greater ease o manoeuvrability, 1,525 mm is

    also recommended.

    Due to space restrictions, a corridor width

    o 1,525 mm is dicult to achieve in some

    areas. The minimum width or private corridors,

    including store and restaurant aisles shall be920 mm.

    In Section A, the principles o CoLATE were

    introduced. The principle that has been

    considered in this sub-section and others in

    these Standards is Co Colour and Contrast,and A Audible Cues, which is described by

    Iantkow as ollows:

    Eective use o colour and contrast designs can

    enhance sae orientation and mobility o people

    with visual impairments. Walls should be in

    contrast with ooring, urniture in good contrast

    with carpeting and surrounding walls, colour/

    contrast queues and cues can be used orwayfnding or even to denote important fxtures

    such as door knobs, door rames, drinking

    ountains, etc.

    Audible queues (and cues) are also a vital

    consideration or people with varied levels o

    vision (particularly or those individuals with no

    vision at all). One can align their path o travel

    according to sounds they know the location

    o, they can relate the distance rom various

    objects by sound, or even track where they are

    located within a structure by knowing a sound

    cue within a structure. A water ountain which

    gives o a distinctive sound within a shopping

    mall is one example.8

  • 8/2/2019 Access Design Standards

    16/90

    1 4 A c c e s s D e s i g n S t a n d a r d s T h e C i t y o C a l g a r y

    There shall be a consistency o materials and

    colours in recurring situations to provide

    satisactory sensory inormation about the

    environment. The acoustic properties omaterials used in interior passageways shall

    be considered in the design. Some sound

    reverberation aids people with vision loss by

    providing a sense o the size o the space and

    the location o walls or openings, while some

    sound absorption helps people who have

    hearing loss by reducing background noise.

    Figure 20. Proper design o an interior corridor.

    B.3.2 Obstructions

    Free-standing or cantilevered staircases,

    escalators, ramps and intermediate foor levels

    shall be avoided or have a barrier to prevent

    accidental access to the overhung area.

    Overhead signs shall have a clearance o 2,100

    mm rom the bottom o the sign to the ground.

    Objects protruding more than 100 mm rom

    the wall with a top surace higher than 680 mm

    shall extend to within 200 mm rom the foor, in

    order to be cane detectable.

    B.3.3 Floor suraces

    Surace materials o circulation routes shall not

    impede pedestrian movement, particularly or

    those in wheelchairs or distort the perception o

    people who are visually impaired.

    Carpets laid on the foor, stairs or ramp suraces

    shall be securely attached. They shall have atight weave, low pile and rm underlay.

    Figure 21. Improper type and installation o carpets.

  • 8/2/2019 Access Design Standards

    17/90

    1 5A c c e s s D e s i g n S t a n d a r d s T h e C i t y o C a l g a r y

    Exposed edges o carpet shall be astened to the

    foor surace with trim along the entire exposed

    edge. The carpet trim shall be beveled with a

    slope o no greater than 1:2 (50 per cent).

    All foor nishes shall be slip resistant,

    continuous, non-glossy and stable. The foor

    surace shall have a coecient o riction no

    less than 0.5, wet or dry.

    Figure 22. Proper type and installation o foor materials.

    B.3.4 Wall suraces

    Wall suraces shall not distort perception or

    cause physical harm, shall not be extremely

    rough or uneven and shall have a matte nish

    to prevent glare.

    Wall suraces shall not be entirely constructed

    with mirror or glass, or else there shall be a

    horizontal warning strip, such as an adhesive

    lm or graphic, that is a minimum o 150 mmwide and placed 1,350 mm above the foor.

    Sharp angles or junctions o nishes shall be

    avoided, and wall xtures shall be recessed,

    i possible.

    Figure 23. Recessed obstruction.

  • 8/2/2019 Access Design Standards

    18/90

    1 6 A c c e s s D e s i g n S t a n d a r d s T h e C i t y o C a l g a r y

    C. Vehicular access

    C.1 Principle/rationale

    Accessible parking shall be designed to be sae

    and convenient, or users o both wheelchairs

    and pedestrians. The requirements o this

    section apply to parking lots, parking structures,

    underground parking, lay-bys and street parking.

    Seasonal conditions shall be considered, as icy

    and wet parking acilities may be treacherous.

    The stall dimensions, location, construction

    materials and parking meters/machines shall be

    accessible. Signage is essential to encourage

    access and proper use.

    C.2 Existing regulations

    Alberta Building Code 2006 A-3.8.2.2.

    Access to Parking Areas

    The Planning Actprovides a mechanism

    or determining the characteristics o our

    communities. Where the Planning Act requiresparking, the building code requires that a

    percentage o parking spaces be designed to

    allow persons using wheelchairs sufcient room

    to get in and out o a vehicle. A barrier-ree path

    o travel shall also be provided rom the parking

    area to the building.

    The designer must provide a properly

    identifed and unobstructed path o travelrom the parking area to the entrance, which

    is accessible. The entrance chosen should be,

    in any case, one normally used by the

    occupants o the building. Long paths o

    travel are not recommended.

    C.3 Proposed standards

    This section applies to vehicular access on the

    property o City owned and operated buildings.

    The City o Calgary Roads and Transportation

    Planning shall be consulted or all matters

    concerning public sidewalks and roads.

    C.3.1 Lay-bys

    Lay-bys are roadside drop-o areas, separated

    rom the fow o vehicular trac and usually

    located in ront o buildings along busy streets.

    Their main unction is to allow passengers to getin and out o vehicles saely and conveniently.

    They are especially benecial or people with

    mobility limitations, seniors, persons with

    strollers or those loading or unloading large or

    heavy items.

    Figure 24. Lay-by.

    The provision o lay-bys shall be encouraged,

    especially where streets are narrow or where

    there is a steady fow o trac.

  • 8/2/2019 Access Design Standards

    19/90

    1 7A c c e s s D e s i g n S t a n d a r d s T h e C i t y o C a l g a r y

    Lay-bys shall be provided close to main

    entrances o buildings. They shall have a

    minimum width o 3,700 mm and a minimum

    length o 7,600 mm.

    Figure 25. Proper dimensions and design o canopyover lay-by.

    A curb maintains a separation between the

    lay-by and the path o travel to acilitate saety

    and proper drainage.

    Where lay-bys are provided, curb ramps shall

    be placed in the lay-by or wheelchair access.

    The curb ramp shall be designed in accordance

    with Section A o these Standards.

    The curb shall be a roll curb to allow an

    accessibility vehicle, or an Access Calgary

    vehicle, to back onto the sidewalk and then

    lower its ramp to load and unload passengers.

    Building entrances adjacent to lay-bys shall be

    covered where possible, to provide shelter rom

    precipitation and to keep the sidewalk ree o

    snow and ice. The minimum clearance o a

    covering shall be 3,000 mm rom the ground.

    It is recognized that it may not be reasonable to

    expect lay-bys in many downtown sites where

    competing interests or land may render lay-

    bys non-unctional or beyond reasonable cost.In all cases, Transportation Planning is to be

    consulted when designing a lay-by.

    C.3.2 Layout o parking areas

    Accessible parking stalls within parking

    lots shall be located as close as possible

    to a main accessible entrance and provide

    enough space to get in and out o a vehicle(see Section C.3.4 or proper dimensions o

    parking stalls). Where operational requirements

    allow, persons with disabilities shall not have to

    pass behind vehicles that would normally back

    out o a space.

    Asphalt, concrete or rm gravel is an acceptable

    parking surace. In gravel parking lots, there

    shall be parking or people with disabilitiesadjoining a hard surace. A paved surace shall

    be provided rom the designated parking stall to

    the sidewalk.

    Curb ramps leading rom parking areas

    to sidewalks shall be designed in accordance

    with Section A o these Standards. In all

    cases, pedestrians and people in wheelchairs

    shall be directed to a sae path o travelleading to the building, instead o orcing

    them into areas designed or vehicular trac

    and water drainage.

  • 8/2/2019 Access Design Standards

    20/90

    1 8 A c c e s s D e s i g n S t a n d a r d s T h e C i t y o C a l g a r y

    Where pedestrians have to walk across

    vehicular routes, there shall be contrast o

    colour and texture.

    Figure 26. Proper placement o parking stalls

    near entrances.

    Parking blocks or wheel stops shall be set back

    so vehicles do not overhang, reducing the

    clear width o accessible routes. Clearances

    behind wheel stops shall allow a wheelchair topass through. In addition, they shall be colour

    contrasted rom the paving material so they

    are not a hazard, in particular to people with

    vision loss.

    A large parking lot shall be divided with

    vegetation into smaller sections ecient or

    snow removal, yet that provide wind protection

    and control driting snow. Landscaping shallbe designed so everyone, including people

    using mobility devices, has the same degree o

    visibility across the parking lot. Consideration

    should be given to CPTED principles (Crime

    Prevention Through Environmental Design)

    when adding landscaping to a parking lot, so as

    not to create unsae situations or the ability or

    people to partake in crime-related activities.

    Figure 27. Proper vegetation placement to minimize theeects o the weather.

  • 8/2/2019 Access Design Standards

    21/90

    1 9A c c e s s D e s i g n S t a n d a r d s T h e C i t y o C a l g a r y

    C.3.3 On-site road parking

    Street parking shall also be made wheelchair

    accessible, since in some areas o the city this

    is the only type o parking available. However,

    current City policy does not allow or mid-block

    ramps. Thereore, accessible parking shall be

    located at both ends o a block.

    Street parking stalls or persons with disabilities

    shall be located adjacent to sidewalk curb

    ramps, to provide easy maneuverability and

    saety rom street to sidewalk. These parking

    stalls shall be 4,000 mm wide, and their length

    shall conorm to the latest Land Use Bylaw. In

    addition, a 2,000 mm access aisle shall be

    painted behind or in ront o the parking stall,

    and the access aisle shall be centered on the

    centerline o the curb ramp (depending on the

    location o the curb ramp).

    Figure 28. Accessible street parking stall.

    Where designated parking stalls are provided

    on the street, height o parking meters (or Park

    Plus machines) shall be in the range o 900 to

    1,100 mm. Parking meters/machines shall notrequire twisting o the wrist or pinching o the

    ngers to operate.

    Parking meters/machines shall be placed at

    either end o street parking stalls with no

    obstructions in ront or to the side o the coin

    slot/card slot. Parking meters/machines shall be

    located in a well-lit and protected area.

    C.3.4 Parking stalls

    An accessible parking stall shall be 4,000 mm

    wide to allow space or an access aisle on either

    side o the parking stall. The increased width

    over the Alberta Building Code minimum

    width o 3,700 mm is required to acilitate

    moving rom a vehicle to a wheelchair or

    or the use o other mobility aids. The greaterwidth allows or the length o the lit o a

    vehicle and the turning space o a wheelchair

    user as he/she disembarks. In all cases, the

    length o parking stalls shall conorm to the

    latest Land Use Bylaw.

  • 8/2/2019 Access Design Standards

    22/90

    2 0 A c c e s s D e s i g n S t a n d a r d s T h e C i t y o C a l g a r y

    Figure 29. Proper placement o parking stallnear entrance.

    Figure 30. Layout and dimensions o single accessibleparking stalls.

    I two adjacent parking spaces are designated

    or people with disabilities, the total width

    o both spaces shall be 7,400 mm, which

    shall include a 2,000 mm wide access aisleseparating the two stalls. Thereore, each stall

    will have a 2,700 mm width available or the

    vehicle and 2,000 mm available or the access

    aisle. The access aisle shall be clearly marked

    with blue hatched lines.

    Figure 31. Adjacent accessible parking stalls10.

  • 8/2/2019 Access Design Standards

    23/90

    2 1A c c e s s D e s i g n S t a n d a r d s T h e C i t y o C a l g a r y

    C.3.5 Signage

    Parking stalls or people with disabilities shall

    be identied with the international symbol o

    access and shall include the words Permit

    Required. The international symbol o access

    shall be posted on a vertical sign and the

    symbol shall be painted on the ground with

    blue paint to aid clear identication o the stall.

    Figure 32. Proper signage or accessible parking stall.

    Paint only the symbol and not the entire parking

    space, as paint is slippery when wet.

    I the location o designated parking stalls is

    not obvious or is not visible rom a distance,directional signage shall be placed along the

    route, to assist in navigation.

    C.3.6 Parkades

    Multi-level parkades shall provide accessible

    parking stalls adjacent to an accessible

    elevator on each level. Where elevators

    are not provided, designated parking shall be

    available at grade.

    I oversized vehicles are required to drop

    o passengers in the parking garage, a

    minimum vertical clearance o 3,000 mm

    shall be provided.

    Figure 33. Clearance requirement or parkades whereoversized vehicles are present.

  • 8/2/2019 Access Design Standards

    24/90

    2 2 A c c e s s D e s i g n S t a n d a r d s T h e C i t y o C a l g a r y

    D. Illumination and acoustics

    D.1. Principle/rationale

    Consistency in the levels o illumination is

    a primary concern or people with vision

    loss, since their ability to adjust rom one

    level to another is oten slow. This is

    particularly important when making the

    transition rom the exterior to the interior.

    Appropriate illumination design includes proper

    placement o light sources, appropriate day

    lighting, and adequate signage11.

    The minimization o ambient noise and the

    reduction o layering o dierent sounds

    improve a persons ability to hear. In addition,

    people with hearing loss rely on adequate

    articial lighting or speech reading, sign

    language or inormative signs. They also

    require spaces to be acoustically designed so

    background noises and echoes do not become

    a problem12.

    D.2 Existing regulations

    Alberta Building Code 2006 3.2.7.1.

    1) An exit, a public corridor or a corridor

    providing access to exit or the public or serving

    patients sleeping rooms or classrooms shall be

    equipped to provide illumination to an average

    level o not less than 50 lx at oor or tread level

    and at angles and intersections at changes olevel where there are stairs or ramps.

    D.3 Proposed standards

    D.3.1 Illumination

    In Section A, the principles o CoLATE wereintroduced. The principle that has been

    considered in this sub-section and others

    in these Standards is L Lighting, which is

    described by Iantkow as ollows:

    Lighting (or perhaps more aptly phrased as

    illumination, since we are reerring to the

    actual way an area is illuminated rather than,

    necessarily, the source or type o lighting) isa vital consideration in providing sae access/

    egress and use o a structure or outdoor area.

    Designers oten use accent lighting to highlight

    a decision making point or a point o interest.

    Even back-lit lighting is used to highlight certain

    points o interest or or inormation purposes.

    Such lighting designs are not desirable or

    most people with visual impairments. Most

    eye conditions require a well-distributed,

    constant level o lighting. Back-lit areas or

    areas where glare is present, or proceeding

    rom a dark lit area to a brightly lit area only

    exacerbate orientation and mobility or people

    with visual impairments.13

  • 8/2/2019 Access Design Standards

    25/90

    2 3A c c e s s D e s i g n S t a n d a r d s T h e C i t y o C a l g a r y

    High levels o consistent illumination with

    minimal glare improve a persons ability to

    see. Illumination levels shall be increased

    to emphasize stairs, entrances, obstacles,inormation signs and hazardous areas.

    The minimum level o illumination emitted by

    illuminated signs shall be 200 lx. Other signs

    shall be illuminated to 100 lx.

    Controls and operating mechanisms shall be

    capable o being illuminated to at least a level

    o 100 lx.Lights must be controlled and directed

    so they do not create glare. Light xtures

    shall be placed to prevent lamps rom shining

    into peoples aces; nor should light xtures

    be positioned so light refects o highly

    refective materials.

    Enhanced illumination or a greater distribution

    o xtures or outdoor areas is important topeople with vision loss. Proper outdoor lighting

    helps people with hearing loss have adequate

    lighting or speech reading.

    Windows shall be designed and located to

    prevent glare, especially in areas o circulation.

    D.3.2 Acoustics

    Carpets or sound-absorbing materials shall be

    used to aid people with hearing loss.

    Background noise can be dicult or a

    hard-o-hearing person. When possible,

    switches shall be installed to turn o noisy

    devices such as ans.

    The placement o speakers o public address

    systems shall not be near crucial areas o

    communication, such as over an inormation or

    service desk.

  • 8/2/2019 Access Design Standards

    26/90

    2 4 A c c e s s D e s i g n S t a n d a r d s T h e C i t y o C a l g a r y

    E. Location o controls, dispensers and receptacles

    E.1 Principle/rationale

    Oten, controls are too high, too low or too ar

    away or people to reach. Some controls are

    dicult to grasp and turn. Design and location

    o controls shall oer simple operation and

    saety. Controls, including thermostats, light

    switches, re alarms and aucets, shall be

    accessible to everyone.

    E.2 Existing regulations

    Alberta Building Code 2006 3.8.1.5.

    Alberta Building Code 2006 7.2.6.7.

    1) I the authority having jurisdiction deems it

    necessary to protect children, the elderly,

    or persons with disabilities or infrmities

    rom burns,

    a) piping used to distribute service hot water

    and other hot water in assembly occupancies,

    care or detention occupancies and residential

    occupancies shall be concealed or insulated,

    and

    b) except as provided by the plumbing

    regulations made pursuant to the Saety Codes

    Act, the temperature o the water rom aucets

    shall be limited to a maximum o 54C.

    E.3 Proposed standards

    E.3.1 General requirements

    Controls, dispensers and receptaclesshall not require the use o two hands,

    nor two simultaneous movements by one

    hand or both hands to operate.

    E.3.2 Saety and emergency controls

    Emergency controls shall not be placed too high

    or people in wheelchairs. They shall not be too

    low, thereby helping to prevent children rom

    misusing them. Emergency controls, such as

    re alarms, shall be located with their highest

    operable parts 1,200 mm above the foor

    (measured to their centre line).

    Figure 34. Proper height or controls.

  • 8/2/2019 Access Design Standards

    27/90

    2 5A c c e s s D e s i g n S t a n d a r d s T h e C i t y o C a l g a r y

    E.3.3 Lighting fxtures

    The highest operable part o light switches

    and other non-emergency controls shall be

    1,000 mm above the foor. Rocker switches are

    preerable to toggle switches, as they are easier

    to use.

    E.3.4 Electrical outlets

    Electrical outlets shall be mounted at a height o

    600 mm, measured rom the foor to the centre

    line o the outlet.

    E.3.5 Faucets

    Automatic water taps or a lever-type aucet shall

    be used or easy operation. Water temperature

    shall be limited in accordance with the Alberta

    Building Code 2006.

    Figure 35. Proper and improper aucet varieties.

  • 8/2/2019 Access Design Standards

    28/90

    2 6 A c c e s s D e s i g n S t a n d a r d s T h e C i t y o C a l g a r y

    F. Building entrances, doors and doorways

    F.1 Principle/rationale

    Wide doorways and easy-to-open doors benet

    everyone. The passage is easier or people with

    disabilities, seniors, people carrying packages

    or wheeling strollers. Automatic doors and

    proper hardware placement makes entrances

    much easier to use.

    A well-designed door is distinguished, yet

    simple, oering direction and orientation to

    users. Proper lighting and signage is a good

    means or accommodating this requirement.

    F.2 Existing regulations

    Alberta Building Code 2006 3.8.1.2.

    1) In addition to the barrier-ree entrances

    required by Sentence (2), not less than 50%

    o the pedestrian entrances to a building in

    Sentence 3.8.1.1.(1), including walkways

    leading to the entrances rom a public

    thoroughare and rom on site parking areas,

    shall be barrier-ree.

    6) I an entrance is equipped with a security

    system, both visual and audible signals shall be

    used to indicate when the door lock is released.

    Figure 36. Vestibule.

    Alberta Building Code 2006 3.3.1.13.

    1) A door that opens into or is located within

    a public corridor or other acility that provides

    access to exit rom a suite shall

    a) Provide a clear opening o not less than

    800 mm i there is only one door lea,

    b) in a doorway with multiple leaves, have the

    active lea providing a clear opening o not less

    than 800 mm, and

    c) Not open onto a step.

  • 8/2/2019 Access Design Standards

    29/90

    2 7A c c e s s D e s i g n S t a n d a r d s T h e C i t y o C a l g a r y

    3) Except as permitted by Sentence (4), door

    release hardware shall be operable by one

    hand and the door shall be openable with not

    more than one releasing operation. (See alsoSentence 3.8.3.3.(3))

    5) Door release hardware shall be installed not

    more than 1,200 mm above the fnished oor.

    8) Controls or the remote release o door

    locking devices permitted by Sentence (6)

    shall be located in an area readily available to

    security personnel.Alberta Building Code 2006 3.4.3.2.

    Alberta Building Code 2006 3.8.3.3.

    3) Door operating devices shall be o a design

    which does not require tight grasping and

    twisting o the wrist as the only means o

    operation. (See Appendix A.)

    11) A vestibule located in a barrier ree path o

    travel shall be arranged to allow the movement

    o wheelchairs between doors and shall provide

    a distance between 2 doors in series o not less

    than 1,200 mm plus the width o any door that

    swings into the space in the path o travel rom

    one door to another.

    F.3 Proposed standards

    F.3.1 Entrances

    Entrances, particularly the main accessibleone, shall be readily distinguishable in the

    acade and shall provide an easy transition into

    the building. The eect o seasonal weather

    conditions, such as strong winds and driting

    snow, shall be mitigated in the design o

    building entrances to ensure normal operation

    o doors.

    When entrances must be located towards theprevailing winds, measures to minimize the

    eects shall be used, such as walls and/or

    vegetation. Drainage shall be directed away

    rom the entrance.

    Doormats with non-slip under padding ease

    the transition rom the outdoor environment to

    interior spaces, by absorbing much o the snow,

    ice and slush accumulated rom winter bootsand shoes. This prevents people rom slipping

    on any smooth foor materials used inside.

    Doormats shall not project more than 13 mm

    above the foor nish.

    Well-designed lighting and signage shall be

    used to enhance identication o an entrance.

    Where operational requirements allow,

    sliding automatic doors shall be installed at

    entrances and entrance vestibules in new

    construction. The sliding automatic doors

    shall have a saety power-ail option, that

    includes a backup battery.

  • 8/2/2019 Access Design Standards

    30/90

    2 8 A c c e s s D e s i g n S t a n d a r d s T h e C i t y o C a l g a r y

    Figure 37. Automatic doors, signage and protection rom

    the elements.

    F.3.2 Specifcations or people with

    vision loss

    Providing adequate lighting or transitions

    rom the exterior to interior assists people with

    vision loss, who may be slower to adjust to

    the dierence in levels o light. Such transition

    space shall be well lit.

    Door push plates shall be o a contrasting

    colour or value, beneting the visually impaired.

    Plate glass doors shall be designed so people

    with vision loss can readily identiy them

    (see Section B).

    Numbers on doors shall be raised and located

    between 1,200 mm and 1,800 mm or easy

    reading by people with vision loss.

    Figure 38. Large, bold and raised lettering labels.

    Due to Building Code regulations, exit doors

    must open outward, which can create a hazard

    or people with vision loss, especially automatic

    swing doors. To rectiy this problem, such doors

    shall be recessed to minimize the hazard or

    people walking beside a building.

    Figure 39. Recessed door.

  • 8/2/2019 Access Design Standards

    31/90

    2 9A c c e s s D e s i g n S t a n d a r d s T h e C i t y o C a l g a r y

    F.3.3 Door openers and hardware

    People with limited mobility, strength or

    balance nd doors, particularly those on the

    exterior o a building, dicult, i not impossible,

    to open. Automatic door openers or power-

    assisted mechanisms shall be used on doors

    in universal paths o travel, such as entrances,

    lobbies, corridors and other major public

    pedestrian thoroughares.

    Figure 40. Proper location o automatic door openers.

    Manual door openers shall be mounted at a

    height o 800 mm to 1,100 mm rom the foor.

    Although Alberta Building Code 2006 allows

    a maximum height o 1,200 mm, door release

    hardware shall be installed between 800 mm to

    1,100 mm.

    Clearance between the handle and the door

    shall be a minimum o 50 mm. This will aid

    those with limited hand unctions and allow the

    door to be opened using only one arm.

    Figure 41. Proper spacing between a door and hardware.

    I a door is opened remotely (as is commonin many multi-amily residential buildings), a

    visual and audible signal shall be used to alert

    both the visitors and the occupants that the

    door lock is released.

    The bottom o a manual door shall have a

    smooth uninterrupted kick plate to protect the

    door rom wheelchair ootrests. A minimum

    height o 300 mm is recommended.

    Figure 42. Kick plate and closer requirements.

  • 8/2/2019 Access Design Standards

    32/90

    3 0 A c c e s s D e s i g n S t a n d a r d s T h e C i t y o C a l g a r y

    F.3.4 Doors and gates

    In any set o two or more doors or gates,

    whether within a building, at an entrance to

    a building or completely outside, the door

    opening shall alternate between right and let

    hand operation. For example, i an entrance has

    three doors, there shall be one set o double

    doors and the third door can be hinged on

    either the let or right hand side. As another

    example, i there are two doors in a series, the

    inner door and outer door should be hinged on

    opposite sides.

    This enables persons to operate the door with

    one hand on the side o their choice and

    avoid the need to reach across or even travel

    backwards through the door. Persons with an

    occupied hand, including those with a support

    white cane, a guide dog and persons carrying

    luggage or packages would be able to use

    their ree hand to open the door without theawkwardness o having to reach across. In no

    circumstance should it be necessary to use two

    hands to open a door.

    Doorways without a door installed in them shall

    be minimum 850 mm wide.

    Door width shall be not less than 920 mm.

    When turnstiles or revolving doors are provided,

    a swing door with an automatic door controlshall be placed immediately to one side o the

    revolving door or turnstile, or easy access by

    people with disabilities.

    Automatic doors shall have a master control that

    can control the door closers, keeping the door

    open or a minimum o eight seconds, with the

    door held at an angle o between 70 and 90

    degrees. As well, the master control allows thedoor to reverse when closing i an object stops

    the door.

    Figure 43. Door closer requirements and requirements ordoors at the top o a ramp.

  • 8/2/2019 Access Design Standards

    33/90

    3 1A c c e s s D e s i g n S t a n d a r d s T h e C i t y o C a l g a r y

    G. Ramps

    G.1 Principle/rationale

    For changes in levels, ramps are essential in

    providing an easier and oten saer means o

    travel or people who are unable to use stairs.

    The slope, width and length o a ramp shall be

    manageable. Signage, tactile cues, protection

    rom the elements and proper landings also

    help increase comort or those using the ramp.

    G.2 Existing regulations

    Alberta Building Code 2006 3.8.3.4.

    G.3 Proposed standards

    G.3.1 General requirements

    Ramps to buildings must be on private property,

    outside o the road right-o-way. Any heating

    systems must also be on private property and

    privately maintained.

    Changes in levels shall be limited, as slopes

    require greater physical exertion and skill rom

    people with disabilities. I ramps are too steep

    or too long, they become obstacles. Slopes

    between 1:25 (our per cent) to 1:20 (ve per

    cent) are recommended.

    The minimum clear width o a ramp shall be

    950 mm between handrails.

    Where passing o wheelchairs is likely to occurrequently, the options are:

    (a) To widen the ramp to 1,800 mm.

    (b) To widen the rest areas to 1,800 mm.

    Figure 44. Proper ramp design.

    Ramps shall have level landings at the top and

    bottom o each run and where they change

    direction. The landings shall be at least as

    wide as the widest ramp run leading to themand have a length not less than 1,500 mm.

    The 1,500 mm accommodates the length o a

    wheelchair as it negotiates a corner.

  • 8/2/2019 Access Design Standards

    34/90

    3 2 A c c e s s D e s i g n S t a n d a r d s T h e C i t y o C a l g a r y

    Figure 45. Ramp design.

    Visual and textural cues at the top and bottom

    o the ramp shall be provided or people

    with vision loss. Non-glare and slip-resistant

    materials shall be used on the ramp surace.

    The maximum cross slope o ramp suraces shall

    be 1:50 (two per cent).

    I a ramp needs to be longer than 18 m, a

    mechanical means o travel shall be considered.

    G.3.2 Exterior ramps

    Exterior ramps shall be protected rom rain,

    snow and ice, or maintained ree o snow and

    ice through regular maintenance or appropriate

    subsurace heating and drainage systems.

  • 8/2/2019 Access Design Standards

    35/90

    3 3A c c e s s D e s i g n S t a n d a r d s T h e C i t y o C a l g a r y

    H. Stairs

    H.1 Principle/rationale

    Some ambulatory people with balance

    problems or vision loss nd stairs easier to use

    than ramps. It is important the rise and run be

    designed so the stairs are not overly strenuous

    or create a hazard. Increased illumination,

    colour contrast, uniormly patterned materials,

    signage and other warning indicators can be

    used to enhance saety.

    Figure 46. Stairs are occasionally preerred to ramps bypeople with disabilities.

    H.2 Existing regulations

    Alberta Building Code 2006 3.3.1.7.

    4) In a barrier-ree path o travel, a downward

    change in elevation shall be signaled by the use

    o a 600 mm wide tactile warning strip placed

    250 mm rom the edge and or the ull widtho a stair, escalator, moving walkway, ramp

    or platorm and identifed using colour and

    brightness contrast.

    Figure 47. Cane detectable warning indicators or stairs.

    Alberta Building Code 2006 3.4.6.1.

    1) The suraces o ramps, and landings and

    treads a) shall have a fnish that is slip resistant,

    and b) i accessible to the public, shall have

    either a colour contrast or a distinctive pattern

    to demarcate the leading edge o the tread and

    the leading edge o the landing, as well as the

    beginning and end o a ramp.

    2) Treads and landings o exterior exit stairs

    more than 10 m high shall be designed to be

    ree o ice and snow accumulations.

    Alberta Building Code 2006 3.4.6.2

    1) Except as permitted by Sentence 3.3.2.13.(1),

    every ight o interior stairs shall have not less

    than 3 risers.

  • 8/2/2019 Access Design Standards

    36/90

    3 4 A c c e s s D e s i g n S t a n d a r d s T h e C i t y o C a l g a r y

    Alberta Building Code 2006 3.3.2.14.

    1) In a Group A, Division 2 occupancy used

    or the serving o ood and beverages, aninterior ight o stairs with ewer than 3 risers is

    permitted provided it

    a) is not less than 900 mm wide,

    b) is illuminated at all times that occupants are

    on the premises, and

    c) has a handrail on each side.

    Alberta Building Code 2006 3.4.6.3.

    2) The length and width o landings shall be at

    least the width o stairways in which they occur,

    except that in a straight run the length o a

    landing need not be more than 1,100 mm.

    3) Where a doorway or stairway empties onto a

    ramp through a side wall, there shall be a level

    area extending across the ull width o the ramp,and or a distance o 300 mm on either side o

    the wall opening, excepting one side when it

    abuts on an end wall.

    4) Where a door or stairway empties onto a

    ramp through an end wall, there shall be a level

    area extending across the ull width o the ramp

    and along its length or not less than 900 mm.

    Alberta Building Code 2006 3.4.6.7.

    3) Treads and risers in every exit stair, except a

    fre escape stair, shall have uniorm run and rise

    in any one ight, and shall not alter signifcantly

    in run and rise in successive ights in any stair

    system. (See Appendix A.)

    4) The leading edge o a stair tread shall have

    either a radius or a bevel between 6 mm and

    10 mm in horizontal dimension.

    5) The ront edge o stair treads in exits and

    public access to exits shall be at right angles to

    the direction o exit travel.

    Figure 48. Proper dimensions or stairs.

    H.3 Proposed standards

    H.3.1 General requirements

    A fight o stairs shall have uniorm dimensions

    and no open risers.

    Nosings shall not have projecting undersides,

    and shall be beveled i extending more than

    25 mm, to prevent catching a toe. Nosings shall

    be beveled not more than 60 with respect to

    the tread surace. This ensures the tread edge is

    more clearly visible in descent.

    Nosings on interior/exterior stairs shall be a

    contrasting colour to aid people with vision loss.

  • 8/2/2019 Access Design Standards

    37/90

    3 5A c c e s s D e s i g n S t a n d a r d s T h e C i t y o C a l g a r y

    Isolated steps shall be avoided, since

    they are oten dicult or people with

    vision loss to detect and act as a barrier to

    people in wheelchairs.

    Illumination shall be positioned to minimize

    glare and shadow.

    A barrier shall be used to prevent access to

    areas under a cantilevered or overhung staircase.

    Figure 49. Avoid overhanging stairs.

    H.3.2 Interior stairs

    Heavily patterned carpets or tiles shall not be

    used on stairs as they create gure-ground

    conusion and obscure the denition o the

    tread nosing.

    H.3.3 Exterior stairs

    Stairs shall be protected rom climatic variations

    or maintained ree o snow and ice. Stairs shall

    not be shaded by vegetation or other elements

    that prevent snow and ice rom melting.

  • 8/2/2019 Access Design Standards

    38/90

    3 6 A c c e s s D e s i g n S t a n d a r d s T h e C i t y o C a l g a r y

    J. Handrails and guards

    J.1 Principle/rationale

    Handrails are important eatures in barrier-ree

    access. They shall be easy to grasp and provide

    a rm and comortable grip. People with

    vision loss use handrails as guides; those with

    mobility impairments use them or leverage to

    get up ramps and the semi-ambulatory rely on

    handrails or balance. It is important handrails

    be placed at a sae and convenient height or

    everyone. Enhance ease o use by incorporating

    colour contrast and uniormity.

    Figure 50. Proper handrails used or guidance.

    J.2 Existing regulations

    Alberta Building Code 2006 3.4.6.4.

    1) A stairway shall have a handrail on at leastone side, but i it is 1,100 mm or more wide, it

    shall have handrails on both sides.

    2) I the required width o a ramp or ight

    o stairs is more than 2,200 mm, one or

    more intermediate handrails continuous

    between landings shall be provided, andlocated so that there will be not more than

    1,650 mm between handrails.

    3) Handrails shall be continuously graspable

    along their entire length and shall have

    a) a circular cross-section with an outside

    diameter not less than 30 mm and not more

    than 43 mm, orb) a non-circular cross-section with a graspable

    portion that has a perimeter not less than 100

    mm and not more than 125 mm and whose

    largest cross-sectional dimension is not more

    than 45 mm.

    4) Handrails on stairs and ramps shall be not

    less than 865 mm and not more than 965 mm

    high, measured vertically rom a line drawn

    through the outside edges o the stair nosing

    or rom the surace o the ramp, except that

    handrails not meeting these requirements are

    permitted provided they are installed in addition

    to the required handrail.

    5) Except where interrupted by doorways or

    newels at changes in direction, at least one

    handrail shall be continuous throughout the

    length o a stairway or ramp, including landings.

    (See Appendix A.)

  • 8/2/2019 Access Design Standards

    39/90

    3 7A c c e s s D e s i g n S t a n d a r d s T h e C i t y o C a l g a r y

    6) Handrails shall be terminated in a manner

    that will not obstruct pedestrian travel or create

    a hazard. (See A-3.4.6.4.(5) in Appendix A.)

    7) At least one handrail at the side o a

    stairway or ramp shall extend horizontally

    not less than 300 mm beyond the top

    and bottom o the stairway or ramp.

    (See A-3.4.6.4.(5) in Appendix A.)

    8) The clearance between a handrail and any

    surace behind it shall be not less than

    a) 50 mm, or

    b) 60 mm i the surace behind the handrail is

    rough or abrasive.

    9) Handrails and their supports shall be

    designed and constructed to withstand

    the loading values obtained rom the non-

    concurrent application o

    a) a concentrated load not less than 0.9 kN

    applied at any point and in any direction or all

    handrails, and

    b) a uniorm load not less than 0.7 kN/m

    applied in any direction to handrails not located

    within dwelling units.

    10) A ramp shall have handrails on both sides.

    J.3 Proposed standards

    In all cases, handrails shall be located on both

    sides o a ramp or stairway.

    The outside diameter or width o a handrail

    shall be 30 mm to 43 mm, to allow those with

    limited hand unction to grasp it rmly. In

    addition, the smaller dimension enables people

    wearing gloves in winter to grasp the handrail

    rmly, with ease. A gap o at least 50 mm shall

    distance the handrail rom the wall.

    In stairwells, especially exits, tactile cues(e.g., several notches or a rough texture) shall

    be placed on the inside or the last 300 mm

    on both ends o the handrail as a signal to

    inorm persons with vision loss that they are

    approaching the last step. A consistent system

    o tactile indicators shall be located on or near

    the handrail at the top and bottom o stairs and

    ramps to indicate ascent and descent.

    All handrails shall contrast rom their

    surroundings through colour or brightness.

    Figure 51. Proper and improper handrail shapeand dimensions.

  • 8/2/2019 Access Design Standards

    40/90

    3 8 A c c e s s D e s i g n S t a n d a r d s T h e C i t y o C a l g a r y

    K. Elevators

    K.1 Principle/rationale

    An elevator is vital to a non-ambulatory person,

    because it oten provides the only orm o

    access to dierent levels o a building. A poorly

    designed elevator can be as much o a barrier

    as stairs. An elevator car must be large enough

    to accommodate people with disabilities.

    Signage and controls in the elevator lobby and

    in the car itsel have a proound impact on the

    accessibility o an elevator. Visual and audio

    indicators are also critical to those with vision

    and hearing loss.

    Figure 52. Well-designed elevator.

    K.2 Existing regulations

    Alberta Building Code 2006 3.8.3.5

    K.3 Proposed standards

    K.3.1 General requirements

    All passenger elevators shall be accessible topeople with disabilities.

    The size o an elevator car must conorm to the

    Alberta Building Code 2006 requirements. A

    code-compliant elevator is large enough in the

    length dimension, but is too small in the width

    dimension to accommodate the turning around

    o a wheelchair.

    Figure 53. An elevator car with dimensions allowing theturning around o a wheelchair.

  • 8/2/2019 Access Design Standards

    41/90

    3 9A c c e s s D e s i g n S t a n d a r d s T h e C i t y o C a l g a r y

    Verbal announcements identiying the foor

    level and the direction o travel shall be

    installed or people with vision loss and or

    those who cannot see the foor indicator at theback o a crowded elevator. Where practical,

    control buttons shall be installed on both sides

    o the elevator door inside the elevator.

    Figure 54. Proper elevator car dimensions.

    K.3.2 Elevator lobbies

    The minimum space in ront o elevator doors

    shall be 1,500 mm.

    Doors on elevators shall start to close ater eight

    seconds rom the ully open position.

    Call buttons shall be located on each wall

    between elevators and shall be easily

    identiable by colour contrast and raised

    symbols. The call buttons shall protrude toenable a user to push with any part o the hand.

    No obstructions shall be placed under elevator

    call buttons.

    Tactile signage in the orm o larger Arabic

    numerals and letters shall also be axed

    at a height o 1,200 mm above the foor on

    both sides o the door opening within theelevator lobby.

    Figure 55. Proper signage.

    Arrival o an elevator shall be indicated by a

    verbal announcement or a clear audible and

    visual signal located within the elevator lobby

    near the door o the arriving car.

  • 8/2/2019 Access Design Standards

    42/90

    4 0 A c c e s s D e s i g n S t a n d a r d s T h e C i t y o C a l g a r y

    Figure 56. Proper design o elevator lobbies.

    K.3.3 Floor registration buttons

    Floor registration buttons shall be raised, since

    fush or recessed buttons are dicult to activate

    by people with vision loss or with limited

    manual dexterity.

    Floor registration buttons within the car shall

    be clearly marked with tactile signage in the

    orm o raised Arabic numerals and letters and,

    i there is room, Braille signage shall be added.

    There shall be a colour contrast between the

    foor registration buttons and the background.

    Figure 57. Proper placement o controls.

    K.3.4 Exterior elevators

    Exterior elevators, i provided, shall be oriented

    away rom the prevailing winds to keep the

    car ree o snow, rain and debris. Waiting

    areas shall be sheltered, positively drained

    and well lit.

    Glass walls shall be installed to enhancesecurity by increasing visibility.

  • 8/2/2019 Access Design Standards

    43/90

    4 1A c c e s s D e s i g n S t a n d a r d s T h e C i t y o C a l g a r y

    L. Public washrooms

    L.1 Principle/rationale

    It is important that washrooms are available

    to serve the needs o people with disabilities.

    Every foor serviced by an elevator shall have

    an accessible washroom that is easily located

    and clearly marked. Accessible washrooms

    shall include hardware that is operable by

    all, appropriate xture type and location, and

    adequate dimensions. An accessible washroom

    shall be sae and, where possible, connected by

    a call system to support sta.

    L.2 Existing regulations

    Alberta Building Code 2006 3.8.2.3. and

    3.8.3.8. to 3.8.3.13.

    L.3 Proposed standards

    L.3.1 Washroom entrances

    The entrances to washrooms are oten dicult,

    i not impossible, or people with disabilitiesto use, especially when there are vestibules

    with two doors. Thereore, it is important to

    either eliminate the doors or provide only one

    entry door to a washroom. Washrooms that are

    designed so doors are not required to prevent

    viewing by passersby are considered ideal.

    Entrances with an L-conguration shall have

    a minimum depth o 1,200 mm to allow awheelchair to turn the corner easily. However,

    L-shaped entrances shall be as wide as possible.

    Figure 58. Proper design o a washroom entrance.

    L.3.2 Water closet stalls

    Water closet stall doors shall have a clear

    opening o 800 mm and swing out o thestall. Water closet stalls or enclosure doors

    shall be equipped with locking devices that

    do not require pinching o the ngers or

    twisting o the wrist to operate. The doors shall

    also be equipped with a hinge that slowly

    closes the door.

    Water closet stalls shall have a clear

    unobstructed space rom the water closetbowl to the door o at least 1,500 mm wide

    by 1,500 mm deep. This will allow or easy

    maneuverability o the wheelchair when in

    the stall. A clear turning radius o 2,250 mm is

    preerred (but not required) to accommodate

    people in power wheelchairs.

  • 8/2/2019 Access Design Standards

    44/90

    4 2 A c c e s s D e s i g n S t a n d a r d s T h e C i t y o C a l g a r y

    Figure 59: Proper dimensions o a water closet stall.

    L.3.3 Washroom fxtures

    In washrooms, dispensers and receptacles

    shall be mounted with their highest operable

    parts above the foor surace within the

    ollowing ranges:

    (a) Paper towel dispensers/hand dryers:

    1,100 mm to 1,200 mm.

    (b) Soap dispensers: 900 mm to 1,000 mm and

    within 500 mm orward grasp reach.

    (c) Toilet paper dispensers: 750 mm to 850 mm.

    (d) Toilet seat cover dispensers: 900 mm to1,000 mm.

    (e) Waste receptacles: 900 mm to 1,000 mm.

    () Grab bars as outlined in ABC 2006,

    3.8.3.8 (2).

    A coat hook shall be mounted on a solid wall.

    All washroom xtures shall be installed or

    saety and ease o use.

    A toilet paper dispenser shall be within reach. It

    shall be located so that its operable part is not

    less than 460 480 mm rom an adjacent wall

    to the centerline o a water closet.

    Figure 60. Proper location o xtures.

  • 8/2/2019 Access Design Standards

    45/90

    4 3A c c e s s D e s i g n S t a n d a r d s T h e C i t y o C a l g a r y

    An automatic or single-unction towel dispenser

    (requiring only one hand and only one movement

    to release the towel) is recommended.

    Figure 61. Properly placed grab bars.

    L.3.4 Lavatory knee space

    To maximize knee space below the lavatory,

    P traps in drain lines shall be oset

    horizontally so that a minimum o 280 mm is

    provided rom the ront o the counter to the

    ace o the P trap. The bottom o the counter

    shall be 735 mm to 800 mm rom the foor.

    Figure 62. Proper knee clearance beneath sink.

    L.3.5 Universal washrooms

    The requirements o Alberta Building Code

    2006, section 3.8.2.3(3) indicates a universal

    washroom is not required in the entrance story

    i a barrier ree path o travel is provided to a

    universal water closet elsewhere.

    However, it shall be made as easy as possible

    or people with vision loss or mobility

    impairments to locate and travel to a washroom.

    A universal male/emale washroom shall be

    located in all buildings not ar rom the main

    entrance on the main foor.

  • 8/2/2019 Access Design Standards

    46/90

    4 4 A c c e s s D e s i g n S t a n d a r d s T h e C i t y o C a l g a r y

    Figure 63. Proper dimensions o a water closet stall.

    Where buildings are staed with ull-time

    security, call buttons or pressable call strips

    shall be installed in all universal washrooms,

    in case a washroom user alls or encounterssome other circumstance that would require

    assistance. Where call buttons are installed,

    they shall be installed on the same wall as the

    side grab bar and, where pressable strips are

    installed, they shall be placed on the same

    walls as the grab bars.

    Universal washrooms are valuable to mothers

    with young children, and a counter shall beprovided with sucient space to change an

    inants diaper.

  • 8/2/2019 Access Design Standards

    47/90

    4 5A c c e s s D e s i g n S t a n d a r d s T h e C i t y o C a l g a r y

    M. Recreational and cultural centres

    M.1 Principle/rationale

    Facilities designed and constructed to meet

    accessibility standards enable people with

    disabilities to take an active part in community

    lie. Proper design o recreational and cultural

    acilities encourages healthy liestyles and

    educational development.

    Not all recreational areas need to be completely

    barrier-ree. A diversity o accessibility within

    a single recreational area enhances everyones

    opportunity to enjoy the outdoors, without

    segregation by disability.

    M.2 Existing regulations

    Alberta Building Code 2006 7.3.3.12.

    Alberta Building Code 2006 7.3.3.15.

    Alberta Building Code 2006 7.3.3.18.

    Alberta Building Code 2006 3.8.3.16. (1)

    Alberta building Code 2006 3.8.3.13

    M.3 Proposed standards

    M.3.1 Swimming pools

    Accessible swimming pools can be essential

    or people with disabilities, who may rely

    on aquatic activities as a orm o rehabilitation

    or exercise.

    There shall be a ramp and stairs with handrails

    on both sides located at the shallow end o

    the pool.

    Figure 64. Proper ramps are the best entrance intoswimming pools.

    Stairs, rather than ladders, shall be provided

    whenever possible, since stairs are more

    easily negotiated and can be used to sit upon

    i wide enough.

    Figure 65. Where ramps are not easible, stairs arepreerred to ladders.

  • 8/2/2019 Access Design Standards

    48/90

    4 6 A c c e s s D e s i g n S t a n d a r d s T h e C i t y o C a l g a r y

    Power hoists shall be provided to assist people

    in wheelchairs with exiting and entering the

    pool. Power hoists are benecial, since ramps

    can be dicult or some people with disabilitiesto use.

    Figure 66. Power hoist into swimming pool.

    Pool depths, along with shallow end and

    deep end, shall be indicated with signage that

    eatures contrasting colour and texture.

    M.3.2 Ice rinks and exercise areas

    Ice rinks shall be designed with the

    consideration o sports played by people with

    disabilities, such as sledge hockey, and or

    spectators who may also be disabled. Player

    benches and penalty boxes shall have Plexiglas

    in ront or viewing. The player benches must

    have two doors 910 mm wide to allow or easy

    egress and access.14

    Figure 67. Proper dimensions and materials or anice rink.

    Seating and handrails shall be available near

    the entrance/exit o an ice rink. Level access

    shall be provided to ice rinks and exercise areas.

    Exercise areas shall include handrails and/

    or wheelchair clearance to some equipment

    to acilitate transer to and rom exercise

    equipment. Raised tactile signage shall beincluded to help identiy dierent types o

    equipment or people with vision loss. Raised

    exercise platorms shall be available as an

    alternative to stretching on the foor or people

    in wheelchairs or the elderly.

  • 8/2/2019 Access Design Standards

    49/90

    4 7A c c e s s D e s i g n S t a n d a r d s T h e C i t y o C a l g a r y

    Figure 68. Raised exercise platorm.

    M.3.3 Exhibits

    Exhibition areas shall also be barrier-ree, or

    an alternative method o interpreting the

    message shall be provided, such as audio-visual

    presentations, large print text or tactile signage.

    Important artiacts, labels and graphics shall

    be placed at an elevation that makes viewing

    comortable or all visitors. Table displays

    shall be located between 1,000 mm to 1,200

    mm above the ground level. Wall-mounted

    displays shall be located between 1,200 mm

    to 1,500 mm above the ground level. Labels on

    horizontal suraces shall be tilted to allow or

    better viewing.

    Figure 69. Proper placement o displays.

    Lighting xtures shall be designed and placed

    to minimize glare and refection.

    M.3.4 Drinking ountains

    Drinking ountains shall extend within a

    maximum distance o 200 mm above the foor,

    with ront panel sloping 50 mm to 90 mm

    inwards. This will allow a close side approach

    or wheelchairs, and will not be hazardous or

    people with vision loss when using a cane.

    Figure 70. Drinking ountain suitable or peoplewith disabilities.

  • 8/2/2019 Access Design Standards

    50/90

    4 8 A c c e s s D e s i g n S t a n d a r d s T h e C i t y o C a l g a r y

    The height o the waterspout shall be between

    780 mm to 915 mm. The operation control shall

    be a push button or a lever-type control.

    Figure 71. Universally designed drinking ountain orpeople who are standing and people who arein wheelchairs.

    M.3.5 Shower fxtures

    A diverter mechanism on the hand-held shower

    shall be provided to protect people with

    disabilities against misdirection o spray.

    A shel or storing soap, sponges and brushes

    shall be provided at 850 mm above foor level.

    Figure 72. Water temperature control.

    M.3.6 Common showers

    Common showers shall have beveled

    thresholds no more than 13 mm in

    height allowing wheelchairs to pass

    over with minimal hindrance.

    A shower wheelchair shall be provided

    or use in the shower room.

    A fexible hand-held shower sprayer shall

    be provided.

    The slope o shower room foor to drain shall

    be 1:20 (ve per cent).

  • 8/2/2019 Access Design Standards

    51/90

    4 9A c c e s s D e s i g n S t a n d a r d s T h e C i t y o C a l g a r y

    Figure 73. Proper shower dimensions.

    M.3.7 Individual change/shower rooms

    Similar to individual washrooms, provision oindividual change/shower rooms or people

    with disabilities allows amily members or

    caregivers o the opposite gender to provide

    assistance without inconveniencing themselves

    or other patrons.

    Individual change rooms shall include an

    elevated changing platorm 1,500 mm wide

    x 1,800 mm long x 480 mm high. The changerooms are to include a 1,500 mm turning radius,

    grab bars, coat hooks and shelving at a height

    o 1,000 mm above the nished foor. A clear

    turning radius o 2,250 mm is preerred

    (but not required) to accommodate people

    in power wheelchairs.

    Figure 74. Proper dimensions or change roomsand showers.

  • 8/2/2019 Access Design Standards

    52/90

    5 0 A c c e s s D e s i g n S t a n d a r d s T h e C i t y o C a l g a r y

    N. Public acilities

    N.1 Principle/rationale

    People with disabilities must attend to day-

    to-day business, such as banking, community

    meetings and registering or recreational or

    educational programs. The excessive height

    o countertops can make these tasks dicult.

    Thereore, an area or people in wheelchairs

    to conduct their business with privacy at a

    convenient height and with adequate knee

    space shall be provided.

    People with disabilities, like most people, enjoy

    going to plays, movies and sporting events.

    However, this is oten impossible because o the

    lack o available seating.

    N.2 Existing regulations

    Alberta Building Code 2006 3.8.2.1.

    Alberta Building Code 2006 3.8.3.6.

    N.3 Proposed standards

    N.3.1 Counters

    CAN/CSA-B651-04 recommends the same

    counter dimensions as the Alberta Building

    Code 2006, but also includes a minimum

    clear foor space o not less than 750 mm x

    1,200 mm in ront o a counter or work surace.

    However, the recommended and preerred

    knee space beneath universal counters intended

    to be used as work suraces shall be 720 mm

    to 800 mm high.

    Figure 75. Dimension requirements or counters.

    Counters shall be cane detectable and

    colour/brightness contrasted rom their

    surroundings and suraces shall have a

    non-glare, matte nish.

    To prevent confict between wheelchair

    access and cane detection, a border with

    contrasting colour and brightness and a

    tactile warning surace shall be laid into

    the foor near the counter. This can be used

    as an indicator or people with vision loss

    approaching a service counter.

    Where a glass partition separates customers

    rom the service personnel, there shall

    be an adequate speaker system to

    acilitate communication.

  • 8/2/2019 Access Design Standards

    53/90

    5 1A c c e s s D e s i g n S t a n d a r d s T h e C i t y o C a l g a r y

    Figure 76. Caeteria counter.

    N.3.2 Caeterias

    The height o counters or conveying trays shall

    be a maximum o 865 mm high.

    The maximum distance to any liquid dispensershall be within reach limitations o wheelchair

    users unless employees are behind the caeteria

    line at all times.

    Food shall be located a maximum o 450 mm

    rom the edge o the counter.

    Figure 77. Proper dimensions or caeteria counters.

    N.3.3 Assembly seating in public acilities

    Designated wheelchair spaces shall be

    spread over dierent areas in a seating

    space, to avoid secluding people using

    wheelchairs to one location.

    Figure 78. Accessible seating shall be distributedthroughout the seating area.

  • 8/2/2019 Access Design Standards

    54/90

    5 2 A c c e s s D e s i g n S t a n d a r d s T h e C i t y o C a l g a r y

    Spaces provided or persons in wheelchairs

    shall provide sightlines equal to those provided

    or the majority o the audience.

    It is recommended that the number o spaces

    required or people using wheelchairs in

    Alberta Building Code 2006, Table 3.8.2.1,

    be increased by at least two per number o

    xed seats to accommodate an increase in the

    population o people using wheelchairs, which

    is anticipated in the uture.

    Preerred designated wheelchair spaces

    Number o fxed seats inseating area

    Number o spacesrequired orwheelchairs

    2 100 4

    101 200 5

    201 300 6

    301 400 7

    401 500 8

    501 900 9

    901 1,300 10

    1,301 1,700 11

    Each increment o up to 400seats in excess o 1,700

    Two additional spaces

    Table 1. Required accessible seating.

    Spaces or persons in wheelchairs shall be level,

    and the path o travel to them shall meet the

    requirements o Section B o these Standards.

    Removable chairs can be installed in public

    acilities to accommodate people using

    wheelchairs, without loss o revenue to

    the owner. I there is no need or thesewheelchair spaces, the seats can be replaced

    or general use.

    Figure 79. Standard seats can be made removable to

    accommodate accessible seating.

    Seats shall be provided or persons with

    orthotics or prostheses. The space or accessible

    seating shall be wide enough to allow people

    to maneuver rom the side, ront or behind with

    their mobility devices.

    Meeting rooms shall be designed so all

    members o the audience have clear sightlines

    to the speaker. Further, the design must limit

    placement o speakers in ront o a window15.

  • 8/2/2019 Access Design Standards

    55/90

    5 3A c c e s s D e s i g n S t a n d a r d s T h e C i t y o C a l g a r y

    N.3.4 Permanent barriers

    I posts are installed as a crowd control measure,

    at least one post shall be removable and shall

    be identied with the international symbol o

    accessibility. I not, an alternative passageway,

    such as a gate similarly marked, shall be

    available or access.

    Bollards shall be placed to minimize

    obstruction to pedestrian fow. The minimum

    clearance between bollards shall be 1,200 mm.

    The minimum height shall be 600 mm, and

    they shall colour contrast rom the surrounding

    paving to be more visible.

    Chains, cables or ropes are not recommended

    as permanent or temporary barriers unless they

    are easily visible. They shall be placed at a

    height o no more than 250 mm and no lower

    than 150 mm, so they are detectable by visually

    impaired people.

    Figure 80. Required dimensions or permanent barriers.

  • 8/2/2019 Access Design Standards

    56/90

    5 4 A c c e s s D e s i g n S t a n d a r d s T h e C i t y o C a l g a r y

    P. Parks, pathways and playgrounds

    P.1 Principle/rationale

    Parks and playgrounds that are accessible

    provide an opportunity or people with

    disabilities to have access to the outdoors and

    to take an active part in community lie. All

    pathways in parks shall be accessible and shall

    be designed to be sae and protected rom the

    elements. Playground equipment and outdoor

    urniture shall not become barriers or people

    with disabilities.

    P.2 Existing regulationsAlberta Building Code 2006 3.8.3.2.

    P.3 Proposed Stand