access design standards
TRANSCRIPT
-
8/2/2019 Access Design Standards
1/90
calgary.ca | call 3-1-1
AccessDesignStandards
Advisory Committeeon AccessibilityMobility, Vision, Cognitive, Hearing
-
8/2/2019 Access Design Standards
2/90
A c c e s s D e s i g n S t a n d a r d s T h e C i t y o C a l g a r y
September 2009
The 2010 edition o The City o Calgary Access Design Standards is largely based on the 2002
edition. However, we wish to grateully acknowledge the ollowing groups and individuals or theirassistance with developing new and revised content or 2010.
The City o Calgary committees
Advisory Committee on Accessibility
Access Design Sub-Committee
The City o Calgary business units/divisions
Calgary Housing Company
Calgary Transit
Community & Neighbourhood Services
Corporate Properties & Buildings
Development & Building Approvals
Land Servicing & Housing
Land Use Planning & Policy
Recreation
Roads
Transportation InrastructureTransportation Planning
Private industry/not-or proft contributors/individuals
Accessible Housing Society
Mark Iantkow
Editorial team
Sarah Alexander
Anna CiarlaUlrik Seward
Janel Smith
Acknowledgements
-
8/2/2019 Access Design Standards
3/90
1A c c e s s D e s i g n S t a n d a r d s T h e C i t y o C a l g a r y
Table o Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Access design standards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3A. Exterior barrier-ree path o travel . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
B. Interior barrier-ree path o travel . . . . . . . . . . . . . . . . . . . . . . . . . . 12
C. Vehicular access. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
D. Illumination and acoustics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
E. Location o controls, dispensers and receptacles . . . . . . . . . . . . . . . 24
F. Building entrances, doors and doorways . . . . . . . . . . . . . . . . . . . . . 26
G. Ramps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
H. Stairs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
J. Handrails and guards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
K. Elevators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
L. Public washrooms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
M. Recreational and cultural centres . . . . . . . . . . . . . . . . . . . . . . . . . 45
N. Public acilities . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
P. Parks, pathways and playgrounds . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Q. Patios . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
R. Emergency egress, alarms and warning suraces . . . . . . . . . . . . . . . 59
S. Communications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
T. Plus-15 System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
U. Public transit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
V. Pedestrian crossings and trac signals . . . . . . . . . . . . . . . . . . . . . . 74W. Crime Prevention through Environmental Design (CPTED) . . . . . . 76
X. Universal Dwelling Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
Figure list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
Endnotes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
Table o Contents
-
8/2/2019 Access Design Standards
4/90
2 A c c e s s D e s i g n S t a n d a r d s T h e C i t y o C a l g a r y
Today, people with disabilities are in the
mainstream o society, where opportunities are
the same or everyone and is enriched by the
diversity o its active and contributing members.
It is important that people o all abilities be
positively supported by their surroundings.
A well-designed environment is sae,
convenient, comortable, age-riendly1
and readily accessible to everyone. Design
solutions that also respond to the climate
variations in a winter city, like Calgary, increase
and enhance the accessibility to the outdoors
throughout the year.
The City o Calgary wishes to set an example
by creating a more livable and accessible
city. To this end, it established the Advisory
Committee on Accessibility (ACA) and
published these Standards.
The Advisory Committee on Accessibility
was established by City Council to improve
access to buildings and other services. The
committee consists o members with disabilities,
representatives rom the community, and City o
Calgary business units. The terms o reerence o
the ACA are:
To review and make recommendations
to City Council through the Standing
Policy Committee on Community and
Protective Services on policy issues, the
accessibility o municipal properties,
inormation and services or people
with disabilities, and to be a resource to
City Council and City Administration in
addressing accessibility issues.
Introduction
-
8/2/2019 Access Design Standards
5/90
3A c c e s s D e s i g n S t a n d a r d s T h e C i t y o C a l g a r y
These Standards represent The City o Calgarys
approach to a universal built environment.
They are intended to complement the Alberta
Building Code. In some cases, these Standardsare intended to enhance accessibility
by requiring measures that exceed the
requirements o the Alberta Building Code 2006.
The contents o these Standards are required to
be integrated into the design and construction
o all new City o Calgary owned/operated
buildings and acilities. The Standards do not
require retrotting o existing buildings. Theyare not intended to be a set o requirements
or projects that are not owned or operated by
The City. However, design proessionals, the
building industry, government departments
and the community as a whole are
encouraged to implement these Standards
in all projects constructed within the city.
Generally, these Standards apply within
the property boundaries o City owned/
operated buildings and acilities. For
construction pertaining to regional pathways,
road right-o-ways and city parks, the
appropriate City department shall be
consulted, in addition to these Standards.
This document is designed both as a
working tool to provide a common point
o reerence and as a means to increasethe awareness o the needs o people
with disabilities, including the elderly.
Formulation o these Standards has been based
primarily on:
1. Experience and knowledge o people with
disabilities rom the community.2. Expertise acquired by The City o Calgary
business units through planning and review
o major projects.
3. Documentation o standards by other
authorities, provinces and countries.
4. Alberta Building Code 2006.
Questions regarding the content o these
standards can be directed to:
Advisory Committee on Accessibility
Administrative Contact
Telephone: 3-1-1
TTY: 403-268-1379
Email: [email protected]
These Standards are comprised o 22 Sections.
Each Section is divided into sub-sections,
as ollows:
1. Principle/rationale:
A statement o the principle/rationale behind
making a particular area accessible.
2. Existing regulations:
Articles o the Alberta Building Code (ABC)
2006 and other recognized standards, relating
to each specic area o concern.
3. Proposed standards:Proposals to improve access and justication or
those proposals. In some cases, the deciencies
o existing regulations are highlighted.
In some sections, graphic illustrations are
provided as supporting inormation. Please be
advised, all measurements in illustrations are in
millimetres, unless otherwise specied.
Access design standards
-
8/2/2019 Access Design Standards
6/90
4 A c c e s s D e s i g n S t a n d a r d s T h e C i t y o C a l g a r y
A.1 Principle/rationale
Everyone wants to be able to move throughout
a city saely, conveniently and independently.
Exterior barrier-ree paths o travel, which
include pathways and sidewalks, can make
movement dicult i not impossible i obstacles
or hazards obstruct the path o travel. These
obstacles and hazards can be weather induced,
as in the case o snow drits. The placement o
exterior items must not obstruct the pathway or
people with visual or mobility impairments.
Consistent tactile suraces within barrier-ree
paths o travel prevent conusion and promote
understanding through textured surace
indicators. When care is taken in the design o
the tactile quality o suraces, those suraces
can support inormation regarding orientation,
direction and location.
The City o Calgary Roads, Transportation
Planning, and Land Use Planning & Policy shall
be consulted or all matters concerning public
sidewalks and roads.
Figure 1. Cane detectable tactile suraces.
A.2 Existing regulations
Alberta Building Code 2006 3.8.3.2.
A.3 Proposed standards
This section applies to exterior pathways and
sidewalks on the property o City owned andoperated buildings.
A.3.1 Suraces and textures
Since ground and foor suraces are an
important aspect o access, they shall be
designed to acilitate sae and easy movement.
The reeze/thaw cycle and positive drainage
are an important consideration when designing
ground suraces.
A. Exterior barrier-ree path o travel
-
8/2/2019 Access Design Standards
7/90
5A c c e s s D e s i g n S t a n d a r d s T h e C i t y o C a l g a r y
Throughout these Standards, Five Basic
Principles or Sae and Eective Environmental
Design or People with Visual Disabilities
have been considered. These ve principleswere developed by Mark Iantkow in 2003
and are best remembered by using the
acronym CoLATE.
Co Colour and contrast
L Lighting
A Audible cues
T Tactile cues
E Ergonomics
The principle considered in this sub-section and
other sections in these Standards is T Tactile
Cues, described by Iantkow as ollows:
Tactile queues (and cues) are a parallel
consideration to audible queuing. One might
align onesel according to the direction o
a wall, curb or planter i there is someindication that such a tactile entity is used in a
consistent way within a structure. Tactile cues
may also be used at decision making points or
waynding (dierent textures on foor suraces;
or textures on walls; or signs in relie placed
consistently next to doorways; or even railings
with dierent textures when approaching
changes in elevation).2
Outdoor ground suraces made o brick or stone
shall be laid on a rm base, level with adjacent
suraces and embedded in concrete.
The City o Calgary is currently researching
the easibility o developing a system o tactile
tiles, provisionally known as Urban Braille, or
use in the citys public sidewalks. These tiles
assist people with vision loss in negotiating
public sidewalks.
Directional tiles are normally thin, linearly
aligned tiles that contrast with the rest othe sidewalk, helping to direct pedestrian
trac. Node tiles along the sidewalk act as
an indicator or deciding to cross a road
or change direction. Intersection curb tiles
indicate curb ramps. Crosswalk directional tiles
are used on crosswalks to direct people saely
across the road.
Please contact the Advisory Committeeon Accessibility (ACA) or updates on the
development o these tactile systems. These
tiles are not to be applied without prior
approval, since consistency and standardization
are necessary or the success o the entire
system. The City intends to develop these
standards urther, and such inormation may be
incorporated into uture editions o the Access
Design Standards.
-
8/2/2019 Access Design Standards
8/90
6 A c c e s s D e s i g n S t a n d a r d s T h e C i t y o C a l g a r y
Figure 2. Crosswalk direction tile3. Figure 3. Node tile4.
Figure 4. Directional tile5. Figure 5. Intersection curb tile.
-
8/2/2019 Access Design Standards
9/90
7A c c e s s D e s i g n S t a n d a r d s T h e C i t y o C a l g a r y
A.3.2 General requirements
The placement o lampposts, transormers,
mailboxes, newspaper boxes, trash containers
and bus shelters, can obstruct the barrier-ree
path o travel. They should be placed outside
the minimum required width o the sidewalk
or pathway.
The minimum width o a sidewalk shall be
1,500 mm (the Transportation Association o
Canada recommends 2,400 mm).
Joints in sidewalks or between bricks or stonesshall not exceed 13 mm in width.
Figure 6. Sidewalk joint.
Sidewalks shall be designed to drain water toprevent puddles and ice build-up.
Rest areas shall be located on one side
o walkways every 30 m. Rest areas shall
have minimum dimensions o 2,400 mm
x 2,400 mm. I benches are included in the
rest areas, they shall conorm with Section P
o these Standards.
Figure 7. Obstructions located out o the direct patho travel.
A.3.3 Obstructions
The Alberta Building Code requires a
horizontally projecting obstruction to extend
within 680 mm above the foor or ground
surace. People with vision loss nd this height
to be above cane detection level. Thereore,
a lower maximum o 200 mm is required toreduce the risk o collision with the obstruction.
Figure 8. Specication or protruding objects toavoid collision.
-
8/2/2019 Access Design Standards
10/90
8 A c c e s s D e s i g n S t a n d a r d s T h e C i t y o C a l g a r y
Gratings, manhole covers, electrical vaults and
other access covers shall be placed adjacent
to walkways, out o the path o travel, unless
prevented by site constraints. I placementwithin the path o travel is unavoidable, the
gratings shall have a maximum clear opening o
13 mm. Due to ventilation requirements,
the gratings on electrical vaults may be
larger (openings no larger than 20 mm wide
x 90 mm long to meet transormer ventilation
requirements, as specied by Enmax).
The long dimension o the openings shalllie perpendicular to the path o travel, and i
small solid plates (like ootprints) are placed in
the direction o pedestrian trac and spaced
to accommodate an average stride, a person
wearing high heels can cross gratings saely.
Guy-wires near walkways shall be clearly
marked to at least 1,980 mm above the ground
and have a physical barrier beneath or be
placed out o the path o travel.
Temporary signs, parked vehicles, or vegetation
shall not block a path o travel.
Figure 11. Clearance between overhanging objects andthe ground.
Figure 9. Requirements or openings in theground surace.
Figure 10. Placement o gratings.
-
8/2/2019 Access Design Standards
11/90
9A c c e s s D e s i g n S t a n d a r d s T h e C i t y o C a l g a r y
Figure 12. Proper placement o obstructions.
A.3.4 Curb ramps
In Calgary, new sidewalks are constructed with
curb ramps. Curb ramps are also constructed
when curb and gutter work is undertaken in
existing sidewalks or when they are replaced.
In designing curb ramps, care shall be taken
to prevent them rom becoming hazardous
to people with vision loss, who may not
notice them and walk inadvertently into the
intersection. Curb ramps located right on
the corner shall be avoided, because they
orce people with vision loss, people using
wheelchairs and people pushing strollers
into the intersection, rather than the sae area
o the crosswalk.
At times, curb radii and trac saety concerns
preclude the alignment o the curb ramp
perpendicular to trac. In such cases,
the curb ramps shall discharge into thepainted crosswalk, as close as possible to a
perpendicular alignment with trac fow.
Figure 13. Proper placement o curb ramps.
A level surace shall be maintained on the
sidewalk behind the curb ramps or smooth
pedestrian and wheelchair travel.
The minimum width o curb ramps, exclusive o
fared sides, shall be 1,500 mm.
-
8/2/2019 Access Design Standards
12/90
1 0 A c c e s s D e s i g n S t a n d a r d s T h e C i t y o C a l g a r y
The slope o a curb ramp shall not exceed 1:12
(eight per cent), and shall be not less than 1:15
(six per cent) unless sidewalk constraints do not
allow these ratios.
Figure 14. Plan view o City standard curb ramp6.
Figure 15. Section and elevation o curb ramp7.
The edges shall be curved rather than cut
sharply, so all the wheels o a wheelchair can
maintain contact with the ground at all times.
Suraces o curb ramps shall be slip resistant.
Curb ramps shall contrast in texture rom the
surrounding sidewalk and the road, so they can
be identied by the visually impaired. A raised
texture is more perceptible.
Drainage shall be designed to prevent water
and snow accumulation at the bottom o curb
ramps. However, catch basins shall not be
located in ront o the curb ramps.
Where the widths o sidewalks provide
adequate space, curb ramps shall be oset rom
the main fow o pedestrian trac and still bewithin the crosswalk area. The corner curb shall
be maintained as a clearly dened edge and be
cane detectable.
Figure 16. Proper layout o intersections.
-
8/2/2019 Access Design Standards
13/90
1 1A c c e s s D e s i g n S t a n d a r d s T h e C i t y o C a l g a r y
Medians in crossings shall have curb
ramps at both sides and a level area no
less than 1,500 mm long. Where a median
island is less than 3.6 m wide, the tworamps and the fat area between shall
all be reduced by an equal amount.
A.3.5 Snow removal
Temporary hazards are oten overlooked. For
example, snow removal oten results in snow
banks along sidewalks, which block access.
Snow removal vehicles oten clear the street,but they must also ensure curbs are not blocked
with snow banks, as it makes it dicult, i not
impossible, to cross the street.
Wind buers, such as ences, hedges and trees,
shall be set back rom the sidewalk so the walk
will be protected rom winds and snow will be
deposited next to the walk, rather than coveringthe path.
Figure 17. Wind buers.
-
8/2/2019 Access Design Standards
14/90
1 2 A c c e s s D e s i g n S t a n d a r d s T h e C i t y o C a l g a r y
B. Interior barrier-ree path o travel
B.1 Principle/rationale
Navigation through interior corridors and
passageways shall be simple and sae.
Passageway widths can create barriers, i
the needs o people with disabilities are not
considered. Strategic placement o objects in a
passageway can reduce collisions and acilitate
cane detection. Surace materials are also an
important consideration or people with vision
loss and the elderly, as they can reduce injury
and disorientation.
B.2 Existing regulations
Alberta Building Code 2006 3.3.1.9.
1) The minimum width o a public corridor shall
be 1,100 mm.
2) Except as required by Sentence 3.3.3.3.(2),
the minimum unobstructed width o a corridor
used by the public or a corridor serving
classrooms or patients sleeping rooms shall be
1,100 mm.
3) Except as permitted by Sentence (4),
obstructions located within 1,980 mm o the
oor shall not project more than 100 mm
horizontally into an exit passageway, a public
corridor, a corridor used by the public or a
corridor serving classrooms or patients sleeping
rooms in a manner that would create a hazard
or a person with a visual disability traveling
adjacent to the walls.
4) The horizontal projection o an obstruction
reerred to in Sentence (3) is permitted to be
more than 100 mm provided the clearance
between the obstruction and the oor is lessthan 680 mm.
Figure 18. Proper height requirements or
protruding objects.
Alberta Building Code 2006 A-3.3.1.9.
4) The sweep o a cane used by blind or
visually impaired persons normally detects
obstructions that are within 680 mm o the oor.
Any obstructions above this height would not
normally be detected and can, thereore, create
a hazard i it projects more than 100 mm intothe path o travel.
-
8/2/2019 Access Design Standards
15/90
1 3A c c e s s D e s i g n S t a n d a r d s T h e C i t y o C a l g a r y
Figure 19. Interior passageway.
B.3 Proposed standards
B.3.1 General requirements
The ideal width o an interior corridor is 1,525
mm. This allows two wheelchairs to pass each
other without diculty. Additional manoeuvring
space is necessary at corners and doorways. The
length o a wheelchair, including ootrest, shallbe considered when determining the turning
radius. Thereore, at corners and doorways, or
greater ease o manoeuvrability, 1,525 mm is
also recommended.
Due to space restrictions, a corridor width
o 1,525 mm is dicult to achieve in some
areas. The minimum width or private corridors,
including store and restaurant aisles shall be920 mm.
In Section A, the principles o CoLATE were
introduced. The principle that has been
considered in this sub-section and others in
these Standards is Co Colour and Contrast,and A Audible Cues, which is described by
Iantkow as ollows:
Eective use o colour and contrast designs can
enhance sae orientation and mobility o people
with visual impairments. Walls should be in
contrast with ooring, urniture in good contrast
with carpeting and surrounding walls, colour/
contrast queues and cues can be used orwayfnding or even to denote important fxtures
such as door knobs, door rames, drinking
ountains, etc.
Audible queues (and cues) are also a vital
consideration or people with varied levels o
vision (particularly or those individuals with no
vision at all). One can align their path o travel
according to sounds they know the location
o, they can relate the distance rom various
objects by sound, or even track where they are
located within a structure by knowing a sound
cue within a structure. A water ountain which
gives o a distinctive sound within a shopping
mall is one example.8
-
8/2/2019 Access Design Standards
16/90
1 4 A c c e s s D e s i g n S t a n d a r d s T h e C i t y o C a l g a r y
There shall be a consistency o materials and
colours in recurring situations to provide
satisactory sensory inormation about the
environment. The acoustic properties omaterials used in interior passageways shall
be considered in the design. Some sound
reverberation aids people with vision loss by
providing a sense o the size o the space and
the location o walls or openings, while some
sound absorption helps people who have
hearing loss by reducing background noise.
Figure 20. Proper design o an interior corridor.
B.3.2 Obstructions
Free-standing or cantilevered staircases,
escalators, ramps and intermediate foor levels
shall be avoided or have a barrier to prevent
accidental access to the overhung area.
Overhead signs shall have a clearance o 2,100
mm rom the bottom o the sign to the ground.
Objects protruding more than 100 mm rom
the wall with a top surace higher than 680 mm
shall extend to within 200 mm rom the foor, in
order to be cane detectable.
B.3.3 Floor suraces
Surace materials o circulation routes shall not
impede pedestrian movement, particularly or
those in wheelchairs or distort the perception o
people who are visually impaired.
Carpets laid on the foor, stairs or ramp suraces
shall be securely attached. They shall have atight weave, low pile and rm underlay.
Figure 21. Improper type and installation o carpets.
-
8/2/2019 Access Design Standards
17/90
1 5A c c e s s D e s i g n S t a n d a r d s T h e C i t y o C a l g a r y
Exposed edges o carpet shall be astened to the
foor surace with trim along the entire exposed
edge. The carpet trim shall be beveled with a
slope o no greater than 1:2 (50 per cent).
All foor nishes shall be slip resistant,
continuous, non-glossy and stable. The foor
surace shall have a coecient o riction no
less than 0.5, wet or dry.
Figure 22. Proper type and installation o foor materials.
B.3.4 Wall suraces
Wall suraces shall not distort perception or
cause physical harm, shall not be extremely
rough or uneven and shall have a matte nish
to prevent glare.
Wall suraces shall not be entirely constructed
with mirror or glass, or else there shall be a
horizontal warning strip, such as an adhesive
lm or graphic, that is a minimum o 150 mmwide and placed 1,350 mm above the foor.
Sharp angles or junctions o nishes shall be
avoided, and wall xtures shall be recessed,
i possible.
Figure 23. Recessed obstruction.
-
8/2/2019 Access Design Standards
18/90
1 6 A c c e s s D e s i g n S t a n d a r d s T h e C i t y o C a l g a r y
C. Vehicular access
C.1 Principle/rationale
Accessible parking shall be designed to be sae
and convenient, or users o both wheelchairs
and pedestrians. The requirements o this
section apply to parking lots, parking structures,
underground parking, lay-bys and street parking.
Seasonal conditions shall be considered, as icy
and wet parking acilities may be treacherous.
The stall dimensions, location, construction
materials and parking meters/machines shall be
accessible. Signage is essential to encourage
access and proper use.
C.2 Existing regulations
Alberta Building Code 2006 A-3.8.2.2.
Access to Parking Areas
The Planning Actprovides a mechanism
or determining the characteristics o our
communities. Where the Planning Act requiresparking, the building code requires that a
percentage o parking spaces be designed to
allow persons using wheelchairs sufcient room
to get in and out o a vehicle. A barrier-ree path
o travel shall also be provided rom the parking
area to the building.
The designer must provide a properly
identifed and unobstructed path o travelrom the parking area to the entrance, which
is accessible. The entrance chosen should be,
in any case, one normally used by the
occupants o the building. Long paths o
travel are not recommended.
C.3 Proposed standards
This section applies to vehicular access on the
property o City owned and operated buildings.
The City o Calgary Roads and Transportation
Planning shall be consulted or all matters
concerning public sidewalks and roads.
C.3.1 Lay-bys
Lay-bys are roadside drop-o areas, separated
rom the fow o vehicular trac and usually
located in ront o buildings along busy streets.
Their main unction is to allow passengers to getin and out o vehicles saely and conveniently.
They are especially benecial or people with
mobility limitations, seniors, persons with
strollers or those loading or unloading large or
heavy items.
Figure 24. Lay-by.
The provision o lay-bys shall be encouraged,
especially where streets are narrow or where
there is a steady fow o trac.
-
8/2/2019 Access Design Standards
19/90
1 7A c c e s s D e s i g n S t a n d a r d s T h e C i t y o C a l g a r y
Lay-bys shall be provided close to main
entrances o buildings. They shall have a
minimum width o 3,700 mm and a minimum
length o 7,600 mm.
Figure 25. Proper dimensions and design o canopyover lay-by.
A curb maintains a separation between the
lay-by and the path o travel to acilitate saety
and proper drainage.
Where lay-bys are provided, curb ramps shall
be placed in the lay-by or wheelchair access.
The curb ramp shall be designed in accordance
with Section A o these Standards.
The curb shall be a roll curb to allow an
accessibility vehicle, or an Access Calgary
vehicle, to back onto the sidewalk and then
lower its ramp to load and unload passengers.
Building entrances adjacent to lay-bys shall be
covered where possible, to provide shelter rom
precipitation and to keep the sidewalk ree o
snow and ice. The minimum clearance o a
covering shall be 3,000 mm rom the ground.
It is recognized that it may not be reasonable to
expect lay-bys in many downtown sites where
competing interests or land may render lay-
bys non-unctional or beyond reasonable cost.In all cases, Transportation Planning is to be
consulted when designing a lay-by.
C.3.2 Layout o parking areas
Accessible parking stalls within parking
lots shall be located as close as possible
to a main accessible entrance and provide
enough space to get in and out o a vehicle(see Section C.3.4 or proper dimensions o
parking stalls). Where operational requirements
allow, persons with disabilities shall not have to
pass behind vehicles that would normally back
out o a space.
Asphalt, concrete or rm gravel is an acceptable
parking surace. In gravel parking lots, there
shall be parking or people with disabilitiesadjoining a hard surace. A paved surace shall
be provided rom the designated parking stall to
the sidewalk.
Curb ramps leading rom parking areas
to sidewalks shall be designed in accordance
with Section A o these Standards. In all
cases, pedestrians and people in wheelchairs
shall be directed to a sae path o travelleading to the building, instead o orcing
them into areas designed or vehicular trac
and water drainage.
-
8/2/2019 Access Design Standards
20/90
1 8 A c c e s s D e s i g n S t a n d a r d s T h e C i t y o C a l g a r y
Where pedestrians have to walk across
vehicular routes, there shall be contrast o
colour and texture.
Figure 26. Proper placement o parking stalls
near entrances.
Parking blocks or wheel stops shall be set back
so vehicles do not overhang, reducing the
clear width o accessible routes. Clearances
behind wheel stops shall allow a wheelchair topass through. In addition, they shall be colour
contrasted rom the paving material so they
are not a hazard, in particular to people with
vision loss.
A large parking lot shall be divided with
vegetation into smaller sections ecient or
snow removal, yet that provide wind protection
and control driting snow. Landscaping shallbe designed so everyone, including people
using mobility devices, has the same degree o
visibility across the parking lot. Consideration
should be given to CPTED principles (Crime
Prevention Through Environmental Design)
when adding landscaping to a parking lot, so as
not to create unsae situations or the ability or
people to partake in crime-related activities.
Figure 27. Proper vegetation placement to minimize theeects o the weather.
-
8/2/2019 Access Design Standards
21/90
1 9A c c e s s D e s i g n S t a n d a r d s T h e C i t y o C a l g a r y
C.3.3 On-site road parking
Street parking shall also be made wheelchair
accessible, since in some areas o the city this
is the only type o parking available. However,
current City policy does not allow or mid-block
ramps. Thereore, accessible parking shall be
located at both ends o a block.
Street parking stalls or persons with disabilities
shall be located adjacent to sidewalk curb
ramps, to provide easy maneuverability and
saety rom street to sidewalk. These parking
stalls shall be 4,000 mm wide, and their length
shall conorm to the latest Land Use Bylaw. In
addition, a 2,000 mm access aisle shall be
painted behind or in ront o the parking stall,
and the access aisle shall be centered on the
centerline o the curb ramp (depending on the
location o the curb ramp).
Figure 28. Accessible street parking stall.
Where designated parking stalls are provided
on the street, height o parking meters (or Park
Plus machines) shall be in the range o 900 to
1,100 mm. Parking meters/machines shall notrequire twisting o the wrist or pinching o the
ngers to operate.
Parking meters/machines shall be placed at
either end o street parking stalls with no
obstructions in ront or to the side o the coin
slot/card slot. Parking meters/machines shall be
located in a well-lit and protected area.
C.3.4 Parking stalls
An accessible parking stall shall be 4,000 mm
wide to allow space or an access aisle on either
side o the parking stall. The increased width
over the Alberta Building Code minimum
width o 3,700 mm is required to acilitate
moving rom a vehicle to a wheelchair or
or the use o other mobility aids. The greaterwidth allows or the length o the lit o a
vehicle and the turning space o a wheelchair
user as he/she disembarks. In all cases, the
length o parking stalls shall conorm to the
latest Land Use Bylaw.
-
8/2/2019 Access Design Standards
22/90
2 0 A c c e s s D e s i g n S t a n d a r d s T h e C i t y o C a l g a r y
Figure 29. Proper placement o parking stallnear entrance.
Figure 30. Layout and dimensions o single accessibleparking stalls.
I two adjacent parking spaces are designated
or people with disabilities, the total width
o both spaces shall be 7,400 mm, which
shall include a 2,000 mm wide access aisleseparating the two stalls. Thereore, each stall
will have a 2,700 mm width available or the
vehicle and 2,000 mm available or the access
aisle. The access aisle shall be clearly marked
with blue hatched lines.
Figure 31. Adjacent accessible parking stalls10.
-
8/2/2019 Access Design Standards
23/90
2 1A c c e s s D e s i g n S t a n d a r d s T h e C i t y o C a l g a r y
C.3.5 Signage
Parking stalls or people with disabilities shall
be identied with the international symbol o
access and shall include the words Permit
Required. The international symbol o access
shall be posted on a vertical sign and the
symbol shall be painted on the ground with
blue paint to aid clear identication o the stall.
Figure 32. Proper signage or accessible parking stall.
Paint only the symbol and not the entire parking
space, as paint is slippery when wet.
I the location o designated parking stalls is
not obvious or is not visible rom a distance,directional signage shall be placed along the
route, to assist in navigation.
C.3.6 Parkades
Multi-level parkades shall provide accessible
parking stalls adjacent to an accessible
elevator on each level. Where elevators
are not provided, designated parking shall be
available at grade.
I oversized vehicles are required to drop
o passengers in the parking garage, a
minimum vertical clearance o 3,000 mm
shall be provided.
Figure 33. Clearance requirement or parkades whereoversized vehicles are present.
-
8/2/2019 Access Design Standards
24/90
2 2 A c c e s s D e s i g n S t a n d a r d s T h e C i t y o C a l g a r y
D. Illumination and acoustics
D.1. Principle/rationale
Consistency in the levels o illumination is
a primary concern or people with vision
loss, since their ability to adjust rom one
level to another is oten slow. This is
particularly important when making the
transition rom the exterior to the interior.
Appropriate illumination design includes proper
placement o light sources, appropriate day
lighting, and adequate signage11.
The minimization o ambient noise and the
reduction o layering o dierent sounds
improve a persons ability to hear. In addition,
people with hearing loss rely on adequate
articial lighting or speech reading, sign
language or inormative signs. They also
require spaces to be acoustically designed so
background noises and echoes do not become
a problem12.
D.2 Existing regulations
Alberta Building Code 2006 3.2.7.1.
1) An exit, a public corridor or a corridor
providing access to exit or the public or serving
patients sleeping rooms or classrooms shall be
equipped to provide illumination to an average
level o not less than 50 lx at oor or tread level
and at angles and intersections at changes olevel where there are stairs or ramps.
D.3 Proposed standards
D.3.1 Illumination
In Section A, the principles o CoLATE wereintroduced. The principle that has been
considered in this sub-section and others
in these Standards is L Lighting, which is
described by Iantkow as ollows:
Lighting (or perhaps more aptly phrased as
illumination, since we are reerring to the
actual way an area is illuminated rather than,
necessarily, the source or type o lighting) isa vital consideration in providing sae access/
egress and use o a structure or outdoor area.
Designers oten use accent lighting to highlight
a decision making point or a point o interest.
Even back-lit lighting is used to highlight certain
points o interest or or inormation purposes.
Such lighting designs are not desirable or
most people with visual impairments. Most
eye conditions require a well-distributed,
constant level o lighting. Back-lit areas or
areas where glare is present, or proceeding
rom a dark lit area to a brightly lit area only
exacerbate orientation and mobility or people
with visual impairments.13
-
8/2/2019 Access Design Standards
25/90
2 3A c c e s s D e s i g n S t a n d a r d s T h e C i t y o C a l g a r y
High levels o consistent illumination with
minimal glare improve a persons ability to
see. Illumination levels shall be increased
to emphasize stairs, entrances, obstacles,inormation signs and hazardous areas.
The minimum level o illumination emitted by
illuminated signs shall be 200 lx. Other signs
shall be illuminated to 100 lx.
Controls and operating mechanisms shall be
capable o being illuminated to at least a level
o 100 lx.Lights must be controlled and directed
so they do not create glare. Light xtures
shall be placed to prevent lamps rom shining
into peoples aces; nor should light xtures
be positioned so light refects o highly
refective materials.
Enhanced illumination or a greater distribution
o xtures or outdoor areas is important topeople with vision loss. Proper outdoor lighting
helps people with hearing loss have adequate
lighting or speech reading.
Windows shall be designed and located to
prevent glare, especially in areas o circulation.
D.3.2 Acoustics
Carpets or sound-absorbing materials shall be
used to aid people with hearing loss.
Background noise can be dicult or a
hard-o-hearing person. When possible,
switches shall be installed to turn o noisy
devices such as ans.
The placement o speakers o public address
systems shall not be near crucial areas o
communication, such as over an inormation or
service desk.
-
8/2/2019 Access Design Standards
26/90
2 4 A c c e s s D e s i g n S t a n d a r d s T h e C i t y o C a l g a r y
E. Location o controls, dispensers and receptacles
E.1 Principle/rationale
Oten, controls are too high, too low or too ar
away or people to reach. Some controls are
dicult to grasp and turn. Design and location
o controls shall oer simple operation and
saety. Controls, including thermostats, light
switches, re alarms and aucets, shall be
accessible to everyone.
E.2 Existing regulations
Alberta Building Code 2006 3.8.1.5.
Alberta Building Code 2006 7.2.6.7.
1) I the authority having jurisdiction deems it
necessary to protect children, the elderly,
or persons with disabilities or infrmities
rom burns,
a) piping used to distribute service hot water
and other hot water in assembly occupancies,
care or detention occupancies and residential
occupancies shall be concealed or insulated,
and
b) except as provided by the plumbing
regulations made pursuant to the Saety Codes
Act, the temperature o the water rom aucets
shall be limited to a maximum o 54C.
E.3 Proposed standards
E.3.1 General requirements
Controls, dispensers and receptaclesshall not require the use o two hands,
nor two simultaneous movements by one
hand or both hands to operate.
E.3.2 Saety and emergency controls
Emergency controls shall not be placed too high
or people in wheelchairs. They shall not be too
low, thereby helping to prevent children rom
misusing them. Emergency controls, such as
re alarms, shall be located with their highest
operable parts 1,200 mm above the foor
(measured to their centre line).
Figure 34. Proper height or controls.
-
8/2/2019 Access Design Standards
27/90
2 5A c c e s s D e s i g n S t a n d a r d s T h e C i t y o C a l g a r y
E.3.3 Lighting fxtures
The highest operable part o light switches
and other non-emergency controls shall be
1,000 mm above the foor. Rocker switches are
preerable to toggle switches, as they are easier
to use.
E.3.4 Electrical outlets
Electrical outlets shall be mounted at a height o
600 mm, measured rom the foor to the centre
line o the outlet.
E.3.5 Faucets
Automatic water taps or a lever-type aucet shall
be used or easy operation. Water temperature
shall be limited in accordance with the Alberta
Building Code 2006.
Figure 35. Proper and improper aucet varieties.
-
8/2/2019 Access Design Standards
28/90
2 6 A c c e s s D e s i g n S t a n d a r d s T h e C i t y o C a l g a r y
F. Building entrances, doors and doorways
F.1 Principle/rationale
Wide doorways and easy-to-open doors benet
everyone. The passage is easier or people with
disabilities, seniors, people carrying packages
or wheeling strollers. Automatic doors and
proper hardware placement makes entrances
much easier to use.
A well-designed door is distinguished, yet
simple, oering direction and orientation to
users. Proper lighting and signage is a good
means or accommodating this requirement.
F.2 Existing regulations
Alberta Building Code 2006 3.8.1.2.
1) In addition to the barrier-ree entrances
required by Sentence (2), not less than 50%
o the pedestrian entrances to a building in
Sentence 3.8.1.1.(1), including walkways
leading to the entrances rom a public
thoroughare and rom on site parking areas,
shall be barrier-ree.
6) I an entrance is equipped with a security
system, both visual and audible signals shall be
used to indicate when the door lock is released.
Figure 36. Vestibule.
Alberta Building Code 2006 3.3.1.13.
1) A door that opens into or is located within
a public corridor or other acility that provides
access to exit rom a suite shall
a) Provide a clear opening o not less than
800 mm i there is only one door lea,
b) in a doorway with multiple leaves, have the
active lea providing a clear opening o not less
than 800 mm, and
c) Not open onto a step.
-
8/2/2019 Access Design Standards
29/90
2 7A c c e s s D e s i g n S t a n d a r d s T h e C i t y o C a l g a r y
3) Except as permitted by Sentence (4), door
release hardware shall be operable by one
hand and the door shall be openable with not
more than one releasing operation. (See alsoSentence 3.8.3.3.(3))
5) Door release hardware shall be installed not
more than 1,200 mm above the fnished oor.
8) Controls or the remote release o door
locking devices permitted by Sentence (6)
shall be located in an area readily available to
security personnel.Alberta Building Code 2006 3.4.3.2.
Alberta Building Code 2006 3.8.3.3.
3) Door operating devices shall be o a design
which does not require tight grasping and
twisting o the wrist as the only means o
operation. (See Appendix A.)
11) A vestibule located in a barrier ree path o
travel shall be arranged to allow the movement
o wheelchairs between doors and shall provide
a distance between 2 doors in series o not less
than 1,200 mm plus the width o any door that
swings into the space in the path o travel rom
one door to another.
F.3 Proposed standards
F.3.1 Entrances
Entrances, particularly the main accessibleone, shall be readily distinguishable in the
acade and shall provide an easy transition into
the building. The eect o seasonal weather
conditions, such as strong winds and driting
snow, shall be mitigated in the design o
building entrances to ensure normal operation
o doors.
When entrances must be located towards theprevailing winds, measures to minimize the
eects shall be used, such as walls and/or
vegetation. Drainage shall be directed away
rom the entrance.
Doormats with non-slip under padding ease
the transition rom the outdoor environment to
interior spaces, by absorbing much o the snow,
ice and slush accumulated rom winter bootsand shoes. This prevents people rom slipping
on any smooth foor materials used inside.
Doormats shall not project more than 13 mm
above the foor nish.
Well-designed lighting and signage shall be
used to enhance identication o an entrance.
Where operational requirements allow,
sliding automatic doors shall be installed at
entrances and entrance vestibules in new
construction. The sliding automatic doors
shall have a saety power-ail option, that
includes a backup battery.
-
8/2/2019 Access Design Standards
30/90
2 8 A c c e s s D e s i g n S t a n d a r d s T h e C i t y o C a l g a r y
Figure 37. Automatic doors, signage and protection rom
the elements.
F.3.2 Specifcations or people with
vision loss
Providing adequate lighting or transitions
rom the exterior to interior assists people with
vision loss, who may be slower to adjust to
the dierence in levels o light. Such transition
space shall be well lit.
Door push plates shall be o a contrasting
colour or value, beneting the visually impaired.
Plate glass doors shall be designed so people
with vision loss can readily identiy them
(see Section B).
Numbers on doors shall be raised and located
between 1,200 mm and 1,800 mm or easy
reading by people with vision loss.
Figure 38. Large, bold and raised lettering labels.
Due to Building Code regulations, exit doors
must open outward, which can create a hazard
or people with vision loss, especially automatic
swing doors. To rectiy this problem, such doors
shall be recessed to minimize the hazard or
people walking beside a building.
Figure 39. Recessed door.
-
8/2/2019 Access Design Standards
31/90
2 9A c c e s s D e s i g n S t a n d a r d s T h e C i t y o C a l g a r y
F.3.3 Door openers and hardware
People with limited mobility, strength or
balance nd doors, particularly those on the
exterior o a building, dicult, i not impossible,
to open. Automatic door openers or power-
assisted mechanisms shall be used on doors
in universal paths o travel, such as entrances,
lobbies, corridors and other major public
pedestrian thoroughares.
Figure 40. Proper location o automatic door openers.
Manual door openers shall be mounted at a
height o 800 mm to 1,100 mm rom the foor.
Although Alberta Building Code 2006 allows
a maximum height o 1,200 mm, door release
hardware shall be installed between 800 mm to
1,100 mm.
Clearance between the handle and the door
shall be a minimum o 50 mm. This will aid
those with limited hand unctions and allow the
door to be opened using only one arm.
Figure 41. Proper spacing between a door and hardware.
I a door is opened remotely (as is commonin many multi-amily residential buildings), a
visual and audible signal shall be used to alert
both the visitors and the occupants that the
door lock is released.
The bottom o a manual door shall have a
smooth uninterrupted kick plate to protect the
door rom wheelchair ootrests. A minimum
height o 300 mm is recommended.
Figure 42. Kick plate and closer requirements.
-
8/2/2019 Access Design Standards
32/90
3 0 A c c e s s D e s i g n S t a n d a r d s T h e C i t y o C a l g a r y
F.3.4 Doors and gates
In any set o two or more doors or gates,
whether within a building, at an entrance to
a building or completely outside, the door
opening shall alternate between right and let
hand operation. For example, i an entrance has
three doors, there shall be one set o double
doors and the third door can be hinged on
either the let or right hand side. As another
example, i there are two doors in a series, the
inner door and outer door should be hinged on
opposite sides.
This enables persons to operate the door with
one hand on the side o their choice and
avoid the need to reach across or even travel
backwards through the door. Persons with an
occupied hand, including those with a support
white cane, a guide dog and persons carrying
luggage or packages would be able to use
their ree hand to open the door without theawkwardness o having to reach across. In no
circumstance should it be necessary to use two
hands to open a door.
Doorways without a door installed in them shall
be minimum 850 mm wide.
Door width shall be not less than 920 mm.
When turnstiles or revolving doors are provided,
a swing door with an automatic door controlshall be placed immediately to one side o the
revolving door or turnstile, or easy access by
people with disabilities.
Automatic doors shall have a master control that
can control the door closers, keeping the door
open or a minimum o eight seconds, with the
door held at an angle o between 70 and 90
degrees. As well, the master control allows thedoor to reverse when closing i an object stops
the door.
Figure 43. Door closer requirements and requirements ordoors at the top o a ramp.
-
8/2/2019 Access Design Standards
33/90
3 1A c c e s s D e s i g n S t a n d a r d s T h e C i t y o C a l g a r y
G. Ramps
G.1 Principle/rationale
For changes in levels, ramps are essential in
providing an easier and oten saer means o
travel or people who are unable to use stairs.
The slope, width and length o a ramp shall be
manageable. Signage, tactile cues, protection
rom the elements and proper landings also
help increase comort or those using the ramp.
G.2 Existing regulations
Alberta Building Code 2006 3.8.3.4.
G.3 Proposed standards
G.3.1 General requirements
Ramps to buildings must be on private property,
outside o the road right-o-way. Any heating
systems must also be on private property and
privately maintained.
Changes in levels shall be limited, as slopes
require greater physical exertion and skill rom
people with disabilities. I ramps are too steep
or too long, they become obstacles. Slopes
between 1:25 (our per cent) to 1:20 (ve per
cent) are recommended.
The minimum clear width o a ramp shall be
950 mm between handrails.
Where passing o wheelchairs is likely to occurrequently, the options are:
(a) To widen the ramp to 1,800 mm.
(b) To widen the rest areas to 1,800 mm.
Figure 44. Proper ramp design.
Ramps shall have level landings at the top and
bottom o each run and where they change
direction. The landings shall be at least as
wide as the widest ramp run leading to themand have a length not less than 1,500 mm.
The 1,500 mm accommodates the length o a
wheelchair as it negotiates a corner.
-
8/2/2019 Access Design Standards
34/90
3 2 A c c e s s D e s i g n S t a n d a r d s T h e C i t y o C a l g a r y
Figure 45. Ramp design.
Visual and textural cues at the top and bottom
o the ramp shall be provided or people
with vision loss. Non-glare and slip-resistant
materials shall be used on the ramp surace.
The maximum cross slope o ramp suraces shall
be 1:50 (two per cent).
I a ramp needs to be longer than 18 m, a
mechanical means o travel shall be considered.
G.3.2 Exterior ramps
Exterior ramps shall be protected rom rain,
snow and ice, or maintained ree o snow and
ice through regular maintenance or appropriate
subsurace heating and drainage systems.
-
8/2/2019 Access Design Standards
35/90
3 3A c c e s s D e s i g n S t a n d a r d s T h e C i t y o C a l g a r y
H. Stairs
H.1 Principle/rationale
Some ambulatory people with balance
problems or vision loss nd stairs easier to use
than ramps. It is important the rise and run be
designed so the stairs are not overly strenuous
or create a hazard. Increased illumination,
colour contrast, uniormly patterned materials,
signage and other warning indicators can be
used to enhance saety.
Figure 46. Stairs are occasionally preerred to ramps bypeople with disabilities.
H.2 Existing regulations
Alberta Building Code 2006 3.3.1.7.
4) In a barrier-ree path o travel, a downward
change in elevation shall be signaled by the use
o a 600 mm wide tactile warning strip placed
250 mm rom the edge and or the ull widtho a stair, escalator, moving walkway, ramp
or platorm and identifed using colour and
brightness contrast.
Figure 47. Cane detectable warning indicators or stairs.
Alberta Building Code 2006 3.4.6.1.
1) The suraces o ramps, and landings and
treads a) shall have a fnish that is slip resistant,
and b) i accessible to the public, shall have
either a colour contrast or a distinctive pattern
to demarcate the leading edge o the tread and
the leading edge o the landing, as well as the
beginning and end o a ramp.
2) Treads and landings o exterior exit stairs
more than 10 m high shall be designed to be
ree o ice and snow accumulations.
Alberta Building Code 2006 3.4.6.2
1) Except as permitted by Sentence 3.3.2.13.(1),
every ight o interior stairs shall have not less
than 3 risers.
-
8/2/2019 Access Design Standards
36/90
3 4 A c c e s s D e s i g n S t a n d a r d s T h e C i t y o C a l g a r y
Alberta Building Code 2006 3.3.2.14.
1) In a Group A, Division 2 occupancy used
or the serving o ood and beverages, aninterior ight o stairs with ewer than 3 risers is
permitted provided it
a) is not less than 900 mm wide,
b) is illuminated at all times that occupants are
on the premises, and
c) has a handrail on each side.
Alberta Building Code 2006 3.4.6.3.
2) The length and width o landings shall be at
least the width o stairways in which they occur,
except that in a straight run the length o a
landing need not be more than 1,100 mm.
3) Where a doorway or stairway empties onto a
ramp through a side wall, there shall be a level
area extending across the ull width o the ramp,and or a distance o 300 mm on either side o
the wall opening, excepting one side when it
abuts on an end wall.
4) Where a door or stairway empties onto a
ramp through an end wall, there shall be a level
area extending across the ull width o the ramp
and along its length or not less than 900 mm.
Alberta Building Code 2006 3.4.6.7.
3) Treads and risers in every exit stair, except a
fre escape stair, shall have uniorm run and rise
in any one ight, and shall not alter signifcantly
in run and rise in successive ights in any stair
system. (See Appendix A.)
4) The leading edge o a stair tread shall have
either a radius or a bevel between 6 mm and
10 mm in horizontal dimension.
5) The ront edge o stair treads in exits and
public access to exits shall be at right angles to
the direction o exit travel.
Figure 48. Proper dimensions or stairs.
H.3 Proposed standards
H.3.1 General requirements
A fight o stairs shall have uniorm dimensions
and no open risers.
Nosings shall not have projecting undersides,
and shall be beveled i extending more than
25 mm, to prevent catching a toe. Nosings shall
be beveled not more than 60 with respect to
the tread surace. This ensures the tread edge is
more clearly visible in descent.
Nosings on interior/exterior stairs shall be a
contrasting colour to aid people with vision loss.
-
8/2/2019 Access Design Standards
37/90
3 5A c c e s s D e s i g n S t a n d a r d s T h e C i t y o C a l g a r y
Isolated steps shall be avoided, since
they are oten dicult or people with
vision loss to detect and act as a barrier to
people in wheelchairs.
Illumination shall be positioned to minimize
glare and shadow.
A barrier shall be used to prevent access to
areas under a cantilevered or overhung staircase.
Figure 49. Avoid overhanging stairs.
H.3.2 Interior stairs
Heavily patterned carpets or tiles shall not be
used on stairs as they create gure-ground
conusion and obscure the denition o the
tread nosing.
H.3.3 Exterior stairs
Stairs shall be protected rom climatic variations
or maintained ree o snow and ice. Stairs shall
not be shaded by vegetation or other elements
that prevent snow and ice rom melting.
-
8/2/2019 Access Design Standards
38/90
3 6 A c c e s s D e s i g n S t a n d a r d s T h e C i t y o C a l g a r y
J. Handrails and guards
J.1 Principle/rationale
Handrails are important eatures in barrier-ree
access. They shall be easy to grasp and provide
a rm and comortable grip. People with
vision loss use handrails as guides; those with
mobility impairments use them or leverage to
get up ramps and the semi-ambulatory rely on
handrails or balance. It is important handrails
be placed at a sae and convenient height or
everyone. Enhance ease o use by incorporating
colour contrast and uniormity.
Figure 50. Proper handrails used or guidance.
J.2 Existing regulations
Alberta Building Code 2006 3.4.6.4.
1) A stairway shall have a handrail on at leastone side, but i it is 1,100 mm or more wide, it
shall have handrails on both sides.
2) I the required width o a ramp or ight
o stairs is more than 2,200 mm, one or
more intermediate handrails continuous
between landings shall be provided, andlocated so that there will be not more than
1,650 mm between handrails.
3) Handrails shall be continuously graspable
along their entire length and shall have
a) a circular cross-section with an outside
diameter not less than 30 mm and not more
than 43 mm, orb) a non-circular cross-section with a graspable
portion that has a perimeter not less than 100
mm and not more than 125 mm and whose
largest cross-sectional dimension is not more
than 45 mm.
4) Handrails on stairs and ramps shall be not
less than 865 mm and not more than 965 mm
high, measured vertically rom a line drawn
through the outside edges o the stair nosing
or rom the surace o the ramp, except that
handrails not meeting these requirements are
permitted provided they are installed in addition
to the required handrail.
5) Except where interrupted by doorways or
newels at changes in direction, at least one
handrail shall be continuous throughout the
length o a stairway or ramp, including landings.
(See Appendix A.)
-
8/2/2019 Access Design Standards
39/90
3 7A c c e s s D e s i g n S t a n d a r d s T h e C i t y o C a l g a r y
6) Handrails shall be terminated in a manner
that will not obstruct pedestrian travel or create
a hazard. (See A-3.4.6.4.(5) in Appendix A.)
7) At least one handrail at the side o a
stairway or ramp shall extend horizontally
not less than 300 mm beyond the top
and bottom o the stairway or ramp.
(See A-3.4.6.4.(5) in Appendix A.)
8) The clearance between a handrail and any
surace behind it shall be not less than
a) 50 mm, or
b) 60 mm i the surace behind the handrail is
rough or abrasive.
9) Handrails and their supports shall be
designed and constructed to withstand
the loading values obtained rom the non-
concurrent application o
a) a concentrated load not less than 0.9 kN
applied at any point and in any direction or all
handrails, and
b) a uniorm load not less than 0.7 kN/m
applied in any direction to handrails not located
within dwelling units.
10) A ramp shall have handrails on both sides.
J.3 Proposed standards
In all cases, handrails shall be located on both
sides o a ramp or stairway.
The outside diameter or width o a handrail
shall be 30 mm to 43 mm, to allow those with
limited hand unction to grasp it rmly. In
addition, the smaller dimension enables people
wearing gloves in winter to grasp the handrail
rmly, with ease. A gap o at least 50 mm shall
distance the handrail rom the wall.
In stairwells, especially exits, tactile cues(e.g., several notches or a rough texture) shall
be placed on the inside or the last 300 mm
on both ends o the handrail as a signal to
inorm persons with vision loss that they are
approaching the last step. A consistent system
o tactile indicators shall be located on or near
the handrail at the top and bottom o stairs and
ramps to indicate ascent and descent.
All handrails shall contrast rom their
surroundings through colour or brightness.
Figure 51. Proper and improper handrail shapeand dimensions.
-
8/2/2019 Access Design Standards
40/90
3 8 A c c e s s D e s i g n S t a n d a r d s T h e C i t y o C a l g a r y
K. Elevators
K.1 Principle/rationale
An elevator is vital to a non-ambulatory person,
because it oten provides the only orm o
access to dierent levels o a building. A poorly
designed elevator can be as much o a barrier
as stairs. An elevator car must be large enough
to accommodate people with disabilities.
Signage and controls in the elevator lobby and
in the car itsel have a proound impact on the
accessibility o an elevator. Visual and audio
indicators are also critical to those with vision
and hearing loss.
Figure 52. Well-designed elevator.
K.2 Existing regulations
Alberta Building Code 2006 3.8.3.5
K.3 Proposed standards
K.3.1 General requirements
All passenger elevators shall be accessible topeople with disabilities.
The size o an elevator car must conorm to the
Alberta Building Code 2006 requirements. A
code-compliant elevator is large enough in the
length dimension, but is too small in the width
dimension to accommodate the turning around
o a wheelchair.
Figure 53. An elevator car with dimensions allowing theturning around o a wheelchair.
-
8/2/2019 Access Design Standards
41/90
3 9A c c e s s D e s i g n S t a n d a r d s T h e C i t y o C a l g a r y
Verbal announcements identiying the foor
level and the direction o travel shall be
installed or people with vision loss and or
those who cannot see the foor indicator at theback o a crowded elevator. Where practical,
control buttons shall be installed on both sides
o the elevator door inside the elevator.
Figure 54. Proper elevator car dimensions.
K.3.2 Elevator lobbies
The minimum space in ront o elevator doors
shall be 1,500 mm.
Doors on elevators shall start to close ater eight
seconds rom the ully open position.
Call buttons shall be located on each wall
between elevators and shall be easily
identiable by colour contrast and raised
symbols. The call buttons shall protrude toenable a user to push with any part o the hand.
No obstructions shall be placed under elevator
call buttons.
Tactile signage in the orm o larger Arabic
numerals and letters shall also be axed
at a height o 1,200 mm above the foor on
both sides o the door opening within theelevator lobby.
Figure 55. Proper signage.
Arrival o an elevator shall be indicated by a
verbal announcement or a clear audible and
visual signal located within the elevator lobby
near the door o the arriving car.
-
8/2/2019 Access Design Standards
42/90
4 0 A c c e s s D e s i g n S t a n d a r d s T h e C i t y o C a l g a r y
Figure 56. Proper design o elevator lobbies.
K.3.3 Floor registration buttons
Floor registration buttons shall be raised, since
fush or recessed buttons are dicult to activate
by people with vision loss or with limited
manual dexterity.
Floor registration buttons within the car shall
be clearly marked with tactile signage in the
orm o raised Arabic numerals and letters and,
i there is room, Braille signage shall be added.
There shall be a colour contrast between the
foor registration buttons and the background.
Figure 57. Proper placement o controls.
K.3.4 Exterior elevators
Exterior elevators, i provided, shall be oriented
away rom the prevailing winds to keep the
car ree o snow, rain and debris. Waiting
areas shall be sheltered, positively drained
and well lit.
Glass walls shall be installed to enhancesecurity by increasing visibility.
-
8/2/2019 Access Design Standards
43/90
4 1A c c e s s D e s i g n S t a n d a r d s T h e C i t y o C a l g a r y
L. Public washrooms
L.1 Principle/rationale
It is important that washrooms are available
to serve the needs o people with disabilities.
Every foor serviced by an elevator shall have
an accessible washroom that is easily located
and clearly marked. Accessible washrooms
shall include hardware that is operable by
all, appropriate xture type and location, and
adequate dimensions. An accessible washroom
shall be sae and, where possible, connected by
a call system to support sta.
L.2 Existing regulations
Alberta Building Code 2006 3.8.2.3. and
3.8.3.8. to 3.8.3.13.
L.3 Proposed standards
L.3.1 Washroom entrances
The entrances to washrooms are oten dicult,
i not impossible, or people with disabilitiesto use, especially when there are vestibules
with two doors. Thereore, it is important to
either eliminate the doors or provide only one
entry door to a washroom. Washrooms that are
designed so doors are not required to prevent
viewing by passersby are considered ideal.
Entrances with an L-conguration shall have
a minimum depth o 1,200 mm to allow awheelchair to turn the corner easily. However,
L-shaped entrances shall be as wide as possible.
Figure 58. Proper design o a washroom entrance.
L.3.2 Water closet stalls
Water closet stall doors shall have a clear
opening o 800 mm and swing out o thestall. Water closet stalls or enclosure doors
shall be equipped with locking devices that
do not require pinching o the ngers or
twisting o the wrist to operate. The doors shall
also be equipped with a hinge that slowly
closes the door.
Water closet stalls shall have a clear
unobstructed space rom the water closetbowl to the door o at least 1,500 mm wide
by 1,500 mm deep. This will allow or easy
maneuverability o the wheelchair when in
the stall. A clear turning radius o 2,250 mm is
preerred (but not required) to accommodate
people in power wheelchairs.
-
8/2/2019 Access Design Standards
44/90
4 2 A c c e s s D e s i g n S t a n d a r d s T h e C i t y o C a l g a r y
Figure 59: Proper dimensions o a water closet stall.
L.3.3 Washroom fxtures
In washrooms, dispensers and receptacles
shall be mounted with their highest operable
parts above the foor surace within the
ollowing ranges:
(a) Paper towel dispensers/hand dryers:
1,100 mm to 1,200 mm.
(b) Soap dispensers: 900 mm to 1,000 mm and
within 500 mm orward grasp reach.
(c) Toilet paper dispensers: 750 mm to 850 mm.
(d) Toilet seat cover dispensers: 900 mm to1,000 mm.
(e) Waste receptacles: 900 mm to 1,000 mm.
() Grab bars as outlined in ABC 2006,
3.8.3.8 (2).
A coat hook shall be mounted on a solid wall.
All washroom xtures shall be installed or
saety and ease o use.
A toilet paper dispenser shall be within reach. It
shall be located so that its operable part is not
less than 460 480 mm rom an adjacent wall
to the centerline o a water closet.
Figure 60. Proper location o xtures.
-
8/2/2019 Access Design Standards
45/90
4 3A c c e s s D e s i g n S t a n d a r d s T h e C i t y o C a l g a r y
An automatic or single-unction towel dispenser
(requiring only one hand and only one movement
to release the towel) is recommended.
Figure 61. Properly placed grab bars.
L.3.4 Lavatory knee space
To maximize knee space below the lavatory,
P traps in drain lines shall be oset
horizontally so that a minimum o 280 mm is
provided rom the ront o the counter to the
ace o the P trap. The bottom o the counter
shall be 735 mm to 800 mm rom the foor.
Figure 62. Proper knee clearance beneath sink.
L.3.5 Universal washrooms
The requirements o Alberta Building Code
2006, section 3.8.2.3(3) indicates a universal
washroom is not required in the entrance story
i a barrier ree path o travel is provided to a
universal water closet elsewhere.
However, it shall be made as easy as possible
or people with vision loss or mobility
impairments to locate and travel to a washroom.
A universal male/emale washroom shall be
located in all buildings not ar rom the main
entrance on the main foor.
-
8/2/2019 Access Design Standards
46/90
4 4 A c c e s s D e s i g n S t a n d a r d s T h e C i t y o C a l g a r y
Figure 63. Proper dimensions o a water closet stall.
Where buildings are staed with ull-time
security, call buttons or pressable call strips
shall be installed in all universal washrooms,
in case a washroom user alls or encounterssome other circumstance that would require
assistance. Where call buttons are installed,
they shall be installed on the same wall as the
side grab bar and, where pressable strips are
installed, they shall be placed on the same
walls as the grab bars.
Universal washrooms are valuable to mothers
with young children, and a counter shall beprovided with sucient space to change an
inants diaper.
-
8/2/2019 Access Design Standards
47/90
4 5A c c e s s D e s i g n S t a n d a r d s T h e C i t y o C a l g a r y
M. Recreational and cultural centres
M.1 Principle/rationale
Facilities designed and constructed to meet
accessibility standards enable people with
disabilities to take an active part in community
lie. Proper design o recreational and cultural
acilities encourages healthy liestyles and
educational development.
Not all recreational areas need to be completely
barrier-ree. A diversity o accessibility within
a single recreational area enhances everyones
opportunity to enjoy the outdoors, without
segregation by disability.
M.2 Existing regulations
Alberta Building Code 2006 7.3.3.12.
Alberta Building Code 2006 7.3.3.15.
Alberta Building Code 2006 7.3.3.18.
Alberta Building Code 2006 3.8.3.16. (1)
Alberta building Code 2006 3.8.3.13
M.3 Proposed standards
M.3.1 Swimming pools
Accessible swimming pools can be essential
or people with disabilities, who may rely
on aquatic activities as a orm o rehabilitation
or exercise.
There shall be a ramp and stairs with handrails
on both sides located at the shallow end o
the pool.
Figure 64. Proper ramps are the best entrance intoswimming pools.
Stairs, rather than ladders, shall be provided
whenever possible, since stairs are more
easily negotiated and can be used to sit upon
i wide enough.
Figure 65. Where ramps are not easible, stairs arepreerred to ladders.
-
8/2/2019 Access Design Standards
48/90
4 6 A c c e s s D e s i g n S t a n d a r d s T h e C i t y o C a l g a r y
Power hoists shall be provided to assist people
in wheelchairs with exiting and entering the
pool. Power hoists are benecial, since ramps
can be dicult or some people with disabilitiesto use.
Figure 66. Power hoist into swimming pool.
Pool depths, along with shallow end and
deep end, shall be indicated with signage that
eatures contrasting colour and texture.
M.3.2 Ice rinks and exercise areas
Ice rinks shall be designed with the
consideration o sports played by people with
disabilities, such as sledge hockey, and or
spectators who may also be disabled. Player
benches and penalty boxes shall have Plexiglas
in ront or viewing. The player benches must
have two doors 910 mm wide to allow or easy
egress and access.14
Figure 67. Proper dimensions and materials or anice rink.
Seating and handrails shall be available near
the entrance/exit o an ice rink. Level access
shall be provided to ice rinks and exercise areas.
Exercise areas shall include handrails and/
or wheelchair clearance to some equipment
to acilitate transer to and rom exercise
equipment. Raised tactile signage shall beincluded to help identiy dierent types o
equipment or people with vision loss. Raised
exercise platorms shall be available as an
alternative to stretching on the foor or people
in wheelchairs or the elderly.
-
8/2/2019 Access Design Standards
49/90
4 7A c c e s s D e s i g n S t a n d a r d s T h e C i t y o C a l g a r y
Figure 68. Raised exercise platorm.
M.3.3 Exhibits
Exhibition areas shall also be barrier-ree, or
an alternative method o interpreting the
message shall be provided, such as audio-visual
presentations, large print text or tactile signage.
Important artiacts, labels and graphics shall
be placed at an elevation that makes viewing
comortable or all visitors. Table displays
shall be located between 1,000 mm to 1,200
mm above the ground level. Wall-mounted
displays shall be located between 1,200 mm
to 1,500 mm above the ground level. Labels on
horizontal suraces shall be tilted to allow or
better viewing.
Figure 69. Proper placement o displays.
Lighting xtures shall be designed and placed
to minimize glare and refection.
M.3.4 Drinking ountains
Drinking ountains shall extend within a
maximum distance o 200 mm above the foor,
with ront panel sloping 50 mm to 90 mm
inwards. This will allow a close side approach
or wheelchairs, and will not be hazardous or
people with vision loss when using a cane.
Figure 70. Drinking ountain suitable or peoplewith disabilities.
-
8/2/2019 Access Design Standards
50/90
4 8 A c c e s s D e s i g n S t a n d a r d s T h e C i t y o C a l g a r y
The height o the waterspout shall be between
780 mm to 915 mm. The operation control shall
be a push button or a lever-type control.
Figure 71. Universally designed drinking ountain orpeople who are standing and people who arein wheelchairs.
M.3.5 Shower fxtures
A diverter mechanism on the hand-held shower
shall be provided to protect people with
disabilities against misdirection o spray.
A shel or storing soap, sponges and brushes
shall be provided at 850 mm above foor level.
Figure 72. Water temperature control.
M.3.6 Common showers
Common showers shall have beveled
thresholds no more than 13 mm in
height allowing wheelchairs to pass
over with minimal hindrance.
A shower wheelchair shall be provided
or use in the shower room.
A fexible hand-held shower sprayer shall
be provided.
The slope o shower room foor to drain shall
be 1:20 (ve per cent).
-
8/2/2019 Access Design Standards
51/90
4 9A c c e s s D e s i g n S t a n d a r d s T h e C i t y o C a l g a r y
Figure 73. Proper shower dimensions.
M.3.7 Individual change/shower rooms
Similar to individual washrooms, provision oindividual change/shower rooms or people
with disabilities allows amily members or
caregivers o the opposite gender to provide
assistance without inconveniencing themselves
or other patrons.
Individual change rooms shall include an
elevated changing platorm 1,500 mm wide
x 1,800 mm long x 480 mm high. The changerooms are to include a 1,500 mm turning radius,
grab bars, coat hooks and shelving at a height
o 1,000 mm above the nished foor. A clear
turning radius o 2,250 mm is preerred
(but not required) to accommodate people
in power wheelchairs.
Figure 74. Proper dimensions or change roomsand showers.
-
8/2/2019 Access Design Standards
52/90
5 0 A c c e s s D e s i g n S t a n d a r d s T h e C i t y o C a l g a r y
N. Public acilities
N.1 Principle/rationale
People with disabilities must attend to day-
to-day business, such as banking, community
meetings and registering or recreational or
educational programs. The excessive height
o countertops can make these tasks dicult.
Thereore, an area or people in wheelchairs
to conduct their business with privacy at a
convenient height and with adequate knee
space shall be provided.
People with disabilities, like most people, enjoy
going to plays, movies and sporting events.
However, this is oten impossible because o the
lack o available seating.
N.2 Existing regulations
Alberta Building Code 2006 3.8.2.1.
Alberta Building Code 2006 3.8.3.6.
N.3 Proposed standards
N.3.1 Counters
CAN/CSA-B651-04 recommends the same
counter dimensions as the Alberta Building
Code 2006, but also includes a minimum
clear foor space o not less than 750 mm x
1,200 mm in ront o a counter or work surace.
However, the recommended and preerred
knee space beneath universal counters intended
to be used as work suraces shall be 720 mm
to 800 mm high.
Figure 75. Dimension requirements or counters.
Counters shall be cane detectable and
colour/brightness contrasted rom their
surroundings and suraces shall have a
non-glare, matte nish.
To prevent confict between wheelchair
access and cane detection, a border with
contrasting colour and brightness and a
tactile warning surace shall be laid into
the foor near the counter. This can be used
as an indicator or people with vision loss
approaching a service counter.
Where a glass partition separates customers
rom the service personnel, there shall
be an adequate speaker system to
acilitate communication.
-
8/2/2019 Access Design Standards
53/90
5 1A c c e s s D e s i g n S t a n d a r d s T h e C i t y o C a l g a r y
Figure 76. Caeteria counter.
N.3.2 Caeterias
The height o counters or conveying trays shall
be a maximum o 865 mm high.
The maximum distance to any liquid dispensershall be within reach limitations o wheelchair
users unless employees are behind the caeteria
line at all times.
Food shall be located a maximum o 450 mm
rom the edge o the counter.
Figure 77. Proper dimensions or caeteria counters.
N.3.3 Assembly seating in public acilities
Designated wheelchair spaces shall be
spread over dierent areas in a seating
space, to avoid secluding people using
wheelchairs to one location.
Figure 78. Accessible seating shall be distributedthroughout the seating area.
-
8/2/2019 Access Design Standards
54/90
5 2 A c c e s s D e s i g n S t a n d a r d s T h e C i t y o C a l g a r y
Spaces provided or persons in wheelchairs
shall provide sightlines equal to those provided
or the majority o the audience.
It is recommended that the number o spaces
required or people using wheelchairs in
Alberta Building Code 2006, Table 3.8.2.1,
be increased by at least two per number o
xed seats to accommodate an increase in the
population o people using wheelchairs, which
is anticipated in the uture.
Preerred designated wheelchair spaces
Number o fxed seats inseating area
Number o spacesrequired orwheelchairs
2 100 4
101 200 5
201 300 6
301 400 7
401 500 8
501 900 9
901 1,300 10
1,301 1,700 11
Each increment o up to 400seats in excess o 1,700
Two additional spaces
Table 1. Required accessible seating.
Spaces or persons in wheelchairs shall be level,
and the path o travel to them shall meet the
requirements o Section B o these Standards.
Removable chairs can be installed in public
acilities to accommodate people using
wheelchairs, without loss o revenue to
the owner. I there is no need or thesewheelchair spaces, the seats can be replaced
or general use.
Figure 79. Standard seats can be made removable to
accommodate accessible seating.
Seats shall be provided or persons with
orthotics or prostheses. The space or accessible
seating shall be wide enough to allow people
to maneuver rom the side, ront or behind with
their mobility devices.
Meeting rooms shall be designed so all
members o the audience have clear sightlines
to the speaker. Further, the design must limit
placement o speakers in ront o a window15.
-
8/2/2019 Access Design Standards
55/90
5 3A c c e s s D e s i g n S t a n d a r d s T h e C i t y o C a l g a r y
N.3.4 Permanent barriers
I posts are installed as a crowd control measure,
at least one post shall be removable and shall
be identied with the international symbol o
accessibility. I not, an alternative passageway,
such as a gate similarly marked, shall be
available or access.
Bollards shall be placed to minimize
obstruction to pedestrian fow. The minimum
clearance between bollards shall be 1,200 mm.
The minimum height shall be 600 mm, and
they shall colour contrast rom the surrounding
paving to be more visible.
Chains, cables or ropes are not recommended
as permanent or temporary barriers unless they
are easily visible. They shall be placed at a
height o no more than 250 mm and no lower
than 150 mm, so they are detectable by visually
impaired people.
Figure 80. Required dimensions or permanent barriers.
-
8/2/2019 Access Design Standards
56/90
5 4 A c c e s s D e s i g n S t a n d a r d s T h e C i t y o C a l g a r y
P. Parks, pathways and playgrounds
P.1 Principle/rationale
Parks and playgrounds that are accessible
provide an opportunity or people with
disabilities to have access to the outdoors and
to take an active part in community lie. All
pathways in parks shall be accessible and shall
be designed to be sae and protected rom the
elements. Playground equipment and outdoor
urniture shall not become barriers or people
with disabilities.
P.2 Existing regulationsAlberta Building Code 2006 3.8.3.2.
P.3 Proposed Stand