MCD10062 Rev. 1.1, 2-Oct-08 Page 1 of 2 www.power-one.com
ACC Controller Module Data Sheet
Features
• User-selectable alarm parameters • Password controlled environment • USB or RS232* Interface and Form “C” dry
alarm contacts • Programmable alarm routing, logic unit and
analog inputs • Ethernet interface + web server support • 1000-event alarm log • Audible Alarm • Remote firmware upgrade Intelligent site management:
• Battery tests and log • Battery voltage and symmetry monitoring • Remaining battery capacity measurement • Low voltage disconnect • Temperature compensation with programmable
compensation factor • Monthly data logging • Site log tools
Description The Power-One Advance Controller Card (ACC) is a pluggable microprocessor controller that provides monitoring and control for a broad range of Power-One DC Power Systems. The ACC monitors all system parameters including: DC voltage, rectifier current, rectifier temperature, system capacity, battery parameters, and circuit breaker status. Alarm and warning notifications are indicated by front panel LEDs, and through potential free alarm contacts that allow remote signaling. External monitoring of alarms is accomplished through a USB or RS232 port using PC-based PowCom™ software. The ACC has an Ethernet port allowing control over a TCP/IP network and web based support. Alarms can be mapped via SNMP traps to customer OSS platforms such as HP Openview™ To meet individual site requirements, the ACC contains a Programmable Logic Unit that can be used to monitor and control specified requirements. This allows individual alarm routing and logic operations to be set as actions, alarms to be triggered, and outputs to be activated based on internal and external signal monitoring, comparing, and processing.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
MCD10062 Rev. 1.1, 2-Oct-08 Page 2 of 2 www.power-one.com
ACC Controller Module Data Sheet
* Pending system configuration ** Pending rectifier used
Input Voltage 18-60 VDC
Current <200 mA
Interface Display Optional 3x16 character LCD
Internal Communication
RS485 Data Bus (64 modules max.)
External Communication
USB or RS232* interface for remote control via modem or directly from a PC with PowComTM software. Ethernet port allowing monitoring and control over a TCP/IP network. Web browser support + SNMP.
Indications Green LED - Power ON Yellow LED - System warning Red LED - System alarm
Signal Input Battery current reading (via shunt) Output voltage reading Analog inputs for battery symmetry reading or general use Battery temperature sensor Load fuse failure Battery fuse failure 2 x Digital inputs
Signal Outputs LVD/PLD disconnect (max 4*) LVD/PLD reconnect 2 x Digital outputs
Software Site upgradeable by Flash memory
Alarms Alarm Contacts 4 (max 10*) potential free change-over
alarm contacts Alarms Low/High Voltage Alarms
Batteries on Discharge Overvoltage Shutdown Alarm High Load (Rectifier Capacity Alarm) Battery Test Failure Battery Symmetry Alarm Mains Failure Module Alarm Urgent Module Alarm Battery Fuse Failure Load Breaker Failure Battery/Load Disconnect Alarm High/Low Battery Temperature Alarms Temperature Probe Failure High/Low AC Voltage** 16 x Additional User Definable Alarms
Other Technical Data Dimensions (WxHxD)
Actual dimensions vary with respect to the system used. Contact Sales.
Weight 0.2kg (0.44 lb) Operating Temp. -40 to +70 °C
Storage Temp. -40 to +85 °C Safety IEC 60950-1, UL60950-1,
& CSA-C22.2 No. 60950-1-03 EMC EN 61000-6-2, EN 61000-6-3,
EN 300 386-2 Environment Storage:
Transport: Operation:
ETS 300 019-2-1 ETS 300 019-2-2 ETS 300 019-2-3
Battery Management Battery Disconnection
Allows voltage controlled disconnection of batteries.
Boost Charging Manual time controlled or automatic boost charging with adjustable time and voltage levels.
Battery Tests Automatic or manual testing of batteries up to six times per year with a 10 test memory. Variables include test duration and end voltage. Battery discontinuance test to ensure battery connection.
Enhanced Battery Monitoring
Monthly logging of essential battery parameters including temperature, temperature hours, current, charging voltage and symmetry voltage, Data logged for 5 years.
Site Logs System tools developed to assist site management. Daily peak load and statistic logs available.
Symmetry Measurement
Optional tool that measures batteries for early detection of thermal runaway.
Temperature Compensation Charging
Allows continuous adjustment of output voltage according to battery temperature. Features include adjustable compensation factor and separate thresholds for high temperature alarms.
Load Shedding (PLD)
Optional feature that allows voltage or time controlled disconnection of non-essential load.
NUCLEAR AND MEDICAL APPLICATIONS - Power-One products are not designed, intended for use in, or authorized for use as critical components in life support systems, equipment used in hazardous environments, or nuclear control systems without the express written consent of the respective divisional president of Power-One, Inc. TECHNICAL REVISIONS - The appearance of products, including safety agency certifications pictured on labels, may change depending on the date manufactured. Specifications are subject to change without notice.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
MCD10014 Rev. 1.1, 14-Sep-07 Page 1 of 4 www.power-one.com
AspiroTM Shelf System Data Sheet
Description Aspiro DC power systems offer a range of solutions for diverse applications such as broadband access, cable head ends, micro/pico BTS Cells, Enterprise, E911, and GSM-R. Aspiro uses highly-efficient, dense, and reliable XR04.48 & XR08.48 rectifier modules and is highly-adaptable to provide a complete solution for today's global applications. Its system management is accomplished via a pluggable PCC system controller, complete with remote accessing functionality with an Ethernet, web server, and SNMP interface. Highly-flexible distribution options offer the optimum 1U or 2U shelf solution for space-critical applications. In addition, installation within compact environments is made simple and includes reduced-depth distribution shelves catering for rear or side cable connection.
Features • RoHS compliant for all six substances
• 1RU and 2RU height solutions
• Wide AC input; 85 to 300VAC
• Wide operating temperature range -40 °C to +75 °C
• Ethernet interface
• Simple installation
• Designed for 300 mm deep ETSI cabinets
• Rear or side cable connection options
• Various fuse options
• International standards compliance
XR04.48 and XR08.48 Rectifier Modules
PCC Supervision Module
Aspiro Shelf System
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
MCD10014 Rev. 1.1, 14-Sep-07 Page 2 of 4 www.power-one.com
AspiroTM Shelf System Data Sheet
System Components
XR04.48/XR08.48 Rectifier Modules
PCC Supervision Module
The Aspiro shelf system utilizes plug-in rectifier modules based upon a soft-switching approach. Features include wide input operating range, wide operating temperature, full self-protection and three LEDs for immediate rectifier status indication. Refer to the XR04.48/XR08.48 Rectifier Module data sheet for further information.
18.2 A 837 W 48 VDC XR08.48
9.1 A 420 W 48 VDC XR04.48
Current (max)
Power (max)
Voltage Model
The PCC Supervision Module is an advanced system supervisor for complete local and remote system monitoring. PCC features include: • Menu guided operation
• Battery management including battery testing
• Ethernet/web server and SNMP Interface
• Low voltage disconnect
• Hot-pluggable unit
• Temperature compensation
• Battery Symmetry measurement
• User-programmable alarm routing
Refer to PCC Controller data sheet for further details.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
MCD10014 Rev. 1.1, 14-Sep-07 Page 3 of 4 www.power-one.com
AspiroTM Shelf System Data Sheet
1U Combination Shelf Option (1.6 kW)
2U Shelf Option (2.4 kW)
2U Shelf Option (3.2 kW)
Distribution Modules The Aspiro power system uses front access fuse distribution modules in order to allow in-service replacement of fuses. The product can be supplied with a variety of fuse arrangements.
• AC Connection – Rear or side screw terminals connection for simple field installation • 19”, 23” or ETSI mounting available • Flexible Connection – Rear or side connection of load circuits and ancillary signals
Additional Features
Aspiro Shelf Options
System Components (Continued)
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
MCD10014 Rev. 1.1, 14-Sep-07 Page 4 of 4 www.power-one.com
AspiroTM Shelf System Data Sheet
Model
Options
1U Combi-Shelf 2U Power System 2U Power System
Output
Output Power (max. per system) 1.6 kW 2.4 kW 3.2 kW
Rectifier Modules (max. per system)
2x 400 W Rectifier or
2x 800 W Rectifier
3x 400 W Rectifier or
3x 800 W Rectifier
4x 400 W Rectifier or
4x 800 W Rectifier
Input
AC Input Connections (230 VAC)
Single Phase
Single Phase or
3-Phase
Single Phase or
3-Phase
Distribution
Battery Fuse (Qty)
1 2 2
Load Fuse (Qty) (max.)
4 15 9
Load GMT Fuse (Qty)
N/A 10 10
Battery
Low Voltage Battery Disconnect (LVBD) Yes
Temperature Compensation Yes
Battery Symmetry Connections 1 2 2
Mechanical
Dimensions W x H x D (mm)
19”/ETSI/23” x 44.45 x 280 19”/ETSI/23” x 88.9 x 280 19”/ETSI/23” x 88.9 x 280
Mounting
19” / ETSI / MID-MOUNT 19” / ETSI / MID-MOUNT 19” / ETSI / MID-MOUNT
Cable Entry
Rear Rear Rear
Options
Partial Load Disconnect (PLD) N/A N/A Yes Yes
NUCLEAR AND MEDICAL APPLICATIONS - Power-One products are not designed, intended for use in, or authorized for use as critical components in life support systems, equipment used in hazardous environments, or nuclear control systems without the express written consent of the respective divisional president of Power-One, Inc. TECHNICAL REVISIONS - The appearance of products, including safety agency certifications pictured on labels, may change depending on the date manufactured. Specifications are subject to change without notice.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
AUG 17, 2006 Page 1 of 2 www.power-one.com
CMP 3.48 Rectifier Module
Features • RoHS lead-solder-exempt compliant • 208/240 VAC input • 48 VDC output • Input overvoltage disconnection • Thermal protection, with derating • Active load sharing • Hot-swappable • Up to 91% efficient • Natural convection cooling • Low weight • International standards compliance
Description The Power-One CMP 3.48, for use in the Galero™ Series of power systems in our convection cooled rectifier series, provides advanced resonance switch mode technology (softswitching). An onboard microcontroller and an RS 485 data bus provide monitoring of basic functions, status, and identification information to the system controller (GMC). The CMP 3.48 rectifier module is optimized for telecom applications and is designed to work in numerous subrack/shelf configurations incorporating the GMC controller and varying distribution options. NUCLEAR AND MEDICAL APPLICATIONS - Power-One products are not designed, intended for use in, or authorized for use as critical components in life support systems, equipment used in hazardous environments, or nuclear control systems without the express written consent of the respective divisional president of Power-One, Inc.
TECHNICAL REVISIONS - The appearance of products, including safety agency certifications pictured on labels, may change depending on the date manufactured. Specifications are subject to change without notice.
Galero Power System
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
AUG 17, 2006 Page 2 of 2 www.power-one.com
CMP 3.48 Rectifier Module
Input Model CMP 3.48
Input Voltage 205-240V AC +10% single phase, 44-66 Hz (185-160V at reduced power output)
Current (max.) <2.5 A
Soft Start <12 A peak max. 5 ms
Harmonics
EN 61000-3-2 (Power factor > 0.98 typical)
Surge Immunity
EN 61000-4-5
Fuse T 3.15A
Connection DIN 41612F
EMC EN 61000-6-2, EN 61000-6-3, FCC Part 15 Class B
Output Model CMP 3.48
Output Voltage
45-56 VDC
Power (max.) 364 W @ 56 VDC 354 W @ 54.5 VDC
Current (max.) 6.5 A
Efficiency (at 55-100% load)
>91%
Tolerance Vout +/- 1.0%
Transient Response
+/- 5% at load variation 10-90% or 90-10% recovery time 10 ms
Load Sharing Typical <5% of nominal current
Ripple <100 mV p-p (BW. 30 MHz)
Psophometric <2 mV, according to CCITT norms
Connection FCI power connector™
EMC EN 61000-6-2, EN 61000-6-4
Mechanical Dimensions (WxHxD)
43 x 120.8 x 264.5 mm (1.7 x 4.75 x 10.4 in.)
Weight 1.1 kg (2.4 lb)
Cooling Natural convection
Insulation Reinforced insulation, tested at: 4.25 kVDC primary-secondary 2.12 kVDC primary-ground 0.75 kVDC secondary-ground
Enclosure IP20
Mounting Up to 7 modules per shelf Other Technical Data Safety EN 60950
UL 1950 and IEC60950 Class 1 CSA C22-2 No. 950
Protection Short-circuit proof, automatic current limiting, selective shutdown of modules at excessive output voltage. Thermal protection reduces the output power at environmental temperatures above maximum level. Shut down at >75 °C. Input over-voltage disconnecting at >265 VAC with automatic reset at >250VAC.
Indications Green LED Red LED
Power ON High output voltage/ shut down, Low voltage/ module failure
Audible Noise
<35 dBA
Operating Temperature
-25 to +55 °C up to 2000 m -25 to +45 °C above 2000 m
Storage Temperature
-40 to +85 °C
Radiated EMC EN 61000-6-2, EN 61000-6-3, FCC Part 15, Class B
Environment Storage: Transport: Operation: Earthquake:
ETS 300 019-2-1 ETS 300 019-2-2 ETS 300 019-2-3 GR 63 Core Zone 4
*Average performance for a single module.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
MCD10086 Rev. 1.1, 2-Oct-08 Page 1 of 2 www.power-one.com
FMP16.48 Rectifier Module Data Sheet
Description The Power-One FMP16.48 rectifier provides extremely reliable DC power in the highest possible density. This rectifier module incorporates the latest in power monitoring solutions using an internal microprocessor that gives up-to-the-second updates to the system controller and adjacent rectifiers. This guarantees tightly controlled load sharing among rectifiers and provides status and identification information to the controller. At only four rack units high, these compact rectifiers provide up to 1600 watts and allow up to 10 rectifier modules in a 23-inch subrack or eight modules in a 19-inch subrack. Designed with diversity in mind, the FMP16.48 rectifier is able to operate in a complete range of indoor and outdoor applications.
23-inch PPR16 Subrack
Features • RoHS lead free solder and lead solder
exempted products are available • Compact 4-rack unit height
• 717 W/L (11.75 W/in³)
• 205/240 VAC single-phase input
• Input overvoltage disconnection
• Thermal protection
• Hot-swappable
• No adjustments required
• 93,5% typical efficiency
• Active and droop current sharing
• International standards compliance
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
MCD10086 Rev. 1.1, 2-Oct-08 Page 2 of 2 www.power-one.com
FMP16.48 Rectifier Module Data Sheet
NUCLEAR AND MEDICAL APPLICATIONS - Power-One products are not designed, intended for use in, or authorized for use as critical components in life support systems, equipment used in hazardous environments, or nuclear control systems without the express written consent of the respective divisional president of Power-One, Inc. TECHNICAL REVISIONS - The appearance of products, including safety agency certifications pictured on labels, may change depending on the date manufactured. Specifications are subject to change without notice.
Input
Model FMP16.48 Input Voltage 100-240 VAC ±15% single
phase (44-66 Hz) (185-85 V at derated output power)
Current (max.) <10 A
Soft Start <13A /1ms
Harmonics
EN 61000-3-2 (Power factor > 0.98 typical)
Surge Immunity EN 61000-4-5
Fuse 2 x F 12.5A (line & neutral)
Connection FCI 51939-066
EMC EN 61000-6-2, EN 61000-6-3, FCC Part 15 Class B
Output Model FMP16.48
Output Voltage 45-57 VDC
Power (max.) 1600 W @ 45-57 VDC
(input >185 VAC)
675 W @ 45-57 VDC
(input 185 - 85 VAC)
Current (max.) 32 A
Efficiency (at 40-90% load)
>93%, typical 93.5%
Tolerance Vout ± 1.0%
Transient Response
± 5% at load variation
10-90% or 90-10%
recovery time 50 ms
Load Sharing <5% of nominal current
Ripple <100 mV p-p (BW 30 MHz)
Psophometric <2 mV, according to CCITT norms
Connection FCI 51939-066
EMC EN 61000-6-2, EN 61000-6-4
Mechanical Dimensions (WxHxD)
51 x 177 x 280 mm (2.0 x 6.97 x 11.02 in)
Weight 2.2 kg (4.85 lb)
Cooling Fan-cooled, speed-controlled, and alarmed
Insulation Reinforced insulation, tested at:
4.25 kVDC primary-secondary 2.12 kVDC primary-ground 0.75 kVDC secondary-ground
Enclosure IP20
Mounting 19in/ 4U subrack up to 8 modules 23in/ 4U subrack up to 10 modules
Other Technical Data Safety EN 60950-1
UL 60950-1, IEC60950-1, and CSA C22.2 No. 60950-1
Protection Short circuit proof, automatic current limiting, selective shutdown of modules at excessive output voltage. Thermal protection reduces the output power at environmental temperatures above maximum level. Shut down at >75 °C with an automatic restart. Input overvoltage disconnecting at >275 VAC with automatic reset at >260 VAC.
Alarms High output voltage/ shutdown, Low voltage/ module failure. Each alarm has an LED indicator on the front panel.
Indications Green LED Yellow LED
Red LED
Power ON Current limit/ thermal protection. Com. failure (flashing) Module failure/ high output voltage/ shutdown
Audible Noise
<60dBA
Operating Temperature
-40 to +65 °C up to 2000 m -40 to +55 °C above 2000 m
Storage Temperature
-60 to +85 °C
Radiated EMC EN 61000-6-2, EN 61000-6-3, FCC Part 15, Class B
Environment Storage: Transport: Operation: Earthquake:
ETS 300 019-2-1 ETS 300 019-2-2 ETS 300 019-2-3 GR 63 Core Zone 4
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
MCD10087 Rev. 1.1, 2-Oct-08 Page 1 of 2 www.power-one.com
FMP 18.48 Rectifier Data Sheet
Description The FMP18.48 rectifier incorporates resonance-soft-switching technology to reduce component stresses, providing increased system reliability and a best-in-class efficiency. With a wide-input operating voltage range of 84-300 VAC and linear derating of output power with input voltage, the FMP18.48 maximizes power availability in demanding utility power environments. These compact rectifiers support up to eight 4U high rectifier units delivering up to 9 kW of power while the 23” shelf can deliver up to 18 kW of power. A wide variety of distribution options are available to provide the maximum system flexibility for a wide range of communications applications that demand efficiency, reliability, and flexibility including wireless base stations, remote switches, and broadband access.
23-inch PPR18 Subrack
Features • RoHS compliant for all six substances
• Leading power density of 807 W/L (13.2 W/in³)
• Rugged Input voltages of 84-300 VAC with linear power derating
• Input overvoltage disconnection
• Thermal protection
• Hot-swappable
• 93% typical efficiency
• International standards compliance
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
MCD10087 Rev. 1.1, 2-Oct-08 Page 2 of 2 www.power-one.com
FMP 18.48 Rectifier Data Sheet
NUCLEAR AND MEDICAL APPLICATIONS - Power-One products are not designed, intended for use in, or authorized for use as critical components in life support systems, equipment used in hazardous environments, or nuclear control systems without the express written consent of the respective divisional president of Power-One, Inc. TECHNICAL REVISIONS - The appearance of products, including safety agency certifications pictured on labels, may change depending on the date manufactured. Specifications are subject to change without notice.
Input
Model FMP 18.48 Input Voltage 100-240 VAC ±15% single
phase (44-66 Hz) up to 300VAC (185-85 V at derated output power)
Current (max.) <11.5 A
Soft Start <13A /1ms
Harmonics
EN 61000-3-2 (Power factor > 0.98 typical)
Surge Immunity EN 61000-4-5
Fuse 2 x F 12.5A (line & neutral)
Connection FCI 51939-066
EMC EN 61000-6-2, EN 61000-6-3, FCC Part 15 Class B
Output Model FMP 18.48
Output Voltage 45-58 VDC
Output Power Characterisitc (50-56 VDC)
Po max = 1800
Linear derate: 1800 to 1050 W
Current (max.) 38 A
Efficiency (at 40-90% load)
>92.5%, typical 93%
Tolerance Vout ± 1.0%
Transient Response
± 5% at load variation
10-90% or 90-10%
recovery time 50 ms
Load Sharing <5% of nominal current
Ripple <100 mV p-p (BW 30 MHz)
Psophometric <2 mV, according to CCITT norms
Connection FCI 51939-066
EMC EN 61000-6-2, EN 61000-6-4
Mechanical Dimensions (WxHxD)
51 x 177 x 280 mm (2.0 x 6.97 x 11.02 in)
Weight 2.2 kg (4.85 lb)
Cooling Fan-cooled, speed-controlled, and alarmed
Insulation Reinforced insulation, tested at:
4.25 kVDC primary-secondary 2.12 kVDC primary-ground 0.75 kVDC secondary-ground
Enclosure IP20
Mounting 19in/ 4U subrack up to 8 modules 23in/ 4U subrack up to 10 modules
Other Technical Data Safety EN 60950-1
UL 60950-1 and IEC 60950-1 CSA C22.2 No. 60950-1
Protection Short circuit proof, automatic current limiting, selective shutdown of modules at excessive output voltage. Thermal protection reduces output power at environmental temperatures above maximum level. Shut down at >70 °C with an automatic restart. Input overvoltage disconnecting at >310 VAC with automatic reset at >=300 VAC.
Alarms High output voltage/ shutdown, Low voltage/ module failure. Each alarm has an LED indicator on the front panel.
Indications Green LED Yellow LED
Red LED
Power ON Fan pre-warning / thermal derating. Com. failure (flashing) Module failure/ high output voltage/ shutdown
Audible Noise
<60 dBA
Operating Temperature
-40 to +55 °C up to 2000 m -40 to +45 °C above 2000 m
Storage Temperature
-60 to +85 °C
Radiated EMC EN 61000-6-2, EN 61000-6-3, FCC Part 15, Class B
Environment Storage: Transport: Operation: Earthquake:
ETS 300 019-2-1 ETS 300 019-2-2 ETS 300 019-2-3 GR 63 Core Zone 4
85V 130V 185V 300V
750W
1050W
1800W
85V 130V 185V 300V
750W
1050W
1800W
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
MCD10064 Rev. 1.5 Page 1 of 2 www.power-one.com
FMP25.48 Rectifier Module Data Sheet
Description The FMP25.48 rectifier incorporates resonant technology to reduce component stresses, providing increased system reliability and a best-in-class efficiency. The rectifier features a wide input operating voltage range to maximize power availability within demanding utility power environments. These compact rectifiers support up to 12.5kW in a 1RU 23” shelf. A wide variety of distribution options are available to provide the maximum system flexibility for a wide range of communications applications that demand efficiency, reliability, and flexibility including wireless base stations, remote switches, and broadband access.
Features • Leading power density of up to 27 W/in3 • Rugged input voltage range of 90-300 VAC • Thermal protection • Hot-swappable • 92.5% typical efficiency • International standards compliance
Typical Configuration 25kW in 23”, 6RU with Controller
Load & Battery Distribution 10kW in 19", 5RU
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
MCD10064 Rev. 1.5 Page 2 of 2 www.power-one.com
FMP25.48 Rectifier Module Data Sheet
Input
Model FMP25.48 Nominal: 100-240V AC Permitted variation: 85-300V AC
Input voltage
Derated Output: 85-180V AC
Current (max.) <18A Soft Start ETSI ETS 300 132-1 Harmonics EN 61000-3-2
Power Factor > 0.98 Typical Surge immunity EN61000-4-5 Fuse Two 25A Fast Blow (Live &
Neutral) EMC EN61000-6-2, EN6100-6-3
FCC Part 15 Class B Output
Output voltage 46-57 VDC Output power (50-56 VDC)
Po Max = 2500W
Efficiency 92.5% Tolerance Vout ± 1.0% Transient response ±5% at load variation 10-90%
or 90-10% recovery time 50 ms
Load sharing <5% of nominal current Ripple <100mV p-p (BW 20 MHz) Psophometric <2mV, according to CCITT norms EMC EN 61000-6-2, EN 61000-6-4
Mechanical Data Dimensions 107 x 337 x 40mm (WxDxH) Weight 2 kg Cooling Fan-cooled,
speed controlled 4.25 kVDC primary-secondary 2.12 kVDC primary-ground
Insulation
0.2 kVDC secondary-ground Enclosure IP20 Mounting 19in/ 1U subrack up to
4 modules
Other Technical Data Safety UL 60950-1/ CAN/CSA-C22.2
No. 60950-1-03, 1st Ed. EN60950-1: 2006 IEC 60950-1:2001
Protection Short circuit proof, automatic current limiting, selective shutdown of modules at excessive output voltage. Thermal protection.
Alarms High output voltage/ shutdown, Low voltage/ module failure.
Indicators Green LED Power ON Yellow LED Current limit, thermal protection Com. failure flashing Red LED Module failure/ high output voltage/ shutdown
Audible noise <60 dBA Operating temperature
-40 ˚C to +55 °C up to 2000 m Reduced spec -40 ˚C to -20 ˚C Derated output power 55 C˚ to 75 ˚C For 3000m altitude derate by 5 ˚C
Storage temperature -60 to +85°C Environment Storage: ETS 300 019-2-1
Transport: ETS 300 019-2-2 Operation: ETS 300 019-2-3 Earthquake: GR 63 Core Zone 4
NUCLEAR AND MEDICAL APPLICATIONS - Power-One products are not designed, intended for use in, or authorized for use as critical components in life support systems, equipment used in hazardous environments, or nuclear control systems without the express written consent of the respective divisional president of Power-One, Inc. TECHNICAL REVISIONS - The appearance of products, including safety agency certifications pictured on labels, may change depending on the date manufactured. Specifications are subject to change without notice.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
AUG 18, 2006 Page 1 of 2 www.power-one.com
FMP 32.48 Rectifier Module
Features • RoHS lead free and lead-solder-exempt
products are available • 697 W/L (11.42 Watts/in3) • Front or mid-mount • 85 to 276 VAC single-phase input • Input overvoltage disconnection • Thermal protection • Hot-swappable • No adjustments required • 93,5% typical efficiency • International standards compliance
Description The Power-One FMP 32.48 rectifier provides extremely reliable DC power in the highest possible density. The module incorporates the latest in power monitoring solutions using an internal microprocessor that gives up-to-the-second updates to the system controller and adjacent rectifiers. This guarantees tightly controlled load sharing among rectifiers and provides status and identification information to the controller. At only four rack units high, these compact rectifiers provide up to 3200 watts and allow up to five rectifier modules in a 23-inch subrack or four modules in a 19-inch subrack. Designed with diversity in mind, the FMP 32.48 rectifier is able to operate in a complete range of indoor and outdoor applications. NUCLEAR AND MEDICAL APPLICATIONS - Power-One products are not designed, intended for use in, or authorized for use as critical components in life support systems, equipment used in hazardous environments, or nuclear control systems without the express written consent of the respective divisional president of Power-One, Inc.
TECHNICAL REVISIONS - The appearance of products, including safety agency certifications pictured on labels, may change depending on the date manufactured. Specifications are subject to change without notice.
23-inch Forza Subrack
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
AUG 18, 2006 Page 2 of 2 www.power-one.com
FMP 32.48 Rectifier Module
Input Model FMP32.48
Input Voltage 2 separate inputs, each at 100-240 VAC ±15% single phase (44-66 Hz) (185-85V at de-rated output power)
Current (max.) <2 x 10 A
Soft Start <2 x 13 A/1 ms
Harmonics
EN 61000-3-2 (Power factor > 0.98 typical)
Surge Immunity EN 61000-4-5
Fuse 4 x F 12.5A (line & neutral)
Connection FCI 51939-066
EMC EN 61000-6-2, EN 61000-6-3, FCC Part 15 Class B
Output Model FMP 32.48
Output Voltage 45-57 VDC
Power (max.) 3200 W @ 50-57 VDC (input >185 VAC) 1350 W @ 50-57 VDC (input 185 - 85 VAC)
Current (max.) 64 A
Efficiency (at 40-90% load)
>93%, typical 93,5%
Tolerance Vout +/- 1.0%
Transient Response
+/- 5% at load variation 10-90% or 90-10% recovery time 50 ms
Load Sharing <5% of nominal current
Ripple <100 mV p-p (BW. 30 MHz)
Psophometric <2 mV, according to CCITT norms
Connection FCI 51939-066
EMC EN 61000-6-2, EN 61000-6-4
MechanicalDimensions (WxHxD)
105 x 177 x 280 mm (4.14 x 6.97 x 11.02 in)
Weight 4.2 kg (9.26 lb)
Cooling Fan cooled, speed controlled, and alarmed
Insulation Reinforced insulation, tested at: 4.25 kVDC primary-secondary 2.12 kVDC primary-ground 0.75 kVDC secondary-ground
Enclosure IP20
Mounting 19 in/ 4U subrack up to 4 modules 23 in/ 4U subrack up to 5 modules
Other Technical Data Safety EN 60950
UL 1950 and IEC60950 CSA C22-2 No. 950
Protection Short-circuit proof, automatic current limiting, selective shutdown of modules at excessive output voltage. Thermal protection reduces the output power at environmental temperatures above maximum level. Shut down at >75 °C with an automatic restart*. Input over-voltage disconnecting at >275 VAC with automatic reset at >260 VAC.
Alarms High output voltage/ shutdown, Low voltage/ module failure. Each alarm has an LED indicator on the front panel and a common potential free contact for external signaling.
Indications Green LED Yellow LED Red LED
Power ON Current limit/ thermal protection. Com. failure (flashing) Module failure/ high output voltage/ shutdown
Audible Noise <60 dBA
Operating Temperature
-40 to +65 °C up to 2000 m -40 to +55°C above 2000 m
Storage Temperature
-60 to +85 °C
Radiated EMC EN 61000-6-2, EN 61000-6-3, FCC Part 15, Class B
Environment Storage: Transport: Operation: Earthquake:
ETS 300 019-2-1 ETS 300 019-2-2 ETS 300 019-2-3 GR 63 Core Zone 4
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Features• High reliability• Simple installation and operation• Natural convection cooling - no fans• RS232 interface for remote operation• Form “C” dry alarm contacts• Intelligent battery management• Pluggable controller and DC distribution
modules• Optional Ethernet (SNMP compatible) interface
module • International standards compliance
DescriptionThe Galero™ Power System provideslarge power system features in cost-effective, rack-mounted form factors.These power solutions providerectification, control and powerdistribution all in one compact systemwhile offering extensive local and remotepower system and battery monitoring.
System management is accomplishedthrough the system controller (GMC).Status indication is made via LED’s, whiledetailed information and remote operationare accomplished through the PC-basedPowComTM software package.
Note: All specifications are subject to change without notification.
Input
Output
Mechanical
Options
Features
Battery
Model Galero 1750 Galero 2450
Input230/400V AC 3-phase205-240V AC 1-phaseSite configurable
230/400V AC 3-phase205-240V AC 1-phaseSite configurable
Inputs (max.) Single input Single input
Rectifier Modules (max.) 5 7
Battery Outputs 1 2 1 2
Load Outputs 10 9 3 2
48V DC Version Yes Yes
Supervision GMC GMC
Battery Symmetry Inputs (max.) 2 2
Low Voltage BatteryDisconnection (LVBD) Yes Yes
Temp. Comp. Charge Yes Yes
Dimensions (WxHxD) 483x125x280mm 483x125x280mm
Mounting 19in., ETSI 19in., ETSI
Cable Entry AC - RearDC and signals -Top
AC - RearDC and signals -Top
Temp. Comp. Charge Yes Yes
Battery SymmetryMeasurement Yes Yes
Ethernet Network Interface Yes Yes
Partial Load Disconnect N/A N/A
Integrated Surge Arrestors N/A N/A
Galero™ Power System
www.power-one.comwww.power-one.com11V0005-033 Galero SY V3.0 Rev. C
Galero™ Power SystemShelf SystemsShelf Systems
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Rectifier Features
Model Voltage Power(max.)
Current(max.)
CMP 3.48 48V DC 364W 6.5A
The Galero Shelf System utilizes plug-in rectifiermodules based on a soft-switching approach.Features include 2xLED for rectifier status indication,thermal protection with de-rating and input over-voltage disconnection with automatic reset.
• Advanced system monitoring• RS232 interface for remote operation• Battery management and testing• Automatic testing• Low voltage battery disconnect (LVBD)• Temperature compensation• Battery symmetry measurement• Monthly logging of battery parameters including “temperature-hours”• Site programmable Flash EPROM• Programmable alarms• Programmable logic circuit• Optional Ethernet interface through SNMP and/or TCP/IP
GMC Features
Rectifier Module
Advanced system supervision is accomplished using amicroprocessor based module that allows both local andremote system monitoring.
Supervision Module - GMC
All-in-one 125 mm high shelf system for integration into standard19” or ETSI cabinets. Complete subrack for five rectifier modules, supervision moduleand DC distribution with battery breakers (1-2) and load breakers(9-10).
Galero 1750 System
All-in-one 125 mm high shelf system for integration intostandard 19” or ETSI cabinets. Complete subrack for seven rectifier modules, supervisionmodule and DC distribution including battery breakers (1-2) andload breakers (2-3).
Galero 2450 System
System Configurations System Components
Galero™ Power SystemShelf Systems
www.power-one.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Rectifier Features
Model Voltage Power(max.)
Current(max.)
CMP 3.48 48V DC 364W 6.5A
The Galero Shelf System utilizes plug-in rectifiermodules based on a soft-switching approach.Features include 2xLED for rectifier status indication,thermal protection with de-rating and input over-voltage disconnection with automatic reset.
• Advanced system monitoring• RS232 interface for remote operation• Battery management and testing• Automatic testing• Low voltage battery disconnect (LVBD)• Temperature compensation• Battery symmetry measurement• Monthly logging of battery parameters including “temperature-hours”• Site programmable Flash EPROM• Programmable alarms• Programmable logic circuit• Optional Ethernet interface through SNMP and/or TCP/IP
GMC Features
Rectifier Module
Advanced system supervision is accomplished using amicroprocessor based module that allows both local andremote system monitoring.
Supervision Module - GMC
All-in-one 125 mm high shelf system for integration into standard19” or ETSI cabinets. Complete subrack for five rectifier modules, supervision moduleand DC distribution with battery breakers (1-2) and load breakers(9-10).
Galero 1750 System
All-in-one 125 mm high shelf system for integration intostandard 19” or ETSI cabinets. Complete subrack for seven rectifier modules, supervisionmodule and DC distribution including battery breakers (1-2) andload breakers (2-3).
Galero 2450 System
System Configurations System Components
Galero™ Power SystemShelf Systems
www.power-one.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Features• High reliability• Simple installation and operation• Natural convection cooling - no fans• RS232 interface for remote operation• Form “C” dry alarm contacts• Intelligent battery management• Pluggable controller and DC distribution
modules• Optional Ethernet (SNMP compatible) interface
module • International standards compliance
DescriptionThe Galero™ Power System provideslarge power system features in cost-effective, rack-mounted form factors.These power solutions providerectification, control and powerdistribution all in one compact systemwhile offering extensive local and remotepower system and battery monitoring.
System management is accomplishedthrough the system controller (GMC).Status indication is made via LED’s, whiledetailed information and remote operationare accomplished through the PC-basedPowComTM software package.
Note: All specifications are subject to change without notification.
Input
Output
Mechanical
Options
Features
Battery
Model Galero 1750 Galero 2450
Input230/400V AC 3-phase205-240V AC 1-phaseSite configurable
230/400V AC 3-phase205-240V AC 1-phaseSite configurable
Inputs (max.) Single input Single input
Rectifier Modules (max.) 5 7
Battery Outputs 1 2 1 2
Load Outputs 10 9 3 2
48V DC Version Yes Yes
Supervision GMC GMC
Battery Symmetry Inputs (max.) 2 2
Low Voltage BatteryDisconnection (LVBD) Yes Yes
Temp. Comp. Charge Yes Yes
Dimensions (WxHxD) 483x125x280mm 483x125x280mm
Mounting 19in., ETSI 19in., ETSI
Cable Entry AC - RearDC and signals -Top
AC - RearDC and signals -Top
Temp. Comp. Charge Yes Yes
Battery SymmetryMeasurement Yes Yes
Ethernet Network Interface Yes Yes
Partial Load Disconnect N/A N/A
Integrated Surge Arrestors N/A N/A
Galero™ Power System
www.power-one.comwww.power-one.com11V0005-033 Galero SY V3.0 Rev. C
Galero™ Power SystemShelf SystemsShelf Systems
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
MCD10018 Rev. 1.0 Page 1 of 2 www.power-one.com
GMC Controller Module Data Sheet
NUCLEAR AND MEDICAL APPLICATIONS - Power-One products are not designed, intended for use in, or authorized for use as critical components in life support systems, equipment used in hazardous environments, or nuclear control systems without the express written consent of the respective divisional president of Power-One, Inc.
TECHNICAL REVISIONS - The appearance of products, including safety agency certifications pictured on labels, may change depending on the date manufactured. Specifications are subject to change without notice.
Features User controls and interfaces:
• User-selectable alarm parameters
• 40-event data logging
• Password-controlled environment
• RS232 Interface and Form “C”dry
alarm contacts
• Programmable alarm routing
• Programmable logic unit
• Intelligent battery management:
• Temperature compensation with programmable
compensation factor
• Automatic and manual load testing
• Battery voltage and symmetry monitoring
• Capacity testing
• Low-voltage disconnect
• Optional plug-in Ethernet interface (PNI module)
Description The Galero™ Microprocessor Controller (GMC) from Power-One provides comprehensive monitoring and control of the Galero Power System. This digital controller monitors total system conditions including DC voltage, rectifier current, rectifier temperature, system capacity, battery parameters, and circuit breaker status. The GMC enables data storage of system configuration information such as battery type, installation date, and system commission date. Visual notification of alarm and warning conditions are indicated by front panel LEDs, while descriptions of the alarms are provided through RS232 communication using PC-based PowCom™ software package. To meet individual site requirements, the GMC contains a Programmable Logic Unit that can be programmed to monitor and control specified requirements. This allows actions to be set, alarms to be triggered, and outputs to be activated based on internal and external signal monitoring, comparing, and processing.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
MCD10018 Rev. 1.0 Page 2 of 2 www.power-one.com
GMC Controller Module Data Sheet
Input Voltage N/A Current <200mA at 48V
Interface Display N/A Internal Communication RS485 data bus External Communication RS232 Serial interface for
remote control from a PC with PowCom software. TCP/IP or SNMP available by using the optional plug-in Ethernet interface (PNI card)
Indications Green LED - Power ON Yellow LED - System Warning Red LED - System alarm
Controls N/A Signal Inputs (via alarm interface)
2 battery symmetry (12V increments) 1 battery temperature sensor 3 analogue inputs for general use 2 digital inputs for general use
Software Site upgradeable through EPROM flash
Language N/A
Alarms Alarm History The last 40 events are saved
and include a time and date stamp.
Alarm Contacts Four potential free changeover alarm contacts. Two open collector outputs for LVD.
Alarms High System Voltage Low System Voltage Load/ Battery Disc. Mains Error DC Fuse Failure Battery Failure Module Failure Battery Temp. Alarm Symmetry Failure Battery Fuse Failure High Load Urgent Module Failure Communication Failure
1* 1* 1* 3* 2* 4* 2* 4* 4* 1* 2* 1* 2*
* All alarms are indicated using an LED . The numbers represent an example of alarm routing: 1) Urgent alarm, 2) Service alarm, 3) Main AC Failure, 4) Battery related failure 16 additional user-defined alarms available.
Other Technical Data Dimensions (WxHxD)
60 x 125 x 250mm (2.4 x 4.9 x 9.8in.)
Weight 0.5kg (1.1lbs.) Operating Temperature
-25 to +55°C
Environment Storage: Transport: Operation:
ETS 300 019-2-1 ETS 300 019-2-2 ETS 300 019-2-3
Battery Management Battery Disconnection
A feature that allows voltage disconnection of batteries.
Boost Charging Manual time controlled or automatic boost charging with adjustable time and voltage levels.
Battery Test Automatic or manual testing of batteries up to four times per year. Variables include: test duration, end voltage, Ah, and allowable symmetry variation.
Symmetry Measurement
Optional tool that measures batteries for early detection of thermal runaway. Allows for separate measurements of up to 2 parallel battery branches, each divided into four blocks.
Temperature Compensation Charging
Allows continuous adjustment of output voltage according to battery temperature. Feature includes adjustable compensation factor and separate thresholds for alarms.
PLD N/A Enhanced Battery Monitoring
Monthly logging of essential battery parameters: average/ peak temperature, temp. hours, current, charging voltage and symmetry voltage. Stores parameters for 5 years.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
MCD10063 Rev. 1.0 Page 1 of 2 www.power-one.com
Guardian Power System Data Sheet(Cabinet System)
Guardian modular DC cabinet systems are designed to meet rigid telecom applications with very high reliability and flexibility for future expansion. Rectifier and battery combination cabinets are configurable to allow 12.5kW or 25kW rectifier capacity together with DC distribution, controller and battery backup in a single footprint. Options include battery and load disconnect, AC surge protection and various DC and AC distributions. Ideal for radio base stations, broadband nodes and core sites.
• Powerful - High density (27W/in³) with configurable configurations of 12.5kW or 25kW and 720 Ah battery backup per cabinet
• Connected – State of the art system controller with self-
guided operation. SNMP and web compatible. • Intelligent – Sophisticated management features
extend the battery life and monitor critical site equipment such as HVAC and generators
• Rugged – Design caters for poor grid quality supply
GUARDIAN POWER SYSTEMS
Protecting your network reliability
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
MCD10063 Rev. 1.0 Page 2 of 2 www.power-one.com
Guardian Power System Data Sheet(Cabinet System)
Technical Specification
Mechanical Dimensions 600 x 600 x 1400/1800/2000mm (WxDxH)
(23.6 x 23.6 x 55.12/70.9/78.74”)
Output Voltage -48VDC
Maximum Power 12.5kW / 25kW
Output Current 250 / 500A
Efficiency 92.50%
Rectifier types FMP25.48G
DC Distribution Battery Breakers 1-6 off (max 125A)
1-3 off (max 250A)
Load Breakers 26 x breakers (2-63A) maximum
Battery Capacity Upto 720Ah using 4 x 180Ah strings
AC Input Voltage 1 or 2 x 230VAC 3 phase TN (Δ)
1 or 2 x 400VAC 3 phase IT (Y)
Frequency 47-63Hz
Input Current <18A per rectifier (FMP25)
Power Factor 0.97
Surge Protection Optional
Monitoring & Control Controller ACC or PCC
Alarm relays 4 standard. Option for 10 with ACC
Local Interface 4 x 20 LCD, 4 key menu, USB*/RS232
Remote interface Ethernet / modem with POWCOM software
Visual Indication Green LED – System On
Yellow LED – Message(s)
Red LED – Alarm(s)
External Digital I/O 2 x Inputs, 2 x Outputs (open collector)
Battery Management Symmetry Inputs 6 or 12*
Programmable LVD 1 x 300A or 500A
Programmable PLD Max 1 or 2* x 125A, 200A, 400A.
Connections Battery Connections Battery cable, M8 lugs
AC connection 16mm² (4 AWG) max.
Load breaker connections Negative termination directly from breakers. Common positive from busbar.
Alarm connections 1.5mm² (14 AWG) max.
Compliance EMC EN 300 386
EN 61000-6-3 (Emission)
EN 61000-6-2 (Immunity)
Safety IEC 60950
Environmental Operating Temperature -40°C to +65°C, derating after 55°C
Storage Temperature -40°C to +85°C
*Option for ACC only NUCLEAR AND MEDICAL APPLICATIONS - Power-One products are not designed, intended for use in, or authorized for use as critical components in life support systems, equipment used in hazardous environments, or nuclear control systems without the express written consent of the respective divisional president of Power-One, Inc. TECHNICAL REVISIONS - The appearance of products, including safety agency certifications pictured on labels, may change depending on the date manufactured. Specifications are subject to change without notice
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
MCD10061 Rev. 1.1 Page 1 of 3 www.power-one.com
iBreaker SeriesiB-PDU, Power Distribution Unit Data Sheet
Applications • Telecom
Safety compliance with EN60950, UL60950, CAN/CSA-C22.2 No.60950, for use inside end-use ITE/Telecommunication Equipment only
Model Summary and Ordering Code Model Number Description
3B350010000 10 iB’s in a 2U x 19” rack; in and out rear connectors
Description Based on Power-One’s revolutionary iBreaker, the modular iB-PDU is a configurable distribution unit 19”x2U. The standard configuration distributes two input A+B sources -36Vdc / -60Vdc to 10 users. The electronic circuit breaker assures no bus voltage drop, remote controllability, durability, reliability and a faster response to short-circuit versus electromagnetic breakers.
The iBreaker device measures current, voltage, and energy consumption; then transmits the information via serial link for precise system monitoring. It allows control of tripping conditions and implements low voltage disconnection functionality for load shedding strategies to preserve critical loads. The iBreaker software provides adjustable configurations that maximize system flexibility. Custom configurations are available.
Features • iB-48V series based Power Distribution
Unit, an electronic limiting, interrupting and monitoring device for standard telecom -48V systems
• Up to 10 power users (-48 VDC Input) in a 10A current range.
• Dimensions: 19” x 2U x 121mm, (482.6 x 88 x 121mm)
• Current rating up to 40A+40A • Constant current delay before tripping
allows no bus voltage drop • Programmability of most relevant
parameters and remote control for status and working values via RS232 port
• Easy to replace • Manual ON/OFF/reset with no-lock
pushbutton switch; accidental tripping free
• CE branded • Conformity to the applicable
requirements of CAN/CSA-C22.2. No. 235 (Supplementary Protectors) and UL 1077 (Supplementary Protectors for Use in Electrical Equipment)
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
MCD10061 Rev. 1.1 Page 2 of 3 www.power-one.com
iBreaker SeriesiB-PDU, Power Distribution Unit Data Sheet
Technical Specifications
iBreaker-PDU Characteristics Input Voltage -36 / -60 VDC
( -48 VDC nominal )
Input Current Rating 50 A (line A); 50A (line B)
Double separated input source line available
Filter for each source line
No. of Electronic switches
10
No. of electro-magnetic circuit breakers
2
Power source /breaking capacity
≥ 5 kA
Reverse polarity protection
iB rating 10A
Max current rating (IMax)
10A
Max inrush current (ILimit)
17A x 10 ms
Max current after trip (Istandby)
< 0.1A
Voltage Drop (typ) 0.15V
Short-circuit sense time
≤ 300 µs (followed by 10 ms pre-programmed current limit interval
Current limit delay time
5 ms (custom delay times available)
Protection Latched overcurrent and short-circuit protection; overtemperature protection; system catastrophic fuse present
General Characteristics Dimensions (WxHxD) 19 x 3.46 x 4.76 in
(482.6 x 88 x 121 mm)
Weight 4.5 kg (12.05 lb)
Operating Temperature -5 °C to +55 °C
Durability (no. of on/off switch operations
20,000 operations
MTBF 1,000,000 hours
Cooling Natural convection
Safety Approvals and Marks
EMC, CE Marked
Front Panel 10 bicolor LEDs; red lit when switches are opened/tripped; green lit when switches are closed
Rear Panel Input connectors: 2 x male inlet (3Pins) FM3W3
Output connectors: 10 x AMP p/n 350825-1
Signal connector: 1 x DB-15Pins type
Remote monitor connector: DB-9Pins RS232 with standard grounding point
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
MCD10061 Rev. 1.1 Page 3 of 3 www.power-one.com
iBreaker SeriesiB-PDU, Power Distribution Unit Data Sheet
Mechanical Drawings
NUCLEAR AND MEDICAL APPLICATIONS - Power-One products are not designed, intended for use in, or authorized for use as critical components in life support systems, equipment used in hazardous environments, or nuclear control systems without the express written consent of the respective divisional president of Power-One, Inc. TECHNICAL REVISIONS - The appearance of products, including safety agency certifications pictured on labels, may change depending on the date manufactured. Specifications are subject to change without notice.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
MCD10066 Rev. 1.0 Page 1 of 2 www.power-one.com
iBreaker Series Data SheetiB Family for Intelligent Distribution
Applications • Telecom
Safety compliance with EN60950, UL60950, CAN/CSA-C22.2 No.60950, for use inside end-use ITE/Telecommunication Equipment only
Model Selection
Model
Current Rating (Amps)
iB-48V-5A 5 iB-48V-10A 10 iB-48V-20A 20 iB-48V-30A 30 iB-48V-40A 40 iB-48V-50A 50 iB-48V-60A 60
Features • iB-48V series is an electronic limiting, interrupting
and monitoring device for standard telecom -48V systems Two models for different input (24V & 48V) and output of 230VAC
• Ratings from 5A to 60A • Constant current delay before tripping allows no bus
voltage drop • Serial communication link with programmability of
most relevant parameters and remote reading of status and working values
• Height, width, and mounting holes compatible with commercial electromechanical breakers
• Optional board controller to easily connect to up to 22 breakers
• CE, cCSAus and Kema marks according to EN/UL/CSA 60950 for ITE and Telecommunication Equipment
• Conformity to the applicable requirements of CAN/CSA-C22.2. No. 235 (Supplementary Protectors) and UL 1077 (Supplementary Protectors for Use in Electrical Equipment)
Description iBreaker Series – Electronic Limiting, Interrupting and Monitoring Device Power-One’s revolutionary iBreaker is a totally new product that increases performance and facilitates the design of telecom 48V power systems. The iBreaker outperforms regular electromechanical interrupting devices by delivering a higher level of reliability, consistency and durability in the field. The load is disconnected in a clean way within 200 microseconds avoiding transients on the DC input bus. The iBreaker device measures current, voltage and energy consumption then transmits the information via serial link for precise system monitoring. It allows control of tripping conditions and implements low-voltage-disconnect functionality for load shedding strategies to preserve critical loads. The iBreaker software provides adjustable configurations that maximize system flexibility.
Accessory List & Ordering Codes
Accessory Model
Description
iB-CTR Controller. Controls up to 22 iB’s iB-BS Bus Strip, allows serial I/O
connection to the individual iB; up to 10 iB’s to one iB-CTR
iB-WI I/O Wire to connect the iB to the iB-BS
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
MCD10066 Rev. 1.0 Page 2 of 2 www.power-one.com
iBreaker Series Data SheetiB Family for Intelligent Distribution
Input
Input voltage range -60 VDC to -36 VDC Isolation 1100 Vrms live circuits to
frame. Frame heat sink is floating and can be connected to Earth.
Input UV protection Automatic; programmable -48V to -36V. Factory setting -35.8V ±0.2V
Input OV protection Automatic, programmable. Factory setting -65V ±0.2V
Output
Tripping conditions Time to trip = 10ms max Overload Automatic with current
limitation; programmable Short circuit Automatic with current
limitation Manual ON/OFF Pushbutton; protected
against accidental activation Remote ON/OFF Serial link Overtemperature Automatic
Other Technical Data Display Status bicolor LED and
ON/OFF pushbutton Operating Temperature -5 ºC to 55 ºC; convection
cooling EMI Immunity: EN61000-6-2
Emissions: EN50081-1 MTBF 1,500,000 hours at 30 ºC
min according to Bellcore TR-NWT-000332
Expected Operational Life 35 years min Safety Approvals CE and EN60950 for ITE
and Telecommunications Equipment
Dimensions WxHxD
0.79" x 2.48" x 4.22" (20 x 63 x 107.38mm)
Dimensions are in mm.
NUCLEAR AND MEDICAL APPLICATIONS - Power-One products are not designed, intended for use in, or authorized for use as critical components in life support systems, equipment used in hazardous environments, or nuclear control systems without the express written consent of the respective divisional president of Power-One, Inc. TECHNICAL REVISIONS - The appearance of products, including safety agency certifications pictured on labels, may change depending on the date manufactured. Specifications are subject to change without notice.
Mechanical Drawings
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
APR 12, 2007 Page 1 of 5 www.power-one.com
Magnum REC-J200EH Rectifier Data Sheet12 kW; Low THD
Description
The Magnum REC-J200EH Rectifier is a 12,000-watt electronic three-phase, switch-mode power supply module which provides low total harmonic distortion (THD). Designed for superior performance in telecom, industrial, and IT applications, its reduced size makes it one of the most compact force-cooled rectifiers in service to deliver 200 amps. Measuring 19" wide, 5.2" high, and with a depth of 19.09", this product has a power density in excess of 7 W/in3.
The REC-J200EH's combines a digitally-controlled, active Power-Factor-Correction circuit with an innovative electronic design to achieve electrical efficiencies in excess of 90% and THD below 5%. It offers minimized cost and reduced installation time, and its reliability ensures maximum system uptime for critical applications.
In addition, a "smart" user interface makes remote or local programming and monitoring of all major rectifier parameters easy. Remote computer communications is available through an RS-485 serial connection interface (SCI). The Magnum is UL listed and CSA, CE, IEC, and Broadcast NEBS Level 3 certified.
Magnum Model Selection and Ordering Information
Model Input Voltage
Nominal 3-Phase (Vrms)
Input Frequency Range (Hz)
Factory Set Programmable Output Voltage
(VDC)
Programmable Output Voltage
Adjustment Range (VDC)
Output Current (Amps)
REC-J200EH 380 to 480 47 to 63 -54.5 -40 to -60 200
Applications
• Telecom • IT • Industrial
Please contact Power-One for information regarding Magnum Rack Systems.
Features • Low profile: 3U overall height • High efficiency: > 91% • Active Power Factor Correction: > 0.99 • Total harmonic distortion: < 5% • 3-phase 380-480 V nominal voltage input
(50 or 60 Hz) with no neutral • One phase fault tolerant • Hot pluggable • Input and output circuit breaker on board • Display and control panel • Thermal overload protection with derating • Not available in the U.S.; please contact a
Power-One representative • 19" or 23" shelf-mountable • Lightweight: 50.26 lb (22.8 kg) • Safety standards: EN 60950, CAN/CSA-C22.2 N°
60950-00 / UL 60950
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
APR 12, 2007 Page 2 of 5 www.power-one.com
Magnum REC-J200EH Rectifier Data Sheet12 kW; Low THD
ELECTRICAL SPECIFICATIONS
Input Specifications Parameter Conditions/Description Min. Nom. Max. Units
AC Input Voltage 3-phase, line-to-line. 340 380 to 480
530 Vrms
Input Frequency 47 63 Hz
Line current unbalance between phases
±10 %
Line current harmonics Meets IEC 61000-3-2.
Power Factor Pout > 25%. > 0.99 W/VA
Total Harmonic Distortion (THD)
Pout > 50%. < 5 %
Turn-ON delay 4.5 sec
Input withstanding voltage
≤560 Vrms
Mains connector P4/63-S-PCD from Multi Contact.
Output Specifications Parameter Conditions/Description Min. Nom. Max. Units
Factory set output voltage
54.5 VDC
Output VDC Adjustment Range
Programmable. 40 60 VDC
Ripple BW 20 MHz. Wide band, BW 20 MHz. Psophometric noise CCITT weighted. Electrical noise.
500 100 2 32
mVpp mVrms mVpp dBrnc
Efficiency (92% @ full load, Vin ≥ 360 Vrms). 92 %
Output Voltage Regulation
±0.4 %
Output Current 200 ADC
Thermally derated current limit
Linear derating from 50 ºC to 70 ºC. 220 ADC @ 50 ºC. 110 ADC @ 70 ºC.
Output Power Continuous. 12 kW
Output Power Continuous; 2-phase operation, 1-phase loss. 6 kW
Hold-up time @ 340 Vrms input and full load. 20 ms
Output voltage rise time
500 ms
Output voltage walk in time
10 s
Current sharing <5 %
Output connection Bus bar copper blades.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
APR 12, 2007 Page 3 of 5 www.power-one.com
Magnum REC-J200EH Rectifier Data Sheet12 kW; Low THD
Fault Protection Parameter Conditions/Description Min. Nom. Max. Units
AC Input Overvoltage Protection
530 Vrms
Input Breaker Protection
Internal circuit breaker with mains On/Off switch.
37.5 A
Output Overcurrent Protection
Current limitation: 220 ADC @ Vout ≤54.5 VDC. 200 ADC @ Vout = 60 VDC.
Output Short Circuit Protection
220 ADC, resumes operation when short is removed.
Output Overvoltage Protection
Three levels of protection: Catastrophic OV: 65 VDC hardware latch. Programmable OV: 56 to 66.1 VDC, default 62 VDC, turn-Off, non-latching. Second OV (delayed 100 ms): 60 VDC (SELV) turn-Off and latch.
Output Undervoltage Protection
Adjustable, just alarm indication, constant current behavior down to 0V.
36V
Overtemperature (OT) Protection
Shutdown if ambient temperature exceeds 70 °C; with automatic self-recovery.
Overtemperature driven by fan failure
Shutdown with latch-up.
Overtemperature threshold
70 °C
Output Protection Internal circuit breaker with power switch and mechanical latch.
350 A
Environmental Specifications Parameter Conditions/Description Min. Nom. Max. Units
Operating Temp at Full Load
Linearly derated to 6 kW at 70 ºC. -5 55 ºC
Altitude Operating. Non-Operating.
13K 40K
ASL ft ASL ft
Storage Temp -40 85 ºC
Humidity 85% relative humidity @ 40 ºC, non-condensing.
Output Voltage Temperature Coefficient
0.01% per ºC within rated load.
EMI EN 55022, class B.
Cooling Forced cooling front to rear.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
APR 12, 2007 Page 4 of 5 www.power-one.com
Magnum REC-J200EH Rectifier Data Sheet12 kW; Low THD
Interface Signals/Controls Parameter Conditions/Description Min. Nom. Max. Units
Alarms Optorelay contact: OV, OT, OC, rectifier fail (AC loss, OV, OT, fan failure).
Connection Molex Mini Fit 15-24-9245 or equivalent.
Regulatory & Safety Parameter Conditions/Description Min. Nom. Max. Units
cCSAus EN 60950, CSA-C22.2 No. 60950-00, UL 60950 Approved.
Kema Approved.
CB Report Approval Approved.
CE Mark for LVD Approved.
RoHS Compliant.
Isolation Primary-to-Secondary: 3000 Vrms. Primary-to-Ground: 1500 Vrms. Secondary-to-Ground: 500 Vdc.
Mechanical Specifications Parameter Conditions/Description Min. Nom. Max. Units
Dimensions Depth (inches). 19.09 in
Depth (mm). 484.9 mm
Width (inches). 19.00 in
Width (mm). 482.6 mm
Height (inches). 5.21 in
Height (mm). 132.3 mm
Weight Pounds. 50.26 lb
Kilograms. 22.8 kg
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
APR 12, 2007 Page 5 of 5 www.power-one.com
Magnum REC-J200EH Rectifier Data Sheet12 kW; Low THD
Reliability Parameter Conditions/Description Min. Nom. Max. Units
Calculated MTBF TR-TSY-000332 (excluding fans) 250,000 Hours Mechanical Outline Drawing: NUCLEAR AND MEDICAL APPLICATIONS - Power-One products are not designed, intended for use in, or authorized for use as critical components in life support systems, equipment used in hazardous environments, or nuclear control systems without the express written consent of the respective divisional president of Power-One, Inc.
TECHNICAL REVISIONS - The appearance of products, including safety agency certifications pictured on labels, may change depending on the date manufactured. Specifications are subject to change without notice.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
SEP 15, 2006 revised to OCT 02, 2006 Page 1 of 2 www.power-one.com
MIDI PODS Enclosure Platform Data SheetAdvance Product Release
Description Extend the life of your network with the MIDI PODS enclosure platform, an ideal solution for all wireless, fiber, and transmission networks. The versatile MIDI PODS outdoor enclosure system supports valuable network equipment, backup batteries, and power systems in a range of severe environmental conditions. The MIDI PODS has a flexible and modular design matched with network equipment to provide a low impact solution. The MIDI PODS rugged construction and a thermally-insulated power cabinet with sealed loop heat exchangers or air conditioners ensures network integrity in the most challenging environments. Its naturally-cooled battery cabinet provides a very cost-effective storage platform.
Features • Modular, versatile design allows selection
of various cabinets to suit most applications
• 19” and 23” power cabinet options provide up to 9RU payload to match network equipment requirements
• Matched power and battery cabinets provide a low impact solution; either can serve as a standalone product
• Flexible thermal management solutions matched to load and environmental parameters
• IP55/NEMA 3R protection rating (power cabinet)
• Simple trouble-free installation, operation, and maintenance
NUCLEAR AND MEDICAL APPLICATIONS - Power-One products are not designed, intended for use in, or authorized for use as critical components in life support systems, equipment used in hazardous environments, or nuclear control systems without the express written consent of the respective divisional president of Power-One, Inc.
TECHNICAL REVISIONS - The appearance of products, including safety agency certifications pictured on labels, may change depending on the date manufactured. Specifications are subject to change without notice.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
SEP 15, 2006 revised to OCT 02, 2006 Page 2 of 2 www.power-one.com
MIDI PODS Enclosure Platform Data Sheet Advance Product Release
Electrical 23” 19” Environmental Control DC Power Various DC systems options to
match line & load requirements Heat exchanger Closed loop door mounted,
55 W/K Distribution Circuit breakers & fuse options
available Air conditioners 600 W
2000 BTU @ L35/L35 Mechanical Accessories Power Cabinet Dimensions (WxDxH)
680 x 650 x 800 600 x 600 x 800 Cable bridges Mating with major OEM BTS equipment.
Battery Cabinet Dimensions (WxDxH)
680 x 650 x 800 680 x 650 x 1100
600 x 600 x 800 Cable gland plates Tailored to suit site RF, DC, AC Coaxial
Security Lockable, vandal-proof hinges, multi-point locking mechanism
Heater 900 W
Cable Entry Bottom Service light Power 65 55 Battery 70/95 60
Weight (kg)
Plinth 15 15
Circulating fans For improved battery ventilation and temperature control
Material Aluzinc, powder coated Grounding bars Located in plinth for Mains, DC & RF
Mounting PAD mounted, Installation via lifting eyes
Standards Compliance
Equipment Mounting Safety IEC 950, UL 950 Height 9RU (with 2RU power subrack) Environmental
Protection IP55 (IEC529) / NEMA Type 3R
Distribution • Flexible AC & DC Load
center options
Environmental Management • Sealed loop heat exchangers
or air conditioners ensure network integrity in the most challenging environments.
Flexible Payload Options • Up to 450 Ah batteries • DC Power Systems • AC load centers • 9RU network equipment such
as radio base stations & microwave equipment
Rugged Cabinet Construction • Rugged, thermally insulated
construction • Lockable cabinet including
vandal-proof hinges and multi-point locking mechanism
• A4 document holder
DC Power • Rugged, flexible rectifier
options to match various load & line conditions
• 65 °C operating temperature ensures maximum uptime in high temperature environments
• 93.5% efficiencies reduces thermal loads
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
OCT 26, 2006 revised to FEB 07, 2007 Page 1 of 2 www.power-one.com
PCC Controller Module Data Sheet
Features
• RoHS compliant for all six substances
User controls and interfaces:
• User-selectable alarm parameters • Password controlled environment • RS232 Interface and Form “C” dry
alarm contacts • Programmable alarm routing, logic unit
and analog inputs • Ethernet interface version available
Intelligent battery management:
• Temperature compensation with programmable compensation factor
• Automatic and manual load testing • Battery voltage and symmetry monitoring • Remaining battery capacity
measurement • Low voltage disconnect Description
The Power-One Prime Controller Card (PCC) is a pluggable microprocessor controller that provides monitoring and control for a broad range of Power-One DC Power Systems. The PCC monitors all system parameters including: DC voltage, rectifier current, rectifier temperature, system capacity, battery parameters, and circuit breaker status. Alarm and warning notifications are indicated by front panel LEDs, and through potential free alarm contacts that allow remote signaling. External monitoring of alarms is accomplished through an RS232 port using PC-based PowCom™ software. The PCC has an optional Ethernet port allowing monitoring and control over a TCP/IP network. Alarms can mapped via SNMP traps to customer OSS platforms such as HP Openview™ To meet individual site requirements, the PCC contains a Programmable Logic Unit that can be used to monitor and control specified requirements. This allows individual alarm routing and logic operations to be set as actions, alarms to be triggered, and outputs to be activated based on internal and external signal monitoring, comparing, and processing.
NUCLEAR AND MEDICAL APPLICATIONS - Power-One products are not designed, intended for use in, or authorized for use as critical components in life support systems, equipment used in hazardous environments, or nuclear control systems without the express written consent of the respective divisional president of Power-One, Inc. TECHNICAL REVISIONS - The appearance of products, including safety agency certifications pictured on labels, may change depending on the date manufactured. Specifications are subject to change without notice.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
OCT 26, 2006 revised to FEB 07, 2007 Page 2 of 2 www.power-one.com
PCC Controller Module Data Sheet
Input Voltage 18-30 VDC (+24 V Version)
30-60 VDC (-48 V Version) Current <200 mA at 48 V/ <400 mA at 24 V Interface Display Optional 3x16 character LCD
Internal Communication
RS485 Data Bus (20 modules max.)
External Communication
RS232 Serial interface for remote control via modem or directly from a PC with PowComTM software. Optional Ethernet port allowing monitoring and control over a TCP/IP network and alarm mapping via SNMP traps.
Indications Green LED - Power ON Yellow LED - System warning Red LED - System alarm
Signal Input Battery current reading (via shunt) Output voltage reading 6 x analog inputs for battery symmetry reading or general use 1 x battery temperature sensor 1 x load fuse failure 1 x battery fuse failure
Signal Outputs 1 x LVD disconnect 1 x PLD disconnect 1 x LVD/PLD reconnect 4 x Alarm contact (Form C) 3 x LED 1 x LCD (option)
Software Site upgradeable by EPROM/ Flash
Alarms Alarm Contacts 4 potential free change-over alarm
contacts Alarms Low Voltage Alarm
High Voltage Alarm Batteries on Discharge Overvoltage Shutdown Alarm High Load (Rectifier Capacity Alarm) Battery Test Failure Battery Symmetry Alarm Mains Failure Module Alarm Urgent Module Alarm Battery Fuse Failure Load Breaker Failure Battery/Load Disconnect Alarm High Battery Temperature Alarm Low Battery Temperature Alarm Temperature Probe Failure 16 x Additional User Definable Alarms
Other Technical Data Dimensions (WxHxD)
Actual dimensions vary with respect to the system used. Contact Sales.
Weight 0.2kg (0.44 lb) Operating Temperature
-40 to +70 °C
Storage Temperature
-40 to +85 °C
EMC EN 61000-6-2, EN 61000-6-3, EN 300 386-2
Environment Storage: Transport: Operation:
ETS 300 019-2-1 ETS 300 019-2-2 ETS 300 019-2-3
Battery Management Battery Disconnection
Allows voltage controlled disconnection of batteries.
Boost Charging
Manual time controlled or automatic boost charging with adjustable time and voltage levels.
Battery Test Automatic or manual testing of batteries up to six times per year. Variables include test duration and end voltage.
Symmetry Measurement
Optional tool that measures batteries for early detection of thermal runaway. Allows for separate measurements of up to 6 parallel battery branches using mid-point measurement.
Temperature Compensation Charging
Allows continuous adjustment of output voltage according to battery temperature. Features include adjustable compensation factor and separate thresholds for high temperature alarms.
Load Shedding (PLD)
Optional feature that allows voltage or time controlled disconnection of non-essential load.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
APR 04, 2007 Page 1 of 2 www.power-one.com
PCS Controller Data Sheet
Features • RoHS lead free and lead-solder-
exempted products are available User Controls and Interfaces: • Simple menu-guided operation using
front panel mounted pushbuttons and an LCD
• User-selectable alarm parameters • 40 event data logging • Password controlled environment • Multiple language options • RS232 Interface and Form “C” dry
alarm contacts Intelligent Battery Management • Temperature compensation with
programmable compensation factor • Automatic and manual load testing • Battery voltage and symmetry
monitoring • Capacity testing • Low voltage disconnect • Monthly data logging
Description The Power-One Power Controller System (PCS) provides comprehensive monitoring and control for a broad range of Power-One’s DC power systems. This digital controller monitors total system conditions including DC voltage, rectifier current, rectifier temperature, system capacity, battery parameters and circuit breaker status. The PCS enables data storage of system configuration information such as battery type, installation date and system commission date. In addition, the PCS is capable of monitoring up to 128 rectifiers and 128 sub-controllers within a power system. Visual notification of alarm and warning conditions are indicated by front panel LEDs, while descriptions of the alarms are provided through an LCD or can optionally be accessed remotely using a PC modem, or over a network using an optional Network Interface (PNI) module. To meet individual site requirements, the PCS contains a logic operator that can be programmed to monitor and control specified requirements. This allows actions to be set, alarms to be triggered, and outputs to be activated based on internal and external signal monitoring, comparing and processing. NUCLEAR AND MEDICAL APPLICATIONS - Power-One products are not designed, intended for use in, or authorized for use as critical components in life support systems, equipment used in hazardous environments, or nuclear control systems without the express written consent of the respective divisional president of Power-One, Inc.
TECHNICAL REVISIONS - The appearance of products, including safety agency certifications pictured on labels, may change depending on the date manufactured. Specifications are subject to change without notice.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
APR 04, 2007 Page 2 of 2 www.power-one.com
PCS Controller Data Sheet
Input Voltage 18 - 72 VDC Current <200 mA at 48V, <400 mA at
24V Interface Display 2x20 character LCD with
backlight Internal Communication
RS485 Data Bus for communication with a maximum of 128 rectifiers and 128 sub-controllers
External Communication
RS232 serial interface for remote control from a PC with PowCom software
Indications Green LED - Power ON Yellow LED - System warning message Red LED - System failure message
Controls Four pushbutton controls Signal Collection
Wide range of interface units with analog and digital input/outputs
Software Site upgradeable by EEPROM flash
Language Multiple language options Alarms Alarm History The last 40 events are saved
and include a time and date stamp.
Alarm Contacts 6 potential free change-over alarm contacts. Two open collector outputs for LVD operation.
Alarms High System Voltage Low System Voltage Load/ Battery Disc. Mains Error Distribution Fuse Failure Battery Failure Module Failure Battery Temp. Alarm Symmetry Fault Battery Fuse Failure High Load Battery Fuse Disc. Urgent Module Failure Communication Failure Partial Load Disc.
1* 2* 4* 3* 4* 6* 5* 6* 6* 4* 5* 5* 4* 5* 4*
* All alarms are indicated using an LED and displayed in the LCD. The numbers represent an example of alarm routing. Sixteen additional alarms are available and are configurable by changing the PCS EEPROM.
Other Technical Data Dimensions (WxHxD)
508 x 133 x 57mm (20 x 5.25 x 2.25in.)
Weight 1.6kg (3.5lbs.) Operating Temperature
-25 to +55°C
Storage Temperature
-50 to +85°C
Environment Storage: Transport: Operation:
ETS 300 019-2-1 ETS 300 019-2-2 ETS 300 019-2-3
Battery Battery Disconnection Allows voltage controlled
disconnection of batteries. Boost Charging Manual time controlled or
automatic boost charging with adjustable time and voltage levels.
Battery Test Automatic or manual testing of batteries up to four times per year with a 10 test memory. Variables include: test duration, end voltage, and amount of Ah’s to be discharged during test.
Symmetry Measurement Optional tool that measures batteries for early detection of thermal runaway. Allows for separate measurements of up to 12 parallel battery branches, each divided into four blocks.
Temperature Compensation Charging
Allows continuous adjustment of output voltage according to battery temperature. Features include adjustable compensation factor and separate thresholds for high temperature alarms.
PLD Optional feature that allows voltage or time controlled disconnection of non-essential load.
Enhanced Battery Monitoring
Monthly logging of essential battery parameters, including temperature, temp. hours, current, charging voltage, and symmetry voltage. Parameters are stored for 5 years.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
MCD10069 Rev. 1.0 Page 1 of 2 www.power-one.com
PODS Enclosure Platform Data Sheet
Description Extend the life of your network with the PODS enclosure platform, an ideal solution for all wireless, fiber, and transmission networks. The versatile PODS outdoor enclosure system supports valuable network equipment, backup batteries, and power systems in a range of severe environmental conditions. The PODS flexible and modular design allows cabinets to be paralleled and matched with network equipment. The PODS rugged seismic-rated aluminium construction with direct fan cooling, sealed loop heat exchangers or air conditioners ensures network integrity in the most challenging environments.
Features
• Modular, versatile design allows cabinets to be paralleled
• 27, 40 & 49 RU payload options to match power, battery, and network equipment requirements
• Flexible thermal management solutions matched to load & environmental parameters
• Seismic rated (Zone 4)
• IP55/NEMA 3R protection rating
• Flexible top and bottom cable entry ports facilitate cable routing to adjoining equipment
NUCLEAR AND MEDICAL APPLICATIONS - Power-One products are not designed, intended for use in, or authorized for use as critical components in life support systems, equipment used in hazardous environments, or nuclear control systems without the express written consent of the respective divisional president of Power-One, Inc.
TECHNICAL REVISIONS - The appearance of products, including safety agency certifications pictured on labels, may change depending on the date manufactured. Specifications are subject to change without notice.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
MCD10069 Rev. 1.0 Page 2 of 2 www.power-one.com
PODS Enclosure Platform Data Sheet
Electrical Environmental Control DC Power Various DC systems options to
match line & load requirements Heat exchanger Closed-loop door mounted air-air,
55, 150, 220 W/K options Distribution Circuit breakers & fuse options
available Air conditioners 650, 1500, 2000 W options
2200/5100/6800 BTU @ L35/L35 Fan filter 200, 350 W/K Mechanical Accessories Dimensions (WxDxH)
800 x 850 x 1364/1940/2350 mm 32" x 34" x 54/77/93"
Cable bridges Mating with major OEM BTS equipment.
Security Lockable, vandal-proof hinges, multi-point locking mechanism
Cable gland plates Tailored to suit site RF, DC, AC Coax needs
Cable Entry Top (left, right, or rear) and bottom Heater 400 W, 900 W
Weight (excl equipment)
Up to 200 kg Grounding bars Mains, DC, RF
Material Marine-grade aluminum Service light Mounting PAD mounted; installation via
removable lifting eyes Smoke Detector
Equipment Mounting Standards Compliance
Height 27, 40, & 49 RU Safety IEC 950, UL 950 Width 23" (with various 19" options) Environmental protection IP55 (IEC529) / NEMA Type 3R Depth 600 mm, 24" Seismic Zone 4
Environmental Management • Direct fan cooling, sealed
loop heat exchangers or air conditioners ensure network integrity in the most challenging environments.
DC Power • Rugged, flexible rectifier
options to match various load & line conditions
• 65oC operating temperature ensures maximum uptime in high temperature environments
• 93.5% efficiencies reduce thermal loads
• Flexible DC load center
Flexible Payload Options • Up to 720 Ah batteries • Network equipment such as
radio base stations & microwave equipment
AC Distribution • Configurable with Surge
protection, RCCD, circuit breakers, generator socket, bypass switch
Rugged Cabinet Construction • Rugged seismic-rated aluminum
construction • Lockable cabinet including vandal-
proof hinges and multi-point locking mechanism
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
MCD10058 Rev. 1.0 Page 1 of 5 www.power-one.com
SLI 15 Inverter Series Data Sheet1500 Watt, 1U Compact Inverters
Description
The SLI 15 Inverter Series provides an ideal solution for telecom, IT, and industrial applications. Due to innovative technology solutions like the patent-pending "Compact Coil", the SLI 15 inverters pack 1500 watts of power into a light (5.6 kg) and compact package that is mountable in 19" racks and is only one rack unit high. The SLI 15 Inverter Series offers four models for different input (24 and 48VDC) and output (115 and 230VAC) voltage combinations. An integrated controller, along with an optional internal Static Transfer Switch (STS) enable flexible and scalable systems which are truly "plug and play", and require no external subsystems. The inverters can be stacked up to the power level needed by each application and also have the capability to be configured for generating a 3-phase voltage source.
Electrical performance of the SLI 15 is exemplary of a top-of-the-market product with efficiency that peaks at 93% and a patent-pending control algorithm that compensates current harmonics on the DC side without using bulky and expensive filters. The SLI 15 includes a powerful on-board Digital Signal Processor (DSP) that allows easy programming of main parameters through use of its front-panel keypad and LCD display. In addition, the SLI 15 can be interfaced with an RS-485 serial communications link.
SLI Inverter Model Selection and Ordering Information
Model 1 Input Voltage
(VDC) Output Voltage Nominal (VAC)
Overall Output Voltage Range
(VAC)
Frequency Range (Hz)
SLI-24-115 24 115 100 to 120 47 to 63
SLI-24-230 24 230 200 to 240 47 to 63
SLI-48-115 48 115 100 to 120 47 to 63
SLI-48-230 48 230 200 to 240 47 to 63 1 The following suffixes should be added to the model number to order options. For an internal Static Transfer Switch, please add the suffix "-STS". For AC terminal blocks, please add the suffix "-SC". For Hot Plug version, please add the suffix “-HP”. For Neutral tied to Ground, please add the suffix “-GN”.
Applications
• Telecom • IT • Industrial
Safety in compliance with IEC60950:1999, 3rd edition; EN60950:2000; UL60950, 3rd edition; CSA Standard C22.2 No.60950-00, 3rd edition
Features • New, compact design: 1U height x 19" width
x 14.94" depth; 19" rack-mountable • High efficiency: up to 93% • True sine wave output • Parallelable output with current share and
synchronization of multiple inverters working in parallel
• Front panel LCD display to monitor and set the main parameters
• RS-485 serial link • Constant input current sink from battery for
extended life • Optional hot-swappable configuration • Optional internal Static Transfer Switch • In the -STS version, ON line (primary source to the
load) or OFF line mode (UPS like) • Configurable for being used as Three Phase
source, 3 units
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
MCD10058 Rev. 1.0 Page 2 of 5 www.power-one.com
SLI 15 Inverter Series Data Sheet1500 Watt, 1U Compact Inverters
ELECTRICAL SPECIFICATIONS
Input Specifications Parameter Conditions/Description Min. Nom. Max. Units
DC Input Voltage Range
20 40
24 48
36 72
VDC
Input Current 24 VDC Models @ 18 VDC: 48 VDC Models @ 36 VDC:
100 48
Amps
Inrush current <10 Amps
Output Specifications Parameter Conditions/Description Min. Nom. Max. Units
Output Power 1500 Watts
Output AC Voltage Range
Standard is Vac floating from Ground; -GN version is available with Neutral connected to Ground (Grid Input shall be supplied by means of an isolation transformer)
110 200
115 230
120 240
VAC
Frequency 50Hz/230Vac, 60Hz/115Vac 50 60 Hz
Efficiency 93 %
Load Power Factor lagging or leading 0.33 1
Crest Factor Ipk/Irms 4
Regulation in single mode
Load: over full operating range. R-Load Line: over full operating range. R-Load
-3 -0.1
+1 +0.1
%
Regulation in parallel mode
Load: over full operating range. R-Load 230 115
-6 -8.5
0 0
%
Total Harmonic Distortion
On Resistive Load. <2 %
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
MCD10058 Rev. 1.0 Page 3 of 5 www.power-one.com
SLI 15 Inverter Series Data Sheet1500 Watt, 1U Compact Inverters
Fault Protection Parameter Conditions/Description Min. Nom. Max. Units
Input Overcurrent Protection
24 VDC Models; Internal Fuse. 48 VDC Models; Internal Fuse.
140 70
Amps
Input Overvoltage Protection
24 VDC Models: 48 VDC Models:
37,5 74
VDC
Input Undervoltage Protection
24 VDC Models: 48 VDC Models:
18 36
VDC
Output Overload 115 VAC Models: 230 VAC Models:
1610 1840
W
Surge 115 VAC Models for 200 ms: 230 VAC Models for 200 ms:
1750 2300
VA
Overvoltage Protection All outputs are set at 115%, ±2 % of nominal.
Undervoltage Protection
All outputs are set at 85%, ±2 % of nominal.
Overcurrent Protection 115 VAC Models: 1 A to 14 A selectable. 230 VAC Models: 1 A to 8 A selectable.
Safety Overcurrent Protection
By safety circuit breaker: 115 VAC Models: 15 A. 230 VAC Models: 10 A.
Short-Circuit Protection
Peak Current type protection: 115 VAC Models: 60 A. 230 VAC Models: 30 A.
Overtemperature Protection
Visual and acoustic indication 5 °C before shutdown at Tamb > 65 °C and at Tint > 100 °C.
Protection Restore Modes
The restore mode of each protection can be individually selected to "latch" or "auto-restart".
Environmental Specifications Parameter Conditions/Description Min. Nom. Max. Units
Operating Temp at Full Load
Power Derating: 75W/ºC: +55 ºC to +65 ºC. -25 55 ºC
Altitude Operating. Non-Operating.
13K 40K
ASL ft ASL ft
Storage Temp -40 85 ºC
Humidity 90% relative humidity @ 40 ºC, non-condensing.
Output Voltage Temperature Coefficient
0.02% per ºC within rated load.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
MCD10058 Rev. 1.0 Page 4 of 5 www.power-one.com
SLI 15 Inverter Series Data Sheet1500 Watt, 1U Compact Inverters
Interface Signals/Controls Parameter Conditions/Description Min. Nom. Max. Units
LCD Panel 2-line LCD panel with keypad for menu navigation.
LED Indicators 4 LED indicators: Front panel GREEN LED indicates inverter is ON. Front panel RED LED indicates a generic fault categorized as: a. Overtemperature (OT), b. Fan fail, c. Input OV, UV, OC, or Output OV, UV, or OC.
General Alarm Signal Activated by an open photo-relay if in fault mode, available at rear signal connector
Serial link RS485 port, 500Vdc isolated, available at rear signal connector
Regulatory & Safety Parameter Conditions/Description Min. Nom. Max. Units
cCSAus Approved.
Kema Approved.
CB Report Approval Approved.
CE Mark for LVD Approved.
RoHS Compliant.
Isolation Primary-to-Secondary: 3000 Vrms. Primary-to-Ground: 1000 Vrms. Secondary-to-Ground: 1500 Vrms. Signal-to-Ground: 0 Vrms.
Mechanical Specifications Parameter Conditions/Description Min. Nom. Max. Units
Dimensions Depth (inches) 14.94 in
Depth (mm) 379.5 mm
Width (inches) 19.00 in
Width (mm) 482.6 mm
Height (inches) 1.71 in
Height (mm) 43.5 mm
Weight Pounds 12.34 lb
Kilograms 5.6 kg
Connections DC input: back left, one 6mm diameter hole at each input bar; hot plug version has PCB bars with pre charging system; subrack for -HP version hosts one inverter, separate purchasing part; plastic DC input cover is available, separate purchasing part
AC output: back right, IEC320 plug is the standard; screw terminal blocks are with the option –SC; -STS version has IEC320 socket marked “Grid Input”
Signal: back centre, female Sub-D 15 poles connector, Molex 89263-6062 or equivalent; general failure alarm, serial port, synchronism for paralleling or three phase, remote on/off. For paralleling inverters, up to 6, ask for paralleling kit, one per inverter, separate purchasing part
Important: -STS and -GN options are compatible just supplying Grind Input by means of an isolation transformer, same indication if Neutral is tied to Ground at customer site.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
MCD10058 Rev. 1.0 Page 5 of 5 www.power-one.com
SLI 15 Inverter Series Data Sheet1500 Watt, 1U Compact Inverters
Reliability Parameter Conditions/Description Min. Nom. Max. Units
Calculated MTBF At 40 °C excluding fan -STS version, at 40°C excluding fan
250,000 200,000
Hours
Mechanical Outline Drawing: NUCLEAR AND MEDICAL APPLICATIONS - Power-One products are not designed, intended for use in, or authorized for use as critical components in life support systems, equipment used in hazardous environments, or nuclear control systems without the express written consent of the respective divisional president of Power-One, Inc.
TECHNICAL REVISIONS - The appearance of products, including safety agency certifications pictured on labels, may change depending on the date manufactured. Specifications are subject to change without notice.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
MCD10067 Rev. 1.0 Page 1 of 2 www.power-one.com
SLI 50 Inverter Series Data Sheet5000 Watt, 2U Compact Inverters
Applications • Telecom
• IT
• Industrial
Features
• Compact design: 2U height; 19" rack mountable • Front panel LCD display to monitor and set
main parameters • High efficiency: up to 93% • True sine wave output • RS485 serial link • Input reflected ripple current <300 ma rms
@ maximum load • Advanced cooling system to optimize fan life
and minimize noise • Parallelable output • Optional external Static Transfer Switch
Description The SLI 50 Series of “Slim Line” inverters provides an ideal solution for telecom, IT, and industrial applications. Due to innovative technology solutions like the patent-pending “Compact Coil", the SLI 50 Series inverters pack 5000 watts of power into a compact package that is 19” rack mountable and only two rack units high. Electrical performance of the SLI Series inverter products is at the top of the market with efficiency that peaks at 93% and a patent-pending control algorithm that compensates current harmonics on the DC side without using bulky and expensive filters. The inverter includes an on-board powerful Digital Signal Processor (DSP) that allows easy programmability of the main parameters on the front panel LCD display and keypad.The SLI Series inverters can be interfaced with RS485.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
MCD10067 Rev. 1.0 Page 2 of 2 www.power-one.com
SLI 50 Inverter Series Data Sheet5000 Watt, 2U Compact Inverters
Input
Nominal input voltage 40-60 VDC (48 VDC) Inrush current ETSI EN 300 132-2
Ver, 2.12, Clause 4.7 Input OC protection Internal MCB 150A (48 VDC) Input OV protection 65 VDC (48 VDC) Input UV protection 36 VDC (48 VDC) Output
Output power 5000 W Output voltage range 230 VAC models:
200 to 240 VAC Frequency 50 or 60 Hz% Overload 230 VAC Models: 5500 VA Efficiency Up to 93% Load PF 0.33 ± 1 leading or lagging Load CF 4 Load regulation -3% ± 1% over full operating
range Line regulation ± 0.1% over full operating
range Output noise and ripple 2% pk-pk (20 Hz /20 MHz) Distortion <2% on resistive load Overvoltage protection All outputs set at 115%
± 2% of nominal Undervoltage protection All outputs set at 85%
± 2% of nominal Overcurrent protection Yes; 230 VAC models; 5A to
25A selectable Safety overcurrent protection
By safety fuse; 230 VAC Models: 30A
Short-circuit protection Yes; Ipk; 230 VAC models: 60A
Overtemperature protection
(Visual and acoustic indication 5 ºC before shutdown) at: Tamb > 65 ºC and at Tint > 100 ºC
Protection restore modes
The restore mode of each protection can be individually selected to "latch" or "auto-restart".
Signal & Control LCD panel * 4-line LCD panel with
keypad for menu navigation Power-On Generic Fault Over Temperature Fan Fail
LED indicators *
Data Communications * General alarm signal: by a photo-relay (open if in fault mode) Safety & Environmental
Full load: -25 ºC to 55 ºC Power derating: 75 W/ ºC; +55 ºC to +65 ºC
Operating temperature range
Storage: -40 ºC to 85 ºC Operating humidity 0 - 90% non-condensing Altitude: operating 13000 feet (3900 meters) Altitude: non-operating 40000 feet Output voltage temperature coefficient
0.02% per ºC within rated load
Safety agency compliance
cCSAus, Kema, CB Report, CE Mark Primary-to-secondary 3000 Vrms Primary-to-ground 1000 Vrms Secondary-to-ground 1500 Vrms
Isolation
Signal-to-ground 0 Vrms
NUCLEAR AND MEDICAL APPLICATIONS - Power-One products are not designed, intended for use in, or authorized for use as critical components in life support systems, equipment used in hazardous environments, or nuclear control systems without the express written consent of the respective divisional president of Power-One, Inc. TECHNICAL REVISIONS - The appearance of products, including safety agency certifications pictured on labels, may change depending on the date manufactured. Specifications are subject to change without notice.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
MCD10065 Rev. 1.1 Page 1 of 2 www.power-one.com
SLI 7 Inverter Series Data Sheet700 Watt, 1U Compact Inverters
Applications • Telecom
• IT
• Industrial
Model Selection Output Model Input Voltage
(VDC) Vo (VAC) Io (AAC) Power
max (W)
SLI 7 24-230 24 230 3 700 SLI 7 48-230 48 230 3 700
Features
• Compact design: 1U height x 19" width x 380mm depth; 19" rack mountable
• Two models for different input (24V & 48V) and output of 230VAC
• High efficiency: up to 90% • True sine wave output • Constant current sunk from DC source for
extended battery life and reduced input filters (patent pending)
• Integrated controller, DSP controlled • Front-panel LED indicators • Force-cooled (rear to sides) • Front connection: AC front plug - DC terminal
blocks • 700W continuous duty • PF 1 to 0.33 (Power Factor) • CF up to 4 (Crest Factor) • Thermal overload protection with derating • Lightweight: 4 kg • 3kV insulation DC-AC; 1.5kVAC AC-PE • Safety standards: EN 60950,
CAN/CSA-C22.2 No. 60950-00 / UL60950
Description The SLI 7 Series, Slim Line Inverter, provides ideal solutions for telecom, IT, and industrial applications. It has lightweight (4 kg) and compact (1U x 19" x 14.8") design, and features peak efficiency up to 90% with a true sine wave output. A unique, patent-pending algorithm compensates current harmonics at the DC side, resulting in extended battery life, reduced dimensions, and improved power density.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
MCD10065 Rev. 1.1 Page 2 of 2 www.power-one.com
SLI 7 Inverter Series Data Sheet700 Watt, 1U Compact Inverters
Input
Nominal input voltage 48 VDC, 24 VDC Input voltage range 40-72 VDC, (20-36 VDC) Input current < 25A, <50A Input UV protection 36V ±1V, (18V ±1V);
hysteresis 3.5V (1.75V) Input OV protection 74V ± 1.5V, 37.5V ± 1.5V Input withstanding voltage
≤75 VDC, (< 40 VDC), unlimited duration
Input protection 30A, (60A); "not replaceable" fuses
Input voltage regulation ± 0.4% Output
Output power 700W / 800VA max continuous
Output voltage 230 VAC or 220 VAC; front selectable
Output frequency 50-60 Hz ± 0.2% Load regulation -3% / +1% Output noise and ripple 2% pk-pk
(20 Hz / 20 MHz) Total harmonic distortion <2% on resistive load Load PF 0.3 Load CF 4 Overvoltage protection -370Vpk ± 2% catastrophic;
latching, 2 ms delayed ; -115% ± 2% of nominal; auto-restart, 200ms delayed
Undervoltage protection 85% ± 2% of nominal; auto-restart, 1S delayed
Overload 4A, 200ms delayed Short circuit protection Peak current 15A Safety short circuit protection
4A, "not replaceable" fuse
Overtemperature protection
Inlet air temperature >67 ºC(shut down)
Internal Overtemperature Protection
Shut down
Other Technical Data Efficiency 90% Safety compliances EN60950:2000,
CSA-C22.2 No. 60950-00, UL60950, IEC60950
EMI EN55022 class A Operating temperature -25 ºC to 55 ºC, 700W.
Linear derating of -40W/ ºC up to 65 ºC
Storage -40 ºC to 85 ºC Cooling Forced cooling, rear to side MTBF 250,000 hours Dimensions WxHxD
19" x 1U x 14.76" (482.6 x 43.5 x 37.5mm)
Weight 4 kg Output connection Front IEC 320 plug Input connection Front screw terminals Signal & Control LEDs 230/220, Power, O.T., fault General failure alarm Pin 1-4, subD-15 pin Serial port Pin 2-3-4, subD-15 pin
NUCLEAR AND MEDICAL APPLICATIONS - Power-One products are not designed, intended for use in, or authorized for use as critical components in life support systems, equipment used in hazardous environments, or nuclear control systems without the express written consent of the respective divisional president of Power-One, Inc. TECHNICAL REVISIONS - The appearance of products, including safety agency certifications pictured on labels, may change depending on the date manufactured. Specifications are subject to change without notice.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
MCD10017 Rev. 1.1 Page 1 of 2 www.power-one.com
XR04.48/XR08.48 Rectifier Module Data Sheet
Description
The XR04.48G (400 W) and XR08.48G (800 W) are a family of single-phase, hot-pluggable, fan-cooled rectifiers. The high power density of this product offers the optimum 1U or 2U shelf solution for space-critical applications.
Both rectifiers offer excellent efficiency as well as wide operating temperature and wide input voltage range. Together with advanced technology they enable cost effective and reliable solutions.
The typical applications for this rectifier are both in indoor and outdoor environments, which is ideal for broadband access, cable head ends, micro/pico BTS Cells, and Enterprise, E911, and GSM-R applications.
19”/1U Aspiro Subrack Shown
Features • Wide AC input; 85 to 300 VAC • Wide operating temperature range
-40 to +75 °C • Designed for 300 mm deep ETSI
compliant systems • Input overvoltage disconnection • Thermal protection • Hot Swappable • 90% typical efficiency • International standards compliance
XR04.48 Rectifier Module
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
MCD10017 Rev. 1.1 Page 2 of 2 www.power-one.com
XR04.48/XR08.48 Rectifier Module Data Sheet
NUCLEAR AND MEDICAL APPLICATIONS - Power-One products are not designed, intended for use in, or authorized for use as critical components in life support systems, equipment used in hazardous environments, or nuclear control systems without the express written consent of the respective divisional president of Power-One, Inc. TECHNICAL REVISIONS - The appearance of products, including safety agency certifications pictured on labels, may change depending on the date manufactured. Specifications are subject to change without notice
Input Model XR04.48G XR08.48G
Input Voltage
85 to 300 VAC (Nominal: 100-240 VAC)
Input Frequency 47 to 63 Hz Max Input Current (Nominal Input)
<5.5 <9.3A
Max Inrush current <20 Arms (100 ms)
Hold-up time 20 ms (typ.) Fuse Two 8A fast
blow (line & neutral)
Two 16 A fast blow (line & neutral)
Output
Output Voltage 46-57 VDC; 53.5 VDC nom Output Power (nom) 400 W 800 W Output current 9.1 A max 18.2 A max
Efficiency
88 %(typ.) at Iout nom
90 %(typ.) at Iout nom
Power Density 7.3 W/in3 14.6 W/in3 Transient Response ± 3% at load variation (10-90% /
90-10%) recovery time 50ms Load sharing <5% of nominal current Output ripple < 100 mV p-p (BW 20 MHz) Psophometric noise <2 mV (accord. ETS300-132-2)
Mechanical
Dimension WxHxD
40.6 (1.6") x 101.62(4") x 228.5(9") mm
Weight 1.1 kg
Output Characteristic
Other Technical Data Operating Temperature Range
-40 to 65°C (derated +65 to +75°C) (for 3000 m altitude derate by 5°C)
Storage temperature
-40 to 85°C
Relative Humidity
10 to 90 %RH (operating) 5 to 95 % RH (storage )
Cooling Fan-cooled, speed-controlled, alarm controlled, air flow direction rear to front
Audible noise <55dBA according ISO7779 Protection Short circuit proof, automatic current limiting,
selective shutdown of modules at excessive output voltage Green Power ON Yellow Current limit/ thermal protection
Fan failure / Over temperature Prewarning / thermal protection Communication Failure (flashing)
LED Indication
Red Module failure/ high output voltage shutdown
Alarms via RS485
High output voltage/ shutdown Low voltage/ module failure
Storage ETS 300 019-2-1 Transport ETS 300 019-2-2 Operation ETS 300 019-2-3 Damp Heat IEC60068-2-78, MIL-STD- 810D section 507.2
Safety
Product Safety
EN60950-1:2001 IEC60950-1-2001
EMC EN61000-6-3:2001 Emission EN61000-6-2:2001 Immunity Insulation EN60950-1/A11:2004 4.25kVDC input to output Reinforced 2.12 kVDC input to chassis Basic 0.5 kVDC output to chassis Functional
UL (tested according EN60950-1/A11:2004) E131905 CAN/CSA-C22.2 No.60950-1-3 TÜV (tested according EN60950-1/A11:2004) CB (tested according EN60950-1/A11:2004)
Approvals
CE
-40V +75
Pmax
Temp
Po
+65-40V +75
Pmax
Temp
Po
+65 85V 300V
Pmax
Vin
Po
85V 300V
Pmax
Vin
Po
Environment
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
SEP 14, 2006 Page 1 of 2 www.power-one.com
Xscend Rectifier Data Sheet
Description The Power-One Xscend rectifier provides extremely reliable, high density DC power. The rectifier incorporates the latest in power monitoring solutions through an internal microprocessor giving up-to-the-second updates to the system controller and adjacent rectifiers. This guarantees tightly-controlled load sharing among rectifiers and provides status and identification information to the controller. At only two rack units high, these compact universal input rectifiers provide up to 1600 watts and allow up to five rectifier modules in a 23-inch shelf or four modules in a 19-inch shelf. Designed with diversity in mind, the Xscend rectifier is able to operate in a complete range of indoor and outdoor applications.
Features • Compact 2-rack unit height • 703 W/L (11.5 W/in3) • Front or mid-mountable • 110V/200-240 VAC single-phase input • Input overvoltage disconnection • Thermal protection in all load situations • Hot-swappable • No adjustments required • 93.5% typical efficiency • Active and droop current sharing • International standards compliance
Xscend Power System
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
SEP 14, 2006 Page 2 of 2 www.power-one.com
Xscend Rectifier Data Sheet
Mechanical Dimensions (WxHxD)
102.87 x 88.9 x 241.3 mm (4.05 x 3.5 x 9.5 in)
Weight 2.3 kg (4.12 lb) Cooling Fan cooled, speed controlled, and alarmed Insulation Reinforced insulation, tested at:
4.25 kVDC primary-secondary 2.12 kVDC primary-ground 0.75 kVDC secondary-ground
Mounting 19 in/ 2U subrack up to 4 modules 23 in/ 2U subrack up to 5 modules
Other Technical Data Safety CSA C22-2 No. 950, UL 1950 and
IEC60950/ EN 60950 Protection Short circuit proof, automatic current limiting,
selective shutdown of modules at excessive output voltage. Thermal protection derates the output power 65°C ambient temperature. Shutdown at >75°C with automatic restart. Shutdown is load dependant, at low load typ 85°C. Input overvoltage disconnection at >275VAC with automatic reset at >260VAC.
Alarms High output voltage/ shutdown, Low voltage/ module failure. Each alarm has an LED indicator on the front panel.
Indications Green LED Yellow LED Red LED
Power ON Current limit/ thermal protection Module failure
Audible Noise <60dBA Operating Temperature
-40 to +65 °C up to 2000 m -40 to +55 °C above 2000 m
Storage Temperature
-40 to +85 °C
Radiated EMC EN 61000-6-2, EN 61000-6-3, FCC Part 15, Class B
Environment Storage: Transport: Operation: Earthquake:
ETS 300 019-2-1 ETS 300 019-2-2 ETS 300 019-2-3 GR 63 Core Zone 4
*Average performance for a single module.
Input Model XR1648 XR1424 Input Voltage 100-240 VAC ±15% single phase
(44-66 Hz) (180-85 VAC at derated output power)
Current (max.) <10 A Soft Start <13 A/1 ms Harmonics >0.98 typical Surge Immunity EN 61000-4-5 Fuse 12.5 A -line, 12.5 A -neutral Connection FCI power connector™ EMC EN 61000-6-2, EN 61000-6-3,
FCC Part 15 Class B
Output Model XR1648 XR1424 Output Voltage 45-57 VDC 22.5-28 VDC
1600 W at >180 VAC (50-57 VDC)
1400 W at >180 VAC (25-28 VDC)
Power (max.)
675 W at 180-85 VAC (50-57 VDC)
675 W at 180-85 VAC (25-28 VDC)
Current (max.) 32 A 56 A Efficiency (at 40-90% load)
>93% (93.5% typical)
>90% (91% typical)
Tolerance Vout +/- 1.0%, constant voltage regulation
Transient Response
+/- 5% at load variation 10-90% or 90-10%
Load Sharing <5% of nominal current Ripple <100 mV p-p (BW. 30 MHz) Psophometric <2 mV, according to CCITT
norms Connection FCI power connector™ EMC EN 61000-6-2, EN 61000-6-4
NUCLEAR AND MEDICAL APPLICATIONS - Power-One products are not designed, intended for use in, or authorized for use as critical components in life support systems, equipment used in hazardous environments, or nuclear control systems without the express written consent of the respective divisional president of Power-One, Inc.
TECHNICAL REVISIONS - The appearance of products, including safety agency certifications pictured on labels, may change depending on the date manufactured. Specifications are subject to change without notice.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
DescriptionXscend modular DC power shelf systemsprovide large power system features in cost-effective, rack-mounted form factors. Theseshelf power solutions provide rectification,system management and power distributionwhile maintaining high reliability and offeringflexibility for future expansion. The Xscendsystems are based on hot-swappablerectifier modules with constant output poweravailable at 1400 (24V) or 1600W (48V) permodule.
System management is accomplishedthrough messages and alarms displayed onthe system controller’s (XCS) LCD screenand can also be displayed remotely via thePC-based PowComTM software package.
Features• AC Input 185-275 VAC
(85-185VAC at de-rated output)
• 48VDC rectifier with up to 1600W output
• 24VDC rectifier with up to 1400W output
• Fan cooled rectifier modules
• Front access design
• Temperature hardened -40°C to +65°C
• 19” or 23” mounting arrangement
• Extensive remote monitoring capabilities
• Modular DC distribution with LVD
• Power Factor Correction
• ETSI Compatible
• Modular system from 32A to 640A
Shelf System
Xscend™ Power SystemShelf System
www.power-one.comwww.power-one.com11V0005-060 Xscend SY V3.1
Xscend™ Power System
Note: All specifications are subject to change without notification.
Input
Output
Mechanical
Options
Features
Battery
Model Xscend 23” Shelf Xscend 19” Shelf
Input 205-250 VAC +/-10% 205-250 VAC +/-10%
Inputs (max.) Single or multiple inputs Single or multiple inputs
Rectifier Modules (max.) 20 16
Battery Outputs - MCB(max.)
4 2
Load Outputs - MCB(max.)
10 8
External Distribution(max.)
25 20
24V DC Version Yes (up to 2 shelves) Yes
48V DC Version Yes Yes
Supervision XCS XCS
Expansion Yes Yes
Battery Symmetry Inputs(max.)
3 3
Low Voltage BatteryDisconnection (LVBD) Yes Yes
Dimensions (WxHxD) 584x133x274mm(23x5.25x10.8in.)
483x133x274mm(19x5.25x10.8in.)
Mounting 23” 19”
Cable Entry Rear Rear
Temp. Comp. Charge Yes Yes
Ethernet NetworkInterface Yes Yes
Modem Interface Yes Yes
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
System Configurations
Xscend™ Power SystemShelf System
System Components
Rectifier Features
Model Voltage Power(max.)
Current(max.)
XR 1648 48V DC 1600W 32A
XR 1424 24V DC 1400W 56A
PCS Features
The Xscend system utilizes plug-in rectifier modules that arebased on a soft-switching approach. Features include 3 LEDs forpower-on, current limit & thermal protection, and module failure.
Rectifier Modules
Advanced system supervision is accomplished using amicroprocessor based control module that allows both localand remote system monitoring.
Supervision Modules
• Menu guided operation• RS232 interface for remote operation• Battery management and testing• Temperature compensation• Battery symmetry measurement• Optional Ethernet interface through SNMP and/or TCP/IP• Advanced battery management and testing• Digital signal collection via internal RS485 bus• Site programmable flash EPROM• Multiple language choices• Programmable alarms• Programmable logic functions and operations• Monthly data logging
Distribution ModuleAdvanced distribution is accomplished using a 5U highexternal distribution shelf. The shelf is based onstandard plug in circuit breakers and is available in 23in.and 19in. configurations.
An all-in-one 3U-9U (single and four shelf configurations)high shelf system that can be installed in 19” telecomcabinet solutions. The system subrack can accommodateup to 16 rectifier modules, a supervision module (XCS)and DC distribution with up to 10 circuit breakers (0- 4battery and 6-10 load breakers). Optional expansiondistribution shelf allows 20 circuit breakers.
Xscend 19in. System
An all-in-one 3U-9U (single and four shelf configurations)high shelf system that can be installed in 23” telecomcabinet solutions. The system subrack can accommodateup to 20 rectifier modules, a supervision module (XCS) andDC distribution with up to 10 circuit breakers (0-4 batteryand 6-10 load breakers). Optional expansion distributionshelf allows 25 circuit breakers.
Xscend 23in. System
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
System Configurations
Xscend™ Power SystemShelf System
System Components
Rectifier Features
Model Voltage Power(max.)
Current(max.)
XR 1648 48V DC 1600W 32A
XR 1424 24V DC 1400W 56A
PCS Features
The Xscend system utilizes plug-in rectifier modules that arebased on a soft-switching approach. Features include 3 LEDs forpower-on, current limit & thermal protection, and module failure.
Rectifier Modules
Advanced system supervision is accomplished using amicroprocessor based control module that allows both localand remote system monitoring.
Supervision Modules
• Menu guided operation• RS232 interface for remote operation• Battery management and testing• Temperature compensation• Battery symmetry measurement• Optional Ethernet interface through SNMP and/or TCP/IP• Advanced battery management and testing• Digital signal collection via internal RS485 bus• Site programmable flash EPROM• Multiple language choices• Programmable alarms• Programmable logic functions and operations• Monthly data logging
Distribution ModuleAdvanced distribution is accomplished using a 5U highexternal distribution shelf. The shelf is based onstandard plug in circuit breakers and is available in 23in.and 19in. configurations.
An all-in-one 3U-9U (single and four shelf configurations)high shelf system that can be installed in 9” telecomcabinet solutions. The system subrack can accommodateup to 16 rectifier modules, a supervision module (XCS)and DC distribution with up to 10 circuit breakers (0- 4battery and 6-10 load breakers). Optional expansiondistribution shelf allows 20 circuit breakers.
Xscend 19in. System
An all-in-one 3U-9U (single and four shelf configurations)high shelf system that can be installed in 23” telecomcabinet solutions. The system subrack can accommodateup to 20 rectifier modules, a supervision module (XCS) andDC distribution with up to 10 circuit breakers (0-4 batteryand 6-10 load breakers). Optional expansion distributionshelf allows 25 circuit breakers.
Xscend 23in. System
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
DescriptionXscend modular DC power shelf systemsprovide large power system features in cost-effective, rack-mounted form factors. Theseshelf power solutions provide rectification,system management and power distributionwhile maintaining high reliability and offeringflexibility for future expansion. The Xscendsystems are based on hot-swappablerectifier modules with constant output poweravailable at 1400 (24V) or 1600W (48V) permodule.
System management is accomplishedthrough messages and alarms displayed onthe system controller’s (XCS) LCD screenand can also be displayed remotely via thePC-based PowComTM software package.
Features• AC Input 185-275 VAC
(85-185VAC at de-rated output)
• 48VDC rectifier with up to 1600W output
• 24VDC rectifier with up to 1400W output
• Fan cooled rectifier modules
• Front access design
• Temperature hardened -40°C to +65°C
• 19” or 23” mounting arrangement
• Extensive remote monitoring capabilities
• Modular DC distribution with LVD
• Power Factor Correction
• ETSI Compatible
• Modular system from 32A to 640A
Shelf System
Xscend™ Power SystemShelf System
www.power-one.comwww.power-one.com11V0005-060 Xscend SY V3.1
Xscend™ Power System
Note: All specifications are subject to change without notification.
Input
Output
Mechanical
Options
Features
Battery
Model Xscend 23” Shelf Xscend 19” Shelf
Input 205-250 VAC +/-10% 205-250 VAC +/-10%
Inputs (max.) Single or multiple inputs Single or multiple inputs
Rectifier Modules (max.) 20 16
Battery Outputs - MCB(max.)
4 2
Load Outputs - MCB(max.)
10 8
External Distribution(max.)
25 20
24V DC Version Yes (up to 2 shelves) Yes
48V DC Version Yes Yes
Supervision XCS XCS
Expansion Yes Yes
Battery Symmetry Inputs(max.)
3 3
Low Voltage BatteryDisconnection (LVBD) Yes Yes
Dimensions (WxHxD) 584x133x274mm(23x5.25x10.8in.)
483x133x274mm(19x5.25x10.8in.)
Mounting 23” 19”
Cable Entry Rear Rear
Temp. Comp. Charge Yes Yes
Ethernet NetworkInterface Yes Yes
Modem Interface Yes Yes
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Features• Single point system voltage adjust• Programmable timer for battery test or
equalization• Digital meters and test points monitor plant
voltages and current• User-adjustable set points for under/over voltage
and low voltage disconnect
DMACController
DescriptionThe Power-One Digital Meter, Alarm and Control Panel (DMAC) provides comprehensivemonitoring and control for Power-One’s Compac™ power systems. This digital controllermonitors system conditions including DC voltage and load current, while providing avariety of alarm and control functions.
DMAC features include user-configurable battery testing, measurement of battery voltageand current & battery equalization.
Front panel LED’s for alarms, including:• Equalize alarm• OV/UV alarm• Major alarm• Minor alarm• Rectifier fail• Breaker alarm
www.power-one.comCourtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Temperature Compensation
Other Technical DataOperatingTemperature -0 to +50°C
StorageTemperature -50 to +85°C
Humidity 10-90% RH, operating, 5-95%storage, non-condensing
AltitudeRange
13,000 ft., derate 7°C/100 ft.above 8000 ft.
Overview
The temperaturecompensation panel works inconjunction with the DMACcontroller. Temperaturecompensation automaticallyadjusts the float voltageaccording to the ambienttemperature.
TemperatureCompensationAlarms
Alarms include temperaturedelta, which indicates batterythermal runaway and sensorfailure. In the event of asensor or panel failure, thecompensation defaults to thenormal float voltage set by thecontroller.
Interface
Note: All specifications are subject to change without notification.
Display Digital amp and digital volt meters
Digital Meters 3.5 digits, +/-2% accuracy
UV/OVAdjustment
22V/29V for 24VDC +/- 1.5V 44V/58V for 48VDC +/- 1.5V
Equalization &Battery TestTimer Range
0.5 seconds to 130 hours
CurrentMeasurementDC Shunt
1200A:50mA
User Controls
Timer reset buttonSystem voltage adjustmentNormal/Bypass test switchEqualize/Battery test switchEqualize Under/Over voltage adjustmentUndervoltage/Overvoltage
ConnectionPoints
System voltage test pointsSystem amperage test points
www.power-one.com11V0005-050 DMAC V3.0
DMACController
Alarms
Alarms
Equalize alarmOV/UV alarmMajor alarmMinor alarmRectifier failBreaker alarm
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
EAU - Shelf Mount
EAUWall Mount
Features
• Allows power systems to be accessed from aTCP/IP Network
• Compliant with PowCom™ software
• Wall mount or 1U, 19” shelf mount
• Uses SNMP protocol for reliable remote access
• 10Base-T Ethernet
• Nine external inputs
• Telnet for system setup
• 10Mbit 7-port HUB
• Easy implementation
Description
The External Alarm Unit (EAU) is a networkadapter that allows a Power-One Controllermodule to be accessed remotely through aTCP/IP network.
The EAU module has nine digital inputs forsupervision of external equipment and a sevenport HUB for interconnection of other networkdevices. Using a 10BASE-T ethernet connection,the EAU connects any Power-One controller to aTCP/IP network. This allows the system to beconfigured locally through PowCom software orremotely through a telnet session.
In addition, the EAU module incorporates IPaddress filtering to prevent unauthorized accessto the power system.
External Alarm UnitEAU Module
www.power-one.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Electrical Supply Voltages 40 to 60VDC, max 5W
CommunicationEthernet Controller IEEE 802.3, half-duplexEthernet HUB 7-ports, 10Base-TExternal Inputs 9 contact closure inputs for remote monitoring
MechanicalWeight Wall mount 0.42kg (0.93lbs.)
Shelf mount 1.14kg (2.51lbs.)
Dimensions (WxHxD) Wall mount 200x40x160mm (7.87x1.57x6.3in.)Shelf mount 19in.x44x155mm (19x1.75x6.1in.)
EnvironmentalAmbient Temperature -10°C to +70°CStorage Temperature -40°C to +85°C
System MonitoringPowCom MonitoringRemote system monitoring is accomplished throughPowCom and Alarm Central software packages.
PowCom is a graphic user interface site monitoringprogram that allows remote access to systemparameters, alarm history, and battery test data at asingle system location.
Alarm Central allows multiple power systems to bemonitored using a hierarchy based window systemthat informs a user of system events, using bothaudible and visual alarms.
SNMP Monitoring SoftwareSystem monitoring can also be accomplishedthrough standard SNMP protocols and an enterprisespecific Management Information Base (MIB).SNMP allows the user to access and monitor systemparameters as well as tracking system variables.
Other Technical Data
Note: All specifications are subject to change without notification.
www.power-one.com11V0005-031 EAU V3.0
EAU ModuleExternal Alarm Unit
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
www.power-one.com
Integrity-One™ Power System Rack Systems
Description The Integrity-One™ Power System is the next generation solution for today's power system needs. Using a modular design, the system is easily upgradeable for future growth. With a capacity up to 1250 amps, the Integrity-One system is ideal for either central office or cell site applications. This system includes multiple options for user-friendly local and remote access. Basic design concepts allow the user to develop system configurations that meet initial network capacity requirements with minimum installation costs while allowing future capacity expansion through module additions or multi-bay configurations. This is accomplished by a wide variety of hot swappable modules, rectifiers and distributions. Standard features in each Integrity system include an advanced microprocessor controller (PCS). This controller offers an extensive list of monitoring and control features that can be accessed locally or remotely through the standard RS232 connection or through the optional Power-One Network Interface box, which allows communication through Ethernet and SNMP protocols. External reporting can also be accomplished by using on-board Form-C contacts. In addition to the three systems listed here, other layouts and individual components are also available for integration into customer provided equipment racks, cabinets, outdoor enclosures, or other power requirements. Please contact Power-One for assistance with your unique requirements.
Features • Modular systems from 50-1250A • Up to 91% efficient • Intelligent, programmable controller • Front access distribution panels with optional
load shedding • Local and remote programming and
monitoring • Hot-swappable rectifiers • User-selectable alarm parameters • 208/240 VAC input • Extensive battery testing and monitoring • Programmable temperature compensation • Compatible with PowCom™ PC-based
software
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
www.power-one.com
The Integrity-One system is available in three different configurations allowing customers to choose the solution that is right for them. Each system uses the same basic components, including:
• System Interface Shelf • Alarm Output Connections • Network Interface (Optional) • Battery LVD (Optional) • PCS Controller • PMP25 Rectifier Modules • SDS / PDS Distribution Shelves • Single or Individual Rectifier AC Inputs
Full Rack System The Integrity-One full rack system allows for up to 1250A at 48V in a single bay by using combinations of Secondary or Primary Distributions. Each rack is capable of holding up to five rectifier shelves for 48V applications providing 1250A or two rectifier shelves for 24V applications providing 1100A. Multiple racks may be paralleled to produce a maximum total system capability of 5000A using a single controller in the primary rack. Half-Height Rack System The Integrity-One Half-Height rack system is available at up to 1100A and can be installed above existing battery stands. The Half-Height system is ideal for systems requiring extended battery backup. Up to 44 load breakers can distribute up to 500A at -48V, or up to 1000A at +24V. Integrity-One Rack with Battery Trays The Integrity-One System with battery trays accommodates up to two rectifier shelves and up to three battery trays creating a complete power system in a single rack. Distribution can be achieved through up to 44 load breakers or fuses (up to 100A rating).
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
www.power-one.com
Integrity-One ™ Power System Rack Systems
Distribution Panels • Hot-swappable distribution shelves • Front, middle and rear distribution
positions (waterfall effect) allow for system cable management
• SDS: Secondary Distribution Shelf • Rated at 500A • Plug in CB’s up to 100A rating • Plug in fuses up to 100A rating • Accommodates up to 22 circuit breakers or fuses • PDS: Primary Distribution Shelf (rated at 1000A) • Up to qty 8 single pole fuses (100-600A) • Up to qty 8 single pole CB’s (up to 250A rating) • Up to qty 3 double pole CB’s (up to 400A rating) • Up to qty 2 triple pole CB’s (up to 600A rating) System Interface Shelf • Easy connection of system alarm
signals and wiring • Optional battery symmetry and
temperature probes • Optional Power-One Network
Interface box (featuring ethernet and SMNP protocol capability)
• Optional low voltage disconnect • Battery shunt
System Components
PCS Controller • RS485 digital signal data bus • Fully programmable • 6 programmable
alarms(upgradeable to 24) • Battery test: manual or automatic • Alarm relay test • Adjustable battery current • Software controlled start-up after
mains outage Rectifier Shelves • RS485 communication bus • 23” shelf allows up to 5 rectifiers
each • Digital current sharing • Individual rectifier or single shelf
AC feed options PMP25 Rectifier • 5 rectifiers into each 4U 23” shelf • Available in 24 or 48VDC • Thermal protection • Fan cooled modules with speed
control and alarms • Hot-swappable • RS485 interface • Low weight • Up to 91% efficiency
Integrity Shown with Optional AC Distribution Box
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
www.power-one.com
Integrity-One ™ Power System Rack Systems
Input Model Integrity-One 48V Integrity-One 24V Input Single or individual Single or individual Inputs Single input for every 6 rectifier positions (4
inputs for 20 rectifier cabinets) Single input
Current (at full load) 16A per rectifier (max.) 16A per rectifier (max.) Fuse 25A per rectifier 25A per rectifier
Output Rectifier Modules 50-1250A 110-1100A Voltage 48V 24V
Efficiency >91% >89%
Components Controller PCS Controller PCS Controller Rectifier PMP 25.48 PMP 25.24
Compliance EMC EN 55022 Class B, FCC Part 15 Class B Safety CSA C22-2 No. 950, UC1950 and IEC60950 / EN 60950
Mechanical Dimensions (WxHxD) 23 x 84 x 23 in.
(584 x 2133 x 584mm) 23 x 46 x 23 in. (584 x 1168 x 584mm)
Mounting (rack) 23” 23” Mounting (base) Mounting holes provided Mounting holes provided Audible Noise <60dBA <60dBA Operating Temperature -25 to +60°C -40 to +65°C Storage Temperature -40 to +85°C -40 to +85°C Note: All specifications are subject to change without notification.
11V0005-011 INTSYS V3.0
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Mini System Data Sheet We are sorry for the inconvenience; the Mini System data sheet is currently being revised. In the interim, please e-mail adam.barnes@power-one for additional Mini System information.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
NOV 01, 2006 Page 1 of 2 www.power-one.com
PCU10 Controller Module Data Sheet
Features User controls and interfaces:
• Simple menu-guided operation using front panel mounted pushbuttons and an LCD
• User-selectable alarm parameters • Data logging of last 40 events • SNMP interface adapter available • RS232 interface and Form “C” dry
alarm contacts • Compatible with PowComTM PC-based
software
Intelligent battery management:
• Temperature compensation with programmable compensation factor
• Automatic and manual load testing • Battery voltage and symmetry monitoring • Remaining battery capacity
measurement • Low voltage disconnect
Description The PCU10 provides monitoring and control for the PPS 10, 11, and 13 power systems. These hot-swappable controller modules supervise AC inputs, output voltages and currents, rectifier performance, battery condition, and breaker status. Visual notification of an alarm condition is provided with an LED. A description of the exact alarm condition is provided through an LCD. Additionally, four Form “C” contacts are provided to indicate a failure.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
NOV 01, 2006 Page 2 of 2 www.power-one.com
PCU10 Controller Module Data Sheet
Other Technical Data Dimensions (WxHxD)
62 x 262 x 232mm (2.4 x 10.3 x 9.1in)
Weight 0.5kg (1.1 lb.) Operating Temperature
-25 to +55 °C
Storage Temperature
-50 to +85 °C
Environment Storage: Transport: Operation:
ETS 300 019-2-1 ETS 300 019-2-2 ETS 300 019-2-3
Battery Management Battery Disconnection
An optional feature that allows voltage disconnection of batteries.
Boost Charging
Manual time controlled or automatic boost charging with adjustable time and voltage levels.
Battery Test Automatic or manual testing of batteries up to four times per year. Variables include: test duration, end voltage, Ah, and allowable symmetry variation.
Symmetry Measurement
Optional tool that measures batteries for early detection of thermal runaway. Allows for separate measurements of up to three parallel battery branches, each divided into four blocks.
Temperature Compensation Charging
Allows continuous adjustment of output voltage according to battery temperature. Feature includes adjustable compensation factor and separate thresholds for alarms.
Load Shedding (PLD)
Optional feature that allows voltage or time controlled disconnection of non-essential load.
Input Voltage 18-72V DC Current <200 mA at 48V, <400 mA at 24V Interface Display 2x16 character LCD Communications RS232 serial interface for remote
control from a PC with PowCom software.
Indications Green LED - Power ON Yellow LED - System warning Red LED - System alarm
Controls Four pushbutton controls allow menu navigation
Alarms Alarm History The last 40 events are saved and
include a time and date stamp. Alarm Contacts Four potential free change over
alarm contacts. Two open collector outputs for LVD.
Alarms High DC Voltage Low DC Voltage Load/ Battery Disc. Battery Fuse Failure DC Fuse Failure Module Failure Urgent Module Failure Main AC Failure Battery Failure Symmetry Failure High Temperature High Load
1* 1* 1* 1* 1* 2* 1* 3* 4* 4* 4* 2*
* All alarms are indicated using an LED and displayed in the LCD. The numbers represent an example of alarm routing: 1) Urgent alarm, 2) Service alarm, 3) Main AC failure, 4) Battery related failure Alarms are configurable by changing the EPROM
NUCLEAR AND MEDICAL APPLICATIONS - Power-One products are not designed, intended for use in, or authorized for use as critical components in life support systems, equipment used in hazardous environments, or nuclear control systems without the express written consent of the respective divisional president of Power-One, Inc. TECHNICAL REVISIONS - The appearance of products, including safety agency certifications pictured on labels, may change depending on the date manufactured. Specifications are subject to change without notice.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
The PCU 5/ 7Controllers are usedin PPS5 and PPS7Power Systems.
DescriptionThe Power-One Control Unit (PCU 5/7) provides monitoring and control for the PPS 5 and PPS 7power systems. These hot-swappable controller modules supervise output voltages, currents, rectifierperformance, battery condition, and breaker status. Visual notification of an alarm condition isprovided with an LED. A description of the exact alarm condition is provided through an LCD.Additionally, four Form “C” contacts are provided to indicate a failure.
FeaturesUser controls and interfaces:
• Simple menu-guided operation using front panel mounted pushbuttons and an LCD
• User-selectable alarm parameters
• Data logging of last 40 events
• SNMP interface adapter available
• RS232 interface and Form “C” dry alarm contacts
• Compatible with PowComTM PC-based software
PCU 5/7Controller
www.power-one.com
Intelligent battery management:
• Temperature compensation with programmable compensation factor
• Automatic and manual load testing
• Battery voltage and symmetry monitoring
• Capacity testing
• Low voltage disconnect
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
InputVoltage 18-72V DC
Current <200 mA at 48V, <400 mA at 24V
Battery Management
Other Technical DataDimensions(WxHxD)
62 x 129 x 231mm (2.4 x 5.1 x 9.1in.)
Weight 0.45kg (1.0lbs.)
OperatingTemperature -25 to +55°C
StorageTemperature -50 to +85°C
EnvironmentStorage: Transport: Operation:
ETS 300 019-2-1ETS 300 019-2-2ETS 300 019-2-3
Alarms
BatteryDisconnection
A feature that allows voltagecontrolled disconnection of batteries.
Boost ChargingManual time controlled or automaticboost charging with adjustable timeand voltage levels.
Battery Test
Automatic or manual testing ofbatteries up to four times per year.Variables include: test duration, endvoltage, Ah, and allowable symmetryvariation.
SymmetryMeasurement
Optional tool that measures batteriesfor early detection of thermalrunaway. Allows for separatemeasurements of up to three parallelbattery branches, each divided intofour blocks.
TemperatureCompensationCharging
Allows continuous adjustment ofoutput voltage according to batterytemperature. Feature includesadjustable compensation factor andseparate thresholds for alarms.
PLD Optional feature that allows voltageor time controlled disconnection ofnon-essential load.
Interface
Note: All specifications are subject to change without notification.
AlarmHistory
The last 40 events are saved andinclude a time and date stamp.
AlarmContacts
Four potential free change overalarm contacts. Two opencollector outputs for LVD.
Alarms
High DC VoltageLow DC VoltageLoad/ Battery Disc. Battery Fuse FailureDC Fuse FailureModule FailureUrgent Module FailureMain AC FailureBattery FailureSymmetry FailureHigh TemperatureHigh Load
1*1*1*1*1*2*1*3*4*4*4*2*
* All alarms are indicated using an LED anddisplayed in the LCD. The numbers represent anexample of alarm routing:1) Urgent alarm, 2) Service alarm, 3) Main AC failure, 4) Battery related failureAlarms are configurable by changing the EPROM
Display 2x16 character LCD
Communication RS232 Serial interface for remote control from a PC withPowCom software.
IndicationsGreen LED - Power ONYellow LED - System warning message Red LED - System alarm
Controls Four pushbutton controls allow menunavigation
www.power-one.com11V0005-027 PCU 5/7 V3.0
ControllerPCU 5/7
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
DescriptionThe Power-One PMP 11 rectifier moduleprovides cost-effective power in a highdensity solution. Built on the latestadvances in the resonance switch modeapproach (soft-switching), the PMP 11 isthe next evolution in our convectioncooled rectifier series.
Optimized for telecom applications, themodule is designed to work in a multitudeof different subrack/shelf configurationsincorporating the PCU/PCS controller andvarying distribution options.
Features• 208/240 VAC input
• 24V, 48V, or 60V DC output
• Input overvoltage disconnection
• Thermal protection
• Active load sharing
• Hot-swappable
• Up to 92% efficient
• International standards compliance
• Natural convection cooling
• Low weight
PPS 10 6500 SystemShown
PMP 11Rectifier Module
www.power-one.comCourtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
InputModel PMP 10.24A PMP 11.48 PMP 11.60
InputVoltage
205-250V AC ±10% single phase, (44-66Hz)185-160V AC at reduced output power
Current(max.) <6.8A <7.0A <7.0A
Soft Start <12A peak maximum 220ms
Harmonics EN 61000-3-2 Power Factor >0.99 at max. load
SurgeImmunity EN 61000-4-5
Fuse T 8A
Connection IEC-320/C14
EMC EN 61000-6-2, EN 61000-6-3, FCC Part 15 Class B
Output
Mechanical
Dimensions 62 x 261 x 231mm (2.4 x 10.3 x 9.1in.)
Weight 3.1kg (6.8lbs.)
Cooling Natural convection
InsulationReinforced insulation tested at:4.25 kV DC primary-secondary, 2.12 kV DC primary-ground,0.75 kV DC secondary ground
Enclosure IP20
Mounting Up to 8 modules per shelf
Other Technical Data
Model PMP 10.24A PMP 11.48 PMP 11.60
Output Voltage 22-28V DC 44-56V DC 56-71V DC
Power (max.) 1000W(25-28V)
1100W (50-57.7V DC)
1100W (60-71V DC)
Current (max.) 43A 23A 18.5A
Efficiency (at 40-90% Load)*
>88% >91% >92%
Tolerance Vout +/- 1%
TransientResponse
+/- 5% at load variation 10-90% or 90-10%, recovery time 10ms
Load Sharing <5% of nominal current
Ripple <100mV p-p (BW. 30MHz)
Psophometric <2mV, according to CCITT norms
Connection DIN 41612F
EMC EN 61000-6-2, EN 61000-6-4
Note: All specifications are subject to change without notification.
SafetyEN 60950UL 1950 and IEC60950 , Class 1CSA C22-2 No. 950
Protection
Short circuit proof, automaticcurrent limiting, selective shutdownof modules at excessive outputvoltage. Thermal protectionreduces the output power atenvironmental temperatures abovemaximum level. Thermalprotection with shut down at>55°C. Automatic restart.* Inputover-voltage disconnection at>275VAC with automatic reset at>260VAC.
Indications
Green LED
Red LED
Red LED
Power ON
High outputvoltage/ shutdown
Low voltage/module failure
AudibleNoise <35dBA
OperatingTemperature*
-25 to +55°C up to 2000m-25 to +45°C above 2000m
StorageTemperature -40 to +85°C
Radiated EMC EN 61000-6-2, EN 61000-6-3,FCC Part 15, Class B
EnvironmentStorage: Transport: Operation:
ETS 300 019-2-1ETS 300 019-2-2ETS 300 019-2-3
*Average performance for a single module.
www.power-one.com11V0005-034 PMP 11 V3.0
PMP 11Rectifier Module
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
NOV 07, 2006 Page 1 of 2 www.power-one.com
PMP 13.48 Rectifier Data Sheet
PPS 10 3900 System Shown
Features • RoHS lead free solder and lead solder
exempted products are available
• 208/240 VAC input
• 48 VDC output
• Input overvoltage disconnection
• Thermal protection
• Active load sharing
• Hot swappable
• Up to 92% efficient
• International standards compliance
• Natural convection cooling
• Low weight
Description The PMP 13.48 is a convection-cooled rectifier delivering superior reliability in harsh environmental conditions where fan-cooled products may not deliver the reliability required to ensure maximum network asset performance. With leading-edge patented resonant conversion topology, the PMP13 industry-leading efficiencies of 93.5% deliver significant operating expenditure savings in the network on utility and HVAC costs. Power-One also recognizes that typical network loads operate between 20-60%; hence the PMP13 unique “flat” efficiency ensures minimal energy loss down to 15% of installed capacity The PMP 13 is optimized for telecom applications, and is designed to work in PPS10 systems incorporating the PCS controller and various distribution options with up to 6 units per 19”/6U shelf and up to 8 units per 23”/6U shelf.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
NOV 07, 2006 Page 2 of 2 www.power-one.com
PMP 13.48 Rectifier Data Sheet
NUCLEAR AND MEDICAL APPLICATIONS - Power-One products are not designed, intended for use in, or authorized for use as components in life support systems, equipment used in hazardous environments, or nuclear control systems without the express written consent of the respective divisional president of Power-One, Inc. TECHNICAL REVISIONS - The appearance of products, including safety agency certifications pictured on labels, may change depending on the date manufactured. Specifications are subject to change without notice.
Input Model PMP 13.48
Input Voltage 205-250 VAC ±10% single phase, (44-66 Hz) (185-160 V at reduced output power)
Current (max.) <6.8 A
Soft Start <12 A peak max. 100 ms
Harmonics
EN 61000-3-2 Power Factor >0.99 at max. load
Surge Immunity
EN 61000-4-5
Fuse T 10A
Connection IEC-320/C14
EMC EN 61000-6-2, EN 61000-6-3, FCC Part 15 Class B
Output Model 13.48
Output Voltage 44 - 56 VDC
Power (max.) 1300 W at 50-56 VDC
Current (max.) 28 A
Efficiency (at 40-90% load)*
>92%
Tolerance Vout ± 1.0%
Transient Response
± 5% at load variation 10-90% or 90-10%, recovery time 10 ms
Load Sharing <5% of nominal current
Ripple <100 mV p-p (BW. 30 MHz)
Psophometric <2 mV, according to CCITT norms
Connection DIN 41612F
EMC EN 61000-6-2, EN 61000-6-4
Mechanical Dimensions (WxHxD)
62 x 261 x 231 mm (2.4 x 10.3 x 9.1 in)
Weight 3.1 kg (6.8 lb)
Cooling Natural Convection
Insulation Reinforced insulation, tested at: 4.25 kVDC primary-secondary 2.12 kVDC primary-ground 0.75 kVDC secondary-ground
Enclosure IP20
Mounting Up to 8 modules per shelf
Other Technical Data Safety EN 60950
UL 1950 and IEC60950 , Class 1 CSA C22-2 No. 950
Protection Short-circuit proof, automatic current limiting, selective shutdown of modules at excessive output voltage. Thermal protection reduces the output power at environmental temperatures above maximum level. Shut down at >75 °C with an automatic restart.* Input overvoltage disconnection at >275 VAC with automatic reset at >260 VAC.
Indications Green LED Red LED Red LED
Power ON High output voltage/ shutdown Low voltage/ module failure
Audible Noise
<35 dBA
Operating Temperature
-25 to +55 °C up to 2000 m -25 to +45 °C above 2000 m
Storage Temperature
-40 to +85 °C
Radiated EMC
EN 61000-6-2, EN 61000-6-3, FCC Part 15, Class B
Environment Storage: Transport: Operation:
ETS 300 019-2-1 ETS 300 019-2-2 ETS 300 019-2-3
*Average performance for a single module.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
DescriptionThe Power-One PMP 25 rectifier usesresonance switch mode technology (softswitching), and incorporates thermalprotection while providing extremely reliableDC power in a small space. Rectifiercommunication is accomplished using digitalinterfaces over an RS485 data bus.Information is transmitted to adjacentrectifiers while providing status andidentification information to the systemcontroller (PCS).
At only 4 rack units high, these compactrectifiers allow for up to five modules in each23in. rack (4 units in 19in. rack) providing upto 250A at 48V or up to 550A at 24V. Withfull power available up to 65°C, PMP 25rectifiers are ideal for any indoor or outdoorapplication.
Features• Compact 4 rack-unit height
• 50A output at 48V
• 110A output at 24V
• 208 / 240 single phase input
• Input over-voltage disconnect
• Hot-swappable rectifiers
• High efficiency, up to 91%
• Active current sharing
• International standards compliance
PPS 25 SystemShown
PMP 25Rectifier Module
www.power-one.comCourtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
InputModel PMP 25.24 PMP 25.48
InputVoltage
196 - 250V AC ±10% single phase, (44-66Hz)176-160V AC at reduced output power
Current(max.) <22A <20A
Soft Start <22A <20A
Harmonics EN 61000-3-2 Power Factor >0.98 at 50-100% load
SurgeImmunity EN 61000-4-5
Fuse F 25A
Connection Harting MH - 21 Signal pins, 3 HC pins
EMC EN 61000-6-2, EN 61000-6-3, FCC Part 15 Class B
Output
MechanicalDimensions 105 x 176 x 455mm
(6.9 x 4.13 x 17.9in.)
Weight 6.2kg (13.6lbs.)
Cooling Fan: speed controlled and monitored
Interface RS485 for communication with thesupervision module
InsulationReinforced insulation tested at: 4.25 kV DC primary-secondary, 2.12 kV DC primary-ground,0.75 kV DC secondary ground
Enclosure IP20
Mounting In 19”/ 4U subrack up to 4In 23”/ 4U subrack up to 5
Other Technical Data
Model PMP 25.24 PMP 25.48
Power (max.) 3080W 2800W
Output Voltage 22-30V DC 44-58V DC
Current (max.) 110A 50A
Efficiency(@ 40-90%Load)*
>89% >91%
Tolerance Vout +/- 0.5%
TransientResponse
+/- 6% at load variation 10-90% or 90-10%, recovery time 150ms
Load Sharing <5% of nominal current
Ripple <100mV p-p (BW. 30MHz)
Psophometric <2mV, according to CCITT norms
Connection 8mm HC-pins
EMC EN 61000-6-2, EN 61000-6-4
Safety EN 60950CSA C22-2 No. 950, UL 1950
Protection
Short circuit proof, automatic currentlimiting, selective shutdown ofmodules at excessive output voltage.Thermal protection reduces theoutput power at environmentaltemperatures above maximum level.Shut down at >75°C with automaticrestart.* Input over-voltagedisconnection at >275VAC withautomatic reset at >260VAC.
Indications
Green LED
Yellow LED
Yellow Flashing
Red LED
Power ON
Thermal Protection
Comm. Error
Module Failure
AudibleNoise <60dBA
OperatingTemperature*
48V: -25 to +60°C 24V: -40 to +65°C
StorageTemperature -40 to +85°C
Radiated EMC EN 61000-6-2, EN 61000-6-3, FCC Part 15, Class B
EnvironmentStorage: Transport: Operation:
ETS 300 019-2-1ETS 300 019-2-2ETS 300 019-2-3
Note: All specifications are subject to change without notification.
* Average performance for a single rectifier
www.power-one.com11V0005-029 PMP 25 V3.0
PMP 25Rectifier Module
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
DescriptionThe Power-One PMP 5 rectifier moduleprovides a cost-effective power solutionin a high density footprint. Built on thelatest advances in the resonance switchmode approach (soft-switching), thePMP 5 is the next evolution in our smallconvection cooled rectifier series.
Optimized for telecom applications, themodule is designed to work in amultitude of different subrack/shelfconfigurations incorporating the Power-One PCU controller and variousdistribution options.
Features• 115/230 VAC input
• 24V, or 48VDC output
• Power factor correction
• Active load sharing
• Hot-swappable
• Low weight
• Natural convection cooling
• International standards compliance
PPR 5/7 SystemShown
PMP 5Rectifier Module
www.power-one.comCourtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
InputModel PMP 5.24 PMP 5.48 PMP
5.24-110PMP5.48-110
InputVoltage
195-276V AC singlephase, (44-66Hz)
93,5-148,5V AC singlephase, (44-66Hz)
Current(max.) <2.9A <5.8A
Soft Start <8A peak max. 5ms <16A peak max. 5ms
Harmonics EN 610555 Power Factor >0.99 at 50-100% load
SurgeImmunity EN 61000-4-5
Fuse T 3,15A T 6A
Connection IEC-320/C14
EMC EN 61000-6-2, EN 61000-6-3, FCC Part 15 Class B
Output
MechanicalDimensions 62 x 129 x 232mm
(2.4 x 5.1 x 9.1in.)
Weight 1.5kg (3.3lbs.)
Cooling Natural convection
InsulationReinforced insulation tested at:4.25 kV DC primary-secondary, 2.12 kV DC primary-ground,2.12 kV DC secondary ground
Enclosure IP20
Mounting In 19” subrack up to 6 modules
Other Technical Data
Model PMP 5.24 PMP 5.48 PMP5.24-110
PMP5.48-110
OutputVoltage
22.5-28VDC
45-56VDC
22.5-28VDC
45-56VDC
Power (max.) 448W 448W 448W 448W
Current(max.) 16A 8A 16A 8A
Efficiency >87% >89% >85% >87%
Tolerance Vout +/- 1%
TransientResponse
+/- 5% at load variation 10-90% or 90-10%,recovery time 10ms
Load Sharing <5% of nominal current
Ripple <100mV p-p (BW. 30MHz)
Psophometric <2mV, according to CCITT norms
Connection DIN 41612F
EMC EN 61000-6-2, EN 61000-6-4
Safety EN 60950
Protection
Short circuit proof, automaticcurrent limiting, selectiveshutdown of modules atexcessive output voltage.
Indications
Green LED
Red LED
Red LED
Power ON
High outputvoltage/ shutdown
Low voltage/module failure
AudibleNoise <35dBA
OperatingTemperature -25 to +55°C
StorageTemperature -40 to +85°C
Radiated EMC EN 61000-6-2, EN 61000-6-3,FCC Part 15, Class B
EnvironmentStorage: Transport: Operation:
ETS 300 019-2-1ETS 300 019-2-2ETS 300 019-2-3
Note: All specifications are subject to change without notification.
www.power-one.com11V0005-066 PMP 5 V3.0 RevD
PMP 5Rectifier Module
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
DescriptionThe Power-One PMP 7 rectifier moduleprovides a cost-effective power solutionin the highest possible density. Built onthe latest advances in the resonanceswitch mode approach (soft-switching),the PMP 7 is the next evolution in oursmall convection cooled rectifier series.
Optimized for telecom applications, themodule is designed to work in a multitudeof different subrack/shelf configurationsincorporating the Power-One PCUcontroller and various distributionoptions.
Features• 208/240 VAC input
• 24V, 48V, or 60V DC output
• Input overvoltage disconnection
• Thermal protection
• Active load sharing
• Hot-swappable
• Up to 92% efficient
• International standards compliance
• Natural convection cooling
• Low weightPPS 7 3500 SystemShown
PMP 7Rectifier Module
www.power-one.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
InputModel PMP 7.24 PMP 7.48 PMP 7.60
InputVoltage
205-250V AC ±10% single phase, (44-66Hz) (-15% for PMP7.60)185-160V at reduced output power
Current(max.) <3.55A <4.35A <4.35A
Soft Start <11A peakmax. 5ms
<15.5A peakmax. 5ms
<20A peakmax. 5ms
Harmonics EN 61000-3-2 Power Factor >0.99 at max. load
SurgeImmunity EN 61000-4-5
Fuse T 6,3A
Connection IEC-320/C14
EMC EN 61000-6-2, EN 61000-6-3, FCC Part 15 Class B
Output
MechanicalDimensions 62 x 129 x 232mm
(2.4 x 5.1 x 9.1in.)
Weight 1.65kg (3.6lbs.)
Cooling Natural convection
InsulationReinforced insulation tested at:4.25 kV DC primary-secondary, 2.12 kV DC primary-ground,0.75 kV DC secondary ground
Enclosure IP20
Mounting In 19” subrack up to 5 modules
Other Technical Data
Model PMP 7.24 PMP 7.48 PMP 7.60
OutputVoltage 22.5-28VDC 45-56VDC 56-70.5VDC
Power (max.) 560W 672W 635W
Current(max.) 20A 12A 9A
Efficiency (at 40-90% load)*
>89.5% >92% >92%
Tolerance Vout +/- 1%
TransientResponse
+/- 5% at load variation 10-90% or 90-10%, recovery time 10ms
Load Sharing <5% of nominal current
Ripple <100mV p-p (BW. 30MHz)
Psophometric <2mV, according to CCITT norms
Connection DIN 41612F
EMC EN 61000-6-2, EN 61000-6-4
SafetyEN 60950UL 1950 and IEC60950 , Class 1CSA C22-2 No. 950
Protection
Short circuit proof, automaticcurrent limiting, selective shutdownof modules at excessive outputvoltage. Thermal protectionreduces the output power atenvironmental temperatures abovemaximum level. Shut down at>75°C with an automatic restart.*Input over-voltage disconnection at>275VAC with automatic reset at>260VAC.
Indications
Green LED
Red LED
Red LED
Power ON
High outputvoltage/ shutdown
Low voltage/module failure
AudibleNoise <35dBA
OperatingTemperature*
-25 to +55°C up to 2000m-25 to +45°C above 2000m
StorageTemperature -40 to +85°C
Radiated EMC EN 61000-6-2, EN 61000-6-3,FCC Part 15, Class B
EnvironmentStorage: Transport: Operation:
ETS 300 019-2-1ETS 300 019-2-2ETS 300 019-2-3
Note: All specifications are subject to change without notification.
*Average performance for a single module.
www.power-one.com11V0005-028 PMP 7 V3.0
PMP 7Rectifier Module
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
OCT 24, 2006 Page 1 of 2 www.power-one.com
Power Network Interface Data Sheet
Description The Power Network Interface (PNI) is an embedded network server that allows Power-One Controller modules to be accessed remotely via Ethernet or SNMP. Access can be achieved via any web browser which has access to the TCP/IP network and. An intuitive graphic user interface provides access and control to system parameters, alarm history, and battery test data. Alarm Central allows multiple power systems to be monitored using a hierarchy-based window system that informs a user of system events, using both audible and visual alarms. SNMP protocol allows enhanced managing capabilities and enables the system to be accessed from any location. Using standard protocols and an enterprise specific Management Information Base (MIB), SNMP allows the user to access and monitor system parameters as well as tracking system variables. The PNI can be supplied as standalone device or installed as a daughter board in PCS controllers.
Features • RoHS lead-free solder and lead-
solder-exempted products are available.
User controls and interfaces:
• Systems can be accessed via any browser which has access to the Ethernet network
• Multiple elements can be viewed and controlled using Alarm Central
• Instantaneous access to: • System parameters • Alarm history • Battery discharge curves
• Uses SNMP protocol for reliable remote access
• Uses RS232, RS485, and 10Base-T Ethernet
• Allows an external modem for backup
• FTP for updating software • Telnet for system diagnostics
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
OCT 24, 2006 Page 2 of 2 www.power-one.com
Power Network Interface Data Sheet
Alarm Central Window
Web Interface
Other Technical Data Power Consumption <2 W Electrical Supply Voltages 18 to 72 VDC, max 2 W Ethernet 10 BaseT Driver/ Receiver with line transformer and EMI filter
half-duplex Ethernet. Communication
Serial Port 2 RS232 ports (1 for PCU/ Setup and 1 for Modem/ PC)
Weight 233 g (0.50 lb) Mechanical
Dimensions 147 x 38 x 84 mm (5.79 x 1.5 x 3.31 in) Ambient Temperature -10 °C to +70 °C Storage Temperature -40 °C to +85 °C
Environmental
Humidity 0% to 95% (non-condensing) Ethernet Supports IEEE 802.3 Ethernet Standard Compliance Serial Port Industry standard 16550 A-compatible UART
NUCLEAR AND MEDICAL APPLICATIONS - Power-One products are not designed, intended for use in, or authorized for use as critical components in life support systems, equipment used in hazardous environments, or nuclear control systems without the express written consent of the respective divisional president of Power-One, Inc. TECHNICAL REVISIONS - The appearance of products, including safety agency certifications pictured on labels, may change depending on the date manufactured. Specifications are subject to change without notice.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
DescriptionThe Power-One PPR 5/7 3 and 6position rectifier backplane provides acost-effective power solution in a highdensity wall-mounted footprint. Thesepower solutions provide rectification,system management, and powerdistribution while maintaining highreliability and offering flexibility forfuture expansion. The PPS 5/7 3 & 6Position systems are based on hot-swappable rectifier modules outputpower available at 450, 560 or 670W permodule.
Features• 115/230 VAC input
• 24V, or 48VDC output
• Serial or parallel alarm configurations
• Active load sharing
• Hot-swappable
• International standards compliance
• Natural convection cooling
• Systems can be paralleled
• Individual rectifier output adjustment6 Position SystemShown
PPR 5/73 & 6 Position Power Systems
www.power-one.comCourtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
www.power-one.com11V0005-065 PPR 5/7 V3.0
PPR 5/73 & 6 Position Power Systems
Note: All specifications are subject to change without notification.
Input
Output
Mechanical
Features
Model PPR 5/7 3-Position PPR 5/7 6-Position
Input115 or 230VAC single phase(Depending on rectifiermodule)"
115 or 230VAC single phase(Depending on rectifiermodule)"
Input Connections 3x4mm² terminal blocks 3x4mm² terminal blocks
Rectifier Modules (max.) 3 6
Load Outputs 2x10mm² - Qty 3 2x10mm² - Qty 6
24V DC Version Yes Yes
48V DC Version Yes Yes
AlarmsCommon alarm for High Voltage/ Shutdown, Low Voltage/Module Failure, Unequal Load Sharing Normally Openedor Normally Closed.
Dimensions (WxHxD) 271x193.5x305mm 484.4x193.5x305mm
Weight 1.2kg (2.65lbs.) 2.5kg (5.5lbs.)
Mounting Wall Mount Wall Mount
Model Voltage Power (max.) Current (max.)
PMP 5.24 24V DC 448W 16A
PMP 5.24 SIC 110* 24V DC 448W 16A
PMP 5.48 SIC 110* 48V DC 448W 8A
PMP 7.24 SIC 24V DC 560W 20A
PMP 7.48 SIC 48V DC 672W 12A
*110V AC input
Available Rectifiers
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Features• High reliability• Simple installation and operation• LCD display for self-guided controller operation• Interfaces standards include RS232, and Form
“C” dry alarm contacts with grouped alarms• Intelligent battery management:
• Temperature compensation(requires optional cables)
• Programmable battery load testing with data logging
• Symmetry (requires optional cables)• Programmable low voltage disconnect
• Optional Ethernet (SNMP compatible) interface module
• Natural convection cooled - no fans• International standards compliance
DescriptionPPS 10 modular DC power cabinet systemsprovide large power plant features in cost-effective, rack-mounted form factors. Thesecabinet power solutions provide rectification,system management, and power distribution whilemaintaining high reliability and offering flexibilityfor future expansion. The PPS 10 systems arebased on hot-swappable rectifier modules withconstant output power available at 1000, 1100 or1300W per module.
System management is accomplished throughmessages and alarms displayed on the systemcontroller’s (PCU/PCS) LCD screen and can alsobe displayed remotely via the PC-based PowComTM
software package.
Input
Output
Mechanical
Options
Features
Battery
PPS 10 Power System
Model PPS 10-10400 PPS 10-18200 PPS 10-23400
Input230/400V 3-phase208-240V 1-phaseSite configurable
230/400V 3-phase208-240V 1-phaseSite configurable
230/400V 3-phase208-240V 1-phaseSite configurable
Inputs (max.) Single input Single input perrectifier subrack
Single input perrectifier subrack
Rectifier Modules (max.) 8 14 18
Battery Outs - MCB (100A) 6 6 Adjustable for site
Load Outs - MCB (2-63A) 20 21 Adjustable for site
24V DC Version Yes Yes (with PCS and max.one rectifier shelf)
Yes
48V DC Version Yes Yes Yes
60V DC Version Yes (on request) Yes (on request) Yes (on request)
Supervision PCS PCU/PCS PCS
Battery Symmetry Inputs 3 3/4 4
Low Voltage BatteryDisconnection (LVBD) Yes Yes Yes
In-Cabinet Battery Yes Yes N/A
Dimensions (WxHxD)
Power Cabinet:600x700x400mmBattery Cabinet: 600x1130x400mm600x1130x600mm
600x1800x400mm600x1800x600mm600x2000x400mm600x2000x600mm
600x1750x400mm600x2150x400mm
Cable Entry Top Top Top/Bottom
Temp. Comp. Charge Yes Yes YesIntegrated SurgeArrestors Yes Yes N/A
Partial Load Disconnect Yes Yes Yes
Hinged Door Access Yes Yes Yes
Battery Cover Yes Yes N/A
Ethernet NetworkInterface Yes Yes Yes
Modem Interface Yes Yes Yes
Cabinet System
ExpansionExpansion subrack N/A Yes Yes
Expansion Cabinet Yes Yes N/A
www.power-one.comwww.power-one.com
Note: All specifications are subject to change without notification.
Cabinet System
11V0005-038 PPS10 SY V3.0
PPS 10 Power System
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Rectifier Features
Model Voltage Power(max.)
Current(max.)
PMP 10.24A SIC 24V DC 1000W 43A
PMP 11.48 SIC 48V DC 1100W 22A
PMP 11.60 SIC 60V DC 1100W 19.5A
PMP 13.48 SIC 48V DC 1300W 28A
PMP 13.48 SIC WIR* 48V DC 1250W 27A
All of the features listed under PCU above, plus:• Advanced battery management and testing• Digital signal collection via internal RS485 bus• Site programmable flash EPROM• Multiple language choices• Programmable alarms• Programmable logic functions and operations• Monthly data logging
PCS Features
The PPS 10 system utilizes plug-in rectifier modules that arebased on a soft-switching approach. Features include 3 LEDs forrectifier status indication, thermal shutdown and inputovervoltage disconnection with an automatic reset.
• Menu guided operation• RS232 interface for remote operation• Battery management and testing• Low voltage battery disconnect (LVBD)• Partial load disconnect (PLD)• Temperature compensation• Battery symmetry measurement• Optional Ethernet interface through SNMP and/or TCP/IP
PCU Features
Rectifier Modules
Advanced system supervision is accomplished using amicroprocessor based control module that allows both local andremote system monitoring.
Supervision Modules
A split cabinet solution, thatallows the power cabinet to beused as a stand alone wallcabinet, or to be installed directlyabove a battery cabinet. Thissystem can accommodate up toeight rectifiers, a supervisionmodule (PCS) and DCdistribution with up to six batterybreakers and twenty loadbreakers. This system can alsobe easily expanded by parallelingadditional slave cabinets.
PPS 10-10400 System
A floor cabinet solution thatcontains two rectifier subracksand space for mounting batteriesat the base of the cabinet. Thissystem can accommodate up tofourteen rectifiers, a supervisionmodule (PCU/PCS) and DCdistribution with up to six batterybreakers and twenty-one loadbreakers. This system can alsobe easily expanded by parallelingadditional slave cabinets.
PPS 10-18200 SystemA floor cabinet solution with abuilt-in DC-bus that enables theplug-in connection of rectifiersubracks and battery/ loadbreaker shelves. This system canaccommodate up to eighteenrectifiers, a supervision module(PCS) and DC distribution with awide range of plug-in DC loaddistributions (low and high ohmic).This system offers flexible systemconfigurations to fit most siterequirements.
PPS 10-23400 System
System Configurations System Components
PPS 10 Power SystemCabinet System
* WideInput Range (100 - 240V AC)
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Rectifier Features
Model Voltage Power(max.)
Current(max.)
PMP 10.24A SIC 24V DC 1000W 43A
PMP 11.48 SIC 48V DC 1100W 22A
PMP 11.60 SIC 60V DC 1100W 19.5A
PMP 13.48 SIC 48V DC 1300W 28A
PMP 13.48 SIC WIR* 48V DC 1250W 27A
All of the features listed under PCU above, plus:• Advanced battery management and testing• Digital signal collection via internal RS485 bus• Site programmable flash EPROM• Multiple language choices• Programmable alarms• Programmable logic functions and operations• Monthly data logging
PCS Features
The PPS 10 system utilizes plug-in rectifier modules that arebased on a soft-switching approach. Features include 3 LEDs forrectifier status indication, thermal shutdown and inputovervoltage disconnection with an automatic reset.
• Menu guided operation• RS232 interface for remote operation• Battery management and testing• Low voltage battery disconnect (LVBD)• Partial load disconnect (PLD)• Temperature compensation• Battery symmetry measurement• Optional Ethernet interface through SNMP and/or TCP/IP
PCU Features
Rectifier Modules
Advanced system supervision is accomplished using amicroprocessor based control module that allows both local andremote system monitoring.
Supervision Modules
A split cabinet solution, thatallows the power cabinet to beused as a stand alone wallcabinet, or to be installed directlyabove a battery cabinet. Thissystem can accommodate up toeight rectifiers, a supervisionmodule (PCS) and DCdistribution with up to six batterybreakers and twenty loadbreakers. This system can alsobe easily expanded by parallelingadditional slave cabinets.
PPS 10-10400 System
A floor cabinet solution thatcontains two rectifier subracksand space for mounting batteriesat the base of the cabinet. Thissystem can accommodate up tofourteen rectifiers, a supervisionmodule (PCU/PCS) and DCdistribution with up to six batterybreakers and twenty-one loadbreakers. This system can alsobe easily expanded by parallelingadditional slave cabinets.
PPS 10-18200 SystemA floor cabinet solution with abuilt-in DC-bus that enables theplug-in connection of rectifiersubracks and battery/ loadbreaker shelves. This system canaccommodate up to eighteenrectifiers, a supervision module(PCS) and DC distribution with awide range of plug-in DC loaddistributions (low and high ohmic).This system offers flexible systemconfigurations to fit most siterequirements.
PPS 10-23400 System
System Configurations System Components
PPS 10 Power SystemCabinet System
* WideInput Range (100 - 240V AC)
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Features• High reliability• Simple installation and operation• LCD display for self-guided controller operation• Interfaces standards include RS232, and Form
“C” dry alarm contacts with grouped alarms• Intelligent battery management:
• Temperature compensation(requires optional cables)
• Programmable battery load testing with data logging
• Symmetry (requires optional cables)• Programmable low voltage disconnect
• Optional Ethernet (SNMP compatible) interface module
• Natural convection cooled - no fans• International standards compliance
DescriptionPPS 10 modular DC power cabinet systemsprovide large power plant features in cost-effective, rack-mounted form factors. Thesecabinet power solutions provide rectification,system management, and power distribution whilemaintaining high reliability and offering flexibilityfor future expansion. The PPS 10 systems arebased on hot-swappable rectifier modules withconstant output power available at 1000, 1100 or1300W per module.
System management is accomplished throughmessages and alarms displayed on the systemcontroller’s (PCU/PCS) LCD screen and can alsobe displayed remotely via the PC-based PowComTM
software package.
Input
Output
Mechanical
Options
Features
Battery
PPS 10 Power System
Model PPS 10-10400 PPS 10-18200 PPS 10-23400
Input230/400V 3-phase208-240V 1-phaseSite configurable
230/400V 3-phase208-240V 1-phaseSite configurable
230/400V 3-phase208-240V 1-phaseSite configurable
Inputs (max.) Single input Single input perrectifier subrack
Single input perrectifier subrack
Rectifier Modules (max.) 8 14 18
Battery Outs - MCB (100A) 6 6 Adjustable for site
Load Outs - MCB (2-63A) 20 21 Adjustable for site
24V DC Version Yes Yes (with PCS and max.one rectifier shelf)
Yes
48V DC Version Yes Yes Yes
60V DC Version Yes (on request) Yes (on request) Yes (on request)
Supervision PCS PCU/PCS PCS
Battery Symmetry Inputs 3 3/4 4
Low Voltage BatteryDisconnection (LVBD) Yes Yes Yes
In-Cabinet Battery Yes Yes N/A
Dimensions (WxHxD)
Power Cabinet:600x700x400mmBattery Cabinet: 600x1130x400mm600x1130x600mm
600x1800x400mm600x1800x600mm600x2000x400mm600x2000x600mm
600x1750x400mm600x2150x400mm
Cable Entry Top Top Top/Bottom
Temp. Comp. Charge Yes Yes YesIntegrated SurgeArrestors Yes Yes N/A
Partial Load Disconnect Yes Yes Yes
Hinged Door Access Yes Yes Yes
Battery Cover Yes Yes N/A
Ethernet NetworkInterface Yes Yes Yes
Modem Interface Yes Yes Yes
Cabinet System
ExpansionExpansion subrack N/A Yes Yes
Expansion Cabinet Yes Yes N/A
www.power-one.comwww.power-one.com
Note: All specifications are subject to change without notification.
Cabinet System
11V0005-038 PPS10 SY V3.0
PPS 10 Power System
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
DEC 11, 2006 Page 1 of 4 www.power-one.com
PPS 10 Power System Data Sheet(Shelf System)
Features • High reliability • Simple installation and operation • LCD display for self-guided controller
operation • Interfaces standards include RS232, and
Form “C” dry alarm contacts with grouped alarms
• Intelligent battery management: • Temperature compensation (requires
optional cables) • Programmable battery load testing
with data logging • Symmetry (requires optional cables) • Programmable low voltage disconnect
• Optional Ethernet (SNMP compatible) interface module
• Natural convection cooled - no fans • International standards compliance
Description PPS 10 modular DC power shelf systems provide large power system features in cost-effective, rack-mounted form factors. These shelf power solutions provide rectification, system management, and power distribution while maintaining high reliability and offering flexibility for future expansion. The PPS 10 systems are based on hot-swappable rectifier modules with constant output power available at 1300 W per module. System management is accomplished through messages and alarms displayed on the system controller’s (PCU/PCS) LCD screen and can also be displayed remotely via the PC-based PowComTM software package.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
DEC 11, 2006 Page 2 of 4 www.power-one.com
PPS 10 Power System Data Sheet(Shelf System)
PPS 10-3900 System An all-in-one 6U high shelf system that can be installed in both 19” and ETSI telecom cabinet solutions. The system subrack can accommodate up to 3 rectifier modules, a supervision module (PCU), and DC distribution with up to 2 battery breakers and 8 load breakers.
PPS 10-7800 System An all-in-one 12U high shelf system that can be installed in 19” telecom cabinet solutions. The system subrack can accommodate up to 6 rectifier modules, a supervision module (PCS) and DC distribution with up to four battery breakers and 15 load breakers. Optional expansion subrack allowing max 12 modules (15.6 kW).
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
DEC 11, 2006 Page 3 of 4 www.power-one.com
PPS 10 Power System Data Sheet(Shelf System)
System Components
Rectifier Modules The PPS 10 system utilizes plug-in rectifier modules that are based on a soft-switching approach. Features include 3 LEDs for rectifier status indication, thermal shutdown, and input overvoltage disconnection with an automatic reset.
Rectifier Features Model Voltage Power (max.) Current (max.) PMP 13.48 SIC 48 VDC 1300 W 28 A
Supervision Modules Advanced system supervision is accomplished using a microprocessor-based control module that allows both local and remote system monitoring.
PCU Features • Menu-guided operation • RS232 interface for remote operation • Battery management and testing • Low voltage battery disconnect (LVBD) • Partial load disconnect (PLD) • Temperature compensation • Battery symmetry measurement • Optional Ethernet interface through SNMP and/or
TCP/IP
PCS Features All of the features listed under PCU above, plus: • Advanced battery management and testing • Digital signal collection via internal RS485 bus • Site programmable flash EPROM • Multiple language choices • Programmable alarms • Programmable logic functions and operations Monthly data logging
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
DEC 11, 2006 Page 4 of 4 www.power-one.com
PPS 10 Power System Data Sheet(Shelf System)
NUCLEAR AND MEDICAL APPLICATIONS - Power-One products are not designed, intended for use in, or authorized for use as critical components in life support systems, equipment used in hazardous environments, or nuclear control systems without the express written consent of the respective divisional president of Power-One, Inc. TECHNICAL REVISIONS - The appearance of products, including safety agency certifications pictured on labels, may change depending on the date manufactured. Specifications are subject to change without notice.
Input Model PPS 10-3900 PPS 10-7800 Input 230/400V 3-phase
208-240V 1-phase Site configurable
230/400V 3-phase 208-240V 1-phase Site configurable
Inputs (max.) Single input Single input Output Rectifier Modules (max.) 3 6 Battery Outs - MCB (100 A) 2 4 Load Outs - MCB (2-63 A) 8 15 Features Supervision PCU PCS Battery Battery Symmetry Inputs 3 4 Low Voltage Battery Disconnection (LVBD)
Yes Yes
Mechanical Dimensions (WxHxD) 485 x 266 x 341 mm 487 x 531 x 308 mm Mounting 19" or ETSI 19" Cable Entry Top Top Options Temp. Comp. Charge Yes Yes Integrated Surge Arrestors N/A Yes Partial Load Disconnect N/A Yes Ethernet Network Interface Yes Yes Modem Interface Yes Yes
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
SEP 27, 2006 Page 1 of 4 www.power-one.com
PPS 16 Power System Data Sheet(Cabinet & Shelf Systems)
Description PPS 16 modular DC power shelf and cabinet systems are designed to meet rigid telecom applications with very high reliability and flexibility for future expansion. The PPS 16 Power Systems are based on hot-swappable rectifier modules with output power available up to 1800 watts per module. System management is accomplished through messages and alarms displayed on the system controller’s LCD screen and can also be viewed and controlled remotely via the PC-based PowCom™ software package.
Features • Up to 18 kW/ 320 A power and 680 Ah
battery backup per cabinet • Simple installation and operation • LCD for self-guided controller operation • Interface standards include RS232, and
Form “C” dry alarm contacts with grouped alarms
• Site programmable supervision unit • Intelligent battery management • Optional Ethernet (SNMP compatible)
interface module • International standards compliance
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
SEP 27, 2006 Page 2 of 4 www.power-one.com
PPS 16 Power System Data Sheet(Cabinet & Shelf Systems)
• Up to 360 A/ 18 kW/ 48 V per cabinet
• Space for 680 Ah backup batteries per cabinet
• Footprint - 600 x 600 mm or 600 x 400 mm
• Height - 1800 or 2000 mm
• Up to 288 A/ 14.4 kW/ 48 V per shelf • 2-6 battery breakers • Max 21 load MCB
Cabinet Solutions (With Batteries) Floor cabinet solutions that combine rectifiers, DC distribution, backup batteries, and monitoring in a single footprint. This system can accommodate up to 10 rectifier modules, a supervision module, and DC distribution with up to 6 battery breakers and 26 load breakers.
Shelf Solutions (19”) 4U and 8U systems accommodating up to 8 rectifier modules, a supervision module, and DC distribution with battery breakers and load breakers.
• Up to 256 A/ 12.8 kW /48 V per shelf • 2-6 battery breakers • Max 26 load MCB
Shelf Solutions (23”) 4U and 8U systems that can accommodate up to 10 rectifier modules, a supervision module, and DC distribution with up to 6 battery breakers and 20 load breakers.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
SEP 27, 2006 Page 3 of 4 www.power-one.com
PPS 16 Power System Data Sheet(Cabinet & Shelf Systems)
System Components Rectifier Modules The PPS 16 system utilizes plug-in rectifier modules that are based on a soft-switching approach. Features include 3 LEDs for rectifier status indication, thermal shutdown, and input overvoltage disconnection with an automatic reset.
Rectifier Features:
Model Input Voltage Power (Max)
Current (Max)
FMP16.48 1600 W 32 A FMP18.48
85-275 VAC
48 VDC 1800 W 36 A
FMP Rectifier Module
Controllers • Menu guided operation • RS232 interface and Form “C” dry alarm contacts • Password controlled environment • Battery management:
• Automatic and/or manual capacity test • Optional battery symmetry measurement with alarm • Optional temperature compensation • Programmable low voltage disconnect from batteries • Optional programmable PLD function for load
shedding • Optional network interface capability • Programmable alarm routing, logic unit, and analog
inputs • Alarm logging history
PCS Module
PCC Module
PCS Features; • Site programmable flash EPROM • Multiple language choices • LCD and front-mounted controls • Monthly battery data logging
PCC Features; • Hot pluggable unit • Control unit with ethernet connection (option)
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
SEP 27, 2006 Page 4 of 4 www.power-one.com
PPS 16 Power System Data Sheet(Cabinet & Shelf Systems)
Input
Model
19” Shelf
23” Shelf
23” Cabinet
AC Inputs
1
2
1
2
1
2
Output
Rectifier Modules (max. per system)
4
8
5
10
5
10
Battery Outputs
1-3
2 to 6
2-4
2 to 6
2-4
2 to 6
Load Outputs (Max) (MCB type dependant)
13
21
16
20
16
20
Controller
Model
PCC
PCS
PCC
PCS/PCC
PCC
PCS/PCC
Battery Battery Symmetry Inputs
6
12
6
6 or 12
6
6 or 12
Low Voltage Battery Disconnect (LVBD)
Yes
Yes
Yes
In-Cabinet Battery
N/A
N/A Up to 680 Ah using 4 x 170 Ah
Mechanical
Dimensions W x H x D (mm)
483x355x300(19 in. x 4U)
483x355x300(19 in. x 8U)
483x355x300(23 in. x 4U)
483x355x300 (23 in. x 8U)
600 x 600 x 1800 600 x 600 x 2000 600 x 400 x 1800 600 x 400 x 2000
Options
Temp. Comp. Charge
Yes
Yes
Yes
Ethernet Network Interface
Yes
Yes
Yes
Modem Interface
Yes
Yes
Yes
NUCLEAR AND MEDICAL APPLICATIONS - Power-One products are not designed, intended for use in, or authorized for use as critical components in life support systems, equipment used in hazardous environments, or nuclear control systems without the express written consent of the respective divisional president of Power-One, Inc. TECHNICAL REVISIONS - The appearance of products, including safety agency certifications pictured on labels, may change depending on the date manufactured. Specifications are subject to change without notice.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Features• High reliability• Simple installation and operation• LCD display for self-guided controller operation• Interfaces standards include RS232, and Form
“C” dry alarm contacts with grouped alarms• Up to 1200A per cabinet• Live expansion up to 6400A• Plug-in ready for various DC distributions and
subracks• Inter-cabinet DC paralleling bus• Site programmable supervision unit• Intelligent battery management• Optional Ethernet (SNMP compatible) interface
module • International standards compliance
DescriptionPPS 25 modular DC power cabinet systems aredesigned to meet rigid telecom applications withvery high reliability and flexibility for futureexpansion. These cabinet power solutionsprovide rectification, system management andpower distribution while allowing configurablesolutions within the same cabinet or through theuse of external distribution cabinets. The PPS 25systems are based on hot-swappable fan-cooledPMP 25 rectifier modules with constant outputpower available at 24V/110A or 48V/50A permodule.
System management is accomplished throughmessages and alarms displayed on the systemcontroller’s (PCS) LCD screen and can also bedisplayed remotely via the PC-based PowComTM
software package.
Note: All specifications are subject to change without notification.
Input
Output
Mechanical
Options
Features
Battery
Model PPS 25 System
Input 230/400V 3-phase (site configurable)
Inputs (max.)Single input for each 6 rectifier positions (4 inputs for 24 rectifier cabinets)
Rectifier Modules (max.) 24 (bulk output feed to battery and load)
Battery Outputs
Several battery breaker modules are available and are based on:MCCB’s: 1x1500A, 2x600A, 4x384AMCB’s: 12x100AKnife fuses: 5xNH1-3
Load Outs - MCB (2-63A)
Several battery breaker modules are available and are based on:MCCB’s: 1x1500A, 2x600A, 2x384A, 4x384AMCB’s: 24x2-63A, 16x80-100A, 24x2-16A high ohmicKnife fuses: 5xNH1-3, 9xNH00
24V DC Version Yes (max. 1200A per cabinet)
48V DC Version Yes
Supervision PCS
Battery Symmetry Inputs 4 (expandable to 12 by adding the optional interface circuit board)
Low Voltage BatteryDisconnection (LVBD) Yes (through a trip coil in each MCCB or contactor)
Dimensions (WxHxD) 600x2150x600mm
Cable Entry Top and/or bottom for cables <50sq/mm (using cable duct)Top or bottom entry for cables >50sq/mm
Plug-in for multiple racks,subracks, and PDU’s
A total of 35U is available for rectifier subracks, distribution, and batterybreaker modules (29U at bottom cable entry)
Temp. Comp. Charge Yes
Partial Load Disconnect Yes
Hinged Door Access Yes
Ethernet NetworkInterface Yes
Modem Interface Yes
ExpansionExpansion Rack Up to six subracks per cabinet, each with four rectifier modules
Expansion Cabinet Expansion cabinet can be be placed to the left or right of existingcabinets, allowing up to 128 rectifier modules
Cabinet System
PPS 25 Power SystemCabinet System
www.power-one.comwww.power-one.com11V0005-039 PPS25 SY V3.0
PPS 25 Power System
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Model Voltage Power(max.) Current (max.)
PMP 25.24 SIC 24V DC 3080W 110A at 28V DC
PMP 25.48 SIC 48V DC 2800W 50A at 56V DC
The PPS 25 system utilizes plug-in rectifier modules that arebased on a soft-switching approach. Features include 3 LEDsfor rectifier status indication, thermal shutdown, and inputovervoltage disconnection with an automatic reset.
• Menu guided operation• RS232 interface for remote operation• Enhanced battery management and testing• Temperature compensation• Site programmable flash EPROM• Supervision for up to 128 rectifiers and 128 micro processors • Multiple language choices• Programmable alarms, logic functions, and operations• Monthly data logging• Optional Ethernet interface through SNMP and/or TCP/IP
PCS Features
Rectifier Modules
Advanced system supervision is accomplished using a microprocessorbased control module that allows both local and remote system monitoring.
Supervision Module
The PPS 25 system offers flexible solutions that fit a large number of siterequirements. Some of these features include:
• Easy configuration with internal or remote DC distribution• Internal DC bus for simple plug-in of load distribution modules, battery
breaker modules, and rectifier subracks• Inter-cabinet paralleling bus for live connection of expansion cabinets• Internal data bus for advanced system monitoring and control• Wide range of plug-in DC load distributions, low and high ohmic
PPS 25 System
PPS 25 with integratedDC distribution
PPS 25 with bulkoutputs feeding remote
DC distributions
• In cabinet vertical DC bus allows live expansion of distribution and rectifier modules
• Separate cable duct for output load cables• Inter cabinet DC bus for live cabinet expansion• Top or bottom cable entry• Matching DC distribution cabinets
Cabinet Features
Innovative and flexible cabinet design.
Cabinet
PPS 25 Cabinet
PCS Supervision Module
PMP 25 Rectifier
Battery Breaker Modules Plugable battery breakermodule, based on MCCB’s,MCB’s or knife fuses
DC DistributionPlugable load distributionmodule, based on MCB’s,MCCB’s or knife fuses. Lowor high ohmic.
System Configurations System Components
PPS 25 Power SystemCabinet System
100mm Cable Duct
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Model Voltage Power(max.) Current (max.)
PMP 25.24 SIC 24V DC 3080W 110A at 28V DC
PMP 25.48 SIC 48V DC 2800W 50A at 56V DC
The PPS 25 system utilizes plug-in rectifier modules that arebased on a soft-switching approach. Features include 3 LEDsfor rectifier status indication, thermal shutdown, and inputovervoltage disconnection with an automatic reset.
• Menu guided operation• RS232 interface for remote operation• Enhanced battery management and testing• Temperature compensation• Site programmable flash EPROM• Supervision for up to 128 rectifiers and 128 micro processors • Multiple language choices• Programmable alarms, logic functions, and operations• Monthly data logging• Optional Ethernet interface through SNMP and/or TCP/IP
PCS Features
Rectifier Modules
Advanced system supervision is accomplished using a microprocessorbased control module that allows both local and remote system monitoring.
Supervision Module
The PPS 25 system offers flexible solutions that fit a large number of siterequirements. Some of these features include:
• Easy configuration with internal or remote DC distribution• Internal DC bus for simple plug-in of load distribution modules, battery
breaker modules, and rectifier subracks• Inter-cabinet paralleling bus for live connection of expansion cabinets• Internal data bus for advanced system monitoring and control• Wide range of plug-in DC load distributions, low and high ohmic
PPS 25 System
PPS 25 with integratedDC distribution
PPS 25 with bulkoutputs feeding remote
DC distributions
• In cabinet vertical DC bus allows live expansion of distribution and rectifier modules
• Separate cable duct for output load cables• Inter cabinet DC bus for live cabinet expansion• Top or bottom cable entry• Matching DC distribution cabinets
Cabinet Features
Innovative and flexible cabinet design.
Cabinet
PPS 25 Cabinet
PCS Supervision Module
PMP 25 Rectifier
Battery Breaker Modules Plugable battery breakermodule, based on MCCB’s,MCB’s or knife fuses
DC DistributionPlugable load distributionmodule, based on MCB’s,MCCB’s or knife fuses. Lowor high ohmic.
System Configurations System Components
PPS 25 Power SystemCabinet System
100mm Cable Duct
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Features• High reliability• Simple installation and operation• LCD display for self-guided controller operation• Interfaces standards include RS232, and Form
“C” dry alarm contacts with grouped alarms• Up to 1200A per cabinet• Live expansion up to 6400A• Plug-in ready for various DC distributions and
subracks• Inter-cabinet DC paralleling bus• Site programmable supervision unit• Intelligent battery management• Optional Ethernet (SNMP compatible) interface
module • International standards compliance
DescriptionPPS 25 modular DC power cabinet systems aredesigned to meet rigid telecom applications withvery high reliability and flexibility for futureexpansion. These cabinet power solutionsprovide rectification, system management andpower distribution while allowing configurablesolutions within the same cabinet or through theuse of external distribution cabinets. The PPS 25systems are based on hot-swappable fan-cooledPMP 25 rectifier modules with constant outputpower available at 24V/110A or 48V/50A permodule.
System management is accomplished throughmessages and alarms displayed on the systemcontroller’s (PCS) LCD screen and can also bedisplayed remotely via the PC-based PowComTM
software package.
Note: All specifications are subject to change without notification.
Input
Output
Mechanical
Options
Features
Battery
Model PPS 25 System
Input 230/400V 3-phase (site configurable)
Inputs (max.)Single input for each 6 rectifier positions (4 inputs for 24 rectifier cabinets)
Rectifier Modules (max.) 24 (bulk output feed to battery and load)
Battery Outputs
Several battery breaker modules are available and are based on:MCCB’s: 1x1500A, 2x600A, 4x384AMCB’s: 12x100AKnife fuses: 5xNH1-3
Load Outs - MCB (2-63A)
Several battery breaker modules are available and are based on:MCCB’s: 1x1500A, 2x600A, 2x384A, 4x384AMCB’s: 24x2-63A, 16x80-100A, 24x2-16A high ohmicKnife fuses: 5xNH1-3, 9xNH00
24V DC Version Yes (max. 1200A per cabinet)
48V DC Version Yes
Supervision PCS
Battery Symmetry Inputs 4 (expandable to 12 by adding the optional interface circuit board)
Low Voltage BatteryDisconnection (LVBD) Yes (through a trip coil in each MCCB or contactor)
Dimensions (WxHxD) 600x2150x600mm
Cable Entry Top and/or bottom for cables <50sq/mm (using cable duct)Top or bottom entry for cables >50sq/mm
Plug-in for multiple racks,subracks, and PDU’s
A total of 35U is available for rectifier subracks, distribution, and batterybreaker modules (29U at bottom cable entry)
Temp. Comp. Charge Yes
Partial Load Disconnect Yes
Hinged Door Access Yes
Ethernet NetworkInterface Yes
Modem Interface Yes
ExpansionExpansion Rack Up to six subracks per cabinet, each with four rectifier modules
Expansion Cabinet Expansion cabinet can be be placed to the left or right of existingcabinets, allowing up to 128 rectifier modules
Cabinet System
PPS 25 Power SystemCabinet System
www.power-one.comwww.power-one.com11V0005-039 PPS25 SY V3.0
PPS 25 Power System
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
AUG 29, 2006 Page 1 of 4 www.power-one.com
Legacy Products- For Reference Only
PPS 7 Power System (Shelf Systems)
Description PPS 7 modular DC power shelf systems provide large power system features in cost-effective, rack-mounted form factors. These shelf-power solutions provide rectification, system management, and power distribution while maintaining high reliability and offering flexibility for future expansion. The PPS 7 systems are based on hot-swappable rectifier modules output power available at 560 or 670 watts per module. System management is accomplished through messages and alarms displayed on the system controller’s (PCU) LCD screen and can also be displayed remotely via the PC-based PowCom™ software. package.
Features • High reliability • Simple installation and operation • LCD display for self-guided controller
operation • RS232 interface for remote operation • Intelligent battery management:
• Temperature compensation (requires optional cables)
• Programmable battery load testing with data logging
• Symmetry (requires optional cables) • Programmable low voltage
disconnect • Optional Ethernet (SNMP compatible)
interface module • Natural convection cooling - no fans • International standards compliance
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
AUG 29, 2006 Page 2 of 4 www.power-one.com
Legacy Products- For Reference Only
PPS 7 Power System (Shelf Systems)
PPS 7-2100 System An all-in-one 3U high shelf system that can be installed in both 19” and ETSI telecom cabinet solutions. The system subrack can accommodate up to three rectifier modules, a supervision module (PCU), and DC distribution with a single battery breaker and six load breakers.
System Configurations
PPS 7-2800 System An all-in-one 3U high shelf system that can be installed in both 19” and ETSI telecom cabinet solutions. The system subrack can accommodate up to four rectifier modules, a supervision module (PCU), and DC distribution with a single battery breaker and a single load breaker.
PPS 7-3500 System An all-in-one 6U high shelf system that can be installed in 19” and ETSI telecom cabinet solutions. The system subrack can accommodate up to five rectifier modules, a supervision module (PCU), and DC distribution with up to two battery breakers and twenty load breakers.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
AUG 29, 2006 Page 3 of 4 www.power-one.com
Legacy Products- For Reference Only
PPS 7 Power System (Shelf Systems)
• Menu-guided operation • RS232 interface for remote operation • Battery management and testing • Low voltage battery disconnect (LVBD) • Temperature compensation • Battery symmetry measurement • Optional Ethernet interface through SNMP and/or TCP/IP • Partial load disconnection (PLD)
Rectifier Modules The PPS 7 system utilizes plug-in rectifier modules that are based on a soft-switching approach. Features include 3 LEDs for rectifier status indication, thermal shutdown, and input overvoltage disconnection with an automatic reset (only on PMP 7 modules).
System Components
Supervision Module (PCU) Advanced system supervision is accomplished using a microprocessor-based control module that allows both local and remote system monitoring.
Rectifier Features Model Voltage Power (Max) Current (Max) PMP 7.24 SIC 24 VDC 560 W 20 A PMP 7.48 SIC 48 VDC 672 W 12 A
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
AUG 29, 2006 Page 4 of 4 www.power-one.com
Legacy Products- For Reference Only
PPS 7 Power System (Shelf Systems)
Input Model PPS 7-2100 PPS 7-2800 PPS 7-3500 Input 230/400V 3-phase
208-240V 1-phase Site configurable
230/400V 3-phase 208-240V 1-phase Site configurable
230/400V 3-phase 208-240V 1-phase Site configurable
Inputs (max.) Single input Single input Single input
Output Rectifier Modules (max.) 3 4 5 Battery Outputs 1 1 2 Load Outputs 6 1 20 24 VDC Version Yes N/A N/A 48 VDC Version Yes Yes Yes
Features Supervision PCU PCU PCU
Battery Battery Symmetry Inputs 1 1 3 Low Voltage Battery Disconnection (LVBD)
Yes Yes Yes
Mechanical Dimensions (WxHxD) 485x133x305 mm 485x133x305 mm 485x266x305 mm Mounting 19”, ETSI, or flush
ETSI mount (site configurable)
19”, ETSI, or flush ETSI mount (site configurable)
19”, ETSI, or flush ETSI mount (site configurable)
Cable Entry Top Top Top
Options Temp. Comp. Charge Yes Ethernet Network Interface
Yes
Modem Interface Yes
NUCLEAR AND MEDICAL APPLICATIONS - Power-One products are not designed, intended for use in, or authorized for use as critical components in life support systems, equipment used in hazardous environments, or nuclear control systems without the express written consent of the respective divisional president of Power-One, Inc. TECHNICAL REVISIONS - The appearance of products, including safety agency certifications pictured on labels, may change depending on the date manufactured. Specifications are subject to change without notice.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
DescriptionThe Power-One Xscend™ Controller System (XCS) provides comprehensive monitoringand control for Power-One’s Xscend DC power systems. This digital controller monitorstotal system conditions including DC voltage, rectifier current, rectifier temperature,system capacity, battery parameters and circuit breaker status.
The XCS enables data storage of system configuration information such as battery type,installation date and system commission date. Visual notification of alarm and warningconditions are indicated by front panel LEDs, while descriptions of the alarms are providedthrough an LCD, or as an option, may be accessed remotely through a modem or aNetwork Interface (PNI) module.
To meet individual site requirements, the XCS contains a logic operator that can beprogrammed to monitor and control specified requirements. This allows actions to be set,alarms to be triggered, and outputs to be activated based on internal and external signalmonitoring, comparing and processing.
FeaturesUser controls and interfaces:
• Simple menu-guided operation using front panel mounted pushbuttons and an LCD
• User-selectable alarm parameters
• 40 event data logging
• Password controlled environment
• Multiple language options
• RS232 Interface and Form “C” dry alarm contacts
XCSController
www.power-one.com
Intelligent battery management:
• Temperature compensation with programmable compensation factor
• Automatic and manual load testing
• Battery voltage and symmetry monitoring
• Capacity testing
• Low voltage disconnect
• Monthly data logging
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
InputVoltage 18-72V DC
Current <200 mA at 48V, <400 mA at 24V
Battery
Other Technical DataDimensions(WxHxD)
483/584 x 44 x 274mm (19/23 x 1.75 x 10.8in.)
Weight 4.94kg (11lbs.)
OperatingTemperature -40 to +65°C
StorageTemperature -50 to +85°C
EnvironmentStorage: Transport: Operation:
ETS 300 019-2-1ETS 300 019-2-2ETS 300 019-2-3
Alarms
BatteryDisconnection
An optional feature that allowsvoltage controlled disconnectionof batteries.
Boost ChargingManual time controlled orautomatic boost charging withadjustable time and voltage levels.
Battery Test
Automatic or manual testing ofbatteries up to four times per yearwith a 10 test memory. Variablesinclude: test duration, end voltage,and amount of Ah’s to bedischarged during test.
SymmetryMeasurement
Optional tool that measuresbatteries for early detection ofthermal runaway. Allows forseparate measurements of up to12 parallel battery branches, eachdivided into four blocks.
TemperatureCompensationCharging
Allows continuous adjustment ofoutput voltage according tobattery temperature. Featuresinclude adjustable compensationfactor and separate thresholds forhigh temperature alarms.
PLD
Optional feature that allowsvoltage or time controlleddisconnection of non-essentialload.
EnhancedBatteryMonitoring
Monthly logging of essentialbattery parameters, includingtemperature, temp. hours, current,charging voltage, and symmetryvoltage. Parameters are storedfor 5 years.
Interface
Note: All specifications are subject to change without notification.
Alarm History The last 40 events are saved andinclude a time and date stamp.
AlarmContacts
6 potential free change-over alarmcontacts. Two open collector outputsfor LVD operation.
Alarms High System VoltageLow System VoltageLoad/ Battery Disc. Mains ErrorDistribution Fuse FailureBattery FailureModule FailureBattery Temp. AlarmSymmetry FaultBattery Fuse FailureHigh LoadBattery Fuse Disc.Urgent Module FailureCommunication FailurePartial Load Disc.
1*2*4*3*4*6*5*6*6*4*5*5*4*5*4*
* All alarms are indicated using an LED and displayed inthe LCD. The numbers represent an example of alarmrouting. Sixteen additional alarms are available and areconfigurable by changing the PCS EEPROM.
Display 2x20 character LCD with backlight
InternalCommunication
RS485 Data Bus for communicationwith a maximum of 128 rectifiers and128 sub-controllers
InternalCommunication
RS232 Serial interface for remote control from a PC withPowCom software
IndicationsGreen LED - Power ONYellow LED - System warning message Red LED - System failure message
Controls Four pushbutton controls
SignalCollection
Wide range of interface units withanalog and digital input/outputs
Software Site upgradeable by EEPROM flash
Language Multiple language options
www.power-one.com11V0005-061 XCS V3.0
ControllerXCS
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com